CSC-326 Transformer Protection IED Engineering and Operation Manual

Size: px
Start display at page:

Download "CSC-326 Transformer Protection IED Engineering and Operation Manual"

Transcription

1 CSC-326 Transformer Protection IED Engineering and Operation Manual

2 CSC-326 Transformer Protection IED Engineering and Operation Manual Compiled: Jin Rui Checked: Hou Changsong Standardized: Li Lianchang Inspected: Cui Chenfan Version: V1.00 Doc.Code:0SF (E) Issued Date:

3 Version:V1.00 Doc. Code: 0SF (E) Issued Date: Copyright owner: Beijing Sifang Automation Co., Ltd Note: The company keeps the right to perfect the instruction. If equipments do not agree with the instruction at anywhere, please contact our company in time. We will provide you with corresponding service. is registered trademark of Beijing Sifang Automation Co., Ltd. We reserve all rights to this document, even in the event that a patent is issued and a different commercial proprietary right is registered. Improper use, in particular reproduction and dissemination to third parties, is not permitted. This document has been carefully checked. If the user nevertheless detects any errors, he is asked to notify us as soon as possible. The data contained in this manual is intended solely for the IED description and is not to be deemed to be a statement of guaranteed properties. In the interests of our customers, we constantly seek to ensure that our products are developed to the latest technological standards as a result it is possible that there may be some differences between the hardware/software product and this information product. Manufacturer: Beijing Sifang Automation Co., Ltd. Tel: , ext Fax: sf_sales@sf-auto.com Website: Add: No.9, Shangdi 4th Street, Haidian District, Beijing, P.R.C

4 Preface Purpose of this manual This manual describes operation, installation, commissioning, protection test and putting the IED into service. The manual includes the following chapters: Introduction, this chapter presents the basic content and have a brief introduction of this manual Local human machine interface, this chapter presents the configuration of HMI interface and how to use the HMI Installing the IED, this chapter introduces the procedure to install IED and how to check that the IED is properly connected to the protection system Read and change setting, this chapter introduces how to read and change the setting value via LHMI or software tool, and switch the setting value group Testing the communication connection and time synchronization, this chapter presents how to test the communication port connection and introduces how to test time synchronization IED testing, this chapter contains that what should be tested and how to test the IED Operating maintenance, this chaper describes the items for maintenance and how to maintain the IED when operating Transportion and storage, this chapter presents how to transport and store the IED Appendix, this chapter presents the significant data and diagram of the IED Target audience This manual mainly face to installation engineer, commissioning engineer and operation engineer with perfessional electric and electrical knowledge, rich experience in protection function, using protection IED, test IED, responsible

5 for the installation, commissioning, maintenance and taking the protection IED in and out of normal service. Applicability of this manual This manual is valid for CSC-326 Transformer Protection IED. Technical support In case of further questions concerning the CSC family, please contact Sifang compay or your local Sifang representative. Safety information Strictly follow the company and international safety regulations. Working in a high voltage environment requires serious approch to aviod human injuries and damage to equipment Do not touch any circuitry during operation. Potentially lethal voltages and currents are present Avoid to touching the circuitry when covers are removed. The IED contains electirc circuits which can be damaged if exposed to static electricity. Lethal high voltage circuits are also exposed when covers are removed Using the isolated test pins when measuring signals in open circuitry. Potentially lethal voltages and currents are present Never connect or disconnect wire and/or connector to or from IED during normal operation. Dangerous voltages and currents are present. Operation may be interrupted and IED and measuring circuitry may be damaged Always connect the IED to protective earth regardless of the

6 operating conditions. Operating the IED without proper earthing may damage both IED and measuring circuitry and may cause injuries in case of an accident. Do not disconnect the secondary connection of current transformer without short-circuiting the transformer s secondary winding. Operating a current transformer with the secondary winding open will cause a high voltage that may damage the transformer and may cause injuries to humans. Do not remove the screw from a powered IED or from an IED connected to power circuitry. Potentially lethal voltages and currents are present Using the certified conductive bags to transport PCBs (modules). Handling modules with a conductive wrist strap connected to protective earth and on an antistatic surface. Electrostatic discharge may cause damage to the module due to electronic circuits are sensitive to this phenomenon Do not connect live wires to the IED, internal circuitry may be damaged When replacing modules using a conductive wrist strap connected to protective earth. Electrostatic discharge may damage the modules and IED circuitry When installing and commissioning, take care to avoid electrical shock if accessing wiring and connection IEDs Changing the setting value group will inevitably change the IEDs operation. Be careful and check regulations before making the change

7 Contents Chapter 1 IED Introduction... 1 Chapter 2 Local human machine interface Introduction Liquid crystal display(lcd) Keyboard IED menu Menu construction Operation status Query reports Set time Contrast Settings IED setting Test binary output Testing operation Chapter 3 Installing IED Unpacking and checking the IED Installing the IED IED connection IED connector Introduction Terminals of Analogue Input Module (AIM) Terminals of Binary Input Module (BIM) Terminals of Binary Output Module (BOM) Terminals of Communication module (COM) Communication ports of CPU module (CPU) Terminals of Power Supply Module (PSM) RS232 port Connecting to protective earth Connecting the power supply module Connecting to CT and VT circuits Connecting the binary inputs and outputs Making the screen connection Optical connections RS485 and RS232 ports connection RS485 port connection RS232 port connection Connecting the GPS Checking before energizing Introduction... 31

8 4.2 Checking the protective earth connection Checking the power supply connection Checking the CT and VT circuits connection Checking the CT circuits connection Checking the VT connection Checking the binary input and output connection Checking the binary input connection Checking the binary output connection Checking the screened cables connection Checking the optical connections Checking the S485 and RS232 port connectios Checking the RS485 port connection Checking RS232 port connection Checking GPS connection Checking the insulation voltage and insulation resistance Checking the insulation voltage Checking the insulation resistance Checking after energizing Introduction Test LCD Test the keyboard Setting the IED time Self-supervision HMI data Checking the software and hardware version Chapter 4 Read and change setting Read and change the setting vaule Read and change the setting value via LHMI Introduction Communication parameter Equipment parameter Setting values and binary settings for protection function Switching the setting group Introduction Method for switching setting group via LHMI Method for switching setting group via binary input Chapter 5 Testing the communication connection and time synchronization Testing the communication connection Testing the Ethernet communication Testing the electrical Ethernet communication Testing the optical Ethernet communication Testing the RS485 port Testing the RS232 port Testing the time synchronization Network mode... 50

9 2.2 Pulse mode IRIG-B mode Chapter 6 IED testing Introduction Points for attention during testing Preparing for test Introduction Connecting test equipment to IED Testing the power supply Checking the self-startup performance DC power on and power off testing Checking the expiry date of power supply Checking the analog channel Checking the zero drift Calibrating Checking the accuracy and the linearity of analog quantitis Checking the polarity of analog quantities Testing binary input Testing binary output Verifying the IED functions Instantaneous differential protection Verifying the settings Completing the test Reference setting list for test Percentage differential protection Verifying the settings Completing the test Reference setting list for test Restricted earth fault protection Verifying the settings Completing the test Reference setting list for test Overexcitation protection Verifying the settings Completing the test Reference setting list for test Overcurrent protection Verifying the settings Completing the test Reference setting list for test Earth fault protection Verifying the settings Completing the test Reference setting list for test

10 8.7 Neutral earth fault protection Verifying the settings Completing the test Reference setting list for test Thermal overload protection Verifying the settings Completing the test Reference setting list for test Overload protection Verifying the settings Completing the test Reference setting list for test Overvoltage protection Verifying the settings Completing the test Reference setting list for test Circuit breaker failure protection Verifying the settings Completing the test Reference setting list for test Dead zone protection Verifying the settings Completing the test Reference setting list for test STUB protection Verifying the settings Completing the test Reference setting list for test Poles discordance protection Verifying the settings Completing the test Reference setting list for test Voltage transformer secondary circuit supervision Verifying the settings Completing the test Reference setting list for test Checking before operation Checking the LED Checking the display on LCD Checking the clock Checking the voltage and current Checking the setting group Checking the setting Checking the binary input

11 9.8 Checking the normal operation mode Trip and close test with the circuit breaker Put into operation Chapter 7 Operating maintenance Attentions during operating Routine checking Periodical checking Operation after updating software or replacing modules Operation after updating software or replacing CPU module Operation after updating software or replacing communication module Operation after replacing the binary input or output module Operation after replacing the analog input module Operation after replacing power supply module The alarm information and measure Alarm information and the measure Chapter 8 Transportation and storage Transportion Storage Chapter 9 Appendix Arrangement diagram of modules Typical diagram

12 Chapter 1 IED Introduction Chapter 1 IED Introduction About this chapter This chapter presents the overview of the operation and engineering about the IED. 1

13 Chapter 1 IED Introduction The Human Machine Interface (HMI) on the IED provides an ideal mechanism for the day to day operation and even advanced use of the IED. The keyboard, LCD and LEDs on the front of the IED are what constitute the HMI. Troubleshooting, monitoring, setting and configuring are all possible via this interface. Through the screens and menu elements available, as well as the keypad, the user is able to navigate throughout the menu structure and move from screen to screen. The IED is unpacked and visually checked. The connection to the protection system has to be checked in order to verify that the installation is successful. The settings for each function must be calculated before the commissioning task. The functions setting menu have been listed in detail so that the user can find and change the required settings directly and correctly. For the different application, the IED can be performed conveniently through switching the setting group. For the functions included in the IED can be tested by users, the testing procedure have been listed as reference to verify that protection function operate correctly. After the IED is in service, some checking items also need to be done for maintenance in order to ensure that the IED is in good condition during operation, some suggestions have been preset as reference and the user can perform some other checking items according to the relevant regulations. 2

14 Chapter 2 Local human machine interface Chapter 2 Local human machine interface About this chapter This chapter describes the structure of human-machine interface (HMI), LCD, LED, keyboard, RS232 and IED menu. Instruction on how to operate with keys, how to configure the LED and menu information introduction. 3

15 Chapter 2 Local human machine interface 1 Introduction The HMI is simple and easy to be used for routine operation, the front plate of the HMI consists of LCD, LED and keyboard. As shown in the following picture, the setting, configuration, monitoring, maintenance and fault analysis can be performed in HMI CSC Figure 1 Front plate with 8 LEDs CSC Figure 2 Front plate with 20 LEDs 1. Liquid crystal display (LCD) 4

16 Chapter 2 Local human machine interface 2. LEDs 3. Shortcut function keys 4. Arrow keys 5. Reset key 6. Quit key 7. Set key 8. RS232 communication port 5

17 Chapter 2 Local human machine interface 2 Liquid crystal display(lcd) The LCD back light of HMI is blue, 8 lines with up to 28 characteristics per line can be displayed. When operating keys are pressed or in the case of IED alarming or operating report appearance, the back light will turn on automatically until the preset time delay elapse after the latest operation or alarm. 6

18 Chapter 2 Local human machine interface 3 Keyboard The keyboard is used to monitor and operate IED. The keyboard has the same look and feel in CSC family. As shown in Figure 1, keyboard is divided into Arrow keys, Reset key, Quit key, Set key and shorcut function keys. The specific instructions on the keys as the following table described: Table 1 HMI keys on the front of the IED Key Function Up arrow key Move up in menu Page up between screens Increase value in setting Down arrow key Move down in menu Page down between screens Decrease value in setting Left arrow key Move left in menu Right arrow key Move Right in menu Reset key Reset the LEDs Return to normal scrolling display state directly Set key Enter main menu or submenu Confirm the setting change Quit key Back to previous menu Cancel the current operation and back to previous menu Return to scrolling display state Lock or unlock current display in the scrolling display state (the lock state is indicated by a key type icon on the upright corner of the LCD) 7

19 Chapter 2 Local human machine interface 4 IED menu 4.1 Menu construction AI Version OpStatus EquipCode Measure BI Impen.Z QueryRpt EventRpt StartRpt AlarmRpt Log Set Time Cur Time Set Time Contrast TestEffect MainMenu Settings CommuPara ProtSet EquipPara ProtContWd Test Menu SOEReset Protocol Setup ModifyPW SetPrint 103Type AI DisplaySet Test BO SimuReSig SwSetGr Testing ViewDrift ViewScale AdjDrift AdjScale PrtSample 8

20 Chapter 2 Local human machine interface Table 2 Full name for the menu Sub-menu Full name Sub-sub menu Full name AI Analog input EquipCode Equipment code OpStatus Operation status Measure Measurement quantity Version IED version BI Binary input Impen.Z Impedance value EventRpt Event reports QueryRpt Query reports AlarmRpt Alarm reports StartRpt Startup report Log Operation logging Set time Setting time Cur Time Current time Set Time Set time Contrast LCD contrast TestEffect Test effect CommuPara Communication parameter ProtSet Protection setting Settings Setting value Test menu Test menu EquipPara Equipment parameter PortContwd Protection binary setting SOEReset SOE reset selection ModifyPW Modify password Setup IED setting SetPrint Setting the print Protocol Protocol selection 103Type 103 function type Test BO Test binary output SimuReSig Simulation remote signalization ViewDrift View zero drift ViewScale View scale Testing Testing operation PrtSample Print sample value SwSetGr Switch setting group AdjDrift Adjust zero drift AdjScale Calibrating 4.2 Operation status Sub menu Sub-sub menu Explanation AI Read the secondary analogue of the selected CPU OpStatus module EquipCode Read the versions, released time and CSC code of all modules 9

21 Chapter 2 Local human machine interface Sub menu Sub-sub menu Explanation Measure Read the analogue value and calculation value Version Read the IED type, date and CPU version BI Read the current status of binary inputs, Off or On Impen.Z Read the impedace value of real and imaginary parts, including: Z a, Z b, Z c, Z ab, Z bc, Z ca 4.3 Query reports Sub menu QueryRpt Sub-sub menu Sub-sub-sub menu Explanation EventRpt Latest Rpt Query the latest event report, press the Set key to see the report Last 6 Rpts Query the latest six event reports, press the Set key to see the report QueryRpt by Date Query the reports by date AlarmRpt Last 6 Rpts Query the latest six alarm reports, press the Set key to see the report QueryRpt by Date Query the reports by date Latest Rpt Query the latest event report, press the Set key to see the report StartRpt Last 6 Rpts Query the latest six event reports, press the Set key to see the report QueryRpt by Date Query the reports by date Log Last 6 Rpts Query the latest six operation reports, press the Set key to see the report QueryRpt by Date Query the reports by date 4.4 Set time Sub menu Sub-sub menu Explanation Set time Cur Time Set Time Modify the time with arrow keys 4.5 Contrast 10

22 Chapter 2 Local human machine interface Sub menu Sub-sub menu Explanation Contrast TestEffect Modify the contrast with arrow keys 4.6 Settings Sub menu Settings Sub-sub menu CommuPara ProtSet Test Menu EquipPara PortContwd Sub-sub-sub Explanation menu BayName Enter into the line name TimeMode NetworkTimeMode PulseTimeMode IRIG-B TimeMode CommAddr Enter into the LON and RS485 address, and the Ethernet 1 and Ethernet 2 address BaudR485 Selection with up or down buttons Common Common protection setting in this menu Current Protection setting relation with current in this menu CBF Protection setting relation with CBF in this menu Distance Distance protection setting in this menu Voltage Protection setting relation with voltage in this menu Reclose Protection setting relation with reclosure in this menu Common Common protection binary setting in this menu Current Protection binary setting relation with current in this menu CBF Protection binary setting relation with CBF in this menu Distance Distance protection binary setting in this menu Voltage Protection binary setting relation with voltage in this menu Reclose Protection binary setting relation with reclosure in this menu 4.7 IED setting 11

23 Chapter 2 Local human machine interface Sub menu Setup Sub-sub menu Sub-sub-sub menu Explanation Manual Reset SOEReset Automatic Reset Really Reset ModifyPW The fatory password: Type IEC code Protocol If communication with automation system via RS485 port, this item can be ignored SetPrint RecPrt Setup Print Mode AI DisplaySet Display Sec Ai Display secondary analog input quantity Display Pri Ai Display primary analog input quantity 4.8 Test binary output Sub menu Sub-sub menu Sub-sub-sub menu Explanation Test BO 4.9 Testing operation Sub menu Sub-sub menu Sub-sub-sub menu Explanation Simu Alarm Simu Connt TransRecData SimuReSig Simu Trip Using or X to select the simulation point Simu BI Simu MST Testing Alarm ViewDrift ViewScale PrtSample SwSetGr Enter into the CPU number AdjDrift AdjScale 12

24 Chapter 3 Installing IED Chapter 3 Installing IED About this chapter This chapter describes how to install the protection IED, introduces connection of the contactor, analogue quantities, binary inputs and outputs and power supply, and what should to do before and after energizing. 13

25 Chapter 3 Installing IED 1 Unpacking and checking the IED Procedure: 1. Remove the transporting case 2. Visually inspect the IED 3. Check all items included in accordace with the delivery documents. Once the IED has been started make sure that the software functions ordered have been included in the delivery 4. Check for transport damages If transport damage is discovered appropriate action must be taken against the latest carrier and the latest SiFang office or representative should be informed. If there are any discrepancies in relation to the delivery documents, the SiFang company should be notified immediately 5. If the protection IED is repacked for transport again, the storage packing of the IED must provide proper degree of protection against possible damage, in accordance with the standard of IEC class 1 and IEC class 1 14

26 Chapter 3 Installing IED 2 Installing the IED Procedure: 1. Insert the IED into cabinet and the bottom of the IED should be supported on the frame of cabinet 2. Fix the IED by tightening all screws against the cabinet. The IED should be fixed in the cabinet and each screw should be firmed 3. Connect the earthing screw on the rear panel to the nearest protective earthing point in the cubicle. The protective earth cables should be green or yellow conductors with cross-sectional area 2.5mm 2 according to electrical regulations and electrical standards requirement The cubicle must be properly connected to station earthing system, using the conductor with cross-sectional area of at least 4mm Power supply module connection The wiring from the cubicle terminal block to the IED terminals must be connected in accordance with the established guidelines for this type of IED. The wires from binary inputs and outputs and the auxiliary power supply must be routed separated from the current transformer cables between the terminal blocks of the cubicle and the IEDs connections. 5. Connection to CT and VT circuits CT and VT are connected to the analogue input module on the rear side of the IED. Using solid conductor with cross-sectional 2.5-6mm 2 (AWG14-10) or stranded conductor with cross-sectional 2.5-4mm 2 (AWG14-12). The screws used for fixation conductor should be tightened. 6. Connecting the binary input and output signals Auxiliary power supply and binary input and output signals are connected using female connectors. Signal wires are connected to a female connector, which is then plugged into the corresponding male connector, located at the rear of the IED. 15

27 Chapter 3 Installing IED 3 IED connection 3.1 IED connector Introduction The quantity and designation of connectors depend upon the ordering information and application. The rear cover plates are prepared with enough space for each configuration in ordering information and the cut-outs that are not in use are covered with a plate from factory. 16

28 Chapter 3 Installing IED Terminals of Analogue Input Module (AIM) b a Table 3 of terminals of AIM b01 b02 b03 b04 b05 b06 b07 b08 b09 b10 b11 b12 a01 a02 a03 a04 a05 a06 a07 a08 a09 a10 a11 a12 Terminal Analogue Input Remark a01 I 1A Star point b01 I 1A a02 I 1B Star point b02 I 1B a03 I 1C Star point b03 I 1C a04 I 2A Star point b04 I 2A a05 I 2B Star point b05 I 2B a06 I 2C Star point Figure 3 Terminals arrangement of AIM b06 I 2C a07 I 1G Star point b07 I 1G a08 I 2G Star point b08 I 2G a09 b09 a10 U 0 Star point b10 U 0 a11 U B Star point b11 U C Star point a12 U A Star point b12 U N 17

29 Chapter 3 Installing IED Terminals of Binary Input Module (BIM) c02 c04 c06 c08 c10 c12 c14 c16 c18 c20 c22 c24 c26 c28 c30 c32 c DC - a DC - a02 a04 a06 a08 a10 a12 a14 a16 a18 a20 a22 a24 a26 a28 a30 a32 c08 BI8 BI group 2 a10 BI9 BI group 1 c10 BI10 BI group 2 a12 BI11 BI group 1 c12 BI12 BI group 2 a14 BI13 BI group 1 c14 BI14 BI group 2 a16 BI15 BI group 1 c16 BI16 BI group 2 a18 BI17 BI group 1 c18 BI18 BI group 2 a20 BI19 BI group 1 c20 BI20 BI group 2 a22 BI21 BI group 1 c22 BI22 BI group 2 a24 BI23 BI group 1 c24 BI24 BI group 2 a26 BI25 BI group 1 c26 BI26 BI group 2 Figure 4 Terminals arrangement of BIM Table 4 of terminals of BIM Terminal Definition Remark a02 BI1 BI group 1 c02 BI2 BI group 2 a04 BI3 BI group 1 c04 BI4 BI group 2 a06 BI5 BI group 1 a28 BI27 BI group 1 c28 BI28 BI group 2 a30 BI29 BI group 1 c30 BI30 BI group 2 a32 DC - Input Common terminal of BI group 1 c32 DC - Input Common terminal of BI group 2 c06 BI6 BI group 2 a08 BI7 BI group 1 18

30 Chapter 3 Installing IED Terminals of Binary Output Module (BOM) Binary Output Module A The module provides 16 output relays for tripping or initiating, with total 16 contacts. R 1 R 3 R 5 R 7 R 9 R 11 R 13 R 15 c a c02 a02 c04 a04 c06 a06 c08 a08 c10 a10 c12 a12 c14 a14 c16 a16 c18 a18 c20 a20 c22 a22 c24 a24 c26 a26 c28 a28 c30 a30 c32 a32 R 2 R 4 R 6 R 8 R 10 R 12 R 14 R 16 Figure 5 Terminals arrangement of BOM A 19

31 Chapter 3 Installing IED Table 5 of terminals of BOM A Terminal Definition Related relay a02 Trip contact 1-0 Output relay 1 c02 Trip contact 1-1 Output relay 1 a04 Trip contact 2-0 Output relay 2 c04 Trip contact 2-1 Output relay 2 a06 Trip contact 3-0 Output relay 3 c06 Trip contact 3-1 Output relay 3 a08 Trip contact 4-0 Output relay 4 c08 Trip contact 4-1 Output relay 4 a10 Trip contact 5-0 Output relay 5 c10 Trip contact 5-1 Output relay 5 a12 Trip contact 6-0 Output relay 6 c12 Trip contact 6-1 Output relay 6 a14 Trip contact 7-0 Output relay 7 c14 Trip contact 7-1 Output relay 7 a16 Trip contact 8-0 Output relay 8 c16 Trip contact 8-1 Output relay 8 a18 Trip contact 9-0 Output relay 9 c18 Trip contact 9-1 Output relay 9 a20 Trip contact 10-0 Output relay 10 c20 Trip contact 10-1 Output relay 10 a22 Trip contact 11-0 Output relay 11 c22 Trip contact 11-1 Output relay 11 a24 Trip contact 12-0 Output relay 12 c24 Trip contact 12-1 Output relay 12 a26 Trip contact 13-0 Output relay 13 c26 Trip contact 13-1 Output relay 13 a28 Trip contact 14-0 Output relay 14 c28 Trip contact 14-1 Output relay 14 a30 Trip contact 15-0 Output relay 15 c30 Trip contact 15-1 Output relay 15 a32 Trip contact 16-0 Output relay 16 c32 Trip contact 16-1 Output relay 16 20

32 Chapter 3 Installing IED Binary Output Module C The module provides 16 output relays for signal, with total 19 contacts. R 4 R 5 R 1 R 2 R 3 R 6 R 7 c a c02 a02 c04 a04 c06 a06 c08 a08 c10 a10 c12 a12 c14 a14 c16 a16 c18 a18 c20 a20 c22 a22 c24 a24 c26 a26 c28 a28 c30 a30 c32 a32 R 8 R 9 R 10 R 11 R 12 R 13 R 14 R 15 R 16 Figure 6 Terminals arrangement of BOM C 21

33 Chapter 3 Installing IED Table 6 of terminals of BOM C Terminal Definition Related relay a02 Signal 1-0, Common terminal of signal contact group 1 c02 Signal 2-0, Common terminal of signal contact group 2 a04 Signal contact 1-1 Output relay 1 c04 Signal contact 2-1 Output relay 1 a06 Signal contact 1-2 Output relay 2 c06 Signal contact 2-2 Output relay 2 a08 Signal contact 1-3 Output relay 3 c08 Signal contact 2-3 Output relay 3 a10 Signal 3-0, Common terminal of signal contact group 3 c10 Signal 4-0, Common terminal of signal contact group 4 a12 Signal contact 3-1 Output relay 4 c12 Signal contact 4-1 Output relay 7 a14 Signal contact 3-2 Output relay 5 c14 Signal contact 4-2 Output relay 6 a16 Signal contact 5-0 Output relay 8 c16 Signal contact 5-1 Output relay 8 a18 Signal contact 6-0 Output relay 9 c18 Signal contact 6-1 Output relay 9 a20 Signal contact 7-0 Output relay 10 c20 Signal contact 7-1 Output relay 10 a22 Signal contact 8-0 Output relay 11 c22 Signal contact 8-1 Output relay 11 a24 Signal contact 9-0 Output relay 12 c24 Signal contact 9-1 Output relay 12 a26 Signal contact 10-0 Output relay 13 c26 Signal contact 10-1 Output relay 13 a28 Signal contact 11-0 Output relay 14 c28 Signal contact 11-1 Output relay 14 a30 Signal contact 12-0 Output relay 15 c30 Signal contact 12-1 Output relay 15 a32 Signal contact 13-0 Output relay 16 c32 Signal contact 13-1 Output relay 16 22

34 Chapter 3 Installing IED Terminals of Communication module (COM) Ethernet port A Ethernet port B Ethernet port C Table 7 of terminals of COM Terminal Definition 01 Null 02 Null 03 Null 04 Null 05 Optional RS485 port - 2B 06 Optional RS485 port - 2A 07 Optional RS485 port - 1B 08 Optional RS485 port - 1A 09 Time synchronization 10 Time synchronization GND 11 Null Figure 7 Terminals arrangement of COM 12 Null 13 Null 14 Null 15 Null 16 Null Ethernet port Ethernet Port A Ethernet Port B Ethernet Port C Optional optical fiber or RJ45 port for station automation system Optional optical fiber or RJ45 port for station automation system Optional optical fiber or RJ45 port for station automation system Figure 8 Examples of COM module 23

35 Chapter 3 Installing IED Communication ports of CPU module (CPU) Table 8 Definition of communication ports of CPU module Ch A RX TX Ports Ch A RX Definition Remote communication channel A optical fiber data receiving port Ch B RX TX Ch A TX Ch B RX Remote communication channel A optical fiber data transmitting port Remote communication channel B optical fiber data receiving port Ch B TX Remote communication channel B optical fiber data transmitting port Figure 9 Communication ports arrangement of CPU module Note: These ports are optional. Figure 10 Examples of CPU module 24

36 Chapter 3 Installing IED Terminals of Power Supply Module (PSM) c a c08 AUX.DC 24V- output 2 c02 c04 DC 24V + OUTPUTS a02 a04 a10 AUX.DC 24V- output 3 c10 AUX.DC 24V- output 4 c06 a06 a12 AUX.DC 24V- output 5 c08 c10 c12 c14 c16 c18 c20 c22 DC 24V - OUTPUTS AUX.DC + INPUT a08 a10 a12 a14 a16 a18 a20 a22 c12 AUX.DC 24V- output 6 a14 Alarm contact A1, for AUX.DC power input failure c14 Alarm contact A0, for AUX.DC power input failure a16 Alarm contact B1, for AUX.DC power input failure c16 Alarm contact B0, for AUX.DC power input failure c24 a24 a18 Isolated terminal, not wired c26 c28 AUX. DC - INPUT a26 a28 c18 Isolated terminal, not wired a20 AUX. power input 1, DC + c30 a30 c20 AUX. power input 2, DC + c32 a32 a22 AUX. power input 3, DC + c22 AUX. power input 4, DC + Figure 11 Terminals arrangement of PSM a24 Isolated terminal, not wired Table 9 of terminals of PSM Terminal Definition a02 AUX.DC 24V+ output 1 c02 AUX.DC 24V+ output 2 a04 AUX.DC 24V+ output 3 c04 AUX.DC 24V+ output 4 a06 Isolated terminal, not wired c06 Isolated terminal, not wired c24 Isolated terminal, not wired a26 AUX. power input 1, DC - c26 AUX. power input 2, DC - a28 AUX. power input 3, DC - c28 AUX. power input 4, DC - a30 Isolated terminal, not wired c30 Isolated terminal, not wired a32 Terminal for earthing c32 Terminal for earthing a08 AUX.DC 24V- output 1 25

37 Chapter 3 Installing IED RS232 port RS232 serial port is located on front plate, the software tool in PC can be connected with the IED via this port to make setting, testing and cofiguration, etc. 3.2 Connecting to protective earth Connect the earthing screw on the rear panel to the nearest protective earthing point in the cubicle. The protective earth cables should be green or yellow conductors with cross-sectional area 2.5mm 2 according to electrical regulations and electrical standards requirement. The cubicle must be properly connected to station earthing system, using the conductor with cross-sectional area of at least 4mm Connecting the power supply module The wiring from the cubicle terminal block to the IED terminals must be connected in accordance with the established guidelines for this type of IED. The wires from binary inputs and outputs and the auxiliary power supply must be routed separated from the current transformer cables between the terminal blocks of the cubicle and the IEDs connections. 3.4 Connecting to CT and VT circuits CT and VT are connected to the analogue input module on the rear side of the IED. Using solid conductor with cross-sectional 2.5-6mm 2 (AWG14-10) or stranded conductor with cross-sectional 2.5-4mm 2 (AWG14-12). The screws used for fixation conductor should be tightened. 3.5 Connecting the binary inputs and outputs Auxiliary power supply and binary input and output signals are connected using female connectors. Signal wires are connected to a female connector, which is then plugged into the corresponding male connector, located at the 26

38 Chapter 3 Installing IED rear of the IED. Procedure: 1. Connect signals to the female connector All wiring to the female connector should be done before it is plugged into the male part and screwed to the case. The conductors can be of rigid type (solid, stranded) or of flexible type. The female connectors accept conductors with a cross section area of mm 2 (AWG 24-15). If two conductors are used in the same terminal, the maximum permissible cross section area is mm 2 (AWG 24-18, each conductor corresponding to one cross section area). If two conductors, each with area 1.5 mm 2 (AWG 15) need to be connected to the same terminal, a ferrule must be used to combine the two conductors, no soldering is needed. Press the locking button by screwdriver to insert the wiring with ferrule into the connector, move away the screwdriver after the ferrule has been inserted into the connector completely to lock the wiring tightly. The follow picture illustrate this process. Figure 12 Connection illustration without inserting the connector 27

39 Chapter 3 Installing IED Figure 13 Connection illustration with inserting the connector 2. Plug the connector to the corresponding back-side mounted male connector 3. Lock the connector by fastening the lock screws 3.6 Making the screen connection When using screened cables always make sure screens are earthed and connected according to applicable engineering methods. This may include checking for appropriate earth points near the IED, for instance, in the cubicle and/or near the source of measuring. Ensure that earth connections are made with short conductors of an adequate cross section, at least 6 mm 2 (AWG10) for single screen connections. 3.7 Optical connections This port is used to transmit the binary data between IEDs, there are two optical ports at the rear side of CPU moduel, Figure 9 and Figure 10, the two ports works in redundancy communication mode. 28

40 Chapter 3 Installing IED The fiber optical cables are very sensitive to handling. Do not bend too sharply. If cable straps are used to fix the cables, apply with loose fit. Always hold the connector, never the cable, when connecting or disconnecting optical fibers. Do not twist, pull or bend the fiber. Invisible damage may increase fiber attenuation thus making communication impossible. Strictly follow the instructions from manufacture for each type of optical cables or connectors. 3.8 RS485 and RS232 ports connection RS485 port connection The RS485 interface is capable of half-duplex service with the signals A/A' and B/B' to transmit signals. The network topology of RS485 adopts bus type of terminal matched, do not support ring or star network. Use the single and continuous channel as bus. The terminating resistance is located on beginning and terminal of the bus cable. The other ports do not need the terminating resistance. As shown in Figure 7 and Figure 8, RS485 port located on the rear side of communication module. The IED provides two electrical isolation RS485 ports, the two ports can work at the same time with IEC protocol supported RS232 port connection One RS232 serial port is provided and located on front plate, which is used to connect personal computer. The RS232 port adopts half-dupex communication mode, usually which is connected with 9-pin D-subminiature female connectors Connection method: direction connection cable for serial port, the IED terminal is pins and the PC termianl is female connector. The terminal of 2, 3, 4 and 5 is connected directly. As shown in the following picture: 29

41 Chapter 3 Installing IED Figure 14 Example for serial port connection The line 4 must be connected directly 3.9 Connecting the GPS Mount the GPS antenna on the building roof or the place of visibility to all direction is obtained, top of the antenna should be horizontal. Mount the antenna to console and fix the console on the building roof with expansion bolts. The turning radius should not be too small when laying the cables. The length of antenna cables is designed strictly based on antenna gain, so, it is not allowed to lengthen, shorten or add connectors that will affect signal reception or can't receive any signals. The principle for mounting GPS antenna is that the position is visible completely to all directions in 360, however, for some special conditions, mount the antenna at the place with best visibility as far as possible. The GPS port is located on the rear side of communication module, as shown in Figure 7 and Figure 8, which can be connected with screened twist-pair cable. 30

42 4 Checking before energizing 4.1 Introduction Chapter 3 Installing IED After completing the IED connections, the related connections need to be checked, this section descirbes what should be checked before energizing. This is done with IED and all connected circuits de-energized. 4.2 Checking the protective earth connection Check the protective earthing connection of IED is connected reliably in accordance with the related electrical regulations and standards. 4.3 Checking the power supply connection Check that the auxiliary power supply voltage remains within the permissible input voltage range under all operating conditions. Check that the polarity is correct. 4.4 Checking the CT and VT circuits connection Checking the CT circuits connection Check that the wiring is in strict accordance with the supplied connection diagram. If any errors appearance, do not continue before any errors are corrected. The following tests shall be performed on every primary CT connected to IED: Primary injection test to verify the current change ratio of the CT, the correct wiring up to the protection IED and correct phase sequence connection (i.e. A, B, C) Polarity checking to prove that the predicted direction of secondary current flow is correct for a given direction of primary current flow CT secondary loop resistance measurement in order to confirm that the current transformer secondary loop DC resistance is within specification and that there are no high resistance joints in the CT winding or wiring 31

43 Chapter 3 Installing IED CT excitation test in order to confirm that the current transformer is of the correct accuracy rating and that there are no shorted turns in the current transformer windings. Manufacturer's design curves should be available for the current transformer in order to compare the actual results Check the earthing of the individual CT secondary circuits to verify that each three-phase set of main CTs is properly connected to the station earth and only at one electrical point Checking the insulation resistance Phase identification of CT shall be made Both primary and secondary sides must be disconnected from the line and IED when plotting the excitation characteristics If the CT secondary circuit earth connection is removed without the current transformer primary being de-energized, dangerous voltages may result in the secondary CT circuits Checking the VT connection Check that the wiring is in strict accordance with the supplied connection diagram. If any errors appearance, do not continue before any errors are corrected. The following tests are recommended: Polarity check VT circuit voltage measurement (primary injection test) Grounding check Phase relationship Insulation resistance check 4.5 Checking the binary input and output connection Checking the binary input connection 32

44 Chapter 3 Installing IED When checking the binary inputs, it's better to disconnect the binary input connector from binary input module. Check all connected signals in order to make sure that both the input level and polarity of voltage are in accordance with the IEDs specifications Checking the binary output connection When checking the binary outputs, it's better to disconnect the binary output connector from binary output module. Check all connected signals in order to make sure that both the input level and polarity of voltage are in accordance with the IEDs specifications. 4.6 Checking the screened cables connection Check that the screened cables are connected correctly. 4.7 Checking the optical connections Check that the Tx and Rx optical connections are correct. 4.8 Checking the S485 and RS232 port connectios Checking the RS485 port connection Check that the RS485 port connections are correct Checking RS232 port connection Check that the RS232 serial port connections are correct. 4.9 Checking GPS connection Check that the GPS connections are correct Checking the insulation voltage and insulation resistance 33

45 Chapter 3 Installing IED Checking the insulation voltage Using the withstand voltage tester to apply correspondung level voltage between tested circuit and earth, and between circuits (e.g. 2000VAC /2800VDC), lasting 1 min. No flashover and breakdown apperance, the leakage current is less than 10mA Checking the insulation resistance Using a rotating meter with 500V to test insulation resistance in turn between analog circuits and earth, and the circuits to each other. Every resistance must not be less than 100 MΩ. And the lasting time for resistance test is not less than 5s to ensure that the value of insulation resistance is read in a steady state. 34

46 5 Checking after energizing 5.1 Introduction Chapter 3 Installing IED After completing of the external circuits connection, checking all connections and energizing the IED, LCD and keyboard should be tested. Check that the software version, serial number and the installed modules are in accordance with ordering information. The IED time need to be set to ensure that the IED time is synchronized with local time. The self-supervision function should also be checked to verify that the IED operates properly. 5.2 Test LCD After energizing the IED, the blue back light of LCD light up, operate the keys to turn pages to check that the LCD display is correct. 5.3 Test the keyboard All the keys on front plate including Arrow keys, Reset key, Set key, Quit key and shortcut key can be operated to check that these keys satisfy with the correpsonding function, the detail functions of each key are described in Table Setting the IED time This procedure describes how to set the IED time from the local HMI. 1. Enter into the time setting menu: Set Time, press the Set button to enter into the setting menu 2. Set the date and time Use the Left and Right arrow buttons to move between the time and date values (year, month, day, hours, minutes and seconds). Use the Up and Down arrow buttons to change the value. 3. Confirm the setting Press the Set button to set the data and clock to the new values. 35

47 Chapter 3 Installing IED 5.5 Self-supervision HMI data Table 10 Self-supervision HMI data Information Detail information Possible reason and solutions Communication fails between CPU and COM module. In this condition either the CPU is working abnormal or Communication Communication the CAN (Controller Area Network) network Fail Failure communication has been interruptted. Check each CPU working state or CAN network on backboard. Write Set Fail Write setting failure Write setting again Write DevPara Fail Write Device parameter failure Write device parameter again Maybe the address of two CPU modules are same, No response for calling CPU configuration one of the two modules is not inserted or connected badly Alarming code XX One of the CPU modules is disabled 5.6 Checking the software and hardware version Enter into menu: OpStatus/EquipCode Checking the software version: In this menu, to check the protection programm version. Check the hardware version: In this menu, to check the equipment code, the version of binary input and output module, communication module and HMI. 36

48 Chapter 4 Read and change setting Chapter 4 Read and change setting About this chapter This chapter describes how to set and read the setting values and parameters either through LHMI or software tool, and how to switch the setting value group. This chapter does not contain instructions on how to calculate the setting value, for the detail setting calculation information please refer to the Technical application manual. 37

49 Chapter 4 Read and change setting 1 Read and change the setting vaule 1.1 Read and change the setting value via LHMI Introduction All the function settings and binary settings can be read and set through LHMI. The user can browse to the desired settings and enter into the appropriate vaules, The parameters for each function can be found in the LHMI. See the Technical applciation manual for a complete list of setting parameters for each function Communication parameter Bay name Enter into menu: Settings/CommPara/BayName Check and change bay name Time synchronization mode SNTP mode Enter into menu: Settings/CommuPara/TimeMode/NetworkTimeMode The time synchronization mode can be changed into network time mode via this setting. PulseTimeMode Enter into menu: Settings/CommuPara/TimeMode/PulesTimeMode The time synchronization mode can be changed into pulse time mode via this setting. IRIG-BTimeMode Enter into menu: Settings/CommuPara/TimeMode/IRIG-BTimeMode 38 The time synchronization mode can be changed into IRIG-B time mode via

50 Chapter 4 Read and change setting this setting Communication address Enter into menu: Settings/CommuPara/CommAddr The address of Lon network, RS485 port, Ethernet port 1and Ethernet 2 can be modified in this setting baud rate Enter into menu: Settings/CommuPara/BaudR baud rate is displayed and modified here Equipment parameter Enter into menu: Settings/EquipPara In this menu, the following items are displayed and can be modified: sampling frequency for recording, rising or falling edge selection for each function. All the functions are enabled or disabled via 1 or 0, 1 means enable, 0 means disable. Left or right keys are used to select value for pre-recording time and the up and down keys are used to change value. Note: when the cursor move to this item, at the bottom of screen, displays the time limit for pre-recording time. Left or right keys are used to select value for post-recording time and the up and down keys are used to change value. Note: when the cursor move to this item, at the bottom of screen, displays the time limit for post-recording time Setting values and binary settings for protection function Introduction Protection setting 39

51 Chapter 4 Read and change setting The menu of protection setting is used to check and modify every function setting, using left and right button to chose the vaule and the up and down buttons are used to modify the value, the upper and lower limits of setting value will be displayed when the cursor move to corresponding setting items. Protection binary setting The protection binary settings are used to enable or disable each function, 1means enable and 0 means disable Common setting Transformer winding connection type Enter into menu: Settings/ProtSet/Pls Input SetGrNo/Common Para Check and set the connection type and vector group angle Rated apparent power of the transformer Enter into menu: Settings/ProtSet/Pls Input SetGrNo/Common Para Check and set the rated apparent power of the transformer Rated value of transformer voltage Enter into menu: Settings/ProtSet/Pls Input SetGrNo/Common Para Check and set the rated value of transformer voltage for each side VT Ratio Enter into menu: Settings/ProtSet/Pls Input SetGrNo/Common Para Check and set the VT ratio for each side Rated current value Enter into menu: Settings/ProtSet/Pls Input SetGrNo/Common Para Check and set the primary and secondary rated current value for each side 40

CSC-150 Busbar Protection IED Technical Application Manual

CSC-150 Busbar Protection IED Technical Application Manual CSC-150 Busbar Protection IED Technical Application Manual CSC-150 Busbar Protection IED Technical Application Manual Compiled: Jin Rui Checked: Hou Changsong Standardized: Li Lianchang Inspected: Cui

More information

Substation Automation Products. Generator protection REG670/650 Relion 670 and 650 series

Substation Automation Products. Generator protection REG670/650 Relion 670 and 650 series Substation Automation Products Generator protection REG670/650 Relion 670 and 650 series A new protection standard for your valuable assets Based on ABB s extensive experience, REG670 and REG650 IEDs (Intelligent

More information

CSC-150 Busbar Protection IED Technical Application Manual

CSC-150 Busbar Protection IED Technical Application Manual CSC-150 Busbar Protection IED Technical Application Manual CSC-150 母线保护装置 技术应用说明书 编制 : 校核 : 标准化审查 : 审定 : 版本号 :V1.02 文件代号 : 出版日期 :2015.9 Version:V1.02 Doc. Code: 0SF.450.087(E) Issued Date:2015.9 Copyright

More information

Relion 670 series. Busbar protection REB670 Installation and commissioning manual

Relion 670 series. Busbar protection REB670 Installation and commissioning manual Relion 670 series Busbar protection REB670 Document ID: 1MRK 505 180-UEN Issued: June 2010 Revision: C Product version: 1.1 Copyright 2010 ABB. All rights reserved Copyright This document and parts thereof

More information

7SR242 Duobias Multi-Function 2-Winding Transformer Protection Relay

7SR242 Duobias Multi-Function 2-Winding Transformer Protection Relay 7SR242 Duobias Multi-Function 2-Winding Transformer Protection Relay Document Release History This document is issue 2010/06. The list of revisions up to and including this issue is: 2010/06 Additional

More information

F1000 User's Manual. (Version: V1.01)

F1000 User's Manual. (Version: V1.01) (Version: V1.01) Contents Chapter 1 Overview... 2 Chapter 2 Installation... 3 2.1 Installation guide... 3 2.1.1 Installation position... 3 2.1.2 NEMA4 standard installation... 3 2.1.3 Environment precautions...

More information

Substation Automation Products. Line differential protection RED670 Relion 670 series

Substation Automation Products. Line differential protection RED670 Relion 670 series Substation Automation Products Line differential protection RED670 Relion 670 series For maximum reliability of your power system The RED670 IED (Intelligent Electronic Device) is designed for protection,

More information

1. Safety Precautions (Read these precautions before use.)

1. Safety Precautions (Read these precautions before use.) R P5102S/N/N1 HMI Installation Guide Thank you for purchasing FATEK HMI. Before installing or operating the unit, please read this installation guide carefully to ensure correct use. 1. Safety Precautions

More information

4 Channel 4~20mA/0~10VDC Analog Data Fiber Link System

4 Channel 4~20mA/0~10VDC Analog Data Fiber Link System USER GUIDE RLH Industries, Inc. The leader in rugged fiber optic technology. U-022 2017A-0330 4 Channel 4~20mA/0~10VDC Analog Data Fiber Link System SYSTEM INSTALLATION INFORMATION Description The 4 Channel

More information

Substation Automation Products. Line distance protection REL670/650 Relion 670 and 650 series

Substation Automation Products. Line distance protection REL670/650 Relion 670 and 650 series Substation Automation Products Line distance protection REL670/650 Relion 670 and 650 series For maximum reliability of your power system REL670 and REL650 line distance protection IEDs (Intelligent Electronic

More information

Substation Automation Products. High impedance differential busbar protection REB650 Relion 650 series

Substation Automation Products. High impedance differential busbar protection REB650 Relion 650 series Substation Automation Products High impedance differential busbar protection REB650 Relion 650 series One IED for a wide range of high impedance differential protection applications ABB introduces a new,

More information

7SR21 Non-Directional 7SR22 Directional Overcurrent Relay

7SR21 Non-Directional 7SR22 Directional Overcurrent Relay 7SR21 Non-Directional 7SR22 Directional Overcurrent Relay Document Release History This document is issue 2010/05. The list of revisions up to and including this issue is: 2010/05 Additional Comms module

More information

HITACHI. EH-150 series PLC EH-RTD8 Resistance Temperature Detective input module Instruction manual. Safety precautions

HITACHI. EH-150 series PLC EH-RTD8 Resistance Temperature Detective input module Instruction manual. Safety precautions HITACHI EH-150 series PLC Resistance Temperature Detective input module Instruction manual Thank you for purchasing a Hitachi Programmable Logic Controller. To operate it safely, please read this instruction

More information

Substation Automation Products. Transformer protection RET670/650 Relion 670 and 650 series

Substation Automation Products. Transformer protection RET670/650 Relion 670 and 650 series Substation Automation Products Transformer protection RET670/650 Relion 670 and 650 series For reliable protection and control of all types of power transformers and reactors The RET670/650 IEDs (Intelligent

More information

GCI-5K INSTALLATION AND OPERATOR S MANUAL

GCI-5K INSTALLATION AND OPERATOR S MANUAL GCI-5K INSTALLATION AND OPERATOR S MANUAL Grid-tied inverter for wind Ningbo Ginlong Technologies 1 INTRODUCTION 2 SAFETY GUIDELINES AND WARNINGS 3 INSTALLATION 3.1 Selecting a location for the inverter

More information

CSC-121 Breaker Protection IED Technical Application Manual

CSC-121 Breaker Protection IED Technical Application Manual CSC-121 Breaker Protection IED Technical Application Manual Version:V1.01 Doc. Code: 0SF.455.058 (E) Issued Date:2012.8 Copyright owner: Beijing Sifang Automation Co., Ltd Note: the company keeps the right

More information

CSC-150 Busbar Protection IED Product Guide

CSC-150 Busbar Protection IED Product Guide CSC-150 Busbar Protection IED Product Guide Version V1.0 Doc. Code: 0SF.492.056(E) Issued Date 201. Copyright owner: Beijing Sifang Automation Co., Ltd. Note: The company keeps the right to perfect the

More information

Substation Automation Products. Bay control REC670/650 Relion 670 and 650 series

Substation Automation Products. Bay control REC670/650 Relion 670 and 650 series Substation Automation Products Bay control REC670/650 Relion 670 and 650 series For optimized control and reliable operation of your switchyard The REC670 and REC650 Bay control IEDs (Intelligent Electronic

More information

Combined Overcurrent and Earth-fault Relay SPAJ 140 C. Product Guide

Combined Overcurrent and Earth-fault Relay SPAJ 140 C. Product Guide Combined Overcurrent and Earth-fault Product Guide Issued: April 1999 Status: Updated Version: C/18.04.2006 Data subject to change without notice Features Three-phase, low-set phase overcurrent unit with

More information

RTU560 Connections and Settings DIN Rail RTU 560CIG10

RTU560 Connections and Settings DIN Rail RTU 560CIG10 Connections and Settings DIN Rail RTU 560CIG10 Application, characteristics and technical data have to be taken from the hardware data sheet: 560CIG10 1KGT 150 719 Operation The 560CIG10 is a DIN rail

More information

EOS-6000 Series Optical A/B Switch User Manual DC Version

EOS-6000 Series Optical A/B Switch User Manual DC Version EOS-6000 Series Optical A/B Switch User Manual DC Version For more information on this and other products: Contact Sales at EMCORE 626-293-3400, or visit www.emcore.com. Table of Contents Table of Contents...2

More information

Installation Guide V290 (Color) This guide provides basic information for Unitronics LCD color touchscreen models V C30B and V T40B.

Installation Guide V290 (Color) This guide provides basic information for Unitronics LCD color touchscreen models V C30B and V T40B. Vision OPLC Installation Guide V290 (Color) This guide provides basic information for Unitronics LCD color touchscreen models V290-19-C30B and V290-19-T40B. General Description Vision OPLCs are programmable

More information

H Series PLC. ! : Indicates Compulsion. EH-150 Analog input module EH-AXH8M Instruction manual. Safety precautions DANGER CAUTION COMPULSION

H Series PLC. ! : Indicates Compulsion. EH-150 Analog input module EH-AXH8M Instruction manual. Safety precautions DANGER CAUTION COMPULSION H Series PLC EH-150 Analog input module EH-AXH8M Instruction manual Thank you for purchasing a Hitachi Programmable Logic Controller. To operate it safely, please read this instruction manual and all the

More information

3710 ACM 3750 PDC 3800 RTU. ISOCOM Communications Card Retrofit Instructions

3710 ACM 3750 PDC 3800 RTU. ISOCOM Communications Card Retrofit Instructions 3710 ACM 3750 PDC 3800 RTU ISOCOM Communications Card Retrofit Instructions Danger During normal operation of this device, hazardous voltages are present which can cause severe injury or death. These

More information

SEL-487B. A Powerful Solution for Busbar Differential Protection. Bus Differential and Breaker Failure Relay

SEL-487B. A Powerful Solution for Busbar Differential Protection. Bus Differential and Breaker Failure Relay Bus Differential and Breaker Failure Relay A Powerful Solution for Busbar Differential Protection Features and Benefits Select the for the differential protection of busbar systems with up to 18 terminals.

More information

Earth-fault Relay SPAJ 110 C. Product Guide

Earth-fault Relay SPAJ 110 C. Product Guide Issued: April 1999 Status: Updated Version: C/12.04.2006 Data subject to change without notice Features Low-set neutral overcurrent stage with definite time or inverse time characteristic High-set neutral

More information

DGSZV-EP DIGITAL GALVANIC LONGITUDINAL DIFFERENTIAL PROTECTION. Application field

DGSZV-EP DIGITAL GALVANIC LONGITUDINAL DIFFERENTIAL PROTECTION. Application field DGSZV-EP DIGITAL GALVANIC LONGITUDINAL DIFFERENTIAL PROTECTION The digital galvanic longitudinal differential protection of type DGSZV-EP is part of device family named EuroProt. This short description

More information

3700 SERIES USER MANUAL

3700 SERIES USER MANUAL SAFETY GUIDE This manual contains the precautions necessary to ensure your personal safety as well as for protection for the products and the connected equipment. These precautions are highlighted with

More information

X-618 Public Address and Voice

X-618 Public Address and Voice X-618 Public Address and Voice Alarm System Installation Manual M_XXXXXX_EN_1.0 Copyright 2012 Honeywell International Inc. All rights reserved. No part of this document may be reproduced in any form

More information

USP-070-B08 USP-104-B10, USP-104-M10 USP-156-B10

USP-070-B08 USP-104-B10, USP-104-M10 USP-156-B10 UniStream HMI Panel Installation Guide USP-070-B10, USP-070-B08 USP-104-B10, USP-104-M10 USP-156-B10 Unitronics UniStream platform comprises control devices that provide robust, flexible solutions for

More information

Serial Data DIN Fiber Link System

Serial Data DIN Fiber Link System USER GUIDE RLH Industries, Inc. The leader in rugged fiber optic technology. U-120 2017A-0420 DIN Fiber Link System COMPACT, RUGGED & TEMPERATURE HARDENED Introduction The DIN Fiber Link system transports

More information

VAMP 221. Table of Contents

VAMP 221. Table of Contents 2 V221/EN M/E019 VAMP 221 Table of Contents Table of Contents 1. General... 7 1.1. VAMP 221 arc protection system components... 7 1.1.1. Central unit VAMP 221... 9 1.1.2. I/O units VAM 12L / VAM 12 LD,

More information

SPA-ZC 200/SPA-ZC 202 IEC /SPA-gateway Modules. Installation Manual

SPA-ZC 200/SPA-ZC 202 IEC /SPA-gateway Modules. Installation Manual Issued: 29.03.2001 Version: A/29.03.2001 Checked: M.K. Approved: We reserve the right to change data without prior notice. Contents: 1. Safety information...4 2. Introduction...5 2.1. Contents of delivery...5

More information

CMU 100 RS485 to 7x, 6x, 5x, 4x Multimode Fiber Optic Star Coupler User Manual

CMU 100 RS485 to 7x, 6x, 5x, 4x Multimode Fiber Optic Star Coupler User Manual CMU 100 RS485 to 7x, 6x, 5x, 4x Multimode Fiber Optic Star Coupler User Manual CMU 100 / 2.5.6.6.6.6.6.6.6 12, CMU 100 / 8.5.6.6.6.6.6.6.6 12, CMU 100 / 2.5.6.6.6.6.6.6 12, CMU 100 / 8.5.6.6.6.6.6.6 12,

More information

MT8050iE series. Installation Instruction (1) (2)

MT8050iE series. Installation Instruction (1) (2) MT8050iE series 3 Installation Instructions Installation Instruction Secure the operator panel in position, using all the fastening holes and the provided brackets and screws: (A) 1 Installation and Startup

More information

1. Safety Precautions (Read these precautions before use.)

1. Safety Precautions (Read these precautions before use.) R P5043S/N HMI Installation Guide Thank you for purchasing FATEK HMI. Before installing or operating the unit, please read this installation guide carefully to ensure correct use. 1. Safety Precautions

More information

Combined Overcurrent and Earth-fault Relay SPAJ 141 C. Product Guide

Combined Overcurrent and Earth-fault Relay SPAJ 141 C. Product Guide Combined Overcurrent and Earth-fault Product Guide Issued: April 1999 Status: Updated Version: C/19.04.2006 Data subject to change without notice Features Three-phase, low-set phase overcurrent unit with

More information

See instructions to download and install the latest version of LinkBoxLON and the user's manual at

See instructions to download and install the latest version of LinkBoxLON and the user's manual at Safety Instructions WARNING Follow carefully this safety and installation instructions. Improper work may lead to serious harmful for your health and also may damage seriously the IntesisBox and/or any

More information

2 Table of Contents 1. TABLE OF CONTENTS. 1. Table of Contents Introduction Wiring Diagram Terminals Review...

2 Table of Contents 1. TABLE OF CONTENTS. 1. Table of Contents Introduction Wiring Diagram Terminals Review... TPR-6 Temperature Protection Relay Instruction Manual Ver. June 1 st 2010 2 Table of Contents 1. TABLE OF CONTENTS 1. Table of Contents... 2 2. Introduction... 3 3. Wiring Diagram... 5 4. Terminals Review...

More information

Sensitive Earth-fault Relay SPAJ 111 C. Product Guide

Sensitive Earth-fault Relay SPAJ 111 C. Product Guide Issued: April 1999 Status: Update Version: C/12.04.2006 Data subject to change without notice Features Sensitive low-set neutral overcurrent stage with definite time characteristic High-set neutral overcurrent

More information

Junos WebApp Secure 5.0 Hardware Guide

Junos WebApp Secure 5.0 Hardware Guide Junos WebApp Secure 5.0 Hardware Guide Junos WebApp Secure 5.0 Hardware Guide This document contains a specification for the MWS1000 hardware appliance, as well as instructions for installation into a

More information

SACE Emax 2 Specification guide

SACE Emax 2 Specification guide SACE Emax 2 Specification guide Specification Number: 26 01 20.17 Product Name: LOW VOLTAGE POWER CIRCUIT BREAKERS PART 1 GENERAL NOTE: ( ) Indicates option or a selection is to be made for quantity or

More information

Feeder protection relay SPAA 121 C. Product Guide

Feeder protection relay SPAA 121 C. Product Guide Issued: April 1999 Status: Updated Version: C/06.03.2006 Data subject to change without notice Features Two-phase low-set phase overcurrent unit with definite time or inverse time characteristic Two-phase

More information

Content REF615 Technical Presentation

Content REF615 Technical Presentation Distribution Automation Relion 615 series Feeder Protection and Control Ver. 2.0 Technical Presentation March 30, 2010 1MRS756407 E Slide 1 Content Technical Presentation highlights March 30, 2010 Slide

More information

Relion 615 series Feeder Protection and Control REF615 Ver. 2.0 Technical Presentation

Relion 615 series Feeder Protection and Control REF615 Ver. 2.0 Technical Presentation Relion 615 series Feeder Protection and Control REF615 Ver. 2.0 Technical Presentation Distribution Automation May 13, 2010 1MRS756407 E Slide 1 Content REF615 Technical Presentation highlights May 13,

More information

Models beginning with 2M, 2L or 2X. Product Description. Technical Specifications. Installation Instructions. Series 2000 Multiple Meter Units (MMUs)

Models beginning with 2M, 2L or 2X. Product Description. Technical Specifications. Installation Instructions. Series 2000 Multiple Meter Units (MMUs) Models beginning with 2M, 2L or 2X Series 2000 Multiple Meter Units (MMUs) Product Description Technical Specifications Installation Instructions February 28 th, 2013 List of Figures...2 List of Tables...2

More information

When any of the following symbols appear, read the associated information carefully. Symbol Meaning Description

When any of the following symbols appear, read the associated information carefully. Symbol Meaning Description Vision OPLC V130 COM Modules: V100-17-CAN, V100-17-RS4/X, V100-17-ET2 This guide shows you how to install an additional communication module in a V130 controller. Instructions and technical specifications

More information

NPI800 NPI800R. First Handling Guide. Phase and earth overcurrent relay

NPI800 NPI800R. First Handling Guide. Phase and earth overcurrent relay Phase and earth overcurrent relay FOREWORD The aim of this handbook is to provide to the User information useful for the commissioning and the tests of NPI800 and NPI800R relays, multifunction digital

More information

SOLARIMMERSION IV Advanced Installation Manual v1.9

SOLARIMMERSION IV Advanced Installation Manual v1.9 SOLARIMMERSION IV Advanced Installation Manual v1.9 1 Contents 1. Overview 2. Technical Specifications 3. Installation Mounting Electrical Installation Clamp Installation Wiring Diagrams 4. Installation

More information

Part No. Description Product Life Cycle Phase *) unit, 24 VDC, spring terminals. unit, 24 VDC, spring terminals, XC version

Part No. Description Product Life Cycle Phase *) unit, 24 VDC, spring terminals. unit, 24 VDC, spring terminals, XC version Ordering Data DATA SHEET TU520 Terminal Unit 1 Ordering Data Part No. Description Product Life Cycle Phase *) 1SAP 214 400 R0001 1SAP 414 400 R0001 TU520-ETH, PROFINET I/O terminal unit, 24 VDC, spring

More information

Monitoring technique. VARIMETER Voltage relay MK 9064N, MH 9064

Monitoring technique. VARIMETER Voltage relay MK 9064N, MH 9064 Monitoring technique VARIMETER Voltage relay MK 9064N, MH 9064 0269462 Your Advantages Preventive maintenance For better productivity Quicker fault locating Precise and reliable Min-, Max. value or window

More information

Energy Management System. Operation and Installation Manual

Energy Management System. Operation and Installation Manual Energy Management System Operation and Installation Manual AA Portable Power Corp 825 S 19 TH Street, Richmond, CA 94804 www.batteryspace.com Table of Contents 1 Introduction 3 2. Packing List 5 3. Specifications

More information

CURRENT PROTECTION RELAY SMPR-1

CURRENT PROTECTION RELAY SMPR-1 CURRENT PROTECTION RELAY SMPR-1 1.- ORION ITALIA SERIES MODBUS PROTOCOL. The ORION ITALIA SERIES implement a subset of the AEG Modicon Modbus serial communication standard. Many devices support this protocol

More information

DRS-LA413. Circuit Breaker Failure Relay. Operating Principle DRS-LA413. Operating Principle. Revision: 2 from Dwg.No.: DIL

DRS-LA413. Circuit Breaker Failure Relay. Operating Principle DRS-LA413. Operating Principle. Revision: 2 from Dwg.No.: DIL Circuit Breaker Failure Relay Operating Principle Revision: 2 from 2005-02-25 Edition: 2005-02-25 _CBF-description_eng.doc Page 1 /14 Table of Contents: 1 GENERAL DESCRIPTION 4 2 FUNCTIONAL DESCRIPTION

More information

INSTALLATION MANUAL. LC 200 Electronic Overload Guard. Software versione PW0501 R 0.3

INSTALLATION MANUAL. LC 200 Electronic Overload Guard. Software versione PW0501 R 0.3 INSTALLATION MANUAL LC 200 Electronic Overload Guard Software versione PW0501 R 0.3 CONTENTS MAIN FEATURES LC 200 TECHNICAL FEATURES Page 2 SYMBOLS Page 3 WARNINGS Page 3 IDENTIFICATION DATA PLATE Page

More information

Installation and commissioning manual REL 505-C1*2.3 Overcurrent protection terminal

Installation and commissioning manual REL 505-C1*2.3 Overcurrent protection terminal Installation and commissioning manual REL 505-C1*2.3 Overcurrent protection terminal About this manual DocID: 1MRK 506 094-UEN Issue date: June 2001 Status: New Version: 2.3 Revision: 00 ABB Automation

More information

This guide provides basic information for Unitronics Models 230/260/280/290 (Non-color Screens).

This guide provides basic information for Unitronics Models 230/260/280/290 (Non-color Screens). Vision OPLC Installation Guide Models 230/260/280/290 (Non-color Screens) This guide provides basic information for Unitronics Models 230/260/280/290 (Non-color Screens). General Description Vision OPLCs

More information

Analog Monitor Installation Manual

Analog Monitor Installation Manual Analog Monitor Installation Manual Part Number: 144-23919 Copyright 2011 Magnetek 1. Preface and Safety Magnetek manufactures products used as components in a wide variety of industrial systems and equipment.

More information

BS 287 DUAL CHANNEL POWER SUPPLY. User Manual. January 2017 V1.0

BS 287 DUAL CHANNEL POWER SUPPLY. User Manual. January 2017 V1.0 BS 287 DUAL CHANNEL POWER SUPPLY User Manual January 2017 V1.0 Table of contents 1.0 SAFETY INSTRUCTIONS... 3 2.0 GENERAL DESCRIPTION PS 289... 4 3.0 MECHANICAL INSTALLATION... 5 4.0 MAINS POWER & SAFETY

More information

When any of the following symbols appear, read the associated information carefully. Symbol Meaning Description

When any of the following symbols appear, read the associated information carefully. Symbol Meaning Description Uni-I/O Modules Installation Guide UIA-0402N Uni-I/O is a family of Input/Output modules that are compatible with the UniStream control platform. This guide provides basic installation information for

More information

See instructions to download and install the latest version of LinkBoxMB and the user's manual at

See instructions to download and install the latest version of LinkBoxMB and the user's manual at Safety Instructions WARNING Follow carefully this safety and installation instructions. Improper work may lead to serious harmful for your health and also may damage seriously the IntesisBox and/or any

More information

Vision OPLC. General Description. Standard Kit Contents. Installation Guide Vision120. This guide provides basic information for Unitronics Vision120.

Vision OPLC. General Description. Standard Kit Contents. Installation Guide Vision120. This guide provides basic information for Unitronics Vision120. Vision OPLC Installation Guide Vision120 This guide provides basic information for Unitronics Vision120. General Description V120 OPLCs are micro-oplcs, rugged programmable logic controllers that comprise

More information

SPECIAL INSTRUCTIONS FOR CAPACITORS COMPACT GENERATORS

SPECIAL INSTRUCTIONS FOR CAPACITORS COMPACT GENERATORS SPECIAL INSTRUCTIONS FOR CAPACITORS COMPACT GENERATORS (WITH CAPACITOR CHARGER BOARD A3517-02) The process depends on Generator and System configuration. This document applies to installation of Capacitors

More information

Quick Start Guide TS A

Quick Start Guide TS A Quick Start Guide TS 930 125-630A DANGER HAZARD OF ELECTRICAL SHOCK, EXPLOSION, OR ARC FLASH Read and understand this quick start guide before installing and operating the transfer switch The installer

More information

DIN Series MINIATURE CIRCUIT BREAKERS, RESIDUAL CURRENT CIRCUIT BREAKERS. Introducing the DIN Series High-quality, high-performance circuit breakers

DIN Series MINIATURE CIRCUIT BREAKERS, RESIDUAL CURRENT CIRCUIT BREAKERS. Introducing the DIN Series High-quality, high-performance circuit breakers DIN Series MINIATURE CIRCUIT BREAKERS, RESIDUAL CURRENT CIRCUIT BREAKERS Introducing the DIN Series High-quality, high-performance circuit breakers Features (1) All models fully comply with IEC regulations

More information

DGBV-EP DIGITAL GENERATOR AND GENERATOR-TRANSFORMER UNIT PROTECTION. Field of application

DGBV-EP DIGITAL GENERATOR AND GENERATOR-TRANSFORMER UNIT PROTECTION. Field of application DGBV-EP DIGITAL GENERATOR AND GENERATOR-TRANSFORMER UNIT PROTECTION Field of application The devices of the EuroProt complex protection family are modular devices. The modules are selected, assembled and

More information

Sensitive definite time or inverse time earth-fault stage for back-up residual earthfault

Sensitive definite time or inverse time earth-fault stage for back-up residual earthfault Issued: April 1999 Status: Updated Version: B/09.11.2001 Data subject to change without notice Features Sensitive restricted earth-fault protection stage for fast, selective earth-fault protection Sensitive

More information

IntesisBox Modbus Server KILSEN KSA-7xx. User s Manual 08/2013 r1.2 eng

IntesisBox Modbus Server KILSEN KSA-7xx. User s Manual 08/2013 r1.2 eng IntesisBox Modbus Server KILSEN KSA-7xx User s Manual 08/2013 r1.2 eng Intesis Software S.L. 2013 All rights reserved. Information in this document is subject to change without notice. The software described

More information

Installation Manual. Table of Contents

Installation Manual. Table of Contents Table of Contents Table of Contents... 4-1 4.1 Confirming the Installation Preparations... 4-1 4.2 Installation Flowchart... 4-1 4.3 Mounting the Switch to the Designated Position... 4-2 4.3.1 Mounting

More information

Analog Input Installation Manual

Analog Input Installation Manual Analog Input Installation Manual August 2011 Part Number: 144-23917 Copyright 2011 Magnetek 1. Preface and Safety Magnetek manufactures products used as components in a wide variety of industrial systems

More information

Model 7705 Control Module

Model 7705 Control Module www.keithley.com Model 7705 Control Module User s Guide PA-696 Rev. D / October 2006 A G R E A T E R M E A S U R E O F C O N F I D E N C E Safety Precautions The following safety precautions should be

More information

EL1142 Series. IEC / IEEE 1613 Hardened 2-Port 10/100BASE-TX to 2-Port 100BASE-FX Media Converter. User s Guide

EL1142 Series. IEC / IEEE 1613 Hardened 2-Port 10/100BASE-TX to 2-Port 100BASE-FX Media Converter. User s Guide EL1142 Series IEC 61850 / IEEE 1613 Hardened 2-Port 10/100BASE-TX to 2-Port 100BASE-FX Media Converter User s Guide All Rights Reserved Dissemination or reproduction of this document, or its contents,

More information

RPV-310 RPV-304. Multifunction Digital Fault Recorder. Instruction Manual

RPV-310 RPV-304. Multifunction Digital Fault Recorder. Instruction Manual RPV-310 RPV-304 Multifunction Digital Fault Recorder Instruction Manual Firmware code: 21vrr Document: rpv.fw21-manual-en-v01 Reason Tecnologia S.A. All rights reserved. Reason follows a policy of continuous

More information

Relion 615 series Transformer Protection and Control RET615 Ver. 2.0 Technical Presentation

Relion 615 series Transformer Protection and Control RET615 Ver. 2.0 Technical Presentation Relion 615 series Transformer Protection and Control RET615 Ver. 2.0 Technical Presentation Distribution Automation May 13, 2010 1MRS756901 A Slide 1 Content RET615 Technical Presentation highlights May

More information

RS-232 Industrial Media Converter

RS-232 Industrial Media Converter USER GUIDE The leader in rugged fiber optic technology. U-151 2018C-0327 Industrial Media Converter COMPACT, RUGGED & TEMPERATURE HARDENED Introduction This Industrial Serial Data media converter transports

More information

Residual overvoltage relay

Residual overvoltage relay Page 1 Issued: April 1999 Status: New Data subject to change without notice Features Definite-time residual overvoltage earthfault protection and supervision Two independent operation stages, e.g. one

More information

Resolver to Digital Expansion Board

Resolver to Digital Expansion Board Resolver to Digital Expansion Board Catalog No. EXB009A01 Installation and Operating Manual 6/98 MN1313 Table of Contents Section 1 General Information............................. 1-1 Introduction....................................

More information

CSC-211 Multifunction Protection IED Product Guide

CSC-211 Multifunction Protection IED Product Guide CSC-211 Multifunction Protection IED Product Guide Version V1.0 Doc. Code: 0SF.492.057(E) Issued Date 201. Copyright owner: Beijing Sifang Automation Co., Ltd. Note: The company keeps the right to perfect

More information

AX3000 Platine Terminal Ethernet TCP/IP

AX3000 Platine Terminal Ethernet TCP/IP AX3000 Platine Terminal Ethernet TCP/IP Model 60 Installation Guide September 00 - Ref: I60IE010-1 Model AX3000/M60 The reproduction of this material, in part or whole, is strictly prohibited. For additional

More information

Compressor Controller MAM 890

Compressor Controller MAM 890 Compressor Controller MAM 890 OPERATION MANUAL Revision 1.0 04.08.2017 Notice Please read all the operation manual before operating the set and keep this manual for further reference. Installation of MAM

More information

When any of the following symbols appear, read the associated information carefully. Symbol Meaning Description

When any of the following symbols appear, read the associated information carefully. Symbol Meaning Description Uni-I/O Modules Installation Guide UID-0808THS Uni-I/O is a family of Input/Output modules that are compatible with the UniStream control platform. This guide provides basic installation information for

More information

Installation Guide V290 (Color) This guide provides basic information for Unitronics LCD color touchscreen models V C30B and V T40B.

Installation Guide V290 (Color) This guide provides basic information for Unitronics LCD color touchscreen models V C30B and V T40B. Vision OPLC Installation Guide V290 (Color) This guide provides basic information for Unitronics LCD color touchscreen models V290-19-C30B and V290-19-T40B. General Description Vision OPLCs are programmable

More information

H704-42(H)(E), H704-42/1(H)(E)

H704-42(H)(E), H704-42/1(H)(E) POWER MONITORING INSTALLATION GUIDE H704-42(H)(E), H704-42/1(H)(E) Branch Current Monitor DANGER NOTICE Installer's Specifications General: Operating Temp. Range 0 to 60 C (32 to 140 F) (

More information

Preparing to Install the Cisco AS5350XM Universal Gateway

Preparing to Install the Cisco AS5350XM Universal Gateway CHAPTER 2 Preparing to Install the Cisco AS5350XM Universal Gateway This chapter describes the tasks you must perform before you begin to install the Cisco AS5350XM universal gateway and includes the following

More information

MYRIAD QLC 4-CHANNEL MONITOR/CONTROLLER INSTRUCTION MANUAL

MYRIAD QLC 4-CHANNEL MONITOR/CONTROLLER INSTRUCTION MANUAL MYRIAD QLC 4-CHANNEL MONITOR/CONTROLLER INSTRUCTION MANUAL VISIT OUR WEBSITE SIGMACONTROLS.COM MYR QLC MANUAL 013114 2 TABLE OF CONTENTS INTRODUCTION 3 Ordering Information Specifications Features WIRING

More information

Industrial Ethernet Optical Fiber Link Adapter FIB-IE-S User Manual

Industrial Ethernet Optical Fiber Link Adapter FIB-IE-S User Manual http://www.fourstar-dy.com Industrial Ethernet Optical Fiber Link Adapter FIB-IE-S User Manual FOURSTAR Electronic Technology Co., Ltd. All rights reserved Contents Preface.... 3 Copyright....3 Version

More information

GRID-TIED SOLAR INVERTER 1.5KW ~ 6.0KW V.1.2

GRID-TIED SOLAR INVERTER 1.5KW ~ 6.0KW V.1.2 USER MANUAL MPI-1500/2000/3000/4000/6000 Series GRID-TIED SOLAR INVERTER 1.5KW ~ 6.0KW V.1.2 WWW.MPPSOLAR.COM WARNING: ONLY A CERTIFIED ELECTRICIAN OR TRAINED ASSEMBLING PROFESSIONAL SHOULD OPEN OR INSTALL

More information

DTS 310. DIN Rail Mounted, Indoor Rated Revenue Grade Electrical Sub-meter. Page 1. Measurlogic MQ A

DTS 310. DIN Rail Mounted, Indoor Rated Revenue Grade Electrical Sub-meter. Page 1. Measurlogic MQ A DTS 310 DIN Rail Mounted, Indoor Rated Revenue Grade Electrical Sub-meter Page 1 1 PRODUCT OVERVIEW... 3 1.1 SUPPLIED ITEMS... 3 1.2 DOCUMENT CONVENTIONS... 4 1.3 PRODUCT SPECIFICATION... 4 1.3.1 Current

More information

Allen-Bradley. User Manual. PLC-5 Backup Communication Module (1785-BCM, 1785-BEM) product icon

Allen-Bradley. User Manual. PLC-5 Backup Communication Module (1785-BCM, 1785-BEM) product icon Allen-Bradley PLC-5 Backup Communication Module User Manual (1785-BCM, 1785-BEM) product icon Important User Information Because of the variety of uses for this product and because of the differences between

More information

TABLE OF CONTENTS TABLE OF CONTENTS... 1 IMPORTANT SAFETY NOTICE...

TABLE OF CONTENTS TABLE OF CONTENTS... 1 IMPORTANT SAFETY NOTICE... TABLE OF CONTENTS TABLE OF CONTENTS... 1 IMPORTANT SAFETY NOTICE... 2 1.0 General Information... 3 1.1 System Components... 3 1.2 Specifications... 3 1.2.1 Torque Ranges... 3 1.2.2 Electrical Specifications...

More information

Relion 650 series. 650 series 2.1 IEC Installation manual

Relion 650 series. 650 series 2.1 IEC Installation manual Relion 650 series 650 series 2.1 IEC Document ID: 1MRK 514 025-UEN Issued: January 2016 Revision: - Product version: 2.1 Copyright 2016 ABB. All rights reserved Copyright This document and parts thereof

More information

MIC-2 MKII, Multi-instrument DATA SHEET

MIC-2 MKII, Multi-instrument DATA SHEET MIC-2 MKII, Multi-instrument DATA SHEET Measurements All 3-phase AC measurements True RMS 4-Quadrant energy Power Quality Analysis Replaces analogue meters RS-485 Modbus RTU protocol TCP/IP Modbus (optional)

More information

Installing the Cisco MDS 9020 Fabric Switch

Installing the Cisco MDS 9020 Fabric Switch CHAPTER 2 This chapter describes how to install the Cisco MDS 9020 Fabric Switch and its components, and it includes the following information: Pre-Installation, page 2-2 Installing the Switch in a Cabinet

More information

DRTS 33. The new generation of advanced test equipments for Relays, Energy meters, Transducers and Power quality meters

DRTS 33. The new generation of advanced test equipments for Relays, Energy meters, Transducers and Power quality meters The new generation of advanced test equipments for Relays, Energy meters, Transducers and Power quality meters Testing all relay technologies: electromechanical, solid state, numerical and IEC61850 Manual

More information

See instructions to download and install the latest version of LinkBoxEIB and the user's manual at

See instructions to download and install the latest version of LinkBoxEIB and the user's manual at Safety Instructions WARNING Follow carefully this safety and installation instructions. Improper work may lead to serious harmful for your health and also may damage seriously the IntesisBox and/or any

More information

Huawei Solar Product Training HUAWEI TECHNOLOGIES CO., LTD.

Huawei Solar Product Training HUAWEI TECHNOLOGIES CO., LTD. Huawei Solar Product Training HUAWEI TECHNOLOGIES CO., LTD. Contents Overview of the Product Range Huawei Solar Inverter Technical Information Huawei Smartlogger Technical Information NetECO Portal Brief

More information

TF501, TF521 Terminal Bases

TF501, TF521 Terminal Bases Ordering Data DATA SHEET TF501, TF521 Terminal Bases 1 Ordering Data Part No. Scope of delivery Product life cycle status 1SAP 117 000 R0271 1SAP 317 000 R0271 1SAP 117 200 R0271 1SAP 317 200 R0271 TF501-CMS,

More information

DESIGO RX Individual room controllers. for fan-coil systems, chilled ceilings and radiators, with LONMARK-compatible bus communications

DESIGO RX Individual room controllers. for fan-coil systems, chilled ceilings and radiators, with LONMARK-compatible bus communications 3 834 DESIO RX Individual room controllers for fan-coil systems, chilled ceilings and radiators, with MARK-compatible bus communications RXC20.1 RXC21.1 The RXC20.1 and RXC21.1 controllers are used for

More information

DRTS 33. The new generation of advanced three phase relay test set

DRTS 33. The new generation of advanced three phase relay test set The new generation of advanced three phase relay test set Testing all relay technologies: electromechanical, solid state, numerical and IEC61850 Local control with color display Simultaneously available:

More information

MCCB-250 MOLDED-CASE CIRCUIT BREAKER TESTER

MCCB-250 MOLDED-CASE CIRCUIT BREAKER TESTER MCCB-250 MOLDED-CASE CIRCUIT BREAKER TESTER USER S MANUAL Vanguard Instruments Company, Inc. 1520 S. Hellman Ave. Ontario, California 91761, USA TEL: (909) 923-9390 FAX: (909) 923-9391 January 2015 Revision

More information