Docket 3628 The Narragansett Electric Company s Service Quality Plan Feeder Ranking Report 3rd Quarter 2006

Size: px
Start display at page:

Download "Docket 3628 The Narragansett Electric Company s Service Quality Plan Feeder Ranking Report 3rd Quarter 2006"

Transcription

1 Laura S. Olton General Counsel Rhode Island October 12, 2006 VIA HAND DELIVERY & ELECTRONIC MAIL Luly E. Massaro, Commission Clerk Rhode Island Public Utilities Commission 89 Jefferson Boulevard Warwick, RI RE: Docket 3628 The Narragansett Electric Company s Service Quality Plan Feeder Ranking Report 3rd Quarter 2006 Dear Ms. Massaro: Enclosed please find ten (10) copies of the Feeder Ranking Report for the third quarter of 2006, filed in accordance with the Additional Reporting Criteria, Item 1, of The Narragansett Electric Company, d/b/a National Grid Service Quality Plan effective January 1, Thank you for your attention to this filing. Please feel free to contact me if you have any questions at (401) Very truly yours, Enclosures Laura S. Olton cc: Docket 3628 Service List Paul Roberti, Esq. Steve Scialabba, Division 280 Melrose Street, Providence, RI T: F: laura.olton@us.ngrid.com

2 Rank Feeder Frequency Town Served Customers Events Duration CMI 1 30F EXETER Feeder Lockout - - heat NORTH KINGSTOWN Fuse Link Failure - - heat Replaced Fuse Link Failure - No Found Replaced line Pole Top Recloser Lockout - Load Imbalance - heat Fuse link - equipment Fuse Link Failure - - heat Replaced Fuse Link Failure - fallen tree Replaced line Fuse Link Failure - fallen tree Replaced line Fuse Link Failure - Tree Branch Replaced Fuse Link Failure - Tree Branch Replaced Fuse Link Failure - fallen tree Replaced line Fuse Link Failure - Tree Branch Replaced Fuse Link Failures - fallen tree Replaced line Fuse Link Failure - No Found Replaced line Fuse Link Failure - Tree Branch Replaced line Planned outage - equipment Replaced line Feeder Lockout - - heat Fuse Link Failure - - heat Replaced line Fuse link - equipment Pole Top Recloser Lockout - - heat Feeder Lockout - - heat Fuse Link Failures - fallen tree Replaced line Fuse Link Failure - Animal Replaced Fuse Link Failure - Tree Vines Replaced Blown riser - cable insulation Repaired cable and replaced riser Feeder lockout - Fallen Tree Removed tree and to normal Fuse Link Failure - Tree Branch Replaced Planned outage - equipment Replaced line Replaced damaged equipment and replaced 2 126W LINCOLN Replaced damaged equipment and replaced SMITHFIELD Replaced damaged equipment and replaced line Replaced damaged equipment and replaced line Fuse Link Failure - Tree Vines Replaced Pole top recloser lockout - tree growth Removed tree condition and to 3 87F WARWICK Feeder lockout - Fallen Tree Removed tree and to normal thunderstorms. 4 87F WARWICK thunderstorms. Fuse Link Failure - Animal Replaced Fuse Link Failure - Animal Replaced

3 Rank Feeder Frequency Town Served Customers Events Duration CMI 5 73J CRANSTON Feeder lockout - Equipment Damage Replaced damaged equipment and restored lightning Performed switching and to lightning Performed switching and to Replaced line overload 6 63F COVENTRY Fuse Link Failure - Animal Replaced WEST WARWICK Tripped CSP Transformer - Reset breaker on transformer Fuse Link Failure - Lightning Replaced Fuse Link Failure - Tree Branch Replaced Closed feeder breaker and to Fuse Link Failure - lightning Replaced line Tripped CSP Transformer - Reset breaker on transformer Fuse Link Failure - Deteriorated equipment Replaced equipment and replaced transformer Fuse Link Failure - Animal Replaced line overload Replaced equipment and replaced transformer Fuse Link Failure - Animal Replaced Fuse Link Failure - Deteriorated equipment Replaced equipment and replaced transformer Fuse Link Failure - Animal Replaced line damage Repaired equipment and replaced transformer 7 57J WARWICK Downed phase conductor - lightning Manually opened feeder breaker, made repairs and returned lightning Tripped CSP Transformer - Fuse Link Failure - - heat Performed switching and to Reset breaker on transformer Replaced Patrolled circuit and returned circuit to normal. Tripped CSP Transformer - Reset breaker on transformer 8 61F EAST GREENWICH Feeder lockout - Fallen Tree Removed tree and to normal WARWICK Fuse Link Failure - lightning Replaced line Feeder Lockout - - heat Fuse Link Failure -overload Replaced Fuse Link Failure - Animal Replaced line 9 87F WARWICK Fuse Link Failure - lightning Replaced line thunderstorms. CRANSTON 10 72F WARWICK Fuse Link Failure -animal Replaced Fuse Link Failure -animal Replaced Fuse Link Failure -equipment. Feeder lockout - tree limbs Removed tree limbs and to Fuse Link Failure -lightning Replaced line Fuse Link Failure - Lightning Replaced Fuse Link Failure - overload - Replaced line Fuse Link Failure - overload - Tripped CSP Transformer - Fuse Link Failure - overload - Replaced line Reset breaker on transformer Replaced Pole top recloser lockout - - Performed switching and to Pole top recloser lockout - - Performed switching and to Fuse Link Failure -animal Replaced Fuse Link Failure - tree branch Replaced line line Fuse Link Failure - Replaced line

4 Rank Feeder Frequency Town Served Customers Events Duration CMI 11 34F GLOCESTER Fuse Link Failure - lightning Replaced line COVENTRY Fuse Link Failure - lightning Replaced FOSTER line SCITUATE Patrolled feeder - no damage found- restored Fuse Link Failure- downed primaries Repaired primary conductors and replaced line - lightning.. Fuse Link Failure -lightning Replaced line Fuse Link Failure - fallen tree Replaced line Fuse Link Failure - tree limb Replaced line Fuse Link Failure - tree limb Replaced line Fuse Link Failure - tree limb Replaced line Fuse Link Failure - tree limb Replaced line Fuse Link Failure - tree limb Replaced line Fuse Link Failure - tree limb Replaced line Fuse Link Failure - Lightning Replaced Fuse Link Failure - Lightning Replaced Fuse Link Failure - tree limb Replaced line Fuse Link Failure - tree limb Replaced line Fuse Link Failure - No Found Replaced line Fuse Link Failure - Lightning Fuse Link Failure - Lightning Fuse Link Failure - deterioration Fuse Link Failure - fallen tree Fuse Link Failure - fallen tree Fuse Link Failure - overload - Replaced Replaced line Replaced Patrolled feeder - no damage found- restored line Replaced line Replaced line Replaced line Fuse Link Failure - tree limb Replaced line Replaced -lightning Replaced line Replaced -lightning Replaced Fuse Link Failure - deterioration Replaced Fuse Link Failure - lightning Replaced line line line Fuse Link Failure - tree limb Replaced Pole top recloser lockout - equipment damage - motor vehicle Repaired damaged equipment and restored 12 6J PROVIDENCE Planned outage - equipment Replaced Fuse Link Failure - lightning Replaced line Fuse Link Failure - lightning Replaced line Fuse Link Failure - lightning Replaced line Fuse Link Failure - lightning Replaced line Pole top recloser lockout - equipment damage - motor vehicle Repaired damaged equipment and restored Feeder lockout - tree limbs Removed tree limbs and to 13 27F CRANSTON Feeder lockout - tree limbs Removed tree limbs and to Fuse Link Failure - lightning Replaced line Fuse Link Failure - lightning Replaced line Fuse Link Failure - Lightning Replaced

5 Rank Feeder Frequency Town Served Customers Events Duration CMI 14 21F WEST WARWICK Fuse Link Failure - Animal Replaced CRANSTON Feeder lockout - Fallen Tree Removed tree and to normal Fuse Link Failure - lightning Replaced line Fuse Link Failure - fallen tree Replaced line Fuse Link Failure - fallen tree Replaced line Fuse Link Failure - downed Repaired conductors and replaced line primaries Fuse Link Failure - lightning Replaced line Fuse Link Failure - lightning Replaced Fuse Link Failure - lightning Replaced line Fuse Link Failure - primary Replaced line contacted pole Fuse Link Failure - overload - Replaced line Fuse Link Failure - overload - Fuse Link Failure - lightning Fuse Link Failure - overload - Replaced line Replaced line Replaced line 15 46F NORTH KINGSTOWN 1945 EAST GREENWICH WARWICK 16 38F SMITHFIELD 2460 JOHNSTON Fuse Link Failure -fallen tree Removed tree and to normal Fuse Link Failure -tree limb Replaced line Fuse Link Failure - lightning Replaced line line Pole top recloser lockout - motor Repaired damaged equipment and restored vehicle Feeder lockout - motor vehicle Repaired damaged equipment and restored Feeder lockout - motor vehicle Repaired damaged equipment and restored Pole top recloser lockout - overload Performed switching and to Fuse Link Failure - lightning Replaced line Fuse Link Failure - lightning Replaced Fuse Link Failure -animal Replaced line Planned outage - load balancing Restored circuit to Fuse Link Failure - overload - heat Replaced 17 63F WEST GREENWICH Fuse Link Failure - lightning Replaced line COVENTRY Fuse Link Failure -tree limb Replaced line Fuse Link Failure - deterioration Replaced Fuse Link Failure -lightning Replaced line Fuse Link Failure - lightning Replaced Fuse Link Failure - overload Replaced Fuse Link Failure -lightning Replaced line Fuse Link Failure -lightning Replaced line Planned outage - equipment Replaced line Fuse Link Failure - Replaced Replaced line - lightning Fuse Link Failure - cable Fuse Link Failure- tree branch Fuse Link Failure - animal J NEWPORT cable cable Replaced line Repaired failed cable and replaced line line Removed tree branch and replaced line Replaced Performed switching and to Repaired failed cable and to The Total No. of cust's Served will vary throughout the year due to new activations, terminations of service or rearrangements of the company's distribution system. DURATION = (Total CMI) / (Total no. of cust's served by feeder) FREQUENCY = (Total no. of cust's interrupted) / (Total no. of cust's served by feeder) TOTAL CUSTOMER MINUTES (CMI) = Sum of [((number of customers interrupted) x ( duration of interruption)) for each event]

6 Certificate of Service I hereby certify that a copy of the cover letter and / or any materials accompanying this certificate has been mailed or hand-delivered to the individuals listed below. October 12, 2006 Joanne M. Scanlon Date Narragansett Electric Company Service Quality Plan Docket Service List Name Distribution List Phone/FAX Laura Olton, Esq. Laura.olton@us.ngrid.com National Grid Joanne.scanlon@us.ngrid.com Melrose Street Providence RI Leo Wold, Esq. Dept. of Attorney General 150 South Main St. Providence RI John Stutz Tellus Institute 11 Arlington St. Boston MA Proberti@riag.state.ri.us Steve.scialabba@ripuc.state.ri.us David.stearns@ripuc.state.ri.us Al.contente@ripuc.state.ri.us Jstutz@tellus.org W. Mark Russo, Esq. mrusso@frlawri.com ext Original & nine (9) copies file w/: Lmassaro@puc.state.ri.us Luly E. Massaro, Commission Clerk Sfrias@puc.state.ri.us Public Utilities Commission 89 Jefferson Boulevard Tmassaro@puc.state.ri.us Warwick RI W. Mark Russo, Esq. mrusso@frlawri.com

STATE OF RHODE ISLAND AND PROVIDENCE PLANTATIONS PUBLIC UTILITIES COMMISSION

STATE OF RHODE ISLAND AND PROVIDENCE PLANTATIONS PUBLIC UTILITIES COMMISSION STATE OF RHODE ISLAND AND PROVIDENCE PLANTATIONS PUBLIC UTILITIES COMMISSION IN RE: ISSUANCE OF ADVISORY OPINION : TO THE ENERGY FACILITY SITING BOARD : REGARDING THE NARRAGANSETT ELECTRIC : DOCKET NO.

More information

STATE OF RHODE ISLAND PUBLIC UTILITIES COMMISSION

STATE OF RHODE ISLAND PUBLIC UTILITIES COMMISSION STATE OF RHODE ISLAND PUBLIC UTILITIES COMMISSION ) IN RE: REVIEW OF NATIONAL GRID ) DOCKET NO. 4780 PROPOSED POWER SECTOR ) TRANSFORMATION VISION AND ) IMPLEMENTATION PLAN ) ) UNOPPOSED MOTION TO INTERVENE

More information

RE: Response to the U.S. Army Corps of Engineers s Questions Related to the Proposed Haymarket Transmission Line

RE: Response to the U.S. Army Corps of Engineers s Questions Related to the Proposed Haymarket Transmission Line Dominion Energy P.O. Box 26666, Richmond, VA 23261 DominionEnergy.com David J. DePippo Senior Counsel Direct: (804) 819-2411 Facsimile: (804) 819-2183 david.j.depippo@dominionenergy.com Via Email Ms. Anna

More information

We are filing, herewith, for effect October 21, 2006, tariff material consisting of:

We are filing, herewith, for effect October 21, 2006, tariff material consisting of: Theresa L. O Brien Vice President Regulatory Affairs September 21, 2006 234 Washington Street Providence, RI 02903 Phone 401 525-3060 Fax 401 525-3064 theresa.obrien@verizon.com Ms. Luly E. Massaro, Commission

More information

We are filing, herewith, for effect July 31, 2004, tariff material consisting of:

We are filing, herewith, for effect July 31, 2004, tariff material consisting of: Theresa L. O Brien Vice President Regulatory Affairs July 1, 2004 234 Washington Street Providence, RI 02903 Phone 401 525-3060 Fax 401 525-3064 theresa.obrien@verizon.com Ms. Luly E. Massaro, Commission

More information

We are filing, herewith, for effect January 7, 2005, tariff material consisting of:

We are filing, herewith, for effect January 7, 2005, tariff material consisting of: Theresa L. O Brien Vice President Regulatory Affairs December 8, 2004 234 Washington Street Providence, RI 02903 Phone 401 525-3060 Fax 401 525-3064 theresa.obrien@verizon.com Ms. Luly E. Massaro, Commission

More information

RE: Docket Electric Infrastructure, Safety, and Reliability Plan FY 2013 Responses to Commission Data Requests Set 2

RE: Docket Electric Infrastructure, Safety, and Reliability Plan FY 2013 Responses to Commission Data Requests Set 2 Luly Massaro FY 2012 Electric ISR Plan December 20, 2010 Thomas R. Teehan Senior Counsel March 12, 2012 VIA HAND DELIVERY & ELECTRONIC MAIL Luly E. Massaro, Commission Clerk Rhode Island Public Utilities

More information

SECTION (16410) - ENCLOSED SWITCHES AND CIRCUIT BREAKERS

SECTION (16410) - ENCLOSED SWITCHES AND CIRCUIT BREAKERS SECTION 26 28 16 (16410) - ENCLOSED SWITCHES AND CIRCUIT BREAKERS PART 1 GENERAL 1.01 SUMMARY A. Section Includes: 1. Individually Mounted Switches and Circuit Breakers Used for the following: a. Service

More information

We are filing herewith, for effect November 1, 2003, tariff material consisting of: Revision of

We are filing herewith, for effect November 1, 2003, tariff material consisting of: Revision of Theresa L. O Brien Vice President Regulatory Affairs October 2, 2003 234 Washington Street Providence, RI 02903 Phone: 401 525-3060 Fax: 401 525-3064 theresa.obrien@verizon.com Ms. Luly Massaro Commission

More information

The Narragansett Electric Company. d/b/a National Grid (Rhode Island Reliability Project) RIPUC Dkt. No Testimony of. Todd G. Kopoyan, P.E.

The Narragansett Electric Company. d/b/a National Grid (Rhode Island Reliability Project) RIPUC Dkt. No Testimony of. Todd G. Kopoyan, P.E. d/b/a National Grid (Rhode Island Reliability Project) RIPUC Dkt. No. 0 Testimony of Todd G. Kopoyan, P.E. February 0, 00 0 0 INTRODUCTION Q. Please state your name and business address. A. My name is

More information

Why is my AFCI tripping?

Why is my AFCI tripping? www.garyklinka.com Page 1 of 21 Instructions: Fee $25 1. Print these pages. 2. Use the included information located on pages 12-20 to answer the 61 questions below. 3. Circle the correct answers and transfer

More information

SECTION ENCLOSED SWITCHES AND CIRCUIT BREAKERS

SECTION ENCLOSED SWITCHES AND CIRCUIT BREAKERS SECTION 262816 - ENCLOSED SWITCHES AND CIRCUIT BREAKERS PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division

More information

Siemens FuseSaver New half-cycle circuit breaker for rural smart grids to minimize operating costs of feeder and spur lines

Siemens FuseSaver New half-cycle circuit breaker for rural smart grids to minimize operating costs of feeder and spur lines Siemens FuseSaver New half-cycle circuit breaker for rural smart grids to minimize operating costs of feeder and spur lines Authors: Dr. Brett Watson, Siemens Ltd., PO Box 4833, Loganholme, QLD 4129, Australia

More information

ELECTRIC SERVICE RELIABILITY IN PENNSYLVANIA 2010

ELECTRIC SERVICE RELIABILITY IN PENNSYLVANIA 2010 E l e c t r i cs e r v i c e R e l i a bi l i t yi n P e n n s y l v a n i a 2010 P e n n s y l v a n i apu b l i cut i l i t yco mmi s s i o n ELECTRIC SERVICE RELIABILITY IN PENNSYLVANIA 2010 Published

More information

Pepco. Reliability Enhancement Plan. For. Montgomery County, Maryland. Including. Distribution System Overview and Reliability Initiatives

Pepco. Reliability Enhancement Plan. For. Montgomery County, Maryland. Including. Distribution System Overview and Reliability Initiatives l pepco A PHI Company Pepco Reliability Enhancement Plan For Montgomery County, Maryland Including Distribution System Overview and Reliability Initiatives August 2010 TABLE OF CONTENTS 1. Executive Summary.

More information

Applying branch circuit breakers and supplementary protectors in North America

Applying branch circuit breakers and supplementary protectors in North America Supersedes June 2017 FAZ-NA-L FAZ-NA FAZ Applying branch circuit breakers and supplementary protectors in North America Introduction Eaton offers three types of miniature circuit breakers for use in North

More information

DISTRIBUTION FEEDER FAULT ANALYSIS TILLAMOOK PEOPLE S UTILITY DISTRICT

DISTRIBUTION FEEDER FAULT ANALYSIS TILLAMOOK PEOPLE S UTILITY DISTRICT DISTRIBUTION FEEDER FAULT ANALYSIS TILLAMOOK PEOPLE S UTILITY DISTRICT SCADA TO DG SITES DIGESTER MW AND MVAR INSTANTANEOUS READINGS FROM SEL 751 RELAY TRASK SUBSTATION LOADING DO NOT WANT TO FEED INTO

More information

FORM FOR PROPOSAL FOR 2014 NATIONAL ELECTRICAL CODE

FORM FOR PROPOSAL FOR 2014 NATIONAL ELECTRICAL CODE FORM FOR PROPOSAL FOR 2014 NATIONAL ELECTRICAL CODE INSTRUCTIONS PLEASE READ CAREFULLY Type or print legibly in black ink. Use a separate copy for each proposal. Limit each proposal to a SINGLE section.

More information

Cereal Hudson. Tariffs. Anthony S. Campagiorni, Esq. Vice President, Regulatory & Governmental Affairs. Requested Revenue Increases

Cereal Hudson. Tariffs. Anthony S. Campagiorni, Esq. Vice President, Regulatory & Governmental Affairs. Requested Revenue Increases 1 Anthony S. Campagiorni, Esq. Vice President, Regulatory & Governmental Affairs P Power. Possibilities Cereal Hudson A FORTIS COMPANY July 28, 2017 Via Electronic Filing By Hand Honorable Kathleen Burgess,

More information

Description TR D

Description TR D Description TR D 78385 270607 Electronic double thermostat with heat curve in a DIN standard bar enclosure 1. Short Description The electronic double thermostat serves to control electric heating panels

More information

Application Switchgear for industrial and advanced commercial applications. U e V AC 277/480 Y V DC 60

Application Switchgear for industrial and advanced commercial applications. U e V AC 277/480 Y V DC 60 DATASHEET - FAZ-C5/2-RT Miniature circuit breaker (MCB), 5A, 2p, C-Char, AC Part no. FAZ-C5/2-RT Catalog No. 102203 Eaton Catalog No. FAZ-C5/2-RT EL-Nummer 1691799 (Norway) Similar to illustration Delivery

More information

STATE OF RHODE ISLAND AND PROVIDENCE PLANTATIONS PUBLIC UTILITIES COMMISSION

STATE OF RHODE ISLAND AND PROVIDENCE PLANTATIONS PUBLIC UTILITIES COMMISSION STATE OF RHODE ISLAND AND PROVIDENCE PLANTATIONS PUBLIC UTILITIES COMMISSION IN RE: THE NARRAGANSETT ELECTRIC COMPANY : d/b/a NATIONAL GRID TARIFF ADVICE TO ADD LED : STREETLIGHTS TO THE COMPANY-OWNED

More information

System Studies for American Transmission Co. s Benson Lake SVC Project

System Studies for American Transmission Co. s Benson Lake SVC Project Helping to keep the lights on, businesses running and communities strong System Studies for American Transmission Co. s Benson Lake SVC Project Adam Manty, Transmission Planning Engineer, ATC Outline Introduction

More information

Explosion-Protected Arc-Fault Protection ExAFCI Arc-Fault Circuit Interrupter

Explosion-Protected Arc-Fault Protection ExAFCI Arc-Fault Circuit Interrupter Installation, Operation & Maintenance Sheet Explosion-Protected Arc-Fault Protection ExAFCI Arc-Fault Circuit Interrupter > Contents 1 Contents 1 Contents...2 2 General Information...2 2.1 Manufacturer...2

More information

DISRIBUTED AUTOMATION FOR BACK-FEED NETWORK POWER RESTORATION

DISRIBUTED AUTOMATION FOR BACK-FEED NETWORK POWER RESTORATION DISRIBUTED AUTOMATION FOR BACK-FEED NETWORK POWER RESTORATION Fahrudin Mekic Zhenyuan Wang Vaibhav Donde Fang Yang James Stoupis ABB Inc. USA ABB Inc. USA ABB Inc. USA ABB Inc. USA ABB Inc. USA fahrudin.mekic@us.abb.com

More information

SECTIONS II - VIII QUANTITY, FORM, AND FILING REQUIREMENTS APPLICATION FILING FEES NOTICE TO COMMUNITY ORGANIZATIONS NOTICE IN UTILITY BILLS

SECTIONS II - VIII QUANTITY, FORM, AND FILING REQUIREMENTS APPLICATION FILING FEES NOTICE TO COMMUNITY ORGANIZATIONS NOTICE IN UTILITY BILLS SECTIONS II - VIII QUANTITY, FORM, AND FILING REQUIREMENTS APPLICATION FILING FEES PROOF OF SERVICE NOTICE TO COMMUNITY ORGANIZATIONS PUBLIC NOTICE NOTICE IN UTILITY BILLS NOTICE OF OWNERS OF PROPERTY

More information

Cost and performance implications of infrastructure investment options in the Eskom Distribution network

Cost and performance implications of infrastructure investment options in the Eskom Distribution network Cost and performance implications of infrastructure investment options in the Eskom Distribution network Dr Clinton Carter-Brown Industry Association Resource Centre Eskom Holdings Limited Martin Cameron

More information

BEFORE THE ARKANSAS PUBLIC SERVICE COMMISSION

BEFORE THE ARKANSAS PUBLIC SERVICE COMMISSION BEFORE THE ARKANSAS PUBLIC SERVICE COMMISSION IN THE MATTER OF THE FORMULA ) RATE PLAN FILINGS OF OKLAHOMA GAS ) GAS AND ELECTRIC COMPANY ) DOCKET NO. -0-FR PURSUANT TO APSC DOCKET ) NO. -0-U ) Direct

More information

A P U B L I C A T I O N O F T H E. Florida Public Service Commission. Electric Power Interruptions

A P U B L I C A T I O N O F T H E. Florida Public Service Commission. Electric Power Interruptions A P U B L I C A T I O N O F T H E Florida Public Service Commission Electric Power Interruptions Momentary Power Interruptions Momentary power interruptions, or outages, are brief disruptions in electric

More information

Fortum SGEM Program Presentation of ongoing research activities

Fortum SGEM Program Presentation of ongoing research activities Fortum SGEM Program Presentation of ongoing research activities MV and LV Network Automation Solutions in EU Benchmarking Research 1 Existing Distribution Grid Little change in the past few decades Mostly

More information

UNITED STATES OF AMERICA BEFORE THE FEDERAL ENERGY REGULATORY COMMISSION ) ) ) ) MOTION TO INTERVENE AND COMMENTS OF THE INDICATED TRANSMISSION OWNERS

UNITED STATES OF AMERICA BEFORE THE FEDERAL ENERGY REGULATORY COMMISSION ) ) ) ) MOTION TO INTERVENE AND COMMENTS OF THE INDICATED TRANSMISSION OWNERS UNITED STATES OF AMERICA BEFORE THE FEDERAL ENERGY REGULATORY COMMISSION North American Electric Reliability Corporation Northeast Power Coordinating Council, Inc. ) ) ) ) Docket No. RC09-3-000 MOTION

More information

Advanced Fuse-Saving Techniques. T. ROUSAN Ameren Illinois USA. J. JERMAKOWICZ S&C Electric Company USA

Advanced Fuse-Saving Techniques. T. ROUSAN Ameren Illinois USA. J. JERMAKOWICZ S&C Electric Company USA 21, rue d Artois, F-75008 PARIS CIGRE US National Committee http : //www.cigre.org 2015 Grid of the Future Symposium Advanced Fuse-Saving Techniques T. ROUSAN Ameren Illinois USA J. JERMAKOWICZ S&C Electric

More information

Dirty Power... A Guide to Surge Suppression & Filtering. Surge & Signal Protection for Business-Critical Continuity. EmersonNetworkPower.

Dirty Power... A Guide to Surge Suppression & Filtering. Surge & Signal Protection for Business-Critical Continuity. EmersonNetworkPower. Headquarters Surge & Signal Protection 328 Water Street Binghamton, NY 13901 T: 607-724-2484 T: 800-288-6169 F: 607-722-8713 Surge & Signal Protection for Business-Critical Continuity Dirty Power... A

More information

1. Coordination of series-rated devices is permitted where indicated on Drawings.

1. Coordination of series-rated devices is permitted where indicated on Drawings. SECTION 16055 - OVERCURRENT PROTECTIVE DEVICE COORDINATION PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and

More information

Welcome. Liberty Utilities Reliability Reporting Workshop. March 15, 2017

Welcome. Liberty Utilities Reliability Reporting Workshop. March 15, 2017 Welcome Liberty Utilities Reliability Reporting Workshop March 15, 2017 1 Agenda Winter storms of 2017 System Overview Reliability Performance Plans for Reliability Improvements Questions 2 Winter Storms

More information

Applying branch circuit breakers and supplementary protectors in North America

Applying branch circuit breakers and supplementary protectors in North America Product Application AP01102005E WMZT WMZS Applying branch circuit breakers and supplementary protectors in North America Introduction Eaton offers two types of miniature circuit breakers for use in North

More information

UL 489 or UL 1077 in control panels and equipment a quick guide

UL 489 or UL 1077 in control panels and equipment a quick guide UL 489 or UL 1077 in control panels and equipment a quick guide A common question that comes up with OEM machine builders and control panel builders is How do I know when to use UL 1077 or UL 489 breakers

More information

ORDER NO * * * * * * * * Pursuant to the Maryland Electricity Service Quality and Reliability Act 1 and the

ORDER NO * * * * * * * * Pursuant to the Maryland Electricity Service Quality and Reliability Act 1 and the ORDER NO. 87754 IN THE MATTER OF THE REVIEW OF ANNUAL PERFORMANCE REPORTS ON ELECTRIC SERVICE RELIABILITY FILED PURSUANT TO COMAR 20.50.12.11 * * * * * * * * BEFORE THE PUBLIC SERVICE COMMISSION OF MARYLAND

More information

Motor-protective circuit-breaker, 3p, Ir=16-25A, screw connection. Product range PKZM4 motor protective circuit-breakers up to 65 A

Motor-protective circuit-breaker, 3p, Ir=16-25A, screw connection. Product range PKZM4 motor protective circuit-breakers up to 65 A DATASHEET - PKZM4-25 Delivery program Motor-protective circuit-breaker, 3p, Ir=16-25A, screw connection Part no. PKZM4-25 Catalog No. 222352 Eaton Catalog No. XTPR025DC1NL EL-Nummer 0004355158 (Norway)

More information

MV overhead feeder automation

MV overhead feeder automation MV overhead feeder automation by John Cossey, Nu-Lec Industries Electricity providers are under immense pressure to improve the reliability of supply to their customers. Providers have a number of options

More information

BEFORE THE PUBLIC UTILITIES COMMISSION OF THE STATE OF CALIFORNIA ) ) ) ) ) )

BEFORE THE PUBLIC UTILITIES COMMISSION OF THE STATE OF CALIFORNIA ) ) ) ) ) ) BEFORE THE PUBLIC UTILITIES COMMISSION OF THE STATE OF CALIFORNIA In the Matter of the Application of SOUTHERN CALIFORNIA EDISON COMPANY (U 338-E for a Permit to Construct Electrical Facilities With Voltages

More information

SECTION OVERCURRENT PROTECTIVE DEVICE COORDINATION STUDY

SECTION OVERCURRENT PROTECTIVE DEVICE COORDINATION STUDY SECTION 26 05 73 OVERCURRENT PROTECTIVE DEVICE PART 1 - GENERAL 1.1 SUMMARY A. Section includes computer-based, fault-current and overcurrent protective device coordination studies. Protective devices

More information

Products Portfolio. Pole mounted Vacuum Recloser

Products Portfolio. Pole mounted Vacuum Recloser Products Portfolio Pole mounted Vacuum Recloser Efacec Switchgear Efacec Switchgear is a leading company in Portugal and a worldwide reference in the development of solutions for power generation, transmission,

More information

Legal Name of the Customer (or, if an individual, individual's name):

Legal Name of the Customer (or, if an individual, individual's name): Instructions An Interconnection Customer who requests a Utah Public Service Commission jurisdictional interconnection must submit this Interconnection Request by hand delivery, mail, or delivery service

More information

Carina Grega Food Network Space Final Thesis Report Electrical Overview. Electrical Overview. Existing System Overview

Carina Grega Food Network Space Final Thesis Report Electrical Overview. Electrical Overview. Existing System Overview Electrical Overview Existing System Overview Chelsea Market is served by Consolidated Edison, the electric utility for most of New York City. The Food Network space is supplied by two separate radial systems

More information

AMEU FuseSaver Highest availability and cost savings for your medium voltage distribution network

AMEU FuseSaver Highest availability and cost savings for your medium voltage distribution network AMEU 2012 FuseSaver Highest availability and cost savings for your medium voltage distribution network October Page 2012 1 Siemens IC AG LMV 2012 MV C PPM Challenges for rural networks Characteristics

More information

LIST OF LICENSED LABORATORIES

LIST OF LICENSED LABORATORIES The following list of licensed laboratories was obtained from the Rhode Island Department of Health on June 1, 2012. The information is provided as a convenience by the Narragansett Bay Commission and

More information

GENERAL INFORMATION. The time it takes to find the fault The time it takes to repair the fault.

GENERAL INFORMATION. The time it takes to find the fault The time it takes to repair the fault. GENERAL INFORMATION Improve customer satisfaction Customer satisfaction is often difficult to measure. One of the key figures used to indicate the performance of a distribution network is SAIDI. SAIDI

More information

2012 Grid of the Future Symposium. Demonstration of Pulsecloser Applications and Benefits in Ameren s Distribution Automation Program

2012 Grid of the Future Symposium. Demonstration of Pulsecloser Applications and Benefits in Ameren s Distribution Automation Program 21, rue d Artois, F-75008 PARIS CIGRE US National Committee http : //www.cigre.org 2012 Grid of the Future Symposium Demonstration of Pulsecloser Applications and Benefits in Ameren s Distribution Automation

More information

Low Voltage Grid Digitalization Rainer Brade Product Manager

Low Voltage Grid Digitalization Rainer Brade Product Manager Low Voltage Grid Digitalization Rainer Brade Product Manager Unrestricted Siemens AG Österreich 2017 siemens.at/future-of-energy Digital Transformation is Happening Now Market Trends From central power

More information

South Tulsa Switch Automation Pilot

South Tulsa Switch Automation Pilot South Tulsa Switch Automation Pilot Presented by: Bret Goodwin, P.E., Distribution System Planning Supervisor AEP-Public Service Company of Oklahoma May 2010 SWEDE Conference Abstract for SWEDE, 2010 Title:

More information

Application Switchgear for industrial and advanced commercial applications. U e V AC 240/ (per pole)

Application Switchgear for industrial and advanced commercial applications. U e V AC 240/ (per pole) DATASHEET - FAZ-C10/2 Miniature circuit breaker (MCB), 10A, 2p, C-Char, AC Similar to illustration Part no. FAZ-C10/2 Catalog No. 278756 Eaton Catalog No. FAZ-C10/2 EL-Nummer 1695166 (Norway) Delivery

More information

July 1, 1999 PUBLIC UTILITIES COMMISSION OF THE STATE OF CALIFORNIA ENERGY DIVISION

July 1, 1999 PUBLIC UTILITIES COMMISSION OF THE STATE OF CALIFORNIA ENERGY DIVISION Donald A. Fellows, Jr. Manager of Revenue and Tariffs July 1, 1999 (U 338-E) PUBLIC UTILITIES COMMISSION OF THE STATE OF CALIFORNIA ENERGY DIVISION SUBJECT: Notice of Proposed Construction of Facilities

More information

2018 NCPSB Members Note: Terms officially end at the January NCPSB meeting following the year indicated.

2018 NCPSB Members Note: Terms officially end at the January NCPSB meeting following the year indicated. 2018 NCPSB Members Note: Terms officially end at the January NCPSB meeting following the year indicated. Board Chair Injury Prevention/Healthcare Dina Burstein, MD Injury Prevention Center at Rhode Island

More information

Application Switchgear for industrial and advanced commercial applications. U e V AC 240/ (per pole) I cs 7,5 ka

Application Switchgear for industrial and advanced commercial applications. U e V AC 240/ (per pole) I cs 7,5 ka DATASHEET - FAZ-C16/1 Miniature circuit breaker (MCB), 16A, 1p, C-Char, AC Part no. FAZ-C16/1 Catalog No. 278561 Eaton Catalog No. FAZ-C16/1 EL-Nummer 0001695154 (Norway) Similar to illustration Delivery

More information

NU-LEC. Loop Automation. Reclosers & Sectionalizers

NU-LEC. Loop Automation. Reclosers & Sectionalizers NU-LEC Loop Automation Reclosers & Sectionalizers 1 NU-LEC LLC NU-LEC LLC is a wholly unit of NU-LEC Industries, Pty, Ltd. Sales and service center for United States, Canada, and the Caribbean. Warehouse

More information

Cutler-Hammer. January 2001

Cutler-Hammer. January 2001 Cutler-Hammer January 0 Vol.,Ref. 2-2 Product Line Overview January 0 Vol., Ref. No. [068] 2 Product Line Description Cutler-Hammer Molded Case Circuit s are designed to provide circuit protection for

More information

Updates and Modifications to Report

Updates and Modifications to Report QUARTERLY COMPLIANCE REPORT (JANUARY 2017) OF SOUTHERN CALIFORNIA EDISON COMPANY (U 338-E) REGARDING STATUS OF TRANSMISSION PROJECTS AND GENERATION INTERCONNECTION PROJECTS Pursuant to Commission Decision

More information

2016 Pennsylvania Electric Reliability Report. Section 1 Introduction Purpose... 1 Background... 1

2016 Pennsylvania Electric Reliability Report. Section 1 Introduction Purpose... 1 Background... 1 Table of Contents Executive Summary 2016 Pennsylvania Electric Reliability Report Section 1 Introduction Purpose... 1 Background... 1 Section 2 Reliability Performance Measures Reliability Performance

More information

Micro-Ohmmeter Model 6292

Micro-Ohmmeter Model 6292 Micro-Ohmmeter Model 6292 Quick Start Guide ENGLISH www.aemc.com CHAUVIN ARNOUX GROUP Statement of Compliance Chauvin Arnoux, Inc. d.b.a. AEMC Instruments certifies that this instrument has been calibrated

More information

Product Description. S&C IntelliNode Interface Module. Table of Contents. Instruction Sheet

Product Description. S&C IntelliNode Interface Module. Table of Contents. Instruction Sheet S&C IntelliNode Interface Module Product Description Table of Contents Section Page Section Page Introduction Qualified Persons.......................... 2 Read this Instruction Sheet..................

More information

Testing of Real Time Power System Control Software

Testing of Real Time Power System Control Software Testing of Real Time Power System Control Software Transpower s Pole 3 Project Presentation to Special Interest Group of ANZTB 7 October 2013 Richard Sherry 1 Summary 1. What does the HVDC Control System

More information

We are filing, herewith, for effect August 5, 2006, tariff material consisting of:

We are filing, herewith, for effect August 5, 2006, tariff material consisting of: Theresa L. O Brien Vice President Regulatory Affairs July 6, 2006 234 Washington Street Providence, RI 02903 Phone 401 525-3060 Fax 401 525-3064 theresa.obrien@verizon.com Ms. Luly E. Massaro, Commission

More information

Free Standing Emergency Department DGL Project No SECTION OVERCURRENT PROTECTIVE DEVICE COORDINATION STUDY PART 1 - GENERAL

Free Standing Emergency Department DGL Project No SECTION OVERCURRENT PROTECTIVE DEVICE COORDINATION STUDY PART 1 - GENERAL SECTION 26 05 73 1.1 SUMMARY OVERCURRENT PROTECTIVE DEVICE COORDINATION STUDY PART 1 - GENERAL A. This Section includes the following: 1. Requirements for computer-based, fault-current and overcurrent

More information

Karl Iliev, San Diego Gas & Electric Company

Karl Iliev, San Diego Gas & Electric Company INTEGRATING DER THROUGH DISTRIBUTION SYNCROPHASORS Karl Iliev, San Diego Gas & Electric Company 2002 San Diego Gas and Electric Co. and Southern California Gas Company. All copyright and trademark rights

More information

October 25, 2016 VIA EFILING AND U.S. MAIL

October 25, 2016 VIA EFILING AND U.S. MAIL October 25, 2016 Daniel P. Wolf Executive Secretary Minnesota Public Utilities Commission 121 East Seventh Place, Suite 350 55101 Eric F. Swanson Direct Dial: (612) 604-6511 Direct Fax: (612) 604-6811

More information

KEY. PPA has been approved (if required) and has Sanction

KEY. PPA has been approved (if required) and has Sanction KEY Status Description Project is under consideration as possible solution to a Concept need, but little or no analysis is available National Grid has internally detemined that the project is an appropriate

More information

FOR RELEASE JUNE 28, / JUSTICE DEPARTMENT AWARDS $13 MILLION TO IMPROVE CRIME REPORTING NATIONWIDE

FOR RELEASE JUNE 28, / JUSTICE DEPARTMENT AWARDS $13 MILLION TO IMPROVE CRIME REPORTING NATIONWIDE FOR RELEASE BJS JUNE 28, 2001 202/307-0703 JUSTICE DEPARTMENT AWARDS $13 MILLION TO IMPROVE CRIME REPORTING NATIONWIDE 70 Year-Old Crime Reporting System Being Replaced WASHINGTON, D.C. The Justice Department

More information

C E R T I F I C A T E O F C O M P L I A N C E

C E R T I F I C A T E O F C O M P L I A N C E Issued to: This is to certify that representative samples of SIEMENS AG DF CP R&D VC 2 WERNER-VON-SIEMENS-STRASSE 48 92224 AMBERG, GERMANY MOTOR CONTROLLERS, MANUAL (See following page for additional information.)

More information

Source-Transfer Application Guide

Source-Transfer Application Guide S&C Model 6802 Automatic Switch Control Source-Transfer Application Guide Table of Contents Section Page Section Page Introduction Qualified Persons.... 2 Read this Instruction Sheet.... 2 Retain this

More information

TeSys IEC Contactors and Overload Relays

TeSys IEC Contactors and Overload Relays TeSys IEC Contactors and Overload Relays Making High-Fault Short-Circuit Current Ratings Simple Schneider Electric is an industry leader in IEC contactors and overload relays, and is recognized as the

More information

Strategies for Evaluating and Integrating SmartyStreets

Strategies for Evaluating and Integrating SmartyStreets Strategies for Evaluating and Integrating SmartyStreets Michael Berry HLN Consulting, LLC AIRA 2018 IIS National Meeting August 14, 2018 Background: SmartyStreets, AIRA, & KIDSNET SmartyStreets is a third-party

More information

Power Quality, Efficiency & Reliability A Global Leader in Innovative...

Power Quality, Efficiency & Reliability A Global Leader in Innovative... Power Quality, Efficiency & Reliability A Global Leader in Innovative... Wire & Cable Management Cable Protection Systems Power Connection & Control Safety Technology Thomas & Betts Solution Sets In today

More information

Application Techniques CENTERLINE 2100 Motor Control Centers

Application Techniques CENTERLINE 2100 Motor Control Centers POWER SYSTEM CONSIDERATIONS FOR PRODUCT SELECTION Application Techniques CENTERLINE 2100 Motor Control Centers Power System Considerations for Product Selection i Power System Considerations for Product

More information

APPLICATION CONTROL GUIDELINES. IntelliROL Power Supply PN Revision Date: March 15, 2017

APPLICATION CONTROL GUIDELINES. IntelliROL Power Supply PN Revision Date: March 15, 2017 APPLICATION CONTROL GUIDELINES IntelliROL Power Supply PN 1176718 Revision Date: March 15, 2017 Table of Contents List of Tables...3 TGW Safety Recommendation...4 Warnings and Safety Instructions...5 Introduction...6

More information

Electronic Service Only

Electronic Service Only December 1,2015 Electronic Service Only James E. Davis 705 112 Stratton Street Logan, WV 25601 Robert Hicks Fast Action Towing and Recovery PO Box 415 Man, WV 25635 RE: Case No. 15-1447-MC-FC James E.

More information

Residential/Commercial/Industrial

Residential/Commercial/Industrial Thank You For Purchasing the BASIC POWER UNIT from the team! 120 Marshalls Creek Road East Stroudsburg, PA 18302 570-872-9666 Residential/Commercial/Industrial IF YOU EXPERIENCE A PROBLEM WITH YOUR PURCHASE,

More information

FAULT DETECTION ISOLATION AND RESTORATION ON THE FEEDER (FDIR): PICK YOUR TECHNOLOGY

FAULT DETECTION ISOLATION AND RESTORATION ON THE FEEDER (FDIR): PICK YOUR TECHNOLOGY FAULT DETECTION ISOLATION AND RESTORATION ON THE FEEDER (FDIR): PICK YOUR TECHNOLOGY Fahrudin Mekic Ken Alloway Cleber Angelo Robert Goodin ABB Inc. USA ABB Inc. USA ABB Inc. USA ABB Inc. USA fahrudin.mekic@us.abb.com.ken.alloway@us.abb.com

More information

24973 Circuit Breaker MINIATURE CIRCUIT BREAKER, 440VAC, 10A, CIRCUIT BREAKER TYPE: STANDARD

24973 Circuit Breaker MINIATURE CIRCUIT BREAKER, 440VAC, 10A, CIRCUIT BREAKER TYPE: STANDARD United States 24973 Circuit Breaker MINIATURE CIRCUIT BREAKER, 440VAC, 10A, CIRCUIT BREAKER TYPE: STANDARD Image not available Product Information Features and Specifications Approvals: IEC 60947-2 Rated

More information

CC Docket Notice of Detariffing of Common Carrier Wireline Broadband Internet Access Transmission Service

CC Docket Notice of Detariffing of Common Carrier Wireline Broadband Internet Access Transmission Service South Central COMMUNICATIONS P.O. BOX 555 ESCALANTE, UTAH 84726 (435) 826-4211 Marlene H. Dortch, Secretary Federal Communications Commission 445 lih Street, SW Washington, D.C. 20554 Re: CC Docket 02-33

More information

May 20, Cheryl Walker Oregon Public Utility Commission 550 Capitol St., NE Suite 215 Salem, OR Re: UCB 34 Preferred Choice Insurance

May 20, Cheryl Walker Oregon Public Utility Commission 550 Capitol St., NE Suite 215 Salem, OR Re: UCB 34 Preferred Choice Insurance Qwest 421 Southwest Oak Street Suite 810 Portland, Oregon 97204 Telephone: 503-242-5420 Facsimile: 503-242-8589 e-mail: carla.butler@qwest.com Carla M. Butler Lead Paralegal May 20, 2008 Cheryl Walker

More information

ver1 on If you have questions, please contact me either at (888) or October 26, 2015

ver1 on If you have questions, please contact me either at (888) or October 26, 2015 ~ ver1 on 5055 North Point Parkway Alpharetta, GA 30022 State Government Affairs October 26, 2015 Public Utility Commission of Oregon 201 High Street SE, Suite 100 Salem, Oregon 97301 RE: MCI Conimunications

More information

Small Generator Interconnection System Impact Study Report. Completed For Q0047

Small Generator Interconnection System Impact Study Report. Completed For Q0047 Small Generator Interconnection Completed For Q0047 Proposed Interconnection PacifiCorp s Existing Goshen Rigby 69 kv Line March 7, 2005 1.0 Description of the Generation Facility Q0047 ( Interconnection

More information

INFRASTRUCTURE ELECTRIC UTILITY CAPITAL IMPROVEMENT PROJECTS DRAFT

INFRASTRUCTURE ELECTRIC UTILITY CAPITAL IMPROVEMENT PROJECTS DRAFT INFRASTRUCTURE ELECTRIC UTILITY CAPITAL IMPROVEMENT PROJECTS 2014-2023 DRAFT November 5, 2012 Project Costs Infrastructure - Electric Utility F - 2 City of Lethbridge Infrastructure - Electric Utility

More information

Application Instantaneous release response current 5-10 x In. Switching capacity Switching Capacity 15 ka (IEC/EN ) U e V AC 230/400

Application Instantaneous release response current 5-10 x In. Switching capacity Switching Capacity 15 ka (IEC/EN ) U e V AC 230/400 Overcurrentswitch,10A,3p,C-Char,AC Partno. FAZ-C10/3 Articleno. 278869 CatalogNo. FAZ-C10/3 Similar to illustration Deliveryprogramme Product range FAZ Application Instantaneous release response current

More information

1510 MOTOR CONTROLLERS

1510 MOTOR CONTROLLERS SECTION 262913- MOTOR CONTROLLERS PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of contract, including general and supplementary conditions and Division 1 specification section,

More information

WiAutoLink Frequently Asked Questions

WiAutoLink Frequently Asked Questions Rev. 0 December 2014 Page 1 of 8 WiAutoLink Frequently Asked Questions December 2014 1 Rev. 0 December 2014 Page 2 of 8 Table of Contents 1 Background... 4 1.1 What is the WiAutoLink Single Phase Electronic

More information

Power Quality of Commercial and Industrial Power Systems

Power Quality of Commercial and Industrial Power Systems Hanover Risk Solutions Power Quality of Commercial and Industrial Power Systems Power quality is a general term used to describe the quality of several different power-related characteristics. These characteristics

More information

Server Technology Inc.

Server Technology Inc. Server Technology Inc. Alternating Phase Power Distribution at the Data Center Rack PDU White Paper STI-100-012 2013-April-18 By Steve Hammond, Product Manager, Server Technology Headquarters Server Technology,

More information

Siemens Fusesaver and Remote Control Unit 3AD8

Siemens Fusesaver and Remote Control Unit 3AD8 Catalog HG 11.43 Edition 2017 Siemens Fusesaver and Remote Control Unit 3AD8 Medium-Voltage Equipment siemens.com/fusesaver 2 Siemens Fusesaver and Remote Control Unit 3AD8 Siemens HG 11.43 2017 R-HG11-FR-001.tif

More information

A Deterministic Analysis Method for Back-feed Power Restoration of Distribution Networks

A Deterministic Analysis Method for Back-feed Power Restoration of Distribution Networks 1 A Deterministic Analysis Method for Back-feed Power Restoration of Distribution Networks Zhenyuan Wang, Vaibhav Donde, Fang Yang, James Stoupis, Member, IEEE Abstract This paper presents a deterministic

More information

: : : : : : : : : : : : : COMPLAINT PARTIES. 1. Plaintiff the State of Rhode Island Department of Revenue ( Department of

: : : : : : : : : : : : : COMPLAINT PARTIES. 1. Plaintiff the State of Rhode Island Department of Revenue ( Department of STATE OF RHODE ISLAND PROVIDENCE, SC. THE STATE OF RHODE ISLAND DEPARTMENT OF REVENUE and THE RHODE ISLAND DEPARTMENT OF ADMINISTRATION, v. Plaintiff, HEWLETT-PACKARD STATE & LOCAL ENTERPRISE SERVICES,

More information

1. This section describes the materials and installation requirements for surge protective devices (SPD) for the protection of all AC electrical

1. This section describes the materials and installation requirements for surge protective devices (SPD) for the protection of all AC electrical Spec Interpretation The purpose of this PowerPoint is to highlight the areas of the written spec and electrical drawings which contain the information required to determine a TPS part number for quoting

More information

FLORIDA DEPARTMENT OF COMMUNITY AFFAIRS DIVISION OF HOUSING AND COMMUNITY DEVELOPMENT BUILDING CODE COMMISSION

FLORIDA DEPARTMENT OF COMMUNITY AFFAIRS DIVISION OF HOUSING AND COMMUNITY DEVELOPMENT BUILDING CODE COMMISSION FLORIDA DEPARTMENT OF COMMUNITY AFFAIRS DIVISION OF HOUSING AND COMMUNITY DEVELOPMENT BUILDING CODE COMMISSION IN RE: PETITION FOR DECLARATORY STATEMENT BY VERIZON WIRELESS PERSONAL COMMUNICATIONS, LP

More information

St. Augustine Exchange Base Rate Area Map -

St. Augustine Exchange Base Rate Area Map - BELLSOUTH BellSouth Telecommunications, Inc. Marshall M. Criser III 150 South Monroe Street Vice-President Suite 400 Regulatory & External Affairs Tallahassee, Florida 32301 marshall.criser@bellsouth.com

More information

OC IEEE IAS/PES Meeting February 21, 2013

OC IEEE IAS/PES Meeting February 21, 2013 San Diego International Airport: Building For The Future, Through Underground Distribution Automation and SCADA OC IEEE IAS/PES Meeting February 21, 2013 1 Presenter: Randy Denton, PE Under Ground Utility

More information

National Grid Local System Plan PAC Presentation October 18, 2017 Melissa Scott and Julia Spatafore, presenter

National Grid Local System Plan PAC Presentation October 18, 2017 Melissa Scott and Julia Spatafore, presenter National Grid Local System Plan 2017 PAC Presentation October 18, 2017 Melissa Scott and Julia Spatafore, presenter Purpose of Local System Plan The Local System Plan (LSP) is a report that: Describes:

More information

City of Ames Street Banner Policy

City of Ames Street Banner Policy The City of Ames is for regulating all banners to be placed in the following locations: Campustown, Downtown, University Boulevard - Lincoln Way to US 30, University Boulevard - ISU Research Park, South

More information

IN THE UNITED STATES DISTRICT COURT FOR THE DISTRICT OF COLORADO

IN THE UNITED STATES DISTRICT COURT FOR THE DISTRICT OF COLORADO IN THE UNITED STATES DISTRICT COURT FOR THE DISTRICT OF COLORADO Criminal Case No. 05-cr-00545-EWN UNITED STATES OF AMERICA, v. Plaintiff, 1. JOSEPH P. NACCHIO, Defendant. SUPPLEMENT TO GOVERNMENT S BILL

More information

Multifunction Relays and Protection Logic Processors in Distribution Substation Applications

Multifunction Relays and Protection Logic Processors in Distribution Substation Applications Multifunction s and Protection Logic Processors in Distribution Substation Applications David Sánchez Escobedo, Eliseo Alcázar Ramírez, Oscar A. Márquez Villanueva, and Héctor J. Altuve Ferrer Schweitzer

More information