DATASHEET - ESR5-NO-41-24VAC-DC Safety relay emergency stop/protective door, 24VDC/AC, 4 enabling paths Part no. ESR5-NO-41-24VAC-DC Catalog No. 118701 EL-Nummer (Norway) 0004133317 Delivery program Product range Electronic safety relays Basic function Emergency stop; emergency switching off Protective door Feedback circuit Features Mounting width mm 22.5 Automatic or manual start Operation Single-channel Supply voltage U s 24 V DC 24 V AC, 50/60 Hz Approval Safety related characteristics Cat. 1 PL c according EN ISO 13849-1 SILCL 1 according to IEC 62061 SIL 1 according to IEC 61508 PL e possible only with the aid of fault exclusions. Number of enabling paths to EN 60204-1 Stop functions category Enable current paths to IEC/EN 60204-1 Stop category 0 4 Signal current paths 1 Instructions For rated voltage surge: safety category 4 when using positively opening switches and routing the cables in separate sheathing. Technical data General Intended use Safety relay for monitoring emergency stop and protective door switch. Module used to safely interrupt electrical circuits. Policies List EMV 2004/108/EG, Maschinen 2006/42/EG Standards EN ISO 13849-1:2008, EN 62061:2005+AC:2010, EN 61508, Parts 1-7:2001, EN 50178:1997, EN 60204-1:2006+A1:2009 Dimensions (W x H x D) mm 22.5 x 99 x 114.5 Mounting width mm 22.5 Weight kg 0,22 Mounting position As required Mounting Top-hat rail IEC/EN 60715, 35 mm Connection type M3 screw terminals Lifespan, mechanical Operations x 10 6 10 Terminal capacity Solid 2 mm 1x (0.2 2.5) 2x (0.2 1) Flexible with ferrule 2 mm 1x (0.25 2.5) 2x (0.25 1) Solid or stranded AWG 24-12 Terminal screw Nm Pozidriv screwdriver Size 2 10/22/2018 Eaton 118701 ED2018 V49.0 EN 1 / 7
Standard screwdriver mm 0.6 x 3.5 Max. tightening torque Nm 0.6 Stripping length mm 7 Material Housing: polyamide PA not reinforced Contacts: Material: silver tin oxide, gold plated (AgSnO2, 0.2 µm Au) Duty factor % DF 100 Operating conditions Climatic environmental conditions Climatic proofing Dry heat to IEC 60068-2-2 Damp heat as per EN 60068-2-3 Ambient temperature Operation ϑ C -20 - +55 Storage ϑ C -40 - +70 Condensation Non-condensing Atmospheric conditions relative humidity % Max. 75 Air pressure (operation) hpa 795-1080 Altitude Above sea level m 2000 Power loss P W 5.16 Ambient conditions, mechanical Degree of protection to VDE 0470-1 Enclosures IP20 Terminals IP20 Degree of Protection Installation location: IP54 B10d [switching cycles] 230000 Protection against direct contact when actuated from front (EN 50274) Finger and back-of-hand proof Vibrations (IEC/EN 60068-2-6) 10-150 Hz Amplitude: 0.15 mm Acceleration: 2 g Clearance in air and creepage distances EN 50178, UL 508, CSA C22.2, No. 14-95 Rated impulse withstand voltage U imp V AC 4000 Insulation Basic isolation Safe isolation, reinforced isolation, and 6 kv between input circuit / NC contacts, and enable current paths. Notes Safety category 4 when using positively opening switches and laying the cables in separate sheathing. Overvoltage category/pollution degree III/2 Stop category Technical safety parameters: Values according to EN ISO 13849-1 Performance level Category Safety integrity level claim limit Safety integrity level according to EN60204-1 according to EN ISO 13849-1 according to EN ISO 13849-1 in accordance with 62061 In accordance with IEC 61508 4,05 PL c Kat. 1 SILCL 1 SIL 1 Probability of failure per hour PFH d -10 x 10 4.05 Prooftest High Demand Months 240 Prooftest Low Demand Months 167 Rated operational voltage U e V AC 230 Rated operational voltage U e V 24 V AC, 24 V DC Permissible range 0.85-1.1 x Ue Rated insulation voltage U i V AC 250 Quadratic summation current A 2 72 A 2 2 2 2 2 2 (I TH = I1 + I2 + I3 + I4 ) Notes Observe derating curve 10/22/2018 Eaton 118701 ED2018 V49.0 EN 2 / 7
Engineering Inrush current A min - max 0.025-6 Minimum switching capacity W 0.4 Control circuit Power supply circuit AC operated 50/60 Hz W 3.4 DC operated W 1.6 Fuse for control circuit supply 24 V short-circuit proof Input data Rated current ma S12:65, S34:40 Current consumption ma AC: 140 DC: 65 Voltage at input, starting and feedback circuit V DC Approx. 24 Max. resistive load of the cable R Ω 22 Short-circuit current A 2.3 Pick-up time (K1, K2) for UN automatic mode, typical t A ms 65 Pick-up time ms normally 20 Reset time (K1, K2) for U N, normally t R ms 45 Recovery time t W ms Approx. 1000 Simultaneity for inputs 1/2 t sync ms Maximum permissible total cable resistance (input and starting circuits for UN) R L Ω 22 Maximum switching frequency Hz 0.5 Status indication LED Green Output data Contact type Non-delayed enable current paths 4 Delayed signal current path 1 Switching voltage min max 15-250 V AC 15-250 V DC Limiting continuous current A per N/O: 6 N/C: 3 Short-circuit protection for output circuits, external Fuse 6 A gl/gg Miniature circuit-breaker with characteristic C: 24 V AC/DC 6 A Output fuse fast 6 Miniature circuit-breaker (24 VAC/VDC) C6 Maximum breaking power Resistive load (τ = 0 ms) 24 V DC W 144 48 V DC W 288 110 V DC W 110 220 V DC W 88 250 V AC VA 1500 Inductive load (τ = 40 ms) 24 V DC W 42 48 V DC W 42 110 V DC W 42 220 V DC W 42 Switching capacity AC-15 DC-13 230 V A 4 A bei 360 S/h 3 A bei 3600S/h In accordance with IEC 60947-5-1 24 V A 4 A bei 360 S/h 2.5 A bei 3600S/h Further information (flip catalog) description 10/22/2018 Eaton 118701 ED2018 V49.0 EN 3 / 7
Electromagnetic compatibility (EMC) Emitted interference In accordance with EN 61000-6-4 Interference immunity according to EN 61000-6-2 Design verification as per IEC/EN 61439 Technical data for design verification Rated operational current for specified heat dissipation I n A 0 Heat dissipation per pole, current-dependent P vid W 0 Equipment heat dissipation, current-dependent P vid W 0 Static heat dissipation, non-current-dependent P vs W 5.16 Heat dissipation capacity P diss W 0 Operating ambient temperature min. C -20 Operating ambient temperature max. C 55 IEC/EN 61439 design verification 10.2 Strength of materials and parts 10.2.2 Corrosion resistance Meets the product standard's requirements. 10.2.3.1 Verification of thermal stability of enclosures Meets the product standard's requirements. 10.2.3.2 Verification of resistance of insulating materials to normal heat Meets the product standard's requirements. 10.2.3.3 Verification of resistance of insulating materials to abnormal heat and fire due to internal electric effects Meets the product standard's requirements. 10.2.4 Resistance to ultra-violet (UV) radiation Meets the product standard's requirements. 10.2.5 Lifting Does not apply, since the entire switchgear needs to be evaluated. 10.2.6 Mechanical impact Does not apply, since the entire switchgear needs to be evaluated. 10.2.7 Inscriptions Meets the product standard's requirements. 10.3 Degree of protection of ASSEMBLIES Does not apply, since the entire switchgear needs to be evaluated. 10.4 Clearances and creepage distances Meets the product standard's requirements. 10.5 Protection against electric shock Does not apply, since the entire switchgear needs to be evaluated. 10.6 Incorporation of switching devices and components Does not apply, since the entire switchgear needs to be evaluated. 10.7 Internal electrical circuits and connections Is the panel builder's responsibility. 10.8 Connections for external conductors Is the panel builder's responsibility. 10.9 Insulation properties 10.9.2 Power-frequency electric strength Is the panel builder's responsibility. 10.9.3 Impulse withstand voltage Is the panel builder's responsibility. 10.9.4 Testing of enclosures made of insulating material Is the panel builder's responsibility. 10.10 Temperature rise The panel builder is responsible for the temperature rise calculation. Eaton will provide heat dissipation data for the devices. 10.11 Short-circuit rating Is the panel builder's responsibility. The specifications for the switchgear must be observed. 10.12 Electromagnetic compatibility Is the panel builder's responsibility. The specifications for the switchgear must be observed. 10.13 Mechanical function The device meets the requirements, provided the information in the instruction leaflet (IL) is observed. Technical data ETIM 7.0 Relays (EG000019) / Device for monitoring of safety-related circuits (EC001449) Electric engineering, automation, process control engineering / Low-voltage switch technology / Monitoring equipment (low-voltage switch technology) / Device for monitoring of safetyrelated circuits (ecl@ss10.0.1-27-37-18-19 [ACO304011]) Model Basic device Suitable for monitoring of position switches Yes Suitable for monitoring of emergency-stop circuits Yes Suitable for monitoring of valves No Suitable for monitoring of optoelectronic protection equipment No Suitable for monitoring of tactile sensors No Suitable for monitoring of magnetic switches No Suitable for monitoring of proximity switches No Type of electric connection Screw connection Rail mounting possible Yes 10/22/2018 Eaton 118701 ED2018 V49.0 EN 4 / 7
Rated control supply voltage Us at AC 50HZ V 0-26.4 Rated control supply voltage Us at AC 60HZ V 0-0 Rated control supply voltage Us at DC V 0-0 Voltage type for actuating AC/DC With detachable clamps Yes Evaluation inputs One- and two-channel With start input Yes With muting function No With feedback circuit Yes Release-delay s 0-0 Number of outputs, safety related, undelayed, with contact 4 Number of outputs, safety related, delayed, with contact 0 Number of outputs, safety related, undelayed, semiconductors 0 Number of outputs, safety related, delayed, semiconductors 0 Number of outputs, signalling function, undelayed, with contact 1 Number of outputs, signalling function, delayed, with contact 0 Number of outputs, signalling function, undelayed, semiconductors 0 Number of outputs, signalling function, delayed, semiconductors 0 Category according to EN 954-1 1 Type of safety acc. IEC 61496-1 None Stop category acc. IEC 60204 0 Performance level acc. EN ISO 13849-1 Level c SIL according to IEC 61508 1 With approval for TÜV Yes With approval for BG BIA No With approval according to UL Yes Width mm 22.5 Height mm 99 Depth mm 114.5 Approvals Product Standards IEC/EN see Technical Data; UL 508; CSA-C22.2 No. 14-95; CE marking UL File No. E29184 UL Category Control No. NKCR; NKCR7 CSA File No. UL report applies to both US and Canada CSA Class No. 3211-83; 3211-03 North America Certification UL listed, certified by UL for use in Canada Degree of Protection IEC: IP20, UL/CSA Type: - Characteristics Characteristic curves 10/22/2018 Eaton 118701 ED2018 V49.0 EN 5 / 7
Derating curve - vertical or horizontal installation position, without clearance Load curve relay - ohmic load 10/22/2018 Eaton 118701 ED2018 V49.0 EN 6 / 7
Dimensions Additional product information (links) IL05013028Z operator manual for electricians IL05013028Z operator manual for electricians description ftp://ftp.moeller.net/documentation/awa_instructions/il05013028z2018_06.pdf http://de.ecat.moeller.net/flip-cat/?edition=hplte&startpage=13.15 10/22/2018 Eaton Industries GmbH http://www.eaton.eu 10/2018 by Eaton Industries GmbH Eaton 118701 ED2018 V49.0 EN 7 / 7