FLM DI 8 M12. Function. Fieldline Modular Device With Eight Digital Inputs. Data Sheet

Similar documents
IB IL 24 DI 16 IB IL 24 DI 16-PAC

IBS IL 24 BK RB-T-2MBD

ILBIB24DO16-DSUB. Inline Block IO Module for INTERBUS With 16 Digital Outputs; Bus Connection via D-SUB Connectors

VersaMax IP I/O Module

VersaMax IP Input Module

ILBPB24DO32. Inline Block IO Module for PROFIBUS With 32 Digital Outputs. AUTOMATIONWORX Data Sheet 6889_en_04. Description

IB IL 120 DI 1. Function. INTERBUS Inline Terminal With One Digital Input in the 120 V AC Voltage Area. Data Sheet 5764B

GFK-2415A March Type of sensor connection

PHOENIX CONTACT - 11/2007. This data sheet is only valid in association with the IB IL SYS PRO UM E user manual.

This data sheet is only valid in association with the IL SYS INST UM E user manual.

IB IL IB IL PAC

IBS IL 24 RB-LK-2MBD:

IB IL 24/48 DOR 2/W-XC-PAC

ILB DN 24 DI16 DO16. Inline Block IO Module for DeviceNet With 16 Digital Inputs and 16 Digital Outputs. AUTOMATIONWORX Data Sheet 6885_en_05

PB IL 24 BK DIO 16/16

IB ST 24 AO 4/EF. INTERBUS-ST analog output module, 4 outputs, 0-10 V, ±10 V, 0-20 ma, 4-20 ma. Data sheet. 1 Description

IB IL AO 2/SF... Inline terminal with two analog outputs. AUTOMATION Data sheet 6655_en_06. 1 Description

VERSAMAX IP PROFINET SCANNER. 1 Description. GFK-2760 June 2012

IBS ST (ZF) 24 BK LB-T

IL CAN BK-TC-PAC. Extract from the online catalog. Order No.:

AXL E IOL AO1 U M12 R

IBS PCI SC/I-T. Controller Board for PC Systems With PCI Bus. Data Sheet 6039B

IB IL RS 232 IB IL RS 232-PAC

PHOENIX CONTACT - 10/2006

ILC 200 IB ILC 200 IB-PAC

AXL E PB DIO16 M12 6P

VersaPoint I/O Module

IBS ST 24 BK-T INTERBUS-S. Data Sheet. Bus Terminal Module. Product Description

FL MC 2000E (SM40) LC

IL CAN BK-TC-PAC. Extract from the online catalog. Order No.:

FL MC 2000T. Fiber optic converter for 10/100Base-Tx to single- or multi-mode fiberglass with SC-duplex and ST connections. Data sheet 3379_en_B

PHOENIX CONTACT - 10/2009

Rexroth Inline terminal with one analog output

8 24 V DC, 8 24 V DC,

Rexroth RECO Fieldline INTERBUS Devices

ILB BT ADIO 2/2/16/16

AXL E EC DI16 M12 6P. Axioline E EtherCAT device, plastic housing, 16 inputs, 24 V DC, M12 fast connection technology. Data sheet.

PHOENIX CONTACT - 11/2008

FL SWITCH Factoryline 5- and 8-port managed switches with optional fiber optic ports and wide temperature ratings. Data sheet.

PSI-MODEM-SHDSL/PB. Broadband PROFIBUS extender, SHDSL PROFIBUS leased line modem. Data sheet _en_03. 1 Description. 1.

RAD-DO8-IFS. I/O extension module, eight digital transistor outputs. Data sheet. 1 Description

PHOENIX CONTACT - 05/2007

PHOENIX CONTACT - 07/2006

FL SWITCH SFNB. Five- and Eight-Port Standard Function Ethernet Switch with Narrow Housing. AUTOMATION Data Sheet 2642_en_H.

MINI-PS AC/10-15DC/8

VL BPC MINI. A configurable industrial computer platform. Data sheet 2930_en_F. 1 Description. 2 Features

IndraControl S67. Fieldbus coupler PROFINET

AXL E PN DI8 DO8 M12 6P

RAD-DI8-IFS. I/O extension module with 8 digital inputs or 2 pulse inputs. INTERFACE Data sheet. 1 Description

IL CAN BK-TC-XC-PAC. Inline CANopen bus coupler Extreme conditions version. Data sheet _en_01. 1 Description

Valueline Industrial PC

VL BPC MINI. A configurable industrial computer platform Intel Atom Z510PT CMAT IPC Module Option [I28] AUTOMATION Data Sheet 2930_en_A.

FL SWITCH SFN(T) 16-Port Standard Function Ethernet Switches for Normal and Extreme Environments. AUTOMATION Data Sheet 2806_en_C

Remote Process Actuation Control System AirLINE PHOENIX INLINE

FL SWITCH SFN 5TX. Extract from the online catalog. Order No.:

EMD-FL-C-10. Electronic monitoring relay for overcurrent and undercurrent monitoring of direct and alternating current in single-phase networks

MINI MCR-SL-MUX-V8-FLK 16

PSI-MODEM-SHDSL/SERIAL

154 PHOENIX CONTACT Courtesy of Power/mation Energy Lane, Saint Paul, MN

VL BPC 100. Valueline configurable box PC. Data sheet 3063_en_E. 1 Description. 2 Features

DEK-OV- 5DC/ 24DC/ 3. Extract from the online catalog. Order No.:

MINI MCR-SL-PT100-UI(-SP)(-NC)

PSR-PC50. SIL 3 coupling relay for safety-related switch on. Data sheet. 1 Description

Redundancy Module QUINT-DIODE/40

Process modules Digital input PMI for 24 V DC inputs for 120 V AC inputs

PHOENIX CONTACT

MINI MCR-SL-UI-2I(-SP)(-NC)

Fieldline. Fieldline Modular bus coupler, PROFIBUS, 8 digital inputs 24 V DC, M12 RF-FLM BK PB M12 DI 8 M12

PHOENIX CONTACT - 06/2006

ELR W1/ 6-24DC. Extract from the online catalog. Order No.:

PHOENIX CONTACT - 11/2008

Profibus-DPV1 Set in IP67 TI-BL67-DPV1-6

Extract from the online catalog

AXL BK PN (-ME) Axioline bus coupler for PROFINET IO. Data sheet. 1 Description

MINI MCR-SL-UI-2I. Configurable signal duplicator. Data sheet. 1 Description

PA ROUTERS. The following criteria can be applied when choosing the network transition:

DI572 Digital Input Module

Installation and Programming Manual. This Manual describes the IBSS InterBus-S Slave, its uses and set up.

TRIO-DIODE/12-24DC/2X10/1X20

PI-EX-ME-2NAM/COC-24VDC

BNI PBS Z001 BNI PBS Z001 BNI PBS Z001 BNI PBS Z001 Short Guide

ABSOLUTE ROTARY ENCODER INTERBUS

Remote Process Actuation Control System AirLINE PHOENIX INLINE

QUINT-PS/ 1AC/24DC/ 5

DI561 Digital Input Module

RAD-DOR4-IFS. I/O extension module, 4 digital relay outputs. INTERFACE Data sheet. 1 Description

PSR-SCP- 24DC/URM4/4X1/2X2/B PSR-SPP- 24DC/URM4/4X1/2X2/B

ABSOLUTE ROTARY ENCODER INTERBUS

Original operating instructions Fail-safe inductive sensor GF711S / / 2013

PSI-MOS-PROFIB/FO 850 T

PLC-OSC- 24DC/ 48DC/100

PHOENIX CONTACT - 12/2007

PSR-MS60. Safety relay for emergency stop, safety door and light grid monitoring. Data sheet. 1 Description

DX561 Digital Input/Output Module

Profibus-DPV1 Set in IP20 TI-BL20-DPV1-2

PI-EX-ME-2NAM/COC-120VAC

DC562, digital input/output module,

SUBCON-PLUS-PROFIB...

PSI-MOS-RS422/FO 850 T

NI REM Remote I/O Overview DATASHEET. Analog Output Module for Remote I/O

Transcription:

Fieldline Modular Device With Eight Digital Inputs Data Sheet 697000 02/2004 This data sheet is only valid in association with the FLS FLM SYS INST UM E user manual or the user manual for your bus system (see "Ordering Data" on page 12). Function The device is designed for use in the Fieldline modular local bus, which is opened by a Fieldline modular bus coupler. It is used to acquire digital signals. Features Connection to the Fieldline modular local bus using M12 connectors (B-encoded) Connection of digital sensors using M12 connectors Flexible voltage supply concept LED diagnostic and status indicators Short-circuit and overload protection of the sensor supply IP65/IP67 protection Figure 1 $ ' % ) The Fieldline device 697000 1

Connections. -! *, * * * 7 6 7 6 7 5-1 1 7 6 " Des. FE LB IN LB OUT U LS IN Meaning Functional earth ground Local bus IN Local bus OUT Voltage supply IN (logic and sensor supply) U LS OUT Voltage supply OUT (logic and sensor supply) for additional devices IN1 to IN8 Inputs 1 to 8 # 1! 1# 1" 1$ $ In general, the maximum current load of 4 A per contact must not be exceeded. % & 1% 1&., 1& Figure 2 $ ' % ) Connections of the Pin Assignment of LB IN/LB OUT Figure 3 * Pin assignment of LB IN/ LB OUT (M12 B-encoded) * 7 6 $ ' % ) % Pin IN OUT 1 DO DO 2 DO DO 3 DI DI 4 DI DI 5 GND GND The thread is used for shielding. 2 697000

Pin Assignment of the Voltage Supply U LS Figure 4 Pin assignment of the voltage supply U LS Pin Assignment of the Inputs 7 6 $ ' % ) $ Pin IN OUT 1 U L +24 V U L +24 V 2 U S GND U S GND 3 U L GND U L GND 4 U S +24 V U S +24 V 5 500 kbaud/ 2 Mbaud 500 kbaud/ 2 Mbaud The transmission speed is switched at the bus coupler. Figure 5 $ $ # ) $ Pin assignment of the inputs Pin Input Socket 1 U S +24 V 2 See Figure 6 3 GND 4 Input 5 FE Assignment of the Input Sockets " #! E JA H = " #! Two input signals can be connected to each input socket. If both inputs of the same socket are used, the other socket must not be used (1 or 2, 3 or 4, 5 or 6, and 7 or 8) (see Figure 6). " 8 " 8 5? A J 5? A J! 5? A J# 5? A J% 5? A J 5? A J" 5? A J$ 5? A J& $ $ # * % Figure 6 Assignment of the input sockets 697000 3

Local LED Diagnostic and Status Indicators 7 5, Figure 7 *, 1 1! 1# 1%., 1& 7 5 LED diagnostic and status indicators of the 1 1" 1$ 1& * 7 6 - $ ' % )! Des. Color D Green LED ON: Flashing, 0.5 Hz: Flashing, 2 Hz: US E XX Flashing, 4 Hz: OFF: Green LED ON: OFF: Meaning Diagnostics Bus active Communications power present, bus not active Communications power present, bus active, I/O error Communications power present, transmission path to the left of the flashing device failed, device to the left of the flashing device failed, devices to the right of the flashing device are not part of the configuration frame Communications power not present, bus not active Voltage supply for inputs IN1 to IN8 Voltage supply present Voltage supply too low Red LED Overload of voltage supply U S ON: Voltage supply overloaded OFF: Voltage supply not overloaded Yellow LED ON: OFF: Status indicators of the inputs Input active Input not active 4 697000

Internal Circuit Diagram Key: * * 7 6 Functional earth ground " 8 # 8 2 + 7 6 OPC " 8 # 8 Protocol chip (bus logic including voltage conditioning) Power supply unit with electrical isolation & Optocoupler LED Input Electrically isolated area $ ' % ) " Figure 8 Internal wiring of the connection points For information on electrically isolated areas, please refer to page 11. 697000 5

Connection Example 1 1 " 8 " 8 $ ' % ) # Figure 9 Typical connection of sensors Connection Notes Meet noise immunity requirements Connect FE using a mounting screw or a cable connection to the FE connection latch (when mounting on a non-conductive surface). Ensure degree of protection To ensure IP65/IP67 protection, cover unused sockets with protective caps. Avoid damage to the electronics Make sure you only supply the sensors with the voltage U S provided at the connection points. Avoid polarity reversal Avoid polarity reversal of the supply voltages U L and U S in order to prevent damage to the device. Observe connection point assignment When connecting the sensors, observe the assignment of the connection points to the IN process data (see "Process Data" on page 7). 6 697000

Programming Data/Configuration Data INTERBUS ID code BE hex (190 dec ) Length code 81 hex Process data channel 8 bits Input address area 8 bits Parameter channel 0 bits (PCP) Register length (bus) 8 bits Other Bus Systems For the programming data of other bus systems, please refer to the appropriate electronic device data sheet (GSD, EDS). For additional information, please refer to the user manuals, see "Ordering Data" on page 12. Process Data Assignment of the Connection Points to the IN Process Data (Byte.bit) Byte Byte 0 view Bit 7 6 5 4 3 2 1 0 Device Input 8 7 6 5 4 3 2 1 For the assignment of the illustrated (byte.bit) view for your INTERBUS control or computer system, please refer to data sheet DB GB IBS SYS ADDRESS, Part No.9000990. 697000 7

Technical Data Device Dimensions * *, 7 6 1 1! 1# 1% 1 1" 1$ 1& 7 5 - % % # $ $ & $ $ "., 1& " '! ' "! % & % & " # % # General Data Order designation Order no. 27 36 28 8 Housing dimensions (width x height x depth) 70 mm x 178 mm x 49.3 mm (2.756 x 7.008 x 1.941 in.) Weight 290 g, approximately Operating mode Process data mode with 8 bits Type of sensor connection 2, 3 or 4-wire technology Permissible temperature (operation) -25 C to +60 C (-13 F to +140 F) Permissible temperature (storage/transport) -25 C to +85 C (-13 F to +185 F) Permissible humidity (storage/transport) 95% For a short period, slight condensation may appear on the housing. Permissible air pressure (operation) 80 kpa to 106 kpa (up to 2000 m [6562 ft.] above sea level) Permissible air pressure (storage/transport) 70 kpa to 106 kpa (up to 3000 m [9843 ft.] above sea level) Degree of protection IP65/IP67 according to IEC 60529 Class of protection Class 3 according to VDE 0106, IEC 60536 8 697000

Mechanical Requirements Vibration test 5g load in each space direction Sinusoidal vibrations according to EN 60068-2-6 Shock test according to EN 60068-2-27 30g load, half sinusoidal wave positive and negative in each space direction For additional information on mechanical requirements and ambient conditions, please contact Phoenix Contact. Voltage Supply Nominal value 24 V DC Tolerance ±25% Current consumption at U L at 24 V DC At 500 kbaud 35 ma, typical (50 ma, maximum) At 2 Mbaud 40 ma, typical (50 ma, maximum) Current consumption at U S at 24 V DC 5 ma, typical, + sensor current (600 ma, maximum) Digital Inputs Number 8 Input design According to IEC 61131-2 Type 1 Definition of switching thresholds Maximum low level voltage Minimum high level voltage U Lmax < 5 V U Hmin > 11 V Nominal input voltage 24 V DC Range -30 V DC < U IN < +30 V DC Nominal input current 5 ma Current flow Linear in the range 2 V < U IN < 30 V Delay time t ON = 3.1 ms, typical t OFF = 4.1 ms, typical Permissible cable length to the sensor < 30 m (98.43 ft.) 697000 9

Input Characteristic Curve Input Voltage (V) Typical Input Current (ma) -30 < U IN < 0.7 0 3 0.5 6 1.0 9 1.6 12 2.3 15 3.0 18 3.8 21 4.5 24 5.2 27 6.0 30 6.7 Sensor Supply Minimum sensor voltage Nominal current per channel Nominal current per device Overload protection Short-circuit protection U S 1 V 600 ma 600 ma Electronic per device Electronic per device Error Messages to the Higher-Level Control or Computer System Sensor supply short-circuit Yes Sensor supply overload Yes If an error is triggered by an overload or short circuit of the sensor supply, the device switches off the sensor supply of the channels and reports an I/O error message to the master. If the sensor supply U S is not sufficiently high, the device reports an I/O error message to the master. 10 697000

Interface Bus system Incoming Bus Coupling of shield connection Transmission speed Outgoing Bus Coupling of shield connection Transmission speed Fieldline modular local bus Directly to FE 500 kbaud/2 Mbaud Directly to FE 500 kbaud/2 Mbaud Electrical Isolation/Isolation of the Voltage Areas For device connection, please note the instructions and regulations in the "Installing the Fieldline Product Range" user manual FLS FLM SYS INST UM E (Order No.2698973). Separate Potentials in the - Test Distance - Test Voltage 24 V supply (bus logic) / FE 500 V AC, 50 Hz, 1 min 24 V supply (bus logic) / digital inputs (sensor supply / I/O) 500 V AC, 50 Hz, 1 min 24 V supply (bus logic) / incoming remote bus 500 V AC, 50 Hz, 1 min 24 V supply (bus logic) / outgoing remote bus 500 V AC, 50 Hz, 1 min Digital inputs (sensor supply / I/O) / FE 500 V AC, 50 Hz, 1 min Digital inputs (sensor supply / I/O) / incoming remote bus 500 V AC, 50 Hz, 1 min Digital inputs (sensor supply / I/O) / outgoing remote bus 500 V AC, 50 Hz, 1 min Incoming remote bus / FE 500 V AC, 50 Hz, 1 min Outgoing remote bus / FE 500 V AC, 50 Hz, 1 min 697000 11

Ordering Data Description Order Designation Order No. Fieldline modular device with eight digital 27 36 28 8 inputs Protective caps (for unused sockets) IBS IP PROT-IO 27 59 91 9 pack of 5 Protective caps (for unused connectors) PROT-M12-M 27 36 19 4 pack of 5 Shielded connector, 5-pos. female connector, SACC-M12FSB-5SC SH 15 13 59 6 B-encoded, for the incoming local bus Shielded connector, 5-pos. male connector, SACC-M12MSB-5SC SH 15 13 57 0 B-encoded, for the outgoing local bus Markers ZBF 12:UNBEDRUCKT 08 09 73 5 pack of 10 "Installing the Fieldline Product Range" FLS FLM SYS INST UM E 26 98 97 3 user manual "Configuring an INTERBUS System Using Devices in the Fieldline Product Range" user manual FLS FLM IB SYS PRO UM E 26 99 06 6 "Configuring a PROFIBUS DP System Using Devices in the Fieldline Product Range" user manual "Configuring a DeviceNet TM System Using Devices in the Fieldline Product Range" user manual "Configuring a CANopen System Using Devices in the Fieldline Product Range" user manual FLS FLM PB SYS PRO UM E 26 99 07 9 FLS FLM DN SYS PRO UM E 26 99 08 2 FLS FLM CO SYS PRO UM E 26 99 09 5 Additional accessories for connecting the sensors can be found in the Phoenix Contact PLUSCON catalog. Make sure you always use the latest documentation. It can be downloaded at www.phoenixcontact.com. 12 697000

Phoenix Contact GmbH & Co. KG Flachsmarktstr. 8 32825 Blomberg Germany +49-52 35-30 0 +49-52 35-34 12 00 www.phoenixcontact.com Worldwide Locations: www.phoenixcontact.com/salesnetwork Phoenix Contact 02/2004 Technical modifications reserved TNR 90 17 98 0 13 697000