For Classroom Use Only! Flying Start PowerFlex 755 AC Drives

Similar documents
Bus Regulation. PowerFlex 755 AC Drives. For Classroom Use Only!

Size, Select and Configure Kinetix and PowerFlex Drives Using Motion Analyzer. For Classroom Use Only!

Product Compatibility and Download Center

Product Compatibility and Download Center

L12 - Studio 5000 and Logix: Basics Lab. For Classroom Use Only!

Basic Drive Programming PowerFlex 755 Basic Start Up

L01 - Effective Design Methods for Integrating Safety Using Logix Controllers. For Classroom Use Only!

GV3000/SE General Purpose (Volts/Hertz) and Vector Duty AC Drive, HP, 230V AC

L09 - Drive Configuration & Programming Lab. For Classroom Use Only!

L18 - PowerFlex Drives Configuration & Programming. For Classroom Use Only!

PowerMonitor 5000 Unit Catalog Number Upgrade

FlexPak 3000 Drive Operator Interface Module (OIM) User s Guide

GuardLogix Controller to Kinetix 6000 Drive with Safe-Off using EtherNet/IP CompactBlock Guard I/O Module

GV3000/SE 230 VAC 1-20 HP General Purpose (Volts/Hertz) and Vector Duty Drive Software Start-Up and Reference Manual Version 6.04

Sizing PlantPAx System Architecture for Optimal Performance. For Classroom Use Only!

Studio 5000 Architect Getting Results Guide

PowerMonitor 1000 Unit Catalog Number Upgrade

Micro800 Programming Basics. For Classroom Use Only!

Color-Sensing Connected Components Building Block. Quick Start

Using GuardShield Light Curtains (Safe 4, Micro 400, or 440L), with ArmorBlock Guard I/O and SmartGuard Controller

Micro800 Programming Basics. For Classroom Use Only!

Allen-Bradley Motors

LiquiFlo AC General Purpose (Volts/Hertz) and Vector Duty Drive Software Start-Up and Reference Manual Version 6.4

InView Firmware Update

Simple Package Measurement Connected Components Building Block. Quick Start

Differential Liquid/Gas Pressure Transmitter

PCI Expansion Slot Kit for 6181P (1500P) Series D Integrated Display Computer

ProcessLogix R510.0 Server Installation Instructions

1336 PLUS II Quick Start Guide

Application Technique. Safety Function: Safety Camera with E-stop

CS3000 MMI SW-Version 6.1 Control and Configuration Software for FlexPak3000 V , GV3000 V and Liqui-Flo. Instruction Manual

Advanced PLC Topics for Micro800 Controllers with Motion Capabilities and CIP Messaging Functionality. For Classroom Use Only!

DriveGuard. Safe-Off Option for PowerFlex 70 AC Drives. User Manual.

Micro800 Programmable Controllers: Getting Started with Motion Control Using a Simulated Axis

Introduction to Micro800 Motion. For Classroom Use Only!

Firmware Manual - EC Series Drives

Throughout this manual we use notes to make you aware of safety considerations:

Teaching Color-Sensing Connected Components Building Block. Quick Start

Micro800 Controllers Starter Pack Quick Start

Using TLS3-GD2 Guardlocking Interlock with ArmorBlock Guard I/O and SmartGuard Controller

Pump Station Controller. Quick Start

The Guardmaster 440C-CR30 Software Configurable Safety Relay Training Demo Lab. For Classroom Use Only!

PowerFlex 70 Safe-Off Control EtherNet/IP Guard I/O Safety Module and GuardLogix Integrated Safety Controller

Position Control via HMI Connected Components Building Block. Quick Start

SequenceManager Controls

Simple Motion Control Connected Components Building Block. Quick Start

Solar Combiner Enclosure

1336-Series Drives to PowerFlex 750-Series Drives

Micro800 Programmable Controllers

ControlLogix Redundancy Update and Module Replacement Guidelines

GuardLogix: Dual Zone Gate Protection with E-stop and Trojan Interlock Switch

GuardLogix: TLS Guardlocking Application

GuardLogix: Safety Gate Application with SensaGuard Switch

Installation Instructions

Installation Instructions

Kinetix 6000 Axis Module and Shunt Module

Catalog Numbers 9308-RSFB64ENE, 9308-RSFB256ENE, 9308-RSFB1024ENE

PowerFlex 700S Drives with Phase II Control (4.002)

Distributed Power System SA3100 Drive Configuration and Programming

ControlLogix SIL2 System Configuration

PowerFlex 700H Drive Firmware (Revision )

GV3000/SE Operator Interface Module (OIM) User Guide Version 2.0 M/N 2RK3000

Installation Instructions

Kinetix 300 Memory Module Programmer

Import/Export Project Components. Programming Manual

L07 - Micro800 PLC Programming with Connected Components Workbench Software. For Classroom Use Only!

Using a Guard Locking Interlock Switch and Light Curtains with DeviceNet Guard I/O and a GuardLogix Controller

CompactLogix Power Supplies Specifications

Adapter Kit for PanelView 1200/1200e Touch Screen Terminal Cutout

DeviceNet Network Configuration

L14 - Speed Integration with Ethernet-enabled CENTERLINE MCCs, Rockwell Software Studio 5000 and IntelliCENTER Software

User Manual. PowerFlex 525 Embedded EtherNet/IP Adapter

PowerFlex 525 DeviceNet Adapter

PanelViewt 1200 Transfer Utility User Manual

Using the 20-HIM-A6 HIM with the LiquiFlo 2.0 AC Drive 20-HIM-A6 Firmware Revision Number or Later

PowerFlex 700H AC Drive Safe Torque Off Option

Unidrive M400 (Frame 1 to 4) Quick Start Guide

InView Communication Modules

Logix5000 Controllers Function Block Diagram

Extending FactoryTalk View Site Edition with ACP ThinManager and Relevance. Doug Coulter

Unidrive M200, M201 (Frame 1 to 4) Quick Start Guide

L11 - FactoryTalk View Site Edition - Building Applications Lab. For Classroom Use Only!

Digital ac/dc (24V) Input Module

Bulletin 1395 ControlNet TM Communication Board

FactoryTalk View Site Edition - Building Applications Lab. For Classroom Use Only!

Orientation F7 Drive Software Technical Manual

SMVector Additional I/O Module Installation and Operation Manual

GV3000/SE AC Drive Quick Reference Version 6.06

PlantPAx Logix Batch and Sequence Manager

Logix5000 Control Systems: Connect a PanelView Plus Terminal over an EtherNet/IP Network

PowerFlex 20-HIM-A6 and 20-HIM-C6S HIM Firmware Revision 1.006

NHP SAFETY REFERENCE GUIDE

QUICK REFERENCE GUIDE

Conext CL-60 Inverter Firmware Upgrade Process

Reliance GV3000 Drive Registers

Getting Results Guide. FactoryTalk Gateway

Profibus DP Expansion Board

AC Variable Speed Drive 0.75kW 250kW / 1HP 350HP Volt 1 & 3 Phase. Advanced User Guide Revision 2.00

Quick Start. PowerFlex 750-Series AC Drives

Quick Start Guide For GVX9000 AF Drives

Transcription:

For Classroom Use Only! Flying Start PowerFlex 755 AC Drives

Important User Information This documentation, whether, illustrative, printed, online or electronic (hereinafter Documentation ) is intended for use only as a learning aid when using Rockwell Automation approved demonstration hardware, software and firmware. The Documentation should only be used as a learning tool by qualified professionals. The variety of uses for the hardware, software and firmware (hereinafter Products ) described in this Documentation, mandates that those responsible for the application and use of those Products must satisfy themselves that all necessary steps have been taken to ensure that each application and actual use meets all performance and safety requirements, including any applicable laws, regulations, codes and standards in addition to any applicable technical documents. In no event will Rockwell Automation, Inc., or any of its affiliate or subsidiary companies (hereinafter Rockwell Automation ) be responsible or liable for any indirect or consequential damages resulting from the use or application of the Products described in this Documentation. Rockwell Automation does not assume responsibility or liability for damages of any kind based on the alleged use of, or reliance on, this Documentation. No patent liability is assumed by Rockwell Automation with respect to use of information, circuits, equipment, or software described in the Documentation. Except as specifically agreed in writing as part of a maintenance or support contract, equipment users are responsible for: properly using, calibrating, operating, monitoring and maintaining all Products consistent with all Rockwell Automation or third-party provided instructions, warnings, recommendations and documentation; ensuring that only properly trained personnel use, operate and maintain the Products at all times; staying informed of all Product updates and alerts and implementing all updates and fixes; and All other factors affecting the Products that are outside of the direct control of Rockwell Automation. Reproduction of the contents of the Documentation, in whole or in part, without written permission of Rockwell Automation is prohibited. Throughout this manual we use the following notes to make you aware of safety considerations: Identifies information about practices or circumstances that can cause an explosion in a hazardous environment, which may lead to personal injury or death, property damage, or economic loss. Identifies information that is critical for successful application and understanding of the product. Identifies information about practices or circumstances that can lead to personal injury or death, property damage, or economic loss. Attentions help you: identify a hazard avoid a hazard recognize the consequence Labels may be located on or inside the drive to alert people that dangerous voltage may be present. Labels may be located on or inside the drive to alert people that surfaces may be dangerous temperatures.

Intro Steps Contents Contents... 3 Before you begin... 4 About this lab... 4 Tools & Prerequisites... 4 Network Setup... 5 About the PowerFlex 755 DHQ Demo Box... 6 Drive Setup Reset Defaults... 7 Drive Setup Auto Tune and Configuration Parameters... 8 Connect to the Drive using Connected Components Workbench... 8 Configuring Drive Parameters... 9 Flying Start... 12 Configuring the Drive Parameters for Flying Start... 12 Demo... 14 Enhanced Flying Start Forward... 14 Sweep Flying Start Forward... 15 Sweep Flying Start Reverse... 16 3 of 19

Before you begin Please review the following information before starting this lab. About this lab This session provides you with an opportunity to explore the Flying Start features of the PowerFlex 755 AC Drive. In this session you will: Demonstrate a scenario in which Flying Start is not used Explore Flying Start Enhanced mode Explore Flying Start Sweep mode This lab takes approximately 40 minutes to complete. Lab Objective At the end of this lab you will be able to: 1. Configure the drive for Flying Start Enhanced 2. Configure the drive for Flying Start Sweep Tools & Prerequisites Software programs required Connected Components Workbench v9.01 RSLinx Classic v3.80.00 Hardware devices required PowerFlex 755 DHQ Demo Box (PN-39023) o PowerFlex 755 AC Drive (20G11-N-B-DM1AA6K32V8) v12.001 Ethernet patch cables Motor with flywheel attached 4 of 19

Network Setup Ethernet Connections 1 PC PF755 Ethernet Port Set IP Address of PowerFlex 755 to 192.168.1.30 by setting the IP address switches. Hundreds 0 Tens 3 Ones 0 Motor with Flywheel attached 5 of 19

About the PowerFlex 755 DHQ Demo Box 6 of 19

Drive Setup Reset Defaults Use the steps below to reset the drive to its default settings. 1. Press the Folders button on the HIM keypad. The button is located on the bottom row of the HIM Keypad (shown circled in the left image below). Pressing the Folders button changes the HIM screen display to the Folders screen (see right image below). 00 PowerFlex 755 240V 4.2A 20G... B4P2 PORTS 00 PowerFlex 755 01 20-HIM-x6 05 Universal Fdbk 06 Dual Encoder 2. Use the Enter key located in the center of the HIM keypad to select 00 PowerFlex 755. 3. Now, use the left or right arrow keys to navigate to the Memory heading, then select Set Defaults. 4. Select This port only, then select the All option using the Enter key. At this time the drive may display Fault 58, which is expected. 5. Clear the fault using the Red stop key (if necessary), then Confirm the reset. 6. Press ESC twice to return to the main display. 7 of 19

Drive Setup Auto Tune and Configuration Parameters Use the settings below to auto tune the drive, and configure certain parameters for the lab. Connect to the Drive using Connected Components Workbench 1. Open Connected Components Workbench using the icon on the desktop. 2. In the Device Toolbox expand Discover, then click Browse Connections in the Device Toolbox to open the Connection Browser. 3. Browse to AB_ETH-1, Ethernet, and select 192.168.1.30, PowerFlex 755. CCW will now connect to the drive, showing its information in the main pane of the software window. 8 of 19

Configuring Drive Parameters 1. Select the Parameters button to view the parameters for the PowerFlex 755 drive. 2. Using the Group drop down list, expand Motor Control and select Motor Data. 3. Fill in the following parameters with the values found on the motor nameplate at this station. Motor NP Volts Motor NP Amps Motor NP Hertz Motor NP RPM Motor NP Power Be sure to press Enter after filling in each value to be sure the entry is confirmed. 4. Next, select Mtr Ctrl Options from the Group drop down list, and change the following parameter, being sure to press Enter after the change: Motor Control Mode Induction FV 9 of 19

5. In the Group drop down menu, expand Drive Cfg and select Preferences. Change the following parameters: 300 Speed Units RPM 301 Access Level - Expert 6. In the Group drop down menu, expand Speed Control, select Speed Reference and change the following parameters: 545 Speed Ref A Select Port 0: Preset Speed 1 (Picture A) 571 Preset Speed 1 1400 (Picture B) Picture A Picture B 7. In the Group drop down menu, select Speed Regulator, and change the following parameter: 636 - Speed Reg BW 5 8. In the Group drop down menu, expand Drive Cfg, then select Braking Features, and change the following parameter: 409 - Dec Inhibit Act Ignore 10 of 19

Auto Tune Follow the steps below to Auto Tune the Drive. 1. Using the Group drop down list, expand Motor Control and select Autotune, then change the Autotune value to Rotate Tune. Be sure to press Enter to confirm the Autotune value change. 2. Turn to the drive, and press the green Start button. The drive will start its auto tune process. Follow its process using the display on the drive HIM module. Inertia Tune The motor has a large disk attached to the end of its shaft. By default, the Inertia parameter has a value of 2.00. In order to make sure that the drive s information is as precise as possible, run an Inertia tune on the drive using CCW to update that value to match the actual Inertia acting on the motor. 1. In CCW, in the Autotune field, select Inertia Tune. 2. Turn to the drive, and press the green Start button. Follow the process on the HIM module of the drive. The drive has now completed its auto tune procedure. And has updated the remaining parameters determined during the process. You can now continue to the next section. 11 of 19

Flying Start The Flying Start feature is used to start an already rotating motor. When a drive is started in normal mode, it will apply a frequency of 0 Hz to the motor and then ramp up to the desired frequency. If the motor is already rotating, the drive will try to force the motor to stop, which will generate large currents, which will cause an overcurrent fault. There are two options to be considered when using the Flying Start feature of the PowerFlex 755 series drive. Enhanced Sweep Use the steps below to configure the drive to allow the motor shaft to continue turning without power, then explore the different options for Flying Start. Configuring the Drive Parameters for Flying Start The steps below will configure the drive to coast to a stop, configure a switch to determine Forward and Reverse Direction, modify the Motor Control Mode, and modify the data displayed on the HIM module to easily view the changing frequency of the drive. 1. Select the Parameters button to view the parameters for the PowerFlex 755 drive. 2. Using the Group drop down list, expand Drive Cfg and select Braking Features. 3. Click the field for Stop Mode A, and select Coast. 4. Using the Group drop down list, expand Feedback & I/O, and select Digin Functions. 12 of 19

5. For 162 - DI Fwd Reverse, change the values to the following: Port 7 1 2 Input 2 6. Verify this change on the HIM module, by watching the display while flipping the IN 2 switch on the demo box. The HIM will display F, then R, as well as an arrow change when flipping the switch back and forth. 7. Make sure the switch is in the Forward position before continuing. 8. In the Group drop down list, select Mtr Ctrl Options found under Motor Control. Change the 35 Motor Ctrl Mode value to Induction SV. 9. In the Groups drop down list, expand Speed Control, and select Slip/Droop Comp. Change the following parameter: 621 Slip RPM at FLA 0 10. Finally, turn to the drive, and on the HIM, select PAR# using the soft keys. With Parameter 1 showing, press the soft key for Enter. The HIM module will now show the Output Frequency value. 13 of 19

Demo In this demonstration, you will see what happens if a motor that is able to rotate without power is commanded to start by the drive. 1. Press the Start button on the HIM module of the drive. 2. Allow the motor to get up to its commanded speed, 1400 RPM. This may take a few moments. 3. Now, press the Stop button on the HIM module, and allow the motor to coast for a minute or so. The drive is no longer controlling the motor the motor will coast to a stop after a long period of time. 4. Press the Start button on the HIM module again. The drive will display a fault HW Overcurrent. This is because the drive will try to bring the motor down to a complete stop before bringing it back up to speed. 5. Clear the fault using the Stop button. Enhanced Flying Start Forward Use the steps below to explore the Enhanced option of the Flying Start feature. 1. In CCW, using the Group drop down list, expand Drive Cfg and select Start Features. 2. Change the 356 - Flying Start Mode parameter to Enhanced. 3. Turn to the drive and press Start. Allow the drive to reach its speed. 4. Press the Stop button to stop the drive. Allow a minute or so to pass so that the motor begins to coast to a stop. 5. Now, press the Start button again. Notice that the drive catches the motor right away, and brings it to its commanded speed. The Enhanced option utilizes Counter-electromotive force, or CEMF. The drive sends current pulses to the motor to find and calculate the CEMF value, and when it finds that value, it is able to send the appropriate current to the motor to catch the motor and then bring it up to the configured speed. 14 of 19

Sweep Flying Start Forward The Sweep option for Flying Start utilizes a different method of finding the motor s speed. Use the steps below to configure the drive for this option, then explore the results of that configuration. 1. In CCW, with the motor still turning, change the Flying Start Mode parameter to Sweep. 2. Change FS Speed Reg Ki to 1000. This value is being changed to better demonstrate the Sweep Flying Start Mode feature. 3. Press the Stop button to stop the drive. Allow a minute or so to pass so that the motor begins to coast to a stop. 4. Now, press the Start button again, paying attention to the frequency displayed on the drive, and the Analog Output gauge to the right of the drive in the demo box. Notice that after a few seconds, the drive will catch the motor and bring it up to the commanded speed. The drive sweeps the output frequency while watching the current in order to find the motor s speed. It will then apply the appropriate power to the motor, bringing it up to the configured speed. 15 of 19

Sweep Flying Start Reverse In some applications, it is possible that the shaft of the motor will be found to be rotating in reverse without power applied. Use the steps below to explore how Sweep Flying Start will address that situation. 1. With the motor still running, flip the IN 2 switch in the demo box to the right. Because the motor was moving in the forward direction, the drive will ramp the motor down to zero, then apply appropriate power to reverse the motor s direction. This may take a few moments, and the HIM module will display a flashing F and arrow. Once the motor is moving in reverse, the HIM display will show R with a reverse arrow. 2. Press the Stop button to stop the drive. Again, allow the motor to coast for a few seconds. 3. Flip the switch to the left, making sure the HIM module is indicating the forward direction. 4. Press the Start Button. The drive will repeat the Sweep process, starting with the forward direction, and when it has determined that the motor is not moving forward, it will then sweep the reverse direction. FS Speed Reg Ki and Kp parameter values The charts below show the frequency and the current being supplied to the motor. The motor is coasting, so when the Start button is pressed on the drive, the drive will output the max forward speed, then start to decrease according to a slope set by parameter 359 (FS Speed Reg Ki). When that frequency matches that of the motor, the current dips, reverses, and the motor is accelerated back to the commanded speed. The chart below shows the change of the current (blue), and the frequency (pink) as a result of this process when using the default Ki (100) and Kp (75) values. 16 of 19

Changed Ki parameter value In the chart below, we see that the frequency trace has a more gradual slope (encircled in red). The drive will take more time to detect the motor at this Ki value 1000. Changed Kp parameter values 17 of 19

In the chart below, we see two sweep procedures, paying close attention to the current trace in blue. Notice that in the procedure on the left, the Kp value is set to 25, which results in a deeper dip in current when the motor has been detected. In the sweep procedure on the right, the Kp value is set to 500, resulting in a shallower dip of current. Reverse Sweep In the case of a motor turning in reverse of commanded direction, a flying start in sweep mode will still work. The frequency will sweep in the forward direction first, and if it does not detect the motor, will begin sweeping in the reverse direction. Once the motor has been detected, the drive will safely bring it to a stopped state, then proceed to bring it to its commanded speed. 18 of 19

Notes Publication CE-DM253-EN-P Sept 2015 Copyright 2014 Rockwell Automation, Inc. All rights reserved. 19 of 19