Distributed Power System SA3100 Diagnostics, Troubleshooting, and Start-Up Guidelines

Size: px
Start display at page:

Download "Distributed Power System SA3100 Diagnostics, Troubleshooting, and Start-Up Guidelines"

Transcription

1 Distributed Power System SA3100 Diagnostics, Troubleshooting, and Start-Up Guidelines Instruction Manual S

2 Throughout this manual, the following notes are used to alert you to safety considerations:! ATTENTION: Identifies information about practices or circumstances that can lead to personal injury or death, property damage, or economic loss. Important: Identifies information that is critical for successful application and understanding of the product.! ATTENTION: Only qualified personnel familiar with the construction and operation of this equipment and the hazards involved should install, adjust, operate, or service this equipment. Read and understand this manual and other applicable manuals in their entirety before proceeding. Failure to observe this precaution could result in severe bodily injury or loss of life. ATTENTION: DC bus capacitors retain hazardous voltages after input power has been disconnected. After disconnecting input power, wait five (5) minutes for the DC bus capacitors to discharge and then check the voltage with a voltmeter to ensure the DC bus capacitors are discharged before touching any internal components. Failure to observe this precaution could result in severe bodily injury or loss of life. ATTENTION: Only qualified Rockwell personnel or other trained personnel who understand the potential hazards involved may make modifications to the regulator configuration, variable configuration, and application tasks. Any modifications may result in uncontrolled machine operation. Failure to observe these precautions could result in damage to equipment and bodily injury. ATTENTION: The user must provide an external, hardwired stop circuit outside of the drive circuitry. This circuit must disable the system in case of improper operation. Uncontrolled machine operation may result if this procedure is not followed. Failure to observe this precaution could result in bodily injury. ATTENTION: Registers and bits in the UDC module that are described as read only or for system use only must not be written to by the user. Writing to these registers and bits may result in improper system operation. Failure to observe this precaution could result in bodily injury. ATTENTION: Connecting or disconnecting a regulator board may result in unexpected machine motion. Turn off power to the drive before replacing a circuit board or its connecting cables. Failure to observe these precautions could result in bodily injury. ATTENTION: The user is responsible for conforming with all applicable local, national, and international codes. Failure to observe this precaution could result in damage to, or destruction of, the equipment. ATTENTION: The circuit boards of the PMI regulator contain static-sensitive components. Do not touch the boards or their connectors. When not installed, circuit boards should be stored in antistatic bags. Failure to observe this precaution could result in damage to, or destruction of, the equipment. The information in this user s manual is subject to change without notice. Ethernet is a trademark of Xerox Corporation. Windows is a trademark of Microsoft Corporation. AutoMax is a trademark of Rockwell Automation Rockwell International Corporation

3 CONTENTS Chapter 1 Chapter 2 Chapter 3 Chapter 4 Introduction 1.1 Related Publications Typographical Conventions Diagnostics and Troubleshooting 2.1 Definition of Terms Used in Diagnostics and Troubleshooting Power-up Diagnostics in the UDC Module and PMI Regulator Interlock Tests Run-time Diagnostics Drive Faults How the System Reacts to Drive Faults MCR Output Control Drive Warnings How to Clear the Drive Fault and Drive Warning Registers Internal DC Bus Diagnostics DC Bus Monitoring During Bridge Test Mode DC Bus Monitoring During Torque Minor Loop Mode PMI Regulator Operating Modes 3.1 Idle Mode Bridge Test Mode PMI Tuning Mode (Automatic Gain Calculation) Run Mode Installation and Start-Up Guidelines 4.1 Using the AutoMax Programming Executive to Access the Rack Environmental Requirements Installing the Motor Installing the Drive Enclosed Drives Open Chassis Drives Wiring the Drive Basic Drive Interconnections Drive Inspection and Start-up Guidelines What To Do After Unexpected Test Results Recommended Test Equipment Physically Inspecting the Drive Physically Inspecting the Motor Checking the Installation with Power Off Testing AC Input Power Modules with AC Power On Testing DC Bus Supplies and DC Input Power Modules Checking the DC Bus Supply Testing DC Input Power Modules with DC Power On Table of Contents I

4 4.7.8 I/O Verification Testing UDC/PMI Regulator Communication Status Testing Flex I/O Registers Testing Feedback Registers and Bits Testing the UDC Module Test Switch Register Testing UDC Module Meter Ports Testing PMI Regulator Meter Ports Performing Uncoupled Motor Tests (Vector) Running Dynamic Motor Tests Updated Drawings and Software Listings (Vector) Appendix A Drive Fault Register... A-1 Appendix B Drive Warning Register... B-1 Appendix C Interlock Register... C-1 Appendix D Diagnostic Fault Code Register... D-1 Appendix E Summary of UDC Module Drive Fault Indicators... E-1 Appendix F PMI Regulator LED Summary... F-1 Appendix G Status of Data in the AutoMax Rack After a STOP_ALL Command or STOP_ALL Fault...G-1 Appendix H AutoMax Programming Executive Access Levels... H-1 Appendix I Appendix J Terminal Block Locations and Test Points...I-1 PMI Regulator Test Points...J-1 II Diagnostics, Troubleshooting, and Start-Up Guidelines

5 List of Figures Figure 2.1 PMI Regulator Operating Modes Overview Figure 3.1 PMI Regulator Operating Modes and Diagnostics Figure 3.2 Internal DC Bus Control Flowchart Figure 3.3 Power Device Test Locations Figure I.1 Terminal Block Locations... I-1 Figure I.2 Terminal Block TB1 (B Frame Drives)... I-2 Figure I.3 Terminal Block TB1 (C and D Frame Drives)... I-3 Figure I.4 Terminal Block TB1 (E, F, and G Frame Drives)... I-4 Figure I.5 Terminal Block TB1 (H Frame Drives)... I-5 Figure J.1 PMI Regulator Mother Board - Test Points... J-2 Table of Contents III

6 IV Diagnostics, Troubleshooting, and Start-Up Guidelines

7 List of Tables Table 1.1 SA3100 Documentation (Binder S-3053) Table 1.2 SA3100 Power Structure Service Manual Cross Reference Table 3.1 PMI Regulator Operating Modes Table 3.2 Bridge Test Connections Table 4.1 UDC/PMI Regulator Communication Status Register Formats Table 4.2 Flex I/O Register Formats Table 4.3 Analog Data Format Table 4.4 Feedback Registers and Bits Table A.1 Effect of a Disconnected Fiber-Optic Cable...A-4 Table of Contents V

8 VI Diagnostics, Troubleshooting, and Start-Up Guidelines

9 CHAPTER 1 Introduction This instruction manual is divided into two sections: 1) a description of SA3100 drive diagnostics and troubleshooting, 2) start-up guidelines. This manual is intended for users of SA3100 drives who have training and experience in AC drive control and who are familiar with all other SA3100 drive documentation. The diagnostics and troubleshooting chapters (chapters 2-3) describe the error checking built into the PMI Regulator operating system and how to use warning and fault registers, LEDs, and the error log to diagnose drive problems. Chapter 4 provides guidelines on starting up SA3100 AC drives. Although initial startup services are usually provided by Rockwell personnel, it is recommended that the user become familiar with the general guidelines in this chapter in order to be better prepared to work with the Rockwell service engineer. 1.1 Related Publications The user must become familiar with the other instruction manuals that describe the SA3100 drive system. The documentation that describes the SA3100 drive is contained in binder S-3053 and is listed in table 1.1. Table 1.1 SA3100 Documentation (Binder S-3053) Document Document Part Number Drive System Overview S-3005 Universal Drive Controller Module S-3007 Fiber Optic Cabling S-3009 SA3100 Drive Configuration & Programming S-3056 SA3100 PMI Regulator S-3057 SA3100 Power Modules S-3058 SA3100 Diagnostics, Troubleshooting, & Start-Up Guidelines S-3059 Information Guide S-3054 Introduction 1-1

10 Power structure replacement parts and service procedures are contained in the instruction manuals listed in table 1.2. Table 1.2 SA3100 Power Structure Service Manual Cross Reference AC Input Voltage 200 VAC VAC [A] DC Bus Input Voltage Nominal HP Frame Size 310 VDC [Q] Use Service Manual 1336 Force- B 6.11 C 6.12 D 6.13 E Diagnostics, Troubleshooting, and Start-Up Guidelines

11 Table 1.2 SA3100 Power Structure Service Manual Cross Reference AC Input Voltage 380 VAC VAC [B] DC Bus Input Voltage Nominal HP Frame Size 513 VDC VDC [R] Use Service Manual 1336 Force- B 6.11 C 6.12 D 6.13 E 6.14 F G H 6.15 Introduction 1-3

12 Table 1.2 SA3100 Power Structure Service Manual Cross Reference AC Input Voltage 500 VAC VAC [C] DC Bus Input Voltage Nominal HP Frame Size 675 VDC VDC [W] Use Service Manual 1336 Force- B 6.11 C 6.12 D 6.13 E 6.14 F G H 6.15 Other related documents that you should refer to include the following: AutoMax Programming Executive Instruction Manual Version 3.5A or later Installing, Operating, and Maintaining Engineered Drive Systems (D2-3115) Additional information about using the SA3100 drive is found in the wiring diagrams, prints, and other documentation shipped with each drive system. Always consult the prints shipped with your drive system for specific information about installing, operating, and maintaining your drive. 1-4 Diagnostics, Troubleshooting, and Start-Up Guidelines

13 1.2 Typographical Conventions The following typographical conventions are used in this manual: Variable names Variables names are shown in all capital letters followed by the appropriate terminating character. The variable names shown in this manual are suggested names only and may vary from the names used in your application. Example: Register names Register names are shown with the initial letters capitalized followed by the corresponding register number for both drive A and drive B. The drive A register number is shown first followed by the drive B register number (A/B). Example: Drive Fault register (202/1202) Bit names Individual bit names are shown with the initial letters capitalized. Also shown, in parentheses, is the bit s register number, bit number, and suggested variable name. Example: Fault Reset bit (register 100/1100, bit 8, FLT_RST@ ) Parameter entry screen titles Parameter entry screen titles and the parameters themselves are shown with the initial letters capitalized. Example: Feedback Data parameter entry screen Introduction 1-5

14 1-6 Diagnostics, Troubleshooting, and Start-Up Guidelines

15 CHAPTER 2 Diagnostics and Troubleshooting The Distributed Power System contains built-in comprehensive diagnostics. In order to diagnose and correct problems quickly, it is important to understand the types of diagnostics that are performed, when they are performed, and how the results are reported. This chapter describes the different types of diagnostics performed by the system s modules and how the results of these diagnostics are reported. This chapter also describes how the system reacts if an error is detected. There are a number of control modes that can be selected by the user for PMI Regulator operation. An overview of these modes is shown in figure 2.1. The Distributed Power System provides diagnostics at each level of operation as shown in figure 3.1. Use these figures as a reference to quickly identify the system's requirements for entering and operating in each mode. These figures also refer to specific sections in the manual that provide additional information. 2.1 Definition of Terms Used in Diagnostics and Troubleshooting For the purpose of describing diagnostics and troubleshooting, this instruction manual will use specific terms to refer to the types of errors that can be detected by the PMI Regulator and the response of the PMI Regulator and UDC module to those errors. A diagnostic is a software routine specifically designed to check for error conditions. There are three types of diagnostics in SA3100 drives: power-up diagnostics, interlock diagnostics, and run-time diagnostics. A drive fault is an error specifically checked for by the PMI Regulator operating system that will shut the drive down. Faults are reported in the Drive Fault register (202/1202) of the UDC module and in the error log for the UDC task in which the fault occurred. A drive shut-down occurs when any fault reported in the Drive register (202/1202) occurs. A drive warning is an error specifically checked for by the PMI Regulator operating system that indicates the drive is not operating in an optimum manner. Drive warnings will not shut the drive down. An error is any condition other than the desired condition. Interlock diagnostics are those diagnostics performed by the PMI Regulator operating system in response to a drive control request from the programmer, e.g., TRQ_RUN@, in register 100/1100 of the UDC module dual port memory. Power-up diagnostics consist of the initial tests for basic functionality performed by all printed circuit board modules. Diagnostics and Troubleshooting 2-1

16 Run-time diagnostics are those diagnostics performed continuously by the PMI Regulator as a background task after it has received its operating system from the UDC module. Power On Idle Select PMI_RUN@, BRG_TST@, or PMI_TUN@ Interlock Tests PMI Tuning Close MCR Minor Loop Run Bridge Test Bus Missing Bus Missing Open MCR Open MCR Figure 2.1 PMI Regulator Operating Modes Overview 2-2 Diagnostics, Troubleshooting, and Start-Up Guidelines

17 2.2 Power-up Diagnostics in the UDC Module and PMI Regulator Power-up diagnostics execute in the UDC module in the AutoMax rack and in the PMI Regulator. When power is applied to the AutoMax rack, the UDC module performs a series of self-tests. When all of the tests are successfully completed, the CARD OK LED on the UDC module's faceplate will turn on. When power is applied to the PMI Regulator, the on-board Processor performs a series of self-tests. When all of the tests are successfully completed, the PMI Regulator s OK LED will turn on. If the PMI Regulator does not pass these tests, it must be replaced. The AC Power Technology circuitry on the PMI Regulator then performs a series of calibration and self-diagnostic tests. When these tests are successfully completed, the DRV RDY LED will turn on. If a failure occurs refer to the description of register 222/1222 in the Drive Configuration and Programming instruction manual (S-3056) for help in identifying the test that failed. After all of the power-up tests are passed, the PMI Regulator requests the appropriate operating system from the UDC module. The UDC module downloads the operating system and the parameter configuration data to the PMI Regulator. The PMI Regulator then runs under the control of its operating system and begins performing the run-time diagnostics. Run-time diagnostics are described in section Interlock Tests Interlock tests are performed by the PMI Regulator whenever one of the PMI Regulator's operating modes is selected by the programmer through the Drive Control register (100/1100). These diagnostics verify that all conditions required for the operating mode selected are satisfied. If the interlock tests are completed successfully, then the operating mode requested by the programmer can be entered. If any of the interlock diagnostics fails, the PMI Regulator will latch a bit in the Interlock register (205/1205) corresponding to the first diagnostic test that failed, and the requested operating mode will not be entered (i.e., the PMI Regulator will remain in the idle mode). If an interlock test failure occurs, follow the procedure below: Step 1. Reset the command bit that is currently set in the Drive Control register (100/1100). Step 2. Correct the condition that caused the test failure. Step 3. Set the desired command bit in the Drive Control register (100/1100). The PMI Regulator will perform the interlock tests each time a rising edge is detected on the command bits. The results of subsequent interlock tests will overwrite the previous test s results. Diagnostics and Troubleshooting 2-3

18 2.4 Run-time Diagnostics Run-time diagnostics are performed continuously by the PMI Regulator after its operating system has been downloaded by the UDC module. These diagnostics test the status of the PMI Regulator and the connected hardware and also check the integrity of the communication link between the UDC module and the PMI Regulator. The results of the diagnostics are stored in either the Drive Warning register (203/1203) or the Drive Fault register (202/1202) in the UDC module s dual port memory. How drive faults and drive warnings are indicated and how they affect the operation of the drive is described in the following sections Drive Faults When the PMI Regulator detects any of the conditions described in the Drive Fault register, it will shut down the drive. To determine the cause of a drive shutdown, the following indicators are provided: Drive Fault register (202/1202) The PMI Regulator will set a bit in the Drive Fault register to indicate the condition that caused the shutdown. The interlock tests check this register for fault conditions that have occurred. Refer to Appendix A for a complete description of the Drive Fault Register. Drive Status Register (200/1200) The PMI Regulator will set the Fault Detected bit (bit 8, FLT@) of the Drive Status register when a drive fault has been detected. LEDs on the UDC module If either DRV FLT A or DRV FLT B is on, a drive fault has been detected for the drive using that communication channel. LEDs on the PMI Regulator The PMI Regulator contains a status/fault LED board. Refer to Appendix E for LED definitions. Error log for the UDC task The error log for the task in which the fault occurred is accessed through the ON LINE menu of the AutoMax Programming Executive. A list of the drive fault error codes can be found in Appendix D. Refer to appropriate AutoMax Programming Executive instruction manual for more information regarding the Programming Executive and the ON LINE menu How the System Reacts to Drive Faults As described in section 2.4.1, if the PMI Regulator detects any of the conditions described in the Drive Fault register, it will shut down the drive. This means that the PMI Regulator responds by disabling the gates of the power devices, causing the motor to begin a coast to stop. When the PMI Regulator detects that current is less 2-4 Diagnostics, Troubleshooting, and Start-Up Guidelines

19 than 2% of the rated motor current, the PMI Regulator will turn off the MCR output. Note that the PMI Regulator will always turn off the MCR output within 300 msec of the fault occurrence even if the 2% current level has not been reached. If any of the following faults are detected by the PMI Regulator, it will disable the gates immediately and set the corresponding bit in the Drive Fault register (202/1202): DC Bus Overvoltage Fault (Bit 0) DC Bus Overcurrent Fault (Bit 1) Ground Current Fault (Bit 2) Instantaneous Overcurrent Fault (Bit 3) Power Supply Fault (Bit 4) Charge Bus Time-Out Fault (Bit 6) Over Temperature Fault (Bit 7) Resolver Broken Wire Fault (Bit 8) Resolver Fault (Bit 9) Overspeed Fault (Bit 10) Power Technology Fault (Bit 11) PMI Regulator Bus Fault (Bit 13) UDC Run Fault (Bit 14) Communications Lost Fault (15) The PMI operating system will then take over turning off the MCR output as described above.! ATTENTION: The UDC task is not stopped automatically when a drive fault occurs. The user must ensure that the application tasks test the Drive Fault register (202/1202) and take the appropriate action if a fault is detected MCR Output Control The MCR output on the PMI Regulator s Resolver & Drive I/O board is used to control an optional M-contactor to turn off power to the motor. This option is selected during UDC module parameter configuration. If the programmer chooses to connect the MCR output to an M-contactor, contacts from this device must be wired to the AUX IN1/MFDBK input as feedback. The PMI operating system will wait for AUX IN1/MFDBK to turn on before executing any operating mode. The Run Permissive input (RPI) on the Resolver & Drive I/O board and the MCR output are interlocked in hardware. The MCR output can be turned on only when the RPI is asserted. The MCR output itself is under the control of the PMI Regulator. Application tasks have no direct control of the MCR output. RPI is controlled by the user. When RPI is off, MCR cannot be activated. Diagnostics and Troubleshooting 2-5

20 The following conditions will cause the MCR output to turn off: Absence of the RPI signal Occurrence of a drive fault Control algorithm is turned off (PMI_RUN@ = 0) After any of the above conditions occurs, the PMI Regulator will wait for current feedback to be less than 2% of rated motor current multiplied by the motor overload ratio. The PMI Regulator will then turn off the MCR output. If this current level has not been reached within 300 msec, the MCR output will be turned off regardless. In addition, if the RPI signal is removed, the MCR output and gate power will be removed under hardware control within approximately 0.5 seconds of the removal of the RPI signal to provide an additional interlock. This is done regardless of the actions taken by the PMI Drive Warnings The PMI Regulator will check for conditions that are not serious enough to shut down the drive, but may affect its performance. If the PMI Regulator detects any of the conditions described in the Drive Warning register, it will set the appropriate bit but will NOT shut down the drive. The user must ensure that the application task tests the Drive Warning register (203/1203) and takes any appropriate action if a warning condition is detected. The PMI Regulator will also set the Warning Detected bit (register 200/1200, bit 9, WRN@) when a drive warning has been detected. Appendix B provides a complete description of the Drive Warning register. Except for I/O faults, drive warnings are not indicated by LEDs (an I/O fault will turn on the I/O FLT LED on the PMI Regulator). Drive warnings are not displayed in the UDC task s error log How to Clear the Drive Fault and Drive Warning Registers After a drive fault has been detected, the programmer must do the following before the drive can be restarted: Step 1. Reset the command bit that is currently set in the Drive Control register (100/1100). Step 2. Correct the fault. Step 3. Set and reset the Fault Reset bit (register 100/1100, bit 8, FLT_RST@) to clear the Drive Fault register (200/1200). (Note that the Fault Reset bit is edge sensitive.) Step 4. Set the desired command bit in the Drive Control register (100/1100). After a drive warning has been detected, the programmer can clear the entire Drive Warning register by setting and resetting the Warning Reset bit (register 100/1100, bit 9, WRN_RST@). (Note that the Warning Reset bit is edge sensitive.) 2-6 Diagnostics, Troubleshooting, and Start-Up Guidelines

21 2.5 Internal DC Bus Diagnostics The status of the DC bus is monitored as part of both the interlock and run-time diagnostics. The DC bus is considered ready when the PMI Regulator detects that the bus voltage is greater than the undervoltage threshold value stored in local tunable UVT_E0% and has reached a steady state, and the pre-charge contactor has closed. This is checked as an interlock test and is then constantly monitored during run-time diagnostics. A complete description of the DC bus pre-charge sequence is provided in the SA3100 Power Modules instruction manual (S-3058). For further details regarding a DC bus fault, see the extended status register 222 (1222) DC Bus Monitoring During Bridge Test Mode If bus voltage drops below the value stored in the undervoltage warning threshold tunable (UVT_E0%) while the PMI Regulator is in bridge test mode, the PMI Regulator will issue a drive warning (203/1203, bit 1, WRN_UV@). If bus voltage continues to drop below the value stored in the power loss fault threshold local tunable (PLT_E0%), the pre-charge contactor will open. While the pre-charge contactor is open, the gates are disabled, and the bridge test is not functional. If bus voltage does not return to the proper level within 10 seconds, a Bus Charge Time-out fault (register 202/1202, bit 6, FLT_CHG@) will occur, and the drive will shut down. If bus voltage returns to the proper level within 10 seconds, the bridge test will return to normal operation DC Bus Monitoring During Torque Minor Loop Mode If bus voltage drops below the value stored in the undervoltage warning threshold tunable (UVT_E0%) while the PMI Regulator is in torque minor loop mode, the PMI Regulator will limit torque in order to avoid further drop in DC bus voltage and issue a drive warning (203/1203, bit 1, WRN_UV@). If bus voltage continues to drop below the value stored in the power loss fault threshold local tunable (PLT_E0%), the pre-charge contactor will open. While the pre-charge contactor is open, the gates of the power devices are disabled, and the motor will begin to coast to stop. If bus voltage returns to the nominal configured value within 10 seconds of the bus voltage dropping to less than the value stored in the power loss fault threshold local tunable, the pre-charge contactor will automatically close and the PMI Regulator will return to using the torque reference currently being requested by the UDC. If bus voltage does not return to the nominal configured value within 10 seconds, a Bus Charge Time-out fault (register 202/1202, bit 6, FLT_CHG@) will occur, and the drive will shut down. Diagnostics and Troubleshooting 2-7

22 2-8 Diagnostics, Troubleshooting, and Start-Up Guidelines

23 CHAPTER 3 PMI Regulator Operating Modes The PMI Regulator s default operating mode is idle. All other operating modes are selected by the programmer in the Drive Control register (100/1100). Table 3.1 shows the available operating modes. Note that the operating modes are mutually exclusive, i.e., only one mode may be enabled at a time (this is checked by the interlock tests). The PMI Regulator s operating modes are shown in figure 3.1 and are described in the following sections. Table 3.1 PMI Regulator Operating Modes Operating Mode Drive Control Register Bit Mode Description Idle The PMI Regulator s default operating mode during which no algorithms are running. Enable PMI Run 0 Executes the control algorithms. Enable Tuning 1 Calculates gain values for the control algorithm. Bridge Test Enable 2 Performs a test to verify gate cable connections and power devices. PMI Regulator Operating Modes 3-1

24 Power-Up Diagnostics Section 2.2 Reg 100 Bit 4 On Pre-Charge Contactor I/M S-3058 Vdc > UVT_E0% + Steady State Condition and Pre-Charge Contactor Closed Bus Ready Idle Section 3.1 Select PMI_RUN@, BRG_TST@, or PMI_TUN@ Interlock Tests Failed Close MCR Section Interlock Tests OK and PMI_TUN@ Reg 100 Bit 1 On Interlock Tests OK PMI Tuning Section 3.3 Tuning Complete Reg 200 Bit 1 On MCR Closed Reg 201 Bit 1 and PMI_RUN@ Reg 100 Bit 0 MCR Closed Reg 201 Bit 1 and BRG_TST@ Reg 100 Bit 2 Minor Loop Run Bridge Test Section 3.4 Section 3.2 Exit if Reg 100 Bit 0 Off or Fault Reg 202 Any Bit or RPI Missing Reg 201 Bit 0 Off Open MCR Section Bus Missing Vdc < PLT_E0% Charge Bus Timeout Fault Reg 202 Bit 6 Bus OK Exit if Reg 100 Bit 1 Off or Fault Reg 202 Any Bit or RPI Missing Reg 201 Bit 0 Off Open MCR Section Bus Missing Vdc < PLT_E0% Charge Bus Timeout Fault Reg 202 Bit 6 Bus OK Figure 3.1 PMI Regulator Operating Modes and Diagnostics 3-2 Diagnostics, Troubleshooting, and Start-Up Guidelines

25 Idle On* Begin 10 Second Timer Wait for AC Line No No Hi HP Common Bus or Hi HP Stand-Alone? Yes AC Line Status From Power Module = TRUE? No More than 10 Seconds Elapsed? Yes Fault Occurs Register 202/1202 Yes Hi HP Stand-Alone? Yes ** Wait for Bus to Charge No Open Pre-Charge Contactor ** Nominal Bus Voltage Reached? No More than 10 Seconds Elapsed? Yes Yes ** PMI Closes Pre-Charge Contactor ** Auxiliary Contacts Closed? No More than 10 Seconds Elapsed? Yes Open Pre-Charge Contactor Yes ** PMI Sets BUS_RDY@ Yes ** Bus Charged Fault Occurs? *BUS_ENA@ must transistion from off to on to start the bus charging process. **BUS_ENA@ must remain on during the drive operation No Figure 3.2 Internal DC Bus Control Flowchart PMI Regulator Operating Modes 3-3

26 3.1 Idle Mode The PMI Regulator s default operating mode after passing the power-up diagnostics and completing the DC bus pre-charge sequence is idle. When in idle mode, the PMI Regulator is waiting for a command from the Drive Control register (100/1100) to change operating modes. In order for the PMI Regulator to enter the requested operating mode, the Interlock tests must be passed. If any of the Interlock tests fails or if any fault is latched in the Drive Fault register (202/1202), the PMI Regulator will remain in the idle mode. The PMI Regulator will return to the idle mode when it exits any of the other operating modes. 3.2 Bridge Test Mode The bridge test mode is used to verify that the power devices in the Power Module work correctly. Enabling this test turns on the power devices one at a time in a user-specified pattern. The operator can then measure the voltages produced across the devices. Note that this test is normally performed at the factory and does not need to be performed by the user unless one or more power devices have been replaced. If required, this test should be performed before enabling any other mode of the PMI Regulator, such as torque minor loop run. Follow the steps below to perform the bridge test: Step 1.! Step 2. Step 3. Step 4. Step 5. Stop the drive if it is running. Turn off and lock out input power. ATTENTION:DC bus capacitors retain hazardous voltages after input power has been disconnected. After disconnecting input power, wait five (5) minutes for the DC bus capacitors to discharge. Then check the voltage across the DC bus to ensure the bus capacitors are discharged before touching any internal components. Failure to observe this precaution could result in severe bodily injury or loss of life. Wait five minutes to allow the DC bus voltage to dissipate. Open the Power Module s cabinet door or chassis cover. Measure the DC bus potential with a voltmeter before working on the drive. Measure the voltage at the DC bus test points as shown in figure 4.1. When the DC bus potential is down to less than 5 volts, touch a 50 ohm, 50 watt or larger resistor between the test points for 20 seconds. This allows any remaining DC bus voltage to dissipate. Remove the resistor and re-measure the DC bus potential, which should now be at 0V. This step and the following steps assume that your installation includes a terminal block between the Power Module and the motor. Disconnect the motor leads from the terminal block to which they are connected. 3-4 Diagnostics, Troubleshooting, and Start-Up Guidelines

27 ! Step 6.! ATTENTION:The bridge test applies the full DC bus voltage to an output phase for the duration of a test. The motor must not be connected to the Drive while performing the bridge test in order to avoid damage to the drive and motor. Failure to observe this precaution could result in damage to, or destruction of, the equipment. If the Power Module and the motor are connected through one set of leads, disconnect the motor leads from the Power Module. You will need to connect the voltmeter directly to the phase U, V, and W outputs of the Power Module. Use table 3.2 to determine the devices to be tested and to identify where to connect the voltmeter. See figure 3.2. Set the voltmeter to the 1000V scale. ATTENTION:The remaining steps are performed with power on. Exercise extreme caution as hazardous voltages exist. Failure to observe this precaution could result in severe bodily injury or loss of life. Power Device Pair Being Tested 1 Table 3.2 Bridge Test Connections Bridge Test Code Register (105/1105) Value 2 Voltmeter Connection for +VDC 3 1. U upper V lower 2. U lower W upper 3. U upper W lower 4. U lower V upper 5. V upper W lower 6. V lower W upper 11H U(+) V( ) 0CH U( ) W(+) 21H U(+) W( ) 0AH U( ) V(+) 22H V(+) W( ) 24H V( ) W(+) 1. It is not necessary to measure all the power device pairs. All possible combinations can be tested by testing either pairs 1 through 4 or 3 through With the bridge test enabled, enter successive values into register 105/1105 to test different device pairs without re-enabling the bridge test. 3. With the bridge test enabled, approximately the nominal bus voltage should be measured across each pair. PMI Regulator Operating Modes 3-5

28 Left Middle Right + Upper DC Bus U V W Lower Gate Driver Gate Driver Gate Driver Figure 3.3 Power Device Test Locations Step 7. Test the bridge by measuring the voltage across the power devices. The bridge test must be enabled and the appropriate value written to the Bridge Test Code register (105/1105) as described below. The value in the Bridge Test Code register specifies which power device pairs to turn on. The value corresponds to a bit pattern, with the bits described as follows: Bit 0: Phase U Upper Power Device Bit 1:Phase V Upper Power Device Bit 2:Phase W Upper Power Device Bit 3:Phase U Lower Power Device Bit 4:Phase V Lower Power Device Bit 5:Phase W Lower Power Device a. Connect the voltmeter to the output terminals U, V, W for the power devices being tested in accordance with table 3.2. b. Turn on power to the drive. c. Clear the Bridge Test Code register (105/1105, TST_CODE%). 3-6 Diagnostics, Troubleshooting, and Start-Up Guidelines

29 Step 8. Step 9. d. Enable the internal DC bus by setting the Bus Enable bit (bit 4 in register 100/1100, BUS_ENA@ ). A complete description of the DC bus pre-charge sequence can be found in the SA3100 Power Modules instruction manual, S e. The drive must pass all the interlock tests and the run permissive input (RPI) must be on. In addition, if it is configured during parameter entry, the MCR output must be turned on by the PMI Regulator to close the M-contactor. f. Set the Bridge Test Enable bit (bit 2 in register 100/100, BRG_TST@ ). The bridge test will remain enabled until the bit is reset by the programmer, a fault is detected, or the RPI input is turned off. g. Enter the proper power device value into register 105/1105, TST_CODE%. The voltmeter should read approximately nominal bus voltage for each power device pair. After testing one pair, turn off power to the drive. Wait five minutes to allow the DC bus voltage to dissipate. Repeat step 4. Select another power device pair and repeat step 7. Test the third power device pair in the same manner. If all the power device pairs have been tested successfully, and no faults have occurred, the test is complete. Reset the Bridge Test Enable bit. If testing a power device pair results in 0 or nearly 0V, both devices have failed. In this case, replace the two power devices. If the test results in more than 0V, but significantly less than nominal bus voltage, one of the two devices in the pair has failed. If testing a power device pair causes an instantaneous overcurrent fault or a bus overcurrent fault (reported in register 202/1202) then a power device has shorted. Note that you must set the Bridge Test Enable bit again to test any other device pairs. If one pair fails the test, you must test a second pair to determine which IGBT module to replace. The second test should include one of the two devices in the pair that failed. If this second pair fails the test, then the IGBT module containing the device that the two pairs have in common should be replaced. If this second pair passes the test, IGBT module containing the device that the two pairs do not have in common should be replaced. For example, if pair 1 in the table (U upper and V lower) fails the test, you could test pair 3 in the table (U upper and W lower) to determine which IGBT module should be replaced. If pair 3 fails, replace the IGBT module switching phase U. If pair 3 passes the test, then the problem is in the IGBT module switching phase V. Refer to the appropriate service manual, as listed in table 1.2, for instructions on replacing an IGBT module. After replacing the IGBT module, repeat this entire procedure beginning at step 1. Step 10. With the test completed, reconnect the motor to the Power Module output. Close and secure the Power Module s cabinet door or chassis cover. PMI Regulator Operating Modes 3-7

30 3.3 PMI Tuning Mode (Automatic Gain Calculation) The programmer sets the Enable Tuning bit (register 100/1100, bit 1, to request the PMI Regulator to calculate the values for the control algorithm. (Refer to the SA3100 Drive Configuration and Programming instruction manual, S3056, for a complete description of these variables.) Because the calculated values are used in the control algorithms, this procedure must be performed before the run mode is selected. In order for the PMI Regulator to perform these calculations, the interlock tests described in section 2.3 must have passed successfully. For the Volts per Hertz regulator, you can tune the characteristic curve by running the motor unloaded and monitoring motor current when going through the frequency range of interest. The curve should be modified to avoid excessive current consumption/transients when going through the frequency range of interest. When the PMI Regulator has completed the calculations (a process that takes less than one second), it will set the Automatic Tuning Complete bit (register 200/1200, bit 1, PMI_ATC@). The PMI Regulator will then return to the idle mode. Turn the Automatic Tuning Complete bit off. 3.4 Run Mode Before executing the run mode, perform the automatic gain calculation procedure (PMI tuning mode) as described in section 3.3. These gain values are used in the control algorithms. If the gain values are not calculated immediately before entering run mode, the motor may not run properly. Note that the Interlock tests do not check the gain values. To execute the run mode, the programmer sets the Enable PMI Loop bit (register 100/1100, bit 0, PMI_RUN@ ). Before the run mode can be executed, all of the following conditions are required: 1. The Interlock tests (described in section 2.3) must be passed successfully. 2. If configured, the M-contactor must be closed (refer to section ). 3. The DC bus must be ready (see section 2.5). 4. The UDC task in the AutoMax rack must be running. The status of the UDC task is indicated by the UDC Task Running bit (register 100/1100, bit 15,UDC_RUN@). If any of these requirements is not met or if a fault is latched in the Drive Fault register (202/1202), the PMI Regulator will remain in the idle mode. If these requirements are met, the PMI Regulator will execute the run command. At this time, the PMI Regulator will set bit 0 in register 200/1200 to indicate the run mode is active. 3-8 Diagnostics, Troubleshooting, and Start-Up Guidelines

31 The minor loop executes until one of the following occurs: The PMI Run Enable bit (register 100/1100, bit 0) is turned off by the application task. A drive fault is detected. Refer to Appendix A for a description of the Drive Fault register. The RPI signal (register 201/1201, bit 0) is removed. PMI Regulator Operating Modes 3-9

32 3-10 Diagnostics, Troubleshooting, and Start-Up Guidelines

33 CHAPTER 4 Installation and Start-Up Guidelines! ATTENTION:Only qualified personnel familiar with the construction and operation of this equipment and the hazards involved should install, adjust, operate, or service this equipment. Read and understand this manual and other applicable manuals in their entirety before proceeding. Failure to observe this precaution could result in severe bodily injury or loss of life. ATTENTION:The user is responsible for conforming with all applicable local, national, and international codes. Failure to observe this precaution could result in damage to, or destruction of, the equipment. This section describes general guidelines that should be followed when verifying the correct installation of the drive hardware and in performing the drive start-up. For more information regarding installation guidelines, refer to instruction manual D (Installing, Operating, and Maintaining Engineered Drive Systems). As part of the start-up procedure, the AutoMax Programming Executive software is used to verify the status of drive I/O and to make drive adjustments. Section 4.1 describes some of the restrictions imposed by the AutoMax Programming Executive software. 4.1 Using the AutoMax Programming Executive to Access the Rack The AutoMax Programming Executive enables four users to access and work in the same rack simultaneously. However, certain restrictions exist when more than one user is working in a rack. The maximum number of users is four (4) per rack (one user connected directly to the rack and three users connected via the DCS/AutoMax Network, or four users connected via the DCS/AutoMax Network). Data access is required for the user to Set/Force COMMON variables. All users must assure that variable values are not written over by other users working in the rack. Task access is required for the user to load a single task and to Set/Tune/Force LOCAL variables in a task. Only one user will be granted Task access for each task in the rack. Rack access is required to load the rack configuration and to load all application tasks (AutoMax tasks and UDC tasks). Installation and Start-Up Guidelines 4-1

34 If a user has Rack access, no other user can make changes in that rack. All other users will be limited to monitoring tasks and variables. Each user can monitor up to 16 COMMON and/or LOCAL variables. A maximum of 32 LOCAL variables per UDC module can be monitored, regardless of the number of users. A maximum of 16 variables per rack can be forced. Appendix G describes the type of access required by the user in order to carry out common Programming Executive operations. Refer to the AutoMax Programming Executive instruction manual for more specific information. 4.2 Environmental Requirements The installation must meet the following requirements: Ambient Temperature Open chassis: 0 to 50 C (32 to 122 F) Enclosed chassis: 0 to 40 C (32 to 104 F) Cooling Air for cooling must be of sufficient quality and flow to avoid recycling the heated exhaust air back into the drive air inlets. Relative humidity 5-95%, non-condensing Altitude 1000 meters (3300 feet) above sea level. Higher altitudes require derating. Air Quality Clean No flammable vapors, chemical fumes, or oil vapor. Clearances Must allow access to the equipment within the cabinets for inspection, maintenance, and replacement. Must provide non-restricted air flow to and from the intake and exhaust openings. See the SA3100 Power Modules instruction manual (S-3058) for more detailed information about installation requirements. 4-2 Diagnostics, Troubleshooting, and Start-Up Guidelines

35 4.3 Installing the Motor The AC motor should be installed in accordance with its own installation instructions. Refer to the instruction manual that was provided for the motor (in the Instruction Book) for specific instructions. 4.4 Installing the Drive The drive is supplied in its own enclosure or in an open-chassis configuration for mounting in a user-supplied enclosure, a motor control center (MCC), or other custom-built control room Enclosed Drives The drive is force ventilated by means of its own internal cooling fan(s). Air is drawn into the enclosure through slots in the cabinet bottom and in the lower portion of the cabinet sides. Air is forced out through internally shielded slots near the top of the cabinet sides. Air intake and exhaust openings are unfiltered Open Chassis Drives Where mounting of an open chassis drive within a user-supplied enclosure is desired, the user is responsible for ensuring that the maximum temperature within the enclosure remains at or below the rated ambient temperature under worst-case operating conditions. Note that the same fan-cooling as described in the previous section will be provided for the drive. 4.5 Wiring the Drive Make certain that the input power to the drive is of the correct voltage and sufficient amperage to support the drive s input current requirements. Note that input power current values must be less than the drive's maximum RMS fault current rating. Refer to the drive chassis and motor nameplates for correct current ratings and input power information. 4.6 Basic Drive Interconnections! ATTENTION:If your drive cabinet is mounted in such a way that the cabinet itself is not grounded, a ground wire must be connected to the drive cabinet to provide safety for personnel. Also the motor frame should be grounded by solidly connecting a ground wire to a screw in the conduit box. Failure to observe these precautions could result in severe bodily injury or loss of life. ATTENTION:The user is responsible for conforming with all applicable local, national, and international codes. Failure to observe this precaution could result in damage to, or destruction of, the equipment. The SA3100 drive requires interconnecting wiring per applicable codes between the drive and the following: input power, the motor, the operator s control station (if used), the resolver, and earth ground. Installation and Start-Up Guidelines 4-3

36 Refer to the Elementary Diagram (W/E) (and the Interconnection Diagram (W/I) if provided) supplied with your drive for these interconnections. Be sure that the W/E number corresponds to that on the drive s nameplate. All interconnecting wiring must be sized and installed in conformance with the National Electrical Code and applicable local or other codes. Unless a standard pre-built fiber-optic cable was included with your system, the fiber-optic cabling that links the UDC module(s) in the AutoMax rack with the PMI Regulator must be installed by someone experienced in installing fiber-optic cables. Unless you have in-house expertise in installing fiber-optic cable, it is recommended that you contact an experienced contractor to perform the installation. Information regarding the selection and installation of fiber-optic cabling is contained in the Distributed Power System Fiber-Optic Cabling instruction manual (S-3009). 4.7 Drive Inspection and Start-up Guidelines! ATTENTION:Only qualified personnel familiar with the construction and operation of this equipment and the hazards involved should install, adjust, operate, or service this equipment. Read and understand this manual and other applicable manuals in their entirety before proceeding. Failure to observe this precaution could result in severe bodily injury or loss of life. ATTENTION:This equipment is at line voltage when AC power is connected to the drive. Whenever power is removed, verify with a voltmeter that the DC bus capacitors are discharged before touching any internal parts of the drive. Failure to observe this precaution could result in severe bodily injury or loss of life. Use the procedures that follow to locate any shipping damage to the drive, to verify proper installation and field wiring, and to start the drive. Recommended Start-Up Sequence 1. Physical inspection of equipment 2. Motor checks 3. Preliminary inspection with power off 4. Inspection with power on 5. I/O verification Before attempting to perform this start-up procedure, you should be familiar with the general arrangement and function of the drive equipment and should verify that it has been installed and wired as described in the following documents, which are included in the Instruction Book provided with your drive system: Wiring Diagrams (W/Ds), Elementary Diagrams (W/Es), Panel Layout Diagrams (W/Ls), Operator's Station Diagrams (W/Os), and Interconnection Diagrams (W/Is) (if supplied) What To Do After Unexpected Test Results Note that if it is not possible to obtain the correct meter reading or proper operation during any of the checks or adjustment procedures described, perform the following steps: Step 1. Stop the drive. 4-4 Diagnostics, Troubleshooting, and Start-Up Guidelines

37 Step 2.! Step 3. Step 4. Step 5. Step 6. Turn off and lock out all incoming power. ATTENTION:DC bus capacitors retain hazardous voltages after input power has been disconnected. After disconnecting input power, wait five (5) minutes for the DC bus capacitors to discharge. Then check the voltage across the DC bus test points to ensure the bus capacitors are discharged before touching any internal components. Failure to observe this precaution could result in severe bodily injury or loss of life. Wait five minutes to allow the DC bus voltage to dissipate. Measure the DC bus potential with a voltmeter before working on the unit. Measure the voltage across the DC + and DC - terminals on terminal block TB1. See Appendix I for terminal block identification. When the DC bus potential is down to less than 5 volts, touch a 50 ohm, 50 W or larger resistor across the DC bus terminals for twenty seconds to allow any remaining voltage to dissipate. Remove the resistor and re-measure the DC bus potential. It should now be 0V. Verify the following: a. All connections are in strict conformance to the wiring diagrams. b. There are no loose or broken connections. c. There are no damaged components. Repeat the original test that failed Recommended Test Equipment Rockwell recommends the following test equipment: Isolated oscilloscope with a current probe and x100 probe for DC bus measurements. An isolation transformer is needed to isolate the oscilloscope and any other equipment. AC and DC clamp-on ammeters Multimeter having a sensitivity of 20KΩ/volt Chart recorder Isolated voltmeter 50 ohm, 50W resistor for discharging bus capacitors A megohmmeter (megger) may be used to reliably verify the absence of inadvertent grounding of the motor. Failure to follow proper procedure when using a megger may cause damage to the drive.! ATTENTION:If a megohmmeter is used, disconnect all leads between the rotating equipment and the drive cabinet. This will prevent damage to electronic circuitry (Power Modules and their associated circuits, etc.) due to the high voltage generated by the megger. Failure to observe this precaution could result in damage to, or destruction of, the equipment. Installation and Start-Up Guidelines 4-5

Distributed Power System SB3000 Synchronous Rectifier &RQILJXUDWLRQDQG3URJUDPPLQJ

Distributed Power System SB3000 Synchronous Rectifier &RQILJXUDWLRQDQG3URJUDPPLQJ Distributed Power System SB3000 Synchronous Rectifier &RQILJXUDWLRQDQG3URJUDPPLQJ Instruction Manual S-3034 Throughout this manual, the following notes are used to alert you to safety considerations:!

More information

Distributed Power System SA3100 Drive Configuration and Programming

Distributed Power System SA3100 Drive Configuration and Programming Distributed Power System SA3100 Drive Configuration and Programming Instruction Manual S-3056-1 Throughout this manual, the following notes are used to alert you to safety considerations:! ATTENTION: Identifies

More information

GV3000/SE 230 VAC 1-20 HP General Purpose (Volts/Hertz) and Vector Duty Drive Software Start-Up and Reference Manual Version 6.04

GV3000/SE 230 VAC 1-20 HP General Purpose (Volts/Hertz) and Vector Duty Drive Software Start-Up and Reference Manual Version 6.04 GV3000/SE 230 VAC 1-20 HP General Purpose (Volts/Hertz) and Vector Duty Drive Software Start-Up and Reference Manual Version 6.04 Instruction Manual D2-3387-4 The information in this manual is subject

More information

LiquiFlo AC General Purpose (Volts/Hertz) and Vector Duty Drive Software Start-Up and Reference Manual Version 6.4

LiquiFlo AC General Purpose (Volts/Hertz) and Vector Duty Drive Software Start-Up and Reference Manual Version 6.4 LiquiFlo AC General Purpose (Volts/Hertz) and Vector Duty Drive Software Start-Up and Reference Manual Version 6.4 Instruction Manual D2-3410-7 The information in this manual is subject to change without

More information

GV3000/SE Operator Interface Module (OIM) User Guide Version 2.0 M/N 2RK3000

GV3000/SE Operator Interface Module (OIM) User Guide Version 2.0 M/N 2RK3000 GV3000/SE Operator Interface Module (OIM) User Guide Version 2.0 M/N 2RK3000 Instruction Manual D2-3342-2 The information in this manual is subject to change without notice. Throughout this manual, the

More information

FlexPak 3000 Drive Operator Interface Module (OIM) User s Guide

FlexPak 3000 Drive Operator Interface Module (OIM) User s Guide FlexPak 3000 Drive Operator Interface Module (OIM) User s Guide Instruction Manual D2-3344 The information in this manual is subject to change without notice. Throughout this manual, the following notes

More information

1395 Node Adapter Board Troubleshooting

1395 Node Adapter Board Troubleshooting 1395 Node Adapter Board Troubleshooting Specifications Electrical: Board power provided by Drive (+5V) Discrete Input 24V DC or 115V AC, jumper selectable Environmental: Ambient Operating Temperature Storage

More information

GV3000/SE General Purpose (Volts/Hertz) and Vector Duty AC Drive, HP, 230V AC

GV3000/SE General Purpose (Volts/Hertz) and Vector Duty AC Drive, HP, 230V AC Software Start-Up and Reference Manual D2-3416-2 GV3000/SE General Purpose (Volts/Hertz) and Vector Duty AC Drive, 30-100 HP, 230V AC Version 6.04 Important User Information Solid-state equipment has operational

More information

Installation Instructions

Installation Instructions Installation Instructions (Catalog Number 1771-OD) This document provides information on: Because of the variety of uses for the products described in this publication, those responsible for the application

More information

SECTION VARIABLE FREQUENCY DRIVES

SECTION VARIABLE FREQUENCY DRIVES PART 1 GENERAL 1.01 DESCRIPTION This specification section establishes the requirements for variable frequency motor drives. The associated motor(s) shall be specified separate from the drive and listed

More information

Installation Instructions

Installation Instructions Installation Instructions Cat. No. 1771 P3, P4, P5 and P5E Use this document as a guide when installing the catalog number 1771-P3, -P4, -P5 or -P5E power supplies. Because of the variety of uses for the

More information

MDM 011-Z1 Regen Resistor

MDM 011-Z1 Regen Resistor MDM 011-Z1 Regen Resistor Date of creation: 10.04.2017 Version date: 10.04.2017 Article number: 09-402-011-Z1-E Publisher: SIGMATEK GmbH & Co KG A-5112 Lamprechtshausen Tel.: 06274/4321 Fax: 06274/4321-18

More information

Distributed Power System High Power SA3000 AC Power Modules

Distributed Power System High Power SA3000 AC Power Modules Distributed Power System High Power SA3000 AC Power Modules 850020 11xxx, 21xxx (534 Amp) 850020 12xxx, 22xxx (972 Amp) 850020 13xxx, 23xxx (1457 Amp) Instruction Manual S-3038 Throughout this manual,

More information

GV3000/SE AC Drive ControlNet Network Communication Option Board M/N 2CN3000

GV3000/SE AC Drive ControlNet Network Communication Option Board M/N 2CN3000 GV3000/SE AC Drive ControlNet Network Communication Option Board M/N 2CN3000 Instruction Manual D2-3390-2 The information in this manual is subject to change without notice. Throughout this manual, the

More information

User s Manual Pulse Encoder Interface Module OTAC-01

User s Manual Pulse Encoder Interface Module OTAC-01 Drive IT Low Voltage AC Drives User s Manual Pulse Encoder Interface Module OTAC-01 2 Safety WARNING! All electrical installation and maintenance work on the drive should be carried out by qualified electricians

More information

Digital ac/dc (24V) Input Module

Digital ac/dc (24V) Input Module Installation Instructions Digital ac/dc (24V) Input Module Catalog Number 1771-IND, Series C Topic Page Important User Information 2 Before You Begin 3 Power Requirements 3 Prevent Electrostatic Discharge

More information

User Guide Regenerative & Non-Regenerative Digital DC Drives 5 to 1000 HP

User Guide Regenerative & Non-Regenerative Digital DC Drives 5 to 1000 HP User Guide Regenerative & Non-Regenerative Digital DC Drives 5 to 1000 HP Quantum III The drive stop and start inputs should not be relied upon alone to ensure the safety of personnel. If a safety hazard

More information

User s Manual. ACS550-PD Stock 3R Irrigation Packaged Drive Supplement to ACS550-U1 User s Manual

User s Manual. ACS550-PD Stock 3R Irrigation Packaged Drive Supplement to ACS550-U1 User s Manual User s Manual ACS550-PD Stock 3R Irrigation Packaged Drive Supplement to ACS550-U1 User s Manual 2 ACS550-PD 3R Irrigation Packaged Drive ACS550 Drive Manuals GENERAL MANUALS ACS550-U1 User s Manual (1

More information

Analog Monitor Installation Manual

Analog Monitor Installation Manual Analog Monitor Installation Manual Part Number: 144-23919 Copyright 2011 Magnetek 1. Preface and Safety Magnetek manufactures products used as components in a wide variety of industrial systems and equipment.

More information

SECTION SOLID-STATE REDUCED VOLTAGE STARTERS

SECTION SOLID-STATE REDUCED VOLTAGE STARTERS SECTION 26 29 13.16 PART 1 - GENERAL 1.1 THE REQUIREMENT A. General: The CONTRACTOR shall provide solid-state reduced voltage motor starters, complete and operable, in accordance with the Contract Documents.

More information

User s Manual. ACS550-PD 3R Irrigation Packaged Drive Supplement to ACS550-U1 User s Manual

User s Manual. ACS550-PD 3R Irrigation Packaged Drive Supplement to ACS550-U1 User s Manual User s Manual ACS550-PD 3R Irrigation Packaged Drive Supplement to ACS550-U1 User s Manual 2 ACS550-PD 3R Irrigation Packaged Drive ACS550 Drive Manuals GENERAL MANUALS ACS550-U1 User s Manual (1 200 HP)

More information

Distributed Power System High Power SB3000 AC Power Modules (Rittal)

Distributed Power System High Power SB3000 AC Power Modules (Rittal) Distributed Power System High Power SB3000 AC Power Modules (Rittal) 804300-S (445 Amp) 804300-T (890 Amp) 804300-V (335 Amp) Instruction Manual S-303 Throughout this manual, the following notes are used

More information

Installing the Cisco AS5400XM Universal Gateway

Installing the Cisco AS5400XM Universal Gateway CHAPTER 3 Installing the Cisco AS5400XM Universal Gateway This chapter guides you through the installation of the Cisco AS5400XM universal gateway and includes the following sections: Setting Up the Chassis,

More information

Installation Instructions

Installation Instructions Installation Instructions Variable Frequency Drive (VFD) 7 ½ - 25 Ton Units with 2 Wire Control WARNING UNINTENDED EQUIPMENT OPERATION Modifying or changing parame eters whose function is not described

More information

Allen-Bradley 1397 AC Tachometer Interface Card

Allen-Bradley 1397 AC Tachometer Interface Card Instructions Allen-Bradley 1397 AC Tachometer Interface Card Cat. No. 1397-AC Contents Topic Page What This Option Provides 1 Where This Option Is Used 1 What These Instructions Contain 1 Specifications

More information

GV3000/SE AC Bookshelf Drive Hardware Reference, Installation, and Troubleshooting Version 6.06

GV3000/SE AC Bookshelf Drive Hardware Reference, Installation, and Troubleshooting Version 6.06 GV3000/SE AC Bookshelf Drive Hardware Reference, Installation, and Troubleshooting Version 6.06 Instruction Manual D2-3427-2 The information in this manual is subject to change without notice. Throughout

More information

Installation Instructions

Installation Instructions Installation Instructions (Cat. No. 1771-OBN Series B) Use this document as a guide when installing the catalog number 1771-OBN series B output module. Because of the variety of uses for the products described

More information

AutoMax Network Communication Option Board for use with GV3000/SE AC Drives M/N 2AX3000

AutoMax Network Communication Option Board for use with GV3000/SE AC Drives M/N 2AX3000 AutoMax Network Communication Option Board for use with GV3000/SE AC Drives M/N 2AX3000 Instruction Manual D2-3308-7 The information in this manual is subject to change without notice. Throughout this

More information

Vector Drive - Troubleshooting Guide

Vector Drive - Troubleshooting Guide Haas Technical Documentation Vector Drive - Troubleshooting Guide Scan code to get the latest version of this document Translation Available The Haas Vector drive is the source of power for the spindle

More information

Operating instructions AS-i SmartLine module AC3200 AC /00 06/2016

Operating instructions AS-i SmartLine module AC3200 AC /00 06/2016 Operating instructions AS-i SmartLine module AC3200 AC3201 80237876/00 06/2016 Contents 1 Preliminary note...3 1.1 Symbols used...3 1.2 Warnings used...3 2 Safety instructions...3 2.1 General...3 2.2 Target

More information

GV3000/SE AC Drive Hardware Reference, Installation, and Troubleshooting VAC Version 6.04

GV3000/SE AC Drive Hardware Reference, Installation, and Troubleshooting VAC Version 6.04 GV3000/SE AC Drive Hardware Reference, Installation, and Troubleshooting -20 HP @ 230 VAC Version 6.04 c Instruction Manual D2-3388-4 The information in this manual is subject to change without notice.

More information

Medium-Voltage Drive SINAMICS SM150. Type 6SL3845. Tests carried out on drives This documentation pertains to SM150 wassergekühlt G20 F03 F72 F79 F76

Medium-Voltage Drive SINAMICS SM150. Type 6SL3845. Tests carried out on drives This documentation pertains to SM150 wassergekühlt G20 F03 F72 F79 F76 Tests carried out on drives This documentation pertains to SM150 wassergekühlt G20 F03 F72 F79 F76 Reference Manual Medium-Voltage Drive SINAMICS SM150 Type 6SL3845 Edition 02/2019 www.siemens.com/drives

More information

GV3000/SE AC Drive HP, 230V AC

GV3000/SE AC Drive HP, 230V AC Hardware Reference, Installation, and Troubleshooting Manual D2-347-2 GV3000/SE AC Drive 30-00 HP, 230V AC Version 6.04 Important User Information Solid-state equipment has operational characteristics

More information

Analog Input Installation Manual

Analog Input Installation Manual Analog Input Installation Manual August 2011 Part Number: 144-23917 Copyright 2011 Magnetek 1. Preface and Safety Magnetek manufactures products used as components in a wide variety of industrial systems

More information

VLT 2800 DRIVE SPECIFICATIONS

VLT 2800 DRIVE SPECIFICATIONS VLT 2800 DRIVE SPECIFICATIONS Drive Input Power Input voltage 3 phase... 200 through 240, or 380 through 460; 3-phase all ratings 200 through 240, 1-phase through 2 HP Input voltage range for full output...

More information

460 to 230 Volt Conversion Kit for FlexPak 3000 or WebPak 3000 Drives

460 to 230 Volt Conversion Kit for FlexPak 3000 or WebPak 3000 Drives 460 to 230 Volt for FlexPak 3000 or WebPak 3000 Drives s: 916FK0100 and 916FK0200 Instruction Manual D2-3329-2! ATTENTION: Only qualified personnel familiar with the construction and operation of this

More information

4 Channel 4~20mA/0~10VDC Analog Data Fiber Link System

4 Channel 4~20mA/0~10VDC Analog Data Fiber Link System USER GUIDE RLH Industries, Inc. The leader in rugged fiber optic technology. U-022 2017A-0330 4 Channel 4~20mA/0~10VDC Analog Data Fiber Link System SYSTEM INSTALLATION INFORMATION Description The 4 Channel

More information

PCI 2 Axis Servo Card

PCI 2 Axis Servo Card Installation Instructions PCI 2 Axis Servo Card (Catalog Number 1784-PM02AE) This manual provides the instructions for installing the PCI 2 Axis Servo card (1784-PM02AE) in a PC computer using the NT operating

More information

ME3 Mobile Cabinet Three Phase Frequency Converter, Operation and Maintenence.

ME3 Mobile Cabinet Three Phase Frequency Converter, Operation and Maintenence. 29-30 Brunel Road, Churchfields Industrial Estate, St. Leonards-on-Sea East Sussex. TN38 9RT. United Kingdom Sales & Service : 01424 853 013 All Other Departments : 01424 853 464 Fax : 01424 852 268 magnuspower.sales@akersolutions.com

More information

Allen-Bradley. User Manual. PLC-5 Backup Communication Module (1785-BCM, 1785-BEM) product icon

Allen-Bradley. User Manual. PLC-5 Backup Communication Module (1785-BCM, 1785-BEM) product icon Allen-Bradley PLC-5 Backup Communication Module User Manual (1785-BCM, 1785-BEM) product icon Important User Information Because of the variety of uses for this product and because of the differences between

More information

SIRIUS CAPACITOR MODULE User Manual. Model number: A-1.7C-M-SD-G Version 1.0; Release Date: April 2018

SIRIUS CAPACITOR MODULE User Manual. Model number: A-1.7C-M-SD-G Version 1.0; Release Date: April 2018 SIRIUS CAPACITOR MODULE User Manual Model number: 3550-48-A-1.7C-M-SD-G Version 1.0; Release Date: April 2018 Introduction The Sirius Capacitor Module ( Sirius ) is supercapacitor-based storage that uses

More information

EOS-6000 Series Optical A/B Switch User Manual DC Version

EOS-6000 Series Optical A/B Switch User Manual DC Version EOS-6000 Series Optical A/B Switch User Manual DC Version For more information on this and other products: Contact Sales at EMCORE 626-293-3400, or visit www.emcore.com. Table of Contents Table of Contents...2

More information

Installation, Operation and Maintenance Manual

Installation, Operation and Maintenance Manual Document 481200 VGD-100 Vari-Green Drive Installation, Operation and Maintenance Manual Please read and save these instructions for future reference. Read carefully before attempting to assemble, install,

More information

GV3000/SE AC Drive Hardware Reference, Installation, and Troubleshooting Version 6.06

GV3000/SE AC Drive Hardware Reference, Installation, and Troubleshooting Version 6.06 GV3000/SE AC Drive Hardware Reference, Installation, and Troubleshooting Version 6.06 Instruction Manual D2-3360-5 The information in this manual is subject to change without notice. Throughout this manual,

More information

Resolver to Digital Expansion Board

Resolver to Digital Expansion Board Resolver to Digital Expansion Board Catalog No. EXB009A01 Installation and Operating Manual 6/98 MN1313 Table of Contents Section 1 General Information............................. 1-1 Introduction....................................

More information

User Manual VX4234 Digital Multimeter Module

User Manual VX4234 Digital Multimeter Module User Manual VX4234 Digital Multimeter Module 070-9139-02 This document applies for firmware version 1.00 and above. General Safety Summary Review the following safety precautions to avoid injury and

More information

Model HM-535 Power Supply Installation and Service Instructions

Model HM-535 Power Supply Installation and Service Instructions Model HM-535 Power Supply Installation and Service Instructions 430-535 0104 2004 Heritage MedCall, Inc SENTRY INSTALLATION & SERVICE INSTRUCTIONS POWER SUPPLY UNIT Model HM-535 IMPORTANT SAFETY INSTRUCTIONS

More information

INSTALLATION INSTRUCTIONS

INSTALLATION INSTRUCTIONS TT-568 /a INSTALLATION INSTRUCTIONS Original Issue Date: 2/ Model: 4/20RES and 4/20RESL Generator Sets Market: Residential/Commercial Subject: RDC and DC Controller Replacement Kits GM79884 and GM79885

More information

Installation Instructions

Installation Instructions Installation Instructions This document provides information on: important pre-installation considerations power supply requirements installing the module connecting the wiring using the indicators for

More information

Regenerative Power Module And Common Bus RPM Panels Instruction Manual

Regenerative Power Module And Common Bus RPM Panels Instruction Manual Regenerative Power Module And Common Bus RPM Panels Instruction Manual Part Number September 2010 Copyright 2010 Magnetek Material Handling PRODUCT MANUAL SAFETY INFORMATION Magnetek, Inc. (Magnetek)

More information

Operating instructions. Speed monitor D / / 2014

Operating instructions. Speed monitor D / / 2014 Operating instructions Speed monitor D200 80005257 / 00 05 / 2014 Contents 1 Preliminary note...4 1.1 Symbols used...4 1.2 Warning signs used...4 2 Safety instructions...5 2.1 General...5 2.2 Target group...5

More information

Symmetra PX 160. Maintenance Bypass Enclosure. Installation 05/

Symmetra PX 160. Maintenance Bypass Enclosure. Installation 05/ Symmetra PX 160 Maintenance Bypass Enclosure Installation 05/2014 www.schneider-electric.com Legal Information The Schneider Electric brand and any registered trademarks of Schneider Electric Industries

More information

SP500 AC Drive Installation and Operation Manual Version 3.1

SP500 AC Drive Installation and Operation Manual Version 3.1 SP500 AC Drive Installation and Operation Manual Version 3. Instruction Manual D2-3356-5 The information in this manual is subject to change without notice. Throughout this manual, the following notes

More information

ACCESS 9340/9360 Meter Input/Output Module

ACCESS 9340/9360 Meter Input/Output Module Installation Manual PMIM-IOMOD-0208 ACCESS 9340/9360 Meter Input/Output Module 9340-60-I/O2222 and 9340-60-I/O26 HAZARD CATEGORIES AND SPECIAL SYMBOLS Read these instructions carefully and look at the

More information

Mitsubishi Electric Automation Instruction Manual FR-A5AC-01

Mitsubishi Electric Automation Instruction Manual FR-A5AC-01 Mitsubishi Electric Automation Instruction Manual FR-A5AC-01 AC Input Interface Option Unit NOTE: CAUTION: WARNING: NOTES, CAUTIONS AND WARNINGS Notes are used to provide additional detail about a procedure.

More information

Installation and Operation Back-UPS BR1000G-IN / BR1500G-IN

Installation and Operation Back-UPS BR1000G-IN / BR1500G-IN Installation and Operation Back-UPS BR1000G-IN / BR1500G-IN Important Safety Information Read the instructions carefully to become familiar with the equipment before trying to install, operate, service

More information

270 MHz Control Modules

270 MHz Control Modules 2400 / 2420 / 2450 Performance Drives A D D E N D U M 270 MHz Control Modules Notices 2000.40(A2) 01 11/08 Copyright 2002-2008 by Unico, Incorporated. All rights reserved. No part of this publication may

More information

Converter SINAMICS G150. Type 6SL37102G

Converter SINAMICS G150. Type 6SL37102G Tests carried out on drives This documentation pertains to LV Umrichter E11 F72 F76 F79 L45 L50 L57 L68 M54 U11 Reference Manual Converter SINAMICS G150 Type 6SL37102G Edition 02/2019 www.siemens.com/drives

More information

High Performance Output Filter Instruction Manual

High Performance Output Filter Instruction Manual High Performance Output Filter Instruction Manual R TECHNOLOGY AND QUALITY ASSURANCE Since 1976 Zener Electric has supplied many thousands of drives to industry. These drives have been installed into numerous

More information

REV 01 DATE: February

REV 01 DATE: February REV 01 DATE: February 26 2018 Avid Controls Inc. 41261 Park 290 Drive, Waller, TX 77484, USA info@avidcontrolsinc.com (+1) (281) 640-8600 Page 1 of 26 Copyright 2018 Avid Controls Inc. DTS-01353-CUS-A-REV_01

More information

S66 Series Electronic Fan Speed Control

S66 Series Electronic Fan Speed Control FANs 121, 125, 1628.3 Product/Technical Bulletin S66 Issue Date 0918 S66 Series Electronic Fan Speed Control The S66 Series Electronic Fan Speed Control is designed to modulate the speed of single-phase,

More information

PowerFlex 400 AC Drive Guide Specification

PowerFlex 400 AC Drive Guide Specification PowerFlex 400 AC Drive Guide Specification Adjustable Frequency Drives with Bypass 3.0 50HP @ 208V AC 3.0 350HP @ 480V AC PART 1 GENERAL 1.01 Quality Assurance A. The manufacturer shall have minimum 5

More information

Power Over Fiber USER GUIDE. SYSTEM INSTALLATION INFORMATION Description. The leader in rugged fiber optic technology. RLH Industries, Inc.

Power Over Fiber USER GUIDE. SYSTEM INSTALLATION INFORMATION Description. The leader in rugged fiber optic technology. RLH Industries, Inc. USER GUIDE RLH Industries, Inc. The leader in rugged fiber optic technology. U-145 2018A-0119 Power Over Fiber SYSTEM INSTALLATI INFORMATI Description Our patented Power Over Fiber (PoF) system provides

More information

Super Remote Meter Interface (RMI) Board For Use With GV3000/SE and VTAC 7 Drives

Super Remote Meter Interface (RMI) Board For Use With GV3000/SE and VTAC 7 Drives Super Remote Meter Interface (RMI) Board For Use With GV3000/SE and VTAC 7 Drives M/N 2SI3000 M/N 2SI3000E Instruction Manual D2-3341-2 The information in this manual is subject to change without notice.

More information

GV3000/SE AC Drive 1-20 HP, 230V AC

GV3000/SE AC Drive 1-20 HP, 230V AC Hardware Reference, Installation, and Troubleshooting Manual D2-3388-5 GV3000/SE AC Drive - 20 HP, 230V AC Version 6.04 Important User Information Solid-state equipment has operational characteristics

More information

PCI 2 Axis Servo Card

PCI 2 Axis Servo Card Installation Instructions PCI 2 Axis Servo Card (Catalog Number 1784-PM02AE) This manual provides the instructions for installing the PCI 2 Axis Servo card (1784-PM02AE) in a PC computer using the NT operating

More information

Quantum III. Compact DC Drive Package. Slitter DC Drive Package. Quantum III

Quantum III. Compact DC Drive Package. Slitter DC Drive Package. Quantum III Compact DC Drive Package The delivers a DC drive package that integrates the intelligence of the Mentor II with a space saving design that incorporates many accessories typically required in the North

More information

MAINTENANCE MANUAL. EDACS REDUNDANT POWER SUPPLY SYSTEM 350A1441P1 and P2 POWER MODULE CHASSIS 350A1441P3, P4, AND P5 POWER MODULES TABLE OF CONTENTS

MAINTENANCE MANUAL. EDACS REDUNDANT POWER SUPPLY SYSTEM 350A1441P1 and P2 POWER MODULE CHASSIS 350A1441P3, P4, AND P5 POWER MODULES TABLE OF CONTENTS MAINTENANCE MANUAL EDACS REDUNDANT POWER SUPPLY SYSTEM 350A1441P1 and P2 POWER MODULE CHASSIS 350A1441P3, P4, AND P5 POWER MODULES TABLE OF CONTENTS SPECIFICATIONS*... 2 INTRODUCTION... 3 DESCRIPTION...

More information

E-Series Site Preparation Guide

E-Series Site Preparation Guide E-Series Site Preparation Guide September 2017 215-11797_A0 doccomments@netapp.com Table of Contents 3 Contents Deciding whether to use this guide... 10 Specifications of the model 3040 40U cabinet...

More information

WOODINVILLE, WA SUPERSTEP 2100 SERIES SEQUENCING PROPORTIONAL LOAD CONTROLLERS INSTALLATION & OPERATING MANUAL. Models: SLC2102-SLC2112

WOODINVILLE, WA SUPERSTEP 2100 SERIES SEQUENCING PROPORTIONAL LOAD CONTROLLERS INSTALLATION & OPERATING MANUAL. Models: SLC2102-SLC2112 SELECTRONIX, INC. WOODINVILLE, WA SUPERSTEP 2100 SERIES SEQUENCING PROPORTIONAL LOAD CONTROLLERS INSTALLATION & OPERATING MANUAL Models: SLC2102-SLC2112 SLC2102X-SLC2112X SLC2152-SLC2162 SLC2170-xx Relay

More information

5504 Thermocouple Analog Input Module

5504 Thermocouple Analog Input Module 550 Thermocouple Analog Input Installation, Operation and Maintenance Setup Manual 5/9/0 Safety Information The information provided in this documentation contains general descriptions and/or technical

More information

Operating instructions. Standstill monitor A / / 2011

Operating instructions. Standstill monitor A / / 2011 Operating instructions Standstill monitor A300 UK 1 2 3 4 5 6 7 8 7390337 / 01 02 / 2011 1 2 3 4 5 6 7 8 switchpoint min max pulse/min power Made in Germany ifm electronic gmbh D 45127 Essen func. I II

More information

PART 1: GENERAL PART 2: PRODUCT. Effective: 12/29/10 Page 1 of 6 FECA-TE-104D

PART 1: GENERAL PART 2: PRODUCT. Effective: 12/29/10 Page 1 of 6 FECA-TE-104D Specification Number: 23 09 33 Product Name: FRENIC-Eco AC Drives for Variable Torque Fan & Pump Applications (1-125Hp at 208/230V and 1-900Hp at 460V) PART 1: GENERAL 1.01 SUMMARY A. This specification

More information

Operating instructions. Switching amplifier DN0210 DN / / 2015

Operating instructions. Switching amplifier DN0210 DN / / 2015 Operating instructions Switching amplifier DN0210 DN0220 UK 80011079 / 00 01 / 2015 Contents 1 Preliminary note...4 1.1 Symbols used...4 1.2 Warning signs used...4 2 Safety instructions...5 2.1 General...5

More information

PowerFlex 40 Sample Specification

PowerFlex 40 Sample Specification PowerFlex 40 Sample Specification GENERAL REFERENCES REGULATORY REQUIREMENTS Designed to meet the following specifications: NFPA 70 - US National Electrical Code NEMA ICS 3.1 - Safety standards for Construction

More information

Models 2601B, 2602B, and 2604B System SourceMeter Instruments Quick Start Guide

Models 2601B, 2602B, and 2604B System SourceMeter Instruments Quick Start Guide Models 2601B, 2602B, and 2604B System SourceMeter Instruments Quick Start Guide Safety precautions Observe the following safety precautions before using this product and any associated instrumentation.

More information

LiquiFlo 2.0 AC Drive User Manual Version 1.4

LiquiFlo 2.0 AC Drive User Manual Version 1.4 LiquiFlo 2.0 AC Drive User Manual Version 1.4 Manufactured for The Trane Company Instruction Manual D2-3496 The information in this manual is subject to change without notice. Throughout this manual, the

More information

Flomatic Smart Card TM Model FDHC-100 (Digital High-Resolution Controller) Configuration and Operation Manual

Flomatic Smart Card TM Model FDHC-100 (Digital High-Resolution Controller) Configuration and Operation Manual The Flomatic FDHC-100 is a high performance Digital positioner intended to control AC actuators, providing 450 points of resolution with quarter turn actuators ranging from 2 sec to 120 sec and rated for

More information

AF-600 FP TM Fan & Pump Drive. (230V to 60HP, 460/575V to 125HP Operating Instructions

AF-600 FP TM Fan & Pump Drive. (230V to 60HP, 460/575V to 125HP Operating Instructions GE AF-600 FP TM Fan & Pump Drive (230V to 60HP, 460/575V to 125HP Operating Instructions Safety Safety WARNING HIGH VOLTAGE! Frequency converters contain high voltage when connected to AC mains input power.

More information

Line reactors SINAMICS. SINAMICS G120P Line reactors. Safety information 1. General. Mechanical installation 3. Electrical installation 4

Line reactors SINAMICS. SINAMICS G120P Line reactors. Safety information 1. General. Mechanical installation 3. Electrical installation 4 Safety information 1 General 2 SINAMICS SINAMICS G120P Mechanical installation 3 Electrical installation 4 Technical specifications 5 Operating Instructions Control version V4.6 11/2013 A5E32845290B AA

More information

Line reactors SINAMICS. SINAMICS G130 Line reactors. Safety information 1. General. Mechanical installation 3. Electrical installation

Line reactors SINAMICS. SINAMICS G130 Line reactors. Safety information 1. General. Mechanical installation 3. Electrical installation Safety information 1 General 2 SINAMICS SINAMICS G130 Mechanical installation 3 Electrical installation 4 Technical specifications 5 Operating Instructions Control version V4.7 04/2014 A5E00331462A Legal

More information

MODERNIZE YOUR DC CRANES. Convert Your DC Controls to State-of-the-Art Energy Efficient OmniPulse DDC Series 2 Drives

MODERNIZE YOUR DC CRANES. Convert Your DC Controls to State-of-the-Art Energy Efficient OmniPulse DDC Series 2 Drives TM MODERNIZE YOUR DC CRANES Convert Your DC Controls to State-of-the-Art Energy Efficient OmniPulse DDC Series 2 Drives Magnetek, the leader in digital power and motion control systems, brings you the

More information

User Manual. Solar Inverter for Water Pump

User Manual. Solar Inverter for Water Pump User Manual Solar Inverter for Water Pump SP Revival Series Version: 1.2 Table Of Contents ABOUT THIS MANUAL... 1 Purpose... 1 Scope... 1 SAFETY INSTRUCTIONS... 1 Inspection... 1 Installation... 1 Operation...

More information

INVERTER INSTRUCTION MANUAL. Relay output function. Plug-in option FR-A7AR PRE-OPERATION INSTRUCTIONS INSTALLATION AND WIRING RELAY OUTPUT

INVERTER INSTRUCTION MANUAL. Relay output function. Plug-in option FR-A7AR PRE-OPERATION INSTRUCTIONS INSTALLATION AND WIRING RELAY OUTPUT INVERTER Plug-in option FR-A7AR INSTRUCTION MANUAL Relay output function PRE-OPERATION INSTRUCTIONS INSTALLATION AND WIRING RELAY OUTPUT 1 2 3 Thank you for choosing this Mitsubishi Inverter plug-in option.

More information

Using a Guard Locking Interlock Switch and Light Curtains with DeviceNet Guard I/O and a GuardLogix Controller

Using a Guard Locking Interlock Switch and Light Curtains with DeviceNet Guard I/O and a GuardLogix Controller Safety Application Example Using a Guard Locking Interlock Switch and Light Curtains with DeviceNet Guard I/O and a GuardLogix Controller Safety Rating: Category 3, according to EN954-1 Introduction...

More information

AD-7830 Servo Amplifier

AD-7830 Servo Amplifier Instruction Manual IM-0606 AD-7830 Servo Amplifier Table of Contents General Information... 2 Introduction... 2 Receiving/Inspection... 2 Storage... 2 Equipment Return... 2 Abbreviations Used in This Manual...

More information

2.) Cabinet setup and preset data shall, as standard, be fully user programmable on a per cabinet or system wide basis.

2.) Cabinet setup and preset data shall, as standard, be fully user programmable on a per cabinet or system wide basis. A21 DIMMER CABINET SPECIFICATION. GENERAL. A.) Overview. 1.) The dimmer cabinets shall be fully digital, designed specifically for architectural and entertainment lighting applications, and shall consist

More information

Test Asset Optimization Services Power Line Utilization Module (PLUM) DATA SHEET

Test Asset Optimization Services Power Line Utilization Module (PLUM) DATA SHEET Test Asset Optimization Services Power Line Utilization Module (PLUM) DATA SHEET Description A Power Line Utilization Module (PLUM) is a device used to monitor the utilization and health parameters of

More information

Artisan Technology Group is your source for quality new and certified-used/pre-owned equipment

Artisan Technology Group is your source for quality new and certified-used/pre-owned equipment Artisan Technology Group is your source for quality new and certified-used/pre-owned equipment FAST SHIPPING AND DELIVERY TENS OF THOUSANDS OF IN-STOCK ITEMS EQUIPMENT DEMOS HUNDREDS OF MANUFACTURERS SUPPORTED

More information

Instruction Bulletin. ALTIVAR 58 Adjustable Speed Drive Controllers

Instruction Bulletin. ALTIVAR 58 Adjustable Speed Drive Controllers Instruction Bulletin 30072-450-01 August 1998 Raleigh, NC, USA ALTIVAR 58 Adjustable Speed Drive Controllers Installation Guide Type N Controllers DANGER HAZARDOUS VOLTAGE Read and understand this bulletin

More information

VLT Line Filter MCC 107 EMC Filter Series VLT Midi Drive FC 280 (K1 K3)

VLT Line Filter MCC 107 EMC Filter Series VLT Midi Drive FC 280 (K1 K3) These instructions provide technical and installation information for the MCC 107 EMC filter series. Only Danfoss qualified personnel is allowed to install this equipment. The personnel must be familiar

More information

3-Phase, Dual-Input 6-Slot Power Supply System STARTUP GUIDE

3-Phase, Dual-Input 6-Slot Power Supply System STARTUP GUIDE 3-Phase, Dual-Input 6-Slot Power Supply System STARTUP GUIDE -ST-01 Page 1 of 10 November 2016 2016 Copyright Lite-On Technology Corporation ALL RIGHTS RESERVED. Lite-On is a trademark of Lite-On Technology

More information

ABB Drives. User s Manual. Modbus Adapter Module RMBA-01

ABB Drives. User s Manual. Modbus Adapter Module RMBA-01 ABB Drives User s Manual Modbus Adapter Module RMBA-01 Modbus Adapter Module RMBA-01 User s Manual 3AFE 64498851 REV A EN EFFECTIVE: 1.3.2002 2002 ABB Oy. All Rights Reserved. Safety instructions Overview

More information

Model P4017 Single Channel USB Oscilloscope. Quick Start Guide

Model P4017 Single Channel USB Oscilloscope. Quick Start Guide Model P4017 Single Channel USB Oscilloscope Quick Start Guide General Warranty BNC warrants that the product will be free from defects in materials and workmanship for 3 years from the date of purchase

More information

CHAPTER MAINTENANCE AND TROUBLESHOOTING. In This Chapter... Maintenance and Inspection Troubleshooting...6 3

CHAPTER MAINTENANCE AND TROUBLESHOOTING. In This Chapter... Maintenance and Inspection Troubleshooting...6 3 CHAPTER MAINTENANCE AND 6 TROUBLESHOOTING In This Chapter... Maintenance and Inspection..........................6 2 Monthly Inspection...................................6 2 Annual Inspection....................................6

More information

Preparing to Install the VG248

Preparing to Install the VG248 CHAPTER 2 To ensure normal system operation, plan your site configuration and prepare your site before installation. Before installing the VG248, review these sections: Preparing the Installation Site,

More information

Innovative Circuit Technology Ltd.

Innovative Circuit Technology Ltd. Innovative Circuit Technology Ltd. Pro Series DC Power Supply INSTRUCTION MANUAL 855-343-001 Models: ICT690-12S/ICT690-12SB ICT690-24S/ICT690-24SB ICT690-48S/ICT690-48SB ICT1190-12S/ICT1190-12SB ICT1190-24S/ICT1190-24SB

More information

ELV12 Series. Instruction Manual

ELV12 Series. Instruction Manual Instruction Manual TDK-Lambda BEFORE USING POWER SUPPLY UNIT Be sure to read this instruction manual thoroughly before using this product. Pay attention to all warnings and cautions before using the unit.

More information

GuardLogix: Dual Zone Gate Protection with E-stop and Trojan Interlock Switch

GuardLogix: Dual Zone Gate Protection with E-stop and Trojan Interlock Switch Safety Application Example GuardLogix: Dual Zone Gate Protection with E-stop and Trojan Interlock Switch Safety Rating: PLd, Cat. 3 to EN ISO 13849.1 2008 Introduction... 2 Important User Information...

More information

Fitting Ah-ha to a machine using Gecko Stepper drives

Fitting Ah-ha to a machine using Gecko Stepper drives Fitting Ah-ha to a machine using Gecko Stepper drives Please note these instructions are for guidance. If you have any doubt on any particular point please check with us. If you have any difficulties in

More information