2 Power Monitoring in the Data Centre: Is the Right Time Now? Introduction Data centre power monitoring has been much discussed over recent years but without necessarily providing IT Managers with real, practical answers to many of the key questions. This paper, by exploring the answers to these questions, is designed as an aid to IT Managers wrestling with the problem of whether to implement power monitoring, what the likely benefits will be, and how to practically implement a power monitoring solution with minimal or no disruption to daily operations. 10 Key Questions 1. How can I reduce the power usage in my data centre? In order to move towards reducing power consumption in a data centre, the power in that data centre must first be monitored, recorded and assessed. This can be an extremely time consuming and costly process and potentially self-defeating if not carried out efficiently. Once some sort of mechanism is in place to enhance IT Managers understanding of the overall power consumption picture, opportunities will present themselves to obtain power usage reductions over time. If power monitoring can be carried out down to rack level, this provides the user with both the ability to make an assessment of what is happening within that rack and the capacity to make comparisons with other racks in the data centre. 2. Which racks in my data centre are using the most power and are the most expensive to run? Monitoring the input supplies on each individual rack will enable users to easily identify which racks are the most costly to run, and which the least. This comparison process can be invaluable in terms of providing a platform to focus on the areas where cost savings may be most easily obtained. Voltage data can be obtained although this is relatively straightforward as it should be fairly constant across the data centre as a whole, especially if power is supplied via a true online UPS. However, the collection of current data (amps) will be crucial to gaining a clear understanding of the variances in power consumption from rack to rack. A useful ratio to use when comparing rack power usage is A (where A is the total current draw of the rack) U (where U is the total amount of U space utilised in the rack) This ratio helps us to make comparisons between different racks irrespective of the amount of capacity utilised in each rack. So for instance: Rack 1 has a total current draw of 24A and U space utilisation of 22U. Rack 2 has a total current draw of 25A and U space utilisation of 30U. AU Ratio for Rack 1 = 1.09 AU Ratio for Rack 2 = 0.83

3 Rack 1 is clearly more power hungry than Rack 2, despite less U space utilisation. The average AU of all the data centre racks can be calculated as soon as monitoring of the total current (A) into each rack is available. Equipment can subsequently be added or taken away from racks in the future and more racks introduced, but the recalculated average AU figure will provide a straightforward means of proving that power usage is becoming more efficient over time, even if total power usage for the data centre increases. The Power Usage Effectiveness (PUE) ratio that is now used widely throughout the IT industry, is extremely useful as an overall measure of the power efficiency of a data centre. However, it is very difficult to use this ratio to compare the power efficiency of one data centre to another, as each and every data centre is different. Some may be running at full capacity, whilst others may be running at considerably less than full capacity. Space constraints (or otherwise) and the nature of the environment itself (the location, nature of the building, etc.) will all contribute to a data centre s PUE. Similarly, it is very difficult to compare the power efficiency of one rack to another but rack power monitoring and the adoption of the AU ratio, do provide a basis for recording and mapping power data over time with a view to achieving significant power usage reductions in the future (and proving that these power reductions have been achieved). 3. Can I reduce the power consumption in my data centre racks? The answer to this question, of course, is Yes, except that it will be possible for the total power consumption to actually increase where spare rack capacity has yet to be utilised. However, as long as power data is being recorded, there s no reason why the AU ratio cannot be reduced. 4. Can I assess whether it is more economical to invest in newer, less power-hungry IT equipment rather than continuing to run my existing equipment? Without the relevant power data, there is no way of knowing what the real power saving benefits will be of implementing new equipment. Power rating plates and specification information may not necessarily provide a reliable means of assessing the real power usage of a particular piece of equipment in site-specific operation. However, as soon as the before and after data can be captured, then it becomes very possible to gain visibility of the economic benefits or otherwise of implementing newer equipment from the power perspective. 5. Can temperature in the data centre be safely increased to help reduce air conditioning and air handling running costs? The hope, of course, is that by raising the temperature, even by very slight amounts, that power usage by the air conditioning and air handling units will be reduced. In order for this process to be successfully carried out, temperature should be monitored throughout the data centre, and ideally within each rack. As data centre cooling can make up such a high percentage of overall data centre power usage, the relationship between temperature and power is a critical one.

4 It can be extremely difficult to decide on what the optimum temperature level is for a particular data centre or server room, especially as different parts of the room and individual racks may be generating more heat than others. The beauty of being able to monitor power down to rack level is that it gives us the opportunity to see what effect, if any, the increase in temperature level has on the power usage in racks: If the power usage is higher this may point to an increase in the activation of server fans or rack fans, for instance. If this increased power usage is happening across multiple racks, it may very well negate the potential savings from running the room temperature at a higher level. Monitoring the rack power, together with temperature, provides us with the opportunity to safely see the effects of raising the temperature without compromising system availability. 6. Can I build up a clear picture of power usage over time that will enable me to reduce my AU ratio and running costs? There are likely to be some eye-opening findings once rack power monitoring is invoked. However, the real benefits will become more evident over the medium to long-term. As more and more relevant data is gathered, day-to-day decisions regarding the network infrastructure can be taken that involve power usage and the associated costs. If a power monitoring device is SNMP compliant, network management systems can be used to ensure that the power data needed is regularly recorded, stored and available for later analysis. However, if the network is expanding, it may be extremely difficult to reduce overall running costs, although it should still be possible to improve the AU ratio over time. 7. What effect do internal computer fans have on the AU ratio? The AU in any given rack will increase if server fans are active and the extent of the increased power draw can be evaluated by monitoring rack power. Internal server fans can use upwards of 10% of the overall power used by a server. Servers with fans that are controlled thermostatically increase fan speed as more cooling is needed and this, in turn, increases the power needed by that server. Rack power monitoring presents IT Managers with the opportunity to gain a clear understanding of the relationships between CPU usage, data centre (and rack) temperature, and power usage. Informed judgements can then be made as to whether it is more economical to reduce the overall room temperature for instance, or implement other mechanisms for reducing power usage such as improving ventilation and airflow. Power monitoring down to rack level may also be the only way of knowing that internal fans are actually becoming operative at all. That information alone could be extremely valuable in terms of understanding what is happening to the power in that rack and how best it can be managed to minimise costs. 8. Can I reduce power usage without compromising network operations? In a static world, the implementation of newer, more power efficient equipment will ultimately result in a reduction in AU. If reductions in the power used to drive rack peripherals (eg. fans in legacy racks) can be achieved, the AU will decrease also.

5 As knowledge surrounding rack power usage increases, so the capacity of the IT manager to implement power reductions will increase also. A sufficient understanding of the power usage situation will ensure that AU reductions will not compromise network availability. 9. Is it possible to be notified immediately about significant changes in data centre power and environmental conditions that may otherwise have serious repercussions for network availability? Monitoring devices are now equipped not only to monitor a variety of sensors (power, temperature, humidity, etc.), but they also have the capacity to provide management personnel with immediate notification should abnormal conditions occur. For example, an over-voltage alarm condition may be cause for concern and need to be investigated further, whilst a high temperature alarm could signify air-conditioning failure. Alerts can typically be provided via , SMS or SNMP. 10. Can a solution to all the above questions be adopted without disruption to the existing network infrastructure and without downtime? Monitoring devices and sensors are now available that can be installed without any downtime. Intelligent PDUs can be installed in racks but the power to the equipment obviously needs to be removed in advance. Unobtrusive sensors that clip round the 16A or 32A input power cable are now available to monitor the current draw within racks. These eliminate the need for network downtime during installation and provide an extremely practical and cost-effective way of implementing power monitoring. Caution will, of course, still need to be observed as usual when running sensor interface cables. Summary Knowledge is power but, ironically, without monitoring power the appropriate decision making knowledge won t exist. It s very unlikely wholesale changes can be made immediately to data centre IT equipment or facilities that will have a significant impact on power usage. However, over time, with suitable data available, informed decisions can be taken that will result in significant data centre power savings. Rack power monitoring enables that data to be collected and utilised in a practical way to facilitate those savings. To ensure IT Managers have the most appropriate data to make informed decisions regarding power usage, environmental monitoring and power monitoring should be carried out alongside each other in the data centre. Power sensors such as the Jacarta intelliamp current sensor are available that can be installed without the need for downtime or disruption to the network, ensuring that power monitoring solutions can be implemented quickly and cost-effectively, irrespective of the age and nature of the data centre. Implementation is best carried out by specialist resellers that have independent access to the required knowledge, tools and products that most adequately suit a customer s power monitoring requirements. See also: Jacarta White Paper: RMS versus Mean: The Importance of True RMS Power Monitoring

Data Center Infrastructure Management (D.C.I.M.)

Data Center Infrastructure Management (D.C.I.M.) Data Center Infrastructure Management (D.C.I.M.) Garies Chong, RCDD, DCDC. BICSI Southeast Asia District Chair Managing Director of EMS Wiring Systems Pte Ltd Data Center Infrastructure Management (D.C.I.M.)

More information

7 Best Practices for Increasing Efficiency, Availability and Capacity. XXXX XXXXXXXX Liebert North America

7 Best Practices for Increasing Efficiency, Availability and Capacity. XXXX XXXXXXXX Liebert North America 7 Best Practices for Increasing Efficiency, Availability and Capacity XXXX XXXXXXXX Liebert North America Emerson Network Power: The global leader in enabling Business-Critical Continuity Automatic Transfer

More information

Engineering and Manufacturing Excellence in Data Centre Infrastructure

Engineering and Manufacturing Excellence in Data Centre Infrastructure Engineering and Manufacturing Excellence in Data Centre Infrastructure Since 1982 Australia s Largest PDU Manufacturer NetSense DCIM Software Intelligent Power PDU s SafetyNet Series 5 CREMS E-Rack 19

More information

ICT Infrastructure Solutions. Real power for virtualisation

ICT Infrastructure Solutions. Real power for virtualisation ICT Infrastructure Solutions Real power for virtualisation Why Eaton? When it comes to the power infrastructure for virtual environments, Eaton is a pioneer. We offer a number of significant advantages.

More information

B&R Enclosures Pty Ltd. The Benefits of Intelligent PDUs White Paper

B&R Enclosures Pty Ltd. The Benefits of Intelligent PDUs White Paper B&R Enclosures Pty Ltd The Benefits of Intelligent PDUs White Paper INTRODUCTION Data centres use every precaution to ensure problems are managed before causing an incident. One of the last lines of defence

More information

Data Centre Optimisation Services

Data Centre Optimisation Services Data Centre Solutions Expertly Engineered Current Total Energy Consumption *14 Tera Watt Hours Estimated Energy Saving 5.6 Tera Watt Hours Potential Energy Consumption 8.4 Tera Watt Hours Average PUE1.8

More information

2016 COOLING THE EDGE SURVEY. Conducted by Vertiv Publication Date: August 30, 2016

2016 COOLING THE EDGE SURVEY. Conducted by Vertiv Publication Date: August 30, 2016 2016 COOLING THE EDGE SURVEY Conducted by Vertiv Publication Date: August 30, 2016 TWO STAGE POWER DISTRIBUTION Table of Contents Section I: Methodology Section II: Key Findings 1. Strategic Importance

More information

Test Asset Optimization Services Power Line Utilization Module (PLUM) DATA SHEET

Test Asset Optimization Services Power Line Utilization Module (PLUM) DATA SHEET Test Asset Optimization Services Power Line Utilization Module (PLUM) DATA SHEET Description A Power Line Utilization Module (PLUM) is a device used to monitor the utilization and health parameters of

More information

IBM Site Enablement Services

IBM Site Enablement Services IBM Site Enablement Services Resilience for Your Data Centre 13/05/2005 Why Site Enablement Services? Hardware and Software are becoming increasingly dependable, but the environment in which they operate

More information

Dominick Lovicott Enterprise Thermal Engineering. One Dell Way One Dell Way Round Rock, Texas

Dominick Lovicott Enterprise Thermal Engineering. One Dell Way One Dell Way Round Rock, Texas One Dell Way One Dell Way Round Rock, Texas 78682 www.dell.com DELL ENTERPRISE WHITEPAPER THERMAL DESIGN OF THE DELL POWEREDGE T610, R610, AND R710 SERVERS Dominick Lovicott Enterprise Thermal Engineering

More information

FREEING HPC FROM THE DATACENTRE

FREEING HPC FROM THE DATACENTRE FREEING HPC FROM THE DATACENTRE ku:l sistem TM COOLING REDEFINED www.iceotope.com ku:l sistem removes the need for inefficient air cooling technologies FREEING HPC FROM THE DATACENTRE Iceotope s patented

More information

Google s Green Data Centers: Network POP Case Study

Google s Green Data Centers: Network POP Case Study Google s Green Data Centers: Network POP Case Study Table of Contents Introduction... 2 Best practices: Measuring. performance, optimizing air flow,. and turning up the thermostat... 2...Best Practice

More information

MEASURE MONITOR UNDERSTAND

MEASURE MONITOR UNDERSTAND MEASURE MONITOR UNDERSTAND Presented by Alistair Hunt Energy Monitoring, Measurement metrics Where and What 1 History & Background Company Timeline 18 Years Comrac & Sinetica founded 15 Years Raritan Integration

More information

Comprehensive Data Center Energy Management Solutions

Comprehensive Data Center Energy Management Solutions FROM INSIGHT TO EFFICIENCY: Comprehensive Data Center Energy Management Solutions Since 1995, facility managers and BAS professionals have relied on the Niagara framework to provide full convergence of

More information

Evaporative free air cooling technology Providing evaporative free air cooling solutions.

Evaporative free air cooling technology Providing evaporative free air cooling solutions. Evaporative free air cooling technology Providing evaporative free air cooling solutions. Creating an effective workspace environment data centre free air cooling technology FreeCool - Evaporative Free

More information

Data Centre Monitoring. Nexans Cabling Solutions

Data Centre Monitoring. Nexans Cabling Solutions Data Centre Monitoring Nexans Cabling Solutions Agenda Changes in LAN usage & management implications Business issues How LANsense can help Traditional model Remote Access GSM CCTV Storage Wireless IT

More information

Survey and Audit Service Schedule. Airflow and Thermal Imaging Survey Service Schedule. Data Centre Solutions Expertly Engineered

Survey and Audit Service Schedule. Airflow and Thermal Imaging Survey Service Schedule. Data Centre Solutions Expertly Engineered Survey and Audit Service Schedule Airflow and Thermal Imaging Survey Service Schedule Data Centre Solutions Expertly Engineered Consult optimisation, audit and survey services Data Centre Services Workspace

More information

Total Modular Data Centre Solutions

Total Modular Data Centre Solutions Sector Data Centre Total Modular Data Centre Solutions www.airedale.com BRITISH MANUFACTURER ENERGY EFFICIENCY CONTROLS SERVICE TRAINING 01 Standardised Modular Designs to fit your needs Our modular system

More information

MSYS 4480 AC Systems Winter 2015

MSYS 4480 AC Systems Winter 2015 MSYS 4480 AC Systems Winter 2015 Module 12: DATA CENTERS By Satwinder Singh 14/05/2015 1 Data Centers Data Centers are specialized environments that safeguard your company's most valuable equipment and

More information

Are all CFD s created equal? Prepared by: Associate Director: Sam Wicks

Are all CFD s created equal? Prepared by: Associate Director: Sam Wicks Are all CFD s created equal? Prepared by: Associate Director: Sam Wicks samwicks@sudlows.com Keeping cool under pressure Imagine waking up at 04:00 to an escalated BMS alert that your Dubai data hub has

More information

Energy Efficiency Best Practice Guide Data Centre and IT Facilities

Energy Efficiency Best Practice Guide Data Centre and IT Facilities 2 Energy Efficiency Best Practice Guide Data Centre and IT Facilities Best Practice Guide Pumping Systems Contents Medium-sized data centres energy efficiency 3 1 Introduction 4 2 The business benefits

More information

84 kw, Tier 3, Direct Expansion, 937 ft 2

84 kw, Tier 3, Direct Expansion, 937 ft 2 [Reference Design 42] 84 kw, Tier 3, Direct Expansion, 937 ft 2 DESIGN OVERVIEW Data Center IT Capacity 84 kw Target Availability Tier 3 Annualized PUE at 100% Load 1.712 Total Racks and Average Density

More information

Data Center Optimized Controls

Data Center Optimized Controls Data Center Optimized Controls Controls Agenda 30 min. Emerson Control Products icom (Dynamic Thermal Optimization) 20 min. Station Rotation Station 1: Controller Challenge Station 2: Wireless Demo 5 min.

More information

Remote Monitoring. for Building HVAC Systems. A unique combination of human expertise and technology helps ensure optimum operation.

Remote Monitoring. for Building HVAC Systems. A unique combination of human expertise and technology helps ensure optimum operation. Remote Monitoring SM for Building HVAC Systems A unique combination of human expertise and technology helps ensure optimum operation. For peace of mind: ProTech SM monitors HVAC systems 24 hours a day

More information

Thermal management. Thermal management

Thermal management. Thermal management Thermal management Thermal management Managing thermal loads is a major challenge for all Data Centre operators. Effecting proper control of the thermal environment drives energy consumption and ultimately

More information

Who Needs Remote Power Management for Power Distribution, Power Measurement and Power Control of 48 VDC Equipment?

Who Needs Remote Power Management for Power Distribution, Power Measurement and Power Control of 48 VDC Equipment? Who Needs Remote Power Management for Power Distribution, Power Measurement and Power Control of 48 VDC Equipment? A Network Power Management White Paper Who Needs Remote Power Management for Power Distribution,

More information

Case Study Leicester City Council

Case Study Leicester City Council Data Centre Solutions...energy efficient by design Case Study Leicester City Council Leicester City Council Deploys New Sub 1.1 PUE3 Data Centre Infrastructure. Designed & Installed by Workspace Technology

More information

for Power Energy and

for Power Energy and Engineered for Power Management: Dell PowerEdge Servers Are Designed to Help Save Energy and Reduce Costs ABSTRACT Keeping up with the rising cost of energy is one of the greatest challenges facing IT

More information

Technology for Constructing Environmentally Friendly Data Centers and Fujitsu s Approach

Technology for Constructing Environmentally Friendly Data Centers and Fujitsu s Approach Technology for Constructing Environmentally Friendly Data Centers and Fujitsu s Approach Hiroshi Nagazono In recent years, IT devices such as servers have come to have high performance and be highly integrated

More information

Cooling on Demand - scalable and smart cooling solutions. Marcus Edwards B.Sc.

Cooling on Demand - scalable and smart cooling solutions. Marcus Edwards B.Sc. Cooling on Demand - scalable and smart cooling solutions Marcus Edwards B.Sc. Schroff UK Limited Data Centre cooling what a waste of money! A 1MW data center needs 177,000,000 kwh in its lifetime of 10

More information

SmartRow Solution Intelligent, Integrated Infrastructure for the Data Center

SmartRow Solution Intelligent, Integrated Infrastructure for the Data Center SmartRow Solution Intelligent, Integrated Infrastructure for the Data Center Deploy a Fully Configured Data Center in Just Weeks Availability, Capacity, Efficiency. You need them and now you can have them

More information

Key Features and Benefits

Key Features and Benefits System Description Since its beginning, Automated Logic has focused on one objective: to develop innovative building automation systems with the latest technologies, which advance operational freedom,

More information

Powering Change in the Data Center. A White Paper from the Experts in Business-Critical Continuity TM

Powering Change in the Data Center. A White Paper from the Experts in Business-Critical Continuity TM Powering Change in the Data Center A White Paper from the Experts in Business-Critical Continuity TM Executive Summary Increases in data center density and diversity are driving change in the power and

More information

Overcoming the Challenges of Server Virtualisation

Overcoming the Challenges of Server Virtualisation Overcoming the Challenges of Server Virtualisation Maximise the benefits by optimising power & cooling in the server room Server rooms are unknowingly missing a great portion of their benefit entitlement

More information

Polar PDUs POWER MANAGEMENT

Polar PDUs POWER MANAGEMENT Polar Power Distribution Units (PDUs) provide the ultimate solution for combining cabinet level power management, environmental monitoring, and cabinet access control in multi-tenant and enterprise data

More information

Ecotel Free Cool 5-15kW

Ecotel Free Cool 5-15kW Precision Air Conditioning Free-cooling Ecotel Free Cool 5-15kW + + Self-contained compact outdoor cabin cooler + + 100% free-cooling + + -48V DC supply option + + Easy serviceability (front component

More information

We protect IT DC-MONITORING. When more surveillance leads to added value. Member of the DATA CENTER GROUP

We protect IT DC-MONITORING. When more surveillance leads to added value. Member of the DATA CENTER GROUP We protect IT DC-MONITORING When more surveillance leads to added value Member of the DATA CENTER GROUP DC-MonIToring How more surveillance leads to added value What is your data center doing right now?

More information

Repeatable IT Hub Rooms

Repeatable IT Hub Rooms Repeatable IT Hub Rooms Repeatable IT Hub Rooms Catalogue Reducing the cost of NCPI through standardisation Data Centre Solutions Expertly Engineered Reducing the costs of NCPI through standardisation

More information

Virtualization and consolidation

Virtualization and consolidation Virtualization and consolidation Choosing a density strategy Implementing a high-density environment Maximizing the efficiency benefit Anticipating the dynamic data center Schneider Electric 1 Topical

More information

Precision Cooling. Precision Cooling Advantages

Precision Cooling. Precision Cooling Advantages Precision Cooling Today s computing technologies compound conventional cooling problems. Blade servers, communications switches and other electronics are being packed into tighter and tighter spaces. Computing

More information

VERTIV SERVICE CAPABILITY

VERTIV SERVICE CAPABILITY VERTIV SERVICE CAPABILITY VERTIV SERVICE CAPABILITY Service Offering Manage the health of your entire critical infrastructure with a service partner who can offer you business continuity. Exactly the level

More information

RaMP Data Center Manager. Data Center Infrastructure Management (DCIM) software

RaMP Data Center Manager. Data Center Infrastructure Management (DCIM) software RaMP Data Center Manager Data Center Infrastructure Management (DCIM) software One solution for both IT and facilities managers As data centers become more complex, it becomes increasingly important to

More information

Combining Cold Aisle Containment with Intelligent Control to Optimize Data Center Cooling Efficiency

Combining Cold Aisle Containment with Intelligent Control to Optimize Data Center Cooling Efficiency A White Paper from the Experts in Business-Critical Continuity TM Combining Cold Aisle Containment with Intelligent Control to Optimize Data Center Cooling Efficiency Executive Summary Energy efficiency

More information

SALAMANDER. Automated Infrastructure Management

SALAMANDER. Automated Infrastructure Management SALAMANDER Automated Infrastructure Management INNOVATION STARTS HERE Facemate is a market leader, providing customers with Data Center Solutions, Networking and Datacenter cabinets, DC Management Software,

More information

Liebert DM. High Performance, Sensible Cooling for Small Computer Rooms and Network Closets

Liebert DM. High Performance, Sensible Cooling for Small Computer Rooms and Network Closets Liebert DM High Performance, Sensible Cooling for Small Computer Rooms and Network Closets Emerson Network Power, a business of Emerson (NYSE: EMR), is a worldwide leader in infrastructure solutions across

More information

Managing Dispersed Remote Office IT: The Challenges and Sentinel s Unified Approach to Remote Site Management

Managing Dispersed Remote Office IT: The Challenges and Sentinel s Unified Approach to Remote Site Management The Challenges and Sentinel s Unified Approach to Remote Site Management A Background to Branch Office IT Doing our own thing Not so long ago, branch offices might have had only a PBX and a VPN back to

More information

Two-Stage Power Distribution: An Essential Strategy to Future Proof the Data Center

Two-Stage Power Distribution: An Essential Strategy to Future Proof the Data Center Two-Stage Power Distribution: An Essential Strategy to Future Proof the Data Center Adapting to Change Concern over the pace of technology change is increasing among data center managers. This was reflected

More information

Copyright 2016 IPT PDUUM Revision

Copyright 2016 IPT PDUUM Revision PDUUM052016 Revision 1.03.250516 Table of Contents Introduction...3 Warranty...3 Installation...3 Operation...3 View...4 Adding PDU Servers...4 Agent Information...5 Graphs...5 Log Views...5 Tools...5

More information

Remote Management of Data Center White Space: What to Manage and How? Ashish Moondra Sr. Product Manager Chatsworth Products

Remote Management of Data Center White Space: What to Manage and How? Ashish Moondra Sr. Product Manager Chatsworth Products Remote Management of Data Center White Space: What to Manage and How? Ashish Moondra Sr. Product Manager Chatsworth Products Learning Outcomes Need for Remote Management of Whitespace Understand Elements

More information

Server room guide helps energy managers reduce server consumption

Server room guide helps energy managers reduce server consumption Server room guide helps energy managers reduce server consumption Jan Viegand Viegand Maagøe Nr. Farimagsgade 37 1364 Copenhagen K Denmark jv@viegandmaagoe.dk Keywords servers, guidelines, server rooms,

More information

SmartZone Rack Energy Kits Energy and Environmental Monitoring for Small Data Centers

SmartZone Rack Energy Kits Energy and Environmental Monitoring for Small Data Centers SmartZone Rack Energy Kits Energy and Environmental Monitoring for Small Data Centers SmartZone Rack Energy Kits Energy and Environmental Monitoring for Small Data Centers SmartZone Rack Energy Kits Features:

More information

APC by Schneider Electric Elite Data Centre Partner

APC by Schneider Electric Elite Data Centre Partner Data Centre Solutions...energy efficient by design APC by Schneider Electric Elite Data Centre Partner APC s leading Elite Data Centre Solutions Partner providing customers with expert advice, integration

More information

The Four 4R s. of Data Center Airflow Management. About Upsite Technologies

The Four 4R s. of Data Center Airflow Management. About Upsite Technologies About Upsite Technologies Upsite Technologies, Inc., a pioneer, and industry thought leader specializing in data center airflow management, provides a full suite of products and services designed to enable

More information

DCIM Solutions to improve planning and reduce operational cost across IT & Facilities

DCIM Solutions to improve planning and reduce operational cost across IT & Facilities DCIM Solutions to improve planning and reduce operational cost across IT & Facilities Presented by: Chi Sen, Director, Data Centre Software Solutions, APJ & EMEA Schneider Electric Data Center Solutions

More information

CA ecometer. Overview. Benefits. agility made possible. Improve data center uptime and availability through better energy management

CA ecometer. Overview. Benefits. agility made possible. Improve data center uptime and availability through better energy management PRODUCT SHEET: CA ecometer CA ecometer Improve data center uptime and availability through better energy management agility made possible CA ecometer helps you to visualize, monitor, and better manage

More information

the closed-loop control system

the closed-loop control system the closed-loop control system A definitive change in cleanroom technology The Connect 2 Cleanrooms closed-loop control system is designed to ensure the cleanroom operates at optimum effectiveness whilst

More information

Ft Worth Data Center Power Metering for Real Time PUE Calculation. Scope of Work

Ft Worth Data Center Power Metering for Real Time PUE Calculation. Scope of Work Ft Worth Data Center Power Metering for Real Time PUE Calculation Scope of Work Prepared for the General Services Administration By Lawrence Berkeley National Laboratory Rod Mahdavi December 13, 2010 Executive

More information

APC APPLICATION NOTE #74

APC APPLICATION NOTE #74 #74 Configuration of InfraStruXure for Data Centers to Support Dell PowerEdge 1855 Abstract Many companies are making plans to incorporate Dell PowerEdge Blade Servers into their data center applications.

More information

DEVELOPING A SERVER ROOM ENVIRONMENT MONITORING SYSTEM USING INTERNET PROTOCOL ENABLED SENSORS

DEVELOPING A SERVER ROOM ENVIRONMENT MONITORING SYSTEM USING INTERNET PROTOCOL ENABLED SENSORS Business Education Journal Volume II Issue I Email: jeditor@cbe.ac.tz Published Online April, 2018 in http://www.cbe.ac.tz/bej DEVELOPING A SERVER ROOM ENVIRONMENT MONITORING SYSTEM USING INTERNET PROTOCOL

More information

Features and Benefits: Power IQ DCIM Monitoring Solutions

Features and Benefits: Power IQ DCIM Monitoring Solutions 1 : Power IQ DCIM Monitoring Solutions Vendor-agnostic Management Energy Efficiency Through one web browser, monitor any device from major manufactures such as APC, Avocent, BayTech, Chatsworth, Cyber

More information

Optimize Your Data Center. Gary Hill VP, Business Development DVL Group, Inc.

Optimize Your Data Center. Gary Hill VP, Business Development DVL Group, Inc. Optimize Your Data Center Gary Hill VP, Business Development DVL Group, Inc. Data Center Age Profile Gartner Group Survey Legacy Data Centers Challenges Under Powered - Room or Racks Inadequate Air Delivery

More information

Building Management Solutions. for Data Centers and Mission Critical Facilities

Building Management Solutions. for Data Centers and Mission Critical Facilities Building Management Solutions for Data Centers and Mission Critical Facilities How Efficient is Your Data Center? Recent years have seen rapid growth in global demand for computing capacity, resulting

More information

The Most Comprehensive DCIM Solution

The Most Comprehensive DCIM Solution The Most Comprehensive DCIM Solution NetZoomDC TM is the complete, enterprise Data Center Infrastructure Management (DCIM) software which Models, Manages, Monitors and Maximizes data center assets, space,

More information

Industry leading low energy evaporative fresh air cooling.

Industry leading low energy evaporative fresh air cooling. Industry leading low energy evaporative fresh air cooling. Freecool Evaporative Free Air Cooling by Workspace Technology delivers innovative low energy cooling for a range of applications including data

More information

Data Center Assessment Helps Keep Critical Equipment Operational. A White Paper from the Experts in Business-Critical Continuity TM

Data Center Assessment Helps Keep Critical Equipment Operational. A White Paper from the Experts in Business-Critical Continuity TM Data Center Assessment Helps Keep Critical Equipment Operational A White Paper from the Experts in Business-Critical Continuity TM Executive Summary The IT infrastructure within many companies has evolved

More information

The Greening of Services

The Greening of Services The Greening of Services CYNET Presentation - Under the scope of GN3Plus Project / NA3-T3 Activity Special Scientists: Nikoletta Tsioroli, Petros Ioannou CYNET 2015 Agenda Introduction NA3-T3 Tasks - Quick

More information

Reducing Data Center Cooling Costs through Airflow Containment

Reducing Data Center Cooling Costs through Airflow Containment FEATURE Reducing Data Center Cooling Costs through Airflow Containment Implementing a containment solution in the data center costs much less than the alternatives of adding air handlers or other supplemental

More information

Geist EMEA. Geist USA. Geist APAC

Geist EMEA. Geist USA. Geist APAC Product Overview Headquartered in Lincoln, Nebraska, Geist designs and manufactures industryleading technology and software to power, cool, monitor and manage critical data center infrastructure. We produce

More information

PLAYBOOK. How Do You Plan to Grow? Evaluating Your Critical Infrastructure Can Help Uncover the Right Strategy

PLAYBOOK. How Do You Plan to Grow? Evaluating Your Critical Infrastructure Can Help Uncover the Right Strategy PLAYBOOK F O R C H A N G E How Do You Plan to Grow? Evaluating Your Critical Infrastructure Can Help Uncover the Right Strategy The world is becoming more digital every day. The demand for feature-rich,

More information

Environmental Monitor (RSMICRO)

Environmental Monitor (RSMICRO) Environmental Monitor (RSMICRO) Monitored Basic & Temperature and humidity are two of the most critical conditions to monitor in computing space. While temperature is often given moderate attention, relative

More information

How much power?! Data Centre Efficiency. How much Money?! Carbon Reduction Commitment (CRC)

How much power?! Data Centre Efficiency. How much Money?! Carbon Reduction Commitment (CRC) How much power?! Data Centre Efficiency The US EPA found in 2006 data centres used 1.5% of total US consumption (5) For Bangor University data centres use approximately 5-10% of the total university electricity

More information

Energy Logic: Emerson Network Power. A Roadmap for Reducing Energy Consumption in the Data Center. Ross Hammond Managing Director

Energy Logic: Emerson Network Power. A Roadmap for Reducing Energy Consumption in the Data Center. Ross Hammond Managing Director Energy Logic: A Roadmap for Reducing Energy Consumption in the Data Center Emerson Network Power Ross Hammond Managing Director Agenda Energy efficiency Where We Are Today What Data Center Managers Are

More information

Scalable, Secure. Jason Rylands

Scalable, Secure. Jason Rylands Energy Efficient, Modular, Scalable, Secure Jason Rylands The planning, construction and operation of IT infrastructure for mission critical applications in reliable Datacentres represents a real challenge.

More information

1.0 Executive Summary. 2.0 Features and Benefits

1.0 Executive Summary. 2.0 Features and Benefits Table of Contents 1.0 EXECUTIVE SUMMARY 2.0 FEATURES AND BENEFITS 3.0 DETAILS OF SERVICE 4.0 Deliverable 5.0 Exclusions 6.0 SCOPE OF RESPONSIBILITY 7.0 PROJECT WORK DETAILS 8.0 ORDERING INFORMATION 9.0

More information

Data Centers. The Environment. December The State of Global Environmental Sustainability in Data Center Design

Data Centers. The Environment. December The State of Global Environmental Sustainability in Data Center Design Data Centers & The Environment The State of Global Environmental Sustainability in Data Center Design December 2018 Today s Data Centers Data centers have a huge impact on the world we live in. Today they

More information

Rittal LCP T3+ High-availability IT cooling with no compromise

Rittal LCP T3+ High-availability IT cooling with no compromise Rittal LCP T3+ High-availability IT cooling with no compromise LCP T3+, the climate for maximum availability... in the financial world Admittedly, we have no solution for overheated markets. But we do

More information

ENCLOSURE HEAT DISSIPATION

ENCLOSURE HEAT DISSIPATION ENCLOSURE HEAT DISSIPATION DATA CENTER SOLUTIONS A White Paper by Great Lakes Case & Cabinet Company www.werackyourworld.com 814.734.7303 Page 2 Introduction Dangerous heat levels inside an enclosure threaten

More information

SMARTAISLE Intelligent, Integrated Infrastructure for the Data Center

SMARTAISLE Intelligent, Integrated Infrastructure for the Data Center SMARTAISLE Intelligent, Integrated Infrastructure for the Data Center SMARTAISLE Deploy an Efficient and Flexible Row-Based Infrastructure Efficiency. Capacity. Availability. Control. The SmartAisle infrastructure

More information

the closed-loop control system

the closed-loop control system the closed-loop control system A definitive change in cleanroom technology The Connect 2 Cleanrooms closed-loop control system is designed to ensure the cleanroom operates at optimum effectiveness whilst

More information

Rittal Cooling Solutions A. Tropp

Rittal Cooling Solutions A. Tropp 1 Rittal Cooling Solutions Presented by Adam Tropp 2 Agenda Cooling Strategies Aisle Containment Chimney Solution Airstream Management Rittal Liquid Cooling Packages Data Monitoring 3 Cooling strategies.

More information

How do I... If you manage a datacenter, we have a solution for you. Sentry : Cabinet Power Distribution Unit Product Family : Metered CDU.

How do I... If you manage a datacenter, we have a solution for you. Sentry : Cabinet Power Distribution Unit Product Family : Metered CDU. If you manage a datacenter, we have a solution for you. How do I... Distribute power to all the equipment in the cabinet? Distribute and load balance 3-phase power? Monitor True RMS input current? Reboot

More information

IBM Integrated Server Farm (ISF)

IBM Integrated Server Farm (ISF) IBM Integrated Server Farm (ISF) TSS HW Services 05/04/2005 Data Centre Trends The density of computing power in a data centre environment has steadily increased in recent years. This trend is driven by

More information

3300 kw, Tier 3, Chilled Water, 70,000 ft 2

3300 kw, Tier 3, Chilled Water, 70,000 ft 2 [Reference Design 22] 3300 kw, Tier 3, Chilled Water, 70,000 ft 2 DESIGN OVERVIEW Data Center IT Capacity 1100 kw per Data Hall 3 Independent Data Halls Design Application Range This design can be applied

More information

Intermediate Certificate in EU Code of Conduct for Data centres

Intermediate Certificate in EU Code of Conduct for Data centres ISEB EUCOC Intermediate Certificate in EU Code of Conduct for Data centres Version: 4.0 Topic 1, Volume A ISEB EUCOC Exam QUESTION NO: 1 Why has the EU Code of Conduct on Data Centres been developed? a.

More information

DCIM Data Center Infrastructure Management Measurement is the first step

DCIM Data Center Infrastructure Management Measurement is the first step DCIM Data Center Infrastructure Management Measurement is the first step Presented by Julius Neudorfer Sponsored by DCIM Data Center Infrastructure Management Measurement is the first step Presented by

More information

Repeatable IT Hub Rooms

Repeatable IT Hub Rooms Repeatable IT Hub Rooms Repeatable IT Hub Rooms Catalogue Reducing the cost of NCPI through standardisation Reducing the costs of NCPI through standardisation The UK Government s plan for growth, published

More information

Retro-Commissioning Report

Retro-Commissioning Report 10 Retro-Commissioning Report Retro-Commissioning Retro-Commissioning is the process for identifying intrinsic operational and energy related issues in the facilities DDC system and providing a mechanism

More information

World Class. Globally Certified. High Availability.

World Class. Globally Certified. High Availability. Intellicentre 2 World Class. Globally Certified. High Availability. Intellicentre 2 Macquarie Park, Sydney 2 Intellicentre 2 A new generation of data centre solutions. Australia s first showcase Tier III

More information

Completing your AWS Cloud SECURING YOUR AMAZON WEB SERVICES ENVIRONMENT

Completing your AWS Cloud SECURING YOUR AMAZON WEB SERVICES ENVIRONMENT Completing your AWS Cloud SECURING YOUR AMAZON WEB SERVICES ENVIRONMENT Introduction Amazon Web Services (AWS) provides Infrastructure as a Service (IaaS) cloud offerings for organizations. Using AWS,

More information

Power Monitoring in the Data Centre

Power Monitoring in the Data Centre Power Monitoring in the Data Centre Fixed or Wireless Steve Strange RCDD ANIXTER INTERNATIONAL Agenda Energy Consumption Case Study Reasons to Monitor Power Monitoring Environmental Monitoring Asset Tags

More information

Ecolibrium. Cloud control. Keeping data centres cool. OCTOBER 2018 VOLUME 17.9 RRP $14.95 PRINT POST APPROVAL NUMBER PP352532/00001

Ecolibrium. Cloud control. Keeping data centres cool. OCTOBER 2018 VOLUME 17.9 RRP $14.95 PRINT POST APPROVAL NUMBER PP352532/00001 Ecolibrium OCTOBER 2018 VOLUME 17.9 RRP $14.95 PRINT POST APPROVAL NUMBER PP352532/00001 Cloud control Keeping data centres cool. COVER FEATURE Cloud control Such is the growth in data centres globally

More information

SmartRow Intelligent, Integrated Infrastructure in a Self-Contained Line-Up. Solutions For Business-Critical Continuity

SmartRow Intelligent, Integrated Infrastructure in a Self-Contained Line-Up. Solutions For Business-Critical Continuity SmartRow Intelligent, Integrated Infrastructure in a Self-Contained Line-Up Solutions For Business-Critical Continuity Deploy a Fully Configured Data Center in Just Weeks Efficiency. Capacity. Availability.

More information

SMARTER BUILDING. Give your buildings a new dimension Scalable solutions for energy and asset management

SMARTER BUILDING. Give your buildings a new dimension Scalable solutions for energy and asset management SMARTER BUILDING Give your buildings a new dimension Scalable solutions for energy and asset management 2 Give your buildings a new dimension, ABB s holistic new energy and asset management concept for

More information

A) Differences between Precision and Comfort Cooling Here are the major differences exist between precision air conditioning and comfort systems.

A) Differences between Precision and Comfort Cooling Here are the major differences exist between precision air conditioning and comfort systems. DATA CENTRE COOLING SYSTEM A) Differences between Precision and Comfort Cooling Here are the major differences exist between precision air conditioning and comfort systems. 1. Cooling Optimized to Electronic

More information

S I T E I N F R A S T R U C T U R E C U R R E N T P R O B L E M S A N D P R O P O S E D S O L U T I O N S

S I T E I N F R A S T R U C T U R E C U R R E N T P R O B L E M S A N D P R O P O S E D S O L U T I O N S Liverpool HEP Computing S I T E I N F R A S T R U C T U R E C U R R E N T P R O B L E M S A N D P R O P O S E D S O L U T I O N S Cooling Air condition and water cooling units that need regular manual

More information

A separate CRAC Unit plant zone was created between the external façade and the technical space.

A separate CRAC Unit plant zone was created between the external façade and the technical space. Nominee: FES Co Ltd Nomination title: HP Cold Cube The Doxford Facility is a highly secure Data Centre. The challenge was to take advantage of the previous investment in highly resilient infrastructure

More information

Innovative. Engineering. Power. structure source. Making the complex, simple. Structure Source PDU s

Innovative. Engineering. Power. structure source. Making the complex, simple. Structure Source PDU s Structure Source PDU s Innovative Power Engineering High Quality Power Distribution for the Data Centre structure source Making the complex, simple structure source product range Rack and Server Power

More information

MECHANICAL AND THERMAL CONSIDERATIONS FOR RACK DEPLOYMENT OF THE DELL POWEREDGE M-SERIES. One Dell Way Round Rock, Texas

MECHANICAL AND THERMAL CONSIDERATIONS FOR RACK DEPLOYMENT OF THE DELL POWEREDGE M-SERIES. One Dell Way Round Rock, Texas One Dell Way Round Rock, Texas 78682 www.dell.com DELL ENTERPRISE WHITEPAPER MECHANICAL AND THERMAL CONSIDERATIONS FOR RACK DEPLOYMENT OF THE DELL POWEREDGE M-SERIES Dominick Lovicott Enterprise Thermal

More information

The Energy. David L. Moss Dell Data Center Infrastructure

The Energy. David L. Moss Dell Data Center Infrastructure The Energy Advantages of Containment Systems David L. Moss Dell Data Center Infrastructure www.dell.com/hiddendatacenter Summary The Uptime Institute estimates that the cost to build a new 20,000 square

More information

Aged Care Security Solutions. security.gallagher.com

Aged Care Security Solutions. security.gallagher.com Aged Care Security Solutions security.gallagher.com Aged care security solutions The safety of residents and staff is the most important thing. Our objective at Gallagher is to create innovative solutions

More information