1 What s New for Data Centers in Title Jeff Stein, PE Taylor Engineering SVLG Workshop November 14, 2013
2 About Jeff Stein Principal, Taylor Engineering now Professional Experience Eley Associates, ACCO Engineered Systems, LBNL, Education Cornell University, BS, 1990 UC Berkeley, MS, 1997 Data Center Design/Commissioning Apple, Brocade, Cisco, ebay, Kaiser, Oracle, Symantec, etc. Research Data center environmental conditions, chiller plant optimization, etc. Energy Codes Title , -2005, -2008, ASHRAE
3 New Title 24 Computer Room Definition a room whose primary function is to house electronic equipment and that has a design equipment power density exceeding 20 watts/ft 2 of conditioned floor area. 3
4 Lighting Envelope Ventilation Computer Rooms Now Covered by All of Title 24, including Mandatory equipment efficiencies for packaged units, chillers, towers, etc. Unlike 90.1, Title 24 does not have separate efficiency category for CRAC units Variable flow and variable speed requirements for chilled water systems New exemption: computer rooms exempt from normal economizer requirements 4
5 New Prescriptive Requirements for Computer Rooms 1. Economizers 2. Reheat 3. Humidification 4. Power Consumption of Fans 5. Fan Control 6. Containment 5
6 Economizers Must have an integrated air or water economizer Air economizer can be air-air heat exchanger if it can meet 100% of load at 55/50 DB/WB. Water economizer must meet 100% of load at 40/35 DB/WB Exceptions: Individual rooms under 5 tons in a building without economizers 50 tons of equipment added to an existing computer room 20 tons of equipment added to new computer room in an existing building If you have a lead system with economizer then you can have a backup system without an economizer 6
7 Reheat No reheat 7
8 Humidification Non-adiabatic humidification (e.g. steam, infrared) is prohibited. Only adiabatic humidification (e.g. direct evaporative, ultrasonic) is permitted. 8
9 Power Consumption of Fans The total fan power at design conditions of each fan system shall not exceed 27 W/kBtuh of net sensible cooling capacity. Can be met by a system with 20ºF ΔT, 2.5 total pressure, 55% fan efficiency and 90% motor/drive efficiency. It can also be met at 3 total pressure and 65% fan efficiency Calculation can account for redundancy. A CRAC unit may be designed for 30 W/kBtuh but will operate at 20 W/kBtuh at peak load because it will not be running at full speed 9
10 Power Consumption of Fans Survey of Recent Projects 10
11 Fan Control Variable speed fans required on: DX units over 5 tons CHW units of any size Must vary fan speed as a function of actual load 11
12 Containment Computer rooms with air-cooled computers in racks and with a design load exceeding 175 kw/room shall include air barriers such that there is no significant air path for computer discharge air to recirculate back to computer inlets without passing through a cooling system. Exceptions: Expansions of existing computer rooms Computer racks with a design load less than 1 kw/rack Equivalent energy performance based on CFD or other analysis 12
13 Performance Approach Modeling Rules Proposed Design is compared to a Baseline Design: If total computer room load > 250 tons then all computer rooms have CHW CRAH units Otherwise all computer rooms have DX CRAC units Baseline building will have separate systems for computer rooms and other spaces User enters peak load in W/ft2. Both models use part-load schedule that varies monthly: 100%, 75%, 50%, 25%, 100%, 75%, etc. 13
14 CRAH Baseline Design supply/return temp: 60ºF / 80ºF CFM sized 110% of the calculated load Fan power: 0.49 W/cfm (e.g. 60% fan efficiency, 2.5 TSP) Airside economizer - differential drybulb control No humidification or reheat CHW plant follows normal Title 24 rules for efficiency of chillers, towers, pumps, staging, etc. Supply Air Temperature and Fan Control Fan volume shall be linearly reset from 100% air flow at 100% cooling load to minimum air flow at 50% cooling load and below. Supply air temperature setpoint shall be linearly reset from 60 o F at 50% cooling load and above to 80 o F at 0% cooling load. 14
15 CRAC Baseline Air-cooled DX Design supply/return temp: 60ºF / 80ºF Fan Control: Constant speed if total cooling capacity for the room < 5 tons, otherwise variable speed Fan power: 0.39 W/cfm for constant speed, 0.49 W/cfm for variable speed Airside economizer (regardless of system size) No humidification or reheat CFM and cooling capacity sized 120% of the calculated load Supply Air Temperature and Fan Control (for variable speed) Fan volume shall be linearly reset from 100% air flow at 100% cooling load to minimum air flow at 50% cooling load and below. Supply air temperature setpoint shall be linearly reset from 60 o F at 50% cooling load and above to 80 o F at 0% cooling load. 15
16 Contact Info Jeff Stein, PE, Principal Taylor Engineering, LLC 1080 Marina Village Parkway Alameda CA
Data Center Energy Savings By the numbers
Data Center Energy Savings By the numbers Chris Kurkjian, PE HP Critical Facility Services provided by EYP Mission Critical Facilities 2008 Hewlett-Packard Development Company, L.P. The information contained
More informationDATA CENTER EFFICIENCY: Data Center Temperature Set-point Impact on Cooling Efficiency
DATA CENTER EFFICIENCY: Data Center Temperature Set-point Impact on Cooling Efficiency September 27 th, 2013 Tejas Desai, PE CEM CEA LEED AP Sameer Behere, PE CEM LEED AP Agenda Problem: Quick fixes can
More informationAPC InRow Cooler Prototype Initial Report - Test Setup Verification. H. Coles, S. Greenberg Contributing: J. Bean (APC) November 18, 2011
APC InRow Cooler Prototype Initial Report - Test Setup Verification H. Coles, S. Greenberg Contributing: J. Bean (APC) November 18, 2011 1 Introduction Contents Technology Description/Attributes Installation
More informationMission Critical Facilities & Technology Conference November 3, 2011 Cooling 101. Nick Gangemi Regional Sales Manager Data Aire
Mission Critical Facilities & Technology Conference November 3, 2011 Cooling 101 Nick Gangemi Regional Sales Manager Data Aire Agenda Exactly what are we talking about ASHRAE TC 9.9 Design best practices
More informationWaterside Economizing in Data Centers: Design and Control Considerations
2009, American Society of Heating, Refrigerating and Air-Conditioning Engineers, Inc. (www.ashrae.org). Published in ASHRAE Transactions 2009, vol. 115, part 2. For personal use only. Additional reproduction,
More informationImplications of Current Thermal Guidelines
Copyright 2010, American Society of Heating, Refrigerating and Air-Conditioning Engineers, Inc. This posting is by permission from ASHRAE Journal/High Performing Buildings. This material may not be copied
More informationCisco Lab Setpoint Increase. Energy Efficient Data Center Demonstration Project
Cisco Lab Setpoint Increase Energy Efficient Data Center Demonstration Project About the Energy Efficient Data Center Demonstration Project The project s goal is to identify key technology, policy and
More informationPassive RDHx as a Cost Effective Alternative to CRAH Air Cooling. Jeremiah Stikeleather Applications Engineer
Passive RDHx as a Cost Effective Alternative to CRAH Air Cooling Jeremiah Stikeleather Applications Engineer Passive RDHx as a Cost Effective Alternative to CRAH Air Cooling While CRAH cooling has been
More informationHIGH DENSITY RACK COOLING CHOICES
WATERCOOLED HIGH PERFORMANCE COMPUTING SYSTEMS AQUILA WHITE PAPER HIGH DENSITY RACK COOLING CHOICES by Phil Hughes Reprinted with permission of Clustered Systems Company, Inc 1 THIS WHITE PAPER DISCUSSES
More informationRetro-Commissioning Report
10 Retro-Commissioning Report Retro-Commissioning Retro-Commissioning is the process for identifying intrinsic operational and energy related issues in the facilities DDC system and providing a mechanism
More informationPerformance Evaluation for Modular, Scalable Cooling Systems with Hot Aisle Containment in Data Centers. Final Report
Performance Evaluation for Modular, Scalable Cooling Systems with Hot Aisle Containment in Data Centers Final Report To The California Energy Commission May 2009 Tengfang Xu Environmental Energy Technologies
More informationFuture of Cooling High Density Equipment. Steve Madara Vice President and General Manager Liebert Precision Cooling Business Emerson Network Power
Future of Cooling High Density Equipment Steve Madara Vice President and General Manager Liebert Precision Cooling Business Emerson Network Power Agenda Issues facing the Data Center Managing the explosive
More informationIs Data Center Free Cooling Feasible in the Middle East? By Noriel Ong, ASEAN Eng., PMP, ATD, PQP
Is Data Center Free Cooling Feasible in the Middle East? By Noriel Ong, ASEAN Eng., PMP, ATD, PQP This case study will evaluate the feasibility of data center free cooling in the Middle East using indirect
More informationSilicon Valley Power Data Center Program Rebate Application
Contact Information Tax Status (check one) Sole Proprietor Contact Name Phone Corporation Partnership Company Email address Government Not-For-Profit Customer/Facility Information Company Name SVP Account
More informationUsing CFD Analysis to Predict Cooling System Performance in Data Centers Ben Steinberg, P.E. Staff Applications Engineer
Using CFD Analysis to Predict Cooling System Performance in Data Centers Ben Steinberg, P.E. Staff Applications Engineer Agenda What is CFD? Applications of CFD Applicability to the Data Center How it
More informationNew Wisconsin Energy Code: What it Means for Me?
2018 Wisconsin Energy Efficiency Expo Hosted by the Wisconsin Association of Energy Engineers New Wisconsin Energy Code: What it Means for Me? May 17, 2018 Shana Scheiber, PE, LEED AP ID+C, WELL AP Building
More informationReclaim Wasted Cooling Capacity Now Updated with CFD Models to Support ASHRAE Case Study Data
White Paper EC9005A Reclaim Wasted Cooling Capacity Now Updated with CFD Models to Support ASHRAE Case Study Data Peer reviewed case study data from ASHRAE now updated with CFD model analysis revealing
More informationData Center Energy and Cost Saving Evaluation
Available online at www.sciencedirect.com ScienceDirect Energy Procedia 75 (2015 ) 1255 1260 The 7 th International Conference on Applied Energy ICAE2015 Data Center Energy and Cost Saving Evaluation Z.
More informationMSYS 4480 AC Systems Winter 2015
MSYS 4480 AC Systems Winter 2015 Module 12: DATA CENTERS By Satwinder Singh 14/05/2015 1 Data Centers Data Centers are specialized environments that safeguard your company's most valuable equipment and
More informationSecond Stakeholder Meeting for Nonresidential HVAC Proposals Based on ASHRAE Revisions to Waterside Economizer
Second Stakeholder Meeting for Nonresidential HVAC Proposals Based on ASHRAE 90.1-2016 Revisions to Waterside Economizer March 15, 2017 Stefan Gracik 510-663-2070 sgracik@integralgroup.com Agenda 1. Background
More informationDigital Realty Data Center Solutions Digital Chicago Datacampus Franklin Park, Illinois Owner: Digital Realty Trust Engineer of Record: ESD Architect
Digital Realty Data Center Solutions Digital Chicago Datacampus Franklin Park, Illinois Owner: Digital Realty Trust Engineer of Record: ESD Architect of Record: SPARCH Project Overview The project is located
More informationTWO FINANCIAL IMPACT STUDIES. Seal IT Equipment Cabinets for Significant Annual Cost Savings and Simple Payback in a Few Short Months
TWO FINANCIAL IMPACT STUDIES Seal IT Equipment Cabinets for Significant Annual Cost Savings and Simple Payback in a Few Short Months TWO FINANCIAL IMPACT STUDIES Seal IT Equipment Cabinets for Significant
More informationEvaluation and Modeling of Data Center Energy Efficiency Measures for an Existing Office Building
Evaluation and Modeling of Data Center Energy Efficiency Measures for an Existing Office Building Dhayanandh Murugan 1, Gabrielle Viola McMorrow 1, Dr.Liping Wang 1, Greenberg Steve 2 1 University of Wyoming,
More informationWelcome Association of Energy Engineers to the Microsoft Technology Center
Welcome Association of Energy Engineers to the Microsoft Technology Center Today s Agenda 10:00 10:30 What s new in data center energy efficiency planning and implementation? 10:30 11:00 ASHRAE data center
More informationREPORT. Energy Efficiency of the San Diego Supercomputer Center and Distributed Data Centers at UCSD. Prepared for:
REPORT Energy Efficiency of the San Diego Supercomputer Center and Distributed Data Centers at UCSD Prepared for: San Diego Supercomputer Center 10100 John J Hopkins Drive San Diego, CA 92037 May 11, 2009
More informationEngineered Energy Solutions An Overview. Controls, Automation and Energy Conservation
Engineered Energy Solutions An Overview Controls, Automation and Energy Conservation Engineered Energy Solutions Independent Control System Integration and Engineering Firm specializing in the energy efficient
More information<Insert Picture Here> Austin Data Center 6Sigma DC CFD Model
Austin Data Center 6Sigma DC CFD Model Keith Ward Keith Ward Data Center Facilities Engineering and Logistics Design Austin Data Center Statistics - Space Original AT&T Designed and
More informationHot vs Cold Energy Efficient Data Centers. - SVLG Data Center Center Efficiency Summit
Hot vs Cold Energy Efficient Data Centers - SVLG Data Center Center Efficiency Summit KC Mares November 2014 The Great Debate about Hardware Inlet Temperature Feb 2003: RMI report on high-performance data
More informationOptimiz Chilled January 25, 2013
Optimiz zing Existing Data Center Chilled Water Plants January 25, 2013 This White Paper describes factors to be consideredd when optimizing an existing data center chilledd water plant. Authored by Michael
More informationIntroducing the Heat Wheel to the Data Center
Introducing the Heat Wheel to the Data Center Robert (Dr. Bob) Sullivan, Ph.D. Data Center Infrastructure Specialist KyotoCooling International Critical Facilities Round Table 1 A New Free Cooling Technique
More informationWhat s on the Horizon for HVAC in Title ? Mark Hydeman, PE, Principal Taylor Engineering, LLC
What s on the Horizon for HVAC in Title 24 2013? Mark Hydeman, PE, Principal Taylor Engineering, LLC http://www.taylor-engineering.com WHAT S WHAT S ON THE ON THE HORIZON HORIZON FOR FOR HVAC HVAC IN TITLE
More informationPrecision Cooling Mission Critical Air Handling Units
M I S S I O N C R I T I CA L C O O L I N G Precision Cooling Mission Critical Air Handling Units Global Expertise for Precision Cooling Solutions STULZ is a privately owned, global manufacturer of highly
More informationData Center Temperature Rise During a Cooling System Outage
Data Center Temperature Rise During a Cooling System Outage White Paper 179 Revision 0 By Paul Lin Simon Zhang Jim VanGilder > Executive summary The data center architecture and its IT load significantly
More informationRecapture Capacity for Existing. and Airflow Optimization
Recapture Capacity for Existing Data Centers Through Cooling and Airflow Optimization Introduction Challenges and Trends Agenda Cooling & Airflow Optimization Takeaways Learning Objectives Recognize opportunities
More informationCombining Cold Aisle Containment with Intelligent Control to Optimize Data Center Cooling Efficiency
A White Paper from the Experts in Business-Critical Continuity TM Combining Cold Aisle Containment with Intelligent Control to Optimize Data Center Cooling Efficiency Executive Summary Energy efficiency
More informationSchneider Electric Cooling Portfolio. Jim Tubbesing Heath Wilson APC/Schneider North Texas Rep Tubbesing Solutions
Schneider Electric Cooling Portfolio Jim Tubbesing Heath Wilson APC/Schneider North Texas Rep Tubbesing Solutions Data Center Cooling Agenda 1. How to size data center, server rooms, IDF rooms, etc in
More informationMoving Containment Inside the Enclosure. Jeff Markle Great Lakes Case & Cabinet
Moving Containment Inside the Enclosure Presented by Jeff Markle Great Lakes Case & Cabinet Containment Containment : To put constraint upon; to restrain; to confine; to keep within bounds Containment
More informationEfficiency of Data Center cooling
Efficiency of Data Center cooling Comparison of data room layouts and cooling systems Bohumil Cimbal Product manager for Cooling Systems in CONTEG Company Objective Basic questions between investor and
More informationSmart Data Centres. Robert M Pe, Data Centre Consultant HP Services SEA
Smart Data Centres Robert M Pe, Data Centre Consultant Services SEA 2006 Hewlett-Packard Development Company, L.P. The information contained herein is subject to change without notice Content Data center
More informationA) Differences between Precision and Comfort Cooling Here are the major differences exist between precision air conditioning and comfort systems.
DATA CENTRE COOLING SYSTEM A) Differences between Precision and Comfort Cooling Here are the major differences exist between precision air conditioning and comfort systems. 1. Cooling Optimized to Electronic
More informationImpact of Air Containment Systems
White Paper June 2012 WP-20 Impact of Air Containment Systems Reducing Energy Consumption Introduction: The Importance of Maintaining Data Center Cooling Energy Efficiency Data centers are mission-critical
More informationVariable Density, Closed-Loop, Water-Cooled Data Center Solution
Variable Density, Closed-Loop, Water-Cooled Data Center Solution Overview Great Lakes Case & Cabinet Co., Inc. has worked with Naissus Thermal Management Solutions, of Toronto, Ontario to develop one of
More informationReducing Data Center Cooling Costs through Airflow Containment
FEATURE Reducing Data Center Cooling Costs through Airflow Containment Implementing a containment solution in the data center costs much less than the alternatives of adding air handlers or other supplemental
More informationOptimizing Chilled Water Plant Performance. David Herman, PE, LEED AP Principal EnerG Associates, LLC
Optimizing Chilled Water Plant Performance David Herman, PE, LEED AP Principal EnerG Associates, LLC Optimizing Chilled Water Plant Learning Objectives Performance Review the design and operating characteristics
More informationYour Solution For Energy and Cost Savings. McQuay Packaged Chiller Plant
Your Solution For Energy and Cost Savings McQuay Packaged Chiller Plant Innovative Solutions for Your Chiller Plant McQuay packaged chiller plants provide energy efficient chillers integrated with pumps,
More informationChilled Water Distribution Design Considerations in Super Tall Buildings. Dusan Mrdalj, Associate, ChapmanBDSP
Chilled Water Distribution Design Considerations in Super Tall Buildings Dusan Mrdalj, Associate, ChapmanBDSP Dusan Mrdalj Bio - MSc Mechanical Engineering - Associate in ChapmanBDSP - 20 years of Professional
More informationE e n rgy g y St S ud u y y Pr P og o r g ams December 2011
Energy Study Programs December 2011 1 Agenda Energy Study Programs Overview Recommissioning Engineering Studies Data Center Studies Custom Rebates What makes a good energy study? 2 Energy Study Program
More informationData Center Temperature Design Tutorial. Ian Seaton Chatsworth Products
Data Center Temperature Design Tutorial Ian Seaton Chatsworth Products What are we going to do today? Explore a process for determining what data center operating temperature will deliver the best total
More information3300 kw, Tier 3, Chilled Water, 70,000 ft 2
[Reference Design 22] 3300 kw, Tier 3, Chilled Water, 70,000 ft 2 DESIGN OVERVIEW Data Center IT Capacity 1100 kw per Data Hall 3 Independent Data Halls Design Application Range This design can be applied
More informationWhere s the Heat Coming From. Leland Sparks Global Account Technical Consultant Belden
Where s the Heat Coming From Leland Sparks Global Account Technical Consultant Belden What is the greatest DC challenge you face? Air Flow to Heat Load Relation Server Inlet Fans Chips Outlet LOAD Dell
More informationInRow Chilled Water. Up to 70kW. Close-coupled, chilled water cooling for medium to large data centers. Row-Based Cooling.
InRow Chilled Water Close-coupled, chilled water cooling for medium to large data centers Up to 0kW > Row-Based Cooling The InRow Chilled Water product design closely couples the cooling with the IT heat
More informationReducing Energy Consumption with
Reducing Energy Consumption with Passive Cooling Ian Cathcart, RCDD Technical Support Manager Technical Support Manager Chatsworth Products, Inc. Thermal Management: Mission Critical Data center heat loads
More information7 Best Practices for Increasing Efficiency, Availability and Capacity. XXXX XXXXXXXX Liebert North America
7 Best Practices for Increasing Efficiency, Availability and Capacity XXXX XXXXXXXX Liebert North America Emerson Network Power: The global leader in enabling Business-Critical Continuity Automatic Transfer
More informationFACT SHEET: IBM NEW ZEALAND DATA CENTRE
FACT SHEET: IBM NEW ZEALAND DATA CENTRE IBM and the Data Centre IBM is the largest occupier of data centre space in the world and currently owns or occupies approximately one million square metres globally.
More informationINT 492 : Selected Topic in IT II (Data Center System Design) 3(3-0-6)
INT 492 : Selected Topic in IT II (Data Center Design) 3(3-0-6) การออกแบบระบบศ นย สารสนเทศ Overview The American Society of Heating, Refrigeration and Air-Conditioning Engineers (ASHRAE) Technical Committee
More informationData center cooling evolution. The hottest way to save energy. Lucio Bustaffa: Product Development Manager BlueBox Group
Data center cooling evolution. The hottest way to save energy Lucio Bustaffa: Product Development Manager BlueBox Group Data Center overview What s happening in the web? 2 Data Center overview What s happening
More informationFinal Thesis Presentation
Final Thesis Presentation Spring 2011 Advisor: Dr. Treado Building Overview Existing Conditions System Evaluation Building Overview Existing Conditions System Evaluation Building Overview Existing Conditions
More informationRittal Cooling Solutions A. Tropp
1 Rittal Cooling Solutions Presented by Adam Tropp 2 Agenda Cooling Strategies Aisle Containment Chimney Solution Airstream Management Rittal Liquid Cooling Packages Data Monitoring 3 Cooling strategies.
More informationChiller Replacement and System Strategy. Colin Berry Account Manager
Chiller Replacement and System Strategy Colin Berry Account Manager Current Situation 4 Existing RTAA chillers All units 23 years old Limited service history One unit MUST be replaced immediately One unit
More informationInternational 6SigmaDC User Conference CFD Modeling for Lab Energy Savings DCSTG Lab Temperature Setpoint Increase
International 6SigmaDC User Conference CFD Modeling for Lab Energy Savings DCSTG Lab Temperature Setpoint Increase Chris Noland cnoland@cisco.com Vipha Kanakakorn vkanakak@cisco.com 3/4/2010 Goal & Limitations
More informationOptimizing Cooling Performance Of a Data Center
ASHRAE www.ashrae.org. Used with permission from ASHRAE Journal. This article may not be copied nor distributed in either paper or digital form without ASHRAE s permission. For more information about ASHRAE,
More informationComprehensive Energy Management & Utility Master Plan
Comprehensive Energy Management & Utility Master Plan OVERVIEW University of Utah & Health Science Campus Overview Campus Transformation Value Drivers and Challenges Integrated Energy Planning Approach
More informationDUKE UNIVERSITY DESIGN & CONSTRUCTION STANDARDS
1 25 95 00 Integrated Automation Control Sequences for HVAC GENERAL The HVAC operational sequences in this guideline are commonly used by Duke University. They are being provided as a preferred design
More informationCurrent Data Center Design. James Monahan Sept 19 th 2006 IEEE San Francisco ComSoc
Current Data Center Design James Monahan Sept 19 th 2006 IEEE San Francisco ComSoc What is the biggest facility problem in your data center? 35% 30% 25% 20% 15% Series1 10% 5% 0% Excessive heat Insufficient
More informationPROCESS & DATA CENTER COOLING. How and Why To Prepare For What s To Come JOHN MORRIS REGIONAL DIRECTOR OF SALES
PROCESS & DATA CENTER COOLING How and Why To Prepare For What s To Come JOHN MORRIS REGIONAL DIRECTOR OF SALES CONGRATULATIONS 2 BOLD PREDICTION 3 Where We Are TODAY Computer Technology NOW advances more
More informationThe Energy. David L. Moss Dell Data Center Infrastructure
The Energy Advantages of Containment Systems David L. Moss Dell Data Center Infrastructure www.dell.com/hiddendatacenter Summary The Uptime Institute estimates that the cost to build a new 20,000 square
More informationCooling Solutions & Considerations for High Performance Computers
Cooling Solutions & Considerations for High Performance Computers White Paper 6 Revision 1 By Rich Whitmore Executive summary The recent advances in high performance computing have driven innovations not
More informationA Design Guidelines Sourcebook January High Performance Data Centers
A Design Guidelines Sourcebook January 2011 High Performance Data Centers Table of Contents Introduction...1 1. Information Technology (IT) Systems...3 2. Air Management...10 3. Air-Side Economizer...19
More informationTop 10 energy conservation measures for data centers. Presented by: Michael G. Bushell, P.E. Willdan Energy Solutions Chicago, Illinois
Top 10 energy conservation measures for data centers Presented by: Michael G. Bushell, P.E. Willdan Energy Solutions Chicago, Illinois December 11, 2014 Top 10 energy conservation measures for data centers
More informationLANL High Performance Computing Facilities Operations. Rick Rivera and Farhad Banisadr. Facility Data Center Management
Slide-1 LANL High Performance Computing Facilities Operations Rick Rivera and Farhad Banisadr Facility Data Center Management Division Slide-2 Outline Overview - LANL Computer Data Centers Power and Cooling
More informationCooling. Highly efficient cooling products for any IT application. For More Information: (866) DATA CENTER SOLUTIONS
Cooling > Highly efficient cooling products for any IT application. DATA CENTER SOLUTIONS For More Information: (866) 787-3271 Sales@PTSdcs.com End-to-End Cooling Solutions from the Closet to the Data
More informationEvaporative free air cooling technology Providing evaporative free air cooling solutions.
Evaporative free air cooling technology Providing evaporative free air cooling solutions. Creating an effective workspace environment data centre free air cooling technology FreeCool - Evaporative Free
More informationRittal White Paper 506: Cold Aisle Containment for Improved Data Center Cooling Efficiency By: Daniel Kennedy
Rittal White Paper 506: Cold Aisle Containment for Improved Data Center Cooling Efficiency By: Daniel Kennedy Executive Summary Increasing power requirements for new servers have created the need to support
More informationIT Air Conditioning Units
IT Air Conditioning Units Modern Flexible Effective Energy Saving CoolTeg Plus and CoolTop overview CoolTeg Plus CW CoolTeg Plus DX CoolTeg Plus XC CoolTop Installation Between IT racks On top of IT rack
More information1.0 Executive Summary. 2.0 Available Features & Benefits
Statement Of Work Energy Management Services Table of Contents 1.0 Executive Summary 2.0 Available Features & Benefits 3.0 Assessment Deliverables Selection 4.0 On Site Assessment Activities 5.0 Exclusions
More informationUser Guide. FreeCool : Free Cooling unit V1.1 ENGY-SVU001A-GB
User Guide FreeCool : Free Cooling unit V1.1 ENGY-SVU001A-GB Table of Contents Introduction...3 General features...4 User interface...5 Top display area... 5 Bottom display area... 5 Main display area...
More informationEnergy Logic: Emerson Network Power. A Roadmap for Reducing Energy Consumption in the Data Center. Ross Hammond Managing Director
Energy Logic: A Roadmap for Reducing Energy Consumption in the Data Center Emerson Network Power Ross Hammond Managing Director Agenda Energy efficiency Where We Are Today What Data Center Managers Are
More informationHIGH DENSITY DATACOM INTEGRATED COOLING SYSTEM.
HIGH DENSITY DATACOM INTEGRATED COOLING SYSTEM. SYSTEM LOGICA is the most advanced alternative to the problem of cooling of server rooms MONTAIR is the trademark which represents excellence on the market
More informationDCIM Data Center Infrastructure Management
DCIM Data Center Infrastructure Management Part 2 Implementation Challenges & Strategic Advantages - Predictive Analysis August 8, 2013 Presented by Julius Neudorfer Sponsored by Today s Topics Implementation
More informationSpecification and Design Catalog. Waterside Economizer
Specification and Design Catalog Waterside Economizer Table of Contents Waterside Economizer Applications.................................................... 4 Application Notes..................................................................
More informationProduct Brochure DENCO Close Control Units Row-DENCO. High Density Cooling for Data Centres
Product Brochure DENCO Close Control Units Row-DENCO High Density Cooling for Data Centres Data Centre Cooling Through a history in close control, we have developed a broad and deep understanding of how
More informationAPC APPLICATION NOTE #126
#16 Selection Procedure for Inow Chilled Water Products By Greg Uhrhan, P.E. and Scott Buell Abstract Proper selection of Inow chilled water cooling systems requires an engineer or technical salesperson
More informationBuilding Re-Tuning (BRT) Lesson 4: SOI Air-Handling Unit Part II
Building Re-Tuning (BRT) Lesson 4: SOI Air-Handling Unit Part II Lesson 4: Sections Review of last class (0:20) Section 1: AHU: Discharge air temperature control (0:45) Break (0:10) Section 2: AHU: Heating
More informationHow Green can you go?
ASHRAE 90.1 2010 It s out..and should be our code in 3 years Work on sealing and testing building envelope, commissioning Cool Roofs..hey were already doing that Extensive Controls enhancements Equipment
More information2013 Building Energy Efficiency Standards Non-Residential HVAC Alterations
B 2013 Building Energy Efficiency Standards Non-Residential HVAC Alterations BUSINESS AND PROFESSIONS CODE, SECTION 7110 Willful or deliberate disregard and violation of the building laws, including the
More informationHigh Density Cooling Solutions that work from Knurr Kris Holla
High Density Cooling Solutions that work from Knurr Kris Holla The Heat Goes On Ó by Knürr A An International Company Ranked #3 in the world Founded 1931 Strong international setting in over 32 countries
More informationDEDICATED HEAT RECOVERY UNIT (DHRC)
DEDICATED HEAT RECOVERY UNIT (DHRC) AHRI CERTIFICATION Air-Conditioning, Heating, and Refrigeration Institute Multistack is AHRI Certified and continues to certify products as they are developed AHRI Certification
More informationinteractive tool for 90.1 available on the ASHRAE website.
providing insights for today s hvac system designer Engineers Newsletter volume 47 2 HVAC-related changes in ASHRAE Standard 90.1-2016 Jurisdictions have begun to adopt ASHRAE 90.1-2013. We now look to
More informationDesigning Ultra-Efficient Building Cooling Systems
Designing Ultra-Efficient Building Cooling Systems Design to Apply Effective Optimization Technologies To Chiller Plants and Air Systems ASHRAE Triangle Chapter Raleigh, NC November 16, 2016 Tom Hartman,
More informationAisleLok Modular Containment vs. Legacy Containment: A Comparative CFD Study of IT Inlet Temperatures and Fan Energy Savings
WHITE PAPER AisleLok Modular Containment vs. : A Comparative CFD Study of IT Inlet Temperatures and Fan Energy Savings By Bruce Long, Upsite Technologies, Inc. Lars Strong, P.E., Upsite Technologies, Inc.
More informationData Center Infrastructure Management (DCIM) By Jesse Zhuo
Data Center Infrastructure Management (DCIM) By Jesse Zhuo Agenda The Evolution of DCIM Users Perspectives Management Methodology by Delta DCIM The Evolution of DCIM What is DCIM DCIM is software for Data
More informationNew Techniques for Energy-Efficient Data Center Cooling
New Techniques for Energy-Efficient Data Center Cooling Applications for Large and Small Data Centers By Wally Phelps Director of Engineering AdaptivCOOL www.adaptivcool.com Copyright Degree Controls,
More informationCreating an Energy-Efficient, Automated Monitoring System for Temperature and Humidity at a World-Class Data Center
About CyrusOne CyrusOne is a world-renowned enterprise data center provider that offers 40 data centers across the U.S., Europe and Asia with a three million-plus square feet of total net rentable space.
More informationFREECOOLING, EVAPORATIVE AND ADIABATIC COOLING TECHNOLOGIES IN DATA CENTER. Applications in Diverse Climates within Europe, Middle East and Africa
FREECOOLING, EVAPORATIVE AND ADIABATIC COOLING TECHNOLOGIES IN DATA CENTER Applications in Diverse Climates within Europe, Middle East and Africa Freecooling, Evaporative and Adiabatic Cooling Technologies
More informationCHILLED WATER. HIGH PRECISION AIR CONDITIONERS, FROM 7 TO 211 kw
IT COOLING CLOSE CONTROL AIR CONDITIONERS CHILLED WATER HIGH PRECISION AIR CONDITIONERS, FROM 7 TO 211 kw 3 Versions available Single chilled water coil Double chilled water coil High temperature IT COOLING
More informationClose-coupled cooling
Close-coupled cooling Intelligently controlled high-performance InRow cooling for the IT environment APC TM by Schneider Electric close-coupled cooling products provide a modular, scalable, and predictable
More informationValidation and Uncertainty Characterization for Energy Simulation
Validation and Uncertainty Characterization for Energy Simulation Multi-Zone HVAC System using ORNL s Flexible Research Platform (FRP) For: ASHRAE SSPC140 June 26, 2016 PM: Joshua New PIs Piljae Im and
More informationIBM - Energy Efficiency Recommissioning: Improving Buildings Systems Efficiency Jean-Pierre Boulianne, Pierre Lefèbvre, Yves Veilleux ICEBO 2013
IBM - Energy Efficiency Recommissioning: Improving Buildings Systems Efficiency Jean-Pierre Boulianne, Pierre Lefèbvre, Yves Veilleux ICEBO 2013 IBM Bromont - Recommissioning IBM Manufacturing Plant Bromont,
More informationRack cooling solutions for high density racks management, from 10 to 75 kw
Rack cooling solutions for high density racks management, from 10 to 75 Superior efficiency, high reliability, low energy consumption Modern data center are characterized by 24/7 operation all year long.
More informationR4 Ventures LLC White Paper
R4 Ventures LLC PR ODUCT IN HARD COPY OR DIGITAL FORM. ALL OFFENDERS WILL BE SUED IN A COURT OF LAW. R4 Ventures LLC White Paper Comparison of energy consumption in kw per ton of cooling Real Time Data
More information