Chilled Water Distribution Design Considerations in Super Tall Buildings. Dusan Mrdalj, Associate, ChapmanBDSP

Size: px
Start display at page:

Download "Chilled Water Distribution Design Considerations in Super Tall Buildings. Dusan Mrdalj, Associate, ChapmanBDSP"

Transcription

1 Chilled Water Distribution Design Considerations in Super Tall Buildings Dusan Mrdalj, Associate, ChapmanBDSP

2 Dusan Mrdalj Bio - MSc Mechanical Engineering - Associate in ChapmanBDSP - 20 years of Professional Experience - 12 Years in the UAE - Involved with design of iconic supertall buildings (WTC AD, OT Dubai )

3 SUPERTALL BUILDINGS AC DESIGN CONSTRAINTS - Building Height vs System Pressure Limitations - Comfort Conditions - Plantroom Space & Access

4 BUILDING HEIGHT

5 HYDROSTATIC PRESSURE IN WATER COLUMN where p = ρ g h p = pressure in liquid (N/m 2, Pa, lb f /ft 2, psf) ρ = density of liquid (kg/m 3, lb/ft 3 ) g = acceleration of gravity (9.81 m/s 2, ft/s 2 ) h = height of fluid column (m, ft)

6 COMFORT CONDITIONS - Temperature - Air Distribution - Stack Effect

7 PLANTROOM SPACE & ACCESS

8 COOLING ENERGY GENERATION Chillers Types (Condensers) Air Cooled Water Cooled

9 CHILLED WATER PRESSURE BREAK CONCEPT Plate Heat Exchanger p3 p2 p1

10 CHILLED WATER TEMP. AT TOB Counter flow Co-current flow Plate HEX Δt 1 C

11 TYPCIAL FCU SELECTION SHEETS

12 FCU CAPACITY VS CHW SUPPLY TEMPERATURE FCU COOLING CAPACITY IN RELATION TO CHW SUPPLY TEMPERATURE FCU Total Capacity (kw) FCU Sensible Capacity (kw) FCU Latent Capacity (kw) Assumed Conditions Standard FCU size 12 at medium speed CHW Delta T: 7 C On-coil DB/WB: 22.5/17 C FCU LATENT CAPACITY IN RELATION TO CHW SUPPLY TEMPERATURE FCU Latent Capacity (kw)

13 FCU CAPACITY VS CHW SUPPLY TEMPERATURE FCU COOLING CAPACITY IN RELATION TO CHW SUPPLY TEMPERATURE FCU Total Capacity (kw) FCU Sensible Capacity (kw) FCU Latent Capacity (kw) Assumed Conditions District Cooling FCU size 12 at medium speed CHW Delta T: 9 C On-coil DB/WB: 22.5/17 C FCU LATENT CAPACITY IN RELATION TO CHW SUPPLY TEMPERATURE FCU Latent Capacity (kw)

14 FCU CAPACITY VS CHW SUPPLY TEMPERATURE FCU COOLING CAPACITY IN RELATION TO CHW SUPPLY TEMPERATURE FCU Total Capacity (kw) FCU Sensible Capacity (kw) FCU Latent Capacity (kw) Assumed Conditions District Cooling FCU size 12 at medium speed CHW Delta T: 9 C On-coil DB/WB: 25/18.7 C FCU LATENT CAPACITY IN RELATION TO CHW SUPPLY TEMPERATURE FCU Latent Capacity (kw)

15 DISTRIBUTION PIPEWORK HEAT GAINS

16 HOW TO RESOLVE 1. CHILLERS AT HIGH ELEVATION 2. LOW TEMPERATURE CHILLERS AT BASE 3. HYBRID SOLUTION

17 CHILLERS AT HIGH ELEVATION PROS CHW generation closer to demand - less distribution losses CHW temperature not affected by pressure breaks Lower temperature CHW easily achieved No requirement for low temperature/glycol chillers Less space for primary services CONS Large plantroom required in premium space up in the building Pressure breaks required in condenser water circuit Special access arrangements for chillers installation & replacement More power needed to be transmitted up the building Noise and vibration issues more severe

18 CHILLERS AT BUILDING BASE PROS Removes need for large plantroom up in the building and associated access Less power up the building required Noise and vibration less of an issue No pressure breaks in condensing circuit required CONS CHW generation farther from demand - more distribution losses Pressure breaks required in CHW circuit Chillers required to operate at low temperature/glycol chillers More space for primary services

19 HYBRID SOLUTIONS Small chillers installed up in the building Designed as a back-up to deal only with critical cooling load (FLS or Server rooms) Can be used to achieve desired CHW supply temperature in case of high fluctuation in cooling load Smaller units in modular arrangement recommended

20 DISTRICT COOLING UTILIZATION

21 STANDARD CHILLERS EFFICIENCY - Air Cooled Chillers - Water Cooled Chillers with Cooling Towers - Water Cooled Chillers with District Cooling - Water Cooled Chillers with Glycol

22 CHILLERS EFFICIENCY SELECTION OPTIONS Option 1 Option 2 Option 3 Option 4 Type: Air Cooled Type: Water Cooled Type: Water Cooled Type: Water Cooled Capacity: 500 TR Capacity: 500 TR Capacity: 500 TR Capacity: 500 TR OA DB: 46 C CW in/out: 35/40 C CW in/out: 12/17 C CW in/out: 12/17 C CHW: 5/14 C CHW: 5/14 C CHW: 5/14 C Glycol: 2/11 C

23 CHILLERS EFFICIENCY SELECTION 1

24 CHILLERS EFFICIENCY SELECTION 2

25 CHILLERS EFFICIENCY SELECTION 3

26 CHILLERS EFFICIENCY SELECTION 4

27 CHILLERS EFFICIENCY COMPARISON Peak Power (kw) Option 1 Option 2 Option 3 Option Option 1 Option 2 Option 3 Option 4

28 CHILLERS EFFICIENCY COMPARISON COP Option 1 Option 2 Option 3 Option Option 1 Option 2 Option 3 Option 4

29 QUESTIONS

7 Best Practices for Increasing Efficiency, Availability and Capacity. XXXX XXXXXXXX Liebert North America

7 Best Practices for Increasing Efficiency, Availability and Capacity. XXXX XXXXXXXX Liebert North America 7 Best Practices for Increasing Efficiency, Availability and Capacity XXXX XXXXXXXX Liebert North America Emerson Network Power: The global leader in enabling Business-Critical Continuity Automatic Transfer

More information

Mission Critical Facilities & Technology Conference November 3, 2011 Cooling 101. Nick Gangemi Regional Sales Manager Data Aire

Mission Critical Facilities & Technology Conference November 3, 2011 Cooling 101. Nick Gangemi Regional Sales Manager Data Aire Mission Critical Facilities & Technology Conference November 3, 2011 Cooling 101 Nick Gangemi Regional Sales Manager Data Aire Agenda Exactly what are we talking about ASHRAE TC 9.9 Design best practices

More information

CHILLED WATER. HIGH PRECISION AIR CONDITIONERS, FROM 7 TO 211 kw

CHILLED WATER. HIGH PRECISION AIR CONDITIONERS, FROM 7 TO 211 kw IT COOLING CLOSE CONTROL AIR CONDITIONERS CHILLED WATER HIGH PRECISION AIR CONDITIONERS, FROM 7 TO 211 kw 3 Versions available Single chilled water coil Double chilled water coil High temperature IT COOLING

More information

Passive RDHx as a Cost Effective Alternative to CRAH Air Cooling. Jeremiah Stikeleather Applications Engineer

Passive RDHx as a Cost Effective Alternative to CRAH Air Cooling. Jeremiah Stikeleather Applications Engineer Passive RDHx as a Cost Effective Alternative to CRAH Air Cooling Jeremiah Stikeleather Applications Engineer Passive RDHx as a Cost Effective Alternative to CRAH Air Cooling While CRAH cooling has been

More information

Future of Cooling High Density Equipment. Steve Madara Vice President and General Manager Liebert Precision Cooling Business Emerson Network Power

Future of Cooling High Density Equipment. Steve Madara Vice President and General Manager Liebert Precision Cooling Business Emerson Network Power Future of Cooling High Density Equipment Steve Madara Vice President and General Manager Liebert Precision Cooling Business Emerson Network Power Agenda Issues facing the Data Center Managing the explosive

More information

Cooling. Highly efficient cooling products for any IT application. For More Information: (866) DATA CENTER SOLUTIONS

Cooling. Highly efficient cooling products for any IT application. For More Information: (866) DATA CENTER SOLUTIONS Cooling > Highly efficient cooling products for any IT application. DATA CENTER SOLUTIONS For More Information: (866) 787-3271 Sales@PTSdcs.com End-to-End Cooling Solutions from the Closet to the Data

More information

Efficiency of Data Center cooling

Efficiency of Data Center cooling Efficiency of Data Center cooling Comparison of data room layouts and cooling systems Bohumil Cimbal Product manager for Cooling Systems in CONTEG Company Objective Basic questions between investor and

More information

What s New for Data Centers in Title Jeff Stein, PE Taylor Engineering

What s New for Data Centers in Title Jeff Stein, PE Taylor Engineering What s New for Data Centers in Title 24-2013 Jeff Stein, PE Taylor Engineering SVLG Workshop November 14, 2013 About Jeff Stein Principal, Taylor Engineering 2000 - now Professional Experience Eley Associates,

More information

Chiller Replacement and System Strategy. Colin Berry Account Manager

Chiller Replacement and System Strategy. Colin Berry Account Manager Chiller Replacement and System Strategy Colin Berry Account Manager Current Situation 4 Existing RTAA chillers All units 23 years old Limited service history One unit MUST be replaced immediately One unit

More information

MSYS 4480 AC Systems Winter 2015

MSYS 4480 AC Systems Winter 2015 MSYS 4480 AC Systems Winter 2015 Module 12: DATA CENTERS By Satwinder Singh 14/05/2015 1 Data Centers Data Centers are specialized environments that safeguard your company's most valuable equipment and

More information

Digital Realty Data Center Solutions Digital Chicago Datacampus Franklin Park, Illinois Owner: Digital Realty Trust Engineer of Record: ESD Architect

Digital Realty Data Center Solutions Digital Chicago Datacampus Franklin Park, Illinois Owner: Digital Realty Trust Engineer of Record: ESD Architect Digital Realty Data Center Solutions Digital Chicago Datacampus Franklin Park, Illinois Owner: Digital Realty Trust Engineer of Record: ESD Architect of Record: SPARCH Project Overview The project is located

More information

APC APPLICATION NOTE #126

APC APPLICATION NOTE #126 #16 Selection Procedure for Inow Chilled Water Products By Greg Uhrhan, P.E. and Scott Buell Abstract Proper selection of Inow chilled water cooling systems requires an engineer or technical salesperson

More information

IT Air Conditioning Units

IT Air Conditioning Units IT Air Conditioning Units Modern Flexible Effective Energy Saving CoolTeg Plus and CoolTop overview CoolTeg Plus CW CoolTeg Plus DX CoolTeg Plus XC CoolTop Installation Between IT racks On top of IT rack

More information

HIGH DENSITY RACK COOLING CHOICES

HIGH DENSITY RACK COOLING CHOICES WATERCOOLED HIGH PERFORMANCE COMPUTING SYSTEMS AQUILA WHITE PAPER HIGH DENSITY RACK COOLING CHOICES by Phil Hughes Reprinted with permission of Clustered Systems Company, Inc 1 THIS WHITE PAPER DISCUSSES

More information

MPC Air-Cooled Chillers MPC-FC Free-Cooling Chillers

MPC Air-Cooled Chillers MPC-FC Free-Cooling Chillers INNOVATE DESIGN APPLY www.motivaircorp.com MPC Air-Cooled Chillers MPC-FC Free-Cooling Chillers ½ - 100 Tons OUR BUSINESS IS COOLING YOURS. When commercial grade isn t enough Motivair is a world-class

More information

Aquaflair. Uniflair TRAC, TRAF and TRAH. Air-cooled chillers, free-cooling chillers and heat pumps with scroll compressors.

Aquaflair. Uniflair TRAC, TRAF and TRAH. Air-cooled chillers, free-cooling chillers and heat pumps with scroll compressors. Aquaflair Uniflair TRAC, TRAF and TRAH Air-cooled chillers, free-cooling chillers and heat pumps with scroll compressors 120-350kW Uniflair TRA ranges 115-350kW Air-cooled Chillers Cooling, Free cooling

More information

Rack cooling solutions for high density racks management, from 10 to 75 kw

Rack cooling solutions for high density racks management, from 10 to 75 kw Rack cooling solutions for high density racks management, from 10 to 75 Superior efficiency, high reliability, low energy consumption Modern data center are characterized by 24/7 operation all year long.

More information

PT CLIMANUSA TATA MEKADATA Citypark Business District Blok F No 05 Jl. Malibu Raya, Cengkareng Jakarta Barat Indonesia. Phone

PT CLIMANUSA TATA MEKADATA Citypark Business District Blok F No 05 Jl. Malibu Raya, Cengkareng Jakarta Barat Indonesia. Phone PT CLIMANUSA TATA MEKADATA Citypark Business District Blok F No 0 Jl. Malibu Raya, Cengkareng Jakarta Barat 70 Indonesia Phone + 4 4 www.climanusa.com Marketing features prominent presence on the world

More information

Next Generation DCP Optimization using MV VSDs

Next Generation DCP Optimization using MV VSDs Next Generation DCP Optimization using MV VSDs Vivek Apte Regional Product Director Johnson Controls - Middle East Cell : +971506243059 IDEA 2016- Dubai 1 Central Plant Optimization Energy and operating

More information

MOLLIER DIAGRAM CAN BE IMPROVED!

MOLLIER DIAGRAM CAN BE IMPROVED! MOLLIER DIAGRAM CAN BE IMPROVED! IMPROVED BASIC COOLING CIRCUIT PERFORMANCE EFFICIENCY USING AN ECONOMISER Eng. Jonny Malachi, VP Operations, Mashav Refrigeration and Air Conditioning Engineering Ltd.

More information

TWO FINANCIAL IMPACT STUDIES. Seal IT Equipment Cabinets for Significant Annual Cost Savings and Simple Payback in a Few Short Months

TWO FINANCIAL IMPACT STUDIES. Seal IT Equipment Cabinets for Significant Annual Cost Savings and Simple Payback in a Few Short Months TWO FINANCIAL IMPACT STUDIES Seal IT Equipment Cabinets for Significant Annual Cost Savings and Simple Payback in a Few Short Months TWO FINANCIAL IMPACT STUDIES Seal IT Equipment Cabinets for Significant

More information

DATA CENTER EFFICIENCY: Data Center Temperature Set-point Impact on Cooling Efficiency

DATA CENTER EFFICIENCY: Data Center Temperature Set-point Impact on Cooling Efficiency DATA CENTER EFFICIENCY: Data Center Temperature Set-point Impact on Cooling Efficiency September 27 th, 2013 Tejas Desai, PE CEM CEA LEED AP Sameer Behere, PE CEM LEED AP Agenda Problem: Quick fixes can

More information

A Data Center Heat Removal System That Saves... 80% Discover Inertech s Award-winning Data Center Heat Removal System

A Data Center Heat Removal System That Saves... 80% Discover Inertech s Award-winning Data Center Heat Removal System A Data Center Heat Removal System That Saves... Infrastructure Power Water up to 40% up to 80% up to 85% Discover Inertech s Award-winning Data Center Heat Removal System A Cool Solution; A Breakthrough

More information

Introducing the Heat Wheel to the Data Center

Introducing the Heat Wheel to the Data Center Introducing the Heat Wheel to the Data Center Robert (Dr. Bob) Sullivan, Ph.D. Data Center Infrastructure Specialist KyotoCooling International Critical Facilities Round Table 1 A New Free Cooling Technique

More information

IBM Symposium Data Center Cooling. EC Systems for HVAC architecture and Direct air Cabinet Cooling

IBM Symposium Data Center Cooling. EC Systems for HVAC architecture and Direct air Cabinet Cooling IBM Symposium 2008 Data Center Cooling EC Systems for HVAC architecture and Direct air Cabinet Cooling Presented by David J. Spofford Product Manager IT/Telecomm 1 Agenda Data Center trends for IT and

More information

InRow Chilled Water. Up to 70kW. Close-coupled, chilled water cooling for medium to large data centers. Row-Based Cooling.

InRow Chilled Water. Up to 70kW. Close-coupled, chilled water cooling for medium to large data centers. Row-Based Cooling. InRow Chilled Water Close-coupled, chilled water cooling for medium to large data centers Up to 0kW > Row-Based Cooling The InRow Chilled Water product design closely couples the cooling with the IT heat

More information

Liebert DCW CATALOGUE

Liebert DCW CATALOGUE Liebert DCW CATALOGUE Chilled Water-Based High Density Cooling For The Data Center LIEBERT DCW Flexible Approaches For Energy Efficient Cooling Save up to 70% in cooling energy usage Data center managers

More information

Variable Density, Closed-Loop, Water-Cooled Data Center Solution

Variable Density, Closed-Loop, Water-Cooled Data Center Solution Variable Density, Closed-Loop, Water-Cooled Data Center Solution Overview Great Lakes Case & Cabinet Co., Inc. has worked with Naissus Thermal Management Solutions, of Toronto, Ontario to develop one of

More information

System Overview. Liquid Cooling for Data Centers. Negative Pressure Cooling Without Risk of Leaks

System Overview. Liquid Cooling for Data Centers. Negative Pressure Cooling Without Risk of Leaks Liquid Cooling for Data Centers System Overview The Chilldyne Cool-Flo System is a direct-to-chip liquid cooling system that delivers coolant under negative pressure. Chilldyne s technologies were designed

More information

Precision Cooling. Precision Cooling Advantages

Precision Cooling. Precision Cooling Advantages Precision Cooling Today s computing technologies compound conventional cooling problems. Blade servers, communications switches and other electronics are being packed into tighter and tighter spaces. Computing

More information

Chiller Plant Optimization: A Case Study

Chiller Plant Optimization: A Case Study Presentation of Chiller Plant Optimization: A Case Study Presented by Michael S. Conway The site Large pharmaceutical client 5 MW cogen 88,000 PPH of boiler capability 8,200 tons of chiller capability

More information

FPS SERIES Super Slim Ceiling Mount Air Handling Units

FPS SERIES Super Slim Ceiling Mount Air Handling Units About Multistack 19, Multistack is well-known in the international air conditioning industry by its invention of modular chiller. Today, Multistack has grown into an international refrigeration & air conditioning

More information

glide glider kw R134a air cooled liquid chillers AND free cooling chillers FREE COOLING SHELL A C CLASS E C Energy Class RCGROUP SpA

glide glider kw R134a air cooled liquid chillers AND free cooling chillers FREE COOLING SHELL A C CLASS E C Energy Class RCGROUP SpA 99 glide air cooled liquid chillers ND free cooling chillers glider 178 1328 Energy Class More efficient + B C D E F G Less efficient R134a CLSS SHELL C E C FREE COOLING 100 air cooled liquid chiller and

More information

Designing Ultra-Efficient Building Cooling Systems

Designing Ultra-Efficient Building Cooling Systems Designing Ultra-Efficient Building Cooling Systems Design to Apply Effective Optimization Technologies To Chiller Plants and Air Systems ASHRAE Triangle Chapter Raleigh, NC November 16, 2016 Tom Hartman,

More information

Rittal Cooling Solutions A. Tropp

Rittal Cooling Solutions A. Tropp 1 Rittal Cooling Solutions Presented by Adam Tropp 2 Agenda Cooling Strategies Aisle Containment Chimney Solution Airstream Management Rittal Liquid Cooling Packages Data Monitoring 3 Cooling strategies.

More information

LCP Hybrid Efficient performance with heat pipe technology

LCP Hybrid Efficient performance with heat pipe technology LCP Hybrid Efficient performance with heat pipe technology 2 LCP Hybrid The whole is more than the sum of its parts The same is true of "Rittal The System." With this in mind, we have bundled our innovative

More information

SUPERSAVER. Energy Efficiency Optimization Software for Freecooling Systems

SUPERSAVER. Energy Efficiency Optimization Software for Freecooling Systems SUPERSAVER Energy Efficiency Optimization Software for Freecooling Systems SUPERSAVER Supersaver Delivers Enhanced Freecooling Efficiency via Integrated Vertiv ICOM Communication Supersaver is the Vertiv

More information

Case study: Energy efficiency improvements in a legacy data centre. Robert Tozer Director Opera>onal Intelligence

Case study: Energy efficiency improvements in a legacy data centre. Robert Tozer Director Opera>onal Intelligence Case study: Energy efficiency improvements in a legacy data centre Robert Tozer Director Opera>onal Intelligence Objec>ves First improve air management Air supply temperature to servers Lower temperature

More information

HVAC System Energy Savings Opportunities

HVAC System Energy Savings Opportunities HVAC System Energy Savings Opportunities Speaker Info M. Lant DuBose Energy Services ConEdison Solutions dubosem@conedsolutions.com (813)285-6340 Wholly owned subsidiary of ConEdison since 2007 Entered

More information

Welcome Association of Energy Engineers to the Microsoft Technology Center

Welcome Association of Energy Engineers to the Microsoft Technology Center Welcome Association of Energy Engineers to the Microsoft Technology Center Today s Agenda 10:00 10:30 What s new in data center energy efficiency planning and implementation? 10:30 11:00 ASHRAE data center

More information

Close-coupled cooling

Close-coupled cooling Close-coupled cooling Intelligently controlled high-performance InRow cooling for the IT environment APC TM by Schneider Electric close-coupled cooling products provide a modular, scalable, and predictable

More information

Saving Water and Operating Costs at NREL s HPC Data Center

Saving Water and Operating Costs at NREL s HPC Data Center Saving Water and Operating Costs at NREL s HPC Data Center Thomas P. Carter, P.E. Johnson Controls Thomas.P.Carter@jci.com David Sickinger National Renewable Energy Laboratory David.Sickinger@nrel.gov

More information

Product Brochure DENCO Close Control Units Row-DENCO. High Density Cooling for Data Centres

Product Brochure DENCO Close Control Units Row-DENCO. High Density Cooling for Data Centres Product Brochure DENCO Close Control Units Row-DENCO High Density Cooling for Data Centres Data Centre Cooling Through a history in close control, we have developed a broad and deep understanding of how

More information

GP SERIES Packaged Chillers

GP SERIES Packaged Chillers Blending Conveying Drying Process Cooling Heat Transfer Size Reduction GP SERIES Packaged Chillers Comprehensive Flexible Versatile Compact unitary designs available in a variety of configurations from

More information

i-accurate_gb_ High precision air-conditioners for data centres cooling, with new inverter technology and R-410A refrigerant, from 6 to 150 kw

i-accurate_gb_ High precision air-conditioners for data centres cooling, with new inverter technology and R-410A refrigerant, from 6 to 150 kw i-accurate_gb_07-2011 igh precision air-conditioners for data centres cooling, with new inverter technology and R-410A refrigerant, from 6 to 150 Coming form 40 years experience in air conditioning and

More information

Communication Register Map - Uniflair Cooling

Communication Register Map - Uniflair Cooling DIGITAL 0 1 1 - - - - DIGITAL 1 2 2 System On (Fan) 0 or 1 boolean R DIGITAL 2 3 3 Compressor 1 0 or 1 boolean R DIGITAL 3 4 4 Compressor 2 0 or 1 boolean R DIGITAL 4 5 5 Compressor 3 0 or 1 boolean R

More information

APC InRow Cooler Prototype Initial Report - Test Setup Verification. H. Coles, S. Greenberg Contributing: J. Bean (APC) November 18, 2011

APC InRow Cooler Prototype Initial Report - Test Setup Verification. H. Coles, S. Greenberg Contributing: J. Bean (APC) November 18, 2011 APC InRow Cooler Prototype Initial Report - Test Setup Verification H. Coles, S. Greenberg Contributing: J. Bean (APC) November 18, 2011 1 Introduction Contents Technology Description/Attributes Installation

More information

IT COOLING AIR CONDITIONERS FOR HIGH DENSITY RACKS AND BLADE SERVERS. RACK COOLING SOLUTIONS FOR HIGH DENSITY RACK MANAGEMENT, FROM 4 TO 75 kw

IT COOLING AIR CONDITIONERS FOR HIGH DENSITY RACKS AND BLADE SERVERS. RACK COOLING SOLUTIONS FOR HIGH DENSITY RACK MANAGEMENT, FROM 4 TO 75 kw IT COOLING AIR CONDITIONERS FOR HIGH DENSITY RACKS AND BLADE SERVERS RACK COOLING SOLUTIONS FOR HIGH DENSITY RACK MANAGEMENT, FROM 4 TO 75 kw IT COOLING AIR CONDITIONERS FOR HIGH DENSITY RACKS AND BLADE

More information

Liebert. AFC from 500 to 1700 kw. The Adiabatic Freecooling Solution with Top-Tier Availability

Liebert. AFC from 500 to 1700 kw. The Adiabatic Freecooling Solution with Top-Tier Availability Liebert AFC from 500 to 1700 kw The Adiabatic Freecooling Solution with Top-Tier Availability Liebert AFC from 500 to 1700 kw Vertiv Vertiv designs, builds and services mission critical technologies that

More information

International 6SigmaDC User Conference CFD Modeling for Lab Energy Savings DCSTG Lab Temperature Setpoint Increase

International 6SigmaDC User Conference CFD Modeling for Lab Energy Savings DCSTG Lab Temperature Setpoint Increase International 6SigmaDC User Conference CFD Modeling for Lab Energy Savings DCSTG Lab Temperature Setpoint Increase Chris Noland cnoland@cisco.com Vipha Kanakakorn vkanakak@cisco.com 3/4/2010 Goal & Limitations

More information

pco 3 Controller User Manual ASPX Digital Scroll, Air Packaged Chiller For Version MCDSV_A02

pco 3 Controller User Manual ASPX Digital Scroll, Air Packaged Chiller For Version MCDSV_A02 pco 3 Controller User Manual ASPX Digital Scroll, Air Packaged Chiller For Version MCDSV_A02 pco 3 Controller User Manual Introduction The Airstack Chiller is a modular air-cooled chiller composed of

More information

Optimizing Chilled Water Plant Performance. David Herman, PE, LEED AP Principal EnerG Associates, LLC

Optimizing Chilled Water Plant Performance. David Herman, PE, LEED AP Principal EnerG Associates, LLC Optimizing Chilled Water Plant Performance David Herman, PE, LEED AP Principal EnerG Associates, LLC Optimizing Chilled Water Plant Learning Objectives Performance Review the design and operating characteristics

More information

HIGH EFFICIENCY Central Chiller

HIGH EFFICIENCY Central Chiller Blending Conveying Drying Process Cooling Heat Transfer Size Reduction HIGH EFFICIENCY Central Chiller Energy Efficient Modular & Expandable Virtually Eliminate Downtime Available in 20-60 ton single units,

More information

How To Draw Chiller Monsters Werewolves Vampires And Zombies

How To Draw Chiller Monsters Werewolves Vampires And Zombies How To Draw Chiller Monsters Werewolves Vampires And Zombies We have made it easy for you to find a PDF Ebooks without any digging. And by having access to our ebooks online or by storing it on your computer,

More information

MCFCW-20-4HS-1 (4-Pipe) High Static Chilled/Hot Water Ceiling Concealed Cased Fan Coil 208/230V 4-Pipe Heating & Cooling Fan Coil 60,000 BTUH

MCFCW-20-4HS-1 (4-Pipe) High Static Chilled/Hot Water Ceiling Concealed Cased Fan Coil 208/230V 4-Pipe Heating & Cooling Fan Coil 60,000 BTUH MCFCW-20-4HS-1 (4-Pipe) High Static Chilled/Hot Water Ceiling Concealed Cased Fan Coil 208/230V 4-Pipe Heating & Cooling Fan Coil 60,000 BTUH 1 Chilled and Hot Water Fan Coil High Static 4-Pipe Nominal

More information

MCFCW-08-4LS-1 (4-Pipe) Low Static Chilled/Hot Water Ceiling Concealed Cased Fan Coil 208/230V 4-Pipe Heating & Cooling Fan Coil 24,000 BTUH

MCFCW-08-4LS-1 (4-Pipe) Low Static Chilled/Hot Water Ceiling Concealed Cased Fan Coil 208/230V 4-Pipe Heating & Cooling Fan Coil 24,000 BTUH MCFCW-08-4LS-1 (4-Pipe) Low Static Chilled/Hot Water Ceiling Concealed Cased Fan Coil 208/230V 4-Pipe Heating & Cooling Fan Coil 24,000 BTUH 1 Chilled and Hot Water Fan Coil Low Static 4-Pipe Nominal Size:

More information

Motivair MLC-SC Air-Cooled Scroll Chillers Tons

Motivair MLC-SC Air-Cooled Scroll Chillers Tons INNOVATE DESIGN APPLY www.motivaircorp.com Motivair MLC-SC Air-Cooled Scroll Chillers 100 285 Tons OUR BUSINESS IS COOLING YOURS. When commercial grade isn t enough Businesses who function in today s advanced

More information

MCFCW-06-4HS-1 (4-Pipe) High Static Chilled/Hot Water Ceiling Concealed Cased Fan Coil 208/230V 4-Pipe Heating & Cooling Fan Coil 18,000 BTUH

MCFCW-06-4HS-1 (4-Pipe) High Static Chilled/Hot Water Ceiling Concealed Cased Fan Coil 208/230V 4-Pipe Heating & Cooling Fan Coil 18,000 BTUH MCFCW-06-4HS-1 (4-Pipe) High Static Chilled/Hot Water Ceiling Concealed Cased Fan Coil 208/230V 4-Pipe Heating & Cooling Fan Coil 18,000 BTUH 1 Chilled and Hot Water Fan Coil High Static 4-Pipe Nominal

More information

Sorensen SG Series - Water Cooled kw V A. Programmable Precision High Power DC Power Supply

Sorensen SG Series - Water Cooled kw V A. Programmable Precision High Power DC Power Supply Sorensen SG Series - Water Cooled Programmable Precision High Power DC Power Supply High Power Density: up to 15 kw in 3U Wide Voltage Range: 0-40 V and 0-60 V, in increments of 5 kw from 5 to 15 kw Fast

More information

Hybrid Warm Water Direct Cooling Solution Implementation in CS300-LC

Hybrid Warm Water Direct Cooling Solution Implementation in CS300-LC Hybrid Warm Water Direct Cooling Solution Implementation in CS300-LC Roger Smith Mississippi State University Giridhar Chukkapalli Cray, Inc. C O M P U T E S T O R E A N A L Y Z E 1 Safe Harbor Statement

More information

2018 Product overview

2018 Product overview 2018 Product overview Project conditioning Evolution goes on During these years, the activity of EMICON has been developed with the production of liquid chillers for conditioning and industrial applications,

More information

Retro-Commissioning Report

Retro-Commissioning Report 10 Retro-Commissioning Report Retro-Commissioning Retro-Commissioning is the process for identifying intrinsic operational and energy related issues in the facilities DDC system and providing a mechanism

More information

Coordinating Liquid and Free Air Cooling with Workload Allocation for Data Center Power Minimization

Coordinating Liquid and Free Air Cooling with Workload Allocation for Data Center Power Minimization Coordinating Liquid and Free Air Cooling with Workload Allocation for Data Center Power Minimization Li Li, Wenli Zheng, Xiaodong Wang, and Xiaorui Wang Dept. of Electrical and Computer Engineering The

More information

CTC Low Temperature Process Chillers

CTC Low Temperature Process Chillers INNOVATE DESIGN APPLY CTC Low Temperature Process Chillers 5-500 Tons OUR BUSINESS IS COOLING YOURS TM When commercial grade isn t enough When it comes to process cooling, every application is unique in

More information

Large Tonnage Chillers. Kingsley Hu Technical Support Engineer

Large Tonnage Chillers. Kingsley Hu Technical Support Engineer Large Tonnage Chillers Kingsley Hu Technical Support Engineer Chongqing Plant Chiller Products Reference Projects Manufacturing Facility Major Milestones Global R&D Talent Production Line introduction

More information

Next Generation Cooling

Next Generation Cooling Next Generation Cooling Server Manufacturer Perspective Practical and Cost Effective David Moss Data Center Strategist Dell 1 Why Chip, Row, or Rack? Density? Energy Don t be scared; I don t see 50kW/rack

More information

MID approval no. DE-08-MI004-PTB004 Date of release

MID approval no. DE-08-MI004-PTB004 Date of release 1. Identification Energy and Flow Computer Flow rate and energy calculator for liquids, gases and water steam E-DB-1000-700-01 MID approval no. DE-08-MI004-PTB004 Date of release 04.01.08 2. Area of Application

More information

Hot vs Cold Energy Efficient Data Centers. - SVLG Data Center Center Efficiency Summit

Hot vs Cold Energy Efficient Data Centers. - SVLG Data Center Center Efficiency Summit Hot vs Cold Energy Efficient Data Centers - SVLG Data Center Center Efficiency Summit KC Mares November 2014 The Great Debate about Hardware Inlet Temperature Feb 2003: RMI report on high-performance data

More information

Liebert DCW Family Chilled Water-Based High Density Cooling For The Data Center. Precision Cooling For Business-Critical Continuity

Liebert DCW Family Chilled Water-Based High Density Cooling For The Data Center. Precision Cooling For Business-Critical Continuity Liebert DCW Family Chilled Water-Based High Density Cooling For The Data Center Precision Cooling For Business-Critical Continuity Flexible Approaches For Energy Efficient Cooling Save up to 70% in cooling

More information

Tier IV Standards as Specified in the TIA 942 Document

Tier IV Standards as Specified in the TIA 942 Document S No Architectural Proximity of visitor parking to data 18.3 m / 60 ft minimum separation with physical barriers to prevent vehicles from 1 center perimeter building walls driving closer 2 Building Construction

More information

Liebert. HPC-S Free Cooling Chiller Designed for the Efficient Cooling of Small Data Centers

Liebert. HPC-S Free Cooling Chiller Designed for the Efficient Cooling of Small Data Centers Liebert HPC-S Free Cooling Chiller Designed for the Efficient Cooling of Small Data Centers Liebert HPC-S FREE COOLING CHILLER Getting To A PUE Of 1.2 Free cooling data center chillers are designed to

More information

HPC/Advanced Cooling Track. Rolf Brink/CEO/Asperitas

HPC/Advanced Cooling Track. Rolf Brink/CEO/Asperitas HPC/Advanced Cooling Track Advanced Cooling Optimising for immersion Rolf Brink/CEO/Asperitas Rolf.Brink@ocproject.net +31 88 96 000 00 www.asperitas.com IMMERSED COMPUTING : AIC24 100% Removal of heat

More information

Final Thesis Presentation

Final Thesis Presentation Final Thesis Presentation Spring 2011 Advisor: Dr. Treado Building Overview Existing Conditions System Evaluation Building Overview Existing Conditions System Evaluation Building Overview Existing Conditions

More information

Energy Logic: Emerson Network Power. A Roadmap for Reducing Energy Consumption in the Data Center. Ross Hammond Managing Director

Energy Logic: Emerson Network Power. A Roadmap for Reducing Energy Consumption in the Data Center. Ross Hammond Managing Director Energy Logic: A Roadmap for Reducing Energy Consumption in the Data Center Emerson Network Power Ross Hammond Managing Director Agenda Energy efficiency Where We Are Today What Data Center Managers Are

More information

HP Modular Cooling System: water cooling technology for high-density server installations

HP Modular Cooling System: water cooling technology for high-density server installations HP Modular Cooling System: water cooling technology for high-density server installations technical brief Abstract... 2 Introduction... 2 Data center trends... 2 Increased power demands... 3 Increased

More information

LANL High Performance Computing Facilities Operations. Rick Rivera and Farhad Banisadr. Facility Data Center Management

LANL High Performance Computing Facilities Operations. Rick Rivera and Farhad Banisadr. Facility Data Center Management Slide-1 LANL High Performance Computing Facilities Operations Rick Rivera and Farhad Banisadr Facility Data Center Management Division Slide-2 Outline Overview - LANL Computer Data Centers Power and Cooling

More information

Total Modular Data Centre Solutions

Total Modular Data Centre Solutions Sector Data Centre Total Modular Data Centre Solutions www.airedale.com BRITISH MANUFACTURER ENERGY EFFICIENCY CONTROLS SERVICE TRAINING 01 Standardised Modular Designs to fit your needs Our modular system

More information

IN-DEPTH UNDERSTANDING OF HVAC EQUIPMENT & SYSTEM SPECIFICATIONS AND PERFORMANCE 11 & 12 JULY 2016 WISMA IEM

IN-DEPTH UNDERSTANDING OF HVAC EQUIPMENT & SYSTEM SPECIFICATIONS AND PERFORMANCE 11 & 12 JULY 2016 WISMA IEM IEM TRAINING CENTRE SDN. BHD. (127273-K) No. 33-1A (1 st Floor), Jalan 52/18, P.O. Box 224 (Jalan Sultan P.O.) 46720 Petaling Jaya, Selangor Darul Ehsan (GST ID No. 001525395456) Telephone No. 03-79586851

More information

Planning for Liquid Cooling Patrick McGinn Product Manager, Rack DCLC

Planning for Liquid Cooling Patrick McGinn Product Manager, Rack DCLC Planning for Liquid Cooling -------------------------------- Patrick McGinn Product Manager, Rack DCLC February 3 rd, 2015 Expertise, Innovation & Delivery 13 years in the making with a 1800% growth rate

More information

200 kw, Tier 3, Chilled Water, 5250 ft 2

200 kw, Tier 3, Chilled Water, 5250 ft 2 [eference Design 4] 200 kw, Tier 3, Chilled Water, 5250 ft 2 DESIGN OVEVIEW Data Center IT Capacity 200 kw Adaptable from 50 kw to 600 kw Target Availability Tier 3 Annualized UE at 100% Load 1.67 in Miami,

More information

How Green can you go?

How Green can you go? ASHRAE 90.1 2010 It s out..and should be our code in 3 years Work on sealing and testing building envelope, commissioning Cool Roofs..hey were already doing that Extensive Controls enhancements Equipment

More information

Liquid Cooling Package LCP Cooling Systems

Liquid Cooling Package LCP Cooling Systems Liquid Cooling Package LCP Cooling Systems 2 Rittal LCP The whole is more than the sum of its parts. The same is true of Rittal The System. With this in mind, we have bundled our innovative enclosure,

More information

Impact of Air Containment Systems

Impact of Air Containment Systems White Paper June 2012 WP-20 Impact of Air Containment Systems Reducing Energy Consumption Introduction: The Importance of Maintaining Data Center Cooling Energy Efficiency Data centers are mission-critical

More information

DATA CENTER PRECISION COOLING: The Need For A Higher Level Of Service Expertise

DATA CENTER PRECISION COOLING: The Need For A Higher Level Of Service Expertise DATA CENTER PRECISION COOLING: The Need For A Higher Level Of Service Expertise TWO STAGE POWER DISTRIBUTION Executive Summary Today s data centers are changing rapidly, and it is more important than ever

More information

Liebert Economizer Cooling Solutions Reduce Cooling Costs by up to 50% Without Compromising Reliability

Liebert Economizer Cooling Solutions Reduce Cooling Costs by up to 50% Without Compromising Reliability Precision Cooling for Business-Critical Continuity TM Liebert Economizer Cooling Solutions Reduce Cooling Costs by up to 50% Without Compromising Reliability DATA CENTER SOLUTIONS For More Information:

More information

Performance Evaluation for Modular, Scalable Cooling Systems with Hot Aisle Containment in Data Centers. Final Report

Performance Evaluation for Modular, Scalable Cooling Systems with Hot Aisle Containment in Data Centers. Final Report Performance Evaluation for Modular, Scalable Cooling Systems with Hot Aisle Containment in Data Centers Final Report To The California Energy Commission May 2009 Tengfang Xu Environmental Energy Technologies

More information

Performance Certification : From Energy Efficiency To Indoor Air Quality. By: Eric Foucherot

Performance Certification : From Energy Efficiency To Indoor Air Quality. By: Eric Foucherot Performance Certification : From Energy Efficiency To Indoor Air Quality By: Eric Foucherot Certified Products for Efficient & Safe Design Certified Performances for HVAC&R Product AIR CONDITIONERS CHILLERS

More information

The Basics of HVAC Operation and the Role of Automation. Mr. Jay Zaino GxP Automation, LLC

The Basics of HVAC Operation and the Role of Automation. Mr. Jay Zaino GxP Automation, LLC Welcome The Basics of HVAC Operation and the Role of Automation Mr. Jay Zaino GxP Automation, LLC Agenda Introduction / Overview HVAC Basics HVAC in Life Science Market Automation s role in it all 1 Introduction

More information

PROCESS & DATA CENTER COOLING. How and Why To Prepare For What s To Come JOHN MORRIS REGIONAL DIRECTOR OF SALES

PROCESS & DATA CENTER COOLING. How and Why To Prepare For What s To Come JOHN MORRIS REGIONAL DIRECTOR OF SALES PROCESS & DATA CENTER COOLING How and Why To Prepare For What s To Come JOHN MORRIS REGIONAL DIRECTOR OF SALES CONGRATULATIONS 2 BOLD PREDICTION 3 Where We Are TODAY Computer Technology NOW advances more

More information

LIFE CYCLE COST ANALYSIS, CRITERIA AND DATA SHEETS DOCUMENT NUMBER: APPLICATION: ELEMENTARY, MIDDLE AND HIGH SCHOOL

LIFE CYCLE COST ANALYSIS, CRITERIA AND DATA SHEETS DOCUMENT NUMBER: APPLICATION: ELEMENTARY, MIDDLE AND HIGH SCHOOL LIFE CYCLE COST ANALYSIS, CRITERIA AND DATA SHEETS DOCUMENT NUMBER: 15000 APPLICATION: ELEMENTARY, MIDDLE AND HIGH SCHOOL DATE OF ISSUE: 10-26-11 - Minor revisions to Data Sheets 04-08-10 - Allowed use

More information

DATA CENTER LIQUID COOLING

DATA CENTER LIQUID COOLING DATA CENTER LIQUID COOLING EFFICIENT, EFFECTIVE, SUSTAINABLE What is Liquid Cooling? Key Trends & Potential Inhibitors Why are Many Owner/Operators Making the Move? Types of Liquid Cooling Solutions Liquid

More information

Existing Building Energy Saving

Existing Building Energy Saving Existing Building Energy Saving Ir Cary Chan Executive Director, HK Green Building Council Aviation industry 1981 1971 1969 1930s 1903 2 3 4 5 6 7 A big gap to fill Convincing responses to your boss! Deliver!

More information

ATS22D17Q soft starter-ats22-control 220V-power 230V(4kW)/ V(7.5kW)

ATS22D17Q soft starter-ats22-control 220V-power 230V(4kW)/ V(7.5kW) Characteristics soft starter-ats22-control 220V-power 230V(4kW)/400...440V(7.5kW) Main Range of product Altistart 22 Product or component type Product destination Product specific application Component

More information

Optimizing Cooling Performance Of a Data Center

Optimizing Cooling Performance Of a Data Center ASHRAE www.ashrae.org. Used with permission from ASHRAE Journal. This article may not be copied nor distributed in either paper or digital form without ASHRAE s permission. For more information about ASHRAE,

More information

Data Center Precision Cooling: The Need For A Higher Level Of Service Expertise. A White Paper from the Experts in Business-Critical Continuity

Data Center Precision Cooling: The Need For A Higher Level Of Service Expertise. A White Paper from the Experts in Business-Critical Continuity Data Center Precision Cooling: The Need For A Higher Level Of Service Expertise A White Paper from the Experts in Business-Critical Continuity Executive Summary Today s data centers are changing rapidly,

More information

Schneider Electric Cooling Portfolio. Jim Tubbesing Heath Wilson APC/Schneider North Texas Rep Tubbesing Solutions

Schneider Electric Cooling Portfolio. Jim Tubbesing Heath Wilson APC/Schneider North Texas Rep Tubbesing Solutions Schneider Electric Cooling Portfolio Jim Tubbesing Heath Wilson APC/Schneider North Texas Rep Tubbesing Solutions Data Center Cooling Agenda 1. How to size data center, server rooms, IDF rooms, etc in

More information

Server Room & Data Centre Energy Efficiency. Technology Paper 003

Server Room & Data Centre Energy Efficiency. Technology Paper 003 Technology Paper 003 Server Room & Data Centre Energy Efficiency Workspace Technology Limited Technology House, PO BOX 11578, Sutton Coldfield West Midlands B72 1ZB Telephone: 0121 354 4894 Facsimile:

More information

Application Manual. Shark. Software for the simulation of refrigeration equipment and air conditioners

Application Manual. Shark. Software for the simulation of refrigeration equipment and air conditioners Page 1 of 184 Software for the simulation of refrigeration equipment and air conditioners Index Software for the simulation of refrigeration equipment and air conditioners... 1 : application description

More information

Critical Facilities Existing Building Commissioning (EBCx)

Critical Facilities Existing Building Commissioning (EBCx) Critical Facilities Existing Building Commissioning (EBCx) Tony DiLeonardo LEED AP, CxA President Wick Fisher White Tracey Jumper CCP President Jump Start Building Commissioning, LLC AIA Quality Assurance

More information

CL20 Rear Cooler. New Generation Computer Room Cooling

CL20 Rear Cooler.  New Generation Computer Room Cooling CL20 Rear Cooler New Generation Computer Room Cooling A New Approach ColdLogik Rear Coolers, produced by USystems, replace the traditional approach to data centre cooling, allowing loads of up to 58 kw

More information