RITZ / Turbine controls DISPLAY

Similar documents
ADVANCED OPERATOR PANEL (AOP)

MobilControl MC 4000 OWNER S MANUAL

FREQUENCY CONVERTER FC102 (QUICK GUIDE)

PTR4-SP Controller User Manual

MX200 SERIES Modbus Card 50P GE Zenith Controls. Operation and Maintenance Manual 50R-2200B 12/00

RAMSES D GB F NL. Installation and operating instructions Room thermostat. RAMSES 832 top2

SHIMPO INSTRUMENTS. FG-7000T Digital Torque Gauge Operation Manual

vacon nx ac drives brake chopper unit (bcu) application user s manual

Operator Manual for Profibus

Operating instructions for RAMSES 811 top2_812 top2 and RAMSES 831 top2_832 top2

Monitoring technique. VARIMETER Voltage relay MK 9064N, MH 9064

Multi-IQ. Firmware: RS232-Data Manager for UPS 4 x RS232 / 1 x LAN-Contacts flash upgradeable. User manual. (Serial Number / Seriennummer)

Data sheet MK 20 GR. Customized solution or off-the-shelf: The choice is yours!

2001VT Temp & CO 2. - air quality sensor/controller NOTE!!! Manual for Installation. General. SenseAir AB

Model No Universal Input Indicator Start-up Guide

GCI-5K INSTALLATION AND OPERATOR S MANUAL

FREQUENCY CONVERTER FC101 (QUICK GUIDE)

FG-7000L Digital Force Gauge Operation Manual

RS Stock No Instruction Manual RS Input Data Logging Thermometer

Busmodul - LonWorks (R)

Supplementary operating instructions for your air curtain system Controller TMC 500

DeviceNet Drive Profile CFW-09

ACS850 User s Guide ACS850 Control Panel

FANCOIL CONTROLLER UNIT TC17B01KNX. Product Handbook

180 Series Keypad. Handbook. Revision 2.1

Technical Explanation for Power Controllers

LC-110/H. Reference Manual

PROFIBUS Additional Board for SMARTCON Control System

From lab to production, providing a window into the process. Universal Input Indicator Start-up Guide. Operating Manual.

SD1. Differential Controller. Operating and Installation Instructions F2 72.3

WEA-Base. User manual for load cell transmitters. UK WEA-Base User manual for load cell transmitters Version 3.4 UK

M2500 Engine Controller Configuration Manual

Unipower HPL600. Unipower HPL600

Scanner 2000 microefm QuickStart. Installing the Scanner Remote Mount. Direct Mount NUFLO. Part No , Rev. A

HGM9580 Bus Tie Bus Parallel Unit USER MANUAL. Smartgen Technology

I/O module (Expansion module)

sbdconfig.exe Software

TECHNICAL MANUAL WATER 300 C 5300 CV/06-00 GB

Products no longer available

Belimo Gateway MP to Modbus RTU - UK24MOD

ver INDU WRC-2000 Controller User s Manual

System-10 BTU Meter BACnet Network Interface Installation Guide

COUNTIS Ci Notice d utilisation GB Operating instructions Bedienungsanleitung NL Gebruiksaanwijzing

FG-3000R Digital Force Gauge Operation Manual

Status line The top line of the LCD display shows the basic status information of the drive.

ETM MD100 Drive System 1/2HP (370W) User Manual. Table of Contents. Drive Features

IPM650 Intelligent Panel-Mount Display

CDN220 HIGH DENSITY I/O ADAPTER USER GUIDE

FG-3000 Digital Force Gauge Operation Manual

Operating instructions Mechatronic flow sensor SBY2xx SBG2xx SBN2xx SB0524

MXIO. Compact I/O module. Summary. Application Compact I/O module for data acquisition and HVAC control systems. Function

LC 502 controller for DuoFlex centralized lubrication systems

MicroTrans EQ Signal Processor. Operation & Maintenance Manual

Monitoring Technique. VARIMETER PRO Multifunction Measuring Relay MK 9300N, MH 9300

RAS+DL Room sensor with remote display Version 2.03

Press Monitoring and Automation Products M1200 PRO-DIE. Numeric Keys Used for inputing program parameters

B-CONTROL MICRO BKM / Jens Brenneis

Installation & Operation

Integriti User Manual. Elite / EliteX LCD Terminal Keypads

Iso DIN. User Manual. 1 channel Earth Fault Monitoring

TABLE OF CONTENTS INTRODUCTION. 3. Analog Input Analog Output Digital Input Digital Output OPERATIONAL DESCRIPITON.. 7 PROGRAMMING AND INITIAL SETUP.

Application program: description and examples

SATEL I-LINK 100 MB I/O-converter User Guide, Version 1.1

Installation & Operation Guide

L300 user manual. Programmable DC Electronic Load CONTENTS. Electronic Load Software CAUTION...2 SAFETY NOTES...2

Ellard Product Instructions

TTC Series Torque Tool Tester Operation Manual

Controller unit for solar thermal systems. primos 600 SR. Installation and operating instructions

D7000 SERIES MODBUS TCP/IP ETHERNET INTERFACE MODULES

SOLARIMMERSION IV Advanced Installation Manual v1.9

Characteristics and functioning

Metasys N2 Instruction Manual VLT Adjustable Frequency Drive. 12/ Revision B

TR TR 608 top TR 609 top D GB F I E NL. Installation and operating instructions Digital time switch. TR 609 top2

SK TU4-CAO-C Part number:

Table of Contents. Laboratory Balances. Instruction Manual - TORBAL AGC Series

Small distributed I/O module

ACCX Air Conditioning

Touchpad User Guide. National Sales. Product Support. Freecall: Ph:

SK CU4-PBR-C Part number:

USER'S GUIDE BARD-LINK TM LC /LC SOLID STATE DUAL UNIT LEAD/LAG CONTROLLER & TEC-EYE HAND-HELD DIAGNOSTIC TOOL

SK CU4-CAO Part number:

SERIES CMT CARBON MONOXIDE GAS TRANSMITTER

Please enter the identity code of your device here!

The accessories described in this manual are of the highest quality, carefully designed and built in order to ensure excellent performance.

1.1.1 Software Version Introduction About this Manual References 2

Ethernet / RS485 Gateway

REMOTE METER USER MANUAL KAMPPTRC

1. Installation. 2. Configuration - Operation. 3. Specifications. Safety

SORDS ELECTRIC ~ MA7200. Sensorless Vector AC Inverter.

EPM Programmer EEPM1RA

FLÄKTGROUP OFFERS A WIDE RANGE OF PER- MANENT MAGNET MOTORS (PM) AND FREQUENCY CONVERTERS FOR PLUG FANS. POWER RANGE IS FROM 0,8 KW TO 15 KW.

User Manual. KE-Relay or KD-Relay Profibus DPV0 Communication Module. Page 1 / 18. KE-PROFI-DP0 Version (NE_NC-KE-PROFI-DP0_MAN_01_10_FN04)

Sampler Controller Type /-22

XT-9100 Technical Bulletin

Contents for How to Use the Simulator Program

SK TU4-PBR Part number:

Product Information SIMATIC S Digital Output Module SM 322; DO 8 120/230 VAC/2 A ISOL

APC Symmetra RM. Operation Manual

02/11/2015

Device manual Field modules DP AC2630 / AC2631 / AC2634 AC2636 / AC2637 / AC / / 2013

Transcription:

RITZ / Turbine controls DISPLAY CANCEL EXIT OK MENU F1 F2 F3 F4 The control/display unit has a CPU, an LCD display and 8 keys. 2 LEDs also display particular operational conditions (e.g. plant ON, faults, warnings, "code broken" etc.). RITZ / Turbine controls / V 1.21 Page: 1 of 17 Date: 28.05.2013

1) Display: 1.1) Basic display In Line 1, the actual rotations are shown on 0/min 0.0A the left while the actual power is displayed on 0m3/h 0.00kW the right. The line below displays the actual flow AUTO START on the left and the actual power on the right (but T-AUF B-ZU N K only when the relevant analogue value has been configured; see: Pos. 3.4 / menu configuration ). If the signal on an analogue input is lower than 3mA, the corresponding position will flash and an error message will be generated. The 3 rd line shows the plant mode (Auto/Manual, Start/Stop). If remote control is activated, an F * appears at the end of the line. The 4 th line shows the outlets which are currently switched on. In front of the display of both valves ( T = Turbine / B = Bypass) you can see whether a final position has been reached ( _ = ON / ^ = OFF). The 5 th line displays faults and warnings. In Manual mode, the lower edge of the LCD shows the current configuration of the function keys; otherwise the date and time are displayed here. [* F = Fernbedienung = remote control] 1.2) Submenus In different submenus target values can be given, for example, and different operational data can be retrieved. The Main Menu is called up using the MENU key. A code query appears first: CODE: 0000 For parameters which are protected by code, the appropriate code must first be entered, so that the parameter can be changed, otherwise the parameters can only be displayed. Codes are entered using the arrow keys (F1...F4). The code is accepted by pressing the OK key. Codes used: Code_1 = 0013 (general code) Code_2 = xxxx (special Ritz code!) RITZ / Turbine controls / V 1.21 Page: 2 of 17 Date: 28.05.2013

2) Keys / LEDs: I O CANCEL / EXIT OK / MENU F1... F4 Manual mode: activate network protection {No function here} Acknowledge fault / Exit menu / Reject input Call up menu / Select position / Accept input The allocation of each of these keys is shown [Green LED] [Red LED] (On the I key) lights up when in Automatic mode, flashes when in Manual mode; - Flashes when a fault/warning appears; - Lights up when all faults/warnings have been acknowledged, but not yet repaired, or if a code is currently (still) broken (i.e. active); 3) Menu management: Press MENU key => after the request for a code, you reach the main menu. Now you can use the arrow keys (F2/F3) to scroll up or down the menu options: ( = cursor) MAIN MENU: Parameter START Parameter STOP Delay times Configuration Time / date Operating hours Diagnose Error memory Use the OK key to accept the desired menu point. Use the EXIT key to return to the basic display. A broken code remains active for max. 15 minutes, or until another code is entered (input > 0). RITZ / Turbine controls / V 1.21 Page: 3 of 17 Date: 28.05.2013

Submenus, general information: Use the arrow keys (F1...F4) to select the desired position. If the OK key is pressed, the cursor jumps to the right to the corresponding variables. The desired value can now be entered using the arrow keys (F1...F4) and then accepted using the OK key. The CANCEL key rejects the entry. Return to the main menu using the EXIT key. 3.1) Parameter START (Only edit if Code_1 has already been input!) PARAM. START Impulse 1: 5s Impulse (turbine open) up to switching threshold Pause 1: 10s Pause (turbine open) up to switching threshold Impulse 2: 5s Impulse (turbine open) from switching threshold Pause 2: 10s Pause (turbine open) from switching threshold Threshold: SPEED Value for evaluating the switching threshold [Speed / Flow / Power] 3.2) Parameter STOP (Only edit if Code_1 has already been input!) PARAM. STOP Impulse 1: Pause 1: Impulse 2: Pause 2: Threshold: 5s Impulse (turbine closed) up to switching threshold 10s Pause (turbine closed) up to switching threshold 5s Impulse (turbine closed) from switching threshold 10s Pause (turbine closed) from switching threshold SPEED Value for evaluating the switching threshold [Speed/ Flow / Power] 3.3) Delay times (Only edit if Code_1 has already been input!) DELAY TIMES Compensation ON: 5s Delay: compensation ON [0-999] Power supply: 5s Delay: power supply fault [0-999] Freq. monitoring: 5s Delay: frequency monitoring fault [0-999] UPS warning: 5s Delay: UPS warning [0-60] Turbine open: 60s Max time until response Turbine Open [0-999] Turbine closed: 60s Max time for response Turbine Closed [0-999] Turb. torque OPEN: 0s Delay: turbine torque open fault [0-999] Turb. torque CLOSED: 0s Delay: turbine torque closed fault [0-999] Turbine temp: 0s Delay: turbine temp. monitoring fault [0-999] Bypass open: 60s Max. time until response Bypass Open [0-999] Bypass closed: 60s Max. time for response Bypass Closed [0-999] By. torque OPEN: 0s Delay: bypass torque open fault [0-999] By. torque CLOSED:0s Delay: bypass torque closed fault [0-999] Bypass temp.: 0s Delay: bypass temp. monitoring fault [0-999] Forced operation: 0h Interval for forced operation of the valve [0-24] RITZ / Turbine controls / V 1.21 Page: 4 of 17 Date: 28.05.2013

3.4) Configuration (Only edit if Code_2 has already been input!) CONFIGURATION Speed AE1 Configuration of analogue input 1 Flow AE2 Configuration of analogue input 2 Power AE3 Configuration of analogue input 3 Output AE4 Configuration of analogue input 4 Language: GERMAN Dialogue language (German, English) RS485 remote control: NO Remote control via RS485 (e.g. Profibus) 3.4.1) Configuration speed AE1 (Only edit if Code_2 has already been input!) CONFIGURATION SPEED Value 4mA: 0/min Speed at value = 4mA Value 20mA: 6000/min Speed at value = 20mA Start threshold: 0/min Switching threshold for start-up process Stop threshold: 0/min Switching threshold for stopping process Max speed: 0/min Threshold for Max Speed fault Offset: 0/min Offset for the Speed value 3.4.2) Configuration flow AE2 (Only edit if Code_2 has already been input!) CONFIGURATION FLOW Value 4mA: 0m3/h Flow at value = 4mA Value 20mA: 999m3/h Flow at value = 20mA Start threshold: 0m3/h Switching threshold for start-up process Stop threshold: 0m3/h Switching threshold for stopping process Offset: 0.0m3/h Offset for the Flow value 3.4.3) Configuration power AE3 (Only edit if Code_2 has already been input!) CONFIGURATION POWER Value 4mA: 0.0A Power at value = 4mA Value 20mA: 400.0A Power at value = 20mA Start threshold:0.0a Switching threshold for start-up process Stop threshold: 0.0A Switching threshold for stopping process Offset: 0.00A Offset for the Power value RITZ / Turbine controls / V 1.21 Page: 5 of 17 Date: 28.05.2013

3.4.4) Configuration output AE4 (Only edit if Code_2 has already been input!) CONFIGURATION OUTPUT Value 4mA: 0.00kW Output at value = 4mA Value 20mA: 200.00kW Output at value = 20mA Offset: 0.00kW Offset for the output value General info: If the value 0 is entered in the parameter Value 20mA, the corresponding value in the basic display will be hidden! 3.5) Time / date (Only edit if Code_1 has already been input!) TIME / DATE Date: Thurs 02.07.2009 Time: 09:55:10 Date format: 0 [0 = DD.MM.YY, 1 = MM/DD/YY, 2 = YY/MM/DD] (DD: day, MM: month, YY: year) 3.6) Operating hours (Only edit if Code_2 has already been input!) OPERATING HOURS Plant: 0 h Operating hours plant 3.7) Diagnostics DIAGNOSTICS Lamps test Turbine V: 0 Lamps test switch on/off 1.20 Current programme version A-Inp.1: 0.00mA Analogue input 1 (speed) A-Inp.2: 0.00mA Analogue input 2 (flow) A-INP.3: 0.00mA Analogue input 3 (power) A-INP.4: 0.00mA Analogue input 4 (output) D-INP: 0000 0000 Status of digital inputs )_ MK20-GR D-OUT: 0000 0000 Status of digital outputs ) (basic unit) INP-4: 0000 0000 Status of digital inputs )_ MK200-8E/4R OUT-4: 0000 0000 Status of digital outputs ) (address: 4) RITZ / Turbine controls / V 1.21 Page: 6 of 17 Date: 28.05.2013

The Lamps Test function can be used to switch the LEDs on and off and to test the multiple error message relay. The remaining positions are only intended for internal test purposes! 3.8) Error memory ERROR MEMORY POWER FAILURE POWER SUPPLY FREQ.MONITORING 00.00.00 Date of the last power failure (shutdown) 00.00.00 Date of the last Power Supply fault 00.00.00 Date of the last Frequency Monitoring fault TURB. TORQUE OPEN 00.00.00 Date of the last Torque Open fault TURB. TOQRUE CLOSED 00.00.00 Date of the last Torque Closed fault TURBINE TEMPERATURE 00.00.00 Date of the last Temperature fault TURBINE NOT OPEN 00.00.00 Date of the last Not Open fault TURBINE NOT CLOSED 00.00.00 Date of the last Not Closed fault BYPASS TORQUE OPEN 00.00.00 Date of the last Torque Open fault BYPASS TORQUE CLOSED 00.00.00 Date of the last Torque Closed fault BYPASS TEMPERATURE 00.00.00 Date of the last Temperature fault BYPASS NOT OPEN 00.00.00 Date of the last Not Open fault BYPASS NOT CLOSED 00.00.00 Date of the last Not Closed fault E/A-MODULE ADR.4 00.00.00 Date of the last MK200-Module fault SPEED SENSOR FLOW SENSOR POWER SENSOR OUTPUT SENSOR MAX SPEED UPS WARNING 00.00.00 Date of the last Speed Sensor fault 00.00.00 Date of the last Flow Sensor fault 00.00.00 Date of the last Power Sensor fault 00.00.00 Date of the last Output Sensor fault 00.00.00 Date of the last Max Speed fault 00.00.00 Date of the last UPS Warning message RITZ / Turbine controls / V 1.21 Page: 7 of 17 Date: 28.05.2013

4) Faults Undervoltage! Undervoltage means that the mains voltage has dropped below approx. 180Vac. This threshold depends on the transformer used! When the undervoltage fault appears, the control s supply voltage must be switched on and off once briefly, so that this fault is acknowledged. All other faults can be acknowledged with the CANCEL key. EEPROM faulty! E/A-Module 04 fault Power supply fault Frequency fault The EEPROM for saving the default settings and the adjustment parameters for the analogue inputs is defective! (Send the controls to be repaired) The extension module MK200-8E/4RA with the Address 4 is not responding! (Check connection cable or module!) The signal on digital input 4 (HR200) has dropped for longer than the preset delay time! The signal on digital input 5 (HR200) has dropped for longer than the preset delay time, when the output Network Protection (HR200) is active! Turb. not OPEN fault The signal Turbine Open on digital input 6 (HR200) has still not appeared after the max time allowed when opening the turbine valves. Turb. not closed fault The signal Turbine Closed on digital input 7 (HR200) has still not appeared after the max time allowed when closing the turbine valves. Turb. torque OPEN fault The signal Turbine Torque Open on digital input 1 (MK200-8E4RA) has dropped for longer than the preset delay time when the turbine valves are opened! Turb. torque CLOSED fault The signal Turbine Torque Closed on digital input 2 (MK200-8E4RA) has dropped for longer than the preset delay time when the turbine valves are closed! Turb. temp. fault The signal Turbine Temperature on digital input 3 (MK200-8E4RA) has dropped for longer than the preset delay time! Bypass not OPEN fault The signal Bypass Open on digital input 4 (MK200-8E4RA) has still not appeared after the max time allowed when opening the bypass valves. RITZ / Turbine controls / V 1.21 Page: 8 of 17 Date: 28.05.2013

By. not CLOSED fault The signal Bypass Closed on digital input 5 (MK200-8E4RA) has still not appeared after the max time allowed when closing the bypass valves. By. torque OPEN fault By. torque CLOSED The signal Bypass Torque Open on digital input 6 (MK200-8E4RA) has dropped for longer than the preset delay time when opening the bypass valves! The signal Bypass Torque Closed on digital input 7 (MK200-8E4RA) has dropped longer than the preset delay time when closing the bypass valves! By. temp. fault The signal Turbine Temperature on digital input 8 (MK200-8E4RA) has dropped for longer than the preset delay time! Speed sensor fault Flow sensor fault Power sensor fault Output sensor fault Max speed fault The signal on analogue input 1 (HR200 / 4-20mA) is outside the permitted range. (Check speed sensor or cabling) The signal on analogue input 2 (HR200 / 4-20mA) is outside the permitted range. (Check flow sensor or cabling) The signal on analogue input 3 (HR200 / 4-20mA) is outside the permitted range. (Check power sensor or cabling) The signal on analogue input 4 (HR200 / 4-20mA) is outside the permitted range. (Check output sensor or cabling) The speed has exceeded the programmed Max Speed threshold (see Pos. 3.4.1) and a threshold of 0 has been programmed. For the sensor faults, only the analogue inputs whose values have been configured (see: Pos. 3.4.x / Value 20mA ) are monitored. Warning: UPS The signal on digital input 8 (HR200) has dropped for longer than the preset delay time! This warning message will not lead to a shutdown! RITZ / Turbine controls / V 1.21 Page: 9 of 17 Date: 28.05.2013

5) Programme sequence 5.1) MANUAL mode (HR200, input 1 = 1) In this mode the function keys (HR200, F1, F4) can be used manually to open or close the valves and the bypass valves. Using the I key (HR200) the Network Protection output can be keyed in (i.e. the output is on, as long as the I key is pressed). The compensation output is not controlled here. 5.2) AUTOMATIC mode (HR200, input 2 = 1) If the external release signal is applied (HR200, input 3 = 1), the start-up process will then be activated. If the external release signal drops again, or if a fault appears, the stopping process will be activated. 5.2.1) Start-up process (see: Pos. 3.1 / Parameter Start) There should be no faults pending! First the output open turbine valves (MK200-8E4RA, output 1) will be controlled via an impulse/pause control with the Impulse 1 / Pause 1 values. If the selected value exceeds the preset threshold (see: Pos. 3.4.x / Start Threshold ), the network protection output (HR200, output 1) will be switched on and the delay time for the compensation will be started (see: Pos. 3.3 / Compensation ON ). If the value 0 is programmed as the Start Threshold value, the start-up process will begin immediately with the values for Impulse 2 / Pause 2. Now the Open Turbine Valves output will be controlled by an impulse/pause control with the Impulse 2 / Pause 2 values. After the expiry of the delay time for the compensation the Compensation output (HR200, output 2) is switched on. As soon as the Open Turbine Valves signal appears (HR200, input 6 = 1), the Open Turbine Valves output is no longer controlled. 5.2.2) Stopping process (see: Pos. 3.2 / Parameter Stop) First the output Compensation is switched off, and the output Close Turbine Valves (MK200-8E4RA, output 2) is controlled via an impulse/pause control with the values Impulse 1 / Pause 1. RITZ / Turbine controls / V 1.21 Page: 10 of 17 Date: 28.05.2013

If the selected value falls below the preset threshold (see: Pos. 3.4.x / Threshold Stop ), the Network Protection output (HR200, output 1) is switched off. If the value 0 is programmed as the Threshold Stop, the stopping process will be immediately begun with the values Impulse 2 / Pause 2. The output Close Turbine Valves will now be controlled via an impulse/pause control with the values Impulse 2 / Pause 2. As soon as the signal Turbine Valves Closed appears (HR200, input 7 = 1), the output Close Turbine Valves is no longer controlled.. 5.2.3) Bypass For Fault and External Release = 1 the output Open Bypass Valves (MK200-8E4RA, output 3) is controlled, otherwise the output Close Bypass Valves (MK200-8E4RA, output 4) is controlled. 5.2.4) Forced operation of the valves (Turbine and Bypass) If the plant is in Automatic Stop mode, and the valves (Turbine and Bypass) are not controlled for at least the Forced Operation time (see Pos. 3.3), the valves will open once completely and then close again completely. If the parameter Forced Operation is programmed to 0, the forced operation is deactivated. 5.3) OFF mode (HR200, input 1+2 = 0) If neither Manual nor AUTOMATIC mode is selected, the plant will be in OFF mode. If during operation the plant switches from AUTOMATIC mode to OFF mode, the Stopping Process is initiated (see: Pos. 5.2.2). 5.4) Remote control via RS485 mode (e.g. Profibus connection) The mode Remote Control via RS485 is only possible if the plant is switched via the digital inputs of the control to Automatic Periphery (HR200, Input 2 = 1). If the mode Remote Control via RS85 is activated (see: Pos. 3.4), and the mode Automatic is selected via the remote control (1.Byte, Bit 0 = 1), then the plant Start or Stop will no longer be done via the External Release input (HR200, input 3), but by the remote control (1.Byte, Bit 2). RITZ / Turbine controls / V 1.21 Page: 11 of 17 Date: 28.05.2013

If the Remote Control via RS85 is activated, and the Manual Mode is selected by remote control (1.Byte, Bit 1 = 1), then the individual valves can be opened/closed via the interface, and the network protection can be switched on/off (for configuration of the individual signals see document AListe_Turbine_v121.pdf ). If the Remote Control RS485 mode is activated, and neither Automatic nor Manual mode is selected via remote control (1.Byte, Bit 0 = 0 and Bit 1 = 0), the digital input External Release (HR200, Input 3) can be used to either stop or start the plant again. If the Remote Control via RS85 mode is activated, and if the Automatic and Manual modes are selected by remote control (1.Byte, Bit 0 = 1 and Bit 1 = 1), the plant will switch to OFF mode! In the event of a communication failure (Timeout) the symbol F will flash in the extreme right of the 3 rd line of the basic display. In this case the plant will be switched back to Periphery Operation (HR200). RITZ / Turbine controls / V 1.21 Page: 12 of 17 Date: 28.05.2013

6) Connections / terminals => Basic unit (MK20-GR / HR200) Term. 1 0V ac Term. 2 18V ac Power supply Term. 3 Protective earth (PE) connection Term. 4 RS485 (+) Term. 5 RS485 (-) Interface Term. 6 RS485 earth Term. 7 Sensor voltage for analogue input 1 Term. 8 Analogue input 1 (4-20mA), Speed Term. 9 Sensor voltage for analogue input 2 Term. 10 Analogue input 2 (4-20mA) Flow Term. 11 Sensor voltage for analogue input 3 Term. 12 Analogue input 3 (4-20mA) Power Term. 13 Sensor voltage for analogue input 4 Term. 14 Analogue input 4 (4-20mA) Output Term. 15 Sensor voltage 24Vdc Term. 16 Dig. input 1 Manual Term. 17 Sensor voltage 24Vdc Term. 18 Dig. input 2 Automatic Term. 19 Sensor voltage 24Vdc Term. 20 Dig. input 3 External release (1=Start) Term. 21 Sensor voltage 24Vdc Term. 22 Dig. input 4 Loss of voltage (1=ok) Term. 23 Sensor voltage 24Vdc Term. 24 Dig. input 5 Frequency monitoring (1=ok) Term. 25 Sensor voltage 24Vdc Term. 26 Dig. input 6 Turbine valves open Term. 27 Sensor voltage 12Vdc Term. 28 Dig. input 7 Turbine valves closed Term. 29 Sensor voltage 12Vdc Term. 30 Dig. input 8 UPS warning (1=ok) Term. 31 Relay output 1 COM Network protection Term. 32 Relay output 1 NO Term. 33 Relay output 2 COM Compensation Term. 34 Relay output 2 NO Term. 35 Relay output 3 COM (Reserve) Term. 36 Relay output 3 NO Term. 37 Relay output 4 COM Ready for operation Term. 38 Relay output 4 NO Term. 39 Relay output 5 COM RESET Term. 40 Relay output 5 NO Term. 41 Relay output 6 COM Term. 42 Relay output 6 NC Collective faults (1=ok) Term. 43 Relay output 6 NO RITZ / Turbine controls / V 1.21 Page: 13 of 17 Date: 28.05.2013

Interface for MK200 module: Term. 44 RS485 (-) Term. 45 RS485 (+) Term. 46 GNDX Term. 47 0V ac Term. 48 18V ac [RS485 interface without terminating resistor RS485 interface with terminating resistor] CAUTION: For cable lengths of more than 30m (digital signals) coupling relays must be used! Shielded cables must be used for the analogue signals! RITZ / Turbine controls / V 1.21 Page: 14 of 17 Date: 28.05.2013

7) Connections / terminals => Module MK200-8E/4Rout (Address: 4) Term. 1 Dig. input 1, turbine valves torque open (1=ok) Term. 2 Dig. input 2, turbine valves torque closed (1=ok) Term. 3 Dig. input 3, turbine valves temperature monitoring (1=ok) Term. 4 Dig. input 4, bypass valves open (1=open) Term. 5 Dig. input 5, bypass valves closed (1=closed) Term. 6 Dig. input 6, bypass valves torque open (1=ok) Term. 7 Dig. input 7, bypass valves torque closed (1=ok) Term. 8 Dig. input 8, bypass valves temperature monitoring (1=ok) Term. 9 +24Vdc (supply voltage for inputs) Term. 12 \_ Relay output 1, open turbine valves Term. 13 / Term. 14 \_ Relay output 1, close turbine valves Term. 16 / Term. 18 \_ Relay output 1, open bypass valves Term. 19 / Term. 20 \_ Relay output 1, close bypass valves Term. 22 / CAUTION: Coupling relays must be used for cables longer than 30m! RITZ / Turbine controls / V 1.21 Page: 15 of 17 Date: 28.05.2013

8) Setting the module address for the MK200 modules The MK200 module addresses are set using the DIP switches, which can be accessed from the right-hand side of the module. The opening is closed with a cover, which must be removed first. DIP switch for setting addresses (address 1 shown here) The module addresses are set with the first 5 DIP switches. Address DIP switches 1 2 3 4 5 1 1 0 0 0 0 2 0 1 0 0 0 3 1 1 0 0 0 4 0 0 1 0 0 5 1 0 1 0 0 6 0 1 1 0 0 7 1 1 1 0 0 0 = OFF (down) 1 = ON (up) The DIP switches 6-8 are reserved and must always be OFF, i.e. in the down position. The DIP switches 9 and 10 switch the interface s terminating resistors. These are normally deactivated (OFF = down). RITZ / Turbine controls / V 1.21 Page: 16 of 17 Date: 28.05.2013

9) Uploading a new programme to the controls The controls must first be switched to programme mode: a) Switch off the control s power supply; b) Press the 0 and F1 keys together to switch the power supply on again. => FLASH load now appears on the display c) The relevant programme (HEX file) can now be transferred to the controls using the PC software ( RSI Flash Programming ). => Launch PC programme => [Open]... Select programme file; => [Burn]... Change interface if needed // Baud rate always 19200! => [OK]...Launch programming; d) If the PC programme reports Transfer successful, the power supply must be quickly switched on and off again. => The basic display should now be shown again. RITZ / Turbine controls / V 1.21 Page: 17 of 17 Date: 28.05.2013