S800 I/O 3BCNIIT F HW02-S800-V0102 Rev. 02/01 Page 1
S800 I/O S800 I/O 3 : Fieldbus Communication Interface (FCI) I/O Module Module Termination Unit (MTU), Compact or Extended version 3BCNIIT F HW02-S800-V0102 Rev. 02/01 Page 2
S800 I/O CI830 PROFIBUS - DP I/O / / I/O I/O 3BCNIIT F HW02-S800-V0102 Rev. 02/01 Page 3
S800 I/O MTU 2, 50 250 2 DIN- / I/O- I/O 3BCNIIT F HW02-S800-V0102 Rev. 02/01 Page 4
S800 I/O FCI I/O I/O MTU MTU S800 I/O 3BCNIIT F HW02-S800-V0102 Rev. 02/01 Page 5
S800 I/O MTU 2 ~ ~ = + - 3BCNIIT F HW02-S800-V0102 Rev. 02/01 Page 6
S800 I/O MTU ~ = + ~ - 3BCNIIT F HW02-S800-V0102 Rev. 02/01 Page 7
S800 I/O FCI I/O Modules Internal bus Superv. 24V A Superv. 24V B A B 24 V D.C. Isolation; - I/O Module to I/O bus, - I/O Module to I/O Module - Isolation channel to channel ( or group) Overload/current protection Optional PROFIBUS-DP RS485 I I AI AO DI 24 V DO 220 V DO 24 V Class 1, Division 2 Certified 3BCNIIT F HW02-S800-V0102 Rev. 02/01 Page 8
S800 I/O SD811, 110-230 V a.c., 24V d.c. 2,5A SD812, 110-230 V a.c., 24V d.c. 5A SD811 3BCNIIT F HW02-S800-V0102 Rev. 02/01 Page 9
S800 I/O Electrical safety IP20, Ventilated modules Overvoltage category, U < 50V, II IEC664 (50V isolation voltage) Overvoltage category, U > 50V, III IEC664 (250V isolation voltage) Meets EC EMC directives (CE Marked) Ambient Temperature +55 C Horizontal mounted modules (both compact & extended MTU) +40 C Vertical mounted modules (compact MTU, +55 C for Extended MTU) Corrosive gases According to ISA class G2 (1000Å/28 days) pollution degree 2 3BCNIIT F HW02-S800-V0102 Rev. 02/01 Page 10
S800 I/O CI830 I/O 2) I/O 3) 162 mm (6,4 ) 104 mm (4 ) 84 mm (3,3 ) 58 mm (2,3 ) 20 mm (0,79 ) 20 mm (0,79 ) 120 mm (4,7 ) Height = 122 mm (4,8 ) 1) Height = 122 mm (4,8 ) 1) 1) Including height of DIN-Rail 2) Compact MTU (2-wire connection) 3) Extended MTU (3-wire connection) 3BCNIIT F HW02-S800-V0102 Rev. 02/01 Page 11
S800 I/O ModuleBus & I/O Clusters ModuleBus FCI I/O ModuleBus FCI I/O ModuleBus FCI I/O-clusters FCI I/O-modules PROFIBUS-DP I/O-station Electrical ModuleBus Optical ModuleBus Optical modem I/O-modules I/O-cluster 3BCNIIT F HW02-S800-V0102 Rev. 02/01 Page 12
S800 I/O modulebus 3BCNIIT F HW02-S800-V0102 Rev. 02/01 Page 13
Optical ModuleBus & I/O Clusters I/O 12 I/O Modules I/O Fiber Optic ModuleBus S800 I/O Station Cluster 1 TB820 Optical Modem Cluster 2 to Cluster 7 3BCNIIT F HW02-S800-V0102 Rev. 02/01 Page 14
Options - Fiber Optic ModuleBus TB820 ModuleBus Modem ModuleBus ModuleBus Modems 7 12 I/O 24 I/O I/O 384 DI/DO 192 AI/AO Fiber Optic ModuleBus TB820 Optical Modem S800 I/O Station Cluster 1 Cluster 2 to Cluster 7 3BCNIIT F HW02-S800-V0102 Rev. 02/01 Page 15
Electrical ModuleBus TK801, Extension Cable, length 0,3, 0,6, 1,2 m (1, 2, 4 ft.) FCI Bus Terminator TB 807 TB 805, Extension cable outlet TB 806, Extension cable inlet Maximum 2.5 meters (8.2 ft.) TK801, Extension cables, 0,3m (1ft.) 0,6m (2 ft.) 1,2m (4 ft.) TB805, Module bus Outlet TB806, Module bus Inlet TB 807 Module bus Termination 3BCNIIT F HW02-S800-V0102 Rev. 02/01 Page 16
Electrical ModuleBus Extension cable TK801 with Outlet TB805 and Inlet TB806 Extension cable used in a S800 I/O-Station 3BCNIIT F HW02-S800-V0102 Rev. 02/01 Page 17
Optical ModuleBus & I/O Clusters - Simplex Connection I/O Station Maximum length of any cable is: 15m (49 Ft.) for Plastic Fiber 200m (667 Ft.) for HCS Glass Fiber Rx Tx Cluster 1 TB820 Cluster 2 TB820 Cluster 3 TB820 Cluster 7 TB820 Rx Tx Rx Tx Rx Tx Rx Tx Simplex FCI TB820 I/O 3BCNIIT F HW02-S800-V0102 Rev. 02/01 Page 18
Optical ModuleBus & I/O Clusters - Duplex Connection I/O Station Maximum length of any cable is: 15m (49 Ft.) for Plastic Fiber 200m (667 Ft.) for HCS Glass Fiber Rx Tx Cluster 1 TB820 Rx Tx Cluster 2 TB820 Rx Tx Cluster 3 TB820 Rx Tx Cluster 7 TB820 Rx Tx Rx Tx Rx Tx Rx Tx Duplex I/O 3BCNIIT F HW02-S800-V0102 Rev. 02/01 Page 19
Optical ModuleBus & I/O Clusters - Mixed Connection I/O Station Maximum length of any cable is: 15m (49 Ft.) for Plastic Fiber 200m (667 Ft.) for HCS Glass Fiber Rx Tx Cluster 1 TB820 Rx Tx Cluster 2 TB820 Rx Tx Cluster 3 TB820 Rx Tx Cluster 7 TB820 Rx Tx Rx Tx Rx Tx 3BCNIIT F HW02-S800-V0102 Rev. 02/01 Page 20
PROFIBUS Dual Media Provides Redundant Physical Path for PROFIBUS data Protects against loss of communication due to cable break PROFIBUS-DP Dual Media Controller RLM 01 S800 I/O Station 3BCNIIT F HW02-S800-V0102 Rev. 02/01 Page 21
S800 I/O 32 I/O 24 I/O I/O Physical bus: RS-485 up to 12 Mbit/s Maximum PROFIBUS-DP length =< 1200m Controller S800 I/O Station PROFIBUS-DP S800 I/O Station Optical Modulebus 1-7 S800 I/O Station 3BCNIIT F HW02-S800-V0102 Rev. 02/01 Page 22
Analog I/O Modules Available AI810 8 ch Analog Input Current Source, 0(4)-20mA, 0-10V, 12 bits, Accuracy 0.2%, Isolation: 1 group of 8 AI820 4 ch Analog Input -20-+20mA, -10-+10V, -5-+5V, 12 bits, Accuracy 0.2%, Isolation: 1 group of 4 AI830 8 ch RTD Input 100 ohm Pt, Ni, Cu, 120 ohm Ni, 0-400 ohm resistor, 15 bits, Accuracy 0.1% AI835 8 ch (7+1 cold junct) Thermocouple Input Type B, C, E, J, K, N, R, S, T, +/-75mV, 14 bits, Accuracy 0.2% AI890 8 ch Analog input with integrated Intrinsic safe interface 0(4)-20mA, 12 bits, Accuracy 0.1%, Isolation: 1 group of 8 3BCNIIT F HW02-S800-V0102 Rev. 02/01 Page 23
Analog I/O Modules Available AO810 8 ch Analog Output 0(4)-20mA, 14 bits, Accuracy 0.2%, Isolation: 1 group of 8 AO820 4 ch Isolated Analog Output -20-+20mA, -10-+10V, -5-+5V, 12 bits, Accuracy 0.2%, Isolation: Individual AO890 8 ch Analog Output with integrated Intrinsic safe interface 0(4)-20mA, 12 bits, Accuracy 0.1%, Isolation: 1 group of 8 3BCNIIT F HW02-S800-V0102 Rev. 02/01 Page 24
Binary I/O Modules Available DI810 16 ch Binary Input 24 VDC, Isulation: 2 groups of 8 DI811 16 ch Binary Input 48 VDC, Isulation: 2 groups of 8 DI814 16 ch Binary Input (current source) 24 VDC, Isulation: 2 groups of 8 DI820 8 ch Binary Input 110 VDC / 120 VAC, Isulation: Individual DI821 8 ch Binary Input 220 VDC / 230 VAC, Isulation: Individual DI890 8 ch Binary Input With integrated Intrinsic Safe barrier Namur or contact, Isulation: Individual DP820 2 ch Pulse counter 0,25 Hz...1,5 MHz 5/24 VDC, Isulation: Individual 3BCNIIT F HW02-S800-V0102 Rev. 02/01 Page 25
Binary I/O Modules Available DO810 16 ch Binary Output (transistor source) 24 VDC, 0.5 A, Isulation: 2 groups of 8 DO814 16 ch Binary Output (transistor sink) 24 VDC, 0.5 A, Isulation: 2 groups of 8 DO815 8 ch Binary Output (transistor source) 24 VDC, 2 A, Isulation: 2 groups of 4 DO820 8 ch Binary Output (Relay N.O) 5-250 V AC/DC, 3A, Isulation: Individual DO821 8 ch Binary Output (Relay N.C) 5-250 V AC/DC, 3A, Isulation: Individual DO890 4 ch Binary Output with integratred Intrinsic safe interface 12 VDC, 40 ma, Isulation: Individual 3BCNIIT F HW02-S800-V0102 Rev. 02/01 Page 26
S800L I/O Modules Available AI801 8 ch Analog Input Current Source, 0(4)-20mA, 0-10V, 12 bits, Accuracy 0.2%, Isulation: 1 group of 8 AO801 8 ch Analog Output 0(4)-20mA, 12 bits, Accuracy 0.2%, Isulation: 1 group of 8 DI801 16 ch Binary Input 24 VDC, Isolation: 1 group of 16 DO801 16 ch Binary output 24 VDC, 0.5 A, Isolation: 1 group of 16 3BCNIIT F HW02-S800-V0102 Rev. 02/01 Page 27
Slide Presentation Information Sheet About the Presentation Title: Control IT S800 I/O Brief: S800 I/O Basic concept Intended Audience: Usage Restrictions: Release : Feb. 1, 2000 No. of Pages: 32 About the Author First edition Revised Special Instructions: Please provide the above information on all presentations. This slide can then be hidden and will not show or print. 3BCNIIT F HW02-S800-V0102 Rev. 02/01 Page 28 Customer (Management), SI, Sales None Patrick Cao : Patrick-peng.cao@cn.abb.com