Planning for Liquid Cooling Patrick McGinn Product Manager, Rack DCLC
|
|
- Sybil Riley
- 5 years ago
- Views:
Transcription
1 Planning for Liquid Cooling Patrick McGinn Product Manager, Rack DCLC February 3 rd, 2015
2 Expertise, Innovation & Delivery 13 years in the making with a 1800% growth rate in the last 5 years 44 patents, 22 patents pending, ISO9001 certification, global supply chain Proven technology Shipping 2,000 systems per month into data centers Shipping 30,000 50,000 units per month to desktop market > 1,850,000+ units sold Global service and supply network Founding member of the Demand Liquid Alliance (DLA) Liquid cooled Intel s Top500 and Green500 cluster
3 A Modular Approach to Liquid Cooling Rack DCLC Solutions Server Module Patented cold plate technology supports multiple combinations of CPUs/GPUs and other types of interposers, heat pipes, or heat spreaders. Manifold Module Reliable stainless steel manifolds employing dry break, quick connect technology in horizontal or vertical chassis, blades or any other server array. Heat Exchange Module Your choice of heat exchange module: Liquid-to-Air or Liquid-to-Liquid. FACILITY WATER NO FACILITY WATER
4 CASE STUDY: Cooling a Supercomputer The Cherry Creek Cluster HPC Setup CoolIT Rack DCLC AHx35 (no facility water) Supermicro FatTwin (4-node GPU front I/O) o 7 chassis per rack o 28 servers per rack Intel Xeon Processors and Coprocessors o 3x Intel Xeon Phi and 2x Intel Xeon CPU s o Featured 9,936 cores o TrueScale Infiniband Results Achieved peak performance of Teraflops Cluster consumed a total of only 74.25kW of power Ranked #400 on Top500 Supercomputers list Ranked #41 on Green500 list Cluster ran live at SC 13 in Denver, CO (as pictured), now housed at SWITCH datacenter for UNLV , CoolIT Systems. All right reserved.
5 A Modular Approach to Liquid Cooling Cooling solutions for all IT demands
6 Why Liquid Cooling? More IT equipment in less space Source: Emerson Network, Data Center 2025 Report, 2014
7 Why Liquid Cooling? Trending towards change Source: Emerson Network, Data Center 2025 Report, 2014
8 Why Liquid Cooling? The key advantages of using liquid cooling Facilitates peak performance for higher powered or overclocked processors Provides a significant reduction in total data center energy consumed Enables extremely high rack densities
9 Access Higher Performance Potential Team EPCC wins Highest Linpack at ISC 14 Student Cluster Competition Secret weapon: LIQUID COOLING (Rack DCLC AHx20) Score: teraflops (or 3.38TFLOP/s per kw) 1st time a team has broken the 10 TFLOP/s barrier within the competition s 3kW power limit Estimated ranking #4 on Green500! , CoolIT Systems. All right reserved.
10 Energy Efficient Data Centers Choices regarding POWER, PACKAGING, COOLING, & ENERGY RECOVERY in data centers drive TCO. THE POWER OF H 2 0 The cooling power in a glass of water is the equivalent to a room full of air , CoolIT Systems. All right reserved.
11 Energy Efficient Data Centers Choices regarding POWER, PACKAGING, COOLING, & ENERGY RECOVERY in data centers drive TCO. Reduce or Eliminate CRAH / CRAC / Chiller Using ASHRAE W3/W4 water and economizing in concert Reduce Server Fan Count 76% reduction in fan power 150 watts per server!! (*CoolIT Rack DCLC, Supermicro Twin 2 ) CPU and DIMM s kept below 60C at 100% CPU utilization Reduce Leakage Current 10% savings! , CoolIT Systems. All right reserved.
12 Densify and increase rack utilization! Full racks of liquid cooled equipment deliver more compute in less space and use less air cooling 2u HEX Switch 2u HEX Switch *HEX is row Switch based CDU 16 kw 32 kw 8 kw , CoolIT Systems. All right reserved.
13 Planning For Liquid Cooling Using Consistent Language Liquid Cooling Classes Facility Water (Celsius) Main Cooling Equipment (How Water temperature made) Supplemental Cooling Equipment IT Equipment Availability Cool IT Systems Rack DCLC W W Chiller & Cooling Tower Water-side Economizer Chiller Now Available W Cooling Tower Chiller W Water-side Economizer (w/ Dry Cooler or Cooling Tower) Nothing Becoming Available, dependent on Future Demand W5 > 45 Building Heating System Cooling Tower Not for HPC Source: 2011 Thermal Guidelines for Liquid Cooled Data Processing Environments (ASHRAE TC 9.9)
14 Why Liquid Cooling? Various Technologies Direct Contact Liquid Cooling Safe and reliable way to remove high % of heat Rigid copper or flexible plastic Centralized or distributed pumping Plastic or metal quick disconnects Tied to a single IT architecture? CoolIT Rack DCLC IBM Power 575 Hydro-Cluster Fujitsu/LSI 16 core SPARC64-IXfx Bullx DLC B720 compute blade
15 Why Liquid Cooling? Various Technologies Single-Phase Immersion Mineral bath, 100% load capture Change spinning disk drives to solid state drives Relocate optical connections Green Revolution Cooling Iceotope Two-Phase Immersion Mostly driven by 3M with the Novec series Early success in alternative markets CoolIT Two-Phase Immersion Study, 2014
16 Why Liquid Cooling? Various Technologies Rear-Door 100% load capture, room neutral Active or passive Single-phase or two-phase High flow of chilled water Level of efficiency depends on environment
17 Why Liquid Cooling? Where to start Reliability Material compatibility Fluid chemistry Fluid discharge Serviceability Access to standard server components Special tools and knowledge for new components Does it require special handling Required Infrastructure Changes Can the liquid cooling be deployed in your current white space? Can the liquid cooling be deployed in you current rack? Control & Monitoring Alarm systems for leak, flow, and temp Reporting and logging of data Language and availability (SNMP, IPMI, Web Server, etc.)
18 Why Liquid Cooling? Installation and Maintenance Installation Appropriate stakeholders onsite (IT, Facilities, Manufacturer) Review of plan, pre-commissioning checklist If retrofit, is uptime affected? Commissioning IT and Infrastructure staff onsite Understand the system and how to troubleshoot Appropriate functional tests completed Set up alarm parameters Service & Maintenance Check early for fluid chemistry and fouling What is the new protocol for cooling device?
19 Reference Groups The Green Grid Liquid Cooling Work Group ASHRAE Technical Committee EE HPC Working Group Liquid Cooling Commissioning
20 Thank you!
Product Guide. Direct Contact Liquid Cooling Industry leading data center solutions for HPC, Cloud and Enterprise markets.
Product Guide Direct Contact Liquid Cooling Industry leading data center solutions for HPC, Cloud and Enterprise markets. www.coolitsystems.com Phone: +1 403.235.4895 The Future of Data Center Cooling
More informationReliable Direct Liquid Cooling for the world's most demanding Data Centers.
Reliable Direct Liquid Cooling for the world's most demanding Data Centers www.coolitsystems.com sales@coolitsystems.com 1-866-621-2665 Unlocking Data Center Potential with Rack DCLC CoolIT Systems reliable
More informationSTULZ Micro DC. with Chip-to-Atmosphere TM Liquid to Chip Cooling
STULZ Micro DC with Chip-to-Atmosphere TM Liquid to Chip Cooling STULZ Micro DC Data center professionals and communication service providers (CSPs) face an increasingly difficult world. The continued
More informationReliable Direct Liquid Cooling for the world's most demanding Data Centers.
Reliable Direct Liquid Cooling for the world's most demanding Data Centers www.coolitsystems.com sales@coolitsystems.com Unlocking Data Center Potential with Rack DCLC CoolIT Systems Rack DCLC solutions
More informationReliable Direct Liquid Cooling for the world's most demanding Data Centers.
Reliable Direct Liquid Cooling for the world's most demanding Data Centers www.coolitsystems.com sales@coolitsystems.com 1-866-621-2665 Unlocking Data Center Potential with Rack DCLC CoolIT Systems Rack
More informationHybrid Warm Water Direct Cooling Solution Implementation in CS300-LC
Hybrid Warm Water Direct Cooling Solution Implementation in CS300-LC Roger Smith Mississippi State University Giridhar Chukkapalli Cray, Inc. C O M P U T E S T O R E A N A L Y Z E 1 Safe Harbor Statement
More informationPassive RDHx as a Cost Effective Alternative to CRAH Air Cooling. Jeremiah Stikeleather Applications Engineer
Passive RDHx as a Cost Effective Alternative to CRAH Air Cooling Jeremiah Stikeleather Applications Engineer Passive RDHx as a Cost Effective Alternative to CRAH Air Cooling While CRAH cooling has been
More informationFREEING HPC FROM THE DATACENTRE
FREEING HPC FROM THE DATACENTRE ku:l sistem TM COOLING REDEFINED www.iceotope.com ku:l sistem removes the need for inefficient air cooling technologies FREEING HPC FROM THE DATACENTRE Iceotope s patented
More informationSystem Overview. Liquid Cooling for Data Centers. Negative Pressure Cooling Without Risk of Leaks
Liquid Cooling for Data Centers System Overview The Chilldyne Cool-Flo System is a direct-to-chip liquid cooling system that delivers coolant under negative pressure. Chilldyne s technologies were designed
More informationCooling Solutions & Considerations for High Performance Computers
Cooling Solutions & Considerations for High Performance Computers White Paper 6 Revision 1 By Rich Whitmore Executive summary The recent advances in high performance computing have driven innovations not
More information18 th National Award for Excellence in Energy Management. July 27, 2017
18 th National Award for Excellence in Energy Management July 27, 2017 ICICI Bank, Data Centre, August Hyderabad 30 & 31, 2017 ICICI Bank - Revolution in Digital Banking Over 100,000 Digital POS in 4 months
More informationLCS Value Proposition November 2014
LCS Value Proposition November 2014 Data Center Trends 2014 Improving Data Center Power Efficiency & Reducing Carbon Footprint Initiatives for raising data center temperatures Data center upgrades for
More informationResults of Study Comparing Liquid Cooling Methods
School of Mechanical Engineering FACULTY OF ENGINEERING Results of Study Comparing Liquid Cooling Methods Dr Jon Summers (J.L.Summers@Leeds.Ac.UK) Institute of ThermoFluids (itf) 54th HPC User Forum, September
More informationHIGH DENSITY RACK COOLING CHOICES
WATERCOOLED HIGH PERFORMANCE COMPUTING SYSTEMS AQUILA WHITE PAPER HIGH DENSITY RACK COOLING CHOICES by Phil Hughes Reprinted with permission of Clustered Systems Company, Inc 1 THIS WHITE PAPER DISCUSSES
More informationEnergy Efficiency and WCT Innovations
Energy Efficiency and WCT Innovations Zeeshan Kamal Siddiqi HPC Leader Middle East, Turkey and Africa (META) Lenovo 2017 Lenovo. All rights reserved. Why do we have a problem? Higher TDP Processors Data
More informationCAS 2K13 Sept Jean-Pierre Panziera Chief Technology Director
CAS 2K13 Sept. 2013 Jean-Pierre Panziera Chief Technology Director 1 personal note 2 Complete solutions for Extreme Computing b ubullx ssupercomputer u p e r c o p u t e r suite s u e Production ready
More informationDATA CENTER LIQUID COOLING
DATA CENTER LIQUID COOLING EFFICIENT, EFFECTIVE, SUSTAINABLE What is Liquid Cooling? Key Trends & Potential Inhibitors Why are Many Owner/Operators Making the Move? Types of Liquid Cooling Solutions Liquid
More informationBENEFITS OF ASETEK LIQUID COOLING FOR DATA CENTERS
BENEFITS OF ASETEK LIQUID COOLING FOR DATA CENTERS Asetek has leveraged its expertise as the world-leading provider of efficient liquid cooling systems to create its RackCDU and ISAC direct-to-chip liquid
More informationMSYS 4480 AC Systems Winter 2015
MSYS 4480 AC Systems Winter 2015 Module 12: DATA CENTERS By Satwinder Singh 14/05/2015 1 Data Centers Data Centers are specialized environments that safeguard your company's most valuable equipment and
More informationFuture of Cooling High Density Equipment. Steve Madara Vice President and General Manager Liebert Precision Cooling Business Emerson Network Power
Future of Cooling High Density Equipment Steve Madara Vice President and General Manager Liebert Precision Cooling Business Emerson Network Power Agenda Issues facing the Data Center Managing the explosive
More informationEfficiency of Data Center cooling
Efficiency of Data Center cooling Comparison of data room layouts and cooling systems Bohumil Cimbal Product manager for Cooling Systems in CONTEG Company Objective Basic questions between investor and
More informationPROCESS & DATA CENTER COOLING. How and Why To Prepare For What s To Come JOHN MORRIS REGIONAL DIRECTOR OF SALES
PROCESS & DATA CENTER COOLING How and Why To Prepare For What s To Come JOHN MORRIS REGIONAL DIRECTOR OF SALES CONGRATULATIONS 2 BOLD PREDICTION 3 Where We Are TODAY Computer Technology NOW advances more
More informationVienna Scientific Cluster s The Immersion Supercomputer: Extreme Efficiency, Needs No Water
CASE STUDY Vienna Scientific Cluster s The Immersion Supercomputer: Extreme Efficiency, Needs No Water Find Out How GRC s Technology Helped VSC Get More Compute for Less. Authors: Toshio Endo, Akira Nukada,
More informationMission Critical Facilities & Technology Conference November 3, 2011 Cooling 101. Nick Gangemi Regional Sales Manager Data Aire
Mission Critical Facilities & Technology Conference November 3, 2011 Cooling 101 Nick Gangemi Regional Sales Manager Data Aire Agenda Exactly what are we talking about ASHRAE TC 9.9 Design best practices
More informationNREL Validates LCS Technology. PRESENTED BY Herb Zien CEO, LiquidCool Solutions
NREL Validates LCS Technology PRESENTED BY Herb Zien CEO, LiquidCool Solutions Learning Objectives As much as 40% of data center power is used to circulate air, and fans in a typical 30-megawatt data center
More informationINNOVATE DESIGN APPLY.
INNOVATE DESIGN APPLY By A whole new cooling experience The Motivair ChilledDoor Rack Cooling System targets the critical cooling requirements of today s modern server rack designs. As technology continues
More informationINNOVATE DESIGN APPLY.
INNOVATE DESIGN APPLY By A whole new cooling experience The Motivair ChilledDoor Rack Cooling System targets the critical cooling requirements of today s modern server rack designs. As technology continues
More informationCHILLED WATER. HIGH PRECISION AIR CONDITIONERS, FROM 7 TO 211 kw
IT COOLING CLOSE CONTROL AIR CONDITIONERS CHILLED WATER HIGH PRECISION AIR CONDITIONERS, FROM 7 TO 211 kw 3 Versions available Single chilled water coil Double chilled water coil High temperature IT COOLING
More informationRittal Cooling Solutions A. Tropp
1 Rittal Cooling Solutions Presented by Adam Tropp 2 Agenda Cooling Strategies Aisle Containment Chimney Solution Airstream Management Rittal Liquid Cooling Packages Data Monitoring 3 Cooling strategies.
More informationA Data Center Heat Removal System That Saves... 80% Discover Inertech s Award-winning Data Center Heat Removal System
A Data Center Heat Removal System That Saves... Infrastructure Power Water up to 40% up to 80% up to 85% Discover Inertech s Award-winning Data Center Heat Removal System A Cool Solution; A Breakthrough
More informationLANL High Performance Computing Facilities Operations. Rick Rivera and Farhad Banisadr. Facility Data Center Management
Slide-1 LANL High Performance Computing Facilities Operations Rick Rivera and Farhad Banisadr Facility Data Center Management Division Slide-2 Outline Overview - LANL Computer Data Centers Power and Cooling
More information7 Best Practices for Increasing Efficiency, Availability and Capacity. XXXX XXXXXXXX Liebert North America
7 Best Practices for Increasing Efficiency, Availability and Capacity XXXX XXXXXXXX Liebert North America Emerson Network Power: The global leader in enabling Business-Critical Continuity Automatic Transfer
More informationDatacenter Efficiency Trends. Cary Roberts Tellme, a Microsoft Subsidiary
Datacenter Efficiency Trends Cary Roberts Tellme, a Microsoft Subsidiary Power Slashing Tools P3 Kill-A-WATT Measures min, max, and instantaneous voltage and current draw Calculates power (watts), kilowatt
More informationWater-Cooling and its Impact on Performance and TCO
Water-Cooling and its Impact on Performance and TCO Matthew T. Ziegler Director, HPC and AI WW BU System Strategy and Architecture mziegler@lenovo.com 2016 Lenovo Internal. All rights reserved. 1 Agenda
More informationINCREASE IT EFFICIENCY, REDUCE OPERATING COSTS AND DEPLOY ANYWHERE
www.iceotope.com DATA SHEET INCREASE IT EFFICIENCY, REDUCE OPERATING COSTS AND DEPLOY ANYWHERE BLADE SERVER TM PLATFORM 80% Our liquid cooling platform is proven to reduce cooling energy consumption by
More informationHow Liquid Cooling Helped Two University Data Centers Achieve Cooling Efficiency Goals. Michael Gagnon Coolcentric October
How Liquid Cooling Helped Two University Data Centers Achieve Cooling Efficiency Goals Michael Gagnon Coolcentric October 13 2011 Data Center Trends Energy consumption in the Data Center (DC) 2006-61 billion
More informationECOBAY: Closed loop water cooled server cabinet for data centers
ECOBAY: Closed loop water cooled server cabinet for data centers ELECTRONICS MANUFACTURING SERVICES Communications Computing Multimedia & Consumer Industrial & Semiconductor Defense & Aerospace Medical
More informationChilled Water Computer Room Air Handler (CRAH) Critical Infrastructure for the World s Leading Data Centers
Chilled Water Computer Room Air Handler (CRAH) Critical Infrastructure for the World s Leading Data Centers DATA CENTER COOLING EXPERTISE Data Center managers have unique needs. Nortek Air Solutions listens
More informationIt`s the size of science & research...
It`s the size of science & research... Arno Ziebart www..com ...which makes a cluster really big. It s the type of management...which makes clusters really smart. ...which makes a cluster really big. It
More informationGreen IT and Green DC
Green IT and Green DC Alex SL Tay Regional Service Product Line Manager Site & Facilities Services, IBM ASEAN 1 What our clients are telling us We are running out of space in our data center We have environmental
More informationData Sheet FUJITSU Server PRIMERGY CX400 M1 Scale out Server
Data Sheet FUJITSU Server Scale out Server Data Sheet FUJITSU Server Scale out Server Scale-Out Smart for HPC, Cloud and Hyper-Converged Computing FUJITSU Server PRIMERGY will give you the servers you
More informationHot vs Cold Energy Efficient Data Centers. - SVLG Data Center Center Efficiency Summit
Hot vs Cold Energy Efficient Data Centers - SVLG Data Center Center Efficiency Summit KC Mares November 2014 The Great Debate about Hardware Inlet Temperature Feb 2003: RMI report on high-performance data
More informationTSUBAME-KFC : Ultra Green Supercomputing Testbed
TSUBAME-KFC : Ultra Green Supercomputing Testbed Toshio Endo,Akira Nukada, Satoshi Matsuoka TSUBAME-KFC is developed by GSIC, Tokyo Institute of Technology NEC, NVIDIA, Green Revolution Cooling, SUPERMICRO,
More informationCooling. Highly efficient cooling products for any IT application. For More Information: (866) DATA CENTER SOLUTIONS
Cooling > Highly efficient cooling products for any IT application. DATA CENTER SOLUTIONS For More Information: (866) 787-3271 Sales@PTSdcs.com End-to-End Cooling Solutions from the Closet to the Data
More informationIs Data Center Free Cooling Feasible in the Middle East? By Noriel Ong, ASEAN Eng., PMP, ATD, PQP
Is Data Center Free Cooling Feasible in the Middle East? By Noriel Ong, ASEAN Eng., PMP, ATD, PQP This case study will evaluate the feasibility of data center free cooling in the Middle East using indirect
More informationINT 492 : Selected Topic in IT II (Data Center System Design) 3(3-0-6)
INT 492 : Selected Topic in IT II (Data Center Design) 3(3-0-6) การออกแบบระบบศ นย สารสนเทศ Overview The American Society of Heating, Refrigeration and Air-Conditioning Engineers (ASHRAE) Technical Committee
More informationOptimiz Chilled January 25, 2013
Optimiz zing Existing Data Center Chilled Water Plants January 25, 2013 This White Paper describes factors to be consideredd when optimizing an existing data center chilledd water plant. Authored by Michael
More informationCooling System Considerations for High Density Colocation and Enterprise Data Centers
Cooling System Considerations for High Density Colocation and Enterprise Data Centers By Rich Whitmore Executive summary The recent advances in computer technology and the growing adoption of high performance
More informationWelcome Association of Energy Engineers to the Microsoft Technology Center
Welcome Association of Energy Engineers to the Microsoft Technology Center Today s Agenda 10:00 10:30 What s new in data center energy efficiency planning and implementation? 10:30 11:00 ASHRAE data center
More informationEnergy Efficient Data Centers
IBM Systems and Technology Group Lab Services Energy Efficient Data Centers Steven Ahladas IBM Corp ahladas@us.ibm.com Keeping our clients in the race. All trends going the same way. IT Servers were an
More informationHPC Solutions in High Density Data Centers
Executive Report HPC Solutions in High Density Data Centers How CyrusOne s Houston West data center campus delivers the highest density solutions to customers With the ever-increasing demand on IT resources,
More informationLiebert DCW Family Chilled Water-Based High Density Cooling For The Data Center. Precision Cooling For Business-Critical Continuity
Liebert DCW Family Chilled Water-Based High Density Cooling For The Data Center Precision Cooling For Business-Critical Continuity Flexible Approaches For Energy Efficient Cooling Save up to 70% in cooling
More informationRear Door Heat Exchanger
Vinod Kamath Power and Thermal Engineering Sep 16, 2005 Problem Statement Rack Power loads are high due to increased compute density. The impact is seen in datacenters as high inlet air temperatures to
More information100% Warm-Water Cooling with CoolMUC-3
100% Warm-Water Cooling with CoolMUC-3 No chillers, no fans, no problems Axel Auweter MEGWARE CTO Workshop on Energy Efficiency in HPC May 30, 2018, Ljubljana!1 MEGWARE Computer Vertrieb und Service GmbH
More informationWHITE PAPER. Oil Immersion Cooling for Today s Data Centers. An analysis of the technology and its business
WHITE PAPER Oil Immersion Cooling for Today s Data Centers An analysis of the technology and its business In response to a growing demand for computing power and technological advancement, server densities
More informationPhil Tuma, Application Development Engineer John Gross, Mechanical Engineering Director Kar-Wing Lau, CEO Charles Benge, Director Mission Critical
E n g i n e e r i n g W o r k s h o p : A d v a n c e d C o o l i n g S o l v i n g t h e E n e r g y C h a l l e n g e t h r o u g h I n n o v a t i o n s i n D a t a C e n t e r C o o l i n g 3m.com/immersion
More informationAir Containment Design Choices and Considerations
Air Containment Design Choices and Considerations Brad J. Murphy, A.Sc.T., ATS, DCDC, DCEP, Principal Racon Data Centres Introduction Introduction Air containment design must consider many different factors
More informationCo-designing an Energy Efficient System
Co-designing an Energy Efficient System Luigi Brochard Distinguished Engineer, HPC&AI Lenovo lbrochard@lenovo.com MaX International Conference 2018 Trieste 29.01.2018 Industry Thermal Challenges NVIDIA
More informationThermal management. Thermal management
Thermal management Thermal management Managing thermal loads is a major challenge for all Data Centre operators. Effecting proper control of the thermal environment drives energy consumption and ultimately
More informationPower & Cooling Considerations for Virtualized Environments
Power & Cooling Considerations for Virtualized Environments Cisco Data Center Day 2008 31-01-2008 APC-MGE Vision & Mission OUR VISION APC-MGE products ensure availability wherever data is created, transmitted
More informationCooling on Demand - scalable and smart cooling solutions. Marcus Edwards B.Sc.
Cooling on Demand - scalable and smart cooling solutions Marcus Edwards B.Sc. Schroff UK Limited Data Centre cooling what a waste of money! A 1MW data center needs 177,000,000 kwh in its lifetime of 10
More informationDigital Realty Data Center Solutions Digital Chicago Datacampus Franklin Park, Illinois Owner: Digital Realty Trust Engineer of Record: ESD Architect
Digital Realty Data Center Solutions Digital Chicago Datacampus Franklin Park, Illinois Owner: Digital Realty Trust Engineer of Record: ESD Architect of Record: SPARCH Project Overview The project is located
More informationLRZ SuperMUC One year of Operation
LRZ SuperMUC One year of Operation IBM Deep Computing 13.03.2013 Klaus Gottschalk IBM HPC Architect Leibniz Computing Center s new HPC System is now installed and operational 2 SuperMUC Technical Highlights
More informationSchneider Electric Cooling Portfolio. Jim Tubbesing Heath Wilson APC/Schneider North Texas Rep Tubbesing Solutions
Schneider Electric Cooling Portfolio Jim Tubbesing Heath Wilson APC/Schneider North Texas Rep Tubbesing Solutions Data Center Cooling Agenda 1. How to size data center, server rooms, IDF rooms, etc in
More informationGreen IT. Finding Practical Efficiencies. Infrastructure Planning and Facilities. Green IT: Finding Practical Efficiencies
Green IT Finding Practical Infrastructure Planning and Facilities Dan Francis dfrancis@ipf.msu.edu David Graff dsgraff@ipf.msu.edu William Lakos wjlakos@ipf.msu.edu 1 2 MSU Historical Energy Efficiency
More informationEnergy Logic: Emerson Network Power. A Roadmap for Reducing Energy Consumption in the Data Center. Ross Hammond Managing Director
Energy Logic: A Roadmap for Reducing Energy Consumption in the Data Center Emerson Network Power Ross Hammond Managing Director Agenda Energy efficiency Where We Are Today What Data Center Managers Are
More informationTotal Modular Data Centre Solutions
Sector Data Centre Total Modular Data Centre Solutions www.airedale.com BRITISH MANUFACTURER ENERGY EFFICIENCY CONTROLS SERVICE TRAINING 01 Standardised Modular Designs to fit your needs Our modular system
More informationCombining Cold Aisle Containment with Intelligent Control to Optimize Data Center Cooling Efficiency
A White Paper from the Experts in Business-Critical Continuity TM Combining Cold Aisle Containment with Intelligent Control to Optimize Data Center Cooling Efficiency Executive Summary Energy efficiency
More informationHPC/Advanced Cooling Track. Rolf Brink/CEO/Asperitas
HPC/Advanced Cooling Track Advanced Cooling Optimising for immersion Rolf Brink/CEO/Asperitas Rolf.Brink@ocproject.net +31 88 96 000 00 www.asperitas.com IMMERSED COMPUTING : AIC24 100% Removal of heat
More informationReducing Data Center Cooling Costs through Airflow Containment
FEATURE Reducing Data Center Cooling Costs through Airflow Containment Implementing a containment solution in the data center costs much less than the alternatives of adding air handlers or other supplemental
More informationHIGH DENSITY DATACOM INTEGRATED COOLING SYSTEM.
HIGH DENSITY DATACOM INTEGRATED COOLING SYSTEM. SYSTEM LOGICA is the most advanced alternative to the problem of cooling of server rooms MONTAIR is the trademark which represents excellence on the market
More informationOptimizing Cooling Performance Of a Data Center
ASHRAE www.ashrae.org. Used with permission from ASHRAE Journal. This article may not be copied nor distributed in either paper or digital form without ASHRAE s permission. For more information about ASHRAE,
More informationIBM Symposium Data Center Cooling. EC Systems for HVAC architecture and Direct air Cabinet Cooling
IBM Symposium 2008 Data Center Cooling EC Systems for HVAC architecture and Direct air Cabinet Cooling Presented by David J. Spofford Product Manager IT/Telecomm 1 Agenda Data Center trends for IT and
More informationData Centers. The Environment. December The State of Global Environmental Sustainability in Data Center Design
Data Centers & The Environment The State of Global Environmental Sustainability in Data Center Design December 2018 Today s Data Centers Data centers have a huge impact on the world we live in. Today they
More informationIT infrastructure Next level for data center. Rittal The System Yavor Panayotov Data center Day
IT infrastructure Next level for data center Rittal The System Yavor Panayotov Data center Day - 2018 1 Rittal The System - Solutions Enclosures Enclosures Small enclosures Command Panel & support arm
More informationHigh Density Cooling Solutions that work from Knurr Kris Holla
High Density Cooling Solutions that work from Knurr Kris Holla The Heat Goes On Ó by Knürr A An International Company Ranked #3 in the world Founded 1931 Strong international setting in over 32 countries
More informationLiebert DCW CATALOGUE
Liebert DCW CATALOGUE Chilled Water-Based High Density Cooling For The Data Center LIEBERT DCW Flexible Approaches For Energy Efficient Cooling Save up to 70% in cooling energy usage Data center managers
More informationIXcellerate Moscow One Datacentre - Phase 1 & 2 Overview
Contents 1. Document Purpose... 2 2. Facility Overview... 2 2.1 Technical Space... 2 2.2 Load Density... 2 2.3 Resilience... 2 2.4 Engineering Plant Maintenance & Service Restoration... 3 3. Engineering
More informationSwitch to Perfection
Switch to Perfection Traditional Data Centre - Temperatures Ideal Air Temperature: 22 C Chilled Water: 7-9 C Heat Load per Rack: Up to 4,5 Chilling & Pump Set The challenge a thermal image Front View of
More informationNext Generation Cooling
Next Generation Cooling Server Manufacturer Perspective Practical and Cost Effective David Moss Data Center Strategist Dell 1 Why Chip, Row, or Rack? Density? Energy Don t be scared; I don t see 50kW/rack
More informationASHRAE Data Center Standards: An Overview
Mission Critical Facilities ASHRAE Data Center Standards: An Overview 10012 North Dale Mabry Highway Suite 109 Tampa, FL 33618 813-792-6009 www.pergravis.com Presenter: Steve Ritzi, CDCE Pergravis is a
More informationSmart Data Centres. Robert M Pe, Data Centre Consultant HP Services SEA
Smart Data Centres Robert M Pe, Data Centre Consultant Services SEA 2006 Hewlett-Packard Development Company, L.P. The information contained herein is subject to change without notice Content Data center
More informationAPC InRow Cooler Prototype Initial Report - Test Setup Verification. H. Coles, S. Greenberg Contributing: J. Bean (APC) November 18, 2011
APC InRow Cooler Prototype Initial Report - Test Setup Verification H. Coles, S. Greenberg Contributing: J. Bean (APC) November 18, 2011 1 Introduction Contents Technology Description/Attributes Installation
More informationRecapture Capacity for Existing. and Airflow Optimization
Recapture Capacity for Existing Data Centers Through Cooling and Airflow Optimization Introduction Challenges and Trends Agenda Cooling & Airflow Optimization Takeaways Learning Objectives Recognize opportunities
More informationProduct Brochure DENCO Close Control Units Row-DENCO. High Density Cooling for Data Centres
Product Brochure DENCO Close Control Units Row-DENCO High Density Cooling for Data Centres Data Centre Cooling Through a history in close control, we have developed a broad and deep understanding of how
More informationData Sheet Fujitsu Server PRIMERGY CX400 M1 Compact and Easy
Data Sheet Fujitsu Server Compact and Easy Data Sheet Fujitsu Server Compact and Easy Scale-Out Smart for HPC, Cloud and Hyper-Converged Computing The Fujitsu Server helps to meet the immense challenges
More informationWhere s the Heat Coming From. Leland Sparks Global Account Technical Consultant Belden
Where s the Heat Coming From Leland Sparks Global Account Technical Consultant Belden What is the greatest DC challenge you face? Air Flow to Heat Load Relation Server Inlet Fans Chips Outlet LOAD Dell
More informationVariable Density, Closed-Loop, Water-Cooled Data Center Solution
Variable Density, Closed-Loop, Water-Cooled Data Center Solution Overview Great Lakes Case & Cabinet Co., Inc. has worked with Naissus Thermal Management Solutions, of Toronto, Ontario to develop one of
More informationDATA CENTER AIR HANDLING COOLING SOLUTIONS
DATA CENTER AIR HANDLING COOLING SOLUTIONS World-class performance and reliability from YORK As data storage and protection needs grow, so can costs and complexity. That s why having the right partner
More informationData Center Temperature Design Tutorial. Ian Seaton Chatsworth Products
Data Center Temperature Design Tutorial Ian Seaton Chatsworth Products What are we going to do today? Explore a process for determining what data center operating temperature will deliver the best total
More informationENCLOSURE HEAT DISSIPATION
ENCLOSURE HEAT DISSIPATION DATA CENTER SOLUTIONS A White Paper by Great Lakes Case & Cabinet Company www.werackyourworld.com 814.734.7303 Page 2 Introduction Dangerous heat levels inside an enclosure threaten
More informationHow to Increase Data Center Efficiency
How to Increase Data Center Efficiency Shivani Shukla Potkar Product Marketing Manager Pentair Electronics Protection High cooling efficiency & and reduced power consumption enhances the balance between
More informationData Center Trends: How the Customer Drives Industry Advances and Design Development
Bablu Kazi, PE MORRISON HERSHFIELD MISSION CRITICAL Data Center Trends: How the Customer Drives Industry Advances and Design Development What does the Customer Need? Scalability P U E Latest Technology
More informationPrefabricated Data Center Solutions: Coming of Age
Prefabricated Data Center Solutions: Coming of Age Steven Carlini - Global Data Center Marketing Director April 2014 Schneider Electric 1 Schneider Electric 2 Your ability to compete relies on the design,
More informationSaving Energy with Free Cooling and How Well It Works
Saving Energy with Free Cooling and How Well It Works Brent Draney HPC Facility Integration Lead Data Center Efficiency Summit 2014-1 - NERSC is the primary computing facility for DOE Office of Science
More informationVirtualization and consolidation
Virtualization and consolidation Choosing a density strategy Implementing a high-density environment Maximizing the efficiency benefit Anticipating the dynamic data center Schneider Electric 1 Topical
More informationHP Modular Cooling System: water cooling technology for high-density server installations
HP Modular Cooling System: water cooling technology for high-density server installations technical brief Abstract... 2 Introduction... 2 Data center trends... 2 Increased power demands... 3 Increased
More informationAdvances in HP Servers with Integrated NVIDIA GPUs
Advances in HP Servers with Integrated NVIDIA GPUs NVIDIA GPU Technology Workshop, Singapore Ed Turkel Group Manager, HPC Segment Product Management July 8, 2014 To out-compute is to out-compete Why High
More informationOver IP Group. Data Centre Infrastructure Management (DCIM)
Over IP Group Data Centre Infrastructure Management (DCIM) Mission To Protect the World s Network Through Innovation Let s Get Connected Over IP Group Agenda The Aim of CenterOS DCIM What is the CenterOS
More informationRack & Enclosure Systems
Knürr CoolTherm 4 35 KW Energy-efficient Server Cabinet Technology With Outstanding Benefits, To Minimize Energy Costs In The Data Center And Help Reduce Carbon Dioxide Emmisions Rack & Enclosure Systems
More information