ZTE ZXCR Series DX In-Row Air Conditioning Product Description

Size: px
Start display at page:

Download "ZTE ZXCR Series DX In-Row Air Conditioning Product Description"

Transcription

1 ZTE ZXCR Series DX In-Row Air Conditioning Product Description

2 Requirements & Challenges Due to the rapid development of telecommunication technology, the related IT equipment s power consumption is increase and heat density is getting higher, therefore the demand of heat dissipation is growing. Point-to-point In-Row cooling system is an efficient solution and technology to overcome the heat density issue. The concept of In-Row system is by reducing the distance between the heat sources and cooling system to allow the cold air flow pass through the hot aisle directly. This methodology can prevent heat and hot air dissipated from the IT equipment accumulated and cycled, in the same time reduce the system PUE. ZTE ZXCR series DX In-Row cooling system adopt energy saving, low power consumption design and applicable in all scenario that required precise control of temperature and humidity condition such as data center, computer room, program controlled switching room, satellite & mobile communication stations and etc. ZTE ZXCR series divided into 300mm and 600mm standardize dimension cabinet which can provide green, energy saving, efficient, reliable, easy maintenance and integration for In-Row cooling system. Benefits and Value for Customers 1. Cooling on demand EC fan with on-demand air volume adjustment, real time temperature adjustment DX unit use inverter, automatically adjust the compression ratio base on cooling demand, to achieve the cooling capacity level. DX unit using the electronic expansion valve, adjust the refrigerant flow rate according to real time temperature, to achieve efficient precision refrigeration. 2. Energy Efficiency

3 Optimize the heat exchanger structure, to achieve maximum heat circulation in limited space. Air-cooled unit with air flow optimization, together with EC fan and inverter to achieve the best performance and reduce energy consumption. Water-cooled unit optimizes piping layout, together with electric two-way valve and EC fan to achieve performance and reduce the energy consumption. Cooling capacity is higher than others 5% - 10%, can use in higher demand environment and provide next generation of Green Data Center s compatible solution. 3. Intelligent Control Multiple control modes, according to customer need for different controlling parameters. Group control function, multiple units can be optimize for operation to reduce the power consumption and enhance Remote control function, unit parameters can be set and controlledremotely to avoid entry by personnel. 4. Easy Maintenance Uniform screw size, easy disassembly and maintenance. Maintenance can be performing from front end and rear end. Variable communication interface for easy troubleshooting. 5. Easy Expansion Adopt 300mm and 600mm standard cabinet size for easy expansion. Varity of power input, applicable in multiple scenario.

4 Product Description ZTE ZXCR DX series In-Row cooling system adopt two cooling capacity: kw which can solve the issue of high cooling density in different environments and applications. ZXCR-3-DX ZXCR-6-DX DX unit adopts DC inverter compressor, EC fan, electronic expansion valve, electrode humidification and condensate pump and other components. By using the DC inverter compressor to compress and deliver the refrigerant to the outdoor condenser for heat circulation, expansion of electronic valve in In-Row system, intelligent EC fan, and supplemented by heating humidification to achieve precision cooling and improve cooling efficiency. With different cooling capacity 23kW, 25kW and 42kW, the in-row AC can be deployed between cabinet, installing close to the heat source, and dynamically matching data center load demand. Besides, the cooling pipe can be up the ceiling or inside the base, and is easy for maintenance from front end and rear end. With high efficiency reliability, easy installation and maintenance, the In-Row AC is widely used in different data center scenarios, providing In-Row cooling solutions for high and medium density data center. DX In-Row AC specifications: Type ZXCR-3R23 ZXCR-3R25 ZXCR-3R25-d ZXCR-6R42 Cooling Return air capacity(kw) 37

5 /RH25% Return air /RH25% Input power consumption(kw) Airflow(m3/h) Electrical heater(kw) 3(Optional) 6(Optional) Humidifier(kg/h) 1.5(Optional) 3(Optional) Pipe size(mm) 25 22/ / /15.88 FLA(A) FLA(including heater and humidifier)(a) Noise(dB) Power supply 380V/3PH/50Hz 380V/3PH/50Hz 190V/3PH/61Hz 380V/3PH/50Hz Weight(kg) (2200) (2200) (2200) 600 Size H W D(mm) Outdoor unit airflow (m3/h) Outdoor unit power consumption(kw) ZXCR Series DX structure

6 EC Fan G4 filter Electronic expansion valve Evaporator Inverter compressor Humidifier Application Scenarios ZXCR series DX In-Row cooling system used in Container Data Center ZXCR series DX In-Row cooling system used in Modular Data Center

IT Air Conditioning Units

IT Air Conditioning Units IT Air Conditioning Units Modern Flexible Effective Energy Saving CoolTeg Plus and CoolTop overview CoolTeg Plus CW CoolTeg Plus DX CoolTeg Plus XC CoolTop Installation Between IT racks On top of IT rack

More information

Product Brochure DENCO Close Control Units Row-DENCO. High Density Cooling for Data Centres

Product Brochure DENCO Close Control Units Row-DENCO. High Density Cooling for Data Centres Product Brochure DENCO Close Control Units Row-DENCO High Density Cooling for Data Centres Data Centre Cooling Through a history in close control, we have developed a broad and deep understanding of how

More information

Rack cooling solutions for high density racks management, from 10 to 75 kw

Rack cooling solutions for high density racks management, from 10 to 75 kw Rack cooling solutions for high density racks management, from 10 to 75 Superior efficiency, high reliability, low energy consumption Modern data center are characterized by 24/7 operation all year long.

More information

SmoothAir Modular Precision Cooling

SmoothAir Modular Precision Cooling TM SmoothAir Modular Precision Cooling ODM/OEM/Customization+ Specialist Support+ Modular Precision Cooling for Smart, Reliable and Green MDC Solution Why Choose Us Products Support Customization Products

More information

IT COOLING AIR CONDITIONERS FOR HIGH DENSITY RACKS AND BLADE SERVERS. RACK COOLING SOLUTIONS FOR HIGH DENSITY RACK MANAGEMENT, FROM 4 TO 75 kw

IT COOLING AIR CONDITIONERS FOR HIGH DENSITY RACKS AND BLADE SERVERS. RACK COOLING SOLUTIONS FOR HIGH DENSITY RACK MANAGEMENT, FROM 4 TO 75 kw IT COOLING AIR CONDITIONERS FOR HIGH DENSITY RACKS AND BLADE SERVERS RACK COOLING SOLUTIONS FOR HIGH DENSITY RACK MANAGEMENT, FROM 4 TO 75 kw IT COOLING AIR CONDITIONERS FOR HIGH DENSITY RACKS AND BLADE

More information

Mission Critical Facilities & Technology Conference November 3, 2011 Cooling 101. Nick Gangemi Regional Sales Manager Data Aire

Mission Critical Facilities & Technology Conference November 3, 2011 Cooling 101. Nick Gangemi Regional Sales Manager Data Aire Mission Critical Facilities & Technology Conference November 3, 2011 Cooling 101 Nick Gangemi Regional Sales Manager Data Aire Agenda Exactly what are we talking about ASHRAE TC 9.9 Design best practices

More information

7 Best Practices for Increasing Efficiency, Availability and Capacity. XXXX XXXXXXXX Liebert North America

7 Best Practices for Increasing Efficiency, Availability and Capacity. XXXX XXXXXXXX Liebert North America 7 Best Practices for Increasing Efficiency, Availability and Capacity XXXX XXXXXXXX Liebert North America Emerson Network Power: The global leader in enabling Business-Critical Continuity Automatic Transfer

More information

IT COOLING EVAPORATIVE COOLING SYSTEM. 2 STAGE INDIRECT ADIABATIC COOLING SYSTEM FOR LARGE DATA CENTERS FROM 80 TO 320 kw

IT COOLING EVAPORATIVE COOLING SYSTEM. 2 STAGE INDIRECT ADIABATIC COOLING SYSTEM FOR LARGE DATA CENTERS FROM 80 TO 320 kw IT COOLING EVAPORATIVE COOLING SYSTEM 2 STAGE INDIRECT ADIABATIC COOLING SYSTEM FOR LARGE DATA CENTERS FROM 8 TO 3 kw IT COOLING EVAPORATIVE COOLING SYSTEM ADIABATIC COOLING FOR HIGH EFFICIENCY - Variable

More information

Introducing the Heat Wheel to the Data Center

Introducing the Heat Wheel to the Data Center Introducing the Heat Wheel to the Data Center Robert (Dr. Bob) Sullivan, Ph.D. Data Center Infrastructure Specialist KyotoCooling International Critical Facilities Round Table 1 A New Free Cooling Technique

More information

PEX (R410A) High Efficiency, Green Solution Precision Cooling for Data Centers

PEX (R410A) High Efficiency, Green Solution Precision Cooling for Data Centers TM PEX (R410A) High Efficiency, Green Solution Precision Cooling for Data Centers WE ARE VERTIV Vertiv, formerly Emerson Network Power, designs, builds, and services mission critical technologies that

More information

DATA CENTER EFFICIENCY: Data Center Temperature Set-point Impact on Cooling Efficiency

DATA CENTER EFFICIENCY: Data Center Temperature Set-point Impact on Cooling Efficiency DATA CENTER EFFICIENCY: Data Center Temperature Set-point Impact on Cooling Efficiency September 27 th, 2013 Tejas Desai, PE CEM CEA LEED AP Sameer Behere, PE CEM LEED AP Agenda Problem: Quick fixes can

More information

InRow Chilled Water. Up to 70kW. Close-coupled, chilled water cooling for medium to large data centers. Row-Based Cooling.

InRow Chilled Water. Up to 70kW. Close-coupled, chilled water cooling for medium to large data centers. Row-Based Cooling. InRow Chilled Water Close-coupled, chilled water cooling for medium to large data centers Up to 0kW > Row-Based Cooling The InRow Chilled Water product design closely couples the cooling with the IT heat

More information

CHILLED WATER. HIGH PRECISION AIR CONDITIONERS, FROM 7 TO 211 kw

CHILLED WATER. HIGH PRECISION AIR CONDITIONERS, FROM 7 TO 211 kw IT COOLING CLOSE CONTROL AIR CONDITIONERS CHILLED WATER HIGH PRECISION AIR CONDITIONERS, FROM 7 TO 211 kw 3 Versions available Single chilled water coil Double chilled water coil High temperature IT COOLING

More information

Efficiency of Data Center cooling

Efficiency of Data Center cooling Efficiency of Data Center cooling Comparison of data room layouts and cooling systems Bohumil Cimbal Product manager for Cooling Systems in CONTEG Company Objective Basic questions between investor and

More information

Combining Cold Aisle Containment with Intelligent Control to Optimize Data Center Cooling Efficiency

Combining Cold Aisle Containment with Intelligent Control to Optimize Data Center Cooling Efficiency A White Paper from the Experts in Business-Critical Continuity TM Combining Cold Aisle Containment with Intelligent Control to Optimize Data Center Cooling Efficiency Executive Summary Energy efficiency

More information

Cooling. Highly efficient cooling products for any IT application. For More Information: (866) DATA CENTER SOLUTIONS

Cooling. Highly efficient cooling products for any IT application. For More Information: (866) DATA CENTER SOLUTIONS Cooling > Highly efficient cooling products for any IT application. DATA CENTER SOLUTIONS For More Information: (866) 787-3271 Sales@PTSdcs.com End-to-End Cooling Solutions from the Closet to the Data

More information

Welcome Association of Energy Engineers to the Microsoft Technology Center

Welcome Association of Energy Engineers to the Microsoft Technology Center Welcome Association of Energy Engineers to the Microsoft Technology Center Today s Agenda 10:00 10:30 What s new in data center energy efficiency planning and implementation? 10:30 11:00 ASHRAE data center

More information

Passive RDHx as a Cost Effective Alternative to CRAH Air Cooling. Jeremiah Stikeleather Applications Engineer

Passive RDHx as a Cost Effective Alternative to CRAH Air Cooling. Jeremiah Stikeleather Applications Engineer Passive RDHx as a Cost Effective Alternative to CRAH Air Cooling Jeremiah Stikeleather Applications Engineer Passive RDHx as a Cost Effective Alternative to CRAH Air Cooling While CRAH cooling has been

More information

MSYS 4480 AC Systems Winter 2015

MSYS 4480 AC Systems Winter 2015 MSYS 4480 AC Systems Winter 2015 Module 12: DATA CENTERS By Satwinder Singh 14/05/2015 1 Data Centers Data Centers are specialized environments that safeguard your company's most valuable equipment and

More information

Schneider Electric Cooling Portfolio. Jim Tubbesing Heath Wilson APC/Schneider North Texas Rep Tubbesing Solutions

Schneider Electric Cooling Portfolio. Jim Tubbesing Heath Wilson APC/Schneider North Texas Rep Tubbesing Solutions Schneider Electric Cooling Portfolio Jim Tubbesing Heath Wilson APC/Schneider North Texas Rep Tubbesing Solutions Data Center Cooling Agenda 1. How to size data center, server rooms, IDF rooms, etc in

More information

Communication Register Map - Uniflair Cooling

Communication Register Map - Uniflair Cooling DIGITAL 0 1 1 - - - - DIGITAL 1 2 2 System On (Fan) 0 or 1 boolean R DIGITAL 2 3 3 Compressor 1 0 or 1 boolean R DIGITAL 3 4 4 Compressor 2 0 or 1 boolean R DIGITAL 4 5 5 Compressor 3 0 or 1 boolean R

More information

Thermal management. Thermal management

Thermal management. Thermal management Thermal management Thermal management Managing thermal loads is a major challenge for all Data Centre operators. Effecting proper control of the thermal environment drives energy consumption and ultimately

More information

STULZ Micro DC. with Chip-to-Atmosphere TM Liquid to Chip Cooling

STULZ Micro DC. with Chip-to-Atmosphere TM Liquid to Chip Cooling STULZ Micro DC with Chip-to-Atmosphere TM Liquid to Chip Cooling STULZ Micro DC Data center professionals and communication service providers (CSPs) face an increasingly difficult world. The continued

More information

PEX+ High Efficiency, Low Operating Cost Precision Solution for Data Centers

PEX+ High Efficiency, Low Operating Cost Precision Solution for Data Centers TM PEX+ High Efficiency, Low Operating Cost Precision Solution for Data Centers WE ARE VERTIV Vertiv, formerly Emerson Network Power, designs, builds, and services mission critical technologies that enable

More information

Future of Cooling High Density Equipment. Steve Madara Vice President and General Manager Liebert Precision Cooling Business Emerson Network Power

Future of Cooling High Density Equipment. Steve Madara Vice President and General Manager Liebert Precision Cooling Business Emerson Network Power Future of Cooling High Density Equipment Steve Madara Vice President and General Manager Liebert Precision Cooling Business Emerson Network Power Agenda Issues facing the Data Center Managing the explosive

More information

High Efficient Data Center Cooling

High Efficient Data Center Cooling Nordborg High Efficient Data Center Cooling Copenhagen Center on Energy Efficiency webinar 12. July 2017 Jörg Saar, Danfoss Cooling 1 Danfoss Cooling Contents 1. Short intro to Danfoss Cooling 2. Introduction

More information

84 kw, Tier 3, Direct Expansion, 937 ft 2

84 kw, Tier 3, Direct Expansion, 937 ft 2 [Reference Design 42] 84 kw, Tier 3, Direct Expansion, 937 ft 2 DESIGN OVERVIEW Data Center IT Capacity 84 kw Target Availability Tier 3 Annualized PUE at 100% Load 1.712 Total Racks and Average Density

More information

Precision Cooling Mission Critical Air Handling Units

Precision Cooling Mission Critical Air Handling Units M I S S I O N C R I T I CA L C O O L I N G Precision Cooling Mission Critical Air Handling Units Global Expertise for Precision Cooling Solutions STULZ is a privately owned, global manufacturer of highly

More information

Ecoflair Air Economizers

Ecoflair Air Economizers Ecoflair Air Economizers Cooling to maximize value for the cloud schneider-electric.com/ecoflair Life is On Schneider Electric 1 Ecoflair takes data center efficiency to new heights 2 Imagine cooling your

More information

Avoidable Mistakes that Compromise Cooling Performance in Data Centers and Network Rooms

Avoidable Mistakes that Compromise Cooling Performance in Data Centers and Network Rooms Avoidable Mistakes that Compromise Cooling Performance in Data Centers and Network Rooms Problem Several cooling system mistakes are very common and avoidable Mistakes compromise availability and increase

More information

Huawei Smart Cooling Solution

Huawei Smart Cooling Solution Huawei Energy Powering the Future Huawei Smart Cooling Solution HUAWEI TECHNOLOGIES CO., LTD. To meet increasing demands of data centers such as IT business integration, virtualization and cloud computing,

More information

Cooling on Demand - scalable and smart cooling solutions. Marcus Edwards B.Sc.

Cooling on Demand - scalable and smart cooling solutions. Marcus Edwards B.Sc. Cooling on Demand - scalable and smart cooling solutions Marcus Edwards B.Sc. Schroff UK Limited Data Centre cooling what a waste of money! A 1MW data center needs 177,000,000 kwh in its lifetime of 10

More information

Rittal Cooling Solutions A. Tropp

Rittal Cooling Solutions A. Tropp 1 Rittal Cooling Solutions Presented by Adam Tropp 2 Agenda Cooling Strategies Aisle Containment Chimney Solution Airstream Management Rittal Liquid Cooling Packages Data Monitoring 3 Cooling strategies.

More information

Variable Density, Closed-Loop, Water-Cooled Data Center Solution

Variable Density, Closed-Loop, Water-Cooled Data Center Solution Variable Density, Closed-Loop, Water-Cooled Data Center Solution Overview Great Lakes Case & Cabinet Co., Inc. has worked with Naissus Thermal Management Solutions, of Toronto, Ontario to develop one of

More information

Liquid Cooling Package LCP Cooling Systems

Liquid Cooling Package LCP Cooling Systems Liquid Cooling Package LCP Cooling Systems 2 Rittal LCP Rittal The System. The whole is more than the sum of its parts. The same is true of Rittal The System. With this in mind, we have bundled our innovative

More information

Evaporative free air cooling technology Providing evaporative free air cooling solutions.

Evaporative free air cooling technology Providing evaporative free air cooling solutions. Evaporative free air cooling technology Providing evaporative free air cooling solutions. Creating an effective workspace environment data centre free air cooling technology FreeCool - Evaporative Free

More information

Industry leading low energy evaporative fresh air cooling.

Industry leading low energy evaporative fresh air cooling. Industry leading low energy evaporative fresh air cooling. Freecool Evaporative Free Air Cooling by Workspace Technology delivers innovative low energy cooling for a range of applications including data

More information

MEASURE MONITOR UNDERSTAND

MEASURE MONITOR UNDERSTAND MEASURE MONITOR UNDERSTAND Presented by Alistair Hunt Energy Monitoring, Measurement metrics Where and What 1 History & Background Company Timeline 18 Years Comrac & Sinetica founded 15 Years Raritan Integration

More information

INNOVATE DESIGN APPLY.

INNOVATE DESIGN APPLY. INNOVATE DESIGN APPLY By A whole new cooling experience The Motivair ChilledDoor Rack Cooling System targets the critical cooling requirements of today s modern server rack designs. As technology continues

More information

Liebert DCW CATALOGUE

Liebert DCW CATALOGUE Liebert DCW CATALOGUE Chilled Water-Based High Density Cooling For The Data Center LIEBERT DCW Flexible Approaches For Energy Efficient Cooling Save up to 70% in cooling energy usage Data center managers

More information

Data Center Energy Savings By the numbers

Data Center Energy Savings By the numbers Data Center Energy Savings By the numbers Chris Kurkjian, PE HP Critical Facility Services provided by EYP Mission Critical Facilities 2008 Hewlett-Packard Development Company, L.P. The information contained

More information

INNOVATE DESIGN APPLY.

INNOVATE DESIGN APPLY. INNOVATE DESIGN APPLY By A whole new cooling experience The Motivair ChilledDoor Rack Cooling System targets the critical cooling requirements of today s modern server rack designs. As technology continues

More information

Virtualization and consolidation

Virtualization and consolidation Virtualization and consolidation Choosing a density strategy Implementing a high-density environment Maximizing the efficiency benefit Anticipating the dynamic data center Schneider Electric 1 Topical

More information

Is Data Center Free Cooling Feasible in the Middle East? By Noriel Ong, ASEAN Eng., PMP, ATD, PQP

Is Data Center Free Cooling Feasible in the Middle East? By Noriel Ong, ASEAN Eng., PMP, ATD, PQP Is Data Center Free Cooling Feasible in the Middle East? By Noriel Ong, ASEAN Eng., PMP, ATD, PQP This case study will evaluate the feasibility of data center free cooling in the Middle East using indirect

More information

NREL Validates LCS Technology. PRESENTED BY Herb Zien CEO, LiquidCool Solutions

NREL Validates LCS Technology. PRESENTED BY Herb Zien CEO, LiquidCool Solutions NREL Validates LCS Technology PRESENTED BY Herb Zien CEO, LiquidCool Solutions Learning Objectives As much as 40% of data center power is used to circulate air, and fans in a typical 30-megawatt data center

More information

Server Room & Data Centre Energy Efficiency. Technology Paper 003

Server Room & Data Centre Energy Efficiency. Technology Paper 003 Technology Paper 003 Server Room & Data Centre Energy Efficiency Workspace Technology Limited Technology House, PO BOX 11578, Sutton Coldfield West Midlands B72 1ZB Telephone: 0121 354 4894 Facsimile:

More information

Aquaflair. Uniflair TRAC, TRAF and TRAH. Air-cooled chillers, free-cooling chillers and heat pumps with scroll compressors.

Aquaflair. Uniflair TRAC, TRAF and TRAH. Air-cooled chillers, free-cooling chillers and heat pumps with scroll compressors. Aquaflair Uniflair TRAC, TRAF and TRAH Air-cooled chillers, free-cooling chillers and heat pumps with scroll compressors 120-350kW Uniflair TRA ranges 115-350kW Air-cooled Chillers Cooling, Free cooling

More information

Liquid Cooling Package LCP Cooling Systems

Liquid Cooling Package LCP Cooling Systems Liquid Cooling Package LCP Cooling Systems 2 Rittal LCP The whole is more than the sum of its parts. The same is true of Rittal The System. With this in mind, we have bundled our innovative enclosure,

More information

REPORT. Energy Efficiency of the San Diego Supercomputer Center and Distributed Data Centers at UCSD. Prepared for:

REPORT. Energy Efficiency of the San Diego Supercomputer Center and Distributed Data Centers at UCSD. Prepared for: REPORT Energy Efficiency of the San Diego Supercomputer Center and Distributed Data Centers at UCSD Prepared for: San Diego Supercomputer Center 10100 John J Hopkins Drive San Diego, CA 92037 May 11, 2009

More information

TWO FINANCIAL IMPACT STUDIES. Seal IT Equipment Cabinets for Significant Annual Cost Savings and Simple Payback in a Few Short Months

TWO FINANCIAL IMPACT STUDIES. Seal IT Equipment Cabinets for Significant Annual Cost Savings and Simple Payback in a Few Short Months TWO FINANCIAL IMPACT STUDIES Seal IT Equipment Cabinets for Significant Annual Cost Savings and Simple Payback in a Few Short Months TWO FINANCIAL IMPACT STUDIES Seal IT Equipment Cabinets for Significant

More information

How Liquid Cooling Helped Two University Data Centers Achieve Cooling Efficiency Goals. Michael Gagnon Coolcentric October

How Liquid Cooling Helped Two University Data Centers Achieve Cooling Efficiency Goals. Michael Gagnon Coolcentric October How Liquid Cooling Helped Two University Data Centers Achieve Cooling Efficiency Goals Michael Gagnon Coolcentric October 13 2011 Data Center Trends Energy consumption in the Data Center (DC) 2006-61 billion

More information

Data center cooling evolution. The hottest way to save energy. Lucio Bustaffa: Product Development Manager BlueBox Group

Data center cooling evolution. The hottest way to save energy. Lucio Bustaffa: Product Development Manager BlueBox Group Data center cooling evolution. The hottest way to save energy Lucio Bustaffa: Product Development Manager BlueBox Group Data Center overview What s happening in the web? 2 Data Center overview What s happening

More information

Next Generation Cooling

Next Generation Cooling Next Generation Cooling Server Manufacturer Perspective Practical and Cost Effective David Moss Data Center Strategist Dell 1 Why Chip, Row, or Rack? Density? Energy Don t be scared; I don t see 50kW/rack

More information

MOLLIER DIAGRAM CAN BE IMPROVED!

MOLLIER DIAGRAM CAN BE IMPROVED! MOLLIER DIAGRAM CAN BE IMPROVED! IMPROVED BASIC COOLING CIRCUIT PERFORMANCE EFFICIENCY USING AN ECONOMISER Eng. Jonny Malachi, VP Operations, Mashav Refrigeration and Air Conditioning Engineering Ltd.

More information

glide glider kw R134a air cooled liquid chillers AND free cooling chillers FREE COOLING SHELL A C CLASS E C Energy Class RCGROUP SpA

glide glider kw R134a air cooled liquid chillers AND free cooling chillers FREE COOLING SHELL A C CLASS E C Energy Class RCGROUP SpA 99 glide air cooled liquid chillers ND free cooling chillers glider 178 1328 Energy Class More efficient + B C D E F G Less efficient R134a CLSS SHELL C E C FREE COOLING 100 air cooled liquid chiller and

More information

A Data Center Heat Removal System That Saves... 80% Discover Inertech s Award-winning Data Center Heat Removal System

A Data Center Heat Removal System That Saves... 80% Discover Inertech s Award-winning Data Center Heat Removal System A Data Center Heat Removal System That Saves... Infrastructure Power Water up to 40% up to 80% up to 85% Discover Inertech s Award-winning Data Center Heat Removal System A Cool Solution; A Breakthrough

More information

Current Data Center Design. James Monahan Sept 19 th 2006 IEEE San Francisco ComSoc

Current Data Center Design. James Monahan Sept 19 th 2006 IEEE San Francisco ComSoc Current Data Center Design James Monahan Sept 19 th 2006 IEEE San Francisco ComSoc What is the biggest facility problem in your data center? 35% 30% 25% 20% 15% Series1 10% 5% 0% Excessive heat Insufficient

More information

Running Your Data Center Under Ideal Temperature Conditions

Running Your Data Center Under Ideal Temperature Conditions TECHNICAL BRIEF Mastering Data Center Environmental Controls to Help Drive Your Bottom Line Running Your Data Center Under Ideal Temperature Conditions Challenge Many data centers waste energy using inefficient

More information

Total Modular Data Centre Solutions

Total Modular Data Centre Solutions Sector Data Centre Total Modular Data Centre Solutions www.airedale.com BRITISH MANUFACTURER ENERGY EFFICIENCY CONTROLS SERVICE TRAINING 01 Standardised Modular Designs to fit your needs Our modular system

More information

HIGH DENSITY RACK COOLING CHOICES

HIGH DENSITY RACK COOLING CHOICES WATERCOOLED HIGH PERFORMANCE COMPUTING SYSTEMS AQUILA WHITE PAPER HIGH DENSITY RACK COOLING CHOICES by Phil Hughes Reprinted with permission of Clustered Systems Company, Inc 1 THIS WHITE PAPER DISCUSSES

More information

COOLING SOLUTIONS. SmartRack Close-Coupled Cooling for IT Environments

COOLING SOLUTIONS. SmartRack Close-Coupled Cooling for IT Environments COOLING SOLUTIONS SmartRack Close-Coupled Cooling for IT Environments Efficient, flexible, manageable cooling reduces costs and simplifies installation. Efficient, flexible, manageable cooling for IT environments

More information

Liebert Economizer Cooling Solutions Reduce Cooling Costs by up to 50% Without Compromising Reliability

Liebert Economizer Cooling Solutions Reduce Cooling Costs by up to 50% Without Compromising Reliability Precision Cooling for Business-Critical Continuity TM Liebert Economizer Cooling Solutions Reduce Cooling Costs by up to 50% Without Compromising Reliability DATA CENTER SOLUTIONS For More Information:

More information

Ten Cooling Solutions to Support High-density Server Deployment. Schneider Electric Data Center Science Center White Paper #42

Ten Cooling Solutions to Support High-density Server Deployment. Schneider Electric Data Center Science Center White Paper #42 Ten Cooling Solutions to Support High-density Server Deployment Schneider Electric Data Center Science Center White Paper #42 1 Introduction 2 Introduction This paper provides 10 approaches for increasing

More information

Precision Cooling for Business-Critical Continuity. Liebert HPC-S. Designed for the Efficient Cooling of Small Data Centers

Precision Cooling for Business-Critical Continuity. Liebert HPC-S. Designed for the Efficient Cooling of Small Data Centers Precision Cooling for Business-Critical Continuity Liebert HPC-S Designed for the Efficient Cooling of Small Data Centers Liebert HPC-S: Enhanced Efficiency Freecooling Chiller Higher energy costs, limited

More information

Close-coupled cooling

Close-coupled cooling Close-coupled cooling Intelligently controlled high-performance InRow cooling for the IT environment APC TM by Schneider Electric close-coupled cooling products provide a modular, scalable, and predictable

More information

COOLING WHAT ARE THE OPTIONS AND THE PROS AND CONS FOR THE VARIOUS TYPES OF DATACENTRES SERVER AND COMMS ROOMS

COOLING WHAT ARE THE OPTIONS AND THE PROS AND CONS FOR THE VARIOUS TYPES OF DATACENTRES SERVER AND COMMS ROOMS COOLING WHAT ARE THE OPTIONS AND THE PROS AND CONS FOR THE VARIOUS TYPES OF DATACENTRES SERVER AND COMMS ROOMS Dr Jon Summers Scientific Leader in Data Centers Part-time Academic in Thermofluids at the

More information

Moving Containment Inside the Enclosure. Jeff Markle Great Lakes Case & Cabinet

Moving Containment Inside the Enclosure. Jeff Markle Great Lakes Case & Cabinet Moving Containment Inside the Enclosure Presented by Jeff Markle Great Lakes Case & Cabinet Containment Containment : To put constraint upon; to restrain; to confine; to keep within bounds Containment

More information

Data Center Trends: How the Customer Drives Industry Advances and Design Development

Data Center Trends: How the Customer Drives Industry Advances and Design Development Bablu Kazi, PE MORRISON HERSHFIELD MISSION CRITICAL Data Center Trends: How the Customer Drives Industry Advances and Design Development What does the Customer Need? Scalability P U E Latest Technology

More information

Liebert DM. High Performance, Sensible Cooling for Small Computer Rooms and Network Closets

Liebert DM. High Performance, Sensible Cooling for Small Computer Rooms and Network Closets Liebert DM High Performance, Sensible Cooling for Small Computer Rooms and Network Closets Emerson Network Power, a business of Emerson (NYSE: EMR), is a worldwide leader in infrastructure solutions across

More information

Liebert. icom Thermal System Controls Greater Data Center Protection, Efficiency & Insight

Liebert. icom Thermal System Controls Greater Data Center Protection, Efficiency & Insight Liebert icom Thermal System Controls Greater Data Center Protection, Efficiency & Insight LIEBERT icom THERMAL SYSTEM CONTROLS All for One, One for All Optimize a Single Cooling Unit With an Intelligent

More information

Liebert DSE Precision Cooling System Industry-best efficiency. Increased capacity. Ensured availability. EFFICIENCY. CAPACITY. AVAILABILITY.

Liebert DSE Precision Cooling System Industry-best efficiency. Increased capacity. Ensured availability. EFFICIENCY. CAPACITY. AVAILABILITY. Liebert DSE Precision Cooling System Industry-best efficiency. Increased capacity. Ensured availability. EFFICIENCY. CAPACITY. AVAILABILITY. Liebert DSE High-Efficiency Precision Cooling System Room-Based

More information

Data Center Design and. Management. Steve Knipple. August 1, CTO / VP Engineering & Operations

Data Center Design and. Management. Steve Knipple. August 1, CTO / VP Engineering & Operations Data Center Design and Energy Management Steve Knipple CTO / VP Engineering & Operations August 1, 2013 Agenda Introduction to EasyStreet Speaker Bio EasyStreet Sustainability Data Center 1 (Retrofit completed

More information

Liebert DCW Family Chilled Water-Based High Density Cooling For The Data Center. Precision Cooling For Business-Critical Continuity

Liebert DCW Family Chilled Water-Based High Density Cooling For The Data Center. Precision Cooling For Business-Critical Continuity Liebert DCW Family Chilled Water-Based High Density Cooling For The Data Center Precision Cooling For Business-Critical Continuity Flexible Approaches For Energy Efficient Cooling Save up to 70% in cooling

More information

Liebert XD. Cooling Solutions For High Heat Density Applications. Precision Cooling For Business-Critical Continuity

Liebert XD. Cooling Solutions For High Heat Density Applications. Precision Cooling For Business-Critical Continuity XD Cooling Solutions For High Heat Density Applications Precision Cooling For Business-Critical Continuity High Density. High Temperatures Today s data center technologies compound conventional cooling

More information

Green Sustainable Data Centres. Checklist - EU Code of Conduct on Data Centres. Annex

Green Sustainable Data Centres. Checklist - EU Code of Conduct on Data Centres. Annex Green Sustainable Data Centres Checklist - EU Code of Conduct on Data Centres Annex This course is produced under the authority of e-infranet: http://e-infranet.eu/ Course team prof. dr. Colin Pattinson,

More information

Retro-Commissioning Report

Retro-Commissioning Report 10 Retro-Commissioning Report Retro-Commissioning Retro-Commissioning is the process for identifying intrinsic operational and energy related issues in the facilities DDC system and providing a mechanism

More information

Energy Logic: Emerson Network Power. A Roadmap for Reducing Energy Consumption in the Data Center. Ross Hammond Managing Director

Energy Logic: Emerson Network Power. A Roadmap for Reducing Energy Consumption in the Data Center. Ross Hammond Managing Director Energy Logic: A Roadmap for Reducing Energy Consumption in the Data Center Emerson Network Power Ross Hammond Managing Director Agenda Energy efficiency Where We Are Today What Data Center Managers Are

More information

Reducing Energy Consumption with

Reducing Energy Consumption with Reducing Energy Consumption with Passive Cooling Ian Cathcart, RCDD Technical Support Manager Technical Support Manager Chatsworth Products, Inc. Thermal Management: Mission Critical Data center heat loads

More information

Data Center Energy and Cost Saving Evaluation

Data Center Energy and Cost Saving Evaluation Available online at www.sciencedirect.com ScienceDirect Energy Procedia 75 (2015 ) 1255 1260 The 7 th International Conference on Applied Energy ICAE2015 Data Center Energy and Cost Saving Evaluation Z.

More information

Data Center Optimized Controls

Data Center Optimized Controls Data Center Optimized Controls Controls Agenda 30 min. Emerson Control Products icom (Dynamic Thermal Optimization) 20 min. Station Rotation Station 1: Controller Challenge Station 2: Wireless Demo 5 min.

More information

PROCESS & DATA CENTER COOLING. How and Why To Prepare For What s To Come JOHN MORRIS REGIONAL DIRECTOR OF SALES

PROCESS & DATA CENTER COOLING. How and Why To Prepare For What s To Come JOHN MORRIS REGIONAL DIRECTOR OF SALES PROCESS & DATA CENTER COOLING How and Why To Prepare For What s To Come JOHN MORRIS REGIONAL DIRECTOR OF SALES CONGRATULATIONS 2 BOLD PREDICTION 3 Where We Are TODAY Computer Technology NOW advances more

More information

4. TARGETED COOLING & AIRFLOW MANAGEMENT

4. TARGETED COOLING & AIRFLOW MANAGEMENT 4.4. TARGETED COOLING & TARGETED COOLING & AIRFLOW MANAGEMENT 4.AIRFLOW TARGETED MANAGEMENTCO 76 79 80 81 82 :: targeted cooling & airflow management 4. TARGETED COOLING & AIRFLOW MANAGEMENT 4.1 - Side

More information

Liebert. CRV Row-Based Cooling Intelligent Precision Cooling For Data Center Equipment

Liebert. CRV Row-Based Cooling Intelligent Precision Cooling For Data Center Equipment Liebert CRV Row-Based Cooling Intelligent Precision Cooling For Data Center Equipment LIEBERT CRV ROW-BASED COOLING System Overview The Liebert CRV is a multi-option, precision data center cooling solution

More information

Liebert. AFC from 500 to 1700 kw. The Adiabatic Freecooling Solution with Top-Tier Availability

Liebert. AFC from 500 to 1700 kw. The Adiabatic Freecooling Solution with Top-Tier Availability Liebert AFC from 500 to 1700 kw The Adiabatic Freecooling Solution with Top-Tier Availability Liebert AFC from 500 to 1700 kw Vertiv Vertiv designs, builds and services mission critical technologies that

More information

Impact of Air Containment Systems

Impact of Air Containment Systems White Paper June 2012 WP-20 Impact of Air Containment Systems Reducing Energy Consumption Introduction: The Importance of Maintaining Data Center Cooling Energy Efficiency Data centers are mission-critical

More information

Five Strategies for Cutting Data Center Energy Costs Through Enhanced Cooling Efficiency

Five Strategies for Cutting Data Center Energy Costs Through Enhanced Cooling Efficiency Five Strategies for Cutting Data Center Energy Costs Through Enhanced Cooling Efficiency A White Paper from the Experts in Business-Critical Continuity TM Executive Summary As electricity prices and IT

More information

Excool Indirect Adiabatic and Evaporative Data Centre Cooling World s Leading Indirect Adiabatic and Evaporative Data Centre Cooling

Excool Indirect Adiabatic and Evaporative Data Centre Cooling World s Leading Indirect Adiabatic and Evaporative Data Centre Cooling Excool Indirect Adiabatic and Evaporative Data Centre Cooling World s Leading Indirect Adiabatic and Evaporative Data Centre Cooling Data Centre Solutions Expertly Engineered Indirect Adiabatic and Evaporative

More information

SMARTAISLE Intelligent, Integrated Infrastructure for the Data Center

SMARTAISLE Intelligent, Integrated Infrastructure for the Data Center SMARTAISLE Intelligent, Integrated Infrastructure for the Data Center SMARTAISLE Deploy an Efficient and Flexible Row-Based Infrastructure Efficiency. Capacity. Availability. Control. The SmartAisle infrastructure

More information

Power & Cooling Considerations for Virtualized Environments

Power & Cooling Considerations for Virtualized Environments Power & Cooling Considerations for Virtualized Environments Cisco Data Center Day 2008 31-01-2008 APC-MGE Vision & Mission OUR VISION APC-MGE products ensure availability wherever data is created, transmitted

More information

Reliability and extended operation

Reliability and extended operation CLIMAVENETA TELECOMSOLUTIONS Units for mobile telecounication applications, with free cooling and full DC Inverter technology. 1,5 20. Low operational and maintenance costs Wide range of full inverter

More information

IT COOLING DATA CENTER COOLING THE MILESTONE OF GREEN DATA CENTER COOLING TECHNOLOGY

IT COOLING DATA CENTER COOLING THE MILESTONE OF GREEN DATA CENTER COOLING TECHNOLOGY IT COOLING DATA CENTER COOLING THE MILESTONE OF GREEN DATA CENTER COOLING TECHNOLOGY IT COOLING RC for IT COOLING RC approach for perfect data center cooling THE FUTURE OF DATA CENTERS BRINGS BOTH ADVANCED

More information

FX 2 Instruction Manual

FX 2 Instruction Manual FX 2 Instruction Manual Climma Compact Version Annapolis MD USA 301 352 6962 info@veco-na.com Introduction: The FX2-DX digital controller operates onboard air conditioning equipment to provide room temperature

More information

HP Modular Cooling System: water cooling technology for high-density server installations

HP Modular Cooling System: water cooling technology for high-density server installations HP Modular Cooling System: water cooling technology for high-density server installations technical brief Abstract... 2 Introduction... 2 Data center trends... 2 Increased power demands... 3 Increased

More information

Liebert PDX from 15 to 120 kw

Liebert PDX from 15 to 120 kw Liebert PDX from 5 to 0 kw The Thermal Management Solution for Small and Medium Data Centers Electronic Expansion Valve Efficiency Digital Scroll Partial Load icom TM Control TCO Optimization Integrated

More information

Liebert. DCL up to 35 kw. Modular Rack Cooling

Liebert. DCL up to 35 kw. Modular Rack Cooling Liebert DCL up to 35 kw Modular Rack Cooling LIEBERT DCL up to 35 kw Vertiv Vertiv designs, builds and services mission critical technologies that enable the vital applications for data centers, communication

More information

PT CLIMANUSA TATA MEKADATA Citypark Business District Blok F No 05 Jl. Malibu Raya, Cengkareng Jakarta Barat Indonesia. Phone

PT CLIMANUSA TATA MEKADATA Citypark Business District Blok F No 05 Jl. Malibu Raya, Cengkareng Jakarta Barat Indonesia. Phone PT CLIMANUSA TATA MEKADATA Citypark Business District Blok F No 0 Jl. Malibu Raya, Cengkareng Jakarta Barat 70 Indonesia Phone + 4 4 www.climanusa.com Marketing features prominent presence on the world

More information

Liebert. DCL up to 35 kw. Modular Rack Cooling

Liebert. DCL up to 35 kw. Modular Rack Cooling Liebert DCL up to 35 kw Modular Rack Cooling LIEBERT DCL up to 35 kw Vertiv Vertiv designs, builds and services mission critical technologies that enable the vital applications for data centers, communication

More information

Liebert PDX from 15 to 120 kw

Liebert PDX from 15 to 120 kw Liebert PDX from 5 to 0 kw The Thermal Management Solution for Small and Medium Data Centers Electronic Expansion Valve Efficiency Digital Scroll Partial Load icom Control TCO Optimization Integrated Solution

More information

Liebert PDX. The Cooling Solution for Small and Medium Data Centers. Digital Scroll. Part Load. Competent Partner Efficiency

Liebert PDX. The Cooling Solution for Small and Medium Data Centers. Digital Scroll. Part Load. Competent Partner Efficiency Liebert PDX The Cooling Solution for Small and Medium Data Centers Competent Partner Efficiency Digital Scroll Part Load icom Control TCO Optimization Integrated Solution Operational Cost Reduction New

More information

HIGH DENSITY DATACOM INTEGRATED COOLING SYSTEM.

HIGH DENSITY DATACOM INTEGRATED COOLING SYSTEM. HIGH DENSITY DATACOM INTEGRATED COOLING SYSTEM. SYSTEM LOGICA is the most advanced alternative to the problem of cooling of server rooms MONTAIR is the trademark which represents excellence on the market

More information