COM600 Station Automation Series IEC Slave (OPC) 3.2. User's Guide

Size: px
Start display at page:

Download "COM600 Station Automation Series IEC Slave (OPC) 3.2. User's Guide"

Transcription

1 IEC

2

3 1RS Issued: Version: E/ IEC Contents: 1. About this manual Copyrights Trademarks General Document conventions Terminology Abbreviations Related documents Document revisions Introduction Product overview IEC101 Slave PC Client features Configuration About this section verview of configuration Building object tree General about building object tree Adding IEC101 Slave PC Client Adding Channel objects Adding Device objects Adding data objects Configuring objects General about configuring objects Configuring IEC101 Slave PC Client properties Configuring Channel Properties Configuring IEC101 Balanced Channel properties Configuring IEC101 Unbalanced Channel properties Configuring Device Properties Configuring IEC101 Device properties Configuring Data objects General about configuring data objects Single point status (SPS) Double point status (DPS) Integer status (INS) Protection activation information (ACT) Directional protection activation information (ACD) Binary counter reading (BCR) easured value (V) Complex measured value (CV)

4 IEC RS WYE Delta (DEL) Controllable single point (SPC) Controllable double point (DPC) Controllable integer status (INC) Binary controlled step position information (BSC) Integer controlled step position information (ISC) Analogue set point (APC) peration About this section Activating Gateway with new configurations IEC101 Slave PC Client diagnostics IEC101 Channel diagnostics IEC101 Device diagnostics Signal diagnostics Technical reference About this section IEC data modeling General about IEC data modeling Single point status (SPS) Double point status (DPS) Integer status (INS) Protection activation information (ACT) Directional protection activation information (ACD) Binary counter reading (BCR) easured value (V) Complex measured value (CV) WYE Delta (DEL) Controllable single point (SPC) Controllable double point (DPC) Controllable integer status (INC) Binary controlled step position information (BSC) Integer controlled step position information (ISC) Analogue set point (APC) Status codes Introduction Link layer status codes Application layer status codes Attributes General about attributes Client attributes Channel attributes

5 1RS IEC Device attributes Appendix Interoperability list for IEC101 PC Client Index

6 6

7 1RS About this manual IEC Copyrights The information in this document is subject to change without notice and should not be construed as a commitment by ABB y. ABB y assumes no responsibility for any errors that may appear in this document. In no event shall ABB y be liable for direct, indirect, special, incidental or consequential damages of any nature or kind arising from the use of this document, nor shall ABB y be liable for incidental or consequential damages arising from use of any software or hardware described in this document. This document and parts thereof must not be reproduced or copied without written permission from ABB y, and the contents thereof must not be imparted to a third party nor used for any unauthorized purpose. The software or hardware described in this document is furnished under a license and may be used, copied, or disclosed only in accordance with the terms of such license. Copyright 2006 ABB. All rights reserved Trademarks ABB is a registered trademark of ABB Group. All other brand or product names mentioned in this document may be trademarks or registered trademarks of their respective holders General This manual provides thorough information on the PC Client for IEC Slave protocol (later in this manual IEC101 Slave PC Client) and the central concepts related to it. You will find instructions on to take it into use. The basic operation procedures are also discussed. Information in this user s guide is intended for application engineers who need to configure IEC101 Slave PC Client in order to establish communication to an PC server. As a prerequisite, you should understand IEC protocol and the basic procedures in C600 Communication Engineering Tool (CET). This user s guide is divided into following sections: 7

8 IEC RS Introduction This section gives an overview of the IEC101 Slave PC Client and states the system requirements to be met when using the client. Configuration In this section you will find an overview of the configuration tasks and instructions on how to create and configure IEC101 Slave PC Client related objects. peration This section covers the basic operation procedures you can carry out when transferring or activating the Communication Gateway C610 computer or Station Computer 615 with new configurations. You are also given instructions on how to monitor and control the IEC101 communication. Technical reference This section contains a list of status codes and information about the IEC data modelling Document conventions The following conventions are used for the presentation of material: The words in names of screen elements (for example, the title in the title bar of a window, the label for a field of a dialog box) are initially capitalized. Capital letters are used for the name of a keyboard key if it is labeled on the keyboard. For example, press the ENTER key. Lowercase letters are used for the name of a keyboard key that is not labeled on the keyboard. For example, the space bar, comma key, and so on. Press CTRL+C indicates that you must hold down the CTRL key while pressing the C key (to copy a selected object in this case). Press ESC E C indicates that you press and release each key in sequence (to copy a selected object in this case). The names of push and toggle buttons are boldfaced. For example, click K. The names of menus and menu items are boldfaced. For example, the File menu. The following convention is used for menu operations: enuname > enu- Item > CascadedenuItem. For example: select File > New > Type. The Start menu name always refers to the Start menu on the Windows taskbar. System prompts/messages and user responses/input are shown in the Courier font. For example, if you enter a value out of range, the following message is displayed: 8

9 1RS IEC Entered value is not valid. The value must be 0 to 30. You may be told to enter the string IF349 in a field. The string is shown as follows in the procedure: IF349 Variables are shown using lowercase letters: sequence name 1.5. Terminology The following is a list of terms associated with the IEC101 Slave PC Client that you should be familiar with. The list contains terms that are unique to ABB or have a usage or definition that is different from standard industry usage. Term Alarm Alarms and Events; AE Data Access; DA Data bject; D Data Set Device Event Intelligent Electronic Device Logical Device; LD Logical Node; LN LN LN Application Guideline for substation automation; LAG An abnormal state of a condition. An PC service for providing information about alarms and events to PC clients. An PC service for providing information about process data to PC clients. Part of a logical node object representing specific information, e.g., status or measurement. From an object-oriented point of view a data object is an instance of a class data object. Ds are normally used as transaction objects; i.e., they are data structures. The data set is the content basis for reporting and logging. The data set contains references to the data and data attribute values. A physical device that behaves as its own communication node in the network, e.g. protection relay. Change of process data or an PC internal value. Normally, an event consists of value, quality and timestamp. A physical IEC device that behaves as its own communication node in the IEC protocol. Representation of a group of functions. Each function is defined as a logical node. A physical device consists of one or several LDs. The smallest part of a function that exchanges data. A LN is an object defined by its data and methods. A communication protocol developed by Echelon. A proprietary method of ABB on top of the standard LN protocol. 9

10 IEC RS Term PC PC item Property Report Control Block SPA SPA device Substation Configuration Language; SCL Series of standards specifications aiming at open connectivity in industrial automation and the enterprise systems that support industry. Representation of a connection to the data source within the PC server. An PC item is identified by a string <object path>:<property name>. Associated with each PC item are Value, Quality and Time Stamp. Named data item. The report control block controls the reporting processes for event data as they occur. The reporting process continues as long as the communication is available. ABB proprietary communication protocol used in substation automation. Protection and/or Control Product supporting the SPA protocol version 2.5 or earlier. XL-based description language for configurations of electrical substation IEDs. Defined in IEC standard Abbreviations The following is a list of abbreviations associated with the IEC101 Slave PC Client that you should be familiar with. See also 1.5, Terminology. Abbreviation AE ASDU BRCB CET DA DCD D GW HI IEC IED LAG LAN LD Alarms and Events Application Service Data Unit Buffered Report Control Block Communication Engineering Tool Data Access Data essage Code Definition Data bject Gateway, component connecting two communication networks together Human achine Interface International Electrotechnical Commission Intelligent Electronic Device LN Application Guideline for substation automation Local Area Network Logical Device 10

11 1RS IEC Abbreviation LK LN LSG NCC NV LE PC P&C RTS SA SCL SLD SNTP SAP RCB URCB XL Lonark interoperable device communicating in LonWorks network. In this document the term is used for devices that do not support the ABB LN/LAG communication. Logical Node LN SPA Gateway Network Control Center Network Variable bject Linking and Embedding LE for Process Control Protection & Control Request To Send Substation Automation Substation Configuration Language Single Line Diagram Simple Network Time Protocol Simple bject Access Protocol Report Control Block Unbuffered Report Control Block extended arkup Language 1.7. Related documents Name of the manual C600 User s Guide RS number 1RS Document revisions Document version/date A/ B/ C/ D/ E/ Product revision History Document created Document revised Document revised Document revised Document revised 11

12 IEC RS Introduction 2.1. Product overview The IEC protocol slave interface of the Communication Gateway C610 and the Station Computer C615 enables master systems communicating with protocol to receive data from and deliver commands to P&C devices connected to the GW. The IEC101 slave is implemented as an PC client, which transfers and converts data between the IEC slave protocol interface and the PC servers of the C600. See C600 for more details. The IEC101 Slave PC Client is configured using the Communication Engineering Tool (CET). Communication Engineering Tool (CET) can also be used for diagnosing and controlling the operation of the IEC101 Slave PC Client. C610/615 has a web server that can be used for remote diagnostic of the Gateway including the IEC101 Slave PC Client. The IEC101 Slave PC Client uses serial communication (RS232 interface). Before you can start using the IEC101 PC Client, at least one PC server has to be configured to provide access to the process devices. In this manual, the term IEC101 Device is used for a virtual station in the C610/615 representing the slave stations visible to the IEC101 master system IEC101 Slave PC Client features The IEC101 Slave PC Client supports the following features: PC Data Access Client v. 1.0/2.0 for accessing data from the PC servers PC Alarms and Events specifications v for diagnostic and control purposes IEC data modeling System supervision: NCC connection supervision Supported IEC data types and functions (see, Interoperability list for IEC101 PC Client for more information): Balanced and unbalanced communication Redundant communication channels Single and double indications easurement values Direct and secured commands Reception of time synchronization Parametrization and disturbance recorder upload via Transparent SPA 12

13 1RS Configuration IEC About this section This section guides you in the configuration tasks required before you can start using the IEC101 Slave PC Client. For information on the IEC data modeling, refer to the C600. First you need to start Communication Engineering Tool (CET) to open a project where at least one PC server has been configured. You can also open and name a new project, where you configure at least one PC server. 1. Select File > pen/anage Project In the pen/anage Project dialog, select the required location for the project: Projects on my computer Projects on network 3. Select New Project on the left. Enter a Project Name. The is optional. 4. Click Create 5. Click pen Project 3.2. verview of configuration Before you can start using the IEC101 Slave PC Client, you need to build and configure an object tree in Communication Engineering Tool (CET) to define the Communication structure within the Gateway object. IEC101 Slave PC Client IEC101 PC Balanced Channel IEC101 PC Unbalanced Channel IEC101 Device (IEC101 IED) Data objects Figure shows an example view of Communication Engineering Tool (CET) including an object tree in the communication structure on the left and bject Properties window displaying the object properties on the right. When configuring PC servers the following characters cannot be used in object names: \ ` ' ' # 13

14 IEC RS IEC101_configuration_overview.bmp Figure Example view of Communication Engineering Tool (CET) The configuration work can basically be divided into two separate tasks: 1. building an object tree, and 2. configuring object properties. First, you need to build an object tree. This is done by adding objects to the object tree, see 3.3.1, General about building object tree and 3.3.5, Adding data objects. Figure shows an example of how the object tree may look like after it has been built. In the example tree you can see the IEC101 PC Client object and its child objects like channels, devices, and data objects. Indentation is used to indicate the parent-child relationship between the objects. After you have added the necessary objects to the object tree in the communication structure, you need to configure them, see 3.4.1, General about configuring objects. Table describes the objects shown in the object tree (Figure 3.2-1). Table IEC101 PC Client related objects bject IEC101 PC Client IEC101 Balanced Channel An object representing the IEC101 PC Client. An object representing the IEC101 channel using balanced communication mode (point to point connection). 14

15 1RS IEC bject IEC101 Unbalanced Channel IEC101 Device (IEC101 IED) Data bject (D) Event Definitions An object representing IEC101 Channel using unbalanced communication mode (polled multipoint connection). IEC101 Device is used for a virtual station in the C610/615 representing the slave stations visible to the IEC101master system. A data object is an instance of one of the IEC Common data classes, for example single point status, measured value etc. Depending on the class, each data object has a set of attributes for monitoring and controlling the object, for instance value, quality and control. Data objects are connected from PC servers to the IEC101 Slave PC Client with the cross reference function. They are shown as child objects of the IEC101 Device object in the object tree. Event definitions are used for the diagnostic PC A&E Server Building object tree General about building object tree The object tree is built in the Communication structure of the C600 Engineering Tool, see Figure It is built by adding objects in a logical order starting from the IEC101 Slave PC Client object. Before the IEC101 Slave PC Client can be taken into use, an PC server has to be configured for the process communication. For more information on this subject, refer to the C600 You have several possible ways to add objects to the object tree in the Communication structure: You can right-click the object to which you want to add a child object. You can copy the object. Add the objects in the following order: 1. IEC101 Slave PC Client 2. IEC101 Balanced Channel / IEC101 Unbalanced Channel 3. IEC101 Device (IEC101 IED) 4. Data objects For information on building a substation structure, refer to C605, C615 HI Configuration anual. 15

16 IEC RS Adding IEC101 Slave PC Client To start building the object tree, add the IEC101 Slave PC Client object in the Communication structure by selecting the Gateway object, right-click it and select New > IEC101 > IEC101 Slave PC Client, Figure Figure Adding a new IEC101 PC Client object AddingClient101.jpg Adding Channel objects After the IEC101 Slave PC Client object has been successfully added, you can continue building the object tree by adding either the IEC101 Balanced Channel object or the IEC101 Unbalanced Channel object. To add IEC101 Channel object: 1. Select an IEC101 Slave PC Client object and right-click it. 2. Add an IEC101 Balanced Channel object or an IEC101 Unbalanced Channel object. 3. Rename the new object. Note that the names of the IEC101 Channels have to be unique. 16

17 1RS IEC Adding Device objects After a channel object has been successfully added, you can continue building the structure by adding the IEC101 Device object. All the data can be connected to one device or divided to several slave devices. Before dividing data to several slave devices, it must be checked that the current protocol mode and the master system support the feature. To add IEC101 Device object: 1. Select a Channel object. 2. Add an IEC101 Device object. 3. Rename the new object. Note that the names within an IEC101 Channel have to be unique Adding data objects Data objects are added somewhat differently than the upper level objects. Basically, you drag and drop the data objects you need from an PC server to the IEC101 Slave PC Client. To add data objects: 1. Select an IEC101 Device object (IEC101 IED) and right-click it. 2. Select Cross References. The Cross References window appears (Figure ). 3. In the Project Explorer, select now a logical node within an PC server, from which you want to connect the data objects to IEC101 Slave PC Client. Note that you can also select an upper level (server, channel, etc.) object and drag and drop it into the Cross Reference window. As a result, all the data objects within the selected object appear now in the Cross References window and can be connected to IEC101 Slave PC Client. 4. Drag and drop the logical node into the Cross References window. The data objects within the logical node appear now in the Cross References window. Note that only data objects that have been given a non zero information value in the Cross References table will be connected to the IEC101 Device. 5. At this point, click Apply to create the cross references (to connect the data objects to the IEC101 Device object). 17

18 IEC RS Figure The Cross References window CrossReferences101.jpg How to use the Cross References window In the Cross References window, you can use a filter file to leave out some of the data objects to be connected to IEC101 Device. Select the filter file to be used from the dropdown menu Active Filter (see Figure ). If there are no filter files listed in the dropdown menu, you can create your own filter file by clicking odify Filter File. You can also modify an existing filter file to meet your needs. The Cross References table allows you to view the data objects by type. Use the tabs in the upper part of the table to do this. Under the General tab, you can see all the data objects and their property values. Here you can sort the data objects by clicking the column heading (bject Name,, Type, etc.). There is a possibility to export the cross references table to icrosoft Excel and to import the table from icrosoft Excel. Clicking Apply connects the data objects to the IEC101 Device. After clicking Apply, you can change the data object values either in the bject Properties window or in the Cross References window. For more detailed instructions on configuring the data object properties in the Cross References window, see , General about configuring data objects. 18

19 1RS Configuring objects IEC General about configuring objects After the objects have been added, you need to configure the object properties. Figure shows an example of how to use Communication Engineering Tool (CET) to configure the object properties for IEC101 Slave PC Client. To configure an object: 1. Select an object in the object tree of the communication structure. 2. The object properties appear now in the bject Properties window. The properties and their values can be viewed as shown in Figure Figure Example of object properties in the bjects Properties window bjprop.jpg 3. Select the property you want to configure. Depending on the property value type, configuring is always done either by selecting a predefined value from a drop-down menu, or entering a text string or a numerical value in a text field. 19

20 IEC RS The available properties for different objects are listed in the following subsections Configuring IEC101 Slave PC Client properties Table lists the configurable IEC101 Client properties and value ranges for them. The actual configuration by using the C600 Communication Engineering Tool (CET) is performed as described in 3.4.1, General about configuring objects. Table IEC101 Slave PC Client properties Property / Parameter Basic aximum PC Server Initialization Time Prog ID AE ProgID DA Time Zone Correction Station/Remote Switch Station/Remote Switch Station/Remote Switch Error Default: Default: 0 Do not check Station/Remote switch position, command always allowed. Check Station/Remote switch position. Default: Do not check Station/Remote switch position, command always allowed. Reject commands if position bad or unknown. Allow commands if position bad or unknown. Default: Reject commands if position bad or unknown Specifies the maximum time in seconds that any connected (configured) PC Server requires to retrieve all its initial data. Instance identification of diagnostic PC alarm and event server. Instance identification of diagnostic PC data access server. The value of this property in minutes is added to the synchronization time received from an IEC101 master. Specifies if a position check for the station remote switch is going to be made. Specifies what to do with commands if the position of the switch is uncertain. 20

21 1RS IEC Configuring Channel Properties Configuring IEC101 Balanced Channel properties The IEC101 Balanced Channel properties that can be configured and value ranges for them can be found in Table The actual configuration by using the C600 Communication Engineering Tool (CET) is performed as described in 3.4.1, General about configuring objects. Table IEC101 Balanced Channel properties Property / Parameter Basic In Use Protocol Communication Port Baud Rate In use Not in use Dafault: In use IEC Balanced Slave 300 bits/s 600 bits/s 1200 bits/s 2400 bits/s 4800 bits/s 9600 bits/s bits/s bits/s bits/s bits/s bits/s bits/s bits/s Default: bits/s Specifies whether the channel is initially in use or not. Protocol Transmission rate used on the channel. 21

22 IEC RS Property / Parameter Communication Port Parity Receiver Data Bit Count Stop Bits Transmitter Data Bit Count Communication Control Carrier Blocking CTS Delay Enquiry Limit Header Timeout Keep Alive Timeout C1...C8 Default: C1 No parity check Even dd Default: Even Default: 8 1 stopbit 2 stopbits Default: 1 stopbit Default: 8 Carrier detect signal is ignored Carrier detect signal must be set Default: Carrier detect signal must be set Default: Default: Default: Default: 5000 Serial port used by the IEC protocol. Number of ports depends on the used hardware. Specifies the parity check used for the characters transferred on the channel. Specifies the number of data bits in each received character. Specifies the number of data bits in each transmitted character. Specifies the number of stop bits attached to each transmitted character. Determines whether the Carrier Detect signal of the serial port must be set in order for the IEC station to receive messages Delay in milliseconds between activation of the RTS signal and start of new transmission. Specifies maximum number of times that a message is transmitted after timeout. aximum waiting time in milliseconds of a link layer response. The connection is considered to be alive if the delay between two consecutive master messages is shorter than the specified time in milliseconds. 22

23 1RS IEC Property / Parameter Link Type perating ode Response Timeout RTS Keepup Delay RTS Keepup Padding Characters Transmission Wait Delay RTS activated during transmission (Unbalanced slave) RTS always active, reception always enabled (Balanced slave) RTS activated during transmission, reception always enabled (Balanced slave) Default: RTS always active, reception always enabled (Balanced slave) Handshaking messages not restarted Handshaking messages restarted Default: Handshaking messages not restarted Default: Default: Default: Default: 15 The type of the data link connection used on the channel. Specifies whether the handshaking messages (request, status of link, reset of remote link) are restarted when a request status of link message is received from the remote end. The time that IEC link waits for the end of the received message in seconds. The number of characters for calculating delay for resetting RTS signal. The number of padding characters inserted to the end of telegram to delay the resetting of RTS signal. Delay in milliseconds between receiving CTS signal and start of transmission Configuring IEC101 Unbalanced Channel properties The IEC101 Unbalanced Channel properties that can be configured and value ranges for them can be found in Table The actual configuration by using the C610 Communication Engineering Tool (CET) is performed as described in 3.4.1, General about configuring objects. Table IEC101 Unbalanced Channel properties Property / Parameter Basic 23

24 IEC RS Property / Parameter In Use Protocol Communication Port Baud Rate Communication Port Parity Receiver Data Bit Count In use Not in use Default: In use IEC Unbalanced Slave 300 bits/s 600 bits/s 1200 bits/s 2400 bits/s 4800 bits/s 9600 bits/s bits/s bits/s bits/s bits/s bits/s bits/s bits/s Default: bits/s C1...C8 Default: C1 No parity check Even dd Default: Even Default: 8 Specifies whether channel is initially in use. Protocol Transmission rate used on the channel. Serial port used by the IEC protocol. Number of ports depends on the used hardware. Specifies the parity check used for the characters transferred on the channel. Specifies the number of data bits in each received character. 24

25 1RS IEC Property / Parameter Stop Bits Transmitter Data Bit Count Communication Control Carrier Blocking CTS Delay Enquiry Limit Header Timeout Keep Alive Timeout Link Type 1 stopbit 2 stopbits Default: 1 stopbit Default: 8 Carrier detect signal is ignored Carrier detect signal must be set Default: Carrier detect signal is ignored Default: Default: Default: Default: 5000 RTS activated during transmission (Unbalanced slave) RTS always active, reception always enabled (Balanced slave) RTS activated during transmission, reception always enabled (Balanced slave) Default: RTS activated during transmission (Unbalanced slave) Specifies the number of data bits in each transmitted character. Specifies the number of stop bits attached to each transmitted character. Determines whether the Carrier Detect signal of the serial port must be set in order for the IEC station to receive messages Delay in milliseconds between activation of the RTS signal and start of new transmission. Specifies maximum number of times that a message is transmitted after timeout. aximum waiting time in milliseconds of a link layer response. The connection is considered to be alive if the delay between two consecutive master messages is shorter than the specified time in milliseconds. The type of the data link connection used on the channel. 25

26 IEC RS Property / Parameter perating ode Response Timeout RTS Keepup Delay RTS Keepup Padding Characters Transmission Wait Delay Handshaking messages not restarted Handshaking messages restarted Default: Handshaking messages not restarted Default: Default: Default: Default: 15 Specifies whether the handshaking messages (request, status of link, reset of remote link) are restarted when a request status of link message is received from the remote end. The time that IEC link waits for the end of the received message in seconds. The number of characters for calculating delay for resetting RTS signal. The number of padding characters inserted to the end of telegram to delay the resetting of RTS signal. Delay in milliseconds between receiving CTS signal and start of transmission Configuring Device Properties Configuring IEC101 Device properties Table lists the configurable properties for IEC101 Device and value ranges for these properties. The actual configuration by using the C600 Communication Engineering Tool (CET) is performed as described in 3.4.1, General about configuring objects. Table IEC101 Device properties Name Basic Diagnostics Enabled Has Redundant Line Value/Value range True False Default: False True False Default: False Specifies whether diagnostic AE events are sent for the station or not. Specifies whether redundant channel is used or not. 26

27 1RS IEC Name In Use Addresses Polling Address Station Address Communication control Reply Window Size Value/Value range In use Not in use Default: In use or Default: 1 The maximum value depends on the corresponding Polling Address Length property value as follows: when Polling Address Length property value is 1, the value range for the Polling Address is and when Polling Address Length property value is 2, the value range for the Polling Address is or Default: 1 The maximum value depends on the corresponding Station Address Length property value as follows: when Station Address Length property value is 1, the value range for the Information Address is and when Station Address Length property value is 2, the value range for the Station Address is Default: 10 Controls whether the station communication is initially in use or not. The link address of the IEC slave station The station address of the IEC slave station (the common address of ASDU in an IEC message) Defines how many data items can be written without a reply or request from the master. 27

28 IEC RS Name Single Char Response Command Handling Command Address Confirmation essages Placed To Class 2 Queue Disable Select-execute Validity Check Execute time-out Lengths Cause of Transmission Length Information Address Length Polling Address Length Value/Value range Disabled Enabled Default: Disabled Default: True False Default: True True False Default: True Default: Default: Default: 2 1, 2 Default: 1 Enables or disables single char responses. The object address of the bitstream process object in the PC Client, where an unrecognized message is handled. Place confirmation messages to class 2 queue instead of class 1 queue. Disable select-execute validity check. The maximum time an execute command is waited after a select command. The length of the cause of transmission field in an IEC message The length of the information object address in octets. Information address maximum value will be as follows: when length = 1, when length = 2 and when length =3. The length of the polling address in octets. Polling address maximum value will be as follows: when length = 1 and when length = 2. 28

29 1RS IEC Name Station Address Length Time Handling Clock Sync Not Required For Valid Timestamp Disable Hour Change Clock essage Summer Time Time Synchronization Queues easurement Queue Threshold easurement Update Queue State Indications Updates Queue Transparent SPA Value/Value range Default: 2 True False Default: True True False Default: True Summer time is not used Summer time is used Default: Summer time is not used Receive clock sync Ignore clock sync Default: Receive clock sync Default: Default: Default: 1000 The length of the station address in octets. Station address maximum value will be as follows: when length = 1 and when length = 2. Received clock synchronization not required for valid timestamp. Disable sending of hour change clock synchronization message. States whether summer time is used or not. Determines the behaviour of the slave device, when it receives a time synchronization message. Defines a threshold (percent of the queue capacity) which causes that update of a measurement removes the oldest entry of the same measurement from the queue. aximum number of measurement process data changes that are stored internally in a queue in the client. aximum number of state indication process data changes that are stored internally in a queue in the client. 29

30 IEC RS Name Value/Value range Transparent SPA apping 01 Transparent SPA apping 02 Transparent SPA apping 03 Transparent SPA apping 30 [IEC Address], [PC Path], [PC Server object name] e.g , Line1.RACK.SPA6, SPA PC Server Defines IEC address for receiving Transparent SPA messages and PC path to the IED where the message is forwarded. Transparent SPA apping 04 Transparent SPA apping 05 Transparent SPA apping 06 Transparent SPA apping 07 Transparent SPA apping 08 Transparent SPA apping 09 Transparent SPA apping 10 Transparent SPA apping 11 Transparent SPA apping 12 Transparent SPA apping 13 Transparent SPA apping 14 Transparent SPA apping 15 Transparent SPA apping 16 Transparent SPA apping 17 Transparent SPA apping 18 Transparent SPA apping 19 Transparent SPA apping 20 Transparent SPA apping 21 Transparent SPA apping 22 Transparent SPA apping 23 Transparent SPA apping 24 Transparent SPA apping 25 Transparent SPA apping 26 Transparent SPA apping 27 Transparent SPA apping 28 Transparent SPA apping 29 30

31 1RS IEC Configuring Data objects General about configuring data objects You can configure data objects either in the bject Properties window or in the Cross References window. The actual configuration in bject Properties window by using the C600 Communication Engineering Tool (CET) is performed as described in 3.4.1, General about configuring objects. The parameters are stored in bject properties in the C600 Communication Engineering Tool (CET) (see the tables for each data object type). Clicking Apply connects the data objects to the IEC101 Device. After clicking Apply the connected data objects will appear as child objects for the IEC101 Device. The cross reference information can then be also modified by selecting the data object and using the object properties window. Note that if you make changes in the object names or structuring of objects of PC Server, which are connected to the IEC101 Device, you must re-open the cross reference tool and verify that the changes are correctly handled and then click Apply to update the IEC101 configuration accordingly. IEC101 Slave PC Client supports data objects for status, measurements, controllable status and controllable analog information. The following subsections list the configurable data object properties for the IEC101 Slave PC Client Single point status (SPS) Information in the table below applies also to the Internal SPS data object. Table Configurable SPS properties for PC client Property/ Parameter Basic Common Data Class Addresses Indication Address Common SPS Default: 0 Common data class according to IEC IEC address for indication 31

32 IEC RS Property/ Parameter Class Interrogation Group ver Write Priority Update Rate Data Class Specific Send as Double Point Send as Inverse Value Time Tag Handling 1 = Class 1 2 = Class 2 Default: 1 = Class (general) or (counter) True (A new information object overwrites an older object in the queue) False (No overwriting) Default: False End of queue = 0 iddle of queue = 1, 2 Beginning of queue = True = 1 False= 0 Default: False True = 1 False = 0 Default: False Do not Send Time Tag = 0 Send Short Format Time Tag = 1 Send Long Format Time Tag = 2 Default: Send Long Format Time Tag Class of ASDU. Data sent from the slave to the master can be assigned to two classes: class 1 and class 2. Data in class 1 is sent with higher priority than data in class 2. Interrogation group general or 1-4 counter interrogation (1...16). Defines whether a new indication value overwrites an older one in the queue. Priority of ASDU. This property defines how the ASDU sent is paced in the class 1 and class 2 queues. aximum update rate of indication changes between PC server and client in milliseconds. 0 means that server sends all the changes to the client. Specifies if a value of indication signal is sent as double point value. Specifies if a value of indication signal is sent as inverse value. Specifies the format of timestamp if one is used: none, short or long. Long time tag format cannot be used with a scaled value. 32

33 1RS IEC Double point status (DPS) Table Configurable DPS properties for PC client Property/ Parameter Basic Common Data Class Addresses Indication Address Common Class Interrogation Group ver Write Priority Update Rate Data Class Specific Send as Inverse Value Send as Single Point DPS Default: 0 1 = Class 1 2 = Class 2 Default: 1 = Class (general) or (counters) 1 = True 0 = False Default: 0 = False End of queue = 0 iddle = 1, 2 Beginning of queue = Default: 0 True = 1 False = 0 Default: False True = 1 False = 0 Default: False Common data class according to IEC IEC address for indication. Class of ASDU. Data sent from the slave to the master can be assigned to two classes: class 1 and class 2. Data in class 1 is sent with higher priority than data in class 2. Interrogation group general or 1-4 counter interrogation. Defines whether a new indication value overwrites an older one in the queue. Priority of ASDU. This property defines how the ASDU sent is placed in the class 1 and class 2 queues. aximum update rate of indication changes between PC server and client in milliseconds. 0 means that server sends all the changes to the client. Specifies if a value of indication signal is sent as inverse value. Specifies if a value of indication signal is sent as single point value. 33

34 IEC RS Property/ Parameter Time Tag Handling Do not Send Time Tag = 0 Send Short Format Time Tag = 1 Send Long Format Time Tag = 2 Default: Send Long Format Time Tag Specifies the format of timestamp if one is used: none, short or long. Long time tag format cannot be used with a scaled value Integer status (INS) Information in the table below applies also to the Internal INS data object. Table Configurable INS properties for PC client Property/ Parameter Basic Common Data Class Addresses Indication Address Common Class Interrogation Group ver Write Priority INS Default: 0 Class 1 = 1 Class 2 = 2 Default: Class 1 = (general) or (counters) True = 1 False = 0 Default: False = End of queue = 0 iddle = 1, 2 Beginning of queue = 3 Common data class according to IEC IEC address for indication. Class of ASDU. Data sent from the slave to the master can be assigned to two classes: class 1 and class 2. Data in class 1 is sent with higher priority than data in class 2. Interrogation group general or 1-4 counter interrogation. Defines whether a new indication value overwrites an older one in the queue. Priority of ASDU. This property defines how the ASDU sent is placed in the class 1 and class 2 queues. 34

35 1RS IEC Property/ Parameter Update Rate Data Class Specific Send as Indication as Value Type Time Tag Handling Default: 0 Send with normalized value = 0 Send with scaled value = 1 Do not Send Time Tag = 0 Send Short Format Time Tag = 1 Send Long Format Time Tag = 2 Default: Send Long Format Time Tag aximum update rate of indication changes between PC server and client in milliseconds. 0 means that server sends all the changes to the client. Specifies whether the value of indication signal is sent as normalized or scaled value. Long timestamp format cannot be used with scaled value. Specifies the format of timestamp if one is used: none, short or long. Long time tag format cannot be used with a scaled value Protection activation information (ACT) Table Configurable ACT properties for PC client Property/ Parameter Basic Common Data Class Addresses General Address Neutral Address Phase A Address Phase B Address Phase C Address Common ACT = Not in use = Not in use = Not in use Common data class according to IEC IEC address for general indication. IEC address for neutral indication IEC address for phase A. IEC address for phase B. IEC address for phase C. 35

36 IEC RS Property/ Parameter Class Interrogation Group ver Write Priority Update Rate Data Class Specific Send as Double Point Send as Inverse Value Time Tag Handling 1 = Class 1 2 = Class 2 Default: 1 = Class (general) or (counters) True = 1 False =0 Default: False = End of queue = 0 iddle = 1, 2 Beginning of queue = Default: 0 True = 1 False = 0 True = 1 False = 0 Do not Send Time Tag = 0 Send Short Format Time Tag = 1 Send Long Format Time Tag = 2 Class of ASDU. Data sent from the slave to the master can be assigned to two classes: class 1 and class 2. Data in class 1 is sent with higher priority than data in class 2. Interrogation group general or 1-4 counter interrogation. Defines whether a new indication value overwrites an older one in the queue. Priority of ASDU. This property defines how the ASDU sent is placed in the class 1 and class 2 queues. aximum update rate of indication changes between PC server and client in milliseconds. 0 means that server sends all the changes to the client. Specifies if the value of indication signal is sent as double point. Specifies the value of indication signal is sent as inverse value. Specifies the format of timestamp if one is used: none, short or long. Long time tag format cannot be used with a scaled value Directional protection activation information (ACD) Table Configurable ACD properties for PC client Property/ Parameter Basic 36

37 1RS IEC Property/ Parameter Common Data Class Addresses General Address Neutral Address Phase A Address Phase B Address Phase C Address Common Class Interrogation Group ver Write Priority Update Rate Data Class Specific Send as Double Point Send as Inverse Point ACD = Not in use = Not in use = Not in use 1 = Class 1 2 = Class 2 Default: 1 = Class (general) or (counters) True = 1 False = 0 Default: False = End of queue = 0 iddle = 1, 2 Beginning of queue = Default: 0 True = 1 False = 0 True = 1 False = 0 Common data class according to IEC IEC address for general indication IEC address for neutral IEC address for phase A IEC address for phase B IEC address for phase C Class of ASDU. Data sent from the slave to the master can be assigned to two classes: class 1 and class 2. Data in class 1 is sent with higher priority than data in class 2. Interrogation group general or 1-4 counter interrogation. Defines whether a new indication value overwrites an older one in the queue. Priority of ASDU. This property defines how the ASDU sent is placed in the class 1 and class 2 queues. aximum update rate of indication changes between PC server and client in milliseconds. 0 means that server sends all the changes to the client. Specifies if a value of indication signal is sent as double point. Specifies if a value of indication signal is sent as inverse value. 37

38 IEC RS Property/ Parameter Time Tag Handling Do not Send Time Tag = 0 Send Short Format Time Tag = 1 Send Long Format Time Tag = 2 Specifies the format of timestamp if one is used: none, short or long. Long time tag format cannot be used with a scaled value Binary counter reading (BCR) Table Configurable BCR properties for PC client Property/ Parameter Basic Common Data Class Addresses Indication Address Common Class Interrogation Group ver Write Priority Update Rate BCR Default:0 Class 1 = 1 Class 2 = 2 Default: Class 1 = (general) or (counters) True = 1 False = 0 Default: False = End of queue = 0 iddle = 1, 2 Beginning of queue = Default: 0 Common data class according to IEC IEC Address for indication. Class of ASDU. Data sent from the slave to the master can be assigned to two classes: class 1 and class 2. Data in class 1 is sent with higher priority than data in class 2. Interrogation group general or 1-4 counter interrogation. Defines whether a new indication value overwrites an older one in the queue. Priority of ASDU. This property defines how the ASDU sent is placed in the class 1 and class 2 queues. aximum update rate of indication changes between PC server and client in milliseconds. 0 means that server sends all the changes to the client. 38

39 1RS IEC Property/ Parameter Data Class Specific Time Tag Handling Do not Send Time Tag = 0 Send Short Format Time Tag = 1 Send Long Format Time Tag = 2 Default: Send Long Format Time Tag Specifies the format of timestamp if one is used: none, short or long. Long time tag format cannot be used with a scaled value easured value (V) Table Configurable V properties for PC client Property/ Parameter Basic Common Data Class Addresses Indication Address Common Class Interrogation Group ver Write Priority V Default:0 Class 1 = 1 Class 2 = 2 Default: Class 2 = (general) or (counters) True = 1 False = 0 Default: True = End of queue = 0 iddle = 1, 2 Beginning of queue = 3 Common data class according to IEC IEC Address for indication. Class of ASDU. Data sent from the slave to the master can be assigned to two classes: class 1 and class 2. Data in class 1 is sent with higher priority than data in class 2. Interrogation group general or 1-4 counter interrogation. Defines whether a new indication value overwrites an older one in the queue. Priority of ASDU. This property defines how the ASDU sent is placed in the class 1 and class 2 queues. 39

40 IEC RS Property/ Parameter Update Rate Data Class Specific Send As easurand As Value Type Time Tag Handling Default: 0 Send with normalized value = 0 Send with scaled value = 1 Send with float value = 2 Do not Send Time Tag = 0 Send Short Format Time Tag = 1 Send Long Format Time Tag = 2 Default: Send Long Format Time Tag aximum update rate of indication changes between PC server and client in milliseconds. 0 means that server sends all the changes to the client. Specifies the type of the indication signal value. Long timestamp format cannot be used with a scaled value. Specifies the format of timestamp if one is used: none, short or long. Long time tag format cannot be used with a scaled value Complex measured value (CV) Table Configurable CV properties for PC client Property/ Parameter Basic Common Data Class Addresses Indication Address Common Class Interrogation Group CV Default:0 Class 1 = 1 Class 2 = 2 Default: Class 2 = (general) or (counters) Common data class according to IEC IEC Address for indication. Class of ASDU. Data sent from the slave to the master can be assigned to two classes: class 1 and class 2. Data in class 1 is sent with higher priority than data in class 2. Interrogation group general or 1-4 counter interrogation. 40

41 1RS IEC Property/ Parameter ver Write Priority Update Rate Data Class Specific Send As easurand As Value Type Time Tag Handling True = 1 False = 0 Default: True = End of queue = 0 iddle = 1, 2 Beginning of queue = Default: 0 Send with normalized value = 0 Send with scaled value = 1 Send with float value = 2 Do not Send Time Tag = 0 Send Short Format Time Tag = 1 Send Long Format Time Tag = 2 Default: Send Long Format Time Tag Defines whether a new indication value overwrites an older one in the queue. Priority of ASDU. This property defines how the ASDU sent is placed in the class 1 and class 2 queues. aximum update rate of indication changes between PC server and client in milliseconds. 0 means that server sends all the changes to the client. Specifies the type of the indication signal value. Long timestamp format cannot be used with a scaled value. Specifies the format of timestamp if one is used: none, short or long. Long time tag format cannot be used with a scaled value WYE Table Configurable WYE properties for PC client Property/ Parameter Basic Common Data Class Addresses Neutral Address WYE = Not in use Common data class according to IEC IEC address for neutral. 41

42 IEC RS Property/ Parameter Phase A Address Phase B Address Phase C Address Common Class Interrogation Group ver Write Priority Update Rate Data Class Specific Send As easurand As Value Type = Not in use = Not in use = Not in use Class 1 = 1 Class 2 = 2 Default: Class 2 = (general) or (counters) True = 1 False = 0 Default: True = End of queue = 0 iddle = 1, 2 Beginning of queue = Default: 1000 Send with normalized value = 0 Send with scaled value = 1 Send with float value = 2 IEC address for phase A. IEC address for phase B. IEC address for phase C. Class of ASDU. Data sent from the slave to the master can be assigned to two classes: class 1 and class 2. Data in class 1 is sent with higher priority than data in class 2. Interrogation group general or 1-4 counter interrogation. Defines whether a new indication value overwrites an older one in the queue. Priority of ASDU. This property defines how the ASDU sent is placed in the class 1 and class 2 queues. aximum update rate of indication changes between PC server and client in milliseconds. 0 means that server sends all the changes to the client. Specifies the type of the indication signal value. Long timestamp format cannot be used with a scaled value. 42

43 1RS IEC Property/ Parameter Time Tag Handling Do not Send Time Tag = 0 Send Short Format Time Tag = 1 Send Long Format Time Tag = 2 Default: Send Long Format Time Tag Specifies the format of timestamp if one is used: none, short or long. Long time tag format cannot be used with a scaled value Delta (DEL) Table Configurable DEL properties for PC client Property/ Parameter Basic Common Data Class Phase AB Address Phase BC Address Phase CA Address Common Class Interrogation Group ver Write DEL = Not in use = Not in use = Not in use Class 1 = 1 Class 2 = 2 Default: Class 2 = (general) or (counters) True = 1 False = 0 Default: True = 1 Common data class according to IEC IEC address for phase AB. IEC address for phase BC. IEC address for phase CA. Class of ASDU. Data sent from the slave to the master can be assigned to two classes: class 1 and class 2. Data in class 1 is sent with higher priority than data in class 2. Interrogation group general or 1-4 counter interrogation. Defines whether a new indication value overwrites an older one in the queue. 43

44 IEC RS Property/ Parameter Priority Update Rate Data Class Specific Send As easurand As Value Type Time Tag Handling End of queue = 0 iddle = 1, 2 Beginning of queue = Default: 1000 Send with normalized value = 0 Send with scaled value = 1 Send with float value = 2 Do not Send Time Tag = 0 Send Short Format Time Tag = 1 Send Long Format Time Tag = 2 Default: Send Long Format Time Tag Priority of ASDU. This property defines how the ASDU sent is placed in the class 1 and class 2 queues. aximum update rate of indication changes between PC server and client in milliseconds. 0 means that server sends all the changes to the client. Specifies the type of the indication signal value. Long timestamp format cannot be used with a scaled value. Specifies the format of timestamp if one is used: none, short or long. Long time tag format cannot be used with a scaled value Controllable single point (SPC) Information in the table below applies also to the Internal SPC data object. Table Configurable SPC properties for PC client Property/ Parameter Basic Common Data Class Addresses Command Address Indication Address SPC Default: Default: 0 Common data class according to IEC IEC address for command. IEC address for indication. 44

45 1RS IEC Property/ Parameter Common Class Interrogation Group ver Write Priority Update Rate Data Class Specific Receive As Inverse Value Send as Double Point Value Send As Inverse Value Time Tag Handling Class 1 = 1 Class 2 = 2 Default: Class 1 = (general) or (counters) True = 1 False = 0 Default: False = End of queue = 0 iddle = 1, 2 Beginning of queue = Default: 0 True = 1 False = 0 True = 1 False = 0 True False Do not Send Time Tag = 0 Send Short Format Time Tag = 1 Send Long Format Time Tag = 2 Default: Send Long Format Time Tag Class of ASDU. Data sent from the slave to the master can be assigned to two classes: class 1 and class 2. Data in class 1 is sent with higher priority than data in class 2. Interrogation group general or 1-4 counter interrogation. Defines whether a new indication value overwrites an older one in the queue. Priority of ASDU. This property defines how the ASDU sent is placed in the class 1 and class 2 queues. aximum update rate of indication changes between PC server and client in milliseconds. 0 means that server sends all the changes to the client. Specifies if a value of indication signal is sent as inverse value. Specifies if a value of indication signal is sent as double point. Specifies the format of timestamp if one is used: none, short or long. Long time tag format cannot be used with a scaled value. 45

46 IEC RS Controllable double point (DPC) Table Configurable DPC properties for PC client Property/ Parameter Basic Common Data Class Addresses Command Address Indication Address Common Class Interrogation Group ver Write Priority Update Rate Data Class Specific Direct perate Receive As Inverse Value Send as Inverse Value DPC Class 1 = 1 Class 2 = 2 Default: Class 1 = (general) or (counters) True = 1 False = 0 Default: False = End of queue = 0 iddle = 1, 2 Beginning of queue = Default: 0 True = 1 False = 0 True = 1 False = 0 True = 1 False = 0 Common data class according to IEC IEC address for command. IEC address for indication. Class of ASDU. Data sent from the slave to the master can be assigned to two classes: class 1 and class 2. Data in class 1 is sent with higher priority than data in class 2. Interrogation group general or 1-4 counter interrogation. Defines whether a new indication value overwrites an older one in the queue. Priority of ASDU. This property defines how the ASDU sent is placed in the class 1 and class 2 queues. aximum update rate of indication changes between PC server and client in milliseconds. 0 means that server sends all the changes to the client. If the value of this attribute is True, then no select is required. Specifies if the received open / close commands are handled inversely. Specifies if a value of indication signal is sent as inverse value. 46

47 1RS IEC Property/ Parameter Send as Single Point Time Tag Handling True = 1 False = 0 Do not Send Time Tag = 0 Send Short Format Time Tag = 1 Send Long Format Time Tag = 2 Default: Send Long Format Time Tag Specifies if a value of indication signal is sent as single point value. Specifies the format of timestamp if one is used: none, short or long. Long time tag format cannot be used with a scaled value Controllable integer status (INC) Table Configurable INC properties for PC client Property/ Parameter Basic Common Data Class Addresses Command Address Indication Address Common Class Interrogation Group ver Write INC Default: Default: 0 Class 1 = 1 Class 2 = 2 Default: Class 1 = (general) or (counters) True = 1 False = 0 Default: False = 0 Common data class according to IEC IEC address for command. IEC address for indication. Class of ASDU. Data sent from the slave to the master can be assigned to two classes: class 1 and class 2. Data in class 1 is sent with higher priority than data in class 2. Interrogation group general or 1-4 counter interrogation. Defines whether a new indication value overwrites an older one in the queue. 47

48 IEC RS Property/ Parameter Priority Update Rate Data Class Specific Send Indication As Value Type Time Tag Handling End of queue = 0 iddle = 1, 2 Beginning of queue = Default: 0 Send with normalized value = 0 Send with scaled value = 1 Do not Send Time Tag = 0 Send Short Format Time Tag = 1 Send Long Format Time Tag = 2 Default: Send Long Format Time Tag Priority of ASDU. This property defines how the ASDU sent is placed in the class 1 and class 2 queues. aximum update rate of indication changes between PC server and client in milliseconds. 0 means that server sends all the changes to the client. Send value of indication signal as normalized or scaled. Long timestamp format cannot be used with a scaled value. Specifies the format of timestamp if one is used: none, short or long. Long time tag format cannot be used with a scaled value Binary controlled step position information (BSC) Table Configurable BSC properties for PC client Property/ Parameter Basic Common Data Class Addresses Command Address Position Address Common Class BSC Class 1 = 1 Class 2 = 2 Default: Class 1 = 1 Common data class according to IEC IEC address for command. IEC address for position. Class of ASDU. Data sent from the slave to the master can be assigned to two classes: class 1 and class 2. Data in class 1 is sent with higher priority than data in class 2. 48

49 1RS IEC Property/ Parameter Interrogation Group ver Write Priority Update Rate Data Class Specific Send Indication As Value Type Time Tag Handling (general) or (counters) True = 1 False = 0 Default: False = End of queue = 0 iddle = 1, 2 Beginning of queue = Default: 0 Send with normalized value = 0 Send with scaled value = 1 Do not Send Time Tag = 0 Send Short Format Time Tag = 1 Send Long Format Time Tag = 2 Default: Send Long Format Time Tag Interrogation group general or 1-4 counter interrogation. Defines whether a new indication value overwrites an older one in the queue. Priority of ASDU. This property defines how the ASDU sent is placed in the class 1 and class 2 queues. aximum update rate of indication changes between PC server and client in milliseconds. 0 means that server sends all the changes to the client. Specifies if the value of indication signal is sent as normalized or scaled. Long timestamp format cannot be used with a scaled value. Specifies the format of timestamp if one is used: none, short or long. Long time tag format cannot be used with a scaled value Integer controlled step position information (ISC) Table Configurable ISC properties for PC client Property/ Parameter Basic Common Data Class Addresses Command Address ISC Common data class according to IEC IEC address for command. 49

50 IEC RS Property/ Parameter Position Address Common Class Interrogation Group ver Write Priority Update Rate Data Class Specific Send Indication As Value Type Time Tag Handling Class 1 = 1 Class 2 = 2 Default: Class 1 = (general) or (counters) True = 1 False = 0 Default: False = End of queue = 0 iddle = 1, 2 Beginning of queue = Default: 0 Send with normalized value = 0 Send with scaled value = 1 Do not Send Time Tag = 0 Send Short Format Time Tag = 1 Send Long Format Time Tag = 2 Default: Send Long Format Time Tag IEC address for position. Class of ASDU. Data sent from the slave to the master can be assigned to two classes: class 1 and class 2. Data in class 1 is sent with higher priority than data in class 2. Interrogation group general or 1-4 counter interrogation. Defines whether a new indication value overwrites an older one in the queue. Priority of ASDU. This property defines how the ASDU sent is placed in the class 1 and class 2 queues. aximum update rate of indication changes between PC server and client in milliseconds. 0 means that server sends all the changes to the client. Specifies if the value of indication signal is sent as normalized or scaled. Long timestamp format cannot be used with a scaled value. Specifies the format of timestamp if one is used: none, short or long. Long time tag format cannot be used with a scaled value. 50

51 1RS IEC Analogue set point (APC) Table Configurable APC properties for PC client Property/ Parameter Basic Common Data Class Addresses Command Address APC Common data class according to IEC IEC address for command. 51

52 IEC RS peration 4.1. About this section This section describes the basic operation procedures you can carry out after the object properties for the IEC101 Slave PC Client have been configured. After this, you can, for example, monitor and control the condition of connections in network. This is done by using the nline diagnostics function in Communication Engineering Tool (CET) Activating Gateway with new configurations For information on activating Gateway with new configurations, refer to C600 User s Guide IEC101 Slave PC Client diagnostics To view version information on IEC101 Slave PC Client or to monitor and control the state of the client, right-click the IEC101 Slave PC Client object and select nline diagnostics, see Figure Figure IEC101 Slave PC Client nline diagnostics In nline diagnostics box you can: reset IEC101 Slave PC Client view the event log file, see Figure clear the event log file IEC101_Slave_PC_Client_nline_diagnostics.jpg 52

53 1RS IEC Figure Event log file Event_Log101.jpg 4.4. IEC101 Channel diagnostics The IEC101 Channel activity can be monitored with the nline diagnostics function. You can also take a channel into use or out of use as described in this section. To monitor and control IEC101 Channel activity: 1. Select the channel you want to monitor in the object tree of Communication Engineering Tool (CET). 2. Right-click the channel. 3. Select nline diagnostics. 53

54 IEC RS Figure IEC101 Channel nline Diagnostics IEC101_Channel _nline_diagnostics.jpg In the Diagnostic counters field, you can monitor the channel activity. The available attributes can be seen in Figure To reset Diagnostic counters, click Reset counters. You can take an IEC101 Channel into use by marking the In use check box. If you unmark the check box, the channel is taken out of use. To manually update diagnostic counters, click Refresh IEC101 Device diagnostics The IEC101 Device communication can be monitored with the nline diagnostics function. You can also take a device into use or out of use as described in this section. To monitor and control IEC101 Device communication: 1. Select the device you want to monitor in the object tree of the Communication Engineering Tool (CET). 2. Right-click the device. 3. Select nline diagnostics. In the Status information field, you can monitor the device status. 54

55 1RS IEC The Diagnostic counters field provides information on device activity. To reset diagnostic counters, click Reset counters. You can take an IEC101 Device into use by marking the In use check box. If you unmark the check box, the device is taken out of use. To manually update diagnostic counters, click Refresh Signal diagnostics The IEC101 Slave PC client has a diagnostic function which makes it possible to monitor the flow of process data changes and commands. The diagnostic function is activated by marking the Diagnostic Events Enabled check box, located in the nline diagnostics function of the IEC101 Device. When the diagnostic function is activated, the IEC101 PC Client Alarm & Event server generates events with information about data changes and commands. To view the event list: 1. Select the IEC101 Slave PC Client object in the object tree of the Communication Engineering Tool (CET). 2. Right-click the IEC101 Slave PC Client. 3. Select Diagnostic AE client (see Figure 4.6-1) Figure IEC101 Slave PC Client Diagnostic AE client IEC101_Diagnostic_AE_Client.jpg Detailed information about field values (ASDU types, qualifier values etc.) can be found in the IEC standard documentation. 55

COM600 Station Automation Series IEC Slave (OPC) 3.1. User's Guide

COM600 Station Automation Series IEC Slave (OPC) 3.1. User's Guide Issued: 30.6.2004 Version: D/21.12.2007 Contents: 1. About this manual... 7 1.1. Copyrights... 7 1.2. Trademarks... 7 1.3. General... 7 1.4. Document conventions... 8 1.5. Terminology... 9 1.6. Abbreviations...

More information

Grid Automation Controller COM IEC Slave (OPC) User's Manual

Grid Automation Controller COM IEC Slave (OPC) User's Manual Grid Automation Controller C600 4.0 1RS755384 Issued: 30.6.2004 Version: L/31.5.2012 Grid Automation Controller C600 4.0 Contents: 1. About this manual... 7 1.1. Copyrights... 7 1.2. Trademarks... 7 1.3.

More information

Station Automation COM600 IEC Master (OPC) 3.3. User's Manual

Station Automation COM600 IEC Master (OPC) 3.3. User's Manual Station Automation C600 IEC 60870-5-101 1RS756703 Issued: 13.2.2009 Version: A/13.2.2009 Station Automation C600 IEC 60870-5-101 Contents: 1. About this manual... 7 1.1. Copyrights... 7 1.2. Trademarks...

More information

Station Automation COM IEC Master (OPC) User's Manual

Station Automation COM IEC Master (OPC) User's Manual Station Automation C600 3.5 IEC 60870-5-101 aster (PC) User's anual 1RS756703 Issued: 13.2.2009 Version: C/30.06.2011 Station Automation C600 3.5 Contents: 1. About this manual... 7 1.1. Copyrights...

More information

Station Automation COM600 IEC Master (OPC) 3.3. User's Manual

Station Automation COM600 IEC Master (OPC) 3.3. User's Manual Station Automation C600 IEC 60870-5-103 1RS752278 Issued: 30.6.2004 Version: E/13.2.2009 Station Automation C600 IEC 60870-5-103 Contents: 1. About this manual... 7 1.1. Copyrights... 7 1.2. Trademarks...

More information

COM600 series, Version 5.0 Modbus Serial Slave (OPC) User's Manual

COM600 series, Version 5.0 Modbus Serial Slave (OPC) User's Manual CO600 series, Version 5.0 odbus Serial Slave (OPC) User's anual 1RS756913 Issued: 9.10.2009 Version: E/24.5.2017 CO600 series, Version 5.0 odbus Serial Slave (OPC) User's anual Contents: 1. About this

More information

Station Automation COM IEC Master (OPC) User's Manual

Station Automation COM IEC Master (OPC) User's Manual Station Automation C600 3.5 IEC 60870-5-104 aster (PC) User's anual 1RS756704 Issued: 13.2.2009 Version: C/30.06.2011 Station Automation C600 3.5 Contents: 1. About this manual... 7 1.1. Copyrights...

More information

COM600 Station Automation Series External OPC Client Access 3.1. User's Guide

COM600 Station Automation Series External OPC Client Access 3.1. User's Guide COM600 Station Automation Series External OPC Client Access 3.1 1MRS755564 Issued: 10.03.2005 Version: C/21.12.2007 COM600 Station Automation Series External OPC Client Access 3.1 Contents: 1. About this

More information

COM600 Station Automation Series MNS is Connectivity (OPC) 3.2. User's Guide

COM600 Station Automation Series MNS is Connectivity (OPC) 3.2. User's Guide MNS is Connectivity 3.2 User's Guide 1MRS756569 Issued: 17.06.2008 Version: A/17.06.2008 User's Guide MNS is Connectivity 3.2 Contents: 1. About this manual... 5 1.1. Copyrights... 5 1.2. Trademarks...

More information

Station Automation COM Logic Processor User's Manual

Station Automation COM Logic Processor User's Manual Station Automation COM600 3.4 1MRS756738 Issued: 13.2.2009 Version: B/06.11.2009 Station Automation COM600 3.4 Contents: 1. About this manual... 5 1.1. Copyrights... 5 1.2. Trademarks... 5 1.3. General...

More information

Station Automation COM600 DNP 3.0 LAN/WAN Master (OPC) 3.3. User's Manual

Station Automation COM600 DNP 3.0 LAN/WAN Master (OPC) 3.3. User's Manual Station Automation C600 DNP 3.0 (PC) 3.3 1RS756566 Issued: 17.06.2008 Version: B/13.2.2009 Station Automation C600 DNP 3.0 (PC) 3.3 Contents: 1. About this manual... 7 1.1. Copyrights... 7 1.2. Trademarks...

More information

Station Automation COM600 Modbus TCP Master (OPC) 3.3. User's Manual

Station Automation COM600 Modbus TCP Master (OPC) 3.3. User's Manual Station Automation C600 odbus TCP aster (PC) 3.3 1RS756445 Issued: 21.12.2007 Version: C/13.2.2009 Station Automation C600 odbus TCP aster (PC) 3.3 Contents: 1. About this manual... 7 1.1. Copyrights...

More information

Connectivity Packages. User's Guide - ANSI Version

Connectivity Packages. User's Guide - ANSI Version Connectivity Packages 1MRS756194 Issued: 30.11.2006 Version: A/30.11.2006 Connectivity Packages Contents Copyrights... 5 1. Introduction...... 7 1.1. Intended audience...... 7 1.2. Related documents.........

More information

System 800xA IEC Connect Configuration

System 800xA IEC Connect Configuration System 800xA IEC 61850 Connect Configuration System Version 6.0 Power and productivity for a better world System 800xA IEC 61850 Connect Configuration System Version 6.0 NOTICE This document contains

More information

System 800xA IEC Connect Configuration

System 800xA IEC Connect Configuration System 800xA IEC 61850 Connect Configuration System Version 5.1 Power and productivity for a better world System 800xA IEC 61850 Connect Configuration System Version 5.1 NOTICE This document contains

More information

MicroSCADA Pro COM 500 *4.1. User s Guide

MicroSCADA Pro COM 500 *4.1. User s Guide MicroSCADA Pro COM 500 *4.1 1MRS751858-MEN Issued: 15.03.2002 Version: C/30.06.2004 MicroSCADA Pro COM 500 *4.1 1. About this manual...7 1.1. Copyrights...7 1.2. Trademarks...7 1.3. General...7 1.4. Use

More information

MicroSCADA Pro SYS IEC Slave Protocol

MicroSCADA Pro SYS IEC Slave Protocol SYS600 9.4 Trace back information: Workspace Main version a54 1MRS758106 Issued: 3.6.2016 Version: C/3.6.2016 Contents SYS600 9.4 1 Copyrights... 2 Introduction... 2.1 This manual... 2.2 Use of symbols...

More information

MicroSCADA Pro SYS

MicroSCADA Pro SYS MicroSCADA Pro SYS 600 9.2 1MRS756170 Issued: 02.03.2007 Version: B/28.03.2008 MicroSCADA Pro SYS 600 9.2 Contents Copyrights...15 1. Introduction...17 1.1. This Manual...17 1.2. Use of symbols...17 1.3.

More information

MicroSCADA Pro SYS IEC Master Protocol

MicroSCADA Pro SYS IEC Master Protocol SYS6 9.4 Trace back information: Workspace Main version a54 1MRS75819 Issued: 3.6.216 Version: C/3.6.216 Contents SYS6 9.4 1 Copyrights... 2 Introduction... 2.1 This manual... 2.2 Use of symbols... 2.3

More information

MicroSCADA Pro SYS IEC Master Protocol

MicroSCADA Pro SYS IEC Master Protocol SYS600 9.4 Trace back information: Workspace Main version a26 Checked in 2014-05-16 1MRS758093 Issued: 16.5.2014 Version: A/16.5.2014 Contents SYS600 9.4 1 Copyrights... 2 Introduction... 2.1 This manual...

More information

Ethernet Adapter. SPA to IEC Gateway. Installation and Commissioning Manual

Ethernet Adapter. SPA to IEC Gateway. Installation and Commissioning Manual SPA-ZC 400 1MRS755347 Issued: 06.10.2004 Version: G/20.05.2009 SPA-ZC 400 Contents Copyrights... 7 1. Introduction...9 1.1. This manual... 9 1.2. Use of symbols... 9 1.3. Intended audience... 9 1.4. Product

More information

Station Automation COM HMI Configuration Manual

Station Automation COM HMI Configuration Manual Station Automation COM600 3.4 1MRS756740 Issued: 13.2.2009 Version: B/06.11.2009 Station Automation COM600 3.4 Contents: 1. About this manual... 5 1.1. Copyrights... 5 1.2. Trademarks... 5 1.3. General...

More information

SPA/ Ethernet Adapter

SPA/ Ethernet Adapter 1MRS755380 Issued: 23.11.2004 Version: F/20.05.2009 Contents Copyrights... 7 1. Introduction...9 1.1. This manual... 9 1.2. Use of symbols... 9 1.3. Intended audience... 9 1.4. Product documentation...

More information

MicroSCADA Pro SYS IEC Slave Protocol

MicroSCADA Pro SYS IEC Slave Protocol SYS 600 9.3 Trace back information: Workspace Main version a9 Checked in 2012-11-09 1MRS756653 Issued: 31.3.2010 Version: B/30.9.2012 Contents SYS 600 9.3 1 Copyrights... 2 Introduction... 2.1 This manual...

More information

IEC Master Driver Help Kepware Technologies

IEC Master Driver Help Kepware Technologies IEC 60870-5-101 Master Driver Help 2014 Kepware Technologies IEC 60870-5-101 Master Driver 2 Table of Contents Table of Contents 2 IEC 60870-5-101 Master Driver Help 3 Overview 3 Channel Setup 4 Device

More information

Protection Terminal REF 54_ Protection Relay REX 521

Protection Terminal REF 54_ Protection Relay REX 521 Protection Terminal Protection Relay 1MRS755260 Issued: 02.04.2004 Version: C/22.06.2004 Protection Terminal Protection Relay Contents 1. About this manual...4 1.1. Copyrights...4 1.2. Trademarks...4

More information

MicroSCADA Pro SYS Connecting LONWORKS Devices

MicroSCADA Pro SYS Connecting LONWORKS Devices MicroSCADA Pro SYS 600 9.3 1MRS756638 Issued: 31.3.2010 Version: A/31.3.2010 MicroSCADA Pro SYS 600 9.3 Contents Copyrights...7 1. Introduction...9 1.1. This manual...9 1.2. Document conventions...9 1.3.

More information

Industrial IT. Fieldbus Basic PROFIBUS DTM / PROFIBUS DTM Builder Version 4.1. Configuration

Industrial IT. Fieldbus Basic PROFIBUS DTM / PROFIBUS DTM Builder Version 4.1. Configuration Industrial IT Fieldbus Basic PROFIBUS DTM / PROFIBUS DTM Builder Version 4.1 Configuration Industrial IT Fieldbus Basic PROFIBUS DTM / PROFIBUS DTM Builder Version 4.1 Configuration NOTICE The information

More information

IEC Master Driver PTC Inc. All Rights Reserved.

IEC Master Driver PTC Inc. All Rights Reserved. 2018 PTC Inc. All Rights Reserved. 2 Table of Contents 1 Table of Contents 2 4 Overview 4 Setup 5 Channel Properties General 5 Channel Properties Serial Communications 6 Channel Properties Write Optimizations

More information

Protection System Simulator SIM600. Installation Manual

Protection System Simulator SIM600. Installation Manual Protection System Simulator SIM600 1MRS756102 Issued: 08.12.2008 Version: B Protection System Simulator SIM600 Contents: 1. About this manual... 5 1.1. Copyrights... 5 1.2. Trademarks... 5 1.3. Guarantee...

More information

IEC Master Driver Help Kepware Technologies

IEC Master Driver Help Kepware Technologies IEC 60870-5-104 Master Driver Help 2014 Kepware Technologies IEC 60870-5-104 Master Help 2 Table of Contents Table of Contents 2 IEC 60870-5-104 Master Driver Help 3 Overview 3 Channel Setup 4 60870 Settings

More information

MicroSCADA Pro. IEC System Design. Configuration Manual

MicroSCADA Pro. IEC System Design. Configuration Manual SYS 600 9.2 1MRS756119 Issued: 23.03.2007 Version: A/23.03.2007 SYS 600 9.2 Contents Copyrights... 5 1. Introduction...7 1.1. This manual... 7 1.2. Use of symbols... 7 1.3. Intended audience... 7 1.4.

More information

MicroSCADA Pro SYS

MicroSCADA Pro SYS MicroSCADA Pro SYS 600 9.2 1MRS756158 Issued: 15.11.2006 Version: A/15.11.2006 MicroSCADA Pro SYS 600 9.2 Contents Copyrights...5 1. Introduction...7 1.1. This manual...7 1.2. Use of symbols...8 1.3.

More information

MicroSCADA Pro SYS Operation Manual

MicroSCADA Pro SYS Operation Manual SYS 600 9.3 Trace back information: Workspace Main version a9 Checked in 2012-11-09 1MRS756635 Issued: 31.3.2010 Version: C/30.09.2012 SYS 600 9.3 Contents 1 Copyrights... 2 Introduction... 2.1 This manual...

More information

Protocol Gateway IEC Master/Slave IEC Client/Server

Protocol Gateway IEC Master/Slave IEC Client/Server Atop Technologies, Inc. Protocol Gateway IEC60870-5-101 Master/Slave IEC60870-5-104 Client/Server Protocol and enode Designer configuration enode Configuration Manual V1.2 September 29 th, 2017 CLIENT/SERVER

More information

MicroSCADA Pro SYS Operation Manual

MicroSCADA Pro SYS Operation Manual MicroSCADA Pro SYS 600 9.2 1MRS756118 Issued: 28.02.2007 Version: B/28.03.2008 MicroSCADA Pro SYS 600 9.2 Contents Copyrights...7 1. Introduction...9 1.1. This manual...9 1.2. Use of symbols...9 1.3.

More information

COM600 series 5.0 Operator's Manual

COM600 series 5.0 Operator's Manual COM600 series 5.0 1MRS756705 Issued: 13.2.2009 Version: F/24.5.2017 COM600 series 5.0 Contents: 1. About this manual... 5 1.1. Copyright... 5 1.2. Disclaimer... 5 1.3. Conformity... 6 1.4. Trademarks...

More information

MicroSCADA Pro SYS IEC System Design

MicroSCADA Pro SYS IEC System Design SYS600 9.4 Trace back information: Workspace Main version a54 1MRS758117 Issued: 3.6.2016 Version: C/3.6.2016 SYS600 9.4 Contents 1 Copyrights... 2 Introduction... 2.1 This manual... 2.2 Use of symbols...

More information

MODBUS Protocol for MiCOM P30 Series

MODBUS Protocol for MiCOM P30 Series MODBUS Protocol for MiCOM P30 Series Substation Protocols Technical Documentation This document does not replace the Technical Manual Version: MiCOM P30, MODBUS Index: B Release: 08 / 2011 MODBUS Protocol

More information

Engineering Manual Security Lock

Engineering Manual Security Lock DigiVis 500 Engineering Manual Security Lock Version 1.0 SP1 DigiVis 500 Engineering Manual Security Lock Version 1.0 SP1 NOTICE The information in this document is subject to change without notice and

More information

MicroSCADA Pro SYS

MicroSCADA Pro SYS MicroSCADA Pro SYS 600 9.2 1MRS756117 Issued: 02.03.2007 Version: B/28.03.2008 MicroSCADA Pro SYS 600 9.2 Contents Copyrights...7 1. Introduction...9 1.1. This manual...9 1.2. Use of symbols...10 1.3.

More information

Ethernet Adapter. Modbus/TCP Brigde. Installation and Commissioning Manual

Ethernet Adapter. Modbus/TCP Brigde. Installation and Commissioning Manual SPA-ZC 400 1MRS756014 Issued: 30.06.2006 Version: B/20.05.2009 SPA-ZC 400 Contents Copyrights... 5 1. Introduction...7 1.1. This manual... 7 1.2. Use of symbols... 7 1.3. Intended audience... 7 1.4. Product

More information

MVI46-103M. User Manual. SLC Platform. IEC Master Communication Module

MVI46-103M. User Manual. SLC Platform. IEC Master Communication Module MVI46-103M SLC Platform IEC 60870-5-103 Master Communication Module User Manual Please Read This Notice Successful application of this module requires a reasonable working knowledge of the Rockwell Automation

More information

MicroSCADA Pro DMS 600 *4.1. Operation Manual

MicroSCADA Pro DMS 600 *4.1. Operation Manual MicroSCADA Pro DMS 600 *4.1 1MRS755274 MicroSCADA Pro DMS 600 *4.1 Issued: 30.6.2004 Version: C/28.2.2005 Contents: 1. About this manual... 11 1.1. Copyrights... 11 1.2. Trademarks... 11 1.3. General...

More information

DAQ Electronics, Inc 262B Old New Brunswick Road, Piscataway, NJ

DAQ Electronics, Inc 262B Old New Brunswick Road, Piscataway, NJ DAQ Electronics, Inc 262B Old New Brunswick Road, Piscataway, NJ 08854-3756 DNP3 Server Configuration CallistoView version 5.0A This is a description of the unique DNP configuration dialogs and files in

More information

User Manual AXON TEST V3.8 IKELOS. Simulator

User Manual AXON TEST V3.8 IKELOS. Simulator AXON TEST V3.8 IKELOS Simulator 2 2014 Axon Group Ltd., Manual The information contained in this document is subject to change without notice. Axon Group Ltda Making great things Technology Development

More information

IEC61850 communication solution WinCC Channel

IEC61850 communication solution WinCC Channel IEC61850 communication solution WinCC Channel Documentation Date: 15.04.2015 Version: 2.03 IEC 61850 communication solution Page 1 of 33 Change history Datum Version Author Changes 19.11.2010 00.1 Mr.

More information

MicroSCADA Pro DMS Operation Manual

MicroSCADA Pro DMS Operation Manual DMS 600 4.2 1MRS755274 Issued: 30.6.2004 Version: E/28.3.2008 DMS 600 4.2 Contents: 1. About this manual... 11 1.1. Copyrights... 11 1.2. Trademarks... 11 1.3. General... 11 1.4. Use of symbols... 12

More information

Industrial IT. 800xA - System PLC Connect System Version 4.0. Operation

Industrial IT. 800xA - System PLC Connect System Version 4.0. Operation Industrial IT 800xA - System PLC Connect System Version 4.0 Operation Industrial IT 800xA - System PLC Connect System Version 4.0 Operation NOTICE The information in this document is subject to change

More information

MicroSCADA Pro SYS External OPC Data Access Client

MicroSCADA Pro SYS External OPC Data Access Client SYS600 9.4 Trace back information: Workspace Main version a54 1MRS758101 Issued: 3.6.2016 Version: C/3.6.2016 SYS600 9.4 Contents 1 Copyrights... 2 About this manual... 2.1 General... 2.2 Use of symbols...

More information

Experion LX Safety Manager Integration Guide

Experion LX Safety Manager Integration Guide Experion LX Safety Manager Integration Guide EXDOC-X119-en-110A February 2014 Release 110 Document Release Issue Date EXDOC-X119-en-1 0A 0 February 2014 Disclaimer This document contains Honeywell proprietary

More information

IEC Master Driver PTC Inc. All Rights Reserved.

IEC Master Driver PTC Inc. All Rights Reserved. 2017 PTC Inc. All Rights Reserved. 2 Table of Contents 1 Table of Contents 2 4 Overview 4 Setup 5 Channel Properties General 5 Channel Properties Ethernet Communications 6 Channel Properties Write Optimizations

More information

CAP 505. User s Guide

CAP 505. User s Guide CAP 505 1MRS752292-MUM CAP 505 Issued: 04.10.2002 Version: L/05.01.2005 1. About this manual...7 1.1. Copyrights...7 1.2. Trademarks...7 1.3. General...7 1.4. Use of symbols...8 1.5. Abbreviations...8

More information

MicroSCADA Pro DMS 600 *4.0. Operation Manual

MicroSCADA Pro DMS 600 *4.0. Operation Manual MicroSCADA Pro DMS 600 *4.0 1MRS755274 MicroSCADA Pro DMS 600 *4.0 Issued: 30.6.2004 Version: A/30.6.2004 Contents: 1. About this manual... 11 1.1. Copyrights...11 1.2. Trademarks...11 1.3. General...11

More information

Multifunction Protection and Switchgear Control Unit. Operator's manual

Multifunction Protection and Switchgear Control Unit. Operator's manual REF 542plus 1MRS755869 Issued: 01.11.2002 Version: C/31.05.2007 REF 542plus Contents Copyrights... 7 1. Introduction...9 1.1. This manual... 9 1.2. Use of symbols... 9 1.3. Intended audience... 9 1.4.

More information

System 800xA 800xA for Freelance Product Guide

System 800xA 800xA for Freelance Product Guide System 800xA 800xA for Freelance Product Guide System Version 6.0 Power and productivity for a better world TM System 800xA 800xA for Freelance Product Guide System Version 6.0 NOTICE This document contains

More information

MicroSCADA Pro SYS

MicroSCADA Pro SYS MicroSCADA Pro SYS 600 9.2 1MRS756156 Issued: 15.11.2006 Version: A/15.11.2006 MicroSCADA Pro SYS 600 9.2 Contents Copyrights...5 1. Introduction...7 1.1. This manual...7 1.2. Use of symbols...8 1.3.

More information

S900 I/O DTM 6.x. System Version 6.0. Power and productivity for a better world TM

S900 I/O DTM 6.x. System Version 6.0. Power and productivity for a better world TM S900 I/O DTM 6.x System Version 6.0 Power and productivity for a better world TM S900 I/O DTM 6.x NOTICE This document contains information about one or more ABB products and may include a description

More information

SCL Tool. Configuration manual

SCL Tool. Configuration manual REF 542plus 1MRS756342 Issued: 30.04.2007 Version: A/31.05.2007 REF 542plus Contents Copyrights... 5 1. Introduction...7 1.1. This manual... 7 1.2. Use of symbols... 7 1.3. Product documentation... 8

More information

MicroSCADA Pro LIB 510 *4.1. Operation Manual

MicroSCADA Pro LIB 510 *4.1. Operation Manual MicroSCADA Pro LIB 510 *4.1 1MRS755361 Issued: 30.06.2004 Version: B/20.12.2004 MicroSCADA Pro LIB 510 *4.1 1. About this manual...7 1.1. Copyrights...7 1.2. Trademarks...7 1.3. General...7 1.4. Use of

More information

DNP3 Master Serial Driver PTC Inc. All Rights Reserved.

DNP3 Master Serial Driver PTC Inc. All Rights Reserved. 2018 PTC Inc. All Rights Reserved. 2 Table of Contents 1 Table of Contents 2 9 Overview 9 Setup 9 Channel Properties General 10 Channel Properties Serial Communications 11 Channel Properties Write Optimizations

More information

Enron Modbus Driver PTC Inc. All Rights Reserved.

Enron Modbus Driver PTC Inc. All Rights Reserved. 2017 PTC Inc. All Rights Reserved. 2 Table of Contents 1 Table of Contents 2 5 Overview 5 Channel Setup 6 Channel Properties - General 6 Channel Properties - Serial Communications 7 Channel Properties

More information

T200 & Flair 200C. IEC communication Appendix to the User Manual. Easergy range. MV electrical network management

T200 & Flair 200C. IEC communication Appendix to the User Manual. Easergy range. MV electrical network management MV electrical network management Easergy range T200 & Flair 200C MV substation control and monitoring units IEC 60870-5-101 communication Appendix to the User Manual Content 1. Introduction... 3 2. References...

More information

Industrial IT. 800xA - Engineering System Version 4.1. Graphics

Industrial IT. 800xA - Engineering System Version 4.1. Graphics Industrial IT 800xA - Engineering System Version 4.1 Graphics Industrial IT 800xA - Engineering System Version 4.1 Graphics NOTICE The information in this document is subject to change without notice

More information

TOP Server V5 to MicroLogix Using DNP3 Ethernet Driver

TOP Server V5 to MicroLogix Using DNP3 Ethernet Driver TOP Server V5 to MicroLogix 1400 Using DNP3 Ethernet Driver Page 2 of 36 Table of Contents INTRODUCTION 3 CONFIGURING THE MICROLOGIX 1400 AS A DNP3 SLAVE 4 CONFIGURING TOP SERVER AS A DNP3 MASTER 9 TESTING

More information

MicroSCADA Pro SYS DNP 3.0 Master Protocol

MicroSCADA Pro SYS DNP 3.0 Master Protocol SYS 600 9.3 Trace back information: Workspace Main version a9 Checked in 0--09 MRS756657 Issued: 3.3.00 Version: B/30.9.0 Contents SYS 600 9.3 Copyrights... Introduction.... This manual.... Use of symbols....3

More information

DNP3 Communication User's manual

DNP3 Communication User's manual MV Network Management Fault tracking Monitoring and Control Merlin Gerin Easergy Range T200 P, T200 I DNP3 Communication User's manual Summary General...2 Functionnalities...2 Characteristics...2 Connection

More information

DNP3 Device Profile Based on DNP XML Schema version Showing both the Device's Capabilities and its Current Configuration

DNP3 Device Profile Based on DNP XML Schema version Showing both the Device's Capabilities and its Current Configuration Page 1 of 17 DNP3 Device Profile Based on DNP XML Schema version 2.11.00 Document Name: MHT410 XML File Document Description: Device Profile for the MHT410 Showing both the Device's and its Current Configuration

More information

Inform IT. Enterprise Historian TM and Profile Historian. Release Notes. Version 3.2/1 Patch 4 for History Services

Inform IT. Enterprise Historian TM and Profile Historian. Release Notes. Version 3.2/1 Patch 4 for History Services Inform IT Enterprise Historian TM and Profile Historian Version 3.2/1 Patch 4 for History Services Release Notes NOTICE The information in this document is subject to change without notice and should not

More information

Plant / field level Process

Plant / field level Process FM Telecontrol IEC 60870-5 Client and Server (Master and Slave) For communication in accordance with IEC 60870-5-101, -103 and -104 Control station Application areas The remote control protocol, according

More information

ABB ABB Oy, Distribution Automation

ABB ABB Oy, Distribution Automation ABB ABB Oy, Distribution Automation Guideline Issued: May 2012 Revision: A / 15 May 2012 COM600 Engineering process overview Engineering approach with.cid files in the SAB600 tool Contents: 1 Scope...

More information

Communication 7. What's in this Chapter? This chapter contains the following sections:

Communication 7. What's in this Chapter? This chapter contains the following sections: Communication 7 What's in this Chapter? This chapter contains the following sections: Section Topic Page 7.1 Modbus Protocol 170 7.2 IEC 60870-5-103 protocol 190 SEPED307003 02/2008 169 7.1 Modbus Protocol

More information

MicroSCADA Pro SYS 600 *9.1

MicroSCADA Pro SYS 600 *9.1 MicroSCADA Pro SYS 600 *9.1 1MRS751861-MEN Issued: 23.03.2003 Version: E/25.02.2005 MicroSCADA Pro SYS 600 *9.1 1. About this manual...5 1.1. Copyrights...5 1.2. Trademarks...5 1.3. General...5 1.4. Use

More information

Modbus Remote Communication Protocol for REM 54_. Technical Description

Modbus Remote Communication Protocol for REM 54_. Technical Description Modbus Remote Communication Protocol for REM 54_ 1MRS 750781-MUM Issued: 08.03.2002 Version: A/18.06.2002 Checked: ML Approved: AF Remote Communication Protocol for REM 54_ Modbus We reserve the right

More information

MicroSCADA Pro SYS 600 *9.1

MicroSCADA Pro SYS 600 *9.1 MicroSCADA Pro SYS 600 *9.1 1MRS751859-MEN Issued: 15.03.2002 Version: C/25.2.2005 MicroSCADA Pro SYS 600 *9.1 1. About this manual...5 1.1. Copyrights...5 1.2. Trademarks...5 1.3. General...5 1.4. Related

More information

Protection and Control IED Manager PCM600 Getting Started Guide

Protection and Control IED Manager PCM600 Getting Started Guide Protection and Control IED Manager PCM600 Document ID: 1MRS757866 Issued: 2018-04-18 Revision: C Product version: 2.9 Copyright 2018 ABB. All rights reserved Copyright This document and parts thereof

More information

IED Configurator. User Manual

IED Configurator. User Manual SystemCORP Embedded Technology Pty Ltd This PDF Document contains internal hyperlinks for ease of navigation. For example, click on any item listed in the Table of Contents to go to that page. General

More information

D400 Substation Data Manager

D400 Substation Data Manager GE Energy D400 Substation Data Manager Software Configuration Guide SWM0066 Version 2.75 Revision 0 General Copyright Notice 2007-2009, General Electric Company. All rights reserved. The information contained

More information

Relion Protection and Control. 615 series IEC Communication Protocol Manual

Relion Protection and Control. 615 series IEC Communication Protocol Manual Relion Protection and Control 615 series IEC 60870-5-103 Communication Protocol Manual Document ID: 1MRS756710 Issued: 2016-05-20 Revision: G Product version: 5.0 FP1 Copyright 2016 ABB. All rights reserved

More information

Rotork Pakscan Driver for DeltaV Programmable Serial Interface Card

Rotork Pakscan Driver for DeltaV Programmable Serial Interface Card Rotork Pakscan Driver for DeltaV Programmable Serial Interface Card USER MANUAL Rev. P1.55 January 2011 DeltaV is a trademark of Emerson Process Management Emerson Process Management. 1998, 1999. All rights

More information

MicroSCADA Pro SYS Historian Monitor Configuration

MicroSCADA Pro SYS Historian Monitor Configuration SYS 600 9.3 Trace back information: Workspace Main version a10 Checked in 2012-11-12 1MRS757708 Issued: 30.9.2012 Version: A/30.9.2012 SYS 600 9.3 Contents 1 Copyrights... 2 Introduction... 2.1 This manual...

More information

Functional Description DOC01 - Digital Operator Control Version 5.2-0

Functional Description DOC01 - Digital Operator Control Version 5.2-0 Functional Description DOC01 - Digital Operator Control Version 5.2-0 3BTG811792-3021 / A Page 1 NOTICE The information in this document is subject to change without notice and should not be construed

More information

Protect IT MNS Motor Management INSUM. Dual Redundancy Guide Version 2.3 ABB

Protect IT MNS Motor Management INSUM. Dual Redundancy Guide Version 2.3 ABB Protect IT MNS Motor Management INSUM Version 2.3 ABB Network Management Guide INSUM Version 2.3 1 NOTICE The information in this document is subject to change without notice and should not be construed

More information

7SG11 Argus 7 Check and System Synchronising Relays

7SG11 Argus 7 Check and System Synchronising Relays 7SG11 Argus 7 Check and System Synchronising Relays Document Release History This document is issue 2010/02. The list of revisions up to and including this issue is: Pre release 2010/02 Document reformat

More information

MicroSCADA Pro SYS 600 *9.1

MicroSCADA Pro SYS 600 *9.1 MicroSCADA Pro SYS 600 *9.1 1MRS751964-MEN Issued: 15.03.2002 Version: C/25.02.2005 MicroSCADA Pro SYS 600 *9.1 1. About this manual...5 1.1. Copyrights...5 1.2. Trademarks...5 1.3. General...5 1.4. Related

More information

IntesisBox MAPS. Configuration & monitoring software of IntesisBox KNX series. User's manual Issue Date: 06/17 r1.0 eng

IntesisBox MAPS. Configuration & monitoring software of IntesisBox KNX series. User's manual Issue Date: 06/17 r1.0 eng IntesisBox MAPS Configuration & monitoring software of IntesisBox KNX series User's manual Issue Date: 06/17 r1.0 eng Intesis Software S.L.U. 2017 All Rights Reserved. Information in this document is subject

More information

Functional Description DIS01 - Digital Input Signal Version 5.2-0

Functional Description DIS01 - Digital Input Signal Version 5.2-0 Functional Description DIS01 - Digital Input Signal Version 5.2-0 3BTG811792-3020 / A Page 1 NOTICE The information in this document is subject to change without notice and should not be construed as a

More information

EuroGateway. IEC Substation Automation System Communication Gateway

EuroGateway. IEC Substation Automation System Communication Gateway EuroGateway IEC 61850 Substation Automation System Communication Gateway Basic Configuration Introduction Communication gateway Substation SCADA Substation HMI IEC 61850 client Temporary storage (disturbance

More information

MicroSCADA Pro SYS Historian Monitor Configuration

MicroSCADA Pro SYS Historian Monitor Configuration SYS600 9.4 Trace back information: Workspace Main version a26 Checked in 2014-05-16 1MRS758121 Issued: 16.5.2014 Version: A/16.5.2014 SYS600 9.4 Contents 1 Copyrights... 2 Introduction... 2.1 This manual...

More information

Series PM130 PLUS Powermeters PM130P/PM130E/PM130EH

Series PM130 PLUS Powermeters PM130P/PM130E/PM130EH Series PM130 PLUS Powermeters PM130P/PM130E/PM130EH IEC60870-5-101/104 Communications Protocol Reference Guide BG0503 Rev. A3 Every effort has been made to ensure that the material herein is complete and

More information

Industrial IT. 800xA - System System Version 4.1. Post Installation

Industrial IT. 800xA - System System Version 4.1. Post Installation Industrial IT 800xA - System System Version 4.1 Post Installation Industrial IT 800xA - System System Version 4.1 Post Installation NOTICE The information in this document is subject to change without

More information

Voltage regulator TAPCON 240

Voltage regulator TAPCON 240 Voltage regulator TAPCON 240 Supplement 2398461/01 Protocol description DNP3 All rights reserved by Maschinenfabrik Reinhausen Copying and distribution of this document and utilization and communication

More information

Overcurrent and Earth-Fault Relay REJ 525. Technical Reference Manual

Overcurrent and Earth-Fault Relay REJ 525. Technical Reference Manual Overcurrent and Earth-Fault Relay MRS75094-MUM Issued: 4.09.998 Version: D/4..2005 Overcurrent and Earth-Fault Relay Contents. About this manual...5.. Copyrights...5.2. Trademarks...5.3. Guarantee...5.4.

More information

System 800xA Multisystem Integration

System 800xA Multisystem Integration System 800xA Multisystem Integration System Version 5.1 Power and productivity for a better world T System 800xA Multisystem Integration System Version 5.1 NOTICE This document contains information about

More information

MicroSCADA Pro SYS

MicroSCADA Pro SYS MicroSCADA Pro SYS 600 9.2 1MRS756155 Issued: 15.11.2006 Version: A/15.11.2006 MicroSCADA Pro SYS 600 9.2 Contents Copyrights...5 1. Introduction...7 1.1. This manual...7 1.2. Use of symbols...8 1.3.

More information

Chapter 6: DNP Introduction. 6.2 Features of the DNP The OSI/ISO model. 6.3 Basic topology

Chapter 6: DNP Introduction. 6.2 Features of the DNP The OSI/ISO model. 6.3 Basic topology 6.1 Introduction DNP3 (Distributed Network Protocol Version 3) is an open, intelligent, robust and efficient modern SCADA protocol designed to optimise the transmission of data acquisition information

More information

NOTE The documentation and/or manuals provided by the IEDs vendors must be read and understood thoroughly prior to configuration.

NOTE The documentation and/or manuals provided by the IEDs vendors must be read and understood thoroughly prior to configuration. ConfigWiz Addendum This is the DNP3.0 client addendum. This addendum describes the pop-up window tabs, fields, and ranges of valid parameters for entry in those fields. NOTE The documentation and/or manuals

More information

General Specifications

General Specifications General Specifications GS 34P02P22-02E DNP3 Communication Portfolio (FCN-500/FCN-RTU) GENERAL This General Specifications document describes the Distributed Network Protocol (DNP3) Communication Portfolio

More information

IEC INTEGRATION KIT FOR PAC PROJECT GUIDE

IEC INTEGRATION KIT FOR PAC PROJECT GUIDE IEC60870-5 INTEGRATION KIT FOR PAC PROJECT GUIDE Form 2098 131015 October, 2013 43044 Business Park Drive Temecula CA 92590-3614 Phone: 800-321-OPTO (6786) or 951-695-3000 Fax: 800-832-OPTO (6786) or 951-695-2712

More information

JetWeb JX6-INT1 Function Description

JetWeb JX6-INT1 Function Description JetWeb JX6-INT1 Function Description Article # 608 640 72 Edition 2.1 December 2003 / Printed in Germany Function Description December 2003 JetWeb JX6-INT1 JETTER AG reserves the right to make alterations

More information