HID. GE Consumer & Industrial Multilin. High Impedance Differential Module Instruction manual GEK Copyright 2005 GE Multilin

Similar documents
CIO. GE Consumer & Industrial Multilin. Remote CAN Digital I/O Module Instruction manual GEK A. Copyright 2006 GE Multilin

High impedance protection relay

High Impedance Protection Relay SPAE010, SPAE011. Product Guide

Type MVTT 14 and MVTT 15: Static Digital Time delay relays

MIVII. GE Consumer & Industrial Multilin. Digital Voltage and Frequency Relay Instruction manual GEK E. Copyright 2007 GE Multilin

ACCESS 9340/9360 Meter Input/Output Module

02/11/2015

MODEL: M5DY SEN TRONIC AG CURRENT LOOP SUPPLY. [2] POWER INPUT AC Power M: V AC (Operational voltage range V, Hz)

S Reclosers Form 4C Microprocessor-Based Recloser Control KME (120V) and KME (240V) Analog Current Metering Accessory Design II

Sensitive definite time or inverse time earth-fault stage for back-up residual earthfault

MULTI 9 System Catalog UL Recognized C60N Supplementary Protectors

Installation Instructions

MIFII-N. GE Consumer & Industrial Multilin. Single Phase Digital Feeder Protection with Recloser Instruction manual GEK C

MMLG 01, 02, 03, 04 MMLB01

satech TSB-14 MAIN FEATURES

SmartBlock I/O Module HE579MIX577/977 Isolated 4/8 Analog Inputs 2/4 Analog Outputs

Arc protection relay. Features Three-phase overcurrent function. Application

MULTI 9 System Catalog UL Recognized NC100H Supplementary Protectors

Earth-fault Relay SPAJ 110 C. Product Guide

Model 7705 Control Module

PGR-3200 MANUAL INSULATION MONITOR

Conductive Sensors 2 to 4-point level controller Type CL with teach-in

CONTROL MICROSYSTEMS and 5407 Relay Output Module. Hardware Manual

LOGIC CONTROLLER INSTALLATION MANUAL NTR 756 B /E

RM4JA01F current measurement relay RM4-J - range ma V AC

1S20. Arc Fault Monitor Relay. Features. Introduction. ARC Fault Protection

PGR-6101 MANUAL GROUND-FAULT & INSULATION MONITOR

Auxiliary Units for 7SR23 High Impedance Protection Energy Management

G650. GE Consumer & Industrial Multilin. Generator Protection & Control System Instruction manual GEK A

Protection Relays PHASE & RESIDUAL OVERCURRENT

Residual overvoltage relay

Sensitive Earth-fault Relay SPAJ 111 C. Product Guide

MMLB 01/MMLB 02 Multi-finger Test Plug/ Single-finger Test Plug Technical Data MMLB_EN_TD_A

OPERATOR S MANUAL 9000U ISOLATOR

RM4JA32MW current measurement relay RM4-J - range A V AC DC

Voltage regulator. SPAU 341 C 1MRS MBG Issued: July 1998 Status: Revised Version: C/ Data subject to change without notice

KUANTECH (SHEN ZHEN) COMPANY LIMITED KSAFD W1UK

Analog Voltage Combination Module

Conductive Sensors 2 to 4-point level controller Type CL with teach-in

Mini Digital Multimeter

DGSZV-EP DIGITAL GALVANIC LONGITUDINAL DIFFERENTIAL PROTECTION. Application field

MIV. GE Consumer & Industrial Multilin. Digital Voltage and Frequency Relay Instruction manual GEK J. Copyright 2005 GE Multilin

Function permission: yes/no. Operating range: 0.10 to 30 xin (step 0.01) Operating time: 0.02 to 300 s (step 0.01 s) Activation level 100%

SIMOCODE 3UF Motor Management and Control Devices

Operating instructions. Standstill monitor A / / 2011

GE Energy Connections Grid Solutions MMLZ. Technical Data Sheet Auxiliary Modules. Publication reference: MMLZ/EN TDS/B

DIAC/DIFC/DSFC. Single Phase Digital O/C. Single phase or ground overcurrent protection for industrial and utility power systems.

Reyrolle Protection Devices. 7SG117 Argus 7 Synchronising Relay. Answers for energy

Autoranging True RMS Multimeter User Manual

INSTRUCTION MANUAL TRIP CIRCUIT SUPERVISION RELAY GKAD1

2C138. Sensitive Earth Fault Relay. Features. Application. Operation

RM4JA31M current measurement relay RM4-J - range ma V AC

170 ADM to 60 VDC Module Base / 170 ADO Pt. Relay Out Module Base. Version 1.0

SmartBlock I/O Module HE579MIX102 Isolated 6 Relay, 12 DC Inputs, 4 Analog Inputs

ATS22D17Q soft starter-ats22-control 220V-power 230V (4kW)/ V(7.5kW)

User's Guide. Digital Multimeter. Model MN42

Motor protection relays

PHASETRONICS. SCR Power Control Specialists. EP1 Series Power Control Single Phase SCR Amps OPERATION & SERVICE MANUAL

PGR-6100 MANUAL GROUND-FAULT & INSULATION MONITOR

RM35JA32MR Current control relay 0.15A 15A, 2 C/O

TM5C12D6T6L compact I/O expansion block TM5-24 I/0-12 DI - 6 DO transistor - 4 AI - 2 AO

IRI1-ES Sensitive Earth Fault Current Relay. Manual IRI1-ES (Revision A)

OPERATING INSTRUCTION

QUICK START GUIDE. vau4/3. Frequency converter. operating instructions /12

Communication & Networking

NewCode. Comprehensive Motor Protection and Control Relay. Relay Field Input and Output LEDs. LED Fault Indicators

This 4200-RM Rack Mount Kit is for installation in 4200-CAB series cabinets only.

Multilin EPM 4600 Metering Solution

Feeder protection relay SPAA 121 C. Product Guide

User Guide True RMS Multimeter Extech EX205T

IO-AO6X I/O Expansion Module 6 Isolated Analog Outputs

em4 Accessories Digital expansions

RM22LA32MR Level control relay RM22-L V AC/DC - 2 C/O

RM35LM33MW liquid level control relay RM35-L V AC/DC

REYROLLE 2RMLG. Operating Recommendations

EPM g Energy. Multilin BUILDING AUTOMATION POWER METER. BACnet /IP Communications and Energy Measurement KEY BENEFITS APPLICATIONS FEATURES

IST ULTRASTAB Power Supply for high precision transducers

S-14 S-14. Compact Digital Multimeter. Compact Digital Multimeter

VM-11 SERIES MODEL VM-11B ACCELERATION INPUT VIBRATION SIGNAL CONDITIONER INSTRUCTION MANUAL. MANUAL No E1.8. Revised in Mar.

RM22TG. Product data sheet Characteristics. three-phase control relay Vac, 2 C/O. Main. Complementary. Network number of phases

SLIMCON-6 24V DC POWERED ISOLATING SIGNAL CONVERTER

FM2. Economical and compact feeder protection for low voltage feeders. Digital Energy Multilin. Monitoring & Metering. Protection and Control

ENhanced TEChnology. Solid insulated vacuum recloser for power distribution system thru 15kV, 27kV, 38kV. Ver.

Installation, Operation and Maintenance Manual

Combined Overcurrent and Earth-fault Relay SPAJ 140 C. Product Guide

Digital Energy Multilin MIFII. Digital Feeder Protection with Recloser. Instruction Manual GEK Q.

Mini Digital Multimeter

Circuit Breaker Analyzer & Timer CAT-P

Temperature I/O Module HE800MIX963 / HE-MIX963* * HE- denotes plastic case.

INSTALLATION AND MAINTENANCE MANUAL FOR GROUND MONITOR GM-300

ATV310H075N4E variable speed drive ATV kw - 1 hp V - 3 phase

Section 4 Ground-Fault Protection Devices

Three Phase Systems-International PC302-I/MTD

BOP QUICK START GUIDE 100W, 200W, 400W. KEPCO An ISO 9001 Company. BIPOLAR OPERATIONAL POWER SUPPLY WARNINGS I INTRODUCTION II SAFETY.

NJ-Series Power Supply Unit NJ-PA/PD

Zenith DS9000 Dispensing System

RM4TA32 three-phase network control relay RM4-T - range V

Conforms to VDE0435/2021 C/250, VDE0110, VDE0106/P100 Conforms to EN , pren

Universal Contact Input Adapter M 3908

Model Number Structure

Transcription:

g GE Consumer & Industrial Multilin HID High Impedance Differential Module Instruction manual GEK-113064 Copyright 2005 GE Multilin GE Multilin 215 Anderson Avenue L6E 1B3 Markham, ON -CANADA T (905) 294 6222 F (905) 294 8512 E gemultilin@ge.com GE Multilin Avda. Pinoa, 10 48170 Zamudio SPAIN T +34 94 485 88 00 F +34 94 485 88 45 E gemultilin.euro@ge.com Internet: www.gemultilin.com

TABLE OF CONTENTS 1. GETTING STARTED 1-1 1.1 IMPORTANT PROCEDURES 1-1 1.1.1. CAUTIONS AND WARNINGS... 1-1 1.2 INSPECTION CHECKLIST 1-2 1.3 SAFETY INSTRUCTIONS 1-4 1.4 HID OVERVIEW 1-5 1.4.1. MOUNTING & WIRING... 1-6 1.4.2. FRONT PLATE BUTTON... 1-6 2. PRODUCT DESCRIPTION 2-1 2.1 INTRODUCTION 2-1 2.1.1. GENERAL OVERVIEW... 2-1 2.2 ORDERING CODE 2-2 2.3 TECHNICAL SPECIFICATIONS. 2-2 2.3.1. VOLTAGE LIMITERS... 2-2 2.3.2. STABILIZING RESISTORS... 2-2 2.3.3. LATCHING RELAY... 2-3 2.3.4. ENVIRONMENTAL... 2-3 2.3.5. TYPE TESTS & CERTIFICATIONS... 2-4 2.3.6. APPROVALS... 2-4 3. HARDWARE 3-1 3.1 MODULE DESCRIPTION 3-1 3.1.1. MOUNTING... 3-2 3.1.2. EXTERNAL CONNECTIONS DIAGRAM... 3-2 3.1.3. CONTROL POWER... 3-3 3.1.4. MECHANICAL DESCRIPTION... 3-3 3.1.5. MOUNTING... 3-3 3.1.6. REAR DESCRIPTION... 3-4 3.1.7. INPUTS... 3-4 4. ACCEPTANCE TESTS 4-1 4.1 WIRING AND NECESSARY EQUIPMENT 4-1 4.2 VISUAL INSPECTION 4-1 4.3 CONTINUITY 4-1 4.4 ISOLATION TEST 4-2 4.5 MEASURES 4-3 4.6 LATCHING RELAY VERIFICATION 4-4 GEK-113064 HID High Impedance Differential Module 1-1

TABLE OF CONTENTS 1-2 HID High Impedance Differential Module GEK-113064

GETTING STARTED 1. GETTING STARTED 1.1 IMPORTANT PROCEDURES To help ensure years of trouble free operation, please read through the following chapter for information to help guide you through the initial installation procedures of your new device. Before attempting to install or use the device, it is imperative that all warnings and cautions in this manual are reviewed to help prevent personal injury, equipment damage, and/or downtime. CAUTION 1.1.1. CAUTIONS AND WARNINGS The operator of this instrument is advised that if the equipment is used in a manner not specified in this manual, the protection provided by the equipment may be impaired. Installation must be according to the national electric code of the appropriate country. FIGURE 1-1 FRONT VIEW OF HID UNITS GEK-113064 HID High Impedance Differential Module 1-1

GETTING STARTED 1.2 INSPECTION CHECKLIST Open the device packaging and inspect the HID for physical damage. Refer to the label on the side of the device and verify that the model number is the correct model ordered. FIGURE 1-2 IDENTIFICATION LABEL (A4454F21) Please ensure that you receive the following items with your device: - Mounting screws for rear terminals and for fixing the device to a cabinet - Wiring diagram - Certificate of compliance For product information, instruction manual updates, please visit the GE Multilin Home Page (www.gemultilin.com). Note: If there is any physical damage noticed on the device, or if any of the contents listed are missing, please contact GE Multilin immediately. 1-2 HID High Impedance Differential Module GEK-113064

GETTING STARTED GE Multilin contact information: SALES Protection and Control North America: Tel: +1-800-547-8629 Fax: +1 905-201-2098 Email: gemultilin@ge.com Europe: Tel: +34 94 485 88 00 Fax: +34 94 485 88 45 Email: gemultilin.euro@ge.com Worldwide: Tel: +1 905-294-6222 Fax: +1 905-201-2098 Email: gemultilin@ge.com SERVICE Protection and Control North America: Tel: +1-800-547-8629 Fax: +1 905-201-2098 Email: multilin.tech@ge.com Europe: Tel: +34 94 485 88 54 Fax: +34 94 485 88 38 Email: multilin.tech.euro@ge.com Worldwide: Tel: +1 905-294-6222 Fax: +1 905-201-2098 Email: multilin.tech@ge.com The information provided herein does not intend to cover all details of variations of the described equipment nor does it take into account the circumstances that may be present in your installation, operating or maintenance activities. Should you wish to receive additional information, or for any particular problem that cannot be solved by referring to the information contained herein, please contact GE MULTILIN. GEK-113064 HID High Impedance Differential Module 1-3

GETTING STARTED 1.3 SAFETY INSTRUCTIONS WARNING In order to prevent personal damage connect the device to ground. For this purpose, please follow the safety instructions below. The ground screw shown in the following figure must be correctly grounded. Grounding screw FIGURE 1-3 GROUNDING SCREW LOCATION GE Multilin will not be responsible for any damage in the device or connected equipment whenever this elemental safety rule is not followed. 1-4 HID High Impedance Differential Module GEK-113064

GETTING STARTED 1.4 HID OVERVIEW High Impedance Differential protection is a well-known principle where stabilizing resistors provide immunity against external faults. HID modules provide resistors together with voltage limiters (MOV) to be used with a high-speed overcurrent relay in order to obtain a high impedance differential protection scheme. External CT's are differentially connected exactly as for traditional high impedance differential protection relaying. FIGURE 1-4 TYPICAL APPLICATION OF AN HID AS A BUSBAR DIFFERENTIAL PROTECTOR GEK-113064 HID High Impedance Differential Module 1-5

GETTING STARTED 1.4.1. MOUNTING & WIRING Please refer to the HARDWARE chapter for detailed device mounting and wiring instructions. Review all WARNINGS and CAUTIONS. 1.4.2. FRONT PLATE BUTTON The HID front plate incorporates a reset pushbutton to reset the latching relay once the fault has been cleared, in order to eliminate the resistors short-circuit. FIGURE 1-5 HID FRONT PANEL 1-6 HID High Impedance Differential Module GEK-113064

2. PRODUCT DESCRIPTION 2.1 INTRODUCTION PRODUCT DESCRIPTION 2.1.1. GENERAL OVERVIEW HID modules provide resistors together with voltage limiters (MOV) to be used with high-speed overcurrent relay in order to get a high impedance differential protection scheme. The overcurrent relay unit connected in series with the resistors provides high-speed operation for busbar faults involving high-magnitude currents. A voltage-limiting element is connected in parallel to avoid excessively high CT secondary voltages, which can damage current inputs when bus faults occurred. Since the overcurrent unit is relied on only for high magnitude currents, its pickup can easily be set high enough to avoid operation for external faults. The procedure for determining the necessary settings and the resulting sensitivity to low-current bus faults is very simple and straightforward, requiring only knowledge of the CT secondary excitation characteristics and their secondary impedance. For the best possible results, all CT's should have the same rating, and should be a type, like a bushing CT with a distributed secondary winding, that has little or no secondary leakage reactance. A voltage-limiting element is connected in parallel, in order to prevent excessively high CT secondary voltages when bus faults occurred. The HID includes voltage-limiting resistors. This feature makes the HID better suited to those applications where high internal fault currents can be encountered. Typical applications include high impedance differential protection for busbars and electrical machines, such as transformers, generators or motors, as well as restricted earth fault protection. HID modules are available in singlephase models for applications such as restricted earth fault protection in a transformer winding, models with two resistors for applications in transformers with two grounded windings, and three-phase models for busbar high impedance differential protection. Each HID module incorporates 2000-Ohm resistors that provide the associated high impedance relay with stability against external faults, and varistors (MOV Metal Oxide Varistors) in order to limit the voltage peak in the secondary under 2 kv during fault conditions. Additionally, a latching relay is incorporated, whose contacts are aimed to shortcircuit the resistors once the associated relay has tripped. This way, the fault current is prevented from circulating through the resistors. The HID front plate incorporates a Reset pushbutton to reset the latching relay once the fault has been cleared, in order to eliminate the resistors short circuit. The external overcurrent unit may also be used to supplement with the implementation of breaker failure protection, since it may include timers, auxiliary contacts, digital inputs and programmable logic. The combination of HID module with a high-speed overcurrent relay can be applied for bus protection in most cases where CTs having negligible leakage reactance are used. This generally includes any kind of current transformers with a toroidal core if the windings (on the tap used) are completely distributed about the core. Additional functionality provided by the additional overcurrent device includes: time stamped sequence of event recorder, waveform capture, data logger, and communication to remote control centers.6 GEK-113064 HID High Impedance Differential Module 2-1

PRODUCT DESCRIPTION 2.2 ORDERING CODE The information required to completely specify the relay is provided in the following table: HID - - APPLICATION 1 1 Winding Transformer REF 1 resistor + 1 MOV 2 2 Winding Transformer REF 2 resistors + 2 MOV 3 Busbar Application. High Impedance Differential Element LATCHING RELAY / POWER SUPPLY 0 Without latching relay 1 48 Vdc Latching relay 2 125 Vdc Latching relay 3 220 Vdc Latching relay 2.3 TECHNICAL SPECIFICATIONS. SPECIFICATIONS ARE SUBJECT TO CHANGE WITHOUT NOTICE. 2.3.1. VOLTAGE LIMITERS TECNOLOGY: MOV (METAL OXYDE VARISTOR) Rated Voltage (VDC): 350 V Rated Voltage (VAC): 290 V Rated Current (VDC): 4.7 ma ± 50% Pick Voltage: 1,900 V Pick Current: 10 A Power Dissipation: 8 W Rated Power Absorption: 5,400 J with latching relay 10,000 J without latching relay 2.3.2. STABILIZING RESISTORS Models with latching relay Models without latching relay 2kΩ 75W 1kΩ 100W 2-2 HID High Impedance Differential Module GEK-113064

PRODUCT DESCRIPTION 2.3.3. LATCHING RELAY RATED VOLTAGE Latching relay option 1 Latching relay option 2 Latching relay option 3 OPERATION RANGES Operation range Consumption Pickup value 48 VDC 125 VDC 220 VDC OPERATING TIME (at rated voltage) Close time (N.O. contact) Open time (N.C. contact) CONTACTS Continuous current Make and carry Breaking ENVIRONMENTAL Temperature range 80 % to 150 % of rated voltage 8 W at rated voltage 60% of rated voltage < 25 ms. < 20 ms. 10 A continuous 20 A during 1 minute 200 A during 1 second 30 A Maximum relative humidity 95% Dielectric Withstand 5000 VA non inductive at 250 Vac 375 W inductive at 125 Vdc. 250 W inductive at 250 Vdc. -20ºC to +60ºC Between independent circuits 2500 Vca one minute Between circuits and ground Between open contact terminals Mechanical life 2500 Vca one minute 1800 Vca one minute More than 10 million operations 2.3.4. ENVIRONMENTAL Operating Temperatures: -20º C to +60º C Ambient Storage Temperatures: -40º C to +80º C Maximum relative humidity 95% Altitude 2000 m. Max Pollution Degree 2 GEK-113064 HID High Impedance Differential Module 2-3

PRODUCT DESCRIPTION 2.3.5. TYPE TESTS & CERTIFICATIONS The HID system complies with the following standards, which include the standards required by Community Directive 89/336 for the CE marking, in line with European standards. It also complies with the European directive requirements for low voltage, and the environmental and operating requirements established in ANSI standards C37.90, IEC 255-5, IEC 255-6 and IEC 68. Electrical Environment Test Standard Class IEC 60255-5 Insulation - Dielectric 2kV IEC 60255-5 Insulation Impulse Voltage 5 kv, 0.5 J. Atmospheric Environment Test Standard IEC 60068-2-1 Temperature Cold Heat IEC 60068-2-2 Temperature Dry Heat IEC 60068-2-3 Relative Humidity - Manufactured under an ISO9001 Registered system. - CE Marking. 2.3.6. APPROVALS 2-4 HID High Impedance Differential Module GEK-113064

HARDWARE 3. HARDWARE WARNING The HID system incorporates components that might be affected by electrostatic discharge currents flowing through certain component terminals. The main source of electrostatic discharges is human body, especially under low humidity conditions, with carpet floors or isolating shoes. If such conditions are present special care should be taken while manipulating HID modules. Operators, before even touching any components, must make sure that their bodies are not charged by either touching a grounded surface or by using an antistatic grounded wrist bracelet. 3.1 MODULE DESCRIPTION The HID units incorporate the following parts: 1. Latching relay 2. Resistors 3. MOV (Metal Oxide Varistor) 4. Reset button - Metallic Case Latching relay 1 2000 OHM 75 W 2 3 MOV 4 RESET BUTTON FIGURE 3-1 INTERNAL MOUNTING VIEW GEK-113064 HID High Impedance Differential Module 3-1

HARDWARE 3.1.1. MOUNTING The HID module is composed of a black metallic stainless steel case. The case contains a metallic panel to which the MOV (Metal Oxide Varistors) and the stabilizing resistors are hooked, as well as the connections base for the latching relay and internal connections among the stabilizing resistors, MOV, and latching relay contacts. Components are mounted on a base screwed to the rear side of the case. The module is closed with the frontal plate where the latching relay reset button is located. The wiring is made in the rear side of the module. Drilling dimensions are shown on the drilling dimension diagram (FIGURE 3-5) 3.1.2. EXTERNAL CONNECTIONS DIAGRAM FIGURE 3-2 HID 32 WIRING DIAGRAM (226B5177) 3-2 HID High Impedance Differential Module GEK-113064

HARDWARE CAUTION 3.1.3. CONTROL POWER Control power supplied to the relay must match the rated voltage of the device. If the voltage is applied to the wrong terminals, damage may occur. TABLE 3-1: CONTROL POWER VOLTAGE RANGE Option RATED VOLTAGE OPERATION RANGE 0 48 Vdc 38.4~57.6 Vdc 1 125 Vdc 100-150 Vdc 2 220 Vdc 176 264 Vdc 3.1.4. MECHANICAL DESCRIPTION The HID module is available in a case of ½ rack four units high. The metallic case of the unit is highly resistant to corrosion. It is made of stainless steel (AISI 304), coated with an epoxy layer, and the rest of the metallic pieces are covered with a high quality resistive coating that has successfully passed at least 96 hours in the salt spray chamber (S/N ASTM B-117). As well, an IP52 (IEC 529) protection degree against dust and water through the front and with the relay mounted in the panel. 3.1.5. MOUNTING The HID module is secured to the panel with the 4 M6 screws provided with the unit. This allows the user access to the front reset button. The wiring is at the rear of the unit. The drilling dimensions are shown on the drilling dimension diagram. GEK-113064 HID High Impedance Differential Module 3-3

HARDWARE 3.1.6. REAR DESCRIPTION The module is wired through the terminal blocks located at the rear of the unit. The maximum recommended cable section for this terminal board, with the appropriate terminal, is 6 mm2 (AWG 10). 1 5 9 1 5 9 2 6 10 2 6 10 3 7 11 3 7 11 4 8 12 4 8 12 A B C D 1 5 9 1 5 9 2 6 10 2 6 10 3 7 11 3 7 11 4 8 12 4 8 12 FIGURE 3-3 REAR TERMINALS DIAGRAM HID inputs are composed of three elements: Stabilizing resistor MOV Contact from latching relay 3.1.7. INPUTS Inputs vary depending on the HID model chosen. Thus, if the model corresponds to a type 1 application in the model selection list, HID will have one single input; two for a type 2 application and three for a type 3 application. HIDs can be supplied with or without latching relay. If the unit includes a latching relay, then MOVs and resistors are dimensioned according to the HLB tripping time, whereas if the unit does not include a latching relay, resistor and varistors are able to support a tripping time of 250ms. 3-4 HID High Impedance Differential Module GEK-113064

HARDWARE HIDs with latching relay use 2 K 75W resistors, while HIDs without latching relay use 1 K 100 W resistors. FIGURE 3-4 INPUT CONNECTIONS Current flows through stabilizing resistors into current input of the overcurrent module. Once high-speed overcurrent module trips, latching relay contacts short-circuit stabilizing resistor plus current input. In this way, excessive heating causing damage to resistors is avoided. MOV is used to avoid over voltages damaging current input, limiting voltage to 1900V. WARNING In order to prevent personal damage connect the relay to ground. For this purpose, please follow the safety instructions below GEK-113064 HID High Impedance Differential Module 3-5

HARDWARE This module can be mounted together with a high-speed overcurrent module or it can be mounted alone. FIGURE 3-5 shows the drilling panel for this situation. FIGURE 3-5 DIMENSIONS AND DRILLING FOR HID MODULE 3-6 HID High Impedance Differential Module GEK-113064

ACCEPTANCE TESTS 4. ACCEPTANCE TESTS Acceptance tests include tests for both HID module and the latching relay 86. For the latching relay, this manual proposes to test the open and close coils operation, and the correct contact activation. 4.1 WIRING AND NECESSARY EQUIPMENT Necessary equipment: 1 AC voltage source. 1 DC voltage power supply. 1 timer. 1 Multi-meter. External wiring diagram: B5180F* NOTE: Groups described in the tests correspond to an HID model with three inputs. For other models, please check the corresponding external wiring diagram. 4.2 VISUAL INSPECTION Verify that the HID unit has not suffered any damage due to its handling and transport. Verify that all the screws are correctly fixed and that the terminal board is in good condition. Check that the information shown on the relay identification label corresponds to the requested relay model. 4.3 CONTINUITY Test equipment: An Multimeter or continuity measurer with a maximum threshold of 110 Ω. Method: Check for continuity between the grounded screw and any metallic point of the case that has no painting on it. GEK-113064 HID High Impedance Differential Module 4-1

ACCEPTANCE TESTS 4.4 ISOLATION TEST IMPORTANT: During all tests, the screw located on the rear of the relay must be grounded. For verifying isolation, independent groups will be created, and voltage will be applied as follows: 2500 RMS volts will be applied progressively among all terminals in a group, short-circuited between them and the case, during one second. In case the Hi-Pot device used to test the relay trips due to excessive consumption, apply the test between each group and ground one at a time. 2500 RMS volts will be applied progressively between groups, during one second. Group 1 (LATCHING RELAY contacts): A5 A6 A7 A8 A9 A10 A11 A12 B1 B2 B3 B4 B5 B6 B7 B8 Group 2 (LATCHING RELAY coils): A1 A4 B9 B12 Group 3 (Pushbutton): C5 C6 C7 C8 Group 4 (Analog Group): C10 C11 C12 D6 D7 D8 D2 D3 D4 Consumption will not be higher than 20 ma. 4-2 HID High Impedance Differential Module GEK-113064

ACCEPTANCE TESTS 4.5 MEASURES Latching relay coil resistor (only for latching relay option) : Latching relay option Terminals A1 A3 Terminals B10 B12 1 (48 Vdc) 340 Ohm 340 Ohm 2 (125 Vdc) 2K15 2K15 3 (220 Vdc) 4K2 4K2 NOTE: An error of 20% will be admitted Resistors Measure: Check that the resistor value between terminals is: 2K with latching relay 1K without latching relay NOTE: An error of 12% will be admitted C12 D8 C11 D7 C10 D6 Thyrites current measure: Thyrite Terminals C12 D4 C11 D3 C10 D2 Applied voltage 290 Vac 2-10 ma 2 10 ma 2-10 ma GEK-113064 HID High Impedance Differential Module 4-3

ACCEPTANCE TESTS 4.6 LATCHING RELAY VERIFICATION Contact test: Check with the external wiring diagram that all the auxiliary contacts of the latching relay are open and, therefore, there is no continuity between them. Apply voltage to terminals +A1 y A4 and verify that latching relay contacts operation time is below 25 ms. Verify that all auxiliary contacts have changed their position to closed and that there is continuity between each pair of them. Apply voltage to terminals +B9 and B12 and verify that latching relay contacts opening time is below 20 ms. Check that all auxiliary contacts have changed to their default position (open) and, therefore, there is no continuity between each pair of them. Lamp: Apply the latching relay rated voltage to terminals CN-A6 and CN-A9 and check that the button lightens up. Switch the voltage off and check the lamp turns off. Press the button and check for continuity between CN-A7 and CN-A8 4-4 HID High Impedance Differential Module GEK-113064