ILBIB24DO16-DSUB. Inline Block IO Module for INTERBUS With 16 Digital Outputs; Bus Connection via D-SUB Connectors

Similar documents
ILBPB24DO32. Inline Block IO Module for PROFIBUS With 32 Digital Outputs. AUTOMATIONWORX Data Sheet 6889_en_04. Description

ILB DN 24 DI16 DO16. Inline Block IO Module for DeviceNet With 16 Digital Inputs and 16 Digital Outputs. AUTOMATIONWORX Data Sheet 6885_en_05

PHOENIX CONTACT - 11/2007. This data sheet is only valid in association with the IB IL SYS PRO UM E user manual.

IB IL 24 DI 16 IB IL 24 DI 16-PAC

IBS IL 24 BK RB-T-2MBD

FLM DI 8 M12. Function. Fieldline Modular Device With Eight Digital Inputs. Data Sheet

This data sheet is only valid in association with the IL SYS INST UM E user manual.

IB ST 24 AO 4/EF. INTERBUS-ST analog output module, 4 outputs, 0-10 V, ±10 V, 0-20 ma, 4-20 ma. Data sheet. 1 Description

IB IL 24/48 DOR 2/W-XC-PAC

IBS IL 24 RB-LK-2MBD:

IB IL AO 2/SF... Inline terminal with two analog outputs. AUTOMATION Data sheet 6655_en_06. 1 Description

VersaPoint I/O Module

IB IL 120 DI 1. Function. INTERBUS Inline Terminal With One Digital Input in the 120 V AC Voltage Area. Data Sheet 5764B

IB IL IB IL PAC

ILC 200 IB ILC 200 IB-PAC

VersaMax IP I/O Module

ILB BT ADIO 2/2/16/16

PHOENIX CONTACT - 10/2009

IBS PCI SC/I-T. Controller Board for PC Systems With PCI Bus. Data Sheet 6039B

PSR-SCP- 24DC/URM4/4X1/2X2/B PSR-SPP- 24DC/URM4/4X1/2X2/B

PHOENIX CONTACT - 07/2006

IBS ST (ZF) 24 BK LB-T

PHOENIX CONTACT - 10/2006

GFK-2415A March Type of sensor connection

MINI-PS AC/10-15DC/8

Rexroth Inline terminal with one analog output

PHOENIX CONTACT - 05/2007

NI REM Remote I/O Overview DATASHEET. Digital Output Module for Remote I/O

8 24 V DC, 8 24 V DC,

IBS ST 24 BK-T INTERBUS-S. Data Sheet. Bus Terminal Module. Product Description

MINI MCR-SL-UI-2I(-SP)(-NC)

PSR-SCP- 24DC/SDC4/2X1/B PSR-SPP- 24DC/SDC4/2X1/B

VL BPC MINI. A configurable industrial computer platform. Data sheet 2930_en_F. 1 Description. 2 Features

AXL E IOL AO1 U M12 R

PSR-SCP- 24DC/SSM/2X1 PSR-SPP- 24DC/SSM/2X1

AXL E PB DIO16 M12 6P

QUINT-PS-3x AC/24DC/10

PHOENIX CONTACT - 11/2008

PHOENIX CONTACT - 04/2008

FL MC 2000E (SM40) LC

PHOENIX CONTACT - 01/2007

VL BPC MINI. A configurable industrial computer platform Intel Atom Z510PT CMAT IPC Module Option [I28] AUTOMATION Data Sheet 2930_en_A.

TRIO-DIODE/12-24DC/2X10/1X20

FL SWITCH SFNB. Five- and Eight-Port Standard Function Ethernet Switch with Narrow Housing. AUTOMATION Data Sheet 2642_en_H.

DX561 Digital Input/Output Module

DC562, digital input/output module,

onlinecomponents.com

MINI MCR-SL-PT100-UI(-SP)(-NC)

PSI-MODEM-SHDSL/SERIAL

PSI-MODEM-SHDSL/PB. Broadband PROFIBUS extender, SHDSL PROFIBUS leased line modem. Data sheet _en_03. 1 Description. 1.

IL CAN BK-TC-PAC. Extract from the online catalog. Order No.:

DI561 Digital Input Module

DC561, digital input/output module,

DI572 Digital Input Module

TF501, TF521 Terminal Bases

AI561 Analog Input Module

AO561 Analog Output Module

PHOENIX CONTACT Features

ETD-BL-1T-230(-PT) Multifunctional time relay with various functions and adjustable times. Data sheet. 1 Description

RAD-DO8-IFS. I/O extension module, eight digital transistor outputs. Data sheet. 1 Description

EMD-FL-C-10. Electronic monitoring relay for overcurrent and undercurrent monitoring of direct and alternating current in single-phase networks

TU531, TU532 Terminal Unit

FL SWITCH 8TX. Extract from the online catalog. Discontinued item. Order No.:

AXL E PN DI8 DO8 M12 6P

QUINT-BUFFER/24DC/24DC/40

Part No. Description Product Life Cycle Phase *) unit, 24 VDC, spring terminals. unit, 24 VDC, spring terminals, XC version

FL SWITCH LM 8TX(-E) FL SWITCH LM 4TX/2FX(-E) FL SWITCH LM 4TX/2FX SM(-E)

DPO A4. Description. Module with 4 digital outputs. Datasheet

PSR-MS60. Safety relay for emergency stop, safety door and light grid monitoring. Data sheet. 1 Description

FL SWITCH SFN(T) 16-Port Standard Function Ethernet Switches for Normal and Extreme Environments. AUTOMATION Data Sheet 2806_en_C

MINI MCR-SL-UI-REL(-SP)

PHOENIX CONTACT - 02/2007

IL CAN BK-TC-PAC. Extract from the online catalog. Order No.:

PHOENIX CONTACT - 06/2007. DANGER OF EXPLOSION! Remove an item only when it is not connected to power or if it is located in the non-explosive area.

PHOENIX CONTACT - 01/2010. Features. DANGER OF EXPLOSION! Only remove equipment when it is disconnected and not in the potentially explosive area.

PHOENIX CONTACT - 06/2006

Valueline Industrial PC

PSM-ME-RS232/TTY-P Interface converter for RS-232 to TTY transmission systems

Power Supply, Primary Switch Mode for Universal Use QUINT-PS AC/48DC/5

IB IL RS 232 IB IL RS 232-PAC

AO523 Analog Input Module

MINI MCR-SL-UI-2I-NC. Extract from the online catalog. Order No.:

NI REM Remote I/O Overview DATASHEET. Analog Output Module for Remote I/O

Redundancy Module QUINT-DIODE/40

RAD-DOR4-IFS. I/O extension module, 4 digital relay outputs. INTERFACE Data sheet. 1 Description

MINI MCR-SL-RPS-I-I. Repeater power supply, active. Data sheet. 1 Description

MINI MCR-SL-UI-2I. Configurable signal duplicator. Data sheet. 1 Description

Power Supply, Primary Switch Mode, Narrow Design MINI-PS AC/24DC/1

AI531 Analog Input Module

DC541 Digital Input/Output Module

PHOENIX CONTACT - 11/2008

STEP-PS/1AC/24DC/1.75

DC522 Digital Input/Output Module

FL SWITCH SFN 5TX. Extract from the online catalog. Order No.:

PHOENIX CONTACT - 12/2007

PI-EX-ME-2NAM/COC-120VAC

PI-EX-ME-2NAM/COC-24VDC

FL MC 2000T. Fiber optic converter for 10/100Base-Tx to single- or multi-mode fiberglass with SC-duplex and ST connections. Data sheet 3379_en_B

RAD-DI8-IFS. I/O extension module with 8 digital inputs or 2 pulse inputs. INTERFACE Data sheet. 1 Description

AX522 Analog Input/Output Module

Transcription:

Inline Block IO Module for INTERBUS With 16 Digital Outputs; Bus Connection via D-SUB Connectors AUTOMATIONWORX Data Sheet 7119_en_02 PHOENIX CONTACT - 03/2007 Description The ILB IB 24 DO16-DSUB module is designed for use within an INTERBUS network. It is used to output digital signals. INTERBUS Features Remote bus connection via D-SUB connector 500 kbps transmission speed Diagnostic and status indicators Output Features Connections for 16 digital actuators Connection of actuators in 2 and 3-wire technology Nominal current per output: 0.5 A Total current of all outputs: 8 A Short-circuit and overload protected outputs Diagnostic and status indicators Please refer to the Mounting and Removing Inline Block IO Modules application note (see Ordering Data on page 2). Make sure you always use the latest documentation. It can be downloaded at www.download.phoenixcontact.com. A conversion table is available on the Internet at www.download.phoenixcontact.com/general/7000_en_00.pdf.

Ordering Data Product Description Type Order No. Pcs./Pkt. Inline Block IO module for INTERBUS with 16 digital outputs; bus connection via D-SUB connectors ILB IB 24 DO16-DSUB 2878528 1 Accessories: Connectors Description Type Order No. Pcs./Pkt. D-SUB connector (female connector), solder connection SUBCON 9/F-SH 2761499 1 D-SUB connector (male connector), solder connection SUBCON 9/M-SH 2761509 1 Accessories: Connectors as Replacement Item Description Type Order No. Pcs./Pkt. Connector for the supply (4-pos. MINI COMBICON) FK-MCP 1,5/5-STF-3,81 1851258 50 Connector for the supply (5-pos. MINI COMBICON) FK-MCP 1,5/6-STF-3,81 1851261 50 Connector for digital 4-channel or 16-channel Inline output terminals, with IB IL SCN-12-OCP 2727624 10 color print Accessories: Other Description Type Order No. Pcs./Pkt. Recommended end clamp; placed both to the right and left of the module to secure it on the DIN rail CLIPFIX 35-5 3022276 50 Documentation Description Type Order No. Pcs./Pkt. Mounting and Removing Inline Block IO Modules application note AH ILB INSTALLATION 9014931 1 INTERBUS Addressing data sheet DB GB IBS SYS ADDRESS 9000990 1 Addressing of 16-Channel ILB Modules application note AH ILB 24 DI/DO 16 ADDRESS 9014962 1 General Introduction to the INTERBUS System user manual IBS SYS INTRO G4 UM E 2745211 1 Configuring and Installing INTERBUS user manual IBS SYS PRO INST UM E 2743802 1 Configuring and Installing the INTERBUS Inline Product Range user manual IB IL SYS PRO UM E 2743048 1 7119_en_02 PHOENIX CONTACT 2

Technical Data General Data Housing dimensions with connectors (width x height x depth) Weight Operating mode Transmission speed Connection method for actuators Housing Dimensions ' # 95 mm x 55 mm x 141 mm 254 g (with connectors) Process data mode with 1 word 500 kbps 2 and 3-wire technology # # % ' )! Figure 1 Housing dimensions of the module (dimensions in mm) Ambient Conditions Regulations Developed according to VDE 0160/EN 50178/IEC 62103, UL 508 Ambient temperature (operation) -25 C to +60 C Ambient temperature (storage/transport) -25 C to +85 C Humidity (operation/storage/transport) 10% to 95%, according to EN 61131-2 Air pressure (operation) 80 kpa to 108 kpa (up to 2000 m above sea level) Air pressure (storage/transport) 66 kpa to 108 kpa (up to 3500 m above sea level) Degree of protection according to IEC 60529 IP20 Class of protection Class 3 according to VDE 0106/IEC 60536 Air and creepage distances According to DIN VDE 0110/IEC 60664, IEC 60664A, DIN VDE 0160/EN 50178/IEC 62103 Housing material Plastic, PVC-free, PBT, self-extinguishing (V0) Pollution degree according to 2; condensation not permitted during operation EN 60664-1/IEC 60664-1, EN 61131-2/IEC 61131-2 Surge voltage class II 7119_en_02 PHOENIX CONTACT 3

Electrical Isolation/Isolation of the Voltage Areas Test Distance Incoming remote bus / outgoing remote bus Incoming remote bus / I/O Incoming remote bus / functional earth ground Outgoing remote bus / I/O Outgoing remote bus / functional earth ground I/O / functional earth ground Mechanical Requirements Vibration test, sinusoidal vibrations according to EN 60068-2-6/IEC 60068-2-6 Shock test according to EN 60068-2-27/IEC 60068-2-27 Broadband noise according to EN 60068-2-64/IEC 60068-2-64 Test Voltage 5g load, 2.5 hours in each space direction 25g load for 11 ms, half sinusoidal wave, 3 shocks in each space direction and orientation 0.78g load, 2.5 hours in each space direction Conformance With EMC Directive 89/336/EEC Noise Immunity Test According to EN 61000-6-2 Electrostatic discharge (ESD) EN 61000-4-2 IEC 61000-4-2 Electromagnetic fields EN 61000-4-3 IEC 61000-4-3 Fast transients (burst) EN 61000-4-4/ IEC 61000-4-4 Surge voltage EN 61000-4-5 IEC 61000-4-5 Conducted interference EN 61000-4-6 IEC 61000-4-6 Noise Emission Test According to EN 61000-6-4 Criterion B 6 kv contact discharge 8 kv air discharge Criterion A Field strength: 10 V/m Criterion B Remote bus: 2 kv Power supply: 2 kv I/O cables: 2 kv Criterion A All interfaces: 1 kv Noise emission of housing EN 55022 Class B (residential) Criterion B DC supply lines: ± 0.5 kv/± 1.0 kv (symmetrical/asymmetrical) Signal lines: ± 0.5 kv/± 0.5 kv (symmetrical/asymmetrical) Criterion A Test voltage 10 V Interface: INTERBUS Incoming remote bus Outgoing remote bus Recommended cable lengths Copper cable (RS-422), connected via 9-pos. D-SUB connector; supply electrically isolated; shielding connected with a capacitor to functional earth ground Copper cable (RS-422), connected via 9-pos. D-SUB connector; supply electrically isolated; shielding directly connected to functional earth ground See INTERBUS system data in the IBS SYS INTRO G4 UM E user manual 7119_en_02 PHOENIX CONTACT 4

24 V Module Supply (Communications Power and Actuator Supply; U L and U A ) Nominal value 24 V DC Tolerance - 15%/+ 20% according to EN 61131-2 Ripple ±5% according to EN 61131-2 Permissible range 19.2 V DC to 30.0 V DC Current consumption at U L 70 ma Current consumption at U A1 and U A2 8 A Safety equipment for communications power Surge protection and protection against polarity reversal Safety equipment for actuator supply Connection Digital Outputs Surge protection Via MINI-COMBICON connector Number 16 Connection method for actuators 2 and 3-wire technology Nominal output voltage U OUT 24 V DC Differential voltage at I nom 1 V Nominal current I nom per channel 0.5 A Total current 2 x 4 A Protection Short-circuit and overload protection Nominal load Ohmic 48 Ω / 12 W Lamp 12 W Inductive 12 VA (1.2 H, 50 Ω) Switching frequency with nominal inductive load Overload response Response with inductive overload Reverse voltage protection against short pulses Resistance to permanently applied reverse voltages Validity of output data after connecting the 24 V voltage supply (power up) Response upon power down Limitation of the voltage induced on circuit interruption One-time unsolicited energy Protective circuit type 0.5 Hz (1.2 H, 50 Ω), maximum Auto restart Output may be damaged Protected against reverse voltages Protected against reverse voltages, permissible current 2 A, maximum 1 ms, typical Overcurrent shutdown 0.7 A, minimum Maximum output current when switched off 10 µa The output follows the supply voltage without delay. -41.0 V 1 J, maximum Integrated free running circuit in the output chip When not loaded, a voltage can be measured even at an output that is not set. Typical Power Dissipation With 24 V Supply Voltage Formula to Calculate the Power Dissipation of the Electronics n 2 P TOT = 1.68 W + (0.11 W + ILi x0.28 ) i=1 Where P TOT Total power dissipation of the module i Continuous index n Number of set outputs (n = 1 to 16) I Li Load current of output i 7119_en_02 PHOENIX CONTACT 5

Limitation of Simultaneity, Derating Ambient Temperature (TA) Maximum Load Current (I) at 100% Simultaneity Maximum Load Current (I) at 50% Simultaneity -25 C to +45 C 16 x 0.5 A 8 x 0.5 A +46 C to +60 C I tot = 8 A - ((TA - 45 C) x 0.267 A/ C) 8 x 0.5 A With an ambient operating temperature of up to 45 C and 100% simultaneity, a load current of 0.5 A per channel is permissible. 1) If all four channels are used at a temperature of > 45 C, the permissible working point must be defined according to the above formula. An example can be found in the Configuring and Installing the & INTERBUS Inline Product Range user manual IB IL SYS PRO UM E. # # $ 6 ) + $ & ' ) Approvals For the latest approvals, please visit www.download.phoenixcontact.com. 7119_en_02 PHOENIX CONTACT 6

Internal Circuit Diagram Local Diagnostic and Status Indicators 7 * ) 4 + 4, * 7 5 7 6 2 + & N & N 7 4 + * ) 4,! -!! -!! # 8 8 7 ), & 7 ), ' $ 7 7 ) 7 ) 7 1 6-4 * 7 5 7 7 ) 7 ) Figure 3 2 9 4 % ' ) # Diagnostic and status indicators of the ILB IB 24 DO16-DSUB module Figure 2 Key: OPC N N N : : : % ' * Internal wiring of the terminal points LED Protocol chip (bus logic) Power supply unit with electrical isolation Optocoupler Short-circuit-proof output Designation Color Meaning BUS UL Green Communications power RC Green Remote bus cable check BA Green Bus active RD Yellow Outgoing remote bus disabled PWR UA1 Green Actuator supply 1 (connector 5 and connector 6 for actuators) UA2 Green Actuator supply 2 (connector 7 and connector 8 for actuators) OUT E Red Short circuit or overload at one of the outputs 1 to 4 Yellow Status indicators of the outputs If the error LED (E) of a group of eight outputs lights up (e.g., connector 5 and connector 6), this indicates that a short circuit or overload is present at one or more of the outputs in this group. 7119_en_02 PHOENIX CONTACT 7

Connecting INTERBUS, the Supply, and Actuators Terminal Point Assignment of the MINI COMBICON Connectors for the Connection of the Supply Voltages (Connectors X1 and X2 in Figure 4 on page 8) : : 7 7 ) 7 ) + 8 8 8 +. -!!!! Terminal Point UL UA1 UA2 NC Assignment 24 V communications power U L 24 V actuator supply U A1 24 V actuator supply U A2 Not used Figure 4 1 * 1*, $, 5 7 * @ A H & % & # 4-6 - 1 :! : # # # # $ $ $ $ # & % ' + $ Terminal point assignment of the connectors 4-6 - 7 6 Terminal Point 0V 0V 0V NC FE Assignment GND GND GND Not used Functional earth ground The terminal points for GND (0V) can have a total current of 8 A per terminal point. The maximum current carrying capacity of 8 A must not be exceeded. If the total output current in your application is > 8 A, the module is to be supplied via a minimum of two GND terminal points (0V). The supply points have the same ground potential. All ground supplies on a module are electrically connected with one another. The communications power is also electrically connected via all contacts. In this way it can supply all potentials with just one supply without the need for additional terminals, see Connection example on page 10. 7119_en_02 PHOENIX CONTACT 8

Terminal Point Assignment of the INTERBUS Connectors (Connectors X 3 and X4 in Figure 4 on page 8) Figure 5 A B # ' $ % &! ' # ),,, 1, 1 /, J? Assignment of the remote bus interfaces (D- SUB connector) Remote OUT (outgoing remote bus) Remote IN (incoming remote bus) *,,, 1, 1 /, J? $ % $ $ &! ' # % % * ' # Assignment Remark/Wire Color in the INTERBUS Standard Cable DO Receive Green DO Receive Yellow DI Transmit Pink DI Transmit Gray GND Reference potential Brown Shield (incoming remote bus) Shield (outgoing remote bus) Shield potential is connected with a capacitor to functional earth ground (FE) of the potential jumper. Shield potential is directly connected to functional earth ground (FE) of the potential jumper. In order to assemble the connectors, proceed as described in the IBS SYS PRO INST UM E user manual. Terminal Point Assignment of the Output Connectors (Connectors 5 to 8 in Figure 4 on page 8) Terminal Point Connector 5 (O1) Connector 6 (O2) Connector 7 (O3) Connector 8 (O4) Assignment 1.1, 2.1 1.1, 2.1 1.1, 2.1 1.1, 2.1 Signal output (OUT) 1.2, 2.2 1.2, 2.2 1.2, 2.2 1.2, 2.2 Ground contact (GND) for 2 and 3-wire termination 1.3, 2.3 1.3, 2.3 1.3, 2.3 1.3, 2.3 FE connection for 3-wire termination 1.4, 2.4 1.4, 2.4 1.4, 2.4 1.4, 2.4 Signal output (OUT) 1.5, 2.5 1.5, 2.5 1.5, 2.5 1.5, 2.5 Ground contact (GND) for 2 and 3-wire termination 1.6, 2.6 1.6, 2.6 1.6, 2.6 1.6, 2.6 FE connection for 3-wire termination 7119_en_02 PHOENIX CONTACT 9

Connection Example # $ % & 7 ). - 7 7 ) 7 6 $ 7 6 $ % ' ) Figure 6 Connection example The numbers above the module illustration identify the connector slots. When connecting the actuators observe the assignment of the terminal points to the process data (see Process Data on page 11). The module has an FE spring (metal clip) on the bottom of the electronics base. This spring creates an electrical connection to the DIN rail. Use grounding terminals to connect the DIN rail to protective earth ground. The module is grounded when it is snapped onto the DIN rail. To ensure reliable functional earth grounding of the module even when the DIN rail is dirty or the metal clip is damaged, Phoenix Contact also recommends grounding the module via one of the FE terminal points. 7119_en_02 PHOENIX CONTACT 10

Programming Data ID code 01 hex (01 dec ) Length code 01 hex Process data channel 16 bits Input address area 0 words Output address area 1 word Parameter channel (PCP) 0 words Register length (bus) 1 word Process Data For the assignment of the illustrated (byte.bit) view to your control or computer system, please refer to the DB GB IBS SYS ADDRESS data sheet. Please refer to the application note for addressing 16-channel ILB modules. The documentation can be downloaded at www.download.phoenixcontact.com. Assignment of the Terminal Points to the OUT Process Data Word (Slots 5 to 8) (Word.bit) view Word Word 0 Bit 15 14 13 12 11 10 9 8 7 6 5 4 3 2 1 0 (Byte.bit) view Byte Byte 0 Byte 1 Bit 7 6 5 4 3 2 1 0 7 6 5 4 3 2 1 0 Module Slot 6 (O2) 5 (O1) 8 (O4) 7 (O3) Terminal point (signal) 2.4 1.4 2.1 1.1 2.4 1.4 2.1 1.1 2.4 1.4 2.1 1.1 2.4 1.4 2.1 1.1 Terminal point (GND) 2.5 1.5 2.2 1.2 2.5 1.5 2.2 1.2 2.5 1.5 2.2 1.2 2.5 1.5 2.2 1.2 Terminal point FE 2.6 1.6 2.3 1.3 2.6 1.6 2.3 1.3 2.6 1.6 2.3 1.3 2.6 1.6 2.3 1.3 Status indicator Slot 6 5 8 7 LED 4 3 2 1 4 3 2 1 4 3 2 1 4 3 2 1 Diagnostics Error Table With Diagnostic Data and Status Indicators Error Type Diagnostic Data Status indicators Actuator supply U A1 or U A2 too low No response UA1 and UA2 LEDs are off Short circuit of a digital output I/O error message LED E of the affected output group is red PHOENIX CONTACT 03/2007 7119_en_02 PHOENIX CONTACT GmbH & Co. KG 32823 Blomberg Germany 11 Phone: +49-(0) 5235-3-00 Fax: +49-(0) 5235-3-4 12 00 www.phoenixcontact.com