Mod-bus device. Installation and user manual. Doc Rev.1 (03/15)

Size: px
Start display at page:

Download "Mod-bus device. Installation and user manual. Doc Rev.1 (03/15)"

Transcription

1 Mod-bus device Installation and user manual Doc Rev.1 (03/15)

2 INDICE 1 General Modbus interface Modbus configuration Connection Connection diagram Register Write enable register Modbus register Master board state table Master board error list Master board warning list Zone Master error list Slave board state table Slave board error list... 11

3 Modbus interface 1 General The Mod-bus device is designed to extend the boiler control with interfaces and inputs and outputs required for example when connecting to building management systems. 2 Modbus interface Using this device is it possible to verify a large number of parameters of the system, check if there is some error in each unit composing the system and modify the set point of the three circuits in a very easy way. in the e2prom of the device and can be changed if required. This can be done using the LabVision software, via the bus connection. In Figura 1 you can see the window of the Labvision software that you can use to change the Modbus address of the device. Please keep in mind that the main power of the interface must be switched off, and again on, after changing the Modbus address. The address setting is read from the e2prom only once, at power up. 2.1 Modbus configuration The default setting for the Modbus (dependant) address is 1. The address setting resides Figura 1 The table below reassume the configuration details: Modbus configuration Protocol Modbus RTU Default slave address 0x01 (settable with LabVision) Supported Modbus commands Read Holding registers (0x03)(*1) Write single holding register (0x06) Baud rate 9600bps Data Length 8 Parity None Stop Bits 2 Physical layer RS485 (two wire) Modbus connection J

4 Connection 3 Connection In Figura 2 is shown the location of connectors and components Figura 2 4

5 Register 3.1 Connection diagram Figura 3 To connect the device to the system: 1) connect the supply power to the J1 connector (3 wires) 2) Connect the bus Argus link to the J8 connector (2 wires) 3) connect the RS485 modbus line to the J7 connector (2 wires at 1-3) Now the device is ready and can manage the system. 4 Register Modbus communicates using words (the contents of 16bit holding registers). Multiple holding registers can be read (up to all of the available registers for the device), writing of holding registers is limited to one register at a time. From Modbus holding register 100 all the Modbus devices found by the Modbus driver are readable including their device type and offset. From holding register 100 plus this offset the Modbus holding registers for this device can be found.the data that is offered by the DEVICE is organised as a list of bytes. Some register can only give us an information (read only register). Other registers give us the possibility to read and write data. Depending on the type of Modbus software used, the holding register addressing range starts either at 0x0000 or at 0x0001. If your Modbus software starts addressing from 0x0000 you can use the holding register addresses shown in the table above. If your Modbus software addressing range starts at 0x0001 then add 1 to the holding register addresses listed in the table above. This is also true for the various test tools available for Modbus. 4.1 Write enable register A special control register is implement to secure modbus write actions / commands. To activate these write actions / commands, first the control register must be written. 5

6 Register Set the write enable register only when initiating a write command to a holding register. Do not send this command when no write enable is needed to prevent holding registers from being corrupted. The Write enable register controls the reading and writing of all the holding registers of a specific device. The Write enable register is the following: Holding Parameter name Range Register 98 (Hex 0062) Write enable device XX When no Modbus communication (reading or writing) is sensed for more than 4,0 Seconds the Write enable register bits will be reset. The bits will also be reset when undefined device ID s (i.e. not in the device list) are set. For safety each one of the three circuits is switched off if there is no modbus communication during a time longer than 4,0 seconds. 4.2 Modbus register The table below shows the parameters available and their address (of the holding registers). 6

7 Modbus device* Register Offset Read Write Parameter name Ram value/parameter N auto conversion Range 152MC ArgusLink Device Address X Device Argus Link Address X Controller State STATE See 152MC state table X Controller Error Code ERROR_NUMBER See 152MC error list X Controller Warning Code WARNING_NUMBER_MASTER See 152MC warning list X X Controller CH setpoint 1 -Setpoint_T_CH_High V Depending on units C / F X X Controller DHW setpoint 2 -Setpoint_T_DHW V Depending on units C / F X X High Outdoor Air temperature 17 -T_CH_High_Limit V Depending on units C / F X X Minimum outdoor air setpoint 37 T_Out_Min V Depending on units C / F X X Low outdoor air temperature 18 T_CH_High_Foot V Depending on units C / F X X Maximum Outdoor air setpoint 38 T_Out_Max V Depending on units C / F X X Night Setback 21 Attenuation_High Depending on units C / F X Header temperature X Outside temperature T_OUT_MEAN V Depending on units C / F X Cascade Firing Rate MAIN_TARGET_POWER V % X Min Firing Rate X System pump GENERAL_PUMP V 0/100 = Off/On 152MC ArgusLink Device Address X Device Argus Link Address X State STATE See 152MC state table X Error Code ERROR_NUMBER See 152MC error list X Warning Code WARNING_NUMBER_MASTER See 152MC warning list X X Boiler CH setpoint 1 -Setpoint_T_CH_High V Depending on units C / F X X Boiler DHW setpoint 2 -Setpoint_T_DHW V Depending on units C / F X X DHW type 6 DHW_Type X X CH mode 14 CH_Type_High X Supply temperature FLOW_TEMP_1 (Supply Temp 1) V Depending on units C / F X Return temperature T_RETURN_FIRST_SLAVE V Depending on units C / F X DHW temperature T_TANK V Depending on units C / F X Firing Rate MAIN_TARGET_POWER V % X Analog in 010_IN_VOLTAGE V 0..10,0V X Analog out MOD_PUMP_POWER V 0..10,0V X CH pump CH_PUMP V 0/100 = Off/On X DHW pump DHW_PUMP V 0/100 = Off/On X Burner High hours / CH Hours High Circuit Active Counter hours X Burner Med hours / DHW Hours Sanitary Circuit Active Counter hours X Burner Low hours Low Circuit Active Counter hours 152MC ArgusLink Device Address X Device Argus Link Address X State STATE See 152MC state table X Error Code ERROR_NUMBER See 152MC error list X Warning Code WARNING_NUMBER_MASTER See 152MC warning list X X Zone temperature CH setpoint 3 Setpoint_T_CH_Low (2nd Circuit) V X Zone Supply temperature T_FLOW_2 (Supply Temp 2) V Depending on units C / F 11(+) X Device Argus Link Address 152ZM ArgusLink Device Address (+) X Error Code ERROR_NUMBER See 152ZM error list 11(+) X Zone temperature CH setpoint CALC_ZONE_SETPOINT V Depending on units C / F 11(+) X Zone Supply temperature FLOW_TEMP V Depending on units C / F 11(+) X Mod Pump Speed Zone Master Pump V 0/100 = Off/On X Device Argus Link Address 152SC ArgusLink Device Address X State STATE See 152SC state table X Error Code ERROR_NUMBER See 152SC error list X Warning Code X Supply temperature FLOW_TEMP_HIGH V Depending on units C / F X Return temperature RETURN_TEMP V Depending on units C / F X Flue gas temperature FLUE_TEMP V Depending on units C / F X Firing Rate TARGET_POWER V % X Flame current FLAMEROD_2 Flamerod value (*) Modbus devices 1, 3 and 11 are the master board; device 11+ are the first zone master. The max number of zone master is 8. The addresses of the other zone master are described in the following table: 7

8 Holding register Zone Master # ArgusLink Device Address First Last Modbus device 4 is the first slave board. The max number of slave board is 31. The addresses of the other slave board are described in the following table: Holding register Slave Control # ArgusLink Device Address First Last

9 4.3 Master board state table # State Description 0 RESET_0 1 RESET_1 2 STANDBY_0 3 HANDLE_DEMAND_HIGH_CIRCUIT 4 HANDLE_DEMAND_LOW_CIRCUIT 5 HANDLE_DEMAND_LOW_&_HIGH_CIRCUIT 6 HANDLE_DEMAND_DHW_CIRCUIT 7 FROST_PROTECTION 8 ALARM_1 9 ERROR_CHECK 10 BURNER_BOOT 11 CLEAR_E2PROM_ERROR 12 STORE_BLOCK_ERROR 13 WAIT_A_SECOND 14 TESTMODE_STATE 15 PUMP_FINETUNING_STATE 4.4 Master board error list # State Description 0 RESET_0 1 RESET_1 2 STANDBY_0 3 HANDLE_DEMAND_HIGH_CIRCUIT 4 HANDLE_DEMAND_LOW_CIRCUIT 5 HANDLE_DEMAND_LOW_&_HIGH_CIRCUIT 6 HANDLE_DEMAND_DHW_CIRCUIT 7 FROST_PROTECTION 8 ALARM_1 9 ERROR_CHECK 10 BURNER_BOOT 11 CLEAR_E2PROM_ERROR 12 STORE_BLOCK_ERROR 13 WAIT_A_SECOND 14 TESTMODE_STATE 15 PUMP_FINETUNING_STATE 4.5 Master board warning list # Warning On Display Description 53 4 T_TANK_OPEN T_TANK_SHORTED 9

10 4.6 Zone Master error list # Error Description 1 E2PROM_READ_ERROR 2 WRONG_EEPROM_SIGNATURE 3 REGISTER_ERROR 10 FLOW_SENSOR_OPEN_ERROR 11 FLOW_SENSOR_SHORTED_ERROR 12 OPT_SENSOR_OPEN_ERROR 13 OPT_SENSOR_SHORTED_ERROR 20 OVERHEAT_ERROR 21 FLOW_OVERHEAT_ERROR 255 NO_ERROR 4.7 Slave board state table # State Description 0 RESET_0 1 RESET_1 2 STANDBY_0 3 SAFETY_OFF 4 SAFETY_ON 5 FLOW_SW_CLOSE 6 PRE_PURGE_1 7 IGNIT_0 8 IGNIT_1 9 BURN_0 10 SHUT_DOWN_RELAY_TEST_0 11 SHUT_DOWN_RELAY_TEST_1 12 POST_PURGE_0 13 POST_PURGE_1 14 PUMP_CH_0 15 PUMP_CH_1 16 ALARM_1 17 ERROR_CHECK 18 BURNER_BOOT 19 CLEAR_E2PROM_ERROR 20 STORE_BLOCK_ERROR 21 WAIT_A_SECOND 10

11 4.8 Slave board error list # Error On display Description Lockout errors 1 A01 IGNIT_ERROR 2 A02 NO_FLOW 4 A04 GV_RELAY_NOT_CLOSING_ERROR 5 A05 GV_RELAY_NOT_OPEN_ERROR 6 A06 SAFETY_RELAY_CLOSED_ERROR 7 A07 SAFETY_RELAY_OPEN_ERROR 8 A08 14MS_XRL_ERROR_1 9 A09 RAM_ERROR 10 A10 E2PROM_ERROR 11 A11 REGISTER_ERROR 12 A12 WRONG_EEPROM_SIGNATURE 13 A13 STACK_ERROR 14 A14 14MS_XRL_ERROR_2 15 A15 20MS_XRL_ERROR_1 16 A16 MAXIMAL_THERMOSTAT_OPEN_ERROR 17 A17 FLOW_SENSOR_TOO_HIGH_LOCK 18 A18 RETURN_SENSOR_TOO_HIGH_LOCK 19 A19 FLUE_GAS_SENSOR_TOO_HIGH_LOCK 20 A20 FLAME_OUT_TOO_LATE_ERROR 21 A21 ROM_ERROR 22 A22 BLOCKING_TOO_LONG_ERROR 23 A23 43MS_ERROR 24 A24 FAN_ERROR 25 A25 20MS_XRL_ERROR_2 Blocking errors 33 E01 FASE_ERROR 34 E02 RESET_BUTTON_ERROR 35 E03 FLOW_SW_ERROR 36 E04 E2PROM_READ_ERROR 37 E05 FLAME_ERROR_2 38 E06 SHORTED_FLUE_SENSOR_ERROR 39 E07 OPEN_FLUE_SENSOR_ERROR 40 E08 NETFREQ_ERROR 41 E09 WD_COMMUNICATION_ERROR 42 E10 SHORTED_FLOW_SENSOR_ERROR 43 E11 OPEN_FLOW_SENSOR_ERROR 44 E12 SHORTED_RETURN_SENSOR_ERROR 45 E13 OPEN_RETURN_SENSOR_ERROR 46 E14 FLOW_SENSOR_TOO_HIGH_BLOCK 47 E15 RETURN_SENSOR_TOO_HIGH_BLOCK 48 E16 FLUE_GAS_SENSOR_TOO_HIGH_BLOCK 49 E17 NO_GROUND_CONNECTED 50 E18 NETFREQ_ERROR_WD 51 E19 LAST_BLOKKING_ERROR 11

12 Doc Rev.1 (03/15)

Modbus Interfacing Version1.3 Release 0 of the 07 April 2017

Modbus Interfacing Version1.3 Release 0 of the 07 April 2017 Modbus Interfacing Version1.3 Release 0 of the 07 April 2017 Modbus specification 1.3.r00.docxx - Pag. 1/10 Contents 1 Modbus Connection... 3 1.1 Modbus configuration... 3 1.2 Modbus Functionality... 3

More information

Uponor Smatrix Move PRO Controller X-159 Modbus RTU interface

Uponor Smatrix Move PRO Controller X-159 Modbus RTU interface Uponor Smatrix Move PRO Controller X-159 Modbus RTU interface PRODUCT INFORMATION The controller can be connected and integrated to a building management system (BMS) through a Modbus-RTU interface over

More information

MODBUS AND BACNET COMMUNICATION INSTRUCTIONS

MODBUS AND BACNET COMMUNICATION INSTRUCTIONS 100275719_2000534455_Rev A MODBUS AND BACNET COMMUNICATION INSTRUCTIONS Power-Fin Models: 2500-5000 WARNING This manual must only be used by a qualified heating installer / service technician. Read all

More information

Gateway MODBUS-to-Opentherm MB-OTG Technical manual. Revision 1 SETECNA. Rel. Date 1 14/09/2016. Page: 1 di 10. Rev /09/2016

Gateway MODBUS-to-Opentherm MB-OTG Technical manual. Revision 1 SETECNA. Rel. Date 1 14/09/2016. Page: 1 di 10. Rev /09/2016 Page: 1 di 10 Gateway MODBUS-to-Opentherm MB-OTG Revision 1 Rel. Date 1 Page: 2 di 10 Table of Contents 1 Introduction... 3 2 Installation... 4 3 Integration... 5 3.1 Communication to the MODBUS, Parameter

More information

MODBUS COMMUNICATION INSTRUCTIONS

MODBUS COMMUNICATION INSTRUCTIONS SYNC-MODB Rev A MODBUS COMMUNICATION INSTRUCTIONS SYNC Models: 1.0-1.3-1.5 WARNING This manual must only be used by a qualified heating installer / service technician. Read all instructions, including

More information

MODBUS AND BACNET COMMUNICATION INSTRUCTIONS

MODBUS AND BACNET COMMUNICATION INSTRUCTIONS FB-MODB_100161012_2000020084_Rev L MODBUS AND BACNET COMMUNICATION INSTRUCTIONS Crest Models: 751-6000 WARNING This manual must only be used by a qualified heating installer / service technician. Read

More information

SCC Inc. LMV5 Series. Installation Instructions. Document No. LV February 12, 2018

SCC Inc. LMV5 Series. Installation Instructions. Document No. LV February 12, 2018 Installation Instructions February 12, 2018 OCI415.30 for use with LMV5... Linkageless Burner Management Systems OCI415.30 Description The OCI415.30 provides the LMV5... family of flame controllers with

More information

Heatronic Introduction. BAS Integration Manual. Table of Contents

Heatronic Introduction. BAS Integration Manual. Table of Contents Heatronic 4000 BAS Integration Manual Introduction The Heatronic 4000 can communicate with a Building Automation System (BAS) using either BACnet IP or Modbus. This manual provides information about boiler

More information

PF MODBUS REGISTER MAP. v1.4 Revised Nov 29, 2016

PF MODBUS REGISTER MAP. v1.4 Revised Nov 29, 2016 PF3107-00 MODBUS REGISTER MAP v1.4 Revised TRADEMARKS AND COPYRIGHT All content is subject to copyright and may not be reproduced in any form without the express written consent of the author. 2016 Profire

More information

PC PROGRAM INSTRUCTIONS FOR CREST and COPPERFIN MODELS

PC PROGRAM INSTRUCTIONS FOR CREST and COPPERFIN MODELS FB-CF-PCP_100161018_2000004582_Rev B PC PROGRAM INSTRUCTIONS FOR CREST and COPPERFIN MODELS WARNING This manual must only be used by a qualified heating installer / service technician. Read all instructions,

More information

MODBUS COMMUNICATION INSTRUCTIONS

MODBUS COMMUNICATION INSTRUCTIONS SYNC-MODB Rev J MODBUS COMMUNICATION INSTRUCTIONS Models: 1.0-1.3-1.5 WARNING This manual must only be used by a qualified heating installer / service technician. Read all instructions, including this

More information

LMV2 / LMV3... Modbus. User Documentation. Building Technologies Division

LMV2 / LMV3... Modbus. User Documentation. Building Technologies Division LMV2 / LMV3... Modbus User Documentation The LMV2... / LMV3... burner management system and this User Documentation are intended for OEMs and system integrators which integrate the system in their products!

More information

PROFIRE PF3100 Modbus Register Map PF

PROFIRE PF3100 Modbus Register Map PF PF 3100 Modbus Register Map R 0.4 PF3100 Modbus Register Map PF3107-00 solutions@profireenergy.com Page 1 of 12 Table of Contents 1. Introduction... 3 General Information... 3 Configuration... 3 Communications...

More information

W8735A1013 EnviraCOM Serial Adapter

W8735A1013 EnviraCOM Serial Adapter W8735A1013 EnviraCOM Serial Adapter INSTALLATION INSTRUCTIONS TABLE OF CONTENTS INSTALLATION... 2 When installing this product... 2 Selecting Location... 2 Mounting W8735A1013 EnviraCOM Serial Adapter...

More information

TR600 with RS485 Appendix 1

TR600 with RS485 Appendix 1 c ZIEHL industrie elektronik GmbH + Co KG Daimlerstraße 13, D 74523 Schwäbisch Hall + 49 791 504-0, info@ziehl.de, www.ziehl.de Temperature Relays and MINIKA Mains Monitoring Digital Panelmeters MINIPAN

More information

Inc. SCC. for use OCI This allows or building managemen. SCC Inc.

Inc. SCC. for use OCI This allows or building managemen. SCC Inc. SCC Inc. Installation Instructions May 8, 2017 OCI417.10 for use with LME7... Flame Safeguards OCI417.10 Description The OCI417. 10 provides the LME7... family of flame safeguards with a Modbus RTU or

More information

MODBUS COMMUNICATION INSTRUCTIONS

MODBUS COMMUNICATION INSTRUCTIONS MODB-I-O Rev B MODBUS COMMUNICATION INSTRUCTIONS Models: Knight 81-286, Knight XL 400-801 and Wall Mount 51-211 WARNIN This manual must only be used by a qualified heating installer / service technician.

More information

MM-A20 BMS Interface for Mitsubishi Electric Split Air-Conditioning

MM-A20 BMS Interface for Mitsubishi Electric Split Air-Conditioning MM-A20 BMS Interface for Mitsubishi Electric Split Air-Conditioning Installation and User Guide www.microtrol.co.uk Contents 1. Supplied Parts...2 2. Important Information...3 3. Product Overview...4

More information

SCC Inc. TS Series TS Touchscreen Kits. Installation Instructions. Document No. TS 1100 February 14, Description

SCC Inc. TS Series TS Touchscreen Kits. Installation Instructions. Document No. TS 1100 February 14, Description SCC Inc. TS Touchscreen Kits for use with LMV3, LMV5 and RWF Controls Installation Instructions February 14, 2017 Touchscreen Plate Kit Description TS series touchscreen kits provide a human machine interface

More information

SCC Inc. TS Series TS Touchscreen Kits. Installation Instructions. Document No. TS 1100 March 16, Description

SCC Inc. TS Series TS Touchscreen Kits. Installation Instructions. Document No. TS 1100 March 16, Description TS Touchscreen Kits for use with LMV3, LMV5 and RWF Controls Installation Instructions March 16, 2016 Touchscreen Plate Kit Description TS series touchscreen kits provide a human machine interface (HMI)

More information

RTD-W Installation Instructions

RTD-W Installation Instructions RTD-W Installation Instructions 0V +V POWER 15-24VDC 0V S1 S2 S3 0V S4 S5 S6 English RTD-W Installation Instructions 100.00 RTD-W Control Interface realtime Control Systems 24VAC/30VDC, 1A REMC P1 P2 RS485

More information

NEXUS NX6100/PPC6000 SERIES MODBUS COMMUNICATIONS

NEXUS NX6100/PPC6000 SERIES MODBUS COMMUNICATIONS MOD-6001 MARCH 15, 2010 NEXUS NX6100/PPC6000 SERIES MODBUS COMMUNICATIONS DESCRIPTION The MODBUS interface is designed to connect Fireye s NX6100 or PPC6000 Nexus Controllers to other devices using the

More information

S7999D SOLA Operator Interface Display

S7999D SOLA Operator Interface Display S7999D Operator Interface Display INSTALLATION INSTRUCTIONS APPLICATION The S7999D is microprocessor-based color touch-screen Operator Interface (OI) display that provides an operator interface for monitoring

More information

Elotech Standard Protocol. for Single R8200 SC

Elotech Standard Protocol. for Single R8200 SC Elotech Standard Protocol interface description / network protocol for Single R8200 SC ELOTECH Industrieelektronik GmbH Verbindungsstraße 27 D - 40723 HILDEN FON +49 2103 / 255 97 0 FAX +49 2103 / 255

More information

SCC Inc. TS Series TS MS Master Panels for Boiler Management, Lead/Lag, and Building Management System Interface. Installation Instructions

SCC Inc. TS Series TS MS Master Panels for Boiler Management, Lead/Lag, and Building Management System Interface. Installation Instructions SCC Inc. TS MS Master Panels for Boiler Management, Lead/Lag, and Building Management System Interface Installation Instructions February 14, 2017 Description A TS MS Series Master Lead/Lag Panel sequences

More information

MXM-50. Modbus Interface for Mitsubishi Air-Conditioning. Installation and User Guide.

MXM-50. Modbus Interface for Mitsubishi Air-Conditioning. Installation and User Guide. MXM-50 Modbus Interface for Mitsubishi Air-Conditioning Installation and User Guide www.innon.co.uk 1. Product Overview The Black Pear MXM-50 unit allows a Modbus building management system (BMS) to monitor

More information

Installation Instructions. Procon IP-32M wir-1_ MITSUBISHI ELECTRIC

Installation Instructions. Procon IP-32M wir-1_ MITSUBISHI ELECTRIC Installation Instructions Procon IP-32M 2371-wir-1_2-0204 MITSUBISHI ELECTRIC Procon IP-32M Overview The Procon IP-32M unit provides an interface between a Mitsubishi City-Multi G50A controller with up

More information

PC PROGRAM INSTRUCTIONS

PC PROGRAM INSTRUCTIONS PC PROGRAM INSTRUCTIONS Models: Power-Fin, Knight, Knight XL, Knight Wall Mount and Armor WARNING This manual must only be used by a qualified heating installer / service technician. Read all instructions,

More information

PC PROGRAM INSTRUCTIONS FOR THE SYNC AND ARMOR X2

PC PROGRAM INSTRUCTIONS FOR THE SYNC AND ARMOR X2 SYNC - PCP Rev B PC PROGRAM INSTRUCTIONS FOR THE SYNC AND ARMOR X2 Models: 1.0 -- 1.3 -- 1.5 WARNING This manual must only be used by a qualified heating installer / service technician. Read all instructions,

More information

MODBUS AND BACNET COMMUNICATION INSTRUCTIONS

MODBUS AND BACNET COMMUNICATION INSTRUCTIONS PBX-PFX-MODB_0066_00006_Rev C MODBUS AND BACNET COMMUNICATION INSTRUCTIONS Power-fin Models: 50-0; 50-00 ARNING This manual must only be used by a qualified heating installer / service technician. Read

More information

J1939/Modbus Slave Gateway FAQ

J1939/Modbus Slave Gateway FAQ J1939/Modbus Slave Gateway FAQ Version 1.0 (For GW-7228/GW-7238D) ICP DAS Co., Ltd. Table of Contents J1939/Modbus Slave Gateway FAQ v1.0 Q01 : How to solve CAN Bus Transmission Fail problem?... 2 Q02

More information

# Trinity Lx Controller Replacement Instructions (Rev. 2)

# Trinity Lx Controller Replacement Instructions (Rev. 2) #8589 Trinity Lx Controller Issue date: 2011-Jan-2 #8589 - Trinity Lx Controller (Rev. 2) Ts80 Replacement Controller - The controller contained in this kit is a direct replacement for the controller found

More information

Tongta Inverter TDS-F8

Tongta Inverter TDS-F8 Tongta Inverter TDS-F8 MODBUS Communication Application Manual Please ensure the user gets this manual, for the optimal use of this device. 1. Introduction: TEK-DRIVE / TDS-F8 INVERTER MODBUS Communication

More information

Optidrive Applications Support Library

Optidrive Applications Support Library Optidrive Applications Support Library Application Note Title AN-ODE-3-038 Related Products Optidrive E3 Overview Level 3 Modbus RTU Control and Register Mapping 1 Fundamental - No previous experience

More information

MODBUS COMMUNICATION INSTRUCTIONS

MODBUS COMMUNICATION INSTRUCTIONS PBX-PFX-MODB Rev A MODBUS COMMUNICATION INSTRUCTIONS Power-fin Models: 50-0; 50-00 ARNING This manual must only be used by a qualified heating installer / service technician. Read all instructions, including

More information

isma-b-mg-ip User Manual Global Control 5 Sp. z o.o. Poland, Warsaw

isma-b-mg-ip User Manual Global Control 5 Sp. z o.o. Poland, Warsaw isma-b-mg-ip User Manual Global Control 5 Sp. z o.o. Poland, Warsaw www.gc5.pl Table of content 1 Introduction... 4 1.1 Revision history... 5 1.2 Safety rules... 5 1.3 Technical specifications... 6 1.4

More information

RTD-RA. realtime. Installation Instructions. English A B. Installation Instructions Control Systems LEDS ALL DIMENSIONS IN MM

RTD-RA. realtime. Installation Instructions. English A B. Installation Instructions Control Systems LEDS ALL DIMENSIONS IN MM RTD-RA Installation Instructions 37.50 LEDS 4 3 2 1 D English Installation Instructions 80.00 80.00 ALL DIMENSIS IN MM C realtime Control Systems A B LEDS 4 3 2 1 D S21 J3 J6 1 2 3 4 J5 5 6 7 0V S1 0V

More information

USER MANUAL. Modbus IHP24-A IHP24-AF IHP24-B IHP24-BF IHP24-F IHP24-I 1/26

USER MANUAL. Modbus IHP24-A IHP24-AF IHP24-B IHP24-BF IHP24-F IHP24-I 1/26 USER MANUAL Modbus IHP24-A IHP24-AF IHP24-B IHP24-BF IHP24-F IHP24-I 1/26 Table of contents 1 General... 3 1.1 Safety instructions... 3 2 Purpose... 4 3 Specifications... 5 3.1 Electrical specifications

More information

RVL470. Heating controller. G2522en. Installation Instructions. 1 Installation. 2 Commissioning Wall mounting DIN rail mounting

RVL470. Heating controller. G2522en. Installation Instructions. 1 Installation. 2 Commissioning Wall mounting DIN rail mounting G2522en Heating controller Installation Instructions RVL470 1 Installation 1.1 Place of installation In a dry room, e.g. the boiler room Mounting choices: In a control panel (on the inner wall or on a

More information

MICROM MODUBUS COMMUNICATIONS

MICROM MODUBUS COMMUNICATIONS MICROM MODUBUS COMMUNICATIONS The protocol to be used is Modbus RTU. This is implemented by the master (PC, PLC, etc.) issuing a poll to the slave (MicroM) and the slave responding with the appropriate

More information

ModBUS Protocol for SMART 3

ModBUS Protocol for SMART 3 ModBUS Protocol for SMART 3 The communication between Smart 3 unit and a CPU is made by means of the ModBUS RTU protocol. Please refer to the specific documentation of the ModBUS RTU protocol for implementing

More information

Modbus Interface Module

Modbus Interface Module INSTRUCTION MANUAL Model : CL-MC03** Series FOR INSTALLER FOR INSTALLER Before using the device, carefully read this installation/instruction manual to ensure proper operation. Keep this manual for future

More information

MODBUS-IN. Modbus Card. User & Installation Manual Xtreme Power Conversion Corporation. All rights reserved.

MODBUS-IN. Modbus Card. User & Installation Manual Xtreme Power Conversion Corporation. All rights reserved. MODBUS-IN User & Installation Manual www.xpcc.com 2014. All rights reserved. (Rev 12/17/14) Thank you for purchasing. This manual contains instructions and warnings that should be followed during the installation,

More information

PC180 MODBUS COMMUNICATION MANUAL INJECTION MANAGEMENT SYSTEM

PC180 MODBUS COMMUNICATION MANUAL INJECTION MANAGEMENT SYSTEM PC180 MODBUS COMMUNICATION MANUAL INJECTION MANAGEMENT SYSTEM Modbus is a trademark of Modicon, Inc. Manual content copyright 2015 Extreme Telematics Corporation. All Rights Reserved. Ver 3.2 10/07/15

More information

Instruction Manual Modbus Converter Unigate-CL-RS

Instruction Manual Modbus Converter Unigate-CL-RS BA_MODBUS-Gateway_e_2011-12-16.doc, Stand: 16.12.2011 (Subject to technical changes) 1 Introduction The Unigate-CL-RS Module serves as gateway between the ExTox RS232 Interface and the bus system of the

More information

It is the installer's responsibility to follow all instructions in this manual and to follow correct electrical practice.

It is the installer's responsibility to follow all instructions in this manual and to follow correct electrical practice. MCD Modbus Module Instructions Important User Information INSTALLATION INSTRUCTIONS: MCD MODBUS MODULE Order Code: 175G9000 1. Important User Information Observe all necessary safety precautions when controlling

More information

LPB/OpenTherm Gateway

LPB/OpenTherm Gateway s OEM ALBATROS2 LPB/OpenTherm Gateway OCI365.0.. Gateway for integrating Boiler Management Units (BMUs) and boiler controllers with OpenTherm () into the Local Process Bus (LPB) A6V10774679_en_a 2015-12-09

More information

Modbus RTU/TCP Installation and Programming Guide PC3400 Particle Counter

Modbus RTU/TCP Installation and Programming Guide PC3400 Particle Counter Chemtrac, Inc. Modbus RTU/TCP Installation and Programming Guide PC3400 Particle Counter Chemtrac, Inc. rev. B111811 Introduction This guide is for use with Chemtrac s PC 3400 D Particle Counters. The

More information

REMOTE CONTROL MYSYSTEM

REMOTE CONTROL MYSYSTEM REMOTE CONTROL MYSYSTEM GENERAL FEATURES... 3 MAIN FUNCTIONS AND EQUIPMENT:... 3 LCD DISPLAY... 4 KEYBOARD:... 5 MAIN LOGIC... 6 BOARD CONFIGURATION... 7 MAIN PARAMETERS LIST:... 7 MAIN PARAMETERS CONFIGURATION:...

More information

Optidrive Applications Support Library

Optidrive Applications Support Library Optidrive Applications Support Library Application Note Title AN-ODV-3-038 Related Products Optidrive Eco Overview Level 3 Modbus RTU Control and Register Mapping 1 Fundamental - No previous experience

More information

MOD-RI Room Interface Modules with Modbus

MOD-RI Room Interface Modules with Modbus Product sheet MOD3.00 Type MOD-RI MOD-RI Room Interface Modules with Modbus The MOD-RI are room interface modules designed to provide room control interface for the building management systems. The MOD-RI

More information

Optidrive VTC Modbus RTU Register Map

Optidrive VTC Modbus RTU Register Map Application Note AN-VTC- 39 Optidrive VTC Modbus RTU Register Map Author: Ning Xu, Invertek Drives Ltd Revision: 2.21 6 September 2006 General This document details the Modbus RTU memory mapping implemented

More information

Modbus Protocol For FTS/FTM 3x&8x

Modbus Protocol For FTS/FTM 3x&8x [ 公司地址 ] Modbus Protocol For FTS/FTM 3x&8x V3.0 Introduction This document describes the protocol detail of Modbus for FTSXX Hardware interface - The interface on the sensor is RS-485. - Hardware named

More information

IntesisBox KNX - AIRZONE

IntesisBox KNX - AIRZONE IntesisBox KNX - AIRZONE Gateway for the integration of Airzone InnoBUS into KNX systems. Full integration of Airzone InnoBUS air conditioning with KNX control systems. CS CS KNX EIB Bus IntesisBox RS485

More information

INTERFACE SPECIFICATION

INTERFACE SPECIFICATION INTERFACE SPECIFICATION MODBUS CONVERTOR UTY-VMGX PART NO. 9708438030 Modbus is registered trademarks of Schneider Electric SA. LONWORKS is registered trademark of Echelon Corporation in the United States

More information

EXD-TEVI Economizer Controller for Tandem Compressors

EXD-TEVI Economizer Controller for Tandem Compressors Technical Bulletin EXD-TEVI is a stand-alone controller for enhanced wet vapor injection for Copeland tandem Scroll compressors in heating applications. Features EXD-TEVI Emerson solution for specified

More information

RS 485 Mini Modbus 1AO

RS 485 Mini Modbus 1AO RS 485 Mini Modbus 1AO Version 1.0 14/08/2014 Manufactured for Thank you for choosing our product. This manual will help you with proper support and proper operation of the device. The information contained

More information

Master Panel. Specifications. Document No. TS-2010 February 15, Product Description. Sample Specification

Master Panel. Specifications. Document No. TS-2010 February 15, Product Description. Sample Specification SCC Inc. Master Panel Product Description February 15, 2017 The Master Panel shall provide lead/lag control and time based, automatic rotation of up to eight (8) boilers, when used in conjunction with

More information

ThermoPad Reference Manual

ThermoPad Reference Manual ThermoPad Reference Manual Revision 0.6 www.coolautomation.com 2/18/2015 2 Table of Contents 1 Revision History 3 2 Specification 4 3 Thermopad Models 5 4 Terminals 6 5 MODBUS Map 7 6 Special Features

More information

PF2100 MODBUS LOGGER CARD SYSTEM SPECIFICATION. v1.0 DRAFT Revised Dec 4, 2014 Last Revised by Alex Messner

PF2100 MODBUS LOGGER CARD SYSTEM SPECIFICATION. v1.0 DRAFT Revised Dec 4, 2014 Last Revised by Alex Messner PF2100 MODBUS LOGGER CARD SYSTEM SPECIFICATION Revised Last Revised by Alex Messner This page was intentionally left blank. Table of Contents 1 Overview... 2 2 User Interface... 3 2.1 LEDs... 3 2.2 Buttons...

More information

Appendix to the Operating Instructions RMx621 with ModBus Interface V Connection to ModBus-IDA System

Appendix to the Operating Instructions RMx621 with ModBus Interface V Connection to ModBus-IDA System Operating Instructions Appendix to the Operating Instructions RMx621 with ModBus Interface V3.03.00 Connection to ModBus-IDA System BA231R/09/en/08.09 71027031 MS Word Endress+Hauser 2 Contents 1 General...

More information

Chapter. Modbus. In This Chapter...

Chapter. Modbus. In This Chapter... Modbus Communication Chapter 7 In This Chapter... Modbus Protocol....7 2 Registers....7 2 Connection with the DirectLOGIC PLC....7 8 Connection with the C-more and C-more Micro HMI panels....7 10 Modbus

More information

SCC Inc. TS Series. Installation Instructions. Document No. TS-1100 July 18, TS Touchscreen Kits for use with LMV3, LMV5 and RWF Controls

SCC Inc. TS Series. Installation Instructions. Document No. TS-1100 July 18, TS Touchscreen Kits for use with LMV3, LMV5 and RWF Controls SCC Inc. TS Touchscreen Kits for use with LMV3, LMV5 and RWF Controls Installation Instructions July 18, 2014 Touchscreen Plate Kit Description TS series touchscreen kits provide a human machine interface

More information

Real Time Clock with Temperature Sensor and RS485/Modbus Comunications

Real Time Clock with Temperature Sensor and RS485/Modbus Comunications Real Time Clock with Temperature Sensor and RS485/Modbus Comunications April 29, 2014 Power 8 20 VDC @ less than 100 MA. Battery connect jumper RS485 Bus Load Jumpers Model: RTC-TI2C Page 1 of 6 Features:

More information

Operating Guide MODBUS (RTU) Communications Option IM/L150 MOD_2. Level Indicator L150 and L160

Operating Guide MODBUS (RTU) Communications Option IM/L150 MOD_2. Level Indicator L150 and L160 Operating Guide MODBUS (RTU) Communications Option IM/L150 MOD_2 Level Indicator L150 and L160 Electrical Safety This equipment complies with the requirements of CEI/IEC 61010-1:2001-2 "Safety requirements

More information

User Guide IM/C250 MOD_3. Modbus (RTU) Communications Option C250 and V250

User Guide IM/C250 MOD_3. Modbus (RTU) Communications Option C250 and V250 User Guide IM/C250 MOD_3 Modbus (RTU) Communications Option C250 and V250 Electrical Safety This instrument complies with the requirements of CEI/IEC 61010-1:2001-2 "Safety requirements for electrical

More information

PM130 Powermeters Reference Guide Modbus Communications Protocol

PM130 Powermeters Reference Guide Modbus Communications Protocol PM130 Powermeters Reference Guide Modbus Communications Protocol BG0310 Rev. A1 SERIES PM130 POWERMETERS COMMUNICATIONS Modbus Communications Protocol REFERENCE GUIDE Every effort has been made to ensure

More information

Specifications Manual

Specifications Manual TCS-NET MODBUS Model name: TCB-IFMB640TLE Contents 1 System Overview... 2 2 RS 485 Communication Parameters... 3 3 Applied Function Codes... 3 4 Exception Response... 4 5 Counters and Registers... 4 6

More information

Naturela Smart Home system

Naturela Smart Home system Naturela Smart Home system User interface for work with controllers NPBC-V3C-xx, used in pellet burners, fireplaces, stoves, and boilers User Manual In order to learn how to work with the Naturela Smart

More information

Intech Micro 2300-A8VI analogue input station MODBUS RTU slave application supplementary manual.

Intech Micro 2300-A8VI analogue input station MODBUS RTU slave application supplementary manual. Intech Micro 2300-A8VI analogue input station MODBUS RTU slave application supplementary manual. MODBUS supplementary manual to the 2300-A8VI Installation Guide. The 2300 series stations are designed to

More information

UNPROTECTED BLOCK READ: 01H (see pages 5, 9-18) format p. 7

UNPROTECTED BLOCK READ: 01H (see pages 5, 9-18) format p. 7 PRODUCTION E340 COMMUNICATION LOGICAL MEMORY MAP Revised July 3, 1995 Revised July 15,1997 Revised May 23,2000 Revised March 1,2001 Revised October 1,2005 ALLEN-BRADLEY PROTOCOL PLC WORD DATA COMMAND CMD

More information

S7999B, S7999C SOLA Local Operator Interface

S7999B, S7999C SOLA Local Operator Interface S7999B, S7999C SOLA Local Operator Interface PRODUCT DATA From behind into a panel cutout (5.45 in. W X 4.3 in. H) using 4 #6-32 screws, nuts and 4 standoffs (provided). Wiring connections to the S7999C

More information

Service Manual ph communication functions

Service Manual ph communication functions Service Manual ph communication functions SM12B06J03-04E-E 1st Edition 2 Contents Introduction 3 1 Communication functions 3 1.1 General 3 2 Connection 3 2.1 Connector pin allocation 3 3 Setting of communication

More information

BCT SERIES CONTROLLERS (VERSION 3.0) RS-485 COMMUNICATION INSTRUCTION MANUAL MODBUS Protocol Reference Guide

BCT SERIES CONTROLLERS (VERSION 3.0) RS-485 COMMUNICATION INSTRUCTION MANUAL MODBUS Protocol Reference Guide BCT SERIES CONTROLLERS (VERSION 3.0) RS-485 COMMUNICATION INSTRUCTION MANUAL MODBUS Protocol Reference Guide 1. COMMUNICATION FUNCTIONS 1.1 General -----------------------------------------------------------------------------------------

More information

Communicative controller for VAV systems

Communicative controller for VAV systems FCR015 Communicative controller for VAV systems Summary FCR015 is a communicative controller for heating and cooling panels and a VAV (variable air volume) damper. It measures temperature and CO 2 concentration

More information

PROGRAMMING INSTRUCTIONS

PROGRAMMING INSTRUCTIONS HOERBIGER Engine Solutions PROGRAMMING INSTRUCTIONS CPU-XL VARISPARK TERMINAL PROGRAM WARNING: WARNING: DEVIATION DEVIATION FROM THESE FROM INSTRUCTIONS THESE INSTRUCTIONS MAY LEAD MAY LEAD TO IMPROPER

More information

SATEL I-LINK 100 MB I/O-converter User Guide, Version 1.1

SATEL I-LINK 100 MB I/O-converter User Guide, Version 1.1 TABLE OF CONTENTS TABLE OF CONTENTS... 1 IMPORTANT NOTICE... 2 PRODUCT CONFORMITY... 3 WARRANTY AND SAFETY INSTRUCTIONS... 4 1 GENERAL... 5 1.1 SATEL I-LINK 100 MODBUS I/O- CONVERTER... 5 2 SPECIFICATIONS...

More information

RTD-NET Installation Instructions

RTD-NET Installation Instructions LED3 SW1 LED4 RTD-NET Installation Instructions 0V +V POWER 15-24VDC English RTD-NET Installation Instructions 100.00 RTD-NET Control Interface realtime Control Systems REMC P1 P2 RS485 D-BUS DB DA GND

More information

MCF. User's Manual. Air Flowmeter NPT Model. for Communication Functions. No. CP-SP-1301E

MCF. User's Manual. Air Flowmeter NPT Model. for Communication Functions. No. CP-SP-1301E No. CP-SP-1301E TM MCF Air Flowmeter NPT Model User's Manual for Communication Functions Thank you for purchasing the MCF Air Flowmeter. This manual contains information for ensuring the correct use of

More information

[ ACD-NA ] User s Manual. O-Sung Electric Machinery Co., Ltd. 136, Hataemal-gil, Wollong-Myeon Paju-si, Gyeonggi-do, Korea

[ ACD-NA ] User s Manual. O-Sung Electric Machinery Co., Ltd. 136, Hataemal-gil, Wollong-Myeon Paju-si, Gyeonggi-do, Korea [ ACD-NA ] User s Manual O-Sung Electric Machinery Co., Ltd. 136, Hataemal-gil, Wollong-Myeon Paju-si, Gyeonggi-do, Korea Tel : (031) 944-3521 / Fax : (031) 944-3525 http://www.osemco.com / ousung@chol.com

More information

E2 Modbus RTU Register Map

E2 Modbus RTU Register Map Application Note AN ODE 01 E2 Modbus RTU Register Map Author: Peter Evans, Invertek Drives Ltd Revision: 1.02 11 June 2008 Software Version: 1.02 General This document details the Modbus RTU memory mapping

More information

VD SERIES CONTROLLERS (VERSION4.0) RS-485 COMMUNICATION INSTRUCTION MANUAL MODBUS Protocol Reference Guide

VD SERIES CONTROLLERS (VERSION4.0) RS-485 COMMUNICATION INSTRUCTION MANUAL MODBUS Protocol Reference Guide VD SERIES CONTROLLERS (VERSION4.0) RS-485 COMMUNICATION INSTRUCTION MANUAL MODBUS Protocol Reference Guide 1. COMMUNICATION FUNCTIONS 1.1 General -----------------------------------------------------------------------------------------1

More information

Softstarters. Type PSTX Fieldbus communication, Fieldbus Plug Modbus RTU. 1SFC132092M0201 June SFC132092M0201 1

Softstarters. Type PSTX Fieldbus communication, Fieldbus Plug Modbus RTU. 1SFC132092M0201 June SFC132092M0201 1 Softstarters Type PSTX Fieldbus communication, Fieldbus Plug Modbus RTU 1SFC132092M0201 June 2017 1SFC132092M0201 1 1 Modbus RTU The Modbus protocol is a fieldbus protocol that provides full control and

More information

HGC Data Manager. Model HDM303 OVERVIEW FEATURES. No. SS2-HDM (Rev.3)

HGC Data Manager. Model HDM303 OVERVIEW FEATURES. No. SS2-HDM (Rev.3) HGC Data Manager Model HDM303 OVERVIEW HGC Data Manager (HDM) is a powerful HGC family component, which adds valuable data management function to the analyzer. Model HDM303 is Fieldbus device and is completed

More information

E2 Modbus RTU Register Map Revision History Version Comments Author Date 1.02 Previous version PAE 11/06/ Revised to new format PAE 09/03/09

E2 Modbus RTU Register Map Revision History Version Comments Author Date 1.02 Previous version PAE 11/06/ Revised to new format PAE 09/03/09 Application Note Title AN-ODE-01 E2 Modbus RTU Register Map Revision History Version Comments Author Date 1.02 Previous version PAE 11/06/08 1.03 Revised to new format PAE 09/03/09 General This document

More information

ORP Arc Sensors. Modbus RTU Programmer s Manual. Firmware version: ERXUM031. ORP Arc Sensors Modbus RTU Programmer s Manual (ERXUM031)

ORP Arc Sensors. Modbus RTU Programmer s Manual. Firmware version: ERXUM031. ORP Arc Sensors Modbus RTU Programmer s Manual (ERXUM031) ORP Arc Sensors RTU Programmer s Manual Firmware version: ERXUM031 624465/01 page 1 / 70 Important Notice All rights reserved. No part of this document may be reproduced, stored in a retrieval system,

More information

IIOT Cloud Solution Intelligent Starter Kit by App(i OS/ Android) EX9017M+EX9486CW-MTCP+APP(i OS/ Android)+EX Cloud

IIOT Cloud Solution Intelligent Starter Kit by App(i OS/ Android) EX9017M+EX9486CW-MTCP+APP(i OS/ Android)+EX Cloud IIOT Cloud Solution ) EX9486C-W-MTCP (Wi-Fi Modbus TCP) Modbus RTU/ASCII Slave to Modbus TCP Master EX9017-M (RS485 2Wire; +/-20mA; +/-10V; +/- 100mV; Modbus RTU) Data send/receive can get from App & Cloud

More information

Modbus Digital Remote I/O. ARM Series. Modbus Sensor Connector Type Digital Remote I/O. Features. User Manual For Communication. Ordering Information

Modbus Digital Remote I/O. ARM Series. Modbus Sensor Connector Type Digital Remote I/O. Features. User Manual For Communication. Ordering Information RM Series Modbus Digital Remote I/O Modbus Connector Type Digital Remote I/O Features Modbus RTU standard protocol Connects with sensor connector, e-con: saves wiring work (sensor connector, CNE Series,

More information

Technical data. Safety notes. Product features

Technical data. Safety notes. Product features Technical data sheet BKN230-MOD 11-00002.F Communication and power supply unit for motorised fire dampers Communication via RTU (RS-48) AC 230 V supply via Euro plug Power is supplied to the actuators

More information

3GV M Modbus RTU Register Map

3GV M Modbus RTU Register Map Application Note AN-ODP- 38 3GV M Modbus RTU Register Map Author: Ning Xu, Invertek Drives Ltd Revision: 2.21 15 June 2007 General This document details the Modbus RTU memory mapping implemented in Optidrive

More information

Modbus MS Card User manual

Modbus MS Card User manual www.eaton.com Modbus MS Card User manual Modbus MS Card User Manual 34009048XT_EN/AB Page 1/46 Contents 1 INTRODUCTION 4 2 PRESENTATION 5 2.1 OVERVIEW 5 2.1.1 Functions 5 2.2 TECHNICAL CHARACTERISTICS

More information

Modbus RTU/TCP GOLD RX/PX/CX/SD, GENERATION C/D Applicable to program version 1.05 and newer versions

Modbus RTU/TCP GOLD RX/PX/CX/SD, GENERATION C/D Applicable to program version 1.05 and newer versions Modbus RTU/TCP GOLD RX/PX/CX/SD, GENERATION C/D Applicable to program version 1.05 and newer versions Overview ModBus can access single addresses or multiple addresses simultaneously; either reading or

More information

VMU-MC. Pulse concentrator. Operating instruction

VMU-MC. Pulse concentrator. Operating instruction EN VMU-MC Pulse concentrator Operating instruction Information property Copyright 2018, CARLO GAVAZZI Controls SpA All rights reserved in all countries. CARLO GAVAZZI Controls SpA reserves the right to

More information

PFC96Evo / PFC144Evo CONTROLLER MODBUS PROTOCOL

PFC96Evo / PFC144Evo CONTROLLER MODBUS PROTOCOL PFC96Evo / PFC144Evo CONTROLLER MODBUS PROTOCOL WARNING Installation, setting, inspection and maintenance operations must be performed only by qualified personnel in charge of it. Any operation must be

More information

DNP 3.0 Serial (RS232/RS485) and Ethernet (TCP/IP) SCADA Interface for TPSD/A36D Chargers with S2A-205T Option 21P or 57T or 57U. Setup Instructions

DNP 3.0 Serial (RS232/RS485) and Ethernet (TCP/IP) SCADA Interface for TPSD/A36D Chargers with S2A-205T Option 21P or 57T or 57U. Setup Instructions La Marche Manufacturing Company www.lamarchemfg.com DNP 3.0 Serial (RS232/RS485) and Ethernet (TCP/IP) SCADA Interface for TPSD/A36D Chargers with S2A-205T Option 21P or 57T or 57U Setup Instructions This

More information

RC-CDTO. Pre-programmed room controller with display, communication and three-point control

RC-CDTO. Pre-programmed room controller with display, communication and three-point control revision 02 2016 RC-CDTO Pre-programmed room controller with display, communication and three-point control RC-CDTO is a complete pre-programmed room controller from the Regio Midi series intended to control

More information

Modbus Communication Tool. User manual

Modbus Communication Tool. User manual Modbus Communication Tool User manual 08/2015 1 Contents 1 Contents... 2 2 Introduction... 3 3 Hardware configuration... 3 4 Login, channel configuration... 4 4.1 Communication settings... 5 5 Module detection...

More information

Rev Carbon Dioxide (CO2) Gas Sensor. TG100 User Manual

Rev Carbon Dioxide (CO2) Gas Sensor. TG100 User Manual Rev. 2.5 TG100 User Manual The TG100 measuring carbon dioxide (chemical formula CO2) is a NDIR (Non-Dispersive Infrared) gas sensor. As it is contactless, it has high accuracy and longer life than sensors

More information

RS485 MODBUS Module 8AO

RS485 MODBUS Module 8AO Version 1.3 12/02/2013 Manufactured for Thank you for choosing our product. This manual will help you with proper support and proper operation of the device. The information contained in this manual have

More information

Chipkin Automation Systems A member of BACnet International

Chipkin Automation Systems A member of BACnet International Chipkin Automation Systems A member of BACnet International CAS-2700-32 CAS Gateway: Inovonics DMP XR500 to BACnet- IP and Modbus-TCP Description The CAS-2700-32 Gateway connects to a daisy chained pair

More information