Lightning and Surge Arresters

Size: px
Start display at page:

Download "Lightning and Surge Arresters"

Transcription

1 / Lightning and Surge Arresters Product overview /3 Introduction /6 Lightning arresters, requirement category I (B) /8 Combination arresters, requirement category I (B) and II (C) /0 Single-pole surge arresters, requirement category II (C) /3 Multipole surge arresters, requirement category II (C), /6 Surge arresters, requirement category III (D) /9 Accessories / Configuring aids 4 /

2 Product overview Lightning and Surge Arresters Overview Lightning arresters requirement category I (B) Combination arresters requirement category I (B) and II (C) Surge arresters requirement category II (C) Surge arresters requirement category III (D) Accessories /

3 Overview Introduction to lightning and overvoltage protection Lightning and overvoltage protection WHY? Powerful information systems form the backbone of our modern industrial society. A fault or the failure of these types of systems can have far-reaching consequences. These can even cause service and industry companies to go bankrupt. The cause of faults are many and electromagnetic influences play a major role. In a highly technical, electromagnetic environment, it is not advisable to simply wait for the mutual influencing of electrical and electronic devices and systems and then pay good money to eliminate the resulting problems. Rather it is essential to plan and take preventative measures that reduce the risk of influences, faults and destruction. In spite of all this, the damage and loss statistics of electronic insurance companies are extremely worrying: more than a quarter of all claims are as a result of overvoltages due to electromagnetic influencing (see diagram, "Causes of damage to electronics"). Other Elementary Negligence Overvoltages Lightning discharges and Switching operations Water Fire Theft Vandalism The causes of damage to electronics in 000, analysis of 8400 claims Causes of overvoltages Depending on their cause, overvoltages are divided into two categories: LEMP (Lightning ElectroMagnetic Pulse) overvoltages caused by atmospheric influences (e.g. direct lightning strikes, electromagnetic lightning fields). SEMP (Switching ElectroMagnetic Pulse) overvoltages caused by switching operations (e.g. disconnection of short-circuits, normal switching of loads). Overvoltages that are the result of thunderstorms are caused by direct/close-up or remote lightning strikes (see diagram on page /4). Direct or close-up strikes are lightning strikes to the lightning protection system of a building, its immediate proximity or to the electrical conductive systems of a building (e.g. l.v. power supply, TC and control lines). The resulting surge currents and voltages are a particular threat to the system to be protected due to their amplitude and power. In the case of direct or close-up lightning strikes, the overvoltages (see diagram on page /4) are caused by the voltage drop at the surge grounding resistance and the resulting increase in potential of the building, compared to the distant environment. This represents the greatest possible loading of an electrical plant in buildings. The characteristic parameters of the surge current (peak value, rate of current rise, charge content, specific energy) can be described using the surge current waveform 0/30 ms (see diagram examples for impulse test currents). These are defined in the international, European and national standards as test current for components and devices for protection in the event of direct strikes. In addition to the voltage drop at the surge grounding resistance, overvoltages also occur in electrical building installations and the connected systems and devices, due to the induction effect of the electromagnetic lightning field (see diagram on page /4: case b). The energy of these induced overvoltages and the resulting pulse currents is considerably less than that of a direct lightning impulse current and is therefore only described with surge current wave 8/0 ms (see diagram examples for impulse test currents). Lightning and Surge Arresters Introduction Components and devices that do not carry currents from direct lightning strikes are therefore checked using surge currents 8/0 ms. [ka] Test pulse current for lightning conductors Test pulse current for lightnung arresters Examples of impulse test currents [ s ] max [ka] Waveform [ s ] Q [As] W/R [J/ ] 7 0/30 37,, 0 6 8/0 0,7,7 0 3 The protection concept Remote strikes are lightning strikes at a greater distance from the objects to be protected, lightning strikes in the medium-voltage overhead system or the immediate proximity thereof, or lightning discharges from cloud to cloud (see diagram on page /4: cases a, b and c). At the same time as these induced overvoltages, the effects of remote strikes on the electrical system of a building are controlled through devices and components, the dimensions of which correspond to surge current wave 8/0 ms. The causes of overvoltages due to switching operations include the following: Switching off of inductive loads (e.g. transformers, reactors, motors), Ignition and interruption of electric arcs (e.g. arc-welding device), Tripping of fuses. The effects of switching operations in the electrical installation of a building are simulated for testing purposes with surge currents of waveform 8/0 ms. To ensure the continuous availability of complex power and information systems, even in the event of direct lightning strikes, further measures for overvoltage protection of electrical and electronic systems are required as well as a building lightning protection system. It is important to take all the causes of overvoltages into account. For this purpose, the lightning protection zone concept is used as described in IEC 63- (DIN VDE 08 Part 03) (see diagram on page /). The building is divided into zones of different danger levels. Using these zones, it is possible to determine the devices and components required for the lightning and overvoltage protection. An EMC-oriented lightning protection zone concept should also include external lightning protection (with air terminals, arresters, grounding), equipotential bonding, room insulation and overvoltage protection for power and information systems. For the definition of lightning protection zones, please use the specifications made in the table. I_ /3

4 Introduction Overview Definition of lightning protection zones Lightning protection zone Description 0 A Zone where objects are exposed to direct lightning strikes and must therefore carry the whole lightning current. The undamped electromagnetic field occurs in this case. 0 B Zone where objects are not exposed to direct lightning strikes but where the undamped electromagnetic field still occurs. Zone where objects are not exposed to direct lightning strikes and in which the currents are reduced compared to Zone 0 A. In this zone, the electromagnetic field may be damped, depending on the insulation measures implemented., 3 If a significant reduction in the conducted currents and/ or the electromagnetic field is required, subsequent zones must be set up. The demand on these zones must be geared towards the required environment zones of the system to be protected. In accordance with the demands and loads made on overvoltage protection devices with regard to their installation site, these are divided into lightning arresters, surge arresters and combination arresters. The highest demands with regard to discharge capacity are made on lightning current and combination arresters, which implement the transition from lightning protection zone 0 A to or 0 A to. These surge arresters must be able to carry lightning partial currents of waveform 0/30 ms several times and thus prevent these destructive currents from penetrating the electrical systems of a building. At the transition area of lightning protection zones 0 B to or at the downstream lightning arrester at the transition area of lightning protection zones to and higher, surge arresters are installed to protect against overvoltages. It is their task to further attenuate the remaining extent of the upstream protection level and restrict the overvoltages in the system, whether they are induced or self-generated. The lightning and overvoltage protective measures at the borders of the lightning protection zones apply in equal measure to the energy and information system. The holistic approach of the measures described in the EMC-oriented lightning protection zone concept means it is possible to achieve permanent plant availability of a modern infrastructure., EH A? J? I A K F I JH E A % &! = > Strike in outer lightning protection, Process framework (in industrial plants), Cables, etc. Voltage drop at surge grounding resistance R st Induced voltage in loops! - 8 = >? 4 A JA I JH E A = Strike in mediumvoltage overhead lines Overvoltage transformer waves on overhead lines, as a result of cloud-cloud lightning strikes 6 I O I JA = 4 I J > M A H I O I JA >? Fields of lightning channel Causes for overvoltages during lightning discharges /4

5 Overview Introduction - ) I_33 3 * M A H A C E A A H E C I O I JA 6 I O I JA 8 A JE= JE * * - EMC-oriented lightning protection zone concept 4 E I K = JE! A H E = EC D J E C F H JA? JE A G K EF JA JE= E C EC D J E K? J H? = A G K EF JA JE= E C K HC A = HHA I JA H /

6 Lightning arresters, requirement category I (B) Overview Supports inclusion of power lines in the lightning protection equipotential bonding For protection of low-voltage load systems against overvoltage, even in the case of direct lightning strikes Max. permissible operational voltage V AC, 0/60 Hz Lightning impulse current test, wave-shaped 0/30 ms The enclosed version can prevent ion emissions, as opposed to self-extinguishing measuring spark gaps: this facilitates the mounting of wiring next to other devices in the system. Supports energy coordination with surge arresters of requirement category II. 8 mm mounting depth Technical specifications Lightning arresters -pole 3-pole -pole Order No. SD7 3-0 SD7 3- SD SD7 38- SD7 33- SD7 3-0 Reference to national regulations SPD class I acc. to Surge arrester requirement category B acc. to SPD type acc. to Approval and marks Requirement category Rated voltage U c (max. permissible V AC operational voltage) IEC 6643-: 998-0; E DIN VDE 067-6: 989-, -6/A: and -6/A: 996-0; EN 6643: 00- U, KEMA, VDE Class I (B) /0 Hz Rated voltage U n V AC 30/0 Hz 400/0 Hz 30/0 Hz Discharge of follow current I f ka rms at voltage U c A rms 3 00 Discharge capacity Lightning impulse current -pole ka (0/30 ms) I imp Lightning impulse current 3-pole ka (0/30 ms) I imp Protection level at U p Lightning operating current monitoring./0 kv ˆ 3. ˆ 4 Response time t A ns ˆ 00 Max. back-up protection, if not already provided by the network Short-circuit strength at max. back-up protection Min. conductor cross-section A 0 gl/gg 60 gl/gg 60 gl/gg ka 0 0 mm 0 solid/finely stranded Max. conductor cross-section mm 0 stranded, 3 finely stranded Temperature range C Degree of protection IP0 Installation 3 mm standard mounting rail acc. to EN 00 Mounting dimensions acc. to DIN MW 4 3 gl/gg /6

7 Selection and ordering data Lightning arresters SD7 38- Dimensional drawings Lightning arresters -pole SD7 3-0 SD7 3- SD7 3-0 SD SD7 38-! $ 9 3-pole SD7 33- $ %! "! # # & Lightning arresters, -pole Lightning and Surge Arresters More information Lightning arresters, requirement category I (B) Discharge capacity MW Order No. Weight PS*/ item P. unit kg Items unenclosed 7 ka SD N-PE unenclosed 00 ka SD enclosed 0 ka SD N-PE enclosed 00 ka SD Lightning arresters, 3-pole enclosed 00 ka 4 SD Lightning arrester with increased follow current discharge capacity, -pole safe disconnection of line-follow currents up to 0 ka eff without back-up fuse unenclosed 0 ka SD Accessories for SD7 3-0, SD and SD7 3-0 to ensure the required mounting dimensions: 8HP molded-plastic distribution system in box sizes and, see catalog LV 30. ) % $ # = " # ' * M K JH= C A = E J= E I = BA EI J=? A B # J E I K = F = HJI # # # # Recommended safety clearance for the installation of surge arresters in the switchgear cabinet. These setup instructions only apply to the unenclosed version (SD7 3-0 and SD7 38-0). % # #! > I_ ,7 43, (= 4 MW) 8 * You can order this quantity or a multiple thereof. /7

8 Combination arresters, requirement category I (B) and II (C) Overview Combination arresters are surge arresters that meet the basic requirement of requirement category I and II, i.e.: - have a lightning stroke current discharge capacity of 7 ka/00 ka (0/30 ms) - can be energy-coordinated with surge arresters of Class II and III, as well as directly with data terminal equipment of overvoltage category l (U n = 30 V AC) Protection level <. kv, corresponding to withstand impulse voltage of overvoltage category I Compact unit for all three-phase systems which is ready for connection Connection system: double terminal design supports "V wiring" option Multifunction terminal in the outgoing circuit Visual operational voltage display Remote signaling using separate, overvoltage-protected display and remote signaling module Overvoltage and atmospheric lightning arrester in a single device Perfect "all in one" solution Cabled complete device for any distribution system (TT, TN-C and TN-S) Easy-to-use device selection thanks to simple description Up to 70 % more space saving than conventional solutions Simple installation on standard mounting rail 8 mm mounting depth Technical specifications Combination arrester TN-C TN-S TT P TT Order No. SD SD SD SD7 34- Reference to national regulations SPD class I acc. to Surge arrester requirement category B acc. to SPD type acc. to Approval and marks Requirement category IEC 6643-: 998-0; E DIN VDE 067-6: 989-, -6/A: and -6/A: 996-0; EN 6643: 00- VDE Class I (B) Rated voltage U c (max. permissible operational voltage) V AC /0 Hz Rated voltage U n V AC 400/0 Hz Discharge of follow current I f ka rms 0 at voltage U c Discharge capacity Lightning impulse current -pole (0/30 ms) I imp ka Lightning impulse current, multipole (0/30 ms) I imp ka Protection level U p at I n Residual voltage at I imp kv ˆ. monitoring./0 Lightning operating current kv ˆ. Response time t A ns ˆ 00 Max. back-up protection, if not already provided by the network Short-circuit strength at max. back-up protection A ka 3 A gl/gg with spur terminal A gl/gg with V terminal /0 Hz Min. conductor cross-section mm 0 solid/finely stranded Max. conductor cross-section mm 3 stranded, 3 finely stranded (L, N, PEN ) mm 0 stranded, 3 finely stranded (L, N, PEN) Temperature range C Degree of protection IP0 Installation 3 mm standard mounting rail acc. to EN 00 Mounting dimensions acc. to DIN MW Operating display for L, L, L 3 Remote display yes, over remote signaling module SD SD Design Remote signaling module Order No. SD SD Remote signaling module for combination arresters SD , SD and SD SD7 34- Connection of the module connection only with the provided terminals of the combination arrester Contact type floating changeover Switching capacity U n /I n V AC V DC 0/0. A 0/0. A; /0. A; 7/0. A Power consumption MW Wavelength of the FOC diode Nm 660 Min. conductor cross-section mm 0. solid/finely stranded Max. conductor cross-section mm 4 solid/finely stranded Temperature range C Degree of protection IP0 Installation 3 mm standard mounting rail acc. to EN 00 Mounting dimensions acc. to DIN MW. /8

9 Selection and ordering data Combination arresters SD SD Dimensional drawings Combination arresters SD Lightning and Surge Arresters Remote signaling modules SD SD Combination arresters, requirement category I (B) and II (C) MW Order No. Weight PS*/ item P. unit kg Items TN-C 6 SD TN-S 8 SD TT 8 SD P TT 8 SD For technical specifications see page /8 Remote signaling modules The remote signaling module is placed on left-hand side of combination arrester and linked to the existing connecting cables. contact: changeover 0 V AC, 0. A 0 V DC, 0. A V DC, 0. A 7 V DC, 0. A contact /: operating status /4: fault scenario for SD , SD and SD combination arrester with 4 connecting cables. SD for SD7 34- combination arrester with connecting cables. SD For technical specifications see page /8. 30 I_0839 I_0844a SD7 34- SD SD ,7 43, (= 6 MW) 8 7 (=, MW) 6,7 43, 8 3! & " " # ' " " & 9 $ % "! # # & * You can order this quantity or a multiple thereof. /9

10 Single-pole surge arresters, Requirement category II (C) Overview For the protection of low-voltage load system against overvoltage High discharge capacity through powerful zinc oxide varistors/ spark gaps (N-PE surge arresters) High monitoring reliability through isolating arrester disconnector, type "Thermo Dynamic Control" with double monitoring Fault indication through red marking in inspection window Multifunction terminals for conductor and busbar connection Simple replacement of surge arrester connectors Simple mounting on standard mounting rail with busbars Design as for multipole version Same connector as for multipole version No interaction limiting phase reactor with surge arresters Class III (formerly D) Technical specifications Order No. SD SD7 30- SD7 30- SD SD SD SD Reference to national regulations SPD class II acc. to Surge arrester requirement category C acc. to SPD type acc. to Approval and marks Requirement category Rated voltage U c (max. permissible operational voltage) IEC 6643-: 998-0; E DIN VDE 067-6: 989-, -6/A: and -6/A: 996/0; EN 6643: 00- U, KEMA, VDE Class II (C) 7 V AC/0 Hz, 30 V DC 33 V AC/ 0 Hz, 40 V DC 7 V AC/ 0 Hz, 30 V DC 33 V AC/ 0 Hz, 40 V DC Discharge of follow current I f A rms 00 at voltage U c Discharge capacity Lightning impulse current -pole (0/30 ms) I imp ka Rated discharge current (8/0 ms) I sn ka Increased discharge current (8/0 ms) I snmax ka 40 Protection level U p Lightning operating current monitoring./0 kv ˆ. Residual voltage at ka (8/0 ms) kv ˆ ˆ. ˆ ˆ. Residual voltage at I sn kv ˆ. Response time t A ns ˆ ˆ 00 Max. back-up protection, if not already provided by the network Short-circuit strength at max. back-up protection A gl/gg ka 0/0 Hz /0 Hz 0/0 Hz /0 Hz Min. conductor cross-section mm. solid/finely stranded Max. conductor cross-section mm 3 stranded, finely stranded Temperature range C Degree of protection IP0 Installation 3 mm standard mounting rail acc. to EN 00 Mounting dimensions acc. to DIN MW Optical function/fault indication yes no Remote display no yes no yes no Floating changeover contact no yes no yes no Switching capacity U n /I n AC: 0 V/0. A DC: 0 V / 0. A; V / 0. A; 7 V/0. Hz AC: 0 V/0. A DC: 0 V / 0. A; V / 0. A; 7 V/0. Hz V AC/ 0 Hz /0

11 Technical specifications Selection and ordering data Lightning and Surge Arresters Order No. SD SD Reference to national regulations SPD class II acc. to surge arrester requirement category C acc. to SPD type acc. to Approval and marks Requirement category Rated voltage U c (max. permissible operational voltage) Discharge capacity Rated discharge current (8/0 ms) I sn ka Increased discharge current (8/0 ms) I snmax ka 40 Protection level U p Residual voltage at ka (8/0 ms) kv ˆ. Residual voltage at I sn kv ˆ Response time t A ns ˆ Max. back-up protection, if not already provided by the network Short-circuit strength at max. back-up protection IEC 6643-: 998-0; E DIN VDE 067-6: 989-, -6/A: and -6/A: 996/0; EN U, KEMA, VDE Class II (C) 38 V AC/0 Hz 00 V DC A gl/gg ka /0 Hz Single-pole surge arresters, Requirement category II (C) Min. conductor cross-section mm. solid/finely stranded Max. conductor cross-section mm 3 stranded, finely stranded Temperature range C Degree of protection IP0 Installation 3 mm standard mounting rail acc. to EN 00 Mounting dimensions acc. to DIN MW Optical function/fault indication yes Remote display no yes Floating changeover contact no yes Switching capacity U n /I n AC: 0 V/0. A DC: 0 V / 0. A; V / 0. A; 7 V/0. Hz MW Order No. Weight PS*/ item P. unit kg Items Surge arresters, -pole acc. to E DIN VDE 067, Part 6/.89 and Part 6/A/03.96 and Part 6/A/0.96 Surge arresters High monitoring reliability through isolating arrester disconnector, type "Thermo Dynamic Control" with double monitoring function Fault indication by red marking in the inspection window Multifunction terminal for conductor and busbar connection -pole Surge arrester rated voltage U c = 7 V SD Surge arrester rated voltage U c = 38 V SD Surge arrester with remote indication ) Same design as SD7 300-, but with additional 3-pole terminal for connection of remote indication When the monitoring device responds (disconnection of the defective arrester from the line supply as a result of overload) the remote signaling connections are switched via a floating changeover contact pole Surge arrester rated voltage U c = 7 V SD ) The devices can be coupled to instabus KNX EIB and AS-i bus or PROFIBUS through potential-free changeover contacts. * You can order this quantity or a multiple thereof. /

12 Single-pole surge arresters, Requirement category II (C) Selection and ordering data Surge arresters, -pole, plug-in Plug-in surge arresters MW Order No. Weight PS*/ item P. unit kg Items Same design as SD7 300-, but -piece, comprising basic element and plugged protective block -pole Surge arrester rated voltage U c = 7 V SD Surge arrester rated voltage U c = 33 V SD SD7 30- SD Plug-in surge arresters with remote indication ) Same design as SD7 30-, but with additional 3-pole terminal for connection of remote indication When the monitoring device responds (disconnection of the defective arrester from the line supply as a result of overload) the remote signaling connections are switched via a floating changeover contact. Surge arrester rated voltage U c = 7 V SD Surge arrester rated voltage U c = 33 V SD Surge arrester rated voltage U c = 38 V SD N-PE surge arrester for 3+ circuitry in the TT network Specially for use in TT system in "3+ circuit" according to DIN V VDE V : between neutral wire N and PE conductor PE/equipotential bonding with lightning impulse current (0/30 ms) ka Surge arrester on the basis of spark gaps Multifunction terminal for conductor and busbar connection Surge arrester rated voltage U c = 7 V SD For technical specifications see page /0. ) The devices can be coupled to instabus KNX EIB and AS-i bus or PROFIBUS through potential-free changeover contacts. E F K J % $ $ = E I J= > K I : - * Dimensional drawings SD7 300-, SD SD7 30- SD7 30-, SD SD7 303-, SD , SD SD I_ ,7 (= MW) Remote indication 43, 64 / * You can order this quantity or a multiple thereof.

13 Overview Same design as surge arrester, but with additional 3-pole terminal for connecting remote indication. When the monitoring device responds (disconnection of the defective arrester from the line supply as a result of overload), the remote signaling terminals are switched by means of a floating changeover contact. Easy installation of the remote indication due to the plug-in terminal. Designs: TN-C, plug-in TN-C, plug-in with remote indication TN-S, plug-in TN-S, plug-in with remote indication TT plug-in TT plug-in with remote indication All device models are available for surge arrester rated voltages of 7 V, 33 V and 38 V (see page /4). Accessories: connectors Models suitable for multipole surge arresters TN-C/TN-S/TT and single-pole surge arresters. Technical specifications Lightning and Surge Arresters Multipole surge arresters, requirement category II (C) The pluggable protective block can be replaced with no need to disconnect the supply voltage or remove the cover plate of the distribution board. Benefits Pre-wired complete units for conventional system types (TN-C, TN-S, TT), comprising a basic part and plug-in protective blocks High discharge capacity through powerful zinc oxide varistors or spark gaps for TT surge arresters High monitoring reliability through isolating arrester disconnector, type "Thermo Dynamic Control" with double monitoring Fault indication by red marking in the inspection window Multifunction terminals for conductor and busbar connection Simple replacement of surge arrester connectors Up to 70 % more space saving than conventional solutions Simple mounting on standard mounting rail with busbars Design as for -pole version No interaction limiting phase reactor with surge arresters Class III (corresp. to D) Same male connectors as for -pole version Multipole lightning arrester without remote indication with remote indication TN-C TN-S TT TN-C TN-S TT Order No. SD7 33- SD7 3- SD7 37- SD7 34- SD7 36- SD7 38- L-N N-PE L-N N-PE Reference to national regulations SPD class II acc. to IEC 6643-: 998; Surge arrester requirement category C acc. to E DIN VDE 067-6: 989-, -6/A: and -6/A: 996-0; SPD type acc. to EN Requirement category Class II (C) Rated arrester voltage U c V AC 7/0 Hz /0 Hz 7/0 Hz /0 Hz (max. permissible operating voltage) Rated voltage U n V AC 30/400/0 Hz Discharge of follow current I f A at voltage U c Discharge capacity Rated discharge current (8/0 ms) I sn ka 0 Increased discharge current (8/0 ms) I snmax ka Protection level U p Residual voltage at ka (8/0 ms) kv ˆ ˆ Residual voltage at I sn kv ˆ. ˆ. Response time t A ns ˆ ˆ 00 ˆ ˆ 00 Max. back-up protection, if not already provided by the network Short-circuit strength at max. back-up protection A gl/gg gl/gg ka 0/0 Hz 0/0 Hz Min. conductor cross-section mm. solid/finely stranded Max. conductor cross-section mm 3 stranded, finely stranded Temperature range C Degree of protection IP0 Installation 3 mm standard mounting rail acc. to EN 00 Mounting dimensions acc. to DIN MW Optical function/fault indication yes no Remote display no yes Floating changeover contact no yes Switching capacity U n /I n AC: 0 V/0. A DC: 0 V / 0. A; V / 0. A; 7 V/0. Hz /3

14 Multipole surge arresters, requirement category II (C) Technical specifications Multipole surge arresters without remote indication with remote indication TN-C TN-S TT TN-C TN-S TT Order No. SD SD7 3-4 SD SD SD SD L-N N-PE L-N N-PE Rated arrester voltage U c V AC 33/0 Hz /0 Hz 33/0 Hz /0 Hz (max. permissible operating voltage) Discharge capacity Rated discharge current (8/0 ms) I sn ka 0 0 Protection level U p Residual voltage at ka (8/0 ms) kv ˆ. ˆ. Residual voltage at I sn kv ˆ. ˆ. Short-circuit strength at max. back-up protection ka /0 Hz /0 Hz Multipole surge arresters without remote indication with remote indication TN-C TN-S TT TN-C TN-S TT Order No. SD7 33- SD7 3- SD7 37- SD7 34- SD7 36- SD7 38- L-N N-PE L-N N-PE Rated arrester voltage U c V AC 38/0 Hz /0 Hz 38/0 Hz /0 Hz (max. permissible operating voltage) Discharge capacity Rated discharge current (8/0 ms) I sn ka 0 0 Protection level U p Residual voltage at ka (8/0 ms) kv ˆ. ˆ. Residual voltage at I sn kv ˆ ˆ Short-circuit strength at max. back-up protection ka /0 Hz /0 Hz Selection and ordering data Surge arresters, multipole, plug-in SD7 37- Surge arrester rated voltage MW Order No. Weight PS*/ item P. unit U c kg Items TN-C 7 V 3 SD V 3 SD V 3 SD TN-C with remote indication 7 V 3 SD V 3 SD V 3 SD TN-S 7 V 4 SD V 4 SD V 4 SD TN-S with remote indication 7 V 4 SD V 4 SD V 4 SD TT 7 V 4 SD V 4 SD V 4 SD TT with remote indication 7 V 4 SD V 4 SD V 4 SD SD7 38- /4 * You can order this quantity or a multiple thereof.

15 Dimensional drawings SD7 33-, SD7 33-4, SD7 33- SD7 34-, SD7 34-4, SD I_63 Lightning and Surge Arresters SD7 3-, SD7 3-4, SD7 3- SD7 36-, SD7 36-4, SD7 36- SD7 37-, SD7 37-4, SD7 37- SD7 38-, SD7 38-4, SD Multipole surge arresters, requirement category II (C) I_ ,7 (= 3 MW) Remote indication , 64 7 (= 4 MW) Remote indication 6,7 43, /

16 Surge arresters, requirement category III (D) Technical specifications Design Protective adapter, protective adapter with line filter Order No. SD7 33-0, SD7 33- Tested acc. to E DIN VDE 067 Part 6/: 89- Requirement category Rated arrester voltage U c (max. permissible operating voltage) III (D) Surge arresters -pole 4-pole Overvoltage safety socket outlet SD SD UB..., UH... E DIN VDE 067, Part 6: 89-, Part 6/A: 96-03, EN 6643-: 00; IEC 6643-: E DIN VDE 067, Part 6: 89-, Part 6/A: and Part 6/A: 96-0 V AC /0 Hz V DC 440/0 Hz 30/0 Hz Rated voltage U n V AC 30/0 Hz 30/0 Hz 00/0 Hz 400/0 Hz Max. power requirements of load 90 W (4 A) W (6 A) Rated current A 6 Rated discharge current (8/0 ms) I sn in ka ka. L(N) PE, L N L+N PE Combined surge kv L(N) PE, L N L+N PE 3 L(N) PE, 3 L N L+N PE 6 L(N) PE 6 L N 0 L+N PE Protection level U p kv. ˆ. L N ˆ. L(N) PE Response time t A ns L N 00 L(N) PE Max. back-up protection, if not already provided by the network ˆ L N ˆ 00 L(N) PE A 4 (only for SD7 33-0) 6 gl/gg or LS C6 3 L L 3 L N N PE 6 L L 6 L N 0 N PE ˆ. L N ˆ. L(N) PE ˆ. L L 3 L(N) PE, L N L+N PE ˆ./ˆ. Min. conductor cross-section mm 0 solid/finely stranded 0. solid/finely stranded 0.7 Max. conductor cross-section. 4 solid/finely stranded. Temperature range C Degree of protection IP0 Installation 3 mm standard mounting rail acc. to EN 00 flush mounting Mounting dimensions acc. to DIN MW. 3 Optical function/fault indication Remote display Contact type NC Switching capacity U n /I n AC: 0 V/0. A DC: 0 V / 0. A; V / 0. A; 7 V/0. Hz /6

17 Benefits For the protection of electronic device against overvoltages (overvoltage category II according to DIN VDE 00-:997-04) Surge arrester of requirement category D according to E DIN VDE 067, Part 6/.89 and 6/A: Selection and ordering data Lightning and Surge Arresters Surge arresters, requirement category III (D) SPD Type 3 according to EN 6643-: 00 SPD class III according to IEC 6643-: 998- Visual function indication (green) Visual fault indication (red) 8 mm mounting depth 3 Surge arresters Complies with E DIN VDE 067, Part 6: 989- and -6/A: Surge arrester, -pole -pole overvoltage protection with monitoring equipment and isolating arrester disconnector Floating remote indication contact (NC contact) for fault indication (no system shutdown) Rated voltage U N = 30 V Surge arrester rated voltage U c = V Surge arrester, 4-pole 4-pole overvoltage protection with monitoring equipment and isolating arrester disconnector Optical function indication for 3 outer conductors (glow lamp green) Floating remote indication contact (NC contact) for fault indication (no system shutdown) Rated voltage U N = 30 V/400 V Surge arrester rated voltage U c = V/440 V MW Order No. Weight PS*/ item P. unit kg Items. SD SD Surge arresters (socket outlet devices) Complies with E DIN VDE 067, Part 6: 989- and -6/A: Siemens socket outlet with overvoltage protection UB.../UH... ) with labeling field and function indicators for the DELTA switch-socket outlet range Protective adapter, socket outlet adapter to protect electronic devices Can be plugged into socket outlets With optical function indication/monitoring Rated current: 6 A Rated voltage: 30 V/0 Hz Nominal discharge current. ka Protective adapter with line filter like SD protective adapter, but with additional line filter against high-frequency noise voltages Rated current: 4 A SD SD For technical specifications see page /6. ) For prices and additional information, see the ET D catalog, "DELTA switches and outlets". * You can order this quantity or a multiple thereof. /7

18 Surge arresters, requirement category III (D) Dimensional drawings SD SD , I_07 N L L L N L L L3 7 (=, MW) 4 (= 3 MW) 6,7 43, 8 Circuit diagrams Surge arresters requirement category III (D) SD $ ) SD $ )! - - A? JH A L E? A! - A? JH A L E? A! " % # % #!! UB... UH... SD SD7 33- > A HI F = K C I I? D K J - % # " #! " = /8

19 Technical specifications Lightning and Surge Arresters Accessories Design Decoupling reactors Through-type terminal Order No. SD SD SD Tested acc. to E DIN VDE 067, Part 6: 989-, Part 6/A: and Part 6/A: Rated arrester voltage U c V AC /0 Hz (max. permissible operating voltage) Nominal voltage V AC 00/0 Hz Rated current A Rated inductance mh ±0 % ±0 % Direct current resistance R cu MW approx. 4 approx. Max. back-up protection, if not already provided by the network Selection and ordering data A 3 gl/gg 63 gl/gg 00 gl/gg 0 gl/gg Short-circuit strength at max. back-up protection ka 0/0 Hz Min. conductor cross-section mm. solid/finely stranded 0 solid/finely stranded. solid/finely stranded Max. conductor cross-section mm 3 stranded/ finely stranded Temperature range C Degree of protection IP0 0 stranded/ 3 finely stranded Installation 3 mm standard mounting rail acc. to EN 00 Mounting dimensions acc. to DIN MW 4 3 stranded/ finely stranded MW Order No. Weight PS*/ item P. unit kg Items Through-type terminal For simple wiring in the different circuit versions (see section, "Configuring aid") -pole SD Male connector for surge arresters Male connectors can be used for both single-pole and multipole surge arresters Male connector for L-N surge arrester Surge arrester rated voltage U C = 7 V SD Male connector for L-N surge arrester Surge arrester rated voltage U C = 33 V SD SD7 39- Male connector for L-N surge arrester Surge arrester rated voltage U C = 38 V SD Busbars Male connector for N-PE surge arrester (TT system) SD Busbar for lightning arrester 8-pole, -phase SD Busbar for surge arrester 4-pole, -phase SD Busbar for combination arrester TN-S/TT and 4-pole residual current protective devices (SM and SM3) SD Busbar for combination arrester TN-S/TT and 4-pole miniature circuit-breaker (SY) SD Busbar for combination arrester TN-C and 3-pole residual current protective devices (SM and SD SM3) Busbar for combination arrester TN-C and 3-pole miniature circuit-breaker (SY) SD Busbar for multipole surge arrester TN-S/TT and 4-pole miniature circuit-breaker (SY) SD Busbar for multipole surge arrester TN-C and 3-pole miniature circuit-breaker (SY) SD * You can order this quantity or a multiple thereof. /9

20 Accessories Selection and ordering data SD Decoupling reactors For the energetic coordination of lightning and surge arresters in the event of a lightning impulse current of 0/30 ms The concentrated inductance replaces the otherwise necessary cable length for decoupling lightning and surge arrester 8 mm mounting depth Rated voltage: 00 V, 0 Hz Hz Inductance: H 0 % MW Order No. Weight PS*/ item P. unit kg Items Rated current: 3 A SD Rated current: 63 A 4 SD Dimensional drawings Through-type terminal -pole SD Decoupling reactors SD SD AI_ I_0766b (= MW) 6,7 43, 8 36 (= MW) 7 (= 4 MW) 6,7 43, 8 /0 * You can order this quantity or a multiple thereof.

21 Overview Requirement categories of surge arresters (SPDs) Lightning current and overvoltage protection is only effective if the prescribed insulation resistance of system sections are taken into account. To do this, the impulse withstand voltage of the different overvoltage categories is coordinated with the protection level U p of the different SPDs. 30/400 V 6 kv IV SE Protection level Rated surge withstand capability and overvoltage class acc. to DIN VDE 00 Part M 4 kv III. kv II The international standard IEC (EN ) distinguishes between four impulse withstand voltage categories for l.v. devices. In particular, the following categories apply to l.v. systems with a nominal line voltage of 30/400 V. Coordinated use of lightning current and surge arresters Cable entry. kv I B C D none <4 kv <. kv <.3 kv Requirement category acc. to E DIN 067 Part 6/A kwh Electric meter I_0800b Decoupling reactor Lightning and Surge Arresters Lightning and Surge Arresters Configuring aids Impulse withstand voltage categories Category Impulse Description withstand voltage IV 6 kv for devices that are upstream of the distribution board III 4 kv for devices that are part of the fixed system (e.g. distribution boards) II. kv for normal impulse withstand voltage devices (e.g. household appliances) I. kv for very sensitive devices (e.g. electronic devices) The adjacent circuit diagram and the above table show that lightning current and surge arresters are divided into requirement categories, depending on their location in the electrical system. German draft standard VDE International standard IEC European standard EN Designation Class B Class I Type Lightning arresters Class C Class II Type Surge arresters for distribution Class D Class III Type 3 Surge arresters for terminal device Siemens SPDs correspond to the following product standards: Germany (VDE 067-6, 996), International (IEC 6643-, 998), Italy (CEI EN 6643-), Austria ÖVE/ÖNORM E 800. I_ Lightning arrester Surge voltage protector Surge voltage protector n In practical use, surge arresters of different requirement categories are more or less connected in parallel. Due to their different response characteristics, discharge capacities and protective tasks, the different types of arrester must be installed in the system such that the ratings of the individual devices are not exceeded, thus ensuring system-wide protection. This requires energy considerations to ensure that a surge current always switches to the surge arrester connected next in series if there is a risk of the relevant surge arrester being overloaded by the surge current. This is called "energy coordination". It must be established between surge arresters of Class I (B) and II (C) and between surge arresters of Class II and III (D). In the latter case, the energy coordination is already present if there is a cable between the surge arrester of Class II and the surge arrester of Class III that is m long. The coordination of SPDs of Class I and II is described in the following section. In the event of lightning strikes, the surge arresters of the requirement category II (C) will respond first due to the low protection level. These surge arresters have a protection level of <. kv. This voltage value is not sufficient to make the parallel-connected series gap of the lightning arrester Class I respond, as their response value is approx. 3. kv. In order not to overload the Class II surge arresters, an additional voltage drop of approx. kv must be generated on the line between B and C surge arresters which, together with the protection level of the surge arrester, reaches the response value of the series gap of the lightning arrester. The voltage drop is achieved in the power systems using the existing cable impedances or the concentrated inductances, the so-called decoupling reactors. The line inductance depends on the cable routing of the PE conductor. If it is routed in a shared cable with L, L, L3 and N, a cable length of at least m is required in order to achieve sufficient inductance and the respective voltage drop. If the PE conductor runs separately from the other lines, at a distance of m or more, a cable length of m is sufficient. If these cable lengths are not possible, then additional decoupling reactors (SD / - ) must be installed between the Class I and Class II arresters. 3 /

22 Configuring aids Overview Lightning arrester L L L3 N Surge arrester Minimum cable lengths: > _ m if PE conductor is not integrated in cable > _ m if PE conductor is integrated in cable l Or: application of a decoupling reactor I_08099b A Follow current discharge capacity The specification of the follow current discharge capability of lightning arresters identifies the level of the max. follow current that the surge arrester can still interrupt on its own without requiring the help of an upstream protective device, such as a fuse or a miniature circuit-breaker. The follow current is caused by a transient short-circuit generated by the lightning arrester when discharging the lightning current as required. The follow current is therefore a short-circuit current and has a frequency of 0 Hz. If the max. possible short-circuit current of the system is smaller than the max. follow current that can be discharged by the SPD, no upstream protective device is required. Otherwise, a fuse or miniature circuit-breaker must be installed. The following sections provide data on the size of the protective device required. The single-pole SD7 3-0 lightning arrester and the SD , SD and SD combination arresters have a follow current discharge capability of 0 ka. I_0788 I_0789 Mounting diagram Circuit diagram F F Decoupling reactor F M Decoupling reactor S P D S P D Lightning arrester Surge arrester Lightning arrester Surge arrester I_08098a Energy coordination of lightning and surge arresters Line formation/ ground connection Line distribution Installation of decoupling reactor necessary if L - L - L3 - N L - L - L3 - N l < m PE installed in separate line PE L - L - L3 - N PE installed in same line I_0900 L - L - L3 - N - PE I_090 l < m The energy coordination of surge arresters of requirement category II and surge arresters of requirement category III is ensured by a cable length of at least m. The energy coordination of combination arresters and surge arresters of Class II is ensured without decoupling reactors. l is the cable length installed between the main switchgear cabinet and the auxiliary switchgear cabinet or between several auxiliary switchgear cabinets. If the length exceeds l 30 m, we recommend that you use a second protection level, in which further surge arresters of requirement category II are installed in the input switchgear cabinet. /

23 Overview Coordination of SPDs with miniature circuit-breakers and fuses The coordination between an SPD and overcurrent protective devices aims to: Protect the SPD against overload through overcurrent, Ensure plant availability, Help discharge line-follow currents, if necessary. The coordination between SPDs and fuses/miniature circuitbreakers should ensure that the: max. permissible peak current I p max and max. permissible energy value I t max of the SPD is not exceeded. This prevents damage to the SPDs and thus, exposure of persons/materials to safety hazards. Description Requirement category Product designation Max. permissible energy value I t max Combination arrester I and II SD , SD , SD pole surge arrester for high potential Lightning and Surge Arresters Configuring aids Basically, there are types of connection schemes: The protective device is in the connecting cable of the SPD. If the circuit-breaker or the fuse blows, this ensures that the power supply is maintained. We recommend the use of a signaling device to signal that the overvoltage protective function has disconnected from the system and is therefore no longer effective. The protection is carried out by the protective device (e.g. house connection fuse), which is located in the power distribution system as standard. In this case, the SPD is protected by the system fuse located in the network. When this fuse blows due to an SPD overload, the system is disconnected from the network. The fuse or miniature circuit-breaker to be used must be dimensioned to suit the conductor cross-sections in the installation. Always take into account the max. permissible number of back-up fuses for the arrester. Max. permissible peak current i p max Comments 600 ka s 8 ka No protection necessary up to 0 ka short-circuit current I SD ka s 8 ka No protection necessary up to 0 ka short-circuit current Enclosed surge arrester I SD7 3-, SD ka s 0 ka Unenclosed surge arrester I SD ka s 3 ka Surge arresters II SD7 300-, SD7 30-, SD7 30-, SD7 303-, SD7 33-, SD7 3-, SD7 37-, SD7 34-, SD ka s 0 ka /3

24 Configuring aids Overview Flow diagram for the coordination of SPD and overvoltage protection The system distribution is implemented according to system standards with switches and fuses. Where required, the lightning/surge arrester should ensure overvoltage protection through fuses or magneto-thermal switches. The planner can use the plant protection located upstream of the SPD or provide a series connection for the surge arrester. The following flow diagram describes the method of procedure when choosing between fuse and switch as overvoltage protection: when using a fuse (recommended), you can refer directly to the tables on pages / and /6, without using the flow diagram. ) + D = H=? JA HEI JE? I B E E= JK HA? EH? K EJ> HA = A H)?? A BB *, A JA H E A I D HJ? EH? K EJA BBA? JEL A? K HHA J?? A BB,, A JA H E A E = N E K L = K A = BF H JA? JEL A L E? A ) ) * H JA? JEL A L E? A B HJD A I O I JA H JA? JEL A L E? A B HJD A, * HA = E C? K HHA J?? A BB F! F = N ; A I! = N H JA? JE * A? A I I = HO B EJE = = HHA I JA HBK I A HA G K M EJ? D I A A? JE * M EJD L A HO D EC D I A A? JEL EJO I JD = J F! F = N! = N * =? K F BK I A M EJ? D H * =? K F BK I A I M EJ? D * =? K F BK I A I A A? JE * M EJD L A HO D EC D I A A? JEL EJO 6 = A E J =?? K J = N > =? K F BK I A 6 = A E J =?? K JI A A? JEL EJO > A JM A A? EH? K EJ> HA = A BK I A ), K JE, F H JA? > O I M EJ? D *, F H JA? > O > =? K F BK I A. * ), * K JE! ),. * K JE ) If the SPD needs to be replaced, an assigned cross-section element enables fast recovery of line operation once the SPD is replaced. ) Recommended, because fuses have a lower voltage drop and ensure better protection. 3) For values, see table on page /3. /4

25 Overview System protected by miniature circuit-breakers The following tables show the conditions under which it is necessary to protect the max. current, as well as the max. rated current of the fuse suitable for the SPD. MCB upstream ) The SD7 3-0 surge arrester does not require a safety fuse up to 0 ka. F Safety fuse Lq Conductor cross-section of system Lq Arrester cross-section to surge arrester Lq3 Conductor cross-section with ground fault Surge arresters SD7 3-0 ) SD7 33-, SD7 3- Lq Lq Lq3 Fuse F Fuse F [gl/gg] [A] [mm ] [mm ] [mm ] [gl/gg] [A] / / / / / / / up to 63 / up to / up to / up to / up to / up to / up to 60 0 / 3 3 / up to 60 > 0 / 3 3 / up to 60 MCB Lq F S P D I_0790 Lq Lq3 Lightning and Surge Arresters Configuring aids We recommend using fuses instead of magneto-thermal switches as they have a lower voltage drop and ensure better protection U prot. -pole and multipole surge arresters SD7 300-, SD7 30-, SD7 30-, SD7 30-4, SD7 303-, SD , SD7 303-, SD , SD7 33-, SD7 34-, SD7 3-, SD7 36-, SD7 37-, SD7 38- MCB upstream Lq Lq Lq3 Fuse F [gl/gg] [A] [mm ] [mm ] [mm ] [A] / / / / / 63 up to 80 3 up to 00 0 up to 0 up to 60 9 up to 00 0 up to 0 / up to > 0 / up to MCB Lq S P D Lq3 Lq I_ Combination arrester SD , SD7 343-, SD Feed-through connection Arrester connection ) MCB upstream Lq = Lq Lq3 MCB upstream ) Follow current discharge capacity 0 ka. / = No arrester protection necessary Lq Lq Lq3 Fuse F [gl/gg] [mm ] [mm ] [gl/gg] [mm ] [mm ] [mm ] [gl/gg] / / 3 0 6* / / / / / / / / 0 / 3 / > 0 / 3 / 3 /

26 Configuring aids Overview Fuse-protected system Fuse upstream Surge arresters SD7 3-0 ) SD7 3-, SD7 33- Lq Lq Lq3 Fuse F Fuse F [gl/gg] [A] [mm ] [mm ] [mm ] [gl/gg] [A] / / / / / / / / 63 / / / / / / / / / / / up to 60 0 / 3 3 / up to 60 0 / 3 3 / up to 60 ) The SD7 3-0 surge arrester does not require a safety fuse up to 0 ka. -pole and multipole surge arresters SD7 300-, SD7 30-, SD7 30-, SD7 30-4, SD7 303-, SD , SD7 303-, SD , SD7 33-, SD7 34-, SD7 3-, SD7 36-, SD7 37-, SD7 38- Fuse upstream Lq Lq Lq3 Fuse F [gl/gg] [A] [mm ] [mm ] [mm ] [A] / / / / / 63 / 80 3 / 00 0 / 0 / 60 9 up to 00 0 up to 0 / up to > 0 / up to Lq I_0793 Lq Lq F F Lq F S P D I_0794 Lq3 S P D Lq3 F Safety fuse Lq Conductor cross-section of system Lq Arrester cross-section to surge arrester Lq3 Conductor cross-section with ground fault Combination arrester SD , SD7 343-, SD Feed-through connection Arrester connection ) MCB Lq = Lq Lq3 MCB Lq Lq Lq3 Fuse F upstream upstream [AgL] [mm ] [mm ] [gl/gg] [mm ] [mm ] [mm ] [gl/gg] / / / / / / / / / / 0 / 3 / > 0 / 0 / ) Follow current discharge capacity 0 ka. / = No arrester protection necessary /6

27 Circuit diagrams Connection overview TN-C system L F Configuring aids 3 L L3 L N N F * Wh F3 Terminal PE PE 6 4 arresters class B 4 arresters class C Arrester module class D I_07b A 7 * For feeding with a TN-C system, the arrester between N and PE is omitted 8 TT system "wiring 3+" ) L F 9 L L3 F F3 L 0 Wh Terminal N N PE PE 3 arresters class B N/PE-arrester class B 3 arresters class C N/PE-arrester class C N/PE arrester module class D I_074c A 3 For protection rating F and F3, see pages /3 to /6. An S-differential must be fitted if the lightning and surge arresters are to be installed upstream of the residual current operated circuitbreaker. ) In the case of single-phase TT systems, the circuit diagram is called "Wiring+". /7

Lightning and Surge Arresters

Lightning and Surge Arresters Lightning and Surge Arresters 5/4 Product overview 5/5 Lightning arresters, requirement category I (B) 5/6 Combined arresters, requirement category I (B) and II (C) 5/7 Single-pole surge arrester, requirement

More information

Overvoltage Protection Devices

Overvoltage Protection Devices Siemens AG 2010 Overvoltage Protection Devices /2 Introduction /3 Lightning Arresters, Type 1 /5 Combination Surge Arresters, Type 1 and Type 2 /7 Surge Arresters, Type 2 /11 Surge Arresters, Type 3 /12

More information

Overvoltage Protection Devices

Overvoltage Protection Devices Siemens AG 2014 Overvoltage Protection Devices /2 Introduction /3 5SD7 lightning arresters, type 1 /5 5SD7 combination surge arresters, type 1 and type 2 /7 5SD7 combination surge arresters, type 1 / type

More information

Overvoltage Protection Devices

Overvoltage Protection Devices Siemens AG 2013 Overvoltage Protection Devices /2 Introduction /3 5SD7 lightning arresters, type 1 /5 5SD7 combination surge arresters, type 1 and type 2 /7 5SD7 surge arresters, type 2 /10 5SD7 surge

More information

Overvoltage Protection Devices

Overvoltage Protection Devices Siemens AG 201 /2 Introduction /3 5SD7 lightning arresters, type 1 /5 5SD7 combination surge arresters, type 1 + type 2 /7 5SD7 combination surge arresters, type 1 / type 2 /9 5SD7 surge arresters, type

More information

Overvoltage Protection Devices

Overvoltage Protection Devices Overvoltage Protection Devices /2 Introduction /3 5SD7 lightning arresters, type 1 /5 5SD7 combination surge arresters, type 1 and type 2 /7 5SD7 surge arresters, type 2 /10 5SD7 surge arresters, type

More information

6/2 Product overview. 6/3 Lightning arresters, type 1. 6/5 Combination surge arresters, type 1 and type 2. 6/7 Surge arresters, type 2

6/2 Product overview. 6/3 Lightning arresters, type 1. 6/5 Combination surge arresters, type 1 and type 2. 6/7 Surge arresters, type 2 iemens AG 2009 BETA rotecting Overvoltage rotection evices /2 roduct overview /3 Lightning arresters, type 1 /5 Combination surge arresters, type 1 and type 2 /7 urge arresters, type 2 /13 urge arresters,

More information

wietap wietap Overvoltage Protection Tensions running high

wietap wietap Overvoltage Protection Tensions running high wietap wietap Overvoltage Protection Tensions running high 2 wietap wietap Overvoltage protection Important information on overvoltage The necessity of overvoltage protection on machines and systems as

More information

BETA Protecting Overvoltage Protection Devices

BETA Protecting Overvoltage Protection Devices iemens AG 2008 BETA rotecting Overvoltage rotection evices /2 roduct overview /3 Lightning arresters, type 1 /5 Combination surge arresters, type 1 and type 2 /7 urge arresters, type 2 /13 urge arresters,

More information

Lightning and Surge Protection of Photovoltaic Installations. Leutron GmbH 2013 Leinfelden-Echterdingen, Germany

Lightning and Surge Protection of Photovoltaic Installations. Leutron GmbH 2013 Leinfelden-Echterdingen, Germany Lightning and Surge Protection of Photovoltaic Installations 1 Lightning and Surge Protection for PV Installations 2 Safeguard from Risks Ups, that was the insurance policy of my house!! 3 Why Lightning

More information

CONTA-ELECTRONICS. CONTA-PROTECT overvoltage protection

CONTA-ELECTRONICS. CONTA-PROTECT overvoltage protection CONTA-ELECTRONICS CONTA-PROTECT overvoltage protection When choosing the correct device for overvoltage protection, it is important to consider the regulations VDE 110-1, IEC 61643-1, EN 61643-11 and VDE

More information

Issued February DATA SHEET 5SX2 MCB. Based on Siemens Industrial Control Catalog

Issued February DATA SHEET 5SX2 MCB. Based on Siemens Industrial Control Catalog Issued February 2011 DATA SHEET 5SX2 MCB Based on Siemens Industrial Control Catalog General Data Trip characteristics Tripping characteristics acc. to EN 60 898 Tripping characteristic A, -5 Type A characteristic

More information

Making the Right Choices In Lightning & Surge Arrestors Some Basics:

Making the Right Choices In Lightning & Surge Arrestors Some Basics: Making the Right Choices In Lightning & Surge Arrestors Some Basics: It is a fact that the Highveld region of South Africa and Lesotho have amongst the highest lightning strikes per square km per annum

More information

NEW surge protective devices

NEW surge protective devices NEW surge protective devices For use in low-voltage systems For overhead power lines and buildings Made in EU ABOUT COMPANY INTRODUCTION Company ELEKTROMEHANIKA & BB d.o.o. was established from recent

More information

Leutron. Lightningand. Surge Protection for Power Net Systems (SPD) with EnerPro Combi-Devices. Seite 0 von14

Leutron. Lightningand. Surge Protection for Power Net Systems (SPD) with EnerPro Combi-Devices. Seite 0 von14 Leutron Lightningand Surge Protection for Power Net Systems (SPD) with EnerPro Combi-Devices Seite 0 von14 Novelties 2003 Combi Surge Protectors Leutron GmbH, 70771 Leinfelden-Echterdingen, Deutschland

More information

Overvoltage Protection for low-voltage supplies

Overvoltage Protection for low-voltage supplies Class I Overvoltage Protection.2 -.3 with sparkover gaps.4 -.9 with high-power varistors.10 -.11 Overvoltage Protection, combination arrester.12 -.15 Class II Overvoltage Protection with varistors.16 -.25

More information

R3&A Limited, Cobourg, ON

R3&A Limited, Cobourg, ON R3&A imited, Cobourg, ON ightning and Surge Protection Devices for North America Easy Choice POWER SUPPY SYSTEMS Main distribution board (Category C) Class I ightning current arrester Subdistribution board

More information

5/2 Product overview. 5/3 Distribution board components. 5/9 Built-in components. 5/17 Mounting components 5. Siemens ET B1 10/2009

5/2 Product overview. 5/3 Distribution board components. 5/9 Built-in components. 5/17 Mounting components 5. Siemens ET B1 10/2009 Siemens AG 9 BETA Protecting SR Busbar Systems /2 Product overview /3 Distribution board components /9 Built-in components /17 Mounting components Siemens ET B1 10/9 BETA Protecting SR Busbar Systems Siemens

More information

C C CIRCUIT-BREAKERS Moulded-case (MCCB), general. 1. Introduction. 2. General description

C C CIRCUIT-BREAKERS Moulded-case (MCCB), general. 1. Introduction. 2. General description CIRCUIT-BREAKERS C C81-21 CIRCUIT-BREAKERS - Contents 1. Introduction 2. General description 3. Rated voltages 3.1 Rated operational voltage (U e ) 3.2 Rated impulse withstand voltage (U imp ) 3.3 Rated

More information

Miniature Circuit Breakers for Railway Applications

Miniature Circuit Breakers for Railway Applications Siemens AG 00 for Railway Applications BETA Low-Voltage Circuit Protection The miniature circuit breakers are used in fixed railway systems and rolling stock for protecting system components against overcurrent

More information

Technical features OVR Surge Protective Devices Type 1 & Type 1+2

Technical features OVR Surge Protective Devices Type 1 & Type 1+2 Type 1 & Type 1+2 TECHNICAL FEATURES Technology Type 1 OVR T1 2 TS Triggered spark-gap Electrical features Standard IEC 61643-1 / EN 61643-11 Type / test class 1 / I Poles 1P - 1P -, 2P 2L 3P 3L 4P 4L

More information

Surge Protection Devices Ex9UE2

Surge Protection Devices Ex9UE2 Surge Protection Devices Ex9UE2 Surge Protection Devices Type 2 (Class II, T2, C) Tested according to EN 61643-11 Maximum continuous operational voltage U c from 275 V up to 440 V AC Versions with 1+0,

More information

2 Principle of lightning protection

2 Principle of lightning protection 2 Principle of lightning protection The system for protecting a building against the effects of lightning must include: bprotection of structures against direct lightning strokes; bprotection of electrical

More information

3 Design of the electrical installation protection system

3 Design of the electrical installation protection system J - Protection against voltage surges in LV 3 Design of the electrical To protect an electrical installation in a building, simple rules apply for the choice of b (s); b its protection system. 3.1 Design

More information

MULTI-POLE PHOTOVOLTAIC SYSTEMS. COMPACT and MODULAR Housing

MULTI-POLE PHOTOVOLTAIC SYSTEMS. COMPACT and MODULAR Housing MULTI-POLE Lightning Current and Surge Arresters for PHOTOVOLTAIC SYSTEMS Class I / (B+C) and Class II / (C) COMPACT and MODULAR Housing 44 PV ISPRO BS(R) 12,5 The PV ISPRO BS(R) 12,5 series of over voltage

More information

SR60 Busbar System 2/1 2/2. General Data. 2/3 Busbar routing. 2/7 Mounting components. 2/13 Accessories

SR60 Busbar System 2/1 2/2. General Data. 2/3 Busbar routing. 2/7 Mounting components. 2/13 Accessories / SR0 Busbar System General Data / Busbar routing / Mounting components / Accessories / SR0 Busbar System General Data Overview The SR0 busbar system is a modular system for busbars, for installation in

More information

Overvoltage Protection

Overvoltage Protection Overvoltage Protection OVR Range FRSOX 0100 03 GB ABB Lightning Protection Group 1 Main causes of transient overvoltages The solution: ABB OVR Surge Protective Device Range Lightning strike A lightning

More information

PHOENIX CONTACT - 08/2009. Features. DANGER OF EXPLOSION! Only remove equipment when it is disconnected and not in the potentially explosive area.

PHOENIX CONTACT - 08/2009. Features. DANGER OF EXPLOSION! Only remove equipment when it is disconnected and not in the potentially explosive area. Primary-switched power supply for building automation INTERFACE Data sheet 103505_en_02 1 Description PHOENIX CONTACT - 08/2009 Features STEP POWER power supply units for building automation The new STEP

More information

Contact protection relay

Contact protection relay Contact protection relay Ordering details SVR 450 08 F0000 The protects sensitive control contacts from excessive load. It can be used with latching function or without. Bounce time of control contacts

More information

STEP-PS/1AC/24DC/1.75

STEP-PS/1AC/24DC/1.75 Primary-switched power supply, 1 AC, output current 1.75 A INTERFACE Data Sheet 103506_en_00 1 Description PHOENIX CONTACT - 05/2008 Features STEP POWER power supply units for building automation The new

More information

Switch Disconnectors, Main and EMERGENCY-STOP Switches

Switch Disconnectors, Main and EMERGENCY-STOP Switches General data Overview Siemens G 2010 1 2 3 NSE0_01931b 4 5 6 7 1 uxiliary switch (3SB for 3K; 3KX for 3KE) 2 IP20 terminal cover (Operator side) 3 3K switch disconnector 4 rcing contacts (only for 3KE)

More information

Surge Protection Devices and Surge Protection Kit

Surge Protection Devices and Surge Protection Kit Surge and Surge Kit SPD s protect electrical and electronic equipment against transients, originating from lightning, switching of transformers, lighting and motors 3. Main protection - class 3 To cut-down

More information

PHOENIX CONTACT - 06/2007. DANGER OF EXPLOSION! Remove an item only when it is not connected to power or if it is located in the non-explosive area.

PHOENIX CONTACT - 06/2007. DANGER OF EXPLOSION! Remove an item only when it is not connected to power or if it is located in the non-explosive area. Primary switched power supply, 3-phase, output current: 40 A INTERFACE Data Sheet 102782_01_en PHOENIX CONTACT - 06/2007 Description TRIO POWER is the rail mountable 24 V power supply unit with basic functions.

More information

interface Overvoltage Protection

interface Overvoltage Protection Overvoltage Protection 569 Contents Contents Low-voltage supply Page Low-voltage supply Selection by function for low-voltage supply The zone concept for lightning protection Applications 572 574 576 Combined

More information

US Catalog March Surge protective devices (SPDs) UL range

US Catalog March Surge protective devices (SPDs) UL range US Catalog March 017 Surge protective devices (SPDs) UL range Surge protective devices (SPDs) UL range Introduction 1 1 OVR surge protective devices Joslyn surge protective devices Marketing tools 4 US

More information

Protection of PHOTOVOLTAIC SYSTEMS against LIGHTNING and OVERVOLTAGE. Surge Protection Device

Protection of PHOTOVOLTAIC SYSTEMS against LIGHTNING and OVERVOLTAGE. Surge Protection Device Protection of PHOTOVOLTAIC SYSTEMS against LIGHTNING and OVERVOLTAGE Surge Protection Device CHOICE OF SURGE PROTECTION DEVICES FOR PHOTOVOLTAIC APPLICATIONS General concept To achieve complete functionality

More information

Minia. Application manual Overvoltage protections

Minia. Application manual Overvoltage protections Minia Application manual Overvoltage protections www.oez.com Overvoltage protections Minia CONTENTS THEORETICAL PART 1. PRINCIPLE OF PROTECTION AGAINST LIGHTNING AND OVERVOLTAGE... 3 1.1. Switching overvoltage...

More information

Product and functional description

Product and functional description Product and functional description Connection example The universal dimmer submodule N 528/41 is an installation device for DIN-rail mounting, with N-system dimensions. It is designed for lighting control,

More information

ENGR. MARITES R. PANGILINAN, P.E.E.

ENGR. MARITES R. PANGILINAN, P.E.E. ENGR. MARITES R. PANGILINAN, P.E.E. WHAT IS LOW VOLTAGE INSULATION COORDINATION AND WHY IT IS IMPORTANT WHERE DO SURGES COME FROM HOW DO SPDs WORK/TYPE OF SPDs SPD SPECIFICATIONS SPD COORDINATION /CASCADING

More information

RESIDUAL CURRENT CIRCUIT BREAKERS OFE (6 ka)

RESIDUAL CURRENT CIRCUIT BREAKERS OFE (6 ka) Residual current circuit breakers MINIA RESIDUAL CURRENT CIRCUIT BREAKERS OFE ( ka) They react to sine-wave residual current (type AC) For protection: against dangerous contact with live parts (I Δn 30

More information

SIMOCODE 3UF Motor Management and Control Devices

SIMOCODE 3UF Motor Management and Control Devices Technical specifications General data applicable to the basic units, current measuring modules, current/voltage measuring modules, expansion modules, decoupling module and operator panel Permissible ambient

More information

MINI-PS AC/10-15DC/8

MINI-PS AC/10-15DC/8 Primary-Switched Power Supply, Narrow Design Data Sheet 08/2004 MINI POWER provides: An extra narrow design, with widths of 22.5 mm, 45 mm, and 67.5 mm (0.886, 1.772, and 2.657 in.) Global use due to a

More information

Technical Data. Circuit Protection - Surge Protection Devices. Ver 1.0 CUSPD1110. Brief product description:

Technical Data. Circuit Protection - Surge Protection Devices. Ver 1.0 CUSPD1110. Brief product description: Technical Data Circuit Protection - Surge Protection Devices Ver 1.0 CUSPD1110 Brief product description: Surge Protection Device (SPD) protect against lightning surges and man made surges such as motors,

More information

PRACTICAL EXAMPLES OF OVERVOLTAGE PROTECTION

PRACTICAL EXAMPLES OF OVERVOLTAGE PROTECTION INTERNAL PROTECTION systems PRACTICAL EXAMPLES OF OVERVOLTAGE PROTECTION INDUSTRIAL INSTALLATIONS 2 1 2 5 5 7 2 2 2 2 4 6 6 7 3 OBJECT: Industrial premises, Industrial complexes, Hospitals, Public buildings

More information

Siemens AG KD Switch Disconnectors SENTRON. Edition December Answers for infrastructure and cities.

Siemens AG KD Switch Disconnectors SENTRON. Edition December Answers for infrastructure and cities. KD Switch Disconnectors SENTRON Edition December 01 Answers for infrastructure and cities. Related catalogs Low-Voltage Power Distribution and LV 10 Electrical Installation Technology SENTRON SIVACON ALPHA

More information

Monitoring technique. VARIMETER Voltage relay MK 9064N, MH 9064

Monitoring technique. VARIMETER Voltage relay MK 9064N, MH 9064 Monitoring technique VARIMETER Voltage relay MK 9064N, MH 9064 0269462 Your Advantages Preventive maintenance For better productivity Quicker fault locating Precise and reliable Min-, Max. value or window

More information

PHOENIX CONTACT - 01/2010. Features. DANGER OF EXPLOSION! Only remove equipment when it is disconnected and not in the potentially explosive area.

PHOENIX CONTACT - 01/2010. Features. DANGER OF EXPLOSION! Only remove equipment when it is disconnected and not in the potentially explosive area. Uninterruptible power supply with integrated power supply unit INTERFACE Data sheet 104211_en_00 1 Description PHOENIX CONTACT - 01/2010 Features The MINI-DC-UPS provide an uninterruptible DC voltage both

More information

QUINT-BUFFER/24DC/24DC/40

QUINT-BUFFER/24DC/24DC/40 Buffer module Data sheet 105496_en_01 PHOENIX CONTACT 2013-11-01 1 Description The QUINT BUFFER buffer module combines the electronic switchover unit and power storage in the same housing. The buffer module

More information

Application-optimised DEHNshield Combined Arrester

Application-optimised DEHNshield Combined Arrester with remote signal- NEW ling contact (FM) Application-optimised Combined Arrester www.dehn-international.com 2 protects residential buildings and special applications Ideally suited for residential buildings

More information

Product and functional description

Product and functional description Product and functional description Connection example The universal dimmer main module N 528/31 is an installation device for DIN-rail mounting, with N-system dimensions. It is designed for lighting control,

More information

Deploying surge protective devices (SPDs) in photovoltaic systems. Technical Information

Deploying surge protective devices (SPDs) in photovoltaic systems. Technical Information Deploying surge protective devices (SPDs) in photovoltaic systems Technical Information 2 00/09.08 Preface Preface Damages caused by overvoltage s are not only responsible for expensive repair costs; they

More information

Operating tunnels safely Overvoltage protection for critical systems in tunnels

Operating tunnels safely Overvoltage protection for critical systems in tunnels Operating tunnels safely Overvoltage protection for critical systems in tunnels Dipl.-Ing. (FH) Martin Sandau Technical Support Business Unit Surge Protection 1 ITS 2013 19/09/13 Operating Tunnels Safely

More information

Surge protection for LED mast lights

Surge protection for LED mast lights Surge protection for LED mast lights White Paper Contents Surge arrester installed in the terminal compartment / distributor of the metal mast Surge arrester installed next to the LED mast light with the

More information

Coordinated Surge Protection

Coordinated Surge Protection DEHN + SÖHNE DS641/E/10.05 The Lightning Flood Wave When lightning hits an installation, high impulse currents and impulse voltages come up within conductive systems which can be compared to an enormous

More information

PHOENIX CONTACT - 07/2006

PHOENIX CONTACT - 07/2006 Buffer module with maintenance-free capacitor-based power storage device INTERFACE Data sheet 102035_03_en PHOENIX CONTACT - 07/2006 Description Short-term mains interruptions are bridged by QUINT BUFFER,

More information

Installation / Control Technique

Installation / Control Technique Installation / Control Technique Interface Relay, Interface Relay System Input-Output Interface Relay IK 3070, I_ 3070 0633 IK 3070 Circuit Diagrams IS 3070 According to IEC/EN 61 810-1 Relay, triac or

More information

PHOENIX CONTACT - 01/2007

PHOENIX CONTACT - 01/2007 Uninterruptible power supply INTERFACE Data Sheet 103123_00_en PHOENIX CONTACT - 01/2007 Description Especially compact and easy-to-use, the new MINI-DC-UPS/ 24 DC/2 is a combination of the power supply

More information

SPM Series Plug-in Surge Protector Type 2/3 (Test Class II/III) Single & Three Phase Surge Arresters

SPM Series Plug-in Surge Protector Type 2/3 (Test Class II/III) Single & Three Phase Surge Arresters The SPM series of modular surge protection devices provides protection of equipment connected to incoming low voltage AC power supplies against the damaging effects of transient over voltages caused by

More information

QUINT-PS/1AC/24DC/10. Extract from the online catalog. Order No.:

QUINT-PS/1AC/24DC/10. Extract from the online catalog. Order No.: Extract from the online catalog QUINT-PS/1AC/24DC/10 Order No.: 2866763 DIN rail power supply unit 24 V DC/10 A, primary-switched mode, 1- phase. The SFB technology (Selective Fusebreaking Technology)

More information

FAZ Supplementary Protectors, FAZ Miniature Circuit Breakers, P2 Disconnect Switches Overview

FAZ Supplementary Protectors, FAZ Miniature Circuit Breakers, P2 Disconnect Switches Overview FAZ Supplementary Protectors, FAZ Miniature Circuit Breakers, P2 Disconnect Switches Overview Supplementary Protectors / Miniature Circuit Breakers Page System overview 10/003 10/001 Supplementary protectors

More information

Operating Instructions

Operating Instructions Introduction To protect the signal lines of field devices and systems in the cabinet against lightning. Pepperl+Fuchs covers the complete range of Surge Protection Barriers. Housing types Depending on

More information

BS th Edition wiring regulations Furse overview

BS th Edition wiring regulations Furse overview BS 7671 18th Edition wiring regulations Furse overview Transient overvoltage protection TRANSIENT OVERVOLTAGE PROTECTION - RISK ASSESSMENT TO BS 7671 Furse electronic systems protection Enhanced solutions

More information

voltage surge protectors low voltage type 1 (class I / B) voltage surge protectors low voltage type 2 (class II / C) Distribution board protection

voltage surge protectors low voltage type 1 (class I / B) voltage surge protectors low voltage type 2 (class II / C) Distribution board protection voltage surge protectors low voltage type 1 (class I / B) voltage surge protectors low voltage type 2 (class II / C) 030 23 030 28 039 21 039 33 039 34 Type 1 voltage surge protectors (V.S.P.) for main

More information

Surge protection for gutter heating systems

Surge protection for gutter heating systems Surge protection for gutter heating systems White Paper Contents Structure without external lightning protection system Structure with external lightning protection system www.dehn-international.com Surge

More information

Residual Current Protective Devices / Arc Fault Detection Devices

Residual Current Protective Devices / Arc Fault Detection Devices Residual Current Protective Devices / Arc Fault Detection Devices SENTRON Configuration Manual Edition 10/015 siemens.com/lowvoltage Introduction 5SV / 5SM3 RCCBs 13 SIQUENCE 5SM3/5SU1 universal current

More information

onlinecomponents.com Overvoltage protection Contents Overvoltage protection Overvoltage protection F.1

onlinecomponents.com Overvoltage protection Contents Overvoltage protection Overvoltage protection F.1 Contents for low-voltage supplies.2 for instrumentation and control equipment.40 for data interfaces.88.1 for low-voltage supplies for low-voltage supplies Class I overvoltage protection with sparkover

More information

Siemens AG RA6 Fuseless Compact Starters. Catalog News LV 1 N April 2008 SIRIUS.

Siemens AG RA6 Fuseless Compact Starters. Catalog News LV 1 N April 2008 SIRIUS. 3RA Fuseless Compact Starters Catalog News LV 1 N April 2008 SIRIUS www.siemens.com/lowvoltage 3RA Fuseless Compact Starters General data Overview 3RA fuseless compact starters and infeed system for 3RA

More information

Motor-protective circuit-breaker, 3p, Ir=16-25A, screw connection. Product range PKZM4 motor protective circuit-breakers up to 65 A

Motor-protective circuit-breaker, 3p, Ir=16-25A, screw connection. Product range PKZM4 motor protective circuit-breakers up to 65 A DATASHEET - PKZM4-25 Delivery program Motor-protective circuit-breaker, 3p, Ir=16-25A, screw connection Part no. PKZM4-25 Catalog No. 222352 Eaton Catalog No. XTPR025DC1NL EL-Nummer 0004355158 (Norway)

More information

SPM Series Plug-in Surge Protection

SPM Series Plug-in Surge Protection SPM Series Plug-in Surge Protection The SPM series of modular surge protection devices provides protection of equipment connected to incoming low voltage AC power supplies against the damaging effects

More information

PROTEC Z LV the universal solution for transient switching protection for LV motors, generators, transformer LV secundaries, VSD and UPS equipment

PROTEC Z LV the universal solution for transient switching protection for LV motors, generators, transformer LV secundaries, VSD and UPS equipment PROTEC Z LV the universal solution for transient switching protection for LV motors, generators, transformer LV secundaries, VSD and UPS equipment NTSA has developed the ultimate solution for protecting

More information

Increased Safety for Switchgear Cabinets CI Arresters with Integrated Backup Fuse

Increased Safety for Switchgear Cabinets CI Arresters with Integrated Backup Fuse Increased Safety for Switchgear Cabinets CI Arresters with Backup Fuse www.dehn-international.com 1 fuse 1 2 fuse monitoring 2 3 Considerable space saving 3 Innovative solution to save space in the switchgear

More information

GLOSSARY OF TERMS. Surge and Lightning Protection ERICO Inc.

GLOSSARY OF TERMS. Surge and Lightning Protection ERICO Inc. GLOSSARY OF TERMS Surge and Lightning Protection ERICO Inc. Air Termination - shall mean that part of a lightning protection system designed to capture the lightning strike. Normally is mounted on the

More information

Power supply CP-C 24/5.0

Power supply CP-C 24/5.0 2CDC 271 064 F0004 Features Supply voltage ranges: 85-264 V AC, 100-350 V DC Output voltage adjustable from 22-28 V DC, default setting 24 V DC 0,5 % 5 A output current Open-circuit, overload and continous

More information

The Wave Breaking Factor and it s Vital Role in Surge Protection Device Coordination. Hans Slagter, DEHN + SOHNE

The Wave Breaking Factor and it s Vital Role in Surge Protection Device Coordination. Hans Slagter, DEHN + SOHNE The Wave Breaking Factor and it s Vital Role in Surge Protection Device Coordination Hans Slagter, DEHN + SOHNE Earthing, Bonding & Surge Protection Conference, Auckland 2012 Discussion topics 1. Introduction

More information

VAL-CP-1S-175. Extract from the online catalog. Order No.:

VAL-CP-1S-175. Extract from the online catalog. Order No.: Extract from the online catalog VAL-CP-1S-175 Order No.: 2859479 Pluggable type 2 arrester (surge arrester) for 1-phase current supply networks with separate N and PE (3-conductor system: L1, N, PE), with

More information

POWER SUPPLY SYSTEMS SPDs for low-voltage installations and equipment

POWER SUPPLY SYSTEMS SPDs for low-voltage installations and equipment SPDs for low-voltage installations and equipment 13 14 Easy Choice 16 Combined SPDs Type 1 Combined 25 49 59 65 113 139 15 ÜS-Schutz Combined Easy Choice L1 L2 L3 N PE SPD (Surge arrester) SPD (Surge arrester)

More information

Product and functional description. Application Program. instabus EIB Technical product information. April (6 x AC 230 V / 0,05 A)

Product and functional description. Application Program. instabus EIB Technical product information. April (6 x AC 230 V / 0,05 A) Product and functional description also functions if the bus cable is not connected or if the bus communication fails. After a long push button action (> 2 s), the other valve group is selected. The yellow

More information

MINI-DC-UPS/12DC/4. Extract from the online catalog. Order No.:

MINI-DC-UPS/12DC/4. Extract from the online catalog. Order No.: Extract from the online catalog MINI-DC-UPS/12DC/4 Order No.: 2866598 Uninterruptible power supply with integrated power supply unit, 4 A, in combination with MINI-BAT/12/DC 1.6 Ah or 2.6 Ah Commercial

More information

Easy Analog RNB130. Technical Information. Primary switched-mode power supply

Easy Analog RNB130. Technical Information. Primary switched-mode power supply Technical Information Easy Analog RNB130 Primary switched-mode power supply Your benefits Small housing, 35 mm (1.38") width High availability Wide range input - can be used world-wide Power reserve (Power

More information

5SL Miniature Circuit Breakers

5SL Miniature Circuit Breakers 5SL Miniature Circuit Breakers BETA Low-Voltage Circuit Protection The new 5SL miniature circuit breaker is intended for use up to ka. The devices have the system features characteristic of all Siemens

More information

Protection Equipment

Protection Equipment Protection Equipment Price groups 41B, 41E, 41F, 41G, 41H, 41J, 42F, 42J, 143, 401 /2 Introduction Motor starter protectors/ circuit breakers SIRIUS 3RV2 motor starter protectors up to 40 A / General data

More information

PT 3-PB-ST. Extract from the online catalog. Order No.:

PT 3-PB-ST. Extract from the online catalog. Order No.: Extract from the online catalog PT 3-PB-ST Order No.: 2858030 Surge protection plug for the base element, normal mode voltage coarse and fine protection for two floating signal wires in IT, common mode

More information

Manual for overvoltage protection for LED luminaires rev 1

Manual for overvoltage protection for LED luminaires rev 1 Kurtatsch, Italy, February 10, 2017 Manual for overvoltage protection for LED luminaires rev 1 Through the introduction of LED luminaires, substantial improvements have been achieved with respect to conventional

More information

QUINT-PS-3x AC/24DC/10

QUINT-PS-3x AC/24DC/10 3-Phase Primary-Switched Power Supply Unit INTERFACE Data Sheet PHOENIX CONTACT - 12/2005 Description QUINT POWER devices are 60...960 W power supply units for universal use. This is ensured by the wide-range

More information

Low voltage. Acti 9. the efficiency you deserve. Catalogue 03/2016

Low voltage. Acti 9. the efficiency you deserve. Catalogue 03/2016 Low voltage Acti 9 the efficiency you deserve Catalogue 03/2016 schneider-electric.com 1 and 2 LV surge s 1 and 2 LV surge s (cont.) The 1 range of surge s meets the normative withstand capability of wave

More information

OPTIMISED LUMINAIRE PROTECTION

OPTIMISED LUMINAIRE PROTECTION OPTIMISED LUMINAIRE PROTECTION LUMINAIRE PROTECTION AND POWER ADJUSTMENT This chapter presents inrush current limiters, electronic components to protect luminaires against mains surges, power reduction

More information

OPTIMISED LUMINAIRE PROTECTION

OPTIMISED LUMINAIRE PROTECTION OPTIMISED LUMINAIRE PROTECTION LUMINAIRE PROTECTION AND POWER ADJUSTMENT This chapter presents inrush current limiters, electronic components to protect luminaires against mains surges, power reduction

More information

Surge protection for frequency converters

Surge protection for frequency converters Surge protection for frequency converters White Paper Contents Basic principle of a frequency converter EMC-compatible shield connection of the motor feeder cable Frequency converter with drives in LPZ

More information

SURGE PROTECTIVE DEVICES

SURGE PROTECTIVE DEVICES SURGE PROTECTIVE DEVICES SUITABLE SOLUTIONS FOR ALL TYPES OF INSTALLATIONS AND ALL RISK LEVELS 1 CONTENT: Introduction Theory and principles Installation rules Legrand offer 2 2 INTRODUCTION Lightning

More information

Page 14-4 Page Page 14-4 SURGE PROTECTION DEVICES TYPE 2 VERSIONS WITH PLUG-IN CARTRIDGE 1P, 1P+N, 2P, 3P, 3P+N, 4P

Page 14-4 Page Page 14-4 SURGE PROTECTION DEVICES TYPE 2 VERSIONS WITH PLUG-IN CARTRIDGE 1P, 1P+N, 2P, 3P, 3P+N, 4P Page -4 Page -4 SURGE PROTECTIO DEVICES TY 1 AD 2 MOOBOCK VERSIOS 1P, 1P+, 2P, 3P, 3P+, 4P IEC impulse current Iimp (10/350μs): 25kA IEC maximum discharge current Imax (8/20μs): 100kA SPD status indicator

More information

FAQ about Drives Technology

FAQ about Drives Technology FAQ about Drives Technology Power supply systems MICROMASTER 4 SINAMICS G120 ID: 25220071 Warranty, liability and support We do not accept any liability for the information contained in this document.

More information

QUINT-PS/ 1AC/24DC/ 5

QUINT-PS/ 1AC/24DC/ 5 Extract from the online catalog QUINT-PS/ 1AC/24DC/ 5 Order No.: 2866750 DIN rail power supply unit 24 V DC/5 A, primary switched-mode, 1- phase. The SFB technology (Selective Fuse Breaking Technology)

More information

MINIATURE CIRCUIT BREAKERS LPN UP TO 63 A (10 ka)

MINIATURE CIRCUIT BREAKERS LPN UP TO 63 A (10 ka) MINIATURE CIRCUIT BREAKERS LPN UP TO 3 A (0 ka) For building, commercial and industrial installations up to 3 A 30/400 V a.c. and 0/440 V d.c. For protection of cables and conductors against overload and

More information

PHOENIX CONTACT - 05/2008. Features. DANGER OF EXPLOSION! Only remove equipment when it is disconnected and not in the potentially explosive area.

PHOENIX CONTACT - 05/2008. Features. DANGER OF EXPLOSION! Only remove equipment when it is disconnected and not in the potentially explosive area. Primary switched power supply, 1-phase, output current: 5 A ITERFACE Data Sheet 103349_en_00 1 Description PHOEIX COTACT - 05/2008 Features TRIO POWER is the DI-rail-mountable power supply unit with basic

More information

OTEC Miniature Circuit Breakers (MCB) OTEC Miniature Circuit Breakers (MCB) OTEC Miniature Circuit Breakers (MCB) Areas of Application

OTEC Miniature Circuit Breakers (MCB) OTEC Miniature Circuit Breakers (MCB) OTEC Miniature Circuit Breakers (MCB) Areas of Application Miniature Circuit Breakers Areas of Application Miniature circuit breakers (MCBs) of the N-System primarily protect cables and conductors against overload and short circuit. Thus, they also protect electrical

More information

Surge Protection Devices Type 1+2

Surge Protection Devices Type 1+2 Surge Protection Devices Type 1+2 Description The combined surge protection devices offer as an all-in-one solution lightning and surge-voltage in one device. They are in accordance with the requirement

More information

Lightning and surge protection for electromobility

Lightning and surge protection for electromobility Lightning and surge protection for electromobility White Paper Contents Danger during thunderstorms Damage caused during charging What happens if lightning strikes when charging? What do the standards

More information

ST 200 M data sheet System pro M compact miniature circuit breakers for supplementary protection acc. to UL 1077

ST 200 M data sheet System pro M compact miniature circuit breakers for supplementary protection acc. to UL 1077 MINIATURE CIRCUIT BREAKERS ST 200 M data sheet System pro M compact miniature circuit breakers for supplementary protection acc. to UL 1077 The ST 200 M miniature circuit breaker provides supplementary

More information

Type Code No. Weight Packaging [g] [pcs]

Type Code No. Weight Packaging [g] [pcs] Surge arresters surge arresters are intended for protection of electrical installations and devices against overvoltage effects, which may occur in atmospheric discharges and switching overvoltages. The

More information

Power Supply, Primary Switch Mode for Universal Use QUINT-PS AC/48DC/5

Power Supply, Primary Switch Mode for Universal Use QUINT-PS AC/48DC/5 Power Supply, Primary Switch Mode for Universal Use -PS-100-240AC/48/5 POWER provides: Preventive function monitoring through professional signaling Global use due to a wide range input A high level of

More information