MicroTech II Remote I/O Panel Installation Manual

Size: px
Start display at page:

Download "MicroTech II Remote I/O Panel Installation Manual"

Transcription

1 MicroTech II Remote I/O Panel Installation Manual Installation Manual IM Group: Controls Part Number: IM 783 Date: November 2006 Supersedes: IM 783-1

2 Table of Contents Notice... 3 Reference Documents... 3 Revision History... 3 Introduction... 4 Panel Location and Mounting... 5 Unpack the Remote I/O Panel... 5 Physical Installation... 5 Tools Required... 5 Before Installation... 5 Mounting... 5 Opening and Closing the Cover... 8 Opening the Cover of a Remote I/O Panel... 8 Closing the Cover of a Remote I/O Panel...8 Field Wiring... 9 Power Wiring... 9 About the Transformer... 9 Connecting Power to the Transformer... 9 Remote I/O Modules Mounting Remote I/O Modules General Control Wiring of Remote I/O Modules Designation of Remote I/O Modules Maintenance Cleaning Parts List Warranty Warranty Return Material Procedure Replacement Parts Page 2 IM 783-2

3 Notice McQuay International reserves the right to change any information contained herein without prior notice. The user is responsible for determining whether this product is appropriate for his or her application. The following are trademarks or registered trademarks of their respective companies. LONWORKS from Echelon Corporation; McQuay and MicroTech II from McQuay International. Reference Documents Company Number Title Available At: McQuay International McQuay International OM 780 MicroTech II Chiller System Manager Operation Manual IM 781 MicroTech II Chiller System Manager Installation Manual All McQuay documents are available at Revision History IM February 28, 2004 First release. IM July 7, 2004 Revised Standard Replacement Parts List. IM August 26, 2004 Added hardwired to Designation of Remote I/O modules section. IM November 28, 2006 Changed entire panel enclosure and wiring schematic per new supplier. IM Page 3

4 Introduction The MicroTech II Remote I/O panel consists of a sheet metal enclosure housing a transformer, and remote I/O modules. These modules provide additional input/output for use with a Chiller System Manager (CSM) supervisory controller. These modules communicate with the supervisory controller via a two wire LONWORKS communications network. The panel can be mounted at strategic locations around the building, near the controlled devices to avoid long runs of control wires back to the supervisory controller. A CSM can control pumps, fans, valves, boilers, etc. The supervisory controllers use remote I/O modules as an expandable platform of inputs and outputs to control different size pump stations, cooling towers, etc. For example, a large chiller plant may have more secondary pumps to control than a smaller plant and fewer remote I/O modules are required to control the smaller plant. Remote I/O modules are not application specific. All the application software resides in the CSM supervisory controller. This means that the same remote I/O modules are used on a CSM. Remote I/O modules may be purchased and mounted in the field. They can also be purchased pre-mounted in a remote I/O panel ready for wall mounting. A remote I/O panel may have from one to four remote I/O modules. The number of modules per panel is determined by job requirements. See the installation manual of the supervisory controller to determine specific uses for the modules. Each module provides the following input/outputs: 4 Universal Inputs 4 Digital Inputs 4 Relay Outputs (normally-open contacts rated for Volts) 2 Analog Outputs (0-10 Volts DC) Remote I/O panels come with either 120 volt or a 240 volt power supplies. See the part number designation table below: Table 1. Remote I/O Panel Part Numbers Number of Modules per Panel 120 Volt 240 Volt ! WARNING Electric shock hazard. Can cause personal injury or equipment damage. This equipment must be properly grounded to the MicroTech II control panel. Connections and service must be performed by trained personnel with experience with the equipment being controlled. Static sensitive components. Can cause equipment damage.! CAUTION Discharge any static electrical charge by touching the bare metal inside the control panel before performing any service work. Never unplug cables, circuit board terminal blocks, or power plugs while power is applied to the panel. Page 4 IM 783-2

5 Panel Location and Mounting Unpack the Remote I/O Panel Unpack the remote I/O panel and inspect the contents of the package for damaged or missing components. If damaged, notify the appropriate carrier at once and contact your local McQuay representative for immediate repair or replacement. Physical Installation Tools Required The following tools and supplies may be required for installation: Small flat-blade screwdriver: used for terminal connections Phillips screwdriver: used to secure the door Before Installation To reduce the risk of condensation resulting from shipping at low temperatures, keep the remote I/O panel at room temperature for at least 24 hours before applying power. Avoid mounting this panel in areas where high electromagnetic interference (EMI) can affect its operation. Mounting Mount the remote I/O panel in a location that allows clearance for wiring, servicing, and module removal. For mounting details and drill hole locations, refer to the Mounting Guide and Mounting Details, Figure 1 and Figure 2. Mount the remote I/O panel within the maximum node-to-node distance to another node of your LONWORKS network. See IM 781 for detail on LONWORKS network wiring and maximum node-to-node distance charts. On a typical network this means the panel must be mounted within 820 ft (250 m) of the nearest LONWORKS device (other devices can be the CSM, a chiller, another remote I/O module, etc). This typical node-to-node distance can be increased to a maximum of 8855-ft (2700 m) by using thicker cable (up to 16 AWG) and doubly terminated networks. This product is intended for indoor use only. Do not expose this unit to ambient conditions outside of the range of 0 to 50 C (32 to 122 F) and relative humidity outside the range 5% to 90%, non-condensing (pollution degree 1). If the controller is mounted inside an enclosure, that enclosure must be designed to keep the unit within its required operating range, considering 40-watts heat dissipation. This is especially important if the panel is mounted inside an enclosure with other heat dissipating equipment. For proper mounting clearances see Figure 2. Minimum clearance from the wall on which the unit is mounted is 0.2 inches (provided by the dimpled mounting feet). Provide ample space so that airflow is not blocked behind the unit. DO NOT mount the unit: In an area where excessive moisture, corrosive fumes, or explosive vapors may be present. Where vibration or shock is likely to occur. In a location subject to electrical noise. This includes large electrical contactors, electrical machinery, variable frequency drives, welding equipment, spark igniters, and other equipment of this nature. The unit is designed to be wall mounted with the transformer situated towards the top of the unit. For the maximum airflow, do not mount the unit oriented in any other way. IM Page 5

6 Figure 1. Remote I/O Panel Mounting Guide Ø.312" (0.79cm).406" (1.03cm) Ø.5" (1.27cm) DETAIL KEYHOLE Upper Mounting Remote I/O Panel Mounting Guide " (45.4cm) Mount with this end up. Note: Drawing not to scale. Verify all measurements before drilling. Lower mounting holes are 0.312" (0.79cm) dia. Clearance for a ¼ screw. 11" (27.94cm) Page 6 IM 783-2

7 Figure 2. Remote I/O Mounting Detail IM Page 7

8 Opening and Closing the Cover Opening the Cover of a Remote I/O Panel Note: The cover is held closed with a latch. The latch requires a tool, such as a straight-blade screw driver, to open. To open, insert a straight-blade screw driver in the screw slot (latch), located on the front cover of the remote I/O panel. Rotate the latch 90 degrees counter-clockwise. The cover will now swing open. Closing the Cover of a Remote I/O Panel Close the cover and insert a straight-blade screw driver in the screw slot, located on the front cover of the remote I/O panel. Rotate the latch 90 degrees clockwise. The cover is now locked shut. Page 8 IM 783-2

9 Field Wiring Following are descriptions of the various field-wiring requirements. Wiring must comply with the National Electrical Code and all local codes and ordinances. Failures caused, or contributed to, by wiring not in accordance with these instructions will not be covered under McQuay International s standard warranty policy. Power Wiring Building power is wired to the transformer supplied with the remote I/O panel. Wire the transformer to an external switch or breaker, as there is no disconnect switch in the unit. Some local codes require the switch to be in sight of the unit. The switch must be capable of 120VAC or 240VAC service (depending on model) to switch the transformer primary. About the Transformer The remote I/O panel ships with a 120VAC or 208/240VAC (depending on model), 40 VA, 50/60 Hz transformer. The transformer provides 24-volt power to the remote I/O modules. The panel ships with from one to four remote I/O modules. Each module requires 10 VA of power. Do not power other devices from this transformer. The following things should be noted about the remote I/O panel transformer:! WARNING Improper wiring can cause severe personal injury or death. All connections must be made in accordance with national and local electrical codes. Use copper conductors only. The transformer must be dedicated to running the devices in the remote I/O panel. Do not power other devices from the transformer. Do not use any other power source or otherwise defeat the isolation provided by the integral transformer. A twowire power source, including a 24V transformer, can cause permanent damage or greatly shorten the life of the unit.! CAUTION Verify that neither wire of the transformer's secondary winding is connected to earth ground or building neutral. Ground loops on the analog inputs and outputs can result and damage the modules or connected equipment. Connecting Power to the Transformer The following procedure is provided for supplying high voltage power to the remote I/O panel: 1. Remove the ½ knockout provided above the transformer. 2. Run the electrical supply wires through the knockout hole. 3. Using the provided two-position terminal block, connect high voltage power to the transformer primary lead wires. 4. Connect a ground wire to the grounding lug provided. IM Page 9

10 ! CAUTION Do not run LONWORKS communication wiring alongside higher-voltage supply or higher-voltage control wiring. Communication problems over the LONWORKS network can occur. On 120 VAC models, connect 120 VAC, 50/60 Hz power to the two position terminal block provided using the information in Table 2. Table VAC models building power termination Type of Wire Building Power Source Typical Color of Wire Termination point Ungrounded Hot Black Either empty terminus of the terminal block Grounded Neutral White Other empty terminus of the terminal block Grounding Ground Green or bare copper Grounding stud On 240 VAC models, connect 208/240 VAC, 50/60 Hz power to the two-position terminal block provided using the information in Table 3. The transformer s primary wiring is factory wired to the terminal block for 240 VAC power. If your power supply is closer to 208 VAC, switch the primary wiring from 240 VAC to 208 VAC by replacing the orange wire in the terminal block with the red wire from the transformer. The remote I/O modules require 24 VAC ± 20%. Table 3. International Models VAC models building power termination Type of Wire Building Power Source Typical Color of Wire Termination point Ungrounded Hot Brown Either empty terminus of the terminal block Ungrounded--Hot Blue Other empty terminus of the terminal block Grounding Ground Green or bare copper Grounding stud When power is supplied to the remote I/O module, a green LED appears. The LED is located on the lower left-hand side on the top of the module. Page 10 IM 783-2

11 Figure 3. Remote I/O Panel General Wiring Diagram Power Supply 120 VAC or 208/240 VAC (depending on model) If the module s relay outputs will be controlling high voltage (230 Volt maximum) devices, bring high voltage control wires to modules 3 and 4 through the top of the panel. Transformer Primary Ground 24 VAC High Voltage Terminals-Orange High Voltage Terminals-Orange 4 th Remote I/O Module 3 rd Remote I/O Module Low Voltage Terminals-Brown Low Voltage Terminals-Brown Blue Yellow Blue Yellow Bring low voltage control wires and LonWorks network cable in through the sides of the panel. Yellow Blue Low Voltage Terminals-Brown Yellow Blue Low Voltage Terminals-Brown Bring low voltage control wires and LonWorks network cable in through the sides of the panel. 2 nd Remote I/O Module 1 st Remote I/O Module High Voltage Terminals-Orange High Voltage Terminals-Orange Legend If the module s relay outputs will be controlling high voltage (230 Volt maximum) devices, bring high voltage control wires to modules 1 and 2 through the bottom of the panel. Notes Factory wiring Field wiring Field wiring terminal 1. Depending on the model ordered, the panel will contain from 1 to 4 modules. Additional modules may be purchased separately and added to a panel in the field. 2. See the supervisory controller installation manual (e.g. IM-781 for the Chiller System Manager) for wiring diagrams of the control wiring. IM Page 11

12 Remote I/O Modules Mounting Remote I/O Modules Each remote I/O module mounts on a DIN rail. The modules are snapped in place on the rail. To remove a module from a rail, slip a flat-head screwdriver into the stirrup located on the base of the module (center tab under the brown terminals). Gently pull the stirrup away from the housing while lifting up on the module. General Control Wiring of Remote I/O Modules The remote I/O panel comes with the 24 VAC power wires supplied from the transformer to the modules. All control wiring is field supplied in accordance with the CSM supervisory controller Installation Manual with which the panel will be used. All wiring must comply with applicable electrical codes and ordinances. Note: Terminals on the remote I/O module accept wire from 20 AWG (0.5 mm 2 ) to 14 AWG (2.5 mm 2 ). Each remote I/O module is equipped with four 230 VAC, digital outputs (i.e. relays). Two are normally open (N.O.) and two are changeover (C.O.) relays. All four normally open contacts are rated for 6 amps continuous current while the normally closed contacts of the two C.O. relays are rated for 1 amp continuous current. These high-voltage relay terminals are the orange touchless terminals on the module (separated from the brown low-voltage terminals). The modules are mounted so that the orange high-voltage terminals are directed toward the top and bottom of the remote I/O panel to keep high-voltage wiring separated from low-voltage wiring (see Figure 3). If you are wiring to remote I/O modules mounted in the remote I/O panel and high-voltage devices are being switched, run the wiring from these devices into the top or bottom of the panel. Connect these wires directly into the touchless orange relay terminals on the high voltage side of the module. Wire the low-voltage and communication wiring into the sides of the panel and connect these wires directly into the brown terminals on the low-voltage side of the modules. If these relays are used for control of high-voltage devices, the wiring must be run separately from any low-voltage wiring. Do not mix relay control of high voltage and low voltage devices on the same module.! WARNING Electric shock hazard. Can cause personal injury or equipment damage. If the remote I/O module relay outputs will be switching higher voltage devices, higher voltage wiring must be run separately from low voltage wiring. Do not mix low-voltage and higher-voltage wires on the relay side (orange terminals) of a remote I/O module. Note: Local wiring guidelines may take precedence over recommendations provided in these instructions. Page 12 IM 783-2

13 Designation of Remote I/O Modules When you receive a remote I/O module(s) in a remote I/O panel, it has not yet been assigned a designation (meaning it has not yet been assigned to be Hardwired, Remote A, Remote B, etc.). The module only becomes a Remote I/O module A (or B, or C, etc.) or a Remote I/O module for Hardwired Chillers after it has been commissioned into the CSM s LONWORKS communications network. This assignment is accomplished at the Device Addressing screen of the CSM user interface. To designate a remote I/O module(s), go to the Device Addressing tab in the CSM user interface. The Device Addressing screen contains both a Chiller table and a Remote I/O table. To designate a remote I/O module, click on the Service Pin button associated with the appropriate Remote I/O device (e.g. Remote I/O - A) in the Remote I/O table. While the Service Pin timer is counting down, (the timer appears as a pop-up box on the screen) press down on the Service Pin button located on the remote I/O module. After you have assigned a module, label it for future reference. Labels are included with the remote I/O panel for this purpose. To designate a module as Hardwired, follow these steps using the CSM user interface: 1. Navigate to the Chiller table 2. Click on the dropdown menu and change the default in the Hardwire Selection field from MicroTech II to Hardwired 3. Click on the Service Pin button associated with that chiller. 4. While the Service Pin timer is counting down, (the timer appears as a pop-up box on the screen) press down on the Service Pin button located on the remote I/O module. 5. After you have assigned a module, label it for future reference. Labels are included with the remote I/O panel for this purpose. IM Page 13

14 Maintenance This section provides information on the following topics: Cleaning Replacement Parts Cleaning If dust or metal filings are present inside the unit, clean with vacuum or compressed air. Otherwise, no cleaning inside the unit is required. Optionally, if the outside of the metal enclosure becomes dirty, you can wipe it with a damp cloth and mild detergent. Parts List Standard replacement parts are listed in Table 4 and can be ordered from stock without restriction. Standard replacement parts cannot be returned for credit and should be disposed of in an appropriate manner. Table 4. Standard Replacement Parts Part Number Description Remote I/O panel Transformer, 120V Remote I/O panel Transformer, 208/240V Remote I/O module Page 14 IM 783-2

15 Warranty Consult your local McQuay Representative for warranty details. Refer to Form Y. To find your local McQuay Representative, go to Warranty Return Material Procedure Defective material may not be returned without prior authorization of authorized factory service personnel of McQuay International in Minneapolis, Minnesota, phone number (763) A "Return Goods" tag must be included with the returned material. Enter the required information to expedite handling and prompt issuance of credits. All parts must be returned to the appropriate McQuay facility, designated on the "Return Goods" tag. Transportation charges must be prepaid. The return of the part does not constitute an order for replacement. Therefore, a purchase order must be entered through the nearest McQuay representative. The order should include part number, model number, and serial number of the unit involved. Credit will be issued on customer's purchase order following an inspection of the returned part and upon determination that the failure is due to defective material or workmanship during the warranty period. Replacement Parts When writing to McQuay for service or replacement parts, refer to the model number and serial number of the unit as stamped on the serial plate attached to the unit. If replacement parts are required, include the date of installation of the unit and date of the failure, along with an explanation of the malfunctions and a description of the replacement parts required. IM Page 15

16 This document contains the most current product information as of this printing. For the most up to-date product information, please go to www. mcquay.com (800)

MicroTech II TM Remote I/O Panel Installation Manual

MicroTech II TM Remote I/O Panel Installation Manual Installation Manual IM 783-0 MicroTech II TM Remote I/O Panel Installation Manual Group: Controls Part Number: IM 783-0 Date: February 2004 Supersedes: New 2004 McQuay International Page 2 IM-783 Table

More information

MicroTech II Applied TM Rooftop Unit Controller and Self-Contained Unit Controller BACnet TM MSTP Communication Module

MicroTech II Applied TM Rooftop Unit Controller and Self-Contained Unit Controller BACnet TM MSTP Communication Module Installation and Maintenance Manual IM 704-3 Group: Controls Part Number: IM 704-3 Date: November 2004 Supersedes: IM 704-2 MicroTech II Applied TM Rooftop Unit Controller and Self-Contained Unit Controller

More information

MicroTech II TM Applied Rooftop Unit Controller and Self-Contained Unit Controller BACnet TM Communication Module BACnet/IP

MicroTech II TM Applied Rooftop Unit Controller and Self-Contained Unit Controller BACnet TM Communication Module BACnet/IP Installation and Maintenance Manual IM 703-3 Group: Controls Part Number: IM 703-3 Date: November 2004 Supersedes: IM 703-2 MicroTech II TM Applied Rooftop Unit Controller and Self-Contained Unit Controller

More information

MicroTech III Applied Terminal Systems BACnet MS/TP Communication Module

MicroTech III Applied Terminal Systems BACnet MS/TP Communication Module Installation and Maintenance Manual IM 928-2 Group: Controls Part Number: 669207702 Date: March 2011 Supersedes: IM 928-1 MicroTech III Applied Terminal Systems BACnet MS/TP Communication Module NOTICE

More information

MicroTech III Water Source Heat Pump BACnet MS/TP Communication Module

MicroTech III Water Source Heat Pump BACnet MS/TP Communication Module Installation and Maintenance Manual IM 928- Group: Controls Part Number: 66920770 Date: July 2009 Supersedes: IM 928 MicroTech III Water Source Heat Pump BACnet MS/TP Communication Module NOTICE Use this

More information

MicroTech III McQuay Chiller Unit Controller BACnet Communication Module (MS/TP)

MicroTech III McQuay Chiller Unit Controller BACnet Communication Module (MS/TP) Installation and Maintenance Manual IM 967 Group: Controls Part Number: IM 967 Date: October 2009 Supercedes: New MicroTech III McQuay Chiller Unit Controller BACnet Communication Module (MS/TP) Pathfinder

More information

Sapling Converter Box

Sapling Converter Box Installation Manual Sapling Converter Box SCB-100-000-1 Version Number 1.2 Current as of March 15, 2015 The Sapling Company, Inc. (+1) 215.322.6063 P. (+1) 215.322.8498 F. 2-Wire Converter Box (SCB-100-000-1)

More information

Junos WebApp Secure 5.0 Hardware Guide

Junos WebApp Secure 5.0 Hardware Guide Junos WebApp Secure 5.0 Hardware Guide Junos WebApp Secure 5.0 Hardware Guide This document contains a specification for the MWS1000 hardware appliance, as well as instructions for installation into a

More information

MicroTech III Chiller Unit Controller BACnet IP Communication Module

MicroTech III Chiller Unit Controller BACnet IP Communication Module Installation and Maintenance Manual IM 966 Group: Controls Part Number: IM 966 Date: October 2009 Supercedes: New MicroTech III Chiller Unit Controller BACnet IP Communication Module Pathfinder Chiller,

More information

MicroTech II Applied Rooftop Unit Controller and Self-Contained Unit Controller BACnet Communication Module MS/TP

MicroTech II Applied Rooftop Unit Controller and Self-Contained Unit Controller BACnet Communication Module MS/TP Installation and Maintenance Manual IM 704-4 Group: Controls Part Number: IM 704 Date: August 2007 Supersedes: IM 704-3 MicroTech II Applied Rooftop Unit Controller and Self-Contained Unit Controller BACnet

More information

Temperature. Power requirements. Weight. Dimensions

Temperature. Power requirements. Weight. Dimensions Installing the Tracer Summit BMTX Building Control Unit Ordering numbers: BMTX001AAB000, BMTX001AAB010, BMTX001AAB001, BMTX001AAB011, BMTX001BAB000, BMTX001BAB010, BMTX001BAB001, BMTX001BAB011, BMTX001DAB000

More information

MicroTech II Applied Rooftop Unit Controller and Self-Contained Unit Controller BACnet Communication Module BACnet/IP

MicroTech II Applied Rooftop Unit Controller and Self-Contained Unit Controller BACnet Communication Module BACnet/IP Installation and Maintenance Manual IM703-2 Group: McQuay Controls Date: February 2002 MicroTech II Applied Rooftop Unit Controller and Self-Contained Unit Controller BACnet Communication Module BACnet/IP

More information

Model HU-224/225. Technical Information TI.224/ Humidity Transduce r FOR ADDITIONAL INFORMATION SEE HU-224/225 DATA SHEET

Model HU-224/225. Technical Information TI.224/ Humidity Transduce r FOR ADDITIONAL INFORMATION SEE HU-224/225 DATA SHEET Model /225 FOR ADDITIONAL INFORMATION SEE /225 DATA SHEET SPECIFICATIONS Accuracy*: ± 2% / ± 3% RH Range: 0-100% RH Hysteresis: ± 1% Supply Voltage:12-40 VDC 12-35 VAC (VDC output units only) Supply Current:

More information

P216 Series Condenser Fan Speed Controller

P216 Series Condenser Fan Speed Controller P216 Series Condenser Fan Speed Controller Installation Instructions P216xxx-x Part No. 24-85895-18, Rev. D Issued 27 August 2015 Applications Refer to the QuickLIT website for the most up-to-date version

More information

TraceTek Leak Detection Master Module Installation Instructions TOOLS REQUIRED STORAGE

TraceTek Leak Detection Master Module Installation Instructions TOOLS REQUIRED STORAGE TTDM-128 TraceTek Leak Detection Master Module Installation Instructions TRACETEK APPROVALS AND CERTIFICATIONS TYPE NM General Signaling Equipment 76LJ GENERAL INFORMATION Please read these instructions

More information

Installing the Tracer MP503 Input/Output Module Ordering number: ,

Installing the Tracer MP503 Input/Output Module Ordering number: , Installing the Tracer MP503 Input/Output Module Ordering number: 4950 0490, 4950 0590 Product overview The Tracer MP503 input/output (I/O) module is a field-installed device used to monitor inputs and

More information

Content. Product Description

Content. Product Description EY-modulo 4 EY-RU482F001 Room Operating Unit with Display for Fan Coil applications EY-RU483F001 Room Operating Unit with Display for VAV applications en Guidelines for the electrician Content 1 Product

More information

INSTRUCTION MANUAL. Instruction Manual. Analog Multi-Tube Vortexer Digital Multi-Tube Vortexer

INSTRUCTION MANUAL. Instruction Manual. Analog Multi-Tube Vortexer Digital Multi-Tube Vortexer INSTRUCTION MANUAL Instruction Manual Analog Multi-Tube Vortexer Digital Multi-Tube Vortexer Table of Contents Package Contents............ 1 Warranty............ 1 Installation............ 2 Maintenance

More information

Operating instructions. Switching amplifier DN0210 DN / / 2015

Operating instructions. Switching amplifier DN0210 DN / / 2015 Operating instructions Switching amplifier DN0210 DN0220 UK 80011079 / 00 01 / 2015 Contents 1 Preliminary note...4 1.1 Symbols used...4 1.2 Warning signs used...4 2 Safety instructions...5 2.1 General...5

More information

Replacing the Power Supply

Replacing the Power Supply APPENDIX B This appendix includes information on how to replace the power supply for the Cisco AS550XM universal gateway and contains the following sections: Safety Recommendations, page B-1 Required Tools

More information

IQ-SBS LCU Series Installation Instructions

IQ-SBS LCU Series Installation Instructions Installation Instructions LCU-1 The IQ-SBS LCU-1 is a self-contained device for integrating control of facility lighting with IQ-SBS. The LCU-1 controls lighting zones, accepts input from override switches

More information

Installation Instructions

Installation Instructions 50ES, 50EZ, 50GL, 50GS, 50GX, 50JS, 50JX, 50JZ, 50SD, 50SZ, 50VL, 50VT, 50XP, 50XZ 601A, 602A, 602B, 604A, 604B, 604D, 607C, 701A, 702A, 702B, 704A, 704B, 704D, 707C PA1P, PA2P, PA3P, PH1P, PH2P, PH3P

More information

CMSA-100 Manual. Cinema Media Server Automation

CMSA-100 Manual. Cinema Media Server Automation CMSA-100 Manual Cinema Media Server Automation 181 Bonetti Drive San Luis Obispo, CA 93401-7397 USA Phone: +1 805 549 0161 Fax: +1 805 549 0163 www.uslinc.com Table of Contents 1. Safety Notice... 3 2.

More information

JanusRAID SA-6692J Hardware User Manual

JanusRAID SA-6692J Hardware User Manual JanusRAID SA-6692J Hardware User Manual 42-30000-5067 SATA II JBOD enclosure Version 1.1 SA-6692J SATA II JBOD enclosure Hardware User Manual Table of Contents Preface... i Chapter 1 System Requirements

More information

REDUNDANCY MODULE TSP-REM360 AND TSP-REM600

REDUNDANCY MODULE TSP-REM360 AND TSP-REM600 REDUNDANCY MODULE TSP-REM360 AND TSP-REM600 Operating Instructions Seite 1 Dimensions drawings: TSP-REM360 Weight: 0.882lb Gewicht: 0.40kg Seite 2 Dimensions drawings: TSP-REM600 Bottom view Top view Side

More information

Secured Series: Hub Plus Kit Single Door Controller Package Installation Manual

Secured Series: Hub Plus Kit Single Door Controller Package Installation Manual Secured Series: Hub Plus Kit Single Door Controller Package Installation Manual This package is designed to simplify the connections to our Secured Series Hub Plus Controller. This will translate into

More information

Torque Series LCD Remote Panel Installation/Operation Manual Model: TQ-DSP-12/24

Torque Series LCD Remote Panel Installation/Operation Manual Model: TQ-DSP-12/24 Torque Series LCD Remote Panel Installation/Operation Manual Model: TQ-DSP-12/24 Section Page Introduction 1 Materials Provided 1 I) Safety Instructions 1 A) Inverter Safety Instructions 1 B) Battery Safety

More information

RE-82 RACK MOUNT DIMMER OWNERS MANUAL. 8 X 2400Watts. Revision /29/2007

RE-82 RACK MOUNT DIMMER OWNERS MANUAL. 8 X 2400Watts. Revision /29/2007 RE-82 RACK MOUNT DIMMER 8 X 2400Watts OWNERS MANUAL Revision 2.4 11/29/2007 Page 2 of 8 RE-82 CONTROL PANEL DESCRIPTION The RE-82 is an 8 channel dimmer with a maximum capacity of 2,400 watts per channel

More information

PLC Racks IC697CHS782/783

PLC Racks IC697CHS782/783 5 1 PLC Racks IC697CHS782/783 (IC697CHS782/783) datasheet Features Accepts 3rd Party VME modules which require 0.8 spacing. Accepts all IC697 PLC module types. Rear mount rack mounts in a 10 (254 mm) deep

More information

MicroTech III Rooftop and Self Contained Unit Controller BACnet IP Communication Module

MicroTech III Rooftop and Self Contained Unit Controller BACnet IP Communication Module Installation and Maintenance Manual IM 916-2 Group: Controls Part Number: IM 916 Date: October 2009 Supercedes: IM 916-1 MicroTech III Rooftop and Self Contained Unit Controller BACnet IP Communication

More information

INSTALLATION INSTRUCTIONS

INSTALLATION INSTRUCTIONS TT-40 9/0 INSTALLATION INSTRUCTIONS Original Issue Date: 9/0 Model: Automatic Transfer Switches Equipped with the Programmable Controller Market: ATS Subject: External Battery Supply Module Kit GM69-KP

More information

Rhino Buffer Module PSM24-BFM600S. Operating Instructions

Rhino Buffer Module PSM24-BFM600S. Operating Instructions Rhino Buffer Module PSM24-BFM600S Operating Instructions RHINO BUFFER MODULE PSM24-BFM600S Description The PSM24-BFM600S Buffer Module will hold the output voltage of a 24 VDC power supply after brownouts

More information

MicroTech Series-100 Application Specific Controller

MicroTech Series-100 Application Specific Controller Installation & Maintenance Data IM 657-1 Group: Controls Part Number: 594861Y Date: March 1998 MicroTech Series-100 Application Specific Controller a0196 1998 McQuay International Contents Contents...2

More information

Component identification

Component identification IO-ATC8 I/O Expansion Module 8 Analog/Thermocouple Inputs The IO-ATC8 is an I/O Expansion Module that can be used in conjunction with specific Unitronics OPLC controllers. The module offers 8 inputs that

More information

Overview These instructions are presented as a guideline for installing and setting up the LX Series Breaker Control Panel.

Overview These instructions are presented as a guideline for installing and setting up the LX Series Breaker Control Panel. LX Breaker Control Panels Installation and Setup Procedure Hubbell Building Automation, Inc. 9601 Dessau Road Building One Suite 100 Austin, Texas 78754 512-450-1100 512-450-1215 Fax www.hubbell-automation.com

More information

Hardware Installation. Tracer MP581 Programmable Controller CNT-SVN01C-EN

Hardware Installation. Tracer MP581 Programmable Controller CNT-SVN01C-EN Hardware Installation Tracer MP581 Programmable Controller CNT-SVN01C-EN Hardware Installation Tracer MP581 Programmable Controller CNT-SVN01C-EN November 2005 Tracer MP581 Programmable Controller Hardware

More information

When any of the following symbols appear, read the associated information carefully. Symbol Meaning Description

When any of the following symbols appear, read the associated information carefully. Symbol Meaning Description Uni-I/O Modules Installation Guide UID-0808R, UID-0808T, UID-1600,UID-0016R, UID-0016T Uni-I/O is a family of Input/Output modules that are compatible with the UniStream control platform. This guide provides

More information

Upgrading and Servicing Guide

Upgrading and Servicing Guide Upgrading and Servicing Guide The only warranties for Hewlett-Packard products and services are set forth in the express statements accompanying such products and services. Nothing herein should be construed

More information

Configurable Output Distribution. 120V / 208V / 240V 60Hz. User Manual English

Configurable Output Distribution. 120V / 208V / 240V 60Hz. User Manual English Configurable Output Distribution 120V / 208V / 240V 60Hz User Manual English TABLE OF CONTENTS IMPORTANT SAFETY INSTRUCTIONS.......................... 1 GLOSSARY OF SYMBOLS....................................

More information

This Datasheet for the IC697CHS790. Rack, 9 Slots, Rear Mount.

This Datasheet for the IC697CHS790. Rack, 9 Slots, Rear Mount. This Datasheet for the IC697CHS790 Rack, 9 Slots, Rear Mount. http://www.cimtecautomation.com/parts/p-14771-ic697chs790.aspx Provides the wiring diagrams and installation guidelines for this GE Series

More information

LONWORKS Plug-In Software

LONWORKS Plug-In Software Installation and Maintenance Manual IM 933 Group: McQuay Controls Part Number: IM 933 Date: September 2008 Supercedes: New LONWORKS Plug-In Software For use with the MicroTech III Unitary Controller -

More information

MicroTech II McQuay Maverick II Rooftop Unit Controller BACnet Communication Module, Ethernet or IP

MicroTech II McQuay Maverick II Rooftop Unit Controller BACnet Communication Module, Ethernet or IP Installation and Maintenance Manual IM 853 Group: Controls Part Number: IM 853 Date: June 2007 Supercedes: New MicroTech II McQuay Maverick II Rooftop Unit Controller BACnet Communication Module, Ethernet

More information

Customer Upgrade Procedure

Customer Upgrade Procedure Customer Upgrade Dell EMC Unity Family Dell EMC Unity All Flash and Unity Hybrid Adding an optional 80-drive DAE disk drive 302-003-780 REV 01 July 2017 This document describes how to add an optional 80-drive

More information

Elapsed Timer Control Panel

Elapsed Timer Control Panel Installation Manual V6.2 Elapsed Timer Control Panel Current as of August 2017 The Sapling Company, Inc. Elapsed Timer Control Panel Table of Contents Table of Contents 2 Important Safety Instructions

More information

Common to all H3DS. Installation of Screw-Less Clamp Models. Tools. Applicable Wires. Applicable Screwdriver. Applicable Wire Sizes

Common to all H3DS. Installation of Screw-Less Clamp Models. Tools. Applicable Wires. Applicable Screwdriver. Applicable Wire Sizes Common to all H3DS Installation of Screw-Less Clamp Models Tools A flat-blade screwdriver should be used to mount the cables. Timers Applicable Screwdriver Flat-blade, Parallel-tip, 2.5 mm diameter Flat-blade,

More information

Solar Combiner Enclosure

Solar Combiner Enclosure Installation Instructions Solar Combiner Enclosure Catalog Numbers 1000-SB006, 1000-SB012 Topic Page Description 1 Important Safety Instructions 3 Nameplate Data 4 Planning for Installation 4 Install the

More information

Emerson Network Power provides customers with technical support. Users may contact the nearest Emerson local sales office or service center.

Emerson Network Power provides customers with technical support. Users may contact the nearest Emerson local sales office or service center. Liebert PSA iton User Manual Version: V2.8 Revision date: November 14, 2005 Emerson Network Power provides customers with technical support. Users may contact the nearest Emerson local sales office or

More information

When any of the following symbols appear, read the associated information carefully. Symbol Meaning Description

When any of the following symbols appear, read the associated information carefully. Symbol Meaning Description Uni-I/O Modules Installation Guide UIA-0402N Uni-I/O is a family of Input/Output modules that are compatible with the UniStream control platform. This guide provides basic installation information for

More information

This Datasheet for the IC670GBI002 24VDC BUS INTERFACE UNIT.

This Datasheet for the IC670GBI002 24VDC BUS INTERFACE UNIT. This Datasheet for the IC670GBI002 24VDC BUS INTERFACE UNIT http://www.qualitrol.com/shop/p-14508-ic670gbi002.aspx Provides the wiring diagrams and installation guidelines for this GE Field Control module.

More information

Operating instructions. Speed monitor D / / 2014

Operating instructions. Speed monitor D / / 2014 Operating instructions Speed monitor D200 80005257 / 00 05 / 2014 Contents 1 Preliminary note...4 1.1 Symbols used...4 1.2 Warning signs used...4 2 Safety instructions...5 2.1 General...5 2.2 Target group...5

More information

PanelView Plus/VersaView CE Terminals and Display Modules

PanelView Plus/VersaView CE Terminals and Display Modules Installation Instructions PanelView Plus/VersaView CE Terminals and Display Modules (Catalog Numbers 2711P-xxxxxx, 6182H-xxxxxx) English Inside: Overview...2 For More Information...2 Modular Components...3

More information

PHASETRONICS. SCR Power Control Specialists. EP1 Series Power Control Single Phase SCR Amps OPERATION & SERVICE MANUAL

PHASETRONICS. SCR Power Control Specialists. EP1 Series Power Control Single Phase SCR Amps OPERATION & SERVICE MANUAL PHASETRONICS Specialists EP1 Series Power Control Single Phase SCR 10-50 Amps OPERATION & SERVICE MANUAL Phasetronics, Inc. P.O. Box 5988 1600 Sunshine Drive Clearwater, FL 33765 (727)573-1900 FAX(727)573-1803

More information

Obtaining Documentation and Submitting a Service Request, page xvii Safety Warnings, page xvii Safety Guidelines, page xx

Obtaining Documentation and Submitting a Service Request, page xvii Safety Warnings, page xvii Safety Guidelines, page xx Preface Obtaining Documentation and Submitting a Service Request, page xvii Safety s, page xvii Safety Guidelines, page xx Obtaining Documentation and Submitting a Service Request For information on obtaining

More information

When any of the following symbols appear, read the associated information carefully. Symbol Meaning Description

When any of the following symbols appear, read the associated information carefully. Symbol Meaning Description Uni-I/O Wide Modules Installation Guide UID-W1616R, UID-W1616T Uni-I/O Wide is a family of Input/Output modules that are compatible with the UniStream control platform. Wide Modules are 1.5 times as wide

More information

BACnet VAV Actuator Start-up Guide IM 1040

BACnet VAV Actuator Start-up Guide IM 1040 BACnet VAV Actuator Start-up Guide IM 1040 Group: Controls Part Number: IM 1040 Date: 3/4/2010 Supersedes: New BACnet VAV Actuator--Electronic Output Start-up Procedures 2010 McQuay International Table

More information

User's Guide. Phase Sequence and Motor Rotation Tester Model

User's Guide. Phase Sequence and Motor Rotation Tester Model User's Guide Phase Sequence and Motor Rotation Tester Model 480403 Introduction Congratulations on your purchase of the Extech Model 408403 Motor and Phase Rotation Indicator. This handheld instrument

More information

Customer Replacement Procedure

Customer Replacement Procedure Customer Replacement Dell EMC Unity Family Dell EMC Unity All Flash and Unity Hybrid Replacing a faulted 80-drive DAE cooling module 302-003-777 REV 01 July 2017 This document describes how to replace

More information

MicroTech II BACnet Communication Module Ethernet/IP

MicroTech II BACnet Communication Module Ethernet/IP Installation & Maintenance Manual IM703-1 Group: McQuay Controls Date: November 2001 MicroTech II BACnet Communication Module Ethernet/IP ASHRAE 135, Annex J 10 BASE-T 2001 McQuay International Contents

More information

Series Amp Pad Mount Quick Connect Input and Output Power Panels

Series Amp Pad Mount Quick Connect Input and Output Power Panels Series 300 2000-4000 Amp Pad Mount Quick Connect Input and Output Power Panels DANGER is used in this manual to warn of a hazard situation which, if not avoided, will result in death or serious injury.

More information

VSD-1MC MANUAL 0-10V / 4-20mA Variable Speed Module with Manual Override

VSD-1MC MANUAL 0-10V / 4-20mA Variable Speed Module with Manual Override MANUAL 0-10V / 4-20mA Variable Speed Module with Manual Override Varifan 3 4 5 6 7 MANUAL 2 8 1 OFF 10 9 AUTO MANUAL SPEED Installation / User s Guide This guide will inform the electrician on proper wiring

More information

When any of the following symbols appear, read the associated information carefully. Symbol Meaning Description

When any of the following symbols appear, read the associated information carefully. Symbol Meaning Description Vision OPLC V350-35-R34/V350-J-R34 Installation Guide The Unitronics V350-35-R34/V350-J-R34 offers the following onboard I/Os: 22 Digital Inputs, configurable via wiring to include 2 Analog and 3 HSC/Shaft-encoder

More information

Installation, Operation and Maintenance Manual

Installation, Operation and Maintenance Manual Document 481200 VGD-100 Vari-Green Drive Installation, Operation and Maintenance Manual Please read and save these instructions for future reference. Read carefully before attempting to assemble, install,

More information

When any of the following symbols appear, read the associated information carefully. Symbol Meaning Description

When any of the following symbols appear, read the associated information carefully. Symbol Meaning Description Uni-I/O Modules Installation Guide UID-0808THS Uni-I/O is a family of Input/Output modules that are compatible with the UniStream control platform. This guide provides basic installation information for

More information

EX-RC1 Remote I/O Adapter

EX-RC1 Remote I/O Adapter EX-RC1 Remote I/O Adapter The EX-RC1 interfaces between Unitronics Vision OPLCs and remote I/O Expansion Modules distributed throughout your system. The adapter is connected to a PLC via CANbus. Each adapter

More information

Installation and Maintenance Manual IM Replacement Intelligent Equipment Gateway

Installation and Maintenance Manual IM Replacement Intelligent Equipment Gateway Installation and Maintenance Manual IM 1229 Group: Controls Replacement Intelligent Equipment Gateway Commercial Rooftop Models: DPS and MPS Applied Rooftop Models: RDS and RPS Part Number: 910159718 Date:

More information

DCM Digital Control Modules

DCM Digital Control Modules DCM Digital Control Modules TECHNICAL MANUAL Version 1.2 November 2011 Safety Precautions Caution Read Instructions: Read and understand all safety and operating instructions before using the equipment.

More information

Preparing to Install the VG248

Preparing to Install the VG248 CHAPTER 2 To ensure normal system operation, plan your site configuration and prepare your site before installation. Before installing the VG248, review these sections: Preparing the Installation Site,

More information

ORB TM 4-20 ma Input Box Installation & Operation Manual

ORB TM 4-20 ma Input Box Installation & Operation Manual IOM ORB TM 4-20 ma Input Box Installation & Operation Manual ORB TM 4-20 ma Input Box Installation & Operation Manual CONTENTS I. HANDLING & STORAGE... 1 Inspection and Handling Disposal and Recycling

More information

Specifications, Installation, and Operating Instructions

Specifications, Installation, and Operating Instructions Specifications, Installation, and Operating Instructions Model: Power Vantage AC Panel Protector CAUTION: The installation of a surge protection device () must be done by qualified electrical personnel.

More information

STR-3 STANDARD 3-PHASE 230 VAC TRANSFORMER CONTROLLER. Mounting and operating instructions

STR-3 STANDARD 3-PHASE 230 VAC TRANSFORMER CONTROLLER. Mounting and operating instructions STANDARD 3-PHASE 230 VAC TRANSFORMER CONTROLLER Mounting and operating instructions Table of contents SAFETY AND PRECAUTIONS 3 PRODUCT DESCRIPTION 4 ARTICLE CODES 4 INTENDED AREA OF USE 4 TECHNICAL DATA

More information

Installation Job Aid for VSP 4850GTS

Installation Job Aid for VSP 4850GTS Installation Job Aid for VSP 4850GTS Notices Release 6.1.0.0 NN46251-308 Issue 02.01 November 2017 Notice paragraphs alert you about issues that require your attention. The following paragraphs describe

More information

S66 Series Electronic Fan Speed Control

S66 Series Electronic Fan Speed Control FANs 121, 125, 1628.3 Product/Technical Bulletin S66 Issue Date 0918 S66 Series Electronic Fan Speed Control The S66 Series Electronic Fan Speed Control is designed to modulate the speed of single-phase,

More information

BS 181 SINGLE CHANNEL POWER SUPPLY USER MANUAL

BS 181 SINGLE CHANNEL POWER SUPPLY USER MANUAL BS 181 SINGLE CHANNEL POWER SUPPLY USER MANUAL Issue 2011 ASL Intercom BV DESIGNED & MANUFACTURED BY: ASL Intercom B.V. Zonnebaan 42 3542 EG Utrecht The Netherlands Tel: +31 (0)30 2411901 Fax: +31 (0)30

More information

MicroTech II McQuay Maverick II Rooftop Unit Controller BACnet Communication Module (MS/TP)

MicroTech II McQuay Maverick II Rooftop Unit Controller BACnet Communication Module (MS/TP) Installation and Maintenance Manual IM 852-2 Group: Controls Part Number: IM 852 Date: January 2008 Supercedes: IM 852-1 MicroTech II McQuay Maverick II Rooftop Unit Controller BACnet Communication Module

More information

When any of the following symbols appear, read the associated information carefully. Symbol Meaning Description

When any of the following symbols appear, read the associated information carefully. Symbol Meaning Description Uni-I/O Modules Installation Guide UIS-04PTN Uni-I/O is a family of Input/Output modules that are compatible with the UniStream control platform. This guide provides basic installation information for

More information

Installing the Cisco AS5400XM Universal Gateway

Installing the Cisco AS5400XM Universal Gateway CHAPTER 3 Installing the Cisco AS5400XM Universal Gateway This chapter guides you through the installation of the Cisco AS5400XM universal gateway and includes the following sections: Setting Up the Chassis,

More information

High Speed Remote I/O Module

High Speed Remote I/O Module High Speed Remote I/O Module EXF-RC15 The Unitronics EXF-RC15 is a High Speed Remote I/O Module that offers three High Speed Counter inputs and four high speed outputs. Overall, the EXF-RC15 offers 9 digital

More information

Model 2380 Rack-Mount Kit

Model 2380 Rack-Mount Kit Keithley Instruments 28775 Aurora Road Cleveland, Ohio 44139 1-800-935-5595 http://www.tek.com/keithley Model 2380 Rack-Mount Kit Installation Instructions Introduction The Model 2380 Fixed Rack-Mount

More information

D-Pack 6 Classic ORDERCODE 50315

D-Pack 6 Classic ORDERCODE 50315 D-Pack 6 Classic ORDERCODE 50315 Congratulations! You have bought a great, innovative product from Showtec. The Showtec D-Pack 6 Classic brings excitement to any venue. Whether you want simple plug-&-play

More information

NI PXIe-1062Q Power Supply Shuttle

NI PXIe-1062Q Power Supply Shuttle USER GUIDE NI PXIe-1062Q Power Supply Shuttle The NI PXIe-1062Q power supply shuttle is a replacement part for the NI PXIe-1062Q chassis. Caution This power supply is not compatible with any other National

More information

The power behind competitiveness. Delta Infrasuite Power Management. Power Distribution Unit. User Manual.

The power behind competitiveness. Delta Infrasuite Power Management. Power Distribution Unit. User Manual. The power behind competitiveness Delta Infrasuite Power Management Power Distribution Unit User Manual www.deltapowersolutions.com Save This Manual This manual contains important instructions and warnings

More information

Power Supply Installation

Power Supply Installation Power Supply Module Overview, on page Installation Guidelines, on page 4 Installing or Replacing an AC Power Supply, on page 6 Installing a DC Power Supply, on page 7 Finding the Power Supply Module Serial

More information

COBEX RECORDERS, INC.

COBEX RECORDERS, INC. INSTALLATION, OPERATION AND SERVICE INSTRUCTIONS FOR CIRCULAR CHART RECORDERS COBEX RECORDERS, INC. CAUTION: IT IS IMPORTANT THAT THESE INSTRUCTIONS BE READ BEFORE INSTALLING THE INSTRUMENT. KEEP THESE

More information

FLEX Ex Spring Clamp Terminal Base

FLEX Ex Spring Clamp Terminal Base Installation Instructions FLEX Ex Spring Clamp Terminal Base (Cat. No. 1797-TB3S) 1 10 11 4 Only remove this cover plug if connecting another terminal base unit. 3 5 6 12 2 7 8 9 41253 Component Identification

More information

PDS8u POWER DISTRIBUTION SYSTEM USER'S MANUAL

PDS8u POWER DISTRIBUTION SYSTEM USER'S MANUAL PDS8u POWER DISTRIBUTION SYSTEM USER'S MANUAL 1 IMPORTANT SAFETY INSTRUCTION READ FIRST This symbol, whenever it appears, alerts you to the presence of uninsulated dangerous voltage inside the enclosure-voltage

More information

Model HM-535 Power Supply Installation and Service Instructions

Model HM-535 Power Supply Installation and Service Instructions Model HM-535 Power Supply Installation and Service Instructions 430-535 0104 2004 Heritage MedCall, Inc SENTRY INSTALLATION & SERVICE INSTRUCTIONS POWER SUPPLY UNIT Model HM-535 IMPORTANT SAFETY INSTRUCTIONS

More information

When any of the following symbols appear, read the associated information carefully. Symbol Meaning Description

When any of the following symbols appear, read the associated information carefully. Symbol Meaning Description Uni-I/O Wide Modules Installation Guide UIS-WCB1 Uni-I/O Wide is a family of Input/Output modules that are compatible with the UniStream control platform. Wide Modules are 1.5 times as wide as Uni-I/O

More information

Hardware Reference Guide For Thin Clients

Hardware Reference Guide For Thin Clients b Hardware Reference Guide For Thin Clients Document Part Number: 254241-001 July 2002 This book provides basic hardware information for this series of Compaq Thin Clients. Å WARNING: Ä CAUTION: 2002 Compaq

More information

SLATE. Digital I/O Module INSTALLATION INSTRUCTIONS R8001D4001

SLATE. Digital I/O Module INSTALLATION INSTRUCTIONS R8001D4001 SLATE Digital I/O Module R8001D4001 INSTALLATION INSTRUCTIONS Scan for more information Application SLATE brings configurable safety and programmable logic together into one single platform. The platform

More information

To connect the AC adapter:

To connect the AC adapter: Replacing the AC Adapter Replacing the AC Adapter 3 Plug the power cord into a wall outlet. The power indicator turns on. To connect the AC adapter: Connect the power cord to the AC adapter. Power indicator

More information

hp uninterruptible power system r12000 xr models installation instructions

hp uninterruptible power system r12000 xr models installation instructions hp uninterruptible power system r000 xr models installation instructions Overview These instructions show how to install an uninterruptible power system (UPS). For detailed information about the UPS, refer

More information

SGI InfiniteStorage 120

SGI InfiniteStorage 120 SGI InfiniteStorage 120 Mass Storage Hardware Topics Edition 003 007-4853-003 Proprietary Rights Notices COPYRIGHT 2006, 2007 SGI. All rights reserved; provided portions may be copyright in third parties,

More information

ENCL-MZ800-WAL ENCL-MX800-PAN MNL TAC I/A Series MicroNet MN 800 Series Controller Installation Instructions. Application.

ENCL-MZ800-WAL ENCL-MX800-PAN MNL TAC I/A Series MicroNet MN 800 Series Controller Installation Instructions. Application. TAC 1354 Clifford Avenue P. O. Box 2940 Loves Park, IL 61132-2940 www.tac.com ENCL-MZ800-WAL ENCL-MX800-PAN MNL-800-101 TAC I/A Series MicroNet MN 800 Series Controller Installation Instructions Application

More information

S4112-ON Series. Setup Guide

S4112-ON Series. Setup Guide S4112-ON Series Setup Guide Notes, cautions, and warnings NOTE: A NOTE indicates important information that helps you make better use of your product. CAUTION: A CAUTION indicates either potential damage

More information

Vision OPLC V TR6/V350-J-TR6

Vision OPLC V TR6/V350-J-TR6 Vision OPLC V350-35-TR6/V350-J-TR6 Installation Guide The Unitronics V350-35-TR6/V350-J-TR6 offers the following onboard I/Os: 8 Digital Inputs, configurable via wiring to include 2 Analog (current/voltage)

More information

Model 2380 Rack-Mount Kit

Model 2380 Rack-Mount Kit Keithley Instruments 28775 Aurora Road Cleveland, Ohio 44139 1-800-935-5595 http://www.tek.com/keithley Model 2380 Rack-Mount Kit Installation Instructions Introduction The Model 2380 Fixed Rack-Mount

More information

HITACHI. EH-150 series PLC EH-RTD8 Resistance Temperature Detective input module Instruction manual. Safety precautions

HITACHI. EH-150 series PLC EH-RTD8 Resistance Temperature Detective input module Instruction manual. Safety precautions HITACHI EH-150 series PLC Resistance Temperature Detective input module Instruction manual Thank you for purchasing a Hitachi Programmable Logic Controller. To operate it safely, please read this instruction

More information

HomeWorks Remote Power Feed-Through Panels

HomeWorks Remote Power Feed-Through Panels power feed-through panels are available in two different sizes, each of which may be either surface-mounted or recess-mounted, in an electrical closet or other equipment room. The number of remote power

More information

Lexmark X203n and X204n Series. Maintenance Guide

Lexmark X203n and X204n Series. Maintenance Guide Lexmark X203n and X204n Series Maintenance Guide February 2011 www.lexmark.com Contents...3 Cleaning the exterior of the printer...3 Cleaning the scanner glass...4 Cleaning the ADF separator rollers...5

More information

Model P4017 Single Channel USB Oscilloscope. Quick Start Guide

Model P4017 Single Channel USB Oscilloscope. Quick Start Guide Model P4017 Single Channel USB Oscilloscope Quick Start Guide General Warranty BNC warrants that the product will be free from defects in materials and workmanship for 3 years from the date of purchase

More information