Safety relays 3TK2845 multifunction device

Size: px
Start display at page:

Download "Safety relays 3TK2845 multifunction device"

Transcription

1 Important notes Table of Contents Product description 1 Safety relays 3TK2845 multifunction device Functional information 2 Technical data 3 Mounting, wiring, commissioning 4 Manual Applications 5 3TK2890-0B Edition 07/2015 NEB /RS-AC/005 Last update: 09 July 2015

2 Safety Notices This manual contains information that you should observe to ensure your own personal safety and prevent material damage. The instructions for your personal safety are marked by a safety alert symbol. Instructions relating solely to material damage are not marked by a safety alert symbol. Depending on the degree of hazard, the warning information is shown as follows in decreasing sequence: Danger indicates that death or serious injury will result if proper precautions are not taken. Warning indicates that death or severe personal injury may result if proper precautions are not taken. Caution with a safety alert symbol indicates that minor personal injury can result if proper precautions are not taken. Caution indicates that property damage may result if proper precautions are not taken. Notice indicates that an undesirable event or state may arise if the relevant notes are not observed. In the event of a number of levels of danger occurring simultaneously, the warning corresponding to the highest level of danger is always used. A warning on a safety alert symbol indicating possible personal injury may also include a warning relating to material damage. Qualified personnel The product/system to which this documentation relates may only be used/operated by personnel qualified for the respective tasks, taking account of the appropriate documentation for those tasks, in particular, the safety and warning notices contained in the documentation. Qualified personnel are defined as persons who are able, thanks to their training and experience in handling these products/systems, to recognize risks and avoid potential hazards. Intended use Note the following: Warning Siemens products may only be used for the applications described in the catalog and the associated technical documentation. If third-party products or components are to be used, they must be recommended or approved by Siemens. To ensure trouble-free and safe operation of the products, they must be appropriately transported, stored, assembled, installed, commissioned, operated and maintained. The permissible environmental conditions must be maintained. The notes in the associated documentation must be complied with. Copyright Siemens AG 2007 All rights reserved The reproduction, transmission, or use of this document or its contents is not permitted without express written authority. Offenders will be liable for damages. All rights, including rights created by patent grant or registration of a utility model or design are reserved. Disclaimer of liability We have reviewed the contents of this publication to ensure consistency with the hardware and software described. Since variance cannot be precluded entirely, we cannot guarantee full consistency. The information in this publication is reviewed regularly and any necessary corrections are included in subsequent editions. We welcome any suggestions for improvement. Technical Assistance: Phone: +49 (911) (8-17 CET) Fax: +49 (911) technical-assistance@siemens.com Internet: SIEMENS AG Industry Sector P.O. Box 4848 D Nuremberg, Germany Siemens AG 2007 Technical data subject to change.

3 Table of Contents 1 Product description TK2845 multifunction device Function, properties Several safety functions combined in one enclosure Examples of using 3TK2845 modules TK2845 order numbers Functional information General Function description Symbol description Versions TK2845-.HB.. "Monitored and automatic start" TK2845-.DB.. "Monitored start" TK2845-.EB.. "Enabling button" TK2845-.FB.. "Spring force interlocked tumbler" TK2845-.GB.. "Magnetic force interlocked tumbler" Technical data Technical data Terminals Terminal assignment Dimensional drawings Mounting, wiring, commissioning Mounting and coding Wiring Meaning of the LED indicators Applications TK2845-.HB40 "Monitored start and automatic start", instantaneous outputs TK2845-.HB41 "Monitored start and automatic start", time-delayed outputs TK2845-.DB40 "Monitored startup", instantaneous outputs TK2845-.DB41 "Monitored start", time-delayed outputs TK2845-.EB40 "Enabling button" TK2845-.FB41/2/4 "Spring force interlocked tumbler" TK2845-.GB41/2/4 "Magnetic force interlocked tumbler" NEB /RS-AC/005 i

4 ii NEB /RS-AC/005

5 Important notes Important notes Purpose of the manual The information provided in this manual is intended to assist with the configuration of safety-oriented functions as part of an overall installation or machine. Target group This manual is aimed at people with the required qualifications to commission and operate the 3TK2845 multifunction device. Scope of validity This manual applies to multifunction devices with the following order numbers: 3TK2845-.HB40 *) 3TK2845-.HB41 *) 3TK2845-.HB42 *) 3TK2845-.HB44 *) 3TK2845-.DB40 *) 3TK2845-.DB41 *) 3TK2845-.DB42 *) 3TK2845-.DB44 *) 3TK2845-.EB40 *) 3TK2845-.EB41 *) 3TK2845-.EB42 *) 3TK2845-.EB44 *) 3TK2845-.FB41 *) 3TK2845-.FB42 *) 3TK2845-.FB44 *) 3TK2845-.GB41 *) 3TK2845-.GB42 *) 3TK2845-.GB44 *) *) 8th position in order no.: 1 = screw terminal, 2 = spring-loaded terminal Shutdown response to power failure / device failure: On all 3TK28 devices, safety integrity level SIL CL 3 refers to the outputs with stop category 0. The time-delayed outputs are redundantly configured but cannot guarantee the set time in case of a failure (e.g. loss of power supply, device failure). These devices enter the safe state in the event of a failure, which always means that the outputs go to "zero" in this case. NEB /RS-AC/005 iii

6 Important notes Standards and approvals You can use the 3TK2845 safety relays in EMERGENCY-STOP facilities complying with ISO ( ) and in safety circuits complying with EN ( ), e.g. for moving covers and protective doors or contactless protective equipment conforming to IEC ( ). Depending on the external wiring, PL e in accordance with DIN EN ISO ( ) or SIL CL 3 in accordance with IEC 62061:2005 ( ) must be achieved. Installation note Measures to be taken to improve immunity to conducted radiofrequency interference: o Spatial separation of sensitive circuits from interference sources o Use of twisted-conductor cables o Sufficient distance between conductors emitting interference and the conductors of sensitive circuits o Right-angled crossing of cables and conductors where possible o Routing of the conductors as close as possible to the ground plane o Use of electrostatic / electromagnetic shields Disclaimer of liability The products described here have been developed to carry out safety-oriented functions as part of a complete plant or machine. A complete safety-oriented system generally features sensors, evaluation units, signaling units, and reliable shutdown concepts. It is the responsibility of the manufacturer to ensure that a system or machine is functioning properly as a whole. Siemens AG, its regional offices, and associated companies (hereinafter referred to as "Siemens") cannot guarantee all the properties of an entire plant, system or machine that has not been designed by Siemens. Nor can Siemens assume liability for recommendations that appear or are implied in the following description. No new guarantee, warranty, or liability claims above those standard to Siemens can be derived from the following description. Up-to-the-minute information You can obtain further assistance by calling the following numbers: Technical Assistance: Phone: +49 (911) (8-17 CET) Fax: +49 (911) or on the Internet at: technical-assistance@siemens.com Internet: SIEMENS AG, Technical Assistance Breslauer Str. 5 D Fuerth, Germany Correction sheet A correction sheet is included at the end of this manual. Please use it to enter your suggestions for improvements, additions and corrections, and send it back to us. This will help us to improve the next edition of the manual. iv NEB /RS-AC/005

7 Product description 1 Chapter Subject Page 1.1 3TK2845 multifunction device Function, properties TK2845 order numbers 1-7 NEB /RS-AC/

8 Product description 1.1 3TK2845 multifunction device Fig. 1-1: Illustration of the device version with screw connection, instantaneous enabling circuit Fig. 1-2: Illustration of the device version with spring-loaded terminals, delayed enabling circuits 1-2 NEB /RS-AC/005

9 Product description 1.2 Function, properties The 3TK2845 multifunction device is used to implement safety-related functions such as EMERGENCY-STOP monitoring, protective door monitoring and monitoring functions using contactless protective equipment (ESPE) such as light curtains and safety shutdown mats in machines with movable components. The device is especially suited for: Use on machines that operate without an interface to a bus system (stand-alone operation) Use on machines requiring several protection functions (e.g. EMERGENCY-STOP and a protective door, enabling button and protective door and locked protective door tumblers) Use on machines having components which must be switched off during operation (e.g. for servicing) The advantage of using this device is the fact that several safety-related functions can be implemented using only one 3TK2845 multifunction device rather than using several safety relays. In addition, the device is also suited for operational switching, cascading and adding safety relays either using contacts or switching electronically. Note: Under the link "Simulation safety switching device 3TK2845", you will find a simulation of the devices that will illustrate the functionality for you. NEB /RS-AC/

10 Product description Several safety functions combined in one enclosure Conventional design Until now, common combinations of safety applications such as EMERGENCY- STOP and protective door monitoring could only be implemented by using several individual safety relays (as in the example shown; Fig. 1-3). Fig. 1-3: Versions: 3TK2841 One safety relay required per safety function 1-4 NEB /RS-AC/005

11 Product description Configuration with 3TK2845 Multifunction devices of the 3TK2845 series combine several functions in one device. These devices are suitable for monitoring up to two safe 2-channel sensors and 1 safe 1-channel sensor (cascading input) and they also offer you the option of connecting a mode switch. Two solid-state enabling circuits and two relay enabling circuits ensure safe shutdown here. Fig. 1-4: Versions: 3TK2845 EMERGENCY-STOP and protective door monitoring + key-operated switch for bridging the protective door in maintenance mode NEB /RS-AC/

12 Product description Examples of using 3TK2845 modules Monitoring of EMERGENCY-STOP and positioning switches with possible maintenance for intervening in a secured area. Monitoring of position switches and possible operation using an enabling button in "unsafe" mode (maintenance). 1-6 NEB /RS-AC/005

13 Product description 1.3 3TK2845 order numbers Monitored and automatic start Screw terminal Spring-loeaded terminal Time delay 3TK2845-1HB40 3TK2845-2HB40 instantaneous 3TK2845-1HB41 3TK2845-2HB41 time-delayed s 3TK2845-1HB42 3TK2845-2HB42 time-delayed s 3TK2845-1HB44 3TK2845-2HB44 time-delayed s Monitored start Screw terminal Spring-loaded terminal Time delay 3TK2845-1DB40 3TK2845-2DB40 instantaneous 3TK2845-1DB41 3TK2845-2DB41 time-delayed s 3TK2845-1DB42 3TK2845-2DB42 time-delayed s 3TK2845-1DB44 3TK2845-2DB44 time-delayed s Enabling button Screw terminal Spring-loaded terminal Time delay 3TK2845-1EB40 3TK2845-2EB40 instantaneous 3TK2845-1EB41 3TK2845-2EB41 time-delayed s 3TK2845-1EB42 3TK2845-2EB42 time-delayed s 3TK2845-1EB44 3TK2845-2EB44 time-delayed s Spring force interlocked tumblers Screw terminal Spring-loaded terminal Time delay 3TK2845-1FB41 3TK2845-2FB41 time-delayed s 3TK2845-1FB42 3TK2845-2FB42 time-delayed s 3TK2845-1FB44 3TK2845-2FB44 time-delayed s Magnetic force interlocked tumblers Screw terminal Spring-loaded terminal Time delay 3TK2845-1GB41 3TK2845-2GB41 time-delayed s 3TK2845-1GB42 3TK2845-2GB42 time-delayed s 3TK2845-1GB44 3TK2845-2GB44 time-delayed s NEB /RS-AC/

14 Product description 1-8 NEB /RS-AC/005

15 Functional information 2 Chapter Subject Page 2.1 General Function description Symbol description Versions TK2845-.HB.. "Monitored and automatic start" TK2845-.DB.. "Monitored start" TK2845-.EB.. "Enabling button" TK2845-.FB.. "Spring force interlocked tumbler" TK2845-.GB.. "Magnetic force interlocked tumbler" 2-24 NEB /RS-AC/

16 Functional information 2.1 General SIRIUS safety relays and the safety chain A safety chain generally consists of the functions detection, evaluation and switching-off. Detection: This means the sensing of a safety requirement, e.g. when an EMERGENCY-STOP facility is actuated or a hazardous area protected by sensors such as light arrays or laser scanners is entered. Evaluation: This means the detection of a safety requirement and the safe initiation of the reaction (e.g. switching-off of the enabling circuits). This means the monitoring of the correct functioning of the actuator and the sensor. Switching-off: This means the switching-off of the hazard (e.g. of a power supply via the downstream contactors). SIRIUS safety relays play a role in the evaluation and reaction part of this safety chain. The safety functions are shown in a uniform schematic diagram (refer to Chapter 2.2) for a quick overview of the special functions of the individual device types. The sensor interface inputs, the actuator interface outputs and enabling circuits, as well as the special safety logic can all be seen at a glance. Cascading input 1. Safe linking of safety relays In this application a higher-level safety relay switches off the 3TK2845 via a safe output and the cascading input. Example: A -- higher-level -- EMERGENCY-STOP circuit must switch off the whole system. Several lower-level functional groups (e.g. protective doors) with local switch-off can be operated. Notice When faults are ruled out (protected laying of the control lead), the application's safety category corresponds to that of the higher-level safety relay. 2. Additional safety sensor circuit The cascading input is AND-connected with the sensor inputs Y12, Y22. PL c according to EN ISO , or SIL CL 2 according to IEC can be achieved when the cascading input is wired to single-channel safety sensors (positive opening) and the routing of the connecting cable is protected. The start function is set to automatic start. Cascading input 1 can be switched with floating or solid-state switching elements. Both types of switching elements must be fed by the same power supply as the device. 2-2 NEB /RS-AC/005

17 Functional information 3. Operational switching The cascading input can be used for operational (non-safe) switching. Switching is possible with floating or solid-state switching elements. Floating switching elements must be fed by the same power supply as the device. 4. Initial device start 4.1 Cross-circuit detection: o If a voltage of + 24 V DC is applied at Y35, cross-circuit evaluation between Y11/Y12 and Y21/Y22 is deactivated (necessary for non-floating sensors, e.g. light barriers). o If a voltage of + 24 V DC is applied at Y65, cross-circuit evaluation between Y41/Y42 and Y51/Y52 is deactivated (necessary for non-floating sensors, e.g. light barriers). o If no voltage is applied at Y35 or Y65, cross-circuit detection is active (necessary for pressure sensitive mats according to the cross-circuit principle, and non-floating sensors, e.g. EMERGENCY-STOP). Note: If 1-channel sensors are used, Y35 (in the case of 1-channel sensor on Y12 or Y22 or Y65 (in the case of 1-channel sensor on Y42 or Y52)) must be supplied with a voltage of +24 V DC. Note: If a pressure sensitive mat is used, it MUST be wired before switching on the device. Otherwise, the device will not detect the pressure sensitive mat, and a device fault will occur when the pressure sensitive mats are actuated. 5. Switch-on conditions o Voltage present at A1/A2. o Sensor circuit Y12/Y22 closed (exception in the case of variant 3TK2845-.EB4.). o Sensor circuit Y42/Y52 closed (exceptions during maintenance). o Cascading input supplied with 24 V DC. o Feedback circuit closed (supplied with 24 V DC). o An ON signal at Y34 is required for monitored start. For the safe monitoring of device function, sensors and actuators, the state of all input variables must remain unchanged for at least 400 ms after the 3TK2845 outputs drop out. If, for example, a sensor circuit is closed during this time, a device fault occurs that can only be remedied by resetting the supply voltage. NEB /RS-AC/

18 Functional information 6. Monitoring the ON button o Both the positive and negative signal change are monitored on the ON button. o If the ON button is pressed for longer than 5s, the ON command is rejected in the device and the device does NOT start when the ON button is released! o Monitored start requires status "1" at input Y34 as the start condition. When this condition is fulfilled, the safe outputs become active, that is, they are set to "1" (depending on the device version). The start signal at input Y34 is only valid when the following applies: - The time sequence of the START signal corresponds to the values " ". - The value "1" must be present for 0.2 to 5 s. 7. Use of a 1-channel sensor connection on Y11/12, Y21/22, or Y41/42, Y51/52 o If a single-channel sensor is to be connected to one of the two 2-channel sensor inputs, cross-circuit detection must be deactivated for this sensor circuit. The single-channel sensor must be supplied with an external + 24 V DC signal in this case. o If a single-channel sensor is desired at sensor input Y11/12, Y21/22, terminal Y35 must also be supplied with + 24 V DC o If a single-channel sensor is desired at sensor input Y41/42, Y51/52, terminal Y65 must also be supplied with + 24 V DC. 8. Monitoring the feedback circuits External actuators such as contactors or pneumatic valves are monitored with the feedback circuit. o The feedback circuit is tested for correct functioning when all enabling circuits are switched off (must be closed within 200 ms after switching off the enabling circuits). If the feedback circuit remains open after opening the enabling circuits, the device assumes a fault state (LED 24 & 44 flash). It must not be possible to switch the device on in this state. o An ON command is not accepted during a fault in the feedback circuit. o If the fault in the feedback circuit is corrected, the device can be started again as normal. o If an actuator with feedback is not used, feedback input Y64 must be supplied with 24 V DC. 2-4 NEB /RS-AC/005

19 Functional information Function description Automatic sensor detection Sensors such as EMERGENCY-STOP control devices or position switches and safety shutdown mats have different modes of operation. While EMERGENCY-STOP control devices, for example, interrupt the sensor circuit when activated, safety shutdown mats establish a cross-circuit between the two input channels of the evaluation system when stepped on. This means that 1. in the case of a sensor which interrupts the sensor circuit, a cross-circuit leads to a fault. 2. in the case of safety shutdown mats an interruption of the sensor circuit leads to a fault. All safety shutdown mats and switching strips operating in a 4-wire configuration that work in accordance with the principle of cross-circuit tripping can be connected to the 3TK2845 safety relay. The tripping of the 3TK2845 is initiated by a cross-circuit in the sensor cables. If the safety shutdown mat resistance is < 1000 Ω for the mat + the connecting leads, safe evaluation is performed in accordance with DIN EN and DIN EN The 3TK2845 automatically detects the mode of operation of the connected sensor. If, during first activation of the sensor after a device restart, 1. opening of the sensor circuits is detected, the 3TK2845 only accepts sensors which open the sensor circuits (floating NC contacts such as EMERGENCY-STOP control devices or position switches). A cross-circuit between the sensor circuits leads to a fault. 2. a cross-circuit is detected between the sensor circuits, the 3TK2845 only accepts sensors causing a sensor circuit short-circuit (safety shutdown mats). Opening of the sensor circuits leads to a fault. NEB /RS-AC/

20 Functional information Symbol description Explanation of symbols Symbol Meaning START button EMERGENCY-STOP Protective door Enabling button Light curtain, light array, light barrier Safety shutdown mat Cross-circuit monitoring Feedback circuit Key-operated switch Table 2-1: Explanation of symbols 2-6 NEB /RS-AC/005

21 Functional information 2.2 Versions TK2845-.HB.. "Monitored and automatic start" The 3TK2845-.HB.. has two sensor inputs (Y11/12; Y21/22) with monitored start, (Y41/42; Y51/52 with automatic start), one cascading input (1, with automatic start) as well as one switching input (key-operated switch). On the output side there are two relay and two enabling circuits and two solid-state enabling circuits as well as one solid-state signaling output. Standard operation In standard operation (key-operated switch "OFF") all enabling circuits are activated. All input blocks are AND-connected to one another and affect all enabling circuits at the same time. Some are time-delayed (in the versions: 3TK2845-.HB41; -.HB42; -.HB44). Maintenance During maintenance (key-operated switch "ON") only two of the four enabling circuits are activated. In this case, sensor input Y42/Y52 (e.g. protective door) has no function. The hazardous area can be entered since the dangerous motion has been switched off via the two inactive enabling circuits. The sensor input Y12/Y22 and the cascading input (1, with automatic start) still affect the active enabling circuits. Monitored start is required: o At initial start after applying the control supply voltage. o After opening and closing sensor circuits Y12/Y22 (even if this is followed by deactivation and reactivation of cascading!) Automatic start takes place: o After closing sensor circuits Y42/Y52 (following "standard operation") o After activation of the cascading input (not on first switching on the device AND after opening and closing of the sensor on Y12/Y22). o After exiting maintenance mode (not if the sensor on Y12/Y22 has been actuated!) NEB /RS-AC/

22 Functional information Outputs: o Standard operation (Y72/Y82 at 0 V): All enabling circuits (13/14, 24, 33/34, 44 or 13/14, 24, 37/38, 48 with the time-delayed versions 3TK2845-.HB41; -.HB42; -.HB44), some time-delayed, switch on with the Start command or on closing of sensor circuit Y42/Y52 (automatic start, if Y12/Y22 was not opened). All enabling circuits are deactivated by actuating a sensor Signaling circuit 52 always switches inversely to the enabling circuits o Maintenance (Y72/Y82 at 24 V DC): If sensor circuit Y12/Y22 or the cascading input (1, with automatic start) is opened during maintenance, all enabling circuits switch off, and signaling circuit 52 is active. Starting maintenance mode from the idle condition: Enabling circuits 13/14 and 24 (13/14 and 48 with the time-delayed versions) switch on with the Start command (if all other switch-on conditions are met at the same time). Enabling circuits 13/14 and 24 switch on when the key-operated switch is actuated (24 V DC at Y72/Y82) regardless of the status at input Y42/Y52 (if the sensor at Y42/Y52 was the only cause of switching off). Signaling circuit 52 pulses with a frequency of 1.2 Hz. Starting maintenance from standard operation (all enabling circuits active). Enabling circuits 33/34 and 44 switch off when maintenance mode is selected, but enabling circuits 13/14 and 24 remain active. Signaling circuit 52 pulses with a frequency of 1.2 Hz. 2-8 NEB /RS-AC/005

23 Functional information Status diagrams Standard Normalbetrieb operation Maintenance Servicebetrieb Standard Normalbetrieb operation Y34 Inputs Eingänge 1 Y12/22 Y42/52 Changeover Umschaltung from Normal- standard / operation Servicebetrieb to maintenance - Y72/82 13/14 Outputs Ausgänge 24 33/ Fig. 2-1: Status diagram: 3TK2845-.HB40 Standard Normalbetrieb operation Maintenance Servicebetrieb Y34 Inputs Eingänge 1 Y12/22 Y42/52 Changeover Umschaltung from Normal- standard / operation Servicebetrieb to maintenance Y72/82 13/14 Outputs Ausgänge 24 37/ t v tv tv tv tv tv Fig. 2-2: Status diagram: 3TK2845-.HB41 NEB /RS-AC/

24 Functional information Connections: Monitored and automatic start instantaneous Inputs (sensors) Outputs (enabling circuit) Sensor Terminals Description Description Terminals 1 Cascading Safe relay output instantaneous or or Y11 Y12 Y21 Y22 Sensor connection Safe solid-state output instantaneous 240 or Y34 START button Y35 refers to Y11/Y12, Y21/Y22 - with cross-circuit detection (not connected) - without cross-circuit detection (with 24V DC = terminal A1 connected) Safe relay output instantaneous or or Y41 Y42 Y51 Y52 Sensor connection Safe solid-state output instantaneous 44 Y65 refers to Y41/Y42, Y51/Y52 Y72 Y82 - with cross-circuit detection (not connected) - without cross-circuit detection (with 24V DC = terminal A1 connected) Key-operated switch Solid-state signaling output 1) (must not be used for safety-related applications) 52 Y64 External device monitoring circuit 1) Solid-state signaling output Enabling circuits active: Enabling circuits inactive: Key-operated switch operation: Signaling output OFF Signaling output ON Signaling output clocked (approx. 1.2 Hz) 2-10 NEB /RS-AC/005

25 Functional information Connections: Monitored and automatic start, time-delayed Inputs (sensors) Outputs (enabling circuit) Sensor Terminals Description Description Terminals 1 Cascading Safe relay output instantaneous or or Y11 Y12 Y21 Y22 Sensor connection Safe solid-state output instantaneous 24 or Y34 START button Y35 refers to Y11/Y12, Y21/Y22 - with cross-circuit detection (not connected) - without cross-circuit detection (with 24V DC = terminal A1 connected) Safe relay output time-delayed or or Y41 Y42 Y51 Y52 Sensor connection Safe solid-state output time-delayed 48 Y65 refers to Y41/Y42, Y51/Y52 Y72 Y82 - with cross-circuit detection (not connected) - without cross-circuit detection (with 24V DC = terminal A1 connected) Key-operated switch Solid-state signaling output 1) (must not be used for safety-related applications) 52 Y64 External device monitoring circuit 1) Solid-state signaling output Enabling circuits active: Enabling circuits inactive: Key-operated switch operation: Signaling output OFF Signaling output ON Signaling output clocked (approx. 1.2 Hz) NEB /RS-AC/

26 Functional information TK2845-.DB.. "Monitored start" The 3TK2845-.DB.. has two sensor inputs (Y42/Y52, Y12/Y22 with monitored start), one cascading input (1, with automatic start) as well as one switching input (key-operated switch). On the output side there are two relay and two enabling circuits and two solid-state enabling circuits as well as one solid-state signaling output. Standard operation In standard operation (key-operated switch "OFF") all enabling circuits are activated. All input blocks are AND-connected to one another and affect all enabling circuits at the same time. Some are time-delayed (in the versions: 3TK2845-.DB41; -.DB42; -.DB44). Maintenance During maintenance (key-operated switch "ON") only two of the four enabling circuits are activated. In this case, sensor input Y42/Y52 (e.g. protective door) has no function. The hazardous area can be entered since the dangerous motion has been switched off via the two inactive enabling circuits. The sensor input Y12/Y22 and the cascading input (1, with automatic start) still affect the active enabling circuits. A monitored start is required: o At initial start of the device. o After opening one or both sensor circuits (Y12/Y22 or Y42/Y52). o After exiting maintenance mode, if the protective door has been opened. Automatic start takes place if: o Cascading input 1 (if no Y12/Y22 or Y42/Y52 sensor has been actuated previously). o Service switch Y72/Y82 (if the protective door has not been opened during maintenance). Outputs: o Standard operation (Y72/Y82 at 0 V): All enabling circuits (13/14, 24, 33/34, 44; or 13/14, 24, 37/38, 48 with the time-delayed versions 3TK2845-.DB41; -.DB42; -.DB44), some time-delayed, switch on with the Start command. All enabling circuits are deactivated by actuating a sensor. Signaling circuit 52 always switches inversely to the enabling circuits. o Maintenance (Y72/Y82 at 24 V DC): If sensor circuit Y12/Y22 or the cascading input (1, with automatic start) is opened during maintenance, all enabling circuits switch off, and signaling circuit 52 is active. Starting maintenance mode from the idle condition: Enabling circuits 13/14 and 24 (13/ and 48 with the time-delayed versions) switch on with the Start command regardless of the status at sensor input Y42/Y52 (if all other switch-on conditions are met at the same time). Signaling circuit 52 pulses with a frequency of 1.2 Hz. Starting maintenance from standard operation (all enabling circuits active) Enabling circuits 33/44 and 44 switch off when maintenance mode Y72/Y82 is selected, but enabling circuits 13/14 and 24 remain active. Signaling circuit 52 pulses with a frequency of 1.2 Hz NEB /RS-AC/005

27 Functional information Status diagrams Standard Normalbetrieb operation Maintenance Servicebetrieb Standard Normalbetrieb operation Y 34 Inputs Eingänge 1 Y 12/22 Y 42/52 Changeover Umschaltung from Normal- standard / Servicebetrieb operation to maintenance - Y 72/82 13/14 Outputs Ausgänge 24 33/ Fig. 2-3: Status diagram: 3TK2845-.DB40 Y34 Inputs Eingänge 1 Y12/22 Y42/52 Y72/82 13/14 Outputs Ausgänge 24 37/ t v t v t v Fig. 2-4: Status diagram: 3TK2845-.DB41 NEB /RS-AC/

28 Functional information Inputs (sensors) Connections: Monitored start instantaneous Outputs (enabling circuit) Sensor Terminals Description Description Terminals 1 Cascading Safe relay output instantaneous or or Y11 Y12 Y21 Y22 Sensor connection Safe solid-state output instantaneous 24 or Y34 START button Y35 refers to Y11/Y12, Y21/Y22 - with cross-circuit detection (not connected) - without cross-circuit detection (with 24V DC = terminal A1 connected) Safe relay output instantaneous or or Y41 Y42 Y51 Y52 Sensor connection Safe solid-state output instantaneous 44 Y65 refers to Y41/Y42, Y51/Y52 Y72 Y82 - with cross-circuit detection (not connected) - without cross-circuit detection (with 24V DC = terminal A1 connected) Key-operated switch Solid-state signaling output 1) (must not be used for safety-related applications) 52 Y64 External device monitoring circuit 1) Solid-state signaling output Enabling circuits active: Enabling circuits inactive: Key-operated switch operation: Signaling output OFF Signaling output ON Signaling output clocked (approx. 1.2 Hz) 2-14 NEB /RS-AC/005

29 Functional information Connections: Monitored start time-delayed Inputs (sensors) Outputs (enabling circuit) Sensor Terminals Description Description Terminals 1 Cascading Safe relay output instantaneous or or Y11 Y12 Y21 Y22 Sensor connection Safe solid-state output instantaneous 24 or Y34 START button Y35 refers to Y11/Y12, Y21/Y22 - with cross-circuit detection (not connected) - without cross-circuit detection (with 24V DC = terminal A1 connected) Safe relay output time-delayed or or Y41 Y42 Y51 Y52 Sensor connection Safe solid-state output time-delayed 48 Y65 refers to Y41/Y42, Y51/Y52 Y72 Y82 - with cross-circuit detection (not connected) - without cross-circuit detection (with 24V DC = terminal A1 connected) Key-operated switch Solid-state signaling output 1) (must not be used for safety-related applications) 52 Y64 External device monitoring circuit 1) Solid-state signaling output Enabling circuits active: Enabling circuits inactive: Key-operated switch operation: Signaling output OFF Signaling output ON Signaling output clocked (approx. 1.2 Hz) NEB /RS-AC/

30 Functional information TK2845-.EB.. "Enabling button" The 3TK2845-.EB.. has two sensor inputs (Y12/Y22 enabling button with automatic start, Y42/Y52 protective door with monitored start/automatic start), one cascading input (1, with automatic start) as well as one switching input (key-operated switch). On the output side there are two relay and two enabling circuits and two solid-state enabling circuits as well as one solid-state signaling output. Standard operation In standard operation (key-operated switch "OFF") all enabling circuits are activated. The cascading input (1, with automatic start) and the protective door input Y42/Y52 are AND-connected with each other and affect all enabling circuits at the same time. Some are time-delayed. Input Y12/Y22 for the enabling button has no function in this context. The opening of the protective door or a missing signal at the cascading input CAS/OS deactivates all enabling circuits. Maintenance During maintenance (key-operated switch "ON") only two of the four enabling circuits are activated. In this case, sensor input Y42/Y52 (e.g. protective door) has no function. The hazardous area can be entered since the dangerous motion has been switched off via the two inactive enabling circuits. The dangerous motion can be started again via the enabling button at sensor input Y12/Y22 despite the protective door being open. Parameterization for monitored/automatic start for sensor circuit Y42/Y52: o If Y32 is at 24 V DC, the device powers up in automatic start. o If there is no voltage at Y32, the device powers up in monitored start. - If the protective door is not opened during maintenance, all enabling circuits close automatically on exiting maintenance mode. This applies to both monitored start and automatic start. If "monitored start" is parameterized: - A monitored start is required: o At initial start after applying the control supply voltage. o After opening and closing sensor circuits Y42/Y52 (even if this is followed by deactivation and reactivation of cascading!) - Automatic start takes place: o After activation of the cascading input (not on first switching of the device AND after opening and closing of the sensor on Y12/Y22 if maintenance mode is not selected). o After exiting maintenance mode (if Y42/Y52 has not been actuated). If "automatic start" is parameterized: o After the switch-on conditions have been met, all enabling circuits switch in (not in maintenance mode!) 2-16 NEB /RS-AC/005

31 Functional information Outputs: - Standard operation (Y72/Y82 at 0 V): o All enabling circuits (13/14, 24, 33/34, 44; or. 13/14, 24, 37/38, 48 with the time-delayed versions 3TK2845-.EB41; -.EB42; -.EB44) switch on with the Start command All enabling circuits are deactivated by actuating the sensor circuit Y42/Y52. o Signaling circuit 52 always switches inversely to the enabling circuits. - Maintenance (Y72/Y82 at 24 V DC): General: If cascading input 1 is opened during maintenance, all enabling circuits switch off, and signaling circuit 52 is active. o When exiting maintenance mode, all enabling circuits switch on only after a renewed Start command (if Y42/Y52 has been actuated). Starting maintenance mode from the idle condition: o Enabling circuits 13/14 and 24 switch on with the Start command regardless of the status at sensor input Y12/Y22 (if all other switch-on conditions are met at the same time). o Outputs 33/34 and 44 (37/38 and 24 with the time-delayed versions) can be activated in maintenance mode with the enabling button (even if door Y12/Y22 is opened). o Signaling circuit 52 pulses with a frequency of 1.2 Hz. Starting maintenance from standard operation (all enabling circuits active). o Enabling circuits 33/44 and 44 (24, 37/38 with the time-delayed versions) switch off when maintenance mode Y72/Y82 is selected, but enabling circuits 13/14 and 24 remain active. o Outputs 33/34 and 44 (37/38 and 24 with the time-delayed versions) can be activated in maintenance mode with the enabling button (even if door Y12/Y22 is opened). o Signaling circuit 52 pulses with a frequency of 1.2 Hz. NEB /RS-AC/

32 Functional information Status diagrams Standard Normalbetrieb operation Maintenance Servicebetrieb Standard Normalbetrieb operation Y34 Inputs Eingänge 1 Y12/22 Y42/52 Changeover Umschaltung from Normal- standard / operation Servicebetrieb to maintenance Y72/82 13/14 Outputs Ausgänge 24 33/ Fig. 2-5: Status diagram: 3TK2845-.EB40 Standard Normalbetrieb operation Maintenance Servicebetrieb Standard Normalbetrieb operation Y34 Inputs Eingänge 1 Y12/22 Y42/52 Changeover Umschaltung from Normal- standard - / Servicebetrieb operation to maintenance -/Servicebetrieb Y72/82 13/14 Ausgänge Outputs 24 37/ t v t v t v t v t v t v Fig. 2-6: Status diagram: 3TK2845-.EB NEB /RS-AC/005

33 Functional information Connections: Enabling button instantaneous Inputs (sensors) Outputs (enabling circuit) Sensor Terminals Description Description Terminals 1 Cascading Safe relay output 13 Y11 Y12 instantaneous 14 Y21 Y22 Sensor connection Safe solid-state output instantaneous 24 or or Y41 Y42 Y41 Y42 Sensor connection Safe relay output instantaneous Y34 START button Y32 - Monitored start (not connected) - Automatic start (with 24 V DC = terminal A1 connected) Safe solid-state output instantaneous 44 Y65 refers to Y41/Y42, Y51/Y52 Y72 Y82 - with cross-circuit detection (not connected) - without cross-circuit detection (with 24V DC = terminal A1 connected) Key-operated switch Solid-state signaling output 1) (must not be used for safety-related applications) 52 Y64 External device monitoring circuit 1) Solid-state signaling output Enabling circuits active: Enabling circuits inactive: Key-operated switch operation: Signaling output OFF Signaling output ON Signaling output clocked (approx. 1.2 Hz) NEB /RS-AC/

34 Functional information Inputs (sensors) Connections: Enabling button time-delayed Outputs (enabling circuit) Sensor Terminals Description Description Terminals 1 Cascading Safe relay output Y11 instantaneous Y12 Y21 Y22 Sensor connection Safe solid-state output instantaneous or or Y41 Y42 Y51 Y52 Sensor connection Safe relay output instantaneous Y34 START button Y32 - Monitored start (not connected) - Automatic start (with 24 V DC = terminal A1 connected) Safe solid-state output instantaneous 48 Y65 refers to Y41/Y42, Y51/Y52 Y72 Y82 - with cross-circuit detection (not connected) - without cross-circuit detection (with 24V DC = terminal A1 connected) Key-operated switch Solid-state signaling output 1) (must not be used for safety-related applications) 52 Y64 External device monitoring circuit 1) Solid-state signaling output Enabling circuits active: Enabling circuits inactive: Key-operated switch operation: Signaling output OFF Signaling output ON Signaling output clocked (approx. 1.2 Hz) 2-20 NEB /RS-AC/005

35 Functional information TK2845-.FB.. "Spring force interlocked tumbler" The 3TK2845-.FB.. has two sensor inputs (Y12/Y22 EMERGENCY-STOP with monitored start, Y42/Y52 protective door with tumbler and monitored start), one cascading input (1, with automatic start) as well as one door enable input. On the output side there are one relay enabling circuit and two solid-state enabling circuits as well as a solenoid control output and a solid-state signaling output. Not enabled If the protective door is not enabled, it cannot be opened. Cessation of the signal at the inputs Y12/Y22 or at the cascading input (1, with automatic start) deactivates the enabling circuits. Enabled The solenoid control output and the second solid-state enabling circuit are activated via a signal to the door enable input after the delay time has passed. This enables the protective door. A monitored start is required: o At initial start of the device. o After opening one or both sensor circuits (Y12/Y22 or Y42/Y52). o After cessation of the door enable (Y82), if the protective door has been opened. Automatic start takes place only: o In the case of a cascading input (if no sensor has been actuated previously). o After cessation of the door enable, if the protective door has not been opened. Outputs: o Standard operation (Y82 at 24 V): Enabling circuits 13/14 and 24 switch on with the Start command. Enabling circuits 13/14 and 24 are deactivated by actuating a sensor. Signaling circuit 52 always switches inversely to the enabling circuits. o Door enabling mode (Y82 at 0 V DC): In the mode for door enabling, outputs 13/14 and 24 are always inactive. Starting the mode for door enabling from the idle condition: Enabling circuits 37/38 and 48 are inactive, and the spring force interlocked tumbler remains enabled (protective door can be opened). Signaling circuit 52 pulses with a frequency of 1.2 Hz. Starting the mode for door enabling from standard operation (all enabling circuits active) Enabling circuits 13/14 and 24 switch off when maintenance Y82 is selected, and enabling circuits 37/38 and 48 switch off after the set time and enable the door tumbler. Signaling circuit 52 pulses with a frequency of 1.2 Hz. NEB /RS-AC/

36 Functional information Status diagram Y34 Start Door Standard Standard Norm albetrieb operation enabling Türfreigabe Norm al Inputs Eingänge 1 Y12/22 Y42/52 Y72 Cascading Kaskadier EMERGENCY NOT HALT Überwacht Stop monitored Protective Schutztür door Überwacht monitored Magnetüberwachung monitoring Y82 Door Türfreigabe enabling Outputs Ausgänge 13/ /38 48 OUT1 OUT2 OUT3 door Türverriegelung interlock OUT4 door Türverriegelung interlock 52 Signaling Meldeausgang output Fig. 2-7: Status diagram: 3TK2845-.FB4. t v 2-22 NEB /RS-AC/005

37 Functional information Connections: Spring force interlocked tumbler Inputs (sensors) Outputs (enabling circuit) Sensor Terminals Description Description Terminals 1 Cascading Safe relay output 13 Y11 instantaneous 14 Y12 Y21 Y22 Y34 Sensor connection START button Safe solid-state output instantaneous 24 Y35 - with cross-circuit detection (not connected) - without cross-circuit detection (with 24V DC = terminal A1 connected) Safe relay output switch-on delay e.g. for door interlock or or Y41 Y42 Y51 Y52 Sensor connection Safe solid-state output switch-on delay e.g. door interlock 48 Y65 refers to Y41/Y42, Y51/Y52 Y72 Y82 Y64 - with cross-circuit detection (not connected) - without cross-circuit detection (with 24V DC = terminal A1 connected) Magnet monitoring Door enable External device monitoring circuit Solid-state signaling output 1) (must not be used for safety-related applications) 52 1) Solid-state signaling output Enabling circuits active: Enabling circuits inactive: Key-operated switch operation: Signaling output OFF Signaling output ON Signaling output clocked (approx. 1.2 Hz) NEB /RS-AC/

38 Functional information TK2845-.GB.. "Magnetic force interlocked tumbler" The 3TK2845-.GB.. has two sensor inputs (Y12/Y22 EMERGENCY-STOP with monitored start, Y42/Y52 protective door with tumbler and monitored start), one cascading input (1, with automatic start) as well as one door enable input. On the output side there are one relay enabling circuit and two solid-state enabling circuits as well as a relay solenoid control output and a solid-state signaling output. Not enabled If the protective door is not enabled, it cannot be opened. Cessation of the signal at the inputs Y12/Y22 or at the cascading input (1, with automatic start) deactivates the enabling circuits (13, 14; 24). Enabled The solenoid control output and the second solid-state enabling circuit are deactivated via a signal to the door enable input after the delay time has passed. This enables the protective door. A monitored start is required: o At initial start of the device. o After opening one or both sensor circuits (Y12/Y22 or Y42/Y52). o After closing the door enable, if the protective door has been opened. Automatic start only: o In the case of a cascading input (if no sensor has been actuated previously). o After closing the door enable, if the protective door has not been opened. Outputs: o Standard operation (Y82 at 24 V DC): Enabling circuits 13/14 and 24 switch on with the Start command. Enabling circuits 13/14 and 24 are deactivated by actuating a sensor. Signaling circuit 52 always switches inversely to the enabling circuits. o Door enabling mode (Y82 at 0 V DC) In the mode for door enabling, outputs 13/14 and 24 are always inactive. Starting the mode for door enabling from the idle condition: Enabling circuits 37/38 and 48 are inactive, and the magnetic force interlocked tumbler remains enabled (protective door can be opened). Signaling circuit 52 pulses with a frequency of 1.2 Hz. Starting the mode for door enabling from standard operation (all enabling circuits active): Enabling circuits 13/14 and 24 switch off when door enabling is selected (Y82 at 0 V DC), and the magnetic force interlocked tumbler becomes inactive after the set time (protective door can be opened). Signaling circuit 52 pulses with a frequency of 1.2 Hz NEB /RS-AC/005

39 Functional information Status diagram Y34 Start Standard Norm albetrieb operation Türfreigabe Door Standard Norm al enabling Inputs Eingänge 1 Y12/22 Y42/52 Cascading Kaskadier EMERGENCY NOT HALT Überwacht Stop monitored Protective Schutztür door Überwacht monitored Y72 Y82 Magnetüberwachung monitoring Door Türfreigabe enabling Outputs Ausgänge 13/ /38 48 OUT1 OUT2 OUT3 door Türverriegelung interlock OUT4 door Türverriegelung interlock 52 Signaling Meldeausgang output Fig. 2-8: Status diagram: 3TK2845-.GB4. t v NEB /RS-AC/

40 Functional information Connections: magnetic force interlocked tumbler Inputs (sensors) Outputs (enabling circuit) Sensor Terminals Description Description Terminals 1 Y11 Cascading Safe relay output instantaneous Y12 Sensor connection Y21 Y22 Safe solid-state output Y34 START button instantaneous Y35 refers to Y11/142, Y21/Y22 - with cross-circuit detection (not connected) - without cross-circuit detection (with 24V DC = terminal A1 connected) Safe relay output off-delay e.g. door interlock or or Y41 Y42 Y51 Y52 Sensor connection Safe solid-state output off-delay e.g. door interlock 48 Y65 refers to Y41/Y42, Y51/Y52 Y72 Y82 Y64 - with cross-circuit detection (not connected) - without cross-circuit detection (with 24V DC = terminal A1 connected) Magnet monitoring Door enable External device monitoring circuit Solid-state signaling output 1) (must not be used for safety-related applications) 52 1) Solid-state signaling output Enabling circuits active: Enabling circuits inactive: Key-operated switch operation: Signaling output OFF Signaling output ON Signaling output clocked (approx. 1.2 Hz) 2-26 NEB /RS-AC/005

41 Technical data 3 Chapter Subject Page 3.1 Technical data Terminals Terminal assignment Dimensional drawings 3-6 NEB /RS-AC/

42 Technical data 3.1 Technical data Type 3TK Standards EN , EN ISO , IEC EMC EN Category in accordance with DIN EN PL e /CAT 4 Safety Integrity Level Claim Limit (SIL CL) 3 Test verification documents Overvoltage category Rated insulation voltage U i Rated impulse withstand voltage U imp Rated control supply voltage V s Operating range Rated power Short-circuit protection TÜV II 300 V 2,5 kv 24 V DC 0,85 to 1,15 U s 5 W Switching frequency z during rated operation /h Response time Release time, (stop category 0) in the case of EMERGENCY-STOP Release time, (Stop category 1) at the safe outputs during EMERGENCY-STOP Supply power buffering Recovery time during EMERGENCY-STOP/ power failure Minimum EMERGENCY-STOP command time START button command time Permissible ambient temperature T a during operation and storage Total resistance of sensor circuit R SG Total capacity of sensor circuit C SG Degree of protection according to EN 60529, enclosure/terminals Touch protection, DIN VDE 0106, Part 100 Weight Permissible mounting position Semiconductor outputs: Short-circuit-proof Use 4 A gl/gg or quick-response fuse-links for the floating safe outputs, e.g. LV HRC type 3NA, DIAZED type 5SB, NEOZED type 5SE Max. 60 ms 45 ms Max. 300 seconds (adjustable) 25 ms At least 200 ms/at least 8 seconds 30 ms 0.2 to 5 seconds 25 to +60 C/ 40 to +80 C Max. 250Ω max. 500 nf IP20 Finger-safe 0.4 kg Shock resistance Sine wave 8/10 and 15/5 g/ms PFH D 6.86 x 10-9 Any PFD 6.1 x 10-4 Table 3-1: Technical data 3-2 NEB /RS-AC/005

43 Technical data Type 3TK HFT 1 Lifetime 20 years SFF [%] > 90 % T1 20 years Table 3-1: Technical data (Contd.) Data sheet You can find all the technical data of the product in the Siemens Industry Online Support. 1. Enter the full article number of the desired device in the "Product" field, and confirm with the Enter key. 2. Click the "Technical data link. NEB /RS-AC/

Safety Relays 3TK2845 Multifunction Device

Safety Relays 3TK2845 Multifunction Device Important Information, Table of Contents Product Description 1 Safety Relays 3TK2845 Multifunction Device Functional Information 2 Technical Data 3 Mounting, Wiring, Initial Start-up 4 Manual Applications

More information

Line reactors SINAMICS. SINAMICS G120P Line reactors. Safety information 1. General. Mechanical installation 3. Electrical installation 4

Line reactors SINAMICS. SINAMICS G120P Line reactors. Safety information 1. General. Mechanical installation 3. Electrical installation 4 Safety information 1 General 2 SINAMICS SINAMICS G120P Mechanical installation 3 Electrical installation 4 Technical specifications 5 Operating Instructions Control version V4.6 11/2013 A5E32845290B AA

More information

PSR DC/ESP4/2X1/1X2

PSR DC/ESP4/2X1/1X2 PSR-...- 24DC/ESP4/2X1/1X2 Safety relay for emergency stop and safety door monitoring Data sheet 100516_en_05 PHOENIX CONTACT 2013-11-21 1 Description The safety relay can be used for emergency stop and

More information

SITOP power supply. Selectivity modules. Overview. Safety notes. Description, device design, dimension drawing. Mounting/removal 3

SITOP power supply. Selectivity modules. Overview. Safety notes. Description, device design, dimension drawing. Mounting/removal 3 Overview Safety notes 1 SITOP power supply Manual Description, device design, dimension drawing 2 Mounting/removal 3 Mounting position, mounting clearances 4 Installation 5 Technical data 6 Safety, approvals,

More information

SAFETY RELAY YRB-4EML-31S MAIN FEATURES

SAFETY RELAY YRB-4EML-31S MAIN FEATURES SAFETY RELAY TYPE 4 SAFETY PROTECTION DEVICE FOR SAFETY LIGHT CURTAINS/BARRIERS MAIN FEATURES For safety light curtains and access control barriers, emergency stop, door switch Safety Integrity Level (SIL)

More information

SINAMICS G130. Terminal Module 150 (TM150) Operating Instructions 03/2013 SINAMICS

SINAMICS G130. Terminal Module 150 (TM150) Operating Instructions 03/2013 SINAMICS SINAMICS G130 Operating Instructions 03/2013 SINAMICS s Safety information 1 General information 2 SINAMICS SINAMICS G130 Mechanical installation 3 Electrical installation 4 Technical specifications 5

More information

DANGER indicates that death or severe personal injury will result if proper precautions are not taken.

DANGER indicates that death or severe personal injury will result if proper precautions are not taken. Preface SIMATIC ET 200S distributed I/O Digital electronic module 2RO NO/NC DC24..48V/5A AC24..230V/5A (6ES7132-4HB50-0AB0) SIMATIC ET 200S distributed I/O Digital electronic module 2RO NO/NC DC24..48V/5A

More information

ST (6ES7132-6FD00-0BB1)

ST (6ES7132-6FD00-0BB1) SIMATIC ET 200SP Digital output module DQ 4x24..230VAC/2A ST (6ES7132-6FD00-0BB1) Manual Edition 02/2014 Answers for industry. DQ 4x24..230VAC/2A ST Preface Guide to documentation 1 SIMATIC ET 200SP DQ

More information

PSR UC/ESAM4/3X1/1X2/B

PSR UC/ESAM4/3X1/1X2/B Safety relay for emergency stop and safety door monitoring Data sheet 105318_en_02 PHOENIX CONTACT 2014-06-13 1 Description The safety relay can be used in safety circuits according to EN 60240-1 and IEC

More information

ET 200S distributed I/O Digital electronic module 2DO AC V (6ES7132-4FB01-0AB0)

ET 200S distributed I/O Digital electronic module 2DO AC V (6ES7132-4FB01-0AB0) SIMATIC ET 200S distributed I/O SIMATIC Preface ET 200S distributed I/O Digital electronic module 2DO AC24..230V (6ES7132-4FB01-0AB0) Properties 1 Parameters 2 Diagnostics 3 Manual 04/2007 A5E01077264-01

More information

Power supply module PS 25W 24VDC (6ES7505-0KA00-0AB0) SIMATIC. S7-1500/ET 200MP Power supply module PS 25W 24VDC (6ES7505-0KA00-0AB0) Preface

Power supply module PS 25W 24VDC (6ES7505-0KA00-0AB0) SIMATIC. S7-1500/ET 200MP Power supply module PS 25W 24VDC (6ES7505-0KA00-0AB0) Preface Power supply module PS 25W 24VDC (6ES7505-0KA00-0AB0) SIMATIC S7-1500/ET 200MP Power supply module PS 25W 24VDC (6ES7505-0KA00-0AB0) Manual Preface Documentation guide 1 Product overview 2 Wiring 3 Parameters

More information

ET 200S distributed I/O system 4DO DC24V/2A ST digital electronic module (6ES7132-4BD32-0AA0)

ET 200S distributed I/O system 4DO DC24V/2A ST digital electronic module (6ES7132-4BD32-0AA0) 4DO DC24V/2A ST digital electronic module (6ES7132-4BD32- SIMATIC Preface 1 Properties 2 Diagnostics 3 ET 200S distributed I/O system 4DO DC24V/2A ST digital electronic module (6ES7132-4BD32- Manual 10/2015

More information

SIMATIC. ET 200S distributed I/O Digital electronic module 4DO DC24V/0.5A ST (6ES7132-4BD02-0AA0) Preface. Properties 2. Diagnostics 3.

SIMATIC. ET 200S distributed I/O Digital electronic module 4DO DC24V/0.5A ST (6ES7132-4BD02-0AA0) Preface. Properties 2. Diagnostics 3. Preface 1 Properties 2 SIMATIC Diagnostics 3 ET 200S distributed I/O Digital electronic module 4DO DC24V/0.5A ST (6ES7132-4BD02- Manual 01/2008 A5E01254028-01 Safety Guidelines This manual contains notices

More information

Siemens Spares. Preface 1. Scope of Delivery 2 SIPLUS CMS4000. Product Characteristics 3 ION PROFIBUS DP SPY T001 Installation and Maintenance 4

Siemens Spares. Preface 1. Scope of Delivery 2 SIPLUS CMS4000. Product Characteristics 3 ION PROFIBUS DP SPY T001 Installation and Maintenance 4 Preface 1 Scope of Delivery 2 Product Characteristics 3 Industrial I/O-Node ION PROFIBUS DP SPY T001 Installation and Maintenance 4 6AT8000-1BA00-5XA0 Notes on the CE Mark 5 References 6 Appendix 7 Release

More information

SINAMICS G130. Voltage Sensing Module 10 (VSM10) Operating instructions 03/2011 SINAMICS

SINAMICS G130. Voltage Sensing Module 10 (VSM10) Operating instructions 03/2011 SINAMICS SINAMICS G130 Operating instructions 03/2011 SINAMICS s Safety information 1 General 2 SINAMICS SINAMICS G130 Voltage Sensing Module 10 (VSM10) Mechanical installation 3 Electrical installation 4 Technical

More information

SIMATIC. ET 200S distributed I/O Digital electronic module 4DO DC24V/0.5 A ST (6ES7132-4BD01-0AA0) Preface. Properties 1. Diagnostics 2.

SIMATIC. ET 200S distributed I/O Digital electronic module 4DO DC24V/0.5 A ST (6ES7132-4BD01-0AA0) Preface. Properties 1. Diagnostics 2. SIMATIC ET 200S distributed I/O Digital electronic module 4DO DC24V/0.5 A ST (6ES7132-4BD01- SIMATIC Preface Properties 1 Diagnostics 2 ET 200S distributed I/O Digital electronic module 4DO DC24V/0.5 A

More information

Power module PM-E DC24V/8A RO SIMATIC. ET 200S distributed I/O Power module PM-E DC24V/8A RO (6ES7138-4CA80-0AB0) Preface. Properties.

Power module PM-E DC24V/8A RO SIMATIC. ET 200S distributed I/O Power module PM-E DC24V/8A RO (6ES7138-4CA80-0AB0) Preface. Properties. Power module PM-E DC24V/8A RO (6ES7138-4CA80-0AB0) SIMATIC ET 200S distributed I/O Power module PM-E DC24V/8A RO (6ES7138-4CA80-0AB0) Preface Properties 1 Parameters 2 Diagnostics 3 Configuring 4 Manual

More information

SINAMICS G130. Voltage Sensing Module 10 (VSM10) Operating Instructions 05/2010 SINAMICS

SINAMICS G130. Voltage Sensing Module 10 (VSM10) Operating Instructions 05/2010 SINAMICS SINAMICS G130 Operating Instructions 05/2010 SINAMICS s Safety information 1 General 2 SINAMICS SINAMICS G130 Voltage Sensing Module 10 (VSM10) Mechanical installation 3 Electrical installation 4 Technical

More information

SIMATIC Ident RFID systems MDS D423 Compact Operating Instructions

SIMATIC Ident RFID systems MDS D423 Compact Operating Instructions SIMATIC Ident RFID systems Compact Operating Instructions Legal information Warning notice system This manual contains notices you have to observe in order to ensure your personal safety, as well as to

More information

PSR-MS60. Safety relay for emergency stop, safety door and light grid monitoring. Data sheet. 1 Description

PSR-MS60. Safety relay for emergency stop, safety door and light grid monitoring. Data sheet. 1 Description SILCL IEC 62061 Safety relay for emergency stop, safety door and light grid monitoring Data sheet 106171_en_01 PHOENIX CONTACT 2015-05-19 1 Description Intended Use The PSR-MS60 safety relay can be used

More information

Original operating instructions Safety relay with relay outputs with and without delay G1502S / / 2016

Original operating instructions Safety relay with relay outputs with and without delay G1502S / / 2016 Original operating instructions Safety relay with relay outputs with and without delay UK G50S 803638 / 00 0 / 06 Contents Preliminary note...4. Symbols used...4 Safety instructions...5 3 Items supplied...6

More information

DI 8x24VDC ST digital input module SIMATIC. ET 200SP DI 8x24VDC ST digital input module (6ES7131-6BF00-0BA0) Preface. Documentation guide

DI 8x24VDC ST digital input module SIMATIC. ET 200SP DI 8x24VDC ST digital input module (6ES7131-6BF00-0BA0) Preface. Documentation guide DI 8x24VDC ST digital input module (6ES7131-6BF00-0BA0) SIMATIC ET 200SP DI 8x24VDC ST digital input module (6ES7131-6BF00-0BA0) Manual Preface Documentation guide 1 Product overview 2 Connecting 3 Parameter

More information

Industrial Controls. Motor management and control devices SIMOCODE pro - Application examples. Introduction 1. Application example

Industrial Controls. Motor management and control devices SIMOCODE pro - Application examples. Introduction 1. Application example Introduction 1 Application example 2 Industrial Controls Motor management and control devices SIMOCODE pro - Application examples Application Manual Example circuits control functions 3 Further application

More information

Manual. Industrial Controls. Motor Management and Control Devices. SIMOCODE pro Fail-Safe Digital Modules. Edition 11/2017. siemens.

Manual. Industrial Controls. Motor Management and Control Devices. SIMOCODE pro Fail-Safe Digital Modules. Edition 11/2017. siemens. Manual Industrial Controls Motor Management and Control Devices SIMOCODE pro Fail-Safe Digital Modules Edition 11/2017 siemens.com Introduction 1 Safety notes 2 SIMOCODE pro SIMOCODE pro - Fail-Safe Digital

More information

SIRIUS Monitoring and Controlling. Overview of safety relays. Safety Integrated. Answers for industry.

SIRIUS Monitoring and Controlling. Overview of safety relays. Safety Integrated. Answers for industry. SIRIUS Monitoring and Controlling Overview of safety relays Safety Integrated Answers for industry. Simpler, faster and more cost-effective to implement a seamless safety chain Today, one of the key success

More information

PSR-SCP- 24DC/SDC4/2X1/B PSR-SPP- 24DC/SDC4/2X1/B

PSR-SCP- 24DC/SDC4/2X1/B PSR-SPP- 24DC/SDC4/2X1/B PSR-SCP- 24DC/SDC4/2X1/B PSR-SPP- 24DC/SDC4/2X1/B Safety Relay for Emergency Stop and Safety Door Circuits INTERFACE Data Sheet 102858_02_en PHOENIX CONTACT - 12/2006 Description The PSR-...- 24DC/SDC4/2X1/B

More information

AS-i Safety Relay Output Module with Diagnostic Slave

AS-i Safety Relay Output Module with Diagnostic Slave AS-i Safety Relay Output Module with Diagnostic Slave User Manual...supports the requirements for AS-i Safety up to SIL3 Revision date: 2016-03-9 Subject to modifications without notice. Generally, this

More information

AS-i Safety Relay Output Module with Diagnostic Slave

AS-i Safety Relay Output Module with Diagnostic Slave AS-i Safety Relay Output Module with Diagnostic Slave User Manual Revision date: 2013-01-30...supports the requirements for AS-i Safety up to SIL3 Subject to modifications without notice. Generally, this

More information

Control unit SG-EFS 104/4L. EN Operating instructions. Innovative by tradition. Version SG-EFS 104/4L AC/DC 24 V

Control unit SG-EFS 104/4L. EN Operating instructions. Innovative by tradition. Version SG-EFS 104/4L AC/DC 24 V Innovative by tradition. Control unit SG-EFS 104/4L EN Operating instructions Version 2 1004128 SG-EFS 104/4L AC/DC 24 V Original instructions Mayser GmbH & Co. KG Örlinger Straße 1 3 89073 Ulm GERMANY

More information

Original operating instructions Safety relay with relay outputs G1501S / / 2016

Original operating instructions Safety relay with relay outputs G1501S / / 2016 Original operating instructions Safety relay with relay outputs G50S UK 8023637 / 00 02 / 206 Contents Preliminary note...4. Symbols used...4 2 Safety instructions...5 3 Items supplied...6 4 Functions

More information

Safety Switching Devices SNO 4003K. Basic device for Emergency-Stop and Safety Gate Applications PI E

Safety Switching Devices SNO 4003K. Basic device for Emergency-Stop and Safety Gate Applications PI E EN 60204-1 Stop category 0 EN 954-1 Safety category 4 Basic device to EN 60204-1 and EN 954-1 single E-stop monitoring. Manual or automatic start Application up to safety category 2 and stop category 0

More information

SECTION 16 LED DIAGNOSTIC FEATURES: EXPANSION UNITS: SCR-31P-i. SCR-73-i. SEU-31-i. SCR-31-42TD-i. SEU-31TD-i

SECTION 16 LED DIAGNOSTIC FEATURES: EXPANSION UNITS: SCR-31P-i. SCR-73-i. SEU-31-i. SCR-31-42TD-i. SEU-31TD-i SECTION 16 VIPER Safety Relays Type: SCR-i (with added diagnostics) SAFETY RELAY FUNCTION: IDEM s VIPER SCR-i range of Safety Relays have been designed in accordance with EN60204-1 for safety circuits

More information

dv/dt filter compact plus Voltage Peak Limiter SINAMICS SINAMICS G120P dv/dt filter compact plus Voltage Peak Limiter Safety information 1 General 2

dv/dt filter compact plus Voltage Peak Limiter SINAMICS SINAMICS G120P dv/dt filter compact plus Voltage Peak Limiter Safety information 1 General 2 dv/dt filter compact plus Voltage Peak Limiter SINAMICS SINAMICS G120P dv/dt filter compact plus Voltage Peak Limiter Operating Instructions Safety information 1 General 2 Mechanical installation 3 Electrical

More information

Safety Technique. SAFEMASTER C Multifunction Safety Module BH 5910

Safety Technique. SAFEMASTER C Multifunction Safety Module BH 5910 Safety Technique SAFEMASTER C Multifunction Safety Module BH 59 47 Block Diagram A+ A S S S4 S S S S4 S S S S4 S S4 S4 S44 S4 PTC Galvanic separation Monitoring logic Monitoring logic Galvanic separation

More information

Line reactors SINAMICS. SINAMICS G130 Line reactors. Safety information 1. General. Mechanical installation 3. Electrical installation

Line reactors SINAMICS. SINAMICS G130 Line reactors. Safety information 1. General. Mechanical installation 3. Electrical installation Safety information 1 General 2 SINAMICS SINAMICS G130 Mechanical installation 3 Electrical installation 4 Technical specifications 5 Operating Instructions Control version V4.7 04/2014 A5E00331462A Legal

More information

SINAMICS. SINAMICS G120P dv/dt filter plus Voltage Peak Limiter. Safety information 1. General. Mechanical installation. Electrical installation 4

SINAMICS. SINAMICS G120P dv/dt filter plus Voltage Peak Limiter. Safety information 1. General. Mechanical installation. Electrical installation 4 Safety information 1 General 2 SINAMICS SINAMICS G120P dv/dt filter plus Voltage Peak Limiter Operating Instructions Mechanical installation 3 Electrical installation 4 Maintenance and servicing 5 Technical

More information

Power module PM-E DC24V HF SIMATIC. ET 200S distributed I/O Power module PM-E DC24V HF (6ES7138-4CA60-0AB0) Preface. Properties.

Power module PM-E DC24V HF SIMATIC. ET 200S distributed I/O Power module PM-E DC24V HF (6ES7138-4CA60-0AB0) Preface. Properties. Power module PM-E DC24V HF (6ES7138-4CA60-0AB0) SIMATIC ET 200S distributed I/O Power module PM-E DC24V HF (6ES7138-4CA60-0AB0) Preface Properties 1 Parameters 2 Diagnostics 3 Configuring 4 Manual 06/2010

More information

Industrial Controls. Safety Integrated Application Manual. ASIsafe circuits for safety technology with AS-Interface safety monitor and DP/AS-i F-Link

Industrial Controls. Safety Integrated Application Manual. ASIsafe circuits for safety technology with AS-Interface safety monitor and DP/AS-i F-Link Safety Integrated Application Manual ASIsafe circuits for safety technology with AS-Interface safety monitor and DP/AS-i F-Link Function Manual 08/2012 Industrial Controls Answers for industry. ASIsafe

More information

Siemens Industrial s

Siemens Industrial s SINAMICS G130 Operating Instructions 05/2010 SINAMICS Siemens Industrial s Sinusoidal filter Safety information 1 General 2 SINAMICS SINAMICS G130 Mechanical installation 3 Electrical installation 4 Technical

More information

Team engineering via Inter Project. Engineering. TIA Portal. Team engineering via Inter Project Engineering. Basics of "Inter Project Engineering"

Team engineering via Inter Project. Engineering. TIA Portal. Team engineering via Inter Project Engineering. Basics of Inter Project Engineering Team engineering via Inter Project Engineering TIA Portal Basics of "Inter Project Engineering" 1 Creating an IPE file 2 Importing an IPE file 3 Team engineering via Inter Project Engineering Getting Started

More information

Safety relay emergency stop/protective door, 24VDC/AC, 4 enabling paths

Safety relay emergency stop/protective door, 24VDC/AC, 4 enabling paths DATASHEET - ESR5-NO-41-24VAC-DC Safety relay emergency stop/protective door, 24VDC/AC, 4 enabling paths Part no. ESR5-NO-41-24VAC-DC Catalog No. 118701 EL-Nummer (Norway) 0004133317 Delivery program Product

More information

SIRIUS Safety Integrated. Modular safety system 3RK3

SIRIUS Safety Integrated. Modular safety system 3RK3 Functional Example CD-FE-I-048-V10-EN SIRIUS Safety Integrated Modular safety system 3RK3 Emergency Stop with monitored Start and Protective Door with automatic start according to category 4 in EN 954-1.

More information

PSR-SCP- 24DC/URM4/4X1/2X2/B PSR-SPP- 24DC/URM4/4X1/2X2/B

PSR-SCP- 24DC/URM4/4X1/2X2/B PSR-SPP- 24DC/URM4/4X1/2X2/B Safety Relay as a Contact Extension Block INTERFACE Data Sheet PHOENIX CONTACT - 05/2006 Description The PSR-...- 24DC/URM4/4X1/2X2/B safety relay can be used as a contact extension block in safety circuits

More information

DANGER indicates that death or severe personal injury will result if proper precautions are not taken.

DANGER indicates that death or severe personal injury will result if proper precautions are not taken. SIMATIC ET 200S distributed I/O SIMATIC ET 200S distributed I/O Digital electronic module 4DI DC24V HF (6ES7131-4BD01-0AB0) Manual Preface Properties 1 Parameters 2 Diagnostics 3 04/2007 A5E01077141-01

More information

Digital output module. DQ 16x24VDC/0.5A BA (6ES7522-1BH10-0AA0) SIMATIC

Digital output module. DQ 16x24VDC/0.5A BA (6ES7522-1BH10-0AA0) SIMATIC Digital output module DQ 16x24VDC/0.5A BA (6ES7522-1BH10-0AA0) SIMATIC S7-1500/ET 200MP Digital output module DQ 16x24VDC/0.5A BA (6ES7522-1BH10-0AA0) Manual Preface Documentation guide 1 Product overview

More information

PSR-SCP- 24DC/SSM/2X1 PSR-SPP- 24DC/SSM/2X1

PSR-SCP- 24DC/SSM/2X1 PSR-SPP- 24DC/SSM/2X1 PSR-SCP- DC/SSM/2X1 PSR-SPP- DC/SSM/2X1 Safety Relay With Downtime Monitoring INTERFACE Data Sheet PHOENIX CONTACT - 05/2006 Description The PSR-...- DC/SSM/2X1 safety relay can be used in safety circuits

More information

Readme SiVArc V14 SP1 Update 6

Readme SiVArc V14 SP1 Update 6 Product version 1 Improvements in Update 6 2 Readme 05/2018 Legal information Warning notice system This manual contains notices you have to observe in order to ensure your personal safety, as well as

More information

Safety relay emergency stop/protective door, 230VAC, 3 enabling paths

Safety relay emergency stop/protective door, 230VAC, 3 enabling paths DATASHEET - ESR5-NO-31-230VAC Safety relay emergency stop/protective door, 230VAC, 3 enabling paths Part no. ESR5-NO-31-230VAC Catalog No. 119380 EL-Nummer (Norway) 4133320 Delivery program Product range

More information

Safety relay emergency stop/protective door, 24V-230VDC/AC, 3 enabling paths

Safety relay emergency stop/protective door, 24V-230VDC/AC, 3 enabling paths DATASHEET - ESR5-NO-31-AC-DC Delivery program Safety relay emergency stop/protective door, 24V-230VDC/AC, 3 enabling paths Part no. ESR5-NO-31-AC-DC Catalog No. 118704 Eaton Catalog No. ESR5-NO-31-AC-DC

More information

Options for ABB drives. User s manual Emergency stop, stop category 0 (option +Q951) for ACS880-07/17/37 drives

Options for ABB drives. User s manual Emergency stop, stop category 0 (option +Q951) for ACS880-07/17/37 drives Options for ABB drives User s manual Emergency stop, stop category 0 (option +Q951) for ACS880-07/17/37 drives List of related manuals Drive hardware manuals and guides ACS880-07 drives (560 to 2800 kw)

More information

Polymer Electric. Operating Instructions. Control Unit SG-EFS 1X4 ZK2/1 8k2. Version 3

Polymer Electric. Operating Instructions. Control Unit SG-EFS 1X4 ZK2/1 8k2. Version 3 Operating Instructions Control Unit SG-EFS 1X4 ZK2/1 8k2 Version 3 1003100 SG-EFS 104 ZK2/1 8k2 24 V=/~ 7500354 SG-EFS 134 ZK2/1 8k2 230 V~ Original instructions GmbH & Co. KG Polymer Electric Örlinger

More information

Industrial Controls. Safety engineering SIRIUS 3SK1 safety relays. Introduction. Product-specific safety information. Product overview for 3SK1

Industrial Controls. Safety engineering SIRIUS 3SK1 safety relays. Introduction. Product-specific safety information. Product overview for 3SK1 Introduction 1 Product-specific safety information 2 Industrial Controls Safety engineering Manual Product overview for 3SK1 3 Safety systems - General information 4 3SK1 devices 5 System configuration

More information

Class documentation. COMOSKDictionary COMOS. Platform Class documentation COMOSKDictionary. Trademarks. General. KDictionary. Programming Manual

Class documentation. COMOSKDictionary COMOS. Platform Class documentation COMOSKDictionary. Trademarks. General. KDictionary. Programming Manual Class documentation COMOSKDictionary COMOS Trademarks 1 General 2 KDictionary 3 Platform Class documentation COMOSKDictionary Programming Manual 04/2012 A5E03777026-01 Legal information Legal information

More information

Operating Instructions

Operating Instructions Innovative by tradition. Operating Instructions Control Unit SG-RSV 239 Version 1 1003986 SG-RSV 239/24 24 V= 1005372 SG-RSV 239/36 36 V= 1003271 SG-RSV 239 50-150 V= Mayser GmbH & Co. KG Örlinger Straße

More information

SR101A. User Information for SR101A. Correct Use

SR101A. User Information for SR101A. Correct Use Correct Use is the low-cost emergency stop safety relay with which machines and systems can be safely switched off by disconnecting the power supply. Internal fault monitoring takes place during restarting

More information

Converter SINAMICS G150. Type 6SL37102G

Converter SINAMICS G150. Type 6SL37102G Tests carried out on drives This documentation pertains to LV Umrichter E11 F72 F76 F79 L45 L50 L57 L68 M54 U11 Reference Manual Converter SINAMICS G150 Type 6SL37102G Edition 02/2019 www.siemens.com/drives

More information

Line filter SINAMICS. SINAMICS G130 Line filter. Safety information 1. General 2. Mechanical installation 3. Electrical installation 4

Line filter SINAMICS. SINAMICS G130 Line filter. Safety information 1. General 2. Mechanical installation 3. Electrical installation 4 Safety information 1 General 2 SINAMICS SINAMICS G130 Mechanical installation 3 Electrical installation 4 Technical specifications 5 Operating Instructions Control version V4.8 07/2016 A5E00331460A Legal

More information

Drive Technology \ Drive Automation \ System Integration \ Services. Manual. Control Cabinet Inverter MOVITRAC B Functional Safety

Drive Technology \ Drive Automation \ System Integration \ Services. Manual. Control Cabinet Inverter MOVITRAC B Functional Safety Drive Technology \ Drive Automation \ System Integration \ Services Manual Control Cabinet Inverter MOVITRAC B Functional Safety Edition 05/2009 16811216 / EN SEW-EURODRIVE Driving the world Content Content

More information

Control unit SG-EFS 104/2W. EN Operating instructions. Innovative by tradition. Version SG-EFS 104/2W 24 V=/~

Control unit SG-EFS 104/2W. EN Operating instructions. Innovative by tradition. Version SG-EFS 104/2W 24 V=/~ Innovative by tradition. Control unit SG-EFS 104/2W EN Operating instructions Version 0.9 1005196 SG-EFS 104/2W 24 V=/~ Original instructions Mayser GmbH & Co. KG Örlinger Straße 1 3 89073 Ulm GERMANY

More information

Device manual SINAMICS SINAMICS G120. Distributed inverter box Control cabinet for wall or floor mounting.

Device manual SINAMICS SINAMICS G120. Distributed inverter box Control cabinet for wall or floor mounting. Device manual SINAMICS SINAMICS G120 Control cabinet for wall or floor mounting Edition 06/2018 www.siemens.com/drives Safety note 1 Description 2 SINAMICS SINAMICS G120 Manual Mounting 3 Connection 4

More information

Medium-Voltage Drive SINAMICS SM150. Type 6SL3845. Tests carried out on drives This documentation pertains to SM150 wassergekühlt G20 F03 F72 F79 F76

Medium-Voltage Drive SINAMICS SM150. Type 6SL3845. Tests carried out on drives This documentation pertains to SM150 wassergekühlt G20 F03 F72 F79 F76 Tests carried out on drives This documentation pertains to SM150 wassergekühlt G20 F03 F72 F79 F76 Reference Manual Medium-Voltage Drive SINAMICS SM150 Type 6SL3845 Edition 02/2019 www.siemens.com/drives

More information

SIMATIC. ET 200SP DQ 4x VAC/2A ST digital output module (6ES7132-6FD00-0BB1) Preface. Guide to documentation. Product overview.

SIMATIC. ET 200SP DQ 4x VAC/2A ST digital output module (6ES7132-6FD00-0BB1) Preface. Guide to documentation. Product overview. Preface Guide to documentation 1 SIMATIC ET 200SP DQ 4x24..230VAC/2A ST digital output module (6ES7132-6FD00-0BB1) Manual Product overview 2 Wiring 3 Parameter assignment/addressing 4 Interrupts/diagnostics

More information

SIMATIC. ET 200SP Open Controller Product information on CPU 1515SP PC. Preface. Product Information. Technical update. Technical specifications 3

SIMATIC. ET 200SP Open Controller Product information on CPU 1515SP PC. Preface. Product Information. Technical update. Technical specifications 3 1BProduct information on CPU 1515SP PC Preface Product Information 1 SIMATIC ET 200SP Open Controller Technical update 2 Technical specifications 3 Product Information 09/2015 A5E35456639-AC 3BLegal information

More information

ISO SINAMICS G110D FAQ

ISO SINAMICS G110D FAQ Cover sheet Safe Torque Off (STO) of an AS-idriven SINAMICS G110D with SIL 3 in compliance with IEC 62061 or PL e in compliance with ISO 13849-1 SINAMICS G110D FAQ November 2012 Service & Support Answers

More information

Operating instructions Safe AS-i input module ASIM-C-M About this document. Content

Operating instructions Safe AS-i input module ASIM-C-M About this document. Content 7 Set-up and maintenance 7.1 Functional testing....10 7.2 Maintenance...10 EN Operating instructions.............pages 1 to 6 Original 8 Disassembly and disposal 8.1 Disassembly....10 8.2 Disposal...10

More information

Description. SIMATIC Sensors. RF systems Wide-range power supply unit for SIMATIC RF systems. Operating Instructions 11/2007 J31069-D0169-U001-A4-7618

Description. SIMATIC Sensors. RF systems Wide-range power supply unit for SIMATIC RF systems. Operating Instructions 11/2007 J31069-D0169-U001-A4-7618 1 SIMATIC Sensors RF systems Wide-range power supply unit for SIMATIC RF systems Operating Instructions 11/2007 J31069-D0169-U001-A4-7618 Safety Guidelines This manual contains notices you have to observe

More information

SR103AM. User Information for SR103AM. Correct Use

SR103AM. User Information for SR103AM. Correct Use Correct Use The is a universal emergency stop safety switching device with three safe relay outputs that can quickly and safely stop the moving parts of a machine or system in case of danger. Applications

More information

SIMATIC. ET 200S distributed I/O 2AO U ST analog electronic module (6ES7135-4FB01-0AB0) Preface. Properties 1. Parameters 2.

SIMATIC. ET 200S distributed I/O 2AO U ST analog electronic module (6ES7135-4FB01-0AB0) Preface. Properties 1. Parameters 2. SIMATIC ET 200S distributed I/O SIMATIC ET 200S distributed I/O 2AO U ST analog electronic module (6ES7135-4FB01-0AB0) Manual Preface Properties 1 Parameters 2 Diagnostics 3 Analog value representation

More information

General Information 1. Connection 2. User Interface 3 ATC5300. Menus 4. Automatic Transfer Controller. Remote Control Software Manual A5E

General Information 1. Connection 2. User Interface 3 ATC5300. Menus 4. Automatic Transfer Controller. Remote Control Software Manual A5E s General Information 1 Connection 2 Automatic Transfer Controller User Interface 3 Menus 4 Remote Control Software Manual Edition 01/2010 A5E02469028-01 Legal information Warning notice system This manual

More information

Datasheet - SRB 301LC/B-24V

Datasheet - SRB 301LC/B-24V 27.01.2016-00:27:16h Datasheet - SRB 301LC/B-24V Guard door monitors and Safety control modules for Emergency Stop applications / General Purpose safety controllers (Series PROTECT SRB) / SRB 301LC/B Fit

More information

SITOP UPS1600 under STEP 7 V13. SITOP UPS1600 under STEP 7 V13. Introduction. Safety notes. Description. Assigning the IP address

SITOP UPS1600 under STEP 7 V13. SITOP UPS1600 under STEP 7 V13. Introduction. Safety notes. Description. Assigning the IP address Introduction 1 Safety notes 2 Description 3 Assigning the IP address 4 SITOP UPS1600 under STEP 7 V13 Getting Started Installing and configuring the SITOP UPS1600 in STEP 7 5 V13 Parameterizing the SITOP

More information

Safety relay emergency stop/protective door, 24VDC/AC, 3 enabling paths

Safety relay emergency stop/protective door, 24VDC/AC, 3 enabling paths DATASHEET - ESR5-NO-31-24VAC-DC Delivery program Safety relay emergency stop/protective door, 24VDC/AC, 3 enabling paths Part no. ESR5-NO-31-24VAC-DC Catalog No. 118702 EL-Nummer (Norway) 4133318 Product

More information

ST (6ES7522-1BH00-0AB0)

ST (6ES7522-1BH00-0AB0) SIMATIC S7-1500 Digital output module DQ 16x24VDC/0.5A ST (6ES7522-1BH00-0AB0) Manual Edition 07/2014 Answers for industry. DQ 16x24VDC/0.5A ST Digital Output Module (6ES7522-1BH00-0AB0) SIMATIC S7-1500/ET

More information

Positive-guided relay outputs: 3 safety contacts (N/O), instantaneous. 1 auxiliary contact (N/C), instantaneous

Positive-guided relay outputs: 3 safety contacts (N/O), instantaneous. 1 auxiliary contact (N/C), instantaneous Gertebild Bildunterschrift Two-hand control device for safety circuits Approvals Zulassungen Unit features Gertemerkmale Positive-guided relay outputs: 3 safety contacts (N/O), instantaneous 1 auxiliary

More information

First Steps in Commissioning CPU. 31xC: Positioning with digital output SIMATIC

First Steps in Commissioning CPU. 31xC: Positioning with digital output SIMATIC First Steps in Commissioning CPU 31xC: Positioning with digital output Introduction 1 Preparation 2 SIMATIC S7-300 First Steps in Commissioning CPU 31xC: Positioning with digital output Learning units

More information

Safety-related controls SIRIUS Safety Integrated

Safety-related controls SIRIUS Safety Integrated Functional Example CD-FE-I-018-V30-EN Safety-related controls SIRIUS Safety Integrated with monitored start up to SIL 1 acc. to IEC 62061 and PL c acc. to ISO 13849-1 with a SIRIUS safety relay 3TK28 with

More information

Phone: Fax: Web: -

Phone: Fax: Web:  - In automated systems, sensors and actuators must interact with one another functionally and safely. The necessary coordination is performed by the programmable Safety Controller. The controller monitors

More information

SIMADYN D Digital Control System. Fiber-Optic Rack Coupling CS12. User Manual. Edition DK No

SIMADYN D Digital Control System. Fiber-Optic Rack Coupling CS12. User Manual. Edition DK No SIMADYN D Digital Control System User Manual Fiber-Optic Rack Coupling CS12 Edition 05.95 DK No. 237741 User Manual, Fiber-Optic Rack Coupling CS12 Edition Status 1 Fiber-Optic Rack Coupling CS12 05.95

More information

Monitoring technique. VARIMETER Voltage relay MK 9064N, MH 9064

Monitoring technique. VARIMETER Voltage relay MK 9064N, MH 9064 Monitoring technique VARIMETER Voltage relay MK 9064N, MH 9064 0269462 Your Advantages Preventive maintenance For better productivity Quicker fault locating Precise and reliable Min-, Max. value or window

More information

Product Information Mixed. Configuration ET 200SP / ET 200AL SIMATIC. ET 200SP Product Information Mixed Configuration ET 200SP / ET 200AL.

Product Information Mixed. Configuration ET 200SP / ET 200AL SIMATIC. ET 200SP Product Information Mixed Configuration ET 200SP / ET 200AL. Product Information Mixed Configuration ET 200SP / ET 200AL SIMATIC ET 200SP Product Information Mixed Configuration ET 200SP / ET 200AL Product Information Preface Application planning 1 Mounting 2 Connection

More information

Drive Technology \ Drive Automation \ System Integration \ Services. Manual. MOVITRAC MC07B Functional Safety

Drive Technology \ Drive Automation \ System Integration \ Services. Manual. MOVITRAC MC07B Functional Safety Drive Technology \ Drive Automation \ System Integration \ Services Manual MOVITRAC Functional Safety Edition 12/2011 19396414 / EN SEW-EURODRIVE Driving the world Contents Contents 1 General Information...

More information

Monitoring Relays. 3UG Monitoring Relays for Electrical and Additional Measurements. Line monitoring 7/61. Overview

Monitoring Relays. 3UG Monitoring Relays for Electrical and Additional Measurements. Line monitoring 7/61. Overview Siemens AG 200 Monitoring Relays Line monitoring Overview Solid-state line monitoring relays provide maximum protection for mobile machines and plants or for unstable networks. Network and voltage faults

More information

Making Hazardous Operations Safe and Productive

Making Hazardous Operations Safe and Productive NEW Safety Guard Switching Unit G9SX-GS Making Hazardous Operations Safe and Productive Making Hazardous Operations Safe and Productive This new addition to the model of Flexible Safety Unit G9SX series

More information

BaseUnits (6ES7193-6BP.../3RK1908-0AP00 ) SIMATIC. ET 200SP BaseUnits. Preface. Guide to the documentation 1. Product overview 2

BaseUnits (6ES7193-6BP.../3RK1908-0AP00 ) SIMATIC. ET 200SP BaseUnits. Preface. Guide to the documentation 1. Product overview 2 BaseUnits (6ES7193-6BP.../3RK1908-0AP00 ) SIMATIC ET 200SP BaseUnits (6ES7193-6BP.../3RK1908-0AP00 ) Manual Preface Guide to the documentation 1 Product overview 2 BaseUnits for I/O modules 3 BaseUnits

More information

SIRIUS Safety Integrated. Modular safety system 3RK3

SIRIUS Safety Integrated. Modular safety system 3RK3 Functional Example CD-FE-I-045-V10-EN SIRIUS Safety Integrated Modular safety system 3RK3 EMERGENCY STOP with Protective Door Monitoring according to category 2 in EN 954-1, with MSS Basic Comments "Safety

More information

Positive-guided relay outputs: 3 safety contacts (N/O), instantaneous. 1 auxiliary contact (N/C), instantaneous

Positive-guided relay outputs: 3 safety contacts (N/O), instantaneous. 1 auxiliary contact (N/C), instantaneous Two-hand control unit for press controllers and safety circuits Approvals Unit features Positive-guided relay outputs: 3 safety contacts (N/O), instantaneous 1 auxiliary contact (N/C), instantaneous 1

More information

SITOP UPS1600 under STEP 7 V5. SITOP UPS1600 under STEP 7 V5. Introduction. Safety notes. Description 3. Assigning the IP address

SITOP UPS1600 under STEP 7 V5. SITOP UPS1600 under STEP 7 V5. Introduction. Safety notes. Description 3. Assigning the IP address Introduction 1 Safety notes 2 Description 3 Getting Started Assigning the IP address 4 Installing and configuring the SITOP UPS1600 in STEP 7 5 V5 Parameterizing the SITOP UPS1600 6 Legal information Warning

More information

S7-300 Programmable Controller

S7-300 Programmable Controller S7-300 Programmable Controller This description belongs to the following documentation packages with the order numbers given: S7 300 Programmable Controller 6ES7 398 8AA02 8BA0 ET 200M Distributed I/O

More information

Operating instructions. Switching amplifier DN0210 DN / / 2015

Operating instructions. Switching amplifier DN0210 DN / / 2015 Operating instructions Switching amplifier DN0210 DN0220 UK 80011079 / 00 01 / 2015 Contents 1 Preliminary note...4 1.1 Symbols used...4 1.2 Warning signs used...4 2 Safety instructions...5 2.1 General...5

More information

Safe timer relay/contact expansion modules

Safe timer relay/contact expansion modules Contact expander module for increasing the number of available contacts, Pulse-on timer relay for step-by-step control of movement sequences, Delay-on energisation timer for unlocking an interlock with

More information

SIMATIC. Communications processor CP 340 first commissioning steps. Getting Started 04/2005 A5E

SIMATIC. Communications processor CP 340 first commissioning steps. Getting Started 04/2005 A5E SIMATIC Communications processor Getting Started 04/2005 A5E00442606-01 Safety Guidelines This manual contains notices you have to observe in order to ensure your personal safety, as well as to prevent

More information

HR1S-AC Safety Relay Modules

HR1S-AC Safety Relay Modules HRS-AC Relay Modules Transistor output provided. Removable terminal block (HRS-AC52P) allows for easy module replacement. Fault diagnosis function with dual safety circuits. Internal relay operations can

More information

PSR-PC50. SIL 3 coupling relay for safety-related switch on. Data sheet. 1 Description

PSR-PC50. SIL 3 coupling relay for safety-related switch on. Data sheet. 1 Description SIL 3 coupling relay for safety-related switch on Data sheet 105818_en_01 PHOENIX CONTACT 2014-08-18 1 Description The PSR-PC50 SIL coupling relay can be used for power adaptation and electrical isolation

More information

SENTRON. Protective devices Selectivity for 3VA molded case circuit breakers. Introduction. Selectivity - terms and definitions

SENTRON. Protective devices Selectivity for 3VA molded case circuit breakers. Introduction. Selectivity - terms and definitions Introduction 1 Selectivity - terms and definitions 2 SENTRON Methods of implementing selectivity using circuit breakers 3 Protective devices Selectivity for 3VA molded case circuit breakers Configuration

More information

COMOS. Platform Class documentation RevisionMaster_dll. Class: RevisionInfo 1. Class: RevisionMaster 2. Programming Manual

COMOS. Platform Class documentation RevisionMaster_dll. Class: RevisionInfo 1. Class: RevisionMaster 2. Programming Manual Class: RevisionInfo 1 Class: RevisionMaster 2 COMOS Platform Class documentation RevisionMaster_dll Programming Manual 03/2017 V10.2.1 A5E39859923-AA Legal information Warning notice system This manual

More information

Operating instructions. Speed monitor D / / 2014

Operating instructions. Speed monitor D / / 2014 Operating instructions Speed monitor D200 80005257 / 00 05 / 2014 Contents 1 Preliminary note...4 1.1 Symbols used...4 1.2 Warning signs used...4 2 Safety instructions...5 2.1 General...5 2.2 Target group...5

More information

Datasheet SRB301ST 24V (V.2)

Datasheet SRB301ST 24V (V.2) 26.10.2016 05:03:31h Datasheet SRB301ST 24V (V.2) Guard door monitors and Safety control modules for Emergency Stop applications / General Purpose safety controllers (Series PROTECT SRB) / SRB301ST Suitable

More information

Operating instructions. Standstill monitor A / / 2011

Operating instructions. Standstill monitor A / / 2011 Operating instructions Standstill monitor A300 UK 1 2 3 4 5 6 7 8 7390337 / 01 02 / 2011 1 2 3 4 5 6 7 8 switchpoint min max pulse/min power Made in Germany ifm electronic gmbh D 45127 Essen func. I II

More information

Industrial Controls. Motor management and control devices SIMOCODE pro. Introduction 1. Configuring a reversing starter. List of abbreviations

Industrial Controls. Motor management and control devices SIMOCODE pro. Introduction 1. Configuring a reversing starter. List of abbreviations Introduction 1 Configuring a reversing starter 2 Industrial Controls A List of abbreviations Motor management and control devices Getting Started 05/2018 A5E40507294002A/RS-AB/002 Legal information Warning

More information

Application Technique. Safety Function: Safety Camera with E-stop

Application Technique. Safety Function: Safety Camera with E-stop Application Technique Safety Function: Safety Camera with E-stop Products: Guardmaster Dual-input Safety Relay, Guardmaster SC300 Safety Camera Safety Rating: PLd, Cat. 3 to EN ISO 13849-1: 2008 2 Safety

More information