M-2001D DIGITAL TAPCHANGER CONTROL SUGGESTED SPECIFICATIONS

Size: px
Start display at page:

Download "M-2001D DIGITAL TAPCHANGER CONTROL SUGGESTED SPECIFICATIONS"

Transcription

1 M-2001D DIGITAL TAPCHANGER CONTROL SUGGESTED SPECIFICATIONS Pole-Top/Pad Mount Digital Tapchanger Control, for metering, monitoring, and operational control of step-voltage load tapchangers shall be provided by a microprocessor-based package. The microprocessor-based package shall be suitable for Pole Top Mounted or Pad Mounted single-phase or three-phase line regulators, substation regulators, and substation LTC transformers. The control shall have the following minimum functional and behavioral attributes: CONTROL FUNCTIONS The control shall include the following features and can be used for pole-mounted or padmounted single-phase or three-phase line regulators, substation regulators, and substation LTC transformer installations where SCADA communications are desired. Automatic/Manual Control: The Control shall have user-selectable control on the front panel for Automatic or Manual operation. In addition, it shall have an option for SCADA command to change the Auto/Manual control state remotely. Automatic/Manual Switch Status: The control shall provide indication of the Automatic/Manual Switch status via the communication ports. Voltage Limits, Tap Position Limits, and Runback: The control shall have Overvoltage and Undervoltage limits that are independently adjustable from 95 V to 135 V in 0.1 V increments. It shall have user-settable Upper and Lower tap position limits, with tap position knowledge active. There shall be an option for an adjustable deadband (above the overvoltage limit) of 1 V to 4 V to set the runback limit. Voltage Reduction: The control shall have three independent steps, each adjustable from 0% to 10% in 0.1% increments of the bandcenter set point. The Voltage Reduction function shall be capable of operating from the front panel or through contact inputs and disabled locally or remotely. LTC Contact Position Tracking: The control shall have a means of acquiring positive LTC transformer contact (tap) position information and tracking that can be integrated into an Integrated Volt VAr Management (IVVM) system. LTC Contact Position Record: The control shall provide a record of the number of times each tap has been passed through. This function shall be user-resettable. Operations Counter: The control shall have a pre-settable counter that records the number of raise and lower operations and increments based on the counter configuration, as set by the user. The counter shall be able to store up to operation counts without being affected by a loss of power supply. Resettable Operations Counter: The control shall have a second software counter, userresettable, similar to the Operations Counter. Neutral Counter: The control shall have a pre-settable neutral counter that records the number of times the Neutral Input is energized. The counter shall be able to store up to operation counts without being affected by a loss of power supply. Bandcenter and Bandwidth: The control shall have an adjustable bandcenter range from 100 V to135 V in 0.1 V increments. The bandwidth shall have an adjustable bandwidth range from 1 V to 10 V in 0.1 V increments. Line Drop Compensation: The control shall have R and X compensation adjustable from 72 V to +72 V in 1 V increments. There shall also be an option for Z compensation with the voltage raise adjustment range from 0 V to +72 V, in increments of 1 V. Page 1 of 8

2 Time-Delay: The control shall have a Definite Time-Delay function adjustable from 1 second to 120 seconds, in 1-second increments and Inverse Time-Delay adjustable from 1 second to 120 seconds, in 1-second increments. Inter-Tap Time-Delay: The control shall have an Inter-Tap Time-Delay to introduce time-delay between tap operations when control is in sequential mode; the time-delay range shall be adjustable from 0 to 60 seconds in 1 second increments and require input from an operation counter validating the tap change operation actually occurred before allowing tap change operation to the next step. Selectable Outputs: The control shall provide user-selectable continuous or pulsed outputs. When the output selection is in continuous mode, an output (raise or lower) signal runs the tapchanger until the voltage moves within the band setting. When pulsed output is selected and initiated, the pulse will continue until it reaches the programmed pulse time-out or a counter contact or motor hold input operates. The pulse length is programmable from 0.2 to 12 seconds, in increments of 0.1 second. Reverse Power Operation: The control shall be able to automatically detect a power flow reversal and determine the direction of power flow, the LTC tap position, and the magnitude of the reverse power voltage to the regulator. The operational choices shall include Ignore (does not use power direction to make control decisions), Block (remain in present tap position and stop operating as a controller), Regulate-in-Reverse (use power reversal as the new source side voltage and change LTC tap position accordingly), and Run-to-Neutral (change LTC taps to the neutral position). CT to VT Phasing Correction: The control shall provide CT to VT phasing correction adjustable from 0 to +330 in 30 increments. VT Ratio Correction: The control shall provide a means of VT correction from 15 V to +15 V in 0.1 V increments Normalizing Voltage: The control shall offer an option for a Normalizing Voltage Multiplier with a range of 0.80 to 1.20 to applied to Meter Out Voltage. This shall be displayed in real-time as Normalizing Voltage for the purpose of allowing the user to overcome differences in the ratio of the PT that the Load Voltage input is using versus the PT the end user or other metering methods are using. Inhibit of Auto Tapchange: The control shall provide an Inhibit of Auto Tapchange function that blocks automatic tapchanger operation in response to external contact closure or software setting. Non-Sequential/SCADA Block Operation: The control shall provide a Non-Sequential/SCADA Block Operation function that blocks automatic tapchanger operation in response to external contact closure or software setting and also resets the time-delay upon momentary external contact closure at the non-sequential input. Transformer Paralleling: The control must provide a means of connection to external transformer balancing equipment for the purpose of operating with two transformers in parallel. A or B Regulator Type: The control shall allow the user to select the type of regulator being used to provide a more accurate source voltage calculation. Self-Test Alarm Output Contacts: The control shall assert an alarm upon loss of power or malfunction of the control. Page 2 of 8

3 User-Programmable Alarm Contacts: The control shall have alarm capability to alert operator personnel to one or more of the following system conditions: Communications Block Invoked Block Lower Voltage Limit Exceeded Reverse Power Flow Condition Detected Tap Block Raise in Effect VAr Bias Lead Abnormal Tap Position SCADA CONTROL MODES Block Raise Voltage Limit Exceeded Voltage Reduction (any step) Invoked Load Current Limit Exceeded Tap Block Lower in Effect VAr Bias Lag LDC/LDZ SCADA Heartbeat: The control shall provide a means of monitoring SCADA heartbeat and change the control s operating mode based on the presence or absence of SCADA communications (using DNP protocol) to the control. SCADA Remote Manual Mode SCADA Heartbeat: The control shall allow the SCADA system to place the unit in Remote Manual mode and perform RAISE and LOWER operations as directed by a central source as long as it detects the presence of the SCADA heartbeat. SCADA Remote Manual Mode: The control shall be capable of operating from SCADA signals received through wired or wireless communications media to command LTC RAISE or LOWER operations. SCADA Remote Management of Local Automatic Control Mode: The voltage regulator control shall have the capability to allow Remote SCADA Management of Local Automatic voltage regulator control. This mode shall employ a SCADA heartbeat feature as described in SCADA Remote Manual Mode SCADA Heartbeat to ignore the SCADA control settings and return the unit to operation using its programmed settings. COMMUNICATIONS The communication ports shall provide access to all features, including metering, software updates, and programming of all functions. This shall be accomplished using a modem or direct serial connection from any PC-compatible personal computer running the control s Communications Software package or via SCADA communications software. Communications Ports: Communication ports shall be optionally available in the following forms: Ethernet 10/100 Mbps through a copper RJ-45 connection (100 Base-T) Ethernet 100Mbps Fiber Optic with ST connectors (100 Base-FX) Serial Ports with RS-485, ST or V-Pin Fiber Optics, or RS-232 Protocols: The control shall support the following standard protocols: DNP3.0 and MODBUS and optional IEC Ethernet Port: The control shall offer an optional 10/100 Mbps Ethernet port through an RJ-45 or Fiber Optic Connection. Bluetooth The control shall have an option for Bluetooth capability to enable wireless access to the control that allows the user to configure the control, read status and metering values, as well as change set points. A generic serial service shall be provided by the control s Bluetooth capability to facilitate establishing initial communications should the Bluetooth not automatically recognize listed services. The Bluetooth feature shall include a secure mode with the Bluetooth module undiscoverable without a user knowing the Bluetooth hardware address in the unit to meet NERC requirements for Bluetooth communications. Page 3 of 8

4 ADVANCED SCADA COMMUNICATIONS True Ethernet The control shall provide an integrated, true 10/100 Mbps Ethernet, auto negotiable, capable of supporting up to eight concurrent sessions and simultaneous multiple protocols with up to eight sockets (concurrent sessions) open at a time. The eight sockets shall be capable of supporting Modbus and DNP over TCP/IP and UDP with up to five of the eight sockets capable of supporting DNP 3.0. This requirement allows users simultaneous remote access to the control via the same physical Ethernet port to view/change settings or retrieve data, without affecting the SCADA communications. Full DNP Implementation The control shall provide full DNP implementation to support both report-by-exception and unsolicited reporting within DNP 3.0 to aid in the reduction of bandwidth requirements. The control shall also provide DNP File Transfer to permit the recovery of data logs and triggered events, oscillography, and device discovery to facilitate setting up the integrated system. The control shall support DNP security as defined in the DNP 3.0 standard. The control shall have DNP addressing capability that allows networking of multiple controls. The DNP implementation shall support the pre-defined global addresses within DNP 3.0 and allow the user to define two additional global addresses. Each control shall be able to be assigned a Device Address, Feeder Address, and Substation Address ranging from 1 to The control shall support broadcast commands from the master to all controls on the network in order to allow some or all controls to act on one command at the same time. The control shall provide a configuration program that allows any point to be mapped into any DNP location and allows dummy filler points to be added to facilitate interoperability by replicating legacy vendor pointmaps to SCADA. This program shall also allow for individual point dead-banding and individual point assignments into Class 1, 2, or 3. Cyber Security Within DNP, the control shall permit multiple master source-address authentications, sourceaddress validation, and multilevel access codes logged with date and time. It shall support Secure DNP authentication using FIPS Secure Hash Standard (SHA-1). The control shall be fully compliant and offer all settings and configuration as defined by the DNP3 user group and IEC The control shall have a 6-15 character password and an audit log that shows when someone is logged on the control and which password was used to gain access to the control, in compliance with NERC CIP standards. The control shall allow for storage of 30 unique passwords within each control and have an SD card slot to allow the use of a password-keyed SD card that the control automatically reads to allow user login. The control s design shall include the ability to disable ports and services not required for normal or emergency operations. In cases where disabling is not possible, the port or service shall be password and access level protected through a communication access security and timeout feature in the communication software. MONITORING/METERING Harmonic Analysis: The control shall measure, log, and display individual harmonics including THD (total harmonics distortion) and the harmonic content of the load voltage and load current up to the 31 st harmonic. Oscillograph Recorder: The control shall have an oscillograph recording function that provides comprehensive data recording (voltage, current, and status input/output signals) for all monitored waveforms (at 16, 32 or 64 samples per cycle). The control shall have a means of downloading oscillograph data via the communications ports to any PC compatible personal computer running the included communications software program. The downloaded data shall be in a format that can be examined and printed. The waveform data shall also be available in COMTRADE file format. Page 4 of 8

5 Real-Time Metering: The control shall meter the following single/three-phase measured and calculated values in real-time: Load Voltage Primary Voltage Tap Position Source Voltage Primary Current Drag Hands Meter Out Voltage Primary Watts Raise/Lower Timer Power Factor Primary VArs Circulating Current Normalizing Voltage Primary VA Operation Control Load Current Frequency Resettable Counter Compensating Voltage Primary Source Voltage Neutral Counter Intertap Timer Present Demand: The control shall provide a Present Demand feature that captures the maximum values during the specified time interval. The user-selectable time interval shall be 15, 30, or 60 minutes. Demand Load Voltage Primary Watts Primary VA Demand Primary Current Primary VArs Demand History (Drag Hands Operation): The control shall have the following drag-hand values stored with date and time stamping, averaged over 32 seconds: Min Load Voltage Max Load Voltage The control shall have capability to store the following drag-hand values with date and time stamping and calculated over the demand of the user-selectable time intervals of 15, 30, or 60 minutes: Max Primary Current (Amps) Max Primary Watts (kw or MW) Max Primary VA (kva or MVA) Max Primary VArs (kvar or MVAr) Power Max VA Energy Metering: The control shall be capable of retaining the following measured values in nonvolatile memory and have a real-time clock to record the date/time stamp for each quantity indicating when the measurement period was initiated. Watt Hours Forward (kwh) Watt Hours Reverse (kwh) Lagging VAr Hours (kvarh) Leading VAr Hours (kvarh) Data Logging: Data logging shall be provided that allows the user to record data internally into nonvolatile memory. The Data Log shall be saved in COMTRADE format and shall be capable of being downloaded using either MODBUS or DNP protocols. Sequence Of Events (SOE): The control shall contain a Sequence of Events recorder for comprehensive time tagged data recording of control parameters that include Voltage, Frequency, Tap Position, Current, Counters, and Harmonics. The Sequence of Events Recorder is triggered by user-selectable programmable parameter logic or manually by the user and shall be capable of recording up to 132 events. Computer Business Equipment and Manufacturers Association (CBEMA) Sag & Swell Recorder: The control shall provide CBEMA monitoring to detect sags and swells and trigger data collection and alarming functions. Page 5 of 8

6 INPUTS The control shall have the following inputs: Load Voltage Input: Nominal 120 VAC, 60 Hz (50 Hz optional); operates properly from 90 VAC to 140 VAC. If set at 60 Hz, the operating system frequency shall be from 55 to 65 Hz; if set at 50 Hz, the operating system frequency shall be from 45 to 55 Hz. The burden imposed on the input shall be 8 VA or less. A voltage transformer connected at the controlled voltage bus shall provide power to the unit. The unit shall be able to withstand twice the voltage input for one second and four times the voltage input for one cycle. Motor Power Input: The motor power input to the control shall be a nominal 120 VAC or 240 VAC, at up to 6 A as required by the load, with no wiring changes required. Motor Seal-In Input: The control shall receive an input from the regulator motor seal-in circuit. Load Current Input: The control shall have line drop compensation provided by a current transformer input with a 0.2 A full-scale rating. The burden imposed on the current source shall be 0.03 VA or less at 200 ma. The control s load current input shall withstand 400 ma for two hours and 4 A for 1 second. Circulating Current Input: The control shall use current transformer input to control transformer paralleling operations. Optional Control Power Backup Input: The control shall have an option for a DC Control Power Backup Input feature to sustain operation of the control in the event of a loss of AC input power to the control and shall be able to respond to Raise and Lower commands as long as the control s motor power remains energized. Counter Input: The control shall have a Counter Input to detect tap position changes; the input shall update two counters, one pre-settable and one resettable. Neutral Tap Position Detect Input: The control shall have a Neutral Position Detect Input to detect the neutral tap position, which assists the tap position function. Source Voltage Input: Nominal 120 VAC, 60 Hz (50 Hz optional); operates properly from 90 VAC to 140 VAC. If set at 60 Hz, the operating system frequency shall be from 55 to 65 Hz; if set at 50 Hz, the operating system frequency shall be from 45 to 55 Hz. The burden imposed on the input shall be 8 VA or less. A voltage transformer connected at the controlled voltage bus shall provide power to the unit. The unit shall withstand twice the voltage input for one second and four times the voltage input for one cycle. The control shall use this input with the Reverse Power Measured feature when reverse power operation is desired and a Source Side PT input is available. Binary Inputs Voltage Reduction 1 and 2 Inputs: The control shall have Voltage Reduction 1 and 2 inputs to provide three levels of programmable voltage reduction that can be manually invoked.. The control shall allow the Voltage Reduction Level 2 input to be used as an auxiliary input that is monitored remotely via SCADA by setting its input to AUX. Non-Sequential/SCADA Block Input: The control shall have non-sequential/scada block input to provide the means to perform non-sequential operations. OUTPUTS The control shall have the following outputs: Raise Output: Capable of switching 6 A at 120 VAC to 240 VAC motor power. Lower Output: Capable of switching 6 A at 120 VAC to 240 VAC motor power. Deadman Alarm Output: Capable of switching 6 A at 120 VAC or 100 ma at 120 Vdc. Page 6 of 8

7 User Programmable Alarm Output: One Form C contact capable of switching 6 A at 125 VAC or 0.2 A at 125 Vdc. Output Contacts: The control shall have one normally open programmable alarm contact capable of switching 6 A at 120 VAC and one normally closed self-test alarm contact capable of switching 6 A at 120 VAC. FRONT PANEL CONTROLS The control shall provide menu driven access to all functions by way of navigational pushbuttons and a two-line alphanumeric display. The control shall have a means of providing password protection to the various levels of control function access. Smart Flash SD Card Slot: The control shall have an SD Card slot that allows the user to perform the following functions without the need for a laptop: Load Set Points Save Set Points Save Data Log Load DNP Configuration Clone Save Clone Load Save DNP Configuration Firmware Update Save Metering Data Save Wake Screen Data Save Oscillographic Records User Access Keycode Quick Capture Save/Load IEC CID Files LED Indicators: The control shall have the following LED Indicators on the front panel: Out-of- Band RAISE, Out-of-Band LOWER, REVERSE POWER flow detected, CPU OK, ALARM, VOLTAGE REDUCTION in effect, MANUAL, LOCAL, and TX/RX transmit and receive. TESTS AND STANDARDS The control shall comply with the following type tests and standards: ELECTRICAL ENVIRONMENT Voltage Measurement Accuracy The control shall have a voltage measuring accuracy of ± 0.3 % when tested in accordance with ANSI/IEEE C standard over a temperature range of 40 C to + 85 C. Dielectric Withstand IEC : Impulse Voltage IEC : Insulation Resistance IEC ,500 VAC for 1 minute applied to each independent circuit to earth 1,500 VAC for 1 minute applied between each independent circuit. 5,000 V pk, +/- polarity applied to each independent circuit to earth 5,000 V pk, +/- polarity applied between each independent circuit 1.2 s by 50 s, 500Ω impedance, three 1 every 5 seconds > 100 MΩ. Surge Immunity IEC : 2,000 V pk Radiated Field Immunity IEEE C MHz 1, V/M IEC MHz 2, V/M Page 7 of 8

8 Conducted Field Immunity IEC Surge Withstand Capacity IEEE C IEEE C jhz V emf 2,500 V pk Oscillatory applied to each independent circuit to earth 2,500 V pk Oscillatory applied to each independent circuit 5,000 V pk Fast Transient applied to each independent circuit to earth 5,000 V pk Fast Transient applied to each independent circuit 2,500 V pk Oscillatory applied to each independent circuit to earth 2,500 V pk Oscillatory applied to each independent circuit 4,000 V pk Fast Transient applied to each independent circuit to earth 4,000 V pk Fast Transient applied to each independent circuit NOTE: Signal is applied to digital data circuit (RS-232, RS-485, Ethernet) ports through capacitive coupling clamp. Fast Transient Disturbance Test IEC Class A (+/- 4 kv, 2.5 khz, 5 khz) NOTE: Disturbance is applied to digital data circuit (RS-485) ports through capacitive coupling clamp. ATMOSPHERIC ENVIRONMENT Temperature: Control shall operate from 40 C to +85 C with either the LCD or Vacuum Flourescent display IEC : Cold, 40 C IEC : Dry Heat, + 85 C IEC : Damp Heat, % RH IEC : Damp Heat Condensing Cycle: 25 C, % RH MECHANICAL ENVIRONMENT The control shall meet the following mechanical environmental specifications: IEC Vibration response Class 1: 0.5 g Vibration endurance Class 1: 1.0 g COMPLIANCE culus-listed per 508 Industrial Control Equipment Industrial Control Equipment Certified for Canada CAN/CSA C22.2 No. 14-m91 culus-listed Component per 508A Table SA1.1 Industrial Control Panels STORAGE PARAMETERS The control s design shall allow for storage under the following conditions: Temperature Range: +5 C to +40 C Humidity: Maximum relative humidity of 80% for temperatures up to 31 C, decreasing from 31 C linearly to 50% relative 40 C Page 8 of 8 File: M-2001D-Sugg-Spec.doc

M-6200A DIGITAL VOLTAGE REGULATOR CONTROL SUGGESTED SPECIFICATIONS

M-6200A DIGITAL VOLTAGE REGULATOR CONTROL SUGGESTED SPECIFICATIONS M-6200A DIGITAL VOLTAGE REGULATOR CONTROL SUGGESTED SPECIFICATIONS Pole-Top/Pad Mount Digital Voltage Regulator Control, for metering, monitoring, and operational control for step-voltage Regulators shall

More information

CONTROLS. Digital Regulator. Digital Regulator Control for General Electric, Siemens, Cooper and Howard Regulators

CONTROLS. Digital Regulator. Digital Regulator Control for General Electric, Siemens, Cooper and Howard Regulators CONTROLS Digital Regulator Control ol M-6200 Digital Regulator Control for General Electric, Siemens, Cooper and Howard Regulators Features Adjustable Bandcenter Adjustable Bandwidth Line Drop Compensation,

More information

Digital Voltage Regulator Control M-6200A

Digital Voltage Regulator Control M-6200A CONTROLS Digital Voltage Regulator Control M-6200A Digital Regulator Control for General Electric, Siemens, Cooper and Howard Regulators Maximum Communication Options For Wired or Wireless Networks Standard

More information

Digital Tapchanger Control M-2001C

Digital Tapchanger Control M-2001C CONTROLS Digital Tapchanger Control M-2001C Digital Tapchanger Control for Transformers and Regulators LTC transformer, substation regulator, and line regulator control provides reliable operation with

More information

Digital Tapchanger Control M 2001D

Digital Tapchanger Control M 2001D CONTROLS Digital Tapchanger Control M 2001D Digital Tapchanger Control for Transformers and Regulators LTC transformer, substation regulator, and line regulator control provides reliable operation with

More information

Instruction Book. M 2001C (Comprehensive) Tapchanger Control

Instruction Book. M 2001C (Comprehensive) Tapchanger Control Instruction Book M 2001C (Comprehensive) Tapchanger Control CONTROLS Digital Tapchanger Control M-2001C Digital Tapchanger Control for Transformers and Regulators Comprehensive Model Shown LTC transformer,

More information

Digital Tapchanger Control M-2001B

Digital Tapchanger Control M-2001B CONTROLS igital Tapchanger Control M-2001B igital Tapchanger Control for Transformers and Regulators Microcontroller-based LTC transformer and regulator control provides reliable operation and expanded

More information

Bus Bar Protection Relay B-PRO 4000

Bus Bar Protection Relay B-PRO 4000 Bus Bar Protection Relay B-PRO 4000 Product Overview The IEC 61850 station bus embedded B-PRO 4000 relay provides complete bus and substation differential protection (low impedance) with CT saturation

More information

Autodaptive Capacitor Control M 2501B

Autodaptive Capacitor Control M 2501B CONTROLS Autodaptive Capacitor Control M 2501B Capacitor Control for Pole-Top Capacitor Banks Increases effectiveness of installed capacitors for voltage control to reduce system losses Adapts reference

More information

UW Purchase Specification Section

UW Purchase Specification Section Page 1 of 9 PART 2 GENERAL 2.01 DESCRIPTION A. Purpose 1. This section covers electrical service meters and sub-meters for use in the Owner's power distribution systems. 2.02 QUALIFICATIONS A. Approved

More information

EM132 EM132. Main Features. Multi-functional 3-Phase Transducer. Energy Meter

EM132 EM132. Main Features. Multi-functional 3-Phase Transducer. Energy Meter EM132 MULTI-FUNCTION TRANSDUCER SATEC EM132 is a Smart DIN Rail Multi-Function Transducer with a local display. It is based on SATEC s best seller PM130 PLUS with an off-the-shelf LCD display (similar

More information

Electronic Submeter with Advanced WiFi Ethernet Capability

Electronic Submeter with Advanced WiFi Ethernet Capability SH RK 100S Electronic Submeter with Advanced WiFi Ethernet Capability AGGRESSIVE TECHNOLOGY W NEIndustry Leading Technology High Performance Metering Technology 0.2% Accuracy Class Revenue Certifiable

More information

Mehta Tech, Inc. TRANSCAN IED For Multi-Function, Multi-Speed Recording

Mehta Tech, Inc. TRANSCAN IED For Multi-Function, Multi-Speed Recording Mehta Tech, Inc. TRANSCAN IED For Multi-Function, Multi-Speed Recording Two independent, simultaneously operating recorders in one package Triggering on input quantities and calculated values, such as

More information

NORTHWESTERN UNIVERSITY PROJECT NAME JOB # ISSUED: 03/29/2017

NORTHWESTERN UNIVERSITY PROJECT NAME JOB # ISSUED: 03/29/2017 SECTION 26 2713 ELECTRICITY METERING PART 1 - GENERAL 1.1 SUMMARY A. Section includes equipment for metering of the electrical power system. B. Related Sections: 1. Section 26 2300 for metering installed

More information

USER MANUAL 2012 V1.1

USER MANUAL 2012 V1.1 SMART MINI POWER SDM630 USER MANUAL 2012 V1.1-1 - Installation and Operation Instructions Important Safety Information is contained in the Maintenance section. Familiarise yourself with this information

More information

BFM-II BFM-II BRANCH FEEDER MONITOR. Highlights

BFM-II BFM-II BRANCH FEEDER MONITOR. Highlights BRANCH FEEDER MONITOR SATEC s is the second generation of Branch Feeder Monitor, providing energy management for multi-point power solutions. Ideal for both new and retrofit projects, the automatically

More information

g Energy Multilin Voltage Regulator Controller DGCV KEy BENEFITS APPLICATIONS FEATURES Metering & Monitoring Voltage Regulation Communications

g Energy Multilin Voltage Regulator Controller DGCV KEy BENEFITS APPLICATIONS FEATURES Metering & Monitoring Voltage Regulation Communications Multilin Voltage Regulator DGCV KEy BENEFITS Increases grid efficiency by optimizing voltage regulation Through deployment of the Volt/VAR system, the Multilin DGCV: - Enables up to a 6% reduction in energy

More information

www. ElectricalPartManuals. com Protective Relays PROTECTION AND CONTROL FUNCTIONS ADVANCED CAPABILITIES

www. ElectricalPartManuals. com Protective Relays PROTECTION AND CONTROL FUNCTIONS ADVANCED CAPABILITIES Protective Relays Electrical Apparatus Capacitor Bank Protection Relay 165-440-900 Figure 1: Edison Idea Relay The capacitor bank protection relay is a member of Cooper Power Systems Edison Idea TM line

More information

Communication Gateway COM 610. Product Guide

Communication Gateway COM 610. Product Guide Communication Gateway COM 610 Product Guide Issued: September 2004 Status: Updated Version: D/17.10.2006 Data subject to change without notice Features Protocol conversion gateway for substation automation:

More information

PM174 PM174 IEEE1159 ADVANCED POWER QUALITY ANALYZER. Features

PM174 PM174 IEEE1159 ADVANCED POWER QUALITY ANALYZER. Features PM174 IEEE1159 ADVANCED POWER QUALITY ANALYZER The PM174 is a compact, multi-function, three-phase AC powermeter and power quality analyzer specially designed to meet the requirements of users ranging

More information

PMC 530 Series Advanced Multifunction Meter

PMC 530 Series Advanced Multifunction Meter IEC 62053 22 Class 0.5S WF Capture @ 128 samples/cycle WF and Data Recording Harmonics & Transient Monitoring I residual Monitoring Setpoint Alarms, SOE Log RS 485 and I/O Capabilities Large, Bright, Backlit

More information

SEL-734B Data Sheet. Advanced Monitoring and Control System. Major Features and Benefits

SEL-734B Data Sheet. Advanced Monitoring and Control System. Major Features and Benefits Advanced Monitoring and Control System Compact Enclosure Full-Size Enclosure Major Features and Benefits The SEL-734B combines volt/var based capacitor bank control with power quality monitoring and advanced

More information

EPM g Energy. Multilin BUILDING AUTOMATION POWER METER. BACnet /IP Communications and Energy Measurement KEY BENEFITS APPLICATIONS FEATURES

EPM g Energy. Multilin BUILDING AUTOMATION POWER METER. BACnet /IP Communications and Energy Measurement KEY BENEFITS APPLICATIONS FEATURES Multilin EPM 6010 BUILDING AUTOMATION POWER METER BACnet /IP Communications and Energy Measurement KEY BENEFITS Rapid integration into BACnet management systems High accuracy multifunction power meter,

More information

EM133 EM133 TOU SMART ENERGY METER. Main Features. Multifunctional 3-Phase Smart Meter. Billing/TOU Energy Meter

EM133 EM133 TOU SMART ENERGY METER. Main Features. Multifunctional 3-Phase Smart Meter. Billing/TOU Energy Meter TOU SMART ENERGY METER SATEC is a Smart DIN Rail TOU Energy Meter. It is based on SATEC s best seller PM130 PLUS with an off-theshelf LCD display (similar to the BFM136 display). The provides the full

More information

Digital Multifunction Meters. Digital Multifunction Meters

Digital Multifunction Meters. Digital Multifunction Meters Digital Multifunction Meters Digital Multifunction Meters DIGITAL MULTIFUNCTIOL METERS SECTION INDEX 1. MFM 3410 3420 3430 3440 6100 & 2000 - Multifunctional Instrument Series 2. EM 3490, 3490SS, 3490DS

More information

Power Meter PowerMonitor 500

Power Meter PowerMonitor 500 ROCKWELL AUTOMATION PROCUREMENT SPECIFICATION PROCUREMENT SPECIFICATION PowerMonitor 500 NOTICE: The specification guidelines in this document are intended to aid in the specification of products. Specific

More information

Multifunction Transducer MT440

Multifunction Transducer MT440 Multifunction Transducer MT440 Voltage and current auto range measurements up to 600V, 12.5A Universal wide auxiliary power supply range 24 300 Vdc, 40 276 Vac Power accuracy class 0.5 (EN 60 688), Up

More information

RT4F-110V/25A RECTIFIER

RT4F-110V/25A RECTIFIER The RT4F-110V/25A is a hot-pluggable switched mode rectifier (SMR) module designed to provide up to 25A of output current into a 110V nominal system. Examples of such systems are 60 cells lead acid (136V

More information

RT4F-48V/50A-WAC RECTIFIER

RT4F-48V/50A-WAC RECTIFIER The RT4F-48V/50A-WAC is a switched mode rectifier (SMR) module designed to provide up to 58A of output current into a 48V nominal system, over a wide range of AC input voltage. This rectifier has been

More information

SDM630M CT USER MANUAL 2016 V4.7. DIN Rail Energy Meter for Single and Three Phase Electrical Systems

SDM630M CT USER MANUAL 2016 V4.7. DIN Rail Energy Meter for Single and Three Phase Electrical Systems SDM630M CT DIN Rail Energy Meter for Single and Three Phase Electrical Systems Measures kwh Kvarh, KW, Kvar, KVA, P, F, PF, Hz, dmd, V, A, THD,etc. Bi-directional measurement IMP & EXP Two pulse outputs

More information

RT4F-120V/20A-WAC RECTIFIER

RT4F-120V/20A-WAC RECTIFIER The RT4F-120V/20A-WAC is a switched mode rectifier/charger module designed to provide up to 20A of output current into a 120V nominal system. This charger has been designed for use in conjunction with

More information

Switching Control Sentinel (SCS) TM For all ABB independent pole operated circuit breakers

Switching Control Sentinel (SCS) TM For all ABB independent pole operated circuit breakers Switching Control Sentinel (SCS) TM For all ABB independent pole operated circuit breakers Switching Control Sentinel (SCS) for circuit breakers Voltage and current transients generated during switching

More information

MID PRELIMINARY DATA SHEET. RI-D Series. Single Phase Multifunction Energy Meter (MID Certified) MID

MID PRELIMINARY DATA SHEET. RI-D Series. Single Phase Multifunction Energy Meter (MID Certified) MID PRELIMINARY DATA SHEET RI-D35-100 Series Single Phase Multifunction Energy Meter (MID Certified) MID direct connected Two pulse outputs LED pulse indication High definition LCD display with white backlight

More information

Multilin EPM Energy and Demand Submeter with Wi-Fi. Monitoring & Metering. Communications. Key Benefits. Applications

Multilin EPM Energy and Demand Submeter with Wi-Fi. Monitoring & Metering. Communications. Key Benefits. Applications Multilin EPM 6100 Energy and Demand Submeter with Wi-Fi The EPM 6100 is a powerful tool that allows customers to monitor and manage their energy usage within factories, businesses and across campuses.

More information

DGC-2000 DIGITAL GENSET CONTROLLER

DGC-2000 DIGITAL GENSET CONTROLLER DGC-2000 DIGITAL GENSET CONTROLLER Basler Electric s Digital Genset Controller (DGC-2000) offers an integrated alternative for genset control and monitoring. Control includes engine starting and shutdown

More information

EM-1000 /EM-2000/ EM-3000 Series Multifunction Power and Energy Meters

EM-1000 /EM-2000/ EM-3000 Series Multifunction Power and Energy Meters Power and Energy Meters Code No. LIT-1900845 Issued December 4, 2013 EM-1000 /EM-2000/ EM-3000 Series Multifunction Power and Energy Meters EM-1000 Series Meter Description The EM-1000 Series monitor is

More information

MINER-S Station Controller. Substation Automation

MINER-S Station Controller. Substation Automation Substation Automation MINER-S Station Controller incorporates traditional RTU functions with new technology in a compact design MINER-S Station Controller combines the functions of a traditional RTU with

More information

Remote Terminal Unit ER1000 APPLICATION FEATURES

Remote Terminal Unit ER1000 APPLICATION FEATURES Remote Terminal Unit ER1000 ERL with more than three decades of expertise in Power System Protection have developed state of the art Automation Solutions. The whole family of ERL s Remote Terminal Unit

More information

B+G E-Tech User Manual for SDM630 SDM630. Din Rail Smart Energy Meter for Single and Three Phase Electrical Systems USER MANUAL 2013 V1.

B+G E-Tech User Manual for SDM630 SDM630. Din Rail Smart Energy Meter for Single and Three Phase Electrical Systems USER MANUAL 2013 V1. SDM630 Din Rail Smart Energy Meter for Single and Three Phase Electrical Systems USER MANUAL 203 V. Important Safety Information is contained in the Maintenance section. Familiarize yourself with this

More information

Bulletin 290/291 ArmorStart LT Distributed Motor Controllers Specifications

Bulletin 290/291 ArmorStart LT Distributed Motor Controllers Specifications Power Circuit Control Circuit (External Source) Control Circuit (Internal Source) Short Circuit Current Rating (SCCR) Application Electrical Ratings Three-phase Number of Poles 3 Input Power Terminals

More information

Transformer Protection Relay

Transformer Protection Relay Transformer Protection Relay T-PRO Product Overview The IEC 61850 station bus embedded T-PRO relay provides complete three-phase multi-winding transformer protection and overload protection, DFR-quality

More information

Protection Relays PHASE & RESIDUAL OVERCURRENT

Protection Relays PHASE & RESIDUAL OVERCURRENT Protection Relays PHASE & RESIDUAL OVERCURRENT Application The relay type NA016 can be used in radial networks as feeder or power transformer protection. In solidly grounded systems the residual overcurrent

More information

Voltage regulator. SPAU 341 C 1MRS MBG Issued: July 1998 Status: Revised Version: C/ Data subject to change without notice

Voltage regulator. SPAU 341 C 1MRS MBG Issued: July 1998 Status: Revised Version: C/ Data subject to change without notice Issued: July 1998 Status: Revised Version: C/08.10.2003 Data subject to change without notice Features Comprehensive voltage regulation for power transformers with on-load tapchangers in distribution substations

More information

MINER-S Station Controller

MINER-S Station Controller MINER-S Station Controller Substation Automation MINER-S Station Controller The MINER-S Station Controller is a SCADA enabled fixed point remote terminal unit (RTU) with a data concentrator, event reporter,

More information

RT4B-110V/12A RECTIFIER

RT4B-110V/12A RECTIFIER The RT4B-110V/12A is a switched mode rectifier (SMR) module designed to provide up to 12A of output current into a 110V nominal system. It can be used with or without a cooling fan. With a fan it runs

More information

MIC-2 Multi-instrument DATA SHEET

MIC-2 Multi-instrument DATA SHEET Measurements All 3-phase AC measurements True RMS 4-Quadrant energy Power Quality Analysis Replaces analogue meters RS-485 Modbus RTU protocol TCP/IP Modbus (optional) Profibus DP (optional) I/O modules

More information

Providing the missing piece in your Condition Based Monitoring platform

Providing the missing piece in your Condition Based Monitoring platform QUALITROL Transformer Monitoring System Providing the missing piece in your Condition Based Monitoring platform Modular design; full customization of monitoring parameters to meet specification Reduce

More information

PMC-630 Series Advanced Multifunction Meter

PMC-630 Series Advanced Multifunction Meter IEC 62053-22 Class 0.5S Compliant 2MB Log Memory Power Quality Monitoring Waveform Recording SOE Log Setpoint Alarms RS-485 and I/O Capabilities I residual Monitoring Large, Bright, Backlit LCD Display

More information

Scout-S Station Controller

Scout-S Station Controller Scout-S Station Controller Substation Automation Scout-S Station Controller The Scout-S Station Controller is a SCADA enabled remote terminal unit (RTU) with a data concentrator, event reporter, and built-in

More information

EPM Multilin ADVANCED POWER QUALITY METER. High Performance Power Quality and Transient Recorder Meter KEY BENEFITS APPLICATIONS FEATURES

EPM Multilin ADVANCED POWER QUALITY METER. High Performance Power Quality and Transient Recorder Meter KEY BENEFITS APPLICATIONS FEATURES Multilin EPM 9900 ADVANCED POWER QUALITY METER High Performance Power Quality and Transient Recorder Meter KEY BENEFITS Auto-calibrating metrology means the meter maintains its accuracy over temperature

More information

www. ElectricalPartManuals. com Protective Relays HIGHLIGHTS PROTECTIVE FUNCTIONS ixp-420 Transformer Protection Relay

www. ElectricalPartManuals. com Protective Relays HIGHLIGHTS PROTECTIVE FUNCTIONS ixp-420 Transformer Protection Relay Protective Relays Electrical Apparatus ixp-420 Transformer Protection Relay 165-420 Figure 1: Edison Idea Relay The ixp-420 is a member of Cooper Power Systems Edison Idea line of protective relays. The

More information

Smart Energy & Power Quality Solutions. UMG 96S Universal flush-mounting measuring instrument

Smart Energy & Power Quality Solutions. UMG 96S Universal flush-mounting measuring instrument Smart Energy & Power Quality Solutions UMG 96S Universal flush-mounting measuring instrument UMG 96S UMG 96S Universal flushmounting measuring instrument Universal flush-mounting measuring instruments

More information

SDM530CT-Modbus USER MANUAL 2015 V1.6. Three Phase Multi-function DIN rail meter. Eastron SDM530CT-Modbus User Manual

SDM530CT-Modbus USER MANUAL 2015 V1.6. Three Phase Multi-function DIN rail meter. Eastron SDM530CT-Modbus User Manual SDM530CT-Modbus Three Phase Multi-function DIN rail meter Measures kwh Kvarh, KW, Kvar, KVA, P, F, PF, Hz, dmd, V, A, etc. Bi-directional measurement IMP & EXP Two pulse outputs RS485 Modbus Din rail mounting

More information

U niversal Measuring Device UMG 96 S. Little Fieldbus Giant. Modbus / Profibus. Harmonics. Memory. Analogue outputs. Digital I/O

U niversal Measuring Device UMG 96 S. Little Fieldbus Giant. Modbus / Profibus. Harmonics. Memory. Analogue outputs. Digital I/O U niversal Measuring Device Little Fieldbus Giant Modbus / Profibus Harmonics Memory Analogue outputs Digital I/O Modem Recorder Profibus Modbus PC I/O Universal Measuring Device Application Application

More information

Comprehensive Modular Genset Controller

Comprehensive Modular Genset Controller Inteligen Learn More Comprehensive Modular Genset Controller Brief Description The Inteligen is a comprehensive controller for single and multiple generating sets operating in standby or parallel to the

More information

PowerLogic power-monitoring units. PM1000 series power meter. Technical data sheet

PowerLogic power-monitoring units. PM1000 series power meter. Technical data sheet PowerLogic power-monitoring units power meter Technical data sheet 2011 Basic energy meters Functions and characteristics PE86261 PE86260 PowerLogic PM1000 power meter. The PowerLogic power meters are

More information

APU 200 Automatic DATA SHEET Gen-set Controller DATA SHEET

APU 200 Automatic DATA SHEET Gen-set Controller DATA SHEET APU 200 Automatic DATA SHEET Gen-set Controller DATA SHEET Measurement input, auto range Up to 1000 V AC L-L Up to 12.5 A (sinusoidal) 16 400 Hz Output Up to four analogue outputs Relay output RS 485 Modbus

More information

PQM - Power Quality Monitoring

PQM - Power Quality Monitoring UMG 96S PQM - Power Quality Monitoring The little field bus giant Universal flush-mounting measuring instruments of the UMG 96S product family are mainly designed for use in low and medium voltage distribution

More information

MIC-2 MKII, Multi-instrument DATA SHEET

MIC-2 MKII, Multi-instrument DATA SHEET MIC-2 MKII, Multi-instrument DATA SHEET Measurements All 3-phase AC measurements True RMS 4-Quadrant energy Power Quality Analysis Replaces analogue meters RS-485 Modbus RTU protocol TCP/IP Modbus (optional)

More information

Metering Devices IQ 300

Metering Devices IQ 300 Effective: May 2001 Page 1 New Information Contents Description Page General Description......... 2 Specifications.............. 3 Field Wiring Connections.... 4 Page 2 Effective: May 2001 Applications

More information

Designed For Reliability Manufactured To Last

Designed For Reliability Manufactured To Last 512/1024 samples/cycle IEC 62053-22 Class 0.2S Compliant IEC 61000-4-30 Class A Sag/Swell, Transient and Flicker Comprehensive Data Recording PQDIF & COMTRADE Compatible 5.7 Color LCD Display @ 640x480

More information

OHIO SEMITRONICS, INC. AC MULTIFUNCTION PROGRAMMABLE TRANSDUCERS & -1000L

OHIO SEMITRONICS, INC. AC MULTIFUNCTION PROGRAMMABLE TRANSDUCERS & -1000L AC PROGRAMMABLE TRANSDUCERS MODBUS OR LONWORKS DESCRIPTION The DMT-1000 is a programmable transducer with an RS-485 bus interface (MODBUS ). It supervises several variables of a poly-phase electrical power

More information

Type VRLTC tap changer

Type VRLTC tap changer Report No. 1ZUA938502-AGC 2, Rev 0 Date: 6 November 2012 Type VRLTC tap changer Ruggedized electronics systems specification & type test data Product Style No Rating By Type VRLTC, on-tank, vacuum reactance

More information

MIC-2 MKII & MIC-2 MKII DIN, Multi-instrument DATA SHEET

MIC-2 MKII & MIC-2 MKII DIN, Multi-instrument DATA SHEET & DIN, Multi-instrument DATA SHEET Measurements All 3-phase AC measurements True RMS 4-Quadrant energy Power Quality Analysis Replaces analogue meters RS-485 Modbus RTU protocol TCP/IP Modbus (optional)

More information

Relion 611 series. 611 series Type Test Certificate

Relion 611 series. 611 series Type Test Certificate Relion 611 series 611 series Document ID: 1MRS757466 Issued: 2016-02-22 Revision: B Product version: 2.0 Copyright 2016 ABB. All rights reserved Table of contents Table of contents Section 1 Section

More information

Voltage Transducer UMT516 / MT516

Voltage Transducer UMT516 / MT516 Voltage Transducer UMT516 / MT516 True RMS AC voltage measurements Voltage auto range measurements up to 600V # Wide frequency measurement range 16 400 Hz High accuracy class 0.2 (IEC-688), 0.1 on communication

More information

PM800 series. Applications

PM800 series. Applications Functions and characteristics PE86134 The PowerLogic meters offers many high-performance capabilities needed to meter and monitor an electrical installation in a compact 96 x 96 mm unit. All models include

More information

IPD163C. Single-Phase Multifunction Meter User Manual Version: V1. August 20, 2017

IPD163C. Single-Phase Multifunction Meter User Manual Version: V1. August 20, 2017 163C Single-Phase Multifunction Meter User Manual Version: V1 August 20, 2017 This manual may not be reproduced in whole or in part by any means without the express written permission from IPD. The information

More information

extending the boundaries of technology evolution of proven technology FEATURES

extending the boundaries of technology evolution of proven technology FEATURES extending the boundaries of technology evolution of proven technology FEATURES IEC 61850 compliant Advanced AC capabilities with comprehensive fault detection Integrated protection functions Disturbance

More information

UMG 20CM. 20 Channel Branch Circuit Monitoring Device with RCM

UMG 20CM. 20 Channel Branch Circuit Monitoring Device with RCM 20 Channel Branch Circuit Monitoring Device with RCM RCM Harmonics via analysis channel Alarm management GridVis Analysis software 20 current channels Interfaces / communication RS485 RTU Accuracy of measurement

More information

VCL-TP, Teleprotection Equipment With Trip Counter Display Panel

VCL-TP, Teleprotection Equipment With Trip Counter Display Panel VCL-TP, Teleprotection Equipment With Trip Counter Display Panel Data Sheet Copyright: Valiant Communications Limited. 2008-2014 1 Product Overview VCL-TP, Teleprotection Equipment is an extremely reliable

More information

Current Fault Signatures and Analysis Auto-calibrating metrology means the meter maintains its accuracy over temperature and time

Current Fault Signatures and Analysis Auto-calibrating metrology means the meter maintains its accuracy over temperature and time Multilin EPM 9900 High Performance Power Quality and Transient Recorder Meter The EPM 9900 is one of the most advanced monitoring products on the market today, providing you with the total picture of energy

More information

InteliLite MRS17 Click Here to Learn More

InteliLite MRS17 Click Here to Learn More InteliLite MRS17 Click Here to Learn More Comprehensive Genset Controller Brief Description The InteliLite is a cost effective controller for generator sets in stand-by and prime power applications. The

More information

Multilin EPM High Performance Power Quality Analysis Socket Meter. Monitoring & Metering. Advanced Communications. Key Benefits.

Multilin EPM High Performance Power Quality Analysis Socket Meter. Monitoring & Metering. Advanced Communications. Key Benefits. Multilin EPM 9800 High Performance Power Quality Analysis Socket Meter With the socket type mounting the EPM 9800 meter is perfect for industrial and utility applications where comprehensive power quality

More information

QUALITROL QTMS Transformer Monitoring System

QUALITROL QTMS Transformer Monitoring System QUALITROL QTMS Transformer System Providing the Missing Piece in Your Condition Based Platform Modular design; full customization of monitoring parameters to meet specification Reduce installation and

More information

NewCode. Comprehensive Motor Protection and Control Relay. Relay Field Input and Output LEDs. LED Fault Indicators

NewCode. Comprehensive Motor Protection and Control Relay. Relay Field Input and Output LEDs. LED Fault Indicators NewCode Comprehensive Motor Protection and Control Relay Relay Field Input and Output LEDs LED Fault Indicators Configurable Memory Module on a T-Bus IrDA and USB Connectors Profibus Address Indicator

More information

Function permission: yes/no. Operating range: 0.10 to 30 xin (step 0.01) Operating time: 0.02 to 300 s (step 0.01 s) Activation level 100%

Function permission: yes/no. Operating range: 0.10 to 30 xin (step 0.01) Operating time: 0.02 to 300 s (step 0.01 s) Activation level 100% Operating range: 0.10 to 30 xin (step 0.01) 50P(2) Activation level 100% Deactivation level 95% Timer accuracy: 30 ms Operating range: 0.10 to 30 xin (step 0.01) 50N/G(2) Activation level 100% Deactivation

More information

NEW MODERNSTE TECHNOLOGIE. Elektronische Messgeräte mit hoher WiFi Ethernet Leistungsfähigkeit. Führende Technologie in der Industrie

NEW MODERNSTE TECHNOLOGIE. Elektronische Messgeräte mit hoher WiFi Ethernet Leistungsfähigkeit. Führende Technologie in der Industrie SH RK 100S Elektronische Messgeräte mit hoher WiFi Ethernet Leistungsfähigkeit NEW MODERNSTE TECHNOLOGIE Führende Technologie in der Industrie Sehr anspruchsvolle Messtechnik Genauigkeitsklasse 0.2% Synchronisierimpuls

More information

INTRODUCTION. The PL-50 MO and PM-250 families represent the. PM-250-H: Horizontal box. PM-250-V: Vertical box

INTRODUCTION. The PL-50 MO and PM-250 families represent the. PM-250-H: Horizontal box. PM-250-V: Vertical box INTRODUCTION The PL-50 MO units are available in the next mechanical version: The PL-50 MO and PM-250 families represent the different solutions that Team Arteche offers for motor protection. Both families

More information

TM221M16TG controller M IO transistor PNP spring

TM221M16TG controller M IO transistor PNP spring Characteristics controller M221 16 IO transistor PNP spring Main Range of product Product or component type [Us] rated supply voltage Discrete input number Analogue input number Discrete output type Discrete

More information

TFS 2100 Traveling Wave Fault Location System

TFS 2100 Traveling Wave Fault Location System Traveling Wave Fault Location System The most accurate overhead transmission and distribution line fault locator Accuracy: ±150m typical regardless the line length Unaffected by fault resistance Suitable

More information

PowerLogic power-monitoring units. Power Meter PM500. Technical data sheet 2006

PowerLogic power-monitoring units. Power Meter PM500. Technical data sheet 2006 PowerLogic power-monitoring units Technical data sheet 2006 Functions and characteristics E90463 The PowerLogic PM500 Power Meter provides all measurement capabilities required to monitor an electrical

More information

MONITORING AND CONTROL REQUIREMENTS FOR DISTRIBUTED GENERATION FACILITIES

MONITORING AND CONTROL REQUIREMENTS FOR DISTRIBUTED GENERATION FACILITIES MONITORING AND CONTROL REQUIREMENTS FOR DISTRIBUTED GENERATION FACILITIES 1. Introduction Real time monitoring and control is necessary to ensure public and employee safety and to protect the integrity

More information

UMG 96RM. UMG 96RM Universal measurement instrument. Areas of application

UMG 96RM. UMG 96RM Universal measurement instrument. Areas of application UMG 96RM UMG 96RM Universal measurement instrument The UMG 96RM is a very compact and powerful universal measurement device designed for use in low and medium voltage distribution systems. In addition

More information

DIN Rail Smart Meter for Single and Three Phase Electrical Systems

DIN Rail Smart Meter for Single and Three Phase Electrical Systems SDM630-Modbus V2 DIN Rail Smart Meter for Single and Three Phase Electrical Systems Measures kwh Kvarh, KW, Kvar, KVA, P, F, PF, Hz, dmd, V, A, etc. Bi-directional measurement IMP & EXP Two pulse outputs

More information

TM221M16R controller M IO relay

TM221M16R controller M IO relay Product data sheet Characteristics TM221M16R controller M221 16 IO relay Complementary Main Discrete I/O number 16 Number of I/O expansion module Supply voltage limits Inrush current Power consumption

More information

Part No. Description Product Life Cycle Phase *) unit, 24 VDC, spring terminals. unit, 24 VDC, spring terminals, XC version

Part No. Description Product Life Cycle Phase *) unit, 24 VDC, spring terminals. unit, 24 VDC, spring terminals, XC version Ordering Data DATA SHEET TU520 Terminal Unit 1 Ordering Data Part No. Description Product Life Cycle Phase *) 1SAP 214 400 R0001 1SAP 414 400 R0001 TU520-ETH, PROFINET I/O terminal unit, 24 VDC, spring

More information

Industry Leading Performance From Simple to Sophisticated The Leader in Power Monitoring and Control

Industry Leading Performance From Simple to Sophisticated The Leader in Power Monitoring and Control www.electroind.com Shark 200T Transducer Only Shark 200 Meter/Transducer From Simple to Sophisticated Simple Multifunction Meter: VSwitch Key 1 Historical Datalogging: VSwitch Key 2 Advanced Power Quality

More information

Type MVTT 14 and MVTT 15: Static Digital Time delay relays

Type MVTT 14 and MVTT 15: Static Digital Time delay relays Type MVTT 4 and MVTT 5: Static Digital Time delay relays Features 000/ setting range Time settings easily selected by means of thumbwheel switches Provide time delayed pick-up, or drop-off Compact construction

More information

SAM Listed LED Optimized Drivers. Environmental. Electrical Specifications at 25 O C E Output Current. Voltage Accuracy

SAM Listed LED Optimized Drivers. Environmental. Electrical Specifications at 25 O C E Output Current. Voltage Accuracy 17 Watt s Model: LD UL SAM Series Drive Mode: Constant Voltage Technology: PFC Off-Line Switch Mode Power: Max. Voltages: 1VDC or 4VDC Currents: 175mA - 1400mA Environmental 1. Operating temperature: Tc

More information

Industry Leading Performance From Simple to Sophisticated The Leader in Power Monitoring and Control

Industry Leading Performance From Simple to Sophisticated The Leader in Power Monitoring and Control www.electroind.com Shark 200T Transducer Only Shark 200 Meter/Transducer From Simple to Sophisticated Simple Multifunction Meter: VSwitch Key 1 Historical Datalogging: VSwitch Key 2 Advanced Power Quality

More information

GRD130 - FEATURES APPLICATION

GRD130 - FEATURES APPLICATION FEATURES Phase undervoltage protection with IDMTL or DTL. Phase overvoltage protection with IDMTL or DTL. Zero phase sequence overvoltage (neutral voltage displacement) protection with IDMTL/DTL. Negative

More information

MW/MVAR Transducer Specifications

MW/MVAR Transducer Specifications GUARANTEED TECHNICAL PARTICULARS (To be submitted by bidder with the tender) MW/MVAR Transducer Specifications Sr.No. Descriptions Details Offered by supplier 1 2 3 4 Transducer suitable for Input Output

More information

FL MC 2000E (SM40) LC

FL MC 2000E (SM40) LC IEC 61850 fiber optic converter with LC fiber optic connection (1310 nm) to convert 100Base-Tx to single- or multi-mode fiber glass Data sheet 3205_en_C 1 Description PHOENIX CONTACT 2014-04-04 2 Features

More information

Smart Energy & Power Quality Solutions. UMG 505 Power analysis, LON and I/O-Vielfalt

Smart Energy & Power Quality Solutions. UMG 505 Power analysis, LON and I/O-Vielfalt Smart Energy & Power Quality Solutions UMG 505 Power analysis, LON and I/O-Vielfalt UMG 505 UMG 505 Power analysis, LON and I/O-Vielfalt Power analysers of the UMG505 product family are mainly designed

More information

PROTECTION RELAYS THE ULTRA LINE NUMERICAL MULTIFUNCTION INTELLIGENT DEVICE FOR PROTECTION, SUPERVISION, METERING AND CONTROL

PROTECTION RELAYS THE ULTRA LINE NUMERICAL MULTIFUNCTION INTELLIGENT DEVICE FOR PROTECTION, SUPERVISION, METERING AND CONTROL MICROPROCESSOR PROTECTION RELAYS THE ULTRA LINE NUMERICAL MULTIFUNCTION INTELLIGENT DEVICE FOR PROTECTION, SUPERVISION, METERING AND CONTROL MICROELETTRICA SCIENTIFICA MANUFACTURES A COMPLETE RANGE OF

More information

Unidades de monitorio de potencia Power Logic ION 8650

Unidades de monitorio de potencia Power Logic ION 8650 Unidades de monitorio de potencia Power Logic ION 8650 Functions and characteristics PB107500 Used to monitor electric energy provider networks, service entrances and substations, PowerLogic meters are

More information

ekorrps MULTIFUNCTIONAL PROTECTION UNIT CONFIGURATION AND GENERAL CHARACTERISTICS LIB

ekorrps MULTIFUNCTIONAL PROTECTION UNIT CONFIGURATION AND GENERAL CHARACTERISTICS LIB MO-067-EN Operation Manual MULTIFUNCTIONAL PROTECTION UNIT CONFIGURATION AND GENERAL CHARACTERISTICS LIB Transformer Substations Secondary Distribution Switchgear Primary Distribution Switchgear Protection

More information

RT12-240V/2.4kW Rectifier Specification

RT12-240V/2.4kW Rectifier Specification The RT12-240V/2.4kW is a switched mode rectifier (SMR) module that delivers up to 2.4kW of output power (and up to 11A output current) into a 240V nominal DC system. The RT12 suits AC supply voltages between

More information

TF501, TF521 Terminal Bases

TF501, TF521 Terminal Bases Ordering Data DATA SHEET TF501, TF521 Terminal Bases 1 Ordering Data Part No. Scope of delivery Product life cycle status 1SAP 117 000 R0271 1SAP 317 000 R0271 1SAP 117 200 R0271 1SAP 317 200 R0271 TF501-CMS,

More information