Fair City Plaza. Task: Diagnose problems, recommend improvements for small municipal district cooling system

Similar documents
UC DAVIS THERMAL ENERGY STORAGE (TES) TANK OPTIMIZATION INVESTIGATION MATTHEW KALLERUD, DANNY NIP, MIANFENG ZHANG TTP289A JUNE 2012

Your Solution For Energy and Cost Savings. McQuay Packaged Chiller Plant

T66 Central Utility Building (CUB) Control System Reliability, Optimization & Demand Management

where we are, where we could be, how we can get there. 12/14/2011

Supplement to PM WSC/WDC-1 MicroTech II for Centrifugal Compressor Water Chillers

Next Generation DCP Optimization using MV VSDs

Building Re-Tuning (BRT) Lesson 4: SOI Air-Handling Unit Part II

MPC Air-Cooled Chillers MPC-FC Free-Cooling Chillers

that may have a direct effect on your bottom line. The question

Water cooled chiller plant (all-variable)

Dykin Engineering Part & Services Sdn. Bhd.

AIR-COOLED A (Surprisingly) Cost-Effective Alternative to Water-Cooled Chiller Plants

Trane mytest Water-cooled Chiller Performance Validation What you spec is what you get *

Table of Contents. Executive Summary Site and Unit Background Chiller Chiller Appendix... 11

CHAPTER/REGIONAL TECHNOLOGY AWARD - SHORT FORM

Driving Proactive Facility Operations with Automated HVAC Diagnostics

REPORT TO THE BUSINESS ADMINISTRATION COMMITTEE

Optimizing Chilled Water Plant Performance. David Herman, PE, LEED AP Principal EnerG Associates, LLC

CASE STUDIES. Brevard Community College: Florida Power & Light. Cape Canaveral Air Force Station: NORESCO

Digital Realty Data Center Solutions Digital Chicago Datacampus Franklin Park, Illinois Owner: Digital Realty Trust Engineer of Record: ESD Architect

The Future. Today. YZ MAGNETIC BEARING CENTRIFUGAL CHILLER

Motivair MLC-SC Air-Cooled Scroll Chillers Tons

DEDICATED HEAT RECOVERY UNIT (DHRC)

Designing Ultra-Efficient Building Cooling Systems

WO P-NF-L-M-407c Spec Submittal

Future of Cooling High Density Equipment. Steve Madara Vice President and General Manager Liebert Precision Cooling Business Emerson Network Power

Retro-Commissioning Report

Position Title: H V A C T E C H N I C I A N. G.E.D. or High School Diploma required, an Associate s Degree is preferred.

Data Center Energy Savings By the numbers

Thermal Diffusivity Instruments DLF-2 with EM-1600

Installation Service. 1.0 Executive Summary. Factory Trained Technician Train Customer Support Staff On Basic Operation Of The Equipment

National Service Center

Optimiz Chilled January 25, 2013

7 Best Practices for Increasing Efficiency, Availability and Capacity. XXXX XXXXXXXX Liebert North America

SCHENDT ENGINEERING PRIOR EXPERIENCE

Trane Engineering News Chiller Plant Case Study: Variable-Primary Flow Series Chillers with Free Cooling

FLORIDA STATE UNIVERSITY MASTER PLAN 10 Utilities

Drives and motors. A guide to using variable speed drives and motors in data centres Meeting your Carbon Reduction Commitment (CRC)

CGWN/CCUN indoor liquid chillers The compact AquaStream² solution

All Rights Reserved - 1

FX2-CHILLER. Digital Control. Operations Manual

Saving Energy and Reducing Costs Through Better Use of Building Automation Systems

Commercial Retro-Commissioning Program Manual for 2016 SECTION 1

Drives Motors and PLCs

Cooling. Highly efficient cooling products for any IT application. For More Information: (866) DATA CENTER SOLUTIONS

DATA CENTER PRECISION COOLING: The Need For A Higher Level Of Service Expertise

EXCEEDING EXPECTATIONS

JEFFERSON COLLEGE COURSE SYLLABUS HRA249 COMMERCIAL REFRIGERATION SYSTEMS. 5 Credit Hours. Prepared by William Kaune November 30, 2010

Data Center Precision Cooling: The Need For A Higher Level Of Service Expertise. A White Paper from the Experts in Business-Critical Continuity

Must possess Universal EPA Section 608 certification; OR Type I AND Type II EPA Section 608 certification.

Large Tonnage Chillers. Kingsley Hu Technical Support Engineer

Presentation. Guaranteed Energy Savings Performance Project

DATA CENTER LIQUID COOLING

MLC Air-Cooled Chillers MLC-FC Free-Cooling Chillers MLC-AD Adiabatic Chillers

Energy Efficiency Retrofit Technologies for RTUs

Chiller Plant Optimization: A Case Study

Building Management Systems (BMS) Back to Basics. Presented By: Andrew Smith Leader Building Technologies A.G. Coombs Advisory

Passive RDHx as a Cost Effective Alternative to CRAH Air Cooling. Jeremiah Stikeleather Applications Engineer

IN-DEPTH UNDERSTANDING OF HVAC EQUIPMENT & SYSTEM SPECIFICATIONS AND PERFORMANCE 11 & 12 JULY 2016 WISMA IEM

GP SERIES Packaged Chillers

DUKE UNIVERSITY DESIGN & CONSTRUCTION STANDARDS

Chiller Replacement and System Strategy. Colin Berry Account Manager

Analyze and Implement: Modernizing an Airport Central Utility Plant

User Guide. FreeCool : Free Cooling unit V1.1 ENGY-SVU001A-GB

Setting New Standards for Ultra High Performance HVAC

Setting New Standards for Ultra High Performance HVAC

Danfoss Turbocor Learning Center

Danfoss Turbocor Learning Center

Technologic 502 Variable Speed Pump Controller

What is the Carrier ChillerVu series counterflow application?

Magnitude magnetic bearing centrifugal chillers

Magnitude magnetic bearing centrifugal chillers

Predictive Maintenance in a Mission Critical Environment

Engineered Energy Solutions An Overview. Controls, Automation and Energy Conservation

19XR CONTROLS UPGRADE with Optional VFD control

Daikin Blueprint: Five New Strategies to Reduce Operational Expenses for Air-cooled Chillers

Carrier Hong Kong Limited. Carrier Comfort Network. - optimizes the performance of HVAC Systems & is the premier solution for Building Control

WSHP-IOP-2 May Installation, Operation, and Programming. Tracer ZN510 Controller

ENCLOSURE HEAT DISSIPATION

32MP Gateway. Overview and Configuration Manual

DOWNLOAD OR READ : TRANE RTAC 155 BINDIG MANUAL PDF EBOOK EPUB MOBI

Commercial HVAC and Other Measures for 7P. Outline

SMART VENTILATION MANAGEMENT: CHANGING THE WAY WE THINK ABOUT VENTILATION

Trane Series S CenTraVac Chillers with AdaptiSpeed Technology tons

DATA CENTER EFFICIENCY: Data Center Temperature Set-point Impact on Cooling Efficiency

Measuring and Managing a Data Center Cooling Shutdown

FOX-50 Heat Flow Meter

HIGH DENSITY DATACOM INTEGRATED COOLING SYSTEM.

CONTROLS. Quantum HD. Heavy Duty Performance In High Definition

Air-Cooled Series R Chiller

REPORT. Energy Efficiency of the San Diego Supercomputer Center and Distributed Data Centers at UCSD. Prepared for:

Datacenter Efficiency Trends. Cary Roberts Tellme, a Microsoft Subsidiary

Achieving Operational Excellence

Drives and motors. A guide to using variable speed drives and motors in data centres Meeting your Carbon Reduction Commitment (CRC)

What is SCADA? What is Telemetry? What is Data Acquisition? Differences between SCADA and DCS? Components of SCADA. Field Instrumentation

1200 West 7th Street, Los Angeles, CA Smart.

Specification and Design Catalog. Waterside Economizer

PROCESS COOLING STUDY WORKSHEET

APC InRow Cooler Prototype Initial Report - Test Setup Verification. H. Coles, S. Greenberg Contributing: J. Bean (APC) November 18, 2011

Control. Part B, Section 2. This section covers the following unit configurations. 3400V 3500V Voltage 1, 2, 3 Pump Piston (D, E, F, G)

Transcription:

Fair City Plaza Task: Diagnose problems, recommend improvements for small municipal district cooling system The Fair City Plaza district cooling system provides chilled water to five buildings in a downtown museum district. In 1996, the system's three chillers were converted to use refrigerant R-134a, and a chilled water storage tank was installed to allow a large part of the system's cooling loads to be met using relatively inexpensive off-peak electricity. Following these modifications, cooling costs have decreased significantly. However, a number of operation and maintenance problems have arisen. The most serious of these is that the chillers have been experiencing major breakdowns. There are also questions about the ability of the system to meet its cooling loads. The HVAC&R Center at the University of Wisconsin was engaged to evaluate the design and operation of the district cooling system, and to review the heating, ventilating and air-conditioning (HVAC) systems in the individual buildings. Our report, which was produced with the support and assistance of Central Power and Light Company and EPRI, summarizes our analysis and conclusions and provides our recommendations for addressing the problems.

System Description Three 450-ton chillers 1.47 million gallon chilled water storage Serves five buildings Convention Center Auditorium Art Museum Museum of Science Harbor Playhouse The district cooling plant consists of three centrifugal chillers each rated at 450 tons cooling capacity, a 1.47-million-gallon chilled water storage tank, and associated pumps, cooling towers and piping. The chillers are rated at 450 tons capacity and 0.80 kw/ton when chilling 900 gpm of chilled water from 54 F to 42 F. The chillers are piped in parallel, each with its own 50 hp pump, with common supply and return headers. Two 200-hp variable-speed secondary pumps, one of which is a backup, circulate water to the five buildings served by the system. The storage tank is piped between the connection of the chiller supply to the secondary pumps, and the chilled water return from the buildings. The chilled water storage tank is designed to store 13,800 ton-hours of cooling, with a 15 F temperature differential (40-55 F). The chillers and pumps are located in a mechanical room in a lower level of the Convention Center. The storage tank is located about 500 feet to the west of the mechanical room. The five buildings are located at distances of 150 to 350 feet from the mechanical room. The current operating strategy eliminates all chiller operation during the electric utility's on-peak hours of 1:00 pm to 7:00 pm, dramatically reducing electric demand charges.

Major Complaints Chillers breaking down Difficulty meeting loads Hard to control the system Equipment deteriorating The most serious problem facing the system at this time is chiller failures. Chiller 1 failed in July 1998, Chiller 2 failed in January and Chiller 3 failed in March of this year, and the repair costs were about $20,000 for each chiller. There has been some question as to whether the chillers and thermal storage tank have sufficient capacity to meet the cooling loads currently existing in the five buildings served by the district cooling system. Currently, the Museum of Science, as well as some of the other buildings, are not receiving sufficient cooling capacity from the central plant. Control valves nearest the plant are sometimes forced open by the high pressure differential. This makes proper temperature control difficult, and also bypasses cold water to the return. Rooftop air-handling units on several buildings have deteriorated from exposure to the weather and are in poor condition. Control valves corrode quickly and some have had to be replaced within three years of being installed.

Operational Difficulties Chillers cycling excessively Air entering the system Can't control flow to loads Not utilizing storage capacity Operators often have to bleed large amounts of air from the system. The EMS logs show many instances when the EMS was commanding a chiller to restart, at one-minute intervals, sometimes for hours at a time. While the logs do not indicate how often the chiller actually started in response to these commands, the operating staff indicated that the chillers often underwent repeated starts and stops. The design of the distribution system has no provision for controlling the chilled water flow to each building at its desired level. The maintenance staff have attempted to adjust flows by setting manual valves but these manual settings cannot respond to changing conditions, and they often have unintended consequences. Operating data show that the storage tank rarely operates with a thermocline layer separating warm and cold regions of the tank, as it should.

2000 1800 1600 1400 1200 1000 800 600 400 200 0 0 2 4 6 8 10 12 14 16 18 20 22 24 1000 900 800 700 600 500 400 300 200 100 0 0 2 4 6 8 10 12 14 16 18 20 22 24 System Analysis Interviewed operators Observed system operation Reviewed trend logs Calculated load profiles 55.0 Tons Load Chiller Charging tank Met by tank Met by chiller Hour 53.0 Design Load Profile 51.0 49.0 Load (Tons) Future Load Profile 47.0 45.0 43.0 Current Load Profile 41.0 39.0 Hour 37.0 35.0 1 11 21 31 41 51 61 71 81 91 101 111 121 131 141 151 161 171 181 191 201 211 221 231 241 251 261 271 281 291 HVAC&R Center staff visited the site, met with plant operating personnel and staff from the buildings served by the system, and observed the condition and operation of the system and its components. With the assistance of CP&L/CSW staff and the plant operators, we gathered data under various normal and simulated operating conditions. We used this information, along with design documentation and historical trend data collected from the automatic control system, to analyze the performance and the capabilities of the system. We developed estimates of the original design load profile, the current load profile, and the near-term future load profile. We evaluated the operation of the chilled-water storage tank, and estimated its capacity under various conditions. Using this information, we developed diagnoses of the problems facing the system, and recommendations to resolve them.

Diagnosis - System No documentation of design intent Limited training for operators Some features "value-engineered" out Return pipe from tank Temperature sensors There is very little documentation on the design intent for this system. The O&M manual supplied by the storage tank manufacturer provides information on the design operating conditions and maintenance requirements for the tank itself. However, the operating staff has received no information on operating modes and control sequences for other parts of the system or for the system as a whole. The distribution system was originally designed with a primarysecondary configuration, but the return pipe from the storage tank to the central plant was deleted to save cost. Hydraulically, the storage tank is located at one end of a common return header, and the chillers are located at the other end. As currently configured, it is not possible to control the return temperature to the storage tank. Much of the instrumentation needed for plant operation was also deleted from the original design to save costs. Without load measurements for each of the buildings, and return temperatures for loads, storage tanks, and chillers, it is difficult for operators to know how well the loads are being met. Without measurements of chiller power draw, there is no way to gauge the efficiency of the system. With no tank level sensor, operators measure the level manually by dropping a line into a hatch on top of the tank.

Diagnosis - Chillers Water leaking from the system Tank level drops below upper diffuser Air enters the piping Pumps become air bound Flow to chillers stops Chiller safeties wired incorrectly flow switch not working properly excessive cycling leads to overheating Incorrect bearings The system has been losing water at an average rate of 525 gallons per day. When the water level falls below the upper tank diffuser, air is drawn into the system. When air collects at the chilled water pumps, the pumps become air bound, flow through the chillers stops, and the chiller shuts down. The flow switches should prevent any compressor operation when there is no flow, but a service technician observed Chiller 1 starting when both its chilled water pump and its condenser water pump were off. It appears that the anti-short-cycling controls are not operating correctly. Frequent starts and stops cause excessive wear and tear on a chiller's motor, gears, and bearings. Even if the 20-minute delay is functioning correctly, repeated starting and stopping causes undue stress on the machine. The breakdowns of Chillers 1 and 2 are linked to mechanical wear and stress on the gears and bearings. Chiller 3 failed because of an overheated motor, which can also be due to excessive starting and stopping. When Chiller 1 was rebuilt in 1998, it was found that one of the impeller bearings was not the correct size, which could have increased the stress on rotating components. This bearing was presumably installed when the chillers were converted to R-134a refrigerant in 1996. The other two chillers may also have had incorrect bearings installed.

Diagnosis - Capacity Low return temperature reduces chiller capacity reduces storage capacity prevents tank from stratifying Flow control disabled low flow reduces capacity Design has no provision for maintaining return temperatures System is capable of meeting future loads A chiller will provide only enough capacity to cool the return water to the setpoint temperature. If the return temperature is low, less capacity is needed to cool it to the setpoint, so less capacity is available. The return temperature to the chillers is nearly always 48 F or less. With the current chilled water supply temperature of 38 F, this limits the chillers to 83% or less of their full capacity. There are no provisions in the design of the system to maintain the required 55 F return temperature to the storage tank. The return temperature to the tank is usually below 47 F, and is almost never above 50 F. This reduces the usable storage capacity of the tank to less than two-thirds of its nominal value. It also limits the ability of the tank to properly stratify. The chiller flow rates change depending on how many chillers are running. The system has automatic control valves to maintain the correct flow rate to each chiller. However, the control valves have been set to a fixed position and do not modulate to control the flow rate. When the flow rate is below its design value, the chiller output is reduced proportionally. Our analysis shows that with appropriate operational changes, the system is capable of meeting current and near-term future loads, with some capacity to spare.

Recommendations Find and repair leak(s) Monitor tank level remotely Correct the chiller controls Install flow control for tank and loads Revise the central plant operating strategy Management-level recommendations include: Create a System Manual with the information needed to understand, operate, and maintain the system. The System Manual should document the design intent, control sequences, equipment capacities, operating procedures, and other pertinent information. Provide training to upgrade the capabilities of the staff. Operators should understand stratified chilled water storage concepts, the design intent for the central plant and associated building systems, and system operating modes and control sequences. Operators should also be familiar with HVAC fundamentals, troubleshooting, and interactions. Operations-level recommendations include: Find and fix the leak(s) in the system Install a level sensor on the storage tank and don't ever let the water level fall below the minimum level. Correct the flow switches and anti-recycle controls on the chillers Restore chiller flow control valves to automatic operation, and provide flow control for storage tank and loads. Revise the operating sequences for the chillers, the thermal storage tank, and the variable-speed secondary pump in order to properly charge the storage tank, operate the chillers more effectively, and better control the chilled water flow.