1 Unit features Positive-guided relay outputs: 2 safety contacts (/O), instantaneous Connection options for: E-STOP pushbutton Reset button LED indicator for: Switch status channel 1/2 Supply voltage See order reference for unit types The circuit is redundant with built-in self-monitoring. The safety function remains effective in the case of a component failure. The correct opening and closing of the safety function relays is tested automatically in each on-off cycle. Safety relay for monitoring E-STOP pushbuttons. Approvals Unit description The safety relay meets the requirements of E and IEC and may be used in applications with E-STOP pushbuttons The safety relay is not suitable for noncontact barriers because a dynamic start is not possible the unit can be started during the delay-on de-energisation time. Safety features The relay conforms to the following safety criteria: Block diagram A2 Y1 Y ~ ( )* = Input Reset/ Start K1 Power K2 ( )* *Only when U B = VAC Galvanic isolation only when U B = VAC
2 Function description Single-channel operation: no redundancy in the input circuit, earth faults in the reset and input circuit are detected. Timing diagram Automatic start: Unit is active once the input circuit has been closed. Manual reset: Unit is active once the input circuit is closed and then the reset circuit is closed. Increase in the number of available contacts by connecting contact expander modules or external contactors/relays. 1 2 a b Reset/Start Power/Input Output safe t1 t2 t1 t2 t1 t2 t1 t2 Key Power: Supply voltage Reset/start: Reset circuit Y1-Y2 Input: Input circuits Output safe: Safety contacts 13-14, : Automatic reset : Manual reset a: Input circuit closes before reset circuit b: Reset circuit closes before input circuit t 1 : Switch-on delay t 2 : Delay-on de-energisation Wiring Please note: Information given in the Technical details must be followed. Outputs 13-14, are safety contacts. To prevent contact welding, a fuse should be connected before the output contacts (see technical details). Calculation of the max. cable runs l max in the input circuit: I max = R lmax R l / km R lmax = max. overall cable resistance (see technical details) R l /km = cable resistance/km Use copper wire that can withstand 60/75 C. Sufficient fuse protection must be provided on all output contacts with capacitive and inductive loads. AC: The cable runs depend on the cable capacitance. Loop circuit, 1 phase: max. l r = 1 km Stub circuit: Cable capacitance C L and therefore the cable runs l s are dependent on the supply voltage U B Cable capacitance C L depends on the supply voltage U B U B [V] C L [nf] Loop circuit Stub circuit Cable runs UB lr A2 AC UB ls A2 AC -2
3 Preparing for operation Supply voltage Supply voltage AC DC A2 L1 PE L+ A2 L- Input circuit Input circuit Single-channel Dual-channel E-STOP S1 without detection of shorts across contacts L+/L1 Safety gate without detection of shorts across contacts S1 L+/L1 Reset circuit Reset circuit Automatic reset E-STOP wiring (single-channel) Safety gate (single-channel) Y1 E-STOP wiring (dual-channel) Safety gate (dual-channel) Y2 Manual reset Y1 S3 Y2 Feedback loop Feedback loop Automatic reset Manual reset Contacts from external contactors Y1 Y2 13 (23) 14 (24) K5 K6 K5 K6 L1 Y1 Y2 13 (23) 14 (24) K5 S3 K6 K5 K6 L1
4 Key Terminal configuration S1 S3 E-STOP pushbutton Reset button Switch operated U B = 24 VAC/DC Gate open Gate closed POWER CH.1/CH Y1 Y A U B AC POWER CH.1/CH Y1 Y A Installation Dimensions The safety relay should be installed in a control cabinet with a protection type of at least IP54. Use the notch on the rear of the unit to attach it to a DI rail. Ensure the unit is mounted securely on a vertical DI rail (35 mm) by using a fixing element (e.g. retaining bracket or an end angle). 121 (4.8") 75 (2.95") 87 (3.42") 22,5 (0,89") -4
5 otice Service life graph This data sheet is only intended for use during configuration. For installation and operation, please refer to the operating instructions supplied with the unit. D ennbetriebstrom (A) GB ominal operating current (A) F Courant coupé (A) E Corriente nominal de servicio (A) ICorrente di esercizio nominale (A) L ominale bedrijfsstroom (A) 10 1 AC15: 230 V DC13: 24 V DC1: 24 V AC1: 230 V D Schaltspielzahl x 10 3 E úmero de ciclos x 10 3 GB Cycles x 10 3 Iumero dei cicli di commutazione x 10 3 F ombre de manœvres x 10 3 L Aantal schakelingen x 10 3 Technical details Electrical data Supply voltage Supply voltage U B AC 42 V, 48 V, 110 V, 115 V, 120 V, 230 V, 240 V Supply voltage U B AC/DC 24 V Voltage tolerance -15 %/+10 % Power consumption at U B AC 2.0 VA Order no.: , , , , , 3.0 VA Order no.: Power consumption at U B DC 1.5 W Order no.: Frequency range AC Hz Residual ripple DC 160 % Voltage and current at input circuit DC: 24.0 V 50.0 ma input circuit DC: 42.0 V 49.0 ma input circuit DC: 48.0 V 45.0 ma input circuit DC: V 14.0 ma input circuit DC: V 17.0 ma input circuit DC: V 16.0 ma input circuit DC: V 8.0 ma input circuit DC: V 7.0 ma reset circuit DC: 24.0 V 40.0 ma Order no.: , , , , , ma Order no.: feedback loop DC: 24.0 V 40.0 ma Order no.: , , , , , ma Order no.: Output contacts in accordance with E Category 2 Safety contacts (/O): 2
6 Electrical data Utilisation category in accordance with E Safety contacts: AC1 at 240 V I min : 0.01 A, I max : 4.00 A Order no.: , , , , , 6.00 A Order no.: P max : 1,000 VA Order no.: , , , , , 1,500 VA Order no.: Safety contacts: DC1 at 24 V I min : 0.01 A, I max : 4.0 A Order no.: , , , , , 6.0 A Order no.: P max : 100 W Order no.: , , , , , 150 W Order no.: Utilisation category in accordance with E Safety contacts: AC15 at 230 V I max : 4.0 A Order no.: , , , , , 5.0 A Order no.: Safety contacts: DC13 at 24 V (6 cycles/min) I max : 4.0 A Order no.: , , , , , 6.0 A Order no.: Contact material AgSnO µm Au External contact fuse protection to E Blow-out fuse, quick Safety contacts: 4 A Order no.: , , , , , , A Order no.: Blow-out fuse, slow Safety contacts: 4 A Circuit breaker 24 VAC/DC, characteristic B/C Safety contacts: 4 A Max. overall cable resistance R lmax input circuits, reset circuits single-channel at U B DC 15 Ohm Order no.: single-channel at U B AC 15 Ohm Order no.: Times Switch-on delay with automatic reset typ. 230 ms Order no.: , , , , , 50 ms Order no.: with automatic reset max. 150 ms Order no.: ms Order no.: , , , , , with automatic reset after power on typ. 230 ms Order no.: , , , , , 50 ms Order no.: with automatic reset after power on max. 150 ms Order no.: ms Order no.: , , , , , with manual reset typ. 140 ms Order no.: , , , , , 35 ms Order no.: with manual reset max. 150 ms Order no.: ms Order no.: , , , , , -6
7 Times Delay-on de-energisation with E-STOP typ. 45 ms Order no.: ms Order no.: , , , , , with E-STOP max. 100 ms Order no.: , , , , , 70 ms Order no.: with power failure typ. 45 ms Order no.: ms Order no.: , , , , , with power failure max. 100 ms Order no.: , , , , , 70 ms Order no.: Recovery time at max. switching frequency 1/s after E-STOP 120 ms Order no.: , , , , , 50 ms Order no.: after power failure 120 ms Order no.: , , , , , 150 ms Order no.: Supply interruption before de-energisation 20 ms Environmental data EMC E , E Vibration in accordance with E Frequency Hz Amplitude 0.35 mm Climatic suitability E Airgap creepage E Ambient temperature C Storage temperature C Protection type Mounting (e.g. control cabinet) IP54 Housing IP40 Terminals IP20 Mechanical data Housing material Housing PPO UL 94 V0 Front ABS UL 94 V0 Max. cross section of external conductors with screw terminals 1 core flexible mm², AWG 2 core, same cross section, flexible: with crimp connectors, without insulating sleeve mm², AWG without crimp connectors or with TWI crimp connectors mm², AWG Torque setting with screw terminals 0.60 m Dimensions Height 87.0 mm Width 22.5 mm Depth mm Weight 190 g Order no.: g Order no.: , , , , , The standards current on 09/04 apply.
8 Max. continuous current umber of contacts I max (A) at U B AC A Order no.: , , , , , A Order no.: , , , , , Order reference Type Features Terminals Order no. 42 VAC Screw terminals VAC Screw terminals VAC Screw terminals VAC Screw terminals VAC Screw terminals VAC Screw terminals VAC Screw terminals VAC/DC Screw terminals
Positive-guided relay outputs: 3 safety contacts (N/O), instantaneous. 1 auxiliary contact (N/C), instantaneous
Safety relay for monitoring E-STOP pushbuttons. Approvals Unit features Positive-guided relay outputs: 3 safety contacts (N/O), instantaneous 1 auxiliary contact (N/C), instantaneous Safe separation of
More informationE-STOP relays, safety gate monitors
Unit features Positive-guided relay outputs: 2 safety contacts (N/O), instantaneous Connection options for: E-STOP pushbutton Reset button LED indicator for: Switch status channel 1/2 Supply voltage See
More informationE-STOP relays, safety gate monitors
Safety relay for monitoring E-STOP pushbuttons, safety gates and light barriers. Approvals Unit features Positive-guided relay outputs: 7 safety contacts (N/O), instantaneous 2 auxiliary contacts (N/C),
More informationE-STOP relays, safety gate monitors
Safety relay for monitoring E-STOP pushbuttons and safety gates. Approvals Unit features Positive-guided relay outputs: 5 safety contacts (N/O), instantaneous 1 auxiliary contact (N/C), instantaneous Connection
More informationE-STOP relay, safety gate monitor
Safety relay for monitoring E-STOP pushbuttons and safety gates. Approvals Unit features Positive-guided relay outputs: 2 safety contacts (N/O), instantaneous 1 semiconductor output Connection options
More informationE-STOP relays, safety gate monitors
Safety relay for monitoring E-STOP pushbuttons and safety gates. Approvals Unit features Positive-guided relay outputs: 2 safety contacts (N/O), instantaneous 2 safety contacts (N/O), delay-on de-energisation
More informationE-STOP relays, safety gate monitors
E-STOP relays, safety gate monitors Up to Category 2, EN 954-1 Unit features Positive-guided relay outputs: 2 safety contacts (N/O), instantaneous Connection options for: E-STOP pushbutton Reset button
More informationE-STOP relays, safety gate monitors
Safety relay for monitoring E-STOP pushbuttons, safety gates and light barriers. Approvals Block diagram Unit features Positive-guided relay outputs: 6 safety contacts (N/O), instantaneous 4 auxiliary
More informationE-STOP relays, safety gate monitors
Safety relay for monitoring E-STOP pushbuttons and safety gates. Approvals Unit features Positive-guided relay outputs: 3 safety contacts (N/O), instantaneous 2 safety contacts (N/O), delay-on de-energisation
More informationPositive-guided relay outputs: 4 safety contacts (N/O), instantaneous
Contact expander module for increasing the number of available contacts Approvals Unit features Positive-guided relay outputs: 4 safety contacts (N/O), instantaneous LED indicator for: Switch status channel
More informationPositive-guided relay outputs: 4 safety contacts (N/O), instantaneous
ohne Abbildung Contact expansion module for increasing the number of available contacts Approvals PZE X4.1P with universal power supply Unit features Positive-guided relay outputs: 4 safety contacts (N/O),
More informationE-STOP relay, safety gate monitor
Safety relay for monitoring E-STOP pushbuttons, safety gates and light barriers. Approvals Unit features Positive-guided relay outputs: 2 safety contacts (N/O), instantaneous 1 semiconductor output Connection
More informationE-STOP relays, safety gate monitors
Unit features Safety features Gertebild ][Bildunterschrift Safety relay for monitoring E-STOP pushbuttons and safety gates. Approvals Gertemerkmale Positive-guided relay outputs: 2 safety contacts (N/O),
More informationE-STOP relays, safety gate monitors
Gertebild ][Bildunterschrift Safety relay for monitoring E-STOP pushbuttons and safety gates. Unit features Gertemerkmale Positive-guided relay outputs: 3 safety contacts (N/O), instantaneous Connection
More informationE-STOP relays, safety gate monitors
Unit features Gertemerkmale Positive-guided relay outputs: 2 safety contacts (N/O), instantaneous Connection options for: E-STOP pushbutton Safety gate limit switch Reset button Light barriers LED indicator
More informationPositive-guided relay outputs: 3 safety contacts (N/O), instantaneous. 1 auxiliary contact (N/C), instantaneous
Unit features Safety features Gertebild ][Bildunterschrift_nur_Not-Halt Safety relay for monitoring E-STOP pushbuttons Approvals Gertemerkmale Positive-guided relay outputs: 3 safety contacts (N/O), instantaneous
More informationE-STOP relays, safety gate monitors
Unit features Safety features Gertebild ][Bildunterschrift_nur_Not-Halt Safety relay for monitoring E-STOP pushbuttons Approvals Gertemerkmale Positive-guided relay outputs: 3 safety contacts (N/O), instantaneous
More informationE-STOP relays, safety gate monitors
Unit features Safety features Gertebild ][Bildunterschrift_NOT_Sch.tuer_Licht Safety relay for monitoring E-STOP pushbuttons, safety gates and light beam devices Gertemerkmale Positive-guided relay outputs:
More informationSafe monitoring relays
monitor for safe standstill monitoring Approvals Block diagram Unit features Positive-guided relay outputs: 2 safety contacts (N/O), instantaneous 1 auxiliary contact (N/C), instantaneous LED indicator
More informationPositive-guided relay outputs: 3 safety contacts (N/O), instantaneous. 1 auxiliary contact (N/C), instantaneous
Two-hand control unit for press controllers and safety circuits Approvals Unit features Positive-guided relay outputs: 3 safety contacts (N/O), instantaneous 1 auxiliary contact (N/C), instantaneous 1
More informationE-STOP relay, safety gate monitor
Unit features Safety features Gertebild ][Bildunterschrift Safety relay for monitoring E-STOP pushbuttons and safety gates. Approvals Gertemerkmale Positive-guided relay outputs: 7 safety contacts (N/O),
More informationE-STOP relays, safety gate monitors
Unit features Safety gates Gertebild ][Bildunterschrift_NOT_Sch.tuer_Licht Safety relay for monitoring E-STOP pushbuttons, safety gates and light beam devices Approvals Gertemerkmale Positive-guided relay
More informationTwo-hand control unit
Gertebild ][Bildunterschrift_Zweihand Two-hand control unit for press controllers and safety circuits Approvals Unit features Gertemerkmale Positive-guided relay outputs: 3 safety contacts (N/O), instantaneous
More informationE-STOP relays, safety gate monitors
Gertebild ][Bildunterschrift Safety relay for monitoring E-STOP pushbuttons and safety gates. Approvals Unit features Gertemerkmale Positive-guided relay outputs: 2 safety contacts (N/O), instantaneous
More informationE-STOP relays, safety gate monitors
Unit features Safety features Gertebild ][Bildunterschrift_nur_Not-Halt Safety relay for monitoring E-STOP pushbuttons Approvals Gertemerkmale Positive-guided relay outputs: 3 safety contacts (N/O), instantaneous
More informationSafety relays PNOZsigma
Safety relays PNOZsigma Configuration guide, safety relays PNOZsigma Technical catalogue 3.2 November 2008 edition Why does Pilz offer more? Because the integrality of our business activities is what sets
More informationSafe timer relay/contact expansion modules
Contact expander module for increasing the number of available contacts, Pulse-on timer relay for step-by-step control of movement sequences, Delay-on energisation timer for unlocking an interlock with
More informationE-STOP relays, safety gate monitors
Unit features Safety features Gertebild ][Bildunterschrift Safety relay for monitoring E-STOP pushbuttons and safety gates. Approvals Gertemerkmale Positive-guided relay outputs: 3 safety contacts (N/O),
More informationSafe timer relay/contact expansion modules
Gertebild Bildunterschrift Contact expander module for increasing the number of available contacts, Pulse-on timer relay for step-by-step control of movement sequences, Delay-on energisation timer for
More informationE-STOP relays, safety gate monitors
Unit features Safety features Gertebild ][Bildunterschrift_NOT_Sch.tuer_Licht Safety relay for monitoring E-STOP pushbuttons, safety gates and light beam devices Approvals Gertemerkmale Positive-guided
More informationE-STOP relays, safety gate monitors
Gertebild ][Bildunterschrift Safety relay for monitoring E-STOP pushbuttons and safety gates. Approvals Unit features Gertemerkmale Relay outputs: 2 safety contacts (N/O), instantaneous 1 semiconductor
More informationE-STOP relays, safety gate monitors
Unit features Safety features Gertebild ][Bildunterschrift_NOT_Sch.tuer_Licht Safety relay for monitoring E-STOP pushbuttons, safety gates and light beam devices Gertemerkmale Positive-guided relay outputs:
More informationE-STOP relays, safety gate monitors
Unit features Safety features Gertebild ][Bildunterschrift Safety relay for monitoring E-STOP pushbuttons and safety gates. Approvals Kein Gerätebild vorhanden Gertemerkmale Positive-guided relay outputs:
More informationTwo-hand control unit
Unit features Safety features Gertebild Bildunterschrift_gertespezifisch Two-hand control device for safety circuits Approvals Gertemerkmale Positive-guided relay outputs: 2 safety contacts (N/O), instantaneous
More informationTwo-hand control unit
Unit features Safety features Gertebild ][Bildunterschrift_Zweihand Two-hand control unit for press controllers and safety circuits Approvals Gertemerkmale Positive-guided relay outputs: 3 safety contacts
More informationSafe monitoring relays
Unit features Unit description Gertebild ][Bildunterschrift_Stillstandswchter Standstill monitor for safe standstill monitoring Approvals Zulassungen Gertemerkmale Positive-guided relay outputs: 2 safety
More informationPositive-guided relay outputs: 3 safety contacts (N/O), instantaneous
Gertebild ][Bildunterschrift Kontakterweiterungen Contact for increasing the number of available contacts Approvals Unit features Gertemerkmale Positive-guided relay outputs: 3 safety contacts (N/O), instantaneous
More informationPositive-guided relay outputs: 3 safety contacts (N/O), instantaneous. 1 auxiliary contact (N/C), instantaneous
Gertebild Bildunterschrift Two-hand control device for safety circuits Approvals Zulassungen Unit features Gertemerkmale Positive-guided relay outputs: 3 safety contacts (N/O), instantaneous 1 auxiliary
More informationPNOZ s1. Safety relays. Operating Manual EN-07
Safety relays Operating Manual- Preface This document is the original document. All rights to this documentation are reserved by Pilz GmbH & Co. KG. Copies may be made for internal purposes. Suggestions
More informationContact expander modules
Gertebild ][Bildunterschrift Kontakterweiterungen Contact expansion module for increasing the number of available contacts Approvals Zulassungen Unit features Gertemerkmale Positive-guided relay outputs:
More informationFaults on the system Proximity switch connection technology:
Speed monitor for connection to a base unit from the PNOZmulti modular safety system Approvals Unit features Monitoring of 2 independent axes Connection of 2 incremental encoders or 4 proximity switches
More informationPNOZ s2. Safety relays. Operating Manual EN-07
Safety relays Operating Manual- Preface This document is the original document. All rights to this documentation are reserved by Pilz GmbH & Co. KG. Copies may be made for internal purposes. Suggestions
More informationElectronic monitoring relays PMDsrange
Unit features Altdaten CMT For DC and AC supplies Normally energised mode Fault latching or automatic reset Normal/test mode External reset button can be connected Description The insulation monitoring
More informationPNOZ s9. Safety relays. Operating Manual EN-08
Safety relays Operating Manual- Preface This document is the original document. All rights to this documentation are reserved by Pilz GmbH & Co. KG. Copies may be made for internal purposes. Suggestions
More informationCan be configured in the PNOZmulti Configurator Semiconductor outputs: or 4 safety outputs in accordance with EN 954-1, Cat. 3
Products Expansion Gertebild mo1p modules PNOZmulti Verwendung/Bildunterschrift_multi_Modul Expansion module for connection to a base unit from the configurable control system PNOZmulti Approvals Unit
More informationSpeed Monitor. Up to PL e of EN ISO PNOZ s30. Unit features
Gertebild ][Bildunterschrift_Drehzahlwchter Speed monitor for safe monitoring of standstill, speed, position, speed range and direction of rotation. Approvals SÜDDEUTSCHLAND Pending Pending Unit features
More information20 inputs for connecting, for example:
Products Base Gertebild units m1p (ETH) Verwendung/Bildunterschrift_multi_Basis Base unit from the configurable control system PNOZmulti Approvals Zulassungen PNOZ m1p Unit features Gertemerkmale_multi_Basis
More informationDatasheet - SRB 402EM-24V
Print - Create PDF - Create EXCEL file 20.04.2011-18:31:35h Datasheet - SRB 402EM-24V Output expanders / SRB 402EM Expander module for contact expansion 4 safety contacts, STOP 0 2 Signalling outputs (Minor
More informationProducts. Base units PNOZmulti Base units PNOZmulti PNOZ m0p (ETH) PNOZ m1p (ETH) PNOZ m2p (ETH) PNOZ m3p (ETH) 2.
Contents Page PNOZ m0p (ETH) -2 PNOZ m1p (ETH) -16 PNOZ m2p (ETH) -31 PNOZ m3p (ETH) -45 2012-02 -1 PNOZ m0p (ETH) Unit features Unit description Products Base Gertebild units m0p (ETH) Verwendung/Bildunterschrift_multi_Basis
More informationPNOZ X2.1. } Safety relays. Operating Manual EN-05
} Safety relays Operating Manual Preface This document is a translation of the original document. All rights to this documentation are reserved by Pilz GmbH & Co. KG. Copies may be made for internal purposes.
More informationPNOZ X1. } Safety relays. Operating Manual EN-08
} Safety relays Operating Manual Preface This document is a translation of the original document. All rights to this documentation are reserved by Pilz GmbH & Co. KG. Copies may be made for internal purposes.
More informationDatasheet - SRB 301LC/B-24V
27.01.2016-00:27:16h Datasheet - SRB 301LC/B-24V Guard door monitors and Safety control modules for Emergency Stop applications / General Purpose safety controllers (Series PROTECT SRB) / SRB 301LC/B Fit
More informationVEO. V2ZS V AC/DC Art.Nr.: V2ZS20P V AC/DC Art.Nr.: TECHNICAL DATA
4 time ranges 4 transition times Supply voltage 12-240V AC/DC 2 normally open contacts Width 22,5 mm Control elements Fine adjustment star contactor Setting of time range star contactor Transit time Status
More informationBNS SERIES - COMPATIBLE SERIES AES SAFETY CONTROLLERS SELECTION CHART AVAILABLE STANDARD MODELS
BNS SERIES - COMPATIBLE SERIES AES SAFETY CONTROLLERS SELECTION CHART AVAILABLE STANDARD MODELS Safety Controller Suitable for use with Coded-Magnet Sensor Part Numbers below BNS250... BNS33... BNS303...
More informationDatasheet SRB301ST 24V (V.2)
26.10.2016 05:03:31h Datasheet SRB301ST 24V (V.2) Guard door monitors and Safety control modules for Emergency Stop applications / General Purpose safety controllers (Series PROTECT SRB) / SRB301ST Suitable
More informationTechnical data. Housing Polyamide housing PA 66, self-extinguishing V0 acc. to UL 94. Supply Rated supply voltage (U n
Safety module CS AT 0 Module for emergency stops, end position monitoring for movable guards with delayed contacts at the opening of the input channels, semiconductor outputs (e.g. light barriers and magnetic
More informationRE17LAMW on-delay timing relay - 1 s..100 h V AC/ DC - solid state output
Characteristics on-delay timing relay - 1 s..100 h - 24..240 V AC/ DC - solid state output Main Range of product Product or component type Discrete output type Width Component name Time delay type Time
More informationControl elements. Fine adjustment. Status indication. 24 V DC typ. 0,25 W / 0,25 VA. 24 V DC typ. 0,03 W / 0,09 VA. 0,15 3 s. 0,5 10 h.
On-Delay 10 time ranges Supply voltage 24-240V AC/DC 1 change-over contact Width 22,5mm Control elements Fine adjustment Setting of time range Status indication LED U/t: Supply voltage LED R: Relay status
More informationDatasheet - SLB 200-C04-1R
14.02.2013-17:06:30h Datasheet - SLB 200-C04-1R Safety light barriers / Safety monitoring modules to monitor safety light barriers / SLB 200-C Up to 2 light barrier pairs SLB 200 can be connected 1 safety
More informationRE17LCBM off-delay timing relay - control - 1 s..100 h V - solid state output
Characteristics off-delay timing relay - control - 1 s..100 h - 24..240 V - solid state output Main Range of product Product or component type Discrete output type Width Component name Time delay type
More informationSECTION 16 LED DIAGNOSTIC FEATURES: EXPANSION UNITS: SCR-31P-i. SCR-73-i. SEU-31-i. SCR-31-42TD-i. SEU-31TD-i
SECTION 16 VIPER Safety Relays Type: SCR-i (with added diagnostics) SAFETY RELAY FUNCTION: IDEM s VIPER SCR-i range of Safety Relays have been designed in accordance with EN60204-1 for safety circuits
More informationDold BH5928 Series 2-Channel Emergency Stop and Safety Gates with Delay
Dold Series 2-Channel Emergency Stop and Safety Gates with Delay -92-61-24-1 Part umber Price Marking Type Voltage Outputs Time Delay -92-61-24-1 2-channel E-STOP / GATE 24 VDC 3.O. time delay positive
More informationRM35LM33MW liquid level control relay RM35-L V AC/DC
Characteristics liquid level control relay RM35-L - 24..240 V AC/DC Complementary reset time maximum switching voltage Main range of product product or component type relay type relay name relay monitored
More informationPHOENIX CONTACT Features
Electronic monitoring relay for temperature monitoring Data sheet 107385_en_00 1 Description PHOENIX CONTACT - 2016-05-10 Features Safety and system availability requirements are constantly on the increase
More informationTwo-hand relay modules SRB 201ZH 44 Schmersal Industrial switching systems
SR 2ZH A 23 3 3 X S2 S A. K K2 PROTECT SR 2ZH Dimensions Two-hand module to DIN EN 574 (997) type III C Plug-in terminals 2 safety enabling outputs feedback output with NC function (floating contact) Electronic
More informationSafety Switching Devices SNO 4003K. Basic device for Emergency-Stop and Safety Gate Applications PI E
EN 60204-1 Stop category 0 EN 954-1 Safety category 4 Basic device to EN 60204-1 and EN 954-1 single E-stop monitoring. Manual or automatic start Application up to safety category 2 and stop category 0
More informationSafety Technique. SAFEMASTER C Multifunction Safety Module BH 5910
Safety Technique SAFEMASTER C Multifunction Safety Module BH 59 47 Block Diagram A+ A S S S4 S S S S4 S S S S4 S S4 S4 S44 S4 PTC Galvanic separation Monitoring logic Monitoring logic Galvanic separation
More informationVEO. V2ZR V AC/DC Art.Nr.: V2ZR10P V AC/DC Art.Nr.: TECHNICAL DATA
Off-Delay 10 time ranges Supply voltage 24-240V AC/DC 1 change-over contact Width 22,5 mm Control elements Fine adjustment Setting of time range Status indication LED U/t: Supply voltage LED R: Relay status
More informationTechnical data. Dimensions: see page 116. ): 4 kv Rated insulation voltage (U i Over-voltage category: Power supply. Rated operating voltage (Un):
Safety module CS AR-91, according to EN 81 Safety modules for the lift automatic floor levelling operation according to EN 81 Main functions For safety applications up to SIL 3 / PL e Choice between automatic
More informationQUINT-PS/1AC/24DC/10. Extract from the online catalog. Order No.:
Extract from the online catalog QUINT-PS/1AC/24DC/10 Order No.: 2866763 DIN rail power supply unit 24 V DC/10 A, primary-switched mode, 1- phase. The SFB technology (Selective Fusebreaking Technology)
More informationRM35UB3. Product data sheet Characteristics. voltage control relay RM35-U - range V AC. Main. Complementary
Characteristics voltage control relay RM35-U - range 194..528 V AC Main Range of product Product or component type Relay type Product specific application Relay name Relay monitored parameters Time delay
More informationVEO. V2UF230V10 Art.Nr.: TECHNICAL DATA
Continous voltage monitoring Mains fluctuation detection Detects voltage drop / short interruptions of at least 10ms Prevents undefined states in switching and control systems Generates reset pulse after
More informationRE22R2QGMR Star-Delta Timing Relay s 300h V AC/DC - 2C/O
Characteristics Star-Delta Timing Relay - 0.05s 300h - 24 240V AC/DC - 2C/O Main Range of product Product or component type Discrete output type Device short name Nominal output current Complementary Contacts
More informationVEO. V2PF480Y/277VSY01 Art.Nr.: V2PF480Y/277VSY01P Art.Nr.: TECHNICAL DATA
Monitoring of phase sequence and phase loss Monitoring of asymmetry Supply voltage 208-480 V AC Supply circuit = measuring circuit 1 change-over contact Width 22,5 mm Control elements Asymmetry Status
More informationRM17UB3. Product data sheet Characteristics. voltage control relay RM17-U - range V AC. Main. Complementary
Characteristics voltage control relay RM17-U - range 183..528 V AC Main Range of product Product or component type Relay type Product specific application Relay name Relay monitored parameters Time delay
More informationRM22TG. Product data sheet Characteristics. three-phase control relay Vac, 2 C/O. Main. Complementary. Network number of phases
Characteristics three-phase control relay 183 528Vac, 2 C/O Main Range of product Product or component type Relay type Network number of phases Relay name Relay monitored parameters Time delay type Switching
More informationTechnical data. Safety parameters: see page 333. DC maximum residual ripple: 10% Supply voltage tolerance: DC consumption: Control circuit
Safety module CS DM-01 Technical data Housing PA 6.6 polyamide housing, self-extinguishing, V0 acc. to UL 94 Protection degree IP40 (housing), IP20 (terminal strip) Dimensions see page 283, design A Two-hand
More informationQUINT-PS/ 1AC/24DC/ 5
Extract from the online catalog QUINT-PS/ 1AC/24DC/ 5 Order No.: 2866750 DIN rail power supply unit 24 V DC/5 A, primary switched-mode, 1- phase. The SFB technology (Selective Fuse Breaking Technology)
More informationArticle No. 6GK59230PS003AA2 6GK59240PS001AA2 Product Name. Power Supply SCALANCE PS924 PoE Input: 120/230V AC; Output: 54V/ 1.
Product Name Type of power supply Electrical data Input Waveform of the input Supply Power Supply SCALANCE PS924 PoE Input: 120/230V AC; Output: 54V/ 1.6A DC; NEC Class 2 single-phase AC Power Supply SCALANCE
More informationSafety Relay F 121 Emergency-Stop Relay, Safety Gate Monitor
Safety Relay F 121 Emergency-Stop Relay, Safety Gate Monitor Features M Safety-category 4 acc. to DIN EN954-1 M Stop-category 0 M Crossfault monitoring M Monitored start (On-switch) or automatic start
More informationZelio Control-modular measurement and control relays 1
Presentation, description 1 106439 RM35 TM111MW Presentation Motor temperature measurement and 50MW and RM35 TM250MW monitor the following, on 3-phase supplies: correct sequencing of phases L1, L2 and
More informationRE17LAMW on-delay timing relay - 1 s..100 h V AC/DC - solid state output
Characteristics on-delay timing relay - 1 s..100 h - 24..240 V AC/DC - solid state output Complementary Control type Voltage range Main Range of product Product or component type Discrete output type Width
More informationRM22LA32MR Level control relay RM22-L V AC/DC - 2 C/O
Product datasheet Characteristics RM22LA32MR Level control relay RM22-L - 24..240 V AC/DC - 2 C/O Main Range of product Product or component type Relay type Relay name Relay monitored parameters Time delay
More informationRM35LM33MW liquid level control relay RM35-L V AC/DC
Characteristics liquid level control relay RM35-L - 24..240 V AC/DC Complementary Reset time Maximum switching voltage [Un] rated nominal voltage Supply voltage limits Operating voltage tolerance Power
More informationPHOENIX CONTACT - 07/2006
Buffer module with maintenance-free capacitor-based power storage device INTERFACE Data sheet 102035_03_en PHOENIX CONTACT - 07/2006 Description Short-term mains interruptions are bridged by QUINT BUFFER,
More informationRE22R2AMR On-delay Timing Relay s 300h V AC/DC - 2C/O
Characteristics On-delay Timing Relay - 0.05s 300h - 24 240V AC/DC - 2C/O Main Range of product Product or component type Discrete output type Device short name Nominal output current Complementary Contacts
More informationRE22R2CMR Off-delay Timing Relay s 300h V AC/DC - 2C/O
Characteristics Off-delay Timing Relay - 0.05s 300h - 24 240V AC/DC - 2C/O Main Range of product Product or component type Discrete output type Device short name Nominal output current Complementary Contacts
More informationRE7YA12BU time delay relay for star-delta starter s - 24 V AC DC - 2OC
Characteristics time delay relay for star-delta starter - 0.05..1 s - 24 V AC DC - 2OC Main Range of product Product or component type Contacts type and composition Component name Time delay type Time
More informationMINI-PS AC/10-15DC/8
Primary-Switched Power Supply, Narrow Design Data Sheet 08/2004 MINI POWER provides: An extra narrow design, with widths of 22.5 mm, 45 mm, and 67.5 mm (0.886, 1.772, and 2.657 in.) Global use due to a
More informationFor full product information, visit Use the SpeedSpec code or scan the QR Code for quick access to the specific web page.
R Safety Monitoring Relays For full product information, visit www.sti.com. Use the SpeedSpec code or scan the QR Code for quick access to the specific web page. Dual-Channel Safety Monitoring Relay Power
More informationQUINT-PS AC/24DC/10
Extract from the online catalog QUINT-PS-100-240AC/24DC/10 Order No.: 2938604 DIN rail power supply unit 24 V DC/10 A, primary switched-mode, 1- phase Commercial data EAN 4017918890537 Pack 1 Pcs. Customs
More informationPower Supply, Primary Switch Mode, Narrow Design MINI-PS AC/24DC/1
Power Supply, Primary Switch Mode, arrow Design -PS-100-240AC/24/1 POWER provides: Extra narrow widths of 22.5, 45, and 67.5 mm (0.886, 1.772, and 2.657 in.) Global use due to a wide range input A high
More informationQUINT-PS/ 1AC/24DC/20/CO
Extract from the online catalog QUINT-PS/ 1AC/24DC/20/CO Order No.: 2320898 DIN rail power supply unit 24 V DC/20 A/CO, dip-coated circuit board, primary-switched, 1-phase. For the first time, SFB (selective
More informationSAFETY RELAY YRB-4EML-31S MAIN FEATURES
SAFETY RELAY TYPE 4 SAFETY PROTECTION DEVICE FOR SAFETY LIGHT CURTAINS/BARRIERS MAIN FEATURES For safety light curtains and access control barriers, emergency stop, door switch Safety Integrity Level (SIL)
More informationOperating instructions Safety-monitoring module SSW 301HV. 1. About this document. Content
7 Disassembly and disposal 7.1 Disassembly....5 7.2 Disposal...5 8 Appendix 8.1 Wiring example...5 E Operating instructions.............pages 1 to 6 Original 9 EU Declaration of conformity x.000 / 11.2017
More informationUniversal Power Supplies
, Features Universal input: 90 264 VAC or 120 30 VDC Active power factor correction (>0.95) High efficiency up to 93% Load share function for up to 3 units in parallel Adjustable output voltage EMI/EMC
More informationSafety relay emergency stop/protective door, 24VDC/AC, 4 enabling paths
DATASHEET - ESR5-NO-41-24VAC-DC Safety relay emergency stop/protective door, 24VDC/AC, 4 enabling paths Part no. ESR5-NO-41-24VAC-DC Catalog No. 118701 EL-Nummer (Norway) 0004133317 Delivery program Product
More informationSNO 4003 K plus. Areas of application for the unit. Connection circuit diagrams. Intended use. Competent persons. Equipment and functional description
SNO 4003 K plus Safety relay for emergency stop and guard door applications SILCL2 in accordance with EN 62061 PL d, Category 3 in accordance with EN ISO 13849-1 Stop category 0 in accordance with DIN
More informationRE7YA12BU. Main. Contacts type and composition Component name Time delay type. 24 V AC/DC at 50/60 Hz V AC/DCat 50/60 Hz
Product datasheet Characteristics RE7YA12BU Main Range of product Product or component type Contacts type and composition Component name Time delay type Time delay range Zelio Time Industrial timing relay
More informationRE22R2KMR Off-delay Timing Relay s 10min V AC/DC - 2C/O
Characteristics Off-delay Timing Relay - 0.05s 10min - 24 240V AC/DC - 2C/O Main Range of product Product or component type Discrete output type Device short name Nominal output current Complementary Contacts
More information