Siemens Fusesaver and Remote Control Unit 3AD8

Size: px
Start display at page:

Download "Siemens Fusesaver and Remote Control Unit 3AD8"

Transcription

1 Catalog HG Edition 2017 Siemens Fusesaver and Remote Control Unit 3AD8 Medium-Voltage Equipment siemens.com/fusesaver

2 2 Siemens Fusesaver and Remote Control Unit 3AD8 Siemens HG R-HG11-FR-001.tif

3 Contents Siemens Fusesaver and Remote Control Unit 3AD8 Medium-Voltage Equipment Catalog HG Replacing: Catalog HG siemens.com/fusesaver Contents Page Rural network challenges 4 5 Fusesaver 6 The Fusesaver system 8 Communications module 11 Siemens Connect software 12 Protection functions and modes 14 Standards and ambient conditions 16 Product range overview and scope of delivery 17 Remote Control Unit 19 RCU principle 20 The RCU system 21 Communications interface and protocol 24 RCU Connect and RCU Probe software 24 Standards, ambient conditions, scope of delivery Product Selection 27 Ordering data and configuration example 28 Selection of Fusesaver 29 Selection of Remote Control Unit 30 Selection of additional equipment 31 Selection of accessories and spare parts 32 2 Technical Data 33 Electrical data, dimensions and weights 34 Dimension drawings 35 3 The products and systems described in this catalog are manufactured and sold according to a certified management system (acc. to ISO 9001, ISO and BS OHSAS 18001). Annex 37 Benefits 38 Inquiry form 39 Configuration aid Foldout page 4 Siemens Fusesaver and Remote Control Unit 3AD8 Siemens HG

4 Rural network challenges In most rural network configurations, the feeder is protected by a circuit-breaker or recloser. Lateral lines (also referred to as T-offs or spur lines) are usually protected by fuses. As a fuse is unable to distinguish between temporary and permanent faults, it blows on ALL faults, causing downstream customers to lose power and requiring a line crew to replace the fuse. In rural networks it may take hours for the line crew to drive to site, patrol the line and reconnect supply. This leads to unnecessary high operating costs for the utility. Furthermore, downstream users are left without power for extended periods of time potentially resulting in financial penalties to the utility. Since typically 80 percent of a rural network s faults are transient, 80 percent of its fuses are blown unnecessarily. Some utilities are moving towards de-fusing their rural networks to avoid this problem and to address fire start risks also associated with fuses. They then depend upon the upstream recloser to clear transient faults on the lateral line. This approach at best greatly increases the number of customers affected by a transient fault. However, it is known that the recloser may not have adequate protection reach, resulting in undetected persistent faults that can cause a danger to the community. Another historic way of dealing with lateral line* faults is with the help of drop-out sectionalizers. This device needs an upstream recloser or circuit-breaker to trip on a fault current. This gives stress to the downstream network for multiple times until the sectionalizer finally drops out. All above discussed scenarios can be improved by using the Siemens Fusesaver. Due to the low customer numbers on rural lateral lines* it was often difficult for the utility to find a cost-effective solution to this problem until now! The network example below shows a Fusesaver in line with a partner fuse and two Fusesavers without a fuse. All Fusesaver devices have the same hardware, but different customer-configurable protection sequences. For a detailed description, please refer to the following sections of this document. *) also referred to as T-offs or spur lines R-HG11-FR--100.tif CB CB CB CB 70 R 25 SS CB FS FS FS Item R CB FS SS Recloser Circuit-breaker Fusesaver Substation Fuse holder and partner fuse Feeder line Lateral line (also referred to as T-off or spur line) 71 HG a_en eps 4 Siemens Fusesaver and Remote Control Unit 3AD8 Siemens HG

5 Contents Contents Page Fusesaver 5 Siemens Fusesaver TM *) 3AD8 R-HG11-FR-101a.tif General 6 The Fusesaver system Design of the switch unit 8 Self powering 8 Vacuum interrupter 9 Magnetic actuator 9 External lever 9 Fusesaver mounting options 10 Line mounting 10 Cross-arm or pole mounting 10 Rating plate 10 Communications module Wireless communications 11 Battery 11 LED 11 Tripping and closing Siemens Connect software Configuration 12 Operation 12 Event data 13 Load profile data 13 Reliability data 13 Protection functions Fusesaver protection overview 14 Configurable dead time 15 Three-phase lockout protection 15 Pseudo three-phase trip protection 15 Pseudo three-phase trip and three-phase lockout 15 Protection modes 16 Standards 16 Ambient conditions 16 Altitude correction factor 16 Number of operating cycles 16 Product range overview 17 Scope of delivery 17 *) TM = Trade Mark Siemens Fusesaver and Remote Control Unit 3AD8 Siemens HG

6 General Siemens Fusesaver 3AD8 1.1 Fusesaver, the world s fastest medium-voltage (MV) outdoor vacuum circuit-breaker, is the most cost-effective solution for optimizing reliability while minimizing operating costs of rural overhead MV networks. It is capable of almost completely removing the impacts of temporary faults on lateral lines. Fusesaver is a new class of intelligent, compact and low-cost single-phase circuit-breaker. The Fusesaver complies with the relevant parts of IEC With on-board microprocessor control and wireless connectivity, Fusesaver has configurable protection, multi-phase operation functions, on-board event history, load profiling and can be integrated into a SCADA system for remote control. It is an electrically floating device that hangs directly from the MV line. With no earth connection, it has no electrical stresses on its insulators, resulting in long life. It self-powers by harvest- ing and storing energy from the line current. Fault detection is achieved with a cutting-edge, high-speed protection algorithm. The Fusesaver is designed to either: Be installed in series with the fuse. When it senses a fault current, it will open before the fuse can melt, and stay open for a pre-determined time (dead time) to clear a transient fault. Then, the Fusesaver closes again reconnecting supply. This is the traditional Open-Close Fusesaver approach Replace the fuse altogether. When installed in this manner the Fusesaver can perform the same Open-Close functionality as above to clear a transient fault but can also perform a second Open operation to clear a permanent fault. For highest flexibility, it is our customers choice, when configuring the Fusesaver, to select between the O-C and the O-CO operating cycle. Siemens Fusesaver [O-1s-C]* with partner fuse Whilst the fuse protects the lateral line, the Fusesaver protects the fuse from transient faults. Performance with temporary faults Performance with permanent faults Current Temporary fault Load current Current Permanent fault Open Dead time Open Dead time Fusesaver Closed 1 30 sec Fusesaver Closed 1 30 sec Blown Fuse Closed HG a_en eps Blown Fuse Closed HG a_en eps In this case, the fault disappears during the Fusesaver s dead time. After closing, the power supply is restored. The fuse did not operate, and the Fusesaver is ready for the next fault. Only the customers on the affected lateral experience an interruption in power during the Fusesaver s dead time, while all other customers on the feeder, including nearby laterals, do not even notice its operation. When the Fusesaver closes, the fault is still present, resulting in an immediate fault current. The Fusesaver will not operate again and allow the fault current to blow the fuse. Loss of power is unavoidable for customers on this lateral, while all other customers receive an uninterrupted power supply. The Siemens Fusesaver restricts blown fuses on lateral lines to unavoidable cases of permanent faults. *Highest customer flexibility: One hardware platform, two selectable operating sequences and multiple other policy file settings 6 Siemens Fusesaver and Remote Control Unit 3AD8 Siemens HG

7 General Siemens Fusesaver 3AD8 Many utilities worldwide have chosen to remove fuses from their overhead network entirely to address reliability, operator safety and fire prevention concerns. The O-CO Fusesaver provides a new solution to improve rural networks reliability. The fuse is no longer necessary to clear a permanent fault. This Open-Close-Open (O-CO) operating sequence is enabled by a next generation electronics platform. The Fusesaver O-CO is a primary protection device, and protection is operational even when the line is unenergized. This is supported by a communications module with on-board battery fitted to each Fusesaver O-CO. As part of this overall new electronics platform, a range of new features and performance enhancements have been implemented as follows: The Fusesaver O-CO maintains two fully configurable protection curves that can be applied to any protection trip The user now has much greater configurability of protection functionality depending upon status of the external lever. Not only can the protection curve be changed, but also the protection sequence and the three-phase lockout and pseudo three-phase trip functions can be enabled or disabled. The protection sequence can be configured to OFF, single shot or O-CO and this can be changed via SCADA control, if an RCU is installed Thermal overload protection provides a self protection against excessive load current Fault passage indication functionality: When a Fusesaver trips to lock-out on a permanent fault, the LED of the communications module will flash every 3 s for a user-defined period of time of up to 7 hours. 1.1 Siemens Fusesaver [O-2s-CO]* without partner fuse The Fusesaver O-CO is the ultimate Fusesaver, as the fuse is not required at all. Performance with temporary faults Performance with permanent faults Current Temporary fault Load current Current Permanent fault Open Dead time Open Dead time Fusesaver Closed 2 30 sec Fusesaver Closed 2 30 sec HG a1_en eps HG a1_en eps In this case, the fault disappears during the Fusesaver s dead time. After closing, the power supply is restored and the Fusesaver is ready for the next fault. Only the customers on the affected lateral experience an interruption in power during the Fusesaver s dead time, while all other customers on the feeder, including nearby lateral, do not even notice its operation. When the Fusesaver closes, the fault is still present, resulting in an immediate fault current. The Fusesaver will operate again and stay open. Loss of power is unavoidable for customers on this lateral, while all other customers receive an uninterrupted power supply. *Highest customer flexibility: One hardware platform, two selectable operating sequences and multiple other policy file settings Siemens Fusesaver and Remote Control Unit 3AD8 Siemens HG

8 The Fusesaver system The Fusesaver system 1.1 In order to minimize installation and operating costs, the Siemens Fusesaver was developed as part of an integrated system of tools and accessories. All system components work together, which permits easy installation, fast commissioning, and reliable operation in all conditions A typical Fusesaver installation includes the following items for each phase: 1 Fusesaver 3 Bird guard 2 Line clamping assembly 4 Communications module R-HG11-FR-102.tif A typical Fusesaver installation includes the following items for each phase: 1. Fusesaver 2. Line clamping assembly 3. Bird guard 4. Communications module Configuration of the unit is achieved through a wireless connection to a PC application called Siemens Connect. Design of the switch unit The Fusesaver is a fully integrated unit consisting of a vacuum interrupter driven by a magnetic actuator. On-board current transformers both power the Fusesaver and provide current measurement inputs into the built-in electronics control and protection module. The external insulation is high grade silicone rubber and the mechanism housing marine grade aluminium for long outdoor life. Self powering mm R-HG11-FR-103.tif The Fusesaver is capable of self powering from the very low line currents found on rural overhead networks. The Fusesaver is manufactured in three models with the low range model requiring as little as 0.15 A line current to power the unit. 1 Dead-end 2 Fault detection current transformer 3 Vacuum interrupter 4 Bird guard (optional) 5 Power current transformer 6 Magnetic actuator 7 Electronic module 8 Siemens Fusesaver and Remote Control Unit 3AD8 Siemens HG

9 Vacuum interrupter, magnetic actuator, external lever Vacuum interrupter The Fusesaver relies upon Siemens well-established vacuum interrupter technology. The vacuum interrupter utilized in the Fusesaver is a specific innovation by Siemens to facilitate the half-cycle fault interruption required to be able to successfully save fuses. 1.1 R-HG11-FR-105.tif R-HG11-FR-104.tif Magnetic actuator The magnetic actuator is another specific innovation by Siemens developed for the Fusesaver to also provide the half-cycle interruption capability. The magnetic actuator can unlatch in less than 2 ms and have the vacuum interrupter contacts fully open within another 4 ms. The magnetic actuator is directly coupled to the position indi cator which is visible from ground level. Fusesaver position indicator External lever The Fusesaver is fitted with an external lever that allows an operator to change the protection and other operational parameters of the Fusesaver. When the lever is in the UP position the LEVER UP settings are in force. R-HG11-FR-06.tif If a line crew is required to work downstream of the Fusesaver, they can pull DOWN the external lever to change the function of the Fusesaver according to the LEVER DOWN settings. Typically these alternative settings would be to either turn the protection OFF, or to implement a fast single-trip protection mode with half-cycle protection. Siemens Fusesaver and Remote Control Unit 3AD8 Siemens HG

10 Fusesaver mounting options, line mounting, cross-arm or pole mounting, rating plate Fusesaver mounting options 1.1 R-HG11-FR-106.tif Fusesaver is an electrically floating device so requires no earthing. This product architecture allows for a number of different mounting options. In all cases the Fusesaver has been designed to be mounted horizontally. Line mounting The preferred method for mounting of the Fusesaver is to hang it directly from the line using the line clamping assembly. The line clamping assembly connects directly to the dead-end of the conductor and ensures that the Fusesaver is hung at its center of mass. A cable connects the Fusesaver terminals to the conductor. Line mounting Cross-arm or pole mounting For locations where it is impractical to line mount the Fusesaver, an alternative is to use a cross-arm or the pole. A composite station post insulator with special end brackets is used to support the Fusesaver. Cross-arm mounting R-HG11-FR-107.tif Pole mounting R-HG11-FR-137.tif Rating plate Rating plate Note: For any request regarding spare parts, subsequent deliveries, etc. the following details are necessary: Type designation Serial No. Year of manufacture 10 Siemens Fusesaver and Remote Control Unit 3AD8 Siemens HG

11 Communications module Communications module The communications module plugs into a three-pin connector on the bottom of the Fusesaver and provides a short range wireless link between the Fusesaver and other devices. It also has a built-in battery. The module allows the crew to interface with Siemens Fusesaver from ground level using a laptop. It can be installed from the ground using a live-line stick equipped with a special communications module attachment tool. 1.1 The communications module has multiple purposes. It can be: Installed temporarily: At time of commissioning to allow the Fusesaver to be configured and tested During service to allow Fusesaver to be manually operated, line data accessed and event logs downloaded. Installed permanently: To allow Open-Close-Open functionality To allow three-phase functionality To improve the Fusesaver performance by reducing the capacitor recharge time and increasing the accuracy of the event log To enable the above functions and also to connect to a Remote Control Unit (RCU) thereby integrating the Fusesaver into the user s SCADA network. Wireless communications The communications module includes an intelligent short range wireless transceiver which enables encrypted communication to the Fusesaver from ground level. The wireless link uses the public 2.4 GHz band with a proprietary protocol. The effective range of the communications module depends on the installation and site conditions. A typical range is 20 m (60 ft) in line of sight. Battery The communications module is normally powered by energy extracted from line current by the Fusesaver. The communications module includes a battery to provide power to run the communications module radio and to manually operate the Fusesaver when the line current is off. LED The communications module has a transparent window on the underside behind which a high intensity LED is localized. When illuminated, this LED is visible from the ground in daylight. This LED is used to assist the operator during commissioning and when manually operating the Fusesaver. Tripping and closing The communications module is fitted with external actuators that may be used to trip or close the Fusesaver. Using the wireless communications between the Fusesavers it is also possible to synchronously trip and close Fusesavers. Communications module Communications module carry case kit R-HG11-FR-110.tif R-HG11-FR-109.tif R-HG11-FR-108.tif Siemens Fusesaver and Remote Control Unit 3AD8 Siemens HG

12 Siemens Connect software 1.1 Siemens Connect software Communication with the Fusesaver is performed using a special Fusesaver PC application, a USB radio antenna, and a short range (approximately 20 meters) radio integrated in the communications module. Fusesaver + communications module communicates with USB-antenna Configuration The Fusesavers are configured wirelessly through the Siemens Connect PC application. All the user needs to do is to identify the Fusesavers to be configured together as a site, load the policy file that includes the protection settings defined by the utility and tell the Fusesaver the type and rating of its partner fuse. The entire process is completed within a few minutes. R-HG11-FR-113a1.tif R-HG11-FR-112.tif R-HG11-FR-111a.tif R-HG11-FR-114a1.tif Operation When on-site, the line crew can access the live data in the Fusesaver using the Siemens Connect PC application. This live data includes: Details of the protection settings in the Fusesaver The Fusesaver open/closed status The load current in each Fusesaver The protection mode that is active Whether the protection is armed Details on the most recent fault Details on the Fusesaver and battery life Status of the communications between Fusesavers (peer communications). The operators also have the ability to trip and close the Fusesaver using controls from the PC. 12 Siemens Fusesaver and Remote Control Unit 3AD8 Siemens HG

13 Siemens Connect software Event data Fusesaver stores a time-stamped history of the major events in its on-board memory. The event record contains a history of up to 3,000 events including protection operations, fault data, outage durations, and configuration changes. The event data can be viewed using the Siemens Connect PC application. Data can be filtered and exported as required. 1.1 R-HG11-FR-115.tif Load profile data The Fusesaver can collect data on the current flowing in each phase of an installation. The Fusesaver can report the following data for each 24 hour period: The minimum current (with time stamp) The maximum peak current (with time stamp) The average daily current. Each time an event log is retrieved from Fusesaver the load profile data is stored onto the PC. The user can then display the data using the Siemens Connect tool in a number of formats. R-HG11-FR-142.tif Reliability data The purpose of the line reliability analysis tool is to allow the user to generate useful reliability performance data for a particular line. The analysis is conducted between a start date and end date that are selected by the user. The reliability statistics reported include the following items on a per phase basis: The recorded number of detected surge events The recorded number of detected fault events The recorded number of fault clearing events The recorded number of permanent fault events The total duration of outages due to permanent fault events. R-HG11-FR-116.tif Siemens Fusesaver and Remote Control Unit 3AD8 Siemens HG

14 Protection functions 1.1 Fusesaver with partner fuse time-current curve (a FAST protection curve is possible to add as shown in the lower picture on this page) Time 10 s d1 d2 100 Current (A) 1000 b K-type 15 A fuse d Fusesaver set to co-ordinate with a 15 A K-type fuse d1 Minimum trip current multiplier (x2) d2 Maximum fault time (0.5 sec) d3 Instantaneous multiplier (x10) d4 Minimum fault time (OFF) d Fuse replacement protection time current curve Time d3 d1 Minimum trip current multiplier ( 2/ 1) d2 Maximum fault time (1.5 sec/1 sec) d 10 s d1 d Current (A) 1000 Fusesaver that replaces a K type 30 A fuse d3 Instantaneous multiplier ( 20/ 8) d4 Minimum fault time (0.1 sec/off) d d3 b d4 NORMAL FAST d4 HG a_en_2.eps HG a_en eps Fusesaver protection time-current curve Fault detection is achieved with a cutting-edge, high speed protection algorithm that is capable of detecting faults within 2 ms. On the first trip the Fusesaver can clear the fault in the first half cycle when required. The default Fusesaver protection algorithm uses an inverse protection curve that is based upon an i 2 t value. When the Fusesaver is installed in series with a partner fuse, the algorithm ensures that the fault is cleared before its partner fuse starts to melt. At time of commissioning, the Fusesaver is configured to know the type and rating of its partner fuse that it is saving. When the Fusesaver is installed as a fuse replacement with the open-close-open functionality, the i 2 t of the inverse curve is set at best to approximately the rating of the fuse being replaced. At time of commissioning, the Fusesaver is configured to know the type and rating of the fuse that it is replacing. The Fusesaver can store two protection curves, a NORMAL and a FAST protection curve. The inverse part of the curve (d) is defined by the i 2 t of the fuse type the Fusesaver is protecting or replacing and is common to both curves. Additional configuration items required for each curve are the pick-up level (d1), the maximum time element (d2), the instantaneous multiplier (d3) and the minimum time element (d4). Minimum trip current multiplier The minimum trip current is a multiple of the fuse rating and sets the pickup level for the protection functionality. This is the current level above which the Fusesaver senses a fault. For example, if the Fusesaver is set for a 12 A fuse and a minimum trip level of x3 is selected, then any current below 36 A will not be recognized as a fault. Maximum fault time setting Once the current has risen above the minimum trip level, the Fusesaver picks the fault and will trip on an inverse-time basis to save the fuse. However, if the inverse-time protection has not tripped the Fusesaver before the maximum fault time is reached, then the Fusesaver will trip. Minimum fault time setting Once the current has risen above the minimum trip level, the Fusesaver has picked up the fault and will trip on an inverse time basis. However, the Fusesaver will not trip before the minimum trip time has been reached. Instantaneous trip setting The Fusesaver runs an inverse time curve to match the fuse that it is protecting. However the Fusesaver can also be set to trip instantaneously for faults above a certain level. The Fusesaver instantaneous protection works as a multiple of the fuse rating. So, for example, if the fuse rating is 10 A and the instantaneous multiplier is set to x5, then the Fusesaver will trip instantly for faults above 50 A. 14 Siemens Fusesaver and Remote Control Unit 3AD8 Siemens HG

15 Protection functions Configurable dead time The dead time is the period after the Fusesaver has tripped on a fault and before it closes. In general, the longer the dead time the greater the chance that a transient fault will be cleared by the operation of the Fusesaver. The dead time is a configuration option in the range 1-30 s (O-C) or 2-30 s (O-CO). Three-phase lockout protection When all the Fusesavers on a line are fitted with communications modules, it is possible to configure them so that if any one of them detects a permanent fault then after a start delay of typically less than 2 s, all three phases will be tripped and stay tripped. The two options are: Three-phase LOCKOUT DISABLED, this is the default Three-phase LOCKOUT ENABLED. Note that three-phase lockout operation can be affected by the position of the protection-off lever. Pseudo three-phase trip protection When all the Fusesavers on a line are fitted with communications modules, it is possible to configure them so that if one detects a fault and trips, the other two phases will trip shortly afterwards (typically less than 2 s). The three phases will then reclose simultaneously after the dead time of the Fusesaver that tripped first. This feature may be used to block backfeed current on a delta load circuit. Pseudo three-phase trip and three-phase lockout When both pseudo three-phase trip and three-phase lockout functions are enabled, the Fusesavers will act like a threephase soft ganged reclosing circuit-breaker. Three-phase lockout protection HG _5_en eps OPEN CLOSED OPEN CLOSED OPEN CLOSED HG _7_en eps Pseudo three-phase trip protection OPEN CLOSED OPEN CLOSED OPEN CLOSED s 50 Time (s) Current (A) Current (B) Current (C) Fusesaver A Fusesaver B Fusesaver C Current (A) Current (B) Current (C) Fusesaver A Fusesaver B Fusesaver C Time (s) Pseudo three-phase trip and three-phase lockout HG _8_en eps Current (A) Current (B) Current (C) OPEN CLOSED OPEN CLOSED OPEN CLOSED Fusesaver A Fusesaver B Fusesaver C Time (s) Siemens Fusesaver and Remote Control Unit 3AD8 Siemens HG

16 Protection modes, standards, ambient conditions, altitude correction factor and number of operating cycles 1.1 Protection modes The operation of the Fusesaver protection can be altered by changing the protection mode. The modes available depend upon whether the Fusesaver is used with a partner fuse or as a fuse replacement. Further, the Fusesaver will store a mode selection that is applicable if the external lever is in the UP or DOWN position to allow users to adjust to different operational requirements when a live line crew is working downstream of a Fusesaver. The following modes are possible: Standards The Fusesaver conforms to the relevant sections of the following standard: IEC Ambient conditions The Fusesaver is suitable for use in outdoor environments with ambient temperatures in the range of 40 C to +50 C and relative humidity in the range of 0 % to 100 %. Mode O-C O-CO Functionality Protection OFF YES YES The Fusesaver will not trip on a fault. Normal YES NO The Fusesaver trips based on the NORMAL curve settings and recloses after the dead time. Fast YES NO The Fusesaver trips based on the FAST curve settings and recloses after the dead time. Normal-normal NO YES The Fusesaver trips based on the NORMAL curve settings. The Fusesaver recloses after the dead time. If the fault is still present the Fusesaver trips a 2 nd time based on the NORMAL curve settings and then stays in the open state. Normal-fast NO YES The Fusesaver trips based on the NORMAL curve settings. The Fusesaver recloses after the dead time. If the fault is still present the Fusesaver trips a 2 nd time based on the FAST curve settings and then stays in the open state. Fast-normal NO YES The Fusesaver trips based on the FAST curve settings. The Fusesaver recloses after the dead time. If the fault is still present the Fusesaver trips a 2nd time based on the NORMAL curve settings and then stays in the open state. Fast-fast NO YES The Fusesaver trips based on the FAST curve settings. The Fusesaver recloses after the dead time. If the fault is still present the Fusesaver trips a 2 nd time based on the FAST curve settings and then stays in the open state. Normal single YES YES The Fusesaver trips based on the NORMAL curve settings. The Fusesaver does not reclose and stays in the open state. Fast single YES YES The Fusesaver trips based on the FAST curve settings. The Fusesaver does not reclose and stays in the open state. The protection mode in force is determined as follows: a) If the external lever is UP, the lever UP settings will be in force. This represents the usual expected operation of the Fusesaver. b) A local operator pulls the external lever down. In this case, the Fusesaver protection is forced to a mode that is predetermined by the user under this situation. c) A remote operator using a SCADA (Supervisory Control and Data Acquisition) system sets the mode. To do this, an RCU must be installed. d) A local operator uses a control panel in an RCU to set the mode. Ambient conditions Altitude correction factor The dielectric strength of air insulation decreases with increasing altitude due to low air density. The rated lightning impulse withstand voltage values specified in the chapter Technical Data apply to a site altitude of 1,000 m above sea level. For an altitude above 1,000 m, the insulation level must be corrected according to the drawing as per IEC The characteristic shown applies to the rated short-duration power-frequency withstand voltage and the rated lightning impulse withstand voltage. To select the devices, the following applies: U U 0 K a U Rated withstand voltage under standard reference atmosphere U 0 Rated withstand voltage requested for the place of installation K a Altitude correction factor according to the opposite diagram Example For a requested rated lightning impulse withstand voltage of 75 kv at an altitude of 2,500 m, an insulation level of 90 kv under standard reference atmosphere is required as a minimum: 90 kv 75 kv 1.2 Number of operating cycles 4 HG a_en eps Altitude correction factor m 4000 Site Site altitude The Fusesaver is maintenance-free for 2,000 operating cycles. The Fusesaver has been type tested for 70 short-circuit breaking operations at 4 ka and 30 short-circuit operations at 6.3 ka. Altitude correction factor HG _en eps 16 Siemens Fusesaver and Remote Control Unit 3AD8 Siemens HG

17 Product range overview and scope of delivery Product range overview The first main selection option is linked to the minimum line current available to power the Fusesaver. Three options are available: Low range Fusesaver Standard range Fusesaver High range Fusesaver. Model type Low range Standard range High range 1.1 Minimum line current for operation A Fuse ratings A 2 to 20 5 to 50 5 to 100 Rated current A Rated short-circuit breaking current I sc ka Rated short-circuit making current I peak ka Rated short-time current ka Rated short-time current duration s Fault break operations at 100 % No The low range, standard range and high range Fusesavers are all available with the following voltage rating options: Rated voltage kv Rated lightning impulse withstand voltage U p kv Rated power-frequency withstand voltage U d (60 s) kv Scope of delivery Fusesaver Operating mechanism Magnetic actuator Switching medium Vacuum interrupter Position indicator OPEN: green/closed: red Sensors Integrated current transformers Mounting assembly Line clamping assembly incl. bird guard (recommended) Pole mounting assembly incl. wildlife guard (recommended) Cross-arm mounting assembly incl. wildlife guard (recommended) Communication With optional communications module Software for operation and configuration Siemens Connect Tools Communications module attachment tool Accessories/spare parts A wide range of accessories and spare parts can be supplied (refer to selection on page 30) Siemens Fusesaver and Remote Control Unit 3AD8 Siemens HG

18 18 Siemens Fusesaver and Remote Control Unit 3AD8 Siemens HG R-HG11-FR-139.tif

19 Contents Contents Page Remote Control Unit 19 General 20 RCU principle 20 R-HG11-FR-117.tif The RCU system 21 RCU cubicle 21 Electronics housing 22 Radio tray 22 Cubicle heater 22 User interface 22 Operator panel 23 Isolated input 23 Solar panel 23 Voltage transformer Remote Control Unit 3AD8 Communications interface 24 Communications protocol 24 RCU Connect software 24 RCU Probe software 24 Standards 25 Ambient conditions 25 Scope of delivery 25 R-HG11-FR-118.tif Remote Control Unit 3AD8 Siemens Fusesaver and Remote Control Unit 3AD8 Siemens HG

20 General Siemens Remote Control Unit 1.2 The Remote Control unit (RCU) is an optional addition to the Fusesaver system used to connect the Fusesaver pole-mounted circuit-breaker into a utility SCADA system. The RCU is a pole-mounted enclosure containing a microprocessor, a short range (approximately 20 m) radio used to communicate with the Fusesaver and a long range radio (or modem). The design and testing of the RCU is according to the relevant parts of IEC :2005 Information technology equipment Safety. RCU principle The RCU acts as an interface between a set of Fusesavers on the power line and a utility SCADA system. To do this, the RCU uses its configuration to find and access installed and running Fusesavers mounted on the power pole. It communicates with the Fusesavers using its built-in short range radio. The Fusesavers are installed on each of the phases of the power line and are organized to work as a set to control that line. One, two or three Fusesavers can be organised in this way for a single-phase, two-phase or three-phase line. An RCU provides access to the Fusesavers on a single power line, so that if there are multiple lines at a site, then a separate RCU is required for each line. On start up, the RCU turns on its short range radio and scans for transmissions from the Fusesavers which match its configuration. When it finds them, it will acquire data from the Fusesavers and put it into its database ready for re-transmission over a long range radio (or modem) back to the utility SCADA system master station using the DNP 3 protocol. The long range radio is mounted in the radio tray by the utility and is provided with power by the RCU electronic system. Data in the RCU database includes information about the Fusesavers and the RCU itself. Usually a subset of this data is mapped into the protocol used by the SCADA system. R-HG11-FR-120.tif R-HG11-FR-121a.tif R-HG11-FR-119a.tif 20 Siemens Fusesaver and Remote Control Unit 3AD8 Siemens HG

21 The RCU system, RCU cubicle The RCU system In order to minimize installation and operating costs, the Siemens Remote Control Unit was developed as part of an integrated system of tools and accessories. All system components work together, which permits easy installation, fast commissioning, and reliable operation in all conditions. A typical Fusesaver and RCU installation includes the following items for each phase: 1. Fusesavers with communications modules 2. Remote Control Unit 3. Solar power Configuration of the RCU is achieved through a wireless connection to a PC application called RCU Connect R-HG11-FR-122.tif A typical Fusesaver and RCU installation includes the following items for each phase: 1 Fusesavers with 3 Solar panel communications modules 2 Remote Control Unit RCU cubicle The RCU enclosure in mounted to the pole using the polemounting bracket and is manufactured from powder-coated stainless steel for long service life. Material options are available at time of ordering including 304 (standard) and 316 grade stainless steel. The RCU enclosure has a handle with internal three-point locking mechanism. An external padlock can be fitted to restrict access. On the top of the RCU enclosure is a high grade UV-stabilized plastic shade hood. This shade hood serves to reduce solar heating and to provide an aperture for the short range radio. 6 1 Conductor 2 Fusesaver 3 Communications module 4 Fuse 7 5 Remote Control Unit 6 Earth connection 7 Mains connection 8 Antenna for long range communications At the rear of the RCU enclosure there is an earth stud and a number of openings fitted with cable glands to allow external wiring to access the internals of the RCU. R-HG11-FR-123.tif Siemens Fusesaver and Remote Control Unit 3AD8 Siemens HG

22 Electronics housing, radio tray, cubicle heater, user interface Electronics housing The electronics housing contains the microprocessor, battery, power connection terminals, data connection points and the user interface for the RCU. The RCU has a simple user interface for operations and maintenance purposes. The RCU front panel has a number of LED indicators. The LEDs are normally off (to reduce power consumption) and turn on automatically while the door is open as controlled by the position of the door switch. R-HG11-FR-124.tif The electronics housing also holds the 12 V, 7.2 Ah lead acid battery. The electronics housing is normally powered by a selectable 115/230 V AC low-voltage supply. 1.2 Radio tray The radio tray is available for fitting the customer-specific radio, modem or other means to connect to the utility s SCADA system. The radio tray hinges down and allows access to the radio behind. When in the hinged up position the tray provides a degree of protection from driving rain. Cubicle heater The cubicle heater is an optional accessory mounted behind the radio tray and connected to the power supply isolator. It has a positive temperature coefficient element which acts as a thermostatic heater keeping the battery and electronic compartment above 15 C for ambient temperatures as low as 40 C. Note that a power supply isolation unit is required if a heater is fitted. User interface The RCU provides a basic user interface on the electronics housing primarily to aid during commissioning. There are a range of toggle switches to allow the local user to turn ON/OFF various parts of the RCU system. An LED indicator display shows the status of the different inputs and outputs of the RCU. R-HG11-FR-127.tif R-HG11-FR-125.tif R-HG11-FR-126.tif 22 Siemens Fusesaver and Remote Control Unit 3AD8 Siemens HG

23 Operator panel, isolated input, solar panel, voltage transformer Operator panel The Fusesaver operator control panel is an optional ac - cessory mounted on the radio tray and connected to the RCU electronics compartment. The operator control panel allows a local user to trip and close the Fusesavers or to change protection mode active in the Fusesavers. It also provides additional status information. Isolated input R-HG11-FR-128.tif The power supply isolation unit is an optional accessory that provides a point of isolation for the electronics housing and the cubicle heater. Where an isolator is fitted the incoming mains is connected to the isolator and the isolator provides sockets for the electronics assembly and for the heater. The isolation unit is required if: The RCU is mains powered and if it is preferred to provide a point of isolation inside the cubicle for changing the electronic housing. Note that the user will still need to provide a point of isolation for the wiring to the RCU. A cubicle heater is fitted. The isolation unit is not an applicable option for a solar powered RCU. Solar panel Where an LV mains supply is not available, Siemens has a solar panel option to provide charge to the batteries. The solar panel is sized to provide adequate charge for energy efficient radios and modems in latitudes less than 45. The panel angle can be adjusted between two settings to optimize performance for given latitudes. The solar panel must be mounted on the same power pole as the RCU. R-HG11-FR-129.tif 1.2 The solar panel is connected into the terminal compartment to a dedicated set of terminals as an alternative to the mains supply. Solar ratings Power ratings Nominal voltage Cell type Value 65 W 12 V Polycrystalline R-HG11-FR-130.tif Voltage transformer Where LV mains is not available and solar power in not practical, the RCU can be powered by a voltage transformer mounted above the RCU and connected to the MV lines. Optional surge arresters are also available. VT ratings Primary voltage 11/22 kv 15 kv 27 kv 11/22 kv 15 kv 27 kv Type p-p p-p p-p p-e p-e p-e R-HG11-FR-131.tif According to IEC Siemens Fusesaver and Remote Control Unit 3AD8 Siemens HG

24 Communications interface, communications protocol, RCU Connect software, RCU Probe software Communications interface In order to communicate with the SCADA system master station a long range radio or modem is required. The RCU electronics provide a serial asynchronous data interface (RS232) and an Ethernet port (RJ45) for this purpose. A purpose-built cable connects the radio/modem to the RCU interface. The design and construction of this cable may be carried out by the customer or as a value added service provided by the Siemens Service Center. Communications protocol The RCU supports the DNP 3.0 over both serial link and IP protocol. 1.2 RCU Connect software RCU Connect is a PC application that allows the user to easily configure a Remote Control Unit and to check the operation of a Remote Control Unit in service. It also provides a means for configuration of the protocol mapping. R-HG11-FR-132.tif RCU Probe software R-HG11-FR-133.tif RCU Probe is a PC program that allows a user to directly connect to the RCU via Ethernet cable to view the current state of the protocol database. RCU Probe allows the user to override the value or qualifiers of all points in the protocol database in order to verify their change of state at the utility SCADA control room. The user may also send controls, times and view some general logging information. The intended users of RCU Probe are the utility SCADA technical staff for the purpose of verifying the correct operation of the SCADA system, communications system and RCU itself. 24 Siemens Fusesaver and Remote Control Unit 3AD8 Siemens HG

25 Standards, ambient conditions, scope of delivery Standards The design and testing of the Remote Control Unit is according to the relevant parts of IEC : 2005 Information technology equipment Safety. Ambient conditions The Remote Control Unit is suitable for use in outdoor environments with ambient temperatures in the range of 40 C to +50 C and relative humidity in the range of 5 % to 95 %. For temperatures below 15 C, the cubicle heater will be required C 40 C HG a eps 1.2 Scope of delivery Specifications Value Power supply 115/230 V AC mains 12 V/7.2 Ah battery backup Solar power options Radio power supply User set variable 3 9 V 2 A or 12 V battery supply 5 A Radio data interface Serial asynchronous RS232 or user set logic levels variable 3 9 V or 10/100 Base T Ethernet Radio compartment size mm Standard protocol DNP 3.0 Software for operation and configuration is: RCU Connect software Weight 18 kg Siemens Fusesaver and Remote Control Unit 3AD8 Siemens HG

26 26 Siemens Fusesaver and Remote Control Unit 3AD8 Siemens HG R-HG11-FR-134.tif

27 Product Selection Contents Contents Page Product Selection 27 Ordering data and configuration example 28 Selection of Fusesaver 29 Selection of Remote Control Unit 30 Selection of additional equipment 31 Selection of accessories and spare parts 32 Siemens Fusesaver 3AD8 Siemens Remote Control Unit (RCU) 3AD8 R-HG11-FR-135a.tif R-HG11-FR-101a.tif 2 Siemens Fusesaver and Remote Control Unit 3AD8 Siemens HG

28 Product Selection Ordering data and configuration example Order number structure The Siemens Fusesaver order number either configures a Siemens Fusesaver or a Remote Control Unit. The relevant data make up the 16-digit order number. The primary part covers the main electrical data of the Fusesaver or specifies an RCU. The secondary part covers the mounting assembly, communication options and others. Order codes Individual equipment versions, marked with 9 or Z in the 8 th to 16 th position, are explained more in detail by a 3-digit order code. Several order codes can be added to the order number in succession and in any sequence. Special versions In case of special versions, -Z is added to the order number and a descriptive order code follows. If several special versions are required, the suffix -Z is listed only once. If a requested special version is not in the catalog and can therefore not be ordered via order code, it has to be identified with Y 9 9 after consultation. The agreement hereto is made between your responsible sales partner and the order processing department. a: alphabetical n: numerical Position: Order codes Order No.: 3 A D n n n n n a a n n n a a n Primary part 1 st position Superior group Switching devices 2 nd position Main group Circuit-breaker 3 rd position Subgroup 2 4 th to 7 th position Basic equipment Design and ratings of the Siemens Fusesaver or selection of a RCU Secondary part 8 th to 16 th position Fusesaver assembly equipment, communication options, RCU options Order codes Group of 3 after the Order No. Format: a n a Special versions ( ) Initiated with -Z Group of 3 after the Order No. Format: a n n Configuration example On the foldout page we offer a configuring aid. Here you can fill in the order number you have determined for your Fusesaver and RCU. Example for Order No.: 3 A D Order codes: 28 Siemens Fusesaver and Remote Control Unit 3AD8 Siemens HG

29 Product Selection Selection of Fusesaver Fusesaver Configuration Position: Order codes Order No.: 3 A D Rated voltage Rated lightning impulse withstand voltage Rated short-duration power-frequency withstand voltage Rated short-circuit breaking current Rated normal current U r U p U d I sc I r kv kv kv ka A A D A A A A D A A A A D A A A A D A A A A D A A A A D A A A Fusesaver assemblies No Fusesaver clamping/mounting assembly 0 Line clamping assembly incl. bird guard (recommended) 1 Pole mounting assembly incl. wildlife guard (recommended) 2 Cross-arm mounting assembly incl. wildlife guard (recommended) 3 In-line tension mounting kit 4 Pole- or cross-arm mounting assembly without insulator 2 or 3 Z T 3 1 Clamping assembly without bird/wildlife guard 1, 2 or 3 Z T 3 2 Mounting brackets in 304 stainlees steel 2, 3 Z T 3 3 Imperial fastener mounting for US market (no fasteners included) 1, 2, 3 or 4 Z T 3 4 Communications module With communications module B Without communications module C 2 Language of operation manual, rating plate English 1 Other languages on request (increased delivery time) 9 R 1 Y Fusesaver additional options Position indicator with interchanged colors Green: CLOSED, Red: OPEN Z T 0 7 Fusesaver configuration example 1 Fusesaver (27 kv, 4 ka, 100 A), 1 line clamping assembly incl. bird guard, 1 communications module 3 A D B A A A 1 Siemens Fusesaver and Remote Control Unit 3AD8 Siemens HG

30 Product Selection Selection of Remote Control Unit (RCU) Remote Control Unit (RCU) Configuration Position: Order codes Order No.: 3 A D Remote Control Unit (RCU) 3 A D A RCU battery type: 7.2 Ah lead acid B RCU enclosure 316 stainless steel, powder-coated stainless steel, powder-coated 3 RCU mounting assembly No RCU mounting assembly 0 Standard pole mounting assembly 1 Side mounting assembly 2 RCU protocol: DNP RCU isolator and heater None External isolated mains input External isolated mains input and heater A B C Operator panel None RCU operator panel Fusesaver OC (Modes) RCU operator panel Fusesaver OCO (Modes) A B D 2 Language of operation manual, rating plate English 1 Other languages on request (increased delivery time) 9 R 1 Y RCU configuration example RCU battery type: 7.2 Ah lead acid, RCU enclosure: 304 stainless steel powder-coated, standard pole mounting assembly, RCU protocol: DNP 3.0, without RCU isolator and heater, without operator panel 3 A D A B A A 1 30 Siemens Fusesaver and Remote Control Unit 3AD8 Siemens HG

31 Product Selection Selection of additional equipment (communication, mounting assembly, demo kits) Fusesaver and RCU Communication, mounting assembly, demo kits Position: Order codes Order No.: 3 A X Fusesaver communication Fusesaver communications module 3 A X A Fusesaver communications module attachment tool 3 A X B Fusesaver PC communications kit 1) 3 A X C Fusesaver communications module carry case kit 2) 3 A X D Fusesaver mounting assembly Fusesaver bird guard 3 A X A Fusesaver wildlife guard (set of 3) 3 A X B Fusesaver cross-arm bracket fish plate kit 3 A X C Fusesaver wildlife guard (1 piece) 3 A X D Fusesaver wildlife guard clip (1 piece) 3 A X E Fusesaver line clamping assembly 3 A X A Fusesaver pole mounting assembly 3 A X B Fusesaver pole mounting assembly without insulator 3 A X E Fusesaver cross-arm mounting assembly 3 A X F Fusesaver cross-arm mounting assembly without Insulator 3 A X J Fusesaver demo kits Fusesaver demo kit (27 kv / 1.5 ka / 40 A Fusesaver) 3) 3 A X D Fusesaver demo kit (27 kv / 4 ka / 100 A Fusesaver) 3) 3 A X E Current injection set (for Fusesaver presentation) 3 A X F 1) 1 PC application: Siemens Connect, 1 USB radio antenna 2) 3 communications module, 1 communications module attachment tool, 1 PC communications kit, 1 heavy-duty case 3) 1 Fusesaver, 1 line clamping assembly, 1 bird guard, 2 communications module, 1 communications module attachment tool, 1 PC communications kit, 1 vacuum interrupter, 1 heavy-duty case 2 Siemens Fusesaver and Remote Control Unit 3AD8 Siemens HG

32 Product Selection Selection of accessories and spare parts Fusesaver and RCU Accessories / spare parts Position: Order codes Order No.: 3 A X RCU accessories / spare parts RCU battery 7.2 Ah lead acid 3 A X A RCU solar panel kit 65 W 3 A X B RCU VT kit p-p 11/22 kv 3 A X C RCU VT kit p-p 15 kv 3 A X D RCU VT kit p-p 27 kv 3 A X E RCU VT kit p-g 11/22 kv 3 A X F RCU VT kit p-g 15 kv 3 A X G RCU VT kit p-g 27 kv 3 A X H RCU serial cable RS232 + power 3 A X I RCU side mounting assembly 3 A X A RCU standard pole mounting assembly 3 A X B RCU radio tray heater (requires RCU external isolated mains input) 3 A X A RCU external isolated mains input 3 A X B RCU operator panel Fusesaver OC (Modes) 3 A X C RCU operator panel Fusesaver OCO (Modes) 3 A X D 2 32 Siemens Fusesaver and Remote Control Unit 3AD8 Siemens HG

33 Technical Data Contents Contents Page Technical Data 33 Electrical data, dimensions and weights 34 Dimension drawings 35 Siemens Fusesaver 3AD8 R-HG11-FR-138.tif 3 Siemens Fusesaver and Remote Control Unit 3AD8 Siemens HG

34 Technical Data Electrical data, dimensions and weights 15.5 kv Rated normal current Minimum line current for operation Fuse rating Rated operating sequence: O-2s-CO/O-1s-C Rated short-circuit breaking current Rated short-circuit making current Rated duration of short-circuit Fault break operations at 100 % Mechanical operations Rated lightning impulse withstand voltage Rated short-duration power-frequency withstand voltage Impedance µω between connections Creepage distance Weight I r I t k I SC I peak t k U p U d Order No. A A A s ka ka s No. No. kv kv µω mm kg 3AD AD AD kv I r I t k I SC I peak t k U p U d A A A s ka ka s No. No. kv kv µω mm kg 3AD AD AD Standards according to IEC Siemens Fusesaver and Remote Control Unit 3AD8 Siemens HG

35 Technical Data Dimension drawings Dimension drawings (mm) Fusesaver Fusesaver with communications module Fusesaver, communications module and line clamping assembly kv Fusesaver pole mounting assembly composite insulator kv Fusesaver cross-arm mounting assembly composite insulator Siemens Fusesaver and Remote Control Unit 3AD8 Siemens HG

36 Technical Data Dimension drawings Dimension drawings (mm) Remote Control Unit (RCU) 3 Solar panel (RCU powering option) 36 Siemens Fusesaver and Remote Control Unit 3AD8 Siemens HG

37 Annex Contents Contents Page Annex 37 Benefits 38 Inquiry form 39 Configuration aid Foldout page R-HG eps R-HG eps 4 Siemens Fusesaver and Remote Control Unit 3AD8 Siemens HG

38 Annex Benefits Benefits Your technology benefits at a glance Half-cycle switching fastest vacuum circuit-breaker on the market Smart-grid-ready with communications module and Remote Control Unit (RCU) Highly integrated and innovative technology Protection, monitoring and control in a single unit Self-powered Your handling benefits at a glance Lightweight (5.5 kg) Fast and easy installation plug and play Simple line installation Safety benefits for live-line crew thanks to half-cycle switching When the external lever is configured to FAST SINGLE mode, this greatly reduces the consequences of accidents during live- line work. With instantaneous protection that breaks the current in a half cycle, arc burns are greatly reduced and survival chances increase. The Fusesaver can be used as a ganged switch. When the actuator on one phase is operated, all phases will synchronously open/close after a delay of approx. 60 sec. This provides the benefit of avoiding ferroresonance and for operators to be cleared off the area when the switching operation occurs. Your cost benefits at a glance Return on investment typically in less than two years Improved network reliability means fewer penalty payments for both SAIFI and SAIDI Reduced operating costs thanks to reduced maintenance callouts Siemens Fusesaver an optimally compact design matched with rapid ROI* Higher availability, lower network maintenance costs the Siemens Fusesaver helps protect your competitive edge. The first saved fuse pays the installation costs, the second saves your money In a typical distribution network, the average outage duration per year (SAIDI) is within the range of hours per lateral line**. Installing a Siemens Fusesaver can reduce this duration to an absolute minimum, saving you thousands of dollars every year. *) Return on Investment **) Also referred to as lateral lines, T-off or T-taps 4 38 Siemens Fusesaver and Remote Control Unit 3AD8 Siemens HG

39 Annex Inquiry form Please copy, fill in and return to your Siemens partner Inquiry concerning Fusesaver and Remote Control Unit 3AD8 Your address Company Please Submit a quotation Call us Visit us Dept. Name Street Postal code/city Country Phone Fax Siemens AG Dept. Name Street Postal code/city Fax 4 Siemens Fusesaver and Remote Control Unit 3AD8 Siemens HG

40 You prefer to configure your Siemens Fusesaver and Remote Control Unit 3AD8 on your own? Please enter the order number in the configuration aid A D Z See page 29 See page 29 See page 29 See page 29 See page 29 See page 29 See page 29, 30 See page 29, 30 See page 29, 30 See page 29, 30 See page 29, 30 See page 29, 30 See page 29, 30 See page 29, 30 3 A D A D A D A D A D A D A D A D

41

AMEU FuseSaver Highest availability and cost savings for your medium voltage distribution network

AMEU FuseSaver Highest availability and cost savings for your medium voltage distribution network AMEU 2012 FuseSaver Highest availability and cost savings for your medium voltage distribution network October Page 2012 1 Siemens IC AG LMV 2012 MV C PPM Challenges for rural networks Characteristics

More information

Siemens FuseSaver New half-cycle circuit breaker for rural smart grids to minimize operating costs of feeder and spur lines

Siemens FuseSaver New half-cycle circuit breaker for rural smart grids to minimize operating costs of feeder and spur lines Siemens FuseSaver New half-cycle circuit breaker for rural smart grids to minimize operating costs of feeder and spur lines Authors: Dr. Brett Watson, Siemens Ltd., PO Box 4833, Loganholme, QLD 4129, Australia

More information

Products Portfolio. Pole mounted Vacuum Recloser

Products Portfolio. Pole mounted Vacuum Recloser Products Portfolio Pole mounted Vacuum Recloser Efacec Switchgear Efacec Switchgear is a leading company in Portugal and a worldwide reference in the development of solutions for power generation, transmission,

More information

S&C IntelliRupter PulseCloser Fault Interrupter Overhead Source-Transfer Application

S&C IntelliRupter PulseCloser Fault Interrupter Overhead Source-Transfer Application Overhead Source-Transfer Application Detailed Functional Specification Guide 1.0 GENERAL 1.01 The automated distribution fault-interrupting system shall conform to the following specification. 1.02 The

More information

NU-LEC. Loop Automation. Reclosers & Sectionalizers

NU-LEC. Loop Automation. Reclosers & Sectionalizers NU-LEC Loop Automation Reclosers & Sectionalizers 1 NU-LEC LLC NU-LEC LLC is a wholly unit of NU-LEC Industries, Pty, Ltd. Sales and service center for United States, Canada, and the Caribbean. Warehouse

More information

Elastimold Molded Vacuum Recloser - MVR

Elastimold Molded Vacuum Recloser - MVR Subject: Elastimold Recloser Technical Specification Date: 4/24/12 File: MVR-RS-0412 Page: 1 of 6 1.0 SCOPE Elastimold Molded Vacuum Recloser - MVR 1.1 This specification covers electrical and mechanical

More information

S&C IntelliRupter PulseCloser Outdoor Distribution (15.5 kv and 27 kv)

S&C IntelliRupter PulseCloser Outdoor Distribution (15.5 kv and 27 kv) Outdo Distribution (15.5 kv and 27 kv) Detailed Functional Specification Guide 1.0 GENERAL 1.01 The automated distribution fault interrupting system shall confm to the following specification. 1.02 The

More information

ENhanced TEChnology. Solid insulated vacuum recloser for power distribution system thru 15kV, 27kV, 38kV. Ver.

ENhanced TEChnology.  Solid insulated vacuum recloser for power distribution system thru 15kV, 27kV, 38kV. Ver. ENhanced TEChnology www.entecene.co.kr Solid insulated vacuum recloser for power distribution system thru 15kV, 27kV, 38kV Ver. 081226 General features We, ENTEC introduce a Solid Insulated Vacuum Recloser

More information

LineScope. Smart Power Monitor. Bulletin DB50C18. US Patent Nos , , and B2

LineScope. Smart Power Monitor. Bulletin DB50C18. US Patent Nos , , and B2 Bulletin DB50C18 LineScope Smart Power Monitor US Patent Nos. 9664710, 9746498, and 9810720B2 14000 Rt. 993, Trafford, PA 15085 p 724-864-4177 f 724-864-9040 e sales@cleavelandprice.com The LineScope Overview

More information

Type SDR reclosers plus controllers and type B-2 recloser bypass switch assembly usa.siemens.com/mediumvoltage

Type SDR reclosers plus controllers and type B-2 recloser bypass switch assembly usa.siemens.com/mediumvoltage Overhead solutions Type SDR reclosers plus controllers and type B-2 recloser bypass switch assembly usa.siemens.com/mediumvoltage Overhead switching products Brochure Your outdoor overhead distribution

More information

3a. IEM Indoor Metal Clad Medium Voltage Switchgear 25KV a. Section INDOOR METAL CLAD MEDIUM VOLTAGE SWTICHGEAR (Std.

3a. IEM Indoor Metal Clad Medium Voltage Switchgear 25KV a. Section INDOOR METAL CLAD MEDIUM VOLTAGE SWTICHGEAR (Std. 3a. IEM Indoor Metal Clad Medium Voltage Switchgear 25KV 16346-1 3a. Section 16346 INDOOR METAL CLAD MEDIUM VOLTAGE SWTICHGEAR (Std. Relays) Part 1 General 1.1 CONDITIONS AND REQUIREMENTS: A. Refer to

More information

OSM PRODUCT GUIDE. OSM AUTOMATIC CIRCUIT RECLOSER 15kV, 27kV & 38kV Models

OSM PRODUCT GUIDE. OSM AUTOMATIC CIRCUIT RECLOSER 15kV, 27kV & 38kV Models OSM PRODUCT GUIDE OSM AUTOMATIC CIRCUIT RECLOSER 15kV, 27kV & 38kV Models 1. Product Guide OSM Automatic Circuit Recloser 15kV 27kV 38kV Models Introduction INTRODUCTION The OSM15, OSM27 and OSM38 automatic

More information

WiAutoLink Frequently Asked Questions

WiAutoLink Frequently Asked Questions Rev. 0 December 2014 Page 1 of 8 WiAutoLink Frequently Asked Questions December 2014 1 Rev. 0 December 2014 Page 2 of 8 Table of Contents 1 Background... 4 1.1 What is the WiAutoLink Single Phase Electronic

More information

ENhanced TEChnology. Solid insulated vacuum recloser for power distrbution system thru 15kV, 27kV, 38kV V 3.1

ENhanced TEChnology.   Solid insulated vacuum recloser for power distrbution system thru 15kV, 27kV, 38kV V 3.1 ENhanced TEChnology www.entecene.co.kr Solid insulated vacuum recloser for power distrbution system thru 15kV, 27kV, 38kV V 3.1 General features We, ENTEC introduce a Solid Insulated Vacuum Recloser encapsulated

More information

InHand Wireless. As an important sector of smart grid building, smart distribution network faces the

InHand Wireless. As an important sector of smart grid building, smart distribution network faces the InHand Wireless Overhead Line System Overhead Line Sensor Key Features: Innovative low current (10A) auto power-harvesting technology, maintains network connection and reliable operation Advanced electronic

More information

Section 4 Ground-Fault Protection Devices

Section 4 Ground-Fault Protection Devices Multi 9 System Catalog Section 4Ground-Fault Protection Devices Section 4Ground-Fault Protection Devices Selection Table The Multi 9 System includes one UL Listed and three IEC rated product families that

More information

Electrical Demand Specification (Reference SOP: )

Electrical Demand Specification (Reference SOP: ) Project: Equipment Description: Location: Equipment No.: Project No: Protocol No.: Content Index 1. GENERAL...3 Design Standards...3 1.1. Standards...3 2. DESIGN...3 2.1. Safety...3 2.2. Circuit protection...3

More information

QUINT-BUFFER/24DC/24DC/40

QUINT-BUFFER/24DC/24DC/40 Buffer module Data sheet 105496_en_01 PHOENIX CONTACT 2013-11-01 1 Description The QUINT BUFFER buffer module combines the electronic switchover unit and power storage in the same housing. The buffer module

More information

MiCOM P124 T&D. Self and Dual Powered Overcurrent Relays

MiCOM P124 T&D. Self and Dual Powered Overcurrent Relays PROTECTION MiCOM P124 Self and Dual Powered Overcurrent Relays MiCOM P124 are numerical relays designed to offer complete overcurrent protection without requiring any external auxiliary supply. They can

More information

S&C 6801M Automatic Switch Operator

S&C 6801M Automatic Switch Operator S&C 6801M Automatic Switch Operator for Overhead Distribution Switches and Disconnects Simple, Economical Switch Automation S&C s 6801M Automatic Switch Operators make it easy to automate new or existing

More information

C C CIRCUIT-BREAKERS Moulded-case (MCCB), general. 1. Introduction. 2. General description

C C CIRCUIT-BREAKERS Moulded-case (MCCB), general. 1. Introduction. 2. General description CIRCUIT-BREAKERS C C81-21 CIRCUIT-BREAKERS - Contents 1. Introduction 2. General description 3. Rated voltages 3.1 Rated operational voltage (U e ) 3.2 Rated impulse withstand voltage (U imp ) 3.3 Rated

More information

Solid insulated vacuum recloser for power distribution system thru 15kV, 27kV, 38kV Version 3.3

Solid insulated vacuum recloser for power distribution system thru 15kV, 27kV, 38kV Version 3.3 www.entecene.co.kr Solid insulated vacuum recloser for power distribution system thru 15kV, 27kV, 38kV Version 3.3 General features We, ENTEC introduce a Solid Insulated Vacuum Recloser encapsulated with

More information

SECTION SWITCHBOARDS

SECTION SWITCHBOARDS SECTION 26 24 13 PART 1 - GENERAL 1.1 SUMMARY A. Work Included: 1. Switchboards 2. Commercial Metering Switchboards 3. Non-Utility Power Meters (Microprocessor-Based Metering Equipment) PART 2 - PRODUCTS

More information

Siemens Vacuum Recloser 3AD. Answers for energy. Medium-Voltage Equipment Selection and Ordering Data. Catalog HG

Siemens Vacuum Recloser 3AD. Answers for energy. Medium-Voltage Equipment Selection and Ordering Data. Catalog HG Medium-Voltage Equipment Selection and Ordering Data Catalog HG 11.42 2011 Answers for energy. R-HG11-172.tif 2 Siemens HG 11.42 2011 Contents Siemens Vacuum Recloser 3AD Medium-Voltage Equipment Catalog

More information

DRTS 64. The new generation of advanced test equipment for Relays, Energy meters, Transducers and Power quality meters.

DRTS 64. The new generation of advanced test equipment for Relays, Energy meters, Transducers and Power quality meters. The new generation of advanced test equipment for Relays, Energy meters, Transducers and Power quality meters Testing all relay technologies: electromechanical, solid state, numerical and IEC61850 Manual

More information

Switch Disconnectors, Main and EMERGENCY-STOP Switches

Switch Disconnectors, Main and EMERGENCY-STOP Switches General data Overview Siemens G 2010 1 2 3 NSE0_01931b 4 5 6 7 1 uxiliary switch (3SB for 3K; 3KX for 3KE) 2 IP20 terminal cover (Operator side) 3 3K switch disconnector 4 rcing contacts (only for 3KE)

More information

Loop Automation. Technical Manual for the ADVC Controller Range

Loop Automation. Technical Manual for the ADVC Controller Range Loop Automation Technical Manual for the ADVC Controller Range Contents List of Figures 5 List of Tables 7 Acronyms 7 Symbols 7 Introduction 8 About this Manual 8 ADVC Controller Firmware Version 9 WSOS

More information

DRTS 66. The new generation of advanced test equipments for Relays, Energy meters, Transducers and Power quality meters

DRTS 66. The new generation of advanced test equipments for Relays, Energy meters, Transducers and Power quality meters The new generation of advanced test equipments for Relays, Energy meters, Transducers and Power quality meters Testing all relay technologies: electromechanical, solid state, numerical and IEC61850 Manual

More information

MC 11 EB-2 Power supply cabinet with external bus, AC version

MC 11 EB-2 Power supply cabinet with external bus, AC version MC 11 EB-2 Power supply cabinet with external bus, AC version USER/MAINTENANCE MANUAL 1 SLOT 0 SLOT 1 SLOT 2 SLOT 3 SLOT 4 SLOT 5 SLOT 6 SLOT 7 SLOT 8 SLOT 9 SLOT 10 SLOT 11 EB-2 (a) MC11 (b) (c) Figures

More information

A P P L I C A T I O N

A P P L I C A T I O N Circuit Breaker timing test set 16 timing channels Motion and speed analyzer Built-in 200 A microohmmeter Up to 4 trip/close coils control Static and dynamic contact resistance measurement Suitable for

More information

ELG4125: System Protection

ELG4125: System Protection ELG4125: System Protection System Protection Any power system is prone to 'faults', (also called short-circuits), which occur mostly as a result of insulation failure and sometimes due to external causes.

More information

CBA HV Circuit Breaker Analyzer and Microhmmeter

CBA HV Circuit Breaker Analyzer and Microhmmeter CBA 2000 HV Circuit Breaker Analyzer and Microhmmeter Built-in 200 A microhmmeter Up to 18 main and 18 resistive contact inputs 12 auxiliary timing inputs Up to 4 trip/close coils control Motion and speed

More information

ATS-16 HV USER MANUAL. Automatic Transfer Switch 16A / 230Vac V090318

ATS-16 HV USER MANUAL. Automatic Transfer Switch 16A / 230Vac V090318 ATS-16 HV Automatic Transfer Switch 16A / 230Vac USER MANUAL V090318 SAFETY Intended use The ATS-16 HV device serves as a power source selector to provide improved power supply for connected loads. ATS-16

More information

DRTS 33. The new generation of advanced test equipments for Relays, Energy meters, Transducers and Power quality meters

DRTS 33. The new generation of advanced test equipments for Relays, Energy meters, Transducers and Power quality meters The new generation of advanced test equipments for Relays, Energy meters, Transducers and Power quality meters Testing all relay technologies: electromechanical, solid state, numerical and IEC61850 Manual

More information

DRTS 33. The new generation of advanced three phase relay test set

DRTS 33. The new generation of advanced three phase relay test set The new generation of advanced three phase relay test set Testing all relay technologies: electromechanical, solid state, numerical and IEC61850 Local control with color display Simultaneously available:

More information

IIM Warwick Court. Williamsburg VA REV 5

IIM Warwick Court. Williamsburg VA REV 5 1 1-757-258-3939 100 Warwick Court Williamsburg VA 23185 REV 5 2 Technical Specification >Accuracy Better than + 1% over a range of 1.5 to 200 amperes with power factor ranging from 1 to 0.5 Approved by

More information

Rapier GX Gas Enclosed Load Break Switch and Sectionaliser up to 38kV with automation or remote control options ENGINEERING BRILLIANT SOLUTIONS

Rapier GX Gas Enclosed Load Break Switch and Sectionaliser up to 38kV with automation or remote control options ENGINEERING BRILLIANT SOLUTIONS Rapier GX Gas Enclosed Load Break Switch and Sectionaliser up to 38kV with automation or remote control options ENGINEERING BRILLIANT SOLUTIONS RAPIER GX Gas Enclosed Switch Our new RAPIER GX, pole-mounted

More information

Catalog. Arc Guard System TM TVOC-2

Catalog. Arc Guard System TM TVOC-2 Catalog Arc Guard System TM TVOC-2 Introduction An even better Arc Guard System TVOC-2, ABB s latest Arc Monitor, builds on the well known TVOC design. Its new functions and features improve an already

More information

Instruction manual. Type SDR 15.5 kv to 27 kv single-phase distribution recloser. Answers for infrastructure.

Instruction manual. Type SDR 15.5 kv to 27 kv single-phase distribution recloser.  Answers for infrastructure. www.usa.siemens.com/reclosers Instruction manual Type SDR 15.5 kv to 27 kv single-phase distribution recloser Installation operation maintenance E50001-F710-A461-X-4A00 Answers for infrastructure. Hazardous

More information

VIP 40/45 VIP 400/410

VIP 40/45 VIP 400/410 40/45 400/410 Selection guide 01 PM100573 40/45 PM100576 400/410 self-powered integrated protection relay Optimised performance for transformer, incomer, feeder and bus riser protection Complete engineered

More information

DRTS 66 can test all the following relays

DRTS 66 can test all the following relays Testing all relay technologies: electromechanical, solid state, numerical and IEC61850 Manual control with color display Simultaneously available: 6 Current and 6 Voltage plus 1 battery simulator outputs

More information

Our Power & Control line of Business offers solutions that safely distribute power to your home or business. Our product range includes Low/Medium

Our Power & Control line of Business offers solutions that safely distribute power to your home or business. Our product range includes Low/Medium Our Power & Control line of Business offers solutions that safely distribute power to your home or business. Our product range includes Low/Medium Voltage Panels and Enclosures designed and built with

More information

MEDIUM VOLTAGE PRODUCTS. UniSec Air-insulated medium voltage secondary distribution switchgear Informed choice for safety

MEDIUM VOLTAGE PRODUCTS. UniSec Air-insulated medium voltage secondary distribution switchgear Informed choice for safety MEDIUM VOLTAGE PRODUCTS UniSec Air-insulated medium voltage secondary distribution switchgear Informed choice for safety 2 UNISEC AIR-INSULATED MEDIUM VOLTAGE SECONDARY DISTRIBUTION SWITCHGEAR Operator

More information

PLT. Breaker-based transfer switch open, closed or soft transition amps. Specification sheet

PLT. Breaker-based transfer switch open, closed or soft transition amps. Specification sheet Specification sheet PLT Breaker-based transfer switch open, closed or soft transition 800 3000 amps Description PLT breaker-based transfer switches are designed for operation and switching of electrical

More information

INSTALLATION PRODUCTS CAA GROUP OCTOBER 2018 Elastimold. Tru-Break switchgear module

INSTALLATION PRODUCTS CAA GROUP OCTOBER 2018 Elastimold. Tru-Break switchgear module INSTALLATION PRODUCTS CAA GROUP OCTOBER 2018 Elastimold Tru-Break switchgear module Tru-Break switchgear module agenda Design platform and value Product specifications Operation Configuration examples

More information

Medium Voltage Distribution. U-Series Three-Phase Recloser/ W-Series Single-Phase Recloser with ADVC Controller

Medium Voltage Distribution. U-Series Three-Phase Recloser/ W-Series Single-Phase Recloser with ADVC Controller Medium Voltage Distribution U-Series Three-Phase Recloser/ W-Series Single-Phase Recloser with ADVC Controller U-Series & W-Series solid dielectric automatic circuit recloser Applications SMART GRID READY

More information

S&C M Series Switch Operator. Sophisticated Microprocessor Control of Overhead Distribution Switches

S&C M Series Switch Operator. Sophisticated Microprocessor Control of Overhead Distribution Switches S&C M Series Switch Operator Sophisticated Microprocessor Control of Overhead Distribution Switches S&C s M Series Switch Operator is a fully integrated, microprocessor-based operator that lets you automate

More information

Specification Voltage Limiting Device

Specification Voltage Limiting Device Engineering Specification Electrical Networks L1-CHE-SPE-152 Specification Voltage Limiting Device Version: 1 Issued: 20 th April 2018 Owner: Chief Engineer Approved By: Andrew Russack Head of Engineering,

More information

Magnetic and Hydraulic-Magnetic Circuit Breaker

Magnetic and Hydraulic-Magnetic Circuit Breaker Description Single or multipole hydraulic-magnetic circuit breakers with trip-free - mechanism and toggle actuation. A choice of switching characteristics ensures suitability for a wide range of applications.

More information

DRTS 3 PLUS Advanced Protection Relay Test Set and Measurement System

DRTS 3 PLUS Advanced Protection Relay Test Set and Measurement System Advanced Protection Relay Test Set and Measurement System Multi-tasking equipment designed for testing protection relays, energy meters, transducers Particularly designed to test RTU (remote terminal unit)

More information

Issued February DATA SHEET 5SX2 MCB. Based on Siemens Industrial Control Catalog

Issued February DATA SHEET 5SX2 MCB. Based on Siemens Industrial Control Catalog Issued February 2011 DATA SHEET 5SX2 MCB Based on Siemens Industrial Control Catalog General Data Trip characteristics Tripping characteristics acc. to EN 60 898 Tripping characteristic A, -5 Type A characteristic

More information

MINER-S Station Controller

MINER-S Station Controller MINER-S Station Controller Substation Automation MINER-S Station Controller The MINER-S Station Controller is a SCADA enabled fixed point remote terminal unit (RTU) with a data concentrator, event reporter,

More information

MV Network Switchgear, Protection and Control

MV Network Switchgear, Protection and Control MV Network Switchgear, Protection and Control Ravinder Negi Manager, Services Execution INDIA Schneider Electric, New Delhi. Agenda An Overview MV Network Basic Definitions Circuit breaker Switchgear Control

More information

63 to 125 A. Functions. Conformity standards. General characteristics. Changeover switches SIRCO VM1 changeover switches.

63 to 125 A. Functions. Conformity standards. General characteristics. Changeover switches SIRCO VM1 changeover switches. comut_004_a_1_cat Changeover switches switches 63 to 125 A switches are manually operated three or four pole switches. They provide, source inversion or switching under load between two low voltage power

More information

Grid Automation packaged solutions Optimal automation of medium voltage grids

Grid Automation packaged solutions Optimal automation of medium voltage grids Grid Automation packaged solutions Optimal automation of medium voltage grids Application principles of the Zone concept Grid Automation (GA) packaged solutions The zone concept offers a method to analyze

More information

CBA 1000 CHARACTERISTICS

CBA 1000 CHARACTERISTICS Circuit Breaker Analyzer and Microhmmeter Circuit Breaker timing test set. Built-in 200 A microhmmeter. 16 timing channels. Up to 4 trip/close coils control. Motion and speed analyzer. Static and dynamic

More information

3RV1 Circuit-Breakers

3RV1 Circuit-Breakers SIRIUS 3R Description Mountable accessories 3RV1 Circuit- Breakers Circuit-breaker S00 with mountable accessories 3 2 1 5.1 NSK-7715a 4 Circuit-breaker S0 with mountable accessories 1 7 3 5.2 2 6 NSK-7716a

More information

Overvoltage Protection Devices

Overvoltage Protection Devices Siemens AG 2010 Overvoltage Protection Devices /2 Introduction /3 Lightning Arresters, Type 1 /5 Combination Surge Arresters, Type 1 and Type 2 /7 Surge Arresters, Type 2 /11 Surge Arresters, Type 3 /12

More information

MiCOM P124. Self and Dual Powered Overcurrent Relays. Protection Relays

MiCOM P124. Self and Dual Powered Overcurrent Relays. Protection Relays 01 Self and Dual Powered Overcurrent Relays are numerical relays designed to offer complete overcurrent protection without requiring any external auxiliary supply. They can be applied to a wide variety

More information

PHOENIX CONTACT - 06/2007. DANGER OF EXPLOSION! Remove an item only when it is not connected to power or if it is located in the non-explosive area.

PHOENIX CONTACT - 06/2007. DANGER OF EXPLOSION! Remove an item only when it is not connected to power or if it is located in the non-explosive area. Primary switched power supply, 3-phase, output current: 40 A INTERFACE Data Sheet 102782_01_en PHOENIX CONTACT - 06/2007 Description TRIO POWER is the rail mountable 24 V power supply unit with basic functions.

More information

IMPORTANT SAFETY INSTRUCTIONS SAVE THESE INSTRUCTIONS

IMPORTANT SAFETY INSTRUCTIONS SAVE THESE INSTRUCTIONS IMPORTANT SAFETY INSTRUCTIONS IMPORTANT SAFETY INSTRUCTIONS SAVE THESE INSTRUCTIONS WARNING (SAVE THESE INSTRUCTIONS): This manual contains important instructions that should be followed during installation

More information

5.1. Motor Protection and Monitoring. Contents. Product Overview. Monitoring Relays. D64R Series Digital Ground Fault Relays...

5.1. Motor Protection and Monitoring. Contents. Product Overview. Monitoring Relays. D64R Series Digital Ground Fault Relays... .1 Ground Fault Relays and Monitors Contents Description Current.................. Phase................... Voltage.................. Ground Fault Relays and Monitors D64R Series Digital Ground Fault Relays....

More information

PHOENIX CONTACT - 07/2006

PHOENIX CONTACT - 07/2006 Buffer module with maintenance-free capacitor-based power storage device INTERFACE Data sheet 102035_03_en PHOENIX CONTACT - 07/2006 Description Short-term mains interruptions are bridged by QUINT BUFFER,

More information

MINI-PS AC/10-15DC/8

MINI-PS AC/10-15DC/8 Primary-Switched Power Supply, Narrow Design Data Sheet 08/2004 MINI POWER provides: An extra narrow design, with widths of 22.5 mm, 45 mm, and 67.5 mm (0.886, 1.772, and 2.657 in.) Global use due to a

More information

Earth-fault Relay SPAJ 110 C. Product Guide

Earth-fault Relay SPAJ 110 C. Product Guide Issued: April 1999 Status: Updated Version: C/12.04.2006 Data subject to change without notice Features Low-set neutral overcurrent stage with definite time or inverse time characteristic High-set neutral

More information

Pulsar EXtreme 2000/3000 VA

Pulsar EXtreme 2000/3000 VA www.mgeups.com MGE UPS SYSTEMS Pulsar EXtreme 2000/3000 VA Installation and user manual P O W E R P R O V I D E R L E I B E R R U P T N T N I E U T H 51033211EN/AC - Page 1 Introduction Thank you for selecting

More information

SECTION ENCLOSED SWITCHES AND CIRCUIT BREAKERS

SECTION ENCLOSED SWITCHES AND CIRCUIT BREAKERS SECTION 262816 - ENCLOSED SWITCHES AND CIRCUIT BREAKERS PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division

More information

Firmware. Control Cable Interface

Firmware. Control Cable Interface SEL-651R-2 Recloser Control with Automatic Network Reconfiguration, Harmonic Analysis, Single-Phase Trip Capability, 6 Voltage Inputs, Power Quality Monitoring, 8 Settings Groups, Template Storage, SEL

More information

Network nodes with gateway

Network nodes with gateway 2 878 Siemeca AMR Network nodes with gateway WTX16.GSM WTX16.IP WTX16.MOD The WT 16 network nodes are used to receive and handle the data transmitted by consumption meters of the Siemeca AMR system. They

More information

POE084824B. PoE 54V/8x0,3A/4x7Ah PoE buffer power supply for up to 8 IP camera. v.1.1 EN* Edition: 7 from

POE084824B. PoE 54V/8x0,3A/4x7Ah PoE buffer power supply for up to 8 IP camera. v.1.1 EN* Edition: 7 from POE084824B v.1.1 PoE 54V/8x0,3A/4x7Ah PoE buffer power supply for up to 8 IP camera. EN* Edition: 7 from 15.11.2017 Supersedes the edition: 6 from 22.11.2016 GREEN POWER CCTV PoE PSU features: DC 54V uninterruptible

More information

THE NEW GENERATION OF ADVANCED TEST EQUIPMENTS FOR RELAYS, ENERGY METERS, TRANSDUCERS AND POWER QUALITY METERS.

THE NEW GENERATION OF ADVANCED TEST EQUIPMENTS FOR RELAYS, ENERGY METERS, TRANSDUCERS AND POWER QUALITY METERS. D R T S 6 6 THE NEW GENERATION OF ADVANCED TEST EQUIPMENTS FOR RELAYS, ENERGY METERS, TRANSDUCERS AND POWER QUALITY METERS. www.isatest.com DRTS 66 The new generation of advanced test equipments for relays,

More information

SACE Emax 2 Specification guide

SACE Emax 2 Specification guide SACE Emax 2 Specification guide Specification Number: 26 01 20.17 Product Name: LOW VOLTAGE POWER CIRCUIT BREAKERS PART 1 GENERAL NOTE: ( ) Indicates option or a selection is to be made for quantity or

More information

Product Description. S&C 5800 Series Automatic Switch Control S&C ELECTRIC COMPANY TABLE OF CONTENTS

Product Description. S&C 5800 Series Automatic Switch Control S&C ELECTRIC COMPANY TABLE OF CONTENTS S&C 5800 Series Automatic Switch Control Product Description TABLE OF CONTENTS Section Page INTRODUCTION Qualified Persons............................... 2 Read this Instruction Sheet.......................

More information

COOPER POWER. Types GN3E and GN3VE electronically controlled, manually closed sectionalizers SERIES. Sectionalizers Catalog Data CA270001EN

COOPER POWER. Types GN3E and GN3VE electronically controlled, manually closed sectionalizers SERIES. Sectionalizers Catalog Data CA270001EN Sectionalizers Catalog Data CA270001EN Supersedes 270-15 May 2014 COOPER POWER SERIES Types GN3E and GN3VE electronically controlled, manually closed sectionalizers Description A sectionalizer is an automatic

More information

Autodaptive Capacitor Control M 2501B

Autodaptive Capacitor Control M 2501B CONTROLS Autodaptive Capacitor Control M 2501B Capacitor Control for Pole-Top Capacitor Banks Increases effectiveness of installed capacitors for voltage control to reduce system losses Adapts reference

More information

Safety switches for hinged doors

Safety switches for hinged doors C Safety switches for hinged doors Selection diagram FR FM FX FZ FK 18 7 9 snap action overlapped CONTACT BLOCKS 21 NC 1NO+ CONDUIT ENTRIES Threaded conduit entries (standard) With cable gland assembled

More information

LASERMET LS-20 INSTRUCTION MANUAL

LASERMET LS-20 INSTRUCTION MANUAL LASERMET LS-20 INSTRUCTION MANUAL LASER SAFETY SHUTTER 00629-53-000 Issue 2 14 December 2012 Lasermet LS-20 Instruction Manual Contents DECLARATION OF CONFORMITY... 3 Concept... 4 Control Options... 4

More information

Product Details. Contents. Features and Mounting Options for SUNNY STRING-MONITOR SSM24-11

Product Details. Contents. Features and Mounting Options for SUNNY STRING-MONITOR SSM24-11 Technical Information Product Details Features and Mounting Options for SUNNY STRING-MONITOR SSM24-11 Contents The Sunny String Monitor SSM24 11 is specifically designed for monitoring large PV generators.

More information

Type SDR 15.5 kv to 38.0 kv distribution vacuum three-phase recloser instruction manual

Type SDR 15.5 kv to 38.0 kv distribution vacuum three-phase recloser instruction manual Type SDR 5.5 kv to 38.0 kv distribution vacuum three-phase recloser instruction manual Installation operation maintenance E5000-F70-A49-V-A400 Answers for energy. Hazardous voltages. Will cause death,

More information

Safety System CES-FD. Non-contact safety system CES-FD- Direct connection to decentralized peripheral systems (e.g. ET200pro) PLC

Safety System CES-FD. Non-contact safety system CES-FD- Direct connection to decentralized peripheral systems (e.g. ET200pro) PLC Non-contact safety system CES-FD- Evaluation of signals in the field Connection of CES read heads Connection to the ET200s and ET200pro Familiar EUCHNER AP interface Functional description Field evaluation

More information

Solid-State Switching Devices

Solid-State Switching Devices Overview 3RF21 3RF20 3RF22 3RF23 SIRIUS 3RF2 solid-state switching devices Solid-state switching devices for resistive loads Solid-state relays Solid-state contactors Function modules Solid-state switching

More information

Model HM-535 Power Supply Installation and Service Instructions

Model HM-535 Power Supply Installation and Service Instructions Model HM-535 Power Supply Installation and Service Instructions 430-535 0104 2004 Heritage MedCall, Inc SENTRY INSTALLATION & SERVICE INSTRUCTIONS POWER SUPPLY UNIT Model HM-535 IMPORTANT SAFETY INSTRUCTIONS

More information

SEL-734B Data Sheet. Advanced Monitoring and Control System. Major Features and Benefits

SEL-734B Data Sheet. Advanced Monitoring and Control System. Major Features and Benefits Advanced Monitoring and Control System Compact Enclosure Full-Size Enclosure Major Features and Benefits The SEL-734B combines volt/var based capacitor bank control with power quality monitoring and advanced

More information

Sicat CMS. siemens.com/mobility. Catenary monitoring system for overhead contact line systems

Sicat CMS. siemens.com/mobility. Catenary monitoring system for overhead contact line systems The contactless catenary monitoring system Sicat CMS continuously monitors the tensile forces in the contact wire and catenary wire and also acquires and evaluates the information. The filtered information

More information

ENERGY /// TE'S CROMPTON INSTRUMENTS TE'S CROMPTON INSTRUMENTS CURRENT TRANSFORMERS

ENERGY /// TE'S CROMPTON INSTRUMENTS TE'S CROMPTON INSTRUMENTS CURRENT TRANSFORMERS ENERGY /// TE'S CROMPTON INSTRUMENTS TE'S CROMPTON INSTRUMENTS CURRENT TRANSFORMERS 2 ENERGY /// TE'S CROMPTON INSTRUMENTS 3 Table of contents I. Tape Wound Measuring and Protection Current MR Series Measuring

More information

ekorrps MULTIFUNCTIONAL PROTECTION UNIT CONFIGURATION AND GENERAL CHARACTERISTICS LIB

ekorrps MULTIFUNCTIONAL PROTECTION UNIT CONFIGURATION AND GENERAL CHARACTERISTICS LIB MO-067-EN Operation Manual MULTIFUNCTIONAL PROTECTION UNIT CONFIGURATION AND GENERAL CHARACTERISTICS LIB Transformer Substations Secondary Distribution Switchgear Primary Distribution Switchgear Protection

More information

Available with actuator function: POWER OPEN - POWER CLOSE FAILSAFE MODULATING FAILSAFE MODULATING. Overview

Available with actuator function: POWER OPEN - POWER CLOSE FAILSAFE MODULATING FAILSAFE MODULATING. Overview Feature rich J+J multi-voltage smart electric actuator with LED status light and function conversion kits. J3C-S20 Overview The J3C-S20 multi-voltage smart electric valve actuator from the European electric

More information

AIR COOLED MODULAR RECTIFIER

AIR COOLED MODULAR RECTIFIER CONTROLLED POWER COMPANY SPECIFICATIONS AIR COOLED MODULAR RECTIFIER Spc1800a1 5JAN1999 SPECIFICATION S-1800-A MODULAR (REMOVABLE AND NON-REMOVABLE MODULES) AIR COOLED RECTIFIER Standard output power range:

More information

CROWN LINE Power Bus Bar Distribution System

CROWN LINE Power Bus Bar Distribution System COWN LINE Power Bus Bar Distribution System COWN LINE Power Bus Bar Distribution System The pluggable bus bar system Currents up to 300 Amps Up to 2 meters in length Pluggable breakers VDE finger proof

More information

Safety switches with separate actuator

Safety switches with separate actuator A Safety switches with separate actuator Selection diagram VF KEYF VF KEYF1 VF KEYF2 VF KEYF3 VF KEYF VF KEYF ACTUATORS CONTACT BLOCKS 9 snap action overlapped FD FP FL FC 21 22 33 3 3NC 2NO+1NC 1NO+ CONDUIT

More information

Maximum Reliability & Excellent Value. Features. UL Listed Withstand & Close-On Ratings. Series 300 Power Transfer Switches

Maximum Reliability & Excellent Value. Features. UL Listed Withstand & Close-On Ratings. Series 300 Power Transfer Switches Series 300 Power Transfer Switches Maximum Reliability & Excellent Value With a Series 300 Transfer Switch, you get a product backed by ASCO Power Technologies, the industry leader responsible for virtually

More information

SIPROTEC easy 7SJ45 Numerical Overcurrent Protection Relay Powered by CTs

SIPROTEC easy 7SJ45 Numerical Overcurrent Protection Relay Powered by CTs SIPROTEC easy 7SJ4 Numerical Overcurrent Protection Relay Powered by CTs Function overview Fig. /1 Description The SIPROTEC easy 7SJ4 is a numerical overcurrent protection relay which is primarily intended

More information

MESP TECHNICAL SPECIFICATION FOR A RECTIFIER UNIT CONTROL & PROTECTION SYSTEM FOR USE IN THE 1500V DC TRACTION SYSTEM

MESP TECHNICAL SPECIFICATION FOR A RECTIFIER UNIT CONTROL & PROTECTION SYSTEM FOR USE IN THE 1500V DC TRACTION SYSTEM Engineering Specification Electrical Networks TECHNICAL SPECIFICATION FOR A RECTIFIER UNIT CONTROL & PROTECTION SYSTEM FOR USE IN THE 1500V Version: 1 Issued: March 2014 Owner: Electrical Networks Asset

More information

IRI1-ES Sensitive Earth Fault Current Relay. Manual IRI1-ES (Revision A)

IRI1-ES Sensitive Earth Fault Current Relay. Manual IRI1-ES (Revision A) IRI1-ES Sensitive Earth Fault Current Relay Manual IRI1-ES (Revision A) Woodward Manual IRI1-ES GB Woodward Governor Company reserves the right to update any portion of this publication at any time. Information

More information

Effective May 2018 Supersedes October 2017

Effective May 2018 Supersedes October 2017 Technical Data TD280028EN Supersedes October 2017 COOPER POWER SERIES NOVA NX-T Recloser, Form 6 NX-T, and Form 6LS NX-TRecloser Control and Accessories Ordering Guide Eaton provides reliable, economical

More information

PHOENIX CONTACT - 08/2009. Features. DANGER OF EXPLOSION! Only remove equipment when it is disconnected and not in the potentially explosive area.

PHOENIX CONTACT - 08/2009. Features. DANGER OF EXPLOSION! Only remove equipment when it is disconnected and not in the potentially explosive area. Primary-switched power supply for building automation INTERFACE Data sheet 103505_en_02 1 Description PHOENIX CONTACT - 08/2009 Features STEP POWER power supply units for building automation The new STEP

More information

S&C Micro-AT Source-Transfer Controls PHOTO SHEET. For use in S&C Metal-Enclosed Gear

S&C Micro-AT Source-Transfer Controls PHOTO SHEET. For use in S&C Metal-Enclosed Gear S&C Micro-AT Source-Transfer Controls are designed for use in S&C Metal-Enclosed Switchgear and Source- Transfer Pad-Mounted Gear, in conjunction with power-operated S&C Mini-Rupter Switches or S&C Alduti-Rupter

More information

EMOSAFE EN-30 1 FEATURES AND ADVANTAGES 2 GENERAL DESCRIPTION. Product Datasheet. Gigabit Network Isolator in aluminium housing December 2015 ENGLISH

EMOSAFE EN-30 1 FEATURES AND ADVANTAGES 2 GENERAL DESCRIPTION. Product Datasheet. Gigabit Network Isolator in aluminium housing December 2015 ENGLISH ENGLISH EMOSAFE EN-30 Product Datasheet Gigabit Network Isolator in aluminium housing December 2015 1 FEATURES AND ADVANTAGES Gigabit Ethernet Hardwearing aluminium housing Optionally usable mounting bracket

More information

IMPROVE CUSTOMER SATISFACTION 3 FUNCTIONAL DESCRIPTION 5 DETECTION PRINCIPLE 6 WHERE SHOULD INDICATORS BE INSTALLED AND WHAT MODEL SHOULD BE USED 7

IMPROVE CUSTOMER SATISFACTION 3 FUNCTIONAL DESCRIPTION 5 DETECTION PRINCIPLE 6 WHERE SHOULD INDICATORS BE INSTALLED AND WHAT MODEL SHOULD BE USED 7 IMPROVE CUSTOMER SATISFACTION 3 FUNCTIONAL DESCRIPTION 5 DETECTION PRINCIPLE 6 WHERE SHOULD INDICATORS BE INSTALLED AND WHAT MODEL SHOULD BE USED 7 LINETROLL 110Eµ 8 LINETROLL 111K 9 LINETROLL L400D 10

More information

BE1-50/51M TIME OVERCURRENT RELAY ADVANTAGES

BE1-50/51M TIME OVERCURRENT RELAY ADVANTAGES BE1-50/51M TIME OVERCURRENT RELAY The BE1-50/51M Time Overcurrent Relay provides economical overload and fault protection for generators, transformers, lines and motors. ADVANTAGES Self powered from 50/60Hz

More information