ETI COMMANDER MNPR INTERFACE SOFTWARE FOR

Size: px
Start display at page:

Download "ETI COMMANDER MNPR INTERFACE SOFTWARE FOR"

Transcription

1 ETI COMMANDER MNPR INTERFACE SOFTWARE FOR ios Instruction Manual Revision 1 ETI Electronic Technology Incorporated 511 Lyons Avenue, Irvington, NJ (973) FAX (973) sales@eti-nj.com

2 THIS PAGE INTENTIONALLY LEFT BLANK

3 REVISIONS Revision Date Details Author 1 01/09/2018 Initial Revision NY i

4 THIS PAGE INTENTIONALLY LEFT BLANK ii

5 SAFETY PRECAUTIONS WARNING There are potentially dangerous/lethal voltages present in and around network protectors and associated equipment. Failure to follow safety precautions and wear proper PPE could result in personal injury and/or death as well as equipment damage. iii

6 THIS PAGE INTENTIONALLY LEFT BLANK iv

7 TABLE OF CONTENTS Installation... 1 Initial Setup... 3 Parameter Screens... 5 Basic Setup Procedure Relay Status Screen Monitor Screen View Waveforms Operations Help/Info Troubleshooting Appendix A. MNPR Characteristics Appendix B. MNPR Pinouts Appendix C. MNPR Default DNP3 Profile Appendix D. MNPR Aux I/O Pinouts Appendix E. Pairing the Bluetooth Module with the ios device Appendix F. Phase Select Details v

8 THIS PAGE INTENTIONALLY LEFT BLANK vi

9 Installation The Commander software can be downloaded from the App Store. Power Button Commander icon. Other icons may appear, too Communications Module Figure 1-1 Before the ios device can communicate with the MNPR, the Bluetooth module must be installed. Do this by simply pressing the module into position over the locating pins on the front of the MNPR (Figure 1-2). Press the button on the side of the Bluetooth module to switch it on for use. Locating Pins Further information on installing the application is in Appendix F. Figure 1-2 1

10 THIS PAGE INTENTIONALLY LEFT BLANK 2

11 Initial Setup Simply tap on the app icon to start the Commander software and you will see the main screen (Figure 2-1). In order to connect to the MNPR, the Bluetooth module must be paired with the ios device. To do this, enable Bluetooth on the ios device by swiping up from the bottom of the screen to open the Control Panel. Tap the Bluetooth icon so that it illuminates blue. A small Bluetooth icon appears at the top right corner of the screen when Bluetooth is enabled. The ios device will ask if you want to find a Bluetooth device the first time you attempt to communicate, such as trying to Read Status or Parameters (Figure 2-2). When prompted, press yes and choose from the list the ETI module you activated earlier. Further detail on this procedure and pairing the Bluetooth adapter is in Appendix E. Settings menu for changing displayed units, etc. Figure 2-1 The Settings Menu allows the user to change the units used to display parameters and settings to either Relay, Protector, or Percent, as well as choose the type of relay being configured. Current can be displayed in Relay Current (based off the 5 Amp secondary of the network protector CT), Protector Current (the actual current through the bus), or as a Percentage of the 3

12 CT rating. For example on a protector with at 1600:5 Amp CT Ratio, 2.5A (Relay Units) is equivalent to 800A (Protector Units) and 50% (Percent). Connect to Bluetooth module Figure 2-2 Verify that the MNPR is powered up, either properly installed in a network protector or powered up on the bench using an ETI (GE) or (WH) Single Phase Power Block. To test the communications, power on the Bluetooth head, tap Parameters, and then tap Read (Figure 3-1). The screen should populate with the relay s settings. If you get a Communications Failure or other message please refer to the Troubleshooting section of this manual. 4

13 Parameter Screens There are six parameter screens. Switch between them by swiping the screen left or right or by tapping the tabs above the page. Once you have completed your selections, return to the main screen by tapping the Back button. Read Button Back/Return to Main Screen Function Buttons Parameter Screens Tap Fields to Change Parameter Figure 3-1 5

14 The following function buttons are available on each of the Parameter screens: Read Reads the current state of the connected MNPR. These parameters are immediately displayed on the screen. Program Writes the parameters back to the MNPR. (available only after a successful Read) Reset Resets the MNPR to its factory default settings (useful if the MNPR is doing something unexpected or there is some uncertainty to the state of its programming). Once the MNPR has been read the settings can be viewed and modified (Figure 3-1). Note: Not all parameters and options are available on all types and styles of MNPR. If a parameter described in this manual does not appear on the screen that simply means it is not supported by the connected MNPR. Read only parameters: SN Displays the serial number of the MNPR. Ver Displays the version of the MNPR firmware. Type Displays the style of MNPR (General Electric (GE) or Westinghouse (WH)). FW Date Firmware revision date. Cycles Number of trip cycles. Main Parameters: Note: Graphical plots of the MNPR operating characteristics are provided for reference in Appendix A. Many of the following settings alter the operating regions shown on those plots. Relay State Indicates the current state of the relay (Trip/Close/Blocked/Float) CT Ratio Select the CT Ratio that matches the network protector. Reclose Volts Minimum three phase average differential voltage necessary to close the protector. The three phase average of the real part of the differential voltages (VTN*COS θ) must exceed this set point. 6

15 In Circle Close mode the three phase average of the magnitude of the differential voltages (VTN) must exceed this value. Reclose Angle Reclose curve lower limit. The protector will not close if the angle between the network voltage and the differential voltage is below this setting. Circle Close Selects the circle close characteristic. Limit Angle (Only available if Circle Close is enabled) Reclose curve upper limit in circle close mode. The protector will not close if the angle between the network voltage and the differential voltage is above this setting. Cross Phase Trip This setting allows the user to set a threshold of negative differential that will cause the MNPR to engage its trip contact. This contact will remain engaged until the negative differential is removed. The setting is compared to the three phase sum of the differentials. Typical situations that would activate the Hard Trip are: Feeder outage, rolled phases and crossed phases. Note: This feature should NOT be used in place of safe work practices. This is NOT a safety feature; it is a program feature only. Trip Mode Selects which of the five trip modes the MNPR is to use: Sensitive In this mode the MNPR will trip the protector when the net reverse power flow exceeds the set point. The three phase average of the signed vector sum of the network voltages multiplied by the currents (VN*I*COS θ)/ VNrms must exceed the set point. Time Delay In this mode the Sensitive criteria must be met for the duration of the time delay period before the network protector will open. However, if during the delay period the Instant Current set point is ever exceeded on one or more phases (such as a fault condition) the network protector will trip immediately (unless an Extended Delay is set, see below). Insensitive This mode is analogous to Time Delay mode if the delay time could be set to infinity. The network protector will not open during normal system conditions (feeder outage, etc.). It will only open when the Insensitive Current set point is exceeded on one or more phases (such as a fault condition). (The Sensitive criteria must also be satisfied for a trip to take place). Watt-Var In this mode the MNPR will rotate the trip region to ensure that the network protector will open under certain circumstances. Both the current at which to rotate and the amount of rotation can be set. 7

16 Delayed Watt-Var In this mode the MNPR will rotate the trip region to ensure that the network protector will open under certain circumstances. Both the current at which to rotate and the amount of rotation can be set. This mode allows a delayed and instant region to be set similar to the Time Delay mode while retaining the Watt-Var characteristic. Depending upon the Trip Mode, additional parameters may appear on the screen: Sensitive Trip This is the minimum reverse current necessary to open the protector. The three phase average of the signed vector sum of the network voltages multiplied by the currents (VN*I*COS θ)/ VNrms must exceed the set point. Instantaneous Current This is the current that must be exceeded on one or more phases in order for the MNPR to bypass the delayed portion of time delay mode. Time Delay This is the time in seconds that the sensitive trip conditions must persist for prior to the MNPR calling for a trip in time delay mode. Extended Delay This is the time in seconds that the trip conditions must persist for prior to the MNPR calling for a trip. This applies to the Instant portion of the Time Delay mode, the Insensitive Trip, and the Delayed Watt-Var. Insensitive Trip This is the current that must be exceeded on one or more phases in order for the MNPR to open in Insensitive mode. Watt-Var Current This is the current that must be exceeded before the MNPR will rotate the trip region in Watt-Var Mode. Watt-Var Angle This is the angle that the MNPR will rotate the trip region when the Watt-Var Current is exceeded. A negative setting rotates the trip line clockwise into the first quadrant. Phase Compensation For GE relays, the phase compensation is set automatically for standard CT ratios, or manually by selecting Special for the CT Ratio setting. Standard PC values are as follows: 5 for 800:5, 1200:5, and 1600:5 10 for 2000:5 and 2500:5 15 for 3000:5 and 3500:5 8

17 You may select between the 5 additional Parameter pages by tapping on them or sliding to them (Figure 3-2). The Read, Program, Back, and Reset buttons work as they do on the Main Parameters screen. You may make changes on all six parameter screens before programming. Anti-Pump / Phase Rotation: Function Buttons Parameters change with AP Algorithm Parameter Screens Figure 3-2 AP Mode Enables one of the two Anti-Pump algorithms. Anti-Pump algorithm - If the Pump Count is exceeded within the Pump Time further closing will be inhibited for the duration of the Pump Delay which can also be set to infinite. Pump Count If Pump Count is exceeded within Pump Time further closing will be inhibited for the duration of Pump Delay. 9

18 Pump Time Time limit in Seconds for Pump Count. Pump Delay Number of seconds closing will be inhibited. Motor Cutoff This anti-pump algorithm is analogous to a bucket with a small hole in the bottom. Every time the protector closes a Close Penalty is added to the bucket. If the Upper Limit is reached the protector will not close again until the Lower Limit is reached. The hole in the bucket will leak one unit every second. Close Penalty Number of close operations. High Limit Once reached the protector will not close again until the lower level is reached. Low Limit Level at which the protector is re-enabled. Phase Rotation Sensitivity When this option is enabled the MNPR will only close if the phase rotation currently applied matches the setting. Rotation Setting Expected phase rotation. Rotation Reading Actual phase rotation. Trip On Incorrect Phase Rotation - When this option is enabled the MNPR will trip when the measured phase rotation does not match the setting. 10

19 Relaxed Close: The MNPR allows a second set of reclose parameters to be preset that can be activated for a preset amount of time (Figure 3-3). This allows a simple method to safely coerce a network protector to close by reducing the thresholds required for closing. Figure 3-3 Relaxed RV (Reclose Volts) The reclose volts setting to be used in relaxed close mode. Relaxed RA (Reclose Angle) The reclose angle setting to be used in relaxed close mode. Relaxed Ph. Offset (Phasing Offset) The phasing offset voltage that will be will be in effect after activation. Relaxed Active Time The time in seconds that the relaxed settings will be in effect after activation. 11

20 Misc. Parameters: Figure 3-4 Close Tilt Angle This setting allows the angle, in degrees, of the close characteristic to be modified. Trip Tilt Angle This setting allows the angle, in degrees, of the trip line of the sensitive trip characteristic to be modified. Sens. Trip Delay Time delay in seconds from sense to trip. Reclose Time Delay Time delay in seconds to reclose. Close Algorithm Select between Average All Phases, All Phases AND d, Average All Angle 1, Average All Angle 2, Average All Angle 3, Circle Close and All Phases OR d. 12

21 Net. Volts too Low Lower limit for valid network voltage. Phase Select Allows the phase order of the network protector to be matched to that of the MNPR. Many styles and vintages of network protectors are wired differently and it is not always the case that the MNPR s Phase 1 will be wired to the network protector s Phase A. The purpose of this setting is to allow the display of all measured per phase values in the desired order, both on the scrolling display and in the View Data screen, irrespective of the physical protector wiring. For an example of how to set this properly please see Appendix F. Care should be taken when adjusting this setting when used in conjunction with phase rotation sensitivity. The "Phase Select" setting is applied before the phase rotation is calculated and thus it could alter the rotation measured by the MNPR. Other than the phase rotation sensitivity, this setting will have no other effect on relay operation or programming. Trip Pulses The number of times the MNPR will pulse its trip contact upon calling for a trip (one second on, one second off). After the required number of pulses the contact will remain active until the network protector opens unless the parameter Trip off after Pulses is checked. A setting of zero will simply turn the output on and hold it until the network protector opens. Phasing Voltage Offset This setting allows the phasing offset on the close characteristic to be adjusted (See Figure A-1 in Appendix A). Low Voltage Trip If the three phase average of network volts falls below this threshold, the MNPR will call for a trip of the network protector. (NOTE: This setting has no effect on the Dead Network close operation of the MNPR ) Trip Contact Off After Pulses When the relay calls for a trip, the trip contact will pulse the number of times specified in the "Trip Pulses" setting. If the network protector fails to open, the contact can either be maintained or released depending on the state of this checkbox. Adjustable Dead Network If enabled, the MNPR will assert the close contact until the set point voltage is reached on any single phase. When set to "OFF", the close contact will de-assert at 13 Volts on any single phase. IOC Enable Input Selects the auxiliary input channel that the relay will monitor to determine if Instantaneous Over Current Trip is enabled. IOC Setting Sets the threshold for the non-directional overcurrent trip characteristic. 13

22 DNP3 Settings: You may setup DNP3 communications parameters on the DNP screen (Figure 3-5). This screen applies to communicating MNPRs only. Figure 3-5 DNP Address DNP3 Address of the MNPR NWP Status Input Selects the auxiliary input channel that the relay will monitor to determine the network protector status (Open/Closed) NWP Status Type Controls the sense of the selected status input channel. An "A Contact" is closed when NWP is closed. A "B Contact" is open when network protector is closed. High Voltage NWP Scaling If this box is checked, the voltages reported via DNP3 on a communicating MNPR will be scaled up by a factor to account for the potential transformers 14

23 (PT s) in the high voltage network protector. Certain versions of the MNPR firmware allow a specific PT ratio to be selected, however older versions will just display a checkbox, which will scale the voltage by a factor of 2.2 for a 277/480V network protector when selected. PT Ratio Potential Transformers (PT) ratio used for scaling DNP3 data. Zero GE Data If checked, the current (as transmitted via DNP) will be zeroed out when the network protector is open and the differential voltage (as transmitted via DNP) will be zeroed when closed. (Protector status is derived from the previously described status input. Option is available on GE relays only) Send DNP Aux Analogs as 12 bit If this box is checked, the auxiliary analog inputs will be reported as 12 bit values via DNP3. If left unchecked the data will be sent as 8 bit values. If the box is checked and the hardware only supports 8-bit inputs, the data will be shifted to 12 bit before sending. DNP Control Inhibit Input Selects the auxiliary input channel that the relay will monitor to determine if DNP control commands should be ignored (local operation of relay only) Enable Unsolicited Responses Enables the MNPR to send unsolicited response messages. Destination Address The DNP3 address that the MNPR will be sending the unsolicited response messages. Response Timeout The total length of time, in seconds, that the MNPR will wait for an acknowledgement of an unsolicited response. Comm Board Rev This is the revision of the communications and aux I/O hardware inside the MNPR. DNP Profile Version The User Version is a user provided version number that is assigned when the profile is created. It is useful for tracking different profile versions, if changes are required. DNP Profile Hash The Hash is a computer-generated signature that identifies the profile. If any changes are made to the profile it will generate a different hash. This is useful to verify that the profile in question matches the desired profile. 15

24 THIS PAGE INTENTIONALLY LEFT BLANK 16

25 Basic Setup Procedure The following describes the minimum configuration necessary to setup a MNPR. Depending upon the specific needs of the utility, this may vary. 1. Tap the Read button on the Parameters screen (Figure 3-1). This will retrieve the current MNPR s settings. 2. If unsure about the state of the MNPR, tap the Reset button on the Parameters screen to reset all of the settings to factory defaults. 3. Ensure the desired units are properly selected. (via the Settings Menu at the top of the main screen) 4. Set the CT Ratio, Trip mode and associated settings, and reclose parameters to the desired values. 5. Tap the Program button to program the MNPR. 6. Tap the Read button again, and verify that the settings programmed in step 3 are correct. 7. The relay should then be tested to verify that the trip and close characteristic perform as desired. 17

26 THIS PAGE INTENTIONALLY LEFT BLANK 18

27 Relay Status Screen Tapping the Status button on the main screen will display the Relay Status Screen (Figure 5-1). This single page contains all status information. Figure 5-1 The status screen lists various items that pertain to the operation of the MNPR. The first few display the current state of the MNPR. This is the current state of the MNPR, not the network protector. 19

28 Float The MNPR is not calling for a trip or close. The network protector should maintain its current position. Trip The MNPR is calling for a trip. Close The MNPR is calling for a close. Blocked The MNPR is blocked (using the block button on the main screen). It will not call for a close even if system conditions permit. Hard Trip The MNPR will hold the trip contact on, even if the network protector is open during a cross phase condition (if cross phase trip is enabled). Phase Angle Wrong This indicates that the reason the MNPR is not calling for a close at the moment is due to the phase angle not being inside the close region. Diff. Volts Too Low This indicates that the reason the MNPR is not calling for a close at the moment is due to the magnitude of the differential volts being below the Reclose Volts setting. Network Volts Too Low This indicates that the MNPR will not close because the three phase average of the network voltage is not exceeding the Network Volts Too Low To Close setting. Using Defaults (Reprogram) The internal memory in which the MNPR stores its operating settings has become corrupt. The MNPR is operating using the default values. You should perform a reset and reprogram the MNPR. Relaxed Close Active This box will be checked when the MNPR is currently operating using the Relaxed Close parameters. Comm Board Detected This indicates whether or not the MNPR has an internal communications board. Anti-Pump Block This indicates that the anti-pump algorithm has been triggered and the MNPR will be blocked from closing. Motor Cutoff Inhibit This indicates that the motor cutoff algorithm has been triggered and the MNPR will be blocked from closing. Phase Rotation Wrong The MNPR will not close because the phase rotation reading does not match the setting. Default DNP Profile This indicates that the MNPR is not using a custom DNP3 Profile. It will use a standard DNP Point List and manually configured parameters. (See the DNP3 Setup and DNP3 Profiles Sections for additional information) 20

29 NWP Status Closed A check in this box indicates that the Network Protection Status is closed. DNP Control Inhibit Active This indicates that the auxiliary input channel selected for the DNP Control Inhibit function is in the active state and remote commands will be ignored. IOC Monitoring (Maint. Mode) Active This indicates that the auxiliary input channel selected for the instantaneous overcurrent function is in the active state and a lockout (Trip & Block) will be initiated if the overcurrent setting is exceeded. IOC Lockout Active - This indicates that the instantaneous overcurrent setting was exceeded and a lockout (Trip & Block) was triggered. The relay will continue to issue a trip until a local unblock command is issued via the relay optical port (remote unblock via DNP will NOT override this lockout). 21

30 THIS PAGE INTENTIONALLY LEFT BLANK 22

31 Monitor: Monitor Screen The Monitor Screen displays the network voltages, differential voltages and relay currents of all three phases as well as the temperature inside the relay (Figure 6-1). Menu Items are available in the Monitor Screen to turn polling on and off and to set the display units. Function Buttons Polling Status Figure 6-1 Temperature 23

32 Current - The load current measured by network protector relay. It can be displayed in either of three units: Relay Units (shown in ma, based off the 5 Amp secondary of the network protector CT) Protector Units (shown in Amps, the actual current through the bus) Percent Units (shown as a percentage of the CT rating) For example on a protector with at 1600:5 Amp CT Ratio 2.5A (Relay Units) is equivalent to 800A (Protector Units) and 50% (Percent Units). Network Voltage The voltage measured at the relay N1, N2, N3 terminals with respect to ground. Note that on a high voltage network protector with potential transformers (PT's), this will not match the voltage on the network protector bus. Transformer Voltage Depending on the relay type, this will display one of three possibilities: 1. Not available. 2. The voltage measured at the relay T1, T2, T3 terminals with respect to ground. Note that on a high voltage network protector with potential transformers (PT's) this will not match the voltage on the network protector bus. 3. The network voltage + the differential voltage. This will be equivalent to the transformer voltage assuming the differential voltage does not reach its maximum value (about 18V on a Westinghouse style relay). Differential Voltage On a Westinghouse style relay, this is the real part (multiplied by the cosine of the angle) of the voltage difference measured between the relay s N and T pins. On a GE style relay, this value is obtained by measuring the current produced through a tertiary winding on the network protector CT, which is proportional to the difference between the N and T bus. Note that this quantity will not match the voltage difference measured by a voltmeter placed across the relays N and T pins. Diff Voltage Magnitude On a Westinghouse style relay, this is the voltage difference measured between the relay N and T pins. Note that on a high voltage network protector with potential transformers (PT s) this will not match the voltage difference measured across the network protector. On a GE style relay this value is obtained by measuring the current produced through a tertiary winding on the network protector CT, which is proportional to the difference between the N and T bus. 24

33 Phase Angle Depending on the state of the network protector (open/closed) this will either show the angle between the network voltage and differential voltage or the angle between the network voltage and current. Relay Temp Internal Relay Temperature. You may select degrees Celsius or Fahrenheit (Figure 6-1). Function Buttons: Read Performs a single read of the MNPR Start Poll Turn the continuous polling feature on and off (Figure 6-1). Polling does not commence until the Polling button is pressed and switched to On. Stop Poll The Start Poll button changes to the Stop Poll button during automatic polling. Tapping the Stop Poll button halts periodic polling. 25

34 Aux I/O: The Auxiliary I/O screen contains readings from various analog and digital sensors. Note: The number of inputs and outputs is dependent upon the specific hardware. Analog Input Readings Digital Output Controls Digital Input and Output Status Figure 6-2 A1 A8 Analog input readings. DI1 DI4 A check mark appears in the box if the corresponding digital input is on. DO1 DO3 A check mark appears in the box if the corresponding digital output is activated. Digital outputs are activated by tapping the corresponding control buttons. 26

35 View Waveforms Tapping the Waves button on the main screen will display the Waveforms (Figure 7-1). Figure 7-1 Read Current Reads the stored current waveforms from the MNPR and displays them. Note: Network voltage is retrieved as well. Read Diff Reads the stored differential voltage waveforms from the MNPR and displays them. V Net 1, V Net 2, V Net 3, V Diff 1, V Diff 2, V Diff 3, I 1, I 2, I 3 These check boxes determine which wave sources are displayed in the graph. 27

36 THIS PAGE INTENTIONALLY LEFT BLANK 28

37 Operations The Operations screen allows manual control over the relay (Figure 8-1). Figure 8-1 Relaxed Close Causes the MNPR to operate from its relaxed close parameters (see the Relaxed Closed settings in the Parameters section described on pages 11-12). Block Blocks (prevents) the relay from tripping. Unblock Removes the block and allows normal operation. Trip Manually trips the relay. 29

38 A confirmation screen will appear before any operation will occur (Figure 8-2) and a message at the bottom of the screen will verify that the operation took place as expected. Figure

39 Help/Info The Help/Info page displays pinouts of the Westinghouse style and GE style MNPR s. You may also review them in Appendix B. Figure

40 THIS PAGE INTENTIONALLY LEFT BLANK 32

41 Troubleshooting If at any time a Communication Failure message is displayed verify the following: - The MNPR is powered, either with a power block or by being installed in an energized network protector. - The Bluetooth module is securely attached and paired to the Android device and its LED is illuminated. - The Bluetooth adapter contains a 9V battery for power. Sometimes the Status LED will come on even when the battery is too exhausted to power the communications. When replacing the 9V battery be sure to note the position of the battery cover before removing it from the adapter so that the orientation will be correct when reinstalled (Figure 9-1). Battery Cover Status LED Power button Figure Ensure that the optical head is oriented correctly on the MNPR. The ETI logo on the label should face the top of the MNPR (the top is the side closest to the optical port). (Note that in some network protectors the MNPR may be mounted sideways) - When Commander is communicating with the MNPR the words Remote Login should be scrolling on the display of the MNPR - Check the window covering the optics on the relay. If it is dirty, oily, scratched, chipped, or compromised in any way communications could be severed. Try wiping it off with a clean cloth. Any glass cleaner can also be applied to the window. Also check the optics on the module for similar problems. 33

42 THIS PAGE INTENTIONALLY LEFT BLANK 34

43 Appendix A. MNPR Characteristics Figure A-1 - Reclose Characteristic 35

44 Figure A-2 - Circle Close Characteristic 36

45 Figure A-3 - Sensitive Trip Characteristic (Low Current Region) NOTES: 1. Divisions are in percentage of 5 amp Current Transformer rating. 37

46 Figure A-4 - Sensitive Trip Characteristic (High Current Region) 38

47 Figure A-5 - Time Delay Trip Characteristic 39

48 Figure A-6 - Insensitive Trip Characteristic 40

49 Figure A-7 - WattVar Trip Characteristic (WA=-60 ) 41

50 Figure A-8 - Inverse WattVar Trip Characteristic (WA=+60 ) 42

51 Figure A-9 - Delayed Watt-Var Characteristic 43

52 THIS PAGE INTENTIONALLY LEFT BLANK 44

53 Appendix B. MNPR Pinouts Figure B-1 - WH Relay Figure B-2 - GE Relay 45

54 THIS PAGE INTENTIONALLY LEFT BLANK 46

55 Appendix C. MNPR Default DNP3 Profile An MNPR with DNP3 profile support that does not have a valid profile loaded will use the following default profile. NOTE: All currents listed under Analog Inputs are in NWP Bus Amps. All currents listed under Analog Outputs are in Relay ma. All Scale Factors are multipliers. Analog Inputs Index Description Class Deadband Scale Factor 0 Reclose Volts Reclose Angle Sensitive Trip (Bus Amps) Time Delay Instant Trip (Bus Amps) Insensitive Trip (Bus Amps) CT Phase Compensation Extended Delay Reclose Time Delay Sensitive Trip Delay I1 (Bus Amps) I2 (Bus Amps) I3 (Bus Amps) VN VN VN Diff Volts Diff Volts Diff Volts Current Angle Current Angle Current Angle Analog Analog Analog Analog Relay Temperature Relay Cycle Counter Relay Serial Number Version Comm S/W Version

56 Analog Inputs (continued) Index Description Class Deadband Scale Factor 32 KW KW KW Kvar Kvar Kvar KVA KVA KVA Total KW Total Kvar Total KVA Analog Analog Analog Analog Differential Angle Differential Angle Differential Angle Differential Magnitude Differential Magnitude Differential Magnitude Trip Tilt Angle Close Tilt Angle Zero Currents on open GE Relay VT VT VT Static Analog Inputs Variation 0x01 Analog Events Variation 0x01 48

57 Analog Outputs Index Description Scale Factor 0 Reclose Volts Reclose Angle 1 2 Sensitive Trip (Relay ma) Time Delay 10 4 Instant Trip (Relay Amps) Insensitive Trip (Relay Amps) CT Phase Compensation 1 8 Extended Delay 1 9 Reclose Time Delay 1 10 Sensitive Trip Delay 1 Digital Inputs Index Description Class 1 Factory Defaults 1 2 Network Volts Too Low To Close 1 5 Watt-Var Trip Mode 1 6 Time Delay Trip Mode 1 7 Insensitive Trip Mode 1 8 Phase Angle Wrong for Closing 1 9 Differential Volts Too Low to Close 1 10 Digital Input Digital Input Digital Output Digital Output Blocked from Closing 1 16 GE Style Relay 1 17 Float 1 18 Calling for Trip 1 19 Calling for Close 1 20 Breaker Status 1 21 Relaxed Close Active 1 22 Digital Input Digital Input Failure to Close 1 25 Failure to Trip 1 Static Digital Inputs Variation 0x01 Digital Events Variation 0x02 49

58 Digital Outputs (CROB) Index Code Description 0 Trip Trip Relay 0 Close Trip Relay 1 Trip Block Relay 1 Close Block Relay 2 Trip Auto 2 Close Auto 3 Trip Open Digital Output 1 3 Close Close Digital Output 1 4 Trip Open Digital Output 2 4 Close Close Digital Output 2 5 Trip Program Relay Settings 5 Close Program Relay Settings 6 Trip Clear Relay Settings Buffer 6 Close Clear Relay Settings Buffer 7 Trip Activate Relaxed Close 7 Close Activate Relaxed Close 8 Trip De-activate Relaxed Close 8 Close De-activate Relaxed Close Functions Select Before Operate Direct Operate Direct Operate, No Acknowledge 50

59 Appendix D. MNPR Aux I/O Pinouts 51

60 52

61 53

62 54

63 55

64 56

65 57

66 58

67 59

68 60

69 Appendix E. Pairing the Bluetooth Module with the ios device The ETI Bluetooth Module is used in conjunction with an ios device and ETI s Commander Software to wirelessly setup and troubleshoot an ETI MNPR. Note: The Bluetooth Module will not work with ios devices. The must be used. 1. Power on the Bluetooth module by pressing the pushbutton on the left side. The blue light on the right side will begin flashing. This indicates that the module is waiting for a connection. The module will remain on for 15 minutes after the last communication with the relay. There is no way to manually turn the module off. In the event that the blue light fails to turn on when the button is pressed, replace the 9V battery under the cover (remove the 4 screws for access and be careful to note the orientation of the cover so it may be replaced the same way). 2. Place the Bluetooth module over the optical window on the MNPR as shown below (MNPR must be powered). Serial Number Push Power button Figure E-1 61

70 4. Make sure Bluetooth is enabled on the ios device by checking for the Bluetooth icon in the upper right status bar (Figure E-2). If absent, enable Bluetooth by swiping up from the bottom of the screen to open the Control Panel (Figure E-3). Tap the Bluetooth icon so that it illuminates blue. Now open the ETI Commander app. Bluetooth Enabled Icon Figure E-2 Control Panel View Bluetooth On/Off Button Swipe up to open Control Panel Figure E-3 62

71 5. Pair the ios device and Bluetooth module by initiating a Read action from any screen (such as the Parameters or Status screens). 6. A window will appear asking if you want to search for a bluetooth module (Figure E-4). Tap Yes and it will show nearby active Bluetooth modules (Figure E-5). Maximum wireless range is feet. Figure E-4 Figure E-5 7. Select the ETI OPTO device with the matching serial number by tapping it. 63

72 8. The currently paired module will be noted on the app s main screen (Figure E-6). It will remain paired as long as Bluetooth is enabled and the module is within range. If the link is broken (such as moving out of range) you will have to find the module again as in steps 5 & 6 the next time you want to connect. If you want to pair with a different Bluetooth module, open the Control Panel as in step 4 and toggle Bluetooth off and on again. This will end any current pairing. Currently paired Bluetooth module Figure E-6 64

73 10. Commander is now ready to be used. Go to the Parameters screen and press Read (Figure E- 7). Read button Figure E-7 65

74 THIS PAGE INTENTIONALLY LEFT BLANK 66

75 Appendix F. Phase Select Details The Phase Select setting found in the Advanced settings menu allows the phase order of the network protector to be matched to that of the MNPR. Many styles and vintages of network protector are wired differently and it is not always the case that the MNPR s Phase 1 will be wired to the network protector s Phase A. The purpose of this setting is to allow the display of all measured per phase values in the desired order, both on the scrolling display and in the View Data screen, irrespective of the physical protector wiring. Care should be taken when adjusting this setting when used in conjunction with phase rotation sensitivity. The "Phase Select" setting is applied before the phase rotation is calculated and thus it could alter the rotation measured by the MNPR. Other than the phase rotation sensitivity, this setting will have no other effect on relay operation or programming. Referring to the partial Westinghouse network protector schematic shown in Figure H-1, it can be seen that the wiring from the left bus bar goes to the MNPR s Phase C input, the middle bus bar goes to the Phase A input, and the right bus bar goes to the Phase B input. In this example, in order for the MNPR to display the phases in the proper left to right order, the Phase Select should be set to CAB. Figure F-1 67

ETI COMMANDER MNPR INTERFACE SOFTWARE FOR ANDROID

ETI COMMANDER MNPR INTERFACE SOFTWARE FOR ANDROID ETI COMMANDER MNPR INTERFACE SOFTWARE FOR ANDROID Instruction Manual Revision 3 ETI Electronic Technology Incorporated 511 Lyons Avenue, Irvington, NJ 07111 (973) 371-5160 FAX (973) 371-1929 www.eti-nj.com

More information

ETI ETI FIELDPRO MNPR INTERFACE SOFTWARE. Instruction Manual Revision 19

ETI ETI FIELDPRO MNPR INTERFACE SOFTWARE. Instruction Manual Revision 19 ETI 521125 FIELDPRO MNPR INTERFACE SOFTWARE Instruction Manual Revision 19 ETI Electronic Technology Incorporated 511 Lyons Avenue, Irvington, NJ 07111 (973) 371-5160 FAX (973) 371-1929 www.eti-nj.com

More information

MNPR Programmer Manual

MNPR Programmer Manual MNPR Programmer Manual IM 7385-002 January 4, 2000 I. Introduction Congratulations! You have purchased the ETI MNPR Microprocessor Network Protector Relay and Programmer. The MNPR is the most advanced

More information

DNP Points List and Implementation for Universal Controls

DNP Points List and Implementation for Universal Controls S&C 6800 Series Automatic Switch Control DNP Points List and Implementation for Universal Controls Table of Contents Section Page Section Page DNP Points List for 6801 Universal Controls...1 6801 Status

More information

DNP Points List and Implementation

DNP Points List and Implementation S&C 6800 Series Automatic Switch Control DNP Points List and Implementation Table of Contents Section Page Section Page DNP Points List for 6801 Controls...1 6801 Status Points...2 6801 Double-bit Status

More information

DNP Points List and Implementation

DNP Points List and Implementation S&C IntelliCap Plus Automatic Capacitor Control DNP Points List and Implementation Table of Contents Section Page Section Page DNP Points List for IntelliCap Plus Controls...1 Status Points....2 Analog

More information

Auto-Sectionalizing Firmware Product Description, Information and Specification

Auto-Sectionalizing Firmware Product Description, Information and Specification g GE Energy Services Product Description, Information and Specification Document Number : PRPI-023 Version : 3.00 Revision : 2 Date : 03.02.10 Classification: GE Energy Services NOTICE OF COPYRIGHT & PROPRIETARY

More information

DENT Instruments ELITEpro Mobile App

DENT Instruments ELITEpro Mobile App DENT Instruments ELITEpro Mobile App Version 3.0 Instruction Guide Revision: Final Draft May 20, 2015 Page 2 of 16 Instruction Guide: ELITEpro Mobile App 2015 DENT Instruments, Inc. All rights reserved.

More information

DNP3 Communications Protocol

DNP3 Communications Protocol Powermeter and Power Quality Analyzer PM174 DNP3 Communications Protocol Reference Guide BG0413 Rev. A3 Every effort has been made to ensure that the material herein is complete and accurate. However,

More information

Abstract. GLV User Manual 1

Abstract. GLV User Manual 1 GLV User Manual 1 Abstract This user manual is a high level document that explains all operational procedures and techniques needed to operate the GLV system in a safe and effective manner. Anyone operating

More information

PFC-10 Power Factor Controller

PFC-10 Power Factor Controller PFC-10 Power Factor Controller Instruction Manual Ver. 6.0 / 2002 (2-2005 update) Table of Contents Page Subject 3 Starter ion 4-5 Installation Notes 6-7 Terminals Review & Control Wiring 8 Front-panel

More information

PG&E Points List for Universal Controls

PG&E Points List for Universal Controls S&C 6800 Series Automatic Switch Control PG&E Points List for Universal Controls Table of Contents Section Page Section Page PG&E Points List for 6802/3 Universal Controls. 1 Response Limit...2 6802/3U

More information

Series 3000 User Manual and Product Features

Series 3000 User Manual and Product Features Series 3000 User Manual and Product Features PN: OXA3501-890000 Revision 1.0 Technical Specifications 1.1 Model Number Description 1. Meter Series S3 Series 3000 meter Figure 1: Series 3000 model number

More information

DNP Points List and Implementation

DNP Points List and Implementation S&C IntelliRupter PulseCloser Fault Interrupter Outdoor Distribution (15.5 kv, 27 kv, and 38 kv) DNP Points List and Implementation Table of Contents Section Page Section Page Introduction...1 Status Points...2

More information

EnCell Battery Cell Monitor

EnCell Battery Cell Monitor EnCell Battery Cell Monitor Instruction Manual Model RCM15S12 NERC Compliant YO R U H T PA TO Z O R E W O D N M I T E enchargepowersystems.com sales@enchargepowersystems.com (888) 407.5040 Contents 1 Warnings,

More information

IntelliCAP PLUS Supplement for Landis & Gyr Telegyr 8979 Protocol

IntelliCAP PLUS Supplement for Landis & Gyr Telegyr 8979 Protocol IntelliCAP PLUS Supplement for Landis & Gyr Telegyr 8979 Protocol March 31, 2003 1135 Atlantic Avenue Alameda, California USA 1023-563 / 3-31-03 IntelliCAP PLUS Capacitor Control Proprietary Notice This

More information

Instruction Manual. ROYTRONIC EXCEL Series AD9 Programming Guide Electronic Metering Pumps

Instruction Manual. ROYTRONIC EXCEL Series AD9 Programming Guide Electronic Metering Pumps Instruction Manual ROYTRONIC EXCEL Series AD9 Programming Guide Electronic Metering Pumps For file reference, please record the following data: Model No: Serial No: Installation Date: Installation Location:

More information

Quick Start Guide TS A

Quick Start Guide TS A Quick Start Guide TS 930 125-630A DANGER HAZARD OF ELECTRICAL SHOCK, EXPLOSION, OR ARC FLASH Read and understand this quick start guide before installing and operating the transfer switch The installer

More information

Source-Transfer Application Guide

Source-Transfer Application Guide S&C Model 6802 Automatic Switch Control Source-Transfer Application Guide Table of Contents Section Page Section Page Introduction Qualified Persons.... 2 Read this Instruction Sheet.... 2 Retain this

More information

CRAGG RAILCHARGER Instruction Manual for 10DTC-12V 20DTC-12V 30DTC-24V 40DTC-12V 60DTC-12V

CRAGG RAILCHARGER Instruction Manual for 10DTC-12V 20DTC-12V 30DTC-24V 40DTC-12V 60DTC-12V CRAGG RAILCHARGER for 10DTC-12V 20DTC-12V 30DTC-24V 40DTC-12V 60DTC-12V Contents 1 Warnings, Cautions, and Notes... 1 2 Description... 2 3 Features... 2 3.1 STANDARD FEATURES... 2 3.2 CHARGER REGULATION...

More information

750/760 Feeder Management Relay Instruction Manual

750/760 Feeder Management Relay Instruction Manual GE Digital Energy 750/760 Feeder Management Relay Instruction Manual Software Revision: 7.4x Manual P/N: 1601-0120-AK Manual Order Code: GEK-106471T GE Digital Energy 650 Markland Street Markham, Ontario

More information

SDR recloser. A PH Fault B PH Fault C PH Fault. Ground Fault. SGF Lockout Aux Power OK. Recloser OK

SDR recloser. A PH Fault B PH Fault C PH Fault. Ground Fault. SGF Lockout Aux Power OK. Recloser OK SDR recloser A PH Fault B PH Fault C PH Fault Ground Fault SGF Lockout Aux Power OK Recloser OK Open Close Reclose ON Hot Line Tag ON All Protn OFF Inst Protn OFF Ground Fault Protn OFF SGF Protn OFF Trip

More information

Comm. RS-232. Analog I/O I N P U T S O U T P U T S. I/O Supply. Logic Supply RET RET Fault

Comm. RS-232. Analog I/O I N P U T S O U T P U T S. I/O Supply. Logic Supply RET RET Fault Model 2220 Analog Input / Output Module Installation Guide 2701E 2203 I/O Supply Logic Supply Fault 1 5 9 13 I N P U T S 2220 Digital Out 02 04 06 08 RET RET +24 +24 Out1 Out4 Out5 Out8 Comm. RS-232 1

More information

PSM-Mobile User s Manual

PSM-Mobile User s Manual 7/23/09 PSM-Mobile User s Manual Contents PSM-Mobile User s Manual...1 Introduction...1 Getting Started (Installing / Starting PSM-Mobile)...2 Free 30 Day Trial...3 PSM-Mobile Main Screen...3 PSM-Mobile

More information

Technical Specifications. Multi Function Meter

Technical Specifications. Multi Function Meter Technical Specifications of Multi Function Meter (SPM300) Class 0.5S Sai PowerrZerve 29/3B, Rajalakshmi Nagar, 1 st Main Road, Velachery Bye Pass, Chennai 600 042. Website :www.spowerz.com Email : info@spowerz.com

More information

DNP Points List and Implementation for the 6802 Vista Control

DNP Points List and Implementation for the 6802 Vista Control S&C 6800 Series Automatic Switch Control DNP Points List and Implementation for the 6802 Vista Control Table of Contents Section Page Section Page DNP Points List for 6802 Vista Control...1 6802 Status

More information

UR Universal Relay Series

UR Universal Relay Series GE Digital Energy UR Universal Relay Series Revision 4.43 Release Notes GE Publication Number: GER-4380Rev1 Copyright 2010 GE Multilin Summary Overview GE Multilin issues the UR 4.43 release that introduces

More information

MultiCube Single Phase Multi-Function Electricity Meter. Installation and Operation

MultiCube Single Phase Multi-Function Electricity Meter. Installation and Operation MultiCube Single Phase Multi-Function Electricity Meter Installation and Operation PREFACE MultiCube Single Phase Meter Operating Guide Revision 5.01 August 2002 This manual represents your meter as manufactured

More information

BE1-50/51M TIME OVERCURRENT RELAY ADVANTAGES

BE1-50/51M TIME OVERCURRENT RELAY ADVANTAGES BE1-50/51M TIME OVERCURRENT RELAY The BE1-50/51M Time Overcurrent Relay provides economical overload and fault protection for generators, transformers, lines and motors. ADVANTAGES Self powered from 50/60Hz

More information

NEW ERA METER. Installation & Operation Guide NE METER

NEW ERA METER. Installation & Operation Guide NE METER NEW ERA METER Installation & Operation Guide NE METER Autoranging Power Supply Installation Diagnostics Per Phase Voltage & Current kwh, Demand and TOU 0.2% Accuracy -40 C to +85 C Watertight Enclosure

More information

Athena Series RMC Hot Runner Controller Configuration and Operation Manual

Athena Series RMC Hot Runner Controller Configuration and Operation Manual Athena Series RMC Hot Runner Controller Configuration and Operation Manual Athena and CompuStep are registered trademarks, and Multi-Comm and SafeChange are trademarks of Athena Controls, Inc. MODBUS is

More information

Installation, Operation and Maintenance Manual

Installation, Operation and Maintenance Manual Document 481200 VGD-100 Vari-Green Drive Installation, Operation and Maintenance Manual Please read and save these instructions for future reference. Read carefully before attempting to assemble, install,

More information

GE Entellisys Low Voltage Switchgear. System Test Kit. User Manual

GE Entellisys Low Voltage Switchgear. System Test Kit. User Manual GE Entellisys Low Voltage Switchgear System Test Kit User Manual DEH-233 Warnings, Cautions, and Notes as used in this publication Warnings WARNING! Warning notices are used in this publication to emphasize

More information

Technical Specifications. Dual Source Energy Meter (EB / DG)

Technical Specifications. Dual Source Energy Meter (EB / DG) Technical Specifications of Dual Source Energy Meter (EB / DG) (SPMG300) Class 0.5S Sai PowerrZerve 29/3B, Rajalakshmi Nagar, 1 st Main Road, Velachery Bye Pass, Chennai 600 042. Website :www.spowerz.com

More information

Copyright: December 2017 Nidec Issue: E

Copyright: December 2017 Nidec Issue: E General Information The manufacturer accepts no liability for any consequences resulting from inappropriate, negligent or incorrect installation or adjustment of the optional parameters of the equipment

More information

WARNING!!!!!!!!! IMPORTANT INFORMATION: READ BEFORE INSTALLATION!

WARNING!!!!!!!!! IMPORTANT INFORMATION: READ BEFORE INSTALLATION! V_Net Relay Module Installation Instructions: Part Number: 230-VM-RELAY WARNING!!!!!!!!! IMPORTANT INFORMATION: READ BEFORE INSTALLATION! The relay outputs of the 230-VM-RELAY module may turn on when not

More information

Contents 1 Warnings, Cautions, and Notes Description Features... 1

Contents 1 Warnings, Cautions, and Notes Description Features... 1 EnCell Contents 1 Warnings, Cautions, and Notes... 1 2 Description... 1 3 Features... 1 3.1 STANDARD FEATURES... 1 3.2 FRONT PANEL FEATURES... 2 3.2.1 Display... 2 3.2.2 OK LED... 2 3.2.3 FAULT LED...

More information

RGM180 Display Series

RGM180 Display Series Quick Start Guide RGM180 Display Series BG0509 REV.A2 RGM180 QUICKSTART LIMITED WARRANTY The manufacturer offers the customer a 24-month functional warranty on the instrument for faulty workmanship or

More information

ESC 201. Installation and Operating Instructions Manual. SG Jan 2015

ESC 201. Installation and Operating Instructions Manual. SG Jan 2015 ESC 201 Installation and Operating Instructions Manual SG-0002-03 Jan 2015 Table of Contents 1.0 FUNCTIONS... 5 2.0 FEATURES... 5 3.0 ESC 201 DESCRIPTION... 6 4.0 GENERAL OPERATIONS... 6 4.1 MANUAL MODE

More information

MiCOM P122C Time-Overcurrent Protection

MiCOM P122C Time-Overcurrent Protection Protection Relays 01 MiCOM P122C Time-Overcurrent Protection Customer Benefits 1A/5A software setting 4 function keys Compact unit for flush and wall-surface mounting Comprehensive measurements Disturbance

More information

MPU-32 ETHERNET/IP INTERFACE

MPU-32 ETHERNET/IP INTERFACE 3714 Kinnear Place Saskatoon, SK Canada S7P 0A6 Ph: (306) 373-5505 Fx: (306) 374-2245 www.littelfuse.com/relayscontrols ETHERNET/IP INTERFACE Revision 0-A-051314 Copyright 2014 Littelfuse Startco All rights

More information

Quantum HD Release Notes

Quantum HD Release Notes Quantum HD Release Notes OS Version 10.17 Released 7-14-2014 To upgrade to OS version 10.17 directly the current OS version must be 10.13 through 10.16. To check the current OS version on the Quantum HD

More information

Models beginning with 2M, 2L or 2X. Product Description. Technical Specifications. Installation Instructions. Series 2000 Multiple Meter Units (MMUs)

Models beginning with 2M, 2L or 2X. Product Description. Technical Specifications. Installation Instructions. Series 2000 Multiple Meter Units (MMUs) Models beginning with 2M, 2L or 2X Series 2000 Multiple Meter Units (MMUs) Product Description Technical Specifications Installation Instructions February 28 th, 2013 List of Figures...2 List of Tables...2

More information

FX2-CHILLER. Digital Control. Operations Manual

FX2-CHILLER. Digital Control. Operations Manual FX2-CHILLER Digital Control Operations Manual Micro Air Corporation Phone (609) 259-2636 124 Route 526 www.microair.net Allentown NJ 08501 Fax (609) 259-6601 Introduction: The FX2-CHILLER digital control

More information

FP5000. Refer to for the latest information on this constantly evolving product

FP5000. Refer to  for the latest information on this constantly evolving product FP5000 Refer to www.eatonelectrical.com for the latest information on this constantly evolving product FP5000 Product Overview Microprocessor design combines protection, metering and control into a single

More information

INSTRUCTION MANUAL STATION CONTROLLER SC1000 MOTOR PROTECTION ELECTRONICS, INC.

INSTRUCTION MANUAL STATION CONTROLLER SC1000 MOTOR PROTECTION ELECTRONICS, INC. INSTRUCTION MANUAL STATION CONTROLLER SC1000 MOTOR PROTECTION ELECTRONICS, INC. 2464 Vulcan Road, Apopka, Florida 32703 Phone: (407) 299-3825 Fax: (407) 294-9435 Revision Date: 9-11-08 Applications: Simplex,

More information

UR Universal Relay Series

UR Universal Relay Series GE Digital Energy UR Universal Relay Series Revision 3.50 Release Notes GE ublication Number: GER-4432 Copyright 2009 GE Multilin Overview Summary GE Multilin issues the UR 3.50 release that introduces

More information

Technical Specificaions. kwh Energy Meter

Technical Specificaions. kwh Energy Meter Technical Specificaions of kwh Energy Meter (SPK301) Class 1.0S Sai PowerrZerve 29/3B, Rajalakshmi Nagar, 1 st Main Road, Velachery Bye Pass, Chennai 600 042. Website :www.spowerz.com Email : info@spowerz.com

More information

ENVIRORANGER ERS 500 NVIRORANGER ERS 500 USER GUIDE. Instruction Manual PL-600 January Rev. 1.2

ENVIRORANGER ERS 500 NVIRORANGER ERS 500 USER GUIDE. Instruction Manual PL-600 January Rev. 1.2 ENVIRORANGER ERS 500 USER GUIDE Instruction Manual PL-600 January 2001 33456000 Rev. 1.2 NVIRORANGER ERS 500 Safety Guidelines Warning notices must be observed to ensure personal safety as well as that

More information

QCPort Cover Control Trouble Shooting Guide

QCPort Cover Control Trouble Shooting Guide QCPort Cover Control Trouble Shooting Guide Technical Document Feb. 2006 Page 1 of 14 QCPort Cover Control Description Door Defeater Address/Options Bucket Latch Breaker Actuator Hasp Lock Keypad Overlay

More information

DEH-433. Warnings, Cautions, and Notes as used in this publication

DEH-433. Warnings, Cautions, and Notes as used in this publication DEH-433 Warnings, Cautions, and Notes as used in this publication Warnings WARNING! Warning notices are used in this publication to emphasize that hazardous voltages, currents, or other conditions that

More information

BE1-51 BE1-51/27C BE1-51/27R TIME OVERCURRENT RELAY

BE1-51 BE1-51/27C BE1-51/27R TIME OVERCURRENT RELAY BE1-51 BE1-51/27C BE1-51/27R TIME OVERCURRENT RELAY The BE1-51 Series of Time Overcurrent Relays is microprocessor-based to provide versatile overload and fault protection on 50Hz or 60Hz systems. ADVANTAGES

More information

D115 The Fast Optimal Servo Amplifier For Brush, Brushless, Voice Coil Servo Motors

D115 The Fast Optimal Servo Amplifier For Brush, Brushless, Voice Coil Servo Motors D115 The Fast Optimal Servo Amplifier For Brush, Brushless, Voice Coil Servo Motors Ron Boe 5/15/2014 This user guide details the servo drives capabilities and physical interfaces. Users will be able to

More information

INTELLIGENT ENERGY / POWER METER OPERATING GUIDE VERSION 3 MAY, 2013

INTELLIGENT ENERGY / POWER METER OPERATING GUIDE VERSION 3 MAY, 2013 INTELLIGENT ENERGY / POWER METER OPERATING GUIDE VERSION 3 MAY, 2013 For the EnGenius User Manual, visit www.kele.com/engenius and click on the Related Documents tab. Operating Guide EnGenius Intelling

More information

Dryer. M720 Programming and Operation Manual. July 15, 2015 Revision 1.51

Dryer. M720 Programming and Operation Manual. July 15, 2015 Revision 1.51 Dryer M720 Programming and Operation Manual July 15, 2015 Revision 1.51 Contents 1 Important Safety Information 1 1.1 FOR YOUR SAFETY - CAUTION!............................. 1 2 Control Overview 2 2.1

More information

SELECTRONIX, INC. SUPERSTEP SERIES 4000 SEQUENCING STEP CONTROLLERS WOODINVILLE, WA INSTALLATION & OPERATING ADDENDUM LOAD LIMIT INPUT CONFIGURATIONS

SELECTRONIX, INC. SUPERSTEP SERIES 4000 SEQUENCING STEP CONTROLLERS WOODINVILLE, WA INSTALLATION & OPERATING ADDENDUM LOAD LIMIT INPUT CONFIGURATIONS SELECTRONIX, INC. WOODINVILLE, WA SUPERSTEP SERIES 4000 SEQUENCING STEP CONTROLLERS INSTALLATION & OPERATING ADDENDUM LOAD LIMIT INPUT CONFIGURATIONS Rev 03/10/19 2 1 Various DC Voltage - 100 % Load Limit

More information

Firmware Manual - EC Series Drives

Firmware Manual - EC Series Drives 1 Firmware Manual - EC Series Drives Doc Ver 1.01 Firmware ver: EC series drives For installation details refer to Hardware Manual Safety: Read safety instruction in hardware manual before installation

More information

FP6000. Type ID Units Writable Possible Values. Count. TCP Register

FP6000. Type ID Units Writable Possible Values. Count. TCP Register FP6000 Category System ID 1032 Vendor Name 32 ASCII no-units 1064 Model Name 32 ASCII no-units 1096 Display Name 32 ASCII no-units 1128 Device Type 32 ASCII no-units 1605 Field Replaceable Unit 1 UINT16

More information

Application Note (Revision NEW) Original Instructions. EGCP-2 Differences

Application Note (Revision NEW) Original Instructions. EGCP-2 Differences Application Note 51199 (Revision NEW) Original Instructions General Precautions Read this entire manual and all other publications pertaining to the work to be performed before installing, operating, or

More information

II. Programming and Adjustments

II. Programming and Adjustments - 35 - Dip es i) Dip for the M-17/27 combination relay box Dip switches are located inside most control boxes and are used to set, enable, or disable various electronic functions operated through the control

More information

7SR242 Duobias Multi-Function 2-Winding Transformer Protection Relay

7SR242 Duobias Multi-Function 2-Winding Transformer Protection Relay 7SR242 Duobias Multi-Function 2-Winding Transformer Protection Relay Document Release History This document is issue 2010/06. The list of revisions up to and including this issue is: 2010/06 Additional

More information

Substation Automation Products. Generator protection REG670/650 Relion 670 and 650 series

Substation Automation Products. Generator protection REG670/650 Relion 670 and 650 series Substation Automation Products Generator protection REG670/650 Relion 670 and 650 series A new protection standard for your valuable assets Based on ABB s extensive experience, REG670 and REG650 IEDs (Intelligent

More information

1 Description of Methodology for Volt / Var Optimization

1 Description of Methodology for Volt / Var Optimization Methodology for Volt / Var Optimization on a Substation Basis May 13th, 2011 Version 1.7 1 Methodology for Volt / Var Optimization (VVO) on a Substation Basis This use case discusses how the utility will

More information

GV3000/SE General Purpose (Volts/Hertz) and Vector Duty AC Drive, HP, 230V AC

GV3000/SE General Purpose (Volts/Hertz) and Vector Duty AC Drive, HP, 230V AC Software Start-Up and Reference Manual D2-3416-2 GV3000/SE General Purpose (Volts/Hertz) and Vector Duty AC Drive, 30-100 HP, 230V AC Version 6.04 Important User Information Solid-state equipment has operational

More information

USER MANUAL 2012 V1.1

USER MANUAL 2012 V1.1 SMART MINI POWER SDM630 USER MANUAL 2012 V1.1-1 - Installation and Operation Instructions Important Safety Information is contained in the Maintenance section. Familiarise yourself with this information

More information

UR Universal Relay Series

UR Universal Relay Series GE Digital Energy UR Universal Relay Series Revision 5.03 Release Notes GE Publication Number: GER-4328 Copyright 2008 GE Multilin Overview Summary GE Multilin issues the UR 5.03 release that introduces

More information

Installation & Operation and Maintenance

Installation & Operation and Maintenance Gas Safety Products Dual Current Monitor Installation & Operation and Maintenance Read these instructions carefully before operating or servicing Rev: 01 Date: 12-02-18 1 CONTENTS Chapter Content Page

More information

Safety Instructions 1-1 Avoid unintended Start General Description 2-2

Safety Instructions 1-1 Avoid unintended Start General Description 2-2 Contents Contents 1 Safety and precautions 1-1 Safety Instructions 1-1 Avoid unintended Start. 1-1 2 Introduction 2-1 General Description 2-2 3 Supported Configuration 3-1 Introduction 3-1 Fixed-speed

More information

HGM9580 Bus Tie Bus Parallel Unit USER MANUAL. Smartgen Technology

HGM9580 Bus Tie Bus Parallel Unit USER MANUAL. Smartgen Technology HGM9580 Bus Tie Bus Parallel Unit USER MANUAL Smartgen Technology This manual is suitable for HGM9580 bus tie bus parallel unit only. Clarification of notation used within this publication. SIGN INSTRUCTION

More information

UCL & Color Logic. 4.0 LEDs. Installation Guide. LxCUSxxxxx, SP05xxLEDxxx & SP05xxSLEDxxx. Universal ColorLogic ColorLogic. 4.

UCL & Color Logic. 4.0 LEDs. Installation Guide. LxCUSxxxxx, SP05xxLEDxxx & SP05xxSLEDxxx. Universal ColorLogic ColorLogic. 4. UCL & Color Logic 4.0 LEDs Installation Guide Universal ColorLogic ColorLogic 4.0 LEDs Universal CrystaLogic LxCUSxxxxx, SP05xxLEDxxx & SP05xxSLEDxxx Copyright 2014 Hayward Industries Table of Contents

More information

DRTS 64. The new generation of advanced test equipment for Relays, Energy meters, Transducers and Power quality meters.

DRTS 64. The new generation of advanced test equipment for Relays, Energy meters, Transducers and Power quality meters. The new generation of advanced test equipment for Relays, Energy meters, Transducers and Power quality meters Testing all relay technologies: electromechanical, solid state, numerical and IEC61850 Manual

More information

ETI. Renewal Parts Catalog. 313NP Network Protector

ETI. Renewal Parts Catalog. 313NP Network Protector ETI ELECTRONIC TECHNOLOGY INCORPORATED 511 LYONS AVENUE, IRVINGTON, NJ 07111 PHONE 973-371-5160 FAX 973-371-1929 E-MAIL sales@eti-nj.com www.eti-nj.com RICHARDS MFG. CO. SALES INC. 517 LYONS AVENUE, IRVINGTON,

More information

SPECIAL CONSIDERATION OF FEEDER PROTECTION FOR BREAKER-AND-A-HALF CONFIGURA- TIONS. G. Steynberg

SPECIAL CONSIDERATION OF FEEDER PROTECTION FOR BREAKER-AND-A-HALF CONFIGURA- TIONS. G. Steynberg SPECIAL CONSIDERATION OF FEEDER PROTECTION FOR BREAKER-AND-A-HALF CONFIGURA- TIONS G. Steynberg Siemens AG; Energy Sector, Energy Automation, Nuremberg 1. INTRODUCTION The breaker-and-a-half configuration

More information

OPERATING GUIDE endicator intelligent energy monitoring

OPERATING GUIDE endicator intelligent energy monitoring OPERATING GUIDE FOR THE ENDICATOR USER MANUAL, visit www.kele.com/endicator and click on the Related Documents tab. OPERATING GUIDE endicator intelligent energy monitoring The endicator energy monitor

More information

GV3000/SE 230 VAC 1-20 HP General Purpose (Volts/Hertz) and Vector Duty Drive Software Start-Up and Reference Manual Version 6.04

GV3000/SE 230 VAC 1-20 HP General Purpose (Volts/Hertz) and Vector Duty Drive Software Start-Up and Reference Manual Version 6.04 GV3000/SE 230 VAC 1-20 HP General Purpose (Volts/Hertz) and Vector Duty Drive Software Start-Up and Reference Manual Version 6.04 Instruction Manual D2-3387-4 The information in this manual is subject

More information

MX200 SERIES Modbus Card 50P GE Zenith Controls. Operation and Maintenance Manual 50R-2200B 12/00

MX200 SERIES Modbus Card 50P GE Zenith Controls. Operation and Maintenance Manual 50R-2200B 12/00 g MX200 SERIES Modbus Card 50P-1105 GE Zenith Controls 50R-2200B 12/00 Operation and Maintenance Manual Table of Contents Overview...01 Page LED Indicator...02 Installation...03 Installing the Network

More information

Energy Management System. Operation and Installation Manual

Energy Management System. Operation and Installation Manual Energy Management System Operation and Installation Manual AA Portable Power Corp 825 S 19 TH Street, Richmond, CA 94804 www.batteryspace.com Table of Contents 1 Introduction 3 2. Packing List 5 3. Specifications

More information

Technical Specifications. Dual Source kwh Energy Meter

Technical Specifications. Dual Source kwh Energy Meter Technical Specifications of Dual Source kwh Energy Meter (SPKG300) Class 0.5S Sai PowerrZerve 29/3B, Rajalakshmi Nagar, 1 st Main Road, Velachery Bye Pass, Chennai 600 042. Website :www.spowerz.com Email

More information

QUICK START. Installation & Programming Guide

QUICK START. Installation & Programming Guide QUICK START Installation & Programming Guide PRECAUTIONS READ AND FOLLOW ALL SAFETY INSTRUCTIONS. CAUTION - RISK OF ELECTRICAL SHOCK. To prevent electrical shock, turn off power at the circuit breaker

More information

HarmonicGuard Series Bus-Applied Active Harmonic Filter Quick Start Unit Software Setup

HarmonicGuard Series Bus-Applied Active Harmonic Filter Quick Start Unit Software Setup HarmonicGuard Series Bus-Applied Active Harmonic Filter Quick Start Unit Software Setup TCI, LLC W132 N10611 Grant Drive Germantown, Wisconsin 53022 Phone: 414-357-4480 Fax: 414-357-4484 Helpline: 800-TCI-8282

More information

Observe all necessary safety precautions when controlling the soft starter remotely. Alert personnel that machinery may start without warning.

Observe all necessary safety precautions when controlling the soft starter remotely. Alert personnel that machinery may start without warning. MCD Profibus Module Instructions Important User Information Installation Instruction: MCD Profibus Module Order Code: 175G9001 1. Important User Information Observe all necessary safety precautions when

More information

M2 OLED Temperature Monitor Instructions PN 1841

M2 OLED Temperature Monitor Instructions PN 1841 M2 OLED Temperature Monitor Instructions PN 1841 Installation Checklist Check for components included Read Warning and Cautions Read page 3 for mounting instructions Read System Overview, Mounting Considerations,

More information

SSV-T and SSC-T High Drop-out Relay. Range amps amps amps amps. Operating Frequency: Temperature Error:

SSV-T and SSC-T High Drop-out Relay. Range amps amps amps amps. Operating Frequency: Temperature Error: 41-766.7 SSV-T and SSC-T High Drop-out Relay device. A magnetic armature, to which leaf-spring mounted contacts are attached, is attracted to the magnetic core upon energization of the switch. When the

More information

Moomba Boats PV480 Color Display

Moomba Boats PV480 Color Display Moomba Boats PV480 Color Display 2018 Owner s Manual 1715055 2017-08-30 We continually strive to bring you the highest quality, full-featured products. As a result, you may find that your actual display

More information

GV3000/SE Operator Interface Module (OIM) User Guide Version 2.0 M/N 2RK3000

GV3000/SE Operator Interface Module (OIM) User Guide Version 2.0 M/N 2RK3000 GV3000/SE Operator Interface Module (OIM) User Guide Version 2.0 M/N 2RK3000 Instruction Manual D2-3342-2 The information in this manual is subject to change without notice. Throughout this manual, the

More information

ETI. Renewal Parts Catalog. 137NP Network Protector

ETI. Renewal Parts Catalog. 137NP Network Protector ETI ELECTRONIC TECHNOLOGY INCORPORATED 511 LYONS AVENUE, IRVINGTON, NJ 07111 PHONE 973-371-5160 FAX 973-371-1929 E-MAIL sales@eti-nj.com www.eti-nj.com ichards Manufacturing Co., Sales Inc. RICHARDS MFG.

More information

Series B9 and C9 Electronic Metering Pumps. Instruction Manual. Manual No : 1796 Rev. : D Rev. Date : 11/2015

Series B9 and C9 Electronic Metering Pumps. Instruction Manual. Manual No : 1796 Rev. : D Rev. Date : 11/2015 Series B9 and C9 Electronic Metering Pumps Manual No : 1796 Rev. : D Rev. Date : 11/2015 sales@novatech-usa.com www.novatech-usa.com Tel: (866) 433-6682 Fax: (866) 433-6684 Tel: (281) 359-8538 Fax: (281)

More information

Troubleshooting. S&C IntelliCap Automatic Capacitor Control. Instruction Sheet Table of Contents

Troubleshooting. S&C IntelliCap Automatic Capacitor Control. Instruction Sheet Table of Contents S&C IntelliCap Automatic Capacitor Control Troubleshooting Table of Contents Section Page Section Page Introduction Qualified Persons.... 2 Read this Instruction Sheet.... 2 Retain this Instruction Sheet....

More information

DRTS 33. The new generation of advanced test equipments for Relays, Energy meters, Transducers and Power quality meters

DRTS 33. The new generation of advanced test equipments for Relays, Energy meters, Transducers and Power quality meters The new generation of advanced test equipments for Relays, Energy meters, Transducers and Power quality meters Testing all relay technologies: electromechanical, solid state, numerical and IEC61850 Manual

More information

MARINER RS. SOFTWARE for ControlLogix HM1756 SGI-TSM. Rev /10/2007

MARINER RS. SOFTWARE for ControlLogix HM1756 SGI-TSM. Rev /10/2007 MARINER RS SOFTWARE for ControlLogix HM1756 SGI-TSM Rev 1.00 1/10/2007 HELM INSTRUMENT COMPANY, INC. 361 WEST DUSSEL DRIVE MAUMEE, OHIO 43537 419-893-4356 419-893-1371 (FAX) TABLE OF CONTENTS Introduction...2

More information

POWER SERIES Plus Watt / VAR / Power Factor Digital Switchboard Meter User s Manual IM2493WVP-3

POWER SERIES Plus Watt / VAR / Power Factor Digital Switchboard Meter User s Manual IM2493WVP-3 POWER SERIES Plus Watt / VAR / Power Factor Digital Switchboard Meter User s Manual General Description The POWER SERIES Plus digital switchboard meters incorporate the latest DSP microprocessor technology.

More information

32MP Gateway. Overview and Configuration Manual

32MP Gateway. Overview and Configuration Manual 32MP Gateway Overview and Configuration Manual 32MP Gateway Overview and Configuration Manual This document is the property of Carrier Corporation and is delivered on the express condition that it is not

More information

XRS 3000 Controller Reference Guide V-2

XRS 3000 Controller Reference Guide V-2 XRS 3000 Controller Reference Guide V-2 XRS-3000 1 WHITE MAIN POWER COLLIGHTLIGHT THREE POSITION KEY SWITCH 1. OFF 2. STANDBY 3. ON XRS-3000 SAFETY CIRCUIT ENGAGED X- RAY PREWARNING X- RAY BEING PRODUCED

More information

Gas Control Manager Program User Manual (for FloBoss 107)

Gas Control Manager Program User Manual (for FloBoss 107) Part D301749X012 August 2016 Gas Control Manager Program User Manual (for FloBoss 107) Remote Automation Solutions Revision Tracking Sheet August 2016 This manual may be revised periodically to incorporate

More information

ACCESS 9340/9360 Meter Input/Output Module

ACCESS 9340/9360 Meter Input/Output Module Installation Manual PMIM-IOMOD-0208 ACCESS 9340/9360 Meter Input/Output Module 9340-60-I/O2222 and 9340-60-I/O26 HAZARD CATEGORIES AND SPECIAL SYMBOLS Read these instructions carefully and look at the

More information

MODBUS RTU I/O Expansion Modules - Models C267, C277, and C287. Installation and Operations Manual Section 50

MODBUS RTU I/O Expansion Modules - Models C267, C277, and C287. Installation and Operations Manual Section 50 MODBUS RTU I/O Expansion Modules - Models C267, C277, and C287 Installation and Operations Manual 00-02-0651 09-01-09 Section 50 In order to consistently bring you the highest quality, full featured products,

More information

BOP QUICK START GUIDE 100W, 200W, 400W. KEPCO An ISO 9001 Company. BIPOLAR OPERATIONAL POWER SUPPLY I INTRODUCTION

BOP QUICK START GUIDE 100W, 200W, 400W. KEPCO An ISO 9001 Company. BIPOLAR OPERATIONAL POWER SUPPLY I INTRODUCTION QUICK START GUIDE I INTRODUCTION KEPCO An ISO 9001 Company. BIPOLAR OPERATIONAL POWER SUPPLY 1.1. SCOPE OF MANUAL. This Quick Start Guide covers simple installation and local operation of the Kepco 100W,

More information

Product Description. S&C 5800 Series Automatic Switch Control S&C ELECTRIC COMPANY TABLE OF CONTENTS

Product Description. S&C 5800 Series Automatic Switch Control S&C ELECTRIC COMPANY TABLE OF CONTENTS S&C 5800 Series Automatic Switch Control Product Description TABLE OF CONTENTS Section Page INTRODUCTION Qualified Persons............................... 2 Read this Instruction Sheet.......................

More information

INSTRUCTION MANUAL FOR VAR/POWER FACTOR CONTROLLER SCP

INSTRUCTION MANUAL FOR VAR/POWER FACTOR CONTROLLER SCP INSTRUCTION MANUAL FOR VAR/POWER FACTOR CONTROLLER SCP 250 Publication: 9 1100 00 99Y Revision: S 04/04 INTRODUCTION This instruction manual provides information about the operation and installation of

More information

I.B. 29C893C. Instructions for Installation, Operation and Maintenance of Breaker Interface Module II

I.B. 29C893C. Instructions for Installation, Operation and Maintenance of Breaker Interface Module II I.B. 29C893C Instructions for Installation, Operation and Maintenance of Breaker Interface Module II I.B. 29C893C Page iii WARRANTY AND LIABILITY INFORMATION NO WARRANTIES, EXPRESSED OR IMPLIED, INCLUDING

More information