Capacity and Power Management: The Forgotten Factors in Disaster Recovery Planning Presented by: Clemens Pfeiffer CTO Power Assure, Inc.

Size: px
Start display at page:

Download "Capacity and Power Management: The Forgotten Factors in Disaster Recovery Planning Presented by: Clemens Pfeiffer CTO Power Assure, Inc."

Transcription

1

2 Capacity and Power Management: The Forgotten Factors in Disaster Recovery Planning Presented by: Clemens Pfeiffer CTO Power Assure, Inc.

3 The Purpose of a Data Center Provide IT equipment a healthy environment to guarantee application service levels

4 Multiple Data Centers Redundancy and Business Continuity

5 Data Center Requirements Reliability Redundancy Enough power & cooling Supporting growth Service level guarantees Tiers 1: Non redundant 2: N+1, redundant components 3: 2N, active/passive 4: 2(N+1), fault tolerant

6 Energy Efficiency vs. Reliability No one ever got fired for using too much electricity, but people get fired all the time for data center outages. A Data Center Manager

7 Application Redundancy Hot/Cold Failover configuration Either location run application Either location provides service Only one active at any time Failover delay Power Both sites always on 1x Peak capacity 2x Power consumption

8 Application Redundancy Hot/Hot Load balanced Both locations run application Both locations provide services Fully synchronized Instant protection Power Both sites always on Low average utilization per site 2x peak emergency capacity 2x power consumption

9 Data Center Cost Facility Cooling Power IT Network Hardware Software CAPEX: $1,000/sqft OPEX: 250W/sqft $219/year/sqft $100,000/rack 10kW per rack Power: $8,760/year Application Services

10 Savings Potential CAPEX What redundancy is needed? UPS/Generator on network only / everything? OPEX What capacity is required to support demand?

11 Yahoo Multiple Tiers in a Single Data Center

12 Integrated View Overall Utilization Facility and IT

13 PAR 4 Reference Data Single Server VMware Cluster 100%: All VMs at 100% Idle: All VMs idle 100% 100% idle idle

14 Virtualization Virtualization Total Resources: 14 Fixed Reservation With QoS, Individually Provisioned (use max utilization as limit for low QoS apps) Total Resources: 11-13, Savings: 7%-20% Shared Reservation With QoS, Group Provisioned (use spare capacity for low QoS apps, shared buffer) Total Resources: 7-8, Savings: 43%-50% 14 Tier 2 Low QoS Tier 4 High QoS 0 Power Assure and PARC patents pending Run LOW QoS Apps for Free!

15 Single Location Savings On-Demand Capacity OFF when not needed Power Savings: 42%

16 Hot/Cold Savings & Requirements reserve capacity with dynamic on/off buffer used Power Savings: 72% Peak Capacity: 1.6x

17 Hot/Hot Savings & Requirements reserve capacity with dynamic on/off buffer used Power Savings: 72% Peak Capacity: 3.5x

18 Example Solution Global Energy Intelligence (opt-in subscription) Energy Trading, Contract Management, Supply, Pricing, Alerts, PAR 4 Integrated Backend Services (hosted or on-premise SaaS) Automation of Standard Operating Procedures using Runbook Process Models GLOBALIZATION AUTOMATION Preventive Maintenance and Alerts What/If Analysis ANALYTICS VISUALIZATION Fully redundant storage 36 month data retention Agentless Data Collection and Action Execution (per Data Center) HISTORIAN Cooling, Power, Temperature, Server Utilization, Application Service Levels COLLECTION

19 Real-Case Example Before 10MW available power PUE 2.3 Central chiller plant Raised floor Open space Hot/Cold secondary site configuration Single speed CRAC units manual on/off Return air to CRAC units set to 72F

20 Discrete Improvements Changes Add VFD controls to CRAC/CRAH units Feed IT inlet temperature to controller Set inlet temperature to 75F Hot/Cold aisle isolation blanket panels Cold aisle containment Hardware Refresh From 2008 HP server (2U, 368W, 133k txn/watt) To 2010 Dell server (1U, 157W, 700k txn/watt) Virtualization Using Power Assure PARC group provisioning

21 Overall Improvement Results After PUE 1.3 Contained cold aisle at 75F Variable speed CRAC unit controlled by IT inlet temp 80% Floor space reduction, 80% power reduction 15x Capacity increase when fully propagated Hot/Hot virtualized and load balanced environment Dynamic application safety buffer Virtually no application service limits + 42% ongoing power savings by moving from always-on to always-available

22 Thank You! Presented by: Clemens Pfeiffer CTO Power Assure, Inc.

MSYS 4480 AC Systems Winter 2015

MSYS 4480 AC Systems Winter 2015 MSYS 4480 AC Systems Winter 2015 Module 12: DATA CENTERS By Satwinder Singh 14/05/2015 1 Data Centers Data Centers are specialized environments that safeguard your company's most valuable equipment and

More information

PROCESS & DATA CENTER COOLING. How and Why To Prepare For What s To Come JOHN MORRIS REGIONAL DIRECTOR OF SALES

PROCESS & DATA CENTER COOLING. How and Why To Prepare For What s To Come JOHN MORRIS REGIONAL DIRECTOR OF SALES PROCESS & DATA CENTER COOLING How and Why To Prepare For What s To Come JOHN MORRIS REGIONAL DIRECTOR OF SALES CONGRATULATIONS 2 BOLD PREDICTION 3 Where We Are TODAY Computer Technology NOW advances more

More information

7 Best Practices for Increasing Efficiency, Availability and Capacity. XXXX XXXXXXXX Liebert North America

7 Best Practices for Increasing Efficiency, Availability and Capacity. XXXX XXXXXXXX Liebert North America 7 Best Practices for Increasing Efficiency, Availability and Capacity XXXX XXXXXXXX Liebert North America Emerson Network Power: The global leader in enabling Business-Critical Continuity Automatic Transfer

More information

Future of Cooling High Density Equipment. Steve Madara Vice President and General Manager Liebert Precision Cooling Business Emerson Network Power

Future of Cooling High Density Equipment. Steve Madara Vice President and General Manager Liebert Precision Cooling Business Emerson Network Power Future of Cooling High Density Equipment Steve Madara Vice President and General Manager Liebert Precision Cooling Business Emerson Network Power Agenda Issues facing the Data Center Managing the explosive

More information

Making the impossible data center a reality.

Making the impossible data center a reality. United Nations ITU WSIS 2016 WINNER E-Environment Malaysia s First Win 2015 ASIA PACIFIC WINNER 2015 Best of Sustainability and Environmental Technology WINNER 2015 Best of Sustainability and Environmental

More information

Data Centre Energy & Cost Efficiency Simulation Software. Zahl Limbuwala

Data Centre Energy & Cost Efficiency Simulation Software. Zahl Limbuwala Data Centre Energy & Cost Efficiency Simulation Software Zahl Limbuwala BCS Data Centre Simulator Overview of Tools Structure of the BCS Simulator Input Data Sample Output Development Path Overview of

More information

Liebert DCW CATALOGUE

Liebert DCW CATALOGUE Liebert DCW CATALOGUE Chilled Water-Based High Density Cooling For The Data Center LIEBERT DCW Flexible Approaches For Energy Efficient Cooling Save up to 70% in cooling energy usage Data center managers

More information

84 kw, Tier 3, Direct Expansion, 937 ft 2

84 kw, Tier 3, Direct Expansion, 937 ft 2 [Reference Design 42] 84 kw, Tier 3, Direct Expansion, 937 ft 2 DESIGN OVERVIEW Data Center IT Capacity 84 kw Target Availability Tier 3 Annualized PUE at 100% Load 1.712 Total Racks and Average Density

More information

DATA CENTER EFFICIENCY: Data Center Temperature Set-point Impact on Cooling Efficiency

DATA CENTER EFFICIENCY: Data Center Temperature Set-point Impact on Cooling Efficiency DATA CENTER EFFICIENCY: Data Center Temperature Set-point Impact on Cooling Efficiency September 27 th, 2013 Tejas Desai, PE CEM CEA LEED AP Sameer Behere, PE CEM LEED AP Agenda Problem: Quick fixes can

More information

Data Center Design and. Management. Steve Knipple. August 1, CTO / VP Engineering & Operations

Data Center Design and. Management. Steve Knipple. August 1, CTO / VP Engineering & Operations Data Center Design and Energy Management Steve Knipple CTO / VP Engineering & Operations August 1, 2013 Agenda Introduction to EasyStreet Speaker Bio EasyStreet Sustainability Data Center 1 (Retrofit completed

More information

18 th National Award for Excellence in Energy Management. July 27, 2017

18 th National Award for Excellence in Energy Management. July 27, 2017 18 th National Award for Excellence in Energy Management July 27, 2017 ICICI Bank, Data Centre, August Hyderabad 30 & 31, 2017 ICICI Bank - Revolution in Digital Banking Over 100,000 Digital POS in 4 months

More information

MEASURE MONITOR UNDERSTAND

MEASURE MONITOR UNDERSTAND MEASURE MONITOR UNDERSTAND Presented by Alistair Hunt Energy Monitoring, Measurement metrics Where and What 1 History & Background Company Timeline 18 Years Comrac & Sinetica founded 15 Years Raritan Integration

More information

DATA CENTRE & COLOCATION

DATA CENTRE & COLOCATION DATA CENTRE & COLOCATION RISING DEMAND FOR HOSTED SERVICES When it comes to hosted IT infrastructure, organisations are looking for highly resilient, highly available and highly scalable facilities at

More information

3300 kw, Tier 3, Chilled Water, 70,000 ft 2

3300 kw, Tier 3, Chilled Water, 70,000 ft 2 [Reference Design 22] 3300 kw, Tier 3, Chilled Water, 70,000 ft 2 DESIGN OVERVIEW Data Center IT Capacity 1100 kw per Data Hall 3 Independent Data Halls Design Application Range This design can be applied

More information

Data center cooling evolution. The hottest way to save energy. Lucio Bustaffa: Product Development Manager BlueBox Group

Data center cooling evolution. The hottest way to save energy. Lucio Bustaffa: Product Development Manager BlueBox Group Data center cooling evolution. The hottest way to save energy Lucio Bustaffa: Product Development Manager BlueBox Group Data Center overview What s happening in the web? 2 Data Center overview What s happening

More information

Hot vs Cold Energy Efficient Data Centers. - SVLG Data Center Center Efficiency Summit

Hot vs Cold Energy Efficient Data Centers. - SVLG Data Center Center Efficiency Summit Hot vs Cold Energy Efficient Data Centers - SVLG Data Center Center Efficiency Summit KC Mares November 2014 The Great Debate about Hardware Inlet Temperature Feb 2003: RMI report on high-performance data

More information

Energy Logic: Emerson Network Power. A Roadmap for Reducing Energy Consumption in the Data Center. Ross Hammond Managing Director

Energy Logic: Emerson Network Power. A Roadmap for Reducing Energy Consumption in the Data Center. Ross Hammond Managing Director Energy Logic: A Roadmap for Reducing Energy Consumption in the Data Center Emerson Network Power Ross Hammond Managing Director Agenda Energy efficiency Where We Are Today What Data Center Managers Are

More information

Passive RDHx as a Cost Effective Alternative to CRAH Air Cooling. Jeremiah Stikeleather Applications Engineer

Passive RDHx as a Cost Effective Alternative to CRAH Air Cooling. Jeremiah Stikeleather Applications Engineer Passive RDHx as a Cost Effective Alternative to CRAH Air Cooling Jeremiah Stikeleather Applications Engineer Passive RDHx as a Cost Effective Alternative to CRAH Air Cooling While CRAH cooling has been

More information

Efficiency of Data Center cooling

Efficiency of Data Center cooling Efficiency of Data Center cooling Comparison of data room layouts and cooling systems Bohumil Cimbal Product manager for Cooling Systems in CONTEG Company Objective Basic questions between investor and

More information

SIX Trends in our World

SIX Trends in our World Data Center Infrastructure for Cloud and Energy Efficiency SIX Trends in our World Connectivity Simplicity StruxureWare TM for data centers TuanAnh Nguyen, Solution Engineer Manager, Vietnam Schneider

More information

<Insert Picture Here> Austin Data Center 6Sigma DC CFD Model

<Insert Picture Here> Austin Data Center 6Sigma DC CFD Model Austin Data Center 6Sigma DC CFD Model Keith Ward Keith Ward Data Center Facilities Engineering and Logistics Design Austin Data Center Statistics - Space Original AT&T Designed and

More information

Oracle Real Application Clusters One Node

Oracle Real Application Clusters One Node Oracle Real Application Clusters One Node Better Virtualization for Databases Bob Thome, Oracle Grid Development Agenda Overview Comparison with VMs and other failover solutions Pricing

More information

Cost Model Energy Benefits DirectAire & SmartAire Overview & Explanation

Cost Model Energy Benefits DirectAire & SmartAire Overview & Explanation Cost Model Energy Benefits DirectAire & SmartAire Overview & Explanation A cost model (See figure 1) has been created to provide the user a simplified method for directly comparing the energy cost of a

More information

Towards the Green Data Centre. Lex Coors Vice President Data Center Technology & Engineering Group

Towards the Green Data Centre. Lex Coors Vice President Data Center Technology & Engineering Group Towards the Green Data Centre Lex Coors Vice President Data Center Technology & Engineering Group DC Emissions: We Have Lift-Off! Data Centre Greenhouse Gas Emissions are projected to quadruple by 2020

More information

Dude Solutions Business Continuity Overview

Dude Solutions Business Continuity Overview Dude Solutions Business Continuity Overview Table of Contents Overview.... 2 Primary and Disaster Recovery Data Centers.... 2 Network Infrastructure.... 3 Emergency Processes.... 3 Power and Cooling Systems....

More information

The Energy. David L. Moss Dell Data Center Infrastructure

The Energy. David L. Moss Dell Data Center Infrastructure The Energy Advantages of Containment Systems David L. Moss Dell Data Center Infrastructure www.dell.com/hiddendatacenter Summary The Uptime Institute estimates that the cost to build a new 20,000 square

More information

DCIM Solutions to improve planning and reduce operational cost across IT & Facilities

DCIM Solutions to improve planning and reduce operational cost across IT & Facilities DCIM Solutions to improve planning and reduce operational cost across IT & Facilities Presented by: Chi Sen, Director, Data Centre Software Solutions, APJ & EMEA Schneider Electric Data Center Solutions

More information

COLOCATION SERVICE DESCRIPTION

COLOCATION SERVICE DESCRIPTION COLOCATION SERVICE DESCRIPTION 1. Contents 2. Executive Summary... 3 2.1 High Level Overview... 3 2.2 Business Benefits of Partnering with ONI... 3 2.3 Restrictions on Disclosure... 3 3. Service Components...

More information

Datacenter Efficiency Trends. Cary Roberts Tellme, a Microsoft Subsidiary

Datacenter Efficiency Trends. Cary Roberts Tellme, a Microsoft Subsidiary Datacenter Efficiency Trends Cary Roberts Tellme, a Microsoft Subsidiary Power Slashing Tools P3 Kill-A-WATT Measures min, max, and instantaneous voltage and current draw Calculates power (watts), kilowatt

More information

Rolf Brink Founder/CEO

Rolf Brink Founder/CEO Rolf Brink Founder/CEO +31 88 96 000 00 www.asperitas.com COPYRIGHT 2017 BY ASPERITAS Asperitas, Robertus Nurksweg 5, 2033AA Haarlem, The Netherlands Information in this document can be freely used and

More information

Liebert DCW Family Chilled Water-Based High Density Cooling For The Data Center. Precision Cooling For Business-Critical Continuity

Liebert DCW Family Chilled Water-Based High Density Cooling For The Data Center. Precision Cooling For Business-Critical Continuity Liebert DCW Family Chilled Water-Based High Density Cooling For The Data Center Precision Cooling For Business-Critical Continuity Flexible Approaches For Energy Efficient Cooling Save up to 70% in cooling

More information

1.0 Executive Summary. 2.0 Available Features & Benefits

1.0 Executive Summary. 2.0 Available Features & Benefits Statement Of Work Energy Management Services Table of Contents 1.0 Executive Summary 2.0 Available Features & Benefits 3.0 Assessment Deliverables Selection 4.0 On Site Assessment Activities 5.0 Exclusions

More information

System Overview. Liquid Cooling for Data Centers. Negative Pressure Cooling Without Risk of Leaks

System Overview. Liquid Cooling for Data Centers. Negative Pressure Cooling Without Risk of Leaks Liquid Cooling for Data Centers System Overview The Chilldyne Cool-Flo System is a direct-to-chip liquid cooling system that delivers coolant under negative pressure. Chilldyne s technologies were designed

More information

Art and Science of Building NUS Data Centres

Art and Science of Building NUS Data Centres Art and Science of Building NUS Data Centres DATA CENTRE @ NUS Contents I. Nostalgia II. III. IV. Science of Elements in a Data Centre NUS DC Live Migration the Art and Challenges Milestones in Pictures

More information

Pros and Cons of Various DC Distribution Architectures

Pros and Cons of Various DC Distribution Architectures Pros and Cons of Various DC Distribution Architectures Source: Solar Powered Datacenter by Google Randy Malik Power Technology And Qualification IBM RTP Raleigh NC Rick Fishbune Power Technology And Qualification

More information

Data Center Trends: How the Customer Drives Industry Advances and Design Development

Data Center Trends: How the Customer Drives Industry Advances and Design Development Bablu Kazi, PE MORRISON HERSHFIELD MISSION CRITICAL Data Center Trends: How the Customer Drives Industry Advances and Design Development What does the Customer Need? Scalability P U E Latest Technology

More information

Rittal Cooling Solutions A. Tropp

Rittal Cooling Solutions A. Tropp 1 Rittal Cooling Solutions Presented by Adam Tropp 2 Agenda Cooling Strategies Aisle Containment Chimney Solution Airstream Management Rittal Liquid Cooling Packages Data Monitoring 3 Cooling strategies.

More information

FREEING HPC FROM THE DATACENTRE

FREEING HPC FROM THE DATACENTRE FREEING HPC FROM THE DATACENTRE ku:l sistem TM COOLING REDEFINED www.iceotope.com ku:l sistem removes the need for inefficient air cooling technologies FREEING HPC FROM THE DATACENTRE Iceotope s patented

More information

Current Data Center Design. James Monahan Sept 19 th 2006 IEEE San Francisco ComSoc

Current Data Center Design. James Monahan Sept 19 th 2006 IEEE San Francisco ComSoc Current Data Center Design James Monahan Sept 19 th 2006 IEEE San Francisco ComSoc What is the biggest facility problem in your data center? 35% 30% 25% 20% 15% Series1 10% 5% 0% Excessive heat Insufficient

More information

Cooling. Highly efficient cooling products for any IT application. For More Information: (866) DATA CENTER SOLUTIONS

Cooling. Highly efficient cooling products for any IT application. For More Information: (866) DATA CENTER SOLUTIONS Cooling > Highly efficient cooling products for any IT application. DATA CENTER SOLUTIONS For More Information: (866) 787-3271 Sales@PTSdcs.com End-to-End Cooling Solutions from the Closet to the Data

More information

Where s the Heat Coming From. Leland Sparks Global Account Technical Consultant Belden

Where s the Heat Coming From. Leland Sparks Global Account Technical Consultant Belden Where s the Heat Coming From Leland Sparks Global Account Technical Consultant Belden What is the greatest DC challenge you face? Air Flow to Heat Load Relation Server Inlet Fans Chips Outlet LOAD Dell

More information

Data Center Temperature Design Tutorial. Ian Seaton Chatsworth Products

Data Center Temperature Design Tutorial. Ian Seaton Chatsworth Products Data Center Temperature Design Tutorial Ian Seaton Chatsworth Products What are we going to do today? Explore a process for determining what data center operating temperature will deliver the best total

More information

Datacentre Milton Keynes Hall C Data sheet

Datacentre Milton Keynes Hall C Data sheet Datacentre Milton Keynes Hall C Data sheet Data sheet Datacentre Milton Keynes Hall C Find us With 10 datacentres, over 4,500 racks and a 10Gb resilient core network between our datacentre locations, Pulsant

More information

How High Temperature Data Centers & Intel Technologies save Energy, Money, Water and Greenhouse Gas Emissions

How High Temperature Data Centers & Intel Technologies save Energy, Money, Water and Greenhouse Gas Emissions Intel Intelligent Power Management Intel How High Temperature Data Centers & Intel Technologies save Energy, Money, Water and Greenhouse Gas Emissions Power savings through the use of Intel s intelligent

More information

Kifer Industrial Park

Kifer Industrial Park FEATURES ±56,358 SF Data Center / Lab / Manufacturing Building The entire facility is built-out with raised floor data center and data center support space Heavy Power Multiple telecom providers Pre-action

More information

World Class. Globally Certified. High Availability.

World Class. Globally Certified. High Availability. Intellicentre 2 World Class. Globally Certified. High Availability. Intellicentre 2 Macquarie Park, Sydney 2 Intellicentre 2 A new generation of data centre solutions. Australia s first showcase Tier III

More information

Green IT. Finding Practical Efficiencies. Infrastructure Planning and Facilities. Green IT: Finding Practical Efficiencies

Green IT. Finding Practical Efficiencies. Infrastructure Planning and Facilities. Green IT: Finding Practical Efficiencies Green IT Finding Practical Infrastructure Planning and Facilities Dan Francis dfrancis@ipf.msu.edu David Graff dsgraff@ipf.msu.edu William Lakos wjlakos@ipf.msu.edu 1 2 MSU Historical Energy Efficiency

More information

Schneider Electric Cooling Portfolio. Jim Tubbesing Heath Wilson APC/Schneider North Texas Rep Tubbesing Solutions

Schneider Electric Cooling Portfolio. Jim Tubbesing Heath Wilson APC/Schneider North Texas Rep Tubbesing Solutions Schneider Electric Cooling Portfolio Jim Tubbesing Heath Wilson APC/Schneider North Texas Rep Tubbesing Solutions Data Center Cooling Agenda 1. How to size data center, server rooms, IDF rooms, etc in

More information

Windows Servers In Microsoft Azure

Windows Servers In Microsoft Azure $6/Month Windows Servers In Microsoft Azure What I m Going Over 1. How inexpensive servers in Microsoft Azure are 2. How I get Windows servers for $6/month 3. Why Azure hosted servers are way better 4.

More information

Pramod Mandagere Prof. David Du Sandeep Uttamchandani (IBM Almaden)

Pramod Mandagere Prof. David Du Sandeep Uttamchandani (IBM Almaden) Pramod Mandagere Prof. David Du Sandeep Uttamchandani (IBM Almaden) Motivation Background Our Research Agenda Modeling Thermal Behavior Static Workload Provisioning Dynamic Workload Provisioning Improving

More information

International 6SigmaDC User Conference CFD Modeling for Lab Energy Savings DCSTG Lab Temperature Setpoint Increase

International 6SigmaDC User Conference CFD Modeling for Lab Energy Savings DCSTG Lab Temperature Setpoint Increase International 6SigmaDC User Conference CFD Modeling for Lab Energy Savings DCSTG Lab Temperature Setpoint Increase Chris Noland cnoland@cisco.com Vipha Kanakakorn vkanakak@cisco.com 3/4/2010 Goal & Limitations

More information

Recapture Capacity for Existing. and Airflow Optimization

Recapture Capacity for Existing. and Airflow Optimization Recapture Capacity for Existing Data Centers Through Cooling and Airflow Optimization Introduction Challenges and Trends Agenda Cooling & Airflow Optimization Takeaways Learning Objectives Recognize opportunities

More information

Power & Cooling Considerations for Virtualized Environments

Power & Cooling Considerations for Virtualized Environments Power & Cooling Considerations for Virtualized Environments Cisco Data Center Day 2008 31-01-2008 APC-MGE Vision & Mission OUR VISION APC-MGE products ensure availability wherever data is created, transmitted

More information

A Green Approach. Thermal

A Green Approach. Thermal A Green Approach to Thermal Management Thermal Management - AGENDA Definitions & Thermal Facts Density Trends Rack Level Management Passive Solutions Thermal Sources & Green Solutions Data Center Layout

More information

Cooling on Demand - scalable and smart cooling solutions. Marcus Edwards B.Sc.

Cooling on Demand - scalable and smart cooling solutions. Marcus Edwards B.Sc. Cooling on Demand - scalable and smart cooling solutions Marcus Edwards B.Sc. Schroff UK Limited Data Centre cooling what a waste of money! A 1MW data center needs 177,000,000 kwh in its lifetime of 10

More information

Reducing Energy Consumption with

Reducing Energy Consumption with Reducing Energy Consumption with Passive Cooling Ian Cathcart, RCDD Technical Support Manager Technical Support Manager Chatsworth Products, Inc. Thermal Management: Mission Critical Data center heat loads

More information

Planning a Green Datacenter

Planning a Green Datacenter Planning a Green Datacenter Dr. Dominique Singy Contribution to: Green IT Crash Course Organisator: Green IT Special Interest Group of the Swiss Informatics Society ETH-Zurich / February 13, Green Data

More information

Availability in the Modern Datacenter

Availability in the Modern Datacenter Availability in the Modern Datacenter Adriana Rangel SIS Research Director IDC Middle East, Turkey & Africa IDC Visit us at IDC.com and follow us on Twitter: @IDC 2 US$ Mn Middle East IT Market Spending

More information

The Evolving Data Center

The Evolving Data Center The Evolving Data Center Dominic Loh Product Manager, Power Quality, APAC Data Centers are enabling global growth Proliferation of mobile computing Digitalization of everything Big Data 2 Evolution of

More information

Switch to Perfection

Switch to Perfection Switch to Perfection Traditional Data Centre - Temperatures Ideal Air Temperature: 22 C Chilled Water: 7-9 C Heat Load per Rack: Up to 4,5 Chilling & Pump Set The challenge a thermal image Front View of

More information

High Performance Computing (HPC) Data Center Proposal

High Performance Computing (HPC) Data Center Proposal High Performance Computing (HPC) Data Center Proposal Imran Latif, Facility Project Manager Scientific & Enterprise Computing Data Centers at BNL 10/14/2015 Quick Facts!! Located on 1 st floor in Building

More information

HCX SERVER PRODUCT BRIEF & TECHNICAL FEATURES SUMMARY

HCX SERVER PRODUCT BRIEF & TECHNICAL FEATURES SUMMARY PRODUCT BRIEF & TECHNICAL FEATURES SUMMARY PRODUCT BRIEF A SERVER OPTIMIZED FOR A HYBRID WORLD The HCX Server is a Windows Server pre-bundled with integrated core IT services designed for small and midsize

More information

Close-coupled cooling

Close-coupled cooling Close-coupled cooling Intelligently controlled high-performance InRow cooling for the IT environment APC TM by Schneider Electric close-coupled cooling products provide a modular, scalable, and predictable

More information

Data Center Infrastructure Management ( DCiM )

Data Center Infrastructure Management ( DCiM ) Page 1 Data Center Infrastructure Management ( DCiM ) DCiM is defined by technology researchers and analysts as the integration of information technology (IT) and facility management disciplines to centralize

More information

How to Increase Data Center Efficiency

How to Increase Data Center Efficiency How to Increase Data Center Efficiency Shivani Shukla Potkar Product Marketing Manager Pentair Electronics Protection High cooling efficiency & and reduced power consumption enhances the balance between

More information

The Shared Data Centre Project

The Shared Data Centre Project David Birds - Data Centre Manager Oxford University Computing Services Networkshop 39 13 th April 2011 Why do we need it? 1. Additional data centre capacity. 2. The opportunity to provide a higher level

More information

1.0 Executive Summary

1.0 Executive Summary Statement of Work - 1 - Power and Cooling Assessment for Data Center Professional Services Service 1.0 Executive Summary Table of Contents 1.0 Executive Summary 2.0 Features & Benefits 3.0 Details of Service

More information

Green Computing: Datacentres

Green Computing: Datacentres Green Computing: Datacentres Simin Nadjm-Tehrani Department of Computer and Information Science (IDA) Linköping University Sweden Many thanks to Jordi Cucurull For earlier versions of this course material

More information

Mission Critical Facilities & Technology Conference November 3, 2011 Cooling 101. Nick Gangemi Regional Sales Manager Data Aire

Mission Critical Facilities & Technology Conference November 3, 2011 Cooling 101. Nick Gangemi Regional Sales Manager Data Aire Mission Critical Facilities & Technology Conference November 3, 2011 Cooling 101 Nick Gangemi Regional Sales Manager Data Aire Agenda Exactly what are we talking about ASHRAE TC 9.9 Design best practices

More information

50 TB. Traditional Storage + Data Protection Architecture. StorSimple Cloud-integrated Storage. Traditional CapEx: $375K Support: $75K per Year

50 TB. Traditional Storage + Data Protection Architecture. StorSimple Cloud-integrated Storage. Traditional CapEx: $375K Support: $75K per Year Compelling Economics: Traditional Storage vs. StorSimple Traditional Storage + Data Protection Architecture StorSimple Cloud-integrated Storage Servers Servers Primary Volume Disk Array ($100K; Double

More information

SmartRow Solution Intelligent, Integrated Infrastructure for the Data Center

SmartRow Solution Intelligent, Integrated Infrastructure for the Data Center SmartRow Solution Intelligent, Integrated Infrastructure for the Data Center Deploy a Fully Configured Data Center in Just Weeks Availability, Capacity, Efficiency. You need them and now you can have them

More information

Overcoming the Challenges of Server Virtualisation

Overcoming the Challenges of Server Virtualisation Overcoming the Challenges of Server Virtualisation Maximise the benefits by optimising power & cooling in the server room Server rooms are unknowingly missing a great portion of their benefit entitlement

More information

SmartRow Intelligent, Integrated Infrastructure in a Self-Contained Line-Up. Solutions For Business-Critical Continuity

SmartRow Intelligent, Integrated Infrastructure in a Self-Contained Line-Up. Solutions For Business-Critical Continuity SmartRow Intelligent, Integrated Infrastructure in a Self-Contained Line-Up Solutions For Business-Critical Continuity Deploy a Fully Configured Data Center in Just Weeks Efficiency. Capacity. Availability.

More information

Green Computing: Datacentres

Green Computing: Datacentres Green Computing: Datacentres Simin Nadjm-Tehrani Department of Computer and Information Science (IDA) Linköping University Sweden Many thanks to Jordi Cucurull For earlier versions of this course material

More information

TWO FINANCIAL IMPACT STUDIES. Seal IT Equipment Cabinets for Significant Annual Cost Savings and Simple Payback in a Few Short Months

TWO FINANCIAL IMPACT STUDIES. Seal IT Equipment Cabinets for Significant Annual Cost Savings and Simple Payback in a Few Short Months TWO FINANCIAL IMPACT STUDIES Seal IT Equipment Cabinets for Significant Annual Cost Savings and Simple Payback in a Few Short Months TWO FINANCIAL IMPACT STUDIES Seal IT Equipment Cabinets for Significant

More information

IT Air Conditioning Units

IT Air Conditioning Units IT Air Conditioning Units Modern Flexible Effective Energy Saving CoolTeg Plus and CoolTop overview CoolTeg Plus CW CoolTeg Plus DX CoolTeg Plus XC CoolTop Installation Between IT racks On top of IT rack

More information

Thermal management. Thermal management

Thermal management. Thermal management Thermal management Thermal management Managing thermal loads is a major challenge for all Data Centre operators. Effecting proper control of the thermal environment drives energy consumption and ultimately

More information

The End of Redundancy. Alan Wood Sun Microsystems May 8, 2009

The End of Redundancy. Alan Wood Sun Microsystems May 8, 2009 The End of Redundancy Alan Wood Sun Microsystems May 8, 2009 Growing Demand, Shrinking Resources By 2008, 50% of current data centers will have insufficient power and cooling capacity to meet the demands

More information

High Density Cooling Solutions that work from Knurr Kris Holla

High Density Cooling Solutions that work from Knurr Kris Holla High Density Cooling Solutions that work from Knurr Kris Holla The Heat Goes On Ó by Knürr A An International Company Ranked #3 in the world Founded 1931 Strong international setting in over 32 countries

More information

Rittal White Paper 506: Cold Aisle Containment for Improved Data Center Cooling Efficiency By: Daniel Kennedy

Rittal White Paper 506: Cold Aisle Containment for Improved Data Center Cooling Efficiency By: Daniel Kennedy Rittal White Paper 506: Cold Aisle Containment for Improved Data Center Cooling Efficiency By: Daniel Kennedy Executive Summary Increasing power requirements for new servers have created the need to support

More information

Maximise Data Center Value

Maximise Data Center Value Maximise Data Center Value with Higher Density Infrastructure Dramatic cost savings enabled; Requires solving unique electrical + cooling challenges; 08 December 2015 Speaker gokhan.gulal@4g.net.tr Genel

More information

Datacentre Reading East 2 Data sheet

Datacentre Reading East 2 Data sheet Datacentre Reading East 2 Data sheet Data sheet Datacentre Reading East 2 Find us With 10 datacentres, over 4,500 racks and a 10Gb resilient core network between our datacentre locations, Pulsant has the

More information

Energy Efficient Data Centers

Energy Efficient Data Centers IBM Systems and Technology Group Lab Services Energy Efficient Data Centers Steven Ahladas IBM Corp ahladas@us.ibm.com Keeping our clients in the race. All trends going the same way. IT Servers were an

More information

Rittal LCP T3+ High-availability IT cooling with no compromise

Rittal LCP T3+ High-availability IT cooling with no compromise Rittal LCP T3+ High-availability IT cooling with no compromise LCP T3+, the climate for maximum availability... in the financial world Admittedly, we have no solution for overheated markets. But we do

More information

Virtualization and consolidation

Virtualization and consolidation Virtualization and consolidation Choosing a density strategy Implementing a high-density environment Maximizing the efficiency benefit Anticipating the dynamic data center Schneider Electric 1 Topical

More information

T66 Central Utility Building (CUB) Control System Reliability, Optimization & Demand Management

T66 Central Utility Building (CUB) Control System Reliability, Optimization & Demand Management T66 Central Utility Building (CUB) Control System Reliability, Optimization & Demand Management Name Doug Demian Title Application Engineer Date November 7 & 8, 2012 Rev 5058-CO900C Copyright 2012 Rockwell

More information

Scalable, Secure. Jason Rylands

Scalable, Secure. Jason Rylands Energy Efficient, Modular, Scalable, Secure Jason Rylands The planning, construction and operation of IT infrastructure for mission critical applications in reliable Datacentres represents a real challenge.

More information

Hybrid Warm Water Direct Cooling Solution Implementation in CS300-LC

Hybrid Warm Water Direct Cooling Solution Implementation in CS300-LC Hybrid Warm Water Direct Cooling Solution Implementation in CS300-LC Roger Smith Mississippi State University Giridhar Chukkapalli Cray, Inc. C O M P U T E S T O R E A N A L Y Z E 1 Safe Harbor Statement

More information

Case study on Green Data Center. Reliance Jio Infocomm Limited

Case study on Green Data Center. Reliance Jio Infocomm Limited Case study on Green Data Center 2 What is data center? Use and functions of Data Center. Basic Infrastructure requirement for data center. Energy consumption heads in data center. 3 What is Data Center

More information

Survey and Audit Service Schedule. Airflow and Thermal Imaging Survey Service Schedule. Data Centre Solutions Expertly Engineered

Survey and Audit Service Schedule. Airflow and Thermal Imaging Survey Service Schedule. Data Centre Solutions Expertly Engineered Survey and Audit Service Schedule Airflow and Thermal Imaging Survey Service Schedule Data Centre Solutions Expertly Engineered Consult optimisation, audit and survey services Data Centre Services Workspace

More information

Evaporative free air cooling technology Providing evaporative free air cooling solutions.

Evaporative free air cooling technology Providing evaporative free air cooling solutions. Evaporative free air cooling technology Providing evaporative free air cooling solutions. Creating an effective workspace environment data centre free air cooling technology FreeCool - Evaporative Free

More information

WHITE PAPER. Solutions OnDemand Hosting Overview

WHITE PAPER. Solutions OnDemand Hosting Overview WHITE PAPER SAS Title Solutions OnDemand Hosting Overview ii Contents Overview... 1 Cary 1 (US) Facility Specifications...2 Cary 2 (US) Facility Specifications (SAS New Cloud Computing Center)...3 Charlotte

More information

Vscale: Real-World Deployments of Next-Gen Data Center Architecture

Vscale: Real-World Deployments of Next-Gen Data Center Architecture Vscale: Real-World Deployments of Next-Gen Data Center Architecture Key takeaways Dell EMC Vscale is a standard, modular, pre-engineered architecture that transforms data centers into an automated, scalable

More information

IT Level Power Provisioning Business Continuity and Efficiency at NTT

IT Level Power Provisioning Business Continuity and Efficiency at NTT IT Level Power Provisioning Business Continuity and Efficiency at NTT Henry M.L. Wong Intel Eco-Technology Program Office Environment Global CO 2 Emissions ICT 2% 98% Source: The Climate Group Economic

More information

Density in the Data Center

Density in the Data Center Density in the Data Center INDUSTRY BRIEF Aug 2014 Density in the datacenter refers to the electric power consumed per square foot of floor space (or unit volume of space), number of servers, and the cooling

More information

+31 88 96 000 00 www.asperitas.com ASPERITAS COMPANY Privately owned and funded Rolf Brink/Markus Mandemaker History Aecorsis BV founded in 2014 Modernising the marine industry Micro datacentre for marine

More information

VMware Join the Virtual Revolution! Brian McNeil VMware National Partner Business Manager

VMware Join the Virtual Revolution! Brian McNeil VMware National Partner Business Manager VMware Join the Virtual Revolution! Brian McNeil VMware National Partner Business Manager 1 VMware By the Numbers Year Founded Employees R&D Engineers with Advanced Degrees Technology Partners Channel

More information

How High-Density Colocation and Enhanced Visibility Improve Business Performance

How High-Density Colocation and Enhanced Visibility Improve Business Performance How High-Density Colocation and Enhanced Visibility Improve Business Performance Steven So Vice President Data Center Business Cloud Business Division NTT Com Asia Limited 11 Sep 2015 NTT Communications

More information

Modular and Scalable Power Converters in the UPS Industry

Modular and Scalable Power Converters in the UPS Industry A-PDF Split DEMO : Purchase from www.a-pdf.com to remove the watermark Modular and Scalable Power Converters in the Industry Ian Wallace Eaton Corporation, Innovation Center 1 Eaton Overview Eaton Electric

More information

Journey to the Cloud Next Generation Infrastructure for the future workforce.

Journey to the Cloud Next Generation Infrastructure for the future workforce. Journey to the Cloud Next Generation Infrastructure for the future workforce. Steven J. Davis Managing Director Infrastructure Consulting ASEAN Accenture What is the Internet & Cloud The Internet traditionally

More information