Safety Considerations Guide

Size: px
Start display at page:

Download "Safety Considerations Guide"

Transcription

1 Trident System Version 1.2 Safety Considerations Guide Triconex An Invensys Company

2 Information in this document is subject to change without notice. Companies, names and data used in examples herein are fictitious unless otherwise noted. No part of this document may be reproduced or transmitted in any form or by any means, electronic or mechanical, for any purpose, without the express written permission of Invensys Systems, Inc Invensys Systems, Inc. All Rights Reserved. Microsoft, Windows, and Windows NT are registered trademarks of Microsoft Corporation. Modbus is a registered trademark of Modicon Corporation. Triconex is a registered trademark of Invensys Systems, Inc.n in the USA and other countries. Cause & Effect Matrix Programming Language Editor (CEMPLE), TriStation 1131, TriStation MSW, Tricon, and Trident are trademarks of Invensys Systems, Inc. in the USA and other countries. All other brands or product names may be trademarks or registered trademarks of their respective owners. Document No Printed in the United States of America.

3 Acknowledgement Triconex acknowledges the generous assistance of TÜV Rheinland/Berlin- Brandenburg in the development of this guide. Their efforts have contributed to the overall quality and integrity of the Trident system. TÜV Rheinland/Berlin-Brandenburg aims to shape technology so that it does not put people and the environment at risk but is of the greatest benefit to them. To achieve this aim, TÜV offers support during the complete life cycle of a product, from concept through development and testing to certification.

4

5 CONTENTS Preface... ix How This Guide Is Organized... ix Related Documents... x Abbreviations Used... xi How to Contact Triconex... xii Requesting Technical Support... xii Gathering Supporting Documentation... xii Contacting Triconex Technical Support... xiii Telephone... xiii Fax... xiii ... xiii Training... xiv Chapter 1 Safety Concepts... 1 Safety Overview... 2 Protection Layers... 3 SIS Factors... 4 SIL Factors... 4 Hazard and Risk Analysis... 5 Safety Integrity Levels... 6 Determining a Safety Integrity Level... 6 Example SIL Calculation... 8 Safety Life Cycle Model Safety Standards General Safety Standards DIN V DIN V VDE IEC 61508, Parts ANSI/ISA S Draft IEC 61511, parts

6 vi Application-Specific Standards DIN VDE EN 54, Part NFPA NFPA NFPA CSA C22.2 NO Chapter 2 Application Guidelines TÜV Rheinland Certification General Guidelines All Safety Systems Emergency Shutdown Systems Burner Management Systems Fire and Gas Systems Guidelines for Trident Controllers Safety-Critical Modules Safety-Shutdown Response Time and Scan Time Disabled Points Alarm Disabled Output Voter Diagnostic Download All at Completion of Project Modbus Master Functions Triconex Peer-to-Peer Communication Sending Node Receiving Node SIL3/AK5 Guidelines Additional Fire and Gas Guidelines SIL3/AK6 Guidelines Additional Fire and Gas Guidelines Project Change and Control Maintenance Overrides Using Serial Communication Additional Recommendations Chapter 3 Fault Management System Architecture System Diagnostics Types of Faults External Faults Internal Faults Operating Modes... 41

7 vii Module Diagnostics Analog Input Modules Analog Input Module Alarms Analog Output Modules Analog Output Module Field Alarms Digital Input Modules Digital Input Module Alarms Digital Output Modules Digital Output Module Alarms Pulse Input Module Pulse Input Module Alarms Solid-State Relay Output Modules Solid-State Relay Output Module Alarms Calculation for Diagnostic Fault Reporting Time Input/Output Processing I/O Module Alarms Main Processor and TriBus External Communication Semaphores MP System Attributes CM System Attributes Chapter 4 Application Development Development Guidelines TriStation Install Check Important TriStation Commands Download Change Upload and Verify Compare to Last Download Setting Scan Time Scan Time Scan Surplus Scan Overrun Sample Safety-Shutdown Programs All I/O Modules Safety-Critical Program EX01_SHUTDOWN Some I/O Modules Safety-Critical Program EX02_SHUTDOWN Defining Function Blocks Partitioned Processes Program EX03_SHUTDOWN... 69

8 viii Alarm Usage Programming Permitted Alarm Remote Access Alarm Response Time Alarm Disabled Points Alarm Appendix A Triconex Peer-to-Peer Communication Data Transfer Time Examples of Peer-to-Peer Applications Fast Send to One Triconex Node Sending Data Every Second to One Node Controlled Use of TR_USEND/TR_URCV Function Blocks Using TR_USEND/TR_URCV Function Blocks for Safety-Critical Data. 75 Sending Node #1 Parameters Receiving Node #3 Parameters Appendix B Function Blocks SYS_CRITICAL_IO Function Block Instructions for Use Structured Text SYS_SHUTDOWN Function Block Structured Text SYS_VOTE_MODE Function Block Structured Text Index... 95

9 Preface This manual provides information about safety concepts and standards that apply to the Trident controller. How This Guide Is Organized This manual is organized as follows: Chapter 1, Safety Concepts Describes safety issues, safety standards, and implementation of safety measures. Chapter 2, Application Guidelines Provides information on industry guidelines and recommendations. Chapter 3, Fault Management Discusses fault tolerance and fault detection. Chapter 4, Application Development Discusses methods for developing applications properly to avoid application faults. Appendix B, Function Blocks Describes the function blocks intended for use in safety-critical applications and shows their Structured Text code.

10 x Related Documents Related Documents The following manuals contain information that is relevant to the use of the system. Trident Planning and Installation Guide TriStation 1131 Developer's Guide for Trident Systems TriStation 1131 Getting Started for Trident Users TriStation 1131 Triconex Libraries Reference

11 Abbreviations Used xi Abbreviations Used The controller is hereafter called Trident, except in cases where the full name must be used to ensure clarity. The TriStation 1131 Developer s Workbench is hereafter called TriStation. The following list provides full names for abbreviations of safety terms used in this guide. BPCS ESD HAZOP MOC MTBF PES PFD PHA PSM RMP RRF SIL SIS SOV SRS SV Basic process control system Emergency shutdown Hazard and operability study Management of change Mean time between failure Programmable electronic system Probability to fail on demand Process hazard analysis Process safety management Risk management program Risk reduction factor Safety integrity level Safety-instrumented system Solenoid-operated valve Safety requirements specification Safety (relief) valve Preface

12 xii How to Contact Triconex How to Contact Triconex You can obtain sales information and technical support for Triconex products from any regional customer center or from corporate headquarters. To locate regional centers, go to the Global Locator page on the Triconex Web site at: Requesting Technical Support You can obtain technical support from any regional center and from offices in Irvine, California and Houston, Texas. If you require emergency or immediate response and are not a participant in the System Maintenance Program (SMP), you may incur a charge. After-hours technical support is billed at the rate specified in the current Customer Satisfaction Price List. Requests for support are prioritized as follows: Emergency requests are given the highest priority Requests from SMP participants and customers with purchase order or charge card authorization are given next priority All other requests are handled on a time-available basis Gathering Supporting Documentation Before contacting corporate technical support, please try to solve the problem by referring to the Triconex documentation. If you are unable to solve the problem, obtain the following information: Error messages and other indications of the problem Sequence of actions leading to the problem Actions taken after the problem occurred If the problem involves a Triconex controller, obtain the model numbers and revision levels for all affected items. This information can be found on the modules, in the System Log Book, or on the TriStation Diagnostic Panel. If the problem involves software, obtain the product version number by selecting the About topic from the Help menu.

13 Requesting Technical Support xiii Contacting Triconex Technical Support If possible, you should contact your regional customer center for assistance. If you cannot contact your regional center, contact technical support for the type of system you are using, either ESD systems or Turbomachinery systems. Please include the following information in your message: Your name and your company name Your location (city, state, and country) Your phone number (area code and country code, if applicable) The time you called Whether this is an emergency Note If you require emergency support and are not an SMP participant, please have a purchase order or credit card available for billing. Emergency calls are responded to on a 24-hour daily basis. Telephone Toll-free number 866-PHON IPS ( ), or Toll number Fax Send your request to the Technical Support Manager. Toll-free number , or Toll number ips.csc@invensys.com Preface

14 xiv Training Training In addition to this documentation, Triconex offers in-house and on-site training. For information on available courses, please contact your regional customer center.

15 CHAPTER 1 Safety Concepts This chapter describes background information about safety concepts and standards. Topics include: Safety Overview Hazard and Risk Analysis Safety Standards Application-Specific Standards

16 2 Safety Overview Safety Overview Modern industrial processes tend to be technically complex, involve substantial energies, and have the potential to inflict serious harm to persons or property during a mishap. The IEC standard defines safety as freedom from unacceptable risk. In other words, absolute safety can never be achieved; risk can only be reduced to an acceptable level. Safety methods to mitigate harm and reduce risk include: Changing the process or mechanical design, including plant or equipment layout Increasing the mechanical integrity of equipment Improving the basic process control system (BPCS) Developing additional or more detailed training procedures for operations and maintenance Increasing the testing frequency of critical components Using a SIS (safety-instrumented system) Installing mitigating equipment to reduce harmful consequences; for example, explosion walls, foams, impoundments, and pressure relief systems Methods that provide layers of protection should be: Independent Verifiable Dependable Designed for the specific safety risk

17 Safety Overview 3 Protection Layers The figure below shows how layers of protection can be used to reduce unacceptable risk to an acceptable level. The amount of risk reduction for each layer is dependent on the specific nature of the safety risk and the impact of the layer on the risk. Economic analysis should be used to determine the appropriate combination of layers for mitigating safety risks. Acceptable Risk Level Mechanical Integrity Inherent Process Risk SV SIS BPCS* Effect of Protection Layers on Process Risk 0 Lower Risk Process Higher Risk * BPCS Basic process control system SIS Safety-instrumented system SV Safety (relief) valve When an SIS is required, one of the following should be determined: Level of risk reduction assigned to the SIS Safety integrity level (SIL) of the SIS Typically, a determination is made according to the requirements of the ANSI/ISA S84.01 or IEC standards during a process hazard analysis (PHA). A process demand is defined as the occurrence of a process deviation that causes an SIS to transition a process to a safe state. Chapter 1 Safety Concepts

18 4 Safety Overview SIS Factors According to the ANSI/ISA S84.01 and IEC standards, the scope of an SIS is restricted to the instrumentation or controls that are responsible for bringing a process to a safe state in the event of a failure. The availability of an SIS is dependent upon: Failure rates and modes of components Installed instrumentation Redundancy Voting Diagnostic coverage Testing frequency SIL Factors A SIL can be considered a statistical representation of the availability of an SIS at the time of a process demand. A SIL is the litmus test of acceptable SIS design and includes the following factors: Device integrity Diagnostics Systematic and common cause failures Testing Operation Maintenance In modern applications, a programmable electronic system (PES) is used as the core of a SIS. The Triconex controller is a state-of-the-art PES optimized for safety-critical applications.

19 Hazard and Risk Analysis 5 Hazard and Risk Analysis In the United States, OSHA Process Safety Management (PSM) and EPA Risk Management Program (RMP) regulations dictate that a PHA be used to identify potential hazards in the operation of a chemical process and to determine the protective measures necessary to protect workers, the community, and the environment. The scope of a PHA may range from a very simple screening analysis to a complex hazard and operability study (HAZOP). A HAZOP is a systematic, methodical examination of a process design that uses a multi-disciplinary team to identify hazards or operability problems that could result in an accident. A HAZOP provides a prioritized basis for the implementation of risk mitigation strategies, such as SISs or ESDs. If a PHA determines that the mechanical integrity of a process and the process control are insufficient to mitigate the potential hazard, an SIS is required. An SIS consists of the instrumentation or controls that are installed for the purpose of mitigating a hazard or bringing a process to a safe state in the event of a process upset. A compliant program incorporates good engineering practice. This means that the program follows the codes and standards published by such organizations as the American Society of Mechanical Engineers, American Petroleum Institute, American National Standards Institute, National Fire Protection Association, American Society for Testing and Materials, and National Board of Boiler and Pressure Vessel Inspectors. Other countries have similar requirements. Chapter 1 Safety Concepts

20 6 Hazard and Risk Analysis Safety Integrity Levels The figure below shows the relationship of DIN V classes and SILs (safety integrity levels). As a required SIL increases, SIS integrity increases as measured by: System availability (expressed as a percentage) Average probability to fail on demand (PFD avg ) Risk reduction factor (RRF, reciprocal of PFD avg ) The relationship between AK class and SIL is extremely important and should not be overlooked. These designations were developed in response to serious incidents that resulted in the loss of life, and are intended to serve as a foundation for the effective selection and appropriate design of safety-instrumented systems. R i s k >10,000 SIL 4 AK 8 AK 7 Standards and Risk Measures R e d u c t I o n Percent Availability PFD avg 10,000 1,000 1, RRF SIL 3 SIL 3 SIL 2 SIL 2 SIL 1 ANSI/ISA S84.01 SIL 1 IEC AK 6 AK 5 AK 4 AK 3 AK 2 AK 1 DIN V Risk Measures Risk Standards Determining a Safety Integrity Level If a PHA (process hazard analysis) concludes that an SIS is required, ANSI/ISA S84.01 and IEC require that a target SIL be assigned. The assignment of a SIL is a corporate decision based on risk management and risk tolerance philosophy. Safety regulations require that the assignment of SILs should be carefully performed and thoroughly documented.

21 Hazard and Risk Analysis 7 Completion of a HAZOP determines the severity and probability of the risks associated with a process. Risk severity is based on a measure of the anticipated impact or consequences, including: On-site consequences Worker injury or death Equipment damage Off-site consequences Community exposure, including injury and death Property damage Environmental impact Emission of hazardous chemicals Contamination of air, soil, and water supplies Damage to environmentally sensitive areas A risk probability is an estimate of the likelihood that an expected event will occur. A risk probability is classified as high, medium, or low, and is often based on a company s or a competitor s operating experience. Several methods of converting HAZOP data into SILs are used. Methods range from making a corporate decision on all safety system installations to more complex techniques, such as an IEC risk graph. Chapter 1 Safety Concepts

22 8 Hazard and Risk Analysis Example SIL Calculation As a PES, the controller is designed to minimize its contribution to the SIL, thereby allowing greater flexibility in the SIS design. Comparison of Percent Availability and PFD R i s k R e d u c t I o n Percent Availability Risk Measures PFD Trident PES* SIL 3 SIS * Trident controller failure rates have been independently calculated by Factory Mutual System. A copy of Factory Mutual Technical Report, Calculation of the Probability of Failure-On-Demand (PFD) for the Triconex Trident System, FMRC J.I , is available upon request. Safety Integrated System Simplified Diagram of Key Elements 3 Pressure Transmitters (2oo3) Sensors TMR Controller (2oo3) PES/Logic Solver 2 Block Valves in Series (1oo2) Final Elements 3 Temperature Transmitters (2oo3)

23 Hazard and Risk Analysis 9 Equation for Calculating PFD avg for Sensors The following simplified equation may be used to calculate PFD avg for sensors (2oo3): PFD avg = (λ DU *TI) 2 where the following variables are supplied by the manufacturer: λ = failure rate DU = dangerous, undetected failure rate TI = test interval in hours Equation for Calculating PFD avg for Block Valves The following simplified equation may be used to calculate PFD avg for block valves (1oo2) in series (final elements): PFD avg = 1/3(λ DU *TI) 2 where the following variables are supplied by the manufacturer: λ = failure rate DU = dangerous, undetected failure rate TI = test interval in hours Equation for Calculating PFD avg for System The following simplified equation may be used to calculate PFD avg for a system. System PFD avg = Sensors PFD avg + Block Valves PFD avg + Controller PFD avg Chapter 1 Safety Concepts

24 10 Hazard and Risk Analysis Using the Equations λdu TI PFDResult Pressure Transmitters (2oo3) 2.28E E-04 Temperature Transmitters (2oo3) 2.85E E-04 Total for Sensors 2.56E-04 Block Valves (1oo2) 2.28E E-05 Total for Block Valves 3.33E-05 Trident Controller PFD avg for System 1.00E E-04 To determine the SIL, compare the calculated PFD avg to the figure on page 8. In this example, the system is acceptable as an SIS for use in SIL3 applications. Safety Life Cycle Model The necessary steps for designing an SIS from conception through decommissioning are described in the safety life cycle. Before the safety life cycle model is implemented, the following requirements should be met: Hazard and operability study has been completed SIS requirement has been determined Target SIL has been determined

25 Hazard and Risk Analysis 11 Safety Life Cycle Model Start Design conceptual process Perform process hazard analysis and risk assessment Apply non-sis protection layers to prevent identified hazards or reduce risk Develop safety requirements document Perform SIS conceptual design and verify it meets the SRS Perform SIS detail design Establish operation and maintenance procedure Pre-start-up safety review assessment SIS start-up operation, maintenance, periodic functional testing Exit No SIS required? Yes Define target SIL SIS installation, commissioning, and pre-startup acceptance test Conceptual process design Modify Modify or decommission SIS? Decommission SIS decommissioning S84.01 Concern Chapter 1 Safety Concepts

26 12 Hazard and Risk Analysis PES Steps in a Safety Life Cycle: 1 Develop a safety requirement specification. An SRS consists of safety functional requirements and safety integrity requirements. An SRS can be a collection of documents or information. Safety functional requirements specify the logic and actions to be performed by an SIS and the process conditions under which actions are initiated. These requirements include such items as consideration for manual shutdown, loss of energy source, etc. Safety integrity requirements specify a SIL and the performance required for executing SIS functions. Safety integrity requirements include: Required SIL for each safety function Requirements for diagnostics Requirements for maintenance and testing Reliability requirements if the spurious trips are hazardous 2 For conceptual design, an engineer should: Define the SIS architecture to ensure the SIL is met; e.g. voting 1oo1, 1oo2, 2oo2, 2oo3 Define the logic solver to meet the highest SIL if different SIL levels are required in a single logic solver Select a functional test interval to achieve the SIL Verify the conceptual design against the SRS 3 Develop a detail design including: General requirements SIS logic solver Field devices Interfaces Energy sources System environment Application logic requirements Maintenance or testing requirements

27 Hazard and Risk Analysis 13 Some key ANSI/ISA S84.01 requirements are: The logic solver shall be separated from the basic process control system. Sensors for SIS shall be separated from the sensors for the BPCS. The logic system vendor shall provide: MTBF data Covert failure listing Frequency of occurrence of identified covert failures Triconex controllers do not contain covert failures (undiagnosed dangerous faults) that are statistically significant Each individual field device shall have its own dedicated wiring to the system I/O. Using a field bus is not allowed! A control valve from the BPCS shall not be used as a single final element for SIL3. The operator interface may not be allowed to change the SIS application software. Maintenance overrides shall not be used as a part of application software or operating procedures. When online testing is required, test facilities shall be an integral part of the SIS design. 4 Develop a pre-start-up acceptance test procedure that provides a fully functional test of the SIS to verify conformance with the SRS. 5 Before startup, establish operational and maintenance procedures to ensure that the SIS functions comply with the SRS throughout the SIS operational life, including: Training Documentation Operating procedures Maintenance program Testing and preventive maintenance Functional testing Documentation of functional testing 6 Before start-up, complete a safety review. Chapter 1 Safety Concepts

28 14 Hazard and Risk Analysis 7 Define procedures for the following: Start-up Operations Maintenance, including administrative controls and written procedures that ensure safety if a process is hazardous while an SIS function is being bypassed Training that complies with national regulations (e.g., OSHA 29 CFR ) Functional testing to detect covert faults that prevent the SIS from operating according to the SRS SIS testing, including: Sensors Logic solver Final elements (e.g., shutdown valves, motors, etc.) 8 To ensure that no unauthorized changes are made to an application, as mandated by OSHA 29 CFR , follow management of change (MOC) procedures. 9 To ensure proper review, decommission an SIS before its permanent retirement from active service.

29 Safety Standards 15 Safety Standards Over the past several years, there has been rapid movement in many countries to develop standards and regulations to minimize the impact of industrial accidents on citizens. The standards described below apply to typical applications. General Safety Standards DIN V In Germany, the methodology of defining the risk to individuals is established in DIN V 19250, Control Technology; Fundamental Safety Aspects To Be Considered for Measurement and Control Equipment. DIN V establishes the concept that safety systems should be designed to meet designated classes, Class 1 (AK1) through Class 8 (AK8). The choice of the class is dependent on the level of risk posed by the process. DIN V attempts to force users to consider the hazards involved in their processes and to determine the integrity of the required safety-related system. DIN V VDE 0801 As the use of programmable electronic systems in safety system designs has become prevalent, it is necessary to determine whether the design of a PES is sufficiently rigorous for the application and for the DIN V class. DIN V VDE 0801, Principles for Computers in Safety-Related Systems, sets forth the following specific measures to be used in evaluating a PES: Design Coding (system level) Implementation and integration Validation Each measure is divided into specific techniques that can be thoroughly tested and documented by independent persons. Thus, DIN V VDE 0801 provides a means of determining if a PES meets certain DIN V classes. Chapter 1 Safety Concepts

30 16 Safety Standards IEC 61508, Parts 1 7 The IEC standard, Functional Safety: Safety Related Systems, is an international standard designed to address a complete SIS for the process, transit, and medical industries. The standard introduces the concept of a safety life cycle model (see figure on page 10) to illustrate that the integrity of an SIS is not limited to device integrity, but is also a function of design, operation, testing, and maintenance. The standard includes 4 SILs that are indexed to a specific probability-to-fail-ondemand (PFD) (see figure on page 6). A SIL assignment is based on the required risk reduction as determined by a PHA. ANSI/ISA S84.01 ANSI/ISA S is the United States standard for safety systems in the process industry. The SIL classes from IEC are used and the DIN V relationships are maintained. ANSI/ISA S does not include the highest SIL class, SIL 4. The S84 Committee determined that SIL 4 is applicable for medical and transit systems in which the only layer of protection is the safetyinstrumented layer. In contrast, the process industry can integrate many layers of protection in the process design. The overall risk reduction from these layers of protection is equal to or greater than that of other industries. Draft IEC 61511, parts 1 3 The IEC standard, Functional Safety: Safety Instrumented Systems for the Process Industry Sector, is an international standard designed to be used as a companion to IEC IEC is intended primarily for manufacturers and suppliers of devices. IEC is intended for SIS designers, integrators, and users in the process-control industry.

31 Safety Standards 17 Application-Specific Standards DIN VDE 0116 DIN VDE 0116 Electrical Equipment Of Furnaces, outlines the German requirements for burner management applications. EN 54, Part 3 EN 54, Part 3, Components of Automatic Fire Detection System: Control and Indicating Equipment, outlines the European requirements for fire detection systems. NFPA 72 NFPA 72, National Fire Alarm Code, outlines the United States requirements for fire alarm systems. NFPA 8501 NFPA 8501, Standard for Single Burner Boiler Operation, outlines the United States requirements for operations using single burner boilers. NFPA 8502 NFPA 8502, Standard for the Prevention of Furnace Explosions/Implosions in Multiple Burner Boilers, outlines the United States requirements for operations using multiple burner boilers. CSA C22.2 NO 199 CSA C22.2 NO 199, Combustion Safety Controls and Solid-State Igniters for Gas and Oil-Burning Equipment, outlines the Canadian requirements for burner management applications. Chapter 1 Safety Concepts

32 18 Safety Standards

33 CHAPTER 2 Application Guidelines This chapter provides information on industry guidelines. Topics include: TÜV Rheinland Certification General Guidelines Guidelines for Trident Controllers

34 20 TÜV Rheinland Certification TÜV Rheinland Certification When used as a PES in an SIS, the Trident controller and its companion programming workstation, the TriStation 1131 Developer s Workbench, have been certified by TÜV Rheinland/Berlin-Brandenburg to meet the requirements of DIN AK5-AK6 and IEC SIL3. If these standards apply to your application, compliance with the guidelines described in this chapter is highly recommended. General Guidelines All Safety Systems This section describes standard industry guidelines that apply to: All safety systems Emergency shutdown (ESD) systems Fire and gas systems Burner management systems The following general guidelines apply to all user-written safety applications and procedures: Functional testing is recommended to verify the correct design and operation. After a safety system is commissioned, no changes to the system software (operating system, I/O drivers, diagnostics, etc.) are allowed without type approval and re-commissioning. Any changes to the application or the control application should be made under strict change-control procedures. For more information on change-control procedures, see Project Change and Control on page 30. All changes should be thoroughly reviewed, audited, and approved by a safety change control committee or group. After an approved change is made, it should be archived. In addition to printed documentation of the application, two copies of the application should be archived on an electronic medium that is writeprotected to avoid accidental changes.

35 General Guidelines 21 Under certain conditions, a PES may be run in a mode that allows an external computer or operator station to write to system attributes. This is normally done by means of a communication link. The following guidelines apply to writes of this type: Serial communication should use Modbus or another approved protocol with CRC checks. Serial communication should not be allowed to write directly to output points For information about writes to safety-related variables that result in disabling safety action, see External Communication on page 47. PID and other control algorithms should not be used for safety-related functions. Each control function should be checked to verify that it does not provide a safety-related function. An SIS PES should be wired and grounded according to the procedures defined by the manufacturer. Emergency Shutdown Systems The safe state of the plant should be a de-energized or low (0) state. For ESD functions, it is recommended that the hardware devices connected to PES outputs should be made of fail-safe components or should have two separate, independent shutdown paths that are periodically inspected. Burner Management Systems The safe state of the plant should be a de-energized or low (0) state. When a safety system is required to conform with the DIN 0116 standard for electrical equipment in furnaces, PES throughput time should ensure that a safe shutdown can be performed within 1 second after a problem in the process is detected. Chapter 2 Application Guidelines

36 22 General Guidelines Fire and Gas Systems Fire and gas applications typically do not have a safe state and should operate continuously to provide protection. The following industry guidelines apply: If inputs and outputs are energized to mitigate a problem, a PES system should detect and alarm open and short circuits in the wiring between the PES and the field devices. An entire PES system should have redundant power supplies. Also, the power supplies that are required to activate critical outputs and read safetycritical inputs should be redundant. All power supplies should be monitored for proper operation. De-energized outputs may be used for normal operation. To initiate action to mitigate a problem, the outputs are energized. This type of system should monitor the critical output circuits to ensure that they are properly connected to the end devices.

37 Guidelines for Trident Controllers 23 Guidelines for Trident Controllers The following topics relate to industry guidelines that are specific to Trident controllers when used as a PES in an SIS: Safety-critical modules Safe shutdown Programming lockout alarm Remote access alarm Scan time and response time alarm Disabled points alarm Disabled output voters Download all Modbus master functions Triconex Peer-to-Peer communication SIL3/AK5 guidelines SIL3/AK5 fire and gas guidelines SIL3/AK6 guidelines SIL3/AK6 fire and gas guidelines Project change and control Chapter 2 Application Guidelines

38 24 Guidelines for Trident Controllers Safety-Critical Modules It is recommended that only the following modules be used for safety-critical applications: Main Processor Module Communication Module Analog Input Module Analog Output Module Digital Input Module Digital Output Module Pulse Input Module The Solid-State Relay Output Module is recommended for non-safety-critical points only. Safety-Shutdown A safety application should include a network that initiates a safe shutdown of the process being controlled when a controller operates in a degraded mode for a specified maximum time. The Triconex Library provides two function blocks to simplify programming a safety-shutdown application: SYS_SHUTDOWN and SYS_CRITICAL_IO. To see the Structured Text code for these function blocks, see Appendix B, Function Blocks. For more information on safety-shutdown networks, see Sample Safety- Shutdown Programs on page 57. Response Time and Scan Time Scan time must be set below 50 percent of the required response time. If scan time is greater than 50 percent, an alarm should be triggered. Disabled Points Alarm A project should not contain disabled points unless there is a specific reason for disabling them, such as initial testing. An alarm should be available to alert the operator that a point is disabled.

39 Guidelines for Trident Controllers 25 Disabled Output Voter Diagnostic A safety application must not disable the output voter diagnostic. Download All at Completion of Project When development and testing of a safety application is completed, use the Download All command on the Control Panel to completely re-load the application to the controller. Modbus Master Functions Modbus Master functions are designed for use with non-critical I/O points only. These functions should not be used for safety-critical I/O points or for transferring safety-critical data using the MBREAD and MBWRITE functions. Triconex Peer-to-Peer Communication Triconex Peer-to-Peer communication enables Triconex controllers (also referred to as nodes) to send and receive information. You should use a redundant Peer-to- Peer network for safety-critical data. If a node sends critical data to another node that makes safety-related decisions, you must ensure that the application on the receiving node can determine whether it has received new data. If new data is not received within the time-out period (equal to half of the processtolerance time), the application on the receiving node should be able to determine the action to take. The specific actions depend on the unique safety requirements of your process. The following sections summarize actions typically required by Peer-to-Peer send and receive functions. Sending Node The actions typically required in the sending application include the following: To send data as quickly as possible, the sending node must set the SENDFLG parameter in the send function to true (1) to ensure new data is sent following the acknowledgment that data was received by the receiving node. Chapter 2 Application Guidelines

40 26 Guidelines for Trident Controllers A TR_USEND-type function block must include a diagnostic variable that is changed each time data is sent. By monitoring this variable, the receiving node can determine whether it has received new data. This diagnostic variable is required because the communication path is not triplicated like the I/O system. The number of TR_USEND functions in an application must be less than or equal to ten because the controller only initiates ten TR_USEND functions per scan. The status of the TR_USEND and TR_PORT_STATUS functions should be monitored in case a network problem requires operator intervention. Receiving Node The actions typically required in the receiving application include the following: If new data is not received within the time-out period, take one of the following actions: Use the last data received for safety-related decisions Use default values for safety-related decisions in the application A diagnostic variable in a TR_USEND-type function block that changes with each new message should be monitored to determine whether a new message has been received. The status of the TR_URCV and TR_PORT_STATUS functions should be monitored in case a network problem requires operator intervention. For information on data transfer time and examples of how to use Peer-to-Peer functions to transfer safety-critical data, see Appendix A, Triconex Peer-to-Peer Communication on page 71.

41 Guidelines for Trident Controllers 27 SIL3/AK5 Guidelines For SIL3/AK5 applications, the following guidelines should be followed: If non-approved modules are used, the inputs and outputs should be checked to verify that they do not affect safety-critical functions of the controller. Two modes control write operations from external hosts: Remote Mode When true, external hosts, such as Modbus master, DCS, etc., can write to aliased variables in the controller. When false, writes are prohibited. Program Mode When true, changes can be made that modify the behavior of the currently running application. For example, Download All, Download Change, declaring variables, enabling/disabling variables, changing values of variables and scan time, etc. Remote mode and program mode are independent of each other. In safety applications, operation in these modes is not recommended. In other words, write operations to the controller from external hosts should be prohibited. If remote mode or program mode becomes true, the application should include the following safeguards: When remote mode is true: The application should turn on an alarm. For example, if using the SYS_SHUTDOWN function block, the ALARM_REMOTE_ACCESS output could be used. Verify that aliased variables adhere to the guidelines described in Maintenance Overrides on page 32. When program mode is true: The application should turn on an alarm. For example, if using the SYS_SHUTDOWN function block, the ALARM_PROGRAMMING_PERMITTED output could be used. Wiring and grounding procedures outlined in the Trident Planning and Installation Guide should be followed. Maintenance instructions outlined in the Trident Planning and Installation Guide should be followed. If degradation to dual mode occurs, repair efforts should be timely. To ensure maximum availability, limits for maximum time in degraded mode should not be imposed. Chapter 2 Application Guidelines

42 28 Guidelines for Trident Controllers If degradation to single mode occurs, continued operation without repair should be limited to 72 hours (three days). The GATENB function allows external hosts to write selected aliased variables even when the remote mode is false. A network using the GATENB function should be thoroughly validated to ensure that only the intended aliased variable range is used. Peer-to-Peer communication must be programmed according to the recommendations in Triconex Peer-to-Peer Communication on page 25. Additional Fire and Gas Guidelines Analog input cards with current loop terminations should be used to read digital inputs. Opens and shorts in the wiring to the field devices should be detectable. The Triconex library function, LINEMNTR, should be used to simplify application development. A controller should be powered by two independent sources. If degradation to dual mode or single mode occurs, repairs should be timely. To ensure maximum availability, limits for maximum time in degraded mode should not be imposed.

43 Guidelines for Trident Controllers 29 SIL3/AK6 Guidelines For SIL3/ AK6 applications, the following guidelines should be followed: DIN V VDE 19250/AK6 applications that require continued operation after detecting an output failure must have a secondary means of operating the output. A secondary means may be an external group relay or a single point on an independent output module that controls a group of outputs. If a relay is used, it should be checked at least every six months, manually or automatically. If non-approved modules are used, the inputs and outputs should be checked to verify that they do not affect safety-critical functions of the controller. Two modes control write operations from external hosts: Remote Mode When true, external hosts, such as Modbus master, DCS, etc., can write aliased data in the controller. When false, writes are prohibited. Program Mode When true, changes can be made that modify the behavior of the currently running application. For example, Download All, Download Change, declaring variables, enabling/disabling variables, changing values of variables and scan time, etc. Remote mode and program mode are independent of each other. In safety applications, operation in these modes is not recommended. In other words, write operations to the controller from external hosts should be prohibited. If remote mode or program mode becomes true, the application should include the following safeguards: When remote mode is true: The application should turn on an alarm. For example, if using the SYS_SHUTDOWN function block, the ALARM_REMOTE_ACCESS output could be used. Verify that aliased variables adhere to the guidelines described in Maintenance Overrides on page 32. When program mode is true: The application should turn on an alarm. For example, if using the SYS_SHUTDOWN function block, the ALARM_PROGRAMMING_PERMITTED output could be used. Wiring and grounding procedures outlined in the Trident Planning and Installation Guide should be followed. Chapter 2 Application Guidelines

44 30 Guidelines for Trident Controllers Maintenance instructions outlined in the Trident Planning and Installation Guide should be followed. If degradation to dual mode occurs, repair efforts should be timely. To ensure maximum availability, limits for maximum time in degraded mode should not be imposed. If degradation to single mode occurs, continued operation without repair should be limited to 1 hour. The GATENB function allows external hosts to write selected aliased variables even when the remote mode is false. A network using the GATENB function should be thoroughly validated to ensure that only the intended aliased variable range is used. Peer-to-Peer communication must be programmed according to the recommendations in Triconex Peer-to-Peer Communication on page 25. Additional Fire and Gas Guidelines Project Change and Control Analog input cards with current loop terminations should be used to read digital inputs. Opens and shorts in the wiring to the field devices should be detectable. The Triconex library function, LINEMNTR, should be used to simplify application development. A controller should be powered by two independent sources. If degradation to dual mode or single mode occurs, repairs should be timely. To ensure maximum availability, limits for maximum time in degraded mode should not be imposed. A change to a project, however minor, should comply with the guidelines of your organization s Safety Change Control Committee (SCCC). The following steps are recommended: 1 Generate a change request defining all changes and reasons for changes, then obtain approval for the changes from the Safety Change Control Committee. 2 Develop a specification for changes, including a test specification, then obtain approval for the specification from the SCCC. 3 Make the appropriate changes to the project, including those related to design, operation, or maintenance documentation.

45 Guidelines for Trident Controllers 31 4 To verify that the configuration in the controller matches the last downloaded configuration, use the Upload and Verify command on the Control Panel. For details, see Upload and Verify in the TriStation 1131 Developer's Guide. 5 Compare the configuration in your project with the configuration that was last downloaded to the controller by printing the Configuration Differences report from the Configuration editor. For details, see Compare to Last Download in the TriStation 1131 Developer's Guide. 6 Print all logic elements and verify that the changes to networks within each element do not affect other sections of the application. 7 Test the changes according to the test specification by using the Emulator Control Panel. 8 Write a test report. 9 Review and audit all changes and test results with the SCCC. 10 When approved by the SCCC, download the changes to the controller. You may make minor changes online only if the changes are absolutely necessary and are tested thoroughly. To enable a Download Change command, select the Enable Programming option in the Set Programming Mode dialog box on the Control Panel if it is not already selected. Note Changing the operating mode to PROGRAM should generate an alarm to remind the operator to return the operating mode to run as soon as possible after the Download Change. For more information, see Programming Permitted Alarm on page Save the downloaded project in TriStation and back up the project. 12 Archive two copies of the project file and all associated documentation. Chapter 2 Application Guidelines

46 32 Guidelines for Trident Controllers Maintenance Overrides Three methods can be used to check safety-critical devices connected to controllers: Special switches are connected to inputs to a controller that deactivate the actuators and sensors undergoing maintenance. The maintenance condition is handled in the logic of the control application. Sensors and actuators are electrically disconnected from a controller and manually checked using special measures. Serial communication to a controller activates the maintenance override condition. This method is useful when space is limited and the maintenance console should be integrated with the operator display. Using Serial Communication For maintenance overrides, two options for serial connection are available: DCS connection using Modbus RTU protocol (or another approved serial protocol). TriStation PC connection, which requires additional, industry-standard safety measures in a controller to prevent downloading a program change during maintenance intervals. For more information on TriStation, see Alarm Usage on page 70.

47 Guidelines for Trident Controllers 33 Design Requirements The following table describes design requirements for handling maintenance overrides when using serial communication. Design Requirements Control program logic and the controller configuration determine whether the desired signal can be overridden Control program logic and/or system configuration specify whether simultaneous overriding in independent parts of the application is acceptable Controller activates the override. The operator should confirm the override condition Direct overrides on inputs and outputs are not allowed, but should be checked and implemented in relation to the application. Multiple overrides in a controller are allowed as long as only one override applies to each safetycritical group. The controller alarm should not be overridden DCS warns the operator about an override condition. The operator continues to receive warnings until the override is removed A second way to remove the maintenance override condition should be available If urgent, a maintenance engineer may remove the override using a hard-wired switch DCS Project Engineer, Commissioner Project Engineer Operator, Maintenance Engineer Project Engineer Project Engineer, Commissioner Project Engineer Responsible Person TriStation Project Engineer, Commissioner Project Engineer, Type Approval Maintenance Engineer, Type Approval Project Engineer, Type Approval N/A Maintenance Engineer, Type Approval Chapter 2 Application Guidelines

48 34 Guidelines for Trident Controllers Design Requirements During an override, proper operating measures should be implemented. The time span for overriding should be limited to one shift (typically no longer than 8 hours). A maintenance override switch (MOS) light on the operator console should be provided (one per a controller or process unit) DCS Project Engineer, Commissioner, DCS, TriStation Responsible Person TriStation Operating Requirements The following table describes operating requirements for handling maintenance overrides when using serial communication. Operating Requirements DCS Responsible Person TriStation Maintenance overrides are enabled for an entire controller or for a subsystem (process unit) Controller activates an override. The operator should confirm the override condition Controller removes an override Operator, Maintenance Engineer Operator, Maintenance Engineer Operator, Maintenance Engineer Maintenance Engineer, Type Approval Maintenance Engineer, Type Approval Maintenance Engineer

Removal of Hardware ESD, Independent of Safety Logic Solver

Removal of Hardware ESD, Independent of Safety Logic Solver Removal of Hardware ESD, Independent of Safety Logic Solver by Sam Roy Executive summary This is a discussion to remove independent hardware based Emergency Shutdown for Logic Solver as identified in ANSI/ISA-84.00.01-2004,

More information

Point Level Transmitters. Pointek CLS200 (Standard) Functional Safety Manual 02/2015. Milltronics

Point Level Transmitters. Pointek CLS200 (Standard) Functional Safety Manual 02/2015. Milltronics Point Level Transmitters Pointek CLS200 (Standard) Functional Safety Manual 02/2015 Milltronics Introduction 1 General safety instructions 2 Pointek Level Instruments Device-specific safety instructions

More information

Functional Safety Processes and SIL Requirements

Functional Safety Processes and SIL Requirements Functional Safety Processes and SIL Requirements Jordi Campos Tüv Süd Process Safety Business Manager Jordi.campos@tuev-sued.es 15-07-14 Terminology Safety Instrumented Systems (SIS) Safety Integrity Level

More information

T72 - Process Safety and Safety Instrumented Systems

T72 - Process Safety and Safety Instrumented Systems T72 - Process Safety and Safety Instrumented Systems Comprehensive Solutions Portfolio for Fail-Safe to TMR Safety Applications PUBLIC Copyright 2018 Rockwell Automation, Inc. All Rights Reserved. 1 Agenda

More information

ED17: Architectures for Process Safety Applications

ED17: Architectures for Process Safety Applications ED17: Architectures for Process Safety Applications Name Pete Skipp Title Process Safety Architect Date November 5 th & 6 th 2012 Copyright 2012 Rockwell Automation, Inc. All rights reserved. Agenda An

More information

Using smart field devices to improve safety system performance

Using smart field devices to improve safety system performance Using smart field devices to improve safety system performance Safety monitoring software can use data from smart field devices to improve safety system performance and operation By Guillermo Pacanins,

More information

T57 - Process Safety and Critical Control What Solution Best Meets Your Needs?

T57 - Process Safety and Critical Control What Solution Best Meets Your Needs? PUBLIC - 5058-CO900H T57 - Process Safety and Critical Control What Solution Best Meets Your Needs? PUBLIC PUBLIC Agenda Introduction To Process Safety Process Safety and Machine Safety Things to Consider

More information

Functional safety manual RB223

Functional safety manual RB223 SD00011R/09/EN/13.13 71238251 Products Solutions Services Functional safety manual RB223 Passive barrier Application Galvanic isolation of active 0/4 to 20 ma signals from transmitters, valves and adjusters,

More information

Type 9160 / Transmitter supply unit / Isolating repeater. Safety manual

Type 9160 / Transmitter supply unit / Isolating repeater. Safety manual Type 9160 / 9163 Transmitter supply unit / Isolating repeater Safety manual Safety manual English Content 1 General information... 3 1.1 Manufacturer... 3 1.2 Information regarding the Safety Manual...

More information

Proline Prowirl 72, 73

Proline Prowirl 72, 73 Functional Safety Manual Vortex flow measuring system with 4 20 ma output signal Application Monitoring of maximum and/or minimum flow in systems which are required to comply with particular safety system

More information

Mobrey Hydratect 2462

Mobrey Hydratect 2462 Mobrey Hydratect 2462 Functional Safety Manual Functional Safety Manual Functional Safety Manual Table of Contents Contents 1Section 1: Introduction 1.1 Scope and purpose of the safety manual..................................

More information

ControlLogix SIL2 System Configuration

ControlLogix SIL2 System Configuration ControlLogix SIL2 System Configuration Using RSLogix 5000 Subroutines Application Technique (Catalog Numbers 1756 and 1492) Important User Information 8 / 2011 Solid state equipment has operational characteristics

More information

COMMON CAUSE AND COMMON SENSE

COMMON CAUSE AND COMMON SENSE COMMON CAUSE AND COMMON SENSE Designing Failure Out of Your SIS Angela E. Summers, Ph.D., P.E. and Glenn Raney Common Cause and Common Sense Designing Failure Out of Your SIS, ISA EXPO 1998, Houston, Texas,

More information

Products Solutions Services. Functional Safety. How to determine a Safety integrity Level (SIL 1,2 or 3)

Products Solutions Services. Functional Safety. How to determine a Safety integrity Level (SIL 1,2 or 3) Products Solutions Services Functional Safety How to determine a Safety integrity Level (SIL 1,2 or 3) Slide 1 Functional Safety Facts Agenda of the next 45 min SIL 1,2 or 3 Let s apply IEC61511 SIS, whats

More information

DeltaV SIS TM. Logic Solver. DeltaV SIS Logic Solver. Introduction. DeltaV SIS Product Data Sheet. World s first smart SIS Logic Solver

DeltaV SIS TM. Logic Solver. DeltaV SIS Logic Solver. Introduction. DeltaV SIS Product Data Sheet. World s first smart SIS Logic Solver February 2016 Page 1 DeltaV SIS TM Logic Solver The DeltaV SIS platform is the world s smart SIS system to use the power of predictive intelligence for increasing the availability of the entire safety

More information

Safety Instrumented Systems: Can They Be Integrated But Separate?

Safety Instrumented Systems: Can They Be Integrated But Separate? Safety Instrumented Systems: Can They Be Integrated But Separate? Written by Merry Kuchle and Trevor MacDougall of Spartan Controls. For questions, please contact Robert Smith. Keywords Safety Instrumented

More information

MANUAL Functional Safety

MANUAL Functional Safety PROCESS AUTOMATION MANUAL Functional Safety Repeater KFD0-CS-(Ex)*.54*, KFD0-CS-(Ex)*.56* ISO9001 2 With regard to the supply of products, the current issue of the following document is applicable: The

More information

Hardware Safety Integrity. Hardware Safety Design Life-Cycle

Hardware Safety Integrity. Hardware Safety Design Life-Cycle Hardware Safety Integrity Architecture esign and Safety Assessment of Safety Instrumented Systems Budapest University of Technology and Economics epartment of Measurement and Information Systems Hardware

More information

Type Switching repeater. Safety manual

Type Switching repeater. Safety manual Type 9170 Switching repeater Safety manual Safety manual English Content 1 General information... 3 1.1 Manufacturer... 3 1.2 Information regarding the Safety Manual... 3 1.3 Area of application... 3 1.4

More information

2oo4D: A New Design Concept for Next-Generation Safety Instrumented Systems 07/2000

2oo4D: A New Design Concept for Next-Generation Safety Instrumented Systems 07/2000 2oo4D: A New Design Concept for Next-Generation Safety Instrumented Systems 07/2000 Copyright, Notices and Trademarks 2000 Honeywell Safety Management Systems B.V. Revision 01 July 2000 While this information

More information

Executive summary. by Michel Bonnet, Maximilien Laforge, and Jean-Baptiste Samuel

Executive summary. by Michel Bonnet, Maximilien Laforge, and Jean-Baptiste Samuel 998-2095-02-21-14AR0 by Michel Bonnet, Maximilien Laforge, and Jean-Baptiste Samuel Executive summary Improper integration of Intelligent Electronic Devices (IED) into medium / high voltage electrical

More information

IQ Pro SIL option TÜV Certified for use in SIL 2 & 3 applications

IQ Pro SIL option TÜV Certified for use in SIL 2 & 3 applications IQ Pro SIL option TÜV Certified for use in SIL 2 & 3 applications IQ Pro range including SIL Safety Function Control Module option is TÜV certified for use in SIL 2 safety applications using a 1 out of

More information

Report. Certificate Z Rev. 00. SIMATIC Safety System

Report. Certificate Z Rev. 00. SIMATIC Safety System Report to the Certificate Z10 067803 0020 Rev. 00 Safety-Related Programmable System SIMATIC Safety System Manufacturer: Siemens AG Gleiwitzer Str. 555 D-90475 Nürnberg Revision 1.1 dated 2019-02-07 Testing

More information

Summary. Business Value

Summary. Business Value Summary Feedwater control systems Tricon Triple Modular Redundant (TMR) Digital System for Feedwater Control and Safety Application in Nuclear Power Plants are critical to the safe and efficient operation

More information

The ApplicATion of SIL. Position Paper of

The ApplicATion of SIL. Position Paper of The ApplicATion of SIL Position Paper of the SIL Platform 1. The Application of SIL: Position Paper of the SIL Platform What is the SIL Platform? Why issue a SIL statement? What are the basics of SIL

More information

Version 5.53 TECHNICAL REFERENCE GUIDE

Version 5.53 TECHNICAL REFERENCE GUIDE Version 5.53 TECHNICAL REFERENCE GUIDE 2009 COPYRIGHT Copyright 2008 SIS-TECH Applications, LP, All Rights Reserved The software product, SIL Solver, any media, printed materials, online or electronic

More information

The evolution of the cookbook

The evolution of the cookbook The evolution of the cookbook Angela E. Summers, Ph.D., P.E Michela Gentile, Ph.D. Mary Kay O Connor Process Safety Center 2006 International Symposium Beyond Regulatory Compliance, Making Safety Second

More information

Safe & available...vigilant!

Safe & available...vigilant! Safe & available...vigilant! Why not have the best of both worlds? The vigilant approach delivers uptime and peace of mind. Operators now have an all-in-one interface to effectively handle both control

More information

BRIDGING THE SAFE AUTOMATION GAP PART 2

BRIDGING THE SAFE AUTOMATION GAP PART 2 BRIDGING THE SAFE AUTOMATION GAP PART 2 Angela E. Summers, Ph.D., P.E., President, SIS-TECH Solutions Bridging the Safe Automation Gap Part 2, 2002 Instrumentation Symposium, Texas A&M University, College

More information

Report. Certificate Z SIMATIC S7 F/FH Systems

Report. Certificate Z SIMATIC S7 F/FH Systems Report to the Certificate Z10 16 06 20080 004 Safety-Related Programmable Systems SIMATIC S7 F/FH Systems Manufacturer: Siemens AG PD PA AE R&D Östliche Rheinbrückenstr. 50 D-76187 Karlsruhe Report no.

More information

A Guide to the Automation Body of Knowledge

A Guide to the Automation Body of Knowledge A Guide to the Automation Body of Knowledge 2nd Edition Vernon L. Trevathan, Editor Table of Contents Preface, xv Basic Continuous Control, 1 1 Process Instrumentation, 3 1.1 Introduction, 3 1.2 Pressure,

More information

SVI II ESD. SIL3 Partial Stroke Test Device October 2007 BW5000-ESD. The only SIL3 Smart ESD device that is live during and after a shutdown.

SVI II ESD. SIL3 Partial Stroke Test Device October 2007 BW5000-ESD. The only SIL3 Smart ESD device that is live during and after a shutdown. SVI II ESD SIL3 Partial Stroke Test Device October 2007 BW5000-ESD The only SIL3 Smart ESD device that is live during and after a shutdown. Patents Pending What is the SVI II ESD? The SVI II ESD is the

More information

Using ControlLogix in SIL 2 Applications

Using ControlLogix in SIL 2 Applications Safety Reference Manual riginal Instructions Using ControlLogix in SIL Applications ControlLogix 5560 and 5570 Controllers Important User Information Read this document and the documents listed in the

More information

Using ControlLogix in SIL2 Applications

Using ControlLogix in SIL2 Applications Using ControlLogix in SIL2 Applications 1756 Series Safety Reference Manual Important User Information Solid state equipment has operational characteristics differing from those of electromechanical equipment.

More information

SmartGuard 600 Controllers

SmartGuard 600 Controllers SmartGuard 600 Controllers Catalog Number 1752-L24BBB Safety Reference Manual Important User Information Solid state equipment has operational characteristics differing from those of electromechanical

More information

Rosemount Functional Safety Manual. Manual Supplement , Rev AG March 2015

Rosemount Functional Safety Manual. Manual Supplement , Rev AG March 2015 Rosemount 2130 Functional Safety Manual Manual Supplement Manual Supplement Contents Contents 1Section 1: Introduction 1.1 Scope and purpose of the safety manual.................................. 1 1.2

More information

Intelligent Valve Controller NDX. Safety Manual

Intelligent Valve Controller NDX. Safety Manual Intelligent Valve Controller NDX Safety Manual 10SM NDX en 5/2017 2 Intelligent Valve Controller NDX Safety Manual Table of Contents 1 General information...3 1.1 Purpose of the document... 3 1.2 Description

More information

Failure Modes, Effects and Diagnostic Analysis

Failure Modes, Effects and Diagnostic Analysis Failure Modes, Effects and Diagnostic Analysis Project: Solenoid Drivers IM72-11Ex/L and IM72-22Ex/L Customer: Hans Turck GmbH & Co. KG Mühlheim Germany Contract No.: TURCK 04/10-20 Report No.: TURCK 04/10-20

More information

Industrial Controls. Motor management and control devices SIMOCODE pro - Application examples. Introduction 1. Application example

Industrial Controls. Motor management and control devices SIMOCODE pro - Application examples. Introduction 1. Application example Introduction 1 Application example 2 Industrial Controls Motor management and control devices SIMOCODE pro - Application examples Application Manual Example circuits control functions 3 Further application

More information

SIS Operation & Maintenance 15 minutes

SIS Operation & Maintenance 15 minutes 2005 Emerson Process Management. All rights reserved. View this and other courses online at www.plantwebuniversity.com. SIS 301 - Operation & Maintenance 15 minutes In this course: 1 Overview 2 Planning

More information

Special Documentation Liquicap M FMI51, FMI52

Special Documentation Liquicap M FMI51, FMI52 SD00198F/00/EN/15.16 71315608 Products Solutions Services Special Documentation Liquicap M FMI51, FMI52 Functional Safety Manual Capacitance level measurement for liquids with a 4-20 ma output signal Table

More information

Drive Technology \ Drive Automation \ System Integration \ Services. Manual. Electronic Motor DRC Functional Safety

Drive Technology \ Drive Automation \ System Integration \ Services. Manual. Electronic Motor DRC Functional Safety Drive Technology \ Drive Automation \ System Integration \ Services Manual Electronic Motor DRC Functional Safety Edition 02/2012 19376812 / EN SEW-EURODRIVE Driving the world Contents Contents 1 General

More information

Failure Modes, Effects and Diagnostic Analysis

Failure Modes, Effects and Diagnostic Analysis Failure Modes, Effects and Diagnostic Analysis Project: Relay couplers IM73-12-R/24VUC and IM73-12-R/230VAC Customer: Hans Turck GmbH & Co. KG Mühlheim Germany Contract No.: TURCK 06/02-16 Report No.:

More information

An Urgent Bulletin from CSA Group

An Urgent Bulletin from CSA Group An Urgent Bulletin from CSA Group Photovoltaic Equipment No. 5 Date: September 21, 2015 See Attachment 1 for Effective Dates. See Attachment 1 for Application Due Dates Announcing: Publication of List

More information

Safe and Fault Tolerant Controllers

Safe and Fault Tolerant Controllers Safe and Fault Tolerant Controllers SIMATIC Safety Integrated for Process Automation Wiring and Evaluation Architectures for Failsafe Digital Input (F-DI)- and Output-Modules (F-DO) of ET 200M Functional

More information

Failure Modes, Effects and Diagnostic Analysis. Rosemount Inc. Chanhassen, MN USA

Failure Modes, Effects and Diagnostic Analysis. Rosemount Inc. Chanhassen, MN USA Failure Modes, Effects and Diagnostic Analysis Project: 8732C Magnetic Flow Transmitter Customer: Rosemount Inc. Chanhassen, MN USA Contract No.: Ros 03/07-26 Report No.: Ros 03/07-26 R001 Version V1,

More information

Line reactors SINAMICS. SINAMICS G120P Line reactors. Safety information 1. General. Mechanical installation 3. Electrical installation 4

Line reactors SINAMICS. SINAMICS G120P Line reactors. Safety information 1. General. Mechanical installation 3. Electrical installation 4 Safety information 1 General 2 SINAMICS SINAMICS G120P Mechanical installation 3 Electrical installation 4 Technical specifications 5 Operating Instructions Control version V4.6 11/2013 A5E32845290B AA

More information

Report. Certificate M6A SIMATIC S7 Distributed Safety

Report. Certificate M6A SIMATIC S7 Distributed Safety Report to the Certificate M6A 17 05 67803 014 Safety-Related Programmable Systems SIMATIC S7 Distributed Safety Manufacturer: Siemens AG DF FA AS Gleiwitzer Str. 555 D-90475 Nürnberg Revision 3.1 dated

More information

FACTORY AUTOMATION. MANUAL VAA-2E-G4-SE Original Instructions Version 1.1

FACTORY AUTOMATION. MANUAL VAA-2E-G4-SE Original Instructions Version 1.1 FACTORY AUTOMATION MANUAL VAA-2E-G4-SE Original Instructions Version 1.1 With regard to the supply of products, the current issue of the following document is applicable: The General Terms of Delivery

More information

MANUAL Functional Safety

MANUAL Functional Safety PROCESS AUTOMATION MANUAL Functional Safety Switch Amplifier HiC283* ISO9001 2 With regard to the supply of products, the current issue of the following document is applicable: The General Terms of Delivery

More information

Functional Safety and Safety Standards: Challenges and Comparison of Solutions AA309

Functional Safety and Safety Standards: Challenges and Comparison of Solutions AA309 June 25th, 2007 Functional Safety and Safety Standards: Challenges and Comparison of Solutions AA309 Christopher Temple Automotive Systems Technology Manager Overview Functional Safety Basics Functional

More information

FMEDA Report Failure Modes, Effects and Diagnostic Analysis and Proven-in-use -assessment KF**-CRG2-**1.D. Transmitter supply isolator

FMEDA Report Failure Modes, Effects and Diagnostic Analysis and Proven-in-use -assessment KF**-CRG2-**1.D. Transmitter supply isolator FMEDA Report Failure Modes, Effects and Diagnostic Analysis and Proven-in-use -assessment Device Model Number: Transmitter supply isolator Pepperl+Fuchs GmbH Mannheim Germany Mannheim norm sheet 1 of 10

More information

White Paper. The Tricon Turbine Control System

White Paper. The Tricon Turbine Control System White Paper The Tricon Turbine Control System Author: Naresh Desai, Sr. Technical Consultant, Invensys What s Inside: 1. Abstract 2. Introduction 3. Major Requirements 4. Tricon Architecture 5. Critical

More information

FMEDA and Proven-in-use Assessment. Pepperl+Fuchs GmbH Mannheim Germany

FMEDA and Proven-in-use Assessment. Pepperl+Fuchs GmbH Mannheim Germany FMEDA and Proven-in-use Assessment Project: Solenoid Drivers HiD2871/2872, HiD2875/2876 and HiD2881 Customer: Pepperl+Fuchs GmbH Mannheim Germany Contract No.: P+F 04/05-08 Report No.: P+F 04/05-08 R021

More information

Failure Modes, Effects and Diagnostic Analysis

Failure Modes, Effects and Diagnostic Analysis Failure Modes, Effects and Diagnostic Analysis Project: One Series SAFETY TRANSMITTER Company: United Electric Controls Watertown, MA USA Contract Number: Q04/04-001 Report No.: UE 12/10-073 R001 Version

More information

EOS-6000 Series Optical A/B Switch User Manual DC Version

EOS-6000 Series Optical A/B Switch User Manual DC Version EOS-6000 Series Optical A/B Switch User Manual DC Version For more information on this and other products: Contact Sales at EMCORE 626-293-3400, or visit www.emcore.com. Table of Contents Table of Contents...2

More information

II ESD. SIL3 Partial Stroke Test Device. The only SIL3 Smart ESD device that is live during and after a shutdown.

II ESD. SIL3 Partial Stroke Test Device. The only SIL3 Smart ESD device that is live during and after a shutdown. SVI II ESD SIL3 Partial Stroke Test Device The only SIL3 Smart ESD device that is live during and after a shutdown. W h a t i s t h e S V I I I E S D? The SVI II ESD is the latest technology in emergency

More information

How flowmeters perform self-verification

How flowmeters perform self-verification How flowmeters perform self-verification Here s how modern flowmeters verify their own measurement performance By Nathan Hedrick, Endress+Hauser, USA Process manufacturing and other industrial facilities

More information

AS-i Safety Relay Output Module with Diagnostic Slave

AS-i Safety Relay Output Module with Diagnostic Slave AS-i Safety Relay Output Module with Diagnostic Slave User Manual Revision date: 2013-01-30...supports the requirements for AS-i Safety up to SIL3 Subject to modifications without notice. Generally, this

More information

Information technology Security techniques Information security controls for the energy utility industry

Information technology Security techniques Information security controls for the energy utility industry INTERNATIONAL STANDARD ISO/IEC 27019 First edition 2017-10 Information technology Security techniques Information security controls for the energy utility industry Technologies de l'information Techniques

More information

Safety Manual. Vibration Control Type 663. Standard Zone-1-21 Zone Edition: English

Safety Manual. Vibration Control Type 663. Standard Zone-1-21 Zone Edition: English Safety Manual Vibration Control Type 663 Standard Zone-1-21 Zone-2-22 Edition: 21.06.2012 English Safety Manual Vibration Control Type 663 Standard Zone-1-21 Zone-2-22 Achtung! Before Start-Up Procedure

More information

ISO INTERNATIONAL STANDARD. Safety of machinery Safety-related parts of control systems Part 1: General principles for design

ISO INTERNATIONAL STANDARD. Safety of machinery Safety-related parts of control systems Part 1: General principles for design INTERNATIONAL STANDARD ISO 13849-1 Second edition 2006-11-01 Safety of machinery Safety-related parts of control systems Part 1: General principles for design Sécurité des machines Parties des systèmes

More information

PSR-SCP- 24DC/SSM/2X1 PSR-SPP- 24DC/SSM/2X1

PSR-SCP- 24DC/SSM/2X1 PSR-SPP- 24DC/SSM/2X1 PSR-SCP- DC/SSM/2X1 PSR-SPP- DC/SSM/2X1 Safety Relay With Downtime Monitoring INTERFACE Data Sheet PHOENIX CONTACT - 05/2006 Description The PSR-...- DC/SSM/2X1 safety relay can be used in safety circuits

More information

Energize to Trip Requirement for SIL 3 according to IEC 61511

Energize to Trip Requirement for SIL 3 according to IEC 61511 Safety Manual 09/2014 Energize to Trip Requirement for SIL 3 according to IEC 61511 SIMATIC S7-400F/FH http://support.automation.siemens.com/ww/view/en/109106504 Warranty and Liability Warranty and Liability

More information

Commissioning and safety manual SIL2

Commissioning and safety manual SIL2 Commissioning and safety manual CAL23MA/S2 SIL2 SIL3 LOREME 12, rue des Potiers d'etain Actipole BORNY - B.P. 35014-57071 METZ CEDEX 3 Téléphone 03.87.76.32.51 - Télécopie 03.87.76.32.52 Nous contacter:

More information

EM-F-7G Safety Extension Module

EM-F-7G Safety Extension Module EM-F-7G Safety Extension Module One-channel control with four safety output channels Features Safety Extension Module provides additional safety outputs for a Primary Safety Device (for example, an E-stop

More information

HART Temperature Transmitter for up to SIL 2 applications

HART Temperature Transmitter for up to SIL 2 applications HART Temperature Transmitter for up to SIL 2 applications Inor Process AB 04/2010 86B520S001 R1.0 1 Introduction... 3 1.1 Field of application... 3 1.2 User benefits... 3 1.3 Manufacturer s safety instructions...

More information

SE Engineering, PC strives to be a leader in the power system engineering field by providing our customers with the highest level of quality,

SE Engineering, PC strives to be a leader in the power system engineering field by providing our customers with the highest level of quality, SE Engineering, PC strives to be a leader in the power system engineering field by providing our customers with the highest level of quality, integrity, and innovation. Our mission is to offer the safest,

More information

Failure Modes, Effects and Diagnostic Analysis

Failure Modes, Effects and Diagnostic Analysis Failure Modes, Effects and Diagnostic Analysis Project: 9106 HART Transparent Repeater and 9107 HART Transparent Driver Customer: PR electronics A/S Rønde Denmark Contract No.: PR electronics 06/03-19

More information

PowerFlex 70 Safe-Off Control EtherNet/IP Guard I/O Safety Module and GuardLogix Integrated Safety Controller

PowerFlex 70 Safe-Off Control EtherNet/IP Guard I/O Safety Module and GuardLogix Integrated Safety Controller Safety Application Example PowerFlex 70 Safe-Off Control EtherNet/IP Guard I/O Safety Module and GuardLogix Integrated Safety Controller Safety Rating: Category 3 (also see Achieving a Cat. 4 Safety Rating)

More information

FMEDA and Prior-use Assessment. Pepperl+Fuchs GmbH Mannheim Germany

FMEDA and Prior-use Assessment. Pepperl+Fuchs GmbH Mannheim Germany FMEDA and Prior-use Assessment Project: Smart Repeater KFD2-SCD(2)-*** and Current/Voltage Repeater KFD2-CD(2)-*** Customer: Pepperl+Fuchs GmbH Mannheim Germany Contract No.: P+F 03/10-12 Report No.: P+F

More information

5504 Thermocouple Analog Input Module

5504 Thermocouple Analog Input Module 550 Thermocouple Analog Input Installation, Operation and Maintenance Setup Manual 5/9/0 Safety Information The information provided in this documentation contains general descriptions and/or technical

More information

Soliphant M with electronic insert FEM54

Soliphant M with electronic insert FEM54 Functional safety manual Soliphant M with electronic insert FEM54 Level Limit Measuring System Application Overfill protection or operating maximum detection of all types of liquids in tanks to satisfy

More information

Integrated and Separate?

Integrated and Separate? Integrated and Separate? A document to aid the demonstration of Independence between Control & Safety by The 61508 Association Overriding key principle...it must be safe! DISCLAIMER: Whilst every effort

More information

Line reactors SINAMICS. SINAMICS G130 Line reactors. Safety information 1. General. Mechanical installation 3. Electrical installation

Line reactors SINAMICS. SINAMICS G130 Line reactors. Safety information 1. General. Mechanical installation 3. Electrical installation Safety information 1 General 2 SINAMICS SINAMICS G130 Mechanical installation 3 Electrical installation 4 Technical specifications 5 Operating Instructions Control version V4.7 04/2014 A5E00331462A Legal

More information

PSR-PC50. SIL 3 coupling relay for safety-related switch on. Data sheet. 1 Description

PSR-PC50. SIL 3 coupling relay for safety-related switch on. Data sheet. 1 Description SIL 3 coupling relay for safety-related switch on Data sheet 105818_en_01 PHOENIX CONTACT 2014-08-18 1 Description The PSR-PC50 SIL coupling relay can be used for power adaptation and electrical isolation

More information

Report. Certificate M6A SIMATIC Safety System

Report. Certificate M6A SIMATIC Safety System Report to the Certificate M6A 067803 0019 Safety-Related Programmable Systems SIMATIC Safety System Manufacturer: Siemens AG Gleiwitzer Str. 555 D-90475 Nürnberg Revision 2.1 dated 2018-09-25 Testing Body:

More information

AS-i Safety Relay Output Module with Diagnostic Slave

AS-i Safety Relay Output Module with Diagnostic Slave AS-i Safety Relay Output Module with Diagnostic Slave User Manual...supports the requirements for AS-i Safety up to SIL3 Revision date: 2016-03-9 Subject to modifications without notice. Generally, this

More information

New developments about PL and SIL. Present harmonised versions, background and changes.

New developments about PL and SIL. Present harmonised versions, background and changes. Safety evevt 2017 Functional safety New developments about PL and SIL. Present harmonised versions, background and changes. siemens.com ISO/ TC 199 and IEC/ TC 44 joint working group 1 - Merging project

More information

SAFETY MANUAL SIL Switch Amplifier

SAFETY MANUAL SIL Switch Amplifier PROCESS AUTOMATION SAFETY MANUAL SIL Switch Amplifier KCD2-SOT-(Ex)*(.LB)(.SP), KCD2-ST-(Ex)*(.LB)(.SP) ISO9001 2 With regard to the supply of products, the current issue of the following document is applicable:

More information

FUNCTIONAL SAFETY CERTIFICATE

FUNCTIONAL SAFETY CERTIFICATE FUNCTIONAL SAFETY CERTIFICATE This is to certify that the GSS (GSA******-*) Series Global Safety Limit Switch Manufactured by Honeywell International Inc. 315 East Stephenson Street, Freeport, Illinois,

More information

FUNCTIONAL SAFETY CERTIFICATE

FUNCTIONAL SAFETY CERTIFICATE FUNCTIONAL SAFETY CERTIFICATE This is to certify that the SI-1Q and SI-2/2.1Q Skilmatic Intelligent Electro-hydraulic Quarter-turn Valve Actuators manufactured by Rotork Fluid Systems Ltd (A Division of

More information

MANUFACTURING TECHNICAL INSTRUCTIONS - SAFETY. Subject: Control Reliability for Machinery & Equipment

MANUFACTURING TECHNICAL INSTRUCTIONS - SAFETY. Subject: Control Reliability for Machinery & Equipment DAIMLERCHRYSLER MANUFACTURING TECHNICAL INSTRUCTIONS - SAFETY Subject: Control Reliability for Machinery & Equipment ISSUE DATE: January 3, 2005 EFFECTIVE DATE: January 31, 2005 REVIEW DATE. June 26, 2007

More information

ACT20X-(2)HTI-(2)SAO Temperature/mA converter. Safety Manual

ACT20X-(2)HTI-(2)SAO Temperature/mA converter. Safety Manual ACT20X-(2)HTI-(2)SAO Temperature/mA converter Safety Manual 1.1 Revision history Version Date Change 00 04/2014 First Edition 01 11/2017 Products added 1.2 Validity This manual is valid for the following

More information

Safety manual for Fisher FIELDVUE DVC6200 SIS Digital Valve Controller, Position Monitor, and LCP200 Local Control Panel

Safety manual for Fisher FIELDVUE DVC6200 SIS Digital Valve Controller, Position Monitor, and LCP200 Local Control Panel Instruction Manual Supplement DVC6200 SIS Digital Valve Controller Safety manual for Fisher FIELDVUE DVC6200 SIS Digital Valve Controller, Position Monitor, and LCP200 Local Control Panel This supplement

More information

Extension to Chapter 2. Architectural Constraints

Extension to Chapter 2. Architectural Constraints Extension to Chapter 2. Architectural Constraints Mary Ann Lundteigen Marvin Rausand RAMS Group Department of Mechanical and Industrial Engineering NTNU (Version 0.1) Lundteigen& Rausand Extension to Chapter

More information

Hardware safety integrity (HSI) in IEC 61508/ IEC 61511

Hardware safety integrity (HSI) in IEC 61508/ IEC 61511 1 Hardware safety integrity (HSI) in IEC 61508/ IEC 61511 ESReDA 2006 June 7-8, 2006 Mary Ann Lundteigen mary.a.lundteigen@ntnu.no mary.a.lundteigen@sintef.no 2 Overview 1. Objective 2. Some concepts &

More information

Safety Manager. Safety Manual. EP-SM.MAN.6283 Issue February Release 151

Safety Manager. Safety Manual. EP-SM.MAN.6283 Issue February Release 151 Safety Manager Safety Manual EP-SM.MAN.6283 Issue 1.0 20 February 2013 Release 151 Document Release Issue Date EP-SM.MAN.6283 151 1.0 February 2013 Notice This document contains Honeywell proprietary information.

More information

Tank terminal demonstrates the electrically operated solution for Emergency Shutdown Valves

Tank terminal demonstrates the electrically operated solution for Emergency Shutdown Valves Case Study Tank terminal demonstrates the electrically operated solution for Emergency Shutdown Valves Botlek Tank Terminal Case Study - 26th April 2013 Botlek Tank Terminal Case Study - 26th April 2013

More information

Safety Manager. Safety Manual. EP-SM.MAN.6283 Issue June Release 145

Safety Manager. Safety Manual. EP-SM.MAN.6283 Issue June Release 145 Safety Manager Safety Manual EP-SM.MAN.6283 Issue 5.3 30 June 2011 Release 145 Document Release Issue Date EP-SM.MAN.6283 145 5.3 June 2011 Notice This document contains Honeywell proprietary information.

More information

System 800xA Safety AC 800M High Integrity Safety Manual

System 800xA Safety AC 800M High Integrity Safety Manual System 800xA Safety AC 800M High Integrity Safety Manual System Version 5.1 Power and productivity for a better world TM System 800xA Safety AC 800M High Integrity Safety Manual System Version 5.1 NOTICE

More information

HI HIPS Logic Solver (2oo3)

HI HIPS Logic Solver (2oo3) General Specifications GS48C00Z00-00E-N HI-100-00 HIPS Logic Solver (2oo3) INTRODUCTION HIPS is the abbreviation for High Integrity Protection System. A HIPS is a specific application of a Safety Instrumented

More information

Packaging User Guide for Temperature Control M221 Project Template

Packaging User Guide for Temperature Control M221 Project Template Packaging EIO0000001762 04/2014 Packaging User Guide for Temperature Control M221 Project Template 04/2014 EIO0000001762.00 www.schneider-electric.com The information provided in this documentation contains

More information

Foundation Fieldbus Safety Instrumented System (FF SIS) FF-SIS Meeting. Hannover. April 21, 2004

Foundation Fieldbus Safety Instrumented System (FF SIS) FF-SIS Meeting. Hannover. April 21, 2004 Foundation Fieldbus Safety Instrumented System (FF SIS) FF-SIS Meeting Hannover April 21, 2004 1 Foundation Fieldbus Safety Instrumented System (FF SIS) Principles of Safety Related Bus-System and Protocols

More information

GuardLogix: Dual Zone Gate Protection with E-stop and Trojan Interlock Switch

GuardLogix: Dual Zone Gate Protection with E-stop and Trojan Interlock Switch Safety Application Example GuardLogix: Dual Zone Gate Protection with E-stop and Trojan Interlock Switch Safety Rating: PLd, Cat. 3 to EN ISO 13849.1 2008 Introduction... 2 Important User Information...

More information

Hytork XL Pneumatic Actuator

Hytork XL Pneumatic Actuator Hytork XL Pneumatic Actuator SIL Safety Manual SIL Safety Manual DOC.SILM.HXL.EN Rev. 0 May 2015 Hytork XL Series DOC.SILM.HXL.EN, Rev. 0 Table of Contents May 2015 Table of Contents Section 1: Functional

More information

Drive Technology \ Drive Automation \ System Integration \ Services. Manual. Control Cabinet Inverter MOVITRAC B Functional Safety

Drive Technology \ Drive Automation \ System Integration \ Services. Manual. Control Cabinet Inverter MOVITRAC B Functional Safety Drive Technology \ Drive Automation \ System Integration \ Services Manual Control Cabinet Inverter MOVITRAC B Functional Safety Edition 05/2009 16811216 / EN SEW-EURODRIVE Driving the world Content Content

More information

Using TLS3-GD2 Guardlocking Interlock with ArmorBlock Guard I/O and SmartGuard Controller

Using TLS3-GD2 Guardlocking Interlock with ArmorBlock Guard I/O and SmartGuard Controller Safety Application Example Using TLS3-GD2 Guardlocking Interlock with ArmorBlock Guard I/O and SmartGuard Controller Guardlocking with On-machine Components Safety Rating: Category 3, according to EN954-1

More information

Safety Manager Safety Manual

Safety Manager Safety Manual Safety Manager Safety Manual EP-SM.MAN.6283 June 2016 Release 160 Document Release Issue Date EP-SM.MAN.6283 160 1.0 June 2016 Disclaimer This document contains Honeywell proprietary information. Information

More information

DK32 - DK34 - DK37 Supplementary instructions

DK32 - DK34 - DK37 Supplementary instructions DK32 - DK34 - DK37 Supplementary instructions Variable area flowmeter Safety manual acc. to IEC 61508:2010 KROHNE CONTENTS DK32 - DK34 - DK37 1 Introduction 3 1.1 Field of application... 3 1.2 User benefits...

More information