MICROTRAX CODED TRACK CIRCUIT SYSTEM SERVICE MANUAL 6470A APPLICATION LOGIC PROGRAMMING

Size: px
Start display at page:

Download "MICROTRAX CODED TRACK CIRCUIT SYSTEM SERVICE MANUAL 6470A APPLICATION LOGIC PROGRAMMING"

Transcription

1 UNION SWITCH & SIGNAL 645 Russell Street Batesburg, SC SERVICE MANUAL 6470A MICROTRAX CODED TRACK CIRCUIT SYSTEM CODED TRACK CIRCUIT/ END-OF-SIDING CONTROLLER CODED TRACK CIRCUIT/ CAB SIGNAL CONTROLLER APPLICATION LOGIC PROGRAMMING April 1996 COPYRIGHT 1996, UNION SWITCH & SIGNAL INC. PRINTED IN USA An ANSALDO Affiliated Company

2

3 TABLE OF CONTENTS I. GENERAL INFORMATION PURPOSE INTRODUCTION Track Communications Local Inputs and Outputs Serial Communications Internal/Programming-Related Functions General Site-Specific Programming System-Level Programming Hardware Configuration SPECIFICATIONS (PROGRAMMING-RELATED) Track Communications Serial Communications Local I/O II FUNCTIONAL DESCRIPTION BASIC OPERATING PRINCIPLES Vital Design Diagnostics Stable System Function ERRORS AND EVENT LOGGING Critical Errors Static and Dynamic Warnings Track Shunting Events User-Defined Events VITAL LOCAL COMMUNICATIONS Acquiring Inputs Vitality of Inputs Redundant Reading Input Instability Check Verification of Less Restrictive Bit Bit Latching Stuck Bit Check Shorted Input Check SM 6470A 4/96 i

4 TABLE OF CONTENTS Delivering Outputs Vitality of Outputs Stability Interval Reading Monitors Stuck Output ("Flip") Check Lamp Filament Tests Conditional Power Supply Basic Function VITAL SERIAL COMMUNICATIONS General Communications Modes OPERATING MODES Basic Prior State Routine CPS Powered Down Recovery System Loading Track Communications General Message Validity Application Logic - Track Interface Information Track Code Types Transmission Code Selection Receive Code Acceptance Shunting and Code Reception System Bit Operations III SYSTEM-LEVEL PROGRAMMING PROCEDURES INTRODUCTION PROGRAMMING LANGUAGE - GENERAL DESCRIPTION Main Program Sections and Statements Introductory Sample Program Basic Format Comments General Compiler Switches ii SM 6470A 4/96

5 TABLE OF CONTENTS Tokens Reserved Words Delimiters User-Defined Bits Bit Uses and Types Status in an Assign Statement Timer Bits Pre-Defined Bits Configuration Bits PROGRAMMING LANGUAGE - DETAILED DESCRIPTION Introduction Program Statement Interface Section Track Interface Section Local I/O Interface Section Slave Interface Section Non-Vital /IO /Local Control Panel Configuration Section Internal Bit Definitions Timer Section Begin Statement Logic Specification General Expression End Statement SUMMARY OF PROGRAMMING GUIDELINES DETAILED PROGRAM EXAMPLE PROGRAMMER GUIDELINES - PROGRAM EXECUTION General Timer List Trigger List General Breaks-Before-Makes Rule Sample Execution - Timer and Trigger Lists Cyclic Logic SM 6470A 2/96 iii

6 TABLE OF CONTENTS IV DEVELOPMENT SYSTEM INTRODUCTION M.T.D.S. AVAILABLE FILES ENVIRONMENT TABLE M.T.D.S. - COMPILER General Symbol Table Listing Comments Symbol and Page Generator Compiler Switch M.T.D.S. - SIMULATOR General Access to Simulator Standard Formats Simulator Operation General Sample Program Help Screen Display I/O Command Display Triggers Command Display Relays Command Display Timers Command Display Configuration Value Command Remove Command No Display Command Color/Monochrome Commands Run Command Execute Command Increment Command Trace Command Relay Set and Clear Commands Input Command Print Command Read Command Pause and Continue Commands Reset Command iv SM 6470A 4/96

7 TABLE OF CONTENTS Reconfiguration Command Quit Command Simulator Diagnostics EPROM FILE FORMAT & PROGRAMMING V SUPPLEMENTAL DATA COMPILER ERROR MESSAGES Token Errors Syntax Errors Semantic Errors SUMMARY OF HARDWARE ADJUSTMENTS CPU Module Circuit Board CPU Module Front Control Panel Color Light and Searchlight Lamp Driver Modules - Front Control Panel APPENDIX A PARTS LIST (DEVELOPMENT SYSTEM COMPONENTS) APPENDIX B EOS SERIAL LINK BOARD AND CABLE DIAGRAMS B.1 Introduction... B-1 B.2 Development System for EOS Serial Link Board... B-1 B.3 Switch Settings and Displays on the EOS Serial Link Board... B-2 B.4 Important Notes... B-7 B.4.1 Additional Error Codes... B-7 B.4.2 Differences between MICROLOK and the EOS Serial Link Board... B-7 APPENDIX C EOS M.T.D.S. - EPROM PROGRAMMER C.1 General...C-1 C.2 Initial Set-up...C-1 C.3 Programmer Operation...C-2 SM 6470A 2/96 v

8 TABLE OF CONTENTS APPENDIX D USING THE CHIPLAB TO PROGRAM MICROTRAX APPLICATION PROMS D.1 Background...D-1 D.2 Programming an Application...D-1 D.3 Selecting the Type of PROM...D-2 D.4 Performing A Blank Check of the Device...D-2 D.5 Selecting the File and Programming the PROM...D-2 D.6 Obtaining the Checksum of the PROM...D-4 D.7 Exiting the Driver...D-5 APPENDIX E MICROTRAX SLEEP MODE DESCRIPTION E.1 Introduction... E-1 E.2 Detailed Description... E-1 E.3 Application Notes... E-2 ILLUSTRATIONS Figure 1-1 General System Application Figure 1-2 General Configuration of Equipment Figure 3-1 Introductory Program Example Figure 3-2 ASSIGN Operators, Sample Execution Figure 3-3 Advanced Program Example Figure 3-4 Route Aspect Table (Per Figure 3-3) Figure 3-5 Color Light Wiring - Board 1 (Per Figure 3-3) Figure 3-6 Color Light Wiring - Board 2 (Per Figure 3-3) Figure 3-7 Isolated I/O Wiring - Board 3 (Per Figure 3-3) Figure 3-8 Searchlight Wiring - Board 1 (Per Figure 3-3) Figure 3-9 Searchlight Wiring - Board 2 (per Figure 3-3) Figure 4-1 MICROTRAX Development System Basic Diagram vi SM 6470A 4/96

9 Section I GENERAL INFORMATION 1.1 PURPOSE This manual provides instructions for system-level application logic programming of the MICROTRAX Coded Track Circuit System. Refer to SM-6470B for the following information: 1. Hardware installation, adjustment, application and maintenance 2. Signal lamp voltage and track circuit shunting sensitivity adjustment 3. Site-specific configuration set-up and monitoring (using portable PC) 4. The various types of MICROTRAX hardware configurations. 1.2 INTRODUCTION (see Figure 1-1) Track Communications The MICROTRAX Coded Track Circuit is a solid-state, microprocessor-based track and line circuit system designed to work in non-electrified territory. It combines the functions of train detection and line wire circuitry, with all communications carried through the rails. Vital integrity is maintained through detection of broken rails and failed insulated rail joints. A single MICROTRAX unit can be used to control two ends of track circuits at an intermediate or end (control) point location. The track code signal format is AC. This signal is connected to the rails through a Track Interface Panel consisting of a transformer and a heavy current inductor. Impedance is 10 ohms at 150 Hz and rises with increasing frequency. This makes the MICROTRAX system compatible with highway crossing motion and predictor equipment without requiring external blocking units. Additionally, the track is terminated at a very low impedance to the frequency components of the coded messages. This enables compatible operation with wide-band terminating shunts and track circuits that range up to 22,000 ft. in length (@ 3 ohms ballast/1000 ft.). An optional Quick Shunt Module reduces the system's 6-12 second shunt response time to less than 0.10 seconds (comparable to relay-based track circuits). Track circuit user adjustments available with the MICROTRAX system include: 1. Enable/disable of each adjacent track circuit 2. Length definition: 0 to 36,000 ft. in 1000 ft. increments 3. Track length adjustment and disabling using on-site PC or unit front panel switches user-defined standard codes with 12 second acceptance time 5. 2 user-defined fast codes with 6 second acceptance time (typically used for tumble-down and sleep) 6. Forced shunt using shunt/link-up code. 6470A 4/96 1-1

10 Section I GENERAL INFORMATION Figure 1-1. General System Application 1-2 SM 6470A 4/96

11 Section I GENERAL INFORMATION Local Inputs and Outputs The MICROTRAX system provides direct drive of color or searchlight signals. Signal lamp outputs are regulated and can be adjusted for the desired lamp voltage (refer to SM-6470B). Hot and cold filament checks and searchlight mechanism checks are provided. Orderly signal downgrades in advance can be provided (selected in the application logic) and communication through the track is uninterrupted. The application program can be written such that a lamp-out condition that does not affect the intended aspect can be reported to the control point for maintainer attention. The user can program a signal downgrade if a failed lamp prevents display of an intended aspect. The MICROTRAX system also provides logic inputs and outputs that are isolated from battery. Isolation is required for I/O running outside the MICROTRAX equipment case/house in accordance with double-break circuit design. Isolated outputs can be used to operate a 250-ohm load such as a switch lock coil, but can be used to operate any 12 volt relay. Typical uses of isolated inputs include: 1. NWP inputs from a remote location. 2. Set signal to red in response to high water or reversed switch input. 3. Fast train shunt detection (in conjunction with Quick Shunt Module) The MICROTRAX system also provides logic inputs and outputs that do not require isolation from battery. These are used for I/O within the MICROTRAX equipment house/case. Non-Isolated I/O are typically used in an interface to a relay-based interlocking control system. At any location where a MICROTRAX unit is driving a vital external output, the unit is equipped with a vital cut-off relay (VCOR), which controls power to these outputs. (The VCOR is internal to the MICROTRAX Coded Track and Cab Signal units, and external to the EOS unit.) This relay is energized so long as CPU internal diagnostics are passed. Any vital failure causes the relay to drop, thus removing power from all outputs. An optional circuit (EOS unit only) can be set up to light a red signal lamp through the back contact of the VCOR when a vital shutdown occurs Serial Communications The MICROTRAX system can be connected to the US&S MICROLOK Vital Interlocking Control system, MICROLOK PLUS Vital + Non-Vital Control Package or EOS Serial Link Module through a dedicated serial communications link. Dual serial ports on the MICROTRAX unit permit daisy-chain connection of up to 16 units under the control of the vital link master. The serial communications port wiring can also be used for signal cross-lighting on double-track rightof-way. (Two hand-shake signals are used to pass one bit of information back and forth; actual serial communications is not used.) This eliminates the need for complex cross-lighting set-ups Internal/Programming-Related Functions General The MICROTRAX system is controlled by a single microprocessor and standard Executive software. The system CPU constantly performs internal and external diagnostics and generates a conditional output signal so long as diagnostics are successful. Failure of any vital diagnostic results in removal of the conditional signal which, in turn, results in removal of power to all outputs. The MICROTRAX unit provides various normal and fault event displays such as power status, lamp and misc. I/O on/off, serial communications status and CPU diagnostics. Additional displays assist the user with on-site programming and hardware adjustments. 6470A 4/96 1-3

12 Section I GENERAL INFORMATION Site-Specific Programming Site-specific programming (e.g. unit ID, number of signal heads) is contained in an EEPROM mounted in the cardfile (inside of motherboard), not the CPU module. This arrangement allows CPU modules to be interchanged between MICROTRAX cardfiles, without having to transfer EPROMs between CPU boards. Site-specific programming is accomplished through a separate RS-232 serial port on the CPU module, using a portable computer. This same port is also available for system debugging and maintenance. The computer runs a special software package that provides the following functions: 1. Read/set of system clock 2. Display unit configuration 3. Reconfiguration of unit 4. Display memory addresses 5. Monitor application logic and application bits 6. Display logged errors and events 7. Capture data into disk files System-Level Programming System-level application functions such as unit type (e.g. end point or intermediate) are contained in an EPROM on the CPU module. The MICROTRAX Development System (M.T.D.S.) allows the user to design and program system-level logic in familiar relay-logic terms. Development system components include compiler software, EPROM "burn-in" software and program simulation. The MICROTRAX unit is capable of operating with various I/O configurations using the same application program. The flexibility of the application program enables one program to be used in different locations with varying I/O. Two different types of configuration items are available: predefined and user defined. User defined items are used solely by the application program. Pre-defined items control unit operations. These include: 1. I/O board configurations 2. Track A/B enable/disable 3. Track circuit length 4. Lamp head 2 enable/disable 5. Vital slave link parameters Resulting capabilities include: 1. Writing an application logic program that does not permit any field re-configurations. 2. Writing an application logic program that permits various I/O configurations using the same application logic program. 3. Defining defaults so that units do not require reconfiguration unless changes are required. 4. User-defined configurations under the complete control of the application. 1-4 SM 6470A 4/96

13 Section I GENERAL INFORMATION Hardware Configuration Each MICROTRAX system consists of an electronics cardfile, one or two Track Interface Panels and an optional Quick Shunt Module. The system cardfile houses various combinations of plug-in printed circuit modules, each with its own front edge control/display panel. A US&S PN-150HD relay is used for those applications with vital outputs (e.g. to signal lamps). This relay is controlled by the system logic and controls power to all vital local outputs. (The relay does not affect the operation of track communications or the vital serial link.) The Track Interface Panel carries all track code communications between the rails and the cardfile and serves as a filter for unwanted track signals and voltage transients. The optional Quick Shunt Module is provided for heavy traffic applications where the fastest possible train shunt response is needed. It reduces the detection time (of the MICROTRAX cardfile system only) from approximately 6-12 seconds to approximately 100 milliseconds. MICROTRAX system component options are listed in Service Manual 6470B. Table 1-1 and Figure 1-2 show the baseline coded track unit. See SM6470B for the hardware configuration of the coded track circuit/ end-of-siding controller and the coded track circuit/ cab signal controller. Note that the cardfile I/O boards also have a number reference in addition to the letter reference. This is in accordance with descriptors in the application logic program. Table 1-1. MICROTRAX System Equipment Ref. Component Options Application Options A Vital Power/Failover Relay Applications with vital outputs B System Power Supply Module All applications C (1*) Color Light Driver Module Side A or B color light signals 2 battery-isolated inputs Searchlight Driver Module Non-Isolated I/O Module Side A or B searchlight signals 2 battery-isolated inputs 4 non-isolated (from battery) inputs 4 non-isolated (from battery) inputs D (2*) Same as item C above Same as item C above E (3*) Isolated I/O Module 4 battery-isolated inputs 2 battery-isolated outputs F Track Interface Module All applications G Sleep Mode Module Remote, low-traffic areas (power conservation) H CPU Module All applications I Track Interface Panel Intermediate, repeater locations: 2 End (control point) locations: 1 J Quick Shunt Module Heavy traffic areas *"Board" location number in application logic program. 6470A 4/96 1-5

14 Section I GENERAL INFORMATION QUICK SHUNT MODULE TRACK INTERFACE PANEL J I Figure 1-2. General Configuration of Equipment 1-6 SM 6470A 4/96

15 Section I GENERAL INFORMATION 1.3 SPECIFICATIONS (PROGRAMMING-RELATED) Coded Track Communications Track Circuit Length: Using Single-Track Panel: Up to 22,000 ft. (@ 3 ohms/1000 ft. ballast) Using Dual-Track Panel: Up to 18,000 ft. (@ 3 ohms/1000 ft. ballast) T.C. Length (by rail type, rail weight and ballast): Single-Track Panel Welded Rail* ohms 100# 21K ft. 25K ft. 29K ft. 118# 22K ft 26K ft. 30K ft. 136# 22K ft. 27K ft. 31K ft. 145# 23K ft. 27K ft. 32K ft. Bonded Rail* ohms 100# 18K ft. 22K ft. 25K ft. 118# l9k ft. 23K ft. 26K ft. 136# l9k ft. 23K ft. 27K ft. 145# 20K ft. 25K ft. 27K ft. *Assumes 100 ft. or shorter #6 AWG (0.78 ohm) track leads at both ends. Longer leads: Reduce max. distance by 1K ft. for each additional 100 ft. leads. Dual-Track Panel: Refer to section Track Codes: Code Format: Message Characteristics: Standard Shunt Response: Quick-Shunt Option: 22 (max.) available for user application 1 fixed codes for internal functions Bipolar 167 or 333 ms pulses Amplitude: 2 VP-P Message length: 2.0 sec. Complete transmit/receive cycle: 6 sec. Detect: 6 to 12 sec. Clear: 12 to 18 sec. (application logic dependent) Detect: 100 msec. (approx.) 6470A 4/96 1-7

16 Section I GENERAL INFORMATION ALL SYSTEMS Track Interface Inductance: - Track Panel N : 10 mh - Track Panel N : 15 mh - Track Panel N : 20 mh - Track Panel N : 40 mh Serial Communications Cardfile Serial Data Ports: Coded Track and Cab Signal: A vital Slave port for MICROTRAX consisting of two 25-pin D connectors for daisy-chaining of units End-of-Siding: - A vital Slave port for MICROTRAX consisting of two 25- pin D connectors for daisy-chaining of units - 1 vital Master port for MICROTRAX- MICROTRAX link - 1 vital Slave port for MICROLOK- MICROTRAX link - 1 non-vital Slave port for GENYSIS- MICROTRAX link Communications Modes: Baud Rates: All links: EIA RS-423 (RS-232C compatible) Vital links: 150, 300, 600, 1200, 1800, 2400 BPS (default: 1200 BPS) MICROTRAX Vital Serial Up to 32 serial input bits I/0 Bits: Up to 32 serial output bits Non-vital links: 150, 300, 600, 1200, 1800, 2400, 4800, 9600 BPS CPU Module 9-Pin Port: EIA RS-232: 1200 and 4800 BPS IBM PC compatible (DOS) Local Signal and Relay I/O Color Light/Searchlight Part nos: N /N or Signal Module N Inputs: Outputs: 2 isolated inputs per module 2 signal heads per module Coded track cardfile: 0, 1 or 2 modules End-of-siding cardfile: 0, 1 or 2 modules 1-8 SM 6470A 4/96

17 Section I GENERAL INFORMATION Single-cab cardfile: 0, 1 or 2 modules Dual-cab cardfile: 0 modules Non-Isolated I/O Module: Part no.: N Inputs: Outputs: 4 non-isolated inputs per module 4 non-isolated outputs per module Coded track cardfile: 0, 1 or 2 modules End-of-siding cardfile: 0 modules Single-cab cardfile: 0 modules Dual-cab cardfile: 0 modules Non-Isolated I/O Module: Inputs: Outputs: Part no.: N X 4 non-isolated inputs per module 4 non-isolated outputs per module Coded track cardfile: 0, 1 or 2 modules End-of-siding cardfile: 0, 1, 2 or 3 modules Single-cab cardfile: 0, 1 or 2 modules Dual-cab cardfile: 0 or 1 module Isolated I/O Module: Part no.: N Inputs: Outputs: 4 isolated inputs per module 2 isolated outputs per module Coded track cardfile: 1 module End-of-siding cardfile: 0 modules Single-cab cardfile: 0 modules Dual-cab cardfile: 0 modules Coder Output Module: Part no.: N Outputs: 2 non-isolated outputs per module (1 output normally used for direction) Coded track cardfile: 0 modules End-of-siding cardfile: 0 modules 6470A 4/96 1-9

18 Section I GENERAL INFORMATION Single-cab cardfile: 0 or 1 module Dual-cab cardfile: 0, 1 or 2 modules Local Control Panel: Part no.: N Non-Vital Inputs: Non-Vital Outputs: 5 inputs per panel 2 outputs per panel Coded track cardfile: 0 panels End-of-siding cardfile: 1 panel Single-cab cardfile: 0 panels Dual-cab cardfile: 0 panels OS Track PCB : Part no.: N Outputs: 2 outputs per PCB (designed to be a MICROTRAX input only) Coded track cardfile: 0 PCBs End-of-siding cardfile: 1 PCB Single-cab cardfile: 0 PCBs Dual-cab cardfile: 0 PCBs 1-10 SM 6470A 4/96

19 Section II FUNCTIONAL DESCRIPTION 2.1 BASIC OPERATING PRINCIPLES Vital Design NOTE This section discusses aspects of MICROTRAX system operation related to system safety. The MICROTRAX system is designed to operate according to the same basic vitality principles as an equivalent relay-based system, specifically: Less Restrictive/More Restrictive State - When an input or output is recognized as a 0, this is the most restrictive state. When the input or output is recognized as a 1, this is the less restrictive state. Failures to Zero - An output or input cannot fail to the less restrictive state. Certain failures can cause an input to be falsely recognized as a 0. This type of failure is permitted because a zero implies the most restrictive state. The MICROTRAX software is also designed to assure safe operation of the system, specifically: Application Logic - The MICROTRAX unit is strictly a logic interpreter that executes and verifies the user's application logic. The application logic must be designed to prevent any unsafe actions. Operational testing of the application logic program is possible with the MICROTRAX Development System simulator (refer to section 4.4). The simulator verifies that the application program accurately represents the logic to be performed. The MICROTRAX Executive software is designed to verify that the application logic is executed correctly. The Executive is not capable of detecting and responding to an unsafe configuration in the application logic. If an unsafe configuration exists, the Executive will still carry out the programming Diagnostics The MICROTRAX system uses software-driven internal diagnostics designed to insure the safest possible operation. Two types of diagnostics are used: background and intrinsic: Background diagnostics perform a unique function separate from the functional code and are not required for basic system operation. Examples include EPROM check sums and CRC tests, timer comparisons and routine trace checks. Intrinsic diagnostic are an integral part of the functional code. For example, certain sections of the code process two sets of data to verify data integrity Stable System Function The MICROTRAX system is event driven. It does not serially read inputs, then perform logic and then deliver outputs. Instead, it reads inputs on a scheduled basis and, if input changes occur that alter logic, the affected portion of the application logic is scheduled. Once the logic has run, outputs are scheduled for delivery. Only outputs from a "stable system" can be delivered to the field. A stable system exists when the effects of one or more bit changes have fully propagated through the logic. The system is designed so that all of that logic will be executed before outputs can be delivered. This prevents delivery of intermediate outputs after only a portion of the application logic had been executed. 6470A 4/96 2-1

20 Section II FUNCTIONAL DESCRIPTION Also as an example, inputs are read and changes trigger some logic. When all logic is executed, the system is marked as stable and outputs are readied for delivery, even if more inputs change state before these outputs are delivered. The outputs may be sent because they are the result of a stable system. The requirement that no intermediate logic outputs be delivered is not violated because the system became stable; changes occurred after the logic was executed. 2.2 ERRORS AND EVENT LOGGING The MICROTRAX system incorporates an error table and a data/event logger. The error table is used to count the number of times any error or warning has been logged. Its range is 0 to 240. This error table is displayed in the DISPlay STATus menu on the CPU Module front panel. An event queue is also provided to log events, and is capable of holding 275 events. Events are described in the following sections Critical Errors Critical Errors result in a system shut down. Then the unit goes through a power-up reset process. All outputs are deenergized. Refer to SM-6470B for a detailed listing of critical error codes Static and Dynamic Warnings Warnings do not always result in a system shutdown. For example, when a color light lamp failure is detected, a warning is logged stating that a lamp filament has failed. A static warning is merely logged. When a dynamic warning occurs, the event will only be logged if another event for the same warning has not been previously logged. For example, in the case of a lamp filament failure event, the diagnostics that detect filament failures are run very frequently. If an event were logged every time that diagnostic failed, the event queue logging memory would be quickly filled. To prevent this, a filament failure is only logged if the warning count is zero (first instance of this warning). Refer to SM-6470B for a detailed listing of static and dynamic warnings Track Shunting Events Track shunting events indicate when a track circuit is shunted and when the shunt is removed. There are two shunt-related events for each track circuit. Thus, at an intermediate location, four possible events can be logged. A "Remove Shunt" event can also be logged. This logs the brief, intermediate state between a presence of a shunt and the absence of a shunt. Refer to section for additional information User-Defined Events Two user-defined bits are provided in the application logic that enable logging of special events not available in the standard error/event log listing. Refer to section for additional information on the use of these bits. 2.3 VITAL LOCAL COMMUNICATIONS Acquiring Inputs MICROTRAX inputs are acquired through a module-by-module sampling process that is completed once every 100 msec. The general procedure during a normal (non-fault) input cycle is as follows: 1. All inputs on a module are scanned and passed to a "bit string manager". 2. The new input values are compared against values sampled during the previous module scan to identify bits that have changed state. 2-2 SM 6470A 4/96

21 Section II FUNCTIONAL DESCRIPTION a. If a bit has changed from a less restrictive state ("1") to a more restrictive state ("0"), the change is immediately accepted (continue to step 3 of this procedure). b. If a bit has changed from a more restrictive state ("0") to a less restrictive state ("1"), it is scanned four times. The bit must show a "1" on all four consecutive scans to be accepted. 3. Accepted bits are put into the memory, triggering all application program equations that make use of these bits Vitality of Inputs Redundant Reading Each scan of inputs consists of several samples of those inputs. This function is designed to filter out transient state changes that may be caused by interfering external signals such as a high-frequency signal. In most cases samples match, thus validating the bit. However, if a discrepancy is observed, the read is repeated. If the discrepancy persists, the read is repeated a second time (three total reads per scan cycle). If matching reads cannot be obtained, the inputs are marked as unstable Input Instability Check After three consecutive reads of unstable inputs on one scan cycle, the inputs are left as previously scanned. On the next 100 msec. scan, if the unstable readings persist for three consecutive reads, then all inputs on that particular module are flagged as unstable and set to the more restrictive state ("0"). Warnings are also logged stating that all inputs have been declared invalid and will remain as such until the inputs become stable and pass several validity/stability checks Verification of Less Restrictive Bit During normal operation, a change of an input bit from a more restrictive ("0") to less restrictive ("1") state is accepted after the bit is reviewed during a fourth board scan (section 2.3.1, step 2). If the less restrictive ("1") state is not verified ("0" on the second, third or fourth scan), the bit stays at the more restrictive state ("0"). No error is logged. The bit must be a "1" on all four consecutive scans to be accepted as a less restrictive input ("1"). This process implies that an input signal must be present for four consecutive scans (100 msec. apart) to be accepted with a new state. A less restrictive-going input ("1") lasting less than 400 msec. is ignored. All signals lasting longer than 400 msec. are accepted Bit Latching Bit latching is the process of securing in memory any input that changes to the more restrictive state ("0"), no matter how briefly. The zero state of the input is held until the processor can act on it. For example, if an external relay contact feeds voltage to the MICROTRAX unit and the relay momentarily drops and picks, the loss of the voltage will be recorded as "0" and will be latched as dropped ("0"), even if the relay returns to the "1" state. This action allows the "0" state to be recognized and processed. After processing of the "0" state, the "1" state is then accepted Stuck Bit Check To verify that all input circuits can place a bit in the more restrictive state ("0"), a standard diagnostic test is performed. This test is run approximately every 100 msec, only when an input is in the less restrictive state ("1"). The following is performed for each input PCB: 6470A 4/96 2-3

22 Section II FUNCTIONAL DESCRIPTION 1. All individual inputs on a given board are forced to the more restrictive ("0") state through a closed loop monitor. 2. All inputs are read and verified that they can, in fact, be forced to the more restrictive state. (This test verifies that no circuit malfunctions have occurred that could stick an input in the less restrictive state). 3. Any input stuck in the less restrictive state is flagged as such with an error counter. The error counter provides for filtering of nuisance errors, enabling all inputs to overcome momentary problems without immediately degrading the level of operation. If the error counter reaches a maximum level of errors before validity checks can clear the counter; the input is internally forced to the more restrictive state until the input changes to a "1" and passes the stuck/ shorted bit test (refer to following section) at least six consecutive times Shorted Input Check Once every 100 msec. all input bits are tested for possible shorts between them, using a standard diagnostic routine in conjunction with the Stuck Bit Test. This test verifies that none of the input circuits have malfunctioned in a way that masks the true condition of other inputs on the module under test. The test involves sequential scanning of every input on every input module: 1. The input under test (must be a "1") is forced into the more restrictive state ("0"). 2. The other inputs on the module are tested to verify that none have changed state. 3. The initially forced input is returned to the less restrictive state ("1"). 4. The next input is forced to the more restrictive state ("0") and all other inputs are checked that none have changed state. 5. Any shorted inputs are flagged as such with an error counter. The error counter provides for filtering of nuisance errors; enabling all inputs to overcome momentary problems (since it is not certain if the other input actually is shorted or the input physically changed state) without instantly degrading the level of operation. If the error counter reaches a maximum level of errors before validity checks can clear the counter, the inputs which are shorted together are internally forced to the more restrictive state ("0") until the inputs are fixed or change to a "1" and pass the stuck/shorted bit test at least six consecutive times Delivering Outputs MICROTRAX outputs are delivered according to the order and timing specified in the application program. The general procedure during a normal (non-fault) output cycle is as follows: 1. Upon triggering of all logic equations and elapsing of all timer-related bits in the application program, resulting output bits are extracted from memory. 2. Output bits are delivered by the CPU to the specified output module on the next 100 millisecond boundary. 3. Monitors on the output circuits return end point data to the CPU. 4. Memory-stored bits and resulting data from the output module are compared by the CPU. 2-4 SM 6470A 4/96

23 Section II FUNCTIONAL DESCRIPTION Vitality of Outputs Stability Interval When a change of input occurs and logic processing commences, the MICROTRAX logic is considered "unstable". Output bits cannot be delivered since their states may be uncertain. After the logic becomes stable, the outputs will be delivered on the next 100 msec. output diagnostic scan cycle. They must be delivered no later than 0.5 seconds after the logic becomes stable again, otherwise a shutdown will occur. This action is designed to ensure that all deliverable output bits are in their most recent state Reading Monitors A separate diagnostic routine reads the monitor circuit on each output. This test is conducted once every 100 msec. The output monitor test is used to ensure that the MICROTRAX system has delivered the correct outputs to the output modules by using the output monitor circuitry located on the modules. These output monitors allow the processor to read the values that it has written to the output modules. The monitors are read and compared to the expected image of the outputs. If these are not in agreement, a system shutdown occurs. This shutdown uses the VCOR to turn all vital outputs off Stuck Output ("Flip") Check The stuck output or "flip" test determines whether an output circuit can change state. It is conducted approximately once every 100 msec. The output flip test verifies the integrity of the output monitor circuitry. The loop back check on the output circuits allows the Executive software to monitor the state of the output drive circuit. The output flip test momentarily "flips" the state of the output to force the monitor to the opposite state. This proves that the monitor has not stuck and is reporting the true state of the output driver. The outputs are then returned to the correct state. This test can be suspended; refer to section , part C Lamp Filament Tests 1. Hot Filament Test (LAMP ON) A. Color Light Lamp Driver Module: To determine whether a color light signal lamp has a missing or damaged bulb (broken filament), the Hot Filament Test is performed every 100 msec. If the system turns a lamp on and the monitor shows no current, a recoverable lamp-out error is placed in memory. This type of lamp failure is accessible in the application logic via the lamp-out bits. Thus, the application can be written to take action if a lamp-out occurs. If the system sends a lamp-off signal and the monitor shows current flowing through the circuit, a non-recoverable error is recorded and a system shutdown is performed (power removed from the lamp driver circuit and all other outputs). B. Searchlight Lamp Driver Module (N ): To determine whether a searchlight signal lamp has a missing or damaged bulb (broken filament), the Hot Filament Test is performed every 100 msec. If the system turns a lamp on and the monitor shows no current, a non-recoverable lamp-out error is placed in memory. (Since this module cannot distinguish between a lamp-out condition and a mechanism failure, this error is critical and produces a system shutdown). If the system sends a lamp-off signal and the monitor shows current flowing through the circuit, a nonrecoverable error is recorded and a system shutdown is performed (power removed from the lamp driver circuit and all other outputs). 6470A 4/96 2-5

24 Section II FUNCTIONAL DESCRIPTION A mechanism check is also performed to verify that the searchlight mechanism is in the correct position. This test is performed on the mechanism once every 0.5 seconds. The aspect of the mechanism under test is turned off for approximately 1.5 msec. A current reading is taken from an analog-to-digital converter (A/D) on this module and verified that the current is essentially zero. After testing, the aspect is returned to its original position. If the A/D reading shows current flowing then the mechanism check is performed again on the next 100 msec. scan cycle to re-verify that the mechanism is actually faulty. If the mechanism is determined to be faulty, a non-recoverable failure is recorded and a system shutdown is produced. C. Searchlight Lampdriver Module (N ) Search Light Lamp Driver Module: To determine whether a Search light signal lamp has a missing or damaged bulb (broken filament), the Hot Filament Test is performed every 100 msec. If the system turns a lamp on and the monitor shows no current, a recoverable lamp-out error is placed in memory. This type of lamp failure is accessible in the application logic via the lamp-out bits. Thus, the application can be written to take action if a lamp-out occurs. If the system sends a lamp-off signal and the monitor shows current flowing through the circuit, a non-recoverable error is recorded and a system shutdown is performed (power removed from the lamp driver circuit and all other outputs). A mechanism check is also performed to verify that the search light mechanism is in the correct position. Two different tests exist when the mechanism is in the RED or YELLOW position: - the mechanism s correspondence input is read to verify the position of the mechanism. - the mechanism is briefly turned off (less than one millisecond) to verify the integrity of the mechanism s correspondence input. If the mechanism is determined to be faulty, a non-recoverable failure is recorded and a system shutdown is produced. 2. Filament "Flip" Test/Cold Filament Test A. Color Light Lamp Driver Module/ Searchlight Lamp Driver Module (N ): : During the lamp driver flip test (refer to section ) with this module, the continuity of the lamp filament is checked when an "off" lamp output is briefly turned on. If no current flow is recorded during this test, a lamp-out bit is set and a warning is logged. This type of lamp-fail is accessible in the application logic so that corrective action can be taken. B. Searchlight Lamp Driver Module (N ): During the lamp driver flip test (refer to section ), the continuity of the lamp filament is checked when an "off" lamp output is briefly turned on. If no current flow is recorded during this test, a critical lamp-out error is placed in memory. (Since this module cannot distinguish between a lamp-out condition and a mechanism failure, a critical error and system shutdown results.). 2-6 SM 6470A 4/96

25 Section II FUNCTIONAL DESCRIPTION C. Suspend Test: The Suspend Test function can be selected separately for each I/O module defined in the application logic. When the Suspend Test bit is high ("1"), the only test that can be suspended is the momentary turn-on of an inactive output during the Stuck Output Check (refer to section ). If the application logic turns on both the output and the Suspend Test Bit, the output is checked. If the output is turned off and the Suspend Test Bit is turned on, the test of the output does not occur.! WARNING THE SUSPEND TEST BIT MUST BE USED WITH GREAT CARE BECAUSE OF THE LONGER TIME THAT IT CREATES FOR DETECTION OF A FAULTY OUTPUT. IF OUTPUTS ARE NOT TESTED PERIODICALLY TO VERIFY THAT THEY CAN BE TURNED ON, A FAILURE MODE COULD ARISE THAT WOULD ALWAYS MAKE THE MONITOR CIRCUITS SHOW AN OFF STATE. IF THIS CONDITION EXISTS WHEN ANOTHER COMPONENT FAILURE OCCURS, THE FAILURE COULD TURN ON AN OUTPUT WITHOUT A CORRESPONDING DETECTION BY THE MONITOR CIRCUIT Conditional Power Supply Basic Function Local inputs and outputs receive their power via a conditional power supply (CPS). If the unit is running properly and diagnostics are successful, the CPS is powered up and outputs and inputs are operational. If the unit detects certain types of errors, the system will run with the CPS powered down (Selective Shutdown Mode). In this special reduced operating mode, local inputs and outputs are not operational, but the track, vital serial links and local control panel still function. Refer to section 2.5 for more information. 2.4 VITAL SERIAL COMMUNICATIONS General Each MICROTRAX unit is equipped with redundant serial data ports to allow vital communications with a MICROLOK, MICROLOK PLUS, or MICROTRAX End-of-Siding serial link module system. This communications channel is referred to as a Vital Serial Link. These ports also allow "daisy chain" linking of up to 16 MICROTRAX units, all controlled by the same MICROLOK or MICROLOK PLUS system. The vital operation of this link is maintained by re-communicating all data to a station, regardless of whether input bits have changed. In all MICROTRAX Vital Serial Links, the MICROTRAX unit always functions as a Slave to a MICROLOK, MICROLOK PLUS or MICROTRAX End-of-siding serial link module system Communications Modes The MICROTRAX slave port utilizes EIA RS-423 (RS-232 compatible) serial communications. There is no internal provision for 20 ma current loop communications; this is accomplished with a Serial 6470A 4/96 2-7

26 Section II FUNCTIONAL DESCRIPTION Communications Adapter Panel (refer to SM-6400B). The Vital Serial Link always operates in the full duplex mode. Only control signals overlap; data messages never overlap. A communication on a MICROTRAX Vital Serial Link consists of a string of data bits transferred sequentially. These bits make up a message that includes an address section (identifying the intended remote unit) and the specific operating data intended for the remote unit. All messages from a MICROLOK, MICROLOK PLUS or MICROTRAX End-of-siding serial link module system are steered by means of "stations", which are defined in the application logic of these systems. 2.5 OPERATING MODES Basic The MICROTRAX system is capable of operating in three different modes: A. Normal: Operational: CPS powered up, I/O active, track communications active B. Selective Shutdown: Operational: CPS powered down, I/O inactive, track communications active, Slave link, Local Control Panel and cross-unit control active. C. Full Shutdown: Non-Operational: CPS powered down, I/O inactive, track communications inactive In the Selective Shutdown mode, the user must manually re-enable the CPS. This is done using the Reset Menu (refer to SM-6470B) or by assigning a 1 to the RESET system bit (executive rev. 4 and higher). Error filtering is provided to reduce likelihood of falsely dropping the CPS while running in the Normal mode. Since the unit can operate with the CPS up or down, the application logic has access to system bit CPS.STATUS. This bit informs the application logic about the state of the CPS. If the CPS is up and I/O is operational, CPS.STATUS is set. If the unit is running in the Selective Shutdown mode, CPS.STATUS is cleared. In systems running with executive rev. 4 and higher, the CPS.STATUS and RESET system bit can be used to write application logic that can attempt to restore a unit running in selected shutdown mode to normal mode. An application logic segment follows: TIMER RESET_CONTROL: SET = 15:MIN CLEAR = 0:SEC;. BEGIN. ASSIGN ~CPS.STATUS TO RESET_CONTROL; ASSIGN RESET_CONTROL TO RESET; In this program, the unit will attempt to restore a unit to Normal mode 15 minutes after it enters selective shutdown mode. The set delay on RESET_CONTROL is needed to prevent rapid attempts to restore the CPS in a unit that may have permanent output faults. 2-8 SM 6470A 4/96

27 Section II FUNCTIONAL DESCRIPTION Prior State Routine A Prior State Routine is used to determine the operating mode of the system. Every time the system is reset, the Prior State Routine examines the number of errors recently logged and the number of resets recently encountered, then determines the operating mode. The following rules are observed during this process: NOTE In the following rules, total running time is defined as the sum of the MICROTRAX execution time with the exception of the time spent in reset routines. The reset routine time is denoted by the message "RES" on the CPU module top alphanumeric display. Refer to SM-6470B for more information on reset routines. 1. System in the Normal mode and error/reset occurs: If more than five errors occurred within 40 seconds of the total running time, or 10 resets occurred within 40 seconds of the total running time, the Selective Shutdown mode is entered. Otherwise, the Normal mode is continued. 2. System in Selective Shutdown mode and error/reset occurs: If more than five errors occurred within 40 seconds of the total running time, or 10 resets occurred within 40 seconds of the total running time, then the Shutdown mode is entered. Otherwise, the Selective Shutdown mode is continued. 3. System in Full Shutdown mode and reset occurs: When the system is in the Full Shutdown mode, no operations occur except toggling of the watchdog circuit (reset inhibited). Diagnostics are also inactive. A reset can only occur as the result of a hardware failure, power fault or operation of the RESET button on the CPU Module. If the system resets while in the Full Shutdown mode, the unit will enter the Selective Shutdown mode CPS Powered Down Recovery The system will not attempt to restore an inactive CPS (unless the RAM that holds the Prior State variables is corrupted/cleared). Manual intervention is required. Refer to SM-6470B for the reset menu procedures. In systems running with executive rev. 4 and higher, the CPS.STATUS and RESET system bit can be used to write application logic that can attempt to restore a unit running in selected shutdown mode to normal mode. 6470A 4/96 2-9

28 Section II FUNCTIONAL DESCRIPTION System Loading The MICROTRAX system provides several warnings/errors indicating that the system cannot perform all its functions in a timely fashion. These warnings/errors indicate that the application logic is too complex for the MICROTRAX system to handle. The codes that will be logged in this situation are: Error Code #2 Error Code #41 Error Code #32 Error Code #40 Error Code #47 Warning Code #86 Error Code #44 Refer to SM-6470B for detailed information on these codes. If these errors are continuously logged, the application logic must be simplified so that the MICROTRAX system can execute it in a timely fashion Track Communications General NOTE Refer to SM-6470B for detailed information on track code formats. The Track Interface Module consists of two transmitters and two receivers which are capable of handling two ends of a track circuit. One transmitter/receiver pair is designated the Master and the other pair the Slave. The basic function of the Track Interface Module is to transmit and receive codes via the rails. The Master is responsible for initiating a message; the Slave will only respond when a valid message is received. When a code transmission is made, the unit will send the first code in an output list whose corresponding output bit is set. If no output bit is set, then system bits TRACK_TDOUT and TRACK_SLEEPOUT are examined. The first one that is set will be sent. If no output bits are set, then a "link-up" code will be sent (which forces a shunt on the receiving unit). If the unit is shunted, then the link-up code must be received before another track code will be accepted or transmitted. Refer to sections through for details of these functions. When a track code is received, special rules apply when the application logic bit is set. For any of the normal aspect codes, the message must be received twice consecutively before it is accepted. Then, two out of three are required to keep the code selected. The special link-up, tumble down and sleep special codes are accepted on one reception. Refer to sections through for details of these functions. Track transmit diagnostics are performed during a message transmission. Monitor tests are performed to verify that the hardware is sending the code intended by the CPU. Before the actual receiver is enabled for message reception, diagnostics are performed to verify the receive signal level, transmit signal level and to select the zero voltage level based on temperature. These diagnostics verify that the various analog-to-digital and voltage levels on the module are operating correctly. Since some of these components vary with temperature, a temperaturecompensated zero voltage or ground is needed to properly process the receive signal SM 6470A 4/96

System Description. Microlok II. Integrated Vital Interlocking, Coded Track Circuit, and Non-vital Code Line Controller

System Description. Microlok II. Integrated Vital Interlocking, Coded Track Circuit, and Non-vital Code Line Controller 1000 TECHNOLOGY DRIVE PITTSBURGH, PA 15219-3120 SM-6800A System Description Microlok II Integrated Vital Interlocking, Coded Track Circuit, and Non-vital Code Line Controller THIS DOCUMENT AND ITS CONTENTS

More information

Microlok II System Startup, Troubleshooting, and Maintenance. Microlok II

Microlok II System Startup, Troubleshooting, and Maintenance. Microlok II UNION SWITCH & SIGNAL 1000 TECHNOLOGY DRIVE PITTSBURGH, PA 15219-3120 SM-6800C Microlok II System Startup, Troubleshooting, and Maintenance Microlok II Integrated Vital Interlocking, Coded Track Circuit,

More information

MicroLok II Wayside Control System - General Information and Configuration Guide

MicroLok II Wayside Control System - General Information and Configuration Guide Wayside Signaling Systems MicroLok II Wayside Control System - General Information and Configuration Guide Ansaldo STS USA ASTS USA s MicroLok II multi-purpose wayside controller has become the rail industry

More information

Ansaldo STS USA (Formerly known as Union Switch & Signal)

Ansaldo STS USA (Formerly known as Union Switch & Signal) Wayside Signaling Systems Ansaldo STS USA AF-902/AF-904 Generation II Digital Like its AF-900 Series predecessor, the AF- 902/AF-904 Generation II (AF-Gen II) Track Circuit outperforms the functions of

More information

PC-250B Solid State Vital Biased Code Following Track Relay

PC-250B Solid State Vital Biased Code Following Track Relay Union Switch & Signal Inc., an Ansaldo Signal company 1000 Technology Drive, Pittsburgh, PA 15219 645 Russell Street, Batesburg, SC 29006 SM 9268 PC-250B Solid State Vital Biased Code Following Track Relay

More information

MMU-16E. NEMA TS-2 Malfunction Management Unit Operations Manual

MMU-16E. NEMA TS-2 Malfunction Management Unit Operations Manual MMU-16E NEMA TS-2 Malfunction Management Unit THIS MANUAL CONTAINS TECHNICAL INFORMATION FOR THE MMU-16E SERIES MALFUNCTION MANAGEMENT UNIT. INCLUDED ARE GENERAL DESCRIPTION, OPERATIONAL DESCRIPTION, INSTALLATION,

More information

Microlok II System Application Logic Programming Guide. Microlok II

Microlok II System Application Logic Programming Guide. Microlok II UNION SWITCH & SIGNAL 1000 TECHNOLOGY DRIVE PITTSBURGH, PA 15219-3120 SM-6800D Microlok II System Application Logic Programming Guide Microlok II Integrated Vital Interlocking, Coded Track Circuit, and

More information

ECC Chaining Modules

ECC Chaining Modules Union Switch & Signal Inc., an Ansaldo Signal company 1000 Technology Drive, Pittsburgh, PA 15219 645 Russell Street, Batesburg, SC 29006 SM 9488 ECC Chaining Modules Input Isolation Module Bipolar Output

More information

INSTRUCTION MANUAL STATION CONTROLLER SC1000 MOTOR PROTECTION ELECTRONICS, INC.

INSTRUCTION MANUAL STATION CONTROLLER SC1000 MOTOR PROTECTION ELECTRONICS, INC. INSTRUCTION MANUAL STATION CONTROLLER SC1000 MOTOR PROTECTION ELECTRONICS, INC. 2464 Vulcan Road, Apopka, Florida 32703 Phone: (407) 299-3825 Fax: (407) 294-9435 Revision Date: 9-11-08 Applications: Simplex,

More information

Microlok Data Design Records (Addressing, File Control, Checking, and FAT Testing)

Microlok Data Design Records (Addressing, File Control, Checking, and FAT Testing) Discipline: Engineering (Signalling) Category: Procedure Microlok Data Design Records (Addressing, File Control, Checking, and FAT Testing) ESD-05-11 Applicability ARTC Network Wide Primary Source Signal

More information

SS2200 Remote Controller

SS2200 Remote Controller SS2200 Remote Controller General Purpose, DC Voltage General The SS2200 Remote Controller is a microprocessor-based programmable controller specifically designed to control single line and dual line centralized

More information

Cardfiles (MicroLok II Applications)

Cardfiles (MicroLok II Applications) Wayside Signaling System Ansaldo STS USA The cardfiles used in MicroLok II systems accommodate the full range of user system applications and PCB configurations in a single rack-mount unit. Unlike earlier

More information

DUAL LOOP DETECTOR WITH MODBUS COMMUNICATIONS

DUAL LOOP DETECTOR WITH MODBUS COMMUNICATIONS LD220 DUAL LOOP DETECTOR WITH MODBUS COMMUNICATIONS USER MANUAL P.O.Box 24 STANFIELD 3613 SOUTH AFRICA Tel: +27 (031) 7028033 Fax: +27 (031) 7028041 Email: proconel@proconel.com Web: www.proconel.com 18/08/2005

More information

Interlocking Solutions. MicroLok II

Interlocking Solutions. MicroLok II Interlocking Solutions 1 Wayside Control System The Ansaldo STS Wayside Control System for mass transit, metro, main lines and freight applications, combines the functions of railway signalling and control

More information

Model HM-535 Power Supply Installation and Service Instructions

Model HM-535 Power Supply Installation and Service Instructions Model HM-535 Power Supply Installation and Service Instructions 430-535 0104 2004 Heritage MedCall, Inc SENTRY INSTALLATION & SERVICE INSTRUCTIONS POWER SUPPLY UNIT Model HM-535 IMPORTANT SAFETY INSTRUCTIONS

More information

output devices. connected to the controller. data communications link. relay systems. user program. MECH1500Quiz1ReviewVersion2 Name: Class: Date:

output devices. connected to the controller. data communications link. relay systems. user program. MECH1500Quiz1ReviewVersion2 Name: Class: Date: Class: Date: MECH1500Quiz1ReviewVersion2 True/False Indicate whether the statement is true or false. 1. The number and type of I/Os cannot be changed in a fixed PLC. 2. In a PLC system, there is a physical

More information

INTRINSICALLY SAFE DUPLEXER PROTECTION. ELECTRONICS, INC Vulcan Road Apopka, Florida MOTOR INSTRUCTION MANUAL

INTRINSICALLY SAFE DUPLEXER PROTECTION. ELECTRONICS, INC Vulcan Road Apopka, Florida MOTOR INSTRUCTION MANUAL INTRINSICALLY SAFE DUPLEXER INSTRUCTION MANUAL MOTOR PROTECTION ELECTRONICS, INC. 2464 Vulcan Road Apopka, Florida 32703 Phone: Website: (407) 299-3825 www.mpelectronics.com Operating Program Revision:

More information

205 CPU NETWORK ADAPTER F2-UNICON

205 CPU NETWORK ADAPTER F2-UNICON 205 CPU NEWORK ADAPER F2-UNICON Network Adapter he F2-UNICON Network Adapter is used to place Automationdirect.com DL205 CPUs (except D2-230 and D2-250) on a RS-422 or RS-485 multi-drop network. he Network

More information

NSM-E Series. NEMA TS-1 Enhanced Signal Monitor Operations Manual

NSM-E Series. NEMA TS-1 Enhanced Signal Monitor Operations Manual NSM-E Series NEMA TS-1 Enhanced Signal Monitor THIS MANUAL CONTAINS TECHNICAL INFORMATION FOR THE NSM-6E and NSM-12E SERIES SIGNAL MONITOR. REVISION: MARCH 2012 pn 888-1206-002 THE NSM-E SERIES SIGNAL

More information

SC2000 MOTOR PROTECTION ELECTRONICS, INC. INSTRUCTION MANUAL. (407) Phone: Website:

SC2000 MOTOR PROTECTION ELECTRONICS, INC. INSTRUCTION MANUAL. (407) Phone: Website: SC2000 INSTRUCTION MANUAL MOTOR PROTECTION ELECTRONICS, INC. 2464 Vulcan Road Apopka, Florida 32703 Phone: Website: (407) 299-3825 www.mpelectronics.com Operating Program Revision: 12 Revision Date: 8-27-14

More information

DNP Points List and Implementation

DNP Points List and Implementation S&C 6800 Series Automatic Switch Control DNP Points List and Implementation Table of Contents Section Page Section Page DNP Points List for 6801 Controls...1 6801 Status Points...2 6801 Double-bit Status

More information

ICS Regent. AC Guarded Digital Output Module 110 VAC (T3464) PD-6021

ICS Regent. AC Guarded Digital Output Module 110 VAC (T3464) PD-6021 ICS Regent PD-6021 AC Guarded Digital Output Module 110 VAC (T3464) Issue 1, March, 06 AC Guarded digital output modules provide guarded switching of user-supplied 110 AC voltages to a maximum of sixteen

More information

SECTION MICROPROCESSORS

SECTION MICROPROCESSORS SECTION 13580 MICROPROCESSORS PART 1 GENERAL 1.01 DESCRIPTION A. The contractor shall furnish a MicroLok II Vital Microprocessor Based Interlocking System (VMIS) and Non-Vital Based Interlocking Systems

More information

Flex Series User Guide

Flex Series User Guide User Programmable Current 4..20mA Digital RS485 Dual & Single Axis Up to 360º 2016 Flex Series User Guide Sensor Installation, Wiring, Flexware App Instructions Page 1 of 33 Page 2 of 33 Table of Contents

More information

Installation and Setup. In This Chapter... Installing the H0 PSCM The Profibus Network Configuring the Module

Installation and Setup. In This Chapter... Installing the H0 PSCM The Profibus Network Configuring the Module Installation and Setup 1 2 In This Chapter.... Installing the H0 PSCM The Profibus Network Configuring the Module 2 2 Installing the H0 PSCM Remove the Slot Cover The first step in installing the option

More information

Installation and Setup

Installation and Setup Installation and Setup 1 In This Chapter Installing the H PBC The Profibus Network Configuring the Controller Installing the H PBC Setting the Node Address Setting the Node Address Profibus DP is usually

More information

DNP Points List and Implementation for Universal Controls

DNP Points List and Implementation for Universal Controls S&C 6800 Series Automatic Switch Control DNP Points List and Implementation for Universal Controls Table of Contents Section Page Section Page DNP Points List for 6801 Universal Controls...1 6801 Status

More information

PART A DIGITAL AXLE COUNTER (SINGLE SECTION)

PART A DIGITAL AXLE COUNTER (SINGLE SECTION) PART A DIGITAL AXLE COUNTER (SINGLE SECTION) 1.0 Introduction Axle counter is a device for monitoring a specified section of track for the presence of vehicle. Conventional axle counters were designed

More information

OPERATIONS MANUAL SSM-18LEPR CONFLICT / VOLTAGE MONITOR

OPERATIONS MANUAL SSM-18LEPR CONFLICT / VOLTAGE MONITOR SSM-18LEPR CONFLICT / VOLTAGE MONITOR THIS MANUAL CONTAINS TECHNICAL INFORMATION FOR THE FOLLOWING SERIES OF CONFLICT/VOLTAGE MONITORS: SSM-18LEPR. INCLUDED ARE GENERAL DESCRIPTION, OPERATIONAL DESCRIPTION,

More information

Pretest Programmable Logic Controllers. Unit 1, Task 1

Pretest Programmable Logic Controllers. Unit 1, Task 1 Pretest Programmable Logic Controllers Unit 1, Task 1 1. What is a PLC? 2. What are the four main components of a PLC? 3. What is a discrete device? 4. What is a pulse-generating device? 5. What term is

More information

PRM Integration Guide with Pepperl+Fuchs HiDMUX2700 HART Multiplexer

PRM Integration Guide with Pepperl+Fuchs HiDMUX2700 HART Multiplexer PRM Integration Guide with Pepperl+Fuchs HiDMUX2700 HART Multiplexer This manual explains how to connect the HiDMUX2700 HART Multiplexer and configure Yokogawa s Plant Resource Manager (PRM) software.

More information

Model NM512. TS1 Conflict Monitor Standard 12 Channel Unit. Naztec Operations Manual. For. Published by

Model NM512. TS1 Conflict Monitor Standard 12 Channel Unit. Naztec Operations Manual. For. Published by Naztec Operations Manual For Model NM512 TS1 Conflict Monitor Standard 12 Channel Unit Published by Naztec, Inc. 820 Park Two Dr. Sugar Land, Texas 77478 Phone: (281) 2407233 Fax: (281) 240-7238 Copyright

More information

Automationdirect.com. D i r e c t L o g i c S D S N e t w o r k M a s t e r. S m a r t D i s t r i b u t e d. S y s t e m M o d u l e

Automationdirect.com. D i r e c t L o g i c S D S N e t w o r k M a s t e r. S m a r t D i s t r i b u t e d. S y s t e m M o d u l e Automationdirect.com D i r e c t L o g i c 4 0 5 S D S N e t w o r k M a s t e r S m a r t D i s t r i b u t e d S y s t e m M o d u l e F 4 - S D S Order Number: F4-SDS-M TRADEMARKS Automationdirect.com

More information

Installation, Testing, and Operating Procedures 30 AMP PORTABLE AND PERMANENT SERIES GFCI SINGLE and MULTIPHASE

Installation, Testing, and Operating Procedures 30 AMP PORTABLE AND PERMANENT SERIES GFCI SINGLE and MULTIPHASE IMPORTANT! Please read all the information on this sheet. SAVE THESE INSTRUCTIONS! NOTICE BEFORE USING READ INSTRUCTIONS COMPLETELY. TO BE INSTALLED BY A QUALIFIED ELECTRICIAN IN ACCORDANCE WITH NATIONAL

More information

DNP Points List and Implementation

DNP Points List and Implementation S&C IntelliRupter PulseCloser Fault Interrupter Outdoor Distribution (15.5 kv, 27 kv, and 38 kv) DNP Points List and Implementation Table of Contents Section Page Section Page Introduction...1 Status Points...2

More information

ICS Regent. Monitored Digital Input Modules 24 VDC (T3411) PD-6031

ICS Regent. Monitored Digital Input Modules 24 VDC (T3411) PD-6031 ICS Regent PD-6031 Monitored Digital Input Modules 24 VDC (T3411) Issue 1, March, 06 Monitored digital input modules provide input sensing for 16 field input devices. With a line monitor device installed

More information

MMU-16LE Series SmartMonitor

MMU-16LE Series SmartMonitor MMU-16LE Series SmartMonitor NEMA TS-2 Enhanced Malfunction Management Unit THIS MANUAL CONTAINS TECHNICAL INFORMATION FOR THE MMU-16LE and MMU16LEip SmartMonitor SERIES MALFUNCTION MANAGEMENT UNIT. REVISION:

More information

BARIX IO12. I/O to RS-485 Modbus converter for commercial interfacing, control and home automation applications PRO D UCT MANUAL. Version: 2.

BARIX IO12. I/O to RS-485 Modbus converter for commercial interfacing, control and home automation applications PRO D UCT MANUAL. Version: 2. BARIX IO12 I/O to RS-485 Modbus converter for commercial interfacing, control and home automation applications PRO D UCT MANUAL Version: 2.01 Date: 06/03/2014 For Firmware Version 10 Table of Contents

More information

Answers to Chapter 2 Review Questions. 2. To convert controller signals into external signals that are used to control the machine or process

Answers to Chapter 2 Review Questions. 2. To convert controller signals into external signals that are used to control the machine or process Answers to Chapter 2 Review Questions 1. To accept signals from the machine or process devices and to convert them into signals that can be used by the controller 2. To convert controller signals into

More information

Product Information SIMATIC S Digital Output Module SM 322; DO 16 UC24/48 V

Product Information SIMATIC S Digital Output Module SM 322; DO 16 UC24/48 V Product Information SIMATIC S7-300 Digital Output Module SM 322; DO 16 UC24/48 V X 2 as of Version 3 4 New Digital Output Module Available The S7-300 Digital Output Module SM 322; DO 16 UC24/48 V has been

More information

Owner s Hardware Service Manual Frank Control Computer System

Owner s Hardware Service Manual Frank Control Computer System Owner s Hardware Service Manual Frank Control Computer System Revision 0105 ABOUT THIS MANUAL This section describes the contents of this manual and how to use this manual effectively. It was designed

More information

Greco Systems DU-58. Operation Manual. A division of e-dnc Inc. 303 E Gurley St. #522 Prescott, AZ USA

Greco Systems DU-58. Operation Manual. A division of e-dnc Inc. 303 E Gurley St. #522 Prescott, AZ USA G r e c o S y s t e m s DU-58 Operation Manual Greco Systems A division of e-dnc Inc. 303 E Gurley St. #522 Prescott, AZ 86301 USA 800-234-7326 COPYRIGHT 1984 GRECO SYSTEMS. ALL RIGHTS RESERVED. The hardware

More information

SC2000 MOTOR PROTECTION ELECTRONICS, INC. INSTRUCTION MANUAL. Phone: (407) Fax: (407) Vulcan Road Apopka, Florida 32703

SC2000 MOTOR PROTECTION ELECTRONICS, INC. INSTRUCTION MANUAL. Phone: (407) Fax: (407) Vulcan Road Apopka, Florida 32703 SC2000 INSTRUCTION MANUAL MOTOR PROTECTION ELECTRONICS, INC. 2464 Vulcan Road Apopka, Florida 32703 Phone: (407) 299-3825 Fax: (407) 294-9435 Operating Program Revision: 10 Revision Date: 1-9-12 STATION

More information

ACTIONI/Q Q498. DC Powered DC Input Field Configurable Isolator with Math Functions

ACTIONI/Q Q498. DC Powered DC Input Field Configurable Isolator with Math Functions ACTIONI/Q Q498 DC Powered DC Input Field Configurable Isolator with Math Functions Q498-0000 Provides 2 Isolated Analog Inputs, 1 Analog Output & 1 Frequency Output, as well as a Discrete Input & Output

More information

SERIES CMT CARBON MONOXIDE GAS TRANSMITTER

SERIES CMT CARBON MONOXIDE GAS TRANSMITTER SERIES CMT CARBON MONOXIDE GAS TRANSMITTER INSTALLATION OPERATION AND MAINTENANCE MANUAL DWYER INTRUMENTS, INC. PO BOX 373, MICHIGAN CITY, IN. 46360 USA PHONE: 800-872-9141 FAX: 219-872-9057 Web: www.dwyer-inst.com

More information

Features. Line Regulation. Load Regulation. Safety. Cooling. Input Connectors. Output Connectors. Overvoltage Protection. Over Temperature Protection

Features. Line Regulation. Load Regulation. Safety. Cooling. Input Connectors. Output Connectors. Overvoltage Protection. Over Temperature Protection Specifications: Input Voltage ( 3 phase ) No of Phases Input Frequency 208VAC ( 170 ~ 265 ) Code: 3P208 415VAC ( 342 ~ 460 ) Code: 3P400 Wye or Delta, 4 wire 3phase and one protective earth. 47 ~ 63Hz

More information

ALTERNATING RELAYS & CONTROLLERS ARM Series

ALTERNATING RELAYS & CONTROLLERS ARM Series ALTERNATING RELAYS & CONTROLLERS ARM Series Process Control Equipment for Hazardous Locations 7M26 UL913 INCLUDES INTRINSICALLY SAFE INPUTS Integrated Duplex Controller SOSO Operation (Sequence-on, Simultaneous-off)

More information

Operating Instructions Extended Cascade Controller MCO 101

Operating Instructions Extended Cascade Controller MCO 101 Operating Instructions Extended Cascade Controller MCO 101 VLT AQUA Drive FC 200 Extended Cascade Controller Option Contents Contents 1. Safety and precautions 3 Safety Instructions 3 Avoid unintended

More information

ISP Tester. Operating Instructions

ISP Tester. Operating Instructions ISP Tester Operating Instructions Rev. 1.3 2 Table of Contents Overview of Operation...3 Connecting Test Cable to ISP Tester...4 Inserting Battery Pack...8 Turning on Main Power...9 Using the Touch Panel

More information

User s Manual. Version 1.0 PAGE 1 OF 38

User s Manual. Version 1.0 PAGE 1 OF 38 User s Manual Version 1.0 PAGE 1 OF 38 1 Table of Contents 2 Overview... 6 3 Launching Project Editor... 8 4 Creating a New Project... 9 4.1 Initial Vehicle validation... 9 4.2 Project Properties Screen...

More information

D1000M SERIES FOR MODBUS SENSOR TO COMPUTER INTERFACE MODULES

D1000M SERIES FOR MODBUS SENSOR TO COMPUTER INTERFACE MODULES D1000M SERIES FOR MODBUS SENSOR TO COMPUTER INTERFACE MODULES D1000 FEATURES Complete sensor to RS-232/RS-485 interface. 500V rms analog input isolation. 15 bit measurement resolution. Continuous self-calibration;

More information

MODBUS RTU I/O Expansion Modules - Models C267, C277, and C287. Installation and Operations Manual Section 50

MODBUS RTU I/O Expansion Modules - Models C267, C277, and C287. Installation and Operations Manual Section 50 MODBUS RTU I/O Expansion Modules - Models C267, C277, and C287 Installation and Operations Manual 00-02-0651 09-01-09 Section 50 In order to consistently bring you the highest quality, full featured products,

More information

5800 Series Non-IntelliTEAM Universal Automatic Switch Control PG&E SCADA Points List

5800 Series Non-IntelliTEAM Universal Automatic Switch Control PG&E SCADA Points List S&C Electric Company 5800 Series Non-IntelliTEAM Universal 5800 Series Non-IntelliTEAM Universal PG&E SCADA Points List PG&E SCADA Points List for: 5801 Universal Control with USBP0S0X Software and 5802

More information

Features. Conducted Emission. Radiated Emission. Line Regulation. Load Regulation. Safety. Cooling. Input Connectors.

Features. Conducted Emission. Radiated Emission. Line Regulation. Load Regulation. Safety. Cooling. Input Connectors. Specifications: Input Voltage ( 1 phase ) ( 3 phase ) No of Phases Input Frequency 230VAC ( 170 ~ 265 ) Code: 1P200 208VAC ( 170 ~ 265 ) Code: 3P208 415VAC ( 342 ~ 460 ) Code: 3P400 1phase or 3phase Wye

More information

MC LINX 1 & 2 USER S GUIDE. 1 Description. 2 Specifications MC LINX 2 MC LINX 1 PROGRAMMABLE RELAY MODULE. INCR & FUNCT Push Buttons

MC LINX 1 & 2 USER S GUIDE. 1 Description. 2 Specifications MC LINX 2 MC LINX 1 PROGRAMMABLE RELAY MODULE. INCR & FUNCT Push Buttons MC LX 1 & 2 USER S GUIDE PROGRAMMABLE RELAY MODULE 1 Description The MC Linx (PN: 10MCLX1 and 10MCLX2) is a programmable relay module that may be used for multiple applications. The module provides removable

More information

Features. Conducted. Emission. Line Regulation. Load Regulation. Safety. Cooling. Input Connectors. Overvoltage Protection. Phase Loss.

Features. Conducted. Emission. Line Regulation. Load Regulation. Safety. Cooling. Input Connectors. Overvoltage Protection. Phase Loss. Features Specifications: High Power Density 3.3KW in 2U 1 phase 240vac input 3 phase input 208VAC / 415VAC options Power Factor Correction Output voltage up to 600V, current up to 400A Built-in RS232 /

More information

CPU 224. The compact high-performance CPU With 24 inputs/outputs on board Expandable with up to 7 expansion modules Design

CPU 224. The compact high-performance CPU With 24 inputs/outputs on board Expandable with up to 7 expansion modules Design CPU 224 The compact high-performance CPU With 24 inputs/outputs on board Expandable with up to 7 expansion modules Design The CPU 224 is equipped with the following: Integral 24 V encoder/load current

More information

ATL20 ATL30 Automatic transfer switch controller

ATL20 ATL30 Automatic transfer switch controller I 194 GB 07 07 ATL20 ATL30 Automatic transfer switch controller REMOTE CONTROL SOFTWARE MANUAL Summary Introduction... 2 Minimum resources of the PC... 2 Installation... 2 Activation of the PC-ATL connection...

More information

Abstract. GLV User Manual 1

Abstract. GLV User Manual 1 GLV User Manual 1 Abstract This user manual is a high level document that explains all operational procedures and techniques needed to operate the GLV system in a safe and effective manner. Anyone operating

More information

Data sheet CPU 115 (115-6BL02)

Data sheet CPU 115 (115-6BL02) Data sheet CPU 115 (115-6BL02) Technical data Order no. 115-6BL02 Type CPU 115 General information Note - Features 16 (20) inputs 16 (12) outputs from which are 2 PWM 50 khz outputs 16 kb work memory,

More information

QPRO Family of XC1700E Configuration PROMs

QPRO Family of XC1700E Configuration PROMs 11 QPRO Family of XC1700E Configuration PROMs Product Specification Features Configuration one-time programmable (OTP) read-only memory designed to store configuration bitstreams of Xilinx FPGA devices

More information

Switching module for AC V and up to three load stages, with manual switching

Switching module for AC V and up to three load stages, with manual switching 8 149 PTM13-M3 DESIGO I/O modules Switching module for AC 24 250 V and up to three load stages, with manual switching PTM13-M3 Signal converter for connection to P-bus, with three interlocked on/off control

More information

PGR-2601 MANUAL DC GROUND-FAULT RELAY

PGR-2601 MANUAL DC GROUND-FAULT RELAY POWR-GARD Ungrounded DC System PGR-2601 SERIES DC Ground-Fault Relay PGR-2601 MANUAL DC GROUND-FAULT RELAY AUGUST 31, 2009 REVISION 1 POWR-GARD DC GROUND-FAULT RELAY PWR TRIP 5 4 3 2 6 - BUS 8 10 15 20

More information

Motors I Automation I Energy I Transmission & Distribution I Coatings. SymbiNet CFW-11. User s Manual

Motors I Automation I Energy I Transmission & Distribution I Coatings. SymbiNet CFW-11. User s Manual Motors I Automation I Energy I Transmission & Distribution I Coatings SymbiNet CFW-11 User s Manual SymbiNet User s Manual Series: CFW-11 Language: English Document Number: 10002033446 / 00 Publication

More information

Din Rail Universal Module 8 inputs / 8 outputs IO88E01KNX

Din Rail Universal Module 8 inputs / 8 outputs IO88E01KNX Din Rail Universal Module 8 inputs / 8 outputs IO88E01KNX Product Handbook Product Description: Din Rail Universal 8 in / 8 out Module Order Code: IO88E01KNX Document Version: 1.1 Date: 22/07/2011 1/64

More information

8520/8520R. User Manual

8520/8520R. User Manual /R User Manual Warranty All products manufactured by SuperLogics are warranted against defective materials for a period of one year from the date of delivery to the original purchaser. Disclaimer SuperLogics

More information

NETRONICS HS3500 CONTROLLER

NETRONICS HS3500 CONTROLLER NETRONICS HS3500 CONTROLLER CUSTOMER NAME CONTROLLER SERIAL # CONTROLLER PART # PERSONALITY SWITCH SETTINGS BULLET PRESS CONFIGURATION DELIVERY DATE Contact the factory for help setting up your application.

More information

P3-SCM. General Specifications

P3-SCM. General Specifications General Specifications Module Type Modules per Base Modules per Group I/O Points Used Field Wiring Connector Operating Temperature Storage Temperature Humidity Environmental Air Vibration Shock Field to

More information

AS-i Safety Relay Output Module with Diagnostic Slave

AS-i Safety Relay Output Module with Diagnostic Slave AS-i Safety Relay Output Module with Diagnostic Slave User Manual...supports the requirements for AS-i Safety up to SIL3 Revision date: 2016-03-9 Subject to modifications without notice. Generally, this

More information

Mounting the Model 2601

Mounting the Model 2601 Control Technology Corporation Model 2601 Automation Controller Installation Guide Model 2601 Automation Controller This document is current as of the following revision levels: Controller Firmware 2.24

More information

DSP240-LPI Inverter Controller Card. Technical Brief

DSP240-LPI Inverter Controller Card. Technical Brief DSP240-LPI Inverter Controller Card Technical Brief September 2006 Manual Release 3.0 Card Revision 3.0 Copyright 2001-2006 Creative Power Technologies P.O. Box 714 MULGRAVE Victoria, 3170 Tel: +61-3-9543-8802

More information

DATA CONNECT ENTERPRISE

DATA CONNECT ENTERPRISE DATA CONNECT ENTERPRISE User s Manual IG202T and IGV23 Modem Document Number 520-01005-001 Rev. A DATA CONNECT Contents Contents... iii Figures... iv Chapter 1 Introduction... 5 Features...6 Applications...7

More information

SC1000 MOTOR PROTECTION ELECTRONICS, INC. INSTRUCTION MANUAL. Phone: (407) Fax: (407) Vulcan Road Apopka, Florida 32703

SC1000 MOTOR PROTECTION ELECTRONICS, INC. INSTRUCTION MANUAL. Phone: (407) Fax: (407) Vulcan Road Apopka, Florida 32703 SC1000 INSTRUCTION MANUAL MOTOR PROTECTION ELECTRONICS, INC. 2464 Vulcan Road Apopka, Florida 32703 Phone: (407) 299-3825 Fax: (407) 294-9435 Operating Program Revision: 8 Revision Date: 5-16-11 STATION

More information

USER INSTRUCTION MANUAL FOR LOADCELL TRANSMITTER MODEL TDC/I/0550 (SOFTWARE: VER2A) INDEX

USER INSTRUCTION MANUAL FOR LOADCELL TRANSMITTER MODEL TDC/I/0550 (SOFTWARE: VER2A) INDEX USER INSTRUCTION MANUAL FOR LOADCELL TRANSMITTER MODEL TDC/I/0550 (SOFTWARE: VER2A) INDEX DOCUMENT NO: TDC 0550 MANUAL - 2 1.0) INTRODUCTION. PAGE 2 1.1) ABOUT THIS MANUAL. PAGE 2 1.2) INTRODUCTION. PAGE

More information

sigma the power to protect Instruction Manual C-453EM

sigma the power to protect Instruction Manual C-453EM sigma monitor relay GROUND Fault RELAY / resistor monitor sigma the power to protect Instruction Manual C-453EM sigma monitor relay Neutral Grounding Resistors (NGR) are an integral and critical component

More information

SECURE DIGITAL ACCESS SYSTEM USING IBUTTON

SECURE DIGITAL ACCESS SYSTEM USING IBUTTON SECURE DIGITAL ACCESS SYSTEM USING IBUTTON Access control forms a vital link in a security chain. Here we describe a secure digital access system using ibutton that allows only authorised persons to access

More information

Model MMU-516L-E. TS2 MMU RS232 and Ethernet (Malfunction Management Unit)

Model MMU-516L-E. TS2 MMU RS232 and Ethernet (Malfunction Management Unit) Naztec Operations Manual For Model MMU-516L-E TS2 MMU RS232 and Ethernet (Malfunction Management Unit) Published by Naztec, Inc. 820 Park Two Dr. Sugar Land, Texas 77478 Phone: (281) 240-7233 Fax: (281)

More information

Data sheet VIPA CPU 115DP (115-6BL22)

Data sheet VIPA CPU 115DP (115-6BL22) Data sheet VIPA CPU 115DP (115-6BL22) Technical data Order no. Type 115-6BL22 VIPA CPU 115DP General information Note - Features Work memory [KB]: 16 Load memory [KB]: 24 Onboard 16x DI / 12x DO / 4x DIO

More information

Measurement Systems Datascan Installation and User Guide

Measurement Systems Datascan Installation and User Guide Measurement Systems Datascan Installation and User Guide Supplied By Contents Contents 1. INTRODUCTION... 1 1.1 GENERAL... 1 1.2 DATASCAN MODULE RANGE... 1 1.2.1 Measurement Processors... 1 1.2.2 Analog

More information

JUMO ecotrans ph 03 Microprocessor transmitter/ switching device for ph/redox voltage and temperature

JUMO ecotrans ph 03 Microprocessor transmitter/ switching device for ph/redox voltage and temperature Page 1/7 JUMO ecotrans 03 Microprocessor transmitter/ switching device for /Redox voltage and temperature with a 2-line LCD for mounting on a 35 mm DIN rail Brief description Depending on the configuration,

More information

Digital ac/dc (24V) Input Module

Digital ac/dc (24V) Input Module Installation Instructions Digital ac/dc (24V) Input Module Catalog Number 1771-IND, Series C Topic Page Important User Information 2 Before You Begin 3 Power Requirements 3 Prevent Electrostatic Discharge

More information

Allen-Bradley Spares

Allen-Bradley Spares 1 Because of the variety of uses for this product and because of the differences between solid state products and electromechanical products, those responsible for applying and using this product must

More information

INSTALLATION INSTRUCTIONS 921P EntryCheck TM

INSTALLATION INSTRUCTIONS 921P EntryCheck TM 80 Avenida Acaso, Camarillo, Ca. 90 (805) 494-06 www.sdcsecurity.com E-mail: service@sdcsecurity.com INSTALLATION INSTRUCTIONS 9P EntryCheck TM The EntryCheck 9P Indoor/Outdoor Keypad is a surface mount

More information

2.) Cabinet setup and preset data shall, as standard, be fully user programmable on a per cabinet or system wide basis.

2.) Cabinet setup and preset data shall, as standard, be fully user programmable on a per cabinet or system wide basis. A21 DIMMER CABINET SPECIFICATION. GENERAL. A.) Overview. 1.) The dimmer cabinets shall be fully digital, designed specifically for architectural and entertainment lighting applications, and shall consist

More information

Safety Control Relay Product Catalog

Safety Control Relay Product Catalog Product Catalog Wall Mount for use with Safety Mats Safety Edges Safety Bumpers Safety Sensors 2 wire Safety Sensors 4 wire DIN Rail Mount Intrinsically Safe Explosion Proof Wall Mount Introduction The

More information

PG&E Points List for Universal Controls

PG&E Points List for Universal Controls S&C 6800 Series Automatic Switch Control PG&E Points List for Universal Controls Table of Contents Section Page Section Page PG&E Points List for 6802/3 Universal Controls. 1 Response Limit...2 6802/3U

More information

DIN-rail mountable relay unit for commercial control, power switching and home automation applications

DIN-rail mountable relay unit for commercial control, power switching and home automation applications BARIX R6 DIN-rail mountable relay unit for commercial control, power switching and home automation applications PRODUCT MANUAL Version: 01.03 Date: 07/20/2005 For Firmware Version 2 Table of Contents

More information

XRS 3000 Controller Reference Guide V-2

XRS 3000 Controller Reference Guide V-2 XRS 3000 Controller Reference Guide V-2 XRS-3000 1 WHITE MAIN POWER COLLIGHTLIGHT THREE POSITION KEY SWITCH 1. OFF 2. STANDBY 3. ON XRS-3000 SAFETY CIRCUIT ENGAGED X- RAY PREWARNING X- RAY BEING PRODUCED

More information

DMX-DALI-DMX interface

DMX-DALI-DMX interface PX 255 DMX-DALI-DMX interface MANUAL R CONTENTS 1. General description... 3 2. Safety conditions... 3 3. Connections and control elements description... 4 4. Navigating the menu... 4 5. Use of the device...

More information

WILO interface module

WILO interface module 8 665 DESIGO I/O-OPEN WILO interface module for two electronically controlled WILO-heating pumps PTM5016V01 Interface module enabling communication between intelligent heating pumps featuring WILO-interfaces

More information

Product Information. Release 3 4 SIMATIC S7-300

Product Information. Release 3 4 SIMATIC S7-300 Product Information SIMATIC S7-300 Relay Output Module SM 322; DO 8 x REL AC230V/5A X 2 Release 3 4 New Relay Output Module Available The S7-300 Relay Output Module SM 322; DO 8 REL AC230V/5A has been

More information

Chapter 4: Architectural Details

Chapter 4: Architectural Details Chapter 4: Architectural Details The previous chapters covered basic EPROM emulation. We designed several advanced features into UniROM that allows it to do much more than simple emulation. This chapter

More information

INSTALLATION AND OPERATING INSTRUCTIONS DSST SYSTEM

INSTALLATION AND OPERATING INSTRUCTIONS DSST SYSTEM INSTALLATION AND OPERATING INSTRUCTIONS DSST SYSTEM PROPORTIONAL and NON-PROPORTIONAL TOGGLE SWITCH RADIO REMOTE CONTROL SYSTEM MODEL FHSTP/DSSTP SERIES FHST/DSST SYSTEM DESCRIPTION The DSST Wireless Control

More information

Product Information on the Manual

Product Information on the Manual Product Information on the Manual Edition 04.2003 S7-300 Module Specifications, Edition 11/2002, (A5E00105505-02) Introduction The S7-300 product family has been enhanced and improved. This document contains

More information

ICS Regent. Communications Package for W INTERPRET. Guarded Peer-Link Communications (T3831) PD-6041

ICS Regent. Communications Package for W INTERPRET. Guarded Peer-Link Communications (T3831) PD-6041 ICS Regent PD-6041 Communications Package for W INTERPRET Guarded Peer-Link Communications (T3831) Issue 1, March, 06 The WINTERPRET Communications Package is an add-in software package that allows you

More information

Product Information SIMATIC S Digital Output Module SM 322; DO 8 120/230 VAC/2 A ISOL

Product Information SIMATIC S Digital Output Module SM 322; DO 8 120/230 VAC/2 A ISOL Product Information SIMATIC S7-300 Digital Output Module SM 322; DO 8 120/230 VAC/2 A ISOL X 2 Release 3 4 New Digital Output Module Available The S7-300 Digital Output Module SM 322; DO 8 120/230 VAC/2

More information

Technical Manual. KNX/DALI ACTUATOR 1x8 channels Art /70100

Technical Manual. KNX/DALI ACTUATOR 1x8 channels Art /70100 KNX/DALI ACTUATOR 1x8 channels Art. 1630.04140/70100 DATEC ELECTRONIC AG Hochbergerstrasse 60C 4057 Basel Tel. +41 61 633 22 25, Fax. +41 61 633 22 27 www.datec.ch, support@datec.ch Because of continuous

More information

BLH. DXp-40 Interface Manual Allen-Bradley Remote I/O WEIGH SYSTEM TECHNOLOGY. TM014 Rev D 6/1/11 Doc 35105

BLH. DXp-40 Interface Manual Allen-Bradley Remote I/O WEIGH SYSTEM TECHNOLOGY. TM014 Rev D 6/1/11 Doc 35105 WEIGH SYSTEM TECHNOLOGY BLH DXp-40 Interface Manual Allen-Bradley Remote I/O TM014 Rev D 6/1/11 Doc 35105 NOTICE BLH makes no representation or warranties of any kind whatsoever with respect to the contents

More information

MAINS DISTRIBUTION UNIT MDU14-CO

MAINS DISTRIBUTION UNIT MDU14-CO MAINS DISTRIBUTION UNIT MDU14-CO Dual Input Auto Changeover 14 Output Mains Distribution Unit. Handbook Television Systems Limited. Vanwall Road, Maidenhead, Berkshire, SL6 4UB Telephone +44 (0)1628 676200,

More information

Control Indicator Module (CIM) - DNP3 Communications Protocol - TECHNICAL MANUAL

Control Indicator Module (CIM) - DNP3 Communications Protocol - TECHNICAL MANUAL Control Indicator Module (CIM) - DNP3 Communications Protocol - TECHNICAL MANUAL Page 1 of 35 Introduction...4 Basic Operation...5 Front Panel Controls and Indicators...5 Real Time Clock Battery Back Up...7

More information