Chilled Water Distribution Design Considerations in Super Tall Buildings. Dusan Mrdalj, Associate, ChapmanBDSP
|
|
- Derick Moody
- 5 years ago
- Views:
Transcription
1 Chilled Water Distribution Design Considerations in Super Tall Buildings Dusan Mrdalj, Associate, ChapmanBDSP
2 Dusan Mrdalj Bio - MSc Mechanical Engineering - Associate in ChapmanBDSP - 20 years of Professional Experience - 12 Years in the UAE - Involved with design of iconic supertall buildings (WTC AD, OT Dubai )
3 SUPERTALL BUILDINGS AC DESIGN CONSTRAINTS - Building Height vs System Pressure Limitations - Comfort Conditions - Plantroom Space & Access
4 BUILDING HEIGHT
5 HYDROSTATIC PRESSURE IN WATER COLUMN where p = ρ g h p = pressure in liquid (N/m 2, Pa, lb f /ft 2, psf) ρ = density of liquid (kg/m 3, lb/ft 3 ) g = acceleration of gravity (9.81 m/s 2, ft/s 2 ) h = height of fluid column (m, ft)
6 COMFORT CONDITIONS - Temperature - Air Distribution - Stack Effect
7 PLANTROOM SPACE & ACCESS
8 COOLING ENERGY GENERATION Chillers Types (Condensers) Air Cooled Water Cooled
9 CHILLED WATER PRESSURE BREAK CONCEPT Plate Heat Exchanger p3 p2 p1
10 CHILLED WATER TEMP. AT TOB Counter flow Co-current flow Plate HEX Δt 1 C
11 TYPCIAL FCU SELECTION SHEETS
12 FCU CAPACITY VS CHW SUPPLY TEMPERATURE FCU COOLING CAPACITY IN RELATION TO CHW SUPPLY TEMPERATURE FCU Total Capacity (kw) FCU Sensible Capacity (kw) FCU Latent Capacity (kw) Assumed Conditions Standard FCU size 12 at medium speed CHW Delta T: 7 C On-coil DB/WB: 22.5/17 C FCU LATENT CAPACITY IN RELATION TO CHW SUPPLY TEMPERATURE FCU Latent Capacity (kw)
13 FCU CAPACITY VS CHW SUPPLY TEMPERATURE FCU COOLING CAPACITY IN RELATION TO CHW SUPPLY TEMPERATURE FCU Total Capacity (kw) FCU Sensible Capacity (kw) FCU Latent Capacity (kw) Assumed Conditions District Cooling FCU size 12 at medium speed CHW Delta T: 9 C On-coil DB/WB: 22.5/17 C FCU LATENT CAPACITY IN RELATION TO CHW SUPPLY TEMPERATURE FCU Latent Capacity (kw)
14 FCU CAPACITY VS CHW SUPPLY TEMPERATURE FCU COOLING CAPACITY IN RELATION TO CHW SUPPLY TEMPERATURE FCU Total Capacity (kw) FCU Sensible Capacity (kw) FCU Latent Capacity (kw) Assumed Conditions District Cooling FCU size 12 at medium speed CHW Delta T: 9 C On-coil DB/WB: 25/18.7 C FCU LATENT CAPACITY IN RELATION TO CHW SUPPLY TEMPERATURE FCU Latent Capacity (kw)
15 DISTRIBUTION PIPEWORK HEAT GAINS
16 HOW TO RESOLVE 1. CHILLERS AT HIGH ELEVATION 2. LOW TEMPERATURE CHILLERS AT BASE 3. HYBRID SOLUTION
17 CHILLERS AT HIGH ELEVATION PROS CHW generation closer to demand - less distribution losses CHW temperature not affected by pressure breaks Lower temperature CHW easily achieved No requirement for low temperature/glycol chillers Less space for primary services CONS Large plantroom required in premium space up in the building Pressure breaks required in condenser water circuit Special access arrangements for chillers installation & replacement More power needed to be transmitted up the building Noise and vibration issues more severe
18 CHILLERS AT BUILDING BASE PROS Removes need for large plantroom up in the building and associated access Less power up the building required Noise and vibration less of an issue No pressure breaks in condensing circuit required CONS CHW generation farther from demand - more distribution losses Pressure breaks required in CHW circuit Chillers required to operate at low temperature/glycol chillers More space for primary services
19 HYBRID SOLUTIONS Small chillers installed up in the building Designed as a back-up to deal only with critical cooling load (FLS or Server rooms) Can be used to achieve desired CHW supply temperature in case of high fluctuation in cooling load Smaller units in modular arrangement recommended
20 DISTRICT COOLING UTILIZATION
21 STANDARD CHILLERS EFFICIENCY - Air Cooled Chillers - Water Cooled Chillers with Cooling Towers - Water Cooled Chillers with District Cooling - Water Cooled Chillers with Glycol
22 CHILLERS EFFICIENCY SELECTION OPTIONS Option 1 Option 2 Option 3 Option 4 Type: Air Cooled Type: Water Cooled Type: Water Cooled Type: Water Cooled Capacity: 500 TR Capacity: 500 TR Capacity: 500 TR Capacity: 500 TR OA DB: 46 C CW in/out: 35/40 C CW in/out: 12/17 C CW in/out: 12/17 C CHW: 5/14 C CHW: 5/14 C CHW: 5/14 C Glycol: 2/11 C
23 CHILLERS EFFICIENCY SELECTION 1
24 CHILLERS EFFICIENCY SELECTION 2
25 CHILLERS EFFICIENCY SELECTION 3
26 CHILLERS EFFICIENCY SELECTION 4
27 CHILLERS EFFICIENCY COMPARISON Peak Power (kw) Option 1 Option 2 Option 3 Option Option 1 Option 2 Option 3 Option 4
28 CHILLERS EFFICIENCY COMPARISON COP Option 1 Option 2 Option 3 Option Option 1 Option 2 Option 3 Option 4
29 QUESTIONS
7 Best Practices for Increasing Efficiency, Availability and Capacity. XXXX XXXXXXXX Liebert North America
7 Best Practices for Increasing Efficiency, Availability and Capacity XXXX XXXXXXXX Liebert North America Emerson Network Power: The global leader in enabling Business-Critical Continuity Automatic Transfer
More informationMission Critical Facilities & Technology Conference November 3, 2011 Cooling 101. Nick Gangemi Regional Sales Manager Data Aire
Mission Critical Facilities & Technology Conference November 3, 2011 Cooling 101 Nick Gangemi Regional Sales Manager Data Aire Agenda Exactly what are we talking about ASHRAE TC 9.9 Design best practices
More informationCHILLED WATER. HIGH PRECISION AIR CONDITIONERS, FROM 7 TO 211 kw
IT COOLING CLOSE CONTROL AIR CONDITIONERS CHILLED WATER HIGH PRECISION AIR CONDITIONERS, FROM 7 TO 211 kw 3 Versions available Single chilled water coil Double chilled water coil High temperature IT COOLING
More informationPassive RDHx as a Cost Effective Alternative to CRAH Air Cooling. Jeremiah Stikeleather Applications Engineer
Passive RDHx as a Cost Effective Alternative to CRAH Air Cooling Jeremiah Stikeleather Applications Engineer Passive RDHx as a Cost Effective Alternative to CRAH Air Cooling While CRAH cooling has been
More informationFuture of Cooling High Density Equipment. Steve Madara Vice President and General Manager Liebert Precision Cooling Business Emerson Network Power
Future of Cooling High Density Equipment Steve Madara Vice President and General Manager Liebert Precision Cooling Business Emerson Network Power Agenda Issues facing the Data Center Managing the explosive
More informationCooling. Highly efficient cooling products for any IT application. For More Information: (866) DATA CENTER SOLUTIONS
Cooling > Highly efficient cooling products for any IT application. DATA CENTER SOLUTIONS For More Information: (866) 787-3271 Sales@PTSdcs.com End-to-End Cooling Solutions from the Closet to the Data
More informationEfficiency of Data Center cooling
Efficiency of Data Center cooling Comparison of data room layouts and cooling systems Bohumil Cimbal Product manager for Cooling Systems in CONTEG Company Objective Basic questions between investor and
More informationWhat s New for Data Centers in Title Jeff Stein, PE Taylor Engineering
What s New for Data Centers in Title 24-2013 Jeff Stein, PE Taylor Engineering SVLG Workshop November 14, 2013 About Jeff Stein Principal, Taylor Engineering 2000 - now Professional Experience Eley Associates,
More informationChiller Replacement and System Strategy. Colin Berry Account Manager
Chiller Replacement and System Strategy Colin Berry Account Manager Current Situation 4 Existing RTAA chillers All units 23 years old Limited service history One unit MUST be replaced immediately One unit
More informationMSYS 4480 AC Systems Winter 2015
MSYS 4480 AC Systems Winter 2015 Module 12: DATA CENTERS By Satwinder Singh 14/05/2015 1 Data Centers Data Centers are specialized environments that safeguard your company's most valuable equipment and
More informationDigital Realty Data Center Solutions Digital Chicago Datacampus Franklin Park, Illinois Owner: Digital Realty Trust Engineer of Record: ESD Architect
Digital Realty Data Center Solutions Digital Chicago Datacampus Franklin Park, Illinois Owner: Digital Realty Trust Engineer of Record: ESD Architect of Record: SPARCH Project Overview The project is located
More informationAPC APPLICATION NOTE #126
#16 Selection Procedure for Inow Chilled Water Products By Greg Uhrhan, P.E. and Scott Buell Abstract Proper selection of Inow chilled water cooling systems requires an engineer or technical salesperson
More informationIT Air Conditioning Units
IT Air Conditioning Units Modern Flexible Effective Energy Saving CoolTeg Plus and CoolTop overview CoolTeg Plus CW CoolTeg Plus DX CoolTeg Plus XC CoolTop Installation Between IT racks On top of IT rack
More informationHIGH DENSITY RACK COOLING CHOICES
WATERCOOLED HIGH PERFORMANCE COMPUTING SYSTEMS AQUILA WHITE PAPER HIGH DENSITY RACK COOLING CHOICES by Phil Hughes Reprinted with permission of Clustered Systems Company, Inc 1 THIS WHITE PAPER DISCUSSES
More informationMPC Air-Cooled Chillers MPC-FC Free-Cooling Chillers
INNOVATE DESIGN APPLY www.motivaircorp.com MPC Air-Cooled Chillers MPC-FC Free-Cooling Chillers ½ - 100 Tons OUR BUSINESS IS COOLING YOURS. When commercial grade isn t enough Motivair is a world-class
More informationAquaflair. Uniflair TRAC, TRAF and TRAH. Air-cooled chillers, free-cooling chillers and heat pumps with scroll compressors.
Aquaflair Uniflair TRAC, TRAF and TRAH Air-cooled chillers, free-cooling chillers and heat pumps with scroll compressors 120-350kW Uniflair TRA ranges 115-350kW Air-cooled Chillers Cooling, Free cooling
More informationRack cooling solutions for high density racks management, from 10 to 75 kw
Rack cooling solutions for high density racks management, from 10 to 75 Superior efficiency, high reliability, low energy consumption Modern data center are characterized by 24/7 operation all year long.
More informationPT CLIMANUSA TATA MEKADATA Citypark Business District Blok F No 05 Jl. Malibu Raya, Cengkareng Jakarta Barat Indonesia. Phone
PT CLIMANUSA TATA MEKADATA Citypark Business District Blok F No 0 Jl. Malibu Raya, Cengkareng Jakarta Barat 70 Indonesia Phone + 4 4 www.climanusa.com Marketing features prominent presence on the world
More informationNext Generation DCP Optimization using MV VSDs
Next Generation DCP Optimization using MV VSDs Vivek Apte Regional Product Director Johnson Controls - Middle East Cell : +971506243059 IDEA 2016- Dubai 1 Central Plant Optimization Energy and operating
More informationMOLLIER DIAGRAM CAN BE IMPROVED!
MOLLIER DIAGRAM CAN BE IMPROVED! IMPROVED BASIC COOLING CIRCUIT PERFORMANCE EFFICIENCY USING AN ECONOMISER Eng. Jonny Malachi, VP Operations, Mashav Refrigeration and Air Conditioning Engineering Ltd.
More informationTWO FINANCIAL IMPACT STUDIES. Seal IT Equipment Cabinets for Significant Annual Cost Savings and Simple Payback in a Few Short Months
TWO FINANCIAL IMPACT STUDIES Seal IT Equipment Cabinets for Significant Annual Cost Savings and Simple Payback in a Few Short Months TWO FINANCIAL IMPACT STUDIES Seal IT Equipment Cabinets for Significant
More informationDATA CENTER EFFICIENCY: Data Center Temperature Set-point Impact on Cooling Efficiency
DATA CENTER EFFICIENCY: Data Center Temperature Set-point Impact on Cooling Efficiency September 27 th, 2013 Tejas Desai, PE CEM CEA LEED AP Sameer Behere, PE CEM LEED AP Agenda Problem: Quick fixes can
More informationA Data Center Heat Removal System That Saves... 80% Discover Inertech s Award-winning Data Center Heat Removal System
A Data Center Heat Removal System That Saves... Infrastructure Power Water up to 40% up to 80% up to 85% Discover Inertech s Award-winning Data Center Heat Removal System A Cool Solution; A Breakthrough
More informationIntroducing the Heat Wheel to the Data Center
Introducing the Heat Wheel to the Data Center Robert (Dr. Bob) Sullivan, Ph.D. Data Center Infrastructure Specialist KyotoCooling International Critical Facilities Round Table 1 A New Free Cooling Technique
More informationIBM Symposium Data Center Cooling. EC Systems for HVAC architecture and Direct air Cabinet Cooling
IBM Symposium 2008 Data Center Cooling EC Systems for HVAC architecture and Direct air Cabinet Cooling Presented by David J. Spofford Product Manager IT/Telecomm 1 Agenda Data Center trends for IT and
More informationInRow Chilled Water. Up to 70kW. Close-coupled, chilled water cooling for medium to large data centers. Row-Based Cooling.
InRow Chilled Water Close-coupled, chilled water cooling for medium to large data centers Up to 0kW > Row-Based Cooling The InRow Chilled Water product design closely couples the cooling with the IT heat
More informationLiebert DCW CATALOGUE
Liebert DCW CATALOGUE Chilled Water-Based High Density Cooling For The Data Center LIEBERT DCW Flexible Approaches For Energy Efficient Cooling Save up to 70% in cooling energy usage Data center managers
More informationVariable Density, Closed-Loop, Water-Cooled Data Center Solution
Variable Density, Closed-Loop, Water-Cooled Data Center Solution Overview Great Lakes Case & Cabinet Co., Inc. has worked with Naissus Thermal Management Solutions, of Toronto, Ontario to develop one of
More informationSystem Overview. Liquid Cooling for Data Centers. Negative Pressure Cooling Without Risk of Leaks
Liquid Cooling for Data Centers System Overview The Chilldyne Cool-Flo System is a direct-to-chip liquid cooling system that delivers coolant under negative pressure. Chilldyne s technologies were designed
More informationPrecision Cooling. Precision Cooling Advantages
Precision Cooling Today s computing technologies compound conventional cooling problems. Blade servers, communications switches and other electronics are being packed into tighter and tighter spaces. Computing
More informationChiller Plant Optimization: A Case Study
Presentation of Chiller Plant Optimization: A Case Study Presented by Michael S. Conway The site Large pharmaceutical client 5 MW cogen 88,000 PPH of boiler capability 8,200 tons of chiller capability
More informationFPS SERIES Super Slim Ceiling Mount Air Handling Units
About Multistack 19, Multistack is well-known in the international air conditioning industry by its invention of modular chiller. Today, Multistack has grown into an international refrigeration & air conditioning
More informationglide glider kw R134a air cooled liquid chillers AND free cooling chillers FREE COOLING SHELL A C CLASS E C Energy Class RCGROUP SpA
99 glide air cooled liquid chillers ND free cooling chillers glider 178 1328 Energy Class More efficient + B C D E F G Less efficient R134a CLSS SHELL C E C FREE COOLING 100 air cooled liquid chiller and
More informationDesigning Ultra-Efficient Building Cooling Systems
Designing Ultra-Efficient Building Cooling Systems Design to Apply Effective Optimization Technologies To Chiller Plants and Air Systems ASHRAE Triangle Chapter Raleigh, NC November 16, 2016 Tom Hartman,
More informationRittal Cooling Solutions A. Tropp
1 Rittal Cooling Solutions Presented by Adam Tropp 2 Agenda Cooling Strategies Aisle Containment Chimney Solution Airstream Management Rittal Liquid Cooling Packages Data Monitoring 3 Cooling strategies.
More informationLCP Hybrid Efficient performance with heat pipe technology
LCP Hybrid Efficient performance with heat pipe technology 2 LCP Hybrid The whole is more than the sum of its parts The same is true of "Rittal The System." With this in mind, we have bundled our innovative
More informationSUPERSAVER. Energy Efficiency Optimization Software for Freecooling Systems
SUPERSAVER Energy Efficiency Optimization Software for Freecooling Systems SUPERSAVER Supersaver Delivers Enhanced Freecooling Efficiency via Integrated Vertiv ICOM Communication Supersaver is the Vertiv
More informationCase study: Energy efficiency improvements in a legacy data centre. Robert Tozer Director Opera>onal Intelligence
Case study: Energy efficiency improvements in a legacy data centre Robert Tozer Director Opera>onal Intelligence Objec>ves First improve air management Air supply temperature to servers Lower temperature
More informationHVAC System Energy Savings Opportunities
HVAC System Energy Savings Opportunities Speaker Info M. Lant DuBose Energy Services ConEdison Solutions dubosem@conedsolutions.com (813)285-6340 Wholly owned subsidiary of ConEdison since 2007 Entered
More informationWelcome Association of Energy Engineers to the Microsoft Technology Center
Welcome Association of Energy Engineers to the Microsoft Technology Center Today s Agenda 10:00 10:30 What s new in data center energy efficiency planning and implementation? 10:30 11:00 ASHRAE data center
More informationClose-coupled cooling
Close-coupled cooling Intelligently controlled high-performance InRow cooling for the IT environment APC TM by Schneider Electric close-coupled cooling products provide a modular, scalable, and predictable
More informationSaving Water and Operating Costs at NREL s HPC Data Center
Saving Water and Operating Costs at NREL s HPC Data Center Thomas P. Carter, P.E. Johnson Controls Thomas.P.Carter@jci.com David Sickinger National Renewable Energy Laboratory David.Sickinger@nrel.gov
More informationProduct Brochure DENCO Close Control Units Row-DENCO. High Density Cooling for Data Centres
Product Brochure DENCO Close Control Units Row-DENCO High Density Cooling for Data Centres Data Centre Cooling Through a history in close control, we have developed a broad and deep understanding of how
More informationGP SERIES Packaged Chillers
Blending Conveying Drying Process Cooling Heat Transfer Size Reduction GP SERIES Packaged Chillers Comprehensive Flexible Versatile Compact unitary designs available in a variety of configurations from
More informationi-accurate_gb_ High precision air-conditioners for data centres cooling, with new inverter technology and R-410A refrigerant, from 6 to 150 kw
i-accurate_gb_07-2011 igh precision air-conditioners for data centres cooling, with new inverter technology and R-410A refrigerant, from 6 to 150 Coming form 40 years experience in air conditioning and
More informationCommunication Register Map - Uniflair Cooling
DIGITAL 0 1 1 - - - - DIGITAL 1 2 2 System On (Fan) 0 or 1 boolean R DIGITAL 2 3 3 Compressor 1 0 or 1 boolean R DIGITAL 3 4 4 Compressor 2 0 or 1 boolean R DIGITAL 4 5 5 Compressor 3 0 or 1 boolean R
More informationAPC InRow Cooler Prototype Initial Report - Test Setup Verification. H. Coles, S. Greenberg Contributing: J. Bean (APC) November 18, 2011
APC InRow Cooler Prototype Initial Report - Test Setup Verification H. Coles, S. Greenberg Contributing: J. Bean (APC) November 18, 2011 1 Introduction Contents Technology Description/Attributes Installation
More informationIT COOLING AIR CONDITIONERS FOR HIGH DENSITY RACKS AND BLADE SERVERS. RACK COOLING SOLUTIONS FOR HIGH DENSITY RACK MANAGEMENT, FROM 4 TO 75 kw
IT COOLING AIR CONDITIONERS FOR HIGH DENSITY RACKS AND BLADE SERVERS RACK COOLING SOLUTIONS FOR HIGH DENSITY RACK MANAGEMENT, FROM 4 TO 75 kw IT COOLING AIR CONDITIONERS FOR HIGH DENSITY RACKS AND BLADE
More informationLiebert. AFC from 500 to 1700 kw. The Adiabatic Freecooling Solution with Top-Tier Availability
Liebert AFC from 500 to 1700 kw The Adiabatic Freecooling Solution with Top-Tier Availability Liebert AFC from 500 to 1700 kw Vertiv Vertiv designs, builds and services mission critical technologies that
More informationInternational 6SigmaDC User Conference CFD Modeling for Lab Energy Savings DCSTG Lab Temperature Setpoint Increase
International 6SigmaDC User Conference CFD Modeling for Lab Energy Savings DCSTG Lab Temperature Setpoint Increase Chris Noland cnoland@cisco.com Vipha Kanakakorn vkanakak@cisco.com 3/4/2010 Goal & Limitations
More informationpco 3 Controller User Manual ASPX Digital Scroll, Air Packaged Chiller For Version MCDSV_A02
pco 3 Controller User Manual ASPX Digital Scroll, Air Packaged Chiller For Version MCDSV_A02 pco 3 Controller User Manual Introduction The Airstack Chiller is a modular air-cooled chiller composed of
More informationOptimizing Chilled Water Plant Performance. David Herman, PE, LEED AP Principal EnerG Associates, LLC
Optimizing Chilled Water Plant Performance David Herman, PE, LEED AP Principal EnerG Associates, LLC Optimizing Chilled Water Plant Learning Objectives Performance Review the design and operating characteristics
More informationHIGH EFFICIENCY Central Chiller
Blending Conveying Drying Process Cooling Heat Transfer Size Reduction HIGH EFFICIENCY Central Chiller Energy Efficient Modular & Expandable Virtually Eliminate Downtime Available in 20-60 ton single units,
More informationHow To Draw Chiller Monsters Werewolves Vampires And Zombies
How To Draw Chiller Monsters Werewolves Vampires And Zombies We have made it easy for you to find a PDF Ebooks without any digging. And by having access to our ebooks online or by storing it on your computer,
More informationMCFCW-20-4HS-1 (4-Pipe) High Static Chilled/Hot Water Ceiling Concealed Cased Fan Coil 208/230V 4-Pipe Heating & Cooling Fan Coil 60,000 BTUH
MCFCW-20-4HS-1 (4-Pipe) High Static Chilled/Hot Water Ceiling Concealed Cased Fan Coil 208/230V 4-Pipe Heating & Cooling Fan Coil 60,000 BTUH 1 Chilled and Hot Water Fan Coil High Static 4-Pipe Nominal
More informationMCFCW-08-4LS-1 (4-Pipe) Low Static Chilled/Hot Water Ceiling Concealed Cased Fan Coil 208/230V 4-Pipe Heating & Cooling Fan Coil 24,000 BTUH
MCFCW-08-4LS-1 (4-Pipe) Low Static Chilled/Hot Water Ceiling Concealed Cased Fan Coil 208/230V 4-Pipe Heating & Cooling Fan Coil 24,000 BTUH 1 Chilled and Hot Water Fan Coil Low Static 4-Pipe Nominal Size:
More informationMotivair MLC-SC Air-Cooled Scroll Chillers Tons
INNOVATE DESIGN APPLY www.motivaircorp.com Motivair MLC-SC Air-Cooled Scroll Chillers 100 285 Tons OUR BUSINESS IS COOLING YOURS. When commercial grade isn t enough Businesses who function in today s advanced
More informationMCFCW-06-4HS-1 (4-Pipe) High Static Chilled/Hot Water Ceiling Concealed Cased Fan Coil 208/230V 4-Pipe Heating & Cooling Fan Coil 18,000 BTUH
MCFCW-06-4HS-1 (4-Pipe) High Static Chilled/Hot Water Ceiling Concealed Cased Fan Coil 208/230V 4-Pipe Heating & Cooling Fan Coil 18,000 BTUH 1 Chilled and Hot Water Fan Coil High Static 4-Pipe Nominal
More informationSorensen SG Series - Water Cooled kw V A. Programmable Precision High Power DC Power Supply
Sorensen SG Series - Water Cooled Programmable Precision High Power DC Power Supply High Power Density: up to 15 kw in 3U Wide Voltage Range: 0-40 V and 0-60 V, in increments of 5 kw from 5 to 15 kw Fast
More informationHybrid Warm Water Direct Cooling Solution Implementation in CS300-LC
Hybrid Warm Water Direct Cooling Solution Implementation in CS300-LC Roger Smith Mississippi State University Giridhar Chukkapalli Cray, Inc. C O M P U T E S T O R E A N A L Y Z E 1 Safe Harbor Statement
More information2018 Product overview
2018 Product overview Project conditioning Evolution goes on During these years, the activity of EMICON has been developed with the production of liquid chillers for conditioning and industrial applications,
More informationRetro-Commissioning Report
10 Retro-Commissioning Report Retro-Commissioning Retro-Commissioning is the process for identifying intrinsic operational and energy related issues in the facilities DDC system and providing a mechanism
More informationCoordinating Liquid and Free Air Cooling with Workload Allocation for Data Center Power Minimization
Coordinating Liquid and Free Air Cooling with Workload Allocation for Data Center Power Minimization Li Li, Wenli Zheng, Xiaodong Wang, and Xiaorui Wang Dept. of Electrical and Computer Engineering The
More informationCTC Low Temperature Process Chillers
INNOVATE DESIGN APPLY CTC Low Temperature Process Chillers 5-500 Tons OUR BUSINESS IS COOLING YOURS TM When commercial grade isn t enough When it comes to process cooling, every application is unique in
More informationLarge Tonnage Chillers. Kingsley Hu Technical Support Engineer
Large Tonnage Chillers Kingsley Hu Technical Support Engineer Chongqing Plant Chiller Products Reference Projects Manufacturing Facility Major Milestones Global R&D Talent Production Line introduction
More informationNext Generation Cooling
Next Generation Cooling Server Manufacturer Perspective Practical and Cost Effective David Moss Data Center Strategist Dell 1 Why Chip, Row, or Rack? Density? Energy Don t be scared; I don t see 50kW/rack
More informationMID approval no. DE-08-MI004-PTB004 Date of release
1. Identification Energy and Flow Computer Flow rate and energy calculator for liquids, gases and water steam E-DB-1000-700-01 MID approval no. DE-08-MI004-PTB004 Date of release 04.01.08 2. Area of Application
More informationHot vs Cold Energy Efficient Data Centers. - SVLG Data Center Center Efficiency Summit
Hot vs Cold Energy Efficient Data Centers - SVLG Data Center Center Efficiency Summit KC Mares November 2014 The Great Debate about Hardware Inlet Temperature Feb 2003: RMI report on high-performance data
More informationLiebert DCW Family Chilled Water-Based High Density Cooling For The Data Center. Precision Cooling For Business-Critical Continuity
Liebert DCW Family Chilled Water-Based High Density Cooling For The Data Center Precision Cooling For Business-Critical Continuity Flexible Approaches For Energy Efficient Cooling Save up to 70% in cooling
More informationTier IV Standards as Specified in the TIA 942 Document
S No Architectural Proximity of visitor parking to data 18.3 m / 60 ft minimum separation with physical barriers to prevent vehicles from 1 center perimeter building walls driving closer 2 Building Construction
More informationLiebert. HPC-S Free Cooling Chiller Designed for the Efficient Cooling of Small Data Centers
Liebert HPC-S Free Cooling Chiller Designed for the Efficient Cooling of Small Data Centers Liebert HPC-S FREE COOLING CHILLER Getting To A PUE Of 1.2 Free cooling data center chillers are designed to
More informationHPC/Advanced Cooling Track. Rolf Brink/CEO/Asperitas
HPC/Advanced Cooling Track Advanced Cooling Optimising for immersion Rolf Brink/CEO/Asperitas Rolf.Brink@ocproject.net +31 88 96 000 00 www.asperitas.com IMMERSED COMPUTING : AIC24 100% Removal of heat
More informationFinal Thesis Presentation
Final Thesis Presentation Spring 2011 Advisor: Dr. Treado Building Overview Existing Conditions System Evaluation Building Overview Existing Conditions System Evaluation Building Overview Existing Conditions
More informationEnergy Logic: Emerson Network Power. A Roadmap for Reducing Energy Consumption in the Data Center. Ross Hammond Managing Director
Energy Logic: A Roadmap for Reducing Energy Consumption in the Data Center Emerson Network Power Ross Hammond Managing Director Agenda Energy efficiency Where We Are Today What Data Center Managers Are
More informationHP Modular Cooling System: water cooling technology for high-density server installations
HP Modular Cooling System: water cooling technology for high-density server installations technical brief Abstract... 2 Introduction... 2 Data center trends... 2 Increased power demands... 3 Increased
More informationLANL High Performance Computing Facilities Operations. Rick Rivera and Farhad Banisadr. Facility Data Center Management
Slide-1 LANL High Performance Computing Facilities Operations Rick Rivera and Farhad Banisadr Facility Data Center Management Division Slide-2 Outline Overview - LANL Computer Data Centers Power and Cooling
More informationTotal Modular Data Centre Solutions
Sector Data Centre Total Modular Data Centre Solutions www.airedale.com BRITISH MANUFACTURER ENERGY EFFICIENCY CONTROLS SERVICE TRAINING 01 Standardised Modular Designs to fit your needs Our modular system
More informationIN-DEPTH UNDERSTANDING OF HVAC EQUIPMENT & SYSTEM SPECIFICATIONS AND PERFORMANCE 11 & 12 JULY 2016 WISMA IEM
IEM TRAINING CENTRE SDN. BHD. (127273-K) No. 33-1A (1 st Floor), Jalan 52/18, P.O. Box 224 (Jalan Sultan P.O.) 46720 Petaling Jaya, Selangor Darul Ehsan (GST ID No. 001525395456) Telephone No. 03-79586851
More informationPlanning for Liquid Cooling Patrick McGinn Product Manager, Rack DCLC
Planning for Liquid Cooling -------------------------------- Patrick McGinn Product Manager, Rack DCLC February 3 rd, 2015 Expertise, Innovation & Delivery 13 years in the making with a 1800% growth rate
More information200 kw, Tier 3, Chilled Water, 5250 ft 2
[eference Design 4] 200 kw, Tier 3, Chilled Water, 5250 ft 2 DESIGN OVEVIEW Data Center IT Capacity 200 kw Adaptable from 50 kw to 600 kw Target Availability Tier 3 Annualized UE at 100% Load 1.67 in Miami,
More informationHow Green can you go?
ASHRAE 90.1 2010 It s out..and should be our code in 3 years Work on sealing and testing building envelope, commissioning Cool Roofs..hey were already doing that Extensive Controls enhancements Equipment
More informationLiquid Cooling Package LCP Cooling Systems
Liquid Cooling Package LCP Cooling Systems 2 Rittal LCP The whole is more than the sum of its parts. The same is true of Rittal The System. With this in mind, we have bundled our innovative enclosure,
More informationImpact of Air Containment Systems
White Paper June 2012 WP-20 Impact of Air Containment Systems Reducing Energy Consumption Introduction: The Importance of Maintaining Data Center Cooling Energy Efficiency Data centers are mission-critical
More informationDATA CENTER PRECISION COOLING: The Need For A Higher Level Of Service Expertise
DATA CENTER PRECISION COOLING: The Need For A Higher Level Of Service Expertise TWO STAGE POWER DISTRIBUTION Executive Summary Today s data centers are changing rapidly, and it is more important than ever
More informationLiebert Economizer Cooling Solutions Reduce Cooling Costs by up to 50% Without Compromising Reliability
Precision Cooling for Business-Critical Continuity TM Liebert Economizer Cooling Solutions Reduce Cooling Costs by up to 50% Without Compromising Reliability DATA CENTER SOLUTIONS For More Information:
More informationPerformance Evaluation for Modular, Scalable Cooling Systems with Hot Aisle Containment in Data Centers. Final Report
Performance Evaluation for Modular, Scalable Cooling Systems with Hot Aisle Containment in Data Centers Final Report To The California Energy Commission May 2009 Tengfang Xu Environmental Energy Technologies
More informationPerformance Certification : From Energy Efficiency To Indoor Air Quality. By: Eric Foucherot
Performance Certification : From Energy Efficiency To Indoor Air Quality By: Eric Foucherot Certified Products for Efficient & Safe Design Certified Performances for HVAC&R Product AIR CONDITIONERS CHILLERS
More informationThe Basics of HVAC Operation and the Role of Automation. Mr. Jay Zaino GxP Automation, LLC
Welcome The Basics of HVAC Operation and the Role of Automation Mr. Jay Zaino GxP Automation, LLC Agenda Introduction / Overview HVAC Basics HVAC in Life Science Market Automation s role in it all 1 Introduction
More informationPROCESS & DATA CENTER COOLING. How and Why To Prepare For What s To Come JOHN MORRIS REGIONAL DIRECTOR OF SALES
PROCESS & DATA CENTER COOLING How and Why To Prepare For What s To Come JOHN MORRIS REGIONAL DIRECTOR OF SALES CONGRATULATIONS 2 BOLD PREDICTION 3 Where We Are TODAY Computer Technology NOW advances more
More informationLIFE CYCLE COST ANALYSIS, CRITERIA AND DATA SHEETS DOCUMENT NUMBER: APPLICATION: ELEMENTARY, MIDDLE AND HIGH SCHOOL
LIFE CYCLE COST ANALYSIS, CRITERIA AND DATA SHEETS DOCUMENT NUMBER: 15000 APPLICATION: ELEMENTARY, MIDDLE AND HIGH SCHOOL DATE OF ISSUE: 10-26-11 - Minor revisions to Data Sheets 04-08-10 - Allowed use
More informationDATA CENTER LIQUID COOLING
DATA CENTER LIQUID COOLING EFFICIENT, EFFECTIVE, SUSTAINABLE What is Liquid Cooling? Key Trends & Potential Inhibitors Why are Many Owner/Operators Making the Move? Types of Liquid Cooling Solutions Liquid
More informationExisting Building Energy Saving
Existing Building Energy Saving Ir Cary Chan Executive Director, HK Green Building Council Aviation industry 1981 1971 1969 1930s 1903 2 3 4 5 6 7 A big gap to fill Convincing responses to your boss! Deliver!
More informationATS22D17Q soft starter-ats22-control 220V-power 230V(4kW)/ V(7.5kW)
Characteristics soft starter-ats22-control 220V-power 230V(4kW)/400...440V(7.5kW) Main Range of product Altistart 22 Product or component type Product destination Product specific application Component
More informationOptimizing Cooling Performance Of a Data Center
ASHRAE www.ashrae.org. Used with permission from ASHRAE Journal. This article may not be copied nor distributed in either paper or digital form without ASHRAE s permission. For more information about ASHRAE,
More informationData Center Precision Cooling: The Need For A Higher Level Of Service Expertise. A White Paper from the Experts in Business-Critical Continuity
Data Center Precision Cooling: The Need For A Higher Level Of Service Expertise A White Paper from the Experts in Business-Critical Continuity Executive Summary Today s data centers are changing rapidly,
More informationSchneider Electric Cooling Portfolio. Jim Tubbesing Heath Wilson APC/Schneider North Texas Rep Tubbesing Solutions
Schneider Electric Cooling Portfolio Jim Tubbesing Heath Wilson APC/Schneider North Texas Rep Tubbesing Solutions Data Center Cooling Agenda 1. How to size data center, server rooms, IDF rooms, etc in
More informationServer Room & Data Centre Energy Efficiency. Technology Paper 003
Technology Paper 003 Server Room & Data Centre Energy Efficiency Workspace Technology Limited Technology House, PO BOX 11578, Sutton Coldfield West Midlands B72 1ZB Telephone: 0121 354 4894 Facsimile:
More informationApplication Manual. Shark. Software for the simulation of refrigeration equipment and air conditioners
Page 1 of 184 Software for the simulation of refrigeration equipment and air conditioners Index Software for the simulation of refrigeration equipment and air conditioners... 1 : application description
More informationCritical Facilities Existing Building Commissioning (EBCx)
Critical Facilities Existing Building Commissioning (EBCx) Tony DiLeonardo LEED AP, CxA President Wick Fisher White Tracey Jumper CCP President Jump Start Building Commissioning, LLC AIA Quality Assurance
More informationCL20 Rear Cooler. New Generation Computer Room Cooling
CL20 Rear Cooler New Generation Computer Room Cooling A New Approach ColdLogik Rear Coolers, produced by USystems, replace the traditional approach to data centre cooling, allowing loads of up to 58 kw
More information