1 NREL Validates LCS Technology PRESENTED BY Herb Zien CEO, LiquidCool Solutions
2 Learning Objectives As much as 40% of data center power is used to circulate air, and fans in a typical 30-megawatt data center circulate 1.4 million cubic feet of air per minute. All data centers need air conditioning and use onsite water for cooling, either in cooling towers or evaporative cooling units. Exposure to air destroys electronics. Free energy can be expensive. 2
3 Question Data Centers are the intersection of power, fiber and cooling. Until now Cooling has driven the decision tree. What if Cooling were not a constraint? What would your Data Center look like? Where would it be located? How much power would you need? 3
4 Imagine a Data Center that Reduces Capital Cost by 15% Reduces Operating Cost by 40% Reduces the Power to Cool by 98% Reduces Total Energy Use by 40% Reduces White Space by 60% Eliminates the Need for Water Supports over 50kW per Rack Improves Reliability and Extends Server Lifetime LiquidCool Solutions technology enables that data center today! 4
5 The Situation Major considerations for successful deployment of IT equipment in the data center: Power Space Cooling Cooling is a major cost factor Power required to cool a data center can match or exceed the power used to run the IT equipment itself Cooling also is often the limiting factor in data center capacity 5
6 This year, Cisco released a whitepaper* describing the typical data center air flow based on ASHRAE requirements for: Room cooling Row cooling Cabinet cooling *Cisco Unified Computing System Site Planning Guide: Data Center Power and Cooling 6
7 It s based on the same air driven technology Google used in its first data center in 1999, and Facebook in its first data center in Nothing has changed except the size. 7
8 The Issue The Problem is Air! Air is an insulator and has no thermal mass. Air wastes space, limits power density and reduces reliability. Oxidation and Corrosion Large Temperature Swings Fans Fail Air cooling also wastes energy Up to 15% of Total Power is used to Move Air Up to 20% More Power is used by Rack Fans Fans Generate Heat that must be Dissipated 8
9 Air Cooling Wastes Energy Air cooling wastes energy in Central Systems 20% to 60% of Data Center Power is used for Cooling 9
10 At the Rack 20% of IT Power actually is used to Circulate Air LiquidCool LSS220 compared to Dell PowerEdge R LiquidCool Solutions, Inc 10
11 The Solution Liquid Cooling - But which one? 1. Cold Plates / Heat Pipes Requires Air Shifts heat from processors Mechanical cooling needed above 85F Maximum rack density ~ 30kW Does not save much energy 2. In-Row Cooling Requires Air Makes the room smaller Mechanical cooling above 80F Maximum rack density ~ 35kW 3. Total Immersion in Fluid Two-phase / Single-phase Eliminates Air Cooling Completely Removes 100% of the Heat in the Liquid Rack density > 75kW 11
12 Cold Plates Indirect cooling of servers through the use of chip-specific, fluidcooled heat exchangers mounted on each chip. Cools the chips through closed loop circulation of high pressure water through cold plates, dumping waste heat using fluid-to-fluid, fluid-to-air heat exchangers. Requires water cooling infrastructure to the rack and CRAC units & fans for cooling of all other components. 12
13 In-Row Cooling Moves the air cooling radiators to the back of the rack. Cools the server through closed loop circulation of water through radiators, dumping waste heat using fluid-to-fluid or fluid-to-air heat exchangers. Requires water infrastructure to the rack & fans are required on servers and back door. 13
14 Two-Phase Total Immersion Servers are fully immersed in lowtemp boiling halogenated fluids Cools the server through vaporization of fluid by hot electronics and re-condensing the fluid on heat exchangers Waste heat is dissipated with a liquid-toliquid heat exchanger Issues Requires Water Cooling to the Rack or Vapor Containment System Operationally Complex Reduced Reliability due to Material Incompatibilities Very Costly because Constant Coolant Replenishment is Required Environmental and Employee Safety Issues 14
15 Single-Phase Total Immersion Reduces Complexity and Cost Eliminates all Water in the Data Room Silent and Simple - no CRAC, no fans, no vibration, no air filters, no airborne contaminants Extremely Energy Efficient: Thermal Efficiency with a true PUE< % lower Power-to-Cool a Data Center compared to Air 94% of Input Energy can be recaptured in the form of a 55oC Liquid Operating Expense is exceptionally low No Water Needed Other Benefits: Reduces Infrastructure Saves Space Electronics Last Longer Input Energy can be Recycled 15
16 Consider this: LCS single-phase data center cooling addresses four key data center issues: 1. Eliminates air cooling completely, 2. Removes 100% of the heat in the liquid, 3. Eliminates water use completely, and 4. Captures high quality heat (above 135F) for reuse. That s right! It uses no water. 16
17 Also consider this: It takes the same amount of air to fill the Empire State Building more than 4 times to remove as much heat as an Olympic-size Pool filled with OptiCool 17
18 Server of the Future Available Today Off-the-Shelf Electronics No Fans or Other Moving Components Within the Chassis Cool liquid is circulated directly to hottest components first. Remaining components are cooled by bulk flow as the dielectric liquid circulates and then exits the chassis Rack-mounted devices are easy to install/remove/maintain 76 Nodes in a 48U Rack Hot Swap Servers in Two Minutes Liquid Submerged Server - Dielectric Fluid Flow Rate: ~ 0.25 gal/min 18
19 Heat Dissipation The World s Smartest Water Heater Pump supplies cool dielectric liquid to multiple IT racks Reuse hot fluid or circulate to a dry cooler Incoming cool fluid can be as warm as 45 C for most applications 19
20 Reduces Infrastructure Not Needed Mechanical Refrigeration Cooling Towers Air Handlers Humidity Control Blade and Rack Fans Mixing Dampers High Ceilings Hot Aisle Water Lower Cost Upfront and Less Maintenance Every Day 20
21 Saves Space Retrofit a 2,000 sq. ft. data center for a federal government agency 21
22 Electronics Last Longer A Long-term Reliability Test has been in continuous operation for 45 months Over 200,000 server hours logged running 24/7 at 100% CPU load No changes to dielectric fluid properties or cooling performance have been detected Internal Components after 36 Months of Operation 22
23 Safe & Eco Friendly Coolant Synthetic hydrocarbon oil formulations with hindered phenol antioxident and viscosity control additives NOT mineral oil...free of wax and other impurities often found in these types of oils 1,400 times more heat capacity by volume than air Cost-effective, non-volatile, and non-toxic Available in standard and low-viscosity Mil-Std formulations High flashpoints suitable for use with electronics (160 C to 190 C) The cooling circuit is sealed and the Core Coolant never needs to be replaced. Highest Thermal Efficiency Reduces datacenter energy usage Recycled Heat Can Reduce Net Datacenter Energy Use by 90% No Water in the Chassis, Rack or White Space Less E-Waste because Chassis can be reused during upgrades 23
24 Reliability / Ease of Service LCS technology eliminates most causes of electronics failures Protection from airborne contaminants Cooler operating temperatures Reduced temperature fluctuation No fans or other moving parts No vibration within devices Protection from ESD effects Highly compatible, protective coolant. A Device can be Swapped in Less Than 2 minutes with No Fluid Loss 24
25 NREL Validation The LSS technology has the following advantages over traditional air-cooled server systems: 1. Maintains a small difference between central processing unit (CPU) and memory temperatures and inlet coolant temperature, allowing for: a. Use of higher temperature coolant b. Higher temperature heat recovery c. Ability to maintain lower electronic temperatures 2. Eliminates the parasitic cooling energy used by fans 3. Lower capital and energy costs in a building that contains a data center because the heat removed from the servers can: a. More effectively be rejected to ambient using lower cost systems b. Be re-used effectively as a heating source for the building. 25
26 NREL Test Setup 26
27 NREL Test Results Data from National Renewable Energy Laboratory tests show that 93% of the electric energy used by LCS servers can be recycled at 60 o C for hot water or building heat. Results for Liquid Submerged Server Experiments at NREL s Advanced HVAC Systems Laboratory Eric Kozubal National Renewable Energy Laboratory Pre-published report July 25,
28 Product Building Blocks LCS produces three platform IT devices: Liquid Submerged Server (LSS), Submerged Cloud Server (SCS) and Submerged Graphics Server (SGS). Liquid Submerged Server (LSS) Submerged Cloud Server (SCS) Submerged Graphics Server (SGS) 28
29 LSS Rack Features: 30-kilowatt rack, equivalent to four aircooled racks Energy Efficient Scalable Easy to Maintain No Moving Parts No Water Electronics protected from humidity, dust, oxidation, and corrosive gases LSS Server 72-Server Rack 29
30 SCS Rack Features: 45kW rack, equivalent to 5 air-cooled racks Energy Efficient Scalable Easy to Maintain No Moving Parts No Water Electronics protected from humidity, dust, oxidation, and corrosive gases 48U 96-Node Rack With Fluid Expansion Reservoir 30
31 RT Rugged Terrain Features: Rugged all-metal enclosure with waterproof I/O connectors Electronics protected from humidity, dust, oxidation, and corrosive gases Fan-free design produces a system that is highly reliable, energy efficient and runs silently Choices for motherboard, CPU and I/O configurations are available to support a wide array of applications 31
32 Edge / Fog Computing Features: No A/C High Power Density Siting Flexibility High Reliability Energy Efficient Quiet Operation Easy to Maintain No Water Office, factory or outdoors 32
33 200 kw Prefabricated Module Features: 200-kilowatt Prefabricated Module Can be transported by cargo plane Rapid field set up Energy Efficient Cooling PUE<1.03 No water Easy to Maintain Electronics protected from humidity, dust, oxidation, and corrosive gases Overall dimensions: 12 x 12 x 20 33
34 750 kw Prefabricated Module Features: 750 kilowatt Prefabricated Module Replaces five air-cooled modules Energy Efficient Cooling PUE<1.03 No water Easy to Maintain No Moving Parts Electronics protected from humidity, dust, oxidation, and corrosive gases Overall dimensions: 12 x 12 x 42 34
35 Lowest Total Cost of Ownership Reduces Capital Cost Saves Space and Eliminates Mechanical Refrigeration, Evaporative Cooling, Rack Fans, Air Handlers, High Ceilings, and Raised Floors Reduces Operating Cost - Reduces power to cool by 98% over air cooling. More than 90% of waste heat can be reclaimed for other uses. There are no chillers, DX units or fans to maintain Conserves Water - No water is used when the ambient dry bulb temperature is less than 110 o F Increases Server Lifetime - Sealed system isolates electronics from the environment Improves Reliability - Eliminates fans and isolates electronics from environmental impurities, dampens thermal cycling and lowers operating temperatures Virtually Silent Operation - Fan noise and vibration are eliminated Supports High Density 35
36 LCS Makes Liquid Cooling Practical Thank you. Herb Zien, CEO LiquidCool Solutions
LCS Value Proposition November 2014
LCS Value Proposition November 2014 Data Center Trends 2014 Improving Data Center Power Efficiency & Reducing Carbon Footprint Initiatives for raising data center temperatures Data center upgrades for
More informationFREEING HPC FROM THE DATACENTRE
FREEING HPC FROM THE DATACENTRE ku:l sistem TM COOLING REDEFINED www.iceotope.com ku:l sistem removes the need for inefficient air cooling technologies FREEING HPC FROM THE DATACENTRE Iceotope s patented
More informationMission Critical Facilities & Technology Conference November 3, 2011 Cooling 101. Nick Gangemi Regional Sales Manager Data Aire
Mission Critical Facilities & Technology Conference November 3, 2011 Cooling 101 Nick Gangemi Regional Sales Manager Data Aire Agenda Exactly what are we talking about ASHRAE TC 9.9 Design best practices
More informationPassive RDHx as a Cost Effective Alternative to CRAH Air Cooling. Jeremiah Stikeleather Applications Engineer
Passive RDHx as a Cost Effective Alternative to CRAH Air Cooling Jeremiah Stikeleather Applications Engineer Passive RDHx as a Cost Effective Alternative to CRAH Air Cooling While CRAH cooling has been
More informationCooling. Highly efficient cooling products for any IT application. For More Information: (866) DATA CENTER SOLUTIONS
Cooling > Highly efficient cooling products for any IT application. DATA CENTER SOLUTIONS For More Information: (866) 787-3271 Sales@PTSdcs.com End-to-End Cooling Solutions from the Closet to the Data
More informationCooling Solutions & Considerations for High Performance Computers
Cooling Solutions & Considerations for High Performance Computers White Paper 6 Revision 1 By Rich Whitmore Executive summary The recent advances in high performance computing have driven innovations not
More informationNext Generation Cooling
Next Generation Cooling Server Manufacturer Perspective Practical and Cost Effective David Moss Data Center Strategist Dell 1 Why Chip, Row, or Rack? Density? Energy Don t be scared; I don t see 50kW/rack
More informationHIGH DENSITY RACK COOLING CHOICES
WATERCOOLED HIGH PERFORMANCE COMPUTING SYSTEMS AQUILA WHITE PAPER HIGH DENSITY RACK COOLING CHOICES by Phil Hughes Reprinted with permission of Clustered Systems Company, Inc 1 THIS WHITE PAPER DISCUSSES
More informationSystem Overview. Liquid Cooling for Data Centers. Negative Pressure Cooling Without Risk of Leaks
Liquid Cooling for Data Centers System Overview The Chilldyne Cool-Flo System is a direct-to-chip liquid cooling system that delivers coolant under negative pressure. Chilldyne s technologies were designed
More informationCooling on Demand - scalable and smart cooling solutions. Marcus Edwards B.Sc.
Cooling on Demand - scalable and smart cooling solutions Marcus Edwards B.Sc. Schroff UK Limited Data Centre cooling what a waste of money! A 1MW data center needs 177,000,000 kwh in its lifetime of 10
More informationRack cooling solutions for high density racks management, from 10 to 75 kw
Rack cooling solutions for high density racks management, from 10 to 75 Superior efficiency, high reliability, low energy consumption Modern data center are characterized by 24/7 operation all year long.
More informationA Data Center Heat Removal System That Saves... 80% Discover Inertech s Award-winning Data Center Heat Removal System
A Data Center Heat Removal System That Saves... Infrastructure Power Water up to 40% up to 80% up to 85% Discover Inertech s Award-winning Data Center Heat Removal System A Cool Solution; A Breakthrough
More informationFuture of Cooling High Density Equipment. Steve Madara Vice President and General Manager Liebert Precision Cooling Business Emerson Network Power
Future of Cooling High Density Equipment Steve Madara Vice President and General Manager Liebert Precision Cooling Business Emerson Network Power Agenda Issues facing the Data Center Managing the explosive
More informationWhere s the Heat Coming From. Leland Sparks Global Account Technical Consultant Belden
Where s the Heat Coming From Leland Sparks Global Account Technical Consultant Belden What is the greatest DC challenge you face? Air Flow to Heat Load Relation Server Inlet Fans Chips Outlet LOAD Dell
More informationWelcome Association of Energy Engineers to the Microsoft Technology Center
Welcome Association of Energy Engineers to the Microsoft Technology Center Today s Agenda 10:00 10:30 What s new in data center energy efficiency planning and implementation? 10:30 11:00 ASHRAE data center
More informationImpact of Air Containment Systems
White Paper June 2012 WP-20 Impact of Air Containment Systems Reducing Energy Consumption Introduction: The Importance of Maintaining Data Center Cooling Energy Efficiency Data centers are mission-critical
More informationMSYS 4480 AC Systems Winter 2015
MSYS 4480 AC Systems Winter 2015 Module 12: DATA CENTERS By Satwinder Singh 14/05/2015 1 Data Centers Data Centers are specialized environments that safeguard your company's most valuable equipment and
More informationProduct Brochure DENCO Close Control Units Row-DENCO. High Density Cooling for Data Centres
Product Brochure DENCO Close Control Units Row-DENCO High Density Cooling for Data Centres Data Centre Cooling Through a history in close control, we have developed a broad and deep understanding of how
More informationIntroducing the Heat Wheel to the Data Center
Introducing the Heat Wheel to the Data Center Robert (Dr. Bob) Sullivan, Ph.D. Data Center Infrastructure Specialist KyotoCooling International Critical Facilities Round Table 1 A New Free Cooling Technique
More informationReducing Data Center Cooling Costs through Airflow Containment
FEATURE Reducing Data Center Cooling Costs through Airflow Containment Implementing a containment solution in the data center costs much less than the alternatives of adding air handlers or other supplemental
More informationBENEFITS OF ASETEK LIQUID COOLING FOR DATA CENTERS
BENEFITS OF ASETEK LIQUID COOLING FOR DATA CENTERS Asetek has leveraged its expertise as the world-leading provider of efficient liquid cooling systems to create its RackCDU and ISAC direct-to-chip liquid
More informationLiebert DCW CATALOGUE
Liebert DCW CATALOGUE Chilled Water-Based High Density Cooling For The Data Center LIEBERT DCW Flexible Approaches For Energy Efficient Cooling Save up to 70% in cooling energy usage Data center managers
More informationEvaporative free air cooling technology Providing evaporative free air cooling solutions.
Evaporative free air cooling technology Providing evaporative free air cooling solutions. Creating an effective workspace environment data centre free air cooling technology FreeCool - Evaporative Free
More informationIT Air Conditioning Units
IT Air Conditioning Units Modern Flexible Effective Energy Saving CoolTeg Plus and CoolTop overview CoolTeg Plus CW CoolTeg Plus DX CoolTeg Plus XC CoolTop Installation Between IT racks On top of IT rack
More informationTotal Modular Data Centre Solutions
Sector Data Centre Total Modular Data Centre Solutions www.airedale.com BRITISH MANUFACTURER ENERGY EFFICIENCY CONTROLS SERVICE TRAINING 01 Standardised Modular Designs to fit your needs Our modular system
More informationMoving Containment Inside the Enclosure. Jeff Markle Great Lakes Case & Cabinet
Moving Containment Inside the Enclosure Presented by Jeff Markle Great Lakes Case & Cabinet Containment Containment : To put constraint upon; to restrain; to confine; to keep within bounds Containment
More informationIs Data Center Free Cooling Feasible in the Middle East? By Noriel Ong, ASEAN Eng., PMP, ATD, PQP
Is Data Center Free Cooling Feasible in the Middle East? By Noriel Ong, ASEAN Eng., PMP, ATD, PQP This case study will evaluate the feasibility of data center free cooling in the Middle East using indirect
More informationMaking the impossible data center a reality.
United Nations ITU WSIS 2016 WINNER E-Environment Malaysia s First Win 2015 ASIA PACIFIC WINNER 2015 Best of Sustainability and Environmental Technology WINNER 2015 Best of Sustainability and Environmental
More informationData center cooling evolution. The hottest way to save energy. Lucio Bustaffa: Product Development Manager BlueBox Group
Data center cooling evolution. The hottest way to save energy Lucio Bustaffa: Product Development Manager BlueBox Group Data Center overview What s happening in the web? 2 Data Center overview What s happening
More information7 Best Practices for Increasing Efficiency, Availability and Capacity. XXXX XXXXXXXX Liebert North America
7 Best Practices for Increasing Efficiency, Availability and Capacity XXXX XXXXXXXX Liebert North America Emerson Network Power: The global leader in enabling Business-Critical Continuity Automatic Transfer
More informationPlanning for Liquid Cooling Patrick McGinn Product Manager, Rack DCLC
Planning for Liquid Cooling -------------------------------- Patrick McGinn Product Manager, Rack DCLC February 3 rd, 2015 Expertise, Innovation & Delivery 13 years in the making with a 1800% growth rate
More informationZTE ZXCR Series DX In-Row Air Conditioning Product Description
ZTE ZXCR Series DX In-Row Air Conditioning Product Description Requirements & Challenges Due to the rapid development of telecommunication technology, the related IT equipment s power consumption is increase
More informationThermal management. Thermal management
Thermal management Thermal management Managing thermal loads is a major challenge for all Data Centre operators. Effecting proper control of the thermal environment drives energy consumption and ultimately
More informationSTULZ Micro DC. with Chip-to-Atmosphere TM Liquid to Chip Cooling
STULZ Micro DC with Chip-to-Atmosphere TM Liquid to Chip Cooling STULZ Micro DC Data center professionals and communication service providers (CSPs) face an increasingly difficult world. The continued
More informationINNOVATE DESIGN APPLY.
INNOVATE DESIGN APPLY By A whole new cooling experience The Motivair ChilledDoor Rack Cooling System targets the critical cooling requirements of today s modern server rack designs. As technology continues
More informationAir Containment Design Choices and Considerations
Air Containment Design Choices and Considerations Brad J. Murphy, A.Sc.T., ATS, DCDC, DCEP, Principal Racon Data Centres Introduction Introduction Air containment design must consider many different factors
More informationINNOVATE DESIGN APPLY.
INNOVATE DESIGN APPLY By A whole new cooling experience The Motivair ChilledDoor Rack Cooling System targets the critical cooling requirements of today s modern server rack designs. As technology continues
More informationPower & Cooling Considerations for Virtualized Environments
Power & Cooling Considerations for Virtualized Environments Cisco Data Center Day 2008 31-01-2008 APC-MGE Vision & Mission OUR VISION APC-MGE products ensure availability wherever data is created, transmitted
More informationRecapture Capacity for Existing. and Airflow Optimization
Recapture Capacity for Existing Data Centers Through Cooling and Airflow Optimization Introduction Challenges and Trends Agenda Cooling & Airflow Optimization Takeaways Learning Objectives Recognize opportunities
More informationLiebert Economizer Cooling Solutions Reduce Cooling Costs by up to 50% Without Compromising Reliability
Precision Cooling for Business-Critical Continuity TM Liebert Economizer Cooling Solutions Reduce Cooling Costs by up to 50% Without Compromising Reliability DATA CENTER SOLUTIONS For More Information:
More informationHow Liquid Cooling Helped Two University Data Centers Achieve Cooling Efficiency Goals. Michael Gagnon Coolcentric October
How Liquid Cooling Helped Two University Data Centers Achieve Cooling Efficiency Goals Michael Gagnon Coolcentric October 13 2011 Data Center Trends Energy consumption in the Data Center (DC) 2006-61 billion
More informationGoogle s Green Data Centers: Network POP Case Study
Google s Green Data Centers: Network POP Case Study Table of Contents Introduction... 2 Best practices: Measuring. performance, optimizing air flow,. and turning up the thermostat... 2...Best Practice
More informationWHITE PAPER. Oil Immersion Cooling for Today s Data Centers. An analysis of the technology and its business
WHITE PAPER Oil Immersion Cooling for Today s Data Centers An analysis of the technology and its business In response to a growing demand for computing power and technological advancement, server densities
More informationSwitch to Perfection
Switch to Perfection Traditional Data Centre - Temperatures Ideal Air Temperature: 22 C Chilled Water: 7-9 C Heat Load per Rack: Up to 4,5 Chilling & Pump Set The challenge a thermal image Front View of
More informationFive Strategies for Cutting Data Center Energy Costs Through Enhanced Cooling Efficiency
Five Strategies for Cutting Data Center Energy Costs Through Enhanced Cooling Efficiency A White Paper from the Experts in Business-Critical Continuity TM Executive Summary As electricity prices and IT
More informationA) Differences between Precision and Comfort Cooling Here are the major differences exist between precision air conditioning and comfort systems.
DATA CENTRE COOLING SYSTEM A) Differences between Precision and Comfort Cooling Here are the major differences exist between precision air conditioning and comfort systems. 1. Cooling Optimized to Electronic
More informationHIGH DENSITY DATACOM INTEGRATED COOLING SYSTEM.
HIGH DENSITY DATACOM INTEGRATED COOLING SYSTEM. SYSTEM LOGICA is the most advanced alternative to the problem of cooling of server rooms MONTAIR is the trademark which represents excellence on the market
More informationLANL High Performance Computing Facilities Operations. Rick Rivera and Farhad Banisadr. Facility Data Center Management
Slide-1 LANL High Performance Computing Facilities Operations Rick Rivera and Farhad Banisadr Facility Data Center Management Division Slide-2 Outline Overview - LANL Computer Data Centers Power and Cooling
More information84 kw, Tier 3, Direct Expansion, 937 ft 2
[Reference Design 42] 84 kw, Tier 3, Direct Expansion, 937 ft 2 DESIGN OVERVIEW Data Center IT Capacity 84 kw Target Availability Tier 3 Annualized PUE at 100% Load 1.712 Total Racks and Average Density
More informationSchneider Electric Cooling Portfolio. Jim Tubbesing Heath Wilson APC/Schneider North Texas Rep Tubbesing Solutions
Schneider Electric Cooling Portfolio Jim Tubbesing Heath Wilson APC/Schneider North Texas Rep Tubbesing Solutions Data Center Cooling Agenda 1. How to size data center, server rooms, IDF rooms, etc in
More informationLiebert DCW Family Chilled Water-Based High Density Cooling For The Data Center. Precision Cooling For Business-Critical Continuity
Liebert DCW Family Chilled Water-Based High Density Cooling For The Data Center Precision Cooling For Business-Critical Continuity Flexible Approaches For Energy Efficient Cooling Save up to 70% in cooling
More informationIndustry leading low energy evaporative fresh air cooling.
Industry leading low energy evaporative fresh air cooling. Freecool Evaporative Free Air Cooling by Workspace Technology delivers innovative low energy cooling for a range of applications including data
More informationHot vs Cold Energy Efficient Data Centers. - SVLG Data Center Center Efficiency Summit
Hot vs Cold Energy Efficient Data Centers - SVLG Data Center Center Efficiency Summit KC Mares November 2014 The Great Debate about Hardware Inlet Temperature Feb 2003: RMI report on high-performance data
More informationPlanning a Green Datacenter
Planning a Green Datacenter Dr. Dominique Singy Contribution to: Green IT Crash Course Organisator: Green IT Special Interest Group of the Swiss Informatics Society ETH-Zurich / February 13, Green Data
More informationResults of Study Comparing Liquid Cooling Methods
School of Mechanical Engineering FACULTY OF ENGINEERING Results of Study Comparing Liquid Cooling Methods Dr Jon Summers (J.L.Summers@Leeds.Ac.UK) Institute of ThermoFluids (itf) 54th HPC User Forum, September
More informationReducing Energy Consumption with
Reducing Energy Consumption with Passive Cooling Ian Cathcart, RCDD Technical Support Manager Technical Support Manager Chatsworth Products, Inc. Thermal Management: Mission Critical Data center heat loads
More informationEcoflair Air Economizers
Ecoflair Air Economizers Cooling to maximize value for the cloud schneider-electric.com/ecoflair Life is On Schneider Electric 1 Ecoflair takes data center efficiency to new heights 2 Imagine cooling your
More informationPower and Cooling for Ultra-High Density Racks and Blade Servers
Power and Cooling for Ultra-High Density Racks and Blade Servers APC White Paper #46 Richard L. Sawyer Director of Data Center Technology American Power Conversion Company 2005 APC corporation What has
More informationENCLOSURE HEAT DISSIPATION
ENCLOSURE HEAT DISSIPATION DATA CENTER SOLUTIONS A White Paper by Great Lakes Case & Cabinet Company www.werackyourworld.com 814.734.7303 Page 2 Introduction Dangerous heat levels inside an enclosure threaten
More informationEfficiency of Data Center cooling
Efficiency of Data Center cooling Comparison of data room layouts and cooling systems Bohumil Cimbal Product manager for Cooling Systems in CONTEG Company Objective Basic questions between investor and
More informationASHRAE IRELAND HVAC FOR DATA CENTRES. Michael Geraghty Building Services Engineer (DipEng) Company owner and managing director
ASHRAE IRELAND HVAC FOR DATA CENTRES Michael Geraghty Building Services Engineer (DipEng) Company owner and managing director michael@entropic.ie OVERVIEW OF THE MARKET SITUATION IN IRELAND Relative Data
More informationData Center Energy Savings By the numbers
Data Center Energy Savings By the numbers Chris Kurkjian, PE HP Critical Facility Services provided by EYP Mission Critical Facilities 2008 Hewlett-Packard Development Company, L.P. The information contained
More informationCHILLED WATER. HIGH PRECISION AIR CONDITIONERS, FROM 7 TO 211 kw
IT COOLING CLOSE CONTROL AIR CONDITIONERS CHILLED WATER HIGH PRECISION AIR CONDITIONERS, FROM 7 TO 211 kw 3 Versions available Single chilled water coil Double chilled water coil High temperature IT COOLING
More informationPROCESS & DATA CENTER COOLING. How and Why To Prepare For What s To Come JOHN MORRIS REGIONAL DIRECTOR OF SALES
PROCESS & DATA CENTER COOLING How and Why To Prepare For What s To Come JOHN MORRIS REGIONAL DIRECTOR OF SALES CONGRATULATIONS 2 BOLD PREDICTION 3 Where We Are TODAY Computer Technology NOW advances more
More informationIT COOLING AIR CONDITIONERS FOR HIGH DENSITY RACKS AND BLADE SERVERS. RACK COOLING SOLUTIONS FOR HIGH DENSITY RACK MANAGEMENT, FROM 4 TO 75 kw
IT COOLING AIR CONDITIONERS FOR HIGH DENSITY RACKS AND BLADE SERVERS RACK COOLING SOLUTIONS FOR HIGH DENSITY RACK MANAGEMENT, FROM 4 TO 75 kw IT COOLING AIR CONDITIONERS FOR HIGH DENSITY RACKS AND BLADE
More informationA Green Approach. Thermal
A Green Approach to Thermal Management Thermal Management - AGENDA Definitions & Thermal Facts Density Trends Rack Level Management Passive Solutions Thermal Sources & Green Solutions Data Center Layout
More informationRittal Cooling Solutions A. Tropp
1 Rittal Cooling Solutions Presented by Adam Tropp 2 Agenda Cooling Strategies Aisle Containment Chimney Solution Airstream Management Rittal Liquid Cooling Packages Data Monitoring 3 Cooling strategies.
More informationThermal Design and Management of Servers
White Paper Thermal Design and Management of Servers Thermal Design and Management of Servers P.1 Overview With the exponential growth of knowledge development, data needs to be stored, processed and secured
More informationDatacenter Efficiency Trends. Cary Roberts Tellme, a Microsoft Subsidiary
Datacenter Efficiency Trends Cary Roberts Tellme, a Microsoft Subsidiary Power Slashing Tools P3 Kill-A-WATT Measures min, max, and instantaneous voltage and current draw Calculates power (watts), kilowatt
More informationASHRAE Data Center Standards: An Overview
Mission Critical Facilities ASHRAE Data Center Standards: An Overview 10012 North Dale Mabry Highway Suite 109 Tampa, FL 33618 813-792-6009 www.pergravis.com Presenter: Steve Ritzi, CDCE Pergravis is a
More informationHigh Density Cooling Solutions that work from Knurr Kris Holla
High Density Cooling Solutions that work from Knurr Kris Holla The Heat Goes On Ó by Knürr A An International Company Ranked #3 in the world Founded 1931 Strong international setting in over 32 countries
More informationYour Solution For Energy and Cost Savings. McQuay Packaged Chiller Plant
Your Solution For Energy and Cost Savings McQuay Packaged Chiller Plant Innovative Solutions for Your Chiller Plant McQuay packaged chiller plants provide energy efficient chillers integrated with pumps,
More information2000 kw, Tier 3, Chilled Water, Prefabricated, sq. ft.
[Reference Design 64] 2000 kw, Tier 3, Chilled Water, refabricated, 23700 sq. ft. DESIGN OVERVIEW Data Center IT Capacity 2000 kw Target Availability Tier 3 Annualized E at 100% Load 1.64 in Miami, FL
More informationVirtualization and consolidation
Virtualization and consolidation Choosing a density strategy Implementing a high-density environment Maximizing the efficiency benefit Anticipating the dynamic data center Schneider Electric 1 Topical
More informationVienna Scientific Cluster s The Immersion Supercomputer: Extreme Efficiency, Needs No Water
CASE STUDY Vienna Scientific Cluster s The Immersion Supercomputer: Extreme Efficiency, Needs No Water Find Out How GRC s Technology Helped VSC Get More Compute for Less. Authors: Toshio Endo, Akira Nukada,
More informationClose-coupled cooling
Close-coupled cooling Intelligently controlled high-performance InRow cooling for the IT environment APC TM by Schneider Electric close-coupled cooling products provide a modular, scalable, and predictable
More informationEnergy Efficient Data Centers
IBM Systems and Technology Group Lab Services Energy Efficient Data Centers Steven Ahladas IBM Corp ahladas@us.ibm.com Keeping our clients in the race. All trends going the same way. IT Servers were an
More informationPerformance Evaluation for Modular, Scalable Cooling Systems with Hot Aisle Containment in Data Centers. Final Report
Performance Evaluation for Modular, Scalable Cooling Systems with Hot Aisle Containment in Data Centers Final Report To The California Energy Commission May 2009 Tengfang Xu Environmental Energy Technologies
More informationProduct Guide. Direct Contact Liquid Cooling Industry leading data center solutions for HPC, Cloud and Enterprise markets.
Product Guide Direct Contact Liquid Cooling Industry leading data center solutions for HPC, Cloud and Enterprise markets. www.coolitsystems.com Phone: +1 403.235.4895 The Future of Data Center Cooling
More informationHow to Increase Data Center Efficiency
How to Increase Data Center Efficiency Shivani Shukla Potkar Product Marketing Manager Pentair Electronics Protection High cooling efficiency & and reduced power consumption enhances the balance between
More informationAPC APPLICATION NOTE #74
#74 Configuration of InfraStruXure for Data Centers to Support Dell PowerEdge 1855 Abstract Many companies are making plans to incorporate Dell PowerEdge Blade Servers into their data center applications.
More informationIt`s the size of science & research...
It`s the size of science & research... Arno Ziebart www..com ...which makes a cluster really big. It s the type of management...which makes clusters really smart. ...which makes a cluster really big. It
More informationData Center Trends: How the Customer Drives Industry Advances and Design Development
Bablu Kazi, PE MORRISON HERSHFIELD MISSION CRITICAL Data Center Trends: How the Customer Drives Industry Advances and Design Development What does the Customer Need? Scalability P U E Latest Technology
More informationThe Efficient Enterprise. All content in this presentation is protected 2008 American Power Conversion Corporation
Ee The Efficient Enterprise All content in this presentation is protected 2008 American Power Conversion Corporation Keystrokes Kilowatts Heat OUT Electricity IN Need for bandwidth exploding Going hyperbolic!
More informationPrecision Cooling Mission Critical Air Handling Units
M I S S I O N C R I T I CA L C O O L I N G Precision Cooling Mission Critical Air Handling Units Global Expertise for Precision Cooling Solutions STULZ is a privately owned, global manufacturer of highly
More informationLCP Hybrid Efficient performance with heat pipe technology
LCP Hybrid Efficient performance with heat pipe technology 2 LCP Hybrid The whole is more than the sum of its parts The same is true of "Rittal The System." With this in mind, we have bundled our innovative
More informationDominick Lovicott Enterprise Thermal Engineering. One Dell Way One Dell Way Round Rock, Texas
One Dell Way One Dell Way Round Rock, Texas 78682 www.dell.com DELL ENTERPRISE WHITEPAPER THERMAL DESIGN OF THE DELL POWEREDGE T610, R610, AND R710 SERVERS Dominick Lovicott Enterprise Thermal Engineering
More informationServer room guide helps energy managers reduce server consumption
Server room guide helps energy managers reduce server consumption Jan Viegand Viegand Maagøe Nr. Farimagsgade 37 1364 Copenhagen K Denmark jv@viegandmaagoe.dk Keywords servers, guidelines, server rooms,
More informationTWO FINANCIAL IMPACT STUDIES. Seal IT Equipment Cabinets for Significant Annual Cost Savings and Simple Payback in a Few Short Months
TWO FINANCIAL IMPACT STUDIES Seal IT Equipment Cabinets for Significant Annual Cost Savings and Simple Payback in a Few Short Months TWO FINANCIAL IMPACT STUDIES Seal IT Equipment Cabinets for Significant
More informationHP Modular Cooling System: water cooling technology for high-density server installations
HP Modular Cooling System: water cooling technology for high-density server installations technical brief Abstract... 2 Introduction... 2 Data center trends... 2 Increased power demands... 3 Increased
More informationGreen IT and Green DC
Green IT and Green DC Alex SL Tay Regional Service Product Line Manager Site & Facilities Services, IBM ASEAN 1 What our clients are telling us We are running out of space in our data center We have environmental
More informationAlfonso Ortega Villanova University Site Director Associate Vice President Research and Graduate Programs James R. Birle Professor of Energy Technology Villanova University www.villanova.edu/es2 Villanova
More informationCurrent Data Center Design. James Monahan Sept 19 th 2006 IEEE San Francisco ComSoc
Current Data Center Design James Monahan Sept 19 th 2006 IEEE San Francisco ComSoc What is the biggest facility problem in your data center? 35% 30% 25% 20% 15% Series1 10% 5% 0% Excessive heat Insufficient
More informationECOBAY: Closed loop water cooled server cabinet for data centers
ECOBAY: Closed loop water cooled server cabinet for data centers ELECTRONICS MANUFACTURING SERVICES Communications Computing Multimedia & Consumer Industrial & Semiconductor Defense & Aerospace Medical
More informationData Center Temperature Design Tutorial. Ian Seaton Chatsworth Products
Data Center Temperature Design Tutorial Ian Seaton Chatsworth Products What are we going to do today? Explore a process for determining what data center operating temperature will deliver the best total
More information100% Warm-Water Cooling with CoolMUC-3
100% Warm-Water Cooling with CoolMUC-3 No chillers, no fans, no problems Axel Auweter MEGWARE CTO Workshop on Energy Efficiency in HPC May 30, 2018, Ljubljana!1 MEGWARE Computer Vertrieb und Service GmbH
More informationLiquid Cooling Package LCP Cooling Systems
Liquid Cooling Package LCP Cooling Systems 2 Rittal LCP Rittal The System. The whole is more than the sum of its parts. The same is true of Rittal The System. With this in mind, we have bundled our innovative
More informationClose Coupled Cooling for Datacentres
Close Coupled Cooling for Datacentres Dr Fathi Tarada Mosen Ltd fathi.tarada@mosenltd.com www.mosenltd.com Agenda Increasing Power Densities Raised Floor Limitations Hot and Cold Aisle Enclosures Close
More informationIT COOLING EVAPORATIVE COOLING SYSTEM. 2 STAGE INDIRECT ADIABATIC COOLING SYSTEM FOR LARGE DATA CENTERS FROM 80 TO 320 kw
IT COOLING EVAPORATIVE COOLING SYSTEM 2 STAGE INDIRECT ADIABATIC COOLING SYSTEM FOR LARGE DATA CENTERS FROM 8 TO 3 kw IT COOLING EVAPORATIVE COOLING SYSTEM ADIABATIC COOLING FOR HIGH EFFICIENCY - Variable
More informationCooling System Considerations for High Density Colocation and Enterprise Data Centers
Cooling System Considerations for High Density Colocation and Enterprise Data Centers By Rich Whitmore Executive summary The recent advances in computer technology and the growing adoption of high performance
More information