Modular Room Control (MRC) Series Expansion Board

Similar documents
FX Input/Output (I/O) Modules XM07 and XM14

S66 Series Electronic Fan Speed Control

TC-9102 Terminal Controller

VC3000 Series Line Voltage Switching Relay Pack Controllers Installation Guide

UNT1100 Series. Binary Output Jumpers AO2 AO1 AO3 AO4 AOCM AOCM AOCM AOCM AO1. AI Switches Job Information N2 Address. Ref N2+ N2- ADDR 0 = ALL OPEN

X47.CE Product Guide

Smart Equipment Controls (SEC)

Extended Digital Controller

P216 Series Condenser Fan Speed Controller

DX-9100 Digital Controller, Version 2

AS-CVTPROx00-0 Zone Bus/N2 Bus Interface Converter

Lab and Central Plant Controller

LN Series Remote Input/Output (I/O) Modules

Suitable for a wide range of installations with wall-mount, flush-mount and hand-held remote control options.

Field selectable application type and room module series, via dip-switches on controller

LX Series Remote Input/Output (I/O) Controller

FX-PCX Expansion Input/Output Modules Catalog Page Code No. LIT Issued April 17, 2015

Onboard Inputs and Outputs. Remote User Interface. Integral LCD User Interface

Series P215PR/RM Direct- and Remote-Mount Pressure-Actuated Condenser Fan Speed Controllers for Single-Phase Motors

E528 Smart Digital Thermostat Product Guide

FX05 Controller. FX05 Controller. Features and Benefits Compatible with standard BAS protocols. LON and N2Open plug-in comm.

PEAK TM. PEAK TM controllers. Mid-Market BAS Smart equipment controllers. HVAC/R controllers

TM-2100 Series Room Command Module

Input/Output Module (IOM) Series Controllers Catalog Page Code No. LIT Issued June 2018

XT-9100 Technical Bulletin

FXVMA Variable Air Volume (VAV) Box Controller

Input/Output Module (IOM) Series Catalog Page

LTEC Heat Pump DDC Controller

Room Controllers. SC3000 Relay Pack

Field Equipment Controller (FEC) Series Catalog Page Code No. LIT Issued June 2018

P216. Condenser fan speed controller. Product bulletin. Features

SE7600E Series Application Guide

HARDWARE GUIDE. Water Loop Controller C1000 Series. Specifications and Operational Guide

TM-2100 Series Room Command Module

Powermite 599 MT Series SAS Electronic Valve Actuator 24 Vac or 24 Vdc, Proportional Control

N2 Dialer Module. Features and Benefits

FX06 Field Controller

VAV Modular Assembly (VMA) 1410/1420

M1000 INTELLIGENT ZONE CONTROL SYSTEM

FX-DIS1710 Local Controller Display Installation Instructions Part No , Rev. B Issued April 2016

Advanced Application Field Equipment Controller (FAC) Catalog Page

SER8300 Room Controller

Temperature controller Ducted systems

Viconics VT76x6W Water-source Heat Pump Controllers Engineering Guide Specification

CONTROL BALL VALVES WITH EQUAL PERCENTAGE CHARACTERISTIC 2010 NEW ELECTRICAL ACTUATORS

FEC - FAC. Metasys controllers. Complex BAS Programmable controllers. Catalog Page. Field Equipment Controllers

FX14 Field Controller

Actuator Commissioning Tool

BACnet PTEC Heat Pump Multi-Stage Controller. Control Applications. Product Description. Product Numbers. Warning/Caution Notation

Medium User Interface (MUI) Version 3

LX Series Free Programmable LX-PRG6x0-11 Controllers and LX Series Input/Output (I/O) Extension Modules

Series P215DP Single/Dual Pressure Input Condenser Fan Speed Controllers For Single Phase Motors (incl. built-in RFI suppression filter)

I ntroduction. RA Fast Running Electric Actuator. Features and Benefits

SE7600E Series Application Guide

DESIGO RX Individual room controllers. for fan-coil systems, chilled ceilings and radiators, with LONMARK-compatible bus communications

FX-PCA Advanced Application Programmable Controller Catalog Page

920 Remote Control (RC) Switches

NT10 Series RS485 Modbus RTU Networking LCD Fan Coil Thermostat

Input/Output Module (IOM) Series Controllers Catalog Page Code No. LIT Issued December 2017

Datasheet. ECB-PTU Series. 1/14. BACnet B-ASC Powered Terminal Unit Programmable Controllers. Overview

Digital Lighting Systems, Inc. PD216. Two Channel Dimmer and Switch Packs PROTOCOL USER'S MANUAL. PD216-UM Rev. E - 02/03

VA-748x Electric Valve Actuators

LN Series Free Programmable LN-PRG6x0-12 Controllers and LN Series Input/Output (I/O) Extension Modules

Installation and Operation. Tracer MP501 Controller CNT-SVX08B-EN

TX-I/O Product Range. Features. Description. Document No January 24, 2007

TEC Heat Pump Multi-Stage Controller. Control Applications. Accessories. Product Description. Product Numbers. Warning/Caution Notation

ASCO 920 Remote Control (RC) Switches

FX-BTCVT Bluetooth Commissioning Converter Installation Instructions

Metasys N1 Network Integration

RCF-230CD. Communicating room thermostat for fan-coil applications with on/off outputs

OP10. Pre-programmed, configurable controller for simple applications

TAC Xenta 101-VF. 3-Speed Fan Coil Controller. TAC Xenta

Digital Lighting Systems, Inc.

TC-8900 Controller Units with PM-8900 Power Modules

TEC Unit Conditioner Controller

COMFORT CONTROL CENTER SERVICE INSTRUCTIONS

FX-2 Control Board ASY-360-XXX Setup and Configuration Guide

THERMOSTATS & CONTROLLERS

Andover Continuum Infinet II i2865/866 VAV Controllers with Built-in Actuator

LTEC Unit Ventilator DDC Controller

MAINTENANCE MANUAL. EDACS REDUNDANT POWER SUPPLY SYSTEM 350A1441P1 and P2 POWER MODULE CHASSIS 350A1441P3, P4, AND P5 POWER MODULES TABLE OF CONTENTS

RCF-230CTD. Room controller for fan-coil applications with outputs for two thermal or one 3-position actuator or function for an electric heater

RS-485 FClink Networking Room Thermostats with LCD for Fan Coil Units

Room Controllers SER8300 Line Voltage Fan Coil Controller with SC3000 Relay Pack

Free Energy Band RCC30U Room Temperature Controller for Four-pipe Fan Coil Unit

S5XX Switch Series Product Guide

Application Engineering

BACnet. b3867 Terminal Controllers

Products :: Circuit Protection :: Hydraulic/Magnetic Circuit Breakers

TEC VAV with 0-10V AO Heat. Modulation and CO2 Monitoring. Controller. Control Applications. Product Description. Accessories.

TeSys IEC Contactors and Overload Relays

Hardware Installation. Tracer MP581 Programmable Controller CNT-SVN01C-EN

OTB1E0DM9LP I/O distributed module OTB - Ethernet TCP/IP m

FCU-4 FAN COIL CONTROLLER

Andover ContinuumTM Infinet II

Electrical Actuators

BACnet B-ASC Powered Terminal Unit Programmable Controllers. Overview

TEC Terminal Box (VAV) Controller

Electrical Actuators

PERCENT OF RATED CURRENT

Transcription:

Installation Instructions Issue Date December 13, 2002 Modular Room Control (MRC) Series Expansion Board Application The Modular Room Control (MRC) system has the ability to expand its input/output capabilities with the use of expansion boards. Expansion boards allow control of the Fan Coil Unit (FCU) or Packaged Terminal Air Conditioning (PTAC) to be moved from the MRC Thermostat to a location that may better fit the specific needs of the hotel. For example, in a retrofit situation, there may not be enough existing wires between the original thermostat and the FCU. Instead of going through the expense and effort of pulling the required number of wires, the existing wires can be used to provide communication between the MRC Thermostat and the expansion board via a local bus. This expansion board could be located within the FCU to locally interface with the inputs and outputs. Additional applications include controlling multiple FCUs or PTACs in parallel (for example, suite application) or controlling line voltage lighting circuits. The expansion boards communicate to the MRC Thermostat through a wired (local bus) or wireless connection when used in conjunction with the Infrared (IR) transceiver. 5-Triac Expansion Board The MRC19-EXP1 Triac Expansion Board is used to expand the functionality of the MRC Thermostat when 24 VAC triac operation is feasible. Use the MRC19-EXP1 expansion board to control compatible low voltage relays or low voltage loads, such as a valve. This expansion board also has one additional Binary Input (BI) that could be used to monitor the window, or compressor alarm in a heat pump, and it has one Analog Input (AI) that could be used as an Aquastat for seasonal changeover. 6-Relay Expansion Board The MRC19-EXP2 Relay Expansion Board has six Single-Pole, Single-Throw (SPST), 100-300 VAC, 20 ampere relays on board. Relays five and six can be configured to switch as a pair, allowing both legs of the circuit to be controlled. Use the MRC19-EXP2 where the use of triac switching on low voltage is not preferred, or when line voltage switching is required. Typical applications would include line voltage switching in FCU or PTAC units or lighting controls. The MRC19-EXP2 also has the additional BI and AI inputs. Analog Expansion Boards The MRC19-EXP3 and MRC19-EXP4 expansion boards have proportional control (0-10 VDC) capabilities, that would be typically used for hot or cold water valves with proportional actuators. The MRC19-EXP3 combines the MRC19-EXP1 5-triac expansion board with an additional Analog Output board. The MRC19-EXP4 combines the MRC19-EXP2 6-relay expansion board with an additional Analog Output board. IR Transceiver (EYE) The MRC19-EYE0 IR transceiver allows wireless communication from the MRC Thermostat to the expansion boards. The transceiver can be surface mounted underneath the FCU/PTAC or mounted within a J box, behind a Decora style cover plate. Communications do not require line of sight to the MRC thermostat. The expansion board provides power for the IR transceiver. 2002 Johnson Controls, Inc. 1 Part No. 24-9778-30, Rev. www.johnsoncontrols.com

Installation The following items are required for control of the expansion boards: the MRC Thermostat an expansion board (one of the four models) an EYE IR transceiver when used with wireless communication (also requires the IR transceiver in the MRC Thermostat) In a typical installation, the expansion board would be installed within the FCU or PTAC equipment electrical cabinet. Power for the expansion board would be provided by the FCU or PTAC power supply. If the MRC19-EXP1 or EXP3 triac models are used, then 24 VAC is required. The MRC19-EXP2 and EXP4 models can be powered by 100 to 300 VAC. 0.9 23 Communication between the MRC Thermostat and the expansion board would be a three wire, minimum 24 gage conductors. See Figure 6 for details. When the MRC19-EYE0 IR transceiver is used, it should be mounted in a position to receive the IR communication from the IR transceiver on the MRC Thermostat. It does not require line of sight between the two IR transceivers. Dimensions Refer to Figure 1 through Figure 5 for dimensions. Figure 1: 5-Triac Expansion Board Dimensions, in. (mm) Wire Color Description 3.0 76 6.0 152 5.5 140 Ground 1 2 3 4 Brown Red Orange Yellow Relay 6 Only Relay 5 & 6 Together 12 VDC PTS # 1 # 4 # 2 # 3 # 5 # 6 AC - LINE 1 AC - LINE 2 or Neutral Figure 2: 6-Relay Expansion Board Dimensions, in. (mm) 2 Modular Room Control (MRC) Series Expansion Boards Installation Instructions

1.1 28 Analog Output Board Figure 3: 5-Triac with 2 Analog Output Relay Expansion Board Dimensions, in. (mm) 1 2 3 4 Wire Color Brown Red Orange Yellow Description Relay 6 Only 12 VDC PTS 3.0 76 Analog Output Board 6.0 152 5.5 140 # 1 # 4 # 5 Ground Relay 5 & 6 Together # 6 # 2 # 3 AC - LINE 1 AC - LINE 2 or Neutral Figure 4: 6-Relay with 2 Analog Output Expansion Board Dimensions, in. (mm) 3.0 76 # 4 Screws (2) (not included) RJ11 Junction (included) 1.2 30 0.9 22 120 3048 12 305 Figure 5: EYE IR Transceiver Dimensions, in. (mm) Modular Room Control (MRC) Series Expansion Boards Installation Instructions 3

Wiring Wiring Connections Required for Expansion Boards! CAUTION: Risk of Shock. Before applying power, make all wiring connections and check the connections. Short-circuited or improperly connected wires may result in permanent damage to the unit. IMPORTANT: Make all wiring connections in accordance with the National Electrical Code (NEC) and all local regulations. Each MRC19-EXP expansion board includes a mounting base and the wiring harness to connect to the appropriate headers on the boards. Refer to Figure 6, Figure 7, and Table 1 for detailed information. Table 1: Header Connector Color Chart There are essentially five connections available on the expansion boards. Each is labeled with a header designation such as through. header this is the connection point for the power supply, outputs and Analog Input. On the relay models, this connection is completed at the factory and does not require a field connection. header this is the connection point for the IR transceiver when used in a wireless application. header this is the connection point for the local bus between the MRC Thermostat and the expansion board. header this is the connection point for a local Binary Input such as a window switch (MRC19-MDS1). header this is the connection point for the Analog Outputs (AO). The two AOs share a common. Header Description Pin Wire Color 1 2 3 4 5 1 Brown 24 VAC 2 Red 24 VAC AGC 12 VDC Auxiliary BI AO1 3 Orange Output # 1 12 VDC S5 TX/RX AO2 4 Yellow Output # 2 IR5 TX 5 Green Output # 3 IR5 RX 6 Blue Output # 4 7 Violet Output # 5 8 Grey Auxiliary AI 4 Modular Room Control (MRC) Series Expansion Boards Installation Instructions

Female Connector 6 5 4 Function CINET A (Blue) CINET B (Green) Input #1 (Yellow) Auxiliary Binary Input ( Window Switch or Compressor Alarm) Wire provided By Field Proportional Outputs (if used) 6-Pin Male Connector (Supplied with Thermostat) Note: See Table 1 for exact color and use for all connections. 3 2 1 S5 Bus (Orange) 12 VDC (Red) (Brown) Auxiliary Analog Input ( Aquastat) To Outputs ( Low Voltage Relays or Valves) 24 VAC and MRC19-EXP3-5 Triac/2 AO Expansion Board Shown Figure 6: Typical Connections when MRC Thermostat Is Hard Wired to the Expansion Boards Via Local Bus Auxiliary Binary Input (Window Switch or Compressor Arm) Proportional Outputs (if used) MRC19-EYE0 (IR Eye) # 1 # 4 # 5 Note: See Table 1 for exact color and use for all connections. # 6 # 2 # 3 MRC19-EXP4-6 Relay/2 AO Expansion Board Shown Line Voltage Figure 7: Typical Connections when MRC Thermostat Is Wireless to the Expansion Boards Modular Room Control (MRC) Series Expansion Boards Installation Instructions 5

Technical Specifications Product Power Requirements Agency Listings Ambient Operating Conditions Ambient Storage Conditions Shipping Weight Modular Room Control (MRC) Series Expansion Board 24 VAC at 50/60 Hz, 24 VDC Nominal, 2.4 VA (MRC19-EXP1 and EXP3) 100 to 300 VAC at 50/60 Hz, (MRC19-EXP2 and EXP4) FCC UL CSA 41 to 149 F (5 to 65 C) 0-95% RH noncondensing 33 to 149 F (1 to 65 C) MRC19-EXP1 and MRC19-EXP3 0.13 lb (0.06 kg) MRC19-EXP2 and MRC19-EXP4 0.89 lb (0.40 kg) The performance specifications are nominal and conform to acceptable industry standards. For application at conditions beyond these specifications, consult the local Johnson Controls office. Johnson Controls, Inc. shall not be liable for damages resulting from misapplication or misuse of its products. Controls Group 507 E. Michigan Street P.O. Box 423 Milwaukee, WI 53201 Published in U.S.A. www.johnsoncontrols.com 6 Modular Room Control (MRC) Series Expansion Boards Installation Instructions