Logix5000 Control Systems: Connect a PanelView Plus Terminal over an EtherNet/IP Network

Similar documents
Logix5000 Control Systems: Connect POINT I/O Modules over a DeviceNet Network

PowerMonitor 1000 Unit Catalog Number Upgrade

Color-Sensing Connected Components Building Block. Quick Start

Teaching Color-Sensing Connected Components Building Block. Quick Start

PowerMonitor 5000 Unit Catalog Number Upgrade

InView Communication Modules

PowerFlex 400 Drive Firmware Version 7.01

Simple Package Measurement Connected Components Building Block. Quick Start

DeviceNet Communications

GuardLogix: Safety Gate Application with SensaGuard Switch

Catalog Numbers 9308-RSFB64ENE, 9308-RSFB256ENE, 9308-RSFB1024ENE

InView Firmware Update

GuardLogix: Dual Zone Gate Protection with E-stop and Trojan Interlock Switch

GuardLogix: TLS Guardlocking Application

PCI Expansion Slot Kit for 6181P (1500P) Series D Integrated Display Computer

MicroLogix 1400 Embedded Web Server

ControlLogix HART Analog I/O Modules

Quick Start. Logix5000 Control Systems: Connect Kinetix 350 Drives over an EtherNet/IP Network

CompactLogix Power Supplies Specifications

Adapter Kit for PanelView 1200/1200e Touch Screen Terminal Cutout

Logix5000 Controllers Messages

DeviceNet Network Configuration

Studio 5000 Architect Getting Results Guide

Logix5000 Controllers Produced and Consumed Tags

Logix5000 Controllers Produced and Consumed Tags

Logix5000 Controllers Function Block Diagram

ProcessLogix R510.0 Server Installation Instructions

Logix5000 Controllers Nonvolatile Memory Card

Using TLS3-GD2 Guardlocking Interlock with ArmorBlock Guard I/O and SmartGuard Controller

POINT I/O and ArmorPOINT I/O EtherNet/IP Adapters

Disconnect Switch and Circuit Breaker Mechanism Specifications Bulletin Number 1494

ControlLogix Redundancy Update and Module Replacement Guidelines

Reference Manual. Rockwell Automation Library of Process Objects: Condition Gate Delay (P_Gate) Version 3.5

GuardLogix Controller to Kinetix 6000 Drive with Safe-Off using EtherNet/IP CompactBlock Guard I/O Module

Kinetix 6000 Axis Module and Shunt Module

CENTERLINE 2100 Motor Control Centers EtherNet/IP Network Adapter

DriveGuard. Safe-Off Option for PowerFlex 70 AC Drives. User Manual.

ControlLogix SIL2 System Configuration

Allen-Bradley Motors

Using GuardShield Light Curtains (Safe 4, Micro 400, or 440L), with ArmorBlock Guard I/O and SmartGuard Controller

DriveTools SP v4.03 Software Patch

Bidirectional (4-sensor, T-type) Muting With MSR42 Relay Connected Components Building Block

SequenceManager Controls

Bidirectional (2-sensor, T-type) Muting With Enable Using MSR42 Relay Connected Components Building Block

Product Compatibility and Download Center

Kinetix 300 Memory Module Programmer

PowerFlex 753 Drives (revision 9.002)

Allen-Bradley to-230V Conversion Kit Cat. Nos FC FC075

Micro800 Programmable Controllers: Getting Started with Motion Control Using a Simulated Axis

Product Compatibility and Download Center

DataSite Accelerator Toolkit

Studio 5000 View Designer Getting Started Guide

PowerFlex 70 Safe-Off Control EtherNet/IP Guard I/O Safety Module and GuardLogix Integrated Safety Controller

Solar Combiner Enclosure

Micro800 Controllers Starter Pack Quick Start

NHP SAFETY REFERENCE GUIDE

PowerFlex 755 Drives (revision 4.002)

USB-to-DeviceNet Cable

Using a Guard Locking Interlock Switch and Light Curtains with DeviceNet Guard I/O and a GuardLogix Controller

Pump Station Controller. Quick Start

20-COMM-H RS485 HVAC Adapter Firmware Revision 2.010

PowerFlex 753 Drives (revision )

Import/Export Project Components. Programming Manual

Drive Software Wizards v2.3

Differential Liquid/Gas Pressure Transmitter

22-COMM-B BACnet MS/TP Adapter Firmware v1.003

Drive Software Wizards v2.2

1203-EN1 EtherNet/IP-to-SCANport Module Firmware v1.005

PanelView 800 HMI Terminals

1203-SSS Smart Self-powered Serial Converter Firmware v3.007

Electronic Keying in Logix5000 Control Systems

20-COMM-P Profibus Adapter Firmware v1.006

PanelView Component HMI Terminals

PanelView 800 HMI Terminals

20-COMM-H RS485 HVAC Adapter Firmware Revision 2.009

Quick Start. PlantPAx System Application Templates System Release 3.0

PowerFlex 753 Drives (revision )

PowerFlex 753 Drives (revision 8.002)

PowerFlex 753 Drives (revision 6.003)

Reference Manual. Rockwell Automation Sequencer Object Version 4.0

20-COMM-E EtherNet/IP Adapter Firmware v4.001

Position Control via HMI Connected Components Building Block. Quick Start

Rockwell Automation Library of Steam Table Instructions

FLEX I/O Dual Port EtherNet/IP Adapter Modules

PowerMonitor 5000 USB Driver

PowerFlex DC Stand-Alone Regulator (SAR) Switching Power Supply Circuit Board

Getting Results Guide. FactoryTalk Gateway

L01 - Effective Design Methods for Integrating Safety Using Logix Controllers. For Classroom Use Only!

1756 ControlLogix Chassis Specifications

PowerFlex 7-Class Human Interface Module Series A Firmware v3.010

DriveTools SP v5.03 Software Patch

PowerFlex 20-HIM-A6 and 20-HIM-C6S HIM Firmware Revision 1.006

PowerFlex DC Stand-Alone Regulator (SAR) Field Circuit Board

POINT I/O and ArmorPOINT I/O Dual Port EtherNet/IP Adapters

PanelView Plus 7 Standard Terminals

DriveTools SP v5.05 Software Patch

PanelView 800 HMI Terminals

20-COMM-M Modbus/TCP Adapter Firmware v2.001

20-COMM-E EtherNet/IP Adapter Firmware Revision 4.002

Simple Motion Control Connected Components Building Block. Quick Start

Transcription:

Quick Start Logix5000 Control Systems: Connect a PanelView Plus Terminal over an EtherNet/IP Network Catalog Numbers Logix5000 Controllers, 2711P PanelView Plus Terminals

Important User Information Solid-state equipment has operational characteristics differing from those of electromechanical equipment. Safety Guidelines for the Application, Installation and Maintenance of Solid State Controls (publication SGI-1.1 available from your local Rockwell Automation sales office or online at http://www.rockwellautomation.com/literature/) describes some important differences between solid-state equipment and hard-wired electromechanical devices. Because of this difference, and also because of the wide variety of uses for solid-state equipment, all persons responsible for applying this equipment must satisfy themselves that each intended application of this equipment is acceptable. In no event will Rockwell Automation, Inc. be responsible or liable for indirect or consequential damages resulting from the use or application of this equipment. The examples and diagrams in this manual are included solely for illustrative purposes. Because of the many variables and requirements associated with any particular installation, Rockwell Automation, Inc. cannot assume responsibility or liability for actual use based on the examples and diagrams. No patent liability is assumed by Rockwell Automation, Inc. with respect to use of information, circuits, equipment, or software described in this manual. Reproduction of the contents of this manual, in whole or in part, without written permission of Rockwell Automation, Inc., is prohibited. Throughout this manual, when necessary, we use notes to make you aware of safety considerations. WARNING: Identifies information about practices or circumstances that can cause an explosion in a hazardous environment, which may lead to personal injury or death, property damage, or economic loss. ATTENTION: Identifies information about practices or circumstances that can lead to personal injury or death, property damage, or economic loss. Attentions help you identify a hazard, avoid a hazard, and recognize the consequence. SHOCK HAZARD: Labels may be on or inside the equipment, for example, a drive or motor, to alert people that dangerous voltage may be present. BURN HAZARD: Labels may be on or inside the equipment, for example, a drive or motor, to alert people that surfaces may reach dangerous temperatures. IMPORTANT Identifies information that is critical for successful application and understanding of the product. Allen-Bradley, Compact I/O, CompactLogix, FactoryTalk, Integrated Architecture, Logix5000, PanelView, POINT I/O, Rockwell Software, Rockwell Automation, RSLinx, RSLogix, RSNetWorx, Stratix 6000, and TechConnect are trademarks of Rockwell Automation, Inc. Trademarks not belonging to Rockwell Automation are property of their respective companies.

Table of Contents Preface Before Using This Publication...................................... 5 Other Logix5000 Control System Quick Starts....................... 8 Use Each Chapter.................................................. 8 Where to Start..................................................... 9 How Hardware Is Connected..................................... 10 Required Software............................................... 10 Parts List........................................................ 11 Additional Resources............................................. 11 Prepare the PanelView Plus Terminal Hardware Chapter 1 Before You Begin................................................ 13 What You Need................................................. 13 Follow These Steps............................................... 14 Mount the PanelView Plus Terminal.............................. 14 Connect the Power Supply....................................... 15 Connect the PanelView Plus Terminal to the EtherNet/IP Network............................................ 16 Assign an IP Address to the PanelView Plus Terminal............... 17 Additional Resources............................................. 19 Chapter 2 Create a PanelView Plus Application Before You Begin................................................ 21 What You Need................................................. 22 Follow These Steps............................................... 23 Install FactoryTalk View Studio Software.......................... 24 Install RSLinx Enterprise Software................................ 28 Create a New Application........................................ 30 Create an RSLinx Enterprise Configuration in FactoryTalk View Machine Edition................................ 31 Create a Device Shortcut to the Controller......................... 33 Create the OB16_Light Indicator................................. 34 Create a Push Button............................................. 38 Test the Indicator and Push Button................................ 40 Add a Goto Configuration Mode Button.......................... 43 Assign Function Keys............................................. 45 Assign an Initial Screen........................................... 46 Transfer to PanelView Plus Terminal.............................. 47 Test the Application on the PanelView Plus Terminal............... 49 Additional Resources............................................. 50 Index.................................................................. 51 Rockwell Automation Publication IASIMP-QS033A-EN-P - March 2012 3

Table of Contents Notes: 4 Rockwell Automation Publication IASIMP-QS033A-EN-P - March 2012

Preface This quick start provides examples and procedures for including a PanelView Plus terminal in a Logix5000 control system over an EtherNet/IP network. The programming examples are not complex, and offer easy solutions to verify that devices are functioning and communicating properly. IMPORTANT This publication describes basic example tasks you can complete when using a PanelView Plus terminal on an EtherNet/IP network. The tasks described are not the only tasks you can complete with the terminal on an EtherNet/IP network. Before Using This Publication You can only use the tasks described in this publication after first completing some prerequisite tasks with a Logix5000 controller. For example, before you can add a PanelView Plus terminal to an RSLogix 5000 project, as described on page 21, you must first create the project in a Logix5000 controller. Table 1 describes the tasks you must complete before using this publication. IMPORTANT The example graphics shown in Table 1 - Required Tasks To Complete Before Using This Quick Start on page 6 are for CompactLogix 5370 L3 controllers. Depending on the Logix5000 controller you are using, the specific steps to complete the tasks described in the table might vary. For more information on how to complete these tasks with specific Logix5000 controllers, see the Integrated Architecture : Logix5000 Control Systems Quick Starts Quick Reference, publication IASIMP-QR024. Rockwell Automation Publication IASIMP-QS033A-EN-P - March 2012 5

1 (Front) 2 (Rear) Preface Table 1 - Required Tasks To Complete Before Using This Quick Start Task Prepare the Logix5000 control system hardware Description Assemble the control system and connect to necessary communication networks. Some components, for example, the desired Logix5000 controller and system power supply, are required. Other components, for example, a network communication module, are optional. These graphics show the assembly of an example Logix5000 controller. Prepare the computer IMPORTANT: This task does not include installation of specific hardware components, for example, PanelView Plus terminals, used over the networks included in your application. Install necessary software, such as RSLogix 5000 software, on your computer. 6 Rockwell Automation Publication IASIMP-QS033A-EN-P - March 2012

Preface Table 1 - Required Tasks To Complete Before Using This Quick Start Task Configure the networks Description Complete required tasks associated with the networks used in your application. For instance, as assign an IP address to the controller or to a communication module in your Logix5000 control system. Create an RSLogix 5000 project Create a project to be used with your Logix5000 controller. A project includes all desired control system components and necessary programming. For example, add ladder logic to test tasks associated with individual system components.. Rockwell Automation Publication IASIMP-QS033A-EN-P - March 2012 7

Preface Other Logix5000 Control System Quick Starts This quick start describes how to use one device on one network in a Logix5000 control system. Typically, though, a Logix5000 control system includes more than the controller and one device on one network. For example, if a Logix5000 control system operates on an EtherNet/IP network, in addition to a controller, power supply, and communication modules, the system might use remote I/O modules, drives and HMI terminals. Other quick starts describe how to use different devices on different networks in Logix5000 control systems. For more information, see the Integrated Architecture: Logix5000 Control Systems Quick Starts Quick Reference, publication IASIMP-QR024. Use Each Chapter The beginning of each chapter contains the following information. You should read these sections before beginning work in each chapter: Before You Begin - This section lists the tasks you must complete before starting the chapter. What You Need - This section lists the tools that are required to complete the tasks in the chapter. Follow These Steps - This section illustrates the steps in the current chapter. 8 Rockwell Automation Publication IASIMP-QS033A-EN-P - March 2012

Preface Where to Start Prerequisite Tasks Described in Before Using This Publication on page 5. 1. Prepare the Logix5000 control system hardware. 2. Prepare the computer. 3. Configure the networks. 4. Create an RSLogix 5000 project. Logix5000 Controller Prepare the PanelView Plus Terminal Hardware page 13 Create a PanelView Plus Application page 21 Rockwell Automation Publication IASIMP-QS033A-EN-P - March 2012 9

8 7 6 5 4 3 2 1 Preface How Hardware Is Connected This quick start demonstrates the following possible control system. Logix5000 Controller with Ethernet Connection Computer Stratix 6000 Managed Switch PanelView Plus Terminal with Built-in EtherNet/IP Port Required Software To complete examples in this quick start, you need the software described in this table. Software Version Required for This Task RSLogix 5000 20.00.00 or later (1) FactoryTalk View Machine Edition (2) RSLinx Enterprise (4) Create or change RSLogix 5000 projects to use PanelView Plus terminals 5.01.00 or later (3) Configure the PanelView Plus terminal and execute runtime tasks 5.00.00 or later Complete the tasks described in Chapter 2, Create a PanelView Plus Application on page 21. (1) RSLogix 5000 software, version 20.00.00 or later is required for use of this quick start because the example Logix5000 controller, and associated tasks, described herein are completed in a CompactLogix L3ER control system. CompactLogix L3ER control systems require RSLogix 5000 software, version 20.00.00 or later. If you connect a PanelView Plus terminal over an EtherNet/IP network in a Logix5000 control system that uses a different controller, the minimum version may differ. (2) When you install the FactoryTalk View Machine Edition software, you automatically install FactoryTalk Services Platform software and RSLinx Enterprise software. (3) You can use version 5.01.00 with some Logix5000 controllers. However, the tasks described in this quick start use a 1769-L36ERM controller. That controller requires you to use version 6.00.00 or later and version 6.00.00 is shown in this publication. (4) This software is automatically installed when you install FactoryTalk View Machine Edition software. 10 Rockwell Automation Publication IASIMP-QS033A-EN-P - March 2012

Preface Parts List You need these parts to use this publication. Quantity Cat. No. Description 1 2711P-K10C4D1 PanelView Plus 1000 with built-in EtherNet/IP network port 1 2711P-RSACDIN DC power supply for PanelView Plus terminals 1 Panel for mounting the terminal, if desired - To complete the tasks described in this quick start, you can prop the PanelView Plus terminal on a desktop. 1 1769-OB16 Compact I/O output module 1 1585J-M8PBJM-2 RJ45-to-RJ45 patchcord Ethernet cables For a list of parts required to complete the prerequisite tasks listed in Table 1 - Required Tasks To Complete Before Using This Quick Start on page 6, see the documentation describing those tasks. Additional Resources Resource PanelView Plus Terminals User Manual, publication 2711P-UM001 AC Power Supply for PanelView Plus/PanelView Plus CE Terminals Installation Instructions, publication 2711P-IN005 Stratix 6000 Ethernet Managed Switch Installation Instructions, publication 1783-UM001, publication 1783-UM004 Stratix 6000 Ethernet Managed Switches Installation Instructions, publication 1783-IN004 Industrial Automation Wiring and Grounding Guidelines, publication 1770-4.1 Product Certifications website, http://www.ab.com Description Describes how to install, configure, and execute runtime tasks for the PanelView Plus terminal. Describes how to install the power supply for a PanelView Plus 1000 terminal. Describes how to configure, operate and troubleshoot a Stratix 6000 managed switch. Describes how to install a Stratix 6000 switch. Provides general guidelines for installing a Rockwell Automation industrial system. Provides declarations of conformity, certificates, and other certification details. You can view or download publications at http://www.rockwellautomation.com/literature/. To order paper copies of technical documentation, contact your local Allen-Bradley distributor or Rockwell Automation sales representative. Rockwell Automation Publication IASIMP-QS033A-EN-P - March 2012 11

Preface Notes: 12 Rockwell Automation Publication IASIMP-QS033A-EN-P - March 2012

Chapter 1 Prepare the PanelView Plus Terminal Hardware In this chapter, you learn how to complete the following tasks: Mount and wire power to a 2711P-K10C4D1 terminal. Configure EtherNet/IP communication for the terminal. Before You Begin You must complete these tasks described in Before Using This Publication on page 5 before using this chapter: Prepare the Logix5000 control system hardware Prepare the computer Configure the networks - The tasks described in this chapter require an EtherNet/IP network. Create an RSLogix 5000 project The example RSLogix 5000 project used in this chapter uses a CompactLogix 5370 L3 controller. What You Need This table lists the products you need to complete the tasks described in this chapter. Quantity Cat. No. Description 1 2711P-K10C4D1 PanelView Plus terminal with built-in EtherNet/IP network port 1 2711P-RSACDIN DC power supply for PanelView Plus terminals 1 Panel for mounting the terminal - Optional when using this publication 1 1585J-M8PBJM-2 RJ45-to-RJ45 patchcord Ethernet cables Rockwell Automation Publication IASIMP-QS033A-EN-P - March 2012 13

8 7 6 5 4 3 2 1 Chapter 1 Prepare the PanelView Plus Terminal Hardware Follow These Steps Mount the PanelView Plus Terminal page 14 Connect the Power Supply GND + page 15 GND Connect the PanelView Plus Terminal to the EtherNet/IP Network page 16 Assign an IP Address to the PanelView Plus Terminal page 16 Mount the PanelView Plus Terminal In normal applications, you mount a PanelView Plus terminal to a panel. For the purpose of this quick start, however, the PanelView Plus can be propped on a desktop to complete the tasks described herein. For complete mounting instructions, see the PanelView Plus Terminals User Manual, publication 2711P-UM001. 14 Rockwell Automation Publication IASIMP-QS033A-EN-P - March 2012

Prepare the PanelView Plus Terminal Hardware Chapter 1 Connect the Power Supply WARNING: Verify that all incoming power is turned off before wiring power. This quick start uses a PanelView Plus 1000 terminal with built-in Ethernet port and a PanelView Plus Logic module, catalog number 2711P-RP1, Series G. The 2711P-RP1 Logic module uses a 2-position terminal block for power connections. 2-position Terminal Block + GND DC - DC + Earth/Ground to Ground Bus GND Complete these steps to connect power to the PanelView Plus terminal. 1. Install the 2711P-RSACDIN DC power supply for the PanelView Plus terminal on a DIN rail. Do not turn on power to the power supply. PanelView Plus POWER 24 VDC POWER SUPPLY 2711P-RSACDIN For detailed information on how to install a 2711P-RSACDIN DC power supply, see the AC Power Supply for PanelView Plus/PanelView Plus CE Terminals Installation Instructions, publication 2711P-IN005. Rockwell Automation Publication IASIMP-QS033A-EN-P - March 2012 15

Chapter 1 Prepare the PanelView Plus Terminal Hardware 2. Gently pull the terminal block off of the PanelView Plus terminal. 3. Connect the 12/24V DC common and 12/24V DC power wires from the power supply to the terminal block, - (common) and + (power). POWER PanelView Plus 24V DC POWER SUPPLY 2711P-RSACDIN + 4. Connect the terminal block to the PanelView Plus terminal. COM 24V Common Power Connect the PanelView Plus Terminal to the EtherNet/IP Network IMPORTANT If you completed the tasks described in the Logix5000 controller quick start for the controller you are using with this quick start, you should already have an Ethernet switch installed on the EtherNet/IP network. If not, install a switch, for example, a Stratix 6000 managed switch, on the EtherNet/IP network before proceeding. 1. Connect one end of the 1585J-M8PBJM-2 RJ45-to- RJ45 patchcord Ethernet cable to the EtherNet/IP port on the PanelView Plus terminal. Front Display on Terminal EtherNet/IP Port 2. Connect the other end of the cable to an Ethernet switch. 8 7 6 5 4 3 2 1 16 Rockwell Automation Publication IASIMP-QS033A-EN-P - March 2012

Prepare the PanelView Plus Terminal Hardware Chapter 1 Assign an IP Address to the PanelView Plus Terminal This graphic shows a 2711P-RP1, Series G terminal. You use the keypad buttons to make choices from the options on the terminal screen. Keypad Buttons If the options on the screen are lines of text, press the direction arrows, that is, up/down and left/right arrows, on the keypad to highlight the option you need and press the enter button. Lines of Text on Screen Keypad Buttons Enter Button Direction Buttons If the option on the screen show specific button number from the keypad, press the matching button on the keypad. For example, to choose the Terminal Settings [F4] option on the screen, press the F4 button on the keypad. Terminal Setting [F4] Option on Screen F4 Button Rockwell Automation Publication IASIMP-QS033A-EN-P - March 2012 17

Chapter 1 Prepare the PanelView Plus Terminal Hardware Complete the following steps to assign an IP address to the PanelView Plus terminal. 1. Apply power to the PanelView Plus terminal. 2. When the initial PanelView Plus terminal configuration screen appears on the terminal, press [F4] on the keypad to access the terminal settings. 3. Press the direction arrows and Enter button on the keypad to navigate this path and access the IP address: Networks and Communications>Network Connections>Network Adaptors>Built-in Ethernet Controller>IP Address [F2]. 4. Press IP address [F1]. 5. Use the numbers on the keypad to assign an IP address to the PanelView Plus terminal. 6. Press the Enter button on the keypad twice. 7. Press Subnet Mask [F2]. 8. Use the numbers on the keypad to assign a subnet mask to the PanelView Plus terminal. 9. Press Enter. 18 Rockwell Automation Publication IASIMP-QS033A-EN-P - March 2012

Prepare the PanelView Plus Terminal Hardware Chapter 1 10. Press OK [F7] to save settings, as shown, and press OK [F7] to acknowledge the reset message. 11. Press [F8] four times until you return to the initial configuration screen. 12. Press [F7] to reset the terminal. 13. Press [F7] to confirm. Additional Resources For a list of additional resources that might assist you when preparing the PanelView Plus terminal hardware, see page 11. Rockwell Automation Publication IASIMP-QS033A-EN-P - March 2012 19

Chapter 1 Prepare the PanelView Plus Terminal Hardware Notes: 20 Rockwell Automation Publication IASIMP-QS033A-EN-P - March 2012

Chapter 2 Create a PanelView Plus Application In this chapter, you learn how to complete the following tasks: Create a push button and a multi-state indicator in FactoryTalk View Studio software. Transfer the application to the 2711P-K10C4D1 drive so you can test communication with the controller. Before You Begin You must complete these tasks before using this chapter: The tasks described in Before Using This Publication on page 5, including: Prepare the Logix5000 control system hardware Prepare the computer Configure the networks - The tasks described in this chapter require an EtherNet/IP network. Create an RSLogix 5000 project- In your RSLogix 5000 project, include a ladder logic rung with Examine On and Output Energize elements as shown. In this example, the alias tag named OB16_Light is an alias for point Local:1:O.Data.0. The example RSLogix 5000 project used in this chapter uses a CompactLogix 5370 L3 controller. Rockwell Automation Publication IASIMP-QS033A-EN-P - March 2012 21

Chapter 2 Create a PanelView Plus Application Install an I/O module with the following conditions: Accessible to the PanelView Plus terminal over the EtherNet/IP network Included in the RSLogix 5000 project used with this quick start. This publication uses a 1769-OB16 digital output module. Prepare the PanelView Plus terminal as described in Chapter 1, Prepare the PanelView Plus Terminal Hardware on page 13, including: Mount the PanelView Plus Terminal Connect the Power Supply Connect the PanelView Plus Terminal to the EtherNet/IP Network Assign an IP Address to the PanelView Plus Terminal What You Need You need the following software to complete the tasks described in this chapter: FactoryTalk View Studio software RSLinx Enterprise software RSLogix 5000 software IMPORTANT This section describes how to install FactoryTalk View Studio software and RSLinx Enterprise software. 22 Rockwell Automation Publication IASIMP-QS033A-EN-P - March 2012

Create a PanelView Plus Application Chapter 2 Follow These Steps Install FactoryTalk View Studio page 24 Test the Indicator and Push Button page 40 Install RSLinx Enterprise Software page 28 Add a Goto Configuration Mode Button page 43 Create a New Application page 30 Assign Function Keys page 45 Create an RSLinx Enterprise Configuration in FactoryTalk View Machine Edition page 31 Assign an Initial Screen page 46 Create a Device Shortcut to the Controller page 33 Transfer to PanelView Plus Terminal page 47 Create the OB16_Light Indicator page 34 Test the Application on the PanelView Plus Terminal page 49 Create a Push Button page 38 Rockwell Automation Publication IASIMP-QS033A-EN-P - March 2012 23

Chapter 2 Create a PanelView Plus Application Install FactoryTalk View Studio Software IMPORTANT The tasks described in this quick start use a 1769-L36ERM controller. That controller requires that you use FactoryTalk View Studio software, version 6.00.00. Therefore, this chapter describes how to use FactoryTalk View Studio software, version 6.00.00. You can use FactoryTalk View Studio software, version 5.01.00 or earlier (known as FactoryTalk View Studio software) with some Logix5000 controllers. If you choose to use FactoryTalk View Studio software, version 5.01.00 or earlier, be aware that some of the tasks described in this chapter may be completed differently in version 5.01.00 or earlier. Your computer have FactoryTalk Services Platform software installed on it before you can use the FactoryTalk View Studio software. This quick start assumes you have FactoryTalk Services Platform installed on your computer, do so now before proceeding with the rest of the tasks described in this chapter. You can install from the same DVD file or downloaded file for FactoryTalk View Studio software. Throughout the installation, click Next to use default software installation settings, except where indicated. TIP As installation progresses and depending on your system configuration, you may be prompted to complete additional set-up tasks not described in this chapter. Follow those prompts and enter information as applies to your installation. This section describes how to install the software from a DVD. The following steps describe clicking on FactoryTalk View Site Edition. This set of steps installs both the FactoryTalk View Site Edition and Machine Edition. You can choose Machine Edition when you launch the software after installation. 1. Verify that all Rockwell Automation software processes are shutdown. 2. When the launch screen appears, use this path to begin the installation process: FactoryTalk View>6.00.00>exe. 6 24 Rockwell Automation Publication IASIMP-QS033A-EN-P - March 2012

Create a PanelView Plus Application Chapter 2 3. Click Install FactoryTalk View Site Edition. 4. Click Install FactoryTalk View Site Edition. All Rockwell Automation software products should be shutdown, as described in step 1. If they are not, the software alerts you to this requirement. 5. Click Yes. 6. Click Next. Rockwell Automation Publication IASIMP-QS033A-EN-P - March 2012 25

Chapter 2 Create a PanelView Plus Application 7. Read the end-user license agreement. 8. Check I accept the terms in the license agreement and click Next. 9. Enter your user name, organization, and software serial number and click Next. 10. Select Complete and click Next. 26 Rockwell Automation Publication IASIMP-QS033A-EN-P - March 2012

Create a PanelView Plus Application Chapter 2 11. Select the Destination Drive and click Next. We recommend you use the default Destination Drive setting. 12. Click Install. 13. When the InstallShield Wizard Completed dialog box appears, click Finish. You have the option to Install FactoryTalk Activation Server. Because the activation server is required to use other Rockwell Automation software and RSLogix 5000 software is already installed and working on your computure, the steps to install the FactoryTalk Activation Server are not shown here. Rockwell Automation Publication IASIMP-QS033A-EN-P - March 2012 27

Chapter 2 Create a PanelView Plus Application Install RSLinx Enterprise Software IMPORTANT Your computer must have RSLinx Enterprise software to use FactoryTalk View Studio software. Immediately following the end of installing FactoryTalk View Studio software, the installation process for RSLinx Enterprise software begins automatically. Throughout the installation, click Next to use default RSLinx Enterprise software installation settings, except when indicated in the following steps. TIP As installation progresses and depending on your system configuration, you may be prompted to complete additional set-up tasks not described in this chapter. 1. Click Next. Follow those prompts and enter information as applies to your installation. 2. Read the license agreement carefully. 3. Check I accept the terms in the license agreement and click Next. 28 Rockwell Automation Publication IASIMP-QS033A-EN-P - March 2012

Create a PanelView Plus Application Chapter 2 4. Enter your user name, organization, and software serial number and click Next. 5. Choose the software setup type and click Next. We recommend you use Standard Feature Set Installation, as shown. 6. Click Install. Rockwell Automation Publication IASIMP-QS033A-EN-P - March 2012 29

Chapter 2 Create a PanelView Plus Application 7. When the InstallShield Wizard Completed dialog box appears, click Finish. You must restart the computer to complete the installation process. 8. Restart your computer. Create a New Application 1. Launch FactoryTalk View Studio software. 2. On the Application Type Selection dialog box, select Machine Edition and click Continue. 30 Rockwell Automation Publication IASIMP-QS033A-EN-P - March 2012

Create a PanelView Plus Application Chapter 2 3. Select the New tab. 4. Name the application (do not use spaces) and click Create. Create an RSLinx Enterprise Configuration in FactoryTalk View Machine Edition 1. In the FactoryTalk View organizer, expand RSLinx Enterprise and double-click Communication Setup. 2. Click Finish. RSLinx Enterprise software opens. Rockwell Automation Publication IASIMP-QS033A-EN-P - March 2012 31

Chapter 2 Create a PanelView Plus Application The Design (Local) tab defines the path from the computer to the controller. The Runtime (Target) tab defines the path from the PanelView Plus terminal to the controller. Local Target Computer The computer needs to communicate with the controller when you are in Test Run mode. This path is defined on the Local tab. Logix5000 Controller Terminal The PanelView Plus terminal also needs to communicate with the controller, but that is sometimes a different path. This path is defined on the Target tab. 32 Rockwell Automation Publication IASIMP-QS033A-EN-P - March 2012

Create a PanelView Plus Application Chapter 2 Create a Device Shortcut to the Controller 1. Expand the EtherNet/IP tree, select your controller and click Add. 2. Type a shortcut name; do not use spaces. 3. Verify that the controller you selected in step 1 is still selected. 4. Click Apply. 5. Click Copy from Design to Runtime. 6. Click OK. Rockwell Automation Publication IASIMP-QS033A-EN-P - March 2012 33

Chapter 2 Create a PanelView Plus Application Create the OB16_Light Indicator 1. Verify that you have created an RSLogix 5000 project that includes an output module and a ladder logic rung with Examine On and Output Energize elements similar to the one shown. This example, the alias tag named OB16_Light is an alias for point Local:1:O:Data.0. You might choose to use a different point on the module. If so, verify that the alias tag is set to the correct module point. 2. Go online with your controller and download the RSLogix 5000 project. 3. Open the Explorer section of FactoryTalk View Machine Edition software as shown in the following graphic. 4. Under Graphics, right-click Displays and choose New. 5. Choose Objects>Indicator Multistate. 34 Rockwell Automation Publication IASIMP-QS033A-EN-P - March 2012

Create a PanelView Plus Application Chapter 2 6. Click and drag to create the indicator. 7. Right-click and choose Properties. 8. On the General tab, select 2 for the Number of states. 9. On the States tab, verify that State0 is selected. 10. In the Caption, type Light is OFF. Rockwell Automation Publication IASIMP-QS033A-EN-P - March 2012 35

Chapter 2 Create a PanelView Plus Application 11. Select State1. 12. In the Caption, type Light is ON. 13. Change the Back Color to yellow. 14. Change the Caption Color to black. 15. On the Connections tab, click... under Tag. The Tag Browser dialog box appears. 16. Right-click your project and select Refresh All Folders. 36 Rockwell Automation Publication IASIMP-QS033A-EN-P - March 2012

Create a PanelView Plus Application Chapter 2 17. Expand the controller shortcut and select the Online folder. The tags created in your RSLogix 5000 project, as described on page 21, appear to the right. IMPORTANT If the tags in your RSLogix 5000 project do not appear, verify that they were created at the controller scope and not the Main Program scope in RSLogix 5000 software. 18. Select the OB16_Light tag. 19. Click OK. The Indicator tag is populated. 20. Click OK. Rockwell Automation Publication IASIMP-QS033A-EN-P - March 2012 37

Chapter 2 Create a PanelView Plus Application Create a Push Button 1. From the Objects menu, select Push Button Maintained. 2. Click and drag to create the push button beneath the indicator. 3. Right-click the push button you just created and select Properties. 4. On the States tab, verify that State0 is selected. 5. In the Caption, type Push to turn light ON. 38 Rockwell Automation Publication IASIMP-QS033A-EN-P - March 2012

Create a PanelView Plus Application Chapter 2 6. Select State1. 7. In the Caption, type Push to turn light OFF. 8. On the Connections tab, click... under Tag in the Value row. The Tag Browser dialog box appears. 9. Expand the controller shortcut and select the Online folder. The tags created in your RSLogix 5000 project, as described on page 21, appear to the right. 10. Select the PB tag. 11. Click OK. Rockwell Automation Publication IASIMP-QS033A-EN-P - March 2012 39

Chapter 2 Create a PanelView Plus Application The Indicator tag is populated. 12. Click OK. 13. From the File menu, choose Save. 14. When prompted for a display title, type PanelView_Plus_project. Test the Indicator and Push Button 1. Verify that the mode switch on your controller is moved to Run. 2. Right-click an unused area of the display and select Display Settings. 3. Change the Maximum Tag Update Rate to 0.05. 4. Click OK. 40 Rockwell Automation Publication IASIMP-QS033A-EN-P - March 2012

Create a PanelView Plus Application Chapter 2 A message appears warning you that the Update Rate changes take effect only after the display is reopened. 5. Click OK. 6. Save the display and close it. 7. Double-click the display name, PanelView_Plus_project in this case, to reopen the display. 8. Click the Play button. Rockwell Automation Publication IASIMP-QS033A-EN-P - March 2012 41

Chapter 2 Create a PanelView Plus Application 9. Click the push button to toggle the state and turn the light on and off. 10. Click the Stop button. 42 Rockwell Automation Publication IASIMP-QS033A-EN-P - March 2012

Create a PanelView Plus Application Chapter 2 Add a Goto Configuration Mode Button 1. From the Objects menu, choose Advanced Goto Configure Mode. 2. Click and drag to create the Goto button next to the push button. 3. Right-click the push button and select Properties. Rockwell Automation Publication IASIMP-QS033A-EN-P - March 2012 43

Chapter 2 Create a PanelView Plus Application 4. On the Label tab, enter Goto Config for the caption. 5. Click OK. The Goto Config button appears. 44 Rockwell Automation Publication IASIMP-QS033A-EN-P - March 2012

Create a PanelView Plus Application Chapter 2 Assign Function Keys If your PanelView Plus does not have a touch screen, you must assign functions keys to the display buttons. This publication uses a PanelView Plus 1000, catalog number 2711P-K10C4D1. That terminal does not have a touch screen. To assign function keys, complete these steps. 1. Right-click the push button and select Key Assignments. 2. Under Select an object, verify that MaintainedPushButton is selected. 3. Select a function key and click Apply. This example uses F2. Rockwell Automation Publication IASIMP-QS033A-EN-P - March 2012 45

Chapter 2 Create a PanelView Plus Application 4. Under Select an object, select GotoConfigureMode. 5. Select a different function key and click Apply. This example uses F3. 6. Click OK. 7. Access the button properties to add the function key names to them, including both states of the indicator. 8. Save your changes. Assign an Initial Screen 1. Under System folder, double-click Startup. 46 Rockwell Automation Publication IASIMP-QS033A-EN-P - March 2012

Create a PanelView Plus Application Chapter 2 2. Check Initial graphic and select PanelView_Plus_project, or the initial display name if different, from the pull-down menu. 3. Click OK. 4. Save your changes. Transfer to PanelView Plus Terminal 1. From the Application menu, choose Create Runtime Application. 2. In Save as type, select the Runtime version that matches your PanelView Plus firmware. To check the PanelView Plus firmware revision, on the terminal select Terminal Setting [F4] System Information About FactoryTalk View ME Station 3. Click Save to accept the default file name. Rockwell Automation Publication IASIMP-QS033A-EN-P - March 2012 47

Chapter 2 Create a PanelView Plus Application 4. From the Tools menu, choose Transfer Utility. 5. Click the... button. 6. Select the.mer file you just created and click Open. 7. Verify the following : Run application when download completes is checked Replace communications is checked Your PanelView Plus is selected for the destination terminal 8. Click Download. The download process may take a few minutes. 48 Rockwell Automation Publication IASIMP-QS033A-EN-P - March 2012

Create a PanelView Plus Application Chapter 2 9. When the Transfer Utility dialog box appears, click OK. 10. Exit the Transfer Utility. Test the Application on the PanelView Plus Terminal 1. On the PanelView Plus terminal, press Load Application [F1]. 2. Select your.mer file and press Load [F2]. 3. Press Yes [F7]. 4. After the application loads, press Run Application [F2]. Rockwell Automation Publication IASIMP-QS033A-EN-P - March 2012 49

Chapter 2 Create a PanelView Plus Application 5. Press the push button and verify that the indicator turns on and that the light on the Compact digital output module turns on. 6. Press the push button again and verify that the indicator and light turn off. Additional Resources For a list of additional resources that might assist you when creating a PanelView Plus application, see page 11. 50 Rockwell Automation Publication IASIMP-QS033A-EN-P - March 2012

Index C connections hardware 10, 15-16 E Ethernet adapter assign IP address 17-19 connect terminal to network 16 F FactoryTalk View Machine Edition requirements 10 FactoryTalk View Studio software install 24-27 H hardware connect Ethernet adapter 16 example control system 10 mount terminal 14 preparation 13-16 required parts 11 wire power 15-16 I IP address assign to Ethernet adapter 17-19 L Logix5000 controllers prerequisite tasks 5-7 P parts PanelView Plus terminal 11 required to complete tasks 11 power connect to terminal 15-16 Q quick starts for devices in Logix5000 control systems 8 R requirements hardware preparation 13-19 parts 11 prerequisite tasks 5-7 software 10 RSLinx Enterprise software install 28-31 requirements 10 RSLogix 5000 software requirements 6, 10 S software FactoryTalk View Machine Edition 10 install FactoryTalk View 24-27 install RSLinx Enterprise 28-31 RSLinx Enterprise 10 RSLogix 5000 10 Stratix 6000 swtich 11 Rockwell Automation Publication IASIMP-QS033A-EN-P - March 2012 51

Index Notes: 52 Rockwell Automation Publication IASIMP-QS033A-EN-P - March 2012

Rockwell Automation Support Rockwell Automation provides technical information on the Web to assist you in using its products. At http://www.rockwellautomation.com/support/, you can find technical manuals, a knowledge base of FAQs, technical and application notes, sample code and links to software service packs, and a MySupport feature that you can customize to make the best use of these tools. For an additional level of technical phone support for installation, configuration, and troubleshooting, we offer TechConnect support programs. For more information, contact your local distributor or Rockwell Automation representative, or visit http://www.rockwellautomation.com/support/. Installation Assistance If you experience a problem within the first 24 hours of installation, review the information that is contained in this manual. You can contact Customer Support for initial help in getting your product up and running. United States or Canada 1.440.646.3434 Outside United States or Canada Use the Worldwide Locator at http://www.rockwellautomation.com/support/americas/phone_en.html, or contact your local Rockwell Automation representative. New Product Satisfaction Return Rockwell Automation tests all of its products to ensure that they are fully operational when shipped from the manufacturing facility. However, if your product is not functioning and needs to be returned, follow these procedures. United States Contact your distributor. You must provide a Customer Support case number (call the phone number above to obtain one) to your distributor to complete the return process. Outside United States Please contact your local Rockwell Automation representative for the return procedure. Documentation Feedback Your comments will help us serve your documentation needs better. If you have any suggestions on how to improve this document, complete this form, publication RA-DU002, available at http://www.rockwellautomation.com/literature/. Rockwell Otomasyon Ticaret A.Ş., Kar Plaza İş Merkezi E Blok Kat:6 34752 İçerenköy, İstanbul, Tel: +90 (216) 5698400 www.rockwel lautomation.com Power, Control and Information Solutions Headquarters Americas: Rockwell Automation, 1201 South Second Street, Milwaukee, WI 53204-2496 USA, Tel: (1) 414.382.2000, Fax: (1) 414.382.4444 Europe/Middle East/Africa: Rockwell Automation NV, Pegasus Park, De Kleetlaan 12a, 1831 Diegem, Belgium, Tel: (32) 2 663 0600, Fax: (32) 2 663 0640 Asia Pacific: Rockwell Automation, Level 14, Core F, Cyberport 3, 100 Cyberport Road, Hong Kong, Tel: (852) 2887 4788, Fax: (852) 2508 1846 Publication IASIMP-QS033A-EN-P - March 2012 Copyright 2012 Rockwell Automation, Inc. All rights reserved. Printed in the U.S.A.