1 Actuator controls AUMATIC ACExC 01.2 Modbus RTU To be used in combination with the operation instructions only! The present short instructions do NOT replace the operation instructions! They are only intended for persons already familiar with the operation instructions where safety instructions, assembly, operation and commissioning are already described in detail! The operation instructions must always be available. Short instructions FO connection

2 Table of contents Table of contents 1. Short description FO connection Basic information 2.2. Terminal compartment: open 2.3. FO cables: connect 2.4. Terminal compartment: close 3. Network topologies Line topology 3.2. Star topology 4. Corrective action LED indications 4.2. Troubleshooting Line and star topology 5. Technical data FO coupler 6. Appendix Calculation of achievable FO range 6.2. Measuring methods 6.3. Reference addresses 6.4. Literature Page

3 Short description 1. Short description AUMA actuator controls with FO connection are intended for use in optical fieldbus networks. The FO connection integrated in the electrical connection enables the conversion from electrical RS-485 signals into optical signals and vice versa. FO connection behaviour is transparent at the bus, i.e. control of AUMA actuators via bus is identical to control via copper cables (RS-485). Contrary to RS-485 based systems, different topologies are possible: Line topology Star topology Apart from the large distances, FO cables offer further advantages: In environments with electromagnetic interference Lightning arrester or overvoltage protection Equipotential earth bonding and earthing Galvanic separation of the actuator Use of common cable trenches for power and signal cables Prevention of interference emissions along the transmission line This allows for customised solutions and various applications such as water/waste water industries, tunnelling, power plants, thermal industry or telecontrol engineering. 3

4 FO connection 2. FO connection 2.1 Basic information Hazardous voltage! Risk of electric shock. Failure to observe this warning can result in death or serious injury. The connection must be carried out exclusively by suitably qualified personnel. Prior to opening: Disconnect both system and device from the mains. Observe basic information contained in this chapter. Observe safety instructions contained in the operation instructions pertaining to the actuator. Eye damage caused by open fibre optic cable ends! NEVER look directly into open cable ends or FO cable connections. Connection or receive problems when ignoring the installation instructions! Only use FO cable connection (connector types) with the wiring techniques indicated in these instructions. Only mount connector types with locking mechanisms in the defined position. Protect unused FO cable connections against contamination or dust with protective caps/plugs supplied by the factory. Connect incoming FO cable with the optical receiver, the outgoing FO cable with the optical sender. NOT vice versa! Do NOT kink FO cables! Observe bending radius of cable manufacturer. Cable and wire types Table 1: Cables and wires according todin VDE 0888 part 3: Core diameter Fibre Range Damping coefficient 62.5 µm or 50 µm 62.5/125 µm Multi-mode graded-index fibre 50/125 µm glass fibre 62.5/125 µm: 2,600 m 50/125 µm: 1,400 m Recommendation: < 3.0 db/km Remove outer sheathing of FO cable at a length of approx. 25 cm to enable ring wiring in the terminal compartment. Figure 1: Plug type FSMA Controls mounted to wall bracket In the event of heavy vibration of the valve, we recommend mounting the actuator controls separately from the actuator on a wall bracket. For information about the wall bracket, refer to operation instructions for the actuator. 4

5 FO connection 2.2 Terminal compartment: open Figure 2: Plug/socket connector: left KES, right KES flameproof [1] Cover [2] Screws for cover [3] O-ring [4] Terminal compartment: Type of protection Ex e [5] Terminal compartment: Type of protection Ex d [6] Frame Hazardous voltage! Risk of electric shock. Disconnect device from the mains before opening. 1. Loosen screws [2] and remove cover [1]. Terminal compartments [4] and [5] are designed either in type of protection Ex e (increased safety) or in type of protection Ex d (flameproof enclosure).hereby, the flameproof interior compartment of the actuator (Ex d) remains closed. 2. Insert cable glands with Ex e approval and suitable for connection cables. The enclosure protection IP stated on the name plate is only ensured if suitable cable glands are used. Example: Name plate shows enclosure protection IP Seal cable entries unused cable entries with approved plugs suitable for the required protection type. 4. Remove cable sheathing and insert the wires into the cable glands. 5. Fasten cable glands with the specified torque to ensure required enclosure protection. 5

6 FO connection 2.3 FO cables: connect 1. Remove safety circlip and take FO coupler off top head rail. Figure 3: FO coupler on top head rail 2. Place FO coupler on fixing plate in "parking position" Figure 4: FO coupler in "parking position" 3. Insert FO cables through cable glands. 4. Link FO connectors crosswise: Optical output of actuator 1 with optical input of actuator 2. Optical input of actuator 1 with optical output of actuator 2. Figure 5: Connection example 6

7 FO connection 2.4 Terminal compartment: close Figure 6: Plug/socket connector: left KES, right KES flameproof [1] Cover [2] Screws for cover [3] O-ring [4] Terminal compartment: Type of protection Ex e [5] Terminal compartment: Type of protection Ex d [6] Frame 1. Clean sealing faces of cover [1] and housing. 2. Plug/socket connector designed as KES flameproof: Preserve joint surfaces with an acid-free corrosion protection agent. 3. Check whether O-ring [3] is in good condition, replace if damaged. 4. Apply a thin film of non-acidic grease (e.g. petroleum jelly) to the O-ring and insert it correctly. Flameproof enclosure, danger of explosion! Risk of death or serious injury. Handle cover and housing parts with care. Joint surfaces must not be damaged or soiled in any way. Do not jam cover during fitting. 5. Fit cover [1] and fasten screws [2] evenly crosswise. 7

8 Network topologies 3. Network topologies 3.1 Line topology When connecting several field devices (actuators) in a network, the structure is called network topology. AUMA offers different network topologies. Figure 7: Structure for line topology Max. FO cable range in km (observe technical data!) [1] FO T-coupler within electrical connection of ACExC 01.2 [2] FO PP-coupler within DCS (imperatively required) [3] FO PP-coupler for any Modbus RTU field device [4] Any Modbus RTU field device Table 2: Number of FO devices (actuators) to be connected in series Baud rate [kbit/s] Maximum number of FO devices Special features of line topology The optical signal is converted into an electrical signal at each device. Prior to transmission to the next device, the electrical signal is converted into an optical signal. Interruption of an FO cable (case A) or failure of an FO connection board (case B) results in loss of control for the subsequent actuators: Case A (standard) Case B (option) As soon as the electrical connection is removed from the ACExC 01.2, FO connection of this actuator is no longer available. As a consequence, communication with the subsequent actuators is lost. To prevent this, FO connection used in the ACExC 01.2 can also be externally supplied with 24 V DC. As soon as the actuator is switched off (motor voltage), the FO connection board of this actuator is no longer available. As a consequence, communication with the 8

9 Network topologies subsequent actuators is lost. To prevent this, the complete ACExC 01.2 can be externally supplied with 24 V DC. 3.2 Star topology Figure 8: Structure for star topology Max. FO cable range in km (observe technical data!) [1] FO PP-coupler within electrical connection of ACExC 01.2 [2] LWL Stich-Koppler in der Leittechnik (zwingend erforderlich) [3] LWL Stich-Koppler für Beliebiges Modbus RTU Feldgerät [4] Any Modbus RTU field device Table 3: Number of FO devices (actuators) to be connected in series Baud rate [kbit/s] Maximum number of FO devices Special features of star topology Failure of an FO cable section or of an actuator's FO connection board has no impact on the operability of the remaining actuators. 9

10 Corrective action 4. Corrective action 4.1 LED indications Figure 9: LEDs on FO coupler [BA] [U] L Bus active (yellow) Operation (green) Table 4: Summary of functions LED Colour BA U L yellow green Function LED flackert: Data from RS485 channel are transmitted via the optical interface. LED is illuminated: Power supply (24 V DC) for FO coupler is available Internal operating voltage (5 V) is available. 4.2 Troubleshooting Line and star topology LEDs on the FO couplers provide important information for troubleshooting. The following tables of this chapter provide basic steps for troubleshooting and elimination via these LEDs. Furthermore, different fieldbus interface states can be requested via the ACExC 01.2 display (Menu Diagnostic M0022). For further information, please refer to Manual (Device integration fieldbus) AC 01.2/ACExC Table 5: Troubleshooting table 1 2 Can actuator be controlled via fieldbus? Green LED [U L ] illuminated? Yes No Yes No Causes and remedies Continue with 4 Continue with 2 FO coupler supplied with voltage (24 V DC). Continue with 4 Continue with 3 10

11 Corrective action 3. 4 Verify power supply (24 V DC) of the FO coupler: Is yellow LED [BA] flickering? Power supply (24 V DC) available? Power supply (24 V DC) not available? Yes Causes and remedies Possible causes and remedies: FO coupler is defective Replace coupler. Remedies: Check fuses within ACExC Restore power supply. Possible causes: Sender on coupler defective FO connection of sender not operable No Possible causes: Slave not properly connected Slave defective Master defective FO coupler receiver or FO connection of receiver defective Is the required FO coupler (BARTEC order no.: WP/6000 or /4000) installed at the master? 11

12 Technical data 5. Technical data Information The following technical data includes standard and optional features. For detailed information on the customer-specific version, refer to the order-relevant data sheet. This data sheet can be downloaded from the Internet at in German and English (indication of commission number required). 5.1 FO coupler Explosion protection (in accordance with EN to EN 50020) Ex de [ib] IIC EC type examination certificates Mounting: TÜV 99 ATEX 1404 Coupler: PTB 97 ATEX 1068 U X FO connection Channels (optical) Data rate Transmission type Fibre Optical budget Network range max. Wave length Operation temperature Power supply Indications (LEDs) FSMA FO plug/socket connector For line topology: 1 x IN/OUT or 2 x IN/OUT For star topology: 1 x IN/OUT Maximum kbit/s Half-duplex Multi-mode, 62.5 (50)/125 µm 8 db at 62.5 µm 4 db at 50 µm fibre 62.5 µm glass fibre: 2,600 m (FO cable damping max. 3.0 db/km, without additional damping) 50 µm glass fibre: 1,400 m (FO cable damping max. 3.0 db/km, without additional damping) 850 nm 25 C to +60 C 24 V DC/75 ma, internally supplied via power supply unit of ACExC For line and star topology: External power supply of the ACExC 01.2 with 24 V DC/500 ma possible. Only when the ACExC 01.2 is operated on external voltage supply will the bus remain uninterrupted in case of a loss of operating voltage. LED UL (green) = device ready for operation (power supply available) LED BA (yellow) = bus active: Data is received via the RS485 channel. Suitable bus systems Required FO modules for the master Modbus RTU Bartec, to be purchased from AUMA or FO coupler for line or star topology - 1 channel FO PP coupler (BARTEC order no.: WP/6000) (AUMA order no.: K ) - 2 channel FO T coupler (BARTEC order no.: WP/4000) (AUMA order no.: K ) Maximum number of FO actuators coupler at the master (at 57.4 kbit/s) 12

13 Appendix 6. Appendix 6.1 Calculation of achievable FO range L max P a K Anz K a L Maximum achievable cable length of FO cable/wire[km] Optical budget [db] (connectible power). Damping of the couplings [db]. Typical values for FST = db, for FSMA = db. Additional number of FO couplings within the FO cable between two actuators (excluding FO couplings at electrical connection of AUMA actuators; damping of these actuators is already included in the optical budget). Specific cable damping [db/km], refer to technical data of the FO cable. Example 1 Standard set-up, i.e. no additional couplings: P = 8 db; Anz K = 0; a K = 0.6 db; a L = 3.0 db/km L max = 2,600 m Example 2 Two couplings within the cable: P = 8 db; Anz K = 2; a K = 0,6 db; a L = 3,0 db/km L max = 2,200 m Figure 10: Example: Two couplings within the cable [1] 1 st FSMA a K coupling = 0.6 db [2] 2 nd FSMA a K coupling = 0.6 db 13

14 Appendix 6.2 Measuring methods Figure 11: Damping measurement 6.3 Reference addresses 6.4 Literature Required FO module for the master: BARTEC Top Holding GmbH Max-Eyth-Straße 16 D Bad Mergentheim Germany Tel.: Fax: FO cables and wires: Network reliability despite multiple points of failure eks Engel GmbH & Co. KG Schützenstr. 2, Wenden-Hillmicke, Tel.: , Christoph P. Wrobel Optische Übertragungstechnik in der Praxis Grundlagen, Komponenten, Installation, Anwendungen Hüthig Verlag ISBN

15 Appendix 15

16 AUMA Riester GmbH & Co. KG P.O.Box 1362 D Muellheim Tel Fax riester@auma.com Y /003/en/1.13 For detailed information on AUMA products refer to the Internet:

Operating Instructions (Translation) 3. Safety Information. 1. Description. 2. Explosion Protection. Supply module Type 17-21BB-170x

Operating Instructions (Translation) 3. Safety Information. 1. Description. 2. Explosion Protection. Supply module Type 17-21BB-170x 1. Description The supply module was developed specially for direct mounting in hazardous areas in Zone 1 and 21 and is ATEX-certified. The supply module is a permanently installed piece of electrical

More information

CMU 100 RS232 to Singlemode Fiber Optic Converter User Manual

CMU 100 RS232 to Singlemode Fiber Optic Converter User Manual CMU 100 RS232 to Singlemode Fiber Optic Converter User Manual CMU 100 / 1.1.S - 0 CMU 100 / 7.1.S - 0 Company: Device: Document: Code: Version: Date: Ediseja 21 CMU 100 / 1.1.S - 0 User manual CMUMU11S

More information

CMU 100 Multimode Fiber Optic to Singlemode Fiber Optic Converter User Manual

CMU 100 Multimode Fiber Optic to Singlemode Fiber Optic Converter User Manual CMU 100 Multimode Fiber Optic to Singlemode Fiber Optic Converter User Manual CMU 100 / 1.6.S - 0 CMU 100 / 7.6.S - 0 Company: Device: Document: Code: Version: Date: Ediseja 21 CMU 100 / 1.6.S - 0 User

More information

Part-turn actuators SGExC 05.1 SGExC 12.1 Control unit: electronic (MWG) with actuator controls AUMATIC ACExC 01.1 Non-Intrusive

Part-turn actuators SGExC 05.1 SGExC 12.1 Control unit: electronic (MWG) with actuator controls AUMATIC ACExC 01.1 Non-Intrusive Part-turn actuators SGExC 05.1 SGExC 12.1 Control unit: electronic (MWG) with actuator controls AUMATIC ACExC 01.1 Non-Intrusive Control Parallel Profibus DP Modbus DeviceNet Foundation Fieldbus Operation

More information

CMU 100 RS485 to 7x, 6x, 5x, 4x Multimode Fiber Optic Star Coupler User Manual

CMU 100 RS485 to 7x, 6x, 5x, 4x Multimode Fiber Optic Star Coupler User Manual CMU 100 RS485 to 7x, 6x, 5x, 4x Multimode Fiber Optic Star Coupler User Manual CMU 100 / 2.5.6.6.6.6.6.6.6 12, CMU 100 / 8.5.6.6.6.6.6.6.6 12, CMU 100 / 2.5.6.6.6.6.6.6 12, CMU 100 / 8.5.6.6.6.6.6.6 12,

More information

ACExC 01.2 Modbus TCP/IP

ACExC 01.2 Modbus TCP/IP General information ACExC 01.2 actuator controls for controlling multi-turn actuators of the SAEx/SAREx.2 type range and part-turn actuators of the SQEx/SQREx.2 type range with interface. Features and

More information

ELECTRIC ACTUATORS Innovations for SGC part-turn actuators and SVC valve actuators

ELECTRIC ACTUATORS Innovations for SGC part-turn actuators and SVC valve actuators ELECTRIC ACTUATORS Innovations for SGC part-turn actuators and SVC valve actuators SGC PART-TURN ACTUATORS 2 SVC GLOBE VALVE ACTUATORS 3 NEWS ON COMPACT ACTUATORS 3 SVC globe valve actuators with enhanced

More information

PHOENIX CONTACT Pin. SUBCON-PLUS M ARCNET, MULTI/MININET (B&R), SYSTEM 2003 (B&R), P-NET SUCONET K1, K2 (EATON/Moeller),

PHOENIX CONTACT Pin. SUBCON-PLUS M ARCNET, MULTI/MININET (B&R), SYSTEM 2003 (B&R), P-NET SUCONET K1, K2 (EATON/Moeller), Fast connector with screw terminal block connection for fieldbus systems Data sheet 00287_en_02 PHOENIX CONTACT 207-04-2 Description The SUBCON-PLUS/... D-SUB series is specifically designed for use in

More information

CMU 100 RS485 to Ethernet Converter User Manual CMU 100 / CMU 100 / 1.M.9 CMU 100 / 1.L.9 CMU 100 / CMU 100 / 7.M.9 CMU 100 / 7.L.

CMU 100 RS485 to Ethernet Converter User Manual CMU 100 / CMU 100 / 1.M.9 CMU 100 / 1.L.9 CMU 100 / CMU 100 / 7.M.9 CMU 100 / 7.L. CMU 100 RS485 to Ethernet Converter User Manual CMU 100 / 1.5.9 CMU 100 / 1.M.9 CMU 100 / 1.L.9 CMU 100 / 7.5.9 CMU 100 / 7.M.9 CMU 100 / 7.L.9-0 0 0 0 0 0 CMU 100 - RS485 to Ethernet Converter Content

More information

FL MC 2000T. Fiber optic converter for 10/100Base-Tx to single- or multi-mode fiberglass with SC-duplex and ST connections. Data sheet 3379_en_B

FL MC 2000T. Fiber optic converter for 10/100Base-Tx to single- or multi-mode fiberglass with SC-duplex and ST connections. Data sheet 3379_en_B Fiber optic converter for 10/100Base-Tx to single- or multi-mode fiberglass with SC-duplex and ST connections Data sheet 3379_en_B 1 Description PHOENIX CONTACT 2015-07-14 2 Features Media converters provide

More information

Part-turn actuators SQ 05.2 SQ 14.2/SQR 05.2 SQR 14.2 Control unit: electronic (MWG) with actuator controls AUMATIC AC 01.

Part-turn actuators SQ 05.2 SQ 14.2/SQR 05.2 SQR 14.2 Control unit: electronic (MWG) with actuator controls AUMATIC AC 01. Part-turn actuators SQ 05.2 SQ 14.2/SQR 05.2 SQR 14.2 Control unit: electronic (MWG) with actuator controls AUMATIC AC 01.2 Non-Intrusive Control Parallel Profibus DP Modbus Foundation Fieldbus Operation

More information

Part-turn actuators SQ 05.2 SQ 14.2/SQR 05.2 SQR 14.2 Control unit: electromechanic with actuator controls AUMATIC AC 01.

Part-turn actuators SQ 05.2 SQ 14.2/SQR 05.2 SQR 14.2 Control unit: electromechanic with actuator controls AUMATIC AC 01. Part-turn actuators SQ 05.2 SQ 14.2/SQR 05.2 SQR 14.2 Control unit: electromechanic with actuator controls AUMATIC AC 01.2 Intrusive Control Parallel Profibus DP Modbus Foundation Fieldbus Operation instructions

More information

MANUAL Surge Protectors

MANUAL Surge Protectors PROCESS AUTOMATION MANUAL Surge Protectors DP-LBF-I1.36.DE and DP-LBF- I1.36.IE With regard to the supply of products, the current issue of the following document is applicable: The General Terms of Delivery

More information

PHOENIX CONTACT - 10/2009

PHOENIX CONTACT - 10/2009 Factory Line Switches With Standard Functions AUTOMATIONWORX Data Sheet PHOENIX CONTACT - 10/2009 Description The range of Factory Line switches with standard functions in numerous versions can be used

More information

MU110-6U. Analog output module 6 channel. User guide

MU110-6U. Analog output module 6 channel. User guide MU110-6U Analog output module 6 channel User guide MU110-6U_2016.12_0221_EN All rights reserved Subject to technical changes and misprints akytec GmbH Vahrenwalder Str. 269 A 30179 Hannover Тел.: +49 (0)

More information

PTB 01 ATEX 2064 U, IECEx PTB U. Example / Beispiel / Exemple: Type Operating Instructions

PTB 01 ATEX 2064 U, IECEx PTB U. Example / Beispiel / Exemple: Type Operating Instructions , Equipment protection fuse with Ex mb II C Gb approval Geräteschutzsicherung mit Zulassung Ex mb II C Gb Fusible de protection d appareil avec homologation Ex mb II C Gb Example / Beispiel / Exemple:

More information

SolConeX Wall-Mounted Socket, 16 A

SolConeX Wall-Mounted Socket, 16 A SolConeX Wall-Mounted Socket, 16 A Operating instructions Additional languages www.stahl-ex.com General Information Contents 1 General Information...2 1.1 Manufacturer...2 1.2 Information Regarding the

More information

Part-turn actuators SGM 04.1 SGM 12.1 SGMR 04.1 SGMR 12.1 with integral actuator controls. Control Parallel Profibus DP Modbus

Part-turn actuators SGM 04.1 SGM 12.1 SGMR 04.1 SGMR 12.1 with integral actuator controls. Control Parallel Profibus DP Modbus Part-turn actuators SGM 04.1 SGM 12.1 SGMR 04.1 SGMR 12.1 with integral actuator controls Control Parallel Profibus DP Modbus Operation instructions Assembly, operation, commissioning Table of contents

More information

PSI-MOS-PROFIB/FO 850 T

PSI-MOS-PROFIB/FO 850 T Extract from the online catalog PSI-MOS-PROFIB/FO 850 T Order No.: 2708261 FO converter with integrated optical diagnosis, alarm contact, for PROFIBUS up to 12 MBit/s, T-coupler with two FO interfaces

More information

FL MC 2000E (SM40) LC

FL MC 2000E (SM40) LC IEC 61850 fiber optic converter with LC fiber optic connection (1310 nm) to convert 100Base-Tx to single- or multi-mode fiber glass Data sheet 3205_en_C 1 Description PHOENIX CONTACT 2014-04-04 2 Features

More information

ELECTRIC ACTUATORS Compact devices for the automation of globe valves, ball valves and butterfl y valves

ELECTRIC ACTUATORS Compact devices for the automation of globe valves, ball valves and butterfl y valves ELECTRIC ACTUATORS Compact devices for the automation of globe valves, ball valves and butterfl y valves SGC PART-TURN ACTUATORS 2 SVC GLOBE VALVE ACTUATORS 3 SGC part-turn actuators and SVC globe valve

More information

Redundancy Module QUINT-DIODE/40

Redundancy Module QUINT-DIODE/40 Redundancy Module QUT DIODE provides: 00% decoupling of power supplies connected in parallel Can be installed in potentially explosive areas Load currents up to 60 A supported Easy assembly by snapping

More information

Multi-turn actuators SA 07.2 SA 16.2/SAR 07.2 SAR 16.2 Control unit: electromechanic with actuator controls AUMATIC AC 01.

Multi-turn actuators SA 07.2 SA 16.2/SAR 07.2 SAR 16.2 Control unit: electromechanic with actuator controls AUMATIC AC 01. Multi-turn actuators SA 07.2 SA 16.2/SAR 07.2 SAR 16.2 Control unit: electromechanic with actuator controls AUMATIC AC 01.2 Intrusive Control Parallel Profibus DP Operation instructions Assembly, operation,

More information

USER MANUAL. Electrical Part-turn Valve Actuators. Rev 5.3 / March 2018 EQS ID 1193 QT 250 and QT Ex Actuator

USER MANUAL. Electrical Part-turn Valve Actuators. Rev 5.3 / March 2018 EQS ID 1193 QT 250 and QT Ex Actuator USER MANUAL Electrical Part-turn Valve Actuators Rev 5.3 / March 2018 EQS ID 1193 QT 250 and QT800 2.4 Ex Actuator Revision 5.3 Page 1 of 26 TABLE OF CONTENTS 1 INTRODUCTION... 3 1.1 VALVE INTERFACE...

More information

Multi-turn actuators SA 07.1 SA 16.1/SAR 07.1 SAR 16.1 Control unit: electronic (MWG) with actuator controls AUMATIC AC 01.

Multi-turn actuators SA 07.1 SA 16.1/SAR 07.1 SAR 16.1 Control unit: electronic (MWG) with actuator controls AUMATIC AC 01. Multi-turn actuators SA 07.1 SA 16.1/SAR 07.1 SAR 16.1 Control unit: electronic (MWG) with actuator controls AUMATIC AC 01.1 Non-Intrusive Control Parallel Profibus DP Modbus DeviceNet Foundation Fieldbus

More information

Part-turn actuators SQ 05.2 SQ 14.2/SQR 05.2 SQR 14.2 Control unit: electronic (MWG) with actuator controls AUMATIC AC 01.

Part-turn actuators SQ 05.2 SQ 14.2/SQR 05.2 SQR 14.2 Control unit: electronic (MWG) with actuator controls AUMATIC AC 01. Part-turn actuators SQ 05.2 SQ 14.2/SQR 05.2 SQR 14.2 Control unit: electronic (MWG) with actuator controls AUMATIC AC 01.2 Non-Intrusive Control Parallel Profibus DP Modbus Foundation Fieldbus Operation

More information

PSI-MOS-RS422/FO 850 T

PSI-MOS-RS422/FO 850 T Extract from the online catalog PSI-MOS-RS422/FO 850 T Order No.: 2708397 FO converter with integrated optical diagnosis, alarm contact, for RS-422/RS-485 4-wire/ INTERBUS to 2 Mbit/s, T-coupler with two

More information

Control unit SG-EFS 104/4L. EN Operating instructions. Innovative by tradition. Version SG-EFS 104/4L AC/DC 24 V

Control unit SG-EFS 104/4L. EN Operating instructions. Innovative by tradition. Version SG-EFS 104/4L AC/DC 24 V Innovative by tradition. Control unit SG-EFS 104/4L EN Operating instructions Version 2 1004128 SG-EFS 104/4L AC/DC 24 V Original instructions Mayser GmbH & Co. KG Örlinger Straße 1 3 89073 Ulm GERMANY

More information

We reserve the right to alter data according to improvements made. Previous documents become invalid with the issue of this document.

We reserve the right to alter data according to improvements made. Previous documents become invalid with the issue of this document. General information AC 01.2 actuator controls for controlling multi-turn actuators of the SA/SAR.2 type range and part-turn actuators of the SQ/SQR type range with interface. Features and functions Power

More information

RAD-DO8-IFS. I/O extension module, eight digital transistor outputs. Data sheet. 1 Description

RAD-DO8-IFS. I/O extension module, eight digital transistor outputs. Data sheet. 1 Description I/O extension module, eight digital transistor outputs Data sheet 105364_en_00 PHOENIX CONTACT 2013-03-26 1 Description The I/O extension module can be used in conjunction with Radioline wireless modules

More information

Vibration Sensor Type 640

Vibration Sensor Type 640 Vibration Sensor Type 640 Standard Zone-1-21 Zone-2-22 Instruction Manual English Instruction Manual Vibration Sensor Type 640 Standard Zone-1-21 Zone-2-22 Edition: 12.04.10 Attention! Before Start-Up

More information

HITACHI. EH-150 series PLC EH-RTD8 Resistance Temperature Detective input module Instruction manual. Safety precautions

HITACHI. EH-150 series PLC EH-RTD8 Resistance Temperature Detective input module Instruction manual. Safety precautions HITACHI EH-150 series PLC Resistance Temperature Detective input module Instruction manual Thank you for purchasing a Hitachi Programmable Logic Controller. To operate it safely, please read this instruction

More information

GRP Flameproof Visual Signal Xenon or Steady LED

GRP Flameproof Visual Signal Xenon or Steady LED GRP Flameproof Visual Signal Xenon Operating instructions Additional languages www.stahl-ex.com General Information Contents 1 General Information...2 1.1 Manufacturer...2 1.2 Information regarding the

More information

Intrinsically safe batch controller Batching Master 110i

Intrinsically safe batch controller Batching Master 110i Intrinsically safe batch controller Batching Master 110i Installation Guide BVS 04 AT E 172 Revision 12.2 IBS BatchControl GmbH Im Sträßchen 2-4 Tel.: ++49 2441 9199 801 53925 Kall Fax.: ++49 2441 9199

More information

PSI-MOS-PROFIB/FO 850 T

PSI-MOS-PROFIB/FO 850 T Extract from the online catalog PSI-MOS-PROFIB/FO 850 T Order No.: 2708261 FO converter with integrated optical diagnosis, alarm contact, for PROFIBUS up to 12 MBit/s, T-coupler with two FO interfaces

More information

Technical Information Promonitor NRF560

Technical Information Promonitor NRF560 TI00462G/08/EN/03.14 71264171 Products Solutions Services Technical Information For tank side monitor and control of Proservo NMS5 intelligent tank gauge Application is a monitoring unit for use with Proservo

More information

SolConeX extra-low voltage flange socket

SolConeX extra-low voltage flange socket SolConeX extra-low voltage flange socket Operating instructions Additional languages www.stahl-ex.com Contents 1 General Information...3 1.1 Manufacturer...3 1.2 Information regarding the operating instructions...3

More information

PROCESS AUTOMATION INSTRUCTION MANUAL FIELDBUS SURGE PROTECTOR F*-LBF-I1.32 F*-LBF-D1.32

PROCESS AUTOMATION INSTRUCTION MANUAL FIELDBUS SURGE PROTECTOR F*-LBF-I1.32 F*-LBF-D1.32 PROCESS AUTOMATION INSTRUCTION MANUAL FIELDBUS SURGE PROTECTOR F*-LBF-I1.32 F*-LBF-D1.32 With regard to the supply of products, the current issue of the following document is applicable: The General Terms

More information

Globe valve actuators SVM 05.1 SVM 07.5 SVMR 05.1 SVMR 07.5 with integral actuator controls. Control Parallel Profibus DP

Globe valve actuators SVM 05.1 SVM 07.5 SVMR 05.1 SVMR 07.5 with integral actuator controls. Control Parallel Profibus DP Globe valve actuators SVM 05.1 SVM 07.5 SVMR 05.1 SVMR 07.5 with integral actuator controls Control Parallel Profibus DP Operation instructions Assembly, operation, commissioning Table of contents Profibus

More information

BVS 17 ATEX E 117 X / IECEx BVS X Types 3320, 3321, 3323, 3360, 3361, 3363 AE3320, AE3321, AE3323, AE3360, AE3361, AE3363

BVS 17 ATEX E 117 X / IECEx BVS X Types 3320, 3321, 3323, 3360, 3361, 3363 AE3320, AE3321, AE3323, AE3360, AE3361, AE3363 BVS 17 ATEX E 117 X / IECEx BVS 17.0100X Types 3320, 3321, 3323, 3360, 3361, 3363 AE3320, AE3321, AE3323, AE3360, AE3361, AE3363 Electromotive control valve with ATEX approval and IECEx approval Elektromotorisches

More information

Actuator controls. AUMATIC AC 01.1 ACExC 01.1 DeviceNet. Operation instructions. Zertifikat-Registrier-Nr /

Actuator controls. AUMATIC AC 01.1 ACExC 01.1 DeviceNet. Operation instructions. Zertifikat-Registrier-Nr / Actuator controls AUMATIC AC 01.1 ACExC 01.1 Zertifikat-Registrier-Nr. 12 100/104 4269 Operation instructions Actuator controls AUMATIC AC 01.1 / ACExC 01.1 Operation instructions Scope of these instructions:

More information

Installation manual plugs and connectors with screw connection (16/32 A)

Installation manual plugs and connectors with screw connection (16/32 A) EN Installation manual plugs and connectors with screw connection (16/32 60003213 Issue 04.2016 2016-04-01 Table of contents 1 About this manual 3 1.1 Structure of the warnings 3 1.2 Symbols used 4 1.3

More information

Technical Data. General specifications Switching element function DC Dual NC Rated operating distance s n 3 mm. Short-circuit protection

Technical Data. General specifications Switching element function DC Dual NC Rated operating distance s n 3 mm. Short-circuit protection NCN-FK-N-V-V 002 Model Number NCN-FK-N-V-V Features Direct mounting on standard actuators Compact and stable housing with terminal compartment connection Fixed setting EC-Type Examination Certificate TÜV99

More information

INSTRUCTION MANUAL WCS-Interface Module, DeviceNet

INSTRUCTION MANUAL WCS-Interface Module, DeviceNet FACTORY AUTOMATION INSTRUCTION MANUAL WCS-Interface Module, DeviceNet WCS-DG210 Part. No. 202340 / DOCT-1305 / 11. june 2007 1 Working principle............................ 6 2 Installation and commissioning.................

More information

BVS 17 ATEX E 117 X / IECEx BVS X Types 3320, 3321, 3323, 3360, 3361, 3363 AE3320, AE3321, AE3323, AE3360, AE3361, AE3363

BVS 17 ATEX E 117 X / IECEx BVS X Types 3320, 3321, 3323, 3360, 3361, 3363 AE3320, AE3321, AE3323, AE3360, AE3361, AE3363 BVS 17 ATEX E 117 X / IECEx BVS 17.0100X Types 3320, 3321, 3323, 3360, 3361, 3363 AE3320, AE3321, AE3323, AE3360, AE3361, AE3363 Electromotive control valve with ATEX approval and IECEx approval Elektromotorisches

More information

PLIN-LWL Optical Coupler for LIN Data Transmission. User Manual. Document version ( )

PLIN-LWL Optical Coupler for LIN Data Transmission. User Manual. Document version ( ) PLIN-LWL Optical Coupler for LIN Data Transmission User Manual Document version 1.1.1 (2017-01-27) Relevant products Product Name Model Part number PLIN-LWL IPEH-004049 All product names mentioned in this

More information

Multi-turn actuator. with actuator controls. SA 07.1 SA 16.1/SAR 07.1 SAR 16.1 Intrusive AUMATIC AC Control: Foundation Fieldbus

Multi-turn actuator. with actuator controls. SA 07.1 SA 16.1/SAR 07.1 SAR 16.1 Intrusive AUMATIC AC Control: Foundation Fieldbus Multi-turn actuator SA 07.1 SA 16.1/SAR 07.1 SAR 16.1 Intrusive with actuator controls AUMATIC AC 01.1 Control: Parallel Profibus DP Profibus DP with FO Modbus Modbus with FO DeviceNet Foundation Fieldbus

More information

CEM M-RS485 INSTRUCTION MANUAL (M014B A)

CEM M-RS485 INSTRUCTION MANUAL (M014B A) Communications interface CEM M-RS485 INSTRUCTION MANUAL (M014B01-03-14A) 2 SAFETY PRECAUTIONS Follow the warnings described in this manual with the symbols shown below. DANGER Warns of a risk, which could

More information

Installation Instruction. HART Add-On Module

Installation Instruction. HART Add-On Module - Translation Typs 17-A1Z0-0005, B7-A2Z0-0033 and G7-A0Z0-0007 Version for: Non hazardous areas ATEX/IECEx Zone 1 and Zone 2 UL Class I Division 1 and Division 2 Document No.: B1-A2Z0-7N0001 / 400570 Revision

More information

SPA-ZC 17. Bus connection module SPA-ZC 17. User s manual and Technical description. Tx SC Rx BB BM MB MM SPA / RS 485 POWER SLAVE 1 MASTER 0

SPA-ZC 17. Bus connection module SPA-ZC 17. User s manual and Technical description. Tx SC Rx BB BM MB MM SPA / RS 485 POWER SLAVE 1 MASTER 0 SPA-ZC 17 Bus connection module User s manual and Technical description 1 2 3 4 5 6 7 8 O N SPA / RS 485 SPA 1100000 RS 485 0011110 SLAVE 1 MASTER 0 Tx SC Rx 2 5 Uaux 80...265 V ~ 18...80 V SPA-ZC 17 RS

More information

RAD-DOR4-IFS. I/O extension module, 4 digital relay outputs. INTERFACE Data sheet. 1 Description

RAD-DOR4-IFS. I/O extension module, 4 digital relay outputs. INTERFACE Data sheet. 1 Description I/O extension module, 4 digital relay outputs INTERFACE Data sheet 104834_en_01 PHOENIX CONTACT 2013-01-21 1 Description The RAD-DOR4-IFS I/O extension module can be used in conjunction with Radioline

More information

Conveyor Belt Alignment Switches from IDEM

Conveyor Belt Alignment Switches from IDEM Conveyor Belt Alignment Switches from IDEM Data Sheet Die-Cast Models Python Line Series Stainless Steel Models Using Conveyor Belt Alignment Switches Application: Conveyor Belt Alignment switches are

More information

Serial Data DIN Fiber Link System

Serial Data DIN Fiber Link System USER GUIDE RLH Industries, Inc. The leader in rugged fiber optic technology. U-120 2017A-0420 DIN Fiber Link System COMPACT, RUGGED & TEMPERATURE HARDENED Introduction The DIN Fiber Link system transports

More information

Digital Output Module 4-Channel Version for Zone 1 Series 9475/

Digital Output Module 4-Channel Version for Zone 1 Series 9475/ www.stahl.de > 4-channel digital output > Intrinsically safe outputs Ex ib > Suitable for Ex i hydraulic valves and solenoid valves > Additional Ex i control input for (in accordance with IEC 61508 through

More information

SUBCON-PLUS-PROFIB...

SUBCON-PLUS-PROFIB... Fast connector for PROFIBUS systems Data sheet 101610_en_10 PHOENIX CONTACT 2017-03-27 1 Description The SUBCON-PLUS-PROFIB... D-SUB series is specifically designed for use in PROFIBUS systems up to 12

More information

RAD-DI8-IFS. I/O extension module with 8 digital inputs or 2 pulse inputs. INTERFACE Data sheet. 1 Description

RAD-DI8-IFS. I/O extension module with 8 digital inputs or 2 pulse inputs. INTERFACE Data sheet. 1 Description I/O extension module with 8 digital inputs or 2 pulse inputs INTERFACE Data sheet 0483_en_00 PHOENIX CONTACT 203-04-05 Description The I/O extension module can be used in conjunction with Radioline wireless

More information

PTB 01 ATEX Example / Beispiel / Exemple. Type Operating Instructions

PTB 01 ATEX Example / Beispiel / Exemple. Type Operating Instructions Device with II 2G EX i approval Geräte mit II 2G EX i Zulassung Appareils avec mode de protection II 2G EX i Example / Beispiel / Exemple Type 6106 Operating Instructions Bedienungsanleitung Manuel d utilisation

More information

Technical Information Fieldgate SFG500

Technical Information Fieldgate SFG500 TI00029S/04/EN/10.16 71324508 Products Solutions Services Technical Information Fieldgate SFG500 Smart Ethernet/PROFIBUS gateway Parallel access to PROFIBUS networks Monitoring of PROFIBUS and HART device

More information

User Manual HMI Linkbox HL01 DP/MPI

User Manual HMI Linkbox HL01 DP/MPI User Manual HMI Linkbox HL01 DP/MPI Part Number: 80860.603 Version: 1 Date: 07.05.2005 Valid for: HL01 DP/MPI Version Date Modifications 1 07.05.2005 First edition This manual, including all illustrations

More information

Actuator controls. AUMA MATIC AM 01.1/ AM 02.1 AMExB 01.1/ AMExC 01.1 Profibus DP. Operation instructions

Actuator controls. AUMA MATIC AM 01.1/ AM 02.1 AMExB 01.1/ AMExC 01.1 Profibus DP. Operation instructions Actuator controls AUMA MATIC AM 0./ AM 02. AMExB 0./ AMExC 0. ISO 900 ISO 400 Certificate Registration No. 2 00 4269 2 04 4269 Operation instructions Actuator controls AUMA MATIC AM/ AMExB/ AMExC Operation

More information

Operating Instructions

Operating Instructions Innovative by tradition. Operating Instructions Control Unit SG-RSV 239 Version 1 1003986 SG-RSV 239/24 24 V= 1005372 SG-RSV 239/36 36 V= 1003271 SG-RSV 239 50-150 V= Mayser GmbH & Co. KG Örlinger Straße

More information

ELECTRIC ACTUATORS with PROFINET interface

ELECTRIC ACTUATORS with PROFINET interface ELECTRIC ACTUATORS with PROFINET interface Top reliability and availability are prime requirements in process automation plants in terms of deployed communication technologies. Robust and versatile Industrial

More information

Control unit SG-EFS 104/2W. EN Operating instructions. Innovative by tradition. Version SG-EFS 104/2W 24 V=/~

Control unit SG-EFS 104/2W. EN Operating instructions. Innovative by tradition. Version SG-EFS 104/2W 24 V=/~ Innovative by tradition. Control unit SG-EFS 104/2W EN Operating instructions Version 0.9 1005196 SG-EFS 104/2W 24 V=/~ Original instructions Mayser GmbH & Co. KG Örlinger Straße 1 3 89073 Ulm GERMANY

More information

Inductive angle sensor with analog output Ri360P1-DSU35TC-ELi-Exi

Inductive angle sensor with analog output Ri360P1-DSU35TC-ELi-Exi ATEX category II 2 G, Ex Zone 1 ATEX category II 2 D, Ex Zone 21 Rectangular, housing DSU35 Plastic, PP-GF30-VO Detection of angular range 0 to 360 P1-Ri-QR14 positioning element included in delivery Measuring

More information

Polymer Electric. Operating Instructions. Control Unit SG-EFS 1X4 ZK2/1 8k2. Version 3

Polymer Electric. Operating Instructions. Control Unit SG-EFS 1X4 ZK2/1 8k2. Version 3 Operating Instructions Control Unit SG-EFS 1X4 ZK2/1 8k2 Version 3 1003100 SG-EFS 104 ZK2/1 8k2 24 V=/~ 7500354 SG-EFS 134 ZK2/1 8k2 230 V~ Original instructions GmbH & Co. KG Polymer Electric Örlinger

More information

AC 01.2 Foundation Fieldbus

AC 01.2 Foundation Fieldbus General information AC 01.2 actuator controls for controlling multi-turn actuators of the SA/SAR.2 type range and part-turn actuators of the SG/SGR type range with interface. Features and functions Power

More information

Polymer Electric. Operating Instructions. Control Unit SG-TRS 3X8. Version 1

Polymer Electric. Operating Instructions. Control Unit SG-TRS 3X8. Version 1 Operating Instructions Control Unit SGTRS 3X8 Version 1 100597 SGTRS 318 110 V= 100596 SGTRS 38 4 V= Original instructions GmbH & Co KG Örlinger Straße 1 3 89073 Ulm GERMANY Tel: +49 731 0610 Fax: +49

More information

H Series PLC. ! : Indicates Compulsion. EH-150 Analog input module EH-AXH8M Instruction manual. Safety precautions DANGER CAUTION COMPULSION

H Series PLC. ! : Indicates Compulsion. EH-150 Analog input module EH-AXH8M Instruction manual. Safety precautions DANGER CAUTION COMPULSION H Series PLC EH-150 Analog input module EH-AXH8M Instruction manual Thank you for purchasing a Hitachi Programmable Logic Controller. To operate it safely, please read this instruction manual and all the

More information

W&T. Universal Fiber Optic Interface Converter W&T. Manual. Universal FO Interface Converter. Model Release 1.0. Subject to error and alteration

W&T. Universal Fiber Optic Interface Converter W&T. Manual. Universal FO Interface Converter. Model Release 1.0. Subject to error and alteration Manual Universal FO Interface Converter Model 81215 Release 1.0 Subject to error and alteration 13 10/2012 by Wiesemann & Theis GmbH Subject to error and alteration: Since it is possible that we make mistakes,

More information

BVS 16 ATEX E 118 X / IECEx BVS X Types 8791, 8792, Additional Instructions. Zusatzanleitung Instruction supplémentaire

BVS 16 ATEX E 118 X / IECEx BVS X Types 8791, 8792, Additional Instructions. Zusatzanleitung Instruction supplémentaire / IECEx BVS 16.0091 X Types 8791, 8792, 8793 Position controller and process controller with II 3G Ex ec ic IIC T4 Gc / II 3D Ex tc IIIC T135 C Dc approval Stellungsregler und Prozessregler mit Zulassung

More information

Type 6150 AS-Interface Module. Type 3372 Electropneumatic Actuator with AS-interface module. Mounting and Operating Instructions EB 6150 EN

Type 6150 AS-Interface Module. Type 3372 Electropneumatic Actuator with AS-interface module. Mounting and Operating Instructions EB 6150 EN Type 6150 AS-Interface Module Type 3372 Electropneumatic Actuator with AS-interface module Mounting and Operating Instructions EB 6150 EN Edition July 2013 Definition of the signal words used in these

More information

Programmable Safety Systems PSS -Range

Programmable Safety Systems PSS -Range Programmable Safety Systems PSS -Range Serie PSS SB 006- Units with two SafetyBUS p Interfaces Operating Manual Item No. 2 4-02 All rights to this documentation are reserved by Pilz GmbH & Co. KG. Copies

More information

ISOMETER isoev425 with coupling device AGH420

ISOMETER isoev425 with coupling device AGH420 with coupling device AGH420 Insulation monitoring device for unearthed DC circuits (IT systems) for charging electric vehicles Preliminary datasheet isoev425_d00126_02_d_xxde/09.2015 with coupling device

More information

onlinecomponents.com

onlinecomponents.com Repeater for RS-485 2-Wire Systems INTERFACE Data Sheet 102964_C01_en 1 Description The PSI-REP-RS485W2 DIN-rail mountable, modular RS-485 repeater is designed to meet the high requirements associated

More information

TU531, TU532 Terminal Unit

TU531, TU532 Terminal Unit Ordering Data DATA SHEET TU531, TU532 Terminal Unit 1 Ordering Data Part No. Description Product Life Cycle Phase *) 1SAP 217 200 R0001 1SAP 217 000 R0001 1SAP 417 000 R0001 TU531, terminal unit, 230 VAC,

More information

REDUNDANCY MODULE TSP-REM360 AND TSP-REM600

REDUNDANCY MODULE TSP-REM360 AND TSP-REM600 REDUNDANCY MODULE TSP-REM360 AND TSP-REM600 Operating Instructions Seite 1 Dimensions drawings: TSP-REM360 Weight: 0.882lb Gewicht: 0.40kg Seite 2 Dimensions drawings: TSP-REM600 Bottom view Top view Side

More information

Redundancy unit CP-A RU

Redundancy unit CP-A RU 2CDC 271 010 F0t06 Features Decoupling of CP power supply units with 2 inputs, each up to 20 A per input / channel Output up to 40 A True redundancy by 100 % decoupling of two parallel connected power

More information

Installation & Operation Manual

Installation & Operation Manual Via Enrico Fermi, 2 I-25015 Desenzano del Garda (BS) - Italy Phone: +39 030 7870787 Fax: +39 030 7870777 www.solexy.net BAF Intrinsically Safe Ethernet Coupler for signals operating in Hazardous Areas

More information

ISOMETER isoev425/isoev425hc with coupling device AGH420

ISOMETER isoev425/isoev425hc with coupling device AGH420 with coupling device AGH420 Insulation monitoring device for unearthed DC circuits (IT systems) for charging electric vehicles isoev425_d00126_04_d_xxen/06.2018 with coupling device AGH420 Insulation monitoring

More information

HST -M2 Switching element with locking mechanism (Translation of Original Manual)

HST -M2 Switching element with locking mechanism (Translation of Original Manual) Installation and Operating Manual for Components HST -M2 Switching element with locking mechanism (Translation of Original Manual) HST-M2 Ident.-No.: 10214 HST-M2 Ident.-No.: 10626 HST-M2 Ident.-No.: 10218

More information

Part No. Description Product Life Cycle Phase *) unit, 24 VDC, spring terminals. unit, 24 VDC, spring terminals, XC version

Part No. Description Product Life Cycle Phase *) unit, 24 VDC, spring terminals. unit, 24 VDC, spring terminals, XC version Ordering Data DATA SHEET TU520 Terminal Unit 1 Ordering Data Part No. Description Product Life Cycle Phase *) 1SAP 214 400 R0001 1SAP 414 400 R0001 TU520-ETH, PROFINET I/O terminal unit, 24 VDC, spring

More information

PHOENIX CONTACT - 01/2008

PHOENIX CONTACT - 01/2008 Ex Basic Terminal Blocks for Intrinsically Safe Signals With Knife Disconnection and Test Connections INTERFACE Data Sheet 102957_00_en PHOENIX CONTACT - 01/2008 1 Description PI-EX-TB and PI-EX-TB/T Ex

More information

Operating instructions AS-i SmartLine module AC3200 AC /00 06/2016

Operating instructions AS-i SmartLine module AC3200 AC /00 06/2016 Operating instructions AS-i SmartLine module AC3200 AC3201 80237876/00 06/2016 Contents 1 Preliminary note...3 1.1 Symbols used...3 1.2 Warnings used...3 2 Safety instructions...3 2.1 General...3 2.2 Target

More information

Interface and Supply module. IPC 3x0i / PSC 3x0i

Interface and Supply module. IPC 3x0i / PSC 3x0i Interface and Supply module IPC 3x0i / PSC 3x0i Installation Guide Version 10 IBS BatchControl GmbH Im Sträßchen 2 4 Tel.: +49 2241 9199801 53925 Kall Fax.: +49 2241 9199871 Germany www.ibs-batchcontrol.com

More information

Inductive sensor NI3-EG08K-Y1-H1341

Inductive sensor NI3-EG08K-Y1-H1341 ATEX category II 1 G, Ex zone 0 ATEX category II 1 D, Ex zone 20 SIL2 as per IEC 61508 Threaded barrel, M8 x 1 Stainless steel, 1.4427 SO DC 2-wire, nom. 8.2 VDC Output acc. to DIN EN 60947-5-6 (NA- MUR)

More information

FL MC 10/100BASE-T/FO-660

FL MC 10/100BASE-T/FO-660 Extract from the online catalog FL MC 10/100BASE-T/FO-660 Order No.: 2708193 FO converter, for converting 10/100Base-T to polymer and HCS fiber, (660 nm), SCRJ FO connection (PROFINET standard), rail-mountable,

More information

Accessories / 7XV5461

Accessories / 7XV5461 Accessories / XV XV two-channel serial optical repeater (for mono-mode FO cable) Fig. / Optical repeater with integrated 0 nm/ nm wave length multiplexer for one single mono-mode FO-cable LSP.tif Function

More information

Inductive Angle Sensor With Analog Output RI360P1-DSU35TC-ELI-EXI

Inductive Angle Sensor With Analog Output RI360P1-DSU35TC-ELI-EXI ATEX category II 2 G, Ex Zone 1 ATEX category II 2 D, Ex Zone 21 Rectangular, housing DSU35 Plastic, PP-GF30-VO Detecting angular positions of 0 to 360 P1-Ri-DSU35 positioning element included in delivery

More information

HST -M1 Switching element with locking mechanism (Translation of Original Manual)

HST -M1 Switching element with locking mechanism (Translation of Original Manual) Installation and Operating Manual for Components HST -M1 Switching element with locking mechanism (Translation of Original Manual) HST-M1 Ident. No.: 10213 HST-M1 Ident. No.: 10219 HST-M1, pictured Ident.

More information

INSTALLATION TECHNOLOGY MADE EASY

INSTALLATION TECHNOLOGY MADE EASY INSTALLATION TECHNOLOGY MADE EASY Pre-assembled branching/terminal boxes for Zone 1 and Zone 21 Each user can enjoy the benefits of the exlink with the pre-assembled branching boxes without having to first

More information

PHOENIX CONTACT - 05/2007

PHOENIX CONTACT - 05/2007 Ex Universal Module Carrier (Motherboard) for Accommodating 3-Wire Measuring Transducers, Intrinsically Safe, for a Maximum of 8 PI Ex Modules INTERFACE Data Sheet 103030_00_en PHOENIX CONTACT - 05/2007

More information

SMS 3xxx/SMS 4xxx Safety switch with separate actuator

SMS 3xxx/SMS 4xxx Safety switch with separate actuator Operating Instructions (Translation of the original instructions) SMS 3xxx/SMS 4xxx Safety switch with separate actuator SMS 3xxx SMS 4xxx Wieland Electric GmbH Brennerstraße 10-14 D-96052 Bamberg Tel.

More information

PHOENIX CONTACT

PHOENIX CONTACT Fiber optic converter for RS-422/RS-485 4-wire/INTERBUS INTERFACE Data sheet 101974_en_04 PHOENIX CONTACT - 2010-01-28 1 Description PSI-MOS-RS422/FO devices convert RS-422/RS-485 4-wire and INTERBUS interfaces

More information

SIWAREX JB Aluminum Housing. Instruction Manual Edition 03/2006

SIWAREX JB Aluminum Housing. Instruction Manual Edition 03/2006 s SIWAREX JB Aluminum Housing Instruction Manual Edition 03/2006 Table of Contents Table of Contents... 2 Warning and Safety Terms... 3 General... 4 1 Technical Description... 5 1.1 Area of Application...

More information

ACP 1703 Ax 1703 CM Fieldbus Interface Ring (3x FO, 1x el.)

ACP 1703 Ax 1703 CM Fieldbus Interface Ring (3x FO, 1x el.) ACP 1703 Ax 1703 CM-0821 Fieldbus Interface Ring (3x FO, 1x el.) Bus interface for an optical field bus or multi-point traffic as optical ring or optical star Features: 3 optical transmitter and receiver

More information

4 Channel 4~20mA/0~10VDC Analog Data Fiber Link System

4 Channel 4~20mA/0~10VDC Analog Data Fiber Link System USER GUIDE RLH Industries, Inc. The leader in rugged fiber optic technology. U-022 2017A-0330 4 Channel 4~20mA/0~10VDC Analog Data Fiber Link System SYSTEM INSTALLATION INFORMATION Description The 4 Channel

More information

D5090S INSTRUCTION MANUAL. D A SIL 3 Relay Output Module for NE Load. DIN-Rail and Termination Board, Model D5090S

D5090S INSTRUCTION MANUAL. D A SIL 3 Relay Output Module for NE Load. DIN-Rail and Termination Board, Model D5090S D5090S INSTRUCTI MANUAL 4 A Relay Output Module for NE, DIN-Rail and Termination Board, Model D5090S D5090-4 A Relay Output Module for NE G.M. International ISM09-3 Characteristics General Description:

More information

Manual Control Unit GFC 32

Manual Control Unit GFC 32 Manual Control Unit 1400004_EN/05.2017 Index 1. Main features 3 2. Technical features 3 3. Installation guidelines 4 4. Preliminary checks 5 5. Electrical connections 5 6. Settings 6 7. Remote control

More information

Operating Instructions

Operating Instructions Introduction To protect the signal lines of field devices and systems in the cabinet against lightning. Pepperl+Fuchs covers the complete range of Surge Protection Barriers. Housing types Depending on

More information

ASM1, ASM1E, ASM2E. AS-i Safety Monitor. Subject to change without prior notice. Technische Änderungen vorbehalten /02

ASM1, ASM1E, ASM2E. AS-i Safety Monitor. Subject to change without prior notice. Technische Änderungen vorbehalten /02 ASM1, ASM1E, ASM2E AS-i Safety Monitor 50101229-2009/02 Technische Änderungen vorbehalten Subject to change without prior notice Information on the use of the connecting and operating instructions These

More information