Planning for Liquid Cooling Patrick McGinn Product Manager, Rack DCLC

Size: px
Start display at page:

Download "Planning for Liquid Cooling Patrick McGinn Product Manager, Rack DCLC"

Transcription

1 Planning for Liquid Cooling Patrick McGinn Product Manager, Rack DCLC February 3 rd, 2015

2 Expertise, Innovation & Delivery 13 years in the making with a 1800% growth rate in the last 5 years 44 patents, 22 patents pending, ISO9001 certification, global supply chain Proven technology Shipping 2,000 systems per month into data centers Shipping 30,000 50,000 units per month to desktop market > 1,850,000+ units sold Global service and supply network Founding member of the Demand Liquid Alliance (DLA) Liquid cooled Intel s Top500 and Green500 cluster

3 A Modular Approach to Liquid Cooling Rack DCLC Solutions Server Module Patented cold plate technology supports multiple combinations of CPUs/GPUs and other types of interposers, heat pipes, or heat spreaders. Manifold Module Reliable stainless steel manifolds employing dry break, quick connect technology in horizontal or vertical chassis, blades or any other server array. Heat Exchange Module Your choice of heat exchange module: Liquid-to-Air or Liquid-to-Liquid. FACILITY WATER NO FACILITY WATER

4 CASE STUDY: Cooling a Supercomputer The Cherry Creek Cluster HPC Setup CoolIT Rack DCLC AHx35 (no facility water) Supermicro FatTwin (4-node GPU front I/O) o 7 chassis per rack o 28 servers per rack Intel Xeon Processors and Coprocessors o 3x Intel Xeon Phi and 2x Intel Xeon CPU s o Featured 9,936 cores o TrueScale Infiniband Results Achieved peak performance of Teraflops Cluster consumed a total of only 74.25kW of power Ranked #400 on Top500 Supercomputers list Ranked #41 on Green500 list Cluster ran live at SC 13 in Denver, CO (as pictured), now housed at SWITCH datacenter for UNLV , CoolIT Systems. All right reserved.

5 A Modular Approach to Liquid Cooling Cooling solutions for all IT demands

6 Why Liquid Cooling? More IT equipment in less space Source: Emerson Network, Data Center 2025 Report, 2014

7 Why Liquid Cooling? Trending towards change Source: Emerson Network, Data Center 2025 Report, 2014

8 Why Liquid Cooling? The key advantages of using liquid cooling Facilitates peak performance for higher powered or overclocked processors Provides a significant reduction in total data center energy consumed Enables extremely high rack densities

9 Access Higher Performance Potential Team EPCC wins Highest Linpack at ISC 14 Student Cluster Competition Secret weapon: LIQUID COOLING (Rack DCLC AHx20) Score: teraflops (or 3.38TFLOP/s per kw) 1st time a team has broken the 10 TFLOP/s barrier within the competition s 3kW power limit Estimated ranking #4 on Green500! , CoolIT Systems. All right reserved.

10 Energy Efficient Data Centers Choices regarding POWER, PACKAGING, COOLING, & ENERGY RECOVERY in data centers drive TCO. THE POWER OF H 2 0 The cooling power in a glass of water is the equivalent to a room full of air , CoolIT Systems. All right reserved.

11 Energy Efficient Data Centers Choices regarding POWER, PACKAGING, COOLING, & ENERGY RECOVERY in data centers drive TCO. Reduce or Eliminate CRAH / CRAC / Chiller Using ASHRAE W3/W4 water and economizing in concert Reduce Server Fan Count 76% reduction in fan power 150 watts per server!! (*CoolIT Rack DCLC, Supermicro Twin 2 ) CPU and DIMM s kept below 60C at 100% CPU utilization Reduce Leakage Current 10% savings! , CoolIT Systems. All right reserved.

12 Densify and increase rack utilization! Full racks of liquid cooled equipment deliver more compute in less space and use less air cooling 2u HEX Switch 2u HEX Switch *HEX is row Switch based CDU 16 kw 32 kw 8 kw , CoolIT Systems. All right reserved.

13 Planning For Liquid Cooling Using Consistent Language Liquid Cooling Classes Facility Water (Celsius) Main Cooling Equipment (How Water temperature made) Supplemental Cooling Equipment IT Equipment Availability Cool IT Systems Rack DCLC W W Chiller & Cooling Tower Water-side Economizer Chiller Now Available W Cooling Tower Chiller W Water-side Economizer (w/ Dry Cooler or Cooling Tower) Nothing Becoming Available, dependent on Future Demand W5 > 45 Building Heating System Cooling Tower Not for HPC Source: 2011 Thermal Guidelines for Liquid Cooled Data Processing Environments (ASHRAE TC 9.9)

14 Why Liquid Cooling? Various Technologies Direct Contact Liquid Cooling Safe and reliable way to remove high % of heat Rigid copper or flexible plastic Centralized or distributed pumping Plastic or metal quick disconnects Tied to a single IT architecture? CoolIT Rack DCLC IBM Power 575 Hydro-Cluster Fujitsu/LSI 16 core SPARC64-IXfx Bullx DLC B720 compute blade

15 Why Liquid Cooling? Various Technologies Single-Phase Immersion Mineral bath, 100% load capture Change spinning disk drives to solid state drives Relocate optical connections Green Revolution Cooling Iceotope Two-Phase Immersion Mostly driven by 3M with the Novec series Early success in alternative markets CoolIT Two-Phase Immersion Study, 2014

16 Why Liquid Cooling? Various Technologies Rear-Door 100% load capture, room neutral Active or passive Single-phase or two-phase High flow of chilled water Level of efficiency depends on environment

17 Why Liquid Cooling? Where to start Reliability Material compatibility Fluid chemistry Fluid discharge Serviceability Access to standard server components Special tools and knowledge for new components Does it require special handling Required Infrastructure Changes Can the liquid cooling be deployed in your current white space? Can the liquid cooling be deployed in you current rack? Control & Monitoring Alarm systems for leak, flow, and temp Reporting and logging of data Language and availability (SNMP, IPMI, Web Server, etc.)

18 Why Liquid Cooling? Installation and Maintenance Installation Appropriate stakeholders onsite (IT, Facilities, Manufacturer) Review of plan, pre-commissioning checklist If retrofit, is uptime affected? Commissioning IT and Infrastructure staff onsite Understand the system and how to troubleshoot Appropriate functional tests completed Set up alarm parameters Service & Maintenance Check early for fluid chemistry and fouling What is the new protocol for cooling device?

19 Reference Groups The Green Grid Liquid Cooling Work Group ASHRAE Technical Committee EE HPC Working Group Liquid Cooling Commissioning

20 Thank you!

Product Guide. Direct Contact Liquid Cooling Industry leading data center solutions for HPC, Cloud and Enterprise markets.

Product Guide. Direct Contact Liquid Cooling Industry leading data center solutions for HPC, Cloud and Enterprise markets. Product Guide Direct Contact Liquid Cooling Industry leading data center solutions for HPC, Cloud and Enterprise markets. www.coolitsystems.com Phone: +1 403.235.4895 The Future of Data Center Cooling

More information

Reliable Direct Liquid Cooling for the world's most demanding Data Centers.

Reliable Direct Liquid Cooling for the world's most demanding Data Centers. Reliable Direct Liquid Cooling for the world's most demanding Data Centers www.coolitsystems.com sales@coolitsystems.com 1-866-621-2665 Unlocking Data Center Potential with Rack DCLC CoolIT Systems reliable

More information

STULZ Micro DC. with Chip-to-Atmosphere TM Liquid to Chip Cooling

STULZ Micro DC. with Chip-to-Atmosphere TM Liquid to Chip Cooling STULZ Micro DC with Chip-to-Atmosphere TM Liquid to Chip Cooling STULZ Micro DC Data center professionals and communication service providers (CSPs) face an increasingly difficult world. The continued

More information

Reliable Direct Liquid Cooling for the world's most demanding Data Centers.

Reliable Direct Liquid Cooling for the world's most demanding Data Centers. Reliable Direct Liquid Cooling for the world's most demanding Data Centers www.coolitsystems.com sales@coolitsystems.com Unlocking Data Center Potential with Rack DCLC CoolIT Systems Rack DCLC solutions

More information

Reliable Direct Liquid Cooling for the world's most demanding Data Centers.

Reliable Direct Liquid Cooling for the world's most demanding Data Centers. Reliable Direct Liquid Cooling for the world's most demanding Data Centers www.coolitsystems.com sales@coolitsystems.com 1-866-621-2665 Unlocking Data Center Potential with Rack DCLC CoolIT Systems Rack

More information

Hybrid Warm Water Direct Cooling Solution Implementation in CS300-LC

Hybrid Warm Water Direct Cooling Solution Implementation in CS300-LC Hybrid Warm Water Direct Cooling Solution Implementation in CS300-LC Roger Smith Mississippi State University Giridhar Chukkapalli Cray, Inc. C O M P U T E S T O R E A N A L Y Z E 1 Safe Harbor Statement

More information

Passive RDHx as a Cost Effective Alternative to CRAH Air Cooling. Jeremiah Stikeleather Applications Engineer

Passive RDHx as a Cost Effective Alternative to CRAH Air Cooling. Jeremiah Stikeleather Applications Engineer Passive RDHx as a Cost Effective Alternative to CRAH Air Cooling Jeremiah Stikeleather Applications Engineer Passive RDHx as a Cost Effective Alternative to CRAH Air Cooling While CRAH cooling has been

More information

FREEING HPC FROM THE DATACENTRE

FREEING HPC FROM THE DATACENTRE FREEING HPC FROM THE DATACENTRE ku:l sistem TM COOLING REDEFINED www.iceotope.com ku:l sistem removes the need for inefficient air cooling technologies FREEING HPC FROM THE DATACENTRE Iceotope s patented

More information

System Overview. Liquid Cooling for Data Centers. Negative Pressure Cooling Without Risk of Leaks

System Overview. Liquid Cooling for Data Centers. Negative Pressure Cooling Without Risk of Leaks Liquid Cooling for Data Centers System Overview The Chilldyne Cool-Flo System is a direct-to-chip liquid cooling system that delivers coolant under negative pressure. Chilldyne s technologies were designed

More information

Cooling Solutions & Considerations for High Performance Computers

Cooling Solutions & Considerations for High Performance Computers Cooling Solutions & Considerations for High Performance Computers White Paper 6 Revision 1 By Rich Whitmore Executive summary The recent advances in high performance computing have driven innovations not

More information

18 th National Award for Excellence in Energy Management. July 27, 2017

18 th National Award for Excellence in Energy Management. July 27, 2017 18 th National Award for Excellence in Energy Management July 27, 2017 ICICI Bank, Data Centre, August Hyderabad 30 & 31, 2017 ICICI Bank - Revolution in Digital Banking Over 100,000 Digital POS in 4 months

More information

LCS Value Proposition November 2014

LCS Value Proposition November 2014 LCS Value Proposition November 2014 Data Center Trends 2014 Improving Data Center Power Efficiency & Reducing Carbon Footprint Initiatives for raising data center temperatures Data center upgrades for

More information

Results of Study Comparing Liquid Cooling Methods

Results of Study Comparing Liquid Cooling Methods School of Mechanical Engineering FACULTY OF ENGINEERING Results of Study Comparing Liquid Cooling Methods Dr Jon Summers (J.L.Summers@Leeds.Ac.UK) Institute of ThermoFluids (itf) 54th HPC User Forum, September

More information

HIGH DENSITY RACK COOLING CHOICES

HIGH DENSITY RACK COOLING CHOICES WATERCOOLED HIGH PERFORMANCE COMPUTING SYSTEMS AQUILA WHITE PAPER HIGH DENSITY RACK COOLING CHOICES by Phil Hughes Reprinted with permission of Clustered Systems Company, Inc 1 THIS WHITE PAPER DISCUSSES

More information

Energy Efficiency and WCT Innovations

Energy Efficiency and WCT Innovations Energy Efficiency and WCT Innovations Zeeshan Kamal Siddiqi HPC Leader Middle East, Turkey and Africa (META) Lenovo 2017 Lenovo. All rights reserved. Why do we have a problem? Higher TDP Processors Data

More information

CAS 2K13 Sept Jean-Pierre Panziera Chief Technology Director

CAS 2K13 Sept Jean-Pierre Panziera Chief Technology Director CAS 2K13 Sept. 2013 Jean-Pierre Panziera Chief Technology Director 1 personal note 2 Complete solutions for Extreme Computing b ubullx ssupercomputer u p e r c o p u t e r suite s u e Production ready

More information

DATA CENTER LIQUID COOLING

DATA CENTER LIQUID COOLING DATA CENTER LIQUID COOLING EFFICIENT, EFFECTIVE, SUSTAINABLE What is Liquid Cooling? Key Trends & Potential Inhibitors Why are Many Owner/Operators Making the Move? Types of Liquid Cooling Solutions Liquid

More information

BENEFITS OF ASETEK LIQUID COOLING FOR DATA CENTERS

BENEFITS OF ASETEK LIQUID COOLING FOR DATA CENTERS BENEFITS OF ASETEK LIQUID COOLING FOR DATA CENTERS Asetek has leveraged its expertise as the world-leading provider of efficient liquid cooling systems to create its RackCDU and ISAC direct-to-chip liquid

More information

MSYS 4480 AC Systems Winter 2015

MSYS 4480 AC Systems Winter 2015 MSYS 4480 AC Systems Winter 2015 Module 12: DATA CENTERS By Satwinder Singh 14/05/2015 1 Data Centers Data Centers are specialized environments that safeguard your company's most valuable equipment and

More information

Future of Cooling High Density Equipment. Steve Madara Vice President and General Manager Liebert Precision Cooling Business Emerson Network Power

Future of Cooling High Density Equipment. Steve Madara Vice President and General Manager Liebert Precision Cooling Business Emerson Network Power Future of Cooling High Density Equipment Steve Madara Vice President and General Manager Liebert Precision Cooling Business Emerson Network Power Agenda Issues facing the Data Center Managing the explosive

More information

Efficiency of Data Center cooling

Efficiency of Data Center cooling Efficiency of Data Center cooling Comparison of data room layouts and cooling systems Bohumil Cimbal Product manager for Cooling Systems in CONTEG Company Objective Basic questions between investor and

More information

PROCESS & DATA CENTER COOLING. How and Why To Prepare For What s To Come JOHN MORRIS REGIONAL DIRECTOR OF SALES

PROCESS & DATA CENTER COOLING. How and Why To Prepare For What s To Come JOHN MORRIS REGIONAL DIRECTOR OF SALES PROCESS & DATA CENTER COOLING How and Why To Prepare For What s To Come JOHN MORRIS REGIONAL DIRECTOR OF SALES CONGRATULATIONS 2 BOLD PREDICTION 3 Where We Are TODAY Computer Technology NOW advances more

More information

Vienna Scientific Cluster s The Immersion Supercomputer: Extreme Efficiency, Needs No Water

Vienna Scientific Cluster s The Immersion Supercomputer: Extreme Efficiency, Needs No Water CASE STUDY Vienna Scientific Cluster s The Immersion Supercomputer: Extreme Efficiency, Needs No Water Find Out How GRC s Technology Helped VSC Get More Compute for Less. Authors: Toshio Endo, Akira Nukada,

More information

Mission Critical Facilities & Technology Conference November 3, 2011 Cooling 101. Nick Gangemi Regional Sales Manager Data Aire

Mission Critical Facilities & Technology Conference November 3, 2011 Cooling 101. Nick Gangemi Regional Sales Manager Data Aire Mission Critical Facilities & Technology Conference November 3, 2011 Cooling 101 Nick Gangemi Regional Sales Manager Data Aire Agenda Exactly what are we talking about ASHRAE TC 9.9 Design best practices

More information

NREL Validates LCS Technology. PRESENTED BY Herb Zien CEO, LiquidCool Solutions

NREL Validates LCS Technology. PRESENTED BY Herb Zien CEO, LiquidCool Solutions NREL Validates LCS Technology PRESENTED BY Herb Zien CEO, LiquidCool Solutions Learning Objectives As much as 40% of data center power is used to circulate air, and fans in a typical 30-megawatt data center

More information

INNOVATE DESIGN APPLY.

INNOVATE DESIGN APPLY. INNOVATE DESIGN APPLY By A whole new cooling experience The Motivair ChilledDoor Rack Cooling System targets the critical cooling requirements of today s modern server rack designs. As technology continues

More information

INNOVATE DESIGN APPLY.

INNOVATE DESIGN APPLY. INNOVATE DESIGN APPLY By A whole new cooling experience The Motivair ChilledDoor Rack Cooling System targets the critical cooling requirements of today s modern server rack designs. As technology continues

More information

CHILLED WATER. HIGH PRECISION AIR CONDITIONERS, FROM 7 TO 211 kw

CHILLED WATER. HIGH PRECISION AIR CONDITIONERS, FROM 7 TO 211 kw IT COOLING CLOSE CONTROL AIR CONDITIONERS CHILLED WATER HIGH PRECISION AIR CONDITIONERS, FROM 7 TO 211 kw 3 Versions available Single chilled water coil Double chilled water coil High temperature IT COOLING

More information

Rittal Cooling Solutions A. Tropp

Rittal Cooling Solutions A. Tropp 1 Rittal Cooling Solutions Presented by Adam Tropp 2 Agenda Cooling Strategies Aisle Containment Chimney Solution Airstream Management Rittal Liquid Cooling Packages Data Monitoring 3 Cooling strategies.

More information

A Data Center Heat Removal System That Saves... 80% Discover Inertech s Award-winning Data Center Heat Removal System

A Data Center Heat Removal System That Saves... 80% Discover Inertech s Award-winning Data Center Heat Removal System A Data Center Heat Removal System That Saves... Infrastructure Power Water up to 40% up to 80% up to 85% Discover Inertech s Award-winning Data Center Heat Removal System A Cool Solution; A Breakthrough

More information

LANL High Performance Computing Facilities Operations. Rick Rivera and Farhad Banisadr. Facility Data Center Management

LANL High Performance Computing Facilities Operations. Rick Rivera and Farhad Banisadr. Facility Data Center Management Slide-1 LANL High Performance Computing Facilities Operations Rick Rivera and Farhad Banisadr Facility Data Center Management Division Slide-2 Outline Overview - LANL Computer Data Centers Power and Cooling

More information

7 Best Practices for Increasing Efficiency, Availability and Capacity. XXXX XXXXXXXX Liebert North America

7 Best Practices for Increasing Efficiency, Availability and Capacity. XXXX XXXXXXXX Liebert North America 7 Best Practices for Increasing Efficiency, Availability and Capacity XXXX XXXXXXXX Liebert North America Emerson Network Power: The global leader in enabling Business-Critical Continuity Automatic Transfer

More information

Datacenter Efficiency Trends. Cary Roberts Tellme, a Microsoft Subsidiary

Datacenter Efficiency Trends. Cary Roberts Tellme, a Microsoft Subsidiary Datacenter Efficiency Trends Cary Roberts Tellme, a Microsoft Subsidiary Power Slashing Tools P3 Kill-A-WATT Measures min, max, and instantaneous voltage and current draw Calculates power (watts), kilowatt

More information

Water-Cooling and its Impact on Performance and TCO

Water-Cooling and its Impact on Performance and TCO Water-Cooling and its Impact on Performance and TCO Matthew T. Ziegler Director, HPC and AI WW BU System Strategy and Architecture mziegler@lenovo.com 2016 Lenovo Internal. All rights reserved. 1 Agenda

More information

INCREASE IT EFFICIENCY, REDUCE OPERATING COSTS AND DEPLOY ANYWHERE

INCREASE IT EFFICIENCY, REDUCE OPERATING COSTS AND DEPLOY ANYWHERE www.iceotope.com DATA SHEET INCREASE IT EFFICIENCY, REDUCE OPERATING COSTS AND DEPLOY ANYWHERE BLADE SERVER TM PLATFORM 80% Our liquid cooling platform is proven to reduce cooling energy consumption by

More information

How Liquid Cooling Helped Two University Data Centers Achieve Cooling Efficiency Goals. Michael Gagnon Coolcentric October

How Liquid Cooling Helped Two University Data Centers Achieve Cooling Efficiency Goals. Michael Gagnon Coolcentric October How Liquid Cooling Helped Two University Data Centers Achieve Cooling Efficiency Goals Michael Gagnon Coolcentric October 13 2011 Data Center Trends Energy consumption in the Data Center (DC) 2006-61 billion

More information

ECOBAY: Closed loop water cooled server cabinet for data centers

ECOBAY: Closed loop water cooled server cabinet for data centers ECOBAY: Closed loop water cooled server cabinet for data centers ELECTRONICS MANUFACTURING SERVICES Communications Computing Multimedia & Consumer Industrial & Semiconductor Defense & Aerospace Medical

More information

Chilled Water Computer Room Air Handler (CRAH) Critical Infrastructure for the World s Leading Data Centers

Chilled Water Computer Room Air Handler (CRAH) Critical Infrastructure for the World s Leading Data Centers Chilled Water Computer Room Air Handler (CRAH) Critical Infrastructure for the World s Leading Data Centers DATA CENTER COOLING EXPERTISE Data Center managers have unique needs. Nortek Air Solutions listens

More information

It`s the size of science & research...

It`s the size of science & research... It`s the size of science & research... Arno Ziebart www..com ...which makes a cluster really big. It s the type of management...which makes clusters really smart. ...which makes a cluster really big. It

More information

Green IT and Green DC

Green IT and Green DC Green IT and Green DC Alex SL Tay Regional Service Product Line Manager Site & Facilities Services, IBM ASEAN 1 What our clients are telling us We are running out of space in our data center We have environmental

More information

Data Sheet FUJITSU Server PRIMERGY CX400 M1 Scale out Server

Data Sheet FUJITSU Server PRIMERGY CX400 M1 Scale out Server Data Sheet FUJITSU Server Scale out Server Data Sheet FUJITSU Server Scale out Server Scale-Out Smart for HPC, Cloud and Hyper-Converged Computing FUJITSU Server PRIMERGY will give you the servers you

More information

Hot vs Cold Energy Efficient Data Centers. - SVLG Data Center Center Efficiency Summit

Hot vs Cold Energy Efficient Data Centers. - SVLG Data Center Center Efficiency Summit Hot vs Cold Energy Efficient Data Centers - SVLG Data Center Center Efficiency Summit KC Mares November 2014 The Great Debate about Hardware Inlet Temperature Feb 2003: RMI report on high-performance data

More information

TSUBAME-KFC : Ultra Green Supercomputing Testbed

TSUBAME-KFC : Ultra Green Supercomputing Testbed TSUBAME-KFC : Ultra Green Supercomputing Testbed Toshio Endo,Akira Nukada, Satoshi Matsuoka TSUBAME-KFC is developed by GSIC, Tokyo Institute of Technology NEC, NVIDIA, Green Revolution Cooling, SUPERMICRO,

More information

Cooling. Highly efficient cooling products for any IT application. For More Information: (866) DATA CENTER SOLUTIONS

Cooling. Highly efficient cooling products for any IT application. For More Information: (866) DATA CENTER SOLUTIONS Cooling > Highly efficient cooling products for any IT application. DATA CENTER SOLUTIONS For More Information: (866) 787-3271 Sales@PTSdcs.com End-to-End Cooling Solutions from the Closet to the Data

More information

Is Data Center Free Cooling Feasible in the Middle East? By Noriel Ong, ASEAN Eng., PMP, ATD, PQP

Is Data Center Free Cooling Feasible in the Middle East? By Noriel Ong, ASEAN Eng., PMP, ATD, PQP Is Data Center Free Cooling Feasible in the Middle East? By Noriel Ong, ASEAN Eng., PMP, ATD, PQP This case study will evaluate the feasibility of data center free cooling in the Middle East using indirect

More information

INT 492 : Selected Topic in IT II (Data Center System Design) 3(3-0-6)

INT 492 : Selected Topic in IT II (Data Center System Design) 3(3-0-6) INT 492 : Selected Topic in IT II (Data Center Design) 3(3-0-6) การออกแบบระบบศ นย สารสนเทศ Overview The American Society of Heating, Refrigeration and Air-Conditioning Engineers (ASHRAE) Technical Committee

More information

Optimiz Chilled January 25, 2013

Optimiz Chilled January 25, 2013 Optimiz zing Existing Data Center Chilled Water Plants January 25, 2013 This White Paper describes factors to be consideredd when optimizing an existing data center chilledd water plant. Authored by Michael

More information

Cooling System Considerations for High Density Colocation and Enterprise Data Centers

Cooling System Considerations for High Density Colocation and Enterprise Data Centers Cooling System Considerations for High Density Colocation and Enterprise Data Centers By Rich Whitmore Executive summary The recent advances in computer technology and the growing adoption of high performance

More information

Welcome Association of Energy Engineers to the Microsoft Technology Center

Welcome Association of Energy Engineers to the Microsoft Technology Center Welcome Association of Energy Engineers to the Microsoft Technology Center Today s Agenda 10:00 10:30 What s new in data center energy efficiency planning and implementation? 10:30 11:00 ASHRAE data center

More information

Energy Efficient Data Centers

Energy Efficient Data Centers IBM Systems and Technology Group Lab Services Energy Efficient Data Centers Steven Ahladas IBM Corp ahladas@us.ibm.com Keeping our clients in the race. All trends going the same way. IT Servers were an

More information

HPC Solutions in High Density Data Centers

HPC Solutions in High Density Data Centers Executive Report HPC Solutions in High Density Data Centers How CyrusOne s Houston West data center campus delivers the highest density solutions to customers With the ever-increasing demand on IT resources,

More information

Liebert DCW Family Chilled Water-Based High Density Cooling For The Data Center. Precision Cooling For Business-Critical Continuity

Liebert DCW Family Chilled Water-Based High Density Cooling For The Data Center. Precision Cooling For Business-Critical Continuity Liebert DCW Family Chilled Water-Based High Density Cooling For The Data Center Precision Cooling For Business-Critical Continuity Flexible Approaches For Energy Efficient Cooling Save up to 70% in cooling

More information

Rear Door Heat Exchanger

Rear Door Heat Exchanger Vinod Kamath Power and Thermal Engineering Sep 16, 2005 Problem Statement Rack Power loads are high due to increased compute density. The impact is seen in datacenters as high inlet air temperatures to

More information

100% Warm-Water Cooling with CoolMUC-3

100% Warm-Water Cooling with CoolMUC-3 100% Warm-Water Cooling with CoolMUC-3 No chillers, no fans, no problems Axel Auweter MEGWARE CTO Workshop on Energy Efficiency in HPC May 30, 2018, Ljubljana!1 MEGWARE Computer Vertrieb und Service GmbH

More information

WHITE PAPER. Oil Immersion Cooling for Today s Data Centers. An analysis of the technology and its business

WHITE PAPER. Oil Immersion Cooling for Today s Data Centers. An analysis of the technology and its business WHITE PAPER Oil Immersion Cooling for Today s Data Centers An analysis of the technology and its business In response to a growing demand for computing power and technological advancement, server densities

More information

Phil Tuma, Application Development Engineer John Gross, Mechanical Engineering Director Kar-Wing Lau, CEO Charles Benge, Director Mission Critical

Phil Tuma, Application Development Engineer John Gross, Mechanical Engineering Director Kar-Wing Lau, CEO Charles Benge, Director Mission Critical E n g i n e e r i n g W o r k s h o p : A d v a n c e d C o o l i n g S o l v i n g t h e E n e r g y C h a l l e n g e t h r o u g h I n n o v a t i o n s i n D a t a C e n t e r C o o l i n g 3m.com/immersion

More information

Air Containment Design Choices and Considerations

Air Containment Design Choices and Considerations Air Containment Design Choices and Considerations Brad J. Murphy, A.Sc.T., ATS, DCDC, DCEP, Principal Racon Data Centres Introduction Introduction Air containment design must consider many different factors

More information

Co-designing an Energy Efficient System

Co-designing an Energy Efficient System Co-designing an Energy Efficient System Luigi Brochard Distinguished Engineer, HPC&AI Lenovo lbrochard@lenovo.com MaX International Conference 2018 Trieste 29.01.2018 Industry Thermal Challenges NVIDIA

More information

Thermal management. Thermal management

Thermal management. Thermal management Thermal management Thermal management Managing thermal loads is a major challenge for all Data Centre operators. Effecting proper control of the thermal environment drives energy consumption and ultimately

More information

Power & Cooling Considerations for Virtualized Environments

Power & Cooling Considerations for Virtualized Environments Power & Cooling Considerations for Virtualized Environments Cisco Data Center Day 2008 31-01-2008 APC-MGE Vision & Mission OUR VISION APC-MGE products ensure availability wherever data is created, transmitted

More information

Cooling on Demand - scalable and smart cooling solutions. Marcus Edwards B.Sc.

Cooling on Demand - scalable and smart cooling solutions. Marcus Edwards B.Sc. Cooling on Demand - scalable and smart cooling solutions Marcus Edwards B.Sc. Schroff UK Limited Data Centre cooling what a waste of money! A 1MW data center needs 177,000,000 kwh in its lifetime of 10

More information

Digital Realty Data Center Solutions Digital Chicago Datacampus Franklin Park, Illinois Owner: Digital Realty Trust Engineer of Record: ESD Architect

Digital Realty Data Center Solutions Digital Chicago Datacampus Franklin Park, Illinois Owner: Digital Realty Trust Engineer of Record: ESD Architect Digital Realty Data Center Solutions Digital Chicago Datacampus Franklin Park, Illinois Owner: Digital Realty Trust Engineer of Record: ESD Architect of Record: SPARCH Project Overview The project is located

More information

LRZ SuperMUC One year of Operation

LRZ SuperMUC One year of Operation LRZ SuperMUC One year of Operation IBM Deep Computing 13.03.2013 Klaus Gottschalk IBM HPC Architect Leibniz Computing Center s new HPC System is now installed and operational 2 SuperMUC Technical Highlights

More information

Schneider Electric Cooling Portfolio. Jim Tubbesing Heath Wilson APC/Schneider North Texas Rep Tubbesing Solutions

Schneider Electric Cooling Portfolio. Jim Tubbesing Heath Wilson APC/Schneider North Texas Rep Tubbesing Solutions Schneider Electric Cooling Portfolio Jim Tubbesing Heath Wilson APC/Schneider North Texas Rep Tubbesing Solutions Data Center Cooling Agenda 1. How to size data center, server rooms, IDF rooms, etc in

More information

Green IT. Finding Practical Efficiencies. Infrastructure Planning and Facilities. Green IT: Finding Practical Efficiencies

Green IT. Finding Practical Efficiencies. Infrastructure Planning and Facilities. Green IT: Finding Practical Efficiencies Green IT Finding Practical Infrastructure Planning and Facilities Dan Francis dfrancis@ipf.msu.edu David Graff dsgraff@ipf.msu.edu William Lakos wjlakos@ipf.msu.edu 1 2 MSU Historical Energy Efficiency

More information

Energy Logic: Emerson Network Power. A Roadmap for Reducing Energy Consumption in the Data Center. Ross Hammond Managing Director

Energy Logic: Emerson Network Power. A Roadmap for Reducing Energy Consumption in the Data Center. Ross Hammond Managing Director Energy Logic: A Roadmap for Reducing Energy Consumption in the Data Center Emerson Network Power Ross Hammond Managing Director Agenda Energy efficiency Where We Are Today What Data Center Managers Are

More information

Total Modular Data Centre Solutions

Total Modular Data Centre Solutions Sector Data Centre Total Modular Data Centre Solutions www.airedale.com BRITISH MANUFACTURER ENERGY EFFICIENCY CONTROLS SERVICE TRAINING 01 Standardised Modular Designs to fit your needs Our modular system

More information

Combining Cold Aisle Containment with Intelligent Control to Optimize Data Center Cooling Efficiency

Combining Cold Aisle Containment with Intelligent Control to Optimize Data Center Cooling Efficiency A White Paper from the Experts in Business-Critical Continuity TM Combining Cold Aisle Containment with Intelligent Control to Optimize Data Center Cooling Efficiency Executive Summary Energy efficiency

More information

HPC/Advanced Cooling Track. Rolf Brink/CEO/Asperitas

HPC/Advanced Cooling Track. Rolf Brink/CEO/Asperitas HPC/Advanced Cooling Track Advanced Cooling Optimising for immersion Rolf Brink/CEO/Asperitas Rolf.Brink@ocproject.net +31 88 96 000 00 www.asperitas.com IMMERSED COMPUTING : AIC24 100% Removal of heat

More information

Reducing Data Center Cooling Costs through Airflow Containment

Reducing Data Center Cooling Costs through Airflow Containment FEATURE Reducing Data Center Cooling Costs through Airflow Containment Implementing a containment solution in the data center costs much less than the alternatives of adding air handlers or other supplemental

More information

HIGH DENSITY DATACOM INTEGRATED COOLING SYSTEM.

HIGH DENSITY DATACOM INTEGRATED COOLING SYSTEM. HIGH DENSITY DATACOM INTEGRATED COOLING SYSTEM. SYSTEM LOGICA is the most advanced alternative to the problem of cooling of server rooms MONTAIR is the trademark which represents excellence on the market

More information

Optimizing Cooling Performance Of a Data Center

Optimizing Cooling Performance Of a Data Center ASHRAE www.ashrae.org. Used with permission from ASHRAE Journal. This article may not be copied nor distributed in either paper or digital form without ASHRAE s permission. For more information about ASHRAE,

More information

IBM Symposium Data Center Cooling. EC Systems for HVAC architecture and Direct air Cabinet Cooling

IBM Symposium Data Center Cooling. EC Systems for HVAC architecture and Direct air Cabinet Cooling IBM Symposium 2008 Data Center Cooling EC Systems for HVAC architecture and Direct air Cabinet Cooling Presented by David J. Spofford Product Manager IT/Telecomm 1 Agenda Data Center trends for IT and

More information

Data Centers. The Environment. December The State of Global Environmental Sustainability in Data Center Design

Data Centers. The Environment. December The State of Global Environmental Sustainability in Data Center Design Data Centers & The Environment The State of Global Environmental Sustainability in Data Center Design December 2018 Today s Data Centers Data centers have a huge impact on the world we live in. Today they

More information

IT infrastructure Next level for data center. Rittal The System Yavor Panayotov Data center Day

IT infrastructure Next level for data center. Rittal The System Yavor Panayotov Data center Day IT infrastructure Next level for data center Rittal The System Yavor Panayotov Data center Day - 2018 1 Rittal The System - Solutions Enclosures Enclosures Small enclosures Command Panel & support arm

More information

High Density Cooling Solutions that work from Knurr Kris Holla

High Density Cooling Solutions that work from Knurr Kris Holla High Density Cooling Solutions that work from Knurr Kris Holla The Heat Goes On Ó by Knürr A An International Company Ranked #3 in the world Founded 1931 Strong international setting in over 32 countries

More information

Liebert DCW CATALOGUE

Liebert DCW CATALOGUE Liebert DCW CATALOGUE Chilled Water-Based High Density Cooling For The Data Center LIEBERT DCW Flexible Approaches For Energy Efficient Cooling Save up to 70% in cooling energy usage Data center managers

More information

IXcellerate Moscow One Datacentre - Phase 1 & 2 Overview

IXcellerate Moscow One Datacentre - Phase 1 & 2 Overview Contents 1. Document Purpose... 2 2. Facility Overview... 2 2.1 Technical Space... 2 2.2 Load Density... 2 2.3 Resilience... 2 2.4 Engineering Plant Maintenance & Service Restoration... 3 3. Engineering

More information

Switch to Perfection

Switch to Perfection Switch to Perfection Traditional Data Centre - Temperatures Ideal Air Temperature: 22 C Chilled Water: 7-9 C Heat Load per Rack: Up to 4,5 Chilling & Pump Set The challenge a thermal image Front View of

More information

Next Generation Cooling

Next Generation Cooling Next Generation Cooling Server Manufacturer Perspective Practical and Cost Effective David Moss Data Center Strategist Dell 1 Why Chip, Row, or Rack? Density? Energy Don t be scared; I don t see 50kW/rack

More information

ASHRAE Data Center Standards: An Overview

ASHRAE Data Center Standards: An Overview Mission Critical Facilities ASHRAE Data Center Standards: An Overview 10012 North Dale Mabry Highway Suite 109 Tampa, FL 33618 813-792-6009 www.pergravis.com Presenter: Steve Ritzi, CDCE Pergravis is a

More information

Smart Data Centres. Robert M Pe, Data Centre Consultant HP Services SEA

Smart Data Centres. Robert M Pe, Data Centre Consultant HP Services SEA Smart Data Centres Robert M Pe, Data Centre Consultant Services SEA 2006 Hewlett-Packard Development Company, L.P. The information contained herein is subject to change without notice Content Data center

More information

APC InRow Cooler Prototype Initial Report - Test Setup Verification. H. Coles, S. Greenberg Contributing: J. Bean (APC) November 18, 2011

APC InRow Cooler Prototype Initial Report - Test Setup Verification. H. Coles, S. Greenberg Contributing: J. Bean (APC) November 18, 2011 APC InRow Cooler Prototype Initial Report - Test Setup Verification H. Coles, S. Greenberg Contributing: J. Bean (APC) November 18, 2011 1 Introduction Contents Technology Description/Attributes Installation

More information

Recapture Capacity for Existing. and Airflow Optimization

Recapture Capacity for Existing. and Airflow Optimization Recapture Capacity for Existing Data Centers Through Cooling and Airflow Optimization Introduction Challenges and Trends Agenda Cooling & Airflow Optimization Takeaways Learning Objectives Recognize opportunities

More information

Product Brochure DENCO Close Control Units Row-DENCO. High Density Cooling for Data Centres

Product Brochure DENCO Close Control Units Row-DENCO. High Density Cooling for Data Centres Product Brochure DENCO Close Control Units Row-DENCO High Density Cooling for Data Centres Data Centre Cooling Through a history in close control, we have developed a broad and deep understanding of how

More information

Data Sheet Fujitsu Server PRIMERGY CX400 M1 Compact and Easy

Data Sheet Fujitsu Server PRIMERGY CX400 M1 Compact and Easy Data Sheet Fujitsu Server Compact and Easy Data Sheet Fujitsu Server Compact and Easy Scale-Out Smart for HPC, Cloud and Hyper-Converged Computing The Fujitsu Server helps to meet the immense challenges

More information

Where s the Heat Coming From. Leland Sparks Global Account Technical Consultant Belden

Where s the Heat Coming From. Leland Sparks Global Account Technical Consultant Belden Where s the Heat Coming From Leland Sparks Global Account Technical Consultant Belden What is the greatest DC challenge you face? Air Flow to Heat Load Relation Server Inlet Fans Chips Outlet LOAD Dell

More information

Variable Density, Closed-Loop, Water-Cooled Data Center Solution

Variable Density, Closed-Loop, Water-Cooled Data Center Solution Variable Density, Closed-Loop, Water-Cooled Data Center Solution Overview Great Lakes Case & Cabinet Co., Inc. has worked with Naissus Thermal Management Solutions, of Toronto, Ontario to develop one of

More information

DATA CENTER AIR HANDLING COOLING SOLUTIONS

DATA CENTER AIR HANDLING COOLING SOLUTIONS DATA CENTER AIR HANDLING COOLING SOLUTIONS World-class performance and reliability from YORK As data storage and protection needs grow, so can costs and complexity. That s why having the right partner

More information

Data Center Temperature Design Tutorial. Ian Seaton Chatsworth Products

Data Center Temperature Design Tutorial. Ian Seaton Chatsworth Products Data Center Temperature Design Tutorial Ian Seaton Chatsworth Products What are we going to do today? Explore a process for determining what data center operating temperature will deliver the best total

More information

ENCLOSURE HEAT DISSIPATION

ENCLOSURE HEAT DISSIPATION ENCLOSURE HEAT DISSIPATION DATA CENTER SOLUTIONS A White Paper by Great Lakes Case & Cabinet Company www.werackyourworld.com 814.734.7303 Page 2 Introduction Dangerous heat levels inside an enclosure threaten

More information

How to Increase Data Center Efficiency

How to Increase Data Center Efficiency How to Increase Data Center Efficiency Shivani Shukla Potkar Product Marketing Manager Pentair Electronics Protection High cooling efficiency & and reduced power consumption enhances the balance between

More information

Data Center Trends: How the Customer Drives Industry Advances and Design Development

Data Center Trends: How the Customer Drives Industry Advances and Design Development Bablu Kazi, PE MORRISON HERSHFIELD MISSION CRITICAL Data Center Trends: How the Customer Drives Industry Advances and Design Development What does the Customer Need? Scalability P U E Latest Technology

More information

Prefabricated Data Center Solutions: Coming of Age

Prefabricated Data Center Solutions: Coming of Age Prefabricated Data Center Solutions: Coming of Age Steven Carlini - Global Data Center Marketing Director April 2014 Schneider Electric 1 Schneider Electric 2 Your ability to compete relies on the design,

More information

Saving Energy with Free Cooling and How Well It Works

Saving Energy with Free Cooling and How Well It Works Saving Energy with Free Cooling and How Well It Works Brent Draney HPC Facility Integration Lead Data Center Efficiency Summit 2014-1 - NERSC is the primary computing facility for DOE Office of Science

More information

Virtualization and consolidation

Virtualization and consolidation Virtualization and consolidation Choosing a density strategy Implementing a high-density environment Maximizing the efficiency benefit Anticipating the dynamic data center Schneider Electric 1 Topical

More information

HP Modular Cooling System: water cooling technology for high-density server installations

HP Modular Cooling System: water cooling technology for high-density server installations HP Modular Cooling System: water cooling technology for high-density server installations technical brief Abstract... 2 Introduction... 2 Data center trends... 2 Increased power demands... 3 Increased

More information

Advances in HP Servers with Integrated NVIDIA GPUs

Advances in HP Servers with Integrated NVIDIA GPUs Advances in HP Servers with Integrated NVIDIA GPUs NVIDIA GPU Technology Workshop, Singapore Ed Turkel Group Manager, HPC Segment Product Management July 8, 2014 To out-compute is to out-compete Why High

More information

Over IP Group. Data Centre Infrastructure Management (DCIM)

Over IP Group. Data Centre Infrastructure Management (DCIM) Over IP Group Data Centre Infrastructure Management (DCIM) Mission To Protect the World s Network Through Innovation Let s Get Connected Over IP Group Agenda The Aim of CenterOS DCIM What is the CenterOS

More information

Rack & Enclosure Systems

Rack & Enclosure Systems Knürr CoolTherm 4 35 KW Energy-efficient Server Cabinet Technology With Outstanding Benefits, To Minimize Energy Costs In The Data Center And Help Reduce Carbon Dioxide Emmisions Rack & Enclosure Systems

More information