1 . General. This procedure describes Pretium EDGE Tap Modules, which are available for both multimode and single mode applications. Compatible with all Pretium EDGE rack-mountable connector housings, TP modules have twelve front-mounted shuttered LC adapters and two connectors in back (Figure ). STNDRD RECOMMENDED PROCEDURE 00- ISSUE OCTOER 0 PGE OF Pretium EDGE Tap Module Installation and Testing SRP 00-, Issue related literature SRP-00-, Pretium EDGE Solution SRP-00-, Multifiber Connector and Port Cleaning with the TKT-CLEN-MFC-M kit table of contents. General.... Precautions.... Tools and Materials.... Connector and dapter Cleaning.... Calculating System Loss.udgets.... The Functionality of the Tap Module Splitters.... Installing Pretium EDGE Tap Modules.... Referencing the Test Equipment for a Tap Module.... Testing Pretium EDGETap Modules.... The module contains fiber optic splitters which divide the incoming optical signals into two outputs, one for live link traffic and one for monitoring. The monitor traffic is routed via the TP -labeled connector to a monitoring device which filters the data and sends it to various software tools for analysis, where it is then viewed in application-layer software for security threats, performance issues, or system optimization. IMPORTNT: Please note that Tap module systems have two outputs for each input, which may require two power meters, and depending on the system configuration, possibly require an additional craftsperson in another location.. If this procedure is reissued, a summary of the changes will appear in this paragraph. HP-0 MDE IN MEXICO US PTENT NO. M : 0 LIVE WRRNTY TP Figure PRETERMINTED SYSTEMS CLES CONNECTORS CLE SSEMLIES HRDWRE TOOL KITS ND CCESSORIES TEST EQUIPMENT SPLICE EQUIPMENT FN-OUT KITS

2 . Precautions. Laser Precautions \WRNING: DO NOT use magnifiers in the presence of laser light - diffused laser light can cause eye damage of focused with optical instruments. Never look directly into the end of a connector that may be carrying laser light. Should accidental eye exposure to laser light be suspected, arrange for an eye examination immediately. Cable Handling Precautions NOTE: Fiber optic cable is sensitive to excessive pulling, bending, and crushing forces. Do not bend cables more sharply than their minimum recommended bend radius. Do not apply more pulling force to the cable assembly than specified. Do not crush the cable or allow it to kink. Doing so may cause damage that can alter the transmission characteristics of the cable; the cable may have to be replaced.. Tools and Materials. The following tools and materials are required for this procedure: Two () power meters with LC port adapters Two () LC-LC jumpers One () SC-LC jumper for the light source One () LC-LC adapter Light source One to LC harness LC port cleaner (p/n CLENER-PORT-LC) Connector and Port Cleaning Tool (p/n 0-0) For multimode applications: Mandrel wrap suitable for your cable type (available in p/n OTS-COMOMN). Connector and dapter Cleaning. Cleaning the LC adapters with an LC port cleaner before each mating is recommended (Figure ). HP-0 Figure. The use of an Connector and Port Cleaning Tool to clean connectors and ports before each mating is recommended (Figure ). HP-0 Figure STNDRD RECOMMENDED PROCEDURE 00- ISSUE OCTOER 0 PGE OF

3 . Calculating System Loss udgets. This section describes how to calculate the loss budgets of a system using a Pretium EDGE Tap Module. Note that you will need to calculate one loss budget for the LIVE system (Figure ) and two different loss budgets for the Tap output (Figure and ). Table indicates the system loss values of the system components: Multimode Fiber Single Mode Fiber OM Ultra-bendable optimized 0µm end-improved single Mode (0 nm) (0 nm) Component Loss, max (d) Loss, max (d) mated loss loss Splitter 0/0 (d).. Splitter 0/0 (d). /..0 /.0 Insertion loss specifications when mated to other system components of a like performance specification Table.. To calculate the system losses, add the loss values of the components as illustrated in the examples shown in Figures,, and. udget loss for a LIVE multimode system using OM fiber and 0 /0 splitters: =. d fiber loss 0/0 splitter mated mated HP-0 0 MDE IN MEXICO Tap Module WRRNTY TP LIVE Note: Fiber loss depends on length of system PnP Module Pretium EDGE Module WRRNTY MDE IN MEXICO 0 Far end Figure STNDRD RECOMMENDED PROCEDURE 00- ISSUE OCTOER 0 PGE OF

4 udget loss for a Tap port test harness multimode system using OM fiber and 0 /0 splitters: =. d fiber loss 0. 0/0 splitter. mated 0 MDE IN MEXICO WRRNTY TP LIVE 0. Note: Fiber loss depends on length of system Tap Module Tap port test harness 0. HP-0 Figure udget loss for a Far end to Tap Port harness multimode system using OM fiber and 0 /0 splitters: =. d fiber loss 0/0 splitter mated mated MDE IN MEXICO Tap Module Tap port test harenss WRRNTY TP LIVE mated 0. Note: Fiber loss depends on length of system 0. PnP Module Pretium EDGE Module WRRNTY MDE IN MEXICO 0 Far end HP-0 Figure STNDRD RECOMMENDED PROCEDURE 00- ISSUE OCTOER 0 PGE OF

5 . The Functionality of the Tap Module Splitters Directionality. In simplest terms, the splitters inside a Tap module act like a divider of a one-way traffic flow in this case, light. The even-numbered LC connectors in a Tap module serve only for source input and their traffic is split between the LIVE and TP outputs (Figure, top). Input into LC # 0 Tap Output on Fiber WRRNTY TP LIVE LIVE output TP Output In the same fashion, the Tap module s oddnumbered LC connectors receive live traffic from the LIVE input port. The input traffic from the LIVE input port is split between the LIVE LC odd fibers and the TP port (Figure, bottom). Tables and in Section provide a full representation of the source and output positions Live output from LC # HP-0 0 Tap Output on Fiber WRRNTY TP LIVE LIVE source TP Output Figure. Tap modules therefore must be tested with directionality in mind. The source must be always connected to the input of the splitter and the meter must be connected to the output of the splitter. Connecting a source to the output of a splitter will result in high attenuation. Wavelength Considerations. The splitters on multimode modules are optimized for 0 nm VCSEL (Vertical-cavity Surface-emitting Lasers), thus when testing multimode systems, use only the 0 nm wavelength.. Single mode systems may be tested at both 0 and 0 nm. STNDRD RECOMMENDED PROCEDURE 00- ISSUE OCTOER 0 PGE OF

6 . Installing a Pretium EDGE Tap Module. Pretium EDGE Tap modules are installed just like their normal Pretium EDGE module counterparts. Refer to the Installation chapter in SRP-00-, Pretium EDGE Solution, for complete instructions. This procedure covers module installation, trouble shooting, and other module-related topics as well.. Install the Tap module and its Tap harness into your system housing (this procedure illustrates an to LC harness).. Referencing the Test Equipment for a Tap Module. Start by powering on the source and meter and allowing a minimum of minutes for them to warm up and stabilize. For multimode systems: set the unit to the 0 nm wavelength. For single mode systems: Set the unit to auto-switch between 0 and 0 nm wavelengths.. To reference the source and two meters: Step : Clean and insert the SC-end of the SC to LC jumper (Reference Jumper no., or RJ) into the output of the light source. Step : Clean and insert the LC end of RJ jumper into the LC port adapter of Meter no. (M) (Figure ). For multimode only: Wrap the jumper times and secure it in a mm mandrel with tape (standard 0 µm multimode procedure). Step : Step : Verify that RJ is acceptable at your system s wavelength(s) and reference this power to 0.00 d. Disconnect and move the meter-end LC of RJ to Meter no. (M) and repeat step. Disconnect M after this step. HP-0 mm mandrel wrap for multimode only Light Source (Tx) Reference Jumper no. RJ 0.00 Meter no. (RX) M Meter no. (RX) M Figure Step : Clean and insert the LC end of RJ into an LC adapter. STNDRD RECOMMENDED PROCEDURE 00- ISSUE OCTOER 0 PGE OF

7 Step : Clean and install an LC to LC jumper- Reference Jumper no. (RJ) into M and the LC adapter (Figure ). multimode only LC adapter Step : Verify that the RJ/ RJ mated are acceptable with a loss 0. d. RJ Reference Jumper no. RJ Step : Disconnect RJ s LC connector from the LC adapter and protect it with a clean dust cap until you are ready to start the system testing. Light Source HP-0 0. d M Figure Dust cap Step : Clean and install an LC to LC jumper- Reference Jumper no. (RJ) into M and the LC adapter (Figure 0). multimode only RJ LC adapter RJ Step 0: Verify that the RJ/RJ mated are acceptable with a loss 0. d. RJ Step : Disconnect RJ s LC connector from the LC adapter and protect it with a clean dust cap. Light Source HP-00 M d M Figure 0 Step : Leave the LC adapter on the end of RJ for the remainder of this procedure since it will be required for mating to the TP port test harness.. Referencing is now complete. Move the Light Source and RJ to the front of the Tap module; move M, RJ, and the LC adapter to the end of the Tap harness; and move M and RJ to the Pretium EDGE modules at the far end of the system (See Figure ). IMPORTNT: From this step on, do NOT the connectors on either the Light Source or meter port adapters. STNDRD RECOMMENDED PROCEDURE 00- ISSUE OCTOER 0 PGE OF

8 . Testing Pretium EDGE Tap Modules. Table provides a complete guide to the testing sequence for testing with the light source at the Tap module () and a meter at Module, or the Far end of the system shown in Figure. Source LC Position at ' Module LC Position Meter no. -TP Port Test Harness To begin testing a Tap module (Figure ): Table Step : Step : Step : Install the Light Source/RJ LC connector into LC number port of the Tap module. Install RJ s LC connector into the number port of the Pretium Edge module (Module in Figure ). Install LC connector number from the Tap port test harness into the LC adapter on the end of RJ. Far end multimode only 0 WRRNTY RJ 0 MDE IN MEXICO Tap Module WRRNTY TP LIVE Link under test Pretium EDGE Module PnP Module MDE IN MEXICO 0.00 d RJ Tap port test harness M Light Source RJ HP-0 M 0.00 d Figure Step : Save or record the first fiber s measurements. The reading will be the total system loss. STNDRD RECOMMENDED PROCEDURE 00- ISSUE OCTOER 0 PGE OF

9 . Table provides a complete guide to the testing sequence for testing with the Light Source at the module ( Far end ) and a meter at Tap module ( ) of the system as shown in Figure. Source LC Position at Meter no. LC Position at : Meter no. -TP Port Test Harness Table. To test the odd-numbered ports at the front of the Tap Module, switch the Near and Far locations of the Light Source/RJ and M/RJ. t the end of the Tap cable assembly, move the LC adapter on M/RJ to connector number (Figure ). 0 Far end multimode only WRRNTY RJ 0 MDE IN MEXICO WRRNTY TP LIVE Link under test PnP Module Pretium EDGE Module MDE IN MEXICO RJ Tap Module 0.00 d Tap port test harness Light Source M RJ and adapter HP d M Figure. To complete the testing of the first Tap module, save or record each fiber s measurements as you follow the sequence shown in Table.. Repeat the steps in this section on the remaining Tap modules. Corning Cable Systems LLC PO ox Hickory, NC 0-0 US FX International Corning Cable Systems reserves the right to improve, enhance, and modify the features and specifications of Corning Cable Systems products without prior notification. Pretium EDGE is a registered trademark of Corning Cable Systems rands, Inc. is a registered trademark of USConec, Ltd. ll other trademarks are the properties of their respective owners. Corning Cable Systems is ISO 00 certified. 0 Corning Cable Systems. ll rights reserved. Published in the US. STNDRD RECOMMENDED PROCEDURE 00- ISSUE OCTOER 0 PGE OF

Mini Wall-mount Building Terminal (WBM)

Mini Wall-mount Building Terminal (WBM) Corning Cable Systems Standard Recommended Procedure (SRP) 003-516 Issue 2, October 2004 Page 1 of 8 Contents Figure 1 WBM 1. General...1 2. Description...2 3. Precautions...2 4. Tools and Materials...3

More information

Corning Distance and Link-Loss Budgets for the Cisco 40GbE BiDi Transceiver

Corning Distance and Link-Loss Budgets for the Cisco 40GbE BiDi Transceiver 9 0 Corning Distance and Link-Loss Budgets for the Cisco 0GbE BiDi Transceiver This paper discusses the following topics for the Cisco bidirectional (BiDi) transceiver: Cisco quad small-form-factor pluggable

More information

Pretium EDGE FX Solutions

Pretium EDGE FX Solutions Pretium EDGE FX Solutions for Enterprise Data Centers and Storage Area Networks Corning Cable Systems Pretium EDGE FX Solutions create a fixed-tray fiber optic tip-to-tip solution for Data Centers and

More information

LTK-400 Series Optical Sources, Meters and Kits Without Data Storage Capabilities

LTK-400 Series Optical Sources, Meters and Kits Without Data Storage Capabilities Features and Benefits High output power and calibrated wavelengths Easy to use, unparalleled performance Rugged handheld design Capable of enduring harsh testing environments Product warranty and calibration

More information

Pretium EDGE HD Solutions A LANscape Pretium Solutions Product

Pretium EDGE HD Solutions A LANscape Pretium Solutions Product Pretium EDGE HD Solutions for Enterprise Data Centers and Storage Area Networks Corning Pretium EDGE HD solutions create a fiber optic tip-to-tip solution for data centers and storage area networks (SANs)

More information

Sheath Removal of 3456-Fiber RocketRibbon Extreme-Density Cable

Sheath Removal of 3456-Fiber RocketRibbon Extreme-Density Cable Sheath Removal of 3456-Fiber RocketRibbon Extreme-Density Cable P/N 004-279-AEN Issue 1 related literature Search www.corning.com/opcomm. Click on Resources/Standard Recommended Procedures. 004-098 Instruction,

More information

Plug & Play Universal Systems

Plug & Play Universal Systems 100G Ready performance Maximum skew of 0.75 ns Product is assured to work in parallel optic applications for Ethernet, Fibre Channel and InfiniBand MTP /LC Duplex Module TRAINING SPLICE EQUIPMENT High-density

More information

Plug & Play Universal Systems

Plug & Play Universal Systems Corning Cable Systems Plug & Play Universal Systems create a fiber optic tip-to-tip solution for data centers and storage area networks (SANs) consisting of housings, modules, panels, harnesses, trunks

More information

Pretium Rack-mountable 1U Housing Hardware

Pretium Rack-mountable 1U Housing Hardware revision history Issue Date Reason for Change table of contents STANDARD RECOMMENDED PROCEDURE 003-649 ISSUE 5 JANUARY 2009 PAGE 1 OF 10 Pretium Rack-mountable 1U Housing Hardware p/n 003-649, Issue 5

More information

OTS-400 Series Optical Sources, Meters, Testers and Kits with Data Storage Capabilities A LANscape Solutions Product

OTS-400 Series Optical Sources, Meters, Testers and Kits with Data Storage Capabilities A LANscape Solutions Product Applications Testing and troubleshooting of various telecommunication networks Description The Corning Cable Systems OTS-400 Series of intelligent and versatile optical meters, sources and testers offers

More information

UniCam Connector Installation Tool Kits

UniCam Connector Installation Tool Kits features and benefits Terminates single-mode and multimode fibers Convenient carrying case Continuity test set (CTS) Visual feedback signal (TKT-UNICAM-PFC) Pretium Cleaver (FBC-05) SPECIFICATION SHEET

More information

Closet Connector Housing (CCH) Splitter Module

Closet Connector Housing (CCH) Splitter Module Closet Connector Housing Features and Benefits Gen III FTTx Splitter with bracket to fit LANscape Solutions housings Enables passive optical network (PON) design with existing LANscape Solutions housings

More information

OTS-400 Series Optical Meters, Sources and Testers A LANscape Solutions Product

OTS-400 Series Optical Meters, Sources and Testers A LANscape Solutions Product OTSK-4MDSD Specs Provided by www.aaatesters.com OTS-400 Series Applications Installation, testing and troubleshooting of LAN, telco, CATV and FTTx networks Description The OTS-400 Series of intelligent

More information

Plug & Play Universal Low-Loss Systems A LANscape Pretium Solutions Product

Plug & Play Universal Low-Loss Systems A LANscape Pretium Solutions Product Applications Data Center LAN/SAN Enterprise Building Backbone -to-the-desk Description Plug & Play Universal Systems are preterminated optical fiber cabling systems designed to dramatically improve performance

More information

ONE SD-LAN Wall Mount Splitter Housing (1LAN-SPLT C)

ONE SD-LAN Wall Mount Splitter Housing (1LAN-SPLT C) CMA-477-AEN 1 General Figure 1 STANDARD RECOMMENDED PROCEDURE 000-000-AEN ISSUE 1 MARCH 2018 I Page 1 2 Carton Contents Installation instruction Wall Mount Splitter housing Cable installation hardware

More information

FEB 2017 Rev F. Verify that all cable assemblies are in good condition.

FEB 2017 Rev F. Verify that all cable assemblies are in good condition. EB 2017 Rev MT RJ Test Kits (listed in igure 1) contain the cable assemblies and adapters needed to field test MT RJ optical fiber system attenuation and polarity using optical power meters having either

More information

OptiSheath Advantage Sealed 4-, 6-, 8- and 12-Port Multiport Terminals

OptiSheath Advantage Sealed 4-, 6-, 8- and 12-Port Multiport Terminals OptiSheath Advantage Sealed 4-, 6-, - and -Port Multiport Terminals P/N 206-33 Issue related literature 006-1 006-156 023_NAFTA_AEN 025_NAFTA_AEN 1. Instruction, Optical Access Connector Cleaning Kit Instruction,

More information

Plug & Play AnyLAN Systems A LANscape Solutions Product

Plug & Play AnyLAN Systems A LANscape Solutions Product Description Corning Cable Systems Plug & Play AnyLAN Systems is a preterminated local area network cabling solution that can be installed up to 50 percent faster per splice or termination point than traditional

More information

OTS-600 Series Optical Sources, Meters, Testers and Kits with Data Storage Capabilities

OTS-600 Series Optical Sources, Meters, Testers and Kits with Data Storage Capabilities features and benefits Large LCD screen and soft key menus Source and meter in one unit Auto wavelength switching and detection USB data ports OTS-600 Series Light Source and Power Meter Photo LAN1193 Ease

More information

Polymer Coated Fiber Cable (PCF)

Polymer Coated Fiber Cable (PCF) Polymer Coated Fiber Cable (PCF) Panduit has introduced a Polymer Coated Fiber (PCF) to their fiber cable offering available in 50µm and 62.5µm core diameters. Along with this cable having a stronger durability

More information

with Fiber Management Bar

with Fiber Management Bar Issue 1, June 2014 SYSTIMAX 1100A Angled Fiber Termination Panel with Fiber Management Bar General The SYSTIMAX 1100A angled fiber termination panel is a 19 wide x 1.75 high (483mm x 44mm) 1U panel designed

More information

Enabling Rapid Multitenant Data Centre (MTDC) Connections

Enabling Rapid Multitenant Data Centre (MTDC) Connections Enabling Rapid Multitenant Data Centre (MTDC) Connections At Corning, we understand the challenges associated with outsourced facilities, whether you re an MTDC/ cloud provider or an enterprise client.

More information

Centrix Platform. Features and Benefits

Centrix Platform. Features and Benefits Features and Benefits Supports 4,320 LC or 2,880 SC ports per frame Saves space through increased port density Available in rear cable acces Designed in compliance with GR-449-CORE, Issue 3 standards Modular

More information

PM-212-SI3 Pocket Optical Power Meter INSTRUCTION MANUAL

PM-212-SI3 Pocket Optical Power Meter INSTRUCTION MANUAL PM-212-SI3 Pocket Optical Power Meter INSTRUCTION MANUAL Revision 2.4 is the registered trademark of OPTOKON, a.s. Other names and trademarks mentioned herein may be the trademarks of their respective

More information

Pretium EDGE Solutions Trunk Cable, 50 µm multimode (OM3)

Pretium EDGE Solutions Trunk Cable, 50 µm multimode (OM3) Pretium EDGE 133 Pretium EDGE Solutions Trunk Cable, 50 Pretium EDGE Solutions trunk cables utilize the MTP Connector, a 12 -fiber push/pull optical connector with a footprint similar to the SC simplex

More information

Wall-Mountable Connector Housings (WCH)

Wall-Mountable Connector Housings (WCH) Features and Benefits Interconnect and cross-connect capabilities Ideal for field splicing and connectorization Accepts CCH cassettes, panels and modules Variety of preterminated and field-installable

More information

Anaerobic-Cure Connectors

Anaerobic-Cure Connectors Features and Benefits Quick-cure epoxy No lamps or ovens needed Minimal tools and no index-matching gel Low installation cost Hand polished for minimum insertion loss Reliability and optical performance

More information

3 Angled Connector Housing (MC) Installation

3 Angled Connector Housing (MC) Installation Angled Connector Housing (MC) Installation Instructions July 1999 4-7047-2554-7 MC Frame Figure 1 Angled Connector Housing (MC) General This document describes the installation of the stubbed MC Angled

More information

Plug & Play Universal Trunks

Plug & Play Universal Trunks 1 1 22.88 115 0 Plug & Play 0 Plug & Play Universal Trunks Plug & Play Universal Systems MTP Trunks provide the backbone of the Plug & Play System. With non - pinned MTPs on both ends of the cable, these

More information

CLOSET CONNECTOR HOUSING

CLOSET CONNECTOR HOUSING CLOSET CONNECTOR HOUSING -01U CCH-02U CCH-03U CCH-04U CCH-01U CCH-02U CCH-03U CCH-04U CCH-01U CCH-02U CCH-03U CCH-04U -01U CCH-02U CCH-03U CCH-04U CCH-01U CCH-02U CCH-03U CCH-04U CCH-01U CCH-02U CCH-03U

More information

5100 Series. Fiberlink. 10/100/1000 Base-T Etheret over one or two single mode or multimode fibers. User s Manual

5100 Series. Fiberlink. 10/100/1000 Base-T Etheret over one or two single mode or multimode fibers. User s Manual Communications Specialties Fiberlink 5100 User s Manual Transmit 10/100/1000 Base-T Ethernet over one or two single mode or multimode fibers. The 5100 Series is full-featured with auto-sensing 10/100/1000

More information

Closet Connector Housings (CCH)

Closet Connector Housings (CCH) Closet Connector Housings (CCH) Designed based on thousands of hours of customer feedback, Corning closet connector housings (CCHs) offer more than two dozen innovative features that make installation

More information

EDGE Solutions Hybrid Trunk, OM4, Low- Loss, MTP to LC Duplex Uniboot, 24 fibres

EDGE Solutions Hybrid Trunk, OM4, Low- Loss, MTP to LC Duplex Uniboot, 24 fibres EDGE MTP trunks are preterminated cables with 12 -fibre MTP connectors or LC duplex connectors on either side. The trunks build up the major skeleton of the passive network infrastructure, and thanks to

More information

10-GbE XFP and SFP+ Transceiver Modules

10-GbE XFP and SFP+ Transceiver Modules LXP-10G-MMLC LXP-10G-SMCL10 LXP-10G-CX4 Product Data Sheet 10-GbE XFP and SFP+ Transceiver Modules Overview The 10-GbE XFP and SFP+ Transceiver Modules enable you to take advantage of 10-GbE connectivity.

More information

MT-RJ OPTICAL FIBER SYSTEMS TESTING. Field Testing Made Easy

MT-RJ OPTICAL FIBER SYSTEMS TESTING. Field Testing Made Easy MT-RJ OPTICL FIER SYSTEMS TESTING Field Testing Made Easy TLE of CONTENTS Introduction...3 Recommended Test Components...4 Testing With Dual Sources and Detectors...5 Testing with a One Port Test Set...9

More information

4 Channel 4~20mA/0~10VDC Analog Data Fiber Link System

4 Channel 4~20mA/0~10VDC Analog Data Fiber Link System USER GUIDE RLH Industries, Inc. The leader in rugged fiber optic technology. U-022 2017A-0330 4 Channel 4~20mA/0~10VDC Analog Data Fiber Link System SYSTEM INSTALLATION INFORMATION Description The 4 Channel

More information

OLS Series Light Sources, OPM Series Optical Power Meters, and Related Test Kits User s Guide

OLS Series Light Sources, OPM Series Optical Power Meters, and Related Test Kits User s Guide OLS Series Light Sources, OPM Series Optical Power Meters, and Related Test Kits User s Guide 2004-2009, AFL Telecommunications, all rights reserved. COM4-00-1001 Revision E, 2009-06-16 Specifications

More information

4 Channel Contact Closure DIN Fiber Link System

4 Channel Contact Closure DIN Fiber Link System USER GUIDE RLH Industries, Inc. The leader in rugged fiber optic technology. U-027 2017A-0420 4 Channel Contact Closure DIN Fiber Link System SYSTEM INSTALLATI INFORMATI Description The 4 Channel Contact

More information

10/100 Ethernet Fiber Link Card System

10/100 Ethernet Fiber Link Card System USER GUIDE RLH Industries, Inc. The leader in rugged fiber optic technology. U-016 2017A-0412 10/100 Ethernet Fiber Link Card System SYSTEM INSTALLATI INFORMATI Description The 10/100 Ethernet Fiber Link

More information

FlexPOD. Fiberlink. Flexible Passive Optical Distributor. User s Manual. Artel Video Systems Fiberlink FlexPOD. Fiberlink FlexPOD is a

FlexPOD. Fiberlink. Flexible Passive Optical Distributor. User s Manual. Artel Video Systems Fiberlink FlexPOD. Fiberlink FlexPOD is a Artel Video Systems Fiberlink FlexPOD User s Manual Fiberlink FlexPOD is a configurable passive optical signal distribution system to create up to 4 different and independent optical coarse wave division

More information

Solutions FOR DATA CENTERS AND STORAGE AREA NETWORKS

Solutions FOR DATA CENTERS AND STORAGE AREA NETWORKS Solutions FOR DATA CENTERS AND STORAGE AREA NETWORKS Xtreme12 is Opticonx s Base-12 cabling solution for easy migration of 10/25/40/50/100 and 400G parallel optics deployments in the data center. This

More information

Power Over Fiber USER GUIDE. SYSTEM INSTALLATION INFORMATION Description. The leader in rugged fiber optic technology. RLH Industries, Inc.

Power Over Fiber USER GUIDE. SYSTEM INSTALLATION INFORMATION Description. The leader in rugged fiber optic technology. RLH Industries, Inc. USER GUIDE RLH Industries, Inc. The leader in rugged fiber optic technology. U-145 2018A-0119 Power Over Fiber SYSTEM INSTALLATI INFORMATI Description Our patented Power Over Fiber (PoF) system provides

More information

PM-212-MPO Pocket Optical Power Meter INSTRUCTION MANUAL

PM-212-MPO Pocket Optical Power Meter INSTRUCTION MANUAL PM-212-MPO Pocket Optical Power Meter INSTRUCTION MANUAL Revision 1.2 is the registered trademark of OPTOKON, a.s. Other names and trademarks mentioned herein may be the trademarks of their respective

More information

Passive Fiber Installation Guide October 2015

Passive Fiber Installation Guide October 2015 12 40Gbps Passive MPO TPs Passive Fiber October 2015 21 40Gbps BiDi Passive TPs 12 40Gbps BiDi Passive TPs 28 1 or 10Gbps Passive TPs 28 1 or 10Gbps Passive TPs available in 56 TPs by adding 28 more TPs

More information

Closet Connector Housings (CCH)

Closet Connector Housings (CCH) features and benefits Interconnect and crossconnect capability Removable, translucent top covers (1U, 2U, 3U), removable rear cover (4U) Internal and external strain-relief options Accepts panels, modules

More information

UniCam Connector Installation Tool Kits

UniCam Connector Installation Tool Kits Applications UniCam Connector installations Local area networks (LANs), including main cross-connect, telecommunications room and telecommunications enclosures Fibre-to-the-desk Data centres Description

More information

Cable Assemblies. An Evolant. Solutions Product

Cable Assemblies. An Evolant. Solutions Product Corning Cable Systems offers the most complete line of connectors and factory-terminated cables, from single-fiber jumpers to high-fiber-count assemblies. As the industry s leading supplier of cable assemblies,

More information

HIGH DENSITY DATA CENTER CABLING GUIDE. Optics DACs Cables Cable Management Fiber TAPs Media Converters

HIGH DENSITY DATA CENTER CABLING GUIDE. Optics DACs Cables Cable Management Fiber TAPs Media Converters HIGH DENSITY DATA CENTER CABLING GUIDE Optics DACs Cables Cable Management Fiber TAPs Media Converters PROVIDING MTP CABLING SOLUTIONS FOR THE SMART DATA CENTER. APPROVED NETWORKS SETS THE STANDARD The

More information

Using Laser-Optimized Multimode Fiber for 1 and 10 Gigabit Campus Backbone Applications

Using Laser-Optimized Multimode Fiber for 1 and 10 Gigabit Campus Backbone Applications Using Laser-Optimized Multimode Fiber for 1 and 10 Gigabit Campus Backbone Applications David Kozischek, Market Manager Enterprise Networks, Corning Optical Communications Systems engineers at Corning

More information

8 Channel Contact Closure DIN Fiber Link System

8 Channel Contact Closure DIN Fiber Link System USER GUIDE The leader in rugged fiber optic technology. U-028 2017B-0420 8 Channel Contact Closure DIN Fiber Link System SYSTEM INSTALLATI INFORMATI Description The RLH 8 Channel Contact Closure DIN Fiber

More information

DATA CENTER SOLUTIONS

DATA CENTER SOLUTIONS DATA CENTER SOLUTIONS MTP Cabling Solutions MTP Cassette Solutions MTP Distribution Center Solutions Aqua 10 (OM3) Gigabit Patchcords Tera Flow Single Mode Bend Insensitive Patchcords Fiber Optic Taps

More information

UniCam High-Performance Connectors, Multimode and Single-Mode

UniCam High-Performance Connectors, Multimode and Single-Mode Features and Benefits Broad operating temperature (-40 to +75 C) Utility and flexibility Factory-polished end face Consistent optical performance Fast termination and no consumables Low installation cost

More information

OptiSheath Aerial Terminal, SCA-9T Series

OptiSheath Aerial Terminal, SCA-9T Series Features and Benefits Design includes aerial hanging brackets Easy installation Quick-release clamps Easy terminal re-entry Individual strain-relief Fiber protection and continuity Cable sealing and reusable

More information

Pretium EDGE Solutions Trunk Cable, OM3, Low-Loss, MTP to MTP, 24 fibres

Pretium EDGE Solutions Trunk Cable, OM3, Low-Loss, MTP to MTP, 24 fibres Corning LANscape Pretium EDGE (Evolved-Density, Growth -Enabled) solutions are high -density preterminated optical cabling systems that simplify installation and improve performance in data centre environments.

More information

Testing Optical Feeds in Wireless Systems Remote Radio Units (RRU) and Distributed Antenna Systems (DAS)

Testing Optical Feeds in Wireless Systems Remote Radio Units (RRU) and Distributed Antenna Systems (DAS) Application Note Testing Optical Feeds in Wireless Systems Remote Radio Units (RRU) and Distributed Antenna Systems (DAS) MT9090A/MU909011A Network Master Optical Fault Locator (OTDR) By Stephen Colangelo

More information

Wall-Mountable Connector Housings (WCH)

Wall-Mountable Connector Housings (WCH) Features and Benefits Interconnect and cross-connect capabilities Ideal for field splicing and connectorization Accepts CCH cassettes, panels and modules Variety of preterminated and field-installable

More information

EDGE8 MTP Trunk Cable

EDGE8 MTP Trunk Cable The EDGE8 trunks utilise 8 -fibre push/pull optical connectors that are pinned on both ends of the cable. The trunks are shipped with strain -relief clips that allow for tool -less installation in EDGE8

More information

Fiber Optic Prism Switch USER S MANUAL

Fiber Optic Prism Switch USER S MANUAL Fiber Optic Prism Switch USER S MANUAL Warranty Newport Corporation warrants this product to be free from defects in material and workmanship for a period of one year from the date of shipment. If found

More information

Coarse Wavelength Division Multiplexing (CWDM) Solutions

Coarse Wavelength Division Multiplexing (CWDM) Solutions Features and Benefits Passive and outside plant hardened No power or temperature-controlled environment required Epoxy-free optical path Higher reliability Low insertion loss and high isolation Minimum

More information

LTS-2A LTS-10 LTS-10C LTS-11 LTS-12

LTS-2A LTS-10 LTS-10C LTS-11 LTS-12 Optical Loss Test Kits LTS-2A LTS-10 LTS-10C LTS-11 LTS-12 Description Fit your application to your budget. Our Optical Loss Test Kits, and Fiber Test Kits combine the dependability and accuracy of our

More information

CSS1 Contractor Series Light Sources and CSM1 Contractor Series Optical Power Meters User s Guide

CSS1 Contractor Series Light Sources and CSM1 Contractor Series Optical Power Meters User s Guide CSS1 Contractor Series Light Sources and CSM1 Contractor Series Optical Power Meters User s Guide www.aflglobal.com or (800) 321-5298, (603) 528-7780 Limited Warranty All NOYES test equipment products

More information

Solutions. Solutions FOR DATA CENTERS AND STORAGE AREA NETWORKS

Solutions. Solutions FOR DATA CENTERS AND STORAGE AREA NETWORKS Solutions Solutions FOR DATA CENTERS AND STORAGE AREA NETWORKS Xtreme8 is Opticonx s Base-8 cabling solution for easy migration of 10/40/100 and 400G parallel optics deployments in the data center. This

More information

Plug & Play Universal Harness, SMF-28 Ultra Single-mode (OS2)

Plug & Play Universal Harness, SMF-28 Ultra Single-mode (OS2) Plug & Play Universal Systems Harnesses have a pinned (male) MTP connector on one end that connects to a Plug & Play Universal Systems trunk or extender trunk, while the other end is equipped with single

More information

6400 CWDM Series. Fiberlink. 4 or 8 Channel Coarse Wave Division Multiplexers for Single Mode Fiber. User s Manual

6400 CWDM Series. Fiberlink. 4 or 8 Channel Coarse Wave Division Multiplexers for Single Mode Fiber. User s Manual Communications Specialties Fiberlink 6400 CWDM Series User s Manual Coarse wave division multiplexers (CWDM) allow 4or 8 fiber optic links to operate at different wavelengths over a single fiber. It s

More information

Corning Optical Network Evolution (ONE ) SD-LAN Ordering Guide

Corning Optical Network Evolution (ONE ) SD-LAN Ordering Guide Corning Optical Network Evolution (ONE ) SD-LAN Ordering Guide Corning SD-LAN Overview Corning Optical Network Evolution (ONE ) Solutions utilize fiber s superior reach and unlimited bandwidth to provide

More information

6100E Series DIGITAL FIBER OPTIC MULTI-CHANNEL AUDIO TRANSPORT SYSTEM

6100E Series DIGITAL FIBER OPTIC MULTI-CHANNEL AUDIO TRANSPORT SYSTEM 00E Series DIGITAL FIBER OPTIC MULTI-CHANNEL AUDIO TRANSPORT SYSTEM WITH DATA OPTIONS BCI reserves the right to make changes to the products described herein without prior notice or consent. No liability

More information

10/100BASE-TX TO 100BASE-FX MEDIA CONVERTERS. KC-300DM Series. Installation Guide

10/100BASE-TX TO 100BASE-FX MEDIA CONVERTERS. KC-300DM Series. Installation Guide 10/100BASE-TX TO 100BASE-FX MEDIA CONVERTERS KC-300DM Series Installation Guide -1- DOC.060215-KC-300D (C) 2003 KTI Networks Inc. All rights reserved. No part of this documentation may be reproduced in

More information

SCT-MMA / SCT-SMA Fiber Optic Adapters

SCT-MMA / SCT-SMA Fiber Optic Adapters SCT-MMA / SCT-SMA Fiber Optic Adapters USER MANUAL ENGLISH i SAFETY WARNINGS Read First: Safety and Operational Information The international electrical symbols used on the instrument or in this manual

More information

LC Adapters and Cable Assemblies

LC Adapters and Cable Assemblies LC Adapters and meet the growing demand for small form factor, high-density fiber optic connectivity with simplex, duplex, single-mode and multimode options. LC connectors reduce space requirements by

More information

SYSTIMAX 360 ipatch Network Manager Module Faceplate Instructions

SYSTIMAX 360 ipatch Network Manager Module Faceplate Instructions Instruction Sheet 860508340 SYSTIMAX Solutions SYSTIMAX 360 ipatch Network Manager Module Faceplate Instructions General The SYSTIMAX 360 ipatch Network Manager module is a SYSTIMAX approved product. This

More information

Pretium EDGE Solutions Trunk Cable, OM4, Low-Loss, MTP to MTP, 24 fibres

Pretium EDGE Solutions Trunk Cable, OM4, Low-Loss, MTP to MTP, 24 fibres Corning Cable 143 Pretium EDGE Solutions Trunk Cable, OM4, Corning Cable Systems LANscape Pretium EDGE (Evolved -Density, Growth -Enabled) Solutions are high density pre -terminated optical cabling systems

More information

AF-OLK5A Series Fiber Optic Test kit

AF-OLK5A Series Fiber Optic Test kit AF-OLK5A Series Fiber Optic Test kit Description The AF-OLK5A series test kits are the complete solution necessary for the installer to test, terminate and trouble shoot fiber optic systems. These test

More information

Application Note AN114

Application Note AN114 Application Note AN114 Fiber Optic Cabling System for Fiber Optic Rotational Sensors in Industrial Environments Objective This application note provides the engineer with guidance on designing and procuring

More information

Installing the ASA 5550

Installing the ASA 5550 CHAPTER 3 Installing the ASA 5550 Caution Read the safety warnings in the Regulatory Compliance and Safety Information for the Cisco ASA 5500 Series and follow proper safety procedures when performing

More information

FlexNAP Outside Plant System

FlexNAP Outside Plant System Features and Benefits Factory-installed, sealed splice points (2, 4, 6, 8 or 12 fibers per tether) Drastically reduces field splicing with a predetermined loss at each waterproof tether attachment point

More information

OptiSheath MultiPort Terminal

OptiSheath MultiPort Terminal Features and Benefits OptiTap cable assembly connector ports for customer drop terminations Lower installation cost and increase speed of customer connection Available stubbed or preterminated with OptiTip

More information

OLS Series Light Sources, OPM Series Optical Power Meters, and Optical Loss Test Kits Quick Reference Guide

OLS Series Light Sources, OPM Series Optical Power Meters, and Optical Loss Test Kits Quick Reference Guide OLS Series Light Sources, OPM Series Optical Power Meters, and Optical Loss Test Kits Quick Reference Guide Warranty All NOYES test equipment products are warranted for a period of (1) one year from the

More information

LBO-H2 Series DIRECT PLUGGABLE LINKBRIDE TM FIBER OPTIC HDMI 2.0 TRANSMISSION SYSTEM

LBO-H2 Series DIRECT PLUGGABLE LINKBRIDE TM FIBER OPTIC HDMI 2.0 TRANSMISSION SYSTEM LBO-H2 Series DIRECT PLUGGABLE LINKBRIDE TM FIBER OPTIC HDMI 2.0 TRANSMISSION SYSTEM BCI reserves the right to make changes to the products described herein without prior notice or consent. No liability

More information

POL-001 Fiber-Optic In-Line Polarizer. Operation Manual

POL-001 Fiber-Optic In-Line Polarizer. Operation Manual POL-001 Fiber-Optic In-Line Polarizer Operation Manual Feb. 18, 2002 General Photonics Corp. Ph: (909) 590-5473 5228 Edison Ave. Fax: (909) 902-5536 Chino, CA 91710 USA www.generalphotonics.com Document

More information

NG3 High-Density Fiber Distribution Frame System Termination, Termination/Splice, VAM, and MPO Panels

NG3 High-Density Fiber Distribution Frame System Termination, Termination/Splice, VAM, and MPO Panels NG3 High-Density Fiber Distribution Frame System Termination, Termination/Splice, VAM, and MPO Panels User Manual ADCP-90-297 Issue 9 3/2010 1685349 Rev A Preface COPYRIGHT All Rights Reserved REVISION

More information

Model GS7000 Node Expanded Fiber Tray Installation Instructions

Model GS7000 Node Expanded Fiber Tray Installation Instructions Model GS7000 Node Expanded Fiber Tray Installation Instructions Overview Introduction The expanded fiber tray is an optional replacement for the standard fiber tray in the Model GS7000 GainMaker Scaleable

More information

The Green Advantage of 10G Optical Fiber

The Green Advantage of 10G Optical Fiber The Green Advantage of 10G Optical Fiber What is the definition of Green? Green. The word invokes natural images of deep forests, sprawling oak trees and financial images of dollar bills. The topic of

More information

Fiber Management Tray 2 Rack Unit (2 RU) Style FMT-G Series

Fiber Management Tray 2 Rack Unit (2 RU) Style FMT-G Series 2 Rack Unit (2 RU) Style FMT-G Series ADC has expanded its Fiber Management Tray (FMT) family to include two rack unit (2 RU) high trays (FMT-G series). Available for termination only (with adapters only,

More information

Optical Component Environmental Test System OCETS Plus Series

Optical Component Environmental Test System OCETS Plus Series COMMUNICATIONS TEST & MEASUREMENT SOLUTIONS Optical Component Environmental Test System OCETS Plus Series Key Features High Return Loss option (HiRL) monitors RL up to 70 db Up to 210 device channels (420

More information

OptiTect Indoor Local Convergence Cabinet, Gen III Series

OptiTect Indoor Local Convergence Cabinet, Gen III Series Features and Benefits Industry-leading cabinet size Significant freight, storage and installation efficiencies Full factory-stubbed cabinets Enables quicker installation and rapid emergency restoration

More information

PoE Powered 10/100BASE-TX to 100BASE-FX Media Converters. KC-351 Series. Installation Guide

PoE Powered 10/100BASE-TX to 100BASE-FX Media Converters. KC-351 Series. Installation Guide PoE Powered 10/100BASE-TX to 100BASE-FX Media Converters KC-351 Series Installation Guide -1- DOC.070820-KC-351 (C) 2007 KTI Networks Inc. All rights reserved. No part of this documentation may be reproduced

More information

Qualification of the optical links for the data readout in LHCb

Qualification of the optical links for the data readout in LHCb Qualification of the optical links for the data readout in LHCb LHCB Technical Note Issue: Draft Revision: 1 Reference: LHCB xxxxx Created: 28 th Jan 2005 Last modified: 11 th Dec 1997 Prepared By: V.

More information

Closet Connector Housing Panels (CCH-CP) A LANscape Solutions Product

Closet Connector Housing Panels (CCH-CP) A LANscape Solutions Product Applications The panels are used with field-installable connectors or in applications where the preconnectorized cables are routed directly from the equipment to the piece of interconnect hardware Provides

More information

10/100BASE-TX TO 100BASE-FX MEDIA CONVERTERS

10/100BASE-TX TO 100BASE-FX MEDIA CONVERTERS 10/100BASE-TX TO 100BASE-FX MEDIA CONVERTERS KC-300DM Series Installation Guide DOC.130923-1- (C) 2003-2013 KTI Networks Inc. All rights reserved. No part of this documentation may be reproduced in any

More information

FuseLite Single-Fiber Splice-On Connectors

FuseLite Single-Fiber Splice-On Connectors features and benefits Broad operating temperature (-40 to +75 C) Factory-polished end face Fusion splice connectivity Splice protection within connector body (03U and 04U) SPECIFICATION SHEET LAN-1455-AEN

More information

Next Generation Frame Fiber Termination Block With MPO Connectors (FTB w/mpo) User Manual

Next Generation Frame Fiber Termination Block With MPO Connectors (FTB w/mpo) User Manual Next Generation Frame Fiber Termination Block With Connectors ( w/) User Manual ADCP-90-372 Issue 2 4/2010 23867-A Block With Connectors 1685947 Rev A Preface COPYRIGHT 2008, ADC Telecommunications, Inc.

More information

Cubro OPTOSLIM TAPs Series (Upto 100 G)

Cubro OPTOSLIM TAPs Series (Upto 100 G) Cubro OPTOSLIM TAPs Series (Upto 100 G) PRODUCT OVERVIEW Network TAPs At a glance Definition A network TAP (test access point) is an external monitoring device that mirrors the traffic that passes between

More information

OPERATIONS GUIDE OWL

OPERATIONS GUIDE OWL Optical Wavelength Laboratories OPERATIONS GUIDE Silicon ZOOM 2 OPTICAL POWER METER Model Numbers: ZO2S ZO2SV OWL Revision 1.13 OWL-INC.COM Optical Wavelength Laboratories (OWL) N9623 West US Hwy 12 Whitewater,

More information

Cisco 100BASE-X Small Form-Factor Pluggable Modules for Fast Ethernet Applications

Cisco 100BASE-X Small Form-Factor Pluggable Modules for Fast Ethernet Applications Data Sheet Cisco 100BASE-X Small Form-Factor Pluggable Modules for Fast Ethernet Applications Product Overview The Cisco 100BASE-X Small Form-Factor Pluggable (SFP) device (Figure 1) is a hot-swappable

More information

Test Equipment Depot Washington Street Melrose, MA TestEquipmentDepot.com. FiberTEK III

Test Equipment Depot Washington Street Melrose, MA TestEquipmentDepot.com. FiberTEK III Test Equipment Depot - 800.517.8431-99 Washington Street Melrose, MA 02176 - TestEquipmentDepot.com FiberTEK III User Manual Page 1 COPYRIGHT NOTICE The information contained in this document is the property

More information

Optical Line Splitter Installation Instructions

Optical Line Splitter Installation Instructions Optical Line Splitter Installation Instructions TECP-96-171 Issue 1 9/2011 Content Page INTRODUCTION............................................................................. 1 1 INSTALLATION.........................................................................

More information

Opt-X Enterprise Fiber Trunk Cables

Opt-X Enterprise Fiber Trunk Cables APPLICATION Factory-terminated and tested fiber trunk cables connect central patching locations to zones or pods. Available terminated with both modular (MTP ) and discrete connectors, these trunks are

More information

Cisco Small Form-Factor Pluggable Modules for Gigabit Ethernet Applications

Cisco Small Form-Factor Pluggable Modules for Gigabit Ethernet Applications Data Sheet Cisco Small Form-Factor Pluggable Modules for Gigabit Ethernet Applications The industry-standard Cisco Small Form-Factor Pluggable (SFP) Gigabit Interface Converter is a hot-swappable input/output

More information

A Closer Look at Fiber Optic Cable Assemblies

A Closer Look at Fiber Optic Cable Assemblies A Closer Look at Fiber Optic Cable Assemblies Our thanks to Siemon for allowing us to reprint the following article Many network performance problems occurring at the physical layer are directly related

More information

2 Channel POTS DIN Fiber Link System

2 Channel POTS DIN Fiber Link System USER GUIDE The leader in rugged fiber optic technology. U-8 07A-040 Channel POTS DIN Fiber Link System SYSTEM INSTALLATION INFORMATION The RLH Channel Plain Old Telephone Service (POTS) DIN Fiber Link

More information