Project: City of Simi Valley Security Upgrades For Exante 360 Steve Bowcut A. Manufacturer s Abbreviations: 1. MK - McKinney 2. SL Seco-Larm 3. SA - Sargent 4. HS - HES 5. HD - HID 6. SU Securitron 7. RO Rockwood 8. AR Adams Rite 9. CS Contractor Selected 10. BO By Owner Door(s): 1 Set: 1.0 2 Magnetic Locks M680BD-335 BLK SU 281300 2 Dual Sense Bar DSB-BKxx BLK SU 281300 1 Touch Bar Cover Plates TCP-BK BLK SU 281300 2 Armored Door Loop K-DSBLK BLK SU 281300 1 Power Supply AQD6-8F8R SU 281300 1 Battery Back-Up Bxx-5 (5Ah) SU 281300 2 Door Position Switch DPS-M BLK SU 281300 Notes: Remove push bars and replace with exit bars using cover plates. Mechanical deadlock to remain unlocked and used only in case of emergency. Controller to be selected and located as part of the PACS design. Power supply and A/C drop location to be coordinated with electrical contractor. Card Reader installed on bollard. Coordination of raceways and back-boxes required. Door(s): Auxilliary Exit/Entrance Set: 2.0
2 Magnetic Locks M680BD-335 BLK SU 281300 2 Dual Sense Bar DSB-BKxx BLK SU 281300 1 Touch Bar Cover Plates TCP-BK BLK SU 281300 2 Armored Door Loop K-DSBLK BLK SU 281300 1 Power Supply AQD6-8F8R SU 281300 1 Battery Back-Up Bxx-5 (5Ah) SU 281300 2 Door Position Switch DPS-M BLK SU 281300 1 Wireless Receiver SK-910RBQ SL 281300 1 Wireless Release Button SD-8103GT-PEQ GRN SL 281300 Notes: Remove push bars and replace with exit bars using cover plates. Mechanical deadlock to remain unlocked and used only in case of emergency. Wireless button installed under desk for remote release. Card reader and PACS controller connection NOT required, but DPS to be monitored. Power supply and A/C drop location to be coordinated with electrical contractor. Coordination of raceways and back-boxes required. Door(s): NE Council Chamber Door Set: 3.0 Notes: Electric strike to be re-used. Existing power to be verified. Controller to be selected and located as part of the PACS design. Council Room Panic Buttons Set: 4.0 1 2 Channel Wireless Receiver SK-910RB2Q SL 281300 2 Wireless Release Button SD-8103GT-PEQ GRN SL 281300 Notes: I/O solution for alarm signal to be selected as part of the PACS design. Door(s): 8, 10 Set:5.0
Door(s): 11 Set: 6.0 Notes: Verify existing electric strike and REX motion sensor: repair, replace, or add as required. Existing power to be verified. Door(s): 12, 16 Set: 7.0 1 Electric Strike 1006Z x 2005M3 613 HS 281300 Notes: Frame modification required. Coordination of raceways and back-boxes required. Centralized power to be provided at controller and distributed to openings. Controller to be selected and located as part of the PACS design. Interlocking Vestibule Door(s): 6, 7 (Equipment Combined) Set: 8.0 2 Card Reader R40 iclass SE BLK HD 281300 2 Door Position Switch DPS-M BLK SU 281300 2 REX Motion Sensor XMS WHT SU 281300 1 Electric Strike 1006Z x 2005M3 613 HS 281300 1 Electric Strike 1006AD x 2005M3 613 HS 281300 Notes: If one of two doors is open, other card reader is disabled and entry is not permitted. Logic for this interlock will be provided by programming of the PACS software. Frame modification required. Coordination of raceways and back-boxes required. Centralized power to be provided at controller and distributed to openings. Controller to be selected and located as part of the PACS design. Door(s): 5 Set: 9.0
Notes: Existing electric strike and HID card reader to be re-used. Verify existing DPS and REX functions: repair, replace, or add as required. Existing power to be verified. Controller to be selected and located as part of the PACS design. Door(s): 14, 15 Set: 10.0 Notes: Verify existing exit bar latch retraction, DPS and REX functions: repair, replace, or add as required. Existing power to be verified. Controller to be selected and located as part of the PACS design. Door(s): 13 Set: 11.0 1 Electric Strike 9600 x 2005M3 613 HS 281300 Notes: Frame modification required. Coordination of raceways and back-boxes required. Centralized power to be provided at controller and distributed to openings. Controller to be selected and located as part of the PACS design. City PD Door(s): 16 Set: 12.0 Notes: Verify existing electrified lockset, DPS and REX functions: repair, replace, or add as required. Existing power to be verified. Controller to be selected and located as part of the PACS design. Set: 13.0 City PD Door(s): 1, 2, 3, 4, 5, 6, 7, 7a, 8, 9, 10, 11,12, 13, 14, 15, 17, 18, 19, 24, 25, 26, 27, 28, 29, 30, 103, 120, SWOT Armory
Notes: Verify existing electrified locking hardware, DPS and REX functions: repair, replace, or add as required. Existing power to be verified. Controller to be selected and located as part of the PACS design. City PD Doors: 20 Set: 14.0 1 Card Reader / Keypad RK40 iclass SE BLK HD 281300 Notes: Verify existing electrified locking hardware, DPS and REX functions: repair, replace, or add as required. Existing power to be verified. Controller to be selected and located as part of the PACS design. Set: 15.0 City PD Interlocking Vestibule Door(s): 22, 23 (Equipment Combined) 2 Card Reader R40 iclass SE BLK HD 281300 Notes: If one of two doors is open, other card reader is disabled and entry is not permitted. Logic for this interlock will be provided by programming of the PACS software. Verify existing electrified locking hardware, DPS and REX functions: repair, replace, or add as required. Controller to be selected and located as part of the PACS design. City PD Motorized Vehicle Gates: 1, 2 Set: 16.0 Notes: Card reader to be installed on gooseneck gate pedestal. Verify proper operation with automated gate equipment. Existing power to be verified. Controller to be selected and located as part of the PACS design. City PD Door(s): 109 Set: 17.0
1 Electric Strike 1006J x 2005M3 630 HS 281300 Notes: Frame modification required. Coordination of raceways and back-boxes required. Exposed conduit, surface mounted boxes and hardware are permitted at this opening. Centralized power to be provided at controller and distributed to openings. Controller to be selected and located as part of the PACS design. City Sanitation Door(s): 1 Set: 18.0 1 Electric Strike 1006J x 2005M3 613 HS 281300 1 Wireless Receiver SK-910RBQ SL 281300 1 Wireless Release Button SD-8103GT-PEQ GRN SL 281300 1 Latch Protector 321 10BE RO 281300 Notes: Frame modification required. Coordination of raceways and back-boxes required. Exposed raceways and back-boxes are NOT permitted at this opening. Centralized power to be provided at controller and distributed to openings. Controller to be selected and located as part of the PACS design. City Sanitation Door(s): 3 Set: 19.0 1 Sngl Gang Handi-Box Surface Mounted CS 281300 1 Cylinder Assembly Supplied by Owner 626 BO 1 Electrified Lock w/rex LC-RX-10G71 LL x 24V 626 SA 281300 1 Power/Signal Transfer Hinge TA2714 4.5 x 4.5 QC8 652 MK 281300 1 Quick-Connect Door Cable QC-C306 MK 281300 Notes: Frame modification required. Coordination of raceways and back-boxes required. Minimize exposed raceways as much as possible. Surface mounted DPS permitted, if necessary. Centralized power to be provided at controller and distributed to openings. Controller to be selected and located as part of the PACS design. Set: 20.0
City Sanitation Door(s): 4 1 Sngl Gang Handi-Box Surface Mounted CS 281300 1 Electric Strike 9600 x 2005M3 630 HS 281300 1 Cylinder Assembly Supplied by Owner 626 BO 1 Touch Bar Cover Plates TCP ALUM SU 281300 1 Exit Device 8803-36 MEC x 3002-11 630 AR 281300 Notes: Frame modification required. Replace existing mechanical exit bar. Use cover plates as required to cover existing door preparation. Coordination of raceways and back-boxes required. Exposed conduit, surface mounted boxes and hardware are permitted at this opening. Centralized power to be provided at controller and distributed to openings. Controller to be selected and located as part of the PACS design. City Sanitation Door(s): Breakroom Set: 21.0 1 Electric Strike 1006J x 2005M3 613 HS 281300 Notes: Frame modification required. Coordination of raceways and back-boxes required. Minimize exposed raceways. Centralized power to be provided at controller and distributed to openings. Controller to be selected and located as part of the PACS design. City Sanitation Door(s): 2 Set: 22.0 1 Wireless Integrated Exit Device LC-N2-IA 8877 ETL 32D SA 281300 1 Cylinder Assembly Supplied by Owner 626 BO 1 Aperio Hub/Transceiver AH30-xxxx WHT SA 281300 1 Aperio External Antenna EXT-10-ANT SA 281300 1 Antenna Cable w/bnc Connector Surface Mounted CS 281300 1 Touch Bar Cover Plates TCP ALUM SU 281300 Notes: Door modification required. Replace existing mechanical exit bar. Use cover plates as required to cover existing door preparation. Controller to be selected and located as part of the PACS design. RS-
485 compliant 5-Conductor pulled from Aperio Hub to controller serial bus. External antenna installed in concealed location on outside of building within 50 ft of door. City Administration Door(s): 1, 4 Set: 23.0 2 Magnetic Locks M680BD-335 BLK SU 281300 2 Dual Sense Bar DSB-BKxx BLK SU 281300 1 Touch Bar Cover Plates TCP-BK BLK SU 281300 2 Armored Door Loop K-DSBLK BLK SU 281300 1 Power Supply AQD6-8F8R SU 281300 1 Battery Back-Up Bxx-5 (5Ah) SU 281300 2 Door Position Switch DPS-M BLK SU 281300 1 2 Channel Wireless Receiver SK-910RB2Q SL 281300 2 Wireless Release Button SD-8103GT-PEQ GRN SL 281300 Notes: Remove push bars and replace with exit bars using cover plates. Re-use pulls provide thru-bolts to install as necessary. Controller to be selected and located as part of the PACS design. Power supply and A/C drop location to be coordinated with electrical contractor. Card Reader installed on mullion. Coordination of raceways and back-boxes required. Exposed raceways and back-boxes are NOT permitted at this opening. Under desk wireless switches installed at administrative locations as required. City Administration Motorized Vehicle Gates: 1 Set: 24.0 Notes: Card reader to be installed on gooseneck gate pedestal. Verify proper operation with automated gate equipment. Existing power to be verified. Controller to be selected and located as part of the PACS design. City Administration Door(s): 2,3 Set: 25.0 1 Wireless Integrated Lock A100-3090H-C-2 121 AR 281300 1 MS Deadlock Lever 4550L-xx 121 AR 281300 1 Cylinder Assembly Supplied by Owner 613 BO
1 Aperio Hub/Transceiver AH30-xxxx WHT SA 281300 1 Aperio External Antenna EXT-10-ANT SA 281300 1 Antenna Cable w/bnc Connector Surface Mounted CS 281300 1 Touch Bar Cover Plates TCP-BLK BLK SU 281300 Notes: Door modification required. Replace existing pull/push. Use cover plates as required to cover existing door preparation. Controller to be selected and located as part of the PACS design. RS-485 compliant 5-Conductor pulled from Aperio Hub to controller serial bus. External antenna installed in concealed location on outside of building within 50 ft of door. City Transportation Door(s): 1=Training Room Set: 26.0 Notes: Re-use existing electric strike and verify operation. Coordination of raceways and back-boxes required. Minimize exposed raceways. Centralized power to be provided at controller and distributed to openings. Controller to be selected and located as part of the PACS design. City Transportation Door(s): 3 Set: 27.0 1 Wireless Integrated Bored Lockset LC-N2-IA10G77 JL 26D SA 281300 1 Cylinder Assembly Supplied by Owner 626 BO 1 Aperio Hub/Transceiver AH30-xxxx WHT SA 281300 1 Aperio External Antenna EXT-10-ANT SA 281300 Notes: Door modification required. Replace existing lockset. Controller to be selected and located as part of the PACS design. RS-485 compliant 5-Conductor pulled from Aperio Hub to controller serial bus. City Transportation Doors: 2, 4, 5, 6 Set: 28.0
Notes: Verify existing electrified locking hardware, DPS and REX functions: repair, replace, or add as required. Existing power to be verified. Controller to be selected and located as part of the PACS design. City Transportation Door(s): Vault Vestibule, 7 Set: 27.0 Wireless Integrated Mortise 1 Lockset LC-N2-IA82276 J 26D SA 281300 1 Cylinder Assembly Supplied by Owner 626 BO 1 Aperio Hub/Transceiver AH30-xxxx WHT SA 281300 1 Aperio External Antenna EXT-10-ANT SA 281300 Notes: Door modification required. Replace existing lockset. Controller to be selected and located as part of the PACS design. RS-485 compliant 5-Conductor pulled from Aperio Hub to controller serial bus.