1 General Specifications GS48C00Z00-00E-N HI HIPS Logic Solver (2oo3) INTRODUCTION HIPS is the abbreviation for High Integrity Protection System. A HIPS is a specific application of a Safety Instrumented System (SIS) designed in accordance with the worldwide agreed and accepted IEC and IEC safety standards and consisting at least of the following three (3) main parts: 1. Sensors (Pressure Transmitters) 2. Logic solver 3. Final elements HIPS functionality is to protect fully autonomously any downstream installation(s) against excess pressure by closing the source of the overpressure. Normally this is done by timely closing one or more dedicated safety shutdown valves preventing further pressurization of the downstream installation. A HIPS is defined by the IEC as a complete loop consisting of sensors (pressure transmitters) logic solver and final elements (shutdown valves), as per the picture below, which should be classified at a certain Safety Integrity Level (SIL). Communication to PAS HIPS LOGIC SOLVER PTs 2oo3 Manifold Flow direction Figure 1 HIPS sketch Pipeline HIPS valve 1 HIPS valve 2 Yokogawa Europe Solutions B.V. PO Box 163, 3800 AD, Amersfoort, The Netherlands Tel: (31) Fax: (31) GS48C00Z00-00E-N Copyright rd Edition February 2013
2 HI of 10 Logic Solver This document describes the design for a HIPS logic solver using Yokogawa s ProSafe-SLS system which is a standalone, hardwired, solid state safety system from a simple design and built with robust, oversized components. The ProSafe-SLS system has proven itself in the field for more than 40 years. The main design criteria that are embedded in this HIPS logic solver are: 1. High integrity. 2. High availability, low demand for maintenance 3. Totally independent of any other system. 4. Robust design. 5. As simple as possible. HIPS Design Considerations The following design criteria are taken into consideration designing the Yokogawa HIPS logic solver: 1. All safety I/O loops are powered by the HIPS logic solver. 2. All safety I/O loops are configured for use with Eexd certified field equipment. 3. The 3 pressure transmitter input loops are configured in a 2oo3 configuration. 4. All safety functions are based on the DTS (de-energise to safe) principle. 5. The logic solver is implemented with the inherently failsafe Yokogawa ProSafe-SLS system (using the CTL (Core Transistor Logic) technique) certified by TÜV for applications up to and including SIL 4 according IEC All digital functions are inherent fail-safe (SIL 4). 7. Supply feeders and AC/DC-converters are installed in a redundant configuration to reduce spurious trips. 8. The solenoid valves per HIPS shutdown valve are configured in a 1oo2 configuration. 9. The HIPS shutdown valves are configured in a 1oo2 configuration. HIPS Philosophy The principle aims and objectives of the HIPS are: 1. The protection of personnel. 2. The protection of plant and equipment. 3. The minimisation of pollution to the environment. The main objective of the HIPS system is to provide reliable means for safely isolating and shutting down the installation downstream of the HIPS valves and to initiate the appropriate alarms when process pressure exceeds the high pressure setpoint. Therefore the HIPS will: 1. Sense automatically an abnormal operation or equipment/process condition. 2. React automatically to this condition by shutting down and/or isolating the downstream installation, preventing any consequential effects of the abnormal condition. 3. Provide system status information for the operator and/or other personnel as appropriate.
3 HI of 10 Basic Principle The Yokogawa 2oo3 HIPS logic solver (HIPS using 2 out of 3 voting), which is available with different options, is based on one (1) single system design allowing optimal production and test results as well as using the most efficient way of logic design, control panel lay out, power supply and mechanical construction. Redundant power supply converters are implemented to reduce spurious trips. This configuration is a worldwide standard and will benefit the engineering effort for customers and subcontractors. The design principle is based on a system with fixed I/O and functionality to meet all basic needs for HIPS logic solvers. The logic and the HIPS control panel are built into one (1) fixed rack which is mounted on the backplane of the cabinet. All field I/O is connected to terminals. The cable entry (power supply, communication and field cables) is at the bottom. The I/O signals will be made available to the ProSafe- COM which is the communication module that deals with the communication between the ProSafe-SLS and the external world. It has two serial, 2-wire RS-485 communication links which can be connected in dual configuration to one external device or as two (2) separate links to separate external devices. This HIPS functionality is fixed and dedicated to be used in predefined process setup with a Manifold, three Pressure transmitters, HIPS Logic solver, HIPS valves, PAS (see Figure 3) and a HIPS control panel (see Figure 4). The HIPS offers the following functionality: 1. The Manifold is equipped with three transmitters and an interlocking system providing functionality that allows only one transmitter to be tested (isolated from the process) at any one time. If the interlocking system is operated and one transmitter is in test mode (isolated from the process), this will be automatically detected by the logic solver. The trip signal from the transmitter in test mode will be disabled from the trip logic, hence the logic solver will change the trip logic from 2oo3 voting to 1oo2 voting on the two transmitters remaining. 2. The Yokogawa HIPS logic solver is equipped with a Proof Test Configuration (PTC). This PTC allows for proof testing the logic solver including the valves when testing only one transmitter. This facility can only be selected by operating a dedicated key-operated switch located on the local control panel in combination with the manifold test mode. When PTC is selected the Yokogawa HIPS automatically changes the trip logic from 2oo3 voting to 1oo3 voting. The transmitter selected for test via the interlocking manifold can now be used to trip the HIPS. The Transmitter High level trip will trip the logic and close the ESDV 1 / 2 HIPS valves. This test will be used to prove: a. Individual transmitter trip settings tripping the HIPS logic solver. b. Adequate closing time of each of the ESDV 1/2 HIPS valves. 3. The Yokogawa HIPS is provided with a dedicated SOV Test facility. This facility allows for proof testing that individual solenoid valves will trip the relevant HIPS valve. This facility can only be operated by using two dedicated key-operated switches located on the HIPS control panel. By operating the first switch ( SOV x-1 where x is 1 or 2 ) the solenoids for each HIPS valve will be tripped. By operating the second ( SOV x-2 ) switch the solenoids for each HIPS valve will be tripped. The consequence of each operation should be of course the closing of the appropriate HIPS valve. 4. The HIPS can be reset by means of: a. Operating the logic reset on the HIPS control panel (reset logic and the HIPS valves). b. Operating individual local HIPS valve reset facilities when option is enabled. c. Operating the PAS HIPS reset and individual HIPS valve reset when this option is enabled. 5. The Process Automation System (PAS) can read dedicated HIPS information like HIPS I/O and alarms via the serial link(s) to the ProSafe-COM and, if the option is enabled, send HIPS reset, individual HIPS valve reset and close commands for the HIPS valves.
4 HI of 10 Figure 2 HIPS functionality overview Figure 3 HIPS Logic solver (2oo3)
5 HI of 10 Figure 4 HIPS logic solver control panel The HIPS control panel is included in the logic solver rack which is located inside the cabinet. The indications on this panel are based on the all dark principle, meaning that under normal operational conditions all indications are off. The panel provides the following functionality: -Input indications: PT tripped (3 off, red), PT in test mode (3 off, yellow) PT deviation (1 off, red). -Control indication: Proof Test Configuration (PTC) active (1 off, yellow). -Output indications: Trip to ESD (1off, red), SOV tripped (4 off, red), HIPS valve closed (2 off, red). -Control equipment: Proof Test Switch (1 off, key-operated), Solenoid Test (2 off, key-operated). -Control equipment: HIPS reset (1 off, pushbutton), Lamptest (1 off, pushbutton). The HIPS drawings are a uniform set of ACAD drawings that use internal tagnames like PT1, PT2, SOV 1, SOV 2, etc. Client tagnames will be shown at the relevant places like the control panel. The coupling between client tagnames and Yokogawa internal tagnames can be contained in the I/O-list. A HIPS system fault is indicated on the HIPS front door and is available as volt-free contact for a hardwired alarm to an external device. The alarms initiating this system alarm are individually available to the ProSafe-COM for serial alarming to external devices.
6 HI of 10 Yokogawa 2oo3 HIPS Configuration The Yokogawa HIPS logic solver is one single rack that is mounted on the panel mounting plate. The logic solver power supply and I/O is connected via a robust connector. Figure 5 Mounting plate HIPS logic solver
7 HI of 10 HIPS Scope The 2oo3 voting HIPS application contains all the basic safety functions necessary to protect the downstream installation against damage as a result of high pressure. On top of this, options have been developed to meet customer s demands on issues not related to the primary safety function. The options chosen will be described in the quotation and are the basis for the table of compliance. If the customer insists on the fulfilment of other requirements that are not foreseen in this solution, Yokogawa will quote a client specific solution. In the quotation phase, options will be chosen that are best fitting the customer s requirements and this will be reflected in the table of compliance. The basic safety functions are pre-described in a Functional design specification (FDS) and Safety Validation Plan (SVP).
8 HI of 10 Included in the standard delivery: Nr Item Description 1 Enclosure Rittal TS8 type cabinet, RAL7035, dimensions 800mmx800mm*2100mm (w*h*d) including 100mm plinth, front access door, mounting plate, auxiliary socket and panel lighting. 2 Redundant AC/DC converters. (85 230Vac / 24Vdc / 10A) 3 Failsafe equipment & design. 4 Pressure transmitter inputs. 5 Pressure transmitter test & maintenance Inputs. 6 HIPS Valve Open/Closed inputs. To reduce spurious trips 2 AC/DC converters are implemented in a redundant (2oo2) configuration. Each converter is well capable of supplying power to the complete HIPS under full load conditions. The logic solver is implemented using ProSafe-SLS, the inherent failsafe hardwired Yokogawa safety system. Each of the three (3) PT s is connected to a separate, failsafe analogue input module (0-20mA) providing a logic signal tripping on an adjustable high pressure setpoint, input linefault (3.6 ma<input>21 ma) and deviation alarming functionality is provided. Each PT has one (1) digital input reading the (ASTAVA Manifold) PT block valve status. When the block valve is closed (for maintenance or test) the PT trip signal will be inhibited to the 2oo3 voting logic and change this logic automatically into 1oo2 voting logic. Open/Close signals are available to ProSafe-COM (modbus). Additionally the closed signals are indicated on the control panel as well and will illuminate when HIPS valves are closed. 7 2oo3 voting. The 2oo3 voting logic will initiate a trip when any two out of three pressure transmitter inputs are generating a trip. 8 1oo2 voting. If one pressure transmitter input is in trip condition the logic automatically changes to 1oo2 voting logic. 9 Proof Test Configuration (1oo3 Voting). 10 SOV Output Test Configuration. 11 Individual solenoid outputs (20W) A key-interlocked Proof Test Switch on the control panel is used to switch the logic solver into a 1oo3 voting configuration. This is required to test the complete HIPS (pipe-to-pipe) at certain time intervals in order to keep the HIPS at the required SIL level. Two (2) key-interlocked SOV Test switches on the control panel are used to prove that each HIPS shutdown valve closes on only one solenoid valve trip. There is one (1) switch ( SOV x-1 ) to test the First solenoid valves on both HIPS valves and one (1) switch ( SOV x-2 ) for the Second solenoids both HIPS valves. Each of the four (4) solenoids is connected to an individual fused failsafe output circuit with a maximum power consumption of 20W at 24Vdc. 12 Control panel. Embedded in the logic solver rack and providing functionality as follows: -Input indications: PT tripped (3), PT in test mode (3) PT deviation (1). -Controls indication: Proof test active (1). -Output indications: Trip to ESD (1), SOV tripped (4), HIPS valve closed (2). -Control equipment: Proof Test (1), Solenoid Test (2). (key-operated switches). -Control equipment: HIPS reset (1), Lamptest (1). (pushbuttons). 13 Documentation Functional Design Specification Safety Validation Plan Detailed design documents: Functional logic diagrams, Loop diagrams Hardware documents: Mechanical and Electrical drawings Operating and maintenance instructions Safety Certification
9 HI of 10 Ordering Ordering code for the standard 2oo3 HIPS consists of a basic code (HIPS2oo3) and if necessary followed by some features and if required followed by option codes as indicated in the table below. CODE Item Description HIPS2oo3 Standard HIPS Yokogawa standard 2oo3 HIPS solution In the standard delivery the following FEATURES are implemented but disabled. When ordering a HIPS logic solver please specify the appropriate code if the project requires these features to be enabled. CODE Item Additional Features -TTV Trip on Transmitter Deviation This feature enables the logic solver to trip on a deviation alarm; i.e. a deviation above a preset value (in %) between the PT s will cause the HIPS to trip. (Note that if this choice is not enabled the deviation indication on the control panel and deviation alarming to the ProSafe-COM will still be operational). -SLC Serial Link Commands This feature enables serial link commands from an external device for the operation of: HIPS reset, ESDV1 close, ESDV 2 close. -IVRC Individual HIPS Valve Reset Commands This feature enables individual HIPS valve reset command from the field. (i.e. from the HIPS valve control boxes). NOTE: If the features SLC and IVRC are both ENABLED it will also be possible to reset the HIPS valves individually from an external device. Additionally the HIPS valves can be individually closed from this device as well. Additionally the following OPTIONS are available: CODE Item Option Option description /MP24 Main Power supply - Main power supply to the HIPS is 24VDC. 24VDC /CS400 Cabinet Size Depth 400cm - Cabinet size: 800*400*1600mm (w*d*h). (front door access) /FP Control Panel on front - HIPS Control Panel is located in the cabinet front door. door. /SP Field I/O- Surge - Field I/O protected on by surge protectors. Protection /IS Intrinsically Safe field - Field inputs connected via intrinsic safe isolators. input /HQ2 HIPS Quantity 2 Two (2) HIPS logic solvers per cabinet. /SL4 SIL Level 4 4 HIPS logic solver is a SIL 4 classified system. /CD Customer Documentation - Special customer required documents can be provided. When option SP is chosen field I/O will be protected by MTL surge protectors: For inputs type:sd32x. For outputs type:sd150x. When option IS is chosen field inputs will be connected via MTL intrinsic safe isolators: For analogue inputs type: MTL For digital inputs type: MTL Example of overall ordering code: HIPS2oo3-TTV-SLC/MP24/IS (2 Features specified, 2 options added)
10 HI of 10 Special Versions If required all kind of HIPS (tailor-made) systems can be built using other or the same building blocks as used for this Yokogawa 2oo3 HIPS. This allows a sophisticated custom-made alignment with customer s wishes but needs more design and test effort. Yokogawa will always strive for the optimal solution. Example of special version: - 3 or 4 HIPS in one cabinet - HIPS logic solver rack to be combined within subcontracting cabinet or console - ATEX (Atmosphères Explosives) zone specific cabinet - Earthquake proof cabinet - Cabinet size custom-made - Cabinet Color - Etc.
Safe & available...vigilant!
Safe & available...vigilant! Why not have the best of both worlds? The vigilant approach delivers uptime and peace of mind. Operators now have an all-in-one interface to effectively handle both control
More informationSVI II ESD. SIL3 Partial Stroke Test Device October 2007 BW5000-ESD. The only SIL3 Smart ESD device that is live during and after a shutdown.
SVI II ESD SIL3 Partial Stroke Test Device October 2007 BW5000-ESD The only SIL3 Smart ESD device that is live during and after a shutdown. Patents Pending What is the SVI II ESD? The SVI II ESD is the
More informationCO General Specifications GS48D62Z00-00E-N GENERAL. ProSafe-COM extended communication system
General Specifications GS48D62Z00-00E-N CO-962-00 ProSafe-COM extended communication system GENERAL Figure 1 ProSafe-COM extended communication system is a multiple protocol communication interface connecting
More informationDigital Output Module 8-Channel Version for Zone 1 Series 9475/
www.stahl.de > 8-channel digital output > Intrinsically safe outputs Ex ia > For Ex i solenoid valves and display elements > Additional Ex i control input for "Plant STOP" (acc. IEC61508 up to SIL2) >
More informationPRM Integration Guide with. MTL 4840 Series HART Multiplexer
PRM Integration Guide with MTL 4840 Series HART Multiplexer This manual explains how to connect the MTL4840 Series HART Multiplexer and configure Yokogawa s Plant Resource Manager (PRM) software. This
More informationII ESD. SIL3 Partial Stroke Test Device. The only SIL3 Smart ESD device that is live during and after a shutdown.
SVI II ESD SIL3 Partial Stroke Test Device The only SIL3 Smart ESD device that is live during and after a shutdown. W h a t i s t h e S V I I I E S D? The SVI II ESD is the latest technology in emergency
More informationDeltaV SIS TM. Logic Solver. DeltaV SIS Logic Solver. Introduction. DeltaV SIS Product Data Sheet. World s first smart SIS Logic Solver
February 2016 Page 1 DeltaV SIS TM Logic Solver The DeltaV SIS platform is the world s smart SIS system to use the power of predictive intelligence for increasing the availability of the entire safety
More informationTank terminal demonstrates the electrically operated solution for Emergency Shutdown Valves
Case Study Tank terminal demonstrates the electrically operated solution for Emergency Shutdown Valves Botlek Tank Terminal Case Study - 26th April 2013 Botlek Tank Terminal Case Study - 26th April 2013
More informationScanner 2000 Steam Mass Flow Transmitter
3352051/2 IM-P335-24 MI Issue 2 Scanner 2000 Steam Mass Flow Transmitter Installation and Maintenance Instructions 1. Safety information 2. Mechanical installation 3. Configuring software 4. Wiring procedures
More informationDigital Output Module 8-Channel Version for Zone 2 Series 9475/
> 8-channel digital output > Intrinsically safe outputs Ex ia > For Ex i solenoid valves and display elements > Line fault monitoring per channel > Diagnostics based on NE107 > Module can be replaced in
More informationIQ Pro SIL option TÜV Certified for use in SIL 2 & 3 applications
IQ Pro SIL option TÜV Certified for use in SIL 2 & 3 applications IQ Pro range including SIL Safety Function Control Module option is TÜV certified for use in SIL 2 safety applications using a 1 out of
More informationINTRINSICALLY SAFE INSTRUMENTATION FOR HAZARDOUS AREAS
INTRINSICALLY SAFE INSTRUMENTATION FOR HAZARDOUS AREAS SHORT FORM 2002 SERIES D1000 Intrinsically Safe Galvanic Isolators SERIES D1000, for DIN Rail Mounting, provide the most simple and cost effective
More informationDescription. Monitoring functions Evaluation of brush length monitoring, digital, non-floating A00
Monitoring functions Evaluation of brush length monitoring, digital, non-floating Evaluation of brush length monitoring, digital, floating A00 A06 Non-floating brush length monitoring with use of KM01
More informationSafety Instrumented Systems: Can They Be Integrated But Separate?
Safety Instrumented Systems: Can They Be Integrated But Separate? Written by Merry Kuchle and Trevor MacDougall of Spartan Controls. For questions, please contact Robert Smith. Keywords Safety Instrumented
More informationChassis Power Supplies
PDC24 / PAC Chassis Power Supplies (PDC24 / PAC) Issue 3 October 2005 INTRODUCTION PURPOSE Two Power Supply Units (PSUs) provide a dual-redundant source of 5.4Vand 12Vdc onto the backplane for the modules
More informationGE Power Management. MMII Intelligent MCC Controller
A concept that will offer reduced overall installed cost and production efficiency through information availability to operators and maintenance. Presentation Overview 6 Applications 6 Protection and Control
More informationSafety Control Relay Product Catalog
Product Catalog Wall Mount for use with Safety Mats Safety Edges Safety Bumpers Safety Sensors 2 wire Safety Sensors 4 wire DIN Rail Mount Intrinsically Safe Explosion Proof Wall Mount Introduction The
More informationFault Tolerant Protection System (Safety PLC with Integrated Overspeed Protection)
Product Specification 03375 (Revision D, 12/2017) Description MicroNet Safety Module Fault Tolerant Protection System (Safety PLC with Integrated Overspeed Protection) The MicroNet Safety Module is a safety
More informationRemoval of Hardware ESD, Independent of Safety Logic Solver
Removal of Hardware ESD, Independent of Safety Logic Solver by Sam Roy Executive summary This is a discussion to remove independent hardware based Emergency Shutdown for Logic Solver as identified in ANSI/ISA-84.00.01-2004,
More informationPolymer Electric. Operating Instructions. Control Unit SG-EFS 1X4 ZK2/1 8k2. Version 3
Operating Instructions Control Unit SG-EFS 1X4 ZK2/1 8k2 Version 3 1003100 SG-EFS 104 ZK2/1 8k2 24 V=/~ 7500354 SG-EFS 134 ZK2/1 8k2 230 V~ Original instructions GmbH & Co. KG Polymer Electric Örlinger
More informationIQ SIL Option. IQ actuators for use in applications up to SIL 3. sira CERTIFICATION
IQ SIL Option IQ actuators for use in applications up to SIL Keeping the World Flowing RELIABILITY IN FLOW CONTROL CRITICAL APPLICATIONS RELIABLE OPERATION WHEN IT MATTERS Assured reliability for critical
More informationT500 DUALTACH. JAQUET T500 DualTach. 2 channel measurement & monitoring instrument 2 CHANNEL TACHOMETER I N C H A R G E O F S P E E D.
1-08 T500 DUALTACH 2 CHANNEL TACHOMETER JAQUET T500 DualTach 2 channel measurement & monitoring instrument JAQUET T500 DualTach 2 channel measurement and monitoring instrument for demanding machine protection
More informationFailure Modes, Effects and Diagnostic Analysis. Rosemount Inc. Chanhassen, MN USA
Failure Modes, Effects and Diagnostic Analysis Project: 8732C Magnetic Flow Transmitter Customer: Rosemount Inc. Chanhassen, MN USA Contract No.: Ros 03/07-26 Report No.: Ros 03/07-26 R001 Version V1,
More informationLoop-powered Transmitter for Thermocouple Type K (NiCr-Ni)
Data sheet 302040_en MTP300i-SIL-K Loop-powered Transmitter for Thermocouple Type K (NiCr-Ni) Properties 2-wire temperature transmitter for DIN rails Galvanic isolated TC-input with cold-junction compensation
More informationSafety manual. This safety manual is valid for the following product versions: Version No. V1R0
Safety manual HART TRANSPARENT driver 9107 This safety manual is valid for the following product versions: 9107-002 Version No. V1R0 0. CONTENTS 1. Observed standards... 2 2. Acronyms and abbreviations...
More informationThe TVC Positioner is designed to provide precise position control of rotary or linear hydraulic or pneumatic actuated valve systems.
TVC Positioner Introduction The TVC Positioner is designed to provide precise position control of rotary or linear hydraulic or pneumatic actuated valve systems. Key Features l Comprehensive diagnostics
More informationControl unit SG-EFS 104/4L. EN Operating instructions. Innovative by tradition. Version SG-EFS 104/4L AC/DC 24 V
Innovative by tradition. Control unit SG-EFS 104/4L EN Operating instructions Version 2 1004128 SG-EFS 104/4L AC/DC 24 V Original instructions Mayser GmbH & Co. KG Örlinger Straße 1 3 89073 Ulm GERMANY
More informationAI-917-A0. Analogue Input Module (4x 0-20 ma)
General Specifications GS48D17A00-00E-N AI-917-A0 Analogue Input Module (4x 0-20 ma) GENERAL Figure 1 This module has four analogue inputs and four logic pulse outputs. AI-917-A0 Analogue Input Module
More informationBackplane. System integration. Backplane
Backplane System integration Backplane Backplanes designed for minimum overall life cycle costs Simple, reliable and professional design Using standard cost-optimised DIN-rail devices Flexible connection
More informationSIL 2/3 Relays for all applications, with or without Line & Load Diagnostics. Product presentation
SIL 2/3 for all applications, with or without Line & Load Diagnostics Product presentation Safety Safety Functions Safety Functions can be basically divided in two main groups: ETS, Energize to Safety
More informationMultiphase Flowmeter FlowSys TopFlow Multiphase Meter Operations Manual
Issue/Rev. 0.1 (5/05) Multiphase Flowmeter FlowSys TopFlow Multiphase Meter Operations Manual Bulletin MNMP003 Contents Section 1 Introduction... Page 3 Section 2 TopFlow MultiPhase Meter... Page 4 Sensor
More informationTURCK Process Automation IS Interface Technology. Interface Modules. IM Series Cabinet
Process Automation IS Interface Technology Interface Modules TURCK's IM series of Isolating Intrinsically Safe Barriers is designed to be a simple and safe way to solve the problems associated with the
More informationThe new reference class F870S
The new reference class F870S Properties Suitable for hazardous areas Zone 1 and 21 Extended measurement and control BVS 10 ATEX E 112, IECex BVS 10.0095 SIL 2 - safety standard Compact system, mounting
More informationHazardous Area Protection
Hazardous Area Protection Global Solutions in Hazardous Area Surge and Lightning Protection Intrinsic Safety When instrumentation is installed in a potentially explosive environment steps must be taken
More informationSMARTSCAN INFORMATION
SMARTSCAN INFORMATION RY4 SERIES SAFETY RELAYS HANDBOOK Smartscan Ltd, Pywell Road, CORBY, NN17 5XJ, UK, Tel: +44 (0) 1536 401313, Fax: +44 (0) 1536 268954, Email: sales@smartscan.com, www.smartscan.co.uk
More informationControl unit SG-EFS 104/2W. EN Operating instructions. Innovative by tradition. Version SG-EFS 104/2W 24 V=/~
Innovative by tradition. Control unit SG-EFS 104/2W EN Operating instructions Version 0.9 1005196 SG-EFS 104/2W 24 V=/~ Original instructions Mayser GmbH & Co. KG Örlinger Straße 1 3 89073 Ulm GERMANY
More informationGeneral. Remote I/O A4/1.
www.stahl.de > Intrinsically safe Ex ia IIC, Ex e, Ex na or Ex nl inputs and outputs > Fieldbus communication: Modbus RTU, Profibus DP V0 and DP V1 HART, Industrial Ethernet, Modbus TCP, EtherNet/IP, PROFINET
More information2oo4D: A New Design Concept for Next-Generation Safety Instrumented Systems 07/2000
2oo4D: A New Design Concept for Next-Generation Safety Instrumented Systems 07/2000 Copyright, Notices and Trademarks 2000 Honeywell Safety Management Systems B.V. Revision 01 July 2000 While this information
More informationDigital Output Module 4-Channel Version for Zone 1 Series 9475/
www.stahl.de > 4-channel digital output > Intrinsically safe outputs Ex ia > For Ex i solenoid valves and display elements > Additional Ex i control input for "Plant STOP" (acc. IEC61508 up to SIL2) >
More informationOperating Instructions. Intrinsically Safe Isolation Relay for Switches Model: REL manual_rel-6_0505
Operating Instructions Intrinsically Safe Isolation Relay for Switches Model: REL-6003 manual_rel-6_0505 1. Contents 1. Contents...2 2. Note...3 3. Instrument Inspection...3 4. Regulation Use...3 5. Operating
More informationIntrinsically Safe Barriers
Intrinsically Safe Barriers Description Page No. Safety Barriers 464-472 Din Rail Isolated Barriers 473-488 477 Intrinsically Safe Barriers Product Overview We have simplified intrinsic safety! Cooper
More informationED17: Architectures for Process Safety Applications
ED17: Architectures for Process Safety Applications Name Pete Skipp Title Process Safety Architect Date November 5 th & 6 th 2012 Copyright 2012 Rockwell Automation, Inc. All rights reserved. Agenda An
More informationSigma XT Ancillary Board (K588)
Sigma XT Ancillary Board (K588) Operation and Maintenance Manual Man-1095 Issue 04 October 2009 Index Section Page 1. Introduction... 3 2. Safety and mounting... 3 3. Technical specification... 4 4. Connecting
More informationICS Regent. Monitored Digital Input Modules 24 VDC (T3411) PD-6031
ICS Regent PD-6031 Monitored Digital Input Modules 24 VDC (T3411) Issue 1, March, 06 Monitored digital input modules provide input sensing for 16 field input devices. With a line monitor device installed
More informationSkilmatic SI3-3 Electric Fail-Safe Actuators
Introducing the 3 rd generation of Skilmatic SI self-contained electric fail-safe actuators. The SI range of self-contained electrohydraulic actuators combining the simplicity of electrical operation with
More informationALTERNATING RELAYS & CONTROLLERS ARM Series
ALTERNATING RELAYS & CONTROLLERS ARM Series Process Control Equipment for Hazardous Locations 7M26 UL913 INCLUDES INTRINSICALLY SAFE INPUTS Integrated Duplex Controller SOSO Operation (Sequence-on, Simultaneous-off)
More informationProline Prowirl 72, 73
Functional Safety Manual Vortex flow measuring system with 4 20 ma output signal Application Monitoring of maximum and/or minimum flow in systems which are required to comply with particular safety system
More informationMACX MCR-EX-SD LP(-SP)
Intrinsically safe solenoid driver for Group IIC gases, loop-powered, current limit 48 ma INTERFACE Data sheet 103468_en_01 PHOENIX CONTACT - 08/2008 1 Description The solenoid driver MACX MCR-EX-SD-24-48-LP(-SP)
More information1/32-DIN TEMPERATURE CONTROLLER INSTALLATION, WIRING AND OPERATION MANUAL FORM 3882
1/32-DIN TEMPERATURE CONTROLLER INSTALLATION, WIRING AND OPERATION MANUAL FORM 3882 This manual is intended for use in support of installation, commissioning and configuration of the 1/32-DIN Temperature
More informationUSER MANUAL. Valve System Test Centre 1/26
USER MANUAL Valve System Test Centre 1/26 Table of contents 1 General... 3 1.1 Safety instructions... 3 2 Application... 4 3 Specifications... 5 3.1 Environment... 5 3.2 Terminals... 5 3.3 Dimensions and
More informationIQM & IQML RANGE CONTROL AND MONITORING FACILITIES. Publication E420E issue 7/02
IQM & IQML RANGE CONTROL AND MONITORING FACILITIES Publication E0E issue 7/0 IQM - STANDARD FACILITIES SPECIFICATION The type IQM actuator specification is generally as described in Publication No. E0E
More informationELECTRONIC AND CONTROL PROCESS DEVICES. reliability. professionalism. Company Profile.
ELECTRONIC AND CONTROL PROCESS DEVICES expertise reliability professionalism Company Profile www.datexel.it expertise reliability professionalism The Company The success of a company depends on many factors:
More informationFailure Modes, Effects and Diagnostic Analysis
Failure Modes, Effects and Diagnostic Analysis Project: 9106 HART Transparent Repeater and 9107 HART Transparent Driver Customer: PR electronics A/S Rønde Denmark Contract No.: PR electronics 06/03-19
More informationSTT 3000 Series STT250 Smart Temperature Transmitters Specifications Models STT25H, STT25S, STT25M, STT25D EN0I-6031 March 2010
STT 3000 Series STT250 Smart Temperature Transmitters Specifications Models STT25H, STT25S, STT25M, STT25D EN0I-6031 March 2010 Introduction Honeywell s STT 3000 family of microprocessor based smart temperature
More informationPF 3100 BMS CARD PRO.FIRE
PF 3100 BMS www.profireenergy.com 1.855.PRO.FIRE 1 TABLE OF CONTENTS PF3100 BMS INFORMATION GUIDE INTRODUCTION... 2 1.1 Functional Description.... 2 1.2 System Requirements.... 2 HARDWARE.... 3 2.1 Card
More informationT4HD: Installation Supplement R8.1.13
THD: Installation Supplement R8.. Smartscan Incorporated 08 Eight Mile Road Livonia MI 8 Tel: (8)77-900 Fax: (8) 77-7 Web: www.smartscaninc.com Smartscan Incorporated Livonia, Michigan THD The use of this
More informationApplying branch circuit breakers and supplementary protectors in North America
Supersedes June 2017 FAZ-NA-L FAZ-NA FAZ Applying branch circuit breakers and supplementary protectors in North America Introduction Eaton offers three types of miniature circuit breakers for use in North
More informationHigh-precision valve control using intelligent positioners. sipart
High-precision valve control using intelligent positioners sipart The SIPART PS2 electropneumatic positioner is number 1 in its field by a very wide margin. Our past experience gathered from 15 years in
More informationDatasheet - AZM300Z-ST-1P2P-A
08.04.2015-16:04:56h Datasheet - AZM300Z-ST-1P2P-A Solenoid interlock / AZM300 Suitable for mounting to profile systems Thermoplastic enclosure 3 different directions of actuation Compact design 3 LEDs
More informationMAINTENANCE MANUAL. EDACS REDUNDANT POWER SUPPLY SYSTEM 350A1441P1 and P2 POWER MODULE CHASSIS 350A1441P3, P4, AND P5 POWER MODULES TABLE OF CONTENTS
MAINTENANCE MANUAL EDACS REDUNDANT POWER SUPPLY SYSTEM 350A1441P1 and P2 POWER MODULE CHASSIS 350A1441P3, P4, AND P5 POWER MODULES TABLE OF CONTENTS SPECIFICATIONS*... 2 INTRODUCTION... 3 DESCRIPTION...
More informationSYSTEM COMPONENTS SYSTEM COMPONENTS MODULES
SYSTEM COMPONENTS SYSTEM COMPONENTS MODULES O U R P R O F E S S I O N MULTIFUNCTIONAL CURRENT CONTROLLED SWITCH MODULES MAIN FEATURES 4 20 ma input Relay output Rail mountable Intrinsically safe Associated
More informationMTL830 SERIES. Cuts installation and cable costs for all IS hazardous-area circuits
830 SERIES Cuts installation and cable costs for all IS hazardous-area circuits Reduce the cost of installing hazardous-area cabling Save installation time, space and weight Highlight problems quickly
More informationDigital Positioner 8049
Compact digital positioner for pneumatic control valves. Positioner can be integrated into valve actuator (no external moving parts for stroke feedback) Wide range of strokes - 8 mm No steady-state air
More informationCONTROL PANEL WIRING SPECIFICATIONS
CONTROL PANEL WIRING ISSUE STATUS FIRST REV DESCRIPTION DATE 001 1 ST ISSUE 22/04/2014 002 1 ST AMMENDMENT 10/03/2017 003 2 ND AMMENDMENT 08/09/2017 THIS DOCUMENT IS DESIGNED TO COVER ALL APPLICATIONS,
More informationtechnical datasheet technical datasheet MTL660 Displays Loop-powered indicators for hazardous areas
technical datasheet technical datasheet MTL0 Displays Loop-powered indicators for hazardous areas Loop powered -0mA Field and panel mounting Environmental protection to IP7 Easy to configure Number of
More informationSafeC S to MSR127 Conversion
Application Note SafeC S to MSR127 Conversion IMPORTANT: A risk assessment must be completed to assure that all tasks and hazards are considered and confirm that the example circuit will provide adequate
More informationTwickenham. Scientific Instruments. The Transfer Control Module (TCM) Instruction manual, release 1.1
.. Twickenham TSI Scientific Instruments The Transfer Control Module (TCM) Instruction manual, release 1.1 Twickenham Scientific Instruments Ltd. Registered in England No 2991094 Registered Office: 61d
More informationEngineering Guideline. pac-carriers Type for Honeywell system Experion Series C I/O
Engineering Guideline pac-carriers Type 995 for Honeywell system Experion Series C I/O pac-carrier Type 995 Engineering Guideline/Honeywell 04..009 pac-carrier Type 995 Integration of conventional process
More informationTerminal Block Catalog Numbers 1719-TB6, 1719-TB6S, 1719-TB8, 1719-TB8S, 1719-TB8Sx2, 1719-TB8x2
Technical Data Communication Adapter Catalog Number 1719-AENTR I/O Module Catalog Numbers 1719-IJ, 1719-IBN8B, 1719-IF4HB, 1719-IR4B, 1719-IT4B, 1719-OB2, 1719-OB2L, 1719-CF4H Power Supply Catalog Number
More informationDigital Output Module 4-Channel Version for Zone 1 Series 9475/
www.stahl.de > 4-channel digital output > Intrinsically safe outputs Ex ib > Suitable for Ex i hydraulic valves and solenoid valves > Additional Ex i control input for (in accordance with IEC 61508 through
More informationOperating instructions. Standstill monitor A / / 2011
Operating instructions Standstill monitor A300 UK 1 2 3 4 5 6 7 8 7390337 / 01 02 / 2011 1 2 3 4 5 6 7 8 switchpoint min max pulse/min power Made in Germany ifm electronic gmbh D 45127 Essen func. I II
More informationSafety Barriers. CEAG safety barriers can be used for all kinds of instrumentation applications.
Safety Barriers Description Safety barriers limit the energy fed to an intrinsically safe circuit so that neither sparks nor thermal effects (hot surfaces) can cause an explosion. CEAG safety barriers
More informationAPPLICATION GUIDE. Interface Modules IM Series.
Interface Modules IM Series APPLICATION GUIDE www.turck.com Interface Technology Interface Modules TURCK's IM series of Isolating Intrinsically Safe Barriers is designed to be a simple and safe way to
More informationOperating Instructions
Operating Instructions System 57 Total environmental solutions Ensure that you read and understand these instructions BEFORE operating the equipment. Please pay particular attention to the Safety Warnings.
More informationRT4F-120V/20A-WAC RECTIFIER
The RT4F-120V/20A-WAC is a switched mode rectifier/charger module designed to provide up to 20A of output current into a 120V nominal system. This charger has been designed for use in conjunction with
More informationHART Temperature Transmitter for up to SIL 2 applications
HART Temperature Transmitter for up to SIL 2 applications Inor Process AB 05/2014 86B520S001 R1.3 1 Introduction... 3 1.1 Field of application... 3 1.2 User benefits... 3 1.3 Manufacturer s safety instructions...
More informationInstallation & Operation and Maintenance
Gas Safety Products Dual Current Monitor Installation & Operation and Maintenance Read these instructions carefully before operating or servicing Rev: 01 Date: 12-02-18 1 CONTENTS Chapter Content Page
More informationD Issue D Original. Instruction Manual. Micro Tool Interface
Instruction Manual D373-60-880 Issue D Original Micro Tool Interface Description SPI Micro-TIM MCM Micro-TIM TEL Micro-TIM SEMI E73 Micro-TIM LAM Alliance Micro-TIM Novellus C3 Micro-TIM Hitachi Micro-TIM
More informationProductDiscontinued. Rosemount TankRadar Rex. Safety Manual For Use In Safety Instrumented Systems. Safety Manual EN, Edition 1 June 2007
Safety Manual Rosemount TankRadar Rex Safety Manual For Use In Safety Instrumented Systems ProductDiscontinued www.rosemount-tg.com Safety Manual Rosemount TankRadar Rex Safety Manual Rosemount TankRadar
More informationDeltaV Safety Instrumented System (SIS) with Electronic Marshalling
DeltaV SIS Process Safety System Product Data Sheet DeltaV Safety Instrumented System (SIS) with Electronic Marshalling Optimized process reliability Simplified safety lifecycle management Flexibility
More informationMicroNet TMR Control System
Product Specification 03363 (Rev. C) MicroNet TMR Control System Applications The MicroNet TMR (triple modular redundant) controller is a state-of-the-art digital control platform designed to reliably
More informationSX90 Process Controller
Local regulations may restrict the use of this product to below the conditions quoted. In the interests of development and improvement of the product, we reserve the right to change the specification without
More informationMEASURING AND MONITORING RELAYS
MEASURING AND MITORING RELAYS Slim Models for Monitoring Current and Voltage NEW Measuring and Monitoring Relays Measuring and Monitoring Relays K8AB Industry First! Measuring and Monitoring Relays Two
More informationHR1S-AC Safety Relay Modules
HRS-AC Relay Modules Transistor output provided. Removable terminal block (HRS-AC52P) allows for easy module replacement. Fault diagnosis function with dual safety circuits. Internal relay operations can
More informationCombinable for All Applications
Combinable for All Applications 3SE5 Position Switches www.siemens.com/sirius-detecting The Clever Answer to Information Diversity in the Field The Comprehensive Range of Position Switches 3SE5 position
More informationIntelligent Valve Controller NDX. Safety Manual
Intelligent Valve Controller NDX Safety Manual 10SM NDX en 5/2017 2 Intelligent Valve Controller NDX Safety Manual Table of Contents 1 General information...3 1.1 Purpose of the document... 3 1.2 Description
More informationInductive sensor Dual sensors with extended temperature range NI4-DSU35TC-2Y1X2/S97
ATEX category II 2 G, Ex zone 1 ATEX category II 1 D, Ex-zone 20 for temperatures up to -25 C SIL2 acc. to IEC 61508 Rectangular, housing DSU35 Plastic, PP-GF30-VO Two outputs for monitoring the position
More informationMobrey Hydratect 2462
Mobrey Hydratect 2462 Functional Safety Manual Functional Safety Manual Functional Safety Manual Table of Contents Contents 1Section 1: Introduction 1.1 Scope and purpose of the safety manual..................................
More informationDigital Output Module 8-Channel Version for Zone 2 Series 9475/
> 8-channel digital output > Intrinsically safe outputs Ex ia > For Ex i solenoid valves and display elements > Line fault monitoring per channel > Diagnostics based on NE107 > Module can be replaced in
More informationFUNCTIONAL SAFETY CERTIFICATE
FUNCTIONAL SAFETY CERTIFICATE This is to certify that the SI-1Q and SI-2/2.1Q Skilmatic Intelligent Electro-hydraulic Quarter-turn Valve Actuators manufactured by Rotork Fluid Systems Ltd (A Division of
More informationEagle Logic Solver (ELS) SPECIFICATION DATA SIL-2 Rated Fire & Gas System
Eagle Logic Solver (ELS) SPECIFICATION DATA SIL-2 Rated Fire & Gas System -1.2 Table of Contents FEATURES............................................... 1 OVERVIEW...............................................
More informationPoint Level Transmitters. Pointek CLS200 (Standard) Functional Safety Manual 02/2015. Milltronics
Point Level Transmitters Pointek CLS200 (Standard) Functional Safety Manual 02/2015 Milltronics Introduction 1 General safety instructions 2 Pointek Level Instruments Device-specific safety instructions
More informationProduct Specifications
Product Specifications VIBROCONTROL 6000 Monitoring System Description of Functionality Overview The VIBROCONTROL 6000 Monitoring System is used for both stand-alone machine protection and condition monitoring
More informationDräger Polytron 8200 Stationary gas detector (CatEx)
Dräger Polytron 8200 Stationary gas detector (CatEx) Quick, reliable and cost-effective detection of combustible gases and vapours in the ambient air: the microprocessor-based transmitter is the result
More informationSafety instructions Overvoltage protection B81-35
Safety instructions Overvoltage protection B81-35 IECEx BVS 15.0084X Intrinsic safety Document ID: 51001 Contents 1 Area of applicability... 3 2 General information... 3 3 Technical data... 5 4 Application
More informationApplying branch circuit breakers and supplementary protectors in North America
Product Application AP01102005E WMZT WMZS Applying branch circuit breakers and supplementary protectors in North America Introduction Eaton offers two types of miniature circuit breakers for use in North
More informationMTL8000-2/x Series Modular I/O
-2/x Series Modular Overview Modules Modules - Overview - 2/2 components Use this option for general purpose or nonhazardous applications, or where the equipment and/or field wiring has to be mounted in
More informationInductive sensor For rotary actuators NI4-DSU35TC-2Y1X2
ATEX category II 2 G, Ex zone 1 ATEX category II 1 D, Ex zone 20 SIL2 (Low Demand Mode) acc. to IEC 61508, PL c acc. to ISO 13849-1 at HFT0 SIL3 (All Demand Mode) acc. to IEC 61508, PL e acc. to ISO 13849-1
More informationSolutions for Oil and Gas
Solutions for Oil and Gas From the control room to the field. Field wiring for hazardous areas Weidmuller offers stainless steel and mild steel enclosures, assembled and certified according to your specific
More informationINTRINSICALLY SAFE Ex ia PSU TYPE AC36W
Title INTRINSICALLY SAFE Ex ia PSU TYPE AC36W USER MANUAL Document Number 66-184-12 Issue 10 10 Update new logo and address 2017.10.18 CW CW PC 09 Added Um as 265V, Io up to 3.3A & IIB data 2017.08.21
More information