NGC-40-BRIDGE CONTROL AND MONITORING MODULES FOR USE WITH THE RAYCHEM NGC-40 SYSTEM INSTALLATION INSTRUCTIONS

Similar documents
NGC-40-BRIDGE. Control and Monitoring Modules for use with the nvent Raychem NGC-40 System Installation Instructions

TT-NRM. Network Relay Module Installation Instructions WARNING:

User Interface Terminal for nvent RAYCHEM NGC Systems Installation Instructions DESCRIPTION TOOLS REQUIRED. Nonhazardous Locations LR67275

The max number of C910 controllers is 8 per ProtoNode.

FLEX Ex Spring Clamp Terminal Base

CONTROL MICROSYSTEMS SDI-12 Interface Module. Hardware Manual

ACS-30-EU-MONI-RMM2-E

SDM-6RO. Expansion Module 6 relay outputs. Manufactured for

INJ-24A Series Quick Installation Guide

MGate MB3170/MB3270 Quick Installation Guide

RS485 MODBUS Module 6RO

Intelligent 4 Port RS-422/485 to 2 Port Ethernet Serial Device Server with PoE

OTB1S0DM9LP I/O distributed module OTB - Modbus non isolated serial link m

TraceTek Leak Detection Master Module Installation Instructions TOOLS REQUIRED STORAGE

4 10/100/1000T Mini-GBIC with 4 IEEE 802.3at High Power PoE Industrial Wide Temperature Switch. User Manual SISTP LRT

MGate 5105-MB-EIP Quick Installation Guide

OTB1S0DM9LP I/O distributed module OTB - Modbus non isolated serial link m

RSTI-EP Slice I/O. PROFINET Scanner EPXPNS001. GFK-2965C November 2017

ASTAT XB/XBm Remote Operator

General Operating, Maintenance and Installation Manual

C Heat Trace Controller

SDM-8AO. Expansion Module 8 analog outputs. Manufactured for

Description. System Event List Alarm Event List All module and channel data Current alarm data (quick view) Nine custom display options.

REDUNDANCY MODULE TSP-REM360 AND TSP-REM600

3500/32M 4-Channel Relay Module

PLC PFC200 Controller PFC200 CS 2ETH RS

MGate 5111 Quick Installation Guide

Carbon Monoxide Sensor - ModBus

Serial Data DIN Fiber Link System

Soft Starter Remote Operator. Section 1.0 Introduction 1.1 Important user information General Manual description...2.

IES User Manual. 8 FE + 1 MM SC Unmanaged Switch -40 to 75, DIN-rail. v

HomeWorks QS Processor

MOXA EtherDevice Switch & PoE Splitter

Installation Instructions

1/32-DIN TEMPERATURE CONTROLLER INSTALLATION, WIRING AND OPERATION MANUAL FORM 3882

iologik E1200 Series Ethernet remote I/O with 2-port Ethernet switch Introduction Remote I/O

DeltaV Bulk Power Supplies

S-series Horizontal Carriers

PTC-101-M12 Hardware Installation Guide

RS485 MODBUS Module 8I8O

iologik E1200 Series Ethernet remote I/O with 2-port Ethernet switch Introduction Remote I/O Daisy-Chained Ethernet I/O Connection

DTM Distributed Transmitter Monitor

GETTING STARTED GUIDE NI AI, 100 S/s/ch Simultaneous, Universal Measurements

12-36 VDC/12-24 VAC Power Option 4-Digit Display, 0.56 (14.2 mm) or 1.20 (30.5 mm)

exp-s1110pe PoE+ Gigabit Ethernet Extenders

HomeWorks QS Processor

S-series Horizontal Carriers

EDS-P510 Series Quick Installation Guide

Installation & Operation Manual

Simple but elegant look and ease of installation make it ideal for various industrial applications.

RSTI-EP Slice I/O. EtherCAT Network Adapter Module EPXETC001. GFK-2967B Septembery 2016

ETHERNET/MFC 010 Technical Datasheet

NetBiter I/O Extender User Manual

DeltaV Bulk Power Supplies

Installation Instructions

Legacy Serial. Legacy Serial Redundant Ring Ethernet Extender DDW-222. High Speed Ethernet extension over copper. Configuration and diagnostics

iologik 2500 Series Quick Installation Guide

iologik E1200H Series

RS 485 Mini Modbus 1AO

Signamax Connectivity Systems

CompactBlock Guard I/O EtherNet/IP Safety Modules

Remote I/O Scanner. Catalog Number 1747-SN. Installation Instructions. Publication

technical datasheet technical datasheet MTL660 Displays Loop-powered indicators for hazardous areas

Lantech. IPES /100TX with 4 PoE Injectors 24~48VDC Industrial Switch. User Manual

Trendmaster* Galvanic Isolator

H704-42(H)(E), H704-42/1(H)(E)

ICF-1150 Series Quick Installation Guide

S SENECA. Installation Manual Z-TWS4. Z-PC Line. Web Multifunction Controller Straton / Linux

RS485 MODBUS Module 8AO

Voltage Transducer UMT516 / MT516

Hardened PoE Ethernet Switch

PTC-101 Quick Installation Guide

Industrial 5-Port Fast Ethernet Switches. with SFP Slot and optional 4 PoE PSE Ports. Basic Model: KSD-541. PoE Model: KSD-541-HP. Installation Guide

LAUREL. Laureate RTD Temperature Panel Meter / Controller ELECTRONICS, INC. Features. Description. Specifications

Installation and commissioning guide SmartLink Host Communication Module (HCM-GPU)

IMC-101 Series Quick Installation Guide

01C06/05. Programmable Controller. TomaHawk 8635A. Key benefits. Typical applications for system control

PSI-MODEM-SHDSL/SERIAL

FB-6SP and FB-12SP. Block device couplers. Data sheet 3177_en_A. 2 Features. 1 Description

PD765 TRIDENT. Trident Series Process & Temperature Meters.

ICF-1150 Series Quick Installation Guide

RS485 MODBUS Module 16I-M

Industrial 5-Port Fast Ethernet Switches with SFP Slot and optional 4 PoE PSE Ports. Basic Model: KSD-541 PoE Model: KSD-541-P. Installation Guide

Hypercable injecteur HPOE - Industrial IEEE 802.3at Gigabit PoE Injector. User Manual. v.1.0 Jun Mail :

1. Introduction. 2. Installation MODBUS INTERFACE

3500/33 16-Channel Relay Module Bently Nevada* Asset Condition Monitoring

Fieldgate SFG500. Technical Information. Intelligent Ethernet/PROFIBUS gateway

EDS-G205A-4PoE Hardware Installation Guide

MAKING MODERN LIVING POSSIBLE AK-255 CO 2. Controller On-Site Installation Guide DANFOSS ELECTRONIC CONTROLS & SENSORS

PD765 TRIDENT. Trident Series Process & Temperature Meters.

RS485 MODBUS Module 8I8RO

ISOMETER isoev425 with coupling device AGH420

WP4200 Platform. control systems. CPU module for WP42xx Systems and Concepts. High performing controller for all types of turbines

Product Description Page. Remote user interface and communications device 409

MODEL: GR8-EM. Communication Adaptor GR8 Series

Digital Output Module 4-Channel Version for Zone 1 Series 9475/

EDS-G205-1GTXSFP Quick Installation Guide

UNT1100 Series. Binary Output Jumpers AO2 AO1 AO3 AO4 AOCM AOCM AOCM AOCM AO1. AI Switches Job Information N2 Address. Ref N2+ N2- ADDR 0 = ALL OPEN

Stride Industrial Ethernet Switches

Assembly MAU. MUX 4 Channels 8 Channels Zone 1

Transcription:

NGC-40-BRIDGE CONTROL AND MONITORG MODULES FOR USE WITH THE RAYCHEM NGC-40 SYSTEM STALLATION STRUCTIONS B C D APPROVALS A Shown not to scale Hazardous Locations Class I, Div. 2, Groups A,B,C,D T4 Class I, Zone 2, AEx nc IIC T4 IP20 Ex nl IIC T4 X 3128486 40 C Ta 65 C Certified to: CAN/CSA STD. C22.2 No. 213-M1987 (R2004) CAN/CSA STD. C22.2 No. 61010-1:2004 EN 61010-1 (2001) CAN/CSA STD. E60079-15:02 (R2006) Confms to: FM Class Number 3600 (11/98) FM Class Number 3611 (10/99) ANSI/UL STD. 60079-15-2009 UL STD. 61010-1 DESCRIPTION The NGC-40-BRIDGE module provides the interface between a panel's internal CAN-based netwk and upstream devices. Multiple communications pts are suppted, allowing serial and Ethernet connections to be used with external devices. TOOLS REQUIRED Small flat-blade screwdriver ADDITIONAL MATERIALS REQUIRED Power supply @150 ma per NGC-40-BRIDGE Custom built CAN cables with RJ-45 connections KIT CONTENTS Item Qty Description A 1 NGC-40-BRIDGE module B 2 CAN bus termination block PTM# 10392-043 C 2 RS-485 termination resists 120 Ω 1% - 1/4 watt D 1 NGC-40-BRIDGE serial cable TTC# 10332-005 (Russia, Kazakhstan, Belarus) F other countries contact your local Pentair representative. WARNG: This component is an electrical device that must be installed crectly to ensure proper operation and to prevent shock fire. F technical suppt, call Pentair Thermal Management at (800) 545-6258. DUSTRIAL HEAT TRACG SOLUTIONS EN-RaychemNGC40Bridge-IM-H58089 02/16 1 / 10

GENERAL Supply voltage ± 10% Internal power consumption < 3.6 W per NGC-40-BRIDGE Ambient operating temperature 40ºC to 65ºC ( 40ºF to 149ºF) Ambient stage temperature 40ºC to 75ºC ( 40ºF to 167ºF) Environment PD2, CAT III Max. altitude 2,000 m (6,562 ft) Humidity 5 90% noncondensing Mounting Din Rail 35 mm ELECTROMAGNETIC COMPATIBILITY Emissions EN 61000-6-3 Emission standard f residential, commercial and light industrial environments Immunity EN 61000-6-2 Immunity standard f industrial environments COMMUNICATIONS COM1, COM2 Type 2-wire RS-485 Cable One shielded twisted pair Length 1,200 m (4,000 ft) maximum Quantity Up to 255 devices per pt Data rate 9600, 19.2K, 38.4K, 57.6K, 115.2K baud Data bits 7 8 Parity None, even, odd Stop bits 0, 1, 2 Tx delay 0 5 sec. Protocol Modbus RTU ASCII Connection terminals Wago cage clamp terminals COMMUNICATIONS COM3 Type RS-232 Cable Custom TTC# 10332-005 Length 15 m (50 ft) maximum Data rate 9600, 19.2K, 38.4K, 57.6K, 115.2K baud Data bits 7 8 Parity None, even, odd Stop bits 0, 1, 2 Tx delay 0 5 sec. Protocol Modbus RTU ASCII Connection terminals RJ-11 CAN NETWORKG PORT Type 2-wire isolated CAN-based peer-peer netwk. Isolated to 300 V. Connection Two 8-pin RJ-45 connects (both may be used f Input Output connections) Protocol Proprietary NGC-40 Topology Daisy chain Length 10 m (33 ft) maximum Quantity Up to 80 CAN nodes per netwk segment Address Unique, facty assigned ETHERNET Type Length Data rates Protocol Connection terminals PROGRAMMG AND SETTG LED indicats Alarm conditions Configuration switch CONNECTION TERMALS Wiring terminals CAN netwking and module power HOUSG Size 10/100 BaseT Ethernet netwk 100 m (328 ft) 10 100 MB/s Modbus/TCP Shielded 8-pin RJ-45 connect on front of module, Configuration lost, CAN communications fail SET/RUN slide switch on front of module Cage clamp, 0.5 to 2.5 mm 2 (24 to 12 AWG) Two RJ-45s, one each and. Provides CAN bus signals and power. 45.1 mm (1.78 in) wide x 87 mm (3.43 in) high x 106.4 mm (4.2 in) deep DUSTRIAL HEAT TRACG SOLUTIONS EN-RaychemNGC40Bridge-IM-H58089 02/16 2 / 10

System Components 45.1 mm (1.78 in) 45.1 mm (1.78 in) 45.1 mm (1.78 in) 45.1 mm (1.78 in) 87 mm (3.43 in) 106.4 mm (4.2 in) 87 mm (3.43 in) Front Top Bottom Back A. Wiring Terminals Terminals Function 1 COM 1 (485) in 2 COM 1 (485) out 3 COM 2 (485) in 4 COM 2 (485) out 5 COM 1 (485) in 6 COM 1 (485) out 7 COM 2 (485) in 8 COM 2 (485) out 9 12 Not used B. Status LEDs Status: Indicates status of the module Off No power Green OK/Nmal Yellow (flashing) Configuration mode Red (flashing) Internal fault Netwk: Indicates CAN netwk activity Off No link detected Green Link OK, receive data packets Yellow Transmit data packets Red (flashing) Netwk err COM: Indicates COM1 & 2 (RS-485) activity Off No activity Green (flashing) Receipt of data packet Yellow (flashing) Transmit of data packet C. Communication Slide Switch D. RS-232 Pt Status: Indicates status of RS-232 pt Top LED Off No activity Green (flashing) Receipt of data packet Bottom LED Off No activity Yellow (flashing) Transmit of data packet E. Ethernet Pt Status: Indicates status of the LAN Top LED Off No LAN detected Green ON, LAN detected Bottom LED Off No LAN activity Yellow (flashing) LAN activity (data packet) F. CAN Bus/ Power G. Reset Button DUSTRIAL HEAT TRACG SOLUTIONS EN-RaychemNGC40Bridge-IM-H58089 02/16 3 / 10

Mounting the NGC-40-BRIDGE Each NGC-40-BRIDGE mounts on a D 35 rail. MOUNTG: Insert the rear bottom of the module into the D rail, then push up and inwards to engage the clip. REMOVAL: Push the module upwards to disengage the clip, then rotate the module toward you. 2 2 1 1 RS-485 Connection Diagrams Nth American Installation Technique COM 1&2 Connections (In) COM 1&2 Connections (Out) and RS-485 Resist Wiring f Com 1 & Com 2 must be terminated on a panel mounted terminal block. No ground wires should be terminated on terminals 9 & 11. Terminate Com shields at the panel mounted field terminal block chassis ground. Wiring f Com 1 & Com 2 must be terminated on a panel mounted terminal block. No ground wires should be terminated on terminals 10 & 12. Terminate Com shields and 120 Ω termination resists (included) at the panel mounted field terminal block as shown. COM 1 In COM 2 In 1 5 9 3 7 11 COM 1 Out 2 6 10 COM 2 Out 4 8 12 Field terminal block To upstream device To upstream device Field terminal block 120 ohm termination resist 120 ohm termination resist DUSTRIAL HEAT TRACG SOLUTIONS EN-RaychemNGC40Bridge-IM-H58089 02/16 4 / 10

RS-485 Connection Diagrams European Installation Technique COM 1&2 Connections (In) Wiring f Com 1 & Com 2 must be terminated on a panel mounted terminal block. No ground wires should be terminated on terminals 9 & 11. Terminate Com shields at the panel mounted field terminal block chassis ground. The Com cable shield from the field terminal block to the Bridge should be terminated at the earth ground bar. Earth grounding COM 1 In bar located at the bridge module 1 5 9 To upstream device Field terminal block COM 1&2 Connections (Out) and RS-485 Resist Wiring f Com 1 & Com 2 must be terminated on a panel mounted terminal block. No ground wires should be terminated on terminals 10 & 12. Terminate Com shields and 120 Ω termination resists (included) at the panel mounted field terminal block as shown. The Com cable shield from the field terminal block to the Bridge should be terminated at the earth ground bar. Earth grounding COM 1 Out bar located at the bridge module 2 6 10 120 ohm termination resist Field terminal block COM 2 In 3 7 11 Earth grounding bar located at the bridge module COM 2 Out Earth grounding bar located at the bridge module 4 8 12 To upstream device 120 ohm termination resist Local RS-232 (COM 3) & Ethernet Switch Setting RS-232 User Interface Configuration Switch A slide switch is provided on the front of the module to allow the user to set the bridge into a known state f configuration of the communication pts, as shown in the following table: Switch Position RS-232 Local RS-232 to Laptop Ethernet To upstream device Bridge Settings SET Configuration mode Modbus address 1 Local RS-232 Protocol RTU Data rate 9600 baud Data bits 8 Stop bits 2 Parity No parity RUN Nmal operating mode Settings based on the user configuration parameters DUSTRIAL HEAT TRACG SOLUTIONS EN-RaychemNGC40Bridge-IM-H58089 02/16 5 / 10

RMM2 Connection Optional When using the field mounted RMM2 f RTD input, it must be connected to the COM 2 In as shown below. Panel COM 2 In 3 7 11 Earth grounding bar located at the bridge module Panel Terminal ~ ~ RS-485 Shielded Twisted Pair To next RMM2 ~ ~ Field DUSTRIAL HEAT TRACG SOLUTIONS EN-RaychemNGC40Bridge-IM-H58089 02/16 6 / 10

NGC-40 CAN Bus Connections f Up to 10 s CAN/Term Bridge 80 s per Bridge Primary Supply* 20 s Redundant Supply* 20 s 1 2 3 4 10 Optional redundant supply * Power supply shall have a means f disconnect from line voltage NGC-40 CAN Bus Connections f Up to 20 s CAN/Term Bridge 80 s per Bridge Primary Supply* 20 s Redundant Supply* 20 s 1 2 3 4 10 Optional redundant supply 11 12 13 14 20 * Power supply shall have a means f disconnect from line voltage DUSTRIAL HEAT TRACG SOLUTIONS EN-RaychemNGC40Bridge-IM-H58089 02/16 7 / 10

CAN / TERM CAN / 24 VDC CAN Bus A termination block (included) is required at each end of the CAN/ bus. See NGC-40 CAN bus connection wiring diagram f me details. block block CAN / TERM CAN / 24 VDC PTM /IO PTM /IO Provide Suitable Panel Enclosure and Determine Locations f NGC-40-BRIDGE Assembly in Panel* 1. Provide suitable panel enclosure The NGC-40-BRIDGE must be mounted in an enclosure to protect its electronic components. F indo applications, use a minimum NEMA 1 enclosure (NEMA 12 recommended). F outdo applications, use a NEMA 4 NEMA 4X enclosure depending on the requirements. Panel do PS1 PTM1 CBM 1 Panel 2 3 4 5 Note: The Raychem NGC-40-BRIDGE is designed f operation in ambient temperatures from 40 C to 65 C ( 40 F to 149 F ). If the ambient temperature is outside this range, a space heater and/ cooling fan will be required in the panel. Alarm light PS2 PS3 C11 PTM3 C1 PTM2 C12 HTC11 C2 HTC1 C113 HTC12 C3 HTC2 C4 HTC13 C4 HTC3 C5 HTC14 C5 HTC4 C16 HTC15 C6 HTC5 C17 HTC16 C7 HTC6 C18 HTC17 C8 HTC7 C19 HTC18 C9 HTC8 C20 HTC19 C10 HTC9 HTC10 HTC20 2. Determine locations f the NGC-40-BRIDGE assembly in the electrical panel. PS4 PTM4 HTC21 HTC22 HTC23 HTC24 HTC25 HTC26 HTC27 HTC28 HTC29 HTC30 The NGC-40-BRIDGE should be located in the rear of the panel. The NGC-40-BRIDGE assembly is an electronic unit and must not be located where it will be exposed to strong magnetic fields excessive vibration. C21 C22 C23 C24 C25 C26 TB C27 C28 C29 C30 *Nth American panel installation techniques DUSTRIAL HEAT TRACG SOLUTIONS EN-RaychemNGC40Bridge-IM-H58089 02/16 8 / 10

NGC-40 CAN Bus Connections f Up to 40 s CAN/Term s Primary Supply* 20 s Redundant Supply* 20 s Bridge 80 s per Bridge 1 2 3 4 10 Optional redundant supply CAN/Term Bridge 80 s per Bridge 11 12 13 14 20 CAN/Term Board ) Primary Supply* 20 s Redundant Supply* 20 s 21 22 23 24 30 Optional redundant supply * Power supply shall have a means f disconnect from line voltage CAN/Term 31 32 33 34 40 DUSTRIAL HEAT TRACG SOLUTIONS EN-RaychemNGC40Bridge-IM-H58089 02/16 9 / 10

WWW.PENTAIRTHERMAL.COM NORTH AMERICA Tel: 1.800.545.6258 Fax: 1.800.527.5703 Tel: 1.650.216.1526 Fax: 1.650.474.7711 thermal.info@pentair.com EUROPE, MIDDLE EAST, AFRICA Tel: 32.16.213.511 Fax: 32.16.213.603 thermal.info@pentair.com ASIA PACIFIC Tel: 86.21.2412.1688 Fax: 86.21.5426.2917 cn.thermal.info@pentair.com LAT AMERICA Tel: 1.713.868.4800 Fax: 1.713.868.2333 thermal.info@pentair.com Pentair, NGC and Raychem are owned by Pentair its global affiliates. All other trademarks are the property of their respective owners. Pentair reserves the right to change specifications without pri notice. 2007-2016 Pentair. DUSTRIAL HEAT TRACG SOLUTIONS EN-RaychemNGC40Bridge-IM-H58089 PCN 1244-009547 02/16 10 / 10