National Fire Protection Association. 1 Batterymarch Park, Quincy, MA Phone: Fax:

Size: px
Start display at page:

Download "National Fire Protection Association. 1 Batterymarch Park, Quincy, MA Phone: Fax:"

Transcription

1 National Fire Protection Association 1 Batterymarch Park, Quincy, MA Phone: Fax: M E M O R A N D U M TO: Members of the NEC-Code Making Panel 3 FROM: Jean O Connor DATE: March 9, 2012 SUBJECT: NFPA 70 ROP Final Ballot Results (A2013 Cycle) The March 8, 2012 date for circulation changes and final receipt of letter ballots has passed. In accordance with the NFPA Regulations Governing Committee Projects, the attached report contains the number of members eligible to vote, the names of principals whose ballots were not returned, and the reasons for negative, affirmative and abstaining comments. Attachment: Final Ballot Results Report

2 1 3-1 Eligible To Vote:14 Affirmative: 14 : 0 Abstain: 0 Not Returned: 0 Entire Document (Log # 1170b ) 3-2 Eligible To Vote:14 Affirmative: 14 : 0 Abstain: 0 Not Returned: 0 Entire Document (Log # 921b ) 3-3 Eligible To Vote:14 Affirmative: 14 : 0 Abstain: 0 Not Returned: Burial Cover (New), 300.5, , , and (Log # 1342 ) 3-4 Eligible To Vote:14 Affirmative: 14 : 0 Abstain: 0 Not Returned: Fire Alarm Circuit (New) and (Log # 2773 ) 3-5 Eligible To Vote:14 Affirmative: 14 : 0 Abstain: 0 Not Returned: Plenum, Informational Note (New) (Log # 3040 ) 3-6 Eligible To Vote:14 Affirmative: 14 : 0 Abstain: 0 Not Returned: Power-Limited Fire Alarm Circuit (PLFA) (New) and (Log # 2775 ) 3-7 Eligible To Vote:14 Affirmative: 14 : 0 Abstain: 0 Not Returned: Type ITC Instrumentation Tray Cable (New) and (Log # 2772 ) 3-8 Eligible To Vote:14 Affirmative: 14 : 0 Abstain: 0 Not Returned: 0 300, Title (Log # 159 ) 3-9 Eligible To Vote:14 Affirmative: 14 : 0 Abstain: 0 Not Returned: (Log # 160 ) Stene, S. The actual text with new words underlined should read as follows: This article covers the general requirements for wiring methods and materials for all wiring installations unless modified by other articles in Chapter Eligible To Vote:14 Affirmative: 13 : 1 Abstain: 0 Not Returned: (Log # 962 ) Burlison, S. It is recognized that increasing voltage from 600 volts to 1000 volts may be applicable to specific installations. However, adequate technical substantiation has not been provided to support the change in this Article Eligible To Vote:14 Affirmative: 14 : 0 Abstain: 0 Not Returned: (Log # 231 )

3 Eligible To Vote:14 Affirmative: 13 : 1 Abstain: 0 Not Returned: (Log # 963 ) Burlison, S. It is recognized that increasing voltage from 600 volts to 1000 volts may be applicable to specific installations. However, adequate technical substantiation has not been provided to support the change in this Article Eligible To Vote:14 Affirmative: 13 : 1 Abstain: 0 Not Returned: (B)300.5(l), and (A) (Log # 3293b ) Mills, T. The Panel should have accepted the proposal and deferred implementation to Panel 5. The IEEE has reviewed all the statements on this subject by various panels. The following represents the IEEE position on the issue of equipment grounding conductor or equipment bonding conductor. Similar proposals have been presented in the past and have been rejected. Reasons given often relate to cost, significant changes in documentation required, or the fact that knowledgeable people understand the use of this conductor. There is no justification for retaining an incorrect and potentially hazardous electrical installation just because this definition has been used in the NEC for many years. Costs associated with documentation changes should never be an argument where safety is concerned. Further, not all electrical practitioners are knowledgeable in the main intent of this conductor. The intent of the proposed change is to provide a descriptive name to a construction element that has resulted in much misunderstanding with possible hazardous operating conditions in electrical installations. The use of the term grounding implies that grounding is its principal function. Although grounding may be desirable, providing an effective fault current path (i.e. bonding) is and should be the emphasis. There are many who assert that a connection to a water pipe meets the needs of equipment grounding, however, this connection does not perform the necessary effective fault current path back to the source. There are two conductors described in the Code performing the same function but named differently. The bonding jumper is a short conductor that insures the electrical integrity of enclosure to raceway. The longer conductor, intended to provide a low impedance path to the source, is presently named a grounding conductor instead of its real function as a bonding conductor. Technically, the definition in Article 100 may be adequate for Panel members and those that teach. Practically, the definition is confusing if the terminology does not fit the function performed. The equipment bonding conductor, as it should be called, provides its primary function whether or not it is grounded. For a grounded system, it is grounded because the system is grounded. For an ungrounded system, it is grounded to limit the voltage due to a lightning strike or contact with a higher voltage system. Changing the name will assist in educating users of the Code as to why they are installing a conductor that needs to be continuous all of the way back to the source Eligible To Vote:14 Affirmative: 14 : 0 Abstain: 0 Not Returned: (C)(2)(d) (Log # 414 ) 3-15 Eligible To Vote:14 Affirmative: 14 : 0 Abstain: 0 Not Returned: (C)(2)(d) (Log # 666 ) 3-15a Eligible To Vote:14 Affirmative: 14 : 0 Abstain: 0 Not Returned: (C)(2)(d) (Log # CP300 ) 3-16 Eligible To Vote:14 Affirmative: 14 : 0 Abstain: 0 Not Returned: (Log # 578 )

4 Eligible To Vote:14 Affirmative: 14 : 0 Abstain: 0 Not Returned: , 300.7, , , , (Log # 1806 ) 3-18 Eligible To Vote:14 Affirmative: 14 : 0 Abstain: 0 Not Returned: , and (A)(2) (Log # 2035 ) 3-19 Eligible To Vote:14 Affirmative: 14 : 0 Abstain: 0 Not Returned: , 300.7, , , , and (Log # 2458 ) 3-20 Eligible To Vote:14 Affirmative: 14 : 0 Abstain: 0 Not Returned: (Log # 2494 ) 3-21 Eligible To Vote:14 Affirmative: 14 : 0 Abstain: 0 Not Returned: (A), 300.5, 300.7, , , and (Log # 2358 ) 3-22 Eligible To Vote:14 Affirmative: 14 : 0 Abstain: 0 Not Returned: (A)300.5, 300.7, , , and (Log # 2380 ) 3-23 Eligible To Vote:14 Affirmative: 14 : 0 Abstain: 0 Not Returned: (A)(1) (Log # 2376 ) 3-24 Eligible To Vote:14 Affirmative: 14 : 0 Abstain: 0 Not Returned: (A)(1) (Log # 3335 ) 3-25 Eligible To Vote:14 Affirmative: 14 : 0 Abstain: 0 Not Returned: (A)(1) Exception No. 1 (Log # 238 ) 3-26 Eligible To Vote:14 Affirmative: 14 : 0 Abstain: 0 Not Returned: (A)(2) Exception No. 1 (Log # 239 ) 3-27 Eligible To Vote:14 Affirmative: 14 : 0 Abstain: 0 Not Returned: (B), and (Log # 1676 ) 3-28 Eligible To Vote:14 Affirmative: 14 : 0 Abstain: 0 Not Returned: (B) and (Log # 1849 )

5 Eligible To Vote:14 Affirmative: 14 : 0 Abstain: 0 Not Returned: (D) (Log # 2308 ) 3-30 Eligible To Vote:14 Affirmative: 14 : 0 Abstain: 0 Not Returned: (D) (Log # 3334 ) 3-31 Eligible To Vote:14 Affirmative: 14 : 0 Abstain: 0 Not Returned: (D) (Log # 3336 ) 3-32 Eligible To Vote:14 Affirmative: 14 : 0 Abstain: 0 Not Returned: (D) Exception No. 3 (Log # 2307 ) 3-33 Eligible To Vote:14 Affirmative: 14 : 0 Abstain: 0 Not Returned: (E) (Log # 2515 ) 3-34 Eligible To Vote:14 Affirmative: 14 : 0 Abstain: 0 Not Returned: (G) (Log # 579 ) 3-35 Eligible To Vote:14 Affirmative: 14 : 0 Abstain: 0 Not Returned: (I) (New) (Log # 806 ) 3-36 Eligible To Vote:14 Affirmative: 13 : 1 Abstain: 0 Not Returned: (Log # 964 ) Burlison, S. It is recognized that increasing voltage from 600 volts to 1000 volts may be applicable to specific installations. However, adequate technical substantiation has not been provided to support the change in this Article Eligible To Vote:14 Affirmative: 14 : 0 Abstain: 0 Not Returned: 0 Table (Log # 1957 ) Stene, S. Add a comma after the word "depth" and after the word "protected" in the first sentence Eligible To Vote:14 Affirmative: 14 : 0 Abstain: 0 Not Returned: 0 Table (Log # 2070 ) 3-39 Eligible To Vote:14 Affirmative: 14 : 0 Abstain: 0 Not Returned: 0 Table (Log # 2733 )

6 Eligible To Vote:14 Affirmative: 14 : 0 Abstain: 0 Not Returned: (B) (Log # 337 ) 3-41 Eligible To Vote:14 Affirmative: 14 : 0 Abstain: 0 Not Returned: (B) Exception (New) (Log # 240 ) 3-42 Eligible To Vote:14 Affirmative: 14 : 0 Abstain: 0 Not Returned: (C) (Log # 1721 ) 3-43 Eligible To Vote:14 Affirmative: 14 : 0 Abstain: 0 Not Returned: (D) (Log # 3078 ) 3-44 Eligible To Vote:14 Affirmative: 12 : 2 Abstain: 0 Not Returned: (D)(3) (Log # 2571 ) Casparro, P. This proposal should have been accepted. Feeder and branch circuit protection, although protected by overcurrent protection, causes a safety problem for the electrical worker. The available fault current at various facilities has been changing all the time with utilities upgrading transformers, new equipment being added to buildings such as computers, electronic ballasts and other office equipment. The utilities aren't necessarily notifying the customers of such changers. If the overcurrent protection isn't changed to match the change in the available fault current present at these facilities, we are putting workers in grave danger. The facilitation of the overcurrent device will be compromised if the change isn't made. Damage to any of the cables or conductors could be deadly to the worker. Whistler, W. Adding feeders and branch circuits to this section would provide a warning for the property owner who is digging on the load of the service. The overcurrent protection (OCP) will not always operate. The OCP will not operate if only one conductor is damaged, however, if a human should contact the damaged conductor they could be electrocuted without operation of the OCP Eligible To Vote:14 Affirmative: 14 : 0 Abstain: 0 Not Returned: (D)(3) (Log # 3079 ) 3-46 Eligible To Vote:14 Affirmative: 14 : 0 Abstain: 0 Not Returned: (I) (Log # 2572 ) 3-47 Eligible To Vote:14 Affirmative: 14 : 0 Abstain: 0 Not Returned: (I) Exception No. 1 (Log # 179 )

7 Eligible To Vote:14 Affirmative: 14 : 0 Abstain: 0 Not Returned: (J) (Log # 89 ) 3-49 Eligible To Vote:14 Affirmative: 14 : 0 Abstain: 0 Not Returned: (A) (Log # 2573 ) 3-50 Eligible To Vote:14 Affirmative: 14 : 0 Abstain: 0 Not Returned: (A) (Log # 2708 ) 3-51 Eligible To Vote:14 Affirmative: 14 : 0 Abstain: 0 Not Returned: (A), Informational Note (New) (Log # 1510 ) Easter, L. NEMA agrees with the Panel action but the revised wording should have included elbows and nipples so that the text would read: "Field-cut threads are those threads that are cut in conduit, elbows, or nipples anywhere other than at the factory where the product is listed. " This proposal was submitted to address proposals submitted during the 2011 cycle that concerned corrosion protection of threads on elbows and nipples. The text the Panel accepted only addresses conduit and not the products of primary concern. Stene, S. Delete the last sentence in the Panel Statement since it already appears as the first sentence Eligible To Vote:14 Affirmative: 14 : 0 Abstain: 0 Not Returned: (B) (Log # 241 ) 3-53 Eligible To Vote:14 Affirmative: 14 : 0 Abstain: 0 Not Returned: (E) (New) (Log # 2535 ) Stene, S. Delete the word "requirement" from the Panel Statement since it is redundant Eligible To Vote:14 Affirmative: 14 : 0 Abstain: 0 Not Returned: (Log # 603 ) 3-55 Eligible To Vote:14 Affirmative: 14 : 0 Abstain: 0 Not Returned: (Log # 1708 ) 3-56 Eligible To Vote:14 Affirmative: 14 : 0 Abstain: 0 Not Returned: Exception (Log # 43 ) 3-57 Eligible To Vote:14 Affirmative: 14 : 0 Abstain: 0 Not Returned: (A)(1) (Log # 391 )

8 Eligible To Vote:14 Affirmative: 14 : 0 Abstain: 0 Not Returned: (B) (Log # 2270 ) 3-59 Eligible To Vote:14 Affirmative: 14 : 0 Abstain: 0 Not Returned: (Log # 1289 ) Stene, S. The submitter did not provide any technical substantiation provided to warrant removing this section from the NEC Eligible To Vote:14 Affirmative: 14 : 0 Abstain: 0 Not Returned: (Log # 1295 ) 3-61 Eligible To Vote:14 Affirmative: 14 : 0 Abstain: 0 Not Returned: (Log # 1372 ) 3-62 Eligible To Vote:14 Affirmative: 14 : 0 Abstain: 0 Not Returned: (Log # 1384 ) 3-63 Eligible To Vote:14 Affirmative: 14 : 0 Abstain: 0 Not Returned: (Log # 145 ) 3-64 Eligible To Vote:14 Affirmative: 14 : 0 Abstain: 0 Not Returned: , Informational Note 1 (Log # 2170 ) 3-65 Eligible To Vote:14 Affirmative: 14 : 0 Abstain: 0 Not Returned: (B)(1) (Log # 348 ) 3-66 Eligible To Vote:14 Affirmative: 14 : 0 Abstain: 0 Not Returned: (C) (Log # 2302 ) 3-67 Eligible To Vote:14 Affirmative: 14 : 0 Abstain: 0 Not Returned: Exception No. 2 (Log # 518 ) 3-68 Eligible To Vote:14 Affirmative: 14 : 0 Abstain: 0 Not Returned: Exception No. 2 (Log # 3252 )

9 Eligible To Vote:14 Affirmative: 14 : 0 Abstain: 0 Not Returned: (Log # 1371 ) 3-70 Eligible To Vote:14 Affirmative: 14 : 0 Abstain: 0 Not Returned: (Log # 3413 ) 3-71 Eligible To Vote:14 Affirmative: 14 : 0 Abstain: 0 Not Returned: (E) (Log # 88 ) 3-72 Eligible To Vote:14 Affirmative: 14 : 0 Abstain: 0 Not Returned: , , and (A)(1) (Log # 1896 ) 3-73 Eligible To Vote:14 Affirmative: 14 : 0 Abstain: 0 Not Returned: (Log # 2758 ) 3-74 Eligible To Vote:14 Affirmative: 14 : 0 Abstain: 0 Not Returned: , (B), and (C) (Log # 2787 ) 3-75 Eligible To Vote:14 Affirmative: 14 : 0 Abstain: 0 Not Returned: , , and (C)(1) (Log # 2812 ) 3-76 Eligible To Vote:14 Affirmative: 14 : 0 Abstain: 0 Not Returned: , Informational Note (Log # 2759 ) Stene, S. In addition to the statement provided, NUCC already has cables or conductors installed by the manufacturer, auxiliary gutters are not raceways, and the additional references provided in the proposal are unnecessary Eligible To Vote:14 Affirmative: 14 : 0 Abstain: 0 Not Returned: , Informational Note (Log # 2822 ) 3-78 Eligible To Vote:14 Affirmative: 14 : 0 Abstain: 0 Not Returned: , Informational Note (Log # 2848 ) 3-79 Eligible To Vote:14 Affirmative: 14 : 0 Abstain: 0 Not Returned: (C) (New) (Log # 2677 ) Stene, S. The third sentence in the Panel Statement should be changed to read as follows: Requiring the wiring methods mounted on the roof to not be removable during roof replacement would be infeasible in many cases.

10 Eligible To Vote:14 Affirmative: 14 : 0 Abstain: 0 Not Returned: 0 Table (A) (Log # 2306 ) 3-81 Eligible To Vote:14 Affirmative: 14 : 0 Abstain: 0 Not Returned: (B) (Log # 1306 ) Clary, S. The panel's rejection of the proposed requirements without an overall nonmetallic covering for some products is based on present listing requirements for Type MI cable. This approach to code development seems to leave the door open for some products to be listed with an overall nonmetallic covering at some time in the future. The NEC should set the base requirement, causing testing laboratories to establishing test standards based on code requirements Eligible To Vote:14 Affirmative: 14 : 0 Abstain: 0 Not Returned: (B) (Log # 2148 ) 3-83 Eligible To Vote:14 Affirmative: 14 : 0 Abstain: 0 Not Returned: (B)(1) and (B)(2) (Log # 2662 ) 3-84 Eligible To Vote:14 Affirmative: 14 : 0 Abstain: 0 Not Returned: (C)(1) (Log # 1307 ) 3-85 Eligible To Vote:14 Affirmative: 14 : 0 Abstain: 0 Not Returned: (C)(1) (Log # 2351 ) 3-86 Eligible To Vote:14 Affirmative: 14 : 0 Abstain: 0 Not Returned: (C)(1) (Log # 2942 ) 3-87 Eligible To Vote:14 Affirmative: 14 : 0 Abstain: 0 Not Returned: (C)(3) (Log # 1512 ) 3-88 Eligible To Vote:14 Affirmative: 14 : 0 Abstain: 0 Not Returned: (New) (Log # 586 ) 3-89 Eligible To Vote:14 Affirmative: 13 : 1 Abstain: 0 Not Returned: 0 300, Part II (Log # 1029 )

11 10 Burlison, S. It is recognized that increasing voltage from 600 volts to 1000 volts may be applicable to specific installations. However, adequate technical substantiation has not been provided to support the change in this Article Eligible To Vote:14 Affirmative: 14 : 0 Abstain: 0 Not Returned: (Log # 1742 ) 3-91 Eligible To Vote:14 Affirmative: 14 : 0 Abstain: 0 Not Returned: (Log # 2274 ) 3-92 Eligible To Vote:14 Affirmative: 14 : 0 Abstain: 0 Not Returned: (New) (Log # 580 ) 3-93 Eligible To Vote:14 Affirmative: 14 : 0 Abstain: 0 Not Returned: (I) (New) (Log # 3220 ) 3-94 Eligible To Vote:14 Affirmative: 14 : 0 Abstain: 0 Not Returned: (New) (Log # 3080 ) 3-95 Eligible To Vote:14 Affirmative: 14 : 0 Abstain: 0 Not Returned: 0 Table (Log # 424 ) 3-96 Eligible To Vote:14 Affirmative: 14 : 0 Abstain: 0 Not Returned: (A)(3) (Log # 3164 ) 3-97 Eligible To Vote:14 Affirmative: 14 : 0 Abstain: 0 Not Returned: (D)(4) (Log # 44 ) 3-98 Eligible To Vote:14 Affirmative: 14 : 0 Abstain: 0 Not Returned: (F) (Log # 1702 ) 3-99 Eligible To Vote:14 Affirmative: 14 : 0 Abstain: 0 Not Returned: (G) (New) (Log # 1051 ) Eligible To Vote:14 Affirmative: 14 : 0 Abstain: 0 Not Returned: (C) (Log # 500 )

12 Eligible To Vote:14 Affirmative: 14 : 0 Abstain: 0 Not Returned: (D)(2) (Log # 333 ) Eligible To Vote:14 Affirmative: 14 : 0 Abstain: 0 Not Returned: (D)(2) (Log # 1511 ) Eligible To Vote:14 Affirmative: 14 : 0 Abstain: 0 Not Returned: (E) Exception (New) (Log # 2769 ) Eligible To Vote:14 Affirmative: 14 : 0 Abstain: 0 Not Returned: (I) (Log # 281 ) Eligible To Vote:14 Affirmative: 11 : 3 Abstain: 0 Not Returned: (J) (Log # 3365 ) Casparro, P. This proposal should have been accepted in principle. The panel statement conflicts with the existing requirement. There is no practical reason to permit temporary branch circuits or feeders in cable assemblies or flexible cords on the floor or ground. Extension cords are permitted to be on the floor or ground because they are GFCI protected. The proposed revision should be accepted in principle as follows: (J) Support of Branch Circuits and Feeders. Cable assemblies and flexible cords and cables shall be supported in place at intervals that ensure that they will be protected from physical damage. Support shall be in the form of staples, cable ties, straps, or similar type fittings installed so as not to cause damage. Cable assemblies and flexible cords and cables shall not be laid in the floor or the ground. Clary, S. The addition of an added requirement, Cable assemblies and flexible cords shall not be permitted to be laid on the floor or the ground, to 590.4(J) makes sense. Various trades can inadvertently damage cables and cords that lay on the ground. Electrical safety is important: A job site is often a wet location. A damaged cable or cord is a potential shock hazard.

13 12 Whistler, W. This proposal should be re-evaluated and perhaps changed to be accep in principle. In most cases unlike the extension cord on the job site the feeders and branch circuits that are being referenced are not protected by a ground fault circuit interrupter (GFCI) for personnel protection. Therefore they should not be afforded the same provisions for installation. The practice of allowing feeders and branch circuits in cable assemblies or flexible cords appears to be in conflict with current interpretation of OSHA regulations which are resulting in fines for employers. The proposed revision to 590.4(J) should be accepted in principle as follows: (J) Support of Branch Circuits and Feeders. Cable assemblies and flexible cords and cables shall be supported in place at intervals that ensure that they will be protected from physical damage. Support shall be in the form of staples, cable ties, straps, or similar type fittings installed so as not to cause damage. Cable assemblies and flexible cords and cables shall not be laid in the floor or the ground. Vegetation shall not be used for support of overhead spans of branch circuits or feeders. Exception: (No change). Burlison, S. The instances cited are all covered by the initial text in 590.4(J) and also 590.4(H) where it states that the flexible cords and cables are to be protected from physical damage. As for wet locations, 590 does not give permission for non-wet location wiring methods to be used "temporarily" in wet locations when they are elsewhere prohibited from use in wet locations. (I said that awkwardly but you get the idea.) The original Panel statement is correct; the existing text does not permit cables to be used in any manner that is not permitted in their respective Articles. (See 590.2(A). and (B).) Kahn, S. While I agree with the panel action, the recommended text to too broad. The submitter has identified a problem that should be considered and incorporated into this section. While extra hard use cords do provide a reasonable degree of protection from anticipated physical damage, cables such as NM cable and SE cable assemblies installed for branch circuits and feeders should be properly supported to reduce the damage and resulting unsafe conditions. The proposal should be adjusted to address and not prohibt normal use of extension cords for temporary installations. NECA recommends that a comment be submitted for the ROC meeting modifying the proposal to reflect the specific problem cited in the panel statement Eligible To Vote:14 Affirmative: 14 : 0 Abstain: 0 Not Returned: (A) (Log # 3343 ) Eligible To Vote:14 Affirmative: 14 : 0 Abstain: 0 Not Returned: (A), Informational Note (New) (Log # 2121 ) 3-107a Eligible To Vote:14 Affirmative: 13 : 1 Abstain: 0 Not Returned: (A)(1) (Log # 3522 )

14 13 Easter, L. NEMA is voting negative. The proposal should have been accepted. When Paragraph 590.6(A) in NFPA was revised for NFPA to separate the outlets between those not part of as well as those part of permanent wiring, the allowance for portable listed GFCI devices for both types of outlets was revised to only permit them only for permanent wired outlets. The allowance was deleted from outlets not part of permanent wiring, thereby permitting only GFCI receptacles or circuit breaker type GFCIs. Since only portable listed GFCI devices are required to have open neutral detection and power removal in such an occurrence, the safety protection provided by the 2008 version was potentially diminished in the 2011 version. The proposal returns the permitting of portable listed GFCI devices to outlets not part of permanent wirings as it was in NFPA , 509.6(A). The added wording is identical to that of the permanent wired outlet section 590.6(A)(2) of NFPA and as it was in NFPA (A). Since outlets not part of permanent wiring are more likely to have an open neutral condition than permanently wired outlets, it is NEMA's position that allowance of usage of portable listed GFCI devices should also be allowed for outlets not part of permanent wiring as it was in NFPA in order to restore the safety level that was provided by NFPA (a). OSHA responses to field questions concerning this topic have recommended use of portable listed GFCI devices to provide this open neutral protection. The re-wording does not prohibit the use of GFCI receptacles, it only adds the allowance of listed portable GFCI devices, as was allowed in the NFPA edition. Such an interpretation of the proposal could also be applied to Paragraph (A)(2) permanent wired outlets of NFPA If Paragraph 590.6(A)(1) of NFPA is revised to require only listed Class A GFCI devices providing open-neutral protection, either circuit breaker, receptacle or portable GFCI NRTL listed devices may be used and the NEMA concern will be resolved. Stene, S. Change the fourth sentence by deleting the word "as" to read as follows: These cord sets should not take the place of the other GFCI protection at the source, since that leaves the extension cord or cable unprotected Eligible To Vote:14 Affirmative: 14 : 0 Abstain: 0 Not Returned: (Log # 998 ) Burlison, S. It is recognized that increasing voltage from 600 volts to 1000 volts may be applicable to specific installations. However, adequate technical substantiation has not been provided to support the change in this Article Eligible To Vote:14 Affirmative: 14 : 0 Abstain: 0 Not Returned: (New) (Log # 106 ) Stene, S. Combine the last two sentences in the Panel Statement to read as follows: Therefore, a shock hazard would not be present and this new section is unnecessary Eligible To Vote:15 Affirmative: 15 : 0 Abstain: 0 Not Returned: (Log # 68 ) Eligible To Vote:15 Affirmative: 15 : 0 Abstain: 0 Not Returned: (Log # 69 )

15 Eligible To Vote:15 Affirmative: 15 : 0 Abstain: 0 Not Returned: (Log # 70 ) Eligible To Vote:15 Affirmative: 15 : 0 Abstain: 0 Not Returned: (Log # 71 ) Eligible To Vote:15 Affirmative: 15 : 0 Abstain: 0 Not Returned: (Log # 72 ) Eligible To Vote:15 Affirmative: 15 : 0 Abstain: 0 Not Returned: (Log # 73 ) Eligible To Vote:15 Affirmative: 15 : 0 Abstain: 0 Not Returned: 0 725, Part I (Log # 1697 ) Eligible To Vote:15 Affirmative: 15 : 0 Abstain: 0 Not Returned: and (Log # 3355 ) Eligible To Vote:15 Affirmative: 14 : 1 Abstain: 0 Not Returned: Cable Routing Assembly, , , , , (Log # 1625 ) Easter, L. NEMA is voting negative on the proposal because it includes requirements for a plenum rated cable routing assembly where there is no corresponding application for the product. While it is permitted as a substitute for the riser and lower rated Cable Routing assemblies, its use in plenums is not permitted by the NEC or by NFPA 90A that has jurisdiction over wiring in air handling plenum spaces. An Informational Note after the requirements for Riser cable routing assemblies would be appropriate in place of the proposed requirement. The Informational note would indicate that Cable routing assemblies that exhibit a maximum peak optical density of 0.5 or less, an average optical density of 0.15 or less, and a maximum flame spread distance of 1.52 m (5 ft) or less when tested in accordance with the plenum test in UL 2024 Signaling, Optical Fiber and Communications Raceways and Cable Routing Assemblies are considered suitable wherever cable routing assemblies that pass the requirements of the test for flame propagation (riser) in UL 2024 Signaling, Optical Fiber and Communications Raceways and Cable Routing Assemblies are required Eligible To Vote:15 Affirmative: 15 : 0 Abstain: 0 Not Returned: Class 2 Circuit (Log # 1278 ) Eligible To Vote:15 Affirmative: 15 : 0 Abstain: 0 Not Returned: Class 3 Circuit (Log # 1279 )

16 Eligible To Vote:15 Affirmative: 15 : 0 Abstain: 0 Not Returned: Non-Safety Control Equipment (New) (Log # 756 ) Eligible To Vote:15 Affirmative: 15 : 0 Abstain: 0 Not Returned: Safety Control Equipment (New) (Log # 755 ) 3-122a Eligible To Vote:15 Affirmative: 15 : 0 Abstain: 0 Not Returned: (K) and (L) (Log # CP301 ) Eligible To Vote:15 Affirmative: 15 : 0 Abstain: 0 Not Returned: (G) (Log # 2817 ) Eligible To Vote:15 Affirmative: 15 : 0 Abstain: 0 Not Returned: (New) (Log # 3485 ) Eligible To Vote:15 Affirmative: 15 : 0 Abstain: 0 Not Returned: (Log # 2943 ) Eligible To Vote:15 Affirmative: 15 : 0 Abstain: 0 Not Returned: (Log # 3140 ) Eligible To Vote:15 Affirmative: 15 : 0 Abstain: 0 Not Returned: (B) and (H) (Log # 1829 ) Eligible To Vote:15 Affirmative: 15 : 0 Abstain: 0 Not Returned: (B) and (H) (Log # 2054 ) Eligible To Vote:15 Affirmative: 15 : 0 Abstain: 0 Not Returned: (B) and (H) (Log # 2421 ) Eligible To Vote:15 Affirmative: 15 : 0 Abstain: 0 Not Returned: (B) and (H) (Log # 2447 ) Eligible To Vote:15 Affirmative: 15 : 0 Abstain: 0 Not Returned: (New) (Log # 3332 )

17 16 Stene, S. Surge protection devices are permitted to be installed, based on the requirements in Article 285, on most electrical systems but are not required to be installed. Whether to install a surge protection device is a design issue based on power surges and lightning in the area where the alarm is installed. Surges could be generated within the building where the alarm is installed. There are certainly areas around the country where lightning and power surges are more common than in other areas but not all burglar alarm systems should be required to have a surge protection device Eligible To Vote:15 Affirmative: 15 : 0 Abstain: 0 Not Returned: (B) (Log # 1014 ) Burlison, S. It is recognized that increasing voltage from 600 volts to 1000 volts may be applicable to specific installations. However, adequate technical substantiation has not been provided to support the change in this Article Eligible To Vote:15 Affirmative: 15 : 0 Abstain: 0 Not Returned: (Log # 2524 ) Eligible To Vote:15 Affirmative: 15 : 0 Abstain: 0 Not Returned: , Informational Note (New) (Log # 2523 ) Eligible To Vote:15 Affirmative: 15 : 0 Abstain: 0 Not Returned: (B) (Log # 2522 ) Eligible To Vote:15 Affirmative: 15 : 0 Abstain: 0 Not Returned: (B)(4)(2) (Log # 1015 ) Eligible To Vote:15 Affirmative: 15 : 0 Abstain: 0 Not Returned: (Log # 1386 ) Eligible To Vote:15 Affirmative: 15 : 0 Abstain: 0 Not Returned: (B) (Log # 1016 ) Eligible To Vote:15 Affirmative: 15 : 0 Abstain: 0 Not Returned: (B) (Log # 1706 ) Eligible To Vote:15 Affirmative: 15 : 0 Abstain: 0 Not Returned: (Log # 1017 ) Burlison, S. It is recognized that increasing voltage from 600 volts to 1000 volts may be applicable to specific installations. However, adequate technical substantiation has not been provided to support the change in this Article.

18 Eligible To Vote:15 Affirmative: 15 : 0 Abstain: 0 Not Returned: , , 727.6, , and , Informational Note (Log # 2638a ) Stene, S. Based on how the NEC has included references to other organizations standards throughout the Code, it is not appropriate to include the edition and revision date Eligible To Vote:15 Affirmative: 15 : 0 Abstain: 0 Not Returned: (A)(5) (Log # 3021 ) Eligible To Vote:15 Affirmative: 15 : 0 Abstain: 0 Not Returned: (Log # 757 ) Eligible To Vote:15 Affirmative: 15 : 0 Abstain: 0 Not Returned: (A), Informational Note 2 (New) (Log # 2678 ) Stene, S. The existing Informational Note in (A) applies only to (A), Exception No. 2 and not to the main requirements in (A). Adding an additional informational note will only cause confusion in the industry. Inspectors and electricians know that Class 2 circuit conductors cannot be installed with power conductors and this restriction is adequately covered in The substantiation is incorrect that a Class 2 circuit should be able to be installed with power conductors using Class 1 conductors and then revert back to a Class 2 wiring method after leaving the power wiring installation. Section (A) permits Class 1 wiring methods and materials to be used for Class 2 and Class 3 circuits but the circuits must still comply with all of the requirements for a Class 2 or a Class 3 circuit. Section does not permit insulation of the conductors to be the only method of separation from power circuits since failure of the insulation from the power circuits could cause a failure of the insulation for the Class 2 or Class 3 circuits. This insulation failure could result in shock and fire hazards that are the main reasons for limiting the Class 2 and Class 3 circuits to the levels provided in Tables 11(A) and 11(B) in Chapter a Eligible To Vote:15 Affirmative: 15 : 0 Abstain: 0 Not Returned: and (New) (Log # 3513 ) Stene, S. There has been no technical substantiation provided in the proposals for and that a Table only method of installation requirement would be better than the present text version. The second paragraph of the substantiation states that there are significant differences between Class 2, Class 3, PLTC circuits and communications circuits. Unlike communications circuits, there are so many different applications where Class 2 and Class 3 circuits are used for control, signaling, and similar circuits with these circuits having to interact with these other Articles in the NEC that a table only approach would not provide the necessary information for these applications. For example, where a Class 2 system is used for low voltage lighting based on Article 411, the wiring methods of Part III of Article 725 must be used and the installation requirements of as well as the power limitations of these circuits must be followed. Riser and plenum requirements of will apply but may require signaling raceways and the use of plenum or riser conductors inside these raceways.

19 Eligible To Vote:15 Affirmative: 15 : 0 Abstain: 0 Not Returned: and (New) (Log # 1056 ) Stene, S. See my affirmative comment on Proposal 3-144a Eligible To Vote:15 Affirmative: 15 : 0 Abstain: 0 Not Returned: and (New) (Log # 2551 ) Eligible To Vote:15 Affirmative: 15 : 0 Abstain: 0 Not Returned: (D)(1) (Log # 2679 ) Eligible To Vote:15 Affirmative: 15 : 0 Abstain: 0 Not Returned: (H) (Log # 2870 ) Eligible To Vote:15 Affirmative: 15 : 0 Abstain: 0 Not Returned: (I)(1) (Log # 1749 ) Eligible To Vote:15 Affirmative: 15 : 0 Abstain: 0 Not Returned: (I)(1) (Log # 1906 ) Eligible To Vote:15 Affirmative: 15 : 0 Abstain: 0 Not Returned: (I)(1) (Log # 2878 ) Eligible To Vote:15 Affirmative: 15 : 0 Abstain: 0 Not Returned: (Log # 1057 ) Eligible To Vote:15 Affirmative: 15 : 0 Abstain: 0 Not Returned: (Log # 2552 ) Eligible To Vote:15 Affirmative: 15 : 0 Abstain: 0 Not Returned: (New) (Log # 2259 ) 3-154a Eligible To Vote:15 Affirmative: 14 : 1 Abstain: 0 Not Returned: (Log # 3514 )

20 19 Stene, S. The following comments apply to the version of Table in the attachment in the dated February 13 from Kimberly Shea. The term `Not Permitted' in the row `In plenum cable routing assemblies' for use in Other Spaces used for Environmental Air as described in (C) was not discussed during the ROP meeting. NFPA 90A does not describe this plenum cable routing assembly, however, there is nothing to prevent a plenum routing assembly from being used in a riser or in another location within a building. Since the product was Listed as a plenum cable routing assembly, it should not be prevented from being installed in suitable locations. This item should be referred to the Technical Correlating Committee (TCC) for review Eligible To Vote:15 Affirmative: 15 : 0 Abstain: 0 Not Returned: (Log # 2311 ) Eligible To Vote:15 Affirmative: 14 : 1 Abstain: 0 Not Returned: (A), (B), and (C) (Log # 1058 ) Easter, L. The text in accepted by the panel permits plenum rated cable routing assemblies to be installed in other spaces used for environmental air as described in (C). Cable Routing assemblies are not permitted by the NEC or by NFPA 90A that has jurisdiction over wiring in air handling plenum spaces. Additionally, the proposed revisions include requirements for a plenum rated cable routing assembly where there is no corresponding application for the product. While it is permitted as a substitute for the riser and lower rated Cable Routing assemblies, its use in plenums is not permitted. See NEMA's comment on Eligible To Vote:15 Affirmative: 15 : 0 Abstain: 0 Not Returned: (A) (Log # 2326 ) Eligible To Vote:15 Affirmative: 14 : 1 Abstain: 0 Not Returned: (A), (B), and (C) (Log # 2553 ) Easter, L. See NEMA's negative on Proposal Eligible To Vote:15 Affirmative: 13 : 2 Abstain: 0 Not Returned: (B)(1) (Log # 1281 ) Clary, S. The submitter provides no (zero) fire loss data to justify increasing cable cost. That is, the submitter fails to supply documented evidence of a problem resulting from the present requirement. The existing requirement permits general purpose cable to penetrate one floor, but not two floors. Referring to the riser cable test as substantiation is confusing. The permission for general purpose cable (Types CL2 & CL3) to penetrate one floor, but not two floors, first appeared in the 1990 edition of the NEC. The requirement has been in the NEC for over 20 years, with no substantiated reason to change. The text developed by the panel, is similar to the 1987 NEC and earlier editions. Lastly, the UL 1666 vertical fire test permits a limited amount of upward flame spread. However, a real fire would impinge on the cable at ceiling level. If the fire is sufficient to cause a riser or general purpose cable to burn, the flame may travel to the floor above. There was a comment during the Panel 3 discussion indicating that fire-stopping may or may not be effective. Hopefully, the NEC TCC will carefully review the panel action on this proposal.

21 20 Stene, S. See my Explanation of Vote on Proposal Eligible To Vote:15 Affirmative: 13 : 2 Abstain: 0 Not Returned: (B)(1) (Log # 2548 ) Clary, S. The submitter provides no (zero) fire loss data to justify increasing cable cost. That is, the submitter fails to supply documented evidence of a problem resulting from the present requirement. The existing requirement permits general purpose cable to penetrate one floor, but not two floors. Referring to the riser cable test as substantiation is confusing. The permission for general purpose cable (Types CL2 & CL3) to penetrate one floor, but not two floors, first appeared in the 1990 edition of the NEC. The requirement has been in the NEC for over 20 years, with no substantiated reason to change. The text developed by the panel, is similar to the 1987 NEC and earlier editions. Lastly, the UL 1666 vertical fire test permits a limited amount of upward flame spread. However, a real fire would impinge on the cable at ceiling level. If the fire is sufficient to cause a riser or general purpose cable to burn, the flame may travel to the floor above. There was a comment during the Panel 3 discussion indicating that fire-stopping may or may not be effective. Hopefully, the NEC TCC will carefully review the panel action on this proposal. Stene, S. The existing text in (B)(1) and (B)(1) does not agree with the existing text in (D). The proposed new text acted on by Panel 3 for Proposal and is different than the text in (D), and both are different than the text in UL 1666 standard for testing of riser cable. Proposals and should be referred to the Technical Correlating Committee (TCC) for review and possible action Eligible To Vote:15 Affirmative: 15 : 0 Abstain: 0 Not Returned: (D)(4) (Log # 596 ) Eligible To Vote:15 Affirmative: 15 : 0 Abstain: 0 Not Returned: (D)(4) (Log # 2585 ) Eligible To Vote:15 Affirmative: 15 : 0 Abstain: 0 Not Returned: (J) (New) (Log # 1570 ) Walsh, R. The proposal is appropriately relocated to section Other Articles in order to clarify the requirements for the cables to be listed for installation in a wet location and the Proposal was reworded to include listing for Corrosive and Damp locations installations a Eligible To Vote:15 Affirmative: 15 : 0 Abstain: 0 Not Returned: (Log # CP303 ) Eligible To Vote:15 Affirmative: 15 : 0 Abstain: 0 Not Returned: (A), (D), and (C), Informational Note (Log # 1308 ) Eligible To Vote:15 Affirmative: 15 : 0 Abstain: 0 Not Returned: (F) (Log # 2031 )

22 Eligible To Vote:15 Affirmative: 15 : 0 Abstain: 0 Not Returned: (G) (Log # 2671 ) Eligible To Vote:15 Affirmative: 15 : 0 Abstain: 0 Not Returned: (Log # 2586 ) Eligible To Vote:15 Affirmative: 15 : 0 Abstain: 0 Not Returned: (Log # 791 ) Eligible To Vote:15 Affirmative: 15 : 0 Abstain: 0 Not Returned: (Log # 796 ) Eligible To Vote:14 Affirmative: 14 : 0 Abstain: 0 Not Returned: (New) (Log # 2109 ) Stene, S. The text in 728.5(A) should not be underlined. The text after the header 'Pulling Lubricants' in 728.5(F) shall not be bold. The text in the second sentence of 728.5(H) shall be reworded to indicate "Splices shall be provided with manufacturers installation instructions' Eligible To Vote:15 Affirmative: 15 : 0 Abstain: 0 Not Returned: Cable Routing Assembly, , , , , (Log # 1626 ) Eligible To Vote:15 Affirmative: 15 : 0 Abstain: 0 Not Returned: Fire Alarm Circuit (Log # 1178 ) Eligible To Vote:15 Affirmative: 15 : 0 Abstain: 0 Not Returned: (Log # 590 ) Eligible To Vote:15 Affirmative: 15 : 0 Abstain: 0 Not Returned: (New) (Log # 2714 ) Eligible To Vote:15 Affirmative: 15 : 0 Abstain: 0 Not Returned: (B) (Log # 2285 ) Eligible To Vote:15 Affirmative: 15 : 0 Abstain: 0 Not Returned: (Log # 2944 )

23 22 Stene, S. The action on this proposal should have been the same action as on Proposal of an accept in principle since both proposals deal with the same issue. Either both should be reject or both should be an accept in principle. The Panel Statements are almost identical Eligible To Vote:15 Affirmative: 15 : 0 Abstain: 0 Not Returned: (Log # 3141 ) Eligible To Vote:15 Affirmative: 15 : 0 Abstain: 0 Not Returned: (A) and (B) (Log # 2108 ) 3-178a Eligible To Vote:15 Affirmative: 15 : 0 Abstain: 0 Not Returned: (Log # CP302 ) Eligible To Vote:15 Affirmative: 15 : 0 Abstain: 0 Not Returned: (New) (Log # 3333 ) Eligible To Vote:15 Affirmative: 15 : 0 Abstain: 0 Not Returned: (Log # 97 ) Eligible To Vote:15 Affirmative: 15 : 0 Abstain: 0 Not Returned: (A) (Log # 1018 ) Burlison, S. It is recognized that increasing voltage from 600 volts to 1000 volts may be applicable to specific installations. However, adequate technical substantiation has not been provided to support the change in this Article Eligible To Vote:15 Affirmative: 15 : 0 Abstain: 0 Not Returned: (B) (Log # 1019 ) Eligible To Vote:15 Affirmative: 15 : 0 Abstain: 0 Not Returned: (B) (Log # 2345 ) Eligible To Vote:15 Affirmative: 15 : 0 Abstain: 0 Not Returned: (A), (B), and (Log # 2388 ) Eligible To Vote:15 Affirmative: 15 : 0 Abstain: 0 Not Returned: (A), (B)(3), and (F) (Log # 2422 )

24 Eligible To Vote:15 Affirmative: 15 : 0 Abstain: 0 Not Returned: (A)(2) and (3), (B)(2) and (3), and (F) (Log # 2055 ) Eligible To Vote:15 Affirmative: 15 : 0 Abstain: 0 Not Returned: (A)(3), (B)(3), and (F) (Log # 1830 ) Eligible To Vote:15 Affirmative: 15 : 0 Abstain: 0 Not Returned: (A)(3), (B)(3), and (F) (Log # 2448 ) Eligible To Vote:15 Affirmative: 15 : 0 Abstain: 0 Not Returned: (A)(3) and (F) (Log # 2871 ) Eligible To Vote:15 Affirmative: 15 : 0 Abstain: 0 Not Returned: (B)(1) (Log # 2312 ) Eligible To Vote:15 Affirmative: 15 : 0 Abstain: 0 Not Returned: (B)(2) (Log # 2313 ) Eligible To Vote:15 Affirmative: 13 : 2 Abstain: 0 Not Returned: (B)(3) (Log # 1282 ) Clary, S. The submitter provides no (zero) fire loss data to justify increasing cable cost. That is, the submitter fails to supply documented evidence of a problem resulting from the present requirement. The existing requirement permits general purpose cable to penetrate one floor, but not two floors. Referring to the riser cable test as substantiation is confusing. The permission for general purpose cable (Types CL2 & CL3) to penetrate one floor, but not two floors, first appeared in the 1990 edition of the NEC. The requirement has been in the NEC for over 20 years, with no substantiated reason to change. The text developed by the panel, is similar to the 1987 NEC and earlier editions. Lastly, the UL 1666 vertical fire test permits a limited amount of upward flame spread. However, a real fire would impinge on the cable at ceiling level. If the fire is sufficient to cause a riser or general purpose cable to burn, the flame may travel to the floor above. There was a comment during the Panel 3 discussion indicating that fire-stopping may or may not be effective. Hopefully, the NEC TCC will carefully review the panel action on this proposal. Stene, S. See my Explanation of Vote on Proposal Eligible To Vote:15 Affirmative: 13 : 2 Abstain: 0 Not Returned: (B)(3) (Log # 2550 )

25 24 Clary, S. The submitter provides no (zero) fire loss data to justify increasing cable cost. That is, the submitter fails to supply documented evidence of a problem resulting from the present requirement. The existing requirement permits general purpose cable to penetrate one floor, but not two floors. Referring to the riser cable test as substantiation is confusing. The permission for general purpose cable (Types CL2 & CL3) to penetrate one floor, but not two floors, first appeared in the 1990 edition of the NEC. The requirement has been in the NEC for over 20 years, with no substantiated reason to change. The text developed by the panel, is similar to the 1987 NEC and earlier editions. Lastly, the UL 1666 vertical fire test permits a limited amount of upward flame spread. However, a real fire would impinge on the cable at ceiling level. If the fire is sufficient to cause a riser or general purpose cable to burn, the flame may travel to the floor above. There was a comment during the Panel 3 discussion indicating that fire-stopping may or may not be effective. Hopefully, the NEC TCC will carefully review the panel action on this proposal. Stene, S. See my Explanation of Vote on Proposal Eligible To Vote:15 Affirmative: 14 : 1 Abstain: 0 Not Returned: (B) Exception (New) (Log # 1571 ) Walsh, R. I disagree with the panel's vote to reject the permissive proposal and stating that the Proposal didn't provide technical substantiation. The insurance industry hasn't tabulated any Fire/Security systems failing due to AFCI protection. However, I agree with the recommendation for the Technical Correlating Committee to forward the proposal to the NFPA 72 Technical Committee Task Group on inter-coordination for comment Eligible To Vote:15 Affirmative: 15 : 0 Abstain: 0 Not Returned: and (New) (Log # 1059 ) Eligible To Vote:15 Affirmative: 14 : 1 Abstain: 0 Not Returned: and (New) (Log # 2554 ) Stene, S. See my Explanation of Vote on Proposal Eligible To Vote:15 Affirmative: 15 : 0 Abstain: 0 Not Returned: and , Informational Note (New) (Log # 2686 ) Eligible To Vote:15 Affirmative: 15 : 0 Abstain: 0 Not Returned: (G)(1) (Log # 1857 ) Eligible To Vote:15 Affirmative: 15 : 0 Abstain: 0 Not Returned: (G)(1) (Log # 2879 ) Eligible To Vote:15 Affirmative: 15 : 0 Abstain: 0 Not Returned: (Log # 1060 ) Eligible To Vote:15 Affirmative: 15 : 0 Abstain: 0 Not Returned: (Log # 2555 )

26 Eligible To Vote:15 Affirmative: 13 : 2 Abstain: 0 Not Returned: (Log # 2687 ) Easter, L. See NEMA's negative on Proposal Stene, S. There is a typo in the Panel Action text where the text states "Replace table a with Table " It should have been "Replace table a with Table " The table modified during the ROP meeting was not a version of Table (a), but was the version distributed at the meeting. The following comments apply to the version of Table provided with the ballot package, not the table in the attachment in the dated February 13 from Kimberly Shea. The term `Not Permitted' in the row `In plenum cable routing assemblies' for use in Other Spaces used for Environmental Air as described in (C) was not discussed during the ROP meeting. NFPA 90A does not describe this plenum cable routing assembly, however, there is nothing to prevent a plenum routing assembly from being used in a riser or in another location within a building. Since the product was Listed as a plenum cable routing assembly, it should not be prevented from being installed in suitable locations. This item should be routed to the Technical Correlating Committee (TCC) for review Eligible To Vote:15 Affirmative: 14 : 1 Abstain: 0 Not Returned: (A) and (B) (Log # 1055 ) Easter, L. See NEMA's negative on Proposal Eligible To Vote:15 Affirmative: 14 : 1 Abstain: 0 Not Returned: (A) and (B) (Log # 2556 ) Easter, L. See NEMA's negative on Proposal Eligible To Vote:15 Affirmative: 13 : 2 Abstain: 0 Not Returned: (B)(1) (Log # 1283 ) Clary, S. The submitter provides no (zero) fire loss data to justify increasing cable cost. That is, the submitter fails to supply documented evidence of a problem resulting from the present requirement. The existing requirement permits general purpose cable to penetrate one floor, but not two floors. Referring to the riser cable test as substantiation is confusing. The permission for general purpose cable (Types CL2 & CL3) to penetrate one floor, but not two floors, first appeared in the 1990 edition of the NEC. The requirement has been in the NEC for over 20 years, with no substantiated reason to change. The text developed by the panel, is similar to the 1987 NEC and earlier editions. Lastly, the UL 1666 vertical fire test permits a limited amount of upward flame spread. However, a real fire would impinge on the cable at ceiling level. If the fire is sufficient to cause a riser or general purpose cable to burn, the flame may travel to the floor above. There was a comment during the Panel 3 discussion indicating that fire-stopping may or may not be effective. Hopefully, the NEC TCC will carefully review the panel action on this proposal. Stene, S. See my Explanation of Vote on Proposal

National Fire Protection Association. 1 Batterymarch Park, Quincy, MA Phone: Fax:

National Fire Protection Association. 1 Batterymarch Park, Quincy, MA Phone: Fax: National Fire Protection Association 1 Batterymarch Park, Quincy, MA 02169-7471 Phone: 617-770-3000 Fax: 617-770-0700 www.nfpa.org M E M O R A N D U M TO: Members of the NEC-Code Making Panel 11 FROM:

More information

National Fire Protection Association. 1 Batterymarch Park, Quincy, MA Phone: Fax:

National Fire Protection Association. 1 Batterymarch Park, Quincy, MA Phone: Fax: National Fire Protection Association 1 Batterymarch Park, Quincy, MA 02169-7471 Phone: 617-770-3000 Fax: 617-770-0700 www.nfpa.org M E M O R A N D U M TO: Code-Making Panel 5 FROM: Kimberly Shea DATE:

More information

National Fire Protection Association. 1 Batterymarch Park, Quincy, MA Phone: Fax:

National Fire Protection Association. 1 Batterymarch Park, Quincy, MA Phone: Fax: National Fire Protection Association 1 Batterymarch Park, Quincy, MA 02169-7471 Phone: 617-770-3000 Fax: 617-770-0700 www.nfpa.org M E M O R A N D U M TO: NEC Code-Making Panel 14 FROM: Kimberly Shea,

More information

National Fire Protection Association. 1 Batterymarch Park, Quincy, MA Phone: Fax:

National Fire Protection Association. 1 Batterymarch Park, Quincy, MA Phone: Fax: National Fire Protection Association 1 Batterymarch Park, Quincy, MA 02169-7471 Phone: 617-770-3000 Fax: 617-770-0700 www.nfpa.org M E M O R A N D U M TO: Members of the NEC-Code Making Panel 13 FROM:

More information

National Fire Protection Association. 1 Batterymarch Park, Quincy, MA Phone: Fax:

National Fire Protection Association. 1 Batterymarch Park, Quincy, MA Phone: Fax: National Fire Protection Association 1 Batterymarch Park, Quincy, MA 02169-7471 Phone: 617-770-3000 Fax: 617-770-0700 www.nfpa.org M E M O R A N D U M TO: Members of the NEC-Code Making Panel 13 FROM:

More information

Spring Test 9 due 05/11/2013

Spring Test 9 due 05/11/2013 Spring Test 9 due 05/11/2013 Multiple Choice Identify the choice that best completes the statement or answers the question. 1. A grounding electrode is. a. a solid conductor b. a circuit conductor that

More information

National Fire Protection Association. 1 Batterymarch Park, Quincy, MA Phone: Fax:

National Fire Protection Association. 1 Batterymarch Park, Quincy, MA Phone: Fax: National Fire Protection Association 1 Batterymarch Park, Quincy, MA 02169-7471 Phone: 617-770-3000 Fax: 617-770-0700 www.nfpa.org M E M O R A N D U M TO: FROM: NFPA Technical Committee on Fundamentals

More information

SECTION TRANSIENT VOLTAGE SUPPRESSION FOR LOW-VOLTAGE ELECTRICAL POWER CIRCUITS

SECTION TRANSIENT VOLTAGE SUPPRESSION FOR LOW-VOLTAGE ELECTRICAL POWER CIRCUITS SECTION 264313 - TRANSIENT VOLTAGE SUPPRESSION FOR LOW-VOLTAGE ELECTRICAL POWER CIRCUITS PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and

More information

SECTION PANELBOARDS

SECTION PANELBOARDS SECTION 16450 PART 1 - GENERAL 1.01 DESCRIPTION A. Section includes requirements for panelboards providing fault interrupting capability and overcurrent protective devices. 1.02 REFERENCE STANDARDS A.

More information

Page 1 of 149 First Revision No. 50-NFPA 79-2012 [ Global Input ] Delete the parenthetical terms used to describe IEC terms that follow terms used in NFPA 79 such as "protective bonding". Add information

More information

Great Western Painting Assured Equipment Grounding Conductor Program OR Ground Fault Circuit Interrupter (GFCI)

Great Western Painting Assured Equipment Grounding Conductor Program OR Ground Fault Circuit Interrupter (GFCI) Assured Equipment Grounding Conductor Program OR Ground Fault Circuit Interrupter (GFCI) GROUND FAULT CIRCUIT INTERRUPTERS Wiring design and protection. - 1926.404 Our company uses ground fault circuit

More information

SECTION (16410) - ENCLOSED SWITCHES AND CIRCUIT BREAKERS

SECTION (16410) - ENCLOSED SWITCHES AND CIRCUIT BREAKERS SECTION 26 28 16 (16410) - ENCLOSED SWITCHES AND CIRCUIT BREAKERS PART 1 GENERAL 1.01 SUMMARY A. Section Includes: 1. Individually Mounted Switches and Circuit Breakers Used for the following: a. Service

More information

Computer Network Design Guide Existing Systems 1 / 6

Computer Network Design Guide Existing Systems 1 / 6 COMPUTER NETWORK DESIGN GUIDELINE FOR EXISTING SYSTEMS DOCUMENT NUMBER: 16765 APPLICATION: ELEMENTARY, MIDDLE AND HIGH SCHOOL DATE OF ISSUE: 11-27-06 - First Issued NOTES: The attached guideline should

More information

SECTION ENCLOSED SWITCHES AND CIRCUIT BREAKERS

SECTION ENCLOSED SWITCHES AND CIRCUIT BREAKERS SECTION 262816 - ENCLOSED SWITCHES AND CIRCUIT BREAKERS PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division

More information

NEC 2008 Code Changes Top 20 Revisions. By: Rafi Wartan, PE, LEED AP

NEC 2008 Code Changes Top 20 Revisions. By: Rafi Wartan, PE, LEED AP NEC 2008 Code Changes Top 20 Revisions By: Rafi Wartan, PE, LEED AP #1 Article 210.4 MULTIWIRE BRANCH CIRCUITS The rule on simultaneous disconnecting means requirements for multiwire branch circuits was

More information

FORM FOR PROPOSAL FOR 2014 NATIONAL ELECTRICAL CODE

FORM FOR PROPOSAL FOR 2014 NATIONAL ELECTRICAL CODE FORM FOR PROPOSAL FOR 2014 NATIONAL ELECTRICAL CODE INSTRUCTIONS PLEASE READ CAREFULLY Type or print legibly in black ink. Use a separate copy for each proposal. Limit each proposal to a SINGLE section.

More information

National Fire Protection Association

National Fire Protection Association National Fire Protection Association 1 Batterymarch Park, Quincy, MA 02169-7471 Phone: 617-770-3000 Fax: 617-770-0700 www.nfpa.org MEMORANDUM TO: FROM: NFPA Technical Committee on Emergency Power Supplies

More information

Spring Test 17 due 06/14/2013

Spring Test 17 due 06/14/2013 Spring Test 17 due 06/14/2013 Multiple Choice Identify the choice that best completes the statement or answers the question. 1. The NEC defines cable as a cylindrical assembly composed of a conductor centered

More information

Stalking the Elusive and Somewhat Strange PV System

Stalking the Elusive and Somewhat Strange PV System A series of articles on photovoltaic (PV) power systems and the National Electrical Code by John Wiles PERSPECTIVES ON PV Stalking the Elusive and Somewhat Strange PV System Photo 1. Framed PV modules

More information

1. Section Lightning Protection for lightning protection system. D. The installation shall be in conformance with NEC Article 285.

1. Section Lightning Protection for lightning protection system. D. The installation shall be in conformance with NEC Article 285. SECTION 26 04 75 - SURGE PROTECTION DEVICES PART 1 - GENERAL 1.1 SUMMARY A. Applicable provisions of the General Conditions, Supplementary General Conditions and Special Conditions shall govern work performed

More information

Fall Test 21 due 12/11/2012

Fall Test 21 due 12/11/2012 Fall Test 21 due 12/11/2012 Multiple Choice Identify the choice that best completes the statement or answers the question. 1. Emergency system transfer equipment, including automatic transfer switches,

More information

Entry Level Assessment Blueprint Electrical Occupations

Entry Level Assessment Blueprint Electrical Occupations Entry Level Assessment Blueprint Electrical Occupations Test Code: 3029 / Version: 01 Specific Competencies and Skills Tested in this Assessment: Safety Apply shop safety rules and ergonomics Explain fire

More information

Spring Test 5 due 4/26/2013

Spring Test 5 due 4/26/2013 Spring Test 5 due 4/26/2013 Multiple Choice Identify the choice that best completes the statement or answers the question. 1. Where fixed multioutlet assemblies are employed, each feet or fraction thereof

More information

To the Technical Committee on Testing and Maintenance of Fire Alarm and Signaling Systems:

To the Technical Committee on Testing and Maintenance of Fire Alarm and Signaling Systems: To the Technical Committee on Testing and Maintenance of Fire Alarm and Signaling Systems: The NFPA 72 First Revisions are now open for ballot. Ballots are due by Monday December 9, 2013 at 11:59 pm ET.

More information

SECTION SURGE PROTECTIVE DEVICES

SECTION SURGE PROTECTIVE DEVICES SECTION 16289 PART 1 GENERAL 1.01 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division 1 Specification Sections, apply to this

More information

SECTION WIRING DEVICES PART 1 - GENERAL. A. Drawings and Division 1 Specification Sections, apply to this Section.

SECTION WIRING DEVICES PART 1 - GENERAL. A. Drawings and Division 1 Specification Sections, apply to this Section. SECTION 16140 WIRING DEVICES 1.01 RELATED DOCUMENTS PART 1 - GENERAL A. Drawings and Division 1 Specification Sections, apply to this Section. 1.02 SUMMARY A. This Section includes receptacles, connectors,

More information

IEC H.P. Rated Pin and Sleeve Sequential contacts engagement during mating and un-mating IEC configurations specific to each voltage and

IEC H.P. Rated Pin and Sleeve Sequential contacts engagement during mating and un-mating IEC configurations specific to each voltage and IEC 60309 H.P. Rated Pin and Sleeve Sequential contacts engagement during mating and un-mating IEC configurations specific to each voltage and amperage to prevent interchangeability of voltages Watertight

More information

MICHIGAN DEPARTMENT OF TRANSPORTATION

MICHIGAN DEPARTMENT OF TRANSPORTATION MICHIGAN DEPARTMENT OF TRANSPORTATION SPECIAL PROVISION FOR GROUNDING, BONDING, LIGHTNING PROTECTION AND SURGE PROTECTION FOR INTELLIGENT TRANSPORTATION SYSTEM EQUIPMENT ITS:CLC 1 of 5 APPR:LWB:DBP:07-31-13

More information

More Questions from Inspectors Numerous PV Systems Pose Issues

More Questions from Inspectors Numerous PV Systems Pose Issues Perspectives on PV More Questions from Inspectors Numerous PV Systems Pose Issues by John Wiles 76 IAEI NEWS March. April 2012 www.iaei.org Photovoltaic (PV) systems prices continue to drop and inspectors

More information

Installation, Testing, and Operating Procedures 30 AMP PORTABLE AND PERMANENT SERIES GFCI SINGLE and MULTIPHASE

Installation, Testing, and Operating Procedures 30 AMP PORTABLE AND PERMANENT SERIES GFCI SINGLE and MULTIPHASE IMPORTANT! Please read all the information on this sheet. SAVE THESE INSTRUCTIONS! NOTICE BEFORE USING READ INSTRUCTIONS COMPLETELY. TO BE INSTALLED BY A QUALIFIED ELECTRICIAN IN ACCORDANCE WITH NATIONAL

More information

Electrical Components and Equipment for General Use Self Inspection Checklist

Electrical Components and Equipment for General Use Self Inspection Checklist Name of School: Optional Information Date of Inspection: Vocational Program/Course/Room: Signature of Inspector: Electrical Components and Equipment for General Use Self Inspection Checklist Guidelines:

More information

Electrical Integration of PV Systems. Ridha Hamidi, Ph.D.

Electrical Integration of PV Systems. Ridha Hamidi, Ph.D. Electrical Integration of PV Systems Ridha Hamidi, Ph.D. 1 Many articles in the NEC are applicable to the electrical integration of a PV system, particularly Article 690. 2 The NEC defines the various

More information

DANGER DANGER: is used in this manual to warn of high voltages capable of causing shock, burns, or death.

DANGER DANGER: is used in this manual to warn of high voltages capable of causing shock, burns, or death. Installation/Operation Manual TABLE OF CONTENTS Page UNPACKING AND INSTALLATION Unpacking and Preliminary Inspection...2, 3 Model Number...9 LOCATION CONSIDERATIONS Environment, Equipment Performance,

More information

DIVISION 16 SECTION Surge Protective Device Submittal (SPD)

DIVISION 16 SECTION Surge Protective Device Submittal (SPD) DIVISION 16 SECTION 16289 Surge Protective Device Submittal (SPD) PART 1 -GENERAL 1.1 RELATED DOCUMENTS A. General: Drawings and general provisions of the Contract, including General and Supplementary

More information

Solar Combiner Enclosure

Solar Combiner Enclosure Installation Instructions Solar Combiner Enclosure Catalog Numbers 1000-SB006, 1000-SB012 Topic Page Description 1 Important Safety Instructions 3 Nameplate Data 4 Planning for Installation 4 Install the

More information

Liebert AccuVar (ACV Series) Surge Protective Device (SPD) (With Noise Filtering) GUIDE SPECIFICATIONS for a Parallel Surge Suppression System

Liebert AccuVar (ACV Series) Surge Protective Device (SPD) (With Noise Filtering) GUIDE SPECIFICATIONS for a Parallel Surge Suppression System Liebert AccuVar (ACV Series) Surge Protective Device (SPD) (With Noise Filtering) GUIDE SPECIFICATIONS for a Parallel Surge Suppression System Part 1 General 1.01 Summary A. These specifications describe

More information

M E M O R A N D U M. NFPA Technical Committee on Means of Egress. Diane Matthews, Technical Projects, Administrator. Date: October 12, 2012

M E M O R A N D U M. NFPA Technical Committee on Means of Egress. Diane Matthews, Technical Projects, Administrator. Date: October 12, 2012 National Fire Protection Association 1 Batterymarch Park, Quincy, MA 02169-7471 Phone: 617-770-3000 Fax: 617-770-0700 www.nfpa.org M E M O R A N D U M To: From: NFPA Technical Committee on Means of Egress

More information

Target Interface / Construction Compliance Inspection Checklist

Target Interface / Construction Compliance Inspection Checklist TES A. Roads-Service, Lanes Common Items Trails and service roads provide adequate access to buildings for maintenance B. Testing Results-provided to the local government construction representative Data

More information

SECTION DISCONNECT SWITCHES

SECTION DISCONNECT SWITCHES SECTION 16440 DISCONNECT SWITCHES PART 1 - GENERAL 1.01 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and other Division 01 Specification

More information

TECH NOTE #: CPS-1 SUMMARY OF APPLICABLE UL AND IEEE STANDARDS

TECH NOTE #: CPS-1 SUMMARY OF APPLICABLE UL AND IEEE STANDARDS TECH NOTE #: CPS-1 SUMMARY OF APPLICABLE UL AND IEEE STANDARDS FOR SURGE PROTECTION DEVICES This Tech Note provides an overview of the key standards associated with surge suppressors and AC powerline filters.

More information

2008 Code Changes for Power Distribution

2008 Code Changes for Power Distribution 2008 Schaedler Yesco Expo 2008 Code Changes for Power Distribution April 17, 2008 / Version 1.0 For internal use only / Copyright Siemens AG 2007. 2008. All rights reserved. Contact Consulting Account

More information

INSTALLATION, OPERATION AND MAINTENANCE MANUAL GE TRANQUELL Series Wall Mounted Low and Medium Exposure Surge Protective Devices (SPDs)

INSTALLATION, OPERATION AND MAINTENANCE MANUAL GE TRANQUELL Series Wall Mounted Low and Medium Exposure Surge Protective Devices (SPDs) ga GE Digital Energy Power Quality INSTALLATION, OPERATION AND MAINTENANCE MANUAL GE TRANQUELL Series Wall Mounted Low and Medium Exposure Surge Protective Devices (SPDs) 2020005003 (12/09) Page 1 of 18

More information

COMMON WORK RESULTS FOR COMMUNICATIONS

COMMON WORK RESULTS FOR COMMUNICATIONS SECTION 270500 - COMMON WORK RESULTS FOR COMMUNICATIONS PART 1 - GENERAL 1.1 RELATED SECTIONS A. All division 27 work shall, in addition to all division 1 specification sections, comply with all of the

More information

SECTION IDENTIFICATION FOR ELECTRICAL SYSTEMS

SECTION IDENTIFICATION FOR ELECTRICAL SYSTEMS SECTION 26 05 53 IDENTIFICATION FOR ELECTRICAL SYSTEMS PART 1 GENERAL 1.1 SUMMARY A. Section Includes: 1. Nameplates. 2. Labels. 3. Wire markers. 4. Conduit markers. 5. Underground Warning Tape. 6. Lockout

More information

NEMA Standards Publication AB Establishing Levels of Selective Coordination for Low Voltage Circuit Breakers

NEMA Standards Publication AB Establishing Levels of Selective Coordination for Low Voltage Circuit Breakers NEMA Standards Publication AB 5-2011 Establishing Levels of Selective Coordination for Low Voltage Circuit Breakers Published by: National Electrical Manufacturers Association 1300 North 17th Street, Suite

More information

Eaton s Innovative Technology Surge Suppression Guideform Specification Low Exposure DIVISION 16 SECTION 16289

Eaton s Innovative Technology Surge Suppression Guideform Specification Low Exposure DIVISION 16 SECTION 16289 PART 1 - GENERAL DIVISION 16 SECTION 16289 TRANSIENT VOLTAGE SURGE SUPPRESSION (TVSS) 1.1 RELATED DOCUMENTS General: Drawings and general provisions of the Contract, including General and Supplementary

More information

Explosion-Protected Arc-Fault Protection ExAFCI Arc-Fault Circuit Interrupter

Explosion-Protected Arc-Fault Protection ExAFCI Arc-Fault Circuit Interrupter Installation, Operation & Maintenance Sheet Explosion-Protected Arc-Fault Protection ExAFCI Arc-Fault Circuit Interrupter > Contents 1 Contents 1 Contents...2 2 General Information...2 2.1 Manufacturer...2

More information

White Paper October 2009

White Paper October 2009 ANSI /UL1449 Third Edition Safety Standard (New UL and NEC standards means new performance levels, test procedures and markings to products and manufacturers) White Paper October 2009 The past two years

More information

Eaton s Innovative Technology Surge Suppression Guideform Specification High Exposure DIVISION 16 SECTION 16289

Eaton s Innovative Technology Surge Suppression Guideform Specification High Exposure DIVISION 16 SECTION 16289 PART 1 - GENERAL DIVISION 16 SECTION 16289 TRANSIENT VOLTAGE SURGE SUPPRESSION (TVSS) 1 RELATED DOCUMENTS General: Drawings and general provisions of the Contract, including General and Supplementary Conditions

More information

M E M O R A N D U M. NFPA Technical Committee on Means of Egress. Diane Matthews, Technical Projects, Administrator. Date: October 12, 2012

M E M O R A N D U M. NFPA Technical Committee on Means of Egress. Diane Matthews, Technical Projects, Administrator. Date: October 12, 2012 National Fire Protection Association 1 Batterymarch Park, Quincy, MA 02169-7471 Phone: 617-770-3000 Fax: 617-770-0700 www.nfpa.org M E M O R A N D U M To: From: NFPA Technical Committee on Means of Egress

More information

Standards Update Notice (SUN) Issued: January 11, 2016

Standards Update Notice (SUN) Issued: January 11, 2016 Standard Information Standard Number: UL 962A Standard Name: Furniture Power Distribution Units Standard Edition and Issue Date: 3 rd Edition Dated September 29, 2014 Date of Revision: September 8, 2015

More information

Testing for safe and efficient branch circuits

Testing for safe and efficient branch circuits Testing for safe and efficient branch circuits Written by Chad Reynolds, Product Manager, IDEAL Test and Measurement Division Branch Circuit Testing Branch circuit wiring and testing practices are primarily

More information

SECTION 16450: NON-AUTOMATIC TRANSFER SWITCH / QUICK CONNECT GENERATOR SWITCHBOARD <S> <OM>

SECTION 16450: NON-AUTOMATIC TRANSFER SWITCH / QUICK CONNECT GENERATOR SWITCHBOARD <S> <OM> SECTION 16450: NON-AUTOMATIC TRANSFER SWITCH / QUICK CONNECT GENERATOR SWITCHBOARD PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General

More information

SECTION WIRING DEVICES

SECTION WIRING DEVICES SECTION 16141 WIRING DEVICES PART 1 - GENERAL 1.01 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division 01 Specification Sections,

More information

SECTION COMMON WORK RESULTS FOR COMMUNICATIONS

SECTION COMMON WORK RESULTS FOR COMMUNICATIONS PART 1 - GENERAL SECTION 270500 - COMMON WORK RESULTS FOR COMMUNICATIONS 1.1 RELATED SECTIONS A. All division 27 work shall, in addition to all division 1 specification sections, comply with all of the

More information

Spring Test 16 due 06/14/2013

Spring Test 16 due 06/14/2013 Spring Test 16 due 06/14/2013 Multiple Choice Identify the choice that best completes the statement or answers the question. Figure 234.142 1. Refer to the information shown in Figure 234.142. Motor 1

More information

EMS. Electrical Management System. Progressive Industries Incorporated Morrisville, North Carolina

EMS. Electrical Management System. Progressive Industries Incorporated Morrisville, North Carolina Progressive Industries Warranty Progressive warrants its products are free from defects in materials and workmanship for a period of three years. This is in lieu of all other warranties, obligations, or

More information

SECTION VARIABLE FREQUENCY MOTOR CONTROLLERS (VFD)

SECTION VARIABLE FREQUENCY MOTOR CONTROLLERS (VFD) SECTION 26 29 23 VARIABLE FREQUENCY MOTOR CONTROLLERS (VFD) PART 1 -GENERAL 1.1 SYSTEM DESCRIPTION A. Definitions: The Variable Speed AC Motor Drive (hereafter referred to as "VFD") shall be designed to

More information

Bulletin Installation of Solar Photovoltaic Systems Section 50; Rules: , , ; Tables 11 and 19 Issued July 2010

Bulletin Installation of Solar Photovoltaic Systems Section 50; Rules: , , ; Tables 11 and 19 Issued July 2010 Ontario Electrical Safety Code - Bulletins 50-1-0 Bulletin 50-1-0 Installation of Solar Photovoltaic Systems Section 50; Rules: 84-020, 84-024, 84-030; Tables 11 and 19 Issued July 2010 Scope (1) Introduction

More information

Introduction to the Inspection Checklist for Rooftop Solar Photovoltaic (PV) Systems in Goshen, IN

Introduction to the Inspection Checklist for Rooftop Solar Photovoltaic (PV) Systems in Goshen, IN Introduction to the Inspection Checklist for Rooftop Solar Photovoltaic (PV) Systems in Goshen, IN This Inspection Checklist for Rooftop Photovoltaic (PV) Systems is based on the Model Inspection Checklist

More information

Surge Protective Devices. STV100K Series. Instruction Manual

Surge Protective Devices. STV100K Series. Instruction Manual Surge Protective Devices STV100K Series Instruction Manual Contents 1.0 Installation... 4 1.1 Environment... 4 1.2 Mounting... 4 1.3 Proper Connection of SPDs... 4 1.4 Mechanical Dimensions... 5 1.5 Voltage

More information

HUBBELL SPIKESHIELD Wired-In Branch Panels Surge Protective Device (SPD)

HUBBELL SPIKESHIELD Wired-In Branch Panels Surge Protective Device (SPD) HUBBELL SPIKESHIELD Wired-In Branch Panels Surge Protective Device (SPD) Instruction Bulletin 8222-0513B Retain for future use. SPIKESHIELD Wired-In Branch Panels 8222-0513B 05/2012 Table of Contents Precautions...

More information

SECTION WIRING DEVICES

SECTION WIRING DEVICES SECTION 26 27 26 WIRING DEVICES PART 1 - GENERAL 1.1 SUMMARY A. Section includes the following: 1. Receptacles, receptacles with integral GFCI, and associated device plates. 2. Twist-locking receptacles.

More information

SECTION TRANSIENT VOLTAGE SURGE SUPPRESSION

SECTION TRANSIENT VOLTAGE SURGE SUPPRESSION SECTION 16709 TRANSIENT VOLTAGE SURGE SUPPRESSION PART 1 GENERAL 1.01 SUMMARY A. Section Includes: Transient Voltage Surge Suppression (TVSS) devices, also known as Surge Protective Devices (SPDs), for

More information

Surge Protective Devices. STV100K Series. Instruction Manual

Surge Protective Devices. STV100K Series. Instruction Manual Surge Protective Devices STV100K Series Instruction Manual Contents 1.0 Installation... 4 1.1 Environment... 4 1.2 Mounting... 4 1.3 Proper Connection of SPDs... 4 1.4 Mechanical Dimensions... 5 1.5 Voltage

More information

MICHIGAN DEPARTMENT OF TRANSPORTATION

MICHIGAN DEPARTMENT OF TRANSPORTATION MICHIGAN DEPARTMENT OF TRANSPORTATION SPECIAL PROVISION FOR GROUNDING, BONDING, LIGHTNING PROTECTION AND SURGE PROTECTION FOR INTELLIGENT TRANSPORTATION SYSTEM EQUIPMENT ITS:CLC 1 of 6 APPR:MDW:JVG:06-08-18

More information

Mitigating Arc Flash Hazards

Mitigating Arc Flash Hazards 1910DB1402 / March, 2015 by Antony Parsons, Ph.D., P.E. and Reza Tajali, P.E. Schneider Electric Engineering Services Make the most of your energy SM Contents 1.0 Introduction... 3 2.0 What is Arc Flash

More information

R-LB R-LX Series Installation, Operation & Maintenance Manual

R-LB R-LX Series Installation, Operation & Maintenance Manual Installation, Operation & Maintenance Manual WARNINGS Safety First Hazardous Voltage & Shock Hazard Only qualified licensed electricians should install or service SPDs Hazardous voltages exist within SPDs

More information

Second Revision No. 1-NFPA [ Global Comment ]

Second Revision No. 1-NFPA [ Global Comment ] Second Revision No. 1-NFPA 79-2017 [ Global Comment ] *************GLOBAL INSTRUCTION - COMP: See Mark's note for clarity*************** Remove all parenthetical terms of (plug/socket) and any variation

More information

M250 (M LL) Safety

M250 (M LL) Safety M250 SAFETY M250 (M250-60-2LL) Safety Important Safety Information This document contains important instructions to use during installation of the Enphase M250 Microinverter. To reduce the risk of electrical

More information

GE Digital Energy. Power Quality

GE Digital Energy. Power Quality GE Digital Energy Power Quality INSTALLATION, OPERATION AND MAINTENANCE MANUAL GE TRANQUELL Enhanced Thermal Protection (ETP) Series Wall Mounted Medium and High Exposure Surge Protective Devices (SPDs)

More information

Ground Fault Current Protection Devices Prevent Costly Production Shutdowns

Ground Fault Current Protection Devices Prevent Costly Production Shutdowns Ground Fault Current Protection Devices Prevent Costly Production Shutdowns Figure.1 Altech s three new series deliver multiple capabilities. In all three series, ground fault sensitivity levels range

More information

Model 2460-KIT. Screw Terminal Connector Kit. Description / September 2014 *P * 1

Model 2460-KIT. Screw Terminal Connector Kit. Description / September 2014 *P * 1 Keithley Instruments 28775 Aurora Road Cleveland, Ohio 44139 1-800-935-5595 http://www.keithley.com Model 2460-KIT Screw Terminal Connector Kit Description The Model 2460-KIT Screw Terminal Connector Kit

More information

MEMORANDUM SUBJECT: APPROVED POWER STRIPS AND SURGE PROTECTORS

MEMORANDUM SUBJECT: APPROVED POWER STRIPS AND SURGE PROTECTORS MEMORANDUM DATE: December 15, 2013 TO: Campus Community FROM: Tim Ridley, CSP, ARM-P Director, Safety and Risk Management SUBJECT: APPROVED POWER STRIPS AND SURGE PROTECTORS Safety & Risk Management inspections

More information

SECTION SWITCHGEAR

SECTION SWITCHGEAR SECTION 26 23 13 SWITCHGEAR PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division 1 Specification Sections,

More information

M215 (M215-60) Safety

M215 (M215-60) Safety M215 QUICK INSTALL GUIDE M215 (M215-60) Safety Important Safety Information This document contains important instructions to use during installation and maintenance of the Enphase M215 Microinverter. To

More information

Installation Instructions

Installation Instructions 50ES, 50EZ, 50GL, 50GS, 50GX, 50JS, 50JX, 50JZ, 50SD, 50SZ, 50VL, 50VT, 50XP, 50XZ 601A, 602A, 602B, 604A, 604B, 604D, 607C, 701A, 702A, 702B, 704A, 704B, 704D, 707C PA1P, PA2P, PA3P, PH1P, PH2P, PH3P

More information

Instruction Manual: IM E

Instruction Manual: IM E Innovative Technology TVSS Products The I.T. Equalizer Installation Instruction Manual: IM01005011E Rev. 2 May 2009 Contents Page 1 Introduction... 1 1.1 Scope... 1 1.2 I.T. Equalizer Catalog Numbering

More information

PDS8u POWER DISTRIBUTION SYSTEM USER'S MANUAL

PDS8u POWER DISTRIBUTION SYSTEM USER'S MANUAL PDS8u POWER DISTRIBUTION SYSTEM USER'S MANUAL 1 IMPORTANT SAFETY INSTRUCTION READ FIRST This symbol, whenever it appears, alerts you to the presence of uninsulated dangerous voltage inside the enclosure-voltage

More information

GENERAL UL th EDITION BID SPEC: SURGE PROTECTIVE DEVICES Prepared by THOR SYSTEMS, INC.

GENERAL UL th EDITION BID SPEC: SURGE PROTECTIVE DEVICES Prepared by THOR SYSTEMS, INC. [Refer to Engineering Notes at End of Spec] Section [16XXX] [264XXX] - SURGE PROTECTIVE DEVICES (SPDs) PART 1 - GENERAL 1.1 SCOPE A. This section includes Surge Protective Devices (SPDs) for low-voltage

More information

Section 1. 1 How to Study This Course & Achieve Your Personal Goals Orientation (J200.I) 1

Section 1. 1 How to Study This Course & Achieve Your Personal Goals Orientation (J200.I) 1 All materials are copyrighted by the National Joint Apprenticeship and Training Committee. No material may be reproduced without the express written permission of the NJATC. Section 1 1 How to Study This

More information

Surge Protective Devices Installation, Operation and Maintenance Manual. LoadTrack LTL

Surge Protective Devices Installation, Operation and Maintenance Manual. LoadTrack LTL LoadTrack LTL Surge Protective Devices Installation, Operation and Maintenance Manual P.O. Box 3760 Winter Park, FL 32790 USA TEL: 800-647-1911 www.tpssurge.com LOADTRACK LTL INSTALLATION, OPERATION AND

More information

Source-Transfer Application Guide

Source-Transfer Application Guide S&C Model 6802 Automatic Switch Control Source-Transfer Application Guide Table of Contents Section Page Section Page Introduction Qualified Persons.... 2 Read this Instruction Sheet.... 2 Retain this

More information

2014 AFCI code compliant safety. Understanding the 2014 NEC. for AFCI protection

2014 AFCI code compliant safety. Understanding the 2014 NEC. for AFCI protection 2014 AFCI code compliant safety Understanding the 2014 NEC for AFCI protection Understanding the code for code compliant safety An arc fault is an unintended arc created by current flowing through an unplanned

More information

SECTION SURGE PROTECTION DEVICES. A. Section includes Surge Protection Devices for low-voltage power, control, and communication equipment.

SECTION SURGE PROTECTION DEVICES. A. Section includes Surge Protection Devices for low-voltage power, control, and communication equipment. SECTION 26 43 00 SURGE PROTECTION DEVICES PART 1 - GENERAL 1.1 SUMMARY A. Section includes Surge Protection Devices for low-voltage power, control, and communication equipment. 1.2 DEFINITIONS A. ATS:

More information

SECTION ELECTRIC METERING

SECTION ELECTRIC METERING SECTION 26 27 13 ELECTRIC METERING SPEC WRITER NOTES: Use this section only for NCA projects Delete between //----// if not applicable to project. Also delete any other item or paragraph not applicable

More information

PanelView Plus/VersaView CE Terminals and Display Modules

PanelView Plus/VersaView CE Terminals and Display Modules Installation Instructions PanelView Plus/VersaView CE Terminals and Display Modules (Catalog Numbers 2711P-xxxxxx, 6182H-xxxxxx) English Inside: Overview...2 For More Information...2 Modular Components...3

More information

Standards Update Notice (SUN) Issued: April 25, 2017

Standards Update Notice (SUN) Issued: April 25, 2017 Standard Information Standard Number: UL 1951 Standard Name: Electric Plumbing Accessories Standard Edition and Issue Date: 2 nd Edition Dated July 22, 2011 Date of Revision: February 21, 2017 Date of

More information

EM-F-7G Safety Extension Module

EM-F-7G Safety Extension Module EM-F-7G Safety Extension Module One-channel control with four safety output channels Features Safety Extension Module provides additional safety outputs for a Primary Safety Device (for example, an E-stop

More information

GROUND FAULT CIRCUIT INTERUPTERS

GROUND FAULT CIRCUIT INTERUPTERS Title: GFCI Effective Date: 11/14/2014 Control Number: THG_0031 Revision Number: 1 Date: 10/21/2015 Annual Review Completed: 5/13/2015 GROUND FAULT CIRCUIT INTERUPTERS CONTENTS I. PURPOSE II. GENERAL REQUIREMENTS

More information

Installation Instructions for Eaton Surge Protective Device XXCFXXX10-DIN and XXCFXXX10-DIN2

Installation Instructions for Eaton Surge Protective Device XXCFXXX10-DIN and XXCFXXX10-DIN2 Supersedes 6/2015 Surge Protective Device XXCFXXX10-DIN and XXCFXXX10-DIN2 XXCFXXX10-DIN Contents Description Page 1.0 Setup...2 1.1 Before Installation...2 1.2 Installation...3 For AC Applications...3

More information

GENERAL UL th EDITION DESIGN-BUILD SPEC: SURGE PROTECTIVE DEVICES Prepared by THOR SYSTEMS, INC.

GENERAL UL th EDITION DESIGN-BUILD SPEC: SURGE PROTECTIVE DEVICES Prepared by THOR SYSTEMS, INC. [Refer to Engineering Notes at End of Spec] Section [16XXX] [264XXX] - SURGE PROTECTIVE DEVICES (SPDs) PART 1 - GENERAL 1.1 SCOPE A. This section includes Surge Protective Devices (SPDs) for low-voltage

More information

Copper Riser And Intrabuilding Cabling

Copper Riser And Intrabuilding Cabling Copper Riser And Intrabuilding Cabling PART 1: GENERAL The Contractor is held responsible to be familiar with the provisions contained herein and with other Sections of this Specification as applicable

More information

Microinverters And The Solar Industry

Microinverters And The Solar Industry Microinverters And The Solar Industry Peter Lum Senior Learning And Development Professional Assistant Professor Skyline College Solar Continues Its Growth 2 Significant Growth Of Microinverters in Solar

More information

(1986; Rev. 1989) Molded Case Circuit Breakers and Molded Case Switches. (1985; Rev. 1988) Enclosures for Electrical Equipment (1000 Volts Maximum)

(1986; Rev. 1989) Molded Case Circuit Breakers and Molded Case Switches. (1985; Rev. 1988) Enclosures for Electrical Equipment (1000 Volts Maximum) Section 16306 50/60-HERTZ (HZ) SOLID STATE FREQUENCY CONVERTER Index PART 1 GENERAL PART 2 PRODUCTS 1.1 References 2.1 Frequency Converters 1.2 Factory Tests 2.2 Conduit and Fittings 1.3 Submittals 2.3

More information

Model 8020-KHV. Kelvin Keithley Triaxial Connector Card. Description / October 2014 *P * 1

Model 8020-KHV. Kelvin Keithley Triaxial Connector Card. Description / October 2014 *P * 1 Keithley Instruments 28775 Aurora Road Cleveland, Ohio 44139 1-800-935-5595 http://www.keithley.com Model 8020-KHV Kelvin Keithley Triaxial Connector Card Description The Model 8020-KHV Keithley HV Connector

More information

hp uninterruptible power system r12000 xr models installation instructions

hp uninterruptible power system r12000 xr models installation instructions hp uninterruptible power system r000 xr models installation instructions Overview These instructions show how to install an uninterruptible power system (UPS). For detailed information about the UPS, refer

More information

B. System Design and Performance Requirements

B. System Design and Performance Requirements Change History Date Description of Change Pages / Sections Modified 6/15/16 Updated division section from 16289 to 26 35 00, removed references to other section numbers 10/14/14 Amend text in section B

More information

Product Description. S&C IntelliNode Interface Module. Table of Contents. Instruction Sheet

Product Description. S&C IntelliNode Interface Module. Table of Contents. Instruction Sheet S&C IntelliNode Interface Module Product Description Table of Contents Section Page Section Page Introduction Qualified Persons.......................... 2 Read this Instruction Sheet..................

More information

BS 181 SINGLE CHANNEL POWER SUPPLY USER MANUAL

BS 181 SINGLE CHANNEL POWER SUPPLY USER MANUAL BS 181 SINGLE CHANNEL POWER SUPPLY USER MANUAL August 2016 This product is designed and manufactured by: ASL Intercom B.V. Zonnebaan 42 3542 EG Utrecht The Netherlands Phone: +31 (0)30 2411901 Fax: +31

More information