1 Training presentation for: AHCA Florida 2016 Annual Conference Finding & Managing Power System Vulnerabilities David Stymiest, CHFM, CHSP, FASHE, (PEin LA MS MA) Copyright 2016, Smith Seckman Reid, Inc.; All rights reserved Major topics Finding common mode failure potential Improving communication Planning for different types of failures Assessing reliability, availability and dependability Importance of inspection, maintenance & testing Lessons learned from natural disasters and other events Disclaimer Content Disclaimer: These slides are only meant to be cue points, which were expounded upon verbally by the original presenter and are not meant to be comprehensive statements of requirements or best practices, nor represent all the content of the presentation. Thus, care should be exercised in interpreting content based solely on the content of these slides. David Stymiest, PE CHFM CHSP FASHE. 1
2 NFPA Disclaimer Although the speaker is on the NFPA Technical Committee on Emergency Power Supplies, which is responsible for NFPA 110 and 111, the views and opinions expressed in this presentation are purely those of the speaker and shall not be considered the official position of NFPA or any of its Technical Committees and shall not be considered to be, nor be relied upon as, a Formal Interpretation. Readers are encouraged to refer to the entire texts of all referenced documents. NFPA members can obtain staff interpretations of NFPA standards at A new paradigm Reliability Probability that system operates and gives the same result on successive trials Availability Probability that system will function at any instant required, including the next instant, and for as long as required from that point Dependability Measures availability, reliability & maintenance support Lessons from real failures Lessons from real failures Things break Ask critical questions Pay attention to the details Commonalities & history Common-mode failures Analyze impact of what if scenarios Importance of testing & maintenance Comprehensive vulnerability analyses David Stymiest, PE CHFM CHSP FASHE. 2
3 MORE lessons from real failures Lessons from real failures Generators run out of fuel No cell service to call for assistance Poor or impossible travel conditions Cascading system failures Staff training FEMA realities during an emergency Ongoing ITM is very important You can t control what you can t control The details will get you Simplified power system Potential vulnerabilities to consider David Stymiest, PE CHFM CHSP FASHE. 3
4 Managing vulnerabilities Finding Prioritizing Assessing Reporting Mitigating Verifying Common-mode failures Failures of two or more components or systems due to a single event or cause Identified failure mode can usually be mitigated by adding extra or redundant equipment Cannot correct unidentified failure modes Uncorrected common mode failure removes advantage of other redundancies Common-mode failures Normal and emergency power equipment on same level Fuel oil transfer pump set subject to flooding Common fuel oil transfer pumps, controls, power circuits Feeders for elevated equipment located in flooded levels Contaminated fuel oil system Co-location of equipment & systems One sump pump or multiple sump pumps on same panel Transfer switch failure David Stymiest, PE CHFM CHSP FASHE. 4
5 Common location / subsystems Paralleled generator sets can mitigate the impact of one generator failure. Can also be subject to common- mode failures: Sharedlocation Shared fuel system Shared cooling system Common distribution Paralleling switchgear Control power failure Internal short circuit (fault) Low probability but very high impact May become apparent when EPSS is energized next. Mitigating vulnerabilities All power systems and equipment Understand Plan Inspect Test Maintain Remove David Stymiest, PE CHFM CHSP FASHE. 5
6 Explaining Normal vs. Emergency Power Generator is usually off Red (Emerg.) Outlet Emergency Generator Explaining Normal vs. Emergency Power Simplified Emergency Power Supply System Generator on Red (Emerg.) Outlet Emergency Generator Types of failures Normal down with emergency power working 1 emergency power branch down, normal working, other branches working Total electrical failure Simultaneously Cascading events speaker to request teaching slides David Stymiest, PE CHFM CHSP FASHE. 6
7 Most common generator failures Starting system problems Fuel oil system problems Cooling system problems Installation error / lack of acceptance testing Inadequate maintenance Overloads generators, breakers, fuses Load shed malfunctions multiple generators fail Other causes of generator failures Lightning power surge damages generator controls Generator auxiliaries on normal power (fans, fuel transfer pumps) Failures during routine testing (thrown engine rod, fuel hose rupture) Other mechanical or electrical failures Generator breaker trips lack of protective coordination Planning for Internal Failures Contingency planning: details important Doesn t need to be long Just needs to be correct for templates David Stymiest, PE CHFM CHSP FASHE. 7
8 Planning for Internal Failures Consider different failure points Different responses Don t wait until failure occurs Approach to vulnerabilities 1. Consider each component 2. What if? scenarios, including feeders 3. Common-mode failure potential 4. All possible causes of those scenarios 5. Address all resulting vulnerabilities Preparedness for power failures Things break Sweat small stuff Small issues can take out systems Different failures When to plan? David Stymiest, PE CHFM CHSP FASHE. 8
9 Vulnerability Analysis: Infrastructure Infrastructure design, features, components, condition, locations, operating flexibility, spares, maintenance histories, vulnerabilities Electrical service and NP distribution EPSS and its auxiliary subsystems (FO +) ATSs, feeders, branches Power system documentation, labeling, failure procedures, test results, training Vulnerability Analysis: Power Sources NP system: major distribution EP system, Gen, ATS, ATS sources Sortinfrastructure systems, facility areas and facility services by each power train By each main switchboard, generator, ATS Equipment or wiring failures take out redundant systems / areas / functions? Common mode failure vulnerability analysis Vulnerability Analysis: Areas For important functional areas, look at: Higher vulnerability from infrastructure analysis Less dependable equipment Poorer documentation Inadequate power failure procedures Inadequate training Higher vulnerability from common mode failure vulnerability analysis All other vulnerability assessment tools David Stymiest, PE CHFM CHSP FASHE. 9
10 System vulnerabilities: examples Inadequate acceptance testing Common-mode failure potential ATSs not maintained regularly Because not bypass-isolation type ATSs not transferred every month Lack of switchboard / breaker maintenance Lack of EES maintenance Vulnerability analysis results Preparedness Activities Additional capacity Emergency equipment Identify additional resources More training / testing Contingency planning Mitigation Activities Policies & procedures Change in process Maintenance program (Plan electrical shutdowns) Infrastructure repair/upgrade Tighten rooms Leak detection Gap analysis for VULNERABILITIES Gap Analysis can also address results of Vulnerability Analysis How vulnerable is EP System to failures? How vulnerable is NP System to failures? Where are the common-mode failure vulnerabilities? How to mitigate these vulnerabilities Short term Long term David Stymiest, PE CHFM CHSP FASHE. 10
11 Gap analysis for SUPPLIED SERVICES Examples: fuel oil supplier, generator or ATS service company, spare parts supplier Service provider vulnerability or over-commitment Systematically identify gaps between where the supplier s crisis management capabilities end and your contingency plans begin. Fix them. PdM Example: Infrared Thermography Predictive maintenance (PdM) vs. calendar-based maintenance (PM) Many facilities already scan NP equipment Include generator panel, paralleling switchgear, and transfer switches in IR scanning scope of work. Scan paralleling switchgear when it is energized. Some other PdM examples Diesel generator fluid testing Fuel oil testing is required annually BEST PRACTICE also testing lubricating oil & cooling water Rotating equipment vibration analysis Ultrasonic analysis David Stymiest, PE CHFM CHSP FASHE. 11
12 Electrical room maintenance Learn from required weekly EPSS inspections Cleaning rooms: minimize contaminants finding their way inside the electrical equipment Change the filters Inspect for evidence of water Leak detection in electrical rooms Warns of water-based vulnerabilities when relocation is not practical Mech/Elect co-locations Elevation issues External water Internal piping leaks Broken sumps Risk assessment considerations Transfer switches maintenance history Normal power operational history Normal power maintenance history User and facility management action plans EP system maintenance shutdowns Thermographic scanning results Infrastructure conditions David Stymiest, PE CHFM CHSP FASHE. 12
13 Competency training for maintainers Responses to various internal failures Responses to simultaneous multiple utility failures Operation of different equipment, not just the same equipment every month Understand and look for second order consequences Thank You! David Stymiest, P.E., CHFM, CHSP, FASHE (P.E. in LA, MS, MA) Senior Consultant Smith Seckman Reid, Inc. Compliance News archives and sign-up are available at: David Stymiest, PE CHFM CHSP FASHE. 13
NFPA members can obtain staff interpretations of NFPA standards at Although the speaker is Chairman of the NFPA.
2014 TAHFM Interlink Conference Managing Electrical Systems for Reliability David Stymiest, PE, CHFM, CHSP, FASHE DStymiest@ssr-inc.com, cell 504.232.1113 Copyright 2014, Smith Seckman Reid, Inc., All
More informationPlanning for Power Failures
David Stymiest, P.E., CHFM, FASHE Senior Consultant Compliance and Facilities Management Smith Seckman Reid, Inc. DStymiest@ssr-inc.com This paper was originally delivered at the ASHE 44 th Annual Conference,
More informationA Practical Guide to Avoiding Disasters in Mission-Critical Facilities. What is a Disaster? Associated Business Issues.
A Practical Guide to Avoiding Disasters in Mission-Critical Facilities Todd Bermont What is a Disaster? An event that can unexpectedly impact the continuity of your business Anything that injures or has
More informationMitigating Arc Flash Hazards
1910DB1402 / March, 2015 by Antony Parsons, Ph.D., P.E. and Reza Tajali, P.E. Schneider Electric Engineering Services Make the most of your energy SM Contents 1.0 Introduction... 3 2.0 What is Arc Flash
More informationTitle Substations - Base Safety & Operating Standards. Reference Number POP 07 - (RIC Standard: EP SP)
Discipline Engineering Standard - NSW Category Electrical Title Reference Number POP 07 - (RIC Standard: EP 99 00 00 04 SP) Document Control Status Date Prepared Reviewed Endorsed Approved Mar 05 Standards
More informationSwitchgear Design Impacts the Reliability of Backup Power Systems
Switchgear Design Impacts the Reliability of Backup Power Systems December 2010/AT307 by Reza Tajali, P.E. Square D Power Systems Engineering Make the most of your energy SM Revision #1 12/10 When a cascaded
More informationIT CONTINUITY, BACKUP AND RECOVERY POLICY
IT CONTINUITY, BACKUP AND RECOVERY POLICY IT CONTINUITY, BACKUP AND RECOVERY POLICY Effective Date May 20, 2016 Cross- Reference 1. Emergency Response and Policy Holder Director, Information Business Resumption
More informationSwitchgear Survival Guide: Ten Tips to Optimize Switchgear and Enhance Reliability
Switchgear Survival Guide: Ten Tips to Optimize Switchgear and Enhance Reliability 1910DB1207 By Hal Theobald, Product Marketing Manager, Schneider Electric Services Summary 1.0 Abstract...3 2.0 Introduction...3
More informationCPS VS UPS FOR POWERING DATA CENTERS
CPS VS UPS FOR POWERING DATA CENTERS HOW THE ADVANTAGES OF A NO BREAK CONVERGED POWER SYSTEM (CPS) PROVIDED BETTER POWER RELIABILITY, SYSTEM AVAILABILITY AND REDUCED COSTS OVER A UNINTERRUPTABLE POWER
More informationSECTION ENCLOSED SWITCHES AND CIRCUIT BREAKERS
SECTION 262816 - ENCLOSED SWITCHES AND CIRCUIT BREAKERS PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division
More informationThe City of St. Petersburg (City) initiated
FWRJ Remote Facility Condition Inspections and Subsequent Integration into the City of St. Petersburg s Asset Management Program Laura Baumberger, Robert Labrie, and Rebecca Overacre The City of St. Petersburg
More informationFlorida State University
Florida State University Disaster Recovery & Business Continuity Planning Overview October 24, 2017 1 Key Readiness Questions Has your department identified the business functions and infrastructure that
More informationPredictive Maintenance in a Mission Critical Environment
CSI 2130 Predictive Maintenance in a Mission Critical Environment This paper discusses the need to proactively protect mechanical and electrical support systems in data processing centers and data storage
More informationZenith Series STS-3 Static Transfer Switches
GE Energy Connections Zenith Series STS-3 Static Transfer Switches 60Hz UL Version, 150-1600AMP Seamless Input Source Transfers for Sensitive Critical Loads. Touching all Areas of the Energy Industry GE
More information9/18/2017 PLANS STRATEGIES AND TOOLS. SAHRA: The 5 Ways to Improve Emergency Management and Business Continuity Plans 9/20/17 3 PRESENTATION AGENDA
PLANS The 5 Ways to Improve STRATEGIES AND TOOLS Emergency Management and Business Continuity Plans PRESENTATION AGENDA Ice Breaker What steps would you take after a flood? 5 Ways to improve emergency
More informationContinuity of Business
White Paper Continuity of Business SAS Continuity of Business initiative reflects our commitment to our employees, to our customers, and to all of the stakeholders in our global business community to be
More informationMinimum Support Needed for a Reliable SCADA System
Minimum Support Needed for a Reliable SCADA System Speaker Bio Jeff Miller, PE, ISI ENV SP Dewberry Automation Manager MEP Service Line Raleigh, NC 22 years experience in Electrical / Instrumentation &
More information7 Best Practices for Increasing Efficiency, Availability and Capacity. XXXX XXXXXXXX Liebert North America
7 Best Practices for Increasing Efficiency, Availability and Capacity XXXX XXXXXXXX Liebert North America Emerson Network Power: The global leader in enabling Business-Critical Continuity Automatic Transfer
More informationTUFTS HEALTH PLAN CORPORATE CONTINUITY STRATEGY
JUNE 2017 TUFTS HEALTH PLAN CORPORATE CONTINUITY STRATEGY OVERVIEW The intent of this document is to provide external customers and auditors with a high-level overview of the Tufts Health Plan Corporate
More informationMassMutual Business Continuity Disclosure Statement
MassMutual Business Continuity Disclosure Statement Overview Resiliency is a high priority at Massachusetts Mutual Life Insurance Company ( MassMutual or the Company ). To that end, significant investments
More informationUnderstanding SCCR. THE BEST ELECTRICAL CONTROLS BUSINESS ON THE PLANET! Unmatched Service Superior Product Quality Advantage Pricing
Understanding SCCR What is SCCR? When it comes to industrial machinery, it s critical to ensure that electrical panels are designed and built with the proper SCCR to maintain the system, eliminate downtime
More information1.0 Executive Summary
Statement of Work - 1 - Power and Cooling Assessment for Data Center Professional Services Service 1.0 Executive Summary Table of Contents 1.0 Executive Summary 2.0 Features & Benefits 3.0 Details of Service
More informationColocation Checklist Not all data centers are created equal.
Colocation Checklist Not all data centers are created equal. They vary in performance, reliability, control and security standards. Know what to look for in a colocation provider with this comprehensive
More informationLVTS RULE 11 CHANGE MANAGEMENT, TESTING AND CERTIFICATION 2018 CANADIAN PAYMENTS ASSOCIATION
LVTS RULE 11 CHANGE MANAGEMENT, TESTING AND CERTIFICATION 2018 CANADIAN PAYMENTS ASSOCIATION This Rule is copyrighted by the Canadian Payments Association. All rights reserved, including the right of reproduction
More informationNFPA 3000 (PS) Standard for an Active Shooter / Hostile Event Response (ASHER) Program IT S A BIG WORLD. LET S PROTECT IT TOGETHER.
NFPA 3000 (PS) Standard for an Active Shooter / Hostile Event Response (ASHER) Program IT S A BIG WORLD. LET S PROTECT IT TOGETHER. TM Active Shooter Incidents: 2000-2017 2 Active Shooter Incidents: 2016
More informationIEEE 2014 T&D Conference Paper 14TD Storm & Flood Hardening of Electrical Substations
1 IEEE 2014 T&D Conference Paper 14TD0564 - Storm & Flood Hardening of Electrical Substations FORUM 2 Transformers, Substations and Switchgear Forum Room: W185BC, Paper: 14TD0564 Tuesday, April 15, 2014
More informationSECTION (16410) - ENCLOSED SWITCHES AND CIRCUIT BREAKERS
SECTION 26 28 16 (16410) - ENCLOSED SWITCHES AND CIRCUIT BREAKERS PART 1 GENERAL 1.01 SUMMARY A. Section Includes: 1. Individually Mounted Switches and Circuit Breakers Used for the following: a. Service
More informationCANADIAN PAYMENTS ASSOCIATION LVTS RULE 11 CHANGE MANAGEMENT, TESTING AND CERTIFICATION
CANADIAN PAYMENTS ASSOCIATION LVTS RULE 11 LVTS Rule 11, December 1998: as amended November 25, 2002, November 24, 2003, May 31, 2004, August 14, 2006, January 28, 2008, August 16, 2010, January 1, 2013,
More informationToday s Webcast starts at 1:00 p.m. Eastern. You will not hear audio until the Webcast begins
Today s Webcast starts at 1:00 p.m. Eastern. You will not hear audio until the Webcast begins Today's Moderator Ed Sulivan Editor Today's Presenter Steve Maling Director, US Field Services Marketing, Schneider
More informationImproving the Resilience of Critical Infrastructure from Natural Hazards
Improving the Resilience of Critical Infrastructure from Natural Hazards David Murphy Assistant Director Natural Hazards Team Civil Contingencies Secretariat Outline Civil Contingencies Secretariat Vulnerability
More informationASCO 7000 SERIES Power Control Systems
ASCO 7000 SERIES Power Control Systems 1 7000 SERIES PCS LINEUP ASCO 7000 SERIES Power Control Systems (PCS) offer the most advanced power management features for mission-critical facilities. Every 7000
More informationData Center Facility Analysis Project. Final Presentation Wednesday, July 22, :30 3:30 PM
Data Center Facility Analysis Project Final Presentation Wednesday, July 22, 2009 1:30 3:30 PM 1 Commonwealth Technology Center Conference Rooms 1 & 2 Enterprise Server Farm (ESF) Facility Data: 1 Technology
More informationPower Quality of Commercial Buildings - Advanced
Buildings - Advanced Hartford Steam Boiler One State Street P.O. Box 5024 Hartford, CT 06102-5024 Tel: (800) 472-1866 www.munichre.com/hsb May 2017 Background Power quality is a general term used to describe
More informationAppendix 3 Disaster Recovery Plan
Appendix 3 Disaster Recovery Plan DRAFT March 5, 2007 Revision XX Qwest Government Services, Inc. 4250 North Fairfax Drive Arlington, VA 22203 A3-i RFP: TQC-JTB-05-0002 March 5, 2007 REVISION HISTORY Revision
More informationThe next generation of knowledge and expertise
The next generation of knowledge and expertise UNDERSTANDING FISMA REPORTING REQUIREMENTS 1 HTA Technology Security Consulting., 30 S. Wacker Dr, 22 nd Floor, Chicago, IL 60606, 708-862-6348 (voice), 708-868-2404
More informationSECTION PANELBOARDS
SECTION 16450 PART 1 - GENERAL 1.01 DESCRIPTION A. Section includes requirements for panelboards providing fault interrupting capability and overcurrent protective devices. 1.02 REFERENCE STANDARDS A.
More informationTable of Contents. Sample
TABLE OF CONTENTS... 1 CHAPTER 1 INTRODUCTION... 4 1.1 GOALS AND OBJECTIVES... 5 1.2 REQUIRED REVIEW... 5 1.3 APPLICABILITY... 5 1.4 ROLES AND RESPONSIBILITIES SENIOR MANAGEMENT AND BOARD OF DIRECTORS...
More informationEXTENDING THE LIFECYCLE OF AGEING DATA CENTRES:
EXTENDING THE LIFECYCLE OF AGEING DATA CENTRES: HOW AND WHAT SHOULD DC s DO FOR RETROFITS Jonathan Price 4 th August 2015 KEY DRIVERS FOR UPGRADING A DATA CENTRE Capacity Resilience Efficiency Lifecycle
More informationInstallation Service. 1.0 Executive Summary. Factory Trained Technician Train Customer Support Staff On Basic Operation Of The Equipment
Installation Service Statement of Work Start-up Service for Cooling Start-up - 1 - Service for Cooling Service 1.0 Executive Summary Table of Contents 1.0 Executive Summary 2.0 Features & Benefits 3.0
More informationEmergency Support Function (ESF) #14a: UTILITIES: Central Electric & Steam. ESF Activation Contact: Cornell IPP Customer Service (607)
Emergency Support Function (ESF) #14a: UTILITIES: Central Electric & Steam ESF Activation Contact: Cornell IPP Customer Service (607)255-5322 Primary Department I. Purpose: Cornell IPP: Utilities and Energy
More informationSTATE DATA CENTER DRAFT PROPOSAL. STATE OF OREGON DATA CENTER 28 October 2016
STATE DATA CENTER DRAFT PROPOSAL 1 PROJECT TEAM 2 SERA Architects, Inc George Hager Patrick Sullivan PAE Engineers Dave Williams Doug Nachtrieb Michael Yee JMB Consulting Group Jon Bayles MEETING GOALS
More informationIXcellerate Moscow One Datacentre - Phase 1 & 2 Overview
Contents 1. Document Purpose... 2 2. Facility Overview... 2 2.1 Technical Space... 2 2.2 Load Density... 2 2.3 Resilience... 2 2.4 Engineering Plant Maintenance & Service Restoration... 3 3. Engineering
More informationStrategies for managing distributed IT environments. Anne-Marie Gignac Vice President Networking Solutions Schneider Electric
Strategies for managing distributed IT environments Anne-Marie Gignac Vice President Networking Solutions Schneider Electric APC by Schneider Electric Anne-Marie Gignac May 8, 2012 Agenda Trends & Challenges
More informationISO STANDARD IMPLEMENTATION AND TECHNOLOGY CONSOLIDATION
ISO STANDARD IMPLEMENTATION AND TECHNOLOGY CONSOLIDATION Cathy Bates Senior Consultant, Vantage Technology Consulting Group January 30, 2018 Campus Orientation Initiative and Project Orientation Project
More informationNational Fire Protection Association. 1 Batterymarch Park, Quincy, MA Phone: Fax:
National Fire Protection Association 1 Batterymarch Park, Quincy, MA 02169-7471 Phone: 617-770-3000 Fax: 617-770-0700 www.nfpa.org M E M O R A N D U M TO: Members of the NEC-Code Making Panel 11 FROM:
More informationSERVERS / SERVICES AT DATA CENTER AND CO-LOCATION POLICY
SERVERS / SERVICES AT DATA CENTER AND CO-LOCATION POLICY National Video Conferencing Network Version 1.0 Released January 01, 2014 HIGHER EDUCATION COMMISSION, PAKISTAN 1 GENERAL The Higher Education Commission
More informationDR Planning. Presented by. Matt Stolk Associate Director Northwest Regional Data Center Florida State University
DR Planning Presented by Matt Stolk Associate Director Northwest Regional Data Center Florida State University Why are we here? Over the last couple of years, business continuity has become more of a priority
More informationMember of the County or municipal emergency management organization
EMERGENCY OPERATIONS PLAN SUUPPORT ANNEX B PRIVATE-SECTOR COORDINATION Coordinating Agency: Cooperating Agencies: Chatham Emergency Management Agency All Introduction Purpose This annex describes the policies,
More informationPresented by Joe Burns Kentucky Rural Water Association July 19, 2005
Infrastructure Security for Public Water and Wastewater Utilities Presented by Joe Burns Kentucky Rural Water Association July 19, 2005 Public Health Security and Bioterrorism Preparedness and Response
More informationEmergency Management BC Update
Emergency Management BC Update Provincial Emergency Program Emergency Management BC Update on Initiatives Union of BC Municipalities 2016 Conference September 29, 2016 Agenda Emergency Management BC Overview
More informationPulse LED Instruction Guide
PARTS LIST Light Fixture Aquarium Frame Mounts Instruction Guide WARNING: To guard against injury, basic precautions should be observed, including the following: A) READ AND FOLLOW ALL SAFETY INSTRUCTIONS.
More informationBuilding a BC/DR Control Library and Regulatory Response Program
Building a BC/DR Control Library and Regulatory Response Program David Garland, Senior Director, Disaster Recovery & Regulatory Compliance, Business Continuity Management CME Group Regulatory Compliance
More informationHazard Management Cayman Islands
Hazard Management Cayman Islands Strategic Plan 2012 2016 Executive Summary HMCI strategic plan outlines the agency s outlook in the next five years and illustrates the main strategies as goals that will
More informationCOOP and Disaster Recovery with Symantec
COOP and Disaster Recovery with Symantec Agenda 1 Setting the Stage 2 Evolving Continuity Landscape 3 Proven Approach to Succeed 4 Symantec Solution Overview 5 Conclusions and Recommendations 2007 Symantec
More informationMedical and Life-Safety Systems
Medical and Life-Safety Systems Balancing Life-Safety and Critical System Reliability PRESENTED BY Michael Fluegeman, PE Principal, PlanNet Learning Objectives Identify the unique operational aspects of
More informationSmall Business Storm Preparedness & Resiliency
Small Business Storm Preparedness & Resiliency Deborah Mills, CFM Dewberry Consultants, LLC Agenda Introduction to small business preparedness and resiliency Beverly MA, Brooklyn, New Orleans case studies
More information10 Reasons Why Your DR Plan Won t Work
10 Reasons Why Your DR Plan Won t Work Jim Damoulakis CTO, GlassHouse Technologies, Inc. Sept. 29, 2005 DR Vision Imagine Prepared to handle multiple categories of disaster Clearly documented policies
More informationAPC by Schneider Electric Elite Data Centre Partner
Data Centre Solutions...energy efficient by design APC by Schneider Electric Elite Data Centre Partner APC s leading Elite Data Centre Solutions Partner providing customers with expert advice, integration
More informationChapter 8: SDLC Reviews and Audit Learning objectives Introduction Role of IS Auditor in SDLC
Chapter 8: SDLC Reviews and Audit... 2 8.1 Learning objectives... 2 8.1 Introduction... 2 8.2 Role of IS Auditor in SDLC... 2 8.2.1 IS Auditor as Team member... 2 8.2.2 Mid-project reviews... 3 8.2.3 Post
More informationCYBER SECURITY FOR WATER AND WASTEWATER UTILITIES PRESENTED BY: DAVID A. CHANDA, PE
CYBER SECURITY FOR WATER AND WASTEWATER UTILITIES PRESENTED BY: DAVID A. CHANDA, PE Cyber Security A Hot Topic NotPetya Cyberattack 2018 Thales Data Threat Report Tempting Cedar Spyware Implementation
More informationStruxureWare Power Monitoring Expert for Healthcare 7.2
StruxureWare Power Monitoring Expert for Healthcare 7.2 Commissioning Guide 7EN42-0070-04 09/2013 Safety Information Read these instructions carefully and look at the equipment to become familiar with
More informationNHS Gloucestershire Clinical Commissioning Group. Business Continuity Strategy
NHS Gloucestershire Clinical Commissioning Group 1 Document Control Title of Document Gloucestershire CCG Author A Ewens (Emergency Planning and Business Continuity Officer) Review Date February 2017 Classification
More information3- and 4-pole switching in UPS installation
Smart tricks to improve power supply reliability White paper series Power Distribution & UPS 3- and 4-pole switching in UPS installation Janne Paananen Technology Manager, Critical Power Solutions, Eaton
More information10 Cybersecurity Questions for Bank CEOs and the Board of Directors
4 th Annual UBA Bank Executive Winter Conference February, 2015 10 Cybersecurity Questions for Bank CEOs and the Board of Directors Dr. Kevin Streff Founder, Secure Banking Solutions 1 Board of Directors
More information1510 MOTOR CONTROLLERS
SECTION 262913- MOTOR CONTROLLERS PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of contract, including general and supplementary conditions and Division 1 specification section,
More informationHow AlienVault ICS SIEM Supports Compliance with CFATS
How AlienVault ICS SIEM Supports Compliance with CFATS (Chemical Facility Anti-Terrorism Standards) The U.S. Department of Homeland Security has released an interim rule that imposes comprehensive federal
More informationData Center Assessment Helps Keep Critical Equipment Operational. A White Paper from the Experts in Business-Critical Continuity TM
Data Center Assessment Helps Keep Critical Equipment Operational A White Paper from the Experts in Business-Critical Continuity TM Executive Summary The IT infrastructure within many companies has evolved
More informationPurpose. ERO Enterprise-Endorsed Implementation Guidance
Lesson Learned CIP Version 5 Transition Program CIP-002-5.1 Requirement R1: Impact Rating of Generation Resource Shared BES Cyber Systems Version: January 29, 2015 Authorized by the Standards Committee
More informationDoDI IA Control Checklist - MAC 1-Classified. Version 1, Release March 2008
DoDI 8500-2 IA Control Checklist - MAC 1-Classified Version 1, Release 1.4 Developed by DISA for the DOD UNTILL FILLED IN CIRCLE ONE FOR OFFICIAL USE ONLY (mark each page) CONFIDENTIAL and SECRET (mark
More informationSRI LANKA STANDARD CODE OF PRACTICE FOR GRID CONNECTED PHOTOVOLTAIC POWER SYSTEMS SLS 1522:2016
SRI LANKA STANDARD CODE OF PRACTICE FOR GRID CONNECTED PHOTOVOLTAIC POWER SYSTEMS SLS 1522:2016 BY H S W Karunaratne Assistant Director - Engineering Sri Lanka Standards Institution. 1 DEFINITIONS Ac module:
More informationDisaster Preparedness Community Emergency Response Team
Disaster Preparedness Community Emergency Response Team Berkeley CERT Disaster Preparedness Unit Objectives Describe the types of hazards to which your community is vulnerable Describe the functions of
More informationATS-16 HV USER MANUAL. Automatic Transfer Switch 16A / 230Vac V090318
ATS-16 HV Automatic Transfer Switch 16A / 230Vac USER MANUAL V090318 SAFETY Intended use The ATS-16 HV device serves as a power source selector to provide improved power supply for connected loads. ATS-16
More informationHOTEL RESILIENT Plan ahead stay ahead. With support from the German Government through
HOTEL RESILIENT Plan ahead stay ahead With support from the German Government through WHAT CAN GO WRONG WILL GO WRONG Murphy s Law More than 40% of hotels do not reopen after large disasters FEMA 2010
More informationTitle System Substation Commissioning Tests. Reference Number PCP 07 - (RIC Standard: EP SP)
Discipline Engineering Standard - NSW Category Electrical Title s Reference Number PCP 07 - (RIC Standard: EP 99 00 00 02 SP) Document Control Status Date Prepared Reviewed Endorsed Approved Mar 05 Standards
More informationWHITE PAPER- Managed Services Security Practices
WHITE PAPER- Managed Services Security Practices The information security practices outlined below provide standards expected of each staff member, consultant, or customer staff member granted access to
More informationOptimized MV Generator Power Plant Architectures for Large Data Centers
Optimized MV Generator Power Plant Architectures for Large Data Centers White Paper 262 Revision 0 by Julien Moreau Malik Megdiche Daniel Radu Executive summary For large (>5 MW) data center applications,
More informationSE Engineering, PC strives to be a leader in the power system engineering field by providing our customers with the highest level of quality,
SE Engineering, PC strives to be a leader in the power system engineering field by providing our customers with the highest level of quality, integrity, and innovation. Our mission is to offer the safest,
More informationPower Quality of Commercial and Industrial Power Systems
Hanover Risk Solutions Power Quality of Commercial and Industrial Power Systems Power quality is a general term used to describe the quality of several different power-related characteristics. These characteristics
More informationSECTION TRANSIENT VOLTAGE SUPPRESSION FOR LOW-VOLTAGE ELECTRICAL POWER CIRCUITS
SECTION 264313 - TRANSIENT VOLTAGE SUPPRESSION FOR LOW-VOLTAGE ELECTRICAL POWER CIRCUITS PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and
More informationHIPAA RISK ADVISOR SAMPLE REPORT
HIPAA RISK ADVISOR SAMPLE REPORT HIPAA Security Analysis Report The most tangible part of any annual security risk assessment is the final report of findings and recommendations. It s important to have
More informationWHITE PAPER. Distribution Substation Outage Investigations. Overview. Introduction. By Ahmad Shahsiah, Ph.D., P.E. March 2018
WHITE PAPER Distribution Substation Outage Investigations By Ahmad Shahsiah, Ph.D., P.E. March 2018 Overview Electrical distribution systems in the United States served approximately 152 million customers
More informationCisco CRS 3-Phase AC Power Distribution Unit Installation Guide 2. Cisco CRS 3-Phase AC Power Distribution Unit 2
Cisco CRS 3-Phase AC Power Distribution Unit Installation Guide Cisco CRS 3-Phase AC Power Distribution Unit Installation Guide 2 Cisco CRS 3-Phase AC Power Distribution Unit 2 Revised: November 18, 2016,
More informationCorporate Security & Emergency Management Summary of Submitted 2015 Budget From Rates
Corporate Security & Emergency Management Summary of Submitted 2015 From Rates Service Expense 2014 2015 Revised Non Tax Revenue Net Tax Supported Expense Draft Non Tax Revenue Net Tax Supported Increase
More informationFundamentals of Circuit Breaker Maintenance. AVO Training Institute, Inc. 2018
Fundamentals of Circuit Breaker Maintenance 1 AVO Training Institute, Inc. 2018 Moderator n Ron Spataro AVO Training Institute Marketing Manager 2 Q&A n Send us your questions and comments during the presentation
More informationReal-Time Health Monitoring of Civil Works to Enhance Emergency Action
Real-Time Health Monitoring of Civil Works to Enhance Emergency Action 2009 Dr. W. Allen Marr, PE President and CEO Geocomp Corporation Andrew R. Sachs Vice President for Crisis & Consequence Management
More informationBecause Security Gives Us Freedom
Because Security Gives Us Freedom PANOPTIC CYBERDEFENSE CYBERSECURITY LEADERSHIP Panoptic Cyberdefense is a monitoring and detection service in three levels: Security Management and Reporting Managed Detection
More information2 ESF 2 Communications
2 ESF 2 Communications THIS PAGE LEFT BLANK INTENTIONALLY Table of Contents 1 Introduction... 1 1.1 Purpose and Scope... 1 1.2 Relationship to Other ESF Annexes... 1 1.3 Policies and Agreements... 1 2
More informationPipeline Unit/Station Control. Combining Unit and Station Control into Siemens PCS 7. Application Brief
Pipeline Unit/Station Control Combining Unit and Station Control into Siemens PCS 7 Application Brief Pipeline Unit/Station Control Application Description... 1 Process Description...1 Process Drawing...1
More informationCable Facility Classification Definitions and Requirements
ENGINEERING COMMITTEE Energy Management Subcommittee AMERICAN NATIONAL STANDARD ANSI/SCTE 226 2015 Cable Facility Classification Definitions and Requirements NOTICE The Society of Cable Telecommunications
More informationDisaster Recovery Committee. Learning Resource Center Specialist
This document is intended to provide operational procedures and serve as a reference for the Key Information Technology Personnel at Community Higher Ed Disaster Recovery Community Higher Ed Disaster Recovery
More informationChapter 18 SaskPower Managing the Risk of Cyber Incidents 1.0 MAIN POINTS
Chapter 18 SaskPower Managing the Risk of Cyber Incidents 1.0 MAIN POINTS The Saskatchewan Power Corporation (SaskPower) is the principal supplier of power in Saskatchewan with its mission to deliver power
More informationQGV Units with G-120 Drives IMMEDIATE ACTION REQUIRED IMPORTANT PRODUCT SAFETY NOTICE
Service Alert Communications To: All Quincy Distributors From: Quincy Compressor Subject: Service Alert #389 Date: 02/01/2013 QGV Units with G-120 Drives IMMEDIATE ACTION REQUIRED IMPORTANT PRODUCT SAFETY
More informationRisk Mitigation of Aging Electrical Infrastructure
Risk Mitigation of Aging Electrical Infrastructure 2014 66 th Annual Conference 2pm Tuesday May 8 th, 2014 Presented by Dick McDonnell Authored by Jeff M. Miller, PE, ENV SP About the Presenter Dick McDonnell
More informationDisasters & The Disaster Response Inspector
Disasters & The Disaster Presenter: William Bracken Tuesday, September 12, 2017 8:00 AM - 9:30 AM Disaster Planning and the Disaster Response Inspector Disaster Planning and the Disaster Course Objectives
More informationEffective: 12/31/17 Last Revised: 8/28/17. Responsible University Administrator: Vice Chancellor for Information Services & CIO
Effective: 12/31/17 Last Revised: 8/28/17 Responsible University Administrator: Vice Chancellor for Information Services & CIO Responsible University Office: Information Technology Services Policy Contact:
More informationTEL2813/IS2820 Security Management
TEL2813/IS2820 Security Management Security Management Models And Practices Lecture 6 Jan 27, 2005 Introduction To create or maintain a secure environment 1. Design working security plan 2. Implement management
More informationVirginia Department of Transportation Hampton Roads Bridge-Tunnel Action Plan Implementing the Independent Review Panel Recommendations
Virginia Department of Transportation Hampton Roads Bridge-Tunnel Action Plan Implementing the Independent Review Panel Recommendations Initial Panel Charge August 2009 To review existing policies and
More informationSubstation SCADA Monitoring
Substation SCADA Monitoring Contact us Today for a FREE quotation to deliver this course at your company?s location. https://www.electricityforum.com/onsite-training-rfq Substations are a critical component
More informationMaintenance Qualification: Improving Compliance and Performance in Pharmaceutical Manufacturing
Qualification: mproving Compliance and Performance in Pharmaceutical Manufacturing This article describes an approach to management that delivers enhanced compliance for direct GMP systems and improved
More informationHow to Underpin Security Transformation With Complete Visibility of Your Attack Surface
How to Underpin Security Transformation With Complete Visibility of Your Attack Surface YOU CAN T SECURE WHAT YOU CAN T SEE There are many reasons why you may be considering or engaged in a security transformation
More information