Arctic P - Series User Manual. Arctic Protocol Gateway (P-2220, P-2250, P-2260)

Size: px
Start display at page:

Download "Arctic P - Series User Manual. Arctic Protocol Gateway (P-2220, P-2250, P-2260)"

Transcription

1 Arctic P - Series User Manual (P-2220, P-2250, P-2260) May 2015

2 Copyright and Trademark Copyright , Viola Systems Ltd. All rights to this manual are owned solely by Viola Systems Ltd. (referred elsewhere in this User s Manual as Viola Systems). All rights reserved. No part of this manual may be transmitted or reproduced in any form or by any means without a prior written permission from Viola Systems. Viola Systems Ltd. Lemminkäisenkatu B FI Turku Finland info@violasystems.com Technical Support Phone: Fax: support@violasystems.com Internet: 2

3 Disclaimer Viola Systems reserves the right to change the technical specifications or functions of its products or to discontinue the manufacture of any of its products or to discontinue the support of any of its products without any written announcement and urges its customers to ensure that the information at their disposal is valid. Viola software and programs are delivered as is. The manufacturer does not grant any kind of warranty including guarantees on suitability and applicability to a certain application. Under no circumstance is the manufacturer or the developer of a program responsible for any damage possibly caused by the use of a program. The names of the programs as well as all copyrights relating to the programs are the sole property of Viola Systems. Any transfer, licensing to a third party, leasing, renting, transportation, copying, editing, translating, modifying into another programming language or reverse engineering for any intent is forbidden without the written consent of Viola Systems. Viola Systems has attempted to verify that the information in this manual is correct with regard to the state of products and software on the publication date of the manual. We assume no responsibility for possible errors which may appear in this manual. Information in this manual may change without prior notice from Viola Systems. 3

4 Declaration of Conformity (according to ISO/IEC Guide 22 and EN 45014) Manufacturer s Name: Viola Systems Ltd. Manufacturer s Address: Lemminkäisenkatu B FI Turku Finland declares that this product: Product Name: conforms to the following standards: EMC: IEC (Edition ) 1. CISPR : Radiated Disturbance 2. CISPR : Conducted Disturbance IEC Immunity Tests 1. EN ( ): Electrostatic Discharge (ESD) 2. EN ( ): Radiated Radio-Frequency Electromagnetic Field 3. EN ( ): Electrical Fast Transient (EFT) 4. EN ( ): Surge 5. EN ( ): Conducted Radio-Frequency Electromagnetic Field Supplementary Information: The product complies with the requirements of the Low Voltage Directive 73/23/EEC and EMC directive 89/336/EEC.! This is a Class A product. In a domestic environment this product may cause radio Interference which may make it necessary for the user to take adequate measures. Manufacturer s Contact Information: Viola Systems Ltd. Lemminkäisenkatu B FI Turku Finland Phone: Fax:

5 Warranty and Safety Instructions Read these safety instructions carefully before using the products mentioned in this manual: Warranty will be void if the product is used in any way in contradiction with the instructions given in this manual or if the product has been tampered with. The devices mentioned in this manual are to be used only according to the instructions described in this manual. Faultless and safe operation of the devices can be guaranteed only if the transport, storage, operation and handling of the devices is appropriate. This also applies to the maintenance of the products. To prevent damage both the product and any terminal devices must always be switched OFF before connecting or disconnecting any cables. It should be ascertained that different devices used have the same ground potential. Before connecting any power cables the output voltage of the power supply should be checked. This product is not fault-tolerant and is not designed, manufactured or intended for use or resale as on-line control equipment or as part of such equipment in any hazardous environment requiring fail- safe performance, such as in the operation of nuclear facilities, aircraft navigation or communication systems, air traffic control, direct life support machines, or weapons systems, in which the failure of Viola Systems manufactured hardware or software could lead directly to death, personal injury, or severe physical or environmental damage. 5

6 Revisions Date Document version 05/ Firmware version Description of changes Manual released 6

7 Contents COPYRIGHT AND TRADEMARK... 2 DISCLAIMER...3 DECLARATION OF CONFORMITY... 4 WARRANTY AND SAFETY INSTRUCTIONS...5 REVISIONS INTRODUCTION About this User s Manual...9 Arctic P-series Protocol Gateways PHYSICAL INTERFACES Front Panel Description...10 Back Panel Description Side Panel Description...14 Product Information Label...15 Firmware Version QUICK INSTALLATION Connection Principle...16 Connecting cables Logging in to Arctic Setting Ethernet port function to LAN Configuring Mobile WAN (cellular network interface) Configuring default gateway NETWORK CONFIGURATION Configuration screens Host and domain names Ethernet WAN Mobile WAN WAN Failover and backup routing settings Ethernet LAN Network monitor Routing Routing parameters Default route WAN redundancy/failover Routing serial <-> Ethernet...26 Network services DNS proxy...26 Network status information System status screen Mobile WAN status LEDs Modem info screen SERIAL PORT CONFIGURATION Configuring a serial port...29 Configuring serial gateway

8 6. ADDITIONAL SYSTEM CONFIGURATION Changing system password Date and time...30 System log...31 Factory default settings Firmware update...31 Configuration profiles IEC-104 APPLICATION SETTINGS General settings Serial settings Network settings IEC-104 Settings IEC-101 settings ASDU Converter...43 Packet collector Other settings MODBUS APPLICATION SETTINGS Introduction Parameters Common parameters Routes Configuring Network Master to Serial Slaves Mode Settings Common parameters Configuring Serial Master to Network Slaves Mode Settings Common Parameters Settings Routes TROUBLESHOOTING...64 SPECIFICATIONS LIMITED WARRANTY TECHNICAL SUPPORT

9 1 Introduction 1.1 About this User s Manual This User s Manual describes the operation of the. All devices in this User s Manual are referred to as Arctic, unless otherwise mentioned. This manual provides introductory information as well as detailed instructions on how to set up and manage the Arctic as part of a network environment. It is intended for anyone involved in installing and managing Arctic devices. It is assumed that the reader of this manual is familiar with basic working principles of Internet technology. Figure Arctic P-series Protocol Gateways The Arctic P-series product family includes a number of Arctic protocol gateway product variants. Arctic protocol gateways provide highly robust network components for rugged industrial environments, ease of use, and proven long-term field operation. Arctic protocol gateways make it possible to have a cost-effective communication system over long distances, at high data rates (up to 100 Mbps) and with integrated protocol conversion support. The protocol conversion feature means that the IEC-101 or Modbus RTU serial devices can be attached to a modern TCP/IP based IEC-104 or Modbus TCP SCADA system. 9

10 2 Physical Interfaces The Arctic unit contains three panels for interface connections and status indication. 2.1 Front Panel Description The front panel of the Arctic consists of the following connectors and switches: Figure 2. Front Panel Description 1. Power supply connector 2. Console serial port (RS1) 3. Power switch 4. Console switch 5. DIP switches 6. Application serial port (RS2) 7. Ethernet connector The Arctic has rails to enable wall or DIN rail mounting. The front panel contains slots for nuts or other mounting accessories (optional) in order to gain access to these rails. Power Supply Connector The Arctic has a VDC power supply connector as shown in the figure below. 10

11 Figure 3. Power supply connector Pin 1 is positive (+) Pin 2 is negative ( ) The unit is protected against reversed polarity in specified voltage range. Power Switch Enables or disables the operation of the Arctic. Console Enable Switch Enables or disables console access. When it is disabled, both serial ports may be used as an application serial port. When the switch is in the right position, RS1 is in serial port mode and when in the left position, RS1 is in console mode. DIP Switches It selects an application port (RS-2) mode and settings (RS-232 or RS-485). By default all are set to 0 when the port is acting as an RS-232. DIP switches 2-4 apply only when RS-485 mode is selected by DIP switch 1. Table 1: DIP Switches Number Function State Explanation 1 0 = RS-232 Selects RS-port operation RS-232/RS = RS HALF/FULL 0 = full Selects between half-duplex (2-wire) and full-duplex (4-wire) 1 = half 3 BIAS 0 = OFF RS-485 biasing 1 = ON 4 TERMINATION 0 = OFF RS-485 termination 1 = ON Serial Ports (RS-232, RS-422/485 -connectors) Arctic has two serial port connectors. These are 9-pin male connectors (DB9). A null modem cable (product code: 3100) may be used to connect the Arctic to a PC. The Arctic supports CTS/RTS flow control. The figure of Arctic s DB9 (DTE) Male connector is shown in the figure below. 11

12 Figure 4. DB9 male connector The serial port 1 (RS1) is a full RS-232 port. The pin description of this port is as follows: Table 2: RS-232 Port PIN Description Pin Number Name Direction Explanation 1 DCD IN Data Carrier Detect 2 RXD IN Received Data 3 TXD OUT Transmitted Data 4 DTR OUT Data Terminal Ready. Handshake output 5 GND - Signal ground. 6 DSR IN Data Set Ready. Handshake input 7 RTS OUT Ready To Send. Handshake output 8 CTS IN Clear To Send. Handshake input 9 RI IN Ring Indicator The serial port 2 (RS2) can be configured either as a half RS-232 or an RS-422/485 (DTE Master). The Pin description is same as in RS1, when in RS-232 mode. The pin description of this port is as follows in RS-485 mode. Table 3: RS-485 Port PIN Description Pin Number RS-485,Full duplex (4-wire) RS-485 Half duplex (2-wire) 1 NC NC 2 RXD+ (in) NC 3 TXD (out) TXD/RXD- (out/in) 4 NC NC 5 GND GND 6 NC NC 7 TXD+ (out) TXD/RXD+ (out/in) 8 RXD (in) NC 9 NC NC! Make sure that you DO NOT connect RS-422 or RS-485 devices to a port which has been configured to operate as an RS-232 port. Ethernet Connector Arctic has an RJ45 connector for 10/100 Mbps Ethernet connection. Maximum length of the Ethernet cable is 100m. 12

13 The figure and pin description of the Arctic s RJ45 Ethernet connector is as follows: Figure 5. RJ45 Ethernet connector Table 4: RJ45 Ethernet connector PIN Description 2.2 Pin Number Name Direction Explanation 1 Rx+ IN Data Receive Positive 2 Rx IN Data Receive Negative 3 Tx+ OUT Data Transmit Positive 4 NC NC Tx OUT Data Transmit Negative 7 NC NC - - Back Panel Description The Arctic has an antenna connector and a slot for a SIM card on the back panel. Figure 6. Back Panel 13

14 1. SMA (female) connector for an antenna. 2. SIM Card slot. 2.3 Side Panel Description The side panel of the device contains ten LEDs which are used to indicate the status of the Arctic and only five of them are connected. The LEDs are numbered from 1 to 10 starting from the rear panel side. A detailed description of each LED is listed below: Figure 7. LED Description Table 5: LED Description LED LED Number 1 Battery 2 Status Power/Error System Eth 1 State Description Not connected ON VPN connection is up Blinking VPN onnection is starting OFF VPN connection is disabled ON Operating power is turned on OFF Operating power is turned off ON Device is starting Blinking Device is operating normally ON Ethernet link is up Blinking Ethernet link is transferring data OFF Ethernet link is down Eth 2 Not connected 14

15 LED LED Number 2.4 State Description 7 LED 1 Not connected 8 LED 2 Not connected 9 LED 3 Not connected 10 LED 4/GPRS Blinking Wireless communication is starting or transferring data OFF Wireless communication is inactive Product Information Label The product information label on the underside of the Arctic contains the following information: 1. Product type 2. Serial number 3. MAC address The Ethernet address (MAC address) of the unit is printed on the product label. Each address code starts with the digits 00:06:70, but the remaining six digits are unique for each unit. Figure 8. Product Information Label 2.5 Firmware Version The Arctic firmware version may be checked from the welcome page ( Log in the device > Welcome ). 15

16 3 Quick Installation 3.1 Connection Principle The Arctic has configurable network interfaces, Ethernet WAN or Ethernet LAN port for a cable network, and Mobile WAN for wireless communication. The WAN interfaces are used for connecting the Arctic to public Internet or private APN. Ethernet LAN is used for connecting other Ethernet devices to the Arctic's local network. The WAN interfaces can be configured to get redundant system where one WAN automatically gets traffic if the other one goes down. For example, if the primary Ethernet connection goes down, the traffic is automatically switched to mobile WAN (secondary connection) and back when the Ethernet interface comes up again. This way the availability of the remote system is better than with just one interface. 3.2 Connecting cables 1. Verify that the power switch is in the OFF position. 2. Connect the Ethernet cable between Arctic (Ethernet LAN connector) and the computer used for the configuration. 3. Connect power supply to Arctic and toggle the power switch to ON position. 4. The power/error LED and function LED should turn on immediately after the power switch is turned on. 5. After the system has initialized, the function LED starts to blink. 3.3 Logging in to Arctic This section describes how to log in to Arctic using web configuration menu. 16

17 1. Configure the computer to use the same IP address space as the Arctic (laptop IP for example with netmask ). Check with ping command. 2. Connect to the Arctic using the web browser. The default IP address of Arctic is (netmask ). Please make sure to connect to a HTTPS port (see the figure below). Figure 9. Browser https example! You can ignore the browser's warning about a self-signed certificate. 17

18 3. Enter the username and password and press Login button in the log-in screen. The actual screen depends on the used web browser.! Default username is viola-adm and default password is violam2m. It is recommended that the default password is changed before the product is connected to a public network. 4. White texts on the blue background on the left are the primary navigation texts and they are always visible on the screen. Individual screens may have their own tabs which split the configuration fields on larger screens. See the figure below. Figure 10. Configuration menu 3.4 Setting Ethernet port function to LAN Disable automatic IP address detection by changing the port function to LAN. If the Port function is at the default setting of auto, the Ethernet LAN port tries to automatically obtain the IP address using DHCP when the device boots. If the DHCP discovery fails, the Arctic automatically uses IP address

19 ! Make the following change before changing any other Ethernet settings. 1. In the left pane, select Network > Ethernet Port. 2. Change Port function to LAN. 3.5 Configuring Mobile WAN (cellular network interface) The Mobile WAN interface is used for connecting the Arctic to a cellular network. The Arctic can use a GPRS (2G), UMTS (3G) or LTE (4G) cellular network connection depending on the product model. Install the SIM card before configuring the Mobile WAN. See Back Panel Description on page 13 for the location of the SIM card slot. 1. Select Network > Mobile WAN from the left menu. 2. Enter the preferred configuration to the configuration fields. 3. Press Submit on the bottom to save the settings. 3.6 Configuring default gateway 1. Select Network WAN Failover from the left menu. 2. Set "WAN Default Route"="Yes". This has to be enabled to use either WAN as default route interface. 3. If the mobile WAN has to be set as a default gateway, set "Primary WAN Interface"="Mobile WAN". This is a typical setting. 4. If Ethernet WAN has to be set as a default gateway: a) Select Network > Ethernet port settings > WAN. b) Set "PrimaryWAN Interface"="EthernetWAN" 19

20 5. If both Ethernet WAN and Mobile WAN configured, define the Backup WAN Interface. If the primary WAN interface comes down, the Arctic automatically switches default route to backup WAN interface. The figure below shows example configuration where Ethernet WAN is configured as default route. Figure 11. Ethernet WAN default route example 6. Press Submit on the bottom to save the settings. 7. Select Tools > Reboot from the left menu and press Reboot button to restart the unit. 20

21 4 Network Configuration This chapter describes how to configure network interfaces Configuration screens Host and domain names Host and domain names can be set from the System General Settings screen. Figure 12. General Settings Ethernet WAN This screen configures the Ethernet WAN interface on Arctic. Figure 13. Ethernet WAN configuration Connectivity Monitor settings are used when WAN redundancy functionality is required. Monitor keeps checking the connection to the given remote host to determine the network status. If the ping does not get an answer for a given time window, it informs the WAN switch logic to try the secondary interface. If the WAN redundancy is implemented by using two separated Ethernet connections with different gateways, the Backup Gateway parameter needs 21

22 to be configured towards the correct backup gateway. Backup Gateway parameter is not needed if WAN redundancy is implemented with wireless connection. See section WAN Failover and backup routing settings on page 23 for more details about WAN redundancy Mobile WAN This screen configures the Mobile WAN interface on the Arctic. The configuration screen fields are described below. PIN code The 2G/3G/LTE cellular networks use a SIM card. The SIM card can be protected by PIN code (personal identification number). If the PIN code is used, it must be entered to Arctic s Mobile WAN settings. Leave the PIN code field empty if no PIN code is used. If a wrong PIN code is entered, correct the code and enter the correct PIN code to the SIM by using a mobile phone. APN By default automatic APN discovery is used. Arctic tries default APN values based on network ID received from cellular network. If automatic settings do not work, set to APN parameter from Automatic to Manual. APN The APN parameter defines the cellular access point name. If APN is set to Manual the access point works as a gateway from the cellular network to internet. There are public and private access points. A public access point is usually defined. A private access point requires contract with a cellular operator. Viola M2M solution is compatible with both public and private access points. Define the access point name as according to information received from the cellular operator. Authentication, username, password If the cellular network requires authentication for using the access point, the access point s username and password need to be defined in the Arctic. In this case, select the authentication type (PAP, password authentication protocol or CHAP, challenge handshake authentication protocol) as according to information received from the cellular operator. DNS selection, DNS servers Allows user defined DNS servers, receiving DNS server IP addresses from cellular network or leaving DNS configuration as disabled. The DNS 22

23 servers are used for resolving names to IP addresses. Figure 14. Mobile WAN configuration To configure the mobile WAN, enable the connection by selecting "Enable"="Yes" on the top of the page and enter PIN code if set, APN name and authentication details if needed. If the Arctic acts as a wireless router to Ethernet devices and DNS is needed, enter DNS configuration as well. When ready, press the Submit button on the bottom of the page to save settings. The Arctic need to be restarted before the mobile WAN configuration is active WAN Failover and backup routing settings WAN Failover screen configures the default gateway settings on the Arctic. 23

24 Figure 15. WAN Failover configuration To enable any default routes, set "WAN Default Route"="Yes". Any route settings are not effective if this parameter is not enabled. Set "On Demand"="Yes" if the backup WAN interface to come up only when primary interface goes down. Disable if both wireless and wired WAN interfaces have to be up all the time Ethernet LAN This screen configures the Ethernet LAN interface on the Arctic. Figure 16. Ethernet LAN Configuration Network monitor This screen configures the interface connectivity monitor on Arctic. 24

25 Figure 17. Network monitor configuration The usage of the monitor is heavily recommended to detect the connection drops Routing Routing parameters There are multiple configuration options that define the routing on Arctic : Ethernet WAN - Gateway (IP address) IP address of router used to reach the internet. Leave empty if unused. WAN Failover - WAN Default Route (selection: Yes/No) Usually "Yes" if default route is defined by "static routes". If the selection logic is done on VPN level select "No" WAN Failover - On Demand (selection: Yes/No) Select "Yes" to activate the backup interfaces only when required. Select "No" to have all the WAN interfaces to be available simultaneously for e.g. VPNs. WAN Failover - Primary WAN Interface (selection: None/Mobile WAN/ Ethernet WAN/Ethernet WAN Secondary) WAN Failover - Backup WAN Interface(selection: None/Mobile WAN/ Ethernet WAN) 25

26 4.2.2 WAN Failover - Secondary Backup WAN Interface (selection: None/Mobile WAN/Ethernet WAN/Ethernet WAN Secondary) These three settings configure the high level default gateways. Must be configured to enable default route. OpenVPN Client Settings - Interface (selection: Any WAN/Ethernet WAN/ Wireless WAN/Ethernet LAN) Which Interface to use for connection OpenVPN Client Settings - Routing mode (selection: None/host/net/default route) This defines how the routing is configured with OpenVPN. See OpenVPN application note. Default route Default route can be configured from WAN Failover screen. See section WAN Failover and backup routing settings on page WAN redundancy/failover To configure redundancy between WAN interfaces, configure multiple WAN interfaces to WAN Failover. See section WAN Failover and backup routing settings on page Routing serial <-> Ethernet See section Serial Port Configuration on page Network services DNS proxy To use this feature, configure the device to use Arctic Ethernet LAN IP address as its DNS server. This way, the DNS queries from the device get routed through the Arctic Network status information System status screen Network status information can be seen from System > Status screen. 26

27 Figure 18. Network status screen Mobile WAN status LEDs See Table 5: LED Description on page COM LED starts to blink when the connection is started. 2. SIM LED starts to blink when SIM card is searched and turns on when the card is found and PIN code accepted. 3. SIM LED starts to blink when the operator network is searched and gets lit when the network is found. 4. COM LED gets lit when the connection is up Modem info screen In troubleshooting situations, checking the system logs helps to identify the problem. Also modem info page can be used to check the status of the wireless modem. 27

28 Figure 19. Modem info screen 28

29 5 Serial Port Configuration 5.1 Configuring a serial port The Arctic P-series supports the following serial port application modes: Application Mode Description Serial device protocol Serial Gateway Transparent connection to any serial device N/A IEC-104 IEC-101 to IEC-104 conversion IEC-101 Modbus Modbus conversion Modbus/RTU or Modbus/ ASCII 1. Select Serial Port and I/O > Serial Port Configuration. 2. Select the serial port mode. 5.2 Configuring serial gateway This section describes how to configure serial <-> IP functionality. The serial gateway feature enables data from the serial port attached device to be routed to Ethernet/mobile network (serial over IP) and vice versa. Serial gateway processes the transmitted data transparently and does not alter it any way except for buffering it for transmission. Because of the transparent communication, any protocols can be used in actual communication between nodes. Figure 20. Serial gateway configuration screen Serial gateway configuration depends on used protocols. 29

30 6 Additional System Configuration 6.1 Changing system password Username and password can be changed from Tools > User Config screen. It is always recommended to change the password from the factory default when the Arctic is connected to a public network. Figure 21. User Config screen 6.2 Date and time Date and time can be changed from System > Time screen. Date and time can be configured either manually entering the time or automatically from connected PC. Figure 22. System time configuration screen, automatic setting Figure 23. Manual setting To set time manually, enter the time and then press Submit button. To copy time from PC, press Copy PC button and answer "Yes" to question about changing time. that the PC may not necessarily have correct time set and that needs validation. Also note that the copy functionality requires JavaScript support from the browser. 30

31 6.3 System log System log is visible on the Tools > System Log screen. To refresh the system log, use web browser reload button. 6.4 Factory default settings Factory default settings can be applied by restarting the unit pressing down reset button until the LEDs blink. To restore factory default settings, go to Tools > Default settings. 6.5 Firmware update Create a backup of the current configuration starting the firmware update. Current running firmware version can be viewed from the System > Status screen. Arctic firmware can be updated in the Tools > Firmware Update screen. Figure 24. Firmware update screen 1. Verify for a valid firmware on the PC before attempting to update the firmware. 2. Select Select file button to open file browsing dialog. The actual dialog depends on the used browser. 3. Select the updated firmware from the file dialog and return to the firmware update screen. 4. Press Update button to start the firmware update. 5. Confirm the update. The update takes a few minutes. 6. Once the update is finished, restart the device. 6.6 Configuration profiles Profiles can be configured and saved for future use. Several profiles are created and selected for the activation. It is possible to import, export and clone profiles, and also reset them to factory default settings. 31

32 Figure 25. Configuration profiles 32

33 7 IEC-104 application settings The IEC-104 and IEC-101 protocols share the same ASDU level messaging but differ on the link level. The IEC-104 is intended for packet-switched TCP/ IP communication whereas the IEC-101 is intended for serial communication. By using the Arctic, the IEC-101 slaves (e.g. RTUs) can be connected to a IEC-104 master (e.g. SCADA). The Arctic requests event from the IEC-101 slave locally and sends them to the IEC-104 master. This eliminates the need to continuously poll the data remotely and therefore reduces the communication costs on pay-per-use wireless network. This approach also eliminates the IEC-101 parameter adjutancy problems caused by variable round-trip delays on wireless networks and makes the information exchange faster and more reliable. You can view and change the application settings in Serial Port and I/O > IEC-104 Gateway (RSx). Figure 26. IEC-104 Application Settings 33

34 7.1 General settings IEC-104 gateway enabled Enables or disables IEC-104 to IEC-101 gateway functionality. Table 6: IEC-104 gateway enabled IEC-104 gateway enabled Boolean N/A Value range No, Yes 7.2 Serial settings The serial settings define the properties of physical serial communication between the Arctic and an IEC-101 slave. The selection between RS-232/422/485 is done with physical DIP switches located below the RS2 serial port. Figure 27. Serial Settings Speed (bps) Table 7: IEC-101 serial communication speed (bps) IEC-101 serial communication speed (bps) Serial speed Bits per second Value range 1200, 2400, 4800, 9600, 19200, 38400, Data bits Table 8: Number of data bits used on IEC-101 serial communication Number of data bits used on IEC-101 serial communication Serial data bits Bits 34

35 Number of data bits used on IEC-101 serial communication Value range 5, 6, 7, 8 Parity Table 9: Parity method used on IEC-101 serial communication Parity method used on IEC-101 serial communication Serial data parity Bits Value range None, Even, Odd Stop bits Table 10: Number of stop bits used on IEC-101 serial communication Parity method used on IEC-101 serial communication Serial data stop bits Bits Value range 1, 2 Use HW flow control Table 11: Number of stop bits used on IEC-101 serial communication HW flow control mechanism (RTS/CTS) on IEC-101 serial communication 7.3 Boolean N/A Value range Yes, No The HW handshaking is available only on RS-232 mode. Network settings The Network settings define the general TCP/IP networking properties between the Arctic and the IEC-104 master. Figure 28. Network Settings 35

36 Network protocol Network protocol defines the network transmission layer protocol (either TCP or UDP) used on IEC-104 network communication. The IEC-104 standard protocol uses TCP but for reliable slow speed packet switched networks (e.g. Mobitex), the UDP protocol can be used to minimize the packets transmitted over network. Table 12: Network protocol on IEC-104 communication Network protocol on IEC-104 communication Network transmission layer protocol N/A Value range UDP, TCP The IEC-104 standard specifies only TCP protocol. Network port to listen Table 13: TCP or UDP port to listen for incoming IEC-104 connections TCP or UDP port to listen for incoming IEC-104 connections Network port Port number Value range The IEC-104 standard specifies TCP port Network idle timeout It defines the idle timeout of the network connection in seconds. If there is no network data received during the specified interval, the connection is closed by Arctic. This parameter is required in order to detect partially closed connections and release the resources for new connections especially if the New connection priority parameter is disabled. Value 0 disables the network idle timeout detection. Table 14: Network idle timeout for IEC-104 connections Network idle timeout for IEC-104 connections Timeout Seconds Value range The network idle timeout must be longer than IEC-104 link test interval (t3). New connection priority It defines the action when a new connection request arrives while a connection is already active. If the set value is No, the new connection is rejected. If the set value is Yes, the present connection is terminated and the new connection is accepted. 36

37 Table 15: New connection priority for IEC-104 connections New connection priority for IEC-104 connections 7.4 Boolean N/A Value range No, Yes It is recommendable to set this value to Yes in normal configurations having only one IEC-104 master. IEC-104 Settings The IEC-104 settings define the properties of IEC-104 link layer and application layer parameters as described in the IEC standard. The IEC-104 communication is carried out between the Arctic and the IEC-104 master over the TCP/IP network. Figure 29. IEC-104 Settings TX window size (k) TX window size defines the maximum number of I format APDUs the Arctic may send before requiring the IEC-104 master to acknowledge them. If there are k unacknowledged frames sent the Arctic will stop polling IEC-101 slave for events until acknowledgement is received. Table 16: IEC-104 TX windows size (k) IEC-104 TX windows size (k) Window size Packets Value range 1-20 The k must be always less than the maximum sequence number defined below. The IEC-104 standard suggests k to be

38 RX window size (w) It defines the maximum number of I format APDUs the Arctic may receive before sending acknowledgement to the IEC-104 master. Table 17: IEC-104 RX windows size (w) IEC-104 RX windows size (w) Window size Packets Value range 1-20 The w should not exceed two-thirds of TX window size k. The IEC-104 standard suggests w to be 8. I frames TX timeout (t1) It defines the timeout in seconds the Arctic waits for acknowledgement from IEC-104 master after sending last I format APDU or control frame (e.g. link test). If no acknowledgement is received during the defined time the Arctic will close the network connection and the IEC-101 link. Table 18: IEC-104 I frames TX timeout (t1) IEC-104 I frames TX timeout (t1) Timeout Seconds Value range The t1 must be longer than the network round-trip-time. The IEC-104 standard suggests 15 seconds. I frames RX timeout (t2) This defines the timeout in seconds from the last received I format APDU before sending acknowledgement. Table 19: IEC-104 I frames RX timeout (t2) IEC-104 I frames RX timeout (t2) Timeout Seconds Value range The t2 must be smaller than t1. The IEC-104 standard suggests 10 seconds. Link test interval (t3) This defines the interval in seconds how often the IEC-104 link is tested if there is no other activity. 38

39 Table 20: IEC-104 link test interval (t3) IEC-104 link test interval (t3) Timeout Seconds Value range Adjust this parameter according to the criticality of the link. The IEC-104 standard suggests 20 seconds but for pay-per-use GPRS connections the practical value may be substantially longer. Suspended timeout This defines the time in seconds how long a connected IEC-104 link can be in suspended state (STOPD) before the Arctic closes the connection. Table 21: IEC-104 suspended timeout IEC-104 suspended timeout Timeout Seconds Value range Using this parameter increases the probability of detecting partially closed network connections especially in UDP mode. Max sequence number These are the maximum sequence number used in IEC-104 communication. The value zero selects the standard value Table 22: IEC-104 suspended timeout IEC-104 suspended timeout Sequence number Packets Value range = as suggested by the IEC-104 standard. Cause of transmission length (IEC-104) It defines the length of IEC-104 Cause of transmission ASDU header field in bytes. Table 23: IEC-104 ASDU cause of transmission length IEC-104 ASDU cause of transmission length Field length Bytes Value range 1-3 The IEC-104 standard defines value 2. 39

40 Common address length (IEC-104) This defines the length of IEC-104 Common address ASDU header field in bytes. Table 24: IEC-104 ASDU common address length IEC-104 ASDU common address length Field length Bytes Value range 1-3 The IEC-104 standard defines value 2. Info object address length (IEC-104) This defines the length of IEC-104 Information object address ASDU header field in bytes. Table 25: IEC-104 ASDU information object address length IEC-104 ASDU information object address length 7.5 Field length Bytes Value range 1-3 The IEC-104 standard defines value 3. IEC-101 settings The IEC-101 settings define the properties of IEC-101 link layer and application layer parameters as described in the IEC standard. The IEC-101 communication is carried out between the Arctic and a IEC-101 slave. Figure 30. IEC-101 Settings 40

41 Slave link address (IEC-101) Table 26: IEC-101 slave link address IEC-101 slave link address Link address N/A Value range The link-level address of IEC-101 slave. Link address field length Defines the length of the IEC-101 link-level address field in bytes. Table 27: IEC-101 slave link address field length IEC-101 slave link address field length Field length Bytes Value range 1, 2 The link-level address of IEC-101 slave. Event poll interval It defines the IEC-101 event polling interval in 0.1 second increments (class 1 or 2 poll). Table 28: IEC-101 event poll interval IEC-101 event poll interval Interval 0.1 seconds Value range The events are polled only when the IEC-104 connection is active. Link test interval It defines the IEC-101 link test interval in 0.1 second increments. Link test is performed if there is no other activity. Table 29: IEC-101 link test interval IEC-101 link test interval Interval 0.1 seconds Value range The link test is performed if there is no other activity during defined interval. 41

42 Keep link open Defines that the IEC-101 link is kept always open even when there is no active IEC-104 connection. If the functionality is enabled the Arctic sends link test frames and restarts the IEC-101 link if the test fails. The events are still not polled before the IEC-104 connection is active. Table 30: IEC-101 keep link open IEC-101 keep link open Boolean N/A Value range No, Yes Some IEC-101 slaves require the link to be continuously open in order to operate. Reply header timeout Defines the timeout Arctic waits the reply to start from IEC-101 slave after command or request. Table 31: IEC-101 reply start timeout IEC-101 reply start timeout Timeout Milliseconds Value range Reply end timeout Defines the maximum duration of IEC-101 slave response. Table 32: IEC-101 reply end timeout IEC-101 reply end timeout Timeout Seconds Value range Retry limit Defines the number of retries sent to a IEC-101 slave in case of no reply. If no reply is still received the Arctic closes the IEC-101 and IEC-104 connections. Table 33: IEC-101 retry limit IEC-101 retry limit Retry limit 42

43 IEC-101 retry limit Retries Value range Cause of transmission length (IEC-101) Defines the length of IEC-101 Cause of transmission ASDU header field in bytes. Table 34: IEC-101 ASDU cause of transmission length IEC-101 ASDU cause of transmission length Field length Bytes Value range 1-3 The IEC-101 standard defines value 1. Common address length (IEC-101) Defines the length of the IEC-101 Common address ASDU header field in bytes. Table 35: IEC-101 ASDU common address length IEC-101 ASDU common address length Field length Bytes Value range 1-3 The IEC-101 standard defines value 2. Info object address length (IEC-101) Defines the length of IEC-101 Information object address ASDU header field in bytes. Table 36: IEC-101 ASDU information object address length IEC-101 ASDU information object address length 7.6 Field length Bytes Value range 1-3 The IEC-101 standard defines value 2. ASDU Converter The ASDU converter can be used to convert ASDU header field lengths between IEC-101 and IEC-104 protocols. 43

44 Figure 31. ASDU Converter Use ASDU converter This defines if the ASDU header level IEC-101 <-> IEC-104 conversion performed. If enabled the ASDU header field lengths are converted between IEC-104 and IEC-101. This parameter must be enabled if the ASDU header lengths differ between the IEC-104 and the IEC-101. Table 37: Use ASDU converter Use ASDU converter Boolean N/A Value range No, Yes The information on the field must fit in the shorter one of the two. It s not possible to convert e.g. value to a one byte field. Use ASDU type replacer The ASDU type replace function can be used to convert an ASDU type (Original type) to another (Applied type) type e.g. in cases when the IEC implementation differs between master and slaves. Table 38: Use ASDU type replacer Use ASDU type replacer Boolean N/A Value range No, Yes Original type The original ASDU type searched by ASDU type replacer. Applied type The new ASDU type is replaced by the original type. 7.7 Packet collector The packet collector can be used to collect many IEC-101 messages/events to a single network packet instead of sending every message separately. 44

45 This function is useful for slow packet switched communication network (e.g. Mobitex) for speeding up especially the general interrogation response. Figure 32. Packet Collector Use packet collector Table 39: Use packet collector Use packet collector Boolean N/A Value range No, Yes Max bytes Max bytes is defined as the maximum bytes trigger for packet collector. Before a new packet is inserted into the packet collector buffer the amount of bytes is checked. If the insertion of the new packet would cause the number of bytes in the packet collector to exceed MAX BYTES the old content is sent to the network before inserting the new one. Table 40: Maximum collected bytes Maximum collected bytes Packet size Bytes Value range The value should be smaller than the MTU/MRU of network used. Max time Max time is deived as the maximum collect time trigger for packet collector in 0.1 secs increments for packet collector. If there has been data on packet collector over MAX TIME the data is sent to network. Table 41: Maximum collected time Maximum collected time Timeout 0.1 seconds 45

46 Maximum collected time Value range The value must be smaller than t1. Max packets Max packets are defined as the maximum amount of IEC-101 packets stored into the packet collector before sending the data to the network. Table 42: Maximum collected packets Maximum collected packets Packet count Packets Value range Other settings Write syslog It defines whether the error messages are stored to system log file or not. Table 43: Write system log Write system log Boolean N/A Value range No, Yes The system log is available by using WEB UI. 46

47 8 Modbus application settings 8.1 Introduction These configuration instructions are intended only for configuring Modbus on Viola Arctic device. The Modbus Gateway is an adapter application enabling conversions between Serial and Network Modbus protocols. The gateway can operate on two modes; either connecting serial Masters to Slaves behind the network or connecting network Master to Serial slaves. The gateway offers following core properties: Supports Modbus RTU and Modbus ASCII serial protocols. 8.2 Supports ModbusTCP, ModbusRTU over TCP, ModbusRTU over UDP, Modbus ASCII over TCP and Modbus ASCII over UDP network protocols. It can generate and filter out gateway exceptions. It can route traffic on network based on Modbus addressing enabling intelligent use of network resources. Makes automatic connection management. Enables multiple server sessions over network. Offers unlimited amount of Masters on serial or Network side. Offers 30 routes over network to slaves. Parameters The parameters are divided into two groups: Common parameters Routes Common parameters define for e.g. the protocols used in serial and network communications, serial port settings and protocol specific timeouts. Route parameters are only required on Serial Master to Network Slaves mode defining the IP and Modbus addresses of slaves behind the network. You can change the parameter values in Serial Port and I/O > Modbus Gateway (RSx) Common parameters The common parameters define general settings and settings for Network Master to Serial Slaves mode. 47

48 Figure 33. Modbus application settings General Settings Gateway Status Table 44: Gateway Status Identifier Gateway Status Description Tthe Modbus gateway functionality enabled for the serial port. Values Enabled Modbus Gateway is enabled Disabled Modbus Gateway is not enabled s Each serial port of Arctic has its own Modbus Gateway definitions. Gateway Mode Table 45: Gateway Mode Identifier Gateway Mode Description The slaves located on network or serial side. Values Network Master to Serial Slaves Slaves are on serial side. Serial Master to Network Slaves Slaves are on network side. 48

49 Identifier Gateway Mode s If slaves are on network side, the routes are also needed to be defined. Protocols Serial Protocol Table 46: Serial Protocol Identifier Serial Protocol Description Defines the Modbus protocol used on serial communication. Values Modbus RTU Serial devices use Modbus RTU protocol Modbus ASCII Serial devices use Modbus ASCII protocol s Modbus RTU is more efficient and should be used whenever possible. Network Protocol Table 47: Network Protocol Identifier Network Protocol Description Defines the TCP/IP and Modbus protocol used on network communication. Values Modbus TCP Modbus TCP protocol over TCP Modbus RTU over TCP Modbus RTU protocol over TCP Modbus RTU over UDP Modbus RTU protocol over UDP Modbus ASCII over TCP Modbus ASCII protocol over TCP Modbus ASCII over UDP Modbus ASCII protocol over UDP s If Viola Systems M2M Gateway is used to tunnel network traffic over SSH, use Modbus RTU over UDP when possible for efficient communication. The SSH tunnel already contains TCP properties like reliable message delivery. Framing Slave Response Timeout Table 48: Slave Response Timeout Identifier Slave response timeout Description Defines the time in microseconds (10E-6 seconds) how long Arctic waits the response from Modbus slave. If the response is not received, Arctic can generate and return Modbus gateway exception. Values microseconds (0 90 seconds) 49

50 Identifier Slave response timeout s The reply timeout of Modbus Master must be greater than the Gateway (Arctic) timeout. Otherwise the flow of request-reply communication is violated. Arctic does not accept a new request before the reply from slave is received or the reply timeout is elapsed. The delays in network communication can vary especially in wireless (e.g. GPRS/EDGE/ Mobitex) networks. When the slaves are located on network side, use e.g. PING to estimate the delay packets spend on network. Inter-Frame Timeout Table 49: Inter-Frame Timeout Identifier Inter-frame timeout Description Defines the idle time in microseconds (10E-6 seconds) that marks the end of Modbus frame in serial communication. If the value is zero, the Gateway uses standard 4 character time. Values microseconds (0 2 seconds) s Use as small value as possible to speed up communication and increase the value if problems arise. Some PC programs can insert unexpected delays between serial characters. Exceptions Generate Gateway Exceptions Table 50: Generate Gateway Exceptions Identifier Generate Gateway exceptions Description Defines does the Gateway generate and return Modbus Gateway exception message to Master if no valid reply is not received from slave. Values Enabled Generation of Gateway exceptions is enabled Disabled - Generation of Gateway exceptions is disabled s This functionality is useful for debugging. See also parameter Pass Gateway exceptions. Pass Gateway Exceptions Table 51: Pass Gateway Exceptions Identifier Pass Gateway exceptions Description Defines are the Gateway exception replies from slave side passed to master. Values Enabled Gateway exception replies are passed to Master Enabled Gateway exception replies are filtered away s filtered away s 50

51 Serial Settings Serial Port Table 52: Serial Port Identifier Serial Port Description Defines the serial port that Gateway uses for Modbus serial communication. Values Port 1 Serial port 1 (RS-232 console/application port) Port 2 Serial port 2 (RS-232/422/485 application port) s If a single serial port or RS-422/485 is required, use Port 2. If Port 1 is used, the console switch of Arctic must be on Application position. DIPswitches below the DB-9 serial connector specify the RS-232/422/485 settings of Port 2. Serial Speed Table 53: Serial Speed Header 1 Speed Description Defines the serial port speed for Modbus communication. Values 300, 1200, 2400, 4800, 9600, 19200, 38400, 57600, bps s Check the speeds supported by connected Modbus equipment. If special serial port speed is required, please contact Viola Systems. Serial Data Bits Table 54: Serial Data Bits Identifier Serial Data bits Description Defines the number of data bits used on Modbus serial communications. Values 5, 6, 7, 8, Auto (8 for Modbus RTU, 7 for Modbus ASCII) s Check the data bits supported by connected Modbus equipment. Generally Modbus RTU communication uses 8 data bits and Modbus ASCII communication uses 7 data bits. Serial Stop Bits Table 55: Serial Stop Bits Identifier Serial Stop bits Description Defines the number of stop bits used on Modbus serial communications. Values 1,2 s 51

52 Serial Parity Table 56: Serial Parity Identifier Serial Parity Description Defines the parity method used on Modbus serial communication Values None no parity method used Even even parity bit generated and inspected Odd odd parity bits generated and inspected s Serial Flow Control Table 57: Serial Flow Control Identifier Serial Flow control Description Defines is the hardware (RTS/CTS) flow control used on Modbus serial communication Values Enabled RTS/CTS flow control used Disabled RTS/CTS flow control not used s Use of hardware flow control is suggested Network Settings Server TCP/UPD Port Table 58: Server TCP/UPD Port Identifier Server TCP/UDP port Description Defines the TCP or UDP port that Masters can form connections to. Default Modbus TCP/IP communication port is 502. Values s If multiple Modbus Gateways are running on same device (for both serial ports) the TCP/UDP communication ports must not be same. Use e.g. ports 502 and 504. The network and Arctic firewalls must enable TCP or UDP communication for that port. Maximum Number of Clients Table 59: Maximum Number of Clients Identifier Maximum number of clients Description Defines how many network masters can be connected to Gateway simultaneously. Values 0-20 s Generally use value at least 2 when using TCP communication. Otherwise if the Gateway does not recognize partially closed 52

53 Identifier Maximum number of clients connection, forming of new connections is not accepted by Gateway before Connection idle timeout is elapsed. Connection Idle Timeout Table 60: Connection Idle Timeout Identifier Connection idle timeout Description If the connected Master hasn t sent valid Modbus packets during that timeout the connection is closed by Arctic and therefore the resources are available for new connections. This parameter is especially useful when the network connection is not reliable causing hanging or partially closed connections. Values seconds s Set this value about two times the polling interval of master. Enable Keepalive Table 61: Enable Keepalive Identifier Enable keepalive Description Defines is the connection testing enabled for TCP network communication. Values Enabled Testing the TCP connection with Master is enabled Disabled Testing the TCP connection with Master is disabled s The testing is done by sending TCP keepalive packets on certain intervals. Routes When the Arctic Modbus Gateway is configured to Serial Master to Network Slaves mode the routes are needed to be defined for each connected Modbus slave. Gateway can route traffic based on Modbus addressing therefore enabling more efficient communication where each slave receives only data addressed to it. Route in Use Table 62: Route in Use Identifier Route in use Description Defines is this route entry used to decide to which IP address Modbus request is sent. Values Yes Route information is used No Route information is not used s If no route is found for Modbus request is it dropped and Gateway exception is generated if enabled. 53

54 Host Table 63: Host Identifier Host Description Defines the IP address or Host name where packets are routed by that entry. Values IP address or Host name s If Host names are used the DNS server IP address is required to be defined on Arctic Network settings. The Network Protocol setting on Common parameters defines the network- and Modbus protocol used on network communication. TCP or UDP Destination Port Table 64: TCP or UDP Destination Port Identifier TCP or UDP destination port Description Defines the UDP or TCP destination port where this route entry sends Modbus requests. Values (Modbus default is 502) s The port must be same as used on the network slave device or Gateway behind network. Filter Slave Address Table 65: Filter Slave Address Identifier Filter slave address Description Defines is the routing based on Modbus addresses used for that entry. If not enabled every Modbus request is routed to this entry. If enabled only Modbus requests having destination address matching the Address list of entry are routed. Values Yes Route entry checks for Modbus destination address No Route entry enables any Modbus destination address s It s generally good to use Modbus address filtering avoiding unnecessary network traffic. Address to Filter Table 66: Address to Filter Identifier Address to filter Description Comma separated list of the Modbus addresses of slaves behind on this route entry (max. 20 pcs.). 54

55 Identifier Address to filter Values Maximum 20 pcs. of comma (,) separated Modbus destination addresses. s The Filter Slave address parameter of Route entry needs to be enabled these addresses to take effect. Connection Idle Timeout Table 67: Connection Idle Timeout Identifier Connection idle timeout Description If there hasn t been communication on this route during given amount of seconds the Gateway automatically closes the TCP connection to slave and therefore frees Slave s communication resources. This is especially useful when multiple Masters access same Slave. Values seconds s Set this parameter about two times the polling interval of Master. Enable TCP Keepalive Table 68: Enable TCP Keepalive Identifier Enable TCP keepalive Description Defines is the connection testing enabled for TCP network communication. Values Enabled Testing the TCP connection with Slave is enabled Disabled Testing the TCP connection with Slave is disabled s 8.3 The testing is done by sending TCP keepalive packets on certain intervals. Configuring Network Master to Serial Slaves Mode When the PLC/RTU slaves supporting serial based Modbus communication are required to be controlled over TCP/IP networks the Gateway on slave side needs to be configured to Network Master-Serial Slaves mode. 55

56 Figure 34. Arctic Modbus Gateway connecting serial slaves to network On that mode, the Arctic acts like network server where Masters (clients) can connect (the default port being 502) and transmit Modbus requests. The Arctic makes conversions between network and serial protocols. If the slave does not reply during defined timeout or if the reply is corrupted, the Arctic sends gateway exception message back to Master if the exception generation is enabled. Otherwise, the reply is returned. Multiple masters can connect simultaneously to Gateway, which handles the multiplexing between masters.! Each Arctic must have a fixed IP address in order the Master to know where to connect. Many client-use optimized networks (like public GPRS, xdsl) does not offer fixed IP addresses but allocate them dynamically. This situation can be solved by using Viola Systems M2M Gateway Settings Common parameters Only the common parameters are configured. The routes are unused on Network Master to Serial Slaves mode. The configuration menu is located on Applications > Modbus GW menu of Arctic WEB configuration. 56

57 Figure 35. Example of common parameters for Network Master to Serial Slaves mode Table 69: Setting guideline for Network Master to Serial Slaves mode Parameter Value Parameter Value Gateway Status Enabled Gateway Mode Network Master to Serial Slaves Serial Protocol Depends on connected Modbus slave Prefer Modbus RTU when possible Network Protocol Depends on Master side If Viola Systems M2M tunneling is used, prefer UDP based Modbus network messaging. Slave response Depends on connected Modbus timeout slave Increase this value if problem is on serial communication. Inter-frame timeout Modbus RTU protocol has standard timeout of 4 character time. Use value 0 for default. Increase this value if the problem is on serial communication. Generate Gateway exceptions Enable or Disable Enabling Gateway Exceptions can help system debugging and testing. Pass Gateway exceptions Enable or Disable Serial Port Select Port 1 or Port 2 Serial Speed Depends on connected Modbus slave. If single serial port or RS-422/485 functionality is required, use Port 2. Serial Data Bits Depends of connected Modbus slave. Use of Auto selects 8 data bits for Modbus RTU and 7 data bits for Modbus ASCII. 57

58 Parameter Value Serial Stop Bits Depends on connected Modbus slave. Serial Parity Depends on connected Modbus slave. Select None, Even or Odd. Serial HW Handshaking Enable if require by slave. Server TCP/ UDP Port Default port for Modbus network communication is 502. Max. Number of clients Normally use minimum value 2. If the network is wireless or If multiple Masters are allowed to unreliable, increase this value connect, then increase the value. if there is a problem during the connection. If multiple Protocol Gateway applications are running on same Arctic, the ports must be different for each application. Use e.g. ports 502 and 504. Connection idle Set about two times the polling timeout interval of Master. If the polling interval is very long (over hour) use e.g. polling interval+200 seconds Enable keepalive Enabled if the polling interval or idle timeout is very long. Saving Parameters When the settings are complete, press the Apply button and permanently store the parameters by clicking on Commit button. Wait for acknowledgement after pressing the Commit button. Now reboot the Arctic by pressing Reboot button. The Arctic is now ready to deliver data from Network Masters to Serial Slaves. 8.4 Configuring Serial Master to Network Slaves Mode When Modbus Master supporting serial based Modbus, communication needs to control slaves over TCP/IP network. The Gateway on Master side needs to be configured to Serial Master Network Slaves mode. 58

59 Figure 36. Arctic connecting serial Master to network On that mode, the Arctic routes serial Modbus packets to network and performs conversions between serial and network protocols. The routing based on Modbus addressing allows intelligent use of network resources, which is especially useful for pay-per-use networks like GPRS. The settings consist of two parts: Common settings Settings for each route Settings Common Parameters The configuration menu is located on Applications > Modbus GW menu of Arctic WEB configuration. 59

60 Figure 37. Example of common parameters for Serial Master to Network Slaves mode Table 70: Setting guideline for Network Master to Serial Slaves mode Parameter Value Gateway Status Enabled Gateway Mode Serial Master to Network Slaves Serial Protocol Depends of connected Modbus Master Prefer Modbus RTU when possible Network Protocol Depends of Slave devices If Viola Systems M2M tunneling is used, prefer UDP based Modbus network messaging. Slave response Depends of connected Modbus timeout slave and delays of TCP/IP network. Increase this value if problems on slave communication. Inter-frame timeout Modbus RTU protocol has standard timeout of 4 character time. Use value 0 for default Increase this value if problems on serial communication Generate Gateway exceptions Enable or Disable Enabling Gateway Exceptions can help system debugging and testing Pass Gateway exceptions Enable or Disable Serial Port Select Port 1 or Port 2 Serial Speed Depends of connected Modbus Master 60 If single serial port or RS-422/485 functionality is required use Port 2

61 Parameter Value Serial Data Bits Depends of connected Modbus Master. Use of Auto selects 8 data bits for Modbus RTU and 7 data bits for Modbus ASCII. Serial Stop Bits Depends of connected Modbus Master Serial Parity Depends of connected Modbus Master. Select None, Even or Odd Serial HW Handshaking Enable if require by Master Server TCP/ UDP Port Default port for Modbus network Value is not used on Serial communication is 502 Master to Network Slaves mode. Max. Number of clients Normally use minimum value 2. If multiple Masters are allowed to connect increase the value. Value is not used on Serial Master to Network Slaves mode. Connection idle Set about two times the polling timeout interval of Master. If the polling interval is very long (over hour) use e.g. polling interval+200 seconds Value is not used on Serial Master to Network Slaves mode. Each route entry has it s own idle timeout. Enable keepalive Value is not used on Serial Master to Network Slaves mode. Each route entry has it s own keepalive setting. Enable if the polling interval or idle timeout is very long. Settings Routes The route entries define how Modbus packets are routed on network from Serial Master to Network Slaves. Up to 30 routes can be specified each having up to 20 slaves. If the routing is based on Modbus addressing is not required or there are more than 20 slaves behind the route, the address filtering for that entry can be disabled. Figure 38. Route summary The route entry can be edited by pressing Edit button. The routes can also be disabled or enabled by pressing following buttons: Disables the Route entry Enables the Route Entry The active routes do not have strikethrough line. 61

62 Pressing the Edit button opens following configuration screen: Figure 39. Route edit Table 71: Setting guidelines for Routes Parameter Value Route in use Enable or Disable Each IP address and TCP/UDP port of slaves needs to be defined on separate route entries. Host The IP address or Host name of slave or Gateway behind the route. If Host names are used the DNS server IP address is required to be defined on Arctic Network settings. The Network Protocol setting on Common parameters defines the network- and Modbus protocol used on network communication. TCP or UDP destination port The TCP or UDP port that slave or Gateway on slave side is listening. Default Modbus port is 502. Filter slave addresses Defines is the routing based on Modbus addresses used for that entry. If not enabled, every Modbus request is routed to this entry. If enabled only Modbus requests having destination address matching the Address list of entry are routed. It s generally good to use routing based on Modbus addressing in order to avoid unnecessary network traffic. Address to filter Comma separated list (max 20 The Filter Slave address pcs.) of Modbus slave addresses parameter of Route entry needs behind this route entry. to be enabled these addresses to take effect. Connection idle timeout (TCP) Set about two times the polling interval of Master. If the polling interval is very long (over hour) use e.g. polling interval+200 seconds. Enable TCP keepalive Enable if the polling interval or idle timeout is very long. 62

Arctic Modbus Gateway Configuration Manual

Arctic Modbus Gateway Configuration Manual Copyright and Trademark Copyright 2004, Viola Systems Ltd. All rights to this manual are owned solely by Viola Systems Ltd. (referred in this manual as Viola Systems). All rights reserved. No part of the

More information

Wireless Gateway ARG600 Single SIM Variant User Manual

Wireless Gateway ARG600 Single SIM Variant User Manual Wireless Gateway ARG600 Single SIM Variant Document ID: 1MRS758456 Issued: 2017-09-22 Revision: B Product version: 3.4 Copyright 2017 ABB. All rights reserved Copyright This document and parts thereof

More information

Wireless Protocol Gateway ARP600 Single SIM Variants User Manual

Wireless Protocol Gateway ARP600 Single SIM Variants User Manual Wireless Protocol Gateway ARP600 Single SIM Variants Document ID: 1MRS758457 Issued: 2015-12-18 Revision: A Product version: A Copyright 2015 ABB. All rights reserved Copyright This document and parts

More information

Wireless Gateway ARG600 Dual SIM Variant User Manual

Wireless Gateway ARG600 Dual SIM Variant User Manual Wireless Gateway ARG600 Dual SIM Variant Document ID: 1MRS758460 Issued: 2017-09-22 Revision: B Product version: 3.4 Copyright 2017 ABB. All rights reserved Copyright This document and parts thereof must

More information

Arctic IEC-104 Gateway User's Manual. Arctic IEC-104 Gateway (2205)

Arctic IEC-104 Gateway User's Manual. Arctic IEC-104 Gateway (2205) (2205) September 2010 Copyright and Trademark Copyright 2008-2010, Viola Systems Ltd. All rights to this manual are owned solely by Viola Systems Ltd. (referred elsewhere in this User s Manual as Viola

More information

+70 C -25 C 95% RH EMC

+70 C -25 C 95% RH EMC +70 C -25 C 95% RH EMC TK701G TK701U TK711U TK704G TK704U TK714U TK704W TK700 The industrial 2G GPRS- and 3G UMTS routers offered by Welotec enables the access to Ethernet devices or a local network remotely

More information

Industrial Serial Device Server

Industrial Serial Device Server 1. Quick Start Guide This quick start guide describes how to install and use the Industrial Serial Device Server. Capable of operating at temperature extremes of -10 C to +60 C, this is the Serial Device

More information

NCOM SERIAL DEVICE SERVER 1XX SERIES USER S MANUAL

NCOM SERIAL DEVICE SERVER 1XX SERIES USER S MANUAL NCOM SERIAL DEVICE SERVER 1XX SERIES USER S MANUAL 2017-07-07 Edition Titan Electronics Inc. Web: www.titan.tw Contents 1. INTRODUCTION... 4 1.1 Key Features... 5 1.2 Specifications... 6 2. PANEL LAYOUT

More information

Arctic User s Manual. Arctic IEC-104 Gateway

Arctic User s Manual. Arctic IEC-104 Gateway Arctic User s Manual Arctic IEC-104 Gateway Version 1.4.8 October 2005 Copyright and Trademark Copyright 2004-2005, Viola Systems Ltd. All rights to this manual are owned solely by Viola Systems Ltd. (referred

More information

SMM Series 3G and GSM Modems. Quick Start Guide. Document Number: Version: 1.2 (20 October, 2015)

SMM Series 3G and GSM Modems. Quick Start Guide. Document Number: Version: 1.2 (20 October, 2015) SMM Series 3G and GSM Modems Quick Start Guide Document Number: 0013-001-000272 () Documentation Control Generation Date: October 20, 2015 Cybertec Pty Limited All rights Reserved. No part of this publication

More information

MRD-310 MRD G Cellular Modem / Router Web configuration reference guide. Web configuration reference guide

MRD-310 MRD G Cellular Modem / Router Web configuration reference guide. Web configuration reference guide Web configuration reference guide 6623-3201 MRD-310 MRD-330 Westermo Teleindustri AB 2008 3G Cellular Modem / Router Web configuration reference guide www.westermo.com Table of Contents 1 Basic Configuration...

More information

NCOM SERIAL DEVICE SERVER 4XX SERIES USER S MANUAL

NCOM SERIAL DEVICE SERVER 4XX SERIES USER S MANUAL NCOM SERIAL DEVICE SERVER 4XX SERIES USER S MANUAL 2017-07-07 Edition Titan Electronics Inc. Web: www.titan.tw Contents 1. INTRODUCTION... 4 1.1 Key Features... 5 1.2 Specifications... 6 2. PANEL LAYOUT

More information

USER S MANUAL. PH232Ex1. #1 RS-232 Serial Port to Ethernet, Terminal Server/Client. Doc No: PH232Ex1-UM-001 IPEX. (IP Electronix)

USER S MANUAL. PH232Ex1. #1 RS-232 Serial Port to Ethernet, Terminal Server/Client. Doc No: PH232Ex1-UM-001 IPEX. (IP Electronix) USER S MANUAL PH232Ex1 Doc No: PH232Ex1-UM-001 #1 RS-232 Serial Port to Ethernet, Terminal Server/Client IPEX (IP Electronix) Contents 1. INTRODUCTION... 3 2. SPECIFICATIONS... 3 3. PACKAGE CHECKLIST...

More information

Motortronics VirtualSCADA VS2-MT Communication Gateway VS2-MT User Manual Revision

Motortronics VirtualSCADA VS2-MT Communication Gateway VS2-MT User Manual Revision Motortronics VirtualSCADA VS2-MT Communication Gateway VS2-MT User Manual Revision 1.03.00 Motortronics / Phasetronics 1600 Sunshine Drive Clearwater, Florida 33765 Tel: 727-573-1819 Fax: 727-573-1803

More information

IDS-141A/181A. Industrial 4-port/8-port slim type serial to Ethernet device server. Features. Introduction. DS-Tool

IDS-141A/181A. Industrial 4-port/8-port slim type serial to Ethernet device server. Features. Introduction. DS-Tool 4/8 Port v1.5 / Dec, 2011 Features 4-port/8-port slim type serial to Ethernet device server Operating Modes : Virtual Com, Tunnel, TCP Server, TCP Client, UDP Multiple host devices : 5 host devices: Virtual

More information

Viola M2M Gateway. OpenVPN Application Note. Document version 1.0 Modified September 24, 2008 Firmware version 2.4

Viola M2M Gateway. OpenVPN Application Note. Document version 1.0 Modified September 24, 2008 Firmware version 2.4 Viola M2M Gateway OpenVPN Application Note Document version 1.0 Modified September 24, 2008 Firmware version 2.4 Contents 1 OpenVPN overview 4 1.1 VPN basics................................................

More information

User Manual A08. User Manual

User Manual A08. User Manual A08 TABLE OF CONTENTS TABLE OF CONTENTS... 1 1. INTRODUCTION... 2 1.1. Key Features... 3 1.2. OS Requirement... 4 1.3. Specification... 4 1.4. Packing List... 4 2. OVERVIEW... 5 2.1. LED Definition...

More information

SSE232-LE Serial Server- User s Manual

SSE232-LE Serial Server- User s Manual www.exemys.com Rev.6 1 Products are in constant evolution to satisfy our customer needs. For that reason, the specifications and capabilities are subject to change without prior notice. Updated information

More information

TK C -25 C 95% RH EMC TK701G TK701U TK704G TK704U TK704W. TK-Series Cellular Router

TK C -25 C 95% RH EMC TK701G TK701U TK704G TK704U TK704W. TK-Series Cellular Router +70 C -25 C 95% RH EMC TK701G TK701U TK704G TK704U TK704W The industrial 2G GPRS- and 3G UMTS routers offered by Welotec enables the access to Ethernet devices or a local network remotely via mobile network

More information

Document Name: User Manual for SC10MK, Modbus RTU to Modbus TCP Converter

Document Name: User Manual for SC10MK, Modbus RTU to Modbus TCP Converter Document Name: User Manual for SC10MK, Modbus RTU to Modbus TCP Converter Login for the first time, please use http://192.168.1.100 To key in user name and password is for identifying authorization. Default

More information

OnCell G3150A-LTE Series

OnCell G3150A-LTE Series OnCell G3150A-LTE Series Rugged LTE serial/ethernet-to-cellular gateways Features and Benefits Dual cellular operator backup with dual-sim GuaranLink for reliable cellular connectivity Rugged hardware

More information

HOME AUTOMATION, INC. Model 93A00-1. Serial Server. User s Manual

HOME AUTOMATION, INC. Model 93A00-1. Serial Server. User s Manual HOME AUTOMATION, INC. Model 93A00-1 Serial Server User s Manual Document Number 93I00-1 Rev. A December, 2009 Introduction The 93A00-1 is a RS232/RS485 to TCP/IP converter integrated with a robust system

More information

MGate 5105-MB-EIP Series

MGate 5105-MB-EIP Series MGate 5105-MB-EIP Series 1-port Modbus RTU/ASCII/TCP-to-EtherNet/IP gateways Features and Benefits Protocol conversion between Modbus and EtherNet/IP Supports EtherNet/IP Scanner/Adapter Supports Modbus

More information

USER MANUAL FOR GS100/GS1003G

USER MANUAL FOR GS100/GS1003G USER MANUAL FOR GS100/GS1003G 1 Table of Contents 1. INTRODUCTION... 3 2. FEATURES... 3 3. OPERATION... 3 4.CONNECTION DETAILS... 4 5.CONFIGURATION... 5 5.1 Hyper Terminal Setting... 5 5.2 GS100 Configuration...

More information

Wireless Gateway ARG600 Product Guide

Wireless Gateway ARG600 Product Guide Wireless Gateway Product Guide Contents 1. Description... 3 2. Complete communication system...3 3. Application... 4 4. Physical interfaces...5 5. Communication... 11 6. Technical data...12 7. Mounting...16

More information

ABLELink. Modbus Gateway MB5000 Series User s Manual

ABLELink. Modbus Gateway MB5000 Series User s Manual ABLELink MB5000 Series User s Manual Version 1.1 Updated in March, 2010 TEL: 886-3-5508137 FAX: 886-3-5508131 http://www.atop.com.tw Table of Contents Table of Contents... 2 Introduction... 4 Features...

More information

NetCom Plus 113. Contact Online. More Pictures. Click on the thumbnails for the large picture. Overview

NetCom Plus 113. Contact Online. More Pictures. Click on the thumbnails for the large picture. Overview VS Vision Systems GmbH / Part Number 6645 Features Controls 1 RS232/422/485 device located virtually anywhere via Ethernet, WLAN or Internet Easy selection of RS232, RS422 or RS485 by single DIP switch

More information

Features. Preliminary. Industrial IEEE b/g/n with 2x10/100Base-T(X) 1x RS-232/422/485 IoT LTE LPWAN Gateway. Introduction

Features. Preliminary. Industrial IEEE b/g/n with 2x10/100Base-T(X) 1x RS-232/422/485 IoT LTE LPWAN Gateway. Introduction IMG-4312-MN Industrial IEEE 802.11 b/g/n with 2x10/100Base-T(X) 1x RS-232/422/485 IoT LTE LPWAN Gateway Features Provide 2x10/100Base-T(x) port and single SIM card slot LTE CAT-M1/CAT-NB1 model included

More information

User Manual Anybus Serial Server

User Manual Anybus Serial Server User Manual Anybus Serial Server Rev. 1.20:1 HMS Industrial Networks AB Germany Japan Sweden U.S.A UK + 49-721 - 96472-0 + 81-45 - 478-5340 + 46-35 - 17 29 20 + 1-773 - 404-3486 + 44 (0) 1908-359301 ge-sales@hms-networks.com

More information

Overview. Table of contents

Overview. Table of contents 1 Table of contents Overview... 1 Applications... 2 Connecting and adjusting of converter... 3 Communication parameters adjusting... 5 RealPort - virtual serial port... 12 Installing virtual serial port

More information

Industrial Device Server IDS-3010 Fiber Series

Industrial Device Server IDS-3010 Fiber Series USER S MANUAL Industrial Device Server IDS-3010 Fiber Series Ver. 1.0, Jan. 2008 Table of Content Getting to Know Your Device Server... 3 1.1 About the IDS-3010 Serial Device Server... 3 1.2 Software Features...

More information

NetCom Plus 113 (NetCom 113, NetCom 113 PRO)

NetCom Plus 113 (NetCom 113, NetCom 113 PRO) VS Vision Systems GmbH / Part Number 6645 Main Features Ethernet to serial 1 port RS232/422/485 Virtual Com Port driver for Windows Secure Server with latest SSL/AES-256 encryption Operation in Driver

More information

NetCom Plus 413 POE. Contact Online. More Pictures. Click on the thumbnails for the large picture. Overview

NetCom Plus 413 POE. Contact Online. More Pictures. Click on the thumbnails for the large picture. Overview VS Vision Systems GmbH / Part Number 6676 NetCom Plus 413 POE Features Controls 4 RS232 or RS422/485 devices located virtually anywhere via Ethernet, WLAN or Internet Easy selection of RS232, RS422 or

More information

EGW1-IA3-MB User s Manual

EGW1-IA3-MB User s Manual www.exemys.com Rev. 0 1 Products are in constant evolution to satisfy our customer needs. For that reason, the specifications and capabilities are subject to change without prior notice. Updated information

More information

Wireless Gateway ARG600 ANSI Product Guide

Wireless Gateway ARG600 ANSI Product Guide Product Guide Contents 1. Description... 3 2. Complete communication system...3 3. Application...4 4. Physical interfaces... 6 5. Communication... 9 6. Technical data... 10 7. Mounting... 14 8. Ordering

More information

EtherSeries Modbus Gateway EMB-2 User s Guide

EtherSeries Modbus Gateway EMB-2 User s Guide EtherSeries Modbus Gateway EMB-2 User s Guide Revised March 25, 2004 Firmware Version 1.4 FCC Statement This device complies with the limits for a Class B digital device, pursuant to Part 15 of the FCC

More information

SATEL I-LINK 100 MB I/O-converter User Guide, Version 1.1

SATEL I-LINK 100 MB I/O-converter User Guide, Version 1.1 TABLE OF CONTENTS TABLE OF CONTENTS... 1 IMPORTANT NOTICE... 2 PRODUCT CONFORMITY... 3 WARRANTY AND SAFETY INSTRUCTIONS... 4 1 GENERAL... 5 1.1 SATEL I-LINK 100 MODBUS I/O- CONVERTER... 5 2 SPECIFICATIONS...

More information

Ethernet Serial Server

Ethernet Serial Server Ethernet Serial Server Users Manual Eport-101, Eport-102, Eport-104, Eport108 1 INTRODUCTION... 1 1.1 FEATURES... 1 1.2 PRODUCT SPECIFICATIONS... 2 1.3 DEFAULT SETTINGS... 3 2 COMMUNICATION MODES... 4

More information

User Manual Anybus Modbus TCP/RTU Gateway

User Manual Anybus Modbus TCP/RTU Gateway User Manual AB7702 Rev. 2.01 Connecting Devices TM HMS Industrial Networks Mailing address: Box 4126, 300 04 Halmstad, Sweden Visiting address: Stationsgatan 37, Halmstad, Sweden E-mail: info@hms-networks.com

More information

RM6000 GPRS Modem / Router

RM6000 GPRS Modem / Router User Manual Version 6.30 AMG Systems Ltd March 2013 3 The Omega Centre Stratton Business Park Biggleswade Bedfordshire, UK SG18 8QB Tel: 44 (0) 1767 600777 sales@amgsystems.com 1. Introduction 2. RM6000

More information

rbox610 Series Robust Din-rail Fanless Embedded System Web Configuration and App Software User s Manual

rbox610 Series Robust Din-rail Fanless Embedded System Web Configuration and App Software User s Manual rbox610 Series Robust Din-rail Fanless Embedded System Web Configuration and App Software User s Manual Disclaimers This manual has been carefully checked and believed to contain accurate information.

More information

TRP-C37M User s Manual

TRP-C37M User s Manual TRP-C37M User s Manual MODBUS TCP to RTU/ASCII Gateway Printed May. 2011 Rev 1.1 Trycom Technology Co., Ltd 1F, No.2-11, Sihu street, Yingge Township, Taipei, Taiwan ROC Tel: 886-2-86781191, Fax: 886-2-86781172

More information

NetCom Plus 111 (NetCom 111)

NetCom Plus 111 (NetCom 111) VS Vision Systems GmbH / Part Number 6640 Main Features Ethernet to serial 1 port RS232 Virtual Com Port driver for Windows Secure Server with latest SSL/AES-256 encryption Operation in Driver Mode, TCP/IP

More information

SMG-1100/6100 User s Manual

SMG-1100/6100 User s Manual User s Manual First Edition, January 2011 www.moxa.com/product 2011 Moxa Inc. All rights reserved. Reproduction without permission is prohibited. User s Manual The software described in this manual is

More information

Communication adapter RS232 over the Wi-Fi ELO E231. User manual

Communication adapter RS232 over the Wi-Fi ELO E231. User manual Communication adapter RS232 over the Wi-Fi ELO E231 User manual Table Of Content: 1.0 Introduction...3 1.1 Application...3 2.0 How does it works?...4 3.0 Installation...4 3.1 Wi-Fi connection...4 3.2 RS-232

More information

Quick Installation Guide

Quick Installation Guide Quick Installation Guide DL-200 Cellular Data logger V1.2_201610 TABLE OF CONTENTS CHAPTER 1 INTRODUCTION... 4 1.1 CONTENTS LIST... 5 1.2 HARDWARE INSTALLATION... 6 1.2.1 WARNING... 6 1.2.2 SYSTEM REQUIREMENTS...

More information

Installation and Configuration Quick Guide R3000. Industrial Dual SIM Cellular VPN Router 2 Eth + 1 RS RS USB Host.

Installation and Configuration Quick Guide R3000. Industrial Dual SIM Cellular VPN Router 2 Eth + 1 RS RS USB Host. Package Contents Installation and Configuration Quick Guide Before installing your R3000 Router, verify the kit contents as following. 1 x Robustel R3000 Industrial Dual SIM Cellular VPN Router (GPS/WiFi

More information

NetBiter Serial Server User Manual

NetBiter Serial Server User Manual User Manual IntelliCom Innovation AB Linjegatan 3D SE-302 50 Halmstad SWEDEN Phone +46 35 18 21 70 Fax +46 35 17 29 09 email info@intellicom.se web www.intellicom.se Revision List Revision Date Author

More information

TRP-C37M User s Manual

TRP-C37M User s Manual TRP-C37M User s Manual MODBUS TCP to RTU/ASCII Gateway Printed OCT. 2010 Rev 1.0 Trycom Technology Co., Ltd 1F, No.2-11, Sihu street, Yingge Township, Taipei, Taiwan ROC Tel: 886-2-86781191, Fax: 886-2-86781172

More information

Features and Benefits. Certifications

Features and Benefits. Certifications MGate 5111 Series 1-port Modbus/PROFINET/EtherNet/IP to PROFIBUS slave gateways Features and Benefits Protocol conversion between Modbus, PROFINET, EtherNet/IP, and PROFIBUS Supports PROFIBUS DP V0 slave

More information

SerialComm ETH-SER-EE9 Serial Device Server / Ethernet to Serial Converter User Manual

SerialComm ETH-SER-EE9 Serial Device Server / Ethernet to Serial Converter User Manual SerialComm ETH-SER-EE9 Serial Device Server / Ethernet to Serial Converter User Manual Version 1.2 - April 22, 2015 CHANGE HISTORY Version Date Description of Changes 1.0 February 16, 2015 Initial Publication

More information

Embedded Modbus TCP Module GS11-MT. User Manual REV 1.1. SST Automation.

Embedded Modbus TCP Module GS11-MT. User Manual REV 1.1. SST Automation. Embedded Modbus TCP Module GS11-MT User Manual REV 1.1 SST Automation E-mail: SUPPORT@SSTCOMM.COM WWW.SSTCOMM.COM Catalog 1 About the Embedded Module... 4 1.1 General...4 1.2 Features... 4 1.3 Specifications...4

More information

NetCom Plus 411 (NetCom 411, NetCom 411 PRO)

NetCom Plus 411 (NetCom 411, NetCom 411 PRO) VS Vision Systems GmbH / Part Number 6670 Main Features Ethernet to serial 4 port RS232 Virtual Com Port driver for Windows Secure Server with latest SSL/AES-256 encryption Operation in Driver Mode, TCP/IP

More information

NetCom Plus 211. Contact Online. More Pictures. Click on the thumbnails for the large picture. Overview

NetCom Plus 211. Contact Online. More Pictures. Click on the thumbnails for the large picture. Overview VS Vision Systems GmbH / Part Number 6650 Features Controls 2 RS232 devices located virtually anywhere via Ethernet, WLAN or Internet Port expansion over USB A connector LAN 1000/100/10 Ethernet auto-detect

More information

LM300 Manager User Manual. Document Version: 1.1 LM300 Firmware Version: Bluetooth Firmware Version:

LM300 Manager User Manual. Document Version: 1.1 LM300 Firmware Version: Bluetooth Firmware Version: LM300 Manager User Manual Document Version: 1.1 LM300 Firmware Version: 2.0.1 Bluetooth Firmware Version: 7.5.4279 LM300 Bluetooth Ethernet Access Point LM300 Manager User Manual i Revision Date Description

More information

NetCom 413 PRO. Contact Online. More Pictures. Klick on the thumbnails for the large picture. Overview

NetCom 413 PRO. Contact Online. More Pictures. Klick on the thumbnails for the large picture. Overview VS Vision Systems GmbH / Part Number 676 Features Controls 4 RS232/422/485 devices located virtually anywhere via Ethernet or Internet Secure encryption on Ethernet LAN interface 10BaseT/100BaseTx Ethernet

More information

RS232/RS485/RS422 to TCP/IP Converter ITEM NO.: RS007

RS232/RS485/RS422 to TCP/IP Converter ITEM NO.: RS007 RS232/RS485/RS422 to TCP/IP Converter ITEM NO.: RS007 RS007 is a universal data converter which support serial RS232, RS422 and RS485 to the TCP / IP intelligent communication converter, it offers RS485/RS422

More information

Industrial 1-port RS422/485 Modbus Gateway

Industrial 1-port RS422/485 Modbus Gateway Industrial 1-port RS422/485 Serial Interface One RS422/485 port with 5-contact terminal block Cost effective for RS422/ to Fast Ethernet 10/100BASE- TX application Supports 4-wire RS422 or 2-wire with

More information

Support 1 RS-232 or RS-485/422 serial port to 1 10/100Base-T(X) self-adaptive Ethernet interface

Support 1 RS-232 or RS-485/422 serial port to 1 10/100Base-T(X) self-adaptive Ethernet interface GW1101 Series Wall Mounting 1 RS-232 or RS-485/422 Modbus Gateway Support 1 RS-232 or RS-485/422 serial port to 1 10/100Base-T(X) self-adaptive Ethernet interface Support conversion between Modbus RTU/ASCII

More information

TRP-C37 User s Manual

TRP-C37 User s Manual TRP-C37 User s Manual Ethernet to RS232/422/485 Converter Printed Oct. 2010 Rev 1.0 Trycom Technology Co., Ltd 1F, No.2-11, Sihu street, Yingge Township, Taipei, Taiwan ROC Tel: 886-2-86781191, Fax: 886-2-86781172

More information

Real/Virtual COM. JetPort Commander

Real/Virtual COM. JetPort Commander INDUSTRIAL SERIAL DEVICE SERVER 1-port RS-232/422/485 Serial Device Server 5601 The 5601 is a RS-232/422/485 to Redundant Serial Device Server. The serial interface is configurable in software and supports

More information

isma-b-mg-ip User Manual Global Control 5 Sp. z o.o. Poland, Warsaw

isma-b-mg-ip User Manual Global Control 5 Sp. z o.o. Poland, Warsaw isma-b-mg-ip User Manual Global Control 5 Sp. z o.o. Poland, Warsaw www.gc5.pl Table of content 1 Introduction... 4 1.1 Revision history... 5 1.2 Safety rules... 5 1.3 Technical specifications... 6 1.4

More information

Installation and Configuration Quick Guide. R3000 Lite. Industrial Dual SIM Cellular VPN Router (1 Eth + 1 RS RS USB Host)

Installation and Configuration Quick Guide. R3000 Lite. Industrial Dual SIM Cellular VPN Router (1 Eth + 1 RS RS USB Host) Package Contents Before installing your R3000 Lite Router, please verify the kit contents as following. 1 x Robustel R3000 Lite Industrial Dual SIM Cellular VPN Router 1 x 3-pin pluggable terminal block

More information

UPGRADING THE ARCTIC FIRMWARE

UPGRADING THE ARCTIC FIRMWARE Viola Systems Ltd. tel +358-(0)201-226 226 Lemminkäisenkatu 14-18B fax +358-(0)201-226 220 FIN-20520, Turku e-mail support@violasystems.com Finland APPLICATION NOTE VA-09-5-2 UPGRADING THE ARCTIC FIRMWARE

More information

iologik E1200H Series

iologik E1200H Series iologik E1200H Series Ethernet remote I/O for offshore wind power applications Features and Benefits User-definable Modbus TCP Slave addressing 2-port Ethernet switch for daisy-chain topologies Active

More information

USR-G781 User Manual. File Version: V Jinan USR IOT Technology Limited 1

USR-G781 User Manual. File Version: V Jinan USR IOT Technology Limited 1 USR-G781 User Manual File Version: V1.0.06.02 1 Contents USR-G781 User Manual...1 Brief Introduction... 4 Features... 4 1. Get Start...5 1.1. Application... 5 1.1.1. Application Diagram...5 1.1.2. Hardware

More information

International Headquarters. European Headquarters

International Headquarters. European Headquarters VLINX VESP211 SERIAL SERVER Document Name: VESP211_R002_1116 Revision: March 2016 This product designed and manufactured in Ottawa, Illinois USA using domestic and imported parts by International Headquarters

More information

MGate 4101-MB-PBS Series

MGate 4101-MB-PBS Series MGate 4101-MB-PBS Series 1-port Modbus RTU/ASCII-to-PROFIBUS slave gateways Features and Benefits Protocol conversion between Modbus and PROFIBUS Supports PROFIBUS DP V0 slave Supports Modbus RTU/ASCII

More information

ECAN-240. (Modbus TCP to 2-port CAN Bus Gateway User manual) ECAN-240 Modbus TCP to 2-port CAN Bus Gateway User Manual, Version 1.0.

ECAN-240. (Modbus TCP to 2-port CAN Bus Gateway User manual) ECAN-240 Modbus TCP to 2-port CAN Bus Gateway User Manual, Version 1.0. ECAN-240 (Modbus TCP to 2-port CAN Bus Gateway User manual) ECAN-240 Modbus TCP to 2-port CAN Bus Gateway User Manual, Version 1.0.0 Page: 1 Table of Contents Table of Contents -----------------------------------------------------------------------------2

More information

Industrial 2-port RS422/485 Modbus Gateway

Industrial 2-port RS422/485 Modbus Gateway 2-port RS422/485 Serial Interface Two RS422/485 ports with 5-contact terminal block Cost effective for RS422/ to Fast Ethernet 10/100BASE- TX application Supports 4-wire RS422 or 2-wire with 5-contact

More information

Arctic User's Manual. Arctic GPRS Router (2270)

Arctic User's Manual. Arctic GPRS Router (2270) Arctic (2270) April 2010 Copyright and Trademark Copyright 2008-2010, Viola Systems Ltd. All rights to this manual are owned solely by Viola Systems Ltd. (referred elsewhere in this User s Manual as Viola

More information

International Headquarters. European Headquarters

International Headquarters. European Headquarters VLINX VESP211 SERIAL SERVER Document Name: VESP211_R002_0613 Revision: 2.0 -- February 2013 This product designed and manufactured in Ottawa, Illinois USA using domestic and imported parts by International

More information

TRP-C37. Ethernet to RS232/422/485 Converter. User s Manual. Printed Apr.2014 Rev 1.3

TRP-C37. Ethernet to RS232/422/485 Converter. User s Manual. Printed Apr.2014 Rev 1.3 TRP-C37 Ethernet to RS232/422/485 Converter User s Manual Printed Apr.2014 Rev 1.3 Trycom Technology Co.,Ltd No.35, Zhongxing Rd., Guishan Township, Taoyuan County 333, Taiwan. Tel : 886-3-350-3351 Fax:

More information

DGH A3000 Configuration Guide For use with DGH Modules

DGH A3000 Configuration Guide For use with DGH Modules DGH A3000 Configuration Guide For use with DGH Modules Revision Date: 12/07/05 Version: 1.00 Contact Information: http://www.dghcorp.com Ph: (603) 622-0452 Fax: (603) 622-0487 Mailing Address: DGH Corporation

More information

GEM80 & ewon Setup Quick Guide

GEM80 & ewon Setup Quick Guide Introduction to the ewon The ewon is an intelligent, programmable Ethernet Gateway, which can be used to bridge GEM 80 PLCs onto an Ethernet network, via the PLC serial port (Port3). This provides network-based

More information

GEM-10 GPRS/Modbus Gateway User Manual. Rev /2012

GEM-10 GPRS/Modbus Gateway User Manual. Rev /2012 GEM-10 GPRS/Modbus Gateway User Manual Rev 1.04 05/2012 1.Introduction 1.1 General Features ENTES GEM-10 GPRS/Modbus Gateway allows you to connect to your devices which communicate using Modbus protocol

More information

WM-120. Serial to Ethernet Module. Serial to Ethernet Module. User Manual. Version 1.0. Infosystem Technology Corporation, Ltd.

WM-120. Serial to Ethernet Module. Serial to Ethernet Module. User Manual. Version 1.0. Infosystem Technology Corporation, Ltd. W M - 1 2 0 User Manual Version 1.0 Infosystem Technology Corporation, Ltd. Index 1. Disclaimers... 1. A. Warranty... 2. B. Trademark... 2. 2. Product Information... 3. A. Introduction... 3. B. Features...

More information

Feature and Benefits. Certifications

Feature and Benefits. Certifications UC-2100 Series Arm-based palm-sized industrial computing platform for IIoT applications Feature and Benefits Armv7 Cortex-A8 1000 MHz processor 1 or 2 auto-sensing 10/100 Mbps Ethernet ports Gigabit Ethernet

More information

UR51 Industrial Cellular Router

UR51 Industrial Cellular Router UR51 Industrial Cellular Router Quick Start Guide 1 Ursalink Technology Co., Ltd. Welcome Thank you for choosing Ursalink UR51 industrial cellular router. This guide describes how to install the UR51 and

More information

Viola M2M Gateway Enterprise Edition

Viola M2M Gateway Enterprise Edition Page 1(5) User Manuals User manuals and other documentation for Viola M2M Gateway product are available at: http://www.violasystems.com/docs/m2mgw/ Overview This document is a short description how to

More information

NetCom Plus 413 (NetCom 413, NetCom 413 PRO)

NetCom Plus 413 (NetCom 413, NetCom 413 PRO) VS Vision Systems GmbH / Part Number 6675 Main Features Ethernet to serial 4 port RS232/422/485 Virtual Com Port driver for Windows Secure Server with latest SSL/AES-256 encryption Operation in Driver

More information

OnCell G3100 Series Quick Installation Guide

OnCell G3100 Series Quick Installation Guide OnCell G3100 Series Quick Installation Guide Edition 4.1, August 2016 Technical Support Contact Information www.moxa.com/support Moxa Americas: Toll-free: 1-888-669-2872 Tel: 1-714-528-6777 Fax: 1-714-528-6778

More information

Installation and Configuration Quick Guide. R3000 Quad. Industrial Cellular VPN Router with 4 Ethernet Ports (4 Eth + 1 RS-232/1 RS USB Host)

Installation and Configuration Quick Guide. R3000 Quad. Industrial Cellular VPN Router with 4 Ethernet Ports (4 Eth + 1 RS-232/1 RS USB Host) Package Contents Before installing your R3000 Quad Router, please verify the kit contents as following. 1 x Robustel GoRugged R3000 Quad Industrial Dual SIM Cellular VPN Router with 4 Ethernet Ports 1

More information

Arm-based palm-sized industrial computers with 2 serial ports and 2 LAN ports. Features and Benefits. Certifications

Arm-based palm-sized industrial computers with 2 serial ports and 2 LAN ports. Features and Benefits. Certifications UC-7100 Series Arm-based palm-sized industrial computers with 2 serial ports and 2 LAN ports Features and Benefits MOXA ART Arm9 32-bit 192 MHz processor 16 or 32 MB RAM 8 or 16 MB Flash ROM Dual or single

More information

Lantech LSC-1102B SERIAL TO TCPIP CONVERTER. User Manual

Lantech LSC-1102B SERIAL TO TCPIP CONVERTER. User Manual Lantech LSC-1102B SERIAL TO TCPIP CONVERTER User Manual V1.0 Sep 2016 Table of Contents 1. Introduction 3 Overview 4 Product Specifications 8 2. Description & Installation 10 Product Panel Views 10 LED

More information

SERIAL TO ETHERNET CONVERTER E-P User Manual

SERIAL TO ETHERNET CONVERTER E-P User Manual SERIAL TO ETHERNET CONVERTER E-P132-100 User Manual 1 Table of Contents Introduction... 4 Overview.. 5 Package Checklist 6 Block Diagram 7 Product Features...8 Product Specifications 9 Converter Description

More information

DeviceMaster RTS 16-Port Hardware Installation

DeviceMaster RTS 16-Port Hardware Installation DeviceMaster RTS -Port Hardware Installation Red underscored text link to Internet URLs. Blue underscored text link to sections within this document or to another document in the library. Note: If you

More information

Industrial 4G LTE Cellular Gateway with 4-Port 10/100TX (2 SIM Card Slots, 2 RS232, 1 RS485, DI/DO, -20~70 degrees C)

Industrial 4G LTE Cellular Gateway with 4-Port 10/100TX (2 SIM Card Slots, 2 RS232, 1 RS485, DI/DO, -20~70 degrees C) Industrial 4G LTE Cellular Gateway with 4-Port 10/100TX (2 SIM Card Slots, 2 RS232, 1 RS485, DI/DO, -20~70 degrees C) Physical Port 3 10/100BASE-TX RJ45 LAN ports, auto-negotiation, auto MDI/MDI-X 1 10/100BASE-TX

More information

TRP-C37. Ethernet to RS232/422/485 Converter. User s Manual. Printed September Rev 1.6

TRP-C37. Ethernet to RS232/422/485 Converter. User s Manual. Printed September Rev 1.6 TRP-C37 Ethernet to RS232/422/485 Converter User s Manual Printed September 1 2015 Rev 1.6 Trycom Technology Co.,Ltd No.35, Zhongxing Rd., Guishan Township, Taoyuan County 333, Taiwan. Tel : 886-3-350-3351

More information

CHIYU. Product Specification BF-450(M)/BF-430. RS232/RS485/RS422 To TCP/IP Converter Module. Release 1.0

CHIYU. Product Specification BF-450(M)/BF-430. RS232/RS485/RS422 To TCP/IP Converter Module. Release 1.0 CHIYU Product Specification BF-450(M)/BF-430 RS232/RS485/RS422 To TCP/IP Converter Module Release 1.0 Date: October 13, 2003 Author: Eric Chang Table of Content 1. Revision History--------------------------------------------------3

More information

Industrial Device Server User s Manual

Industrial Device Server User s Manual Industrial Device Server User s Manual IDS-5042 Series Version 1.00 Aug 2010. ORing Industrial Networking Corp. 4F., NO.3, Lane235, Baociao Rd.Sindian City, Taipei County 23145 Taiwan, R.O.C. Tel: + 886

More information

MGate TM EIP3000 DF1 to EtherNet/IP Gateway User s Manual

MGate TM EIP3000 DF1 to EtherNet/IP Gateway User s Manual MGate TM EIP3000 DF1 to EtherNet/IP Gateway User s Manual First Edition, June 2009 www.moxa.com/product 2009 Moxa Inc. All rights reserved. Reproduction without permission is prohibited. MGate EIP3000

More information

USER MANUAL. SATEL i-link. I/O-converter. Version 1.4

USER MANUAL. SATEL i-link. I/O-converter. Version 1.4 USER MANUAL SATEL i-link I/O-converter Version 1.4 TABLE OF CONTENTS TABLE OF CONTENTS... 2 IMPORTANT NOTICE... 3 PRODUCT CONFORMITY... 4 WARRANTY AND SAFETY INSTRUCTIONS... 5 1 GENERAL... 6 1.1 SATEL

More information

tsh-700 Series User Manual

tsh-700 Series User Manual tsh-700 Series User Manual Tiny Serial Port Sharer Aug. 2017 Ver. 1.6 WARRANTY All products manufactured by ICP DAS are warranted against defective materials for a period of one year from the date of delivery

More information

Arm-based DIN-rail industrial computers with 4 serial ports, 2 LAN ports, 8 DI/DO, and VGA. Features and Benefits. Certifications

Arm-based DIN-rail industrial computers with 4 serial ports, 2 LAN ports, 8 DI/DO, and VGA. Features and Benefits. Certifications IA260 Series Arm-based DIN-rail industrial computers with 4 serial ports, 2 LAN ports, 8 DI/DO, and VGA Features and Benefits Cirrus Logic EP9315 Arm9 CPU, 200 MHz 128 MB RAM onboard, 32 MB flash disk

More information

iopac 8500 Series Rugged modular RTU controllers Overview Programmable Controllers High Sampling Rate Analog Input Prerecord Feature

iopac 8500 Series Rugged modular RTU controllers Overview Programmable Controllers High Sampling Rate Analog Input Prerecord Feature Programmable Controllers iopac 8500 Series Award-winning Product Rugged modular RTU controllers Dedicated ARM (RISC) CPUs for the main system and each I/O module Millisecond timestamp granularity for digital

More information

UR72 & UR75 Industrial Cellular Router

UR72 & UR75 Industrial Cellular Router UR72 & UR75 Industrial Cellular Router Quick Start Guide 1 Ursalink Technology Co., Ltd. Welcome Thank you for choosing Ursalink UR72/UR75 industrial cellular router. This guide describes how to install

More information

ZyWALL 70. Internet Security Appliance. Quick Start Guide Version 3.62 December 2003

ZyWALL 70. Internet Security Appliance. Quick Start Guide Version 3.62 December 2003 ZyWALL 70 Internet Security Appliance Quick Start Guide Version 3.62 December 2003 Introducing the ZyWALL The ZyWALL 70 is the ideal secure gateway for all data passing between the Internet and the LAN.

More information

Features and Benefits. Certifications

Features and Benefits. Certifications NPort IA5000 Series 1 and 2-port serial device servers for industrial automation Features and Benefits Socket modes: TCP server, TCP client, UDP Patented ADDC (Automatic Data Direction Control) for 2-wire

More information

LM300 Bluetooth Ethernet Access Point/Server 3 Simultaneous Bluetooth SPP Connections

LM300 Bluetooth Ethernet Access Point/Server 3 Simultaneous Bluetooth SPP Connections TECHNOLOGIES Bluetooth Ethernet Access Point/Server 3 Simultaneous Bluetooth SPP Connections Android XP Vista Part No Bluetooth Features Supports 3 simultaneous Bluetooth SPP Connections CSR Bluecore 04

More information