5905 Ethernet Gateway Module

Size: px
Start display at page:

Download "5905 Ethernet Gateway Module"

Transcription

1 5905 Ethernet Gateway Module Installation, Operation and Maintenance Setup Manual 5/19/2011

2 Safety Information The information provided in this documentation contains general descriptions and/or technical characteristics of the performance of the products contained herein. This documentation is not intended as a substitute for and is not to be used for determining suitability or reliability of these products for specific user applications. It is the duty of any such user or integrator to perform the appropriate and complete risk analysis, evaluation and testing of the products with respect to the relevant specific application or use thereof. Neither Schneider Electric nor any of its affiliates or subsidiaries shall be responsible or liable for misuse of the information contained herein. If you have any suggestions for improvements or amendments or have found errors in this publication, please notify us. No part of this document may be reproduced in any form or by any means, electronic or mechanical, including photocopying, without express written permission of Schneider Electric. All pertinent state, regional, and local safety regulations must be observed when installing and using this product. For reasons of safety and to help ensure compliance with documented system data, only the manufacturer should perform repairs to components. When devices are used for applications with technical safety requirements, the relevant instructions must be followed. Failure to use Schneider Electric software or approved software with our hardware products may result in injury, harm, or improper operating results. Failure to observe this information can result in injury or equipment damage Schneider Electric. All rights reserved. Document (Version ) 5/19/2011 2

3 Safety Information Table of Contents Safety Information...5 About The Book...8 At a Glance... 8 Overview...9 Installation Field Wiring RS-232 Serial Port RS-485 Port Power Connections Configuration Jumpers LED Indicators Status and Error LEDs Operation Operation Application Examples Network Protocols Configuration Direct Serial Port Setup Connection Telnet Network Connection Setup Configuration Parameters Maintenance Troubleshooting Specifications Appendix A: Forcing a New IP Address Document (Version ) 5/19/2011 3

4 Safety Information Index of Figures Figure1: 5905 Module Layout Figure 2: RS-232 Port Connector (DTE) Figure 3: RS-232 Wiring (DTE) to DTE Figure 4: 5905 RS-485 Terminal Block Connection, P Figure 5: RS-485 Field Wiring Four Wire Mode Figure 6: RS-485 Field Wiring Two Wire Mode Figure 7: 5905 Ethernet RJ-45 Connection Figure 8: Modbus/TCP Access to Modbus RTU Figure 9: Multiple Access to Modbus RTU Figure 10: Modbus/RTU RS-485 Bridging Through Ethernet Figure 11: Modbus/RTU RS-232 Bridging Through Ethernet Document (Version ) 5/19/2011 4

5 Safety Information Safety Information Read these instructions carefully, and look at the equipment to become familiar with the device before trying to install, operate, or maintain it. The following special messages may appear throughout this documentation or on the equipment to warn of potential hazards or to call attention to information that clarifies or simplifies a procedure. The addition of this symbol to a Danger or Warning safety label indicates that an electrical hazard exists, which will result in personal injury if the instructions are not followed. This is the safety alert symbol. It is used to alert you to potential personal injury hazards. Obey all safety messages that follow this symbol to avoid possible injury or death. DANGER DANGER indicates an imminently hazardous situation which, if not avoided, will result in death or serious injury. WARNING WARNING indicates a potentially hazardous situation which, if not avoided, can result in death or serious injury. CAUTION CAUTION indicates a potentially hazardous situation which, if not avoided, can result in minor or moderate. CAUTION CAUTION used without the safety alert symbol, indicates a potentially hazardous situation which, if not avoided, can result in equipment damage.. Document (Version ) 5/19/2011 5

6 PLEASE NOTE Safety Information Electrical equipment should be installed, operated, serviced, and maintained only by qualified personnel. No responsibility is assumed by Schneider Electric for any consequences arising out of the use of this material. A qualified person is one who has skills and knowledge related to the construction and operation of electrical equipment and the installation, and has received safety training to recognize and avoid the hazards involved. BEFORE YOU BEGIN Do not use this product on machinery lacking effective point-of-operation guarding. Lack of effective point-of-operation guarding on a machine can result in serious injury to the operator of that machine. EQUIPMENT OPERATION HAZARD CAUTION Verify that all installation and set up procedures have been completed. Before operational tests are performed, remove all blocks or other temporary holding means used for shipment from all component devices. Remove tools, meters, and debris from equipment. Failure to follow these instructions can result in injury or equipment damage. Follow all start-up tests recommended in the equipment documentation. Store all equipment documentation for future references. Software testing must be done in both simulated and real environments. Verify that the completed system is free from all short circuits and grounds, except those grounds installed according to local regulations (according to the National Electrical Code in the U.S.A, for instance). If high-potential voltage testing is necessary, follow recommendations in equipment documentation to prevent accidental equipment damage. Before energizing equipment: Remove tools, meters, and debris from equipment. Close the equipment enclosure door. Remove ground from incoming power lines. Perform all start-up tests recommended by the manufacturer. OPERATION AND ADJUSTMENTS The following precautions are from the NEMA Standards Publication ICS (English version prevails): Document (Version ) 5/19/2011 6

7 Safety Information Regardless of the care exercised in the design and manufacture of equipment or in the selection and ratings of components, there are hazards that can be encountered if such equipment is improperly operated. It is sometimes possible to misadjust the equipment and thus produce unsatisfactory or unsafe operation. Always use the manufacturer s instructions as a guide for functional adjustments. Personnel who have access to these adjustments should be familiar with the equipment manufacturer s instructions and the machinery used with the electrical equipment. Only those operational adjustments actually required by the operator should be accessible to the operator. Access to other controls should be restricted to prevent unauthorized changes in operating characteristics. Document (Version ) 5/19/2011 7

8 About The Book About The Book At a Glance Document Scope Validity Notes This manual describes the operation and maintenance of the 5905 Ethernet Gateway module. This document is valid for all versions of the 5905 Ethernet Gateway module. Product Related Information WARNING UNINTENDED EQUIPMENT OPERATION The application of this product requires expertise in the design and programming of control systems. Only persons with such expertise should be allowed to program, install, alter and apply this product. Follow all local and national safety codes and standards. Failure to follow these instructions can result in death, serious injury or equipment damage. User Comments We welcome your comments about this document. You can reach us by at technicalsupport@controlmicrosystems.com. Document (Version ) 5/19/2011 8

9 Overview Overview The model 5905 Ethernet gateway converts RS-232/485 Modbus communication into Modbus/TCP on Ethernet. Two packaging versions are available the DINrail mountable Model 5905 which is used with SCADAPack controller; and the 5905SA which is used with personal computers and other RS-232/485 equipment. The model 5905SA is powered using an AC adapter. Applications include in-plant I/O and connectivity between SCADAPack and operator workstations, other PLC devices, and SCADA systems communication, using standard Modbus. The SA version may be used to tie in other devices, which use Modbus, such as PID controllers, Variable Frequency Drives (VFD), and UPS power systems. Support for RS-232 using RTS/CTS handshaking, allows the 5905 to be used as a gateway between Ethernet LAN and commonly used half-duplex SCADA communications media. Examples of devices which often require half-duplex support include the 5902 Bell 202 modem, radio modems, and various other halfduplex modems. The 5905 gateway allows interfacing of multiple or dualredundant host computers that need to be able to communicate to SCADA systems over a single communications channel. Multi-drop communication over RS-485, or half-duplex modems and radios, allows up to 255 Modbus slave devices to be connected to a 5905 Ethernet gateway by configuring the gateways with their IP addresses, and at the master end, define which Modbus slave stations can be found at each 5905 slave gateway. Up to 255 Modbus slaves can be connected to each gateway, and up to 8 TCP/IP connections are supported by each Document (Version ) 5/19/2011 9

10 Installation Installation The 5905 Ethernet Gateway is available in two standard versions, the model 5905 and the model 5905SA. The model 5905 is a standard 5000 module that connects to the system I/O Bus as an integrated part of a Control Microsystems system. The model 5905SA is a stand-alone version of the 5905 and is used with other devices such as personal computers. Both versions of the modem are identical in every respect except that the 5905SA is powered using a 9VDC AC adapter and has rubber feet for desktop mounting. J2 IInstalled for Bus Operation J3 Installed for SA Operation I/O Bus Connector I/O Bus Connector J5 RS485 Rx term J6 RS485 Tx Term J8 RS232: Left RS485: Right J10 2 Wire: Left 4 Wire: Right J115V from P4 pin 9 P6 AC Adaptor P4 Rs232 Connection P3 Ethernet Connection P5 RS485 Connection Figure1: 5905 Module Layout Field Wiring The 5905 module has four connectors for field wiring. Refer to Figure1: 5905 Module Layout for the location of these connectors. The RS-232 serial communication port, labeled P4, is a 9 pin, D-sub-miniature connector, DE-9S, configured as a DTE (Data Terminal Equipment). Refer to section 0-RS-232 Serial Port for more information. Document (Version ) 5/19/

11 RS-232 Serial Port Installation The RS-485 serial communication port, labeled P5, is a 5 position removable terminal block. This terminal block supports 2 or 4 wire RS-485 wiring. Refer to section 0-RS-485 Port for more information. The Ethernet connection is terminated at the RJ-45 modular jack labeled P3. The RJ-45 modular jack pin-out is compatible with standard Ethernet cables. See section 0-Ethernet Connection for more information. The 9VDC AC adapter connection, labeled P6, is used with an AC Adapter available from Control Microsystems. This connection is used with the 5905SA module only. See section SA Power Connection for more information. The RS-232 port is a 9-pin D-sub-miniature connector (DE-9P) configured as Data Terminal Equipment (DTE). Figure 2: RS-232 Port Connector (DTE) and Table 1: RS-232 Connections describe the RS-232 connector. 1 NC 2 RxD 3 TxD 4 NC 5 GND 6 NC 7 RTS 8 CTS 9 NC Figure 2: RS-232 Port Connector (DTE) A description of each pin signal is shown in Table 1: RS-232 Connections. In this table a MARK is a voltage of +3 volts or greater and a SPACE is a voltage of 3 volts or less. Table 1: RS-232 Connections Pin Type Description Pin1 NC No connection Pin 2 RxD Input Data transmitted by the Ethernet LAN is input on this pin. The level is SPACE on standby and MARK for transmitted data. The RX LED is on for a MARK level. Pin 3 TxD Output Data received from the Ethernet LAN is output on this pin. The level is SPACE on standby and MARK for received data. The Tx LED is on for a MARK level. Pin 4 NC No connection. Pin 5 This pin is connected to the I/O system ground. Ground Pin 6 NC No connection. Document (Version ) 5/19/

12 Installation Pin Type Description Pin 7 RTS Pin 8 CTS 5905 Connection to DTE Output Input This pin is a MARK if full-duplex operation is selected for the port. This pin is set to a MARK just before and during transmission of data if half-duplex operation is selected. This pin is set to a SPACE when no data is being transmitted. A MARK level is required for the communication port to transmit data. When the attached device does not provide this signal, the controller keeps the line at a MARK. When the attached device does provide this signal, it sets CTS to MARK to allow the 5905 module to transmit data. Pin 9 NC The 5905 may be powered from pin 9 of the RS-232 connector, P4. There are a number of restrictions with respect to the 5VDC tolerance and fuse considerations. This feature may not be available on some of the initial production 5905 modules. Contact Control Microsystems Technical Support for further information when using this method of powering the 5905 module. The serial cable that is provided with the 5905 module is suitable for connecting the module to a DTE (Data Terminal Equipment) device such as a SCADAPack controller. Other DTE devices such as a personal computer may require a longer serial cable. This type of cable is commonly referred to as a null modem or computer to computer cable. Figure 3: RS-232 Wiring (DTE) to DTE shows a typical serial connection. DTE 5905 (DTE) DCD 1 TxD 2 RxD RxD 3 TxD DTR 4 GND 5 GND DSR 6 RTS 7 RTS CTS See device specifications for pin numbers Pin 9 may be connected to the 5V power supply. Use caution when connecting to this pin. 8 CTS 9 5 Volt Figure 3: RS-232 Wiring (DTE) to DTE Document (Version ) 5/19/

13 Installation RS-232 wiring requires shielded cable. The shield should be connected to chassis ground at one end of the cable only. The DE-9 connector shell is a good ground point. A maximum cable length of 50ft (15.2m) is allowed. Improperly shielded cable may result in the installation not complying with FCC or DOC radio interference regulations. RS-485 Port The RS-485 port transmits and receives differential voltages to other RS-485 devices. The RS-485 specification allows a maximum of 32 devices. A maximum cable length of 4000 feet (1200 m) terminated at each end is recommended. The RS-485 port has a 5 position removable terminal block for connections to the RS-485 network. Figure 4: 5905 RS-485 Terminal Block Connection, P5 and Table 2: RS-485 Connections describe this connector. The signal grounds of the RS-485 devices are not connected together but instead are referenced to their respective incoming electrical grounds. The grounds of the RS-485 devices need to be within several volts of each other. The RS-485 port operates in two or four wire mode. Four jumpers need to be set for the correct operation of the RS-485 port; Rx Term, J5; Tx Term, J6; RS232/485, J8 and 2Wire/4Wire, J10. The correct settings of these and other jumpers can be found in chapter Configuration Jumpers Tx -- + Rx -- Figure 4: 5905 RS-485 Terminal Block Connection, P5 A description of each terminal block signal for connector P5 is shown in Table 2: RS-485 Connections. Table 2: RS-485 Connections Pins Type Description Pin1 Pin 2 +TxD Pin 3 -TxD Chassis Ground Output Output Terminate one end of the shield of the RS-485 cable to this pin. Data received from the Ethernet LAN is output on this pin. This is the +side of a differential output that meets the RS-485 specification. Data received from the Ethernet LAN is output on this pin. This is the side of a differential output that meets the RS-485 specification. Pin 4 Input Data transmitted to the Ethernet LAN is input on this pin. Document (Version ) 5/19/

14 Installation Pins Type Description +RxD Pin 5 -RxD Input This is the +side of a differential input that meets the RS- 485 specification. Data transmitted to the Ethernet LAN is input on this pin. This is the side of a differential input that meets the RS- 485 specification. RS-485 Four Wire Operation Four-wire operation uses one pair of wires for transmitting data and a second pair for receiving data. The transmitting pair is connected to the terminals marked +Tx and Tx on the termination block. The receiving pair are connected to the terminals marked +Rx and Rx. See Figure 5: RS-485 Field Wiring Four Wire Mode for wiring details. Other RS- 485 Device RX + RX TX + TX First station in network requires terminations. Other RS- 485 Device RX + RX TX + TX RS-485 network 4000 feet (1200 m) maximum length 5905 RX + RX TX + TX Last station in network requires terminations. RS-485 Two Wire Operation Figure 5: RS-485 Field Wiring Four Wire Mode Two-wire operation uses one pair of wires for transmitting and receiving data. The +TX terminal is connected to the +RX terminal. The TX terminal is connected to the RX terminal. This pair of wires becomes the transmitting and receiving pair. See Figure 6: RS-485 Field Wiring Two Wire Mode for wiring details. Document (Version ) 5/19/

15 Installation Other RS- 485 Device RX + RX TX + TX First station in network requires terminations. Other RS- 485 Device RX + RX TX + TX RS-485 network 4000 feet (1200 m) maximum length 5905 RX + RX TX + TX Last station in network requires terminations. Termination Resistors Ethernet Connection Figure 6: RS-485 Field Wiring Two Wire Mode Termination resistors are required on the first and last station on the RS-485 wire pair. Other stations should not have termination resistors. Resistors for receiver and transmitter termination are pre-installed on the 5905 module. Refer to chapter Configuration Jumpers for instructions on connecting the termination resistors. The 5905 module uses a traditional termination scheme with one 120-ohm resistor across the line. Special receivers have been used such that the received data will be in an idle state for the following conditions on the RX pair: open inputs, terminated inputs, and shorted inputs. This termination scheme may not be compatible with other RS-485 devices. RS-485 receivers that cannot tolerate a differential input voltage of 0 volts (line terminated but not driven) should be terminated with resistors that bias the line to a known state during these conditions. The Ethernet network connects to the RJ-45 modular jack labeled P3. The RJ-45 jack mates with 8-pin connector and cable assemblies common to Ethernet 10Base-T applications. Pins 1,2,3 and 6 are used. Pins 4,5,7, and 8 are not used. See Figure 7: 5905 Ethernet RJ-45 Connection for pin connections. Document (Version ) 5/19/

16 Installation RJ-45 1: TD+ 2: TD- 3: RD+ 4: nc 5: nc 6: RD- 7: nc 8: nc Power Connections Figure 7: 5905 Ethernet RJ-45 Connection The 5905 module may be powered in any one of the following ways: 5VDC applied to the 5905 from the I/O Bus. 9VDC applied to the 5905SA from P6. 5VDC applied to the 5905 from pin 9 on the RS-232 connector, P4. The 5905 module is for use with Class 2 outputs only. I/O Bus Connection The 5905 module is normally powered through the connection to the system I/O Bus. The 5905 module is connected to the system I/O Bus using a cable connected to P1 or P2. Refer to the System Configuration Guide, at the beginning of this manual, for complete information on the system I/O Bus cabling. 5905SA Power Connection The 5905SA version of the Ethernet gateway is powered using an AC adapter (Control Microsystems part number: TBUM210040) connected to P6. The AC adapter plugs into a 120VAC supply and provides 9VDC to the 5905SA. This AC adapter is shipped with 5905SA modules. To power the 5905SA module using the AC adapter: Check that the AC adapter is not connected to the 120VAC supply. Locate connector P6 on the 5905 module. Refer to Figure1: 5905 Module Layout for the location of P6. Insert the small female plug on the AC adapter assembly into connector P6. Plug the AC adapter into a 120VAC supply. RS-232 Connection The 5905 may be powered from pin 9 of the RS-232 connector, P5. There are a number of restrictions with respect to the 5VDC tolerance and fuse Document (Version ) 5/19/

17 Configuration Jumpers LED Indicators Installation considerations. This feature may not be available on some of the initial production 5905 modules. Contact Control Microsystems Technical Support for further information when using this method of powering the 5905 module. The 5905 module uses six configuration jumpers for setting the operating conditions. These jumpers are described in the table below. Refer to Figure1: 5905 Module Layout above for the location of each jumper. Jumper Description Setting J2 Reset source When installed a Reset from a controller on the I/O Bus will Reset the 5905 module. Install for normal operation. Not installed for SA (standalone) operation. J3 LED Enable When installed, the LED enable from I/O Bus will be disabled removing LED power saving. The LEDs will be enabled. Not installed for normal operation. Install for SA (stand-alone) operation. J5 J6 J8 J10 J11 Rx Termination Tx Termination RS-232 / RS- 485 selection 2Wire / 4Wire selection 5V Power from P4, pin 9 When installed a 120 resistor terminates the RS-485 Rx lines. When installed a 120 resistor terminates the RS-485 Tx lines. Place jumper to the left when the serial port is RS-232. Place jumper to the right when the serial port is RS-485. Place jumper to the left when the RS-485 port is configured as 2 wire. Place jumper to the right when the RS-485 port is configured as 4 wire. For RS-232 operation a jumper is placed on J10 in either position When installed the 5905 may be powered with 5V from P4, pin 9. This jumper is normally not installed. Refer to section RS-232 Serial Port and section Power Connections for further details. The 5905 module has five LEDs to indicate module operation and status. The SCADAPack controller can disable the power to these LEDs to conserve power. LED Color Function Status Red See section Status and Error LEDs Operation below for details. Error Red See section Status and Error LEDs Operation below for details. Document (Version ) 5/19/

18 Installation LED Color Function Status Red See section Status and Error LEDs Operation below for details. Link Red ON when a link has been established with an Ethernet Network. Tx Clear ON when data received from the LAN is transmitted out the serial ports on the Tx lines. Rx Clear ON when data is being received on the serial ports on the Rx pins. Status and Error LEDs Operation Together the STATUS and ERROR LEDs display the status of the 5905 module. If the ERROR LED is on or blinking, the STATUS LED will give a diagnostics code. If the ERROR LED is off the STATUS LED shows the status of the communication channel. ERROR LED On Blinking Continuously Blinking Continuously Off STATUS LED Blinking Continuously Blinking 4 Times Blinking 5 Times Blinking Continuously Condition A telnet connection has been made to the 5905 module and the 5905 module is in the configuration mode. The 5905 module is going through its reset sequence. This normally occurs when the 5905 module is powered up or when the configuration has been changed, or, The 5905 module contains the factory default IP address, or, A terminal connection has been made to the RS-232 port and the 5905 module is in the configuration mode. The 5905 module IP address is already in use on the network. Channel is idle with no connection to a network. Off On The 5905 module is connected to the network. Document (Version ) 5/19/

19 Operation Operation Application Examples Modbus/TCP Access to Modbus RTU When it comes to planning data communication for open, multi-vendor industrial control systems, Modbus is the undisputed first choice of end users and integrators alike. The Modbus protocol defines how a Master device polls one or more Slave devices to read and write data in real-time with RS-232, RS-422, or RS-485 serial data communication. Modbus/TCP is an extension of serial Modbus, which defines how Modbus messages are encoded within and transported over TCP/IP-based networks. Modbus/TCP is just as simple to implement and flexible to apply as serial Modbus. Complete information for Modbus/TCP and serial Modbus may be found on-line at The following section describes some of the applications in which the 5905 Ethernet Gateway may be used in a Modbus/TCP network. The model 5905 Ethernet gateway allows Modbus RTU, or Modbus ASCII, master and slave stations to communicate using an Ethernet LAN. The 5905 converts RS-232/485 Modbus serial communication into Modbus/TCP on Ethernet. In the application shown in Figure 8: Modbus/TCP Access to Modbus RTU a PC is running a Modbus/TCP host MMI application and is connected to the Ethernet LAN using an internal Ethernet port. The host PC can communicate with any number of Modbus/TCP slave stations. Also connected to the Ethernet LAN is a SCADAPack master station using a 5905 Ethernet gateway module. The SCADAPack and the host PC are each polling the RS-485 network of SCADAPack controllers located at Site C. Figure 8: Modbus/TCP Access to Modbus RTU Document (Version ) 5/19/

20 Multiple Access to Modbus RTU Operation The 5905 Ethernet gateway supports multiple master stations communicating with single or multiple slave stations across an Ethernet LAN. The 5905 module supports up to 8 Modbus/TCP connections per module. The configuration shown in Figure 9: Multiple Access to Modbus RTU has three Modbus/TCP master stations communicating with a single Modbus slave station. Two of the master stations shown are PCs running Modbus/TCP applications and connected to the Ethernet LAN using internal Ethernet ports. The third master station is a SCADAPack controller connected to the Ethernet LAN using a 5905 Ethernet gateway module. The slave station is a SCADAPack controller connected to the Ethernet LAN using a 5905 Ethernet gateway module. Figure 9: Multiple Access to Modbus RTU Modbus/RTU RS-485 Bridging Through Ethernet Support for RS-485, two or four-wire, serial communication allows the 5905 modules to be used as a gateway between a PC running a host Man Machine Interface (MMI) application and multi-drop RS-485 networks using an Ethernet LAN. In the example shown in Figure 10: Modbus/RTU RS-485 Bridging Through Ethernet the PC is connected to the Ethernet LAN using the stand-alone version of the 5905 Ethernet gateway. The RS-485 network is connected to the Ethernet LAN through a 5905 mounted with a SCADAPack controller. This example shows the host PC communicating with a single RS-485 network connected to the Ethernet LAN. This configuration may be expanded to include up to eight RS-485 networks connected to the Ethernet LAN via 5905 modules. Document (Version ) 5/19/

21 Operation Figure 10: Modbus/RTU RS-485 Bridging Through Ethernet Modbus/RTU RS-232 Bridging Through Ethernet Support for RS-232 serial communication using RTS/CTS handshaking allows the 5905 modules to be used as a gateway between a PC running a host Man Machine Interface (MMI) application and a network consisting of SCADAPack controllers using half-duplex, 5902 Bell 202 leased line modems. In the example shown in Figure 11: Modbus/RTU RS-232 Bridging Through Ethernet the PC is connected to the Ethernet LAN using the stand-alone version of the 5905 Ethernet gateway. The leased line network is connected to the Ethernet LAN through a 5905 Ethernet gateway module and a 5902 Bell 202 modem. This type of configuration will support many types of networks using half-duplex devices. One example would be using radio communication instead of dedicated leased lines. This example shows the host PC communicating with a single leased line network connected to the Ethernet LAN. This configuration may be expanded to include up to eight leased line networks connected to the Ethernet LAN via 5905 modules. Figure 11: Modbus/RTU RS-232 Bridging Through Ethernet Document (Version ) 5/19/

22 Network Protocols Operation The 5905 Ethernet gateway uses TCP/IP protocols for network communication. Per the Modbus/TCP specification, the Modbus data messages are transported by TCP for error-free data transport end-to-end. The IP protocol defines addressing, routing and data block handling over the network. Document (Version ) 5/19/

23 Configuration Configuration Direct Serial Port Setup Connection Configuration of the 5905 Ethernet Gateway module is made with the 5905 in the Setup mode. The 5905 may be put into the Setup mode using a direct serial port connection to the RS-232 port or a remote Telnet connection over the TCP/IP network. Once either type of connection is made with the 5905 a prompt is displayed allowing the user to enter the Setup mode. The recommended method for initially configuring the 5905 is to use the direct serial connection to enter the Setup mode. The default factory IP address of does not allow a Telnet connection. Once the IP address has been set to a unique value in the network a remote Telnet connection can be made. The 5905 configuration is stored in nonvolatile memory and is retained if power is removed from the module. The configuration can be changed any time. The 5905 will automatically reset after the configuration has been changed and stored. To enter the Setup mode using a direct serial port connection requires an ASCII terminal or a PC running a terminal emulation program such as the HyperTerminal accessory included with Windows 95/98/NT. To establish a direct serial port connection with the 5905 Ethernet Gateway and a PC running Windows HyperTerminal: In the HyperTerminal Connect To dialog box select a direct connection using an available port on the PC. In the Port Settings dialog select; Bits per second: 9600 Data bits: 8 Parity: none Stop bits: 1 Flow control: none Connect the PC serial port and the 5905 RS-232 serial port, P4, using a null modem (computer to computer) cable. Check that the 232/485 jumper, J8, on the 5905 is set for 232. To enter Setup mode: Cycle the power to the 5905 by removing and then re-applying power. When the power is re-applied the 5905 will start a self-test. Approximately one half second later the ERROR LED will start to blink. Three lowercase x characters need to be sent to the 5905, from HyperTerminal, within approximately one second after the ERROR LED starts to blink, to enable the Setup mode. Document (Version ) 5/19/

24 Telnet Network Connection The easiest way to enter Setup mode is to hold down the x key when reapplying power to the When the Setup mode is enabled the message shown in the box below is displayed in the HyperTerminal window. **Control Microsystems 5905 Ethernet Gateway Serial Number Software Version 01.1b1 (990423) Press Enter to go into Setup Mode, wait to close Configuration Press the enter key, <enter>, to enter the Setup mode, otherwise after a short delay the 5905 will automatically restart using the currently stored settings. Go to section Setup Configuration Parameters for details on changing the 5905 configuration. If the above procedure does not work perform this simple test of the cable. When power is cycled to the 5905 an asterisk character (*) will be displayed in the HyperTerminal window. If the * is not visible then either the null modem cable is incorrect or the HyperTerminal program is not configured properly. The ERROR and STATUS LEDs indicate when the 5905 module is in the configuration mode using a direct serial connection. See section Status and Error LEDs Operation for details. If the assigned IP address is known then a Telnet connection on port 9999 may be established with the 5905 Ethernet gateway. To establish a Telnet connection with the 5905: From the Window 95/98/NT Start menu select Run. In the Run dialog type telnet in the file to open box. In the Telnet window select Remote System from the Connect menu. In the Connect dialog select; Host Name: xxx.xxx.xxx.xxx Port: 9999 Term Type: vt100 where xxx.xxx.xxx.xxx is the known 5905 network IP address. Select the connect pushbutton to enable the Setup mode. The message shown in the box below is displayed in the HyperTerminal window. **Control Microsystems 5905 Ethernet Gateway Serial Number Software Version 01.1b1 (990423) Press Enter to go into Setup Mode, wait to close Press the enter key, <enter>, to enter the Setup mode, otherwise after a short delay the 5905 will automatically restart using the currently stored settings. Document (Version ) 5/19/

25 Configuration Go to sectionsetup Configuration Parameters for details on changing the 5905 configuration. Factory IP Address The 5905 Ethernet Gateway is shipped with a factory default IP address of , which automatically enables the DHCP (Dynamic Host Configuration Protocol) within the The default factory IP of does not allow a Telnet to access the Refer to Appendix A: Forcing a New IP Address for complete information on using ARP (Address Resolution Protocol) to set a network IP address for the The ERROR LED blinks four times and then the STATUS and ERROR LEDs blink four times in unison when the 5905 is powered with the factory default IP address. Setup Configuration Parameters When the Setup mode is initially entered, using a direct serial port connection or a remote telnet connection, the Setup configuration menu is displayed as shown in the box below Setup, Control Microsystems, Inc. 1) Network/IP Settings: Ethernet Interface Autodetect TPI IP Address /DHCP Default Gateway not set --- Netmask not set --- 2) Serial & Mode Settings: Protocol... Modbus/RTU,Slave(s) attached Serial Interface ,8,N,1,RS232 3) Modem Control Settings: RTS Output... Fixed High/Active 4) Advanced Modbus Protocol settings: Slave Addr/Unit Id Source.. Modbus/TCP header Modbus Serial Broadcasts... Disabled Character,Message Timeout ms,05000 ms D)efault settings, S)ave, Q)uit without save Select Command or parameter set (1..4) to change: For each settings the current values are shown. If no change is required for a selection press the <enter> key and the current value is not changed. The Document (Version ) 5/19/

26 Network/IP Settings Configuration configuration menu displays the factory default configuration until changes are made and saved. The 5905 configuration settings are changed as they are edited. The settings are made permanent when the SAVE command is used. Each setting in the configuration menu is explained in the following paragraphs. The Network/IP Settings menu is used to define the IP address of the 5905 Ethernet Gateway. To enter this menu type 1 at the Select Command prompt at the bottom of the screen. IP Address The first octet of the IP address is displayed in brackets. Simply type a new IP address octet or press <enter> to accept the displayed value. Each of the four IP address octets is displayed in turn for editing. The IP address needs to be set to a unique value in the network. If the network IP address for the 5905 is not known then usually the administrator of the TCP/IP network needs to be contacted for an available address. If the 5905 Ethernet Gateway modules are the only devices on the network then the IP address block XXX, where the last number, XXX, is 0 to 254, may be used. Setting the last number to the last digit of the hardware address will make the IP address easy to remember. The 5905 module provides a convenient location at the top of the module to record the IP address. The 5905 Ethernet Gateway supports Dynamic Host Configuration Protocol (DHCP). The IP address is set to to activate DHCP. For information on using ARP to set an IP address, refer to Appendix A: Forcing a New IP Address. The 5905 will reset and generate an error message on the RS232 serial every 30 seconds if the IP address entered is already in use on the network. The error message is: ERROR: IP address conflict with xx.xx.xx.xx.xx.xx where xx.xx.xx.xx.xx.xx is the hardware Ethernet address of an existing network IP address. Set Gateway IP Address (Y/N) Set Netmask (N for default) The default value is N for this selection. When the 5905 communicates to remote TCP/IP networks through a router or gateway select Y and enter the default gateway IP address within the local network. If in doubt consult the network administrator. The default value is N for this selection. When N is selected the 5905 will automatically use the standard netmask appropriate for the IP address entered. Document (Version ) 5/19/

27 Serial & Mode Settings Attached Device (1=Slave, 2=Master) Configuration The netmask defines which part of the IP address is the network and which part is the host or Users who want a non-standard netmask need to enter the number of host bits in the IP address. The Serial & Mode Settings menu is used to define the serial port and protocol parameters for the 5905 Ethernet Gateway. To enter this menu type 2, and then enter, at the Select Command prompt at the bottom of the screen. The device attached to the 5905 may be a Modbus protocol master station to poll other Modbus/TCP devices or slave station to be polled by remote Modbus/TCP devices. The default selection for the attached device is Slave. To accept the default selection press the enter key. To change the selection to Master enter 2. Serial Protocol (1=Modbus/RTU, 2=Modbus/ASCII) The 5905 module supports both MODBUS RTU protocol and MODBUS ASCII protocol. The default selection is Modbus RTU. To accept the default selection press the enter key. To change the protocol to Modbus ASCII enter 2. The 5905 Ethernet Gateway converts both to and from Modbus/TCP completely. Any combination of Modbus RTU and Modbus ASCII devices may share a Modbus/TCP network. Interface Type (1=RS-232, 2= Four-wire RS-485, 3= Two-wire RS-485) Enter Serial Parameters (BBBB, D, P, S) The 5905 Ethernet Gateway supports an RS-232 serial interface to the attached device or an RS-485 serial interface to a single or multiple attached devices. The RS-485 interface may be selected for two-wire or four-wire operation. The default selection is for an RS-232 interface. To accept the default selection press the enter key. To select a four-wire RS-485 interface enter 2. To select two-wire RS-485 interface enter 3. Check that jumper J8 and jumper J10 on the 5905 are set for the interface selected. The serial parameters for the interface selected are entered in the format (baud rate, data bits, parity, stop bits). The default serial parameters selection is (9600, 8, n, 1). Selectable ranges for the baud rate are; 300, 600, 1200, 2400, 4800, 9600, 19200, or Selectable ranges for the number of data bits are; 7 or 8. Selectable ranges for the parity type are; none (n), odd (o) or even (e). Document (Version ) 5/19/

28 Modem Control Settings RTS/CTS Mode (1=Fixed 2=Variable) Selectable ranges for the number of stop bits are; 1 or 2. Configuration The serial parameters need to match, exactly, the serial port settings of the attached device(s). Regardless of Serial Parameters settings the 5905 configuration is done using the RS-232 serial port with the settings 9600,8,N,1. The Modem Control Settings menu is used to enable or disable hardware handshaking on the 5905 Ethernet Gateway RS-232 serial port. To enter this menu type 3, and then enter, at the Select Command prompt at the bottom of the screen. The parameters in this selection control the request to send (RTS) / clear to send (CTS) handshaking for half-duplex devices attached to the RS-232 serial port. Typically RTS/CTS handshaking is used with leased line or radio modems such as the 5902 Bell 202 modem. This selection determines whether RTS/CTS handshaking is used on the RS-232 serial port. The default selection is 1 for the RTS/CTS outputs fixed high. Selecting 1 disables RTS/CTS handshaking and closes the Modem Control Settings menu. Selecting 2 enables RTS/CTS handshaking and opens further selections for controlling the RTS/CTS handshaking. Delay After Output of RTS ( msec, 5ms resolution) Wait for CTS to Go Active (N/Y) Normally a half-duplex device attached to the 5905 RS-232 serial port will respond with a CTS signal when the 5905 module asserts the RTS signal. This is normal hardware handshaking operation. If the device attached to the RS-232 serial port cannot respond with a CTS signal, the 5905 can be set to delay from 0 to 1275 msec before continuing with data transmission. This selection has a default value of 0. A value other than zero is required only if the attached device is non-standard. To change the selection enter a value in msec and press the enter key. This selection is used in conjunction with the Wait for CTS to Go Active selection. This selection determines whether the 5905 waits for a CTS response from the attached device or continues with data transmission after the delay entered in the Delay After Output of RTS selection above. The default selection is N. This causes 5905 to ignore the CTS response from the attached device. Data transmission will occur after the delay entered in Document (Version ) 5/19/

29 Configuration section Delay After Output of RTS ( msec, 5ms resolution) section above. Selecting Y causes the 5905 to wait for the CTS response from the attached device. Check that the serial cable is properly wired to support this signal when selecting Y. Delay After CTS Going Active ( msec, 5ms resolution) This selection is only available if RTS/CTS Mode is selected as variable and the Wait for CTS to Go Active is selected as yes. When the 5905 detects that the attached device has asserted CTS, it can be set to delay from 0 to 1275 msec before transmitting data. The default selection is 0 msec. To change the selection enter a value in msec and press the enter key. Delay Dropping RTS After Transmitting ( msec, 5ms resolution) Advanced Modbus Protocol Settings When the 5905 completes data transmission, it can be set to delay from 0 to 1275 msec before dropping the RTS output. The default selection is 0 msec. The Advanced Modbus Protocol Settings menu is used to define the slave addressing and handling of Modbus broadcast messages. This menu also allows setting of the character and message timeout values for processing Modbus messages. To enter this menu type 4, and then <enter>, at the Select Command prompt at the bottom of the screen. Slave address (0 for auto, or fixed otherwise) Allow Modbus Broadcasts (1=Yes 2=No) Modbus/TCP includes a Unit Id field, which is used to address multiple Modbus slaves at a single IP address. Unfortunately, some first generation software drivers assumed a single slave at each IP address and set the Unit Id field to 0. To support these older applications, the 5905 allows a fixed Modbus address to be entered for the attached slave device. A slave address other than 0 will limit the 5905 to a single attached device. Setting the slave address value to 0 will enable the 5905 to use the Modbus/TCP Unit Id as received, allowing multiple attached slave devices. This is the default setting. This selection is available only if the slave address is set for 0 (auto). Answer Y and the 5905 module allows a Modbus/TCP Unit ID of 0 to be sent as a Modbus Broadcast. Answer N and a Unit Id of 0 is changed to a Modbus slave address of 1. The 5905 module supports a Modbus broadcast message only when a serial slave device is attached. A Modbus broadcast message from a serial master device is discarded by the 5905, regardless of this parameter setting. Document (Version ) 5/19/

30 Character Timeout ( msec, 5ms resolution) Configuration This selection sets the timeout, in milliseconds, between characters within both RTU and ASCII protocols. Modbus RTU protocol defines a 3.5 character timeout, but many modern devices have various interrupts, which can cause 5 to 10 character pauses during transmission. The default value for this selection is 50 msec for Modbus RTU protocol. This selection value fixed at 1000msec for Modbus ASCII protocol. To change the selection enter a value in msec and press the enter key. Setting this value below 50msec will not improve performance and may even make it worse uses an intelligent length-predicting algorithm to detect endof-message in Modbus/RTU. This character timeout is only used with userdefined or non-standard Modbus functions. Message Timeout ( msec, 250ms resolution) Unit ID to IP Address Lookup Table This selection sets the timeout, in milliseconds, that the 5905 will wait for a response from a connected slave. If the 5905 waits for the message timeout value without seeing a valid response from the connected slave, it will return Modbus exception response 0x0B (hex) to the Modbus/TCP requesting Master. The default selection is 1000 msec. To change the selection enter a value and press the <enter> key. This menu is visible only when a Modbus master device is attached to the 5905, as defined in menu item 2 above. To enter this menu type 5, and then enter, at the Select Command prompt at the bottom of the screen. The Unit ID to IP Address Lookup Table is used to map Modbus slave address to network IP address. When the attached master device sends a master message to a slave station the 5905 checks the Lookup table to see which IP address to send the master message. The Lookup table can map multiple slave addresses to a single network IP address. The Lookup table may contain a maximum 8 entries, representing 8 separate IP addresses. When a Modbus slave address is not found in the table the 5905 returns an exception response to the attached master. An example of a Unit ID to IP Address Lookup Table is shown in the box below. In this example there are seven entries in the Lookup table, with each entry having an individual IP address. This example shows that slave stations 1 through 10 are attached to a 5905, or other Modbus/TCP slave, at IP address D)elete, E)xit - select function Delete entry number 1): : Document (Version ) 5/19/

31 Configuration 2): : ): : ): : ): : ): : ): : A)dd, D)elete, E)xit - select function Modbus addr from (211) Select Function A)dd, D)elete, E)xit Modbus Address From Modbus addr to (211) 255 Slave IP address (010) 197.(000) 168.(000) 000.(000) 177 This selection allows for adding or deleting Lookup table entries and exiting the Unit ID to IP Address Lookup Table menu selection. Selecting E, or exit, closes the Unit ID to IP Address Lookup Table and returns to the main menu. Any changes made to the table are saved. Selecting D, or delete, allows an entry to be deleted. At the Delete entry number prompt, type in the entry number to be deleted. Selecting A, or add, allows an entry to be added to the Lookup table. When this selection is made the following prompts are displayed, in order, creating a new table entry. Enter the start address of the slave stations attached to the 5905, or other Modbus/TCP slave, at the Slave IP Address. Modbus Address To Slave IP Address Enter the end address of the slave stations attached to the 5905, or other Modbus/TCP slave, at the Slave IP Address. If a single slave address is at a Slave IP Address then the Modbus Address From entry and the Modbus Address To entry will be the same. This is the network IP address of the remote 5905 Ethernet Gateway or other Modbus/TCP slave. Basic Commands (Delete / Save / Quit) The 5905 offers 3 basic commands: Document (Version ) 5/19/

32 Configuration Default Settings (D) Save Settings (S) Entering D resets parameters to the factory default settings. Changes to the Network/IP Settings menu are not reset to factory default settings. Entering S stores the currently displayed parameter settings into non-volatile memory and exits the setup mode. Quit Without Saving Settings (Q) Entering Q throws away any parameter changes you have made and exits the setup mode. Document (Version ) 5/19/

33 Maintenance Maintenance This module requires no routine maintenance. If the module is not functioning correctly, contact Control Microsystems Technical Support for more information and instructions for returning the module for repair. Troubleshooting Condition Cannot configure 5905 using direct connection. Cannot Telnet to the 5905 module. Solutions Check that jumper J8 is in the RS232 position. Check that terminal settings are set as described in section Direct Serial Port Setup Connection section. Check that the serial cable between the PC and the 5905 module is a DTE-DTE cable. Check that the IP address used is correct. Check that the port used is Document (Version ) 5/19/

34 Specifications Specifications Disclaimer: Control Microsystems reserves the right to change product specifications. For more information visit LAN Compatibility Network Protocols SCADA Protocols RS-232/485 Data Rate Duplex RTS/CTS Delay RTS Hold Time Configuration Visual Indicators Dimensions Ethernet Termination RS-232 Termination RS-485 Termination Mounting Packaging Environment Part Number Ethernet: Version 2.0/IEEE IP:ARP, TCP, SNMP, TFTP Modbus RTU or ASCII 300 to 38,400 Full or half. Half requires the DTE to implement hardware RTS/CTS handshake Settable during 5905 configuration Settable during 5905 configuration Telnet over Ethernet or locally connected terminal emulator firmware may be updated over the network using TFTP client Ethernet Link Status, Tx (serial data from LAN), Rx (serial data to LAN), Error & Status 4.25 inch (108mm) wide X inch (118mm) high X 1.75 inch (44mm) deep RJ-45, 10Base-T (twisted pair), 10M bits/second DE9P connector, DTE Removable terminal strip 5 pole, removable terminal block 12 to 22 AWG 15 amp contacts Model X 35 DIN rail Model 5905SA desktop, rubber feet or DIN rail Corrosion resistant zinc plated steel with black enamel paint 5% RH to 95% RH, non-condensing 0C/32F to 50C /122F Model 5905 Ethernet Gateway, RS-232 or RS- 485 for use with Modbus RTU or ASCII communication Model 5905SA Stand-alone version Document (Version ) 5/19/

5521 Potentiometer Analog Input Module

5521 Potentiometer Analog Input Module 55 Potentiometer Analog Input Installation, Operation and Maintenance Setup Manual 5/9/0 Safety Information The information provided in this documentation contains general descriptions and/or technical

More information

5504 Thermocouple Analog Input Module

5504 Thermocouple Analog Input Module 550 Thermocouple Analog Input Installation, Operation and Maintenance Setup Manual 5/9/0 Safety Information The information provided in this documentation contains general descriptions and/or technical

More information

5401 and 5402 Digital I/O Modules

5401 and 5402 Digital I/O Modules 50 and 50 Digital I/O Modules Installation, Operation and Maintenance Setup Manual 5/9/0 Safety Information The information provided in this documentation contains general descriptions and/or technical

More information

SCADAPack E Target 5 DF1 PLC Interface

SCADAPack E Target 5 DF1 PLC Interface SCADAPack E Target 5 DF1 PLC Interface 2 Table of Contents Part I 3 1 Technical... Support 3 2 Safety... Information 4 3 Overview... 7 4 I/O Device... Interface 7 4.1 Input Devices... 9 4.2 Output Devices...

More information

SCADAPack E Idec PLC Interface Manual

SCADAPack E Idec PLC Interface Manual SCADAPack E Idec PLC Interface Manual 2 SCADAPack E Idec PLC Interface Manual Table of Contents Part I Idec PLC Interface 3 1 Technical... Support 3 2 Safety... Information 4 3 Preface... 6 4 Overview...

More information

5403 and 5404 Digital Input Modules

5403 and 5404 Digital Input Modules 503 and 50 Digital Input Modules Installation, Operation and Maintenance Setup Manual //07 Copyright 0-07 Schneider Electric Canada Inc. All rights reserved. 503 and 50 Digital Input Modules The information

More information

5502 Differential Analog Input Module

5502 Differential Analog Input Module 550 Differential Analog Input Installation, Operation and Maintenance Setup Manual //07 Copyright 0-07 Schneider Electric Canada Inc. All rights reserved. 550 Differential Analog Input The information

More information

SCADAPack E 5405 Digital Input Hardware Manual

SCADAPack E 5405 Digital Input Hardware Manual SCADAPack E 5405 Digital Input Hardware Manual 2 SCADAPack E 5405 Digital Input Hardware Manual Table of Contents Part I 5405 Digital Input Module 3 1 Technical... Support 3 2 Safety... Information 4 3

More information

SCADAPack 32 Controller

SCADAPack 32 Controller SCADAPack 32 Controller Installation, Operation and Maintenance Manual 5/19/2011 Safety Information The information provided in this documentation contains general descriptions and/or technical characteristics

More information

5910 Ethernet Gateway Module

5910 Ethernet Gateway Module Hardware Manual 2/24/2017 Copyright 2014-2017 Schneider Electric Canada Inc. All rights reserved. 5910 Ethernet Gateway Module The information provided in this documentation contains general descriptions

More information

Packaging User Guide for Temperature Control M221 Project Template

Packaging User Guide for Temperature Control M221 Project Template Packaging EIO0000001762 04/2014 Packaging User Guide for Temperature Control M221 Project Template 04/2014 EIO0000001762.00 www.schneider-electric.com The information provided in this documentation contains

More information

5604 Input/Output (I/O) Module

5604 Input/Output (I/O) Module 5604 Input/Output (I/O) Module Installation, Operation and Maintenance Setup Manual 5/19/2011 Safety Information The information provided in this documentation contains general descriptions and/or technical

More information

SoMachine Scan for Buttons Linked to ZBRN Modules Harmony ZBRN Library Guide

SoMachine Scan for Buttons Linked to ZBRN Modules Harmony ZBRN Library Guide SoMachine EIO0000001868 11/2016 SoMachine Scan for Buttons Linked to ZBRN Modules Harmony ZBRN Library Guide 11/2016 EIO0000001868.04 www.schneider-electric.com The information provided in this documentation

More information

5601/5601A Input / Output (I/O) Module

5601/5601A Input / Output (I/O) Module 5601/5601A Input / Output (I/O) Module Installation, Operation and Maintenance Setup Manual 5/19/2011 Safety Information The information provided in this documentation contains general descriptions and/or

More information

CONTROL MICROSYSTEMS SDI-12 Interface Module. Hardware Manual

CONTROL MICROSYSTEMS SDI-12 Interface Module. Hardware Manual 5915 SDI-12 Interface Module Hardware Manual CONTROL MICROSYSTEMS SCADA products... for the distance 48 Steacie Drive Telephone: 613-591-1943 Kanata, Ontario Facsimile: 613-591-1022 K2K 2A9 Technical Support:

More information

SCADAPack E ISaGRAF Quick Start Guide

SCADAPack E ISaGRAF Quick Start Guide SCADAPack E ISaGRAF Quick Start Guide 2 SCADAPack E ISaGRAF Quick Start Guide Table of Contents Part I ISaGRAF 3 Quick Start Guide 3 1 Technical... Support 3 2 Safety... Information 4 3 Preface... 6 4

More information

LXM32. Explanation for detected error E 733F. Expert Support Machine Solution

LXM32. Explanation for detected error E 733F. Expert Support Machine Solution LXM32 Explanation for detected error E 733F Expert Support Machine Solution The information provided in this documentation contains general descriptions and/or technical characteristics of the performance

More information

SCADAPack E Koyo DirectNET PLC Interface Manual

SCADAPack E Koyo DirectNET PLC Interface Manual SCADAPack E Koyo DirectNET PLC Interface Manual 2 SCADAPack E Koyo DirectNET PLC Interface Manual Table of Contents Part I Koyo DirectNET PLC Interface 3 1 Technical... Support 3 2 Safety... Information

More information

multisys User manual Technical parameters D2-MSMT-1 Gateway from Modbus TCP to Modbus RTU, serial RS _EDEBDA _EN

multisys User manual Technical parameters D2-MSMT-1 Gateway from Modbus TCP to Modbus RTU, serial RS _EDEBDA _EN User manual Technical parameters multisys D2-MSMT-1 Gateway from Modbus TCP to Modbus RTU, serial RS485 System I English Your partner for network analysis KBR Kompensationsanlagenbau GmbH does not accept

More information

SCADAPack 100 Controller

SCADAPack 100 Controller Installation, Operation and Maintenance Setup Manual 2/24/2017 Copyright 2014-2017 Schneider Electric Canada Inc. All rights reserved. The information provided in this documentation contains general descriptions

More information

Ethernet Modbus X80 Gateway Device Type Manager

Ethernet Modbus X80 Gateway Device Type Manager Ethernet Modbus X80 Gateway Device Type Manager EIO0000001315 10/2012 Ethernet Modbus X80 Gateway Device Type Manager User Manual 10/2012 EIO0000001315.00 www.schneider-electric.com The information provided

More information

SCADAPack E 5505 RTD Input Hardware Manual

SCADAPack E 5505 RTD Input Hardware Manual SCADAPack E 5505 RTD Input Hardware Manual 2 SCADAPack E 5505 RTD Input Hardware Manual Table of Contents Part I 5505 RTD Input Module 3 1 Technical... Support 3 2 Safety... Information 4 3 Overview...

More information

EtherSeries Modbus Gateway EMB-2 User s Guide

EtherSeries Modbus Gateway EMB-2 User s Guide EtherSeries Modbus Gateway EMB-2 User s Guide Revised March 25, 2004 Firmware Version 1.4 FCC Statement This device complies with the limits for a Class B digital device, pursuant to Part 15 of the FCC

More information

174 CEV Modbus to Ethernet Bridge User Guide. 890USE19500 Version 1.0

174 CEV Modbus to Ethernet Bridge User Guide. 890USE19500 Version 1.0 174 CEV 300 20 Modbus to Ethernet Bridge User Guide 890USE19500 Version 1.0 31005108 00 2 890USE19500 September 2003 Table of Contents Safety Information.................................... 5 About the

More information

Momentum 170ENT11001/170ENT11002 Ethernet Communications Adapter User Guide

Momentum 170ENT11001/170ENT11002 Ethernet Communications Adapter User Guide Momentum 31004109 09/2017 Momentum 170ENT11001/170ENT11002 Ethernet Communications Adapter User Guide 09/2017 31004109.07 www.schneider-electric.com The information provided in this documentation contains

More information

SCADAPack E ISaGRAF 3 I/O Connection Reference

SCADAPack E ISaGRAF 3 I/O Connection Reference SCADAPack E ISaGRAF 3 I/O Connection Reference 2 SCADAPack E ISaGRAF 3 I/O Connection Reference Table of Contents Part I ISaGRAF 3 I/O Connection 4 1 Technical... Support 4 2 Safety... Information 5 3

More information

User Manual A08. User Manual

User Manual A08. User Manual A08 TABLE OF CONTENTS TABLE OF CONTENTS... 1 1. INTRODUCTION... 2 1.1. Key Features... 3 1.2. OS Requirement... 4 1.3. Specification... 4 1.4. Packing List... 4 2. OVERVIEW... 5 2.1. LED Definition...

More information

5607 Input/Output (I/O) Module

5607 Input/Output (I/O) Module 5607 Input/Output (I/O) Module Installation, Operation and Maintenance Setup Manual 5/19/2011 Safety Information The information provided in this documentation contains general descriptions and/or technical

More information

USER S MANUAL. PH232Ex1. #1 RS-232 Serial Port to Ethernet, Terminal Server/Client. Doc No: PH232Ex1-UM-001 IPEX. (IP Electronix)

USER S MANUAL. PH232Ex1. #1 RS-232 Serial Port to Ethernet, Terminal Server/Client. Doc No: PH232Ex1-UM-001 IPEX. (IP Electronix) USER S MANUAL PH232Ex1 Doc No: PH232Ex1-UM-001 #1 RS-232 Serial Port to Ethernet, Terminal Server/Client IPEX (IP Electronix) Contents 1. INTRODUCTION... 3 2. SPECIFICATIONS... 3 3. PACKAGE CHECKLIST...

More information

Security Quick Start Guide

Security Quick Start Guide 2 Table of Contents Part I 4 1 Technical... Support 4 2 Safety... Information 5 3 Introduction... 7 4 Security... Overview 8 5 How to... Configure DNP3 Secure Authentication 11 5.1 Check RTU Firm... w

More information

SCADAPack 350E Hardware Manual

SCADAPack 350E Hardware Manual SCADAPack 350E Hardware Manual 2 Table of Contents Part I 4 1 Technical... Support 4 2 Safety... Information 5 3 Introduction... 8 4 Installation... 9 4.1 Field Wiring... 11 5 Power... Supply Overview

More information

XPSMCMx Fieldbus Expansion Modules Instruction Sheet (Original Language)

XPSMCMx Fieldbus Expansion Modules Instruction Sheet (Original Language) XPSMCMx Fieldbus Expansion Modules EAV8283001 12/2014 XPSMCMx Fieldbus Expansion Modules Instruction Sheet (Original Language) 12/2014 EAV8283001.00 www.schneider-electric.com The information provided

More information

User Manual Revision English

User Manual Revision English Document code: MN67118_ENG Revision 2.002 Page 1 of 12 User Manual Revision 2.002 English RS232 / RS485 - Converter (Order Code: HD67118) Suitable for Heavy supervisor for Website information: www.adfweb.com?product=hd67118

More information

SCADAPack 32. Smart RTU

SCADAPack 32. Smart RTU SCADAPack 32 Smart RTU 1 Compared to the SCADAPack 300 platform, the SCADAPack 32 is a higher performance Smart RTU built to meet the demands of larger applications including support for up to 10 gas flow

More information

Schneider Electric AB DH485 Protocol XBT N/R/RT

Schneider Electric AB DH485 Protocol XBT N/R/RT Schneider Electric AB DH485 Protocol XBT N/R/RT 33004016 06/2008 33004016.01 2 33004016 06/2008 Table of Contents Safety Information....................................5 About the Book.......................................7

More information

CONTROL MICROSYSTEMS. TeleSAFE Micro16 Controller. Hardware Manual

CONTROL MICROSYSTEMS. TeleSAFE Micro16 Controller. Hardware Manual TeleSAFE Micro16 Controller Hardware Manual CONTROL MICROSYSTEMS SCADA products... for the distance 48 Steacie Drive Telephone: 613-591-1943 Kanata, Ontario Facsimile: 613-591-1022 K2K 2A9 Technical Support:

More information

Industrial Serial Device Server

Industrial Serial Device Server 1. Quick Start Guide This quick start guide describes how to install and use the Industrial Serial Device Server. Capable of operating at temperature extremes of -10 C to +60 C, this is the Serial Device

More information

Acti 9 Communication System

Acti 9 Communication System Acti 9 Communication System Diagnostics User Manual 05/2012 DOCA0042EN-00 www.schneider-electric.com This document contains general descriptions and/or general technical specifications of the products

More information

Serial Communications Accessories SITRANS RD200/300. Operating Instructions 05/2013 SITRANS

Serial Communications Accessories SITRANS RD200/300. Operating Instructions 05/2013 SITRANS Serial Communications Accessories SITRANS RD200/300 Operating Instructions 05/2013 SITRANS Siemens Auto SIT SITRANS RD300RANS RD300 Safety Guidelines: Warning notices must be observed to ensure personal

More information

DGH A3000 Configuration Guide For use with DGH Modules

DGH A3000 Configuration Guide For use with DGH Modules DGH A3000 Configuration Guide For use with DGH Modules Revision Date: 12/07/05 Version: 1.00 Contact Information: http://www.dghcorp.com Ph: (603) 622-0452 Fax: (603) 622-0487 Mailing Address: DGH Corporation

More information

MU110-6U. Analog output module 6 channel. User guide

MU110-6U. Analog output module 6 channel. User guide MU110-6U Analog output module 6 channel User guide MU110-6U_2016.12_0221_EN All rights reserved Subject to technical changes and misprints akytec GmbH Vahrenwalder Str. 269 A 30179 Hannover Тел.: +49 (0)

More information

RS-232/422/485 to Copper or Fiber. Ethernet Converter. User s Manual

RS-232/422/485 to Copper or Fiber. Ethernet Converter. User s Manual RS-232/422/485 to Copper or Fiber Ethernet Converter User s Manual Table Of Contents TABLE OF CONTENTS... 1 INTRODUCTION... 3 PRODUCT OVERVIEW... 3 PRODUCT FEATURES... 3 PACKING LIST... 4 LED INDICATORS...

More information

RTU560 Connections and Settings DIN Rail RTU 560CIG10

RTU560 Connections and Settings DIN Rail RTU 560CIG10 Connections and Settings DIN Rail RTU 560CIG10 Application, characteristics and technical data have to be taken from the hardware data sheet: 560CIG10 1KGT 150 719 Operation The 560CIG10 is a DIN rail

More information

RTU560 Remote Terminal Unit Connections and Settings

RTU560 Remote Terminal Unit Connections and Settings Remote Terminal Unit Connections and Settings Communication Unit 560CMG10 Application, characteristics and technical data have to be taken from the hardware data sheet: 560CMG10 1KGT 150 645 Operation

More information

MGate TM EIP3000 DF1 to EtherNet/IP Gateway User s Manual

MGate TM EIP3000 DF1 to EtherNet/IP Gateway User s Manual MGate TM EIP3000 DF1 to EtherNet/IP Gateway User s Manual First Edition, June 2009 www.moxa.com/product 2009 Moxa Inc. All rights reserved. Reproduction without permission is prohibited. MGate EIP3000

More information

DATA CONNECT ENTERPRISE

DATA CONNECT ENTERPRISE DATA CONNECT ENTERPRISE User s Manual IG202T and IGV23 Modem Document Number 520-01005-001 Rev. A DATA CONNECT Contents Contents... iii Figures... iv Chapter 1 Introduction... 5 Features...6 Applications...7

More information

Serial Communication Converters & Adapters Instruction Manual

Serial Communication Converters & Adapters Instruction Manual Serial Communication Converters & Adapters Instruction Manual RS-232 to RS-422/485 Converter Isolated RS-232 to RS-422/485 Converter USB to RS-232 Converter USB to RS-422/485 Converter Isolated USB to

More information

T1K MODBUS Base Controller Specifications

T1K MODBUS Base Controller Specifications Base Controller 1 2 In This Chapter.... Base Controller Setting the DIP Switches Setting the Rotary Address Switches Port Pin out and Wiring RJ12 Serial Port Pin out and Wiring 2 2 Base Controller General

More information

CONTROL MICROSYSTEMS and 5601A Input/Output (I/O) Module. Hardware Manual

CONTROL MICROSYSTEMS and 5601A Input/Output (I/O) Module. Hardware Manual 5601 and 5601A Input/Output (I/O) Module Hardware Manual CONTROL MICROSYSTEMS SCADA products... for the distance 48 Steacie Drive Telephone: 613-591-1943 Kanata, Ontario Facsimile: 613-591-1022 K2K 2A9

More information

EQ-DCM User Manual Revision 1.02 Sep 10, 2013

EQ-DCM User Manual  Revision 1.02 Sep 10, 2013 EQ-DCM User Manual www.equustek.com Revision 1.02 Sep 10, 2013 Contents INTRODUCTION...5 ABOUT THIS MANUAL... 5 INTENDED AUDIENCE... 5 HARDWARE SPECIFICATIONS...6 PHYSICAL SPECIFICATIONS... 6 HARDWARE

More information

Instruction Bulletin

Instruction Bulletin Instruction Bulletin 63249-401-200/A4 03/2005 POWERLINK TM G3 Controller NF1000G3 for use with POWERLINK G3 Systems Retain for future use. NOTICE Read these instructions carefully and look at the equipment

More information

Square D Clipsal Pascal Automation Controller

Square D Clipsal Pascal Automation Controller Square D Clipsal Pascal Automation Controller SLC5500PACA For Use with Wired C-Bus Networks Instruction Bulletin Retain for future use. Square D Clipsal Pascal Automation Controller 63249-420-258A2 Instruction

More information

Installation and Programming Manual

Installation and Programming Manual PMN Manual PMN Installation and Programming Manual This Manual describes the PMN PowerLogic Modbus Plus Network module, its uses and set up. Effective: 12 August, 1999 Niobrara Research & Development Corporation

More information

PowerLogic ION7550 RTU option

PowerLogic ION7550 RTU option 70052-0213-02 PRODUCT OPTION 01/2011 PowerLogic ION7550 RTU option The PowerLogic ION7550 Remote Terminal Unit (RTU) option is designed for data acquisition from WAGES (water, air, gas, electricity, steam)

More information

ABB Drives. User s Manual. Modbus Adapter Module RMBA-01

ABB Drives. User s Manual. Modbus Adapter Module RMBA-01 ABB Drives User s Manual Modbus Adapter Module RMBA-01 Modbus Adapter Module RMBA-01 User s Manual 3AFE 64498851 REV A EN EFFECTIVE: 1.3.2002 2002 ABB Oy. All Rights Reserved. Safety instructions Overview

More information

Ethernet Serial Server

Ethernet Serial Server Ethernet Serial Server Users Manual Eport-101, Eport-102, Eport-104, Eport108 1 INTRODUCTION... 1 1.1 FEATURES... 1 1.2 PRODUCT SPECIFICATIONS... 2 1.3 DEFAULT SETTINGS... 3 2 COMMUNICATION MODES... 4

More information

SCADAPack Input/Output Module Hardware Manual. Version: February 2016

SCADAPack Input/Output Module Hardware Manual. Version: February 2016 SCADAPack Version: Date: February 2016 Table of Contents 1 Legal Information...6 2 Technical Support...7 3 Safety Information...8 4 Documentation...11 Check 5 About this Manual...13 6 About the 5607 I/O

More information

General Specifications. P2-SCM Serial Communications

General Specifications. P2-SCM Serial Communications General Specifications Module Type Intelligent Modules per Base I/O Points Used Field Wiring Connector Operating Temperature Storage Temperature Humidity Environmental Air Vibration Shock Field to Logic

More information

3710 ACM 3750 PDC 3800 RTU. ISOCOM Communications Card Retrofit Instructions

3710 ACM 3750 PDC 3800 RTU. ISOCOM Communications Card Retrofit Instructions 3710 ACM 3750 PDC 3800 RTU ISOCOM Communications Card Retrofit Instructions Danger During normal operation of this device, hazardous voltages are present which can cause severe injury or death. These

More information

CONTROL MICROSYSTEMS Analog Output Module. Hardware Manual

CONTROL MICROSYSTEMS Analog Output Module. Hardware Manual 5304 Analog Output Module Hardware Manual CONTROL MICROSYSTEMS SCADA products... for the distance 48 Steacie Drive Telephone: 613-591-1943 Kanata, Ontario Facsimile: 613-591-1022 K2K 2A9 Technical Support:

More information

SCADAPack Smart RTU

SCADAPack Smart RTU SCADAPack 330 334 Smart RTU 1 Built on the proven SCADAPack 300 platform, the SCADAPack 330 and 334 feature high-performance 32-bit processing, highspeed LAN, serial and USB communications, integrated

More information

MGate MB3000 Modbus Gateway User Manual

MGate MB3000 Modbus Gateway User Manual MGate MB3000 Modbus Gateway User Manual Sixth Edition, July 2012 www.moxa.com/product 2012 Moxa Inc. All rights reserved. MGate MB3000 Modbus Gateway User s Manual The software described in this manual

More information

16/24 Port 10/100 Auto-Sensing Dual Speed Ethernet Switch

16/24 Port 10/100 Auto-Sensing Dual Speed Ethernet Switch 12 Omnitron Systems Technology, Inc. Omnitron Systems Technology, Inc. 1 FlexSwitch TM 600X 16/24 Port /0 -Sensing Dual Speed Ethernet Switch User s ual 27 Mauchly #201, Irvine, CA 92618 (949) 250-65 Fax:

More information

INSTALLATION INSTRUCTIONS

INSTALLATION INSTRUCTIONS INSTALLATION INSTRUCTIONS BACnet Communication Card RXRX-AY01 RECOGNIZE THIS SYMBOL AS AN INDICATION OF IMPORTANT SAFETY INFORMATION! WARNING THESE INSTRUCTIONS ARE INTENDED AS AN AID TO QUALIFIED, LICENSED

More information

User Manual Revision English

User Manual Revision English Document code: MN67562_ENG Revision 1.005 Page 1 of 14 User Manual Revision 1.005 English PROFIBUS Slave / Modbus Slave - Converter (Order Code: HD67562) for Website information: www.adfweb.com?product=hd67562

More information

ControlKeeper 4. General Information. Connecting Relay Loads. Installation Sheet. Getting Started. Power Supply Wiring. Mounting the Cabinet

ControlKeeper 4. General Information. Connecting Relay Loads. Installation Sheet. Getting Started. Power Supply Wiring. Mounting the Cabinet General Information ControlKeeper 4 Installation Sheet Model# CK4-120NO- Model# CK4-277NO The ControlKeeper-4 model is shipped in one package and is configured with either a 120V or a 277V transformer.

More information

CONTROL MICROSYSTEMS. SCADAPack 100 Controller. Hardware Manual

CONTROL MICROSYSTEMS. SCADAPack 100 Controller. Hardware Manual SCADAPack 100 Controller Hardware Manual CONTROL MICROSYSTEMS SCADA products... for the distance 48 Steacie Drive Telephone: 613-591-1943 Kanata, Ontario Facsimile: 613-591-1022 K2K 2A9 Technical Support:

More information

ABLELink. Modbus Gateway MB5000 Series User s Manual

ABLELink. Modbus Gateway MB5000 Series User s Manual ABLELink MB5000 Series User s Manual Version 1.1 Updated in March, 2010 TEL: 886-3-5508137 FAX: 886-3-5508131 http://www.atop.com.tw Table of Contents Table of Contents... 2 Introduction... 4 Features...

More information

User's Manual PLC09 Modbus Converter for PAL-AT Leak Detection System

User's Manual PLC09 Modbus Converter for PAL-AT Leak Detection System User's Manual PLC09 Modbus Converter for PAL-AT Leak Detection System PermAlert ESP, Inc. 7720 Lehigh Ave. Niles, IL 60714 847-966-2190 2 INDEX 1.0 Introduction 4 1.1 Features 4 2.0 Installation 4 2.1

More information

4170 POS System Installation Guide

4170 POS System Installation Guide 4170 POS System 4170 Installation Guide Thank you for selecting UTC RETAIL s innovative Model 4170 Point of Sale solution! This Installation Guide will help you efficiently install the 4170 POS. The document

More information

CONTROL MICROSYSTEMS and 5407 Relay Output Module. Hardware Manual

CONTROL MICROSYSTEMS and 5407 Relay Output Module. Hardware Manual 506 and 507 Relay Output Module Hardware Manual CONTROL MICROSYSTEMS SCADA products... for the distance Steacie Drive Telephone: 63-59-93 Kanata, Ontario Facsimile: 63-59-0 KK A9 Technical Support: -6-676

More information

EcoStruxure Power Commission Installation Guide

EcoStruxure Power Commission Installation Guide EcoStruxure Power Commission DOCA0134EN 03/2019 EcoStruxure Power Commission Installation Guide 03/2019 DOCA0134EN-04 www.schneider-electric.com The information provided in this documentation contains

More information

IO-AO6X I/O Expansion Module 6 Isolated Analog Outputs

IO-AO6X I/O Expansion Module 6 Isolated Analog Outputs IO-AO6X I/O Expansion Module 6 Isolated Analog Outputs The IO-AO6X is an I/O Expansion Module that can be used in conjunction with specific Unitronics OPLC controllers. The module offers 6 12-bit isolated

More information

Application Note: Using Modbus With the Conext CL Series. Important Safety Instructions

Application Note: Using Modbus With the Conext CL Series. Important Safety Instructions : Using Modbus With the Conext CL Series 976-0317-01-01 Rev A Important Safety Instructions READ AND SAVE THESE INSTRUCTIONS - DO NOT DISCARD This document contains important safety instructions that must

More information

Schneider Electric Floating License Manager

Schneider Electric Floating License Manager Schneider Electric Floating License Manager EIO0000001078 11/2012 Schneider Electric Floating License Manager User Manual 12/2012 EIO0000001078.01 www.schneider-electric.com The information provided in

More information

Installation and Setup

Installation and Setup 1 2 Setup In This Chapter.... Installing the Ethernet Base Controller EBC Network Identifiers Setting the Node Address 10BaseT / 100BaseT Network Cabling Maximum 10BaseT / 100BaseT Cable Length Specifications

More information

CONTROL MICROSYSTEMS and 5404 Digital Input Module. Hardware Manual

CONTROL MICROSYSTEMS and 5404 Digital Input Module. Hardware Manual 503 and 50 Digital Input Module Hardware Manual CONTROL MICROSYSTEMS SCADA products... for the distance Steacie Drive Telephone: 63-59-93 Kanata, Ontario Facsimile: 63-59-0 KK A9 Technical Support: -6-676

More information

MGate MB3000 Modbus Gateway User s Manual

MGate MB3000 Modbus Gateway User s Manual User s Manual Seventh Edition, May 2013 www.moxa.com/product 2013 Moxa Inc. All rights reserved. User s Manual The software described in this manual is furnished under a license agreement and may be used

More information

Modbus Installation and Troubleshooting for AP9635/AP9635CH Network Management Card By Gary Ware. Introduction

Modbus Installation and Troubleshooting for AP9635/AP9635CH Network Management Card By Gary Ware. Introduction [ APPLICATION NOTE #168 ] APPLICATION NOTE #xx Modbus Installation and Troubleshooting for AP9635/AP9635CH By Gary Ware PROJECT AT A GLANCE Project Type Modbus installation Applications Data centers with

More information

NCOM SERIAL DEVICE SERVER 1XX SERIES USER S MANUAL

NCOM SERIAL DEVICE SERVER 1XX SERIES USER S MANUAL NCOM SERIAL DEVICE SERVER 1XX SERIES USER S MANUAL 2017-07-07 Edition Titan Electronics Inc. Web: www.titan.tw Contents 1. INTRODUCTION... 4 1.1 Key Features... 5 1.2 Specifications... 6 2. PANEL LAYOUT

More information

ADAM-4510 RS-422/RS-485 Repeater ADAM-4510S Isolated RS-422/485 Repeater ADAM-4520 Isolated RS-422/485 Converter Startup Manual

ADAM-4510 RS-422/RS-485 Repeater ADAM-4510S Isolated RS-422/485 Repeater ADAM-4520 Isolated RS-422/485 Converter Startup Manual ADAM-510 RS-/RS-85 Repeater ADAM-510S Isolated RS-/85 Repeater ADAM-50 Isolated RS-/85 Converter Startup Manual Packing List Before you begin installing your module, please make sure that the following

More information

MODEL CIO-EN MODBUS/TCP, MODBUS/RTU I/O MODULE

MODEL CIO-EN MODBUS/TCP, MODBUS/RTU I/O MODULE INSTALLATION INSTRUCTIONS Revision B1 Rapid City, SD, USA, 05/2009 MODEL CIO-EN MODBUS/TCP, MODBUS/RTU I/O MODULE BE SURE POWER IS DISCONNECTED PRIOR TO INSTALLATION! FOLLOW NATIONAL, STATE AND LOCAL CODES.

More information

NCOM SERIAL DEVICE SERVER 4XX SERIES USER S MANUAL

NCOM SERIAL DEVICE SERVER 4XX SERIES USER S MANUAL NCOM SERIAL DEVICE SERVER 4XX SERIES USER S MANUAL 2017-07-07 Edition Titan Electronics Inc. Web: www.titan.tw Contents 1. INTRODUCTION... 4 1.1 Key Features... 5 1.2 Specifications... 6 2. PANEL LAYOUT

More information

General Operating, Maintenance and Installation Manual

General Operating, Maintenance and Installation Manual General Operating, Maintenance and Installation Manual Hardware Platform for Protocol Converter Small Embedded Controller - SEC2-91056 Erlangen Telephone +49 9131 92076-0 Fax: +49 9131 92076-10 Internet:

More information

RS-232 / RS-422 / RS-485 over Fast Ethernet Media Converter

RS-232 / RS-422 / RS-485 over Fast Ethernet Media Converter RS-232 / RS-422 / RS-485 over Fast Ethernet Media Converter Serial Interface One RS-232/422/485 port to one 100Base-FX Media Converter Cost-effective solution for RS-232 to Ethernet application Supports

More information

User Manual Revision English

User Manual Revision English Document code: MN67251_ENG Revision 1.001 Page 1 of 18 User Manual Revision 1.001 English NMEA 2000 / DeviceNet - Converter (Order Code: HD67251-A1 - HD67251-A3 - HD67251-A4) for Website information: www.adfweb.com?product=hd67251-a1

More information

Conettix ITS-D6682-INTL

Conettix ITS-D6682-INTL Conettix ITS-D6682-INTL EN Installation Guide Ethernet Network Adapter Conettix ITS-D6682-INTL Installation Guide Contents Contents 1.0 Introduction... 3 1.1 Network Interface... 3 1.2 Serial Interface...

More information

Installation and User Guide

Installation and User Guide Installation and User Guide Trademarks and Notices Notice Comtrol Corporation. SPECIFICALLY DISCLAIMS THE IMPLIED WARRANTIES OF MERCHANTABILITY AND FITNESS OF THIS PRODUCT FOR A PARTICULAR PURPOSE. Comtrol

More information

ICP PANEL-TEC PEX3000 II

ICP PANEL-TEC PEX3000 II ICP PANEL-TEC PEX3000 II MODBUS PORT EXPANDER INSTALLATION AND OPERATION GUIDE REVISION HISTORY Revision Date Author Comments 000 29 Aug 2008 Keira Majors Initial release. 001 16 Sep 2008 David Walker

More information

Installing and Configuring Rialto Analytic Appliances

Installing and Configuring Rialto Analytic Appliances Installing and Configuring Rialto Analytic Appliances Important Safety Information This manual provides installation and operation information and precautions for the use of this camera. Incorrect installation

More information

Setting up a Serial to Ethernet Adapter to Work with a Siemens Milltronics Instrument and KEPServerEX

Setting up a Serial to Ethernet Adapter to Work with a Siemens Milltronics Instrument and KEPServerEX Data Communications Reference AG020716 Setting up a Serial to Ethernet Adapter to Work with a Siemens Milltronics Instrument and KEPServerEX Objective: Equipment: To communicate with a Siemens Milltronics

More information

Modbus Plus to Ethernet Bridge 174 CEV User Guide

Modbus Plus to Ethernet Bridge 174 CEV User Guide 31005104 2/2010 Modbus Plus to Ethernet Bridge 174 CEV 200 40 User Guide 2/2010 31005104.03 www.schneider-electric.com The information provided in this documentation contains general descriptions and/or

More information

Unity Pro OSLoader User Manual

Unity Pro OSLoader User Manual Unity Pro 35006156 12/2015 Unity Pro OSLoader User Manual 12/2015 35006156.14 www.schneider-electric.com The information provided in this documentation contains general descriptions and/or technical characteristics

More information

SCADAPack E Operational Reference Manual

SCADAPack E Operational Reference Manual SCADAPack E Operational Reference Manual 2 SCADAPack E Operational Reference Manual Table of Contents Part I SCADAPack E Operational Reference 5 1 Technical... Support 5 2 Safety... Information 6 3 Preface...

More information

TRP-C37M User s Manual

TRP-C37M User s Manual TRP-C37M User s Manual MODBUS TCP to RTU/ASCII Gateway Printed May. 2011 Rev 1.1 Trycom Technology Co., Ltd 1F, No.2-11, Sihu street, Yingge Township, Taipei, Taiwan ROC Tel: 886-2-86781191, Fax: 886-2-86781172

More information

MT8050iE series. Installation Instruction (1) (2)

MT8050iE series. Installation Instruction (1) (2) MT8050iE series 3 Installation Instructions Installation Instruction Secure the operator panel in position, using all the fastening holes and the provided brackets and screws: (A) 1 Installation and Startup

More information

485DRCI. Industrial RS-232 to RS-422/485 Converter B&B ELECTRONICS PRODUCT INFORMATION. Specifications Serial Technology

485DRCI. Industrial RS-232 to RS-422/485 Converter B&B ELECTRONICS PRODUCT INFORMATION. Specifications Serial Technology 485DRCI RS-232 RS-485 2-Wrie RS-422/485 4-Wire RS-232 CON. RS-422/485 CON. Data Rate Isolation Surge Protection Industrial Bus Source Input Voltage Power Consumption Connector p/n 7207r3 485DRCI-4108ds

More information

SCADAPack E Input/Output Module Hardware Manual. Version: March 2016

SCADAPack E Input/Output Module Hardware Manual. Version: March 2016 SCADAPack E Version: Date: March 2016 Table of Contents 1 Legal Information...6 2 Technical Support...7 3 Safety Information...8 4 Documentation...11 Check 5 About this Manual...13 6 About the 5606 I/O

More information

Serial to Ethernet Converter

Serial to Ethernet Converter Serial to Ethernet Converter User s Manual Version 1.1 2004 Infosystem Technology Corporation Disclaimers The information in this manual has been carefully checked and is believed to be accurate. Infosystem

More information

USER S MANUAL. PH485Ex1. #1 RS-485 Serial Port to Ethernet, Terminal Server/Client. Doc No: PH485Ex1-UM-001 IPEX. (IP Electronix)

USER S MANUAL. PH485Ex1. #1 RS-485 Serial Port to Ethernet, Terminal Server/Client. Doc No: PH485Ex1-UM-001 IPEX. (IP Electronix) USER S MANUAL PH485Ex1 Doc No: PH485Ex1-UM-001 #1 RS-485 Serial Port to Ethernet, Terminal Server/Client IPEX (IP Electronix) Contents 1. INTRODUCTION... 3 2. SPECIFICATIONS... 3 3. PACKAGE CHECKLIST...

More information