New Design Strategies for Energy Saving. Intelligent free-cooling

Similar documents
Aquaflair. Uniflair TRAC, TRAF and TRAH. Air-cooled chillers, free-cooling chillers and heat pumps with scroll compressors.

Aquaflair. BREC & BREF kW 380V/3ph/60Hz - 460V/3ph/60Hz. Air-cooled chillers and free-cooling chillers with double screw compressors

Aquaflair. BREC/F and BCEC/F kw

IT COOLING EVAPORATIVE COOLING SYSTEM. 2 STAGE INDIRECT ADIABATIC COOLING SYSTEM FOR LARGE DATA CENTERS FROM 80 TO 320 kw

Precision Cooling for Business-Critical Continuity. Liebert HPC-S. Designed for the Efficient Cooling of Small Data Centers

Rack cooling solutions for high density racks management, from 10 to 75 kw

Liebert HPC. Freecooling Scroll Chillers for the Efficient Cooling of Data Centers

CHILLED WATER. HIGH PRECISION AIR CONDITIONERS, FROM 7 TO 211 kw

Data Center Energy Savings By the numbers

Ecoflair Air Economizers

FREECOOLING, EVAPORATIVE AND ADIABATIC COOLING TECHNOLOGIES IN DATA CENTER. Applications in Diverse Climates within Europe, Middle East and Africa

Total Modular Data Centre Solutions

Trane Engineering News Chiller Plant Case Study: Variable-Primary Flow Series Chillers with Free Cooling

glide glider kw R134a air cooled liquid chillers AND free cooling chillers FREE COOLING SHELL A C CLASS E C Energy Class RCGROUP SpA

Data center cooling evolution. The hottest way to save energy. Lucio Bustaffa: Product Development Manager BlueBox Group

7 Best Practices for Increasing Efficiency, Availability and Capacity. XXXX XXXXXXXX Liebert North America

Motivair MLC-SC Air-Cooled Scroll Chillers Tons

IT COOLING AIR CONDITIONERS FOR HIGH DENSITY RACKS AND BLADE SERVERS. RACK COOLING SOLUTIONS FOR HIGH DENSITY RACK MANAGEMENT, FROM 4 TO 75 kw

Perfect Cooling. A perfect climate for high performance servers

Industry leading low energy evaporative fresh air cooling.

Liebert. HPC-S Free Cooling Chiller Designed for the Efficient Cooling of Small Data Centers

Liebert AFC from 500 to 1450 kw. The Adiabatic Freecooling Solution with Top-Tier Availability

MOLLIER DIAGRAM CAN BE IMPROVED!

Liebert AFC from 500 to 1450 kw. The Adiabatic Freecooling Solution with Top-Tier Availability

A Data Center Heat Removal System That Saves... 80% Discover Inertech s Award-winning Data Center Heat Removal System

High Efficient Data Center Cooling

Liebert. AFC from 500 to 1700 kw. The Adiabatic Freecooling Solution with Top-Tier Availability

HIGH DENSITY DATACOM INTEGRATED COOLING SYSTEM.

Ecotel Free Cool 5-15kW

Future of Cooling High Density Equipment. Steve Madara Vice President and General Manager Liebert Precision Cooling Business Emerson Network Power

Mission Critical Facilities & Technology Conference November 3, 2011 Cooling 101. Nick Gangemi Regional Sales Manager Data Aire

Precision Cooling Mission Critical Air Handling Units

Product Brochure DENCO Close Control Units Row-DENCO. High Density Cooling for Data Centres

Schneider Electric Cooling Portfolio. Jim Tubbesing Heath Wilson APC/Schneider North Texas Rep Tubbesing Solutions

2018 Product overview

Is Data Center Free Cooling Feasible in the Middle East? By Noriel Ong, ASEAN Eng., PMP, ATD, PQP

Chiller. CG 010 to 130. Remote Air Cooled Condensers Engineering Data Manual. 9.4 to 131 kw

Liebert HPC Freecooling Chiller

Evaporative free air cooling technology Providing evaporative free air cooling solutions.

MPC Air-Cooled Chillers MPC-FC Free-Cooling Chillers

Munters Data Center Cooling Solutions. Simon Young & Craig MacFadyen Munters Data Centers

Efficiency of Data Center cooling

LCP Hybrid Efficient performance with heat pipe technology

Precision Cooling for Business-Critical Continuity. Liebert HPC-M. The Data Center FreeCooling Chiller with the Lowest Impact on the Environment

4-step Chiller and Heat Pump Controller

WHAT IS THE DIGI-RTU South 59 th Street Omaha, NE bes-tech.net

Digital Realty Data Center Solutions Digital Chicago Datacampus Franklin Park, Illinois Owner: Digital Realty Trust Engineer of Record: ESD Architect

Cooling on Demand - scalable and smart cooling solutions. Marcus Edwards B.Sc.

APPLIED SYSTEM AWS FAMILY FOR LARGE APPLICATIONS PRODUCT LEAFLET. Capacity from 600 to 2,010kWr. Engineered for flexibility and performance

Impact of Air Containment Systems

How Green can you go?

Liquid Cooling Package LCP Cooling Systems

IT environmental range and data centre cooling analysis

CLIMATE. CUSTOMIZED. CyberHandler2 from 30KW to 520 KW. The indirect evaporative free-cooling Air Handling Unit

UPGRADE PROGRAM. V250 Series Pumps vs V301 Series Pumps. Technical Memo

GP SERIES Packaged Chillers

MEASURE MONITOR UNDERSTAND

Switch to Perfection

Rack & Enclosure Systems

Liebert PDX from 15 to 120 kw

HIGH EFFICIENCY Central Chiller

Table of Contents. Executive Summary Site and Unit Background Chiller Chiller Appendix... 11

Data Center Optimized Controls

DATA CENTER EFFICIENCY: Data Center Temperature Set-point Impact on Cooling Efficiency

Cooling. Highly efficient cooling products for any IT application. For More Information: (866) DATA CENTER SOLUTIONS

Planning a Green Datacenter

Liebert Economizer Cooling Solutions Reduce Cooling Costs by up to 50% Without Compromising Reliability

i-accurate_gb_ High precision air-conditioners for data centres cooling, with new inverter technology and R-410A refrigerant, from 6 to 150 kw

TECHNICAL MANUAL WATER 300 C 5300 CV/06-00 GB

Air-Cooled Series R Chiller

Data Center Energy and Cost Saving Evaluation

Liebert. AFC from 500 to 1450 kw. The Adiabatic Freecooling Solution with Top-Tier Availability CERTIFIED HVAC-HYGIENE.

MSYS 4480 AC Systems Winter 2015

Datacenter Efficiency Trends. Cary Roberts Tellme, a Microsoft Subsidiary

Supplement to PM WSC/WDC-1 MicroTech II for Centrifugal Compressor Water Chillers

Liebert PDX from 15 to 120 kw

UPGRADE PROGRAM. V70 Series Pumps vs V81T Series Pumps

WHAT IS THE DIGI-RTU South 59 th Street Omaha, NE bes-tech.net

Fair City Plaza. Task: Diagnose problems, recommend improvements for small municipal district cooling system

Global Optimisation of Chiller Sequencing and Load Balancing Using Shuffled Complex Evolution

Optimizing Chilled Water Plant Performance. David Herman, PE, LEED AP Principal EnerG Associates, LLC

White paper adaptive IT infrastructures

Close-coupled cooling

Liebert DCW Family Chilled Water-Based High Density Cooling For The Data Center. Precision Cooling For Business-Critical Continuity

IEC DATA CENTRE INDIRECT EVAPORATIVE COOLING SYSTEM

SUPERSAVER. Energy Efficiency Optimization Software for Freecooling Systems

Designing Ultra-Efficient Building Cooling Systems

X-SHARK v User guide

Chiller Replacement and System Strategy. Colin Berry Account Manager

Rittal LCP T3+ High-availability IT cooling with no compromise

Application Manual. Shark. Software for the simulation of refrigeration equipment and air conditioners

Drives and motors. A guide to using variable speed drives and motors in data centres Meeting your Carbon Reduction Commitment (CRC)

DEDICATED HEAT RECOVERY UNIT (DHRC)

ENCLOSURE HEAT DISSIPATION

IT infrastructure Next level for data center. Rittal The System Yavor Panayotov Data center Day

AIR COOLED HEAT PUMPS WITH SCREW COMPRESSORS AND AXIAL FANS

AIR COOLED CONDENSERS

Introducing the Heat Wheel to the Data Center

CTC Low Temperature Process Chillers

Variable Density, Closed-Loop, Water-Cooled Data Center Solution

Transcription:

New Design Strategies for Energy Saving Intelligent free-cooling

Intelligent New strategies for energy saving When designing mission critical systems for processing applications or highly technological environments, reliabilty and energy saving are fundamental. Intelligent free-cooling is the ideal solution. B D E D 1 Free-cooling coil Free-cooling pump Evaporator Main onboard pump Non return valve 2 3 E E E Supplied by Uniflair Not supplied by Uniflair FIGURE 1 FIGURE 1. Diagram showing units with free cooling and an onboard pump for the primary circuit. B D B D B T echnological environments which house hi-tech equipment and/or particular processes requiring guaranteed uninterrupted optimum operating conditions, as well as many industrial processes, very often have higher breakdown costs than the cost of the equipment itself. Designing a reliable system means choosing a unit which is intrinsically reliable, and therefore designed and built in such way as to guarantee an extremely low breakdown and inefficiency rate, as well as creating suitable reserves by having one or more additional units. The n+1 logic ensures that there is always a unit in stand-by which guarantees emergency intervention in the event of any type of problem. Free-cooling If the system involves technological systems or industrial processes which operate continuously throughout the year, and therefore also with low external temperatures, it is energetically convenient to use systems which have been designed to exploit these conditions; cooling systems with a free-cooling device are a typical solution. Not only do these units have a lower energy consumption than traditional systems, they also limit the quantity of indirect O² emissions into the atmosphere and, therefore, contribute to safeguarding the environment and reducing green house gases. If the external temperatures are low enough, it is possible to reduce or even eliminate, depending on the external temperature, the use the refrigerant part of the chiller, i.e. the compressors, which are the components principally responsible for energy consumption, by exploiting the air/water exchangers which are integrated in the unit itself. nalysis of the climatic profiles of the main European cities shows that the most frequent temperatures are between 0 and 15 ; this analysis has enabled the creation of free-cooling methods which maximise performance within this temperature range. For this reason, Uniflair units which are equipped with 1

free-cooling devices allow operation even when the external temperature is able to guarantee only partial rather than complete dissipation of the thermal load. In these cases, operation is referred to as mixed: the chiller uses external air to pre-cool the water in the system, allowing the compressors to work less and create energy savings. There are, therefore, three operating modes: 1 2 3 Stand-by Unit ON Unit ON Mechanical cooling. With temperatures higher than 15, the free-cooling unit operates as a traditional chiller, dissipating the thermal load of the evaporator with the compressors (fans and compressors operating); Mixed cooling. When the external temperature is between 5 and 15, the air guarantees only partial, rather than complete, dissipation of the thermal load. t lower temperatures the control system activates the free-cooling pump at 15 and the water is routed to the air/water exchangers which are placed in series in the evaporator, so that it has to dissipate a lower thermal load (fan operation, free-cooling pump and, in part, the compressors); Free-cooling. When the external temperature is low enough, the air/ water exchangers allow the complete dissipation of the thermal load without needing the compressors (fan operation and free-cooling pump). Intelligent free-cooling By combining the above concepts in applications where uninterrupted operation is required, units equipped with a free-cooling device featuring a redundancy logic can be installed and therefore part of the available cooling capacity is in stand-by. The same consideration can be made regarding the available free-cooling capacity. The principle which forms the basis of intelligent free-cooling is that of also exploiting, when external temperatures allow, the air/ water exchangers of the unit/s in stand-by. By linking all of the air/water exchangers together, it is possible for the water which is to be cooled to flow through all of the free-cooling coils which are available. Since, in Uniflair free-cooling units, the water is sent to the free-cooling coils by a pump and not by a simple three-way valve, it is in fact also possible to use the exchangers of the units in stand-by and therefore increase the free-cooling capacity which is available and, consequently, its application, with evident advantages in terms of energy saving. Hydraulic circuits When carrying out the hydraulic connections between the air/water exchangers, two separate cases need to be identified: Units equipped with an on-board pump on the primary circuit Installations supplied with a primary pump outside the unit (placed on the suction or discharge side). The system design can vary depending on each particular situation. Units equipped with an onboard pump Figure 1 shows the solution when there is an onboard pump for the primary circuit.by analyzing a situation such as the one shown, where unit 1 is in stand-by, units 2 and 3 are operating and the three units are connected together with an intelligent free-cooling solution and when the external temperature is low enough for free-cooling to be activated, the control of the two units which are operating activates the fans in the stand-by unit (1) and the free-cooling pump (B) of the units themselves (2 and 3); this happens in such a way that the water arriving from the system is sent to all of the available the free-cooling coils. See Figure 2. Finally, the difference in pressure, which is due to the fact that the pump which is installed onboard the standby unit (1) is at a standstill, prevents a by-pass through the evaporator of this unit. FIGURE 2 FIGURE 2. Diagram showing the flow of water to all of the available free cooling coils, including the one on the stand-by unit. FIGURE 3. Diagram in which the units are without onboard pumps but with a pump for the primary circuit up or down stream of the refrigerant group. In this case, it is necessary to equip the units with devices which isolate the stand-by unit. For this reason a motorized valve is placed on the inlet line and a non return valve on the outlet line. FIGURE 3 2

a b B D E F Motorized valve oil Free-cooling pump Evaporator Motorized valve Main pump 1 2 3 E-OFF Supplied by Uniflair Not supplied by Uniflair FIGURE 4. n example of the circuit outlined in the previous diagrams where units 1 and 3 are operating and 2 is in stand-by. The units are equipped with an additional internal motorized valve in order to prevent an eventual by-pass through the evaporator of the stand-by unit. OFF R R R -OFF -ON -ON E-ON FIGURE 5. n example of a unit with intelligent free cooling. E-ON FIGURE 4 Installation equipped with a pump for the primary circuit outside the unit If there isn t an onboard pump, but one has been mounted up or down stream from the chillers, it is necessary to equip the unit with devices which isolate the standby unit. For this reason, a motorized valve is usually placed on the inlet line and a non return valve on the outlet line, as can be seen in figure 3. During operation, the stand-by unit is isolated by the motorized valve which is placed on the aspiration line and the non return valve which is placed on the discharge line. In figure 4, operation with units 1 and 3 operating and unit 2 in stand-by is shown. When considering an intelligent free-cooling solution for installations of this type, it is necessary for the units to be equipped with an additional internal motorized valve in order to prevent an eventual by-pass through the evaporator of the stand-by unit. omparative analysis In order to verify the economic convenience of an intelligent free-cooling solution, two different solutions have been compared using a Uniflair BRF1306 unit, which can be seen in figure 5. This unit has the following characteristics: ooling capacity: about 300 kw Partialisazion steps: 6 (the units are equipped with 6 scroll compressors) Number of fans: 6 common type of installation has been chosen as an example featuring 3 units of which 1 is in stand-by: 2 units operating singularly 2 + 1 units in intelligent free-cooling mode There is a noticeable increase in the heat which is exchanged in both types of systems with intelligent free-cooling compared to an installation where the units are not linked. This increase allows an added annual energy saving of between 3% and 7% according to the diametric profile when compared to a traditional free-cooling installation. Moreover, when compared to a traditional system, the energy saving can reach 50%. The installation will now be analysed in detail by examining the following points: Pressure drop Water flow Heat exchange capacity Energy efficiency Pressure drop When comparing the two situations, a first analysis must be carried out regarding the difference in water flow in each of the two cases. See figure 6. Since connecting the free-cooling coils to each other increases the cross section of water flow by 1/5 for each pump compared to that for a single unit, the pres- 3

sure drop which each pump meets is halved. In the solution with connected units it is also necessary, however, to consider the pressure drop which is due to the interconnected collectors. Provisionally, these pressure drops can be estimated at being about 20% of the total pressure drop and with the following result: P (2+1) ~ P 2 = + 20% (P 2 ) 2 The decrease in the pressure drop implies an increase in the water flow and it is therefore necessary to compare the water flow in both cases. Water capacity Given that the water flow at nominal conditions is 70 m³/h, and considering the reduction in the pressure drop (which changes from 24 m w.c.m to 16.8 w.c.m), it is possible to obtain a new resistive curve and consequently the new water flow with the connected units, which is about 80-81m³/h. The water flow for each group of free-cooling coils is: (81 x 2)/3 = 54 m³/h. There is, therefore, a reduction in the flow per group of free-cooling coils from 70 m³/h to 54 m³/h and therefore a reduction of about 23%. TBLE 1 Energy saving in terms of mw/h and economic saving % for annual operation between an intelligent free-cooling system and traditional free-cooling Energy saving [kwh] [%] Frankfurt 34560 5% Rome 31587 3% Milan 29132 4% Manchester 46008 6% Paris 36954 4% msterdam 42558 7% Stockholm 28167 5% Madrid 36743 4% Berlin 31525 4% London 46018 6% openhagen 38077 6% Heat exchange capacity It is now necessary to analyse how the water flow varies the heat transfer capacity of the free-cooling coils. By using analytical procedures, which for reasons of brevity are not shown here, it is possible to demonstrate how when considering the water flow in the two cases: 1) for single units: water flow = 70000 l/h 2) for connected units: water flow = 70000 l/h - 23% = 53900 l/h it is possible to establish the thermal exchange co-efficient value which, by interconnecting the free-cooling exchangers, can theoretically increase by up to 40%. The heat exchanged in the free-cooling coils will now be examined. This is given by: with set-point: 10 ) are hypothesized, the temperature before the free-cooling pump is calculated proportionally: Tin = 10 11 l/h + 15 70 l/h = 14,3 81 l/h Therefore, the relationship between the heat which is effectively exchanged in the two cases is: Q (2+1) = (K(2+1) S (2+1)) (ΔT (acqua/aria)) (2+1) =1,43 0,93 = 1,33 Q (2) (K 2 S2) (ΔT (acqua/aria)) 2 Q (2+1) = 1,33 Q 2 Therefore, by interconnecting the free-cooling exchangers, the heat exchanged can increase by up to 33%. FIGURE 6. omparison examining water flow in each of the two cases. Since connecting the free cooling coils to each other increases the cross section of water flow by by 1/5 for each pump compared to that for a single unit, the pressure drop which each pump meets is halved. Q = K S ΔT acqua/aria It can be observed, therefore, that the heat exchanged depends not only on the capacity of the K S exchange, but also by the difference between the temperature of the inlet water and the ambient air. Since the system is sized according to the water flow at nominal conditions, if this value increases, a by-pass situation will be created. Given that the nominal water flow is 70000 l/h, and that the system is sized according to this flow, if this flow increases, a certain amount of this flow will be re-circulated, as shown in figure 7. If an external temperature of 5 (total free-cooling temperature) and a water temperature of 15 (ΔT = 5 SingleUnit P2 onnected units P(2+1) FIGURE 6 4

TBLE 2 omparison between the energy consumption of standard chillers, free-cooling chillers and intelligent free-cooling chillers bsorbed power [MWh] Standard hillers Free-cooling hillers Intelligent Free-cooling hillers Frankfurt 1107 747 712 Rome 1245 1056 1025 Milan 1144 815 786 Manchester 1116 789 743 Paris 1178 910 873 msterdam 1062 651 609 Stockholm 1001 541 513 Madrid 1204 938 902 Berlin 1088 707 676 London 1103 154 708 openhagen 1061 638 599 References: ooling capacity to be supplied: 568 kw Outlet water temperature with external temperature less than 15 : 15 Outlet water temperature with external temperature higher than 15 : 7 TBLE 3 omparison between the energy consumption of standard chillers and intelligent free-cooling chillers References as in table 2 FIGURE 7 Energy saving Standard Vs Intelligent Free-cooling hillers hillers [MWh] [%] Frankfurt 394 36 % Rome 220 18 % Milan 357 31 % Manchester 373 33 % Paris 304 26 % msterdam 452 43 % Stockholm 487 49 % Madrid 301 25 % Berlin 411 38 % London 394 36 % openhagen 462 44 % 70000 l/h 81000 l/h FIGURE 7. Recirculation of a certain amount of the nominal water flow when compared to the predicted value if the effective water flow increases as described in the text. Energy efficiency When comparing the absorbed power for both cases in free-cooling mode, it is necessary first of all to divide the analysis into two types of operation: total free-cooling or mixed free-cooling. In order to do this, a reference value must be hypothesized for the cooling capacity which is to be supplied to the system; this value can be reasonably considered that of the cooling capacity of the two units with: External temperature: 5 Inlet water temperature: 15 which is therefore, according to the characteristics of these units, 2 x 284 = 568 kw. By taking 568 kw as a reference value, it is therefore possible to evaluate at which external temperatures this capacity can be supplied by the units using only free-cooling coils or if it is also necessary to use a part of the refrigerant circuit capacity. From this comparison, it can be noted that when using two single units the cooling capacity is fully supplied by the free-cooling coils only. t Text 5 ; with three interconnected units the cooling capacity is fully supplied by the free-cooling coils at Text 7. In fact, the cooling capacity supplied by the system if the units are connected with an intelligent free-cooling system is higher by 33%. With external temperatures which are less than 5 for each single unit, and 7 for the connected units, the free-cooling coils fully dissipate the thermal load (which is presumed to be constant) and the temperature of the water is controlled by modulating the fan speed. Therefore, to compare the electrical absorption of the two solutions it is necessary to evaluate: the fan rotation speed and consequently their absorption the power absorption of the free-cooling pump, considering the difference in water flow and therefore the power absorption of the two solutions. From the diagram shown above, it can be noted that with the units which are linked together with intelligent free-cooling, the power absorption is less than that of the single unit when the external temperature is higher than 0, this is due to two factors: 1) not using the cooling capacity of the compressors (from 7 to 5 ) 2) the possibility of decreasing the fan rotation speed to below 5 compared to the single units. The power absorption of the two solutions is very similar below 0 ; this is due to the fact that the fan rotation speed, and therefore their power absorption, is very low due to the thermal exchange by natural convection on the free-cooling coils, and that in the total electrical absorption there is extra absorption by the free-cooling pump due to the increase in water flow from the connected units (7 kw instead of 6,5 kw). With external temperatures which are higher than 5 for the single units, and 7 for the connected units, the free-cooling coils do not fully dissipate the thermal load 5

(which is presumed to be constant) so it is necessary to use part of the cooling capacity of the compressors. lso in this case, however, the increase in cooling capacity due to intelligent free-cooling enables the compressors to be used less as shown in figure 9. The difference in electrical absorption translates into a significant energy saving, especially considering that a unit which has a free-cooling device already provides higher energy saving levels. It is possible to evaluate the possible energy savings in different European cities on the basis of this data by examining their respective climatic profiles, as can be seen in table 1. Tables 2 and 3 show a comparison with the annual energy consumptions of traditional systems. bsorbed power [kw] 50,0 45,0 40,0 35,0 30,0 25,0 20,0 onclusions European climatic profiles are associated with a concentration in two temperature ranges, around 8-12 and 18-22. Units or other apparatus which operate in an efficient way throughout the year need to have a higher performance in these temperature slots; this is why in free-cooling in general it is important to maximise the energy saving in mixed operation, rather than at temperatures lower than 0-5 where there is a noticeable energy saving, but also a reduced possibility of use. ccording to this logic, intelligent freecooling installations can be a solution to further reduce total electrical absorption by using the resources which are already available to ensure reliability of the system and therefore limit any extra costs. 15,0 10,0-10 FIGURE 8-9 -8-7 -6-5 -4-3 -2-1 0 1 2 3 4 5 6 7 Single unit onnected unit External temperature [ ] FIGURE 8. If the units are connected with intelligent free cooling, the absorbed power is lower than that of single units for external temperatures higher than 0, for the reasons described in the text. 120,0 110,0 100,0 90,0 80,0 bsorbed power [kw] 70,0 60,0 50,0 40,0 FIGURE 9. With external temperatures which are higher than 5 for the single units, and 7 for the connected units, the free-cooling coils do not fully dissipate the thermal load (which is presumed to be constant) so it is necessary to use part of the cooling capacity of the compressors. lso in this case, however, the increase in cooling capacity due to intelligent free-cooling enables the compressors to be used less. 30,0 25,0 20,0 10,0 FIGURE 9 0,0-10 -9-8 -7-6 -5-4 -3-2 -1 0 1 2 3 4 5 6 7 8 9 10 11 12 Single unit onnected unit External temperature [ ] Uniflair policy is one of continuos technological innovation and the ompany therefore reserves the right to amend any data herein without prior notice. ll rights reserved. Reproduction in whole or in part is prohibited. 6

05REF208X1-03/07 Uniflair Sp Viale della Tecnica, 2 35026 onselve (Pd) Italy Tel. +39 049 5388211 Fax +39 049 5388212 info@uniflair.com uniflair.com