ICS Regent. Relay Output Modules. Low Power and High Power (T3446L and T3446H) PD-6017

Similar documents
ICS Regent. AC Guarded Digital Output Module 110 VAC (T3464) PD-6021

ICS Regent. Multiplexed I/O Modules PD-6035 (T3491)

ICS Regent. Monitored Digital Input Modules 24 VDC (T3411) PD-6031

ICS Regent. Guarded Analog Output Modules. 4 to 20 ma (T3480) PD-6026

ICS Regent. Thermocouple Input Assembly. Input Module, Mux, Termination Panel and Cable (T3431-IM, T3431-Mux, T3431-TP and T3431-CA) PD-6024

Electronic timer CT-ERS.12 ON-delayed with 1 c/o contact Data sheet

RT4F-120V/20A-WAC RECTIFIER

Electronic timer CT-ERD.12

Electronic timer CT-ERS.21

RT4F-110V/25A RECTIFIER

Contact protection relay

RT4B-110V/12A RECTIFIER

Model Number Structure

G3PC. Model Number Structure. Solid State Relays with Failure Detection Function. Model Number Legend

Electronic timer CT-AHD.22

Electronic timer CT-ARS.11

TM3SAF. Main. Device short name

TM3AI4 module TM3-4 analog inputs

PGR-2601 MANUAL DC GROUND-FAULT RELAY

RT4F-48V/50A-WAC RECTIFIER

MODEL CIO-EN MODBUS/TCP, MODBUS/RTU I/O MODULE

TM3TI4 module TM3-4 inputs temperature

TM3SAC5RG SAFETY MODULE FOR PLC TM2xx, 1 FUNCTION, CAT3, SPRING TERMINALS

TM3TI8T module TM3-8 inputs temperature

RT12-240V/2.4kW Rectifier Specification

D6030S - D6030D INSTRUCTION MANUAL. D SIL 3 Switch/Proximity Detector Repeater Relay Output. Models D6030S, D6030D

RE7RB13MW adjustable off-delay timing relay s V AC DC - 2OC

RE7YA12BU time delay relay for star-delta starter s - 24 V AC DC - 2OC

RE22R2QGMR Star-Delta Timing Relay s 300h V AC/DC - 2C/O

78 Series Electromechanical Relay Selection Guide

TM3DI16 module TM3-16 inputs

TM3TI4 module TM3-4 inputs temperature

ATS01N206RT soft starter for asynchronous motor - ATS01-6 A V

RM4TA32 three-phase network control relay RM4-T - range V

TM3DI16G module TM3-16 inputs spring

ATS01N232RT soft starter for asynchronous motor - ATS01-32 A V

D64RP18 INSTRUCTION MANUAL N.O. N.C V AC/DC TEST/ RESET

RM22TG. Product data sheet Characteristics. three-phase control relay Vac, 2 C/O. Main. Complementary. Network number of phases

TU531, TU532 Terminal Unit

Trusted High Integrity Power Supply System ( Vac and 24 Vdc)

TF501, TF521 Terminal Bases

RE22R2CMR Off-delay Timing Relay s 300h V AC/DC - 2C/O

RM4TR31 three-phase network control relay RM4-T - range V

OTB1E0DM9LP I/O distributed module OTB - Ethernet TCP/IP m

Messaging module CP-C MM

RT7-48V/6kW Specification

ATSU01N209LT soft starter for asynchronous motor - ATSU01-9 A V KW

AO523 Analog Input Module

SE-135 MANUAL GROUND-FAULT GROUND-CHECK MONITOR

RE22R2QTMR Star-Delta Timing Relay s 300h V AC/DC - 2C/O

TM3TM3 module TM3-2 temperature inputs and 1 analog output

TM241C40R controller M IO relay

Allen-Bradley PLCs. 100 Programmable Controller Processor Unit -Catalog Nos LPI01, -LP102, -LP103, -LP104 SLC TM. The Unit

RM17TG. Main. Product or component type. Product specific application. Relay monitored parameters. Switching capacity in VA

Electronic timer CT-EBD.12 Flasher starting with ON with 1 c/o (SPDT) contact

RE9RA21MW7 off-delay timing relay s V AC -

170 ADM to 60 VDC Module Base / 170 ADO Pt. Relay Out Module Base. Version 1.0

XPSMCMDI Input expansion module with screw term

RE17LAMW on-delay timing relay - 1 s..100 h V AC/DC - solid state output

TM3SAK. Main. Device short name

Electronic timer CT-APS.21 OFF-delayed with 2 c/o (SPDT) contacts

ILBIB24DO16-DSUB. Inline Block IO Module for INTERBUS With 16 Digital Outputs; Bus Connection via D-SUB Connectors

Part No. Description Product Life Cycle Phase *) unit, 24 VDC, spring terminals. unit, 24 VDC, spring terminals, XC version

RM4UA33M voltage measurement relay RM4-U - range V V AC

ABL8BBU24200 battery control module V DC - 24 V - 20 A - for regulated SMPS

XPSMCMDO Digital output pairs expansion modules with screw term

SE-701 MANUAL GROUND-FAULT MONITOR

TM258LD42DT4L compact base M I/O - 24 V DC

This Datasheet for the IC660BBA020. Block 24/48Vdc Analog 4 Inputs / 2 Outputs.

This Datasheet for the IC660BBA020. Block 24/48Vdc Analog 4 Inputs / 2 Outputs.

Electronic timer CT-ARS.11 OFF-delayed without auxiliary voltage with 1 c/o (SPDT) contact

RE17LAMW on-delay timing relay - 1 s..100 h V AC/ DC - solid state output

CompactBlock Guard I/O EtherNet/IP Safety Modules

RE7RM11BU off-delay timing relay with control contact s - 24 V AC DC - 1OC

RE22R2AMR On-delay Timing Relay s 300h V AC/DC - 2C/O

Voltage Current Front-mounting bracket

This Datasheet for the IC660BBR100. Block Relay Output Normally Closed 16 Circuits.

BNS SERIES - COMPATIBLE SERIES AES SAFETY CONTROLLERS SELECTION CHART AVAILABLE STANDARD MODELS

Monitoring technique. VARIMETER Voltage relay MK 9064N, MH 9064

FL MC 2000E (SM40) LC

Industrial Power Supplies

RE22R2AMR On-delay Timing Relay s 300h V AC/DC - 2C/O

PGR-4700 MANUAL SENSITIVE GROUND-FAULT RELAY

DC541 Digital Input/Output Module

ABS2EC01EB input interface module mm - solid state - 24 V DC

Electronic timer CT-SDD.22 Star-delta change-over with 2 n/o contacts

Industrial Power Supplies

Solid-state Timer. Ordering Information. Ultra-slim Timer for G2R Relay Socket. H3RN-jj. Accessories (Order Separately) Connecting Socket

MAINTENANCE MANUAL. EDACS REDUNDANT POWER SUPPLY SYSTEM 350A1441P1 and P2 POWER MODULE CHASSIS 350A1441P3, P4, AND P5 POWER MODULES TABLE OF CONTENTS

MAXIOM. Data Sheet. Lighting Relay Panel. Overview Leverage the Power of BAS Integration

RE17LCBM off-delay timing relay - control - 1 s..100 h V - solid state output

RE8TA31BU industrial timing relay s - type A - 24 V AC/DC, V AC - 1 C/O

TPE 1464 Series Pressure Transducer

OTB1E0DM9LP I/O distributed module OTB - Ethernet TCP/IP m

02/11/2015

RE22R1QMQ star-delta timing relay - 230VAC/440VAC - 1 C/O

RE7YA12BU. Main. Contacts type and composition Component name Time delay type. 24 V AC/DC at 50/60 Hz V AC/DCat 50/60 Hz

Voltage monitoring relays CM-ESS.1 For single-phase AC/DC voltages

ABE7R16S210 sub-base - soldered electromechanical relays ABE7-16 channels - relay 10 mm

RM4JA01F current measurement relay RM4-J - range ma V AC

Transcription:

ICS Regent PD-6017 Relay Output Modules Low Power and High Power (T3446L and T3446H) Issue 1, March, 06 Relay output modules provide control of eight user output loads. Two types of relay output modules are available providing dry contact relay closure outputs for switching a variety of AC and DC voltages to field loads. Each module's triplicated I/O Safetybus interface ensures that no Regent system failure can incorrectly apply power to an output and that no failure in the module can affect the operation of the Regent system or other I/O modules in the system. Features Eight isolated, dry contact relay outputs: four Form-C, and four form-a or Form-B selectable. Hot replaceable. Automatic self-testing of triplicated I/O Safetybus circuits and many simplex logic circuits. High power modules (T3446H) operate up to 250 VAC/125 VDC switching loads rated at 500 VA or 100 Watts. Low power modules (T3446L) operate up to 125 VAC/VDC switching loads rated at 60 VA or 30 Watts. Individual front panel indicators on each module show active and fault status, shutdown state, and output status (logic side). TÜV certified, Risk Class 5, non-interfering. Industrial Control Services 1

Relay Output Modules (T3446L, H) Module Operation A block diagram of a typical relay output module is shown in Figure 1. The processor modules send triplicated write data commands to the output module over the I/O Safetybus. The processors addressing data and data write commands are voted by the module (preventing I/O Safetybus failures upstream from the module from affecting module operation). The voted result is then passed to the I/O bus interface logic. Figure 1. Block Diagram of a Relay Output Module. The voted output data from the I/O bus interface logic is then used to drive the output circuits. Logic output drive signals energize the coils of relays mounted on the printed circuit board. Relay contacts provide dry-contact switching of load devices. When the output is logically turned on, the relay coil is energized (closing the N.O. contact), and when the output is 2 Industrial Control Services

(T3446L, H) Relay Output Modules logically turned off, the relay coil is de-energized (closing the N.C. contact). The relay provides logic-to-field isolation between the module s logic and field circuits protecting the output module from field signal over voltages, transients, and other electrical disturbances. Both types of relay output module use UL 508 approved relays. Testing and Diagnostics Each module s voter circuits are periodically tested by the processor modules. Discrepant data are sent through one of three legs of the I/O Safetybus to determine whether the module s voter is able to outvote the incorrect data. A failure to return the correct majority-voted result to the processors produces an I/O module error indication at the processor modules and a module fault indication at the I/O module. Each type of module has a unique identification code that is read by the controller. This code lets the controller know which type of module is installed in each I/O chassis slot and how to address that module and its points specifically. If a module is removed, or is replaced with a module of a different type, the processor modules will indicate an I/O module error. Loopback logic tests periodically write data to the module and then read it back to determine whether the module s I/O bus interface logic is functioning correctly. Front Panel Indicators The relay output module is shown in Figure 2. The front panel contains active and fault status indicators, a shutdown indicator, and output status indicators for each output circuit. Active and Fault Status Indicators These green and red LEDs indicate the overall health of the module. During normal operation the green ACTIVE indicator flashes at the controller's scan rate. If a module fault is detected the red FAULT indicator turns on and the green indicator turns off. PD-6017 Mar-06 3

Relay Output Modules (T3446L, H) Shutdown Indicator Upon loss of communications with the controller, output modules enter either a shutdown or hold fault mode. If the I/O assembly is set to shutdown, the red SHUTDOWN indicator will turn on when communications with the controller are lost. If the I/O assembly is set to hold, the SHUTDOWN indicator will always be off (see page 13, Fault Mode Jumper). Note: When the module is installed in the I/O chassis or when logic power (from the I/O power supply modules) is first applied to the module, it will be in the shutdown mode until the first output scan, regardless of the fault mode jumper settings. Also, removing two I/O transceiver modules, two I/O power supply modules, or two power legs will cause the module to be in the shutdown mode. Output Status Indicators The output status indicators are yellow LEDs located on the logic-side (coil) of the relay output. There are eight output status indicators one for each output. These indicators are lit when the output relay coil is energized, closing the normally open contact. 4 Industrial Control Services

(T3446L, H) Relay Output Modules Figure 2. Relay Output Module. PD-6017 Mar-06 5

Relay Output Modules (T3446L, H) Application Simplex Configuration Relay output modules provide a suitable interface to noncritical output devices. These non-critical devices typically include status alarms or other field devices that are not used for primary safety shutdown purposes. Although much of the circuitry on the relay output module is automatically tested, some logic circuits and the field-side output switch are simplex and non-tested. This simplex configuration is illustrated in Figure 3. For safety-critical outputs requiring fail-safe or fault tolerant output configurations, Guarded digital output modules should be used. Figure 3. Simplex Relay Output Configuration. Field Wiring Field wiring terminal blocks on the I/O chassis are used to connect power sources and loads to the module. The terminal blocks are located directly above and below the slot where the module is installed. Each terminal block consists of ten #6 wire clamp screw terminals capable of holding two 12 AWG wires. Each module has two terminals for each Form-A or Form-B selectable relay (channels 1, 2, 7, and 8), and three terminals for each Form-C relay (channels 3, 4, 5, and 6). Figure 4 shows the correct field wiring connections for the relay output modules. 6 Industrial Control Services

(T3446L, H) Relay Output Modules Figure 4. Module Wiring. PD-6017 Mar-06 7

Relay Output Modules (T3446L, H) Important! Voltages greater than 50 volts, or of different polarities or phase, should not be connected across the N.C. and N.O. contacts in a single Form-C relay. Do not use the relay output for voltage selection under these conditions. If voltage selection is required, two separate relay output channels should be used. Relay Operation The relays used on the T3446L contain SPDT contacts. For the Form-A or Form-B selectable outputs, a jumper in the module is used to select Form-A (N.O.) or Form-B (N.C.) action. The relays used on the T3446H contain two SPST contacts (one normally closed and one normally open). Jumpers within the module are also used to select the relay form. On the Form-C output, there is no guarantee for make-before-break or break-before-make. Output Form Selection Two sets of jumper posts are used to select the output form for the selectable relays. The jumper locations are shown in Figure 5. The jumper post designations are shown in Table 1. Only one jumper shunt can be installed for each relay. The modules are shipped with the jumpers positioned for normally open contact outputs. Table 1. Jumper Designations. 8 Industrial Control Services

(T3446L, H) Relay Output Modules PD-6017 Mar-06 Jumper Form Description E110 NO1 Selects normally open for relay 1 E111 NC1 Selects normally closed for relay 1 E120 NO2 Selects normally open for relay 2 E121 NC2 Selects normally closed for relay 2 E170 NO7 Selects normally open for relay 7 E171 NC7 Selects normally closed for relay 7 E180 NO8 Selects normally open for relay 8 E181 NC8 Selects normally closed for relay 8 9

Relay Output Modules (T3446L, H) Figure 5. Jumper Locations. Operating Envelope Figure 6 shows the voltage and current operating envelopes for the T3446L and T3446H. The T3446L relays are initially gold clad and have an initial resistance of 50 mohm maximum. However, operation at high voltages and currents will remove the gold and the closed resistance will increase substantially. This increased resistance reduces its ability to subsequently switch very low power loads. 10 Industrial Control Services

(T3446L, H) Relay Output Modules As with any relay, operating at higher voltages and currents will result in decreased relay life. Figure 7 shows the voltage and current versus service life for the relays. Figure 6. Voltage and Current Operating Envelopes. PD-6017 Mar-06 11

Relay Output Modules (T3446L, H) 100000 10000 1000 100 10 0 0.4 0.8 1.2 1.6 2 2.4 0 0.4 0.8 1.2 1.6 2 2.4 100000 10000 1000 100 10 Figure 7. Voltage and Current vs. Service Life. Relay Protection Each relay circuit must be fused externally to protect the relay and the load. Modules are also fused internally with factory-replaceable fuses to protect the I/O assembly and the module s printed circuit board. If an inductive load is connected, a suitable snubber must be externally provided. 12 Industrial Control Services

(T3446L, H) Relay Output Modules Fault Mode Jumper The fault mode jumper is located behind the ID switch cover in the lower left-hand corner of each I/O chassis. The position of the fault mode jumper determines the module's response to system level faults. The fault mode jumper s position will cause all output modules in the I/O chassis to either shutdown (turn off all outputs) or to hold (hold the last state) after a system level failure occurs. An example of a system level failure is the failure of two processor modules. Keying The I/O chassis can be physically keyed to prevent accidental damage caused by inserting a module into a slot wired for a different module type. Figure 8 illustrates how the slot keys are installed on the I/O chassis slot field wiring connectors. The slot key positions for the relay output module are listed in Table 2. Both versions of the relay output module use the same slot key positions. Table 2. Slot Key Positions. PD-6017 Mar-06 Module Upper Connector Lower Connector T3446H T3446L 17 2 13

Relay Output Modules (T3446L, H) Figure 8. Installing Slot Keys. Configuration Each output module is configured using the WINTERPRET I/O Configuration Editor. In the editor you will perform the three steps described below to configure the output module. 14 Industrial Control Services

(T3446L, H) Relay Output Modules 1) Set the Module Type: Position the cursor on the module slot you wish to define. Choose Set Module Type from the Edit Menu and select the relay output module from the list. 2) Edit the Module Definition: Choose Edit Module Definition from the Edit Menu. A dialog box will open where you can define the output point definitions. Figure 9. Relay Output Module Definition. 3) Edit each point: Choose Edit from the Module Definition dialog box to define a name and description for each output point. In the Digital Output Point dialog, enter names and values for the configuration fields as described below. Figure 10. Defining a Digital Output Point. PD-6017 Mar-06 15

Relay Output Modules (T3446L, H) Name Also called the tag name, this is the name used in the application program to reference the output point. The name can be up to 12 characters long. Description This 40-character field provides a place to describe the output point definition. The description is used to help document your system (it does not affect application program operation). Comm Protect Marking the Comm Protect check box protects the point from changes by communications functions such as data write, forcing, and load initial value when Comm Protect is enabled. Initial Value The initial value for the output is loaded to the Regent when you load the I/O configuration and also when you load the application program that controls the output. Final Value The final value for the output is loaded to the Regent when the application program that controls the output is deleted. Unless special circumstances exist, you should always enter zero, so that the output is turned off when you delete the application program that controls it. Output Module Definition In addition to configuring output point definitions, you can configure an output module definition to represent the combined state of all eight output points. The module definition represents the eight output point definitions as signed, 16-bit integers. In this format, the eight outputs are the least significant bits with output point 1 as the LSB. The eight most significant bits are always zero. Programming Outputs are controlled by writing application programs that solve for output values. For example, placing an output tag name on a coil in ladder logic will cause the output to turn on when there is power flow to the coil in the ladder logic rung. You can also reference the logic state of the output in your 16 Industrial Control Services

(T3446L, H) Relay Output Modules control logic by using a contact element (or similar element) with the output point name. Maintenance No periodic maintenance or calibration is required for this module. If a module is to be replaced, verify the replacement module s relay form configuration matches the original relay output module. Fuses for each output are located inside the module. These fuses are for protection of the I/O chassis connectors and module circuit board only, and are not field-replaceable. Should an internal fuse blow, it indicates that the module is being used for output loads in excess of the safe rating of the module and the I/O chassis. Modules with blown fuses should be returned to ICS for repair or replacement. Safety Considerations The relay output modules are TÜV certified as noninterfering, and can be used in a safety system for simplex non-safety critical outputs. For safety critical outputs, guarded output modules should be used (model T3481, T3484, T3485 or T3488 are recommended). PD-6017 Mar-06 17

Relay Output Modules (T3446L, H) Specifications Safetybus Power 1.0 load units Number of Outputs Eight isolated circuits (four Form-C contacts, four selectable N.O. or N.C. contacts) Voltage Range Load Current Minimum Load Surge Current Over Voltage Protection T3446L 0.1 to 125 VAC/DC 2.0 amps 0.1 VDC/10 ma 20 amps, 16 msec T3446H 5 to 250 VAC 5 to 125 VDC 2.0 amps 5 VDC/10 ma 20 amps, 16 msec 750 VAC, 1 minute 1000 VAC, 1 minute 110 VAC, 0.3 amps 24 VDC, 1 amp 110 VAC, 0.2 amps 24 VDC, 0.3 amp 250 VAC, 2 amps 50 VDC, 2 amps 250 VAC, 2 amps 30 VDC, 2 amps 60 VA, 30 W 20 VA, 10 W 500 VA, 100 W 500 VA, 60 W 50 mohms, initial 30 mohms, initial Rated Load resistive inductive Maximum Switching resistive inductive Contact Resistance Breakdown Voltage Logic to field 1000 VAC 750 VAC Chnl to chnl 2500 VAC Turn-On Delay 5 msec Turn-Off Delay 2 msec Heat Dissipation 4.5 Watts, 15 BTUs/hour Same channel 18 Industrial 2000 VAC 1000 VAC 2500 VAC 10 msec 10 msec 4.5 Watts, 15 BTUs/hour Control Services

(T3446L, H) Relay Output Modules Fusing (internal) Operating Temperature One 3.5 A, slow blow per output Note: Internal fuses are for protection of the printed circuit board only. Each output should be individually fused outside the module with a fuse rated for the output load. 0 to 60 C (32 to 140 F) Storage Temperature -40 to 85 C (-40 to 185 F) Operating Humidity 0 to 95% relative humidity, non-condensing Vibration 10 to 55 Hz: ±0.15mm Shock Operating: 15 g, ½ sine wave, 11 msec Electromagnetic Interference IEC 801 Part 2 - Electrostatic Discharges IEC 801 Part 3 - Radiated Electromagnetic Fields ANSI/IEEE C37.90 - Surge Withstand Capability Safety Level 3: Contact discharge of 6 kv Level 3: 10 V/M, 27 MHz 500 MHz 1 kv damped 1 MHz sine wave Certified to DIN V VDE 0801 (non-interfering) and designed to meet UL 508 and CSA 22.2, No. 142-M1981 Dimensions Height: Width: Depth: Weight PD-6017 Mar-06 12.6" (320 mm) 1.27" (32 mm) 10.12" (257 mm) 4.0 lbs (1.8 kg) 19

Relay Output Modules (T3446L, H) 20 Industrial Control Services