Company Directive ENGINEERING SPECIFICATION EE SPEC: 136

Similar documents
MESP TECHNICAL SPECIFICATION FOR A RECTIFIER UNIT CONTROL & PROTECTION SYSTEM FOR USE IN THE 1500V DC TRACTION SYSTEM

Diodes or VDR s fitted internally if requested.

Specification Voltage Limiting Device

3 Pole Contactors with AC operating coils

D2600 Relay. 1. Relay Types. 2. Technical Data

RMS Product Presentation

INSTRUCTION SHEET. Eaton Logic Controller ELCB Controllers

1S20. Arc Fault Monitor Relay. Features. Introduction. ARC Fault Protection

the Interactive Catalog

Positive-guided relay outputs: 3 safety contacts (N/O), instantaneous. 1 auxiliary contact (N/C), instantaneous

PGR-6101 MANUAL GROUND-FAULT & INSULATION MONITOR

Positive-guided relay outputs: 3 safety contacts (N/O), instantaneous. 1 auxiliary contact (N/C), instantaneous

Ultra Slim Relays 24

29 $ Manual Motor Starters FREESHIPPING. MOTOR CONTROLS 25. Features: MMS-32H Frame. MMS-63H Frame.

TeSys IEC Contactors and Overload Relays

CONTROL PANEL WIRING SPECIFICATIONS

EAO Your Expert Partner for Human Machine Interfaces. EAO Product Information. Series 19

Allen-Bradley PLCs. 100 Programmable Controller Processor Unit -Catalog Nos LPI01, -LP102, -LP103, -LP104 SLC TM. The Unit

Indicator, round, raised, full face with plastic matt chrome bezel, 22.5 mm mounting, lamp block included. Yellow Green

PERFORMANCE SPECIFICATION

ict contactors EN 61095, IEC 1095 Interference

RPM42P7 power plug-in relay - Zelio RPM - 4 C/O V AC - 15 A - with LED

IELR Rail-Mount Series Magnetic Circuit Protectors

E-STOP relays, safety gate monitors

E-STOP relays, safety gate monitors

SE-135 MANUAL GROUND-FAULT GROUND-CHECK MONITOR

Multifunction Transducer MT440

IELR Series

SECTION SWITCHBOARDS

KFA-37HD8. Relay-type Annunciators with LED Lights. Features 6-36 KFA-37HD8

1.5 Solid State Relays

RXM4AB1BD miniature plug-in relay - Zelio RXM - 4 C/O - 24 V DC - 6 A

AUXILIARY RELAYS FOR TRIPPING APPLICATIONS

MG24434 Supplementary Protector SUPPLEMENTARY PROTECTOR, 240VAC, 16A, CIRCUIT BREAKER TYPE: STANDARD

SSV-T and SSC-T High Drop-out Relay. Range amps amps amps amps. Operating Frequency: Temperature Error:

RE7RB13MW adjustable off-delay timing relay s V AC DC - 2OC

Monitoring Relays. SIRIUS 3UG Monitoring Relays for Stand-Alone Installation. Line monitoring. 8/62 Siemens IC Overview

4 C/O. Contact material AgNi AgNi gold-plated Nominal contact current Inrush current

Push buttons and selectors

PRODUCT SPECIFICATION. PC Board Relays. Series.

E-STOP relays, safety gate monitors

PERFORMANCE SPECIFICATION SHEET

IEC Contactors. Auxiliary Contact Blocks GENERAL

E-STOP relays, safety gate monitors

3RM1 Hybrid Starters 6SIRIUS. contents. Industrial Controls Product Catalog 2017

E-STOP relays, safety gate monitors

Products :: Circuit Protection :: Hydraulic/Magnetic Circuit Breakers

Micro Contactor MA Series

MODULES FOR SAFETY AND MONITORING

www. ElectricalPartManuals. com jllill,.'1.1. Type SBF-1 Breaker Failure Relay

LATCHING AUXILIARY RELAYS

BE1-50/51M TIME OVERCURRENT RELAY ADVANTAGES

Vector Drive - Troubleshooting Guide

Function permission: yes/no. Operating range: 0.10 to 30 xin (step 0.01) Operating time: 0.02 to 300 s (step 0.01 s) Activation level 100%

Company Directive STANDARD TECHNIQUE: TP18A/1. Application of Connection Control Panels for Soft Intertrip and/or Voltage Constraint Schemes

Technical data. Dimensions: see page 116. ): 4 kv Rated insulation voltage (U i Over-voltage category: Power supply. Rated operating voltage (Un):

DIN Series MINIATURE CIRCUIT BREAKERS, RESIDUAL CURRENT CIRCUIT BREAKERS. Introducing the DIN Series High-quality, high-performance circuit breakers

V REG.-Nr. 3919, Z E214024

Two-hand control unit

Positive-guided relay outputs: 3 safety contacts (N/O), instantaneous. 1 auxiliary contact (N/C), instantaneous

MESP TECHNICAL SPECIFICATION FOR SCADA CABLING IN SUBSTATIONS

E-STOP relays, safety gate monitors

2C138. Sensitive Earth Fault Relay. Features. Application. Operation

MOTION LABORATORIES CHAIN HOIST MOTOR CONTROL SYSTEMS MANUAL. Basic Outline of Operation for Distro Controllers

DRTS 3 PLUS Advanced Protection Relay Test Set and Measurement System

Ihr autorisierter Distributor: Neumüller Elektronik GmbH

PERFORMANCE SPECIFICATION SHEET

Operating instructions. Switching amplifier DN0210 DN / / 2015

Product and functional description

RE48ATM12MW on-delay timing relay s..300 h V AC - 2 OC

Digital Multifunction Meters. Digital Multifunction Meters

Safe timer relay/contact expansion modules

HID. GE Consumer & Industrial Multilin. High Impedance Differential Module Instruction manual GEK Copyright 2005 GE Multilin

IMP/ 001 / 014 Policy for the Protection of Distribution Networks

PowerLogic power-monitoring units. Power Meter PM500. Technical data sheet 2006

Product and functional description

ENhanced TEChnology. Solid insulated vacuum recloser for power distribution system thru 15kV, 27kV, 38kV. Ver.

Mini Contactors & Overloads

Switching module for AC V and up to three load stages, with manual switching

RM4TR31 three-phase network control relay RM4-T - range V

PERFORMANCE SPECIFICATION SHEET

Residual overvoltage relay

Digital Frequency Divider INSTRUCTION MANUAL CONTENTS. 1. Working Principle Installation Setting Up Technical Data 4.

RE8TA31BU industrial timing relay s - type A - 24 V AC/DC, V AC - 1 C/O

2T105. Multi Range Digital Setting Time Delay Relay. Features. Application. Operation

BE1-51 BE1-51/27C BE1-51/27R TIME OVERCURRENT RELAY

PSR-SCP- 24DC/SDC4/2X1/B PSR-SPP- 24DC/SDC4/2X1/B

Expansion Unit Catalog Nos , - 152, - 153, - 154, - 156, -E157

60103 Circuit Breaker

(1) Description of Operation. Autoreclose. 7SR224 Recloser Controller. (1) Description of Operation 7SR224 Appendix 2) Single/Triple Autoreclose

RE8YG31BUTQ industrial timing relay s - type Qc - 24 V AC/DC, V AC - 1C/O

RE17LAMW on-delay timing relay - 1 s..100 h V AC/DC - solid state output

Safe monitoring relays

Combined Overcurrent and Earth-fault Relay SPAJ 141 C. Product Guide

Chassis Power Supplies

E-STOP relays, safety gate monitors

Magnetically Actuated Safety Interlock Switches

E3S-A. Built-in Amplifier Photoelectric Sensor (Medium Size) Ordering Information. Built-in Amplifier Photoelectric Sensors. Horizontal. 7 m.

Mini Contactors. Mini Contactor Relays 4-pole 20 Auxiliary Contact Blocks. Interface Contactor Relays. Mini Contactors 22 Auxiliary Contact Blocks

MRA1 Trip circuit supervision. Manual MRA1 (Revision A)

Transcription:

Company Directive ENGINEERING SPECIFICATION EE SPEC: 136 Ancillary Electrical Equipment for Use in Conjunction with Switchgear and Protection/Control Panels NOTE: The current version of this document is stored in the WPD Corporate Information Database. Any other copy in electronic or printed format may be out of date. Copyright 2017 Western Power Distribution IMPLEMENTATION PLAN EE SPEC:136 June 2017-1 of 29 -

IMPLEMENTATION PLAN Introduction This document specifies the ancillary equipment to be used in conjunction with switchgear and protection / control panels. Main Changes This is a new document and replaces information on ancillary equipment included in other Engineering Specification documents. Impact of Changes This document replaces the information on ancillary items currently contained in EE SPEC: 3, EE SPEC: 86 and EE SPEC: 87. Implementation Actions Managers shall ensure that all staff involved with the specification, installation and maintenance of HV, EHV and 132kV switchboards and protection / control / alarm panels are aware of and adhere to the requirements of this document. Implementation Timetable This document shall be implemented on issue for the specification of new or replacement ancillary equipment. EE SPEC:136 June 2017-2 of 29 -

REVISION HISTORY Document Revision & Review Table Date Comments Author June 2017 This is a new document that replaces the requirements for ancillary equipment included in other EE Specification documents. The most significant changes are listed below: i5m transducers have been introduced Incandescent lamps have been replaced by LED clusters Andy Hood EE SPEC:136 June 2017-3 of 29 -

INDEX 1.0 INTRODUCTION 2.0 PROTECTION AND ALARM RELAYS 3.0 AUXILIARY RELAYS AND CONTACTORS 4.0 CONTROL AND SELECTOR SWITCHES 5.0 TRANSDUCERS 6.0 PUSH BUTTONS AND LAMPS APPENDIX A APPENDIX B APPENDIX C APPENDIX D APPENDIX E APPENDIX F APPENDIX G AUXILIARY RELAY DATA SHEETS TRANSDUCER DATA SHEETS PUSH BUTTON AND LAMP DATA SHEETS SUPERSEDED DOCUMENTATION ASSOCIATED DOCUMENTATION IMPACT ON COMPANY KEY WORDS EE SPEC:136 June 2017-4 of 29 -

1.0 INTRODUCTION 1.1 This document details the ancillary equipment to be used in conjunction with switchgear and protection/control panels. 1.2 This is a new document and replaces information on ancillary equipment held in sections of other Engineering Specification documents including EE SPEC: 3, EE SPEC: 86 and EE SPEC: 87. 2.0 PROTECTION AND ALARM RELAYS 2.1 Protection, alarm and control relays shall comply with ENATS 48-4, ENATS 48-5, BSEN 60255, IEC 60255, BSEN 61810 and BSEN 61811 as applicable and be of a type and make approved for use within Western Power Distribution. 2.2 The approved relay list is contained within the current version of Engineering Specification EE SPEC: 98. 2.3 Alternative relays can be submitted to the Technical Policy Manager for evaluation. 3.0 AUXILIARY RELAYS AND CONTACTORS 3.1 Auxiliary relays and small contactors shall comply with ENATS 50-18. 3.2 Datasheets for auxiliary relays used for telecontrol purposes are provided in Appendix A. 3.3 Relays operated by WPDs telecontrol system are switched in both the +ve and -ve circuits. Unless otherwise specified, relays shall be suitable for use with the D.C. auxiliary supply voltage/s specified on the Switchgear Enquiry / Ordering Schedule. If there is any doubt over the required relay ratings the tenderer shall confirm the requirements with WPD at the time of tender. 4.0 CONTROL AND SELECTOR SWITCHES 4.1 Control and selector switches and their handles shall meet the requirements of ENATS 50-18 and BS EN 60947-3 and shall be adequately rated for the application. Switches used within trip or close circuits shall as a minimum satisfy the following requirements: Category AC22A (switching of mixed resistive and inductive ac. loads): 32A at 250/415V Category AC23A (switching of motor loads or other highly ac. inductive loads): 28A at 250/415V Category DC21 (switching of resistive dc. loads): 3.5A at 110V 4.2 Datasheets for control and selector switches are provided in Appendix B. EE SPEC:136 June 2017-5 of 29 -

5.0 TRANSDUCERS 5.1 All transducers shall comply with BS EN 60688 and shall be self-powered unless otherwise specified in the schedule. They shall be located to allow easy access for testing and removal. The following general requirements also apply: Temperature reference range: 0 o C to 50 o C Operating temperature range: -10 o C to +55 o C Output voltage: 25Vdc (open circuit voltage) 15Vdc (compliance voltage) Burden on output: 1000 ohms (maximum) 100 ohms (typical) Resistor in outstation: 333.3 ohms (15mA at 5V) Output load: Compliance voltage/maximum rated output. 5.2 Where programmable transducers are provided they shall be pre-programmed by the panel supplier in accordance with the data sheet. 5.3 Data sheets for specific types of transducers are provided in Appendix C. 6.0 PUSH BUTTONS AND LED LAMPS 6.1 Push button switches shall meet the requirements of ESI Standard 50-18 unless otherwise modified by this document. Switches shall be Class I or higher. 6.2 Switching system shall be snap action. 6.3 Contact terminals shall be screw type. 6.4 Contacts shall be hard silver. 6.5 The voltage supply for LEDs shall be both 110V AC and DC. The supply may be manually switched from AC to DC. 6.6 Data sheets and drawings for push button switches and lamps are provided in Appendix D. EE SPEC:136 June 2017-6 of 29 -

APPENDIX A AUXILLIARY RELAY DATA SHEET REFERENCE: AR1 Relay Function: Relay Coil: Relay Type: 1) Circuit Breaker Open 2) Circuit Breaker Close 3) Tap-change Control Auto 4) Tap-change Control Manual 5) Tap-change Raise 6) Tap-change Lower 48V DC or 24V DC (as specified in Enquiry/Ordering Schedule) Continuous rating with transient suppression diode Self Reset Approved Relays: Reference: Arteche / Schneider 48V DC: RD-2SYDI 48VDC OP.00001 24V DC: RD-2SYDI 24VDC OP.00001 Relay Socket: DN DE IP10 Relay Retaining Clip: E-41 Terminal Allocation: Terminal No. 1 2 3 5 7 4 6 8 Relay coil with diode Terminal 1 ve, Terminal 2 +ve 3 5 normally open contact 3 7 normally closed contact 4 6 normally open contact 4 8 normally closed contact Description of Function EE SPEC:136 June 2017-7 of 29 -

APPENDIX A (continued) AUXILLIARY RELAY DATA SHEET REFERENCE: AR2 Functions: Relay Coil: Relay Type: Operating Convention: 1) SEF In / Out of Service 2) Instantaneous In / Out of Service 3) Auto Reclose In / Out of Service 4) Tap-change Control 3% Voltage Reduction In / Out 5) Tap-change Control 6% Voltage Reduction In / Out 6) Tap-change Control Independent / Manual 7) Tap-change Control Raise Inhibit Operate Coil: 48V DC or 24V DC (as specified in ordering schedule) Continuous rating with transient suppression diode Reset Coil: 48V DC or 24V DC (as specified in ordering schedule) Intermittent rating with transient suppression Latching When the relay is reset the function is In Service and when the operate coil is energised the function is Out of Service. Approved Relays: Arteche / Schneider Reference: 48V DC: BF-3BB 48VDC 24V DC: BF-3BB 24VDC Relay Socket: FN DE IP10 Relay Retaining Clip: E-31 Terminal Allocation: Terminal No. 10-14 1-2 7-3 - 11 8-4 - 12 9-5- 13 Description of Function Main relay coil with diode and normally closed contact. Terminal 14 +ve, Terminal 10 -ve Reset relay coil with diode and normally open contact. Terminal 1 -ve, terminal 2 +ve 7 3 normally open contact 3 11 normally closed contact 8 4 normally open contact 4 12 normally closed contact 9-5 normally open contact 5 13 normally closed contact EE SPEC:136 June 2017-8 of 29 -

APPENDIX A (continued) AUXILLIARY RELAY DATA SHEET REFERENCE: AR3 Functions: Relay Coil: Relay Type: 1) Auto Reclose Counter Reset 2) Protection Reset 48V DC or 24V DC (as specified in Enquiry/Ordering Schedule) Continuous rating with transient suppression diode Self Reset Approved relays: Reference: Arteche / Schneider 48V DC: RD-2SYDI 48VDC OP.00001 24V DC: RD-2SYDI 24VDC OP.00001 Relay Socket: DN DE IP10 Relay Retaining Clip: E-41 Terminal Allocation: Terminal No. 1 2 3 5 7 4 6 8 Relay coil with diode Terminal 1 ve, Terminal 2 +ve 3 5 normally open contact 3 7 normally closed contact 4 6 normally open contact 4 8 normally closed contact Description of Function EE SPEC:136 June 2017-9 of 29 -

APPENDIX A (continued) AUXILLIARY RELAY DATA SHEET REFERENCE: AR4 Function: Relay Coil: Relay Type: Operating Convention: 1) Arc Suppression Coil Shorting Switch Auto/Non-Auto Operate Coil: 48V DC or 24V DC (as specified in ordering schedule) Continuous rating with transient suppression diode Reset Coil: 48V DC or 24V DC (as specified in ordering schedule) Intermittent rating with transient suppression Latching When the relay is reset the function is in Auto and when the operate coil is energised the function is in Non-Auto. Approved relays: Reference: Relay Socket: Arteche / Schneider 48V DC: BF-3BB 48VDC 24V DC: BF-3BB 24VDC FN DE IP10 Relay Retaining Clip: E-31 Terminal Allocation: Terminal No. 10-14 1-2 7-3 - 11 8-4 - 12 9-5- 13 Description of Function Main relay coil with diode and normally closed contact. Terminal 14 +ve, terminal 10 -ve Reset relay coil with diode and normally open contact. Terminal 1 -ve, terminal 2 +ve 7 3 normally open contact 3 11 normally closed contact 8 4 normally open contact 4 12 normally close contact 9-5 normally open contact 5 13 normally closed contact EE SPEC:136 June 2017-10 of 29 -

APPENDIX A (continued) AUXILLIARY RELAY DATA SHEET REFERENCE: AR5 Function: Relay Coil: Min. Operating Current: Relay Contact: Other Details: 1) Protection Trip Status Relay Current Operated. Wound with conductor of minimum cross-sectional area of 1.5 sq mm Type A: 0.4A, duration 40 to 120 milliseconds* Type B: 0.15A duration 40 to 120 milliseconds* Reed relay, one normally open contact Contact Rating, 1.0 to 20mA 48V DC Insulation Test 2kV, 50Hz for 1 minute Relay to be enclosed in a mild steel case covered by a heat shrink plastic sleeve. The magnetic screening shall be sufficient to prevent spurious operations by the passage of fault current through adjacent metalwork. The security of the connections to the coil winding is of paramount importance and the coil winding wire shall be used to form the connection tails without intermediate joints. The coil windings shall have the positive tail clearly marked. Relay requires a separate terminal block. Approved Relay: Reference: Control Engineering Ltd 892 Type A (0.4A) 892 Type B (0.15A) * Note: For most switchgear an operating current of 0.4A is applicable. EE SPEC:136 June 2017-11 of 29 -

APPENDIX A (continued) AUXILLIARY RELAY DATA SHEET REFERENCE: AR6 Function: Relay Coil: Relay Type: 1) AC/DC Indication Auxiliary Relay 110V AC continuous rating Self Reset Approved relays: Reference: Relay Base: Arteche / Schneider RF-4SY 110VAC OP00001 FN-DE-IP10 Relay Retaining Clip: E-40 Terminal Allocation: Terminal No. Description of Function 1 2 110V AC relay coil 7 3-11 12 4-8 13 5 9 14 6 10 7 3 normally open contact 3 11 normally closed contact 8 4 normally open contact 4 12 normally closed contact 9 5 normally open contact 5 13 normally closed contact 10 6 normally open contact 6 10 normally closed contact EE SPEC:136 June 2017-12 of 29 -

APPENDIX A (continued) AUXILLIARY RELAY DATA SHEET REFERENCE: AR7 Function: Relay Coil: Relay Type: 1) ASC SEF Enable / Disable Operate Coil: 48V DC or 24V DC (as specified in ordering schedule) Continuous rating with transient suppression diode Self Reset Approved relays: Reference: Relay Socket: Arteche / Schneider 48V DC: RF-4SYDI 48VDC OP.00001 24V DC: RF-4SYDI 24VDC OP.00001 DN DE IP10 Relay Retaining Clip: E-41 Terminal Allocation: Terminal No. 1 2 3 7 11 4 8 12 5 9 13 6 10 14 Relay coil with diode Terminal 1 ve, Terminal 2 +ve 3 7 normally open contact 3 11 normally closed contact 4 8 normally open contact 4 12 normally closed contact 5 9 normally open contact 5 13 normally closed contact 6 10 normally open contact 6 14 normally closed contact Description of Function EE SPEC:136 June 2017-13 of 29 -

APPENDIX A (continued) AUXILLIARY RELAY DATA SHEET REFERENCE: AR8 Function: Relay Coil: Relay Type: Operating Convention: 1) Tap-change Control Lockout Relay Operate Coil: 110V AC Continuous Rating Reset Coil: 100V AC Continuous Rating Latching When the relay is reset the scheme is reset and when the operate relay is energised the scheme is locked out Approved relays: Reference: Relay Socket: Arteche / Schneider BF-4 110VDC FN DE IP10 Relay Retaining Clip: E-31 Terminal Allocation: Terminal No. Description of Function B1 2 110V AC operate relay coil 1 2 110V AC reset relay coil 3 7 11 3 7 normally open contact 3 11 normally closed contact 4 8 12 4 8 normally open contact 4 12 normally closed contact 5 9 13 5 9 normally open contact 5 13 normally closed contact 6 10 14 6 10 normally open contact 6 14 normally closed contact EE SPEC:136 June 2017-14 of 29 -

APPENDIX B TRANSDUCER DATA SHEET REFERENCE: TD1 Function: Input Current: Current Transducer (1 ampere) 1.0A AC (nominal) 1.5A AC (full scale continuous) Output Current: 0 to 10mA DC (nominal) Accuracy: Class 0.2 15mA DC (full scale) 25mA DC (maximum) Excessive Input: Transducer shall withstand: 3x rated current continuously 4x rated current for 5 minutes 25x rated current for 3 seconds 50x rated current for 1 second Reference: GE Grid Solutions i5mcx2h1clnrx Important - Transducer shall be supplied pre-programmed by the panel supplier in accordance with the above requirements EE SPEC:136 June 2017-15 of 29 -

APPENDIX B (continued) TRANSDUCER DATA SHEET REFERENCE: TD2 Function: Input Voltage: Output Current: AC Voltage Transducer (110 Volts AC) 110V AC (nominal) 132V AC (full scale continuous) 0 to 2mA DC for input voltage of 0 to 88V AC 2 to 10mA DC for input voltage 88V to 132V AC Accuracy: Class 0.2 Excessive Input: Reference: Transducer shall withstand: 1.5x rated voltage continuously Shall withstand 2x rated voltage for 10 seconds GE Grid Solutions i5mvx2h1clnrx Important - Transducer shall be supplied pre-programmed by the panel supplier in accordance with the above requirements EE SPEC:136 June 2017-16 of 29 -

APPENDIX B (continued) TRANSDUCER DATA SHEET REFERENCE: TD4 Function: Input Current: Ampere / Voltage / Watt / VAR Transducer (110 volts, 1 ampere) 1.0A AC (nominal) 1.5A AC (full scale continuous) Input Voltage: 110V AC (nominal) 132V AC (full scale continuous) Output: Amperes: 0 to 10mA DC (nominal) 15mA DC (full scale) 25mA DC (maximum) Voltage: Watts: Vars: 0 to 2mA DC for input voltage 0 88V a.c. 2 to 10mA DC for input voltage 88V to 132V a.c. 10mA D.C. to 0 to +10mA D.C. (nominal) Reverse power flow produces negative output Forward power flow produces positive output 10mA D.C. to 0 to +10mA D.C. (nominal) Leading Vars produce negative output Lagging Vars produce positive output Accuracy: Excessive Input: Reference: Connection: Class 0.2 for current and voltage measurements Class 0.5S for power measurements Transducer shall withstand: 2x rated current continuously 5x rated current for 10s 20x current for 1s 1.2x rated voltage continuously 2x rated voltage for 10s GE Grid Solutions I5MTX2H1NCLLLLRX 4 wire, unbalanced Important Transducer shall be supplied pre programmed by the panel supplier in accordance with the above requirements EE SPEC:136 June 2017-17 of 29 -

APPENDIX B (continued) TRANSDUCER DATA SHEET REFERENCE: TD5 Function: Auxiliary Supply: Input: Output: Accuracy: Reference: Tap Position Indication (TPI) Transducer 110V AC (nominal) 80V AC (min) 130Va.c. (max.) 3VA burden Chain Resistance 150 to 10,000 ohms 0 to 10mA DC 2% of full scale reading Fundamentals Ltd FTPT/2 EE SPEC:136 June 2017-18 of 29 -

APPENDIX B (continued) TRANSDUCER DATA SHEET REFERENCE: TD6 Function: DC Voltage Transducer The transducer auxiliary supply range, input voltage and output current shall be in accordance with the following table: Battery Voltage (DC Volts) Auxiliary Supply Range (DC Volts) Input Voltage (DC Volts) Output Current (ma DC) 24 30 48 110 220 19 to 70 19 to 70 19 to 70 70 to 300 70 to 300 Min. Max. Min. Max Min. Max Min. Max. Min. Max. 20V 29V 25V 36V 40V 58V 80V 140V 160V 280V 0mA 10mA 0mA 10mA 0mA 10mA 0mA 10mA 0mA 10mA Accuracy: Reference: +/- 0.5% or less GE Grid Solutions I5MVX2L1CLNRX (19 to 70V DC Auxiliary Supply) I5MVX2H1CLNRX (70 to 300V DC Auxiliary Supply) EE SPEC:136 June 2017-19 of 29 -

APPENDIX C PUSH BUTTON SWITCH AND LAMP DATA SHEET REFERENCE: PB1 Switch Functions: Button Description: Contact Arrangement: 1) Auto Reclose In 2) SEF In 3) Instantaneous Protection In 4) ASC Shorting Switch Non-Auto 5) Tap-change Control Independent 6) Tap-change Control Parallel Clear Button / Lens with 110V lamp and guard 2x NO contacts, 1x NC contact Engraving Requirements: 1) 2) A-R IN SEF IN 3) 4) INST IN ASC SS AUTO CLOSING NON-AUTO 5) 6) TCC INDEPENDENT TCC PARALLEL Details: Black Lettering on white background EAO (Elektro-Apparatebau Olten AG) Manufacturer s Reference Description 704.030.7 Illuminated Clear Push Button 704.600.7 Extended Ring 704.900.3 Contact Block 2 N/O 704.900.2 Contact Block 1 N/C RS 208-841 130V AC/DC BA9 LED Cluster EE SPEC:136 June 2017-20 of 29 -

PUSH BUTTON SWITCH AND LAMP DATA SHEET APPENDIX C (continued) REFERENCE: PB2 Switch Functions: Button Description: Contact Arrangement: Label Engraving: 1) Auto Reclose Out 2) SEF Out 3) Instantaneous Protection Out 4) ASC Shorting Switch Auto Clear Button / Lens with 110V lamp and guard 2x NO contacts, 1x NC contact 1) 2) A-R SEF OUT OUT 3) 4) INST OUT ASC SS AUTO CLOSING AUTO Black Lettering on white background EAO (Elektro-Apparatebau Olten AG) Details: Manufacturer s Reference Description 704.030.7 Illuminated Clear Push Button 704.600.7 Extended Ring 704.900.3 Contact Block 2 N/O 704.900.2 Contact Block 1 N/C RS 208-841 130V AC/DC BA9 LED Cluster EE SPEC:136 June 2017-21 of 29 -

PUSH BUTTON SWITCH AND LAMP DATA SHEET APPENDIX C (continued) REFERENCE: PB3 Switch Function: Button Description: Switch Contact Arrangement: Label Engraving: 1) Auto Reclose counter reset 2) Auto Reclose lockout reset 3) ASC Scheme Lockout Reset Black button with guard 2x NO contacts 1) 2) A-R COUNTER RESET A-R LOCKOUT RESET 3) ASC SCHEME LOCKOUT RESET Black Lettering on white background EAO (Elektro-Apparatebau Olten AG) Details: Manufacturer s Reference Description 704.010.0 Black Push Button 704.600.7 Extended Ring 704.900.3 Contact Block 2 N/O EE SPEC:136 June 2017-22 of 29 -

PUSH BUTTON SWITCH AND LAMP DATA SHEET APPENDIX C (continued) REFERENCE: PB4 Switch Function: Button Description: Switch Contact Arrangement: 1) ASC shorting switch test close Black button with guard 2x NO contacts, 2x NC contacts Label Engraving: 1) ASC SHORTING SWITCH TEST CLOSE Black Lettering on white background EAO (Elektro-Apparatebau Olten AG) Details: Manufacturer s Reference Description 704.010.0 Black Push Button 704.600.7 Extended Ring 704.900.3 Contact Block 2 N/O 704.900.4 Contact Block 2 N/C EE SPEC:136 June 2017-23 of 29 -

PUSH BUTTON SWITCH AND LAMP DATA SHEET APPENDIX C (continued) REFERENCE: IL1 Indication Lamp Function: Description: 1) SEF Auto Enabled Clear Lens Indicator Label Engraving: 1) SEF AUTO ENABLED Black Lettering on white background EAO (Elektro-Apparatebau Olten AG) Details: Manufacturer s Reference Description 704.002.7 Clear Indicator RS 208-841 130V AC/DC BA9 LED Cluster EE SPEC:136 June 2017-24 of 29 -

PUSH BUTTON SWITCH AND LAMP DATA SHEET APPENDIX C (continued) REFERENCE: IL2 Indication Lamp Function: Description: 1) Circuit breaker closed, or 2) ASC shorting switch closed Red Lens Indicator Label Engraving: 1) CB CLOSED 2) ASC SS CLOSED Black Lettering on white background EAO (Elektro-Apparatebau Olten AG) Details: Manufacturer s Reference Description 704.002.2 Red Indicator RS 208-841 130V AC/DC BA9 LED Cluster EE SPEC:136 June 2017-25 of 29 -

PUSH BUTTON SWITCH AND LAMP DATA SHEET APPENDIX C (continued) REFERENCE: IL3 Function: Description: 1) Circuit breaker open, or 2) ASC shorting switch open Green Lens Indicator Label Engraving: 1) CB OPEN 2) ASC SS OPEN Black Lettering on white background EAO (Elektro-Apparatebau Olten AG) Details: Manufacturer s Reference Description 704.002.5 Green Indicator RS 208-841 130V AC/DC BA9 LED Cluster EE SPEC:136 June 2017-26 of 29 -

PUSH BUTTON SWITCH AND LAMP DATA SHEET APPENDIX C (continued) REFERENCE: IL4 Indication Lamp Function: Description: 1) Circuit Breaker Springs Charged Blue Lens Indicator Label Engraving: 1) SPRINGS CHARGED Black Lettering on white background EAO (Elektro-Apparatebau Olten AG) Details: Manufacturer s Reference Description 704.002.6 Blue Indicator RS 208-841 130V AC/DC BA9 LED Cluster EE SPEC:136 June 2017-27 of 29 -

PUSH BUTTON SWITCH AND LAMP DATA SHEET APPENDIX C (continued) REFERENCE: IL5 Indication Lamp Function: Description: ASC Alarm Amber Lens Indicator Label Engraving: 1) ASC ALARM Black Lettering on white background EAO (Elektro-Apparatebau Olten AG) Details: Manufacturer s Reference Description 704.002.4 Yellow Indicator RS 208-841 130V AC/DC BA9 LED Cluster EE SPEC:136 June 2017-28 of 29 -

SUPERSEDED DOCUMENTATION APPENDIX D EE SPEC 3/4 shall be withdrawn from the WPD Policy Index on 30 November 2017 and from the WPD TechInfo website on 1 August 2017 following issue of this document. ASSOCIATED DOCUMENTATION APPENDIX E EE SPEC:87 EE SPEC:98 IMPACT ON COMPANY POLICY APPENDIX F This document is relevant to all staff involved in the specification, purchase, installation and commissioning of 132kV 66kV, 33kV and 11kV circuit breakers, transformers and associated protection and control systems. KEY WORDS APPENDIX G Circuit Breaker, Panel, Cubicle, Protection, Alarm, Transducer, Telecontrol, Auxiliary Relay. EE SPEC:136 June 2017-29 of 29 -