Installation and Operating Instructions

Size: px
Start display at page:

Download "Installation and Operating Instructions"

Transcription

1 A Leader in Level and Analytical Measurement Installation and Operating Instructions For the Universal IV Density Compensation Module (DCM) For Assistance Call

2 AMETEK Drexelbrook makes no warranty of any kind with regard to the material contained in this manual, including, but not limited to, implied warranties or fitness for a particular purpose. Drexelbrook shall not be liable for errors contained herein or for incidental or consequential damages in connection with the performance or use of material. Copyright AMETEK Drexelbrook

3 EDO# UIVCM-DCM Issue # 4 Universal IV CM Model 4-20 ma Water Cut Meter-Density Compensation with HART Protocol An ISO 9001 Certified Company 205 Keith Valley Road, Horsham, PA Telephone: Fax: drexelbrook.info@ametek.com Website:

4 Contents

5 Contents Section 1: Introduction 1.1 System Description Unpacking Model Numbering, System Electronics, Probe & DCM Module (Model UDO System) Model UDR Retofit Module (DCM Module) In-Line Spool Piece Probe Insertion Probe Process Connection... 5 Section 2: Installation 2.1 Mounting the Unit Wiring the Electroninc Unit Direct Connection to Coriolis/PLC Direct Connection to Coriolis/PLC Power Wiring UIV CM to DCM Module Universal IV CM Wiring Density Compensation Wiring Master & Slave Wiring Configuration SPST Relay Wiring Initial Start Up Validate CM Operation Modbus Validation Section 3: Configuration & Calibration 3.1 Calibration of the CM Module Operating the User Interface Calibration Modes & Field Calibration Menu Tree Configuration Using the Menu Table Modbus Register Maps (Integer, Floating Poiint & Long Integer) Configuration Auto Detect Section 4: Specifications 4.1 Transmitter Specifications Section 5: Troubleshooting 5.1 Identifying a Problem/Solution Troubleshooting Connections Error Codes Section 6: Hazardous Location Approval Supplementary Instructions 6.1 General Safety Information and Device Description Warning Device Description Electrical Connections & Commissioning Commissioning Start-up Checklist The Compartment Cover Opening the Cover Closing the Cover Standards and Approvals Section 7: Control Drawings 7.1 ATEX / IECEX FM US / FMC Section 8: Approval Certificates 8.1 FM / FMC Approval Certificates ATEX / IECEX Approval Certificates CE Mark Declaration of Conformity Section 9: Terms & Conditions 9.1 Terms and Conditions...117

6 Page Has No Content

7 Section 1 Introduction

8 Universal IV CM Density Compensated Model Section 1: Introduction 1.1 System Description The instructions in this manual are for the AMETEK Drexelbrook - Universal IV CM with Density Compensation Module. They are supplementary to the Universal IV CM or Universal IV CM Model with Temperature Compensation instruction manual. The system measures the percentage of water in oil and compensates for changes in oil density using input from a customer supplied density measurement device. Each AMETEK Drexelbrook Universal IV CM-DO system consists of a 1. Density Compensation Module (DCM) - Power - four-wire - HART ma - Modbus 2. UIV CM or UIV CMT RF Admittance transmitter -with a 700 series sensing element 3. Customer Supplied Coriolis meter or other device providing density & temperature outputs via ModBus 1.2 Unpacking Carefully remove the contents of the carton and check each item against the packing list before destroying any packing material. If there is any shortage or damage, report it immediately to the factory. 1

9 1.3 Model Numbering System Electronics, Probe & DCM Module (Model UDO System) Introduction 2

10 Universal IV CM Density Compensated Model 1.3 Model Numbering (Continued) Model UDR Retrofit Module (DCM Module) 3

11 Introduction 1.3 Model Numbering (Continued) In-Line Spool Piece Probe 4

12 Universal IV CM Density Compensated Model 1.3 Model Numbering (Continued) Insertion Probe 5

13 Section 2 Installation

14 Universal IV CM Density Compensated Model Section 2: Installation 2.1 Mounting the Unit There are 2 electronic units for the Density Compensation Cut Monitor. The DCM is a remote mounted unit. This module has connections for 24 VDC power, a 4 20 ma signal loop, Modbus digital output and a relay (SPST). The Cut Monitor Transmitter is either mounted integral to the probe or remote mounted. This unit is connected to the probe and power is provided by the Density Compensation Module. Reference the Universal IV Cut Monitor manual for mounting of this module Remote electronic units are designed for field mounting, but should be mounted in a location as free as possible from vibration, corrosive atmospheres, and any possibility of mechanical damage. For convenience at start-up, mount the instrument in a reasonably accessible location. Ambient temperatures should be between -40 F and 167 F (-40 C and 75 C) Spool Probe Cut Monitor (CM) Density Compensation Module (DCM) 7

15 Installation 2.2 Wiring the Electronic Unit Direct Connection to Coriolis DIrect Connection to a PLC 8

16 Universal IV CM Density Compensated Model Power Wiring to Universal IV CM to the DCM Module The DCM backboard wiring to the CM must go through the bottom of the DCM housing or else the transmitter will not secure properly. Due to the potential for switching interference on the relay it is recommended the relay wires exit the housing via the opposite port of the other wiring entering the housing. If trying to communicate via HART on the 4-20 Loop, you must have a 250Ω Resistor. 9

17 Installation Universal IV CM Wiring Due to the low power consumption of the instrument, the wiring need only be light gauge (e.g. 20 AWG) between the Density Compensation Module and Cut Monitor Module. Remove the DCM electronic unit to access the Customer Wiring Terminal Board. This is accomplished by unscrewing the 2 screws at the 3 o clock and 9 o clock positions. The captive screws can then be used to lift the electronics from the housing Density Compensation Module Wiring The signal connections are made to the terminal block on the front of the Density Compensation Module chassis Power Wiring Due to the low power consumption of the instrument, the wiring need only be light gauge (e.g. 20 AWG). Shielded twisted pair cables are recommended Supply Voltage requirement is 19-30VDC. *Shield wire may be Grounded at the identified housing screw or cut depending on the power configuration. Ground Screw 10

18 Universal IV CM Density Compensated Model (4-20mA) HART 7.0 Signal Loop Wiring Due to the low power consumption of the instrument, the wiring need only be light gauge (e.g. 20 AWG) for the 4 20 ma signal loop. Shielded twisted pair cables are recommended. Supply Voltage requirement is 19-30VDC. Minimum loop resistance for HART communications is 250 Ω. Minimum 22mA is required at the 4-20mA input terminals. *Shield wire may be Grounded at the identified housing screw or cut depending on the power configuration Ground Screw 11

19 Modbus Communications Wiring Installation Due to the low power consumption of the instrument, the wiring need only be light gauge (e.g. 20 AWG) for the Modbus digital output. Shielded 3 wire cable is recommended. 12

20 Universal IV CM Density Compensated Model Master & Slave Wiring Configurations Master In the Master configuration the DCM is the Modbus master and requests density, temperature and flow rate data from the connected slave device (Coriolis, PLC, etc.). The corrected Water cut is transmitted to the control system from the DCM via the 4 20 ma loop and all other parameters via HART Slave In the Slave configuration the external Modbus master, typically a PLC, is writing density, temperature and flow data to the DCM slave. The corrected Water cut is transmitted back to the control system from the DCM via the 4 20 ma loop and all other parameters via HART SPST Relay Wiring Selection of the wire size should be based on the power that will be switched. Due to the potential for switching interference on the relay it is recommended the relay wires exit the housing via the left port and all other wiring exit the housing via the right port. 13

21 Installation 2.3 Initial Start Up Verify wiring configuration per section Power up the Cut Monitor (CM) and the Density Compensation Module (DCM) 1. If both units power up properly then skip #2 below 2. If both units fail to power up properly then verify the following voltage levels Minimum voltage at any of these points should be 19VDC. If not check the power supply to ensure sufficient output rating. 3. After obtaining proper voltages wait 60 seconds for full power up, proceed to next step 4. If the display shows a CRITICAL COMM LOSS error, verify the 4-20mA loop wiring 5. If the display shows a MB Master Invalid Response Failure the you may have an incorrect Modbus register address, this will be corrected later. 6. Confirm the Modbus wires are correct. Measure from A to B, voltage should be approximately 2.5 VDC. If it is negative, swap the Modbus wires. 7. Verify the loop current output matches at the PLC and DCM You may have to enable the 4-20mA Loop Display on the DCM. If so, proceed to Section 3.4. The displayed value of current does not matter at this point, only that they match. If they differ slightly, you can correct this later by performing a trim and calibration. 8. If they do not match, check wiring. If they do match, proceed to the next section. Validate CM Operation. 14

22 Universal IV CM Density Compensated Model 2.4 Validate CM Operation Verify the capacitance values on the CM and DCM match. 1. If they do not match, you shoul dsee a "HART 5 CRITICAL COMM LOSS FAILURE "on the DCM. To clear this, power cycle the CM only bu removing the 4-20mA leads on the CM for 10 seconds then replace them. If the capacitance values are still mismatched, it is likely a faulty cut monitor (CM) transmitter. Contact Drexelbrook Service department Verify matching capacitance values are appropriate for the application. <14pF pf >40 pf Problem Confirm Scenario Problem (A) While powered, remove CM transmitter from back board. If the CAP value changes on the tramsitter the transmitter is fine., go to (B). If the CAP value remains fixed, power cycle the CM transmitter and restart the CAP check. If the value continues to remain locked, replace the Cm transmitter. (B) While connected, remove the probe from the system. Touch the outside of the probe, if the CAP value doesn't change on the CM, replace the probe and the cable. (A) Remove CM transmitter. Liftprobe leads from the backboard. Ohm check probe ground (GND) and verify it is not shorted. If it is not OPEN, verify probe install. (Insure probe is plumb and not angled and hitting the wall of the pipe. (B) While connected, remove probe from the install; if CAP value drops sharply, then the probe was shorted. Check the probe installation If you have an expected value from the center column, the CM is operating normally in current conditions. Proceed ro the next section 2.5 Modbus Validation 15

23 Installation 2.5 Modbus Validation Establish Modbus communication. Note: The Coriolis provides a Density, Temperature and Flow output Insure that your Modbus wires are installed correctly. Using a voltmeter, measure between A & B terminals. Measurement should be approximately +2.5VDC Determine appropriate Modbus operatiung mode (either Master or Slave) in menu 5.1. Complete the worksheet at the end of this section to use as a reference. Function control of the PLC must be be in mode 4 [read/write] regardless of Master/Slave setting. If you ssee the following locked into the DCM then Modbus is NOT communicating with the DCM. Density --KG/M3-- Temperature --DEGC-- Flow --L/MIN When using the DCM as a Master: If possible, confirm these settings in a workshop prior to site installation with a Modbus simulator on a computer (in Master mode) with the PLC/Flow computer set up used. In our exaples to follow we are using "Simply Modbus" as our simulator. This will enable you to verify Function Control is correct, what Address format (see tabe below) is required for proper communication, as well as verifying hex values sent and received are appropriate. If using a MicroLink RS-485 Converter, ensure the red lead is connected to "B" on the DCM. Address Formt Chart Big Endian Low Byte 1st, High Word 1st Big Endian Swap High Byte 1st, High Word 1st Little Endian Swap Low Word 1st, High Byte 1st Littel Endian Low Word 1st, Low Byte 1st 16

24 Universal IV CM Density Compensated Model 2.5 Modbus Validation (Continued) The following image depicts data simulated as a Coriolis using "Simply Modbus" software. Your settings will likely differ. This is an example of good communicatons 17

25 2.5 Modbus Validation (Continued) In this instance, the green LEDs are lit signifying slave ID and Function Code (fc) match. The data is found and displayed properly, and the cyclic redundancy check (CRC) or checksum was completed successfully. The circled section in the log shows >>> Question from DCM and < Response from simulator/ PLC This is an example of bad communicatons Installation In this instance, the Modbus wires are incorrect, and must be swapped. The first 2 pairs of Hex values should match Slave ID (01) and function code (04) of the DCM. The LEDs are out signifying it is not set up correct, as can be seen with no response given. The circled section in the log shows >>> Question from DCM. There is no response from simulator/ PLC 18

26 Universal IV CM Density Compensated Model 2.5 Modbus Validation (Continued) Again, if you see the following locked into the DCM, Modbus is not communicating with the DCM Density --KG/M3-- Temperature --DEGC-- Flow --L/MIN If you see a density value on the DCM other than 830 KG/M3, data has been received. If the received data does not match the Coriolis, check your address format! Verify DCM density value matches Coriolis. If Coriolis is set to API and DCM is set to Density the measurements may be correct you must ensure the PLC is providing the correct unit conversion. If the DCM willdo do all the conversions, look at the settings for the scalers in STExplorer. Do not change the DCM to output API until the DCM is set up and the first calibration has been performed with oil flow in the system. This can be adjusted through Menu item 1.2 If they do not match, ensure the PLC is converting API to density. By default, the DCM is set to density, but may be changed to API through menu When using the DCM as a Slave: This method is not recommended unless you have a dedicated PLC technician or programer available. Refer to Modbus Register Maps, Section 3.6. Determine appropriate Slave Register Address to write to. Record units and values below.utilize these register addresses when programing your PLC Data Register Density API Density [ / ] Temperature [ Deg ] Volume Flowrate [ / min] Ensure the the DCM menu 5.1 is set to slave Calibrate. Once the system is communicating, prepare system for calibration. Proceed to section and pefrform 1st calibration point. A scond calibration point should be performed once you have a known deviation in API of product of at least 5 API. The greater the chnage the better the DCM can compensate. 19

27 Installation 2.5 Modbus Validation (Continued) 20

28 Universal IV CM Density Compensated Model 2.5 Modbus Validation (Continued) 21

29 Section 3 Configuration & Calibration

30 Universal IV CM Density Compensated Model Section 3: Configuring the Device 3.0 Calibration & Configuration 3.1 Calibration of the Cut Monitor Module Normally the Cut Monitor transmitter will not require calibration. All that is required is it be configured with the correct Water Cut Range. 3.2 Operating the User Interface Configuration and calibration of the DCM is performed via the display keypad or STExplorerTM PC software. Reference Menu Tree (Ref 3.6.) and Configuration Menu Table (Ref 3.5). - When a button is pressed a visual indication appears on the left of the display (Bar). - To access the menu, press and holds the ENTER button for approximately 5 seconds. Note visual indication on left side display increments at 1 bar/second. - Use the UP and DOWN buttons to scroll through the available menu selection items. - Press ENTER to access sub-menu items - To EDIT a value, press the ENTER button once Value will flash on last digit - Navigate left (Back) or right (Enter) to highlight the appropriate character - Settings that can be changed will be flashing - In numeric fields pressing ENTER will move the flashing digit to the right. When the far right digit is flashing pressing ENTER accepts the entry - Press ENTER to accept the change. - In numeric fields pressing back will move the flashing digit to the left. - Press the BACK button to exit to the previous menu level - Pressing and holding the BACK button for 5 seconds exits the menu to the display mode. Note visual indication on left side display increments at 1 bar/second. - The unit will automatically exit the menu and return to normal display if no input is received in 60 approximately seconds 23

31 Configuration and Calibration 3.3 Calibration Modes & Field Calibration Overview There are two different calibration and calculation modes supported by the CM-DC, Two Point and Multi-Cal calculation modes. Each mode is meant to address the different calibration needs of the various processes throughout the handling of crude oil in the oil and gas industry. In general, Two Point calibration is best suited for single stream crude oil handling application like wellhead LACTs. Under typical wellhead LACT applications, changes in oil density are small over time, typically 2-3 API max. Under these conditions, it is recommended that the DCM be configured for Two Point calibration mode and field calibrated per the corresponding calibration process indicated in this section. In oil handling application where it is common for oil API variation to be greater than 3 API or in application where multiple oil streams are processed through the same LACT system, MultiCal calibration mode can provide superior measurement performance. This material variation is typical in Truck Unloading and Rail Car collection stations. Under these conditions, it is recommended that the DCM be configured for MultiCal calibration mode and field calibrated per the corresponding calibration process indicated in this section Setting the Calibtration Mode Use the following procedure to configure the DCM calibration mode. 1. Navigate to the CAL MOD menu at address 2.4 and press ENTER to access menu. a. At his point, the DCM will be displaying the current calibration mode. 2. To change the calibration mode, press ENTER to edit the value, then press UP or DOWN to selected the desired calibration mode and accept the change by pressing ENTER. a. The new calibration mode is now active. 3. Press and hold the BACK button for 5 seconds to return to the meter display Adding a Calibration Point The procedure for adding a calibration point is the same whether the calibration point is for CUTCAL1 (menu address 2.1), CUTCAL2 (menu address 2.2), or MULTCAL (menu address 2.3). CUTCAL1 and CUTCAL2 are used when the DCM is in TWO POINT calibration mode and the MULTCAL menu is used when the DCM is in MULTCAL mode. Please see section for instructions on how to set the calibration mode. 24

32 Universal IV CM Density Compensated Model 3.3 Calibration Modes & Field Calibration (continued) Adding a Calibration Point (continued) Use the following procedure to add a calibration point to the DMC. 1. Navigate to the sub-menu for the calibration point to be added. Use menu address 2.1 for CUTCAL1, menu address 2.2 for CUTCAL2 or menu address 2.3 for MULTICAL and enter the sub-menu. a. NOTE: the X in the following menu address would be determined based on the calibration point being calibrated. 2. Store the required calibration data into the DCM by selecting the STORE function at menu item 2.X.1 and change the value from NO to YES and accept the change by pressing ENTER. a. This stores all the required calibration information into the DCM. 3. Retrieve a sample of the oil being processed and perform a Water Content Test to determine the true percentage of water in the process flow. a. The sample should be collected at the same time that step 2 was completed. This ensures the stored calibration data is representative of the collected sample. b. Either a centripetal or titration testing methods can be used. Which method to use is generally indicated by the site managing contractor. 4. Once the true water content of the collected sample is determined, store the actual water percent into the DCM by selecting the ACT CAL function at menu item 2.X.2. Enter the actual water percent of the sample and accept the change by pressing ENTER. a. This completes the calibration process. 5. Press and hold the BACK button for 5 seconds to return to the meter display. a. The H2O cut should read the entered water cut percentage Clearing a Calibration Point User calibration data can be cleared and reset to default values for either calibration points 1 and 2 as well as all multi point calibration data. This data is independently reset through a dedicated menu in each of the CUTCAL1 (menu address 2.1), CUTCAL2 (menu address 2.2), or MULTCAL (menu address 2.3) menus. To clear the user calibration data, complete the following procedure. 1. Navigate to the sub-menu for the calibration data to be cleared. Use menu address 2.1 for CUTCAL1, menu address 2.2 for CUTCAL2 or menu address 2.3 for MULTCAL and enter the sub-menu. a. NOTE: the X in the following menu address would be determined based on the calibration data to be cleared. 2. Clear the calibration data in the DCM by selecting the CLEAR function at menu item 2.X.3 and change the value from NO to YES and accept the change by pressing ENTER. a. This clears the calibration information in the DCM. 3. Press and hold the BACK button for 5 seconds to return to the meter display. 25

33 Configuration and Calibration 3.3 Calibration Modes & Field Calibration (continued) Two Point Calibration Two point calibration mode uses two fixed material calibrations to model the behavior of the process material being measured. Calibration of the DCM while in Two Point calibration mode involves teaching the DCM the electrical properties over a span of process temperature to ensure the proper correction due to temperature affects. Density correction factors are also calculated during this process. To perform a Two Point Calibration, complete the following calibration process Calibration Procedure for Point 1 1. Complete the initial commissioning process and insure the UIV CM-DC system is properly install and configured. Refer to section 2.0 for details on initial setup and commissioning. 2. Navigate the DCM to the CAL MOD menu at address 2.4 and verify the unit is set to TWO PT to activate the Two Point calibration mode. a. See section 3.2 Operating the User Interface for details on navigating the DCM menu system. b. See section Setting the Calibration Mode for details on verifying and changing the calibration mode. 3. Place the oil processing system into Normal Operating Mode. a. For LACT applications this means actively pumping oil through the wellhead LACT and allowing roughly 1-2 minutes for the system to stabilize and all air/gas to be removed from the system. b. For Truck/Rail Car unloading stations this means actively transferring oil through the unloading LACT and allowing roughly 1-2 minutes for the system to stabilize and all air/gas to be removed from the system. 4. Navigate to the CUTCAL1 sub-menu at menu address 2.1 and enter the sub-menu by pressing ENTER. 5. Add the new calibration point by following the procedure indicated in section Adding a Calibration Point. 6. Press and hold the BACK button for 5 seconds to return to the meter display. a. The H2O cut should read the entered water cut percentage Calibration Procedure for Point 2 1. Calibration of point 2 should be complete after point 1 is calibrated. For the best results, perform calibration of point 2 when the process conditions are at least 10 F different in temperature or 2 API different in density from point Navigate the DCM to the CAL MOD menu at address 2.4 and verify the unit is set to TWO PT to activate the Two Point calibration mode. a. See section 3.2 Operating the User Interface for details on navigating the DCM menu system. b. See section Setting the Calibration Mode for details on verifying and changing the calibration mode. 26

34 Universal IV CM Density Compensated Model Calibration Procedure for Point 2 (continued) 1. Place the oil processing system into Normal Operating Mode. a. For LACT applications this means actively pumping oil through the wellhead LACT and allowing roughly 1-2 minutes for the system to stabilize and all air/gas to be removed from the system. b. For Truck/Rail Car unloading stations this means actively transferring oil through the unloading LACT and allowing roughly 1-2 minutes for the system to stabilize and all air/gas to be removed from the system. 4. Navigate to the CUTCAL2 sub-menu at menu address 2.3 and enter the sub-menu by pressing ENTER. 5. Add the new calibration point by following the procedure indicated in section Adding a Calibration Point. 6. Press and hold the BACK button for 5 seconds to return to the meter display. The H2O cut should read the entered water cut percentage MultiCal - Multi Point Calibration MultiCal is used in applications where the process material is regularly changing. This is typical in truck and rail unloading stations as well as custom processes where batches of material are processed. This calibration and calculation mode holds up to 10 separate calibration points used to profile the material being presented to the CM-DC system. Once calibrated, the DCM will actively determine the calibration values to uses by searching all available calibration points and selecting the best match to the material currently being processed. When the next load/batch of oil is processed, the system will automatically reselect the best calibration settings. New calibration data can be added at any time and will automatically be managed by the DCM. For best results, at least 2 calibration data points should be added for each different material presented to the system. These 2 calibration points are recommended to be at least 10 F different in material temperature if possible. This can be done over the course of several hours or days as the availability of the material and its temperature allow. Other material calibration points may also be added between the time point 1 and point 2 of a given material are calibrated. Once all 10 calibration positions are filled, the DCM will begin overwriting the oldest calibration point. It is also recommended that if the DCM is indicating an accurate density corrected water cut percentage that the system NOT be calibrated as this may cause undesirable results. 27

35 Configuration and Calibration Calibration Procedure for MultiCal 1. Complete the initial commissioning process and insure the UIV CM-DC system is properly install and configured. Refer to section 2.0 for details on initial setup and commissioning. 2. Place the oil processing system into Normal Operating Mode. a. For LACT applications this means actively pumping oil through the wellhead LACT and allowing roughly 1-2 minutes for the system to stabilize and all air/gas to be removed from the system. b. For Truck/Rail Car unloading stations this means actively transferring oil through the unloading LACT and allowing roughly 1-2 minutes for the system to stabilize and all air/gas to be removed from the system. 3. Navigate the DCM to the CAL MOD menu at address 2.4 and verify the unit is set to MULTCAL to activate the Multi Point calibration mode. a. See section 3.2 Operating the User Interface for details on navigating the DCM menu system. b. See section Setting the Calibration Mode for details on verifying and changing the calibration mode. 4. Navigate to the MULTCAL sub-menu at menu address 2.3 and enter the sub-menu by pressing ENTER. 5. Add the new calibration point by following the procedure indicated in section Adding a Calibration Point. 6. Press and hold the BACK button for 5 seconds to return to the meter display. The H2O cut should read the entered water cut percentage. 28

36 Universal IV CM Density Compensated Model 3.4 Menu Tree 29

37 Configuration and Calibration 3.5 Menu Table 1 Menu Function (Display Abbreviation) Setup (SETUP) Configuration Menu Table Values (Display Abbreviation) Description 1.1 UNITS OF MEASUREMENT (UNITS) 1.2 DENSITY UNITS (DEN UNT) English Metric [Default] API [Default] STD Basic units of measurement of all entities Selects units for view and entering density related data 2 LIVE CAIBRATION (CAL) 2.1 FIRST CAL POINT (CUTCAL1) STORES REQUIRED CAL DATA (STORE) ENTER ACTUAL PCT_H20 FOR CAL POINT (ACT CAL) CLEARS USER CAL DATA (CLEAR) 2.2 SECOND CAL POINT (CUTCAL2) STORES REQUIRED CAL DATA (STORE) ENTER ACTUAL PCT_H20 FOR CAL POINT (ACT CAL) CLEARS USER CAL DATA (CLEAR) 2.3 MULTI POINT CAL (MLTICAL) YES NO [Default] Numeric value YES NO [Default] YES NO [Default] Numeric value YES NO [Default] Used when a sample can be evaluated on site and results entered when the same temperature and cut conditions apply Stores the measurement parameters required Enter the actual water cut determined from sample Clears the calibration data for point 1 Stores the measurement parameters required Enter the actual water cut determined from sample Clears the calibration data for point 2 30

38 Universal IV CM Density Compensated Model 3.5 Menu Table (Continued) Menu Function (Display Abbreviation) STORES REQ CAL DATA (STORE) ENTER ACTUAL PCT_H20 FOR CAL POINT (ACT CAL) CLEARS USER CAL DATA (CLEAR) 2.4 CALCUALTION MODE (CAL MOD) YES Values (Display Abbreviation) NO [Default] Numeric value YES NO [Default] Two Point [Default] Multi Cal Description Stores the sample data point Enter the actual water cut determined from sample Clears the calibration data for this point Selects two point or multipoint calibration mode 3 OUTPUT (OUTPUT) 3.1 LOW RANGE VALUE (LRV) 3.2 UPPER RANGE VALUE (URV) 3.3 SETUP DAMPIING (DAMPING) SELECT DAMPING MODE (MODE) ENTER DAMPING TIME (TIME) 3.4 DIVERSION RELAY (DIV RLY) ENABLE/DISABLE DIVERT RELAY (DIV ENA) DIVERSION SETPOINT (DIV SET) DIV TIME ON DELAY IN SECONDS (DLY ON) DIV TIME OFF DELAY IN SECONDS (DLY OFF) Numeric value Lower Range Value in % water equivalent to 4 ma 0 output. Typically not required to be changed Numeric value Upper Range Range Value in % water equivalent to 1 20 ma output. Loop current damping factor 0 None 1 LC Only 2 Digital, 3 Both 0-9 Seconds Eneter damping time in seconds Enable Enables or Disables the divert relay Disable [Default] Numeric value Enter the threshold in % watercut to toggle the relay [Default] Numeric Value [Default] Numeric Value [Default] 31

39 Configuration and Calibration 3.5 Menu Table (Continued) Menu Function (Display Abbreviation) 3.5 4MA TRIM (TRIM 4) MA TRIM (TRIM 20) 3.7 FIXED LOOP CURRENT OUTPUT (FIX OUT) Values (Display Abbreviation) Numeric Value 4 Numeric Value 20 Numeric Value 4 Description Setsthe loop current for the 4mA trim Sets the loop current for the 20mA trim Used to set the fixed loop current output for diagnostic purposes 4 UIV CUT MONITOR (UIV CM) 4.1 PADDED CAPACITANCE VALUE (PAD CAP) 4.2 RANGE OF CAPACITANCE (RANGE) 4.3 ENABLE/DISABLE HART 5 COMMUNICATIONS (CM COMM) 4.4 COMMUNICATIONS TEST WITH UIV CM (COM TST) Numeric Value 0-No Upper Value (read Only) 1 Enable [Default] DIsable Value (Read Only) Success Failure Padded Cap Value Selects the range of capacitance Enables or disables the HART 5 communications Indicates the status of the HART 5 Communications 5 (CORIOLIS) 5.1 CONFIGURE CORIOLIS AS MASTER/ SLAVE (MODE) 5.2 COMMUNICATION SETUP (COM SET) SET BAUD RATE (BAUD) SET NUM OF BITS IN DATABYTE (BITS) SET STOP BITS (ST BIT) Master [Default] Slave Numeric Value 1200, 9600, 9200, etc [Default] Value 7 or 8 [Default] Value 0 or 1 [Default] 32 Used to configure Coriolis as master or slave Communications settings for the Coriolis meter Baud Rate Used to set then umber of bits in a databyte Sets the stop bits

40 Universal IV CM Density Compensated Model 3.5 Menu Table (Continued) SET PARITY (PARITY) Menu Function (Display Abbreviation) MODBUS PROTOCOL FRAME FORMAT (PROTOCOL) MODBUS RESPONSE TIMOUT (TIMEOUT) CONFIGURE AS MASTER OR SLAVE (CONFIG) /16 BIT ADDRESS BYTES (BYTES) SET LITTLE/BIG ENDIAN ADDRESS (ADD FMT) SET SLAVE ADDRESS ID (SLAV ID) 5.3 MODBUS REGISTER SETTINGS (REG SET) DENSITY (DENSITY) ENA/DIS (ENA/DIS) ADDRESS (ADDRESS) SET THE DATA TYPE (DTA TYP) RESISTER (SCALER) FLOW (FLOW) ENA/DIS (ENA/DIS) 1 Even Values (Display Abbreviation) 2 Odd [Default] 1 RTU [Default] 0 ASCII [Default] 0=8 1=16 [Default] 2=32 0=Big-Endian, 2=Big-Endian Swap 1=Little-Endian Swap [Default] 3=Little-Endian [Default] Enable Disable Numeric Value 0-No Upper 249 [Default] Integer Long Float [Default] Enron 1 [Default] Enable Disable 33 Description Sets the parity Sets the Modbus protocol frame format Eneter Modbus Response Timeout Used to configure the master/slave Used to set the number of address bytes Used to set the format of the address Used to set the slave address ID Sets the data type of the data

41 Configuration and Calibration 3.5 Menu Table (Continued) ADDRESS (ADDRESS) Menu Function (Display Abbreviation) SET THE DATA TYPE (DTA TYP) RESISTER (SCALER) TEMPERATURE (TEMP) ENA/DIS (ENA/DIS) ADDRESS (ADDRESS) SET THE DATA TYPE (DTA TYP) RESISTER (SCALER) 5.4 AUTO DETECT MODBUS (AUTODET) TEST ADDRESS (TST ADD) TEST VALUE (TST VAL) PERFOM AUTO-DTEC (DETECT) 5.5 FLOWRATE DETECT (FLW DET) TEST ADDRESS (EN/DIS) FLOWRATE THRESHOLD (FLW THR) Values (Display Abbreviation) Numeric Value 0-No Upper 253 [Default] Integer, Long, Float [Default], Enron 1 [Default] Enable [Default] Disable Numeric Value 0-No Upper 251 [Default] Integer,Long Float [Default], Enron 1 [Default] Numeric Value 0-No Upper 249 [Default] Numeric Value 0-No Upper [Default] Yes No [Default] Enable Disable [Default] Numeric Value 0-No Upper 10 [Default] Description Sets the data type of the data Sets the data type of the data Used to auto detect the Modebus settings Used to test reister address The expected test value Executes the auto detect functuionality USed to detect when there is low process flow Enable or disable the flowrate detection Sets the flowrate detect threshold 34

42 Universal IV CM Density Compensated Model 3.5 Menu Table (Continued) 6 DISPLAY (DISPLAY) 6.1 Menu Function (Display Abbreviation) ENABLE/DISABLE AUTO TOGGLE (TOGGLE?) 6.2 %WATER OUT (H20) 6.3 CAP (CAP) MA (4-20) 6.5 DENSITY (DENSITY) 6.6 TEMP (TEMP) 6.7 FLOW (FLOW) Yes Values (Display Abbreviation) No [Default] Enable [Default] Disable Enable [Default] Disable Enable [Default] Disable Enable [Default] Disable Enable [Default] Disable Enable [Default] Disable Description Used to determine if paremeters list will be auto toggled in meter mode Percentage water cut Capacitance value 4-20 ma current output Density fro the Coriolis Temperature of the mixture Flow rate 7 SERVICE (SERVICE) 7.1 RESTORE FACTORY DEFAULTS OF SYSTEM (RST FAC) 7.2 LCD CONTRAST ADJUSTMENT (CONTRST) 7.3 SOFTWARE VERSIONS (SW VER) RCM VERSION (RCM VER) CUT MONITOR PRE AMP VERSION (PREAMP) Yes No [Default] Value [Default] Value Read only Date Code Value Read only Date Code Restore factory defaults of the system Used to adjust the contrast ratio of the LCD screen 35

43 Configuration and Calibration 3.5 Menu Table (Continued) Menu Function (Display Abbreviation) CUT MONITOR OUTPUT MODULE (CUT MOD) 7.4 MENU SCROLL ENABLE/DISABLE (MSCROLL) 7.5 PARAMETER DISPLAYED ON POWERUP (MENUIDX) 7.6 CALIBRATION PARAETERS (CAL PAR) OIL DIELECTRIC CONSTANT A (AKOD) OIL DIELECTRIC CONSTANT B (BKOD) EFFECTIVE CAPACITANCE (EFF CAP) EFFECTIVE DENSITY (EFF DEN) EFFECTIVE TEMPERATURE (EFF TMP) Value Values (Display Abbreviation) Read only Date Code Enable [Default] Disable 0=H20 [Default] 1=Capacitance 2=4-20mA 3=Density 4=Temperature 5=Flow Value (Ref Only) Value (Ref Only) Value (Ref Only) Description Enable or Disables the scrolling of menu descriptions Parameter displayed on powerup Oil Constant Dielectric Parameter A Oil Constant Dielectric Parameter B Effective Capacitance on Calibration 1 pf Value (Ref Only) Effective Density on Calibration 1 KG/M 3 Value (Ref Only) Effective Temperature on Calibration 1 Deg C 36

44 Universal IV CM Density Compensated Model 3.6 Modbus Register Maps Integer (16 bit signed) Formats Signed 16 bit Integer, 16 bits of data per register 1 Register needed to get value English Units, inches & degrees F Signed 16 bit Integer, 16 bits of data per register 1 Register needed to get value Metric Units, centimeters & degrees C Enron Modbus, Signed 16 bit Integer, 16 bits of data per register 1 Register needed to get value English Units, inches & degrees F 37

45 Configuration and Calibration Integer Formats (continued) Enron Modbus, Signed 16 bit Integer, 16 bits of data per register 1 Register needed to get value Metric Units, centimeters & degrees C Floating Point Formats Floating Point, 32 bit Integer, 16 bits of data per register Two registers needed to get value English Units, inches & degrees F Floating Point, 32 bit Integer, 16 bits of data per register Two registers needed to get value Metric Units, centimeters & degrees C 38

46 Universal IV CM Density Compensated Model Floating Point Format (Continued) Floating Point, 32 bit Integer, 32 bits of data per register Two registers needed to get value English Units, inches & degrees F Floating Point, 32 bit Integer, 32 bits of data per register 2 registers needed to get value Metric Units, centimeters & degrees C Enron Modbus, Floating Point, 32 bit Integer, 32 bits of data per register 1 Register needed to get value English Units, inches & degrees F 39

47 Configuration and Calibration Floating Point Format (Continued) Enron Modbus, Floating Point, 32 bit Integer, 32 bits of data per register 1 Register needed to get value Metric Units, centimeters & degrees C Long Integer (32 bit) Formats Long Integer, 32 bit, 16 bits of data per register Two registers needed to get value English Units, inches & degrees F Long Integer, 32 bit, 16 bits of data per register Two registers needed to get value Metric Units, centimeters & degrees C 40

48 Universal IV CM Density Compensated Model Long Integer (32 bit) Formats (Continued) Long Integer, 32 bit, 32 bits of data per register Two registers needed to get value English Units, inches & degrees F Long Integer, 32 bit, 32 bits of data per register Two registers needed to get value Metric Units, centimeters & degrees C Enron Modbus, Long Integer, 32 bit, 32 bits of data per register 1 Register needed to get value English Units, inches & degrees F 41

49 3.6.3 Long Integer (32 bit) Formats (Continued) Enron Modbus, Long Integer, 32 bit, 32 bits of data per register 1 Register needed to get value Metric Units, centimeters & degrees C Configuration and Calibration 42

50 Universal IV CM Density Compensated Model 3.7 Configuration Configuration consists of verifying the following parameters are set properly and editing them as required. Default settings are specified in the Configuration Menu Table (Ref 3.2.2). Setup: 1.1 and 1.2 Output: 3.1 through 3.4 Coriolis: 5.1 through 5.3 Display: 6.1 through 6.6 Service: 7.1 through Auto Detect Due to the complex nature of Modbus setups we are providing a function that automatically detects the attached Modbus device settings. There are several pieces of basic communications information that once configured, the remaining settings can be automatically detected by the DCM Using Auto Detect A. Configure the basic communications settings. These settings are retrieved from the connected Modbus device and then entered into the DCM using the below menu items. 1. Baud Rate [Menu Address 5.2.1] 9600 [DEFAULT] 2. Data Bits [Menu Address 5.2.2] 8 Bits [DEFAULT] 3. Stop Bits [Menu Address 5.2.3] 1 [DEFAULT] 4. Parity [Menu Address 5.2.4] Odd [DEFAULT] B. Configure the auto detect test settings. 1. Test Address [Menu Address 5.4.1] 249 [DEFAULT] 2. Test Value [Menu Address 5.4.2] [DEFAULT] C. Perform the auto detect operation 1. Detect [Menu Address 5.4.3] No [DEFAULT] D. Navigate to the above menu address and change the value to Yes. This will start the auto detection process. E. Upon completion of the auto detection process, if successful, the display will indicate Success and the updated device settings will be applied. If the auto detection process is unsuccessful the display will read Failed - Check Comm Settings and no device settings will be changed. For additional information reference section 5.2 Troubleshooting autodetect failure. 43

51 Section 4 Specifications

52 Universal IV CM Density Compensated Model Section 4: Specifications 4.1 Transmitter Specifications Technology RF Admittance / Capacitance Supply Voltage 19-30VDC, 4-wire external powered Ouput/Digital Protocol 4-20mA, HART Compatible with HART Accuracy and Resolution Water Cut Nominal Water Cut Water Cut Range Resolution** Variance* 0 to 1% +/ to 5% +/ * The measurement accuracy of an inline, dynamic water cut measurement is dependent upon many process variables including: oil dielectric consistency, fluid velocity at the sample point, mounting geometry and homogeneity of the oil/water emulsion. The values above represent nominal water cut measurement variances for a properly installed sensor under consistent measurement point conditions. ** The smallest water cut step that the instrument can resolve Load Resistance Maximum 550 ohms at 30 VDC Minimum 250 ohms for HART protocol Ambient Temperature -40 C to 75 C (-40 F to 167 F) Process Temperature Up 232 C (450 F) Transmitter will compensate for the effects of temperature when the water is in liquid state (eg. 32 F to 212 F (-0 C to 100 C at ambient pressure) Process Pressure Up 103 bar (1,500 psi), probe dependent Density Transmitter will compensate for the effects of changing density in the process flow Response Time 350 msec nominal (no damping applied) 1-90 seconds programmable damping time Supply Voltage Effect 0.2% of full scale max Start-Up Time < 12 seconds Configuration and Calibration Standard LCD display and keypad are built-in STExplorer PC-based software (free download) Emission and Surge Protection Compliant with IEC , 3, 4, 6, 8 Compliant with CISPR11 Group I, Class B Enclosure Rating Meets Environmental Protection to NEMA 4X & IP66 Approvals Intrinsically Safe (IS) Explosion Proof (XP) without IS barrier FM, FMc, ATEX, IECEx CE Mark 45

53 Section 5 Normal Maintenance

54 Universal IV CM Density Compensated Model Section 5: Troubleshootioing 5.1 Identifying a Problem/Symptom Use Table 5-1 as a guide to find and correct a problem when it occurs. Most problems are not related to transmitter failure. It is important to be methodical when tracking down a problem. If you experience a problem that you cannot solve using this guide, call the Drexelbrook 24- hour Service You may also us: drexelbrook.service@ametek.com. Further service information may be found at our World Wide Web address When you contact us, be prepared to give the service person as much information as you can about the model numbers, serial numbers, application requirements, and the materials 5.2 Troubleshooting Connections When troubleshooting the connections, verify the following items. 1. Loop devices are wired in series. 2. There is at least 250 ohms total loop resistance for HART communications. 3. There is at least 19 VDC available for the transmitter when a loop current of 20 ma is flowing. 4. The open circuit voltage does not exceed 30 VDC 5. Power the unit from a portable source. 3 9 volt batteries in series will produce 27 VDC 47

55 Normal Maintenance Table 5.1 Problem /Symptom Tests in order of probability No display on DCM Check power Section Reference Comments No display on U-IV CM Check power at DCM Section Check power at UIV-CM U-IV CM manual Can t communicate HART with Check modem is connected to Section Often a result of loop connection DCM using Drexelbrook PC correct loop connections problems or output current > 20 Software Check for 250 Ω resistance (min.) ma in the loop. Check voltage at DCM Try another modem Power from a battery source 0 ma output all the time Check voltage at transmitter Section Probable loop problem. (no measurable output current at Check polarity of loop Faulty connection in loop any time) No Modbus communication Verify wiring on terminals A and B Section Wiring/polarity incorrect More than 20 ma output all the Check display for error message Table 5-2 Probable fault condition time Check for moisture in housing Output erratic - (output jumps Check probe and cable U-IV CM manual Erratic readings often show actual around noticeably in terms of Check for radio interference process conditions. Look for seconds or minutes) Check for noise on loop bubbles. stratification, etc Output intermittent (output jumps Check signal loop connections Section Intermittent loop connection quickly usually between >4mA Possible water slug and some on scale value Inaccurate readings (% water Check calibration Section 3.2 readings are incorrect compared Check method of comparison to sample) Reading does not change with Check cables U-IV CM manual Verify % water reading water cut Check sensing element URV too high Check LRV/URV Output goes in opposite direction from water cut change Check LRV/URV Configuration Menu Table Probable LRV/URV reversal 48

56 Universal IV CM Density Compensated Model Table 5.1 (Continued- Application Related Problems) Problem /Symptom Gas bubbles Separation of oil and water Tests in order of probability Reference DCM display error code See Error code table 5.2 Comments The presence of gas bubbles will decrease the dielectric constant of the liquid and therefore the reading. Bubbles must be eliminated for proper operation. Situations that can result in pressure drops, such as changing pipe diameters, should be avoided A homogeneous mixture is required for proper operation. Consider using an upstream mixer if separation is suspected 49

57 Normal Maintenance 5.3 Error Codes There are 3 levels of error codes that are displayed by the DCM Failure: Unit failed and is not capable of providing a measurement. Current is set to 22 ma Error: A problem has been detected. Unit is capable of providing a measurement but accuracy may be reduced. Warning: An unusual condition has been detected. Unit is operational and accuracy is not affected. Table 5.2 Code Display Message Description Actions FAILURE 01 CALCULATION INVALID DATA Entered and measured 1. Cycle power. FAILURE parameters cannot be used for 2. Hardware Failure - Contact calculations factory FAILURE 02 CALCULATION INVALID Calculation failure 1. Check U-IV is operating RESULT FAILURE properly 2. Verify capacitance >25pF; if > 50pF consult factory 3. Verify temperature and density inputs from Coriolis are correct 4. Consult factory FAILURE 03 FLASH CKSM FAILURE Factory flash checksum failure Lost factory calibration/trim values FAILURE 04 IM CRITICAL COMM LOSS Inter microprocessor loss of FAILURE communication Hardware Failure - Contact factory 1. Check Loop Voltage. 2. Hardware Failure - Contact factory FAILURE 05 MB MASTER CRITICAL COMM Modbus master no response Check connections to DCM or LOSS FAILURE Terminating resistor FAILURE 06 MB MASTER INVALID Modbus master received an Check Modbus configuration. RESPONSE FAILURE invalid response Ref Configuration Menu Table sections 5 & 6. Verify data addresses are correct. If they are correct try incrementing the address by 1. Addresses should always be odd. FAILURE 07 MB SLAVE INVALID REQUEST Modbus slave received an invalid Check Modbus configuration. FAILURE request Ref Configuration Menu Table section 5 FAILURE 08 HART 5 CRITICAL COMM LOSS Hart Master connection failure Hardware Failure - Contact FAILURE factory 50

58 Universal IV CM Density Compensated Model 5.3 Error Codes (Continued) Table 5.2 Code Display Message Description Actions ERROR 01 CALCULATION K EFF EXCEEDS Calculated effective dielectric 1. Cycle power. K H2O ERROR constant exceeds water dielectric 2. Hardware Failure - Contact constant factory ERROR 02 CALCULATION EFF CAP Calculated effective capacitance 1. Calibrate DCM RANGE ERROR is outside of expected limits 2. Verify U-IV CM is operating correctly. Reference U-IV CM manual 3.Contact factory ERROR 03 CALCULATION AIR CAP RANGE Calculated air capacitance is 1. Verify U-IV CM & Coriolis are ERROR outside of expected limits operating correctly. 2. Verify Cut Monitor is for the correct pipe size. 3.Contact factory ERROR 04 CALCULATION EFF DENSITY Calculated effective (mixture) 1. Verify U-IV CM & Coriolis are RANGE ERROR density is outside of expected operating correctly limits 2.Contact factory ERROR 05 CALCULATION H2O DENSITY Calculated water density is 1. Verify U-IV CM & Coriolis are RANGE ERROR outside of expected limits operating correctly 2.Contact factory ERROR 06 CALCULATION OIL DENSITY Calculated oil density is outside of 1. Verify U-IV CM & Coriolis are RANGE ERROR expected limits operating correctly 2.Contact factory ERROR 07 CALCULATION TEMPERATURE RANGE ERROR Calculated temperature is outside of expected limits ERROR 08 CALCULATION K EFF RANGE Calculated effective dielectric ERROR constant is outside of expected limits ERROR 09 CALCULATION K EFF RANGE Calculated water dielectric ERROR constant is outside of expected limits ERRPR 10 CALCULATION FLOWRATE THRESHOLD ERROR Flow rate has dropped below threshold. Density value is locked on last density before threshold drop ERROR 11 FIELD FLASH CKSM ERROR Field flash checksum failure Lost customer configuration ERROR 12 IM INTERMITTENT COMM LOSS Inter microprocessor intermittent ERROR loss of communication 1. Verify U-IV CM & Coriolis are operating correctly 2.Contact factory 1. Verify U-IV CM & Coriolis are operating correctly 2.Contact factory 1. Verify U-IV CM & Coriolis are operating correctly 2.Contact factory 1. If system is not running, no action required 2. Verify Coriolis operating properly 3. Consult factory Reconfigure DCM No Action required 51

59 Normal Maintenance 5.3 Error Codes (Continued) Table 5.2 Code Display Message Description Actions ERROR 13 MB INTERMITTENT COMM LOSS ERROR Modbus master intermittent loss of communication Check connections to DCM or Terminating resistor ERROR 14 MB MASTER INVALID RESPONSE ERROR Modbus master error in response Modbus setup error - check register addresses. If they are correct, try incrementing the address by 1. Addresses should always be odd. ERROR 15 MB INVALID DENSITY VALUE ERROR Modbus density value is outside of expected limits (<700 / >1050) 1. Verify value vs. Coriolis. If the same no action required. 2. Modbus setup error - check register addresses. If they are correct, try incrementing the address by 1. Addresses should always be odd. DCM in master mode only 3. Verify parameter is enabled ERROR 16 MB INVALID TEMPERATURE VALUE ERROR Modbus temperature value is outside of expected limits (<-50 C / >300 C) 1. Verify value vs. Coriolis. If the same no action required. 2. Modbus setup error - check register addresses. If they are correct, try incrementing the address by 1. Addresses should always be odd. DCM in master mode only 3. Verify parameter is enabled ERROR 17 MB INVALID FLOWRATE VALUE ERROR Modbus flow rate value is outside of expected limits 1. Verify value vs. Coriolis. If the same no action required. 2. Modbus setup error - check register addresses. If they are correct, try incrementing the address by 1. Addresses should always be odd. DCM in master mode only 3. Verify parameter is enabled ERROR 18 MB SLAVE INVALID REQUEST ERROR- Modbus slave error in request Modbus setup error - check register addresses ERROR 19 HART 5 INTERMITTENT COMM LOSS ERROR HART5 intermittent comm. loss ERROR 20 PV OVER RANGE WARNING ERROR 21 PV OVER RANGE ERROR WARNING 01 HART 5 COMM DISABLED WARNING HART5 has been disabled by the user 52

60 Page Has No Content

61 Section 6 Hazardous Locations

62 Universal IV CM Density Compensated Model Section 6: Hazardous Location Approval Supplementary Installation & Operating Instructions 6.1 General safety information Warning Device Description This document contains installation instructions for potentially explosive atmosphere applications. The Universal U IV CM Denisty Compensation System is approved for use in hazardous locations when properly installed. Control drawings detailing installation guidelines are available in Section 6.4. Always Install to Local Codes / Requirements / Directives as Mandated by the Authority Having Jurisdiction. The aluminum enclosure must be protected from mechanical friction and impact that could cause ignition capable sparks. Installation, Start-Up, and Service should only be performed by personnel trained in explosive atmosphere installations. Substitution of Components May Impair Intrinsic Safety. Each AMETEK Drexelbrook Universal IV CM-DC system consists of a Density Compensation unit - Power - four-wire - HART ma - Modbus UIV CM or UIV CMT RF Admittance transmitter -with a 700 series sensing element Capacitance is transmitted to the DCM from a UIV CM via HART 5.0. Required density and temperature data are transmitted to the DCM via Modbus from an external source such as a Coriolis meter. Configuration and calibration of the DCM is accomplished via the onboard keypad and LCD display Or Remotely by a PC running STExplorer T.M. software with a HART modem 55

63 Hazardous Locations Electrical connection Commissioning WARNING! Read the following information carefully. Live Maintenance should only be carried out by Skilled Personnel trained in explosion protection methods. Test Equipment used to perform Live Maintenance must be certified to use in the associated hazardous area. Intrinsically Safe Installations When the Universal IV CM Density System is installed as an intrinsically safe device per the agency control drawings, the housing cover may be safely opened. For system configuration, remove the view port housing cover to access the display keypad for local system configuration. Explosionproof or Flameproof Installations No Live maintenance is permitted. Disconnect power to the device and check that the atmosphere is clear of hazardous substances. Start-up checklist Do not connect power until you have gone through the checklist below 1. Are the wetted components (gasket, flange and sensing element) resistant to the corrosive properties of the tank product? 2. Does the information given on the nameplate correspond with the application? 3. Ex d applications: Have you connected the equipotential bonding system correctly? 4. Ex i applications: Are you using an intrinsic barrier within the correct parameters? 5. Did you install cable entries of the correct internal diameter so that there is a good seal around the cable? Are the cable glands suitably certified per the application and the hazardous area parameters? 6. Do not use the earth terminal in the wiring compartment: use the equipotential bonding system. 6.2 The Compartment Cover Viewport Cleaning: The viewport is made of Borosilicate glass and can be cleaned with any common glass cleaning product (e.g.: Windex, Isopropyl alcohol, etc.) that is suitable for the Class and Division rating of the specific system installation. 56

64 Universal IV CM Density Compensated Model Opening the cover Procedure 1. Unscrew cover stop, if applicable 2. Unscrew terminal compartment cover Closing the cover Warning: Ex d [ia] applications Check that the terminal compartment cover is screwed tight and the cover stop (if applicable) is fastened tightly to the cover. 6.3 Standards and Approvals FM US Approvals - Install per CD TThe Density Compensation Module is rated as Explosionproof for Class I, Division 1, Groups C & D; Dust lgnitionproof for Class II & Ill, Division 1, Groups E-G and Class I, Zone 1, Group lib Hazardous (Classified) Locations with an integral sensor that is Intrinsically Safe for Class I, II & Ill, Groups A-G and Class I, Zone 1 Hazardous (Classified) Locations. The Remote version is rated as Explosionproof Class I, Division 1, Groups C & D; Dust-lgnitionproof for Class II & Ill, Division 1, Groups E-G and Class I, Zone 1, Group lib Hazardous (Classified) Locations with connections to a 700 Series sensor that is Intrinsically Safe for Class I, II & Ill, Groups A-G and Class I, Zone 1 Hazardous (Classified) Locations FM Canada Approvals - Install per CD The Density Compensation Module is rated as Explosionproof for Class I, Division 1, Groups C & D; Dust lgnitionproof for Class II & Ill, Division 1, Groups E-G and Class I, Zone 1, Group lib Hazardous Locations with an integral sensor that is Intrinsically Safe for Class I, II & Ill, Groups A-G and Class I, Zone 1 Hazardous Locations. The Remote version is rated as Explosionproof Class I, Division 1, Groups C & D; Dust-lgnitionproof for Class II & Ill, Division 1, Groups E-G and Class I, Zone 1, Group lib Hazardous Locations with connections to a 700 Series sensor that is Intrinsically Safe for Class I, II & Ill, Groups A-G and Class I, Zone 1 Hazardous Locations.Class I, Zone 1, Group lib Hazardous Locations with connections to a 700 Series sensor that is Intrinsically Safe for Class I, II & Ill, Groups A-G and Class I, Zone 1 Hazardous Locations. 57

65 Hazardous Locations 6.3 Standards and Approvals (Continued) ATEX Approvals - Install per CD Universal IV Level Transmitter Remote Density Communications Module II 2 G Ex d IIB T4 Gb II 2 D Ex tb IIIC T90 C Db -40 C Ta +75 C; IP66 FM12ATEX0018X SPECIFIC CONDITIONS OF USE: THE APPARATUS ENCLOSURE CONTAINS ALUMINUM AND IS CONSIDERED TO CONSTITUTE A POTENTIAL RISK OF IGNITION BY IMPACT OR FRICTION. CARE MUST BE TAKEN INTO ACCOUNT DURING INSTALLITION AND USE TO PREVENT IMACT OR FRICTION IECEx Approvals - Install per CD Universal IV Level Transmitter Remote Density Communications Module Ex d ia IIB T4 Gb Ex tb ia IIIC T90 C Db -40 C Ta +75 C; IP66 IECEx FMG X SPECIFIC CONDITIONS OF USE: THE APPARATUS ENCLOSURE CONTAINS ALUMINUM AND IS CONSIDERED TO CONSTITUTE A POTENTIAL RISK OF IGNITION BY IMPACT OR FRICTION. CARE MUST BE TAKEN INTO ACCOUNT DURING INSTALLITION AND USE TO PREVENT IMACT OR FRICTION 58

66 Page Has No Content

67 Section 7 Control Drawings

68 Universal IV CM Density Compensated Model Section 7.0: Control Drawings 7.1 ATEX / IECEX 61

69 Control Drawings 7.1 ATEX / IECEX (Continued) 62

70 Universal IV CM Density Compensated Model 7.1 ATEX / IECEX (Continued) 63

71 Control Drawings 7.1 ATEX / IECEX (Continued) 64

72 Universal IV CM Density Compensated Model 7.1 ATEX / IECEX (Continued) 65

73 Control Drawings 7.1 ATEX / IECEX (Continued) 66

74 Universal IV CM Density Compensated Model 7.1 ATEX / IECEX (Continued) 67

75 Control Drawings 7.1 ATEX / IECEX (Continued) 68

76 Universal IV CM Density Compensated Model 7.2 FM US / FMC 69

77 Control Drawings 7.2 FM US / FMC (Continued) 70

78 Universal IV CM Density Compensated Model 7.2 FM US / FMC (Continued) 71

79 Control Drawings 7.2 FM US / FMC (Continued) 72

80 Universal IV CM Density Compensated Model 7.2 FM US / FMC (Continued) 73

81 Control Drawings 7.2 FM US / FMC (Continued) 74

82 Universal IV CM Density Compensated Model 7.2 FM US / FMC (Continued) 75

83 Control Drawings 7.2 FM US / FMC (Continued) 76

84 Universal IV CM Density Compensated Model 7.2 FM US / FMC (Continued) 77

85 Control Drawings 7.2 FM US / FMC (Continued) 78

86 Universal IV CM Density Compensated Model 7.2 FM US / FMC (Continued) 79

87 Control Drawings 7.2 FM US / FMC (Continued) 80

88 Universal IV CM Density Compensated Model 7.2 FM US / FMC (Continued) 81

89 Control Drawings 7.2 FM US / FMC (Continued) 82

90 Universal IV CM Density Compensated Model 7.2 FM US / FMC (Continued) 83

91 Control Drawings 7.2 FM US / FMC (Continued) 84

92 Universal IV CM Density Compensated Model 7.2 FM US / FMC (Continued) 85

93 Control Drawings 7.2 FM US / FMC (Continued) 86

94 Universal IV CM Density Compensated Model 7.2 FM US / FMC (Continued) 87

95 Control Drawings 7.2 FM US / FMC (Continued) 88

96 Page Has No Content

97 Section 8 Approval Certificates

98 Universal IV CM Density Compensated Model Section 8.0: Approval Certificates 8.1 FM US Approval Certificate 91

99 Approval Certificates 8.1 FM US Approval Certificate (Continued) 92

100 Universal IV CM Density Compensated Model 8.1 FM US Approval Certificate (Continued) 93

101 Approval Certificates 8.1 FM US Approval Certificate (Continued) 94

102 Universal IV CM Density Compensated Model 8.1 FM US Approval Certificate (Continued) 95

103 Approval Certificates 8.1 FM US Approval Certificate (Continued) 96

104 Universal IV CM Density Compensated Model 8.1 FM Canada Approval Certificate 97

105 Approval Certificates 8.1 FM Canada Approval Certificate (Continued) 98

106 Universal IV CM Density Compensated Model 8.1 FM Canada Approval Certificate (Continued) 99

107 Approval Certificates 8.1 FM Canada Approval Certificate (Continued) 100

108 Universal IV CM Density Compensated Model 8.1 FM Canada Approval Certificate (Continued) 101

109 Approval Certificates 8.1 FM Canada Approval Certificate (Continued) 102

110 Universal IV CM Density Compensated Model 8.2 IECEx Approval Certificate 103

111 Approval Certificates 8.2 IECEx Approval Certificate (Continued) 104

112 Universal IV CM Density Compensated Model 8.2 IECEx Approval Certificate (Continued) 105

113 Approval Certificates 8.2 IECEx Approval Certificate (Continued) 106

114 Universal IV CM Density Compensated Model 8.2 ATEX Approval Certificate 107

115 Approval Certificates 8.2 ATEX Approval Certificate (Continued) 108

116 Universal IV CM Density Compensated Model 8.2 ATEX Approval Certificate (Continued) 109

117 Approval Certificates 8.2 ATEX Approval Certificate (Continued) 110

Universal IV Water Cut Meter

Universal IV Water Cut Meter DREXELBROOK DATA SHEET Universal IV Water Cut Meter with Density Compensation Use the Best For over 50 years, Drexelbrook has been the world s leader in capacitive based measurements by providing reliable

More information

DREXELBROOK. Datasheet Universal IV In-Line Water Cut Meter. with Spool Piece Mounting USE THE BEST APPLICATIONS. Eliminate Routine Maintenance

DREXELBROOK. Datasheet Universal IV In-Line Water Cut Meter. with Spool Piece Mounting USE THE BEST APPLICATIONS. Eliminate Routine Maintenance USE THE BEST For over 50 years, Drexelbrook has been the world s leader in capacitive based measurements by providing reliable and accurate products at a reasonable cost. We offer the highest pressure

More information

MTII4200 Level Transmitter Installation, Operation & Maintenance Instructions

MTII4200 Level Transmitter Installation, Operation & Maintenance Instructions Specialists in Liquid Level Indication MTII4200 Level Transmitter Installation, Operation & Maintenance Instructions Section: M500 Bulletin: M500.31 Date: 05-17-16 Supersedes: 09-30-11 1. INTRODUCTION

More information

Family of Water Cut Analyzers

Family of Water Cut Analyzers Phase Dynamics Technology for Precision Measurements Phase Dynamics, Inc. 1251 Columbia Drive Richardson, TX 75081 USA E-Mail sales@phasedynamics.com Tel: 972-680-1550 Fax: 972-680-3262 Family of Water

More information

Model 675 DREXELBROOK. Shark Cage Submersible Level Transmitter DATA SHEET. Description. Features. Applications.

Model 675 DREXELBROOK. Shark Cage Submersible Level Transmitter DATA SHEET. Description. Features. Applications. DREXELBROOK DATA SHEET Model 675 Shark Cage Model 675 Shark Cage with 3.5" flush diaphragm pressure via its sensing element, an ion implanted silicon semiconductor chip with integral Wheatstone Bridge

More information

SERIES CMT CARBON MONOXIDE GAS TRANSMITTER

SERIES CMT CARBON MONOXIDE GAS TRANSMITTER SERIES CMT CARBON MONOXIDE GAS TRANSMITTER INSTALLATION OPERATION AND MAINTENANCE MANUAL DWYER INTRUMENTS, INC. PO BOX 373, MICHIGAN CITY, IN. 46360 USA PHONE: 800-872-9141 FAX: 219-872-9057 Web: www.dwyer-inst.com

More information

INTRINSICALLY SAFE DUPLEXER PROTECTION. ELECTRONICS, INC Vulcan Road Apopka, Florida MOTOR INSTRUCTION MANUAL

INTRINSICALLY SAFE DUPLEXER PROTECTION. ELECTRONICS, INC Vulcan Road Apopka, Florida MOTOR INSTRUCTION MANUAL INTRINSICALLY SAFE DUPLEXER INSTRUCTION MANUAL MOTOR PROTECTION ELECTRONICS, INC. 2464 Vulcan Road Apopka, Florida 32703 Phone: Website: (407) 299-3825 www.mpelectronics.com Operating Program Revision:

More information

Series ULT Ultrasonic Level Transmitter

Series ULT Ultrasonic Level Transmitter Bulletin L-45 Series ULT Ultrasonic Level Transmitter Specifications - Installation and Operating Instructions 3 29/32 [99.21] 4 9/32 [108.74] 2X 1/2 NPT ø3 21/64 [84.53] 8 1/16 [204.79] Series ULT Ultrasonic

More information

1/32-DIN TEMPERATURE CONTROLLER INSTALLATION, WIRING AND OPERATION MANUAL FORM 3882

1/32-DIN TEMPERATURE CONTROLLER INSTALLATION, WIRING AND OPERATION MANUAL FORM 3882 1/32-DIN TEMPERATURE CONTROLLER INSTALLATION, WIRING AND OPERATION MANUAL FORM 3882 This manual is intended for use in support of installation, commissioning and configuration of the 1/32-DIN Temperature

More information

MYRIAD LC1 LEVEL CONTROLLER INSTRUCTION MANUAL

MYRIAD LC1 LEVEL CONTROLLER INSTRUCTION MANUAL MYRIAD LC1 LEVEL CONTROLLER INSTRUCTION MANUAL VISIT OUR WEBSITE SIGMACONTROLS.COM MYR LC1 MANUAL 062114 TABLE OF CONTENTS INTRODUCTION 3 Ordering Information Specifications Features Dimensions WIRING

More information

RS-FS-N01 Wind speed transmitter user's Guide (485type)

RS-FS-N01 Wind speed transmitter user's Guide (485type) RS-FS-N01 Wind speed transmitter user's Guide (485type) Issue: V1.0 1 2 Context 1. Introduction... 4 2. Installation instructions...5 3. Configure the software installation and use... 6 4. Communication

More information

P3-SCM. General Specifications

P3-SCM. General Specifications General Specifications Module Type Modules per Base Modules per Group I/O Points Used Field Wiring Connector Operating Temperature Storage Temperature Humidity Environmental Air Vibration Shock Field to

More information

RS-FX-N01 wind transmitter user's Guide (485type)

RS-FX-N01 wind transmitter user's Guide (485type) RS-FX-N01 wind transmitter user's Guide (485type) Issue:. V1. 0 1 2 Context 1. Introduction...4 2. Installation instructions... 5 3. Configure the software installation and use...7 4. Communication Protocol...

More information

DWYER INSTRUMENTS, INC. Series AVUL Air Velocity Transmitter. Specifications - Installation and Operating Instructions.

DWYER INSTRUMENTS, INC. Series AVUL Air Velocity Transmitter. Specifications - Installation and Operating Instructions. Series AVUL Air Velocity Transmitter Specifications - Installation and Operating Instructions Bulletin P-AVUL 3-49/64 [95.71] 2-43/64 [67.92] 1/2 NPS 3-3/16 [80.81] 1-19/32 [40.59] 31/32 24.58 3-33/64

More information

MYRIAD QLC 4-CHANNEL MONITOR/CONTROLLER INSTRUCTION MANUAL

MYRIAD QLC 4-CHANNEL MONITOR/CONTROLLER INSTRUCTION MANUAL MYRIAD QLC 4-CHANNEL MONITOR/CONTROLLER INSTRUCTION MANUAL VISIT OUR WEBSITE SIGMACONTROLS.COM MYR QLC MANUAL 013114 2 TABLE OF CONTENTS INTRODUCTION 3 Ordering Information Specifications Features WIRING

More information

2 Table of Contents 1. TABLE OF CONTENTS. 1. Table of Contents Introduction Wiring Diagram Terminals Review...

2 Table of Contents 1. TABLE OF CONTENTS. 1. Table of Contents Introduction Wiring Diagram Terminals Review... TPR-6 Temperature Protection Relay Instruction Manual Ver. June 1 st 2010 2 Table of Contents 1. TABLE OF CONTENTS 1. Table of Contents... 2 2. Introduction... 3 3. Wiring Diagram... 5 4. Terminals Review...

More information

Fox Thermal Instruments, Inc.

Fox Thermal Instruments, Inc. Fox Thermal Instruments, Inc. THERMAL MASS FLOW METER & TEMPERATURE TRANSMITTER FT3 View www.foxthermalinstruments.com 399 Reservation Road Marina, CA. 93933 104845 Rev. D Notice FOX THERMAL INSTRUMENTS

More information

Carbon Monoxide Sensor - ModBus

Carbon Monoxide Sensor - ModBus Introduction The CO Sensor uses an electrochemical sensor to monitor CO level in a range of 0 to 500 ppm and communicates via an RS-485 network configured for ModBus protocol. Before Installation Read

More information

Soft Starter Remote Operator. Section 1.0 Introduction 1.1 Important user information General Manual description...2.

Soft Starter Remote Operator. Section 1.0 Introduction 1.1 Important user information General Manual description...2. Section 1.0 Introduction 1.1 Important user information... 2 1.2 General... 2 1.3 Manual description...2 Contents Section 2.0 Specification 2.1 General technical data...3 2.2 Dimensions...3 Section 3.0

More information

Transducers & Transmitters HART USERS MANUAL. GP:50 New York LTD Long Road Grand Island, NY USA

Transducers & Transmitters HART USERS MANUAL. GP:50 New York LTD Long Road Grand Island, NY USA Transducers & Transmitters Industrial & Aerospace Pressure Measurement WWW.GP50.COM HART USERS MANUAL GP:50 New York LTD. 2770 Long Road Grand Island, NY 14072 USA Tel. (716) 773-9300 Fax (716) 773-5019

More information

Zone Pressure Touch (ZPT) Sensor with Attached Tube (-AT) - Low Pressure Range Unit Installation and Operation Instructions

Zone Pressure Touch (ZPT) Sensor with Attached Tube (-AT) - Low Pressure Range Unit Installation and Operation Instructions Product Identification BAPI s Touch Low Range Pressure Sensor with Attached Static Pressure Probe is an accurate, rugged and economical solution for measuring and reporting duct/building static pressure,

More information

LC-110/H. Reference Manual

LC-110/H. Reference Manual LC-110/H Reference Manual 1. Introduction...1 1.1 Customer Service...1 1.2 Standard Equipment...2 1.3 Safety information...2 2. Calibrator Interface and Operation...5 2.1 Milliamp Source...6 2.2 Milliamp

More information

Zone Pressure Touch Sensor - Standard Range

Zone Pressure Touch Sensor - Standard Range Overview The Zone Pressure Touch (ZPT) Sensor is an accurate, rugged and economical solution for measuring and reporting duct/ building static pressure, room-to-room differential pressure or air velocities/volumes.

More information

INSTRUCTION MANUAL STATION CONTROLLER SC1000 MOTOR PROTECTION ELECTRONICS, INC.

INSTRUCTION MANUAL STATION CONTROLLER SC1000 MOTOR PROTECTION ELECTRONICS, INC. INSTRUCTION MANUAL STATION CONTROLLER SC1000 MOTOR PROTECTION ELECTRONICS, INC. 2464 Vulcan Road, Apopka, Florida 32703 Phone: (407) 299-3825 Fax: (407) 294-9435 Revision Date: 9-11-08 Applications: Simplex,

More information

isma-b-mg-ip User Manual Global Control 5 Sp. z o.o. Poland, Warsaw

isma-b-mg-ip User Manual Global Control 5 Sp. z o.o. Poland, Warsaw isma-b-mg-ip User Manual Global Control 5 Sp. z o.o. Poland, Warsaw www.gc5.pl Table of content 1 Introduction... 4 1.1 Revision history... 5 1.2 Safety rules... 5 1.3 Technical specifications... 6 1.4

More information

Table of Contents. General Information. Document Sure-Aire Flow Monitoring System. User and Service Manual WARNING CAUTION

Table of Contents. General Information. Document Sure-Aire Flow Monitoring System. User and Service Manual WARNING CAUTION Document 476092 User and Service Manual Installation, Operation and Maintenance Manual Please read and save these instructions for future reference. Read carefully before attempting to assemble, install,

More information

F-3100 FLOW METER NETWORK INTERFACE Installation and Operation Guide

F-3100 FLOW METER NETWORK INTERFACE Installation and Operation Guide MODBUS FLOW AND ENERGY MEASUREMENT F-3100 FLOW METER NETWORK INTERFACE Installation and Operation Guide 11451 Belcher Road South, Largo, FL 33773 USA Tel +1 (727) 447-6140 Fax +1 (727) 442-5699 0725-2

More information

SATEL I-LINK 100 MB I/O-converter User Guide, Version 1.1

SATEL I-LINK 100 MB I/O-converter User Guide, Version 1.1 TABLE OF CONTENTS TABLE OF CONTENTS... 1 IMPORTANT NOTICE... 2 PRODUCT CONFORMITY... 3 WARRANTY AND SAFETY INSTRUCTIONS... 4 1 GENERAL... 5 1.1 SATEL I-LINK 100 MODBUS I/O- CONVERTER... 5 2 SPECIFICATIONS...

More information

EE360. High-End Moisture in Oil Transmitter. Typical applications. Features EE360 EE360. (+34)

EE360. High-End Moisture in Oil Transmitter. Typical applications. Features EE360 EE360. (+34) is dedicated for reliable monitoring of lubrication, hydraulic and insulation oils as well as diesel fuel. In addition to highly accurate measurement of water activity (a w ) and temperature (T), calculates

More information

Zone Pressure Touch (ZPT) Sensor - Standard Range

Zone Pressure Touch (ZPT) Sensor - Standard Range Product Identification BAPI s Touch Pressure Sensor is an accurate, rugged and economical solution for measuring and reporting duct/ building static pressure, room-to-room differential pressure or air

More information

RS485 MODBUS Module 6RO

RS485 MODBUS Module 6RO Version 2.0 12/02/2013 Manufactured for Thank you for choosing our product. This manual will help you with proper support and proper operation of the device. The information contained in this manual have

More information

TRACKER 240 SERIES. Load Cell and Weighing Indicators. A Precision Measurement Instrument with Outstanding Features

TRACKER 240 SERIES. Load Cell and Weighing Indicators. A Precision Measurement Instrument with Outstanding Features TRACKER 240 SERIES Load Cell and Weighing Indicators A Precision Measurement Instrument with Outstanding Features TRACKER 240 SERIES INDICATORS Ratiometric Measurement Tare and Auto Transducer Excitation

More information

MODEL 173 PROBE TYPE LEVEL TRANSMITTER With HART INSTALLATION, OPERATION, AND MAINTENANCE INSTRUCTIONS DELTA CONTROLS CORPORATION

MODEL 173 PROBE TYPE LEVEL TRANSMITTER With HART INSTALLATION, OPERATION, AND MAINTENANCE INSTRUCTIONS DELTA CONTROLS CORPORATION MODEL 173 PROBE TYPE LEVEL TRANSMITTER With HART INSTALLATION, OPERATION, AND MAINTENANCE INSTRUCTIONS DELTA CONTROLS CORPORATION MODEL NUMBERING SYSTEM MODEL SECTION DESCRIPTION BASIC TYPE - HOUSING &

More information

ASTAT XB/XBm Remote Operator

ASTAT XB/XBm Remote Operator ASTAT XB/XBm Remote Operator User Manual 1 Introduction 1.1 Important User Information Observe all necessary safety precautions when controlling the soft starter remotely. Alert personnel that machinery

More information

4511 MODBUS RTU. Configuration Manual. Universal transmitter. No. 4114MCM100(1402)

4511 MODBUS RTU. Configuration Manual. Universal transmitter. No. 4114MCM100(1402) 4511 MODBUS RTU Configuration Manual 4114 Universal transmitter 4114MCM100(1402) 4114 CONTENTS Introduction... 3 Modbus basics... 3 Modbus RTU... 3 Supported Function Codes... 3 Modbus Parameters and factory

More information

Wireless Transducer MOTOR PROTECTION ELECTRONICS, INC. INSTRUCTION MANUAL. (407) Phone: Website:

Wireless Transducer MOTOR PROTECTION ELECTRONICS, INC. INSTRUCTION MANUAL. (407) Phone: Website: Wireless Transducer INSTRUCTION MANUAL MOTOR PROTECTION ELECTRONICS, INC. 2464 Vulcan Road Apopka, Florida 32703 Phone: Website: (407) 299-3825 www.mpelectronics.com Operating Program Revision: 2 Revision

More information

4511 MODBUS RTU. Configuration Manual. Universal transmitter. No. 4114MCM101(1445) For 4511 devices from ser. no:

4511 MODBUS RTU. Configuration Manual. Universal transmitter. No. 4114MCM101(1445) For 4511 devices from ser. no: 4511 MODBUS RTU Configuration Manual 4114 Universal transmitter 4114MCM101(1445) For 4511 devices from ser. no: 141590001 4114 CONTENTS Introduction... 3 Modbus basics...3 Modbus RTU...3 4511 Supported

More information

Manual of Electrical Installation for Pressure Probes KS and KS-SIL2 series

Manual of Electrical Installation for Pressure Probes KS and KS-SIL2 series Manual of Electrical Installation for Pressure Probes KS and KS-SIL2 series GEFRAN SAFETY GUARANTEE Code 8594A Edition 2/204 Contents. General precautions pag 2 2. Transmitters with amplified analog output

More information

Intech Micro 2300-RTD6 analogue input station MODBUS RTU slave application supplementary manual.

Intech Micro 2300-RTD6 analogue input station MODBUS RTU slave application supplementary manual. Intech Micro 2300-RTD6 analogue input station MODBUS RTU slave application supplementary manual. MODBUS supplementary manual to the 2300-RTD6 Installation Guide. The 2300 series stations are designed to

More information

4511 MODBUS RTU. Configuration Manual. Universal transmitter. No. 4116MCM101(1445) For 4511 devices from ser. no:

4511 MODBUS RTU. Configuration Manual. Universal transmitter. No. 4116MCM101(1445) For 4511 devices from ser. no: 4511 MODBUS RTU Configuration Manual 4116 Universal transmitter 4116MCM101(1445) For 4511 devices from ser. no: 141590001 4116 CONTENTS Introduction... 1 Modbus basics... 1 Modbus RTU... 1 4511 Supported

More information

Digital Level Sensor. Consistent accuracy, unparalleled reliability. Answers for energy.

Digital Level Sensor. Consistent accuracy, unparalleled reliability. Answers for energy. Digital Level Sensor Consistent accuracy, unparalleled reliability Answers for energy. 2 Consistent accuracy Unparalleled reliability The Siemens Digital Level Sensor (DLS) is an engineered solution for

More information

4511 MODBUS RTU. Configuration Manual. Universal trip amplifier. No. 4131MCM100(1402)

4511 MODBUS RTU. Configuration Manual. Universal trip amplifier. No. 4131MCM100(1402) 4511 MODBUS RTU Configuration Manual 4131 Universal trip amplifier 4131MCM100(1402) 4131 CONTENTS Introduction... 3 Modbus basics... 3 Modbus RTU... 3 Supported Function Codes... 3 Modbus Parameters and

More information

TABLE OF CONTENTS INTRODUCTION. 3. Analog Input Analog Output Digital Input Digital Output OPERATIONAL DESCRIPITON.. 7 PROGRAMMING AND INITIAL SETUP.

TABLE OF CONTENTS INTRODUCTION. 3. Analog Input Analog Output Digital Input Digital Output OPERATIONAL DESCRIPITON.. 7 PROGRAMMING AND INITIAL SETUP. DIVERSIFIED HEAT TRANSFER SERIES 700 STEAM GENERATOR CONTROLLER INSTRUCTION MANUAL VISIT OUR WEBSITE AT SIGMACONTROLS.COM SERIES 700 DHT STEAM GENERATOR MANUAL 042514 2 TABLE OF CONTENTS INTRODUCTION.

More information

ABB Drives. User s Manual. Modbus Adapter Module RMBA-01

ABB Drives. User s Manual. Modbus Adapter Module RMBA-01 ABB Drives User s Manual Modbus Adapter Module RMBA-01 Modbus Adapter Module RMBA-01 User s Manual 3AFE 64498851 REV A EN EFFECTIVE: 1.3.2002 2002 ABB Oy. All Rights Reserved. Safety instructions Overview

More information

MST2000 Loop Powered Multivariable SMARTFLOW Transmitter

MST2000 Loop Powered Multivariable SMARTFLOW Transmitter MST2000 Loop Powered Multivariable SMARTFLOW Transmitter MST2000 Loop Powered Multivariable SMARTFLOW Transmitter Brandt Instruments MST2000 Series Loop Powered Multivariable SMARTFLOW Transmitter sets

More information

MU110-6U. Analog output module 6 channel. User guide

MU110-6U. Analog output module 6 channel. User guide MU110-6U Analog output module 6 channel User guide MU110-6U_2016.12_0221_EN All rights reserved Subject to technical changes and misprints akytec GmbH Vahrenwalder Str. 269 A 30179 Hannover Тел.: +49 (0)

More information

Electro-Magnetic Flowmeters Converters

Electro-Magnetic Flowmeters Converters Data Sheet D-FMC-MagMaster-Conv_5 Electro-Magnetic Flowmeters Converters MagMaster Pulsed DC technology incorporates benefits of AC systems Keypad configurable A choice of engineering parameters in engineering

More information

SP6R Level Controller Operation Manual

SP6R Level Controller Operation Manual SP6R Level Controller Operation Manual www.sjerhombus.com SP6R LEVEL CONTROLLER INTRODUCTION SJE-Rhombus, an industry leader in water and wastewater pump controls, introduces the SP6R Level Controller.

More information

MODEL CIO-EN MODBUS/TCP, MODBUS/RTU I/O MODULE

MODEL CIO-EN MODBUS/TCP, MODBUS/RTU I/O MODULE INSTALLATION INSTRUCTIONS Revision B1 Rapid City, SD, USA, 05/2009 MODEL CIO-EN MODBUS/TCP, MODBUS/RTU I/O MODULE BE SURE POWER IS DISCONNECTED PRIOR TO INSTALLATION! FOLLOW NATIONAL, STATE AND LOCAL CODES.

More information

KOBOLD TDA Series Digital Temperature Transmitter

KOBOLD TDA Series Digital Temperature Transmitter KOBOLD TDA Series Digital Temperature Transmitter TDA-15 Series User Instructions KOBOLD Instruments Inc. 1801 Parkway View Drive Pittsburgh, PA 15205 Phone (412) 788-2830 Fax (412)-788-4890 www.koboldusa.com

More information

Athena Series RMC Hot Runner Controller Configuration and Operation Manual

Athena Series RMC Hot Runner Controller Configuration and Operation Manual Athena Series RMC Hot Runner Controller Configuration and Operation Manual Athena and CompuStep are registered trademarks, and Multi-Comm and SafeChange are trademarks of Athena Controls, Inc. MODBUS is

More information

RS-485 MicroLinK HM Setup Software Installation Operation & Specifications Manual

RS-485 MicroLinK HM Setup Software Installation Operation & Specifications Manual RS-485 MicroLinK HM RS-485 HART Protocol Modem HART Device to Modbus Accumulator DIN Rail Mount 101-0035 Setup Software Installation Operation & Specifications Manual The RS-485 MicroLink-HM 101-0035 is

More information

General Specifications. P2-SCM Serial Communications

General Specifications. P2-SCM Serial Communications General Specifications Module Type Intelligent Modules per Base I/O Points Used Field Wiring Connector Operating Temperature Storage Temperature Humidity Environmental Air Vibration Shock Field to Logic

More information

4511 MODBUS RTU. Configuration Manual. Universal trip amplifier. No. 4131MCM101(1445) For 4511 devices from ser. no:

4511 MODBUS RTU. Configuration Manual. Universal trip amplifier. No. 4131MCM101(1445) For 4511 devices from ser. no: 4511 MODBUS RTU Configuration Manual 4131 Universal trip amplifier 4131MCM101(1445) For 4511 devices from ser. no: 141590001 4131 CONTENTS Introduction... 1 Modbus basics... 1 Modbus RTU... 1 4511 Supported

More information

Instruction Manual. T3110 T3110L T3110Ex

Instruction Manual. T3110 T3110L T3110Ex www.cometsystem.cz Instruction Manual T3110 T3110L T3110Ex Programmable transmitter of temperature, relative humidity and other calculated humidity values with 4-20 ma outputs Copyright: COMET System,

More information

CDD4 Duct Carbon Dioxide Transmitter

CDD4 Duct Carbon Dioxide Transmitter Drill or punch a 1-1/8 or 1-1/4 hole in the duct at the preferred location and insert the probe into the hole to mark the enclosure mounting holes. Remove the unit and drill the four mounting holes. Clean

More information

DLA. DMX512 Analyzer. DLA Users Manual SV2_00 B.lwp copyright ELM Video Technology, Inc.

DLA. DMX512 Analyzer. DLA Users Manual SV2_00 B.lwp copyright ELM Video Technology, Inc. DLA DMX512 Analyzer DLA DLA-HH 1 Table Of Contents IMPORTANT SAFEGUARDS... 2 DLA OVERVIEW... 3 CONNECTION... 3 OPERATION... 3 HARDWARE SETUP... 4 DLA-HH (PORTABLE) LAYOUT... 4 CHASSIS LAYOUT... 4 DLA MENU

More information

Product Data. Model 675 Shark Cage Submersible Level Transmitter ELECTRONIC PRESSURE MEASUREMENT PRODUCTS DESCRIPTION FEATURES APPLICATIONS

Product Data. Model 675 Shark Cage Submersible Level Transmitter ELECTRONIC PRESSURE MEASUREMENT PRODUCTS DESCRIPTION FEATURES APPLICATIONS EPMP - 1 DESCRIPTION The Model 675 is specifically designed for slurry and highly viscous applications where clogging of the sensor area is common. The Model 675 uses a 3.5" flush diaphragm to prevent

More information

EC700. Pulses concentrator. User instructions

EC700. Pulses concentrator. User instructions EC700 Pulses concentrator User instructions Contents Hazards and warning... 3 Initial checks... 3 Introduction... 4 Jbus/Modbus Communication... 5 Installation... 6 Configuration... 9 Use... 9 Programming...

More information

Advanced Test Equipment Rentals ATEC (2832)

Advanced Test Equipment Rentals ATEC (2832) Established 1981 Advanced Test Equipment Rentals www.atecorp.com 800-404-ATEC (2832) Rosemount 2088 and 2090 Appendix B Rosemount 275 HART Communicator Overview....................................... page

More information

Sidewinder Pumps Inc. AC C1D2 Timer/Controller

Sidewinder Pumps Inc. AC C1D2 Timer/Controller Sidewinder Pumps Inc. AC C1D2 Timer/Controller Page 1 of 14 Rev 4/26/17 Table of Contents 1. Warnings --------------------------------------------------------------------------------------------------

More information

Smart Wireless THUM Adapter

Smart Wireless THUM Adapter Reference Manual Smart Wireless THUM Adapter www.rosemount.com Reference Manual Smart Wireless THUM Adapter Smart Wireless THUM Adapter Smart Wireless THUM Adapter Hardware Revision 1 HART Device Revision

More information

installation Operation ADDRESS product diagram H8030/8031 INSTALLATION GUIDE

installation Operation ADDRESS product diagram H8030/8031 INSTALLATION GUIDE POWER MONITORING INSTALLATION GUIDE H8030/8031 H8030/8031 Modbus Energy Meter Networked kw/kwh Transducer Product Identification Model Max Amps CT Size Enhanced Data Stream Meters H8030-0100- 100 H8030-0300-

More information

SDM-6RO. Expansion Module 6 relay outputs. Manufactured for

SDM-6RO. Expansion Module 6 relay outputs. Manufactured for Version 1.0 5.02.2014 Manufactured for Thank you for choosing our product. This manual will help you with proper support and proper operation of the device. The information contained in this manual have

More information

Micro Motion Model 7950 and Model 7951 Signal Converters

Micro Motion Model 7950 and Model 7951 Signal Converters Product Data Sheet PS-001316, Rev. B April 2013 Micro Motion Model 7950 and Model 7951 Signal Converters Micro Motion Model 7950 and Model 7951 signal converters are the perfect complement to Micro Motion

More information

OPERATION MANUAL MODEL TT-LP

OPERATION MANUAL MODEL TT-LP TURTLE TOUGH OPERATION MANUAL MODEL TT-LP 2-Wire Isolated ph/orp Transmitter turtletough.com.au CONTENT INITIAL INSPECTION 3 INTRODUCTION 3 ASSEMBLY 4 PREPARATION 5 Connection Diagram of Turtle Tough Sensors

More information

RHE27. Rack/Panel Mount Multifunction Coriolis Flow Transmitter

RHE27. Rack/Panel Mount Multifunction Coriolis Flow Transmitter RHE27 Rack/Panel Mount Multifunction Coriolis Flow Transmitter Features Rack/Panel Mounting Operate with RHM sensor in hazardous area Selectable Units for Mass, Volume, Density and Temperature Positive,

More information

InLinK HM Setup Software Installation & Operation Manual

InLinK HM Setup Software Installation & Operation Manual InLinK HM HART Protocol Modem Module with HART Device to Modbus Accumulator for OEM Applications 101-0014 Setup Software Installation & Operation Manual InLink-HM 101-0014 is a complete OEM HART protocol

More information

MYRIAD RTU REMOTE TELEMETRY UNITS INSTRUCTION MANUAL

MYRIAD RTU REMOTE TELEMETRY UNITS INSTRUCTION MANUAL MYRIAD RTU REMOTE TELEMETRY UNITS INSTRUCTION MANUAL VISIT OUR WEBSITE SIGMACONTROLS.COM MYR RTU MANUAL 061314 2 TABLE OF CONTENTS INTRODUCTION 3 Ordering Information Specifications Features WIRING 8 Dwg

More information

MicroTrans EQ Signal Processor. Operation & Maintenance Manual

MicroTrans EQ Signal Processor. Operation & Maintenance Manual MicroTrans EQ Signal Processor Operation & Maintenance Manual Engineered for accuracy, applicability, durability and simplicity in HVAC air systems and industrial process control loops TABLE OF CONTENTS

More information

T2314, T2414. Instruction Manual

T2314, T2414. Instruction Manual Atmospheric pressure transmitter T2314, T2414 with RS232 / RS485 serial output Instruction Manual Instruction Manual Device type Pressure Output Galvanic isolated output T2314 RS232 - T2414 RS485 Device

More information

TRANSDUCER T4311, T4411

TRANSDUCER T4311, T4411 TRANSDUCER T4311, T4411 Programmable temperature transducer for RTD Pt1000 sensor with serial output RS232 and RS485 Instruction manual Instruction Manual for use of transducer: T4311 (RS232), T4411 (RS485)

More information

Sidewinder Pumps Inc. AC Timer/Controller

Sidewinder Pumps Inc. AC Timer/Controller Sidewinder Pumps Inc. AC Timer/Controller Page 1 of 12 Rev 032417 Table of Contents 1. Warnings-------------------------------------------------------------------------------------------------- 3 1.1.

More information

OPERATING INSTRUCTIONS

OPERATING INSTRUCTIONS OPERATING INSTRUCTIONS ULTRAFLO UFD3 ULTRASONIC CLAMP-ON FLOW METER FIXED OPTION PORTABLE OPTION (877) 356-5463 (p) 330-331-7331 (f) 330-331-7172 www.flo-corp.com 2017 FLO-CORP REVA 1116 1 Introduction

More information

EX-RC1 Remote I/O Adapter

EX-RC1 Remote I/O Adapter EX-RC1 Remote I/O Adapter The EX-RC1 interfaces between Unitronics Vision OPLCs and remote I/O Expansion Modules distributed throughout your system. The adapter is connected to a PLC via CANbus. Each adapter

More information

TPE 1464 Series Pressure Transducer

TPE 1464 Series Pressure Transducer TPE 1464 Series Pressure Transducer Description The KMC TPE 1464 series of pressure transducers incorporate a gauge pressure transmitter featuring low hysteresis, excellent repeatability, and longterm

More information

Level Plus. Magnetostrictive Liquid-Level Sensors with Temposonics Technology. Accessories Catalog

Level Plus. Magnetostrictive Liquid-Level Sensors with Temposonics Technology. Accessories Catalog Level Plus ostrictive Liquid-Level Sensors with Temposonics Technology Accessories Catalog SENSORS Document 551103 Revision C Floats, s, Meters, Enclosures, Indicators, Interface Terminals and Programming

More information

Operating Instructions and Description of Instrument Function Prothermo NMT539

Operating Instructions and Description of Instrument Function Prothermo NMT539 BA01026G/08/EN/19.15 71308663 Products Solutions Services Operating Instructions and Description of Instrument Function Prothermo NMT539 Temperature Basic Device Layout of Prothermo NMT539 Prothermo NMT539

More information

KOBOLD PDA Series Digital Pressure Transmitter

KOBOLD PDA Series Digital Pressure Transmitter KOBOLD PDA Series Digital Pressure Transmitter PDA-153 Series User Instructions KOBOLD Instruments Inc. 1801 Parkway View Drive Pittsburgh, PA 15205 Phone (412) 788-2830 Fax (412)-788-4890 www.koboldusa.com

More information

Flex Series User Guide

Flex Series User Guide User Programmable Current 4..20mA Digital RS485 Dual & Single Axis Up to 360º 2016 Flex Series User Guide Sensor Installation, Wiring, Flexware App Instructions Page 1 of 33 Page 2 of 33 Table of Contents

More information

Level-Lance Model 5400A

Level-Lance Model 5400A Sales Manual Section 100 PRODUCT SPECIFICATION 5400A GENERAL DESCRIPTION The ROBERTSHAW Level-Lance Model 5400A is a microprocessor based, multi-point On-Off capacitance type level detection system. Utilizing

More information

TORRIX-HART. Technical Documentation. The magnetostrictive level sensor with HART Protocol. Edition: Version: 5 Article no.

TORRIX-HART. Technical Documentation. The magnetostrictive level sensor with HART Protocol. Edition: Version: 5 Article no. Technical Documentation TORRIX-HART The magnetostrictive level sensor with HART Protocol Edition: 2016-10 Version: 5 Article no.: 207095 FAFNIR GmbH Schnackenburgallee 149 c 22525 Hamburg Germany Tel:

More information

JT400 Multivariable Transmitter

JT400 Multivariable Transmitter Product Specification Sheet JT400 Multivariable Transmitter Wireless Ultra Low Power Platform with Integrated, Chart Replacement Data Logging and I/O The industry s first, ultra-low power, multivariable

More information

JERGUSON MTII4300. Installation, Operation, & Maintenance Instructions IOM M per CDC

JERGUSON MTII4300. Installation, Operation, & Maintenance Instructions IOM M per CDC Installation, Operation, & Maintenance Instructions per CDC-17-251 2017.09 JERGUSON MTII4300 Table of Contents 1. INTRODUCTION... 3 2. PRODUCT DESCRIPTION... 4 2.1 MTII4300 TM Transmitter Specifications...

More information

K10 Intrinsically Safe Electro-Pneumatic Positioner Operating Manual

K10 Intrinsically Safe Electro-Pneumatic Positioner Operating Manual K0 Intrinsically Safe Electro-Pneumatic Positioner Operating Manual Pneumatic Connection Single Acting Actuator (Spring Return): For single acting actuators Outlet Port 2 is to be plugged. Outlet Port

More information

MGate 4101-MB-PBS Series

MGate 4101-MB-PBS Series MGate 4101-MB-PBS Series 1-port Modbus RTU/ASCII-to-PROFIBUS slave gateways Features and Benefits Protocol conversion between Modbus and PROFIBUS Supports PROFIBUS DP V0 slave Supports Modbus RTU/ASCII

More information

Operator Manual for Profibus

Operator Manual for Profibus PROCESS ANALYSERS SERVOPRO MultiExact Operator Manual for Profibus Part Number: Revision: Language: 05410007A 0 UK English This page intentionally blank LIST OF CONTENTS Section Page 1. DESCRIPTION AND

More information

Specifications - Installation and Operating Instructions. Duracell is a registered trademark of The Gillette Company.

Specifications - Installation and Operating Instructions. Duracell is a registered trademark of The Gillette Company. Bulletin P-DM-1100 Series DM-1000 DigiMag Digital Differential Pressure Gage Specifications - Installation and Operating Instructions The Series DM-1000 DigiMag Digital Differential Pressure Gage is the

More information

HIGH-VOLTAGE DC METER

HIGH-VOLTAGE DC METER HIGH-VOLTAGE DC METER Javelin D PD644 0-300 VDC input NEMA 4X, IP65 front Scale in engineering units Sunlight readable LED display 4-20 ma analog output Two form C 3 A relays option RS-485 serial communications

More information

RS485 MODBUS Module 8I8O

RS485 MODBUS Module 8I8O Expansion Module 8 digital inputs, 8 digital outputs Version 2.2 12/01/2014 Manufactured for Thank you for choosing our product. This manual will help you with proper support and proper operation of the

More information

Table of Contents. Introduction... 2 Description...2 Specifications...3 Installation.. 5 Calibration.. 6 General Maintenance...7

Table of Contents. Introduction... 2 Description...2 Specifications...3 Installation.. 5 Calibration.. 6 General Maintenance...7 User's Manual: Series 330I Model 330I DC-Powered Three-Way Isolator Table of Contents Page Introduction... 2 Description....2 Specifications....3 Installation.. 5 Calibration.. 6 General Maintenance...7

More information

AUTOMATION. Operator s Manual PG-7. Full Access. Doc Part Rev B, 07/18. Automation Products Group, Inc.

AUTOMATION. Operator s Manual PG-7. Full Access. Doc Part Rev B, 07/18. Automation Products Group, Inc. AUTOMATION P R O D U C T S GROUP, INC. Operator s Manual PG-7 Full Access Doc. 9003312 Part 200180 Rev B, 07/18 Tel: 1/888/525-7300 Fax: 1/435/753-7490 www.apgsensors.com E-mail: sales@apgsensors.com PG7

More information

technical datasheet technical datasheet MTL660 Displays Loop-powered indicators for hazardous areas

technical datasheet technical datasheet MTL660 Displays Loop-powered indicators for hazardous areas technical datasheet technical datasheet MTL0 Displays Loop-powered indicators for hazardous areas Loop powered -0mA Field and panel mounting Environmental protection to IP7 Easy to configure Number of

More information

DR7100 SERIES Supplementary instructions

DR7100 SERIES Supplementary instructions DR700 SERIES Supplementary instructions Guided Radar (TDR) Level Instrument for 2-wire control systems Supplementary Instructions for ATEX applications AMETEK Drexelbrook - EDO -0-2, DR700-LM ATEX, Issue

More information

Copyright Extract from Conditions of Sale Safety Warning

Copyright Extract from Conditions of Sale Safety Warning KD420 User Manual Copyright 2004-2013 KK Systems Ltd. No reproduction of any part of this document, in any form, is allowed without prior written permission from KKSystems Ltd. All other copyrights and

More information

CDD4 Series Room CO2 Transmitter Installation Instructions

CDD4 Series Room CO2 Transmitter Installation Instructions CDD4 Series Room CO2 Transmitter Installation Instructions Introduction The CO2 transmitter uses Infrared Technology to monitor CO2 levels and outputs a linear 4-20 ma or 0-5/0-10 Vdc signal. Options include

More information

ABL8BBU24400 battery control module V DC - 24 V - 40 A - for regulated SMPS

ABL8BBU24400 battery control module V DC - 24 V - 40 A - for regulated SMPS Characteristics battery control module - 24..28.8 V DC - 24 V - 40 A - for regulated SMPS Main Range of product Product or component type Input voltage Output voltage Maximum output current Complementary

More information

TOXALERT MODEL AIR 2000

TOXALERT MODEL AIR 2000 TOXALERT MODEL AIR 2000 NOTE: Toxalert s Model GVU-CO 2 Sensor is the same as the Air2000R. Microprocessor-based, Infrared Environmental CO 2 Sensor OPERATOR S MANUAL TOXALERT TM INTERNATIONAL INC. P.O.

More information

Interface Definition RISH EM 2340/1320/30/ _Rev. D - 8/2016

Interface Definition RISH EM 2340/1320/30/ _Rev. D - 8/2016 Interface Definition RISH EM 2340/1320/30/40 1 2-60-006-00-00494_Rev. D - 8/2016 2 Section DIGITAL MULTIFUNCTION INSTRUMENT Contents 1. Introduction Programmable Multi-function Energy Meter Installation

More information

SC2000 MOTOR PROTECTION ELECTRONICS, INC. INSTRUCTION MANUAL. (407) Phone: Website:

SC2000 MOTOR PROTECTION ELECTRONICS, INC. INSTRUCTION MANUAL. (407) Phone: Website: SC2000 INSTRUCTION MANUAL MOTOR PROTECTION ELECTRONICS, INC. 2464 Vulcan Road Apopka, Florida 32703 Phone: Website: (407) 299-3825 www.mpelectronics.com Operating Program Revision: 12 Revision Date: 8-27-14

More information