CRITICAL CONTROLS - PRODUCT OVERVIEW FUME HOOD CONTROLLER (FHC) The FHC is designed to control face velocity on variable volume fume hoods with audible and visual indicating alarms. The Fume Hood Controller can ensure a safe working environment by constantly monitoring and adjusting the ehaust to maintain a correct face velocity. The controller supports multiple air control devices including Venturi valves, LDV ehaust valves and Variable frequency drives. The controller comes standard with the both sidewall and sash position sensor inputs and both can be used together. The FHC is valve mounted and includes an analog input for monitoring the static pressure across the valve, alarming if minimum static pressures are met and can be used during test and balance to set up the system. The FHC integrates with the Price Laboratory space controller when airflow control calls for maintaining a volumetric offset between supply, general ehaust and fume hood ehaust flows. The FHC comes standard as a BTL certified native BACnet device for simple integration with building management systems. Product Features Fume Hood Controller (FHC): High speed flash base microprocessor Multi-stage surge protection against voltage spikes on 24 VAC input Simple connections to sidewall sensors (SWS) using RJ-12 jacks 3 Sash position sensor inputs (10kΩ) Pluggable terminal blocks Mnet high-speed fume hood network port Pressure port input, 0-5 w.c. (For measuring DP across Price Venturi Valve) LED s for Lnet data TX/RX, Lnet wiring fault, and RS-485 termination Sidewall Sensor (SWS) Features Ultra Low flow digital temperature compensated pressure transducer 25 ft. sensor cable with quick-connect installation Sidewall assembly with easy-to-mount hardware Sash Position Sensor (SPS) Features Ultra long life potentiometer (over 250,000 cycles) Stainless steel cable for chemical resistance and strength Metal mounting grommet for stable installation and reliability Robust plastic cover for protection against airborne chemical agents Fume Hood Interface (FHI) Designed with audible and visual alarms FHI Backlot LCD screen with LED sidebars Password protected menu Easy to use MENU system for fast and simple setup of system Service port on back for use with Price LINKER2 setup software Included RJ45 plenum rated cable for fast, error free hookup Setup Wizard walk through setup of PFHC when first powered up 1 of 4
SPECIFICATIONS Input Power (PRPM): Environmental (operating): Environmental (storage): Inputs: Sidewall pressure sensor: Outputs: Indicators: Connections: Communication: 24 VAC, 50/60 Hz, 15VA (plus eternal loads), Class 2 10 C to 50 C (50 F to 122 F), 0% to 95% R.H. (non-condensing) -30 C to 50 C (-22 F to 122 F), 0% to 95% R.H. (non-condensing) 2 Binary inputs: (Configurable for duct pressure status from LMX), 2 Analog inputs: 0-10 VDC inputs (configurable for sash sensor, sidewall sensor, flow measuring station, or duct pressure from LMX) Accuracy better than 0.2% FS near zero, temperature compensated 2 dry binary outputs rated at 0.2 amps each (maimum 24 VAC/ VDC), protected with thermal fuse, 2 analog outputs: (10mA maimum, 0-10 VDC), configurable for pressure and alarm outputs RGB LEDs on Monitor side indicator bars and LCD screen Status LEDs on all I/O RJ45, RJ-12, Removable terminal blocks. Fume hood communication port, RJ-45 connection Optional Native BACnet MS/TP (BTL Listed) Specifications subject to change without notice FHI Display: 5 1/8 H 3 1/4 W 1 3/16 D - Fire Retardant Anti-Microbial Plastic FHI Wall Plate: 4.5 H 4.6 W 2 D Stainless Steel with Fire Retardant Plastic Sensor Cover 3 1/4 W 1 3/16 D 4.6 W 3.5 clearance from wall for bend radius of cable 2 D 5 1/8 H 4.5 H 2 of 4
TYPICAL WIRING SELECTION CHART FHM FUME HOOD MONITOR FHC FUME HOOD CONTROLLER LSC LABORATORY SPACE CONTROLLER Side wall Sensor Face Velocity Monitoring Side wall Sensor Face Velocity Control Sash Position Sensor Face Velocity Control Combination Sidewall/Sash Position Face Velocity Control Analog Valve Pressure Output Volumetric Offset Control Temperature Control Humidity Control Room Pressure Monitor Native BACnet 3 of 4
PRODUCT CODE FHC-FHIKP-SWS-SPS1-OCC-PLSC Model Hood Interface Sidewall Pressure Sensor Sash Position Sensor Occupancy Sensor Network Connectivity FHC - Fume Hood Controller FHI-KP - Standard Keypad Interface with 2 Line Display SWS - 1 Sidewall Face Velocity Sensor SWS2-2 Sidewall Face Velocity Sensors SPS1,SPS2, SPS3 - Sash Position Sensor OCC - Infrared Fume Hood Occupancy Sensor Blank - None PLSC - Network connection to PLSC BAC - Native BACnet MS/TP interface 4 of 4
CRITICAL CONTROLS - PRODUCT OVERVIEW FUME HOOD MONITOR (FHM) The Fume Hood Monitor (FHM) is designed to provide intelligent monitoring of fumehoods with native BACnet communication. Using the latest in microcontroller and sensor technologies the FHM can measure airflow using a crossflow sensor in the duct and, using a sash position sensor, display the face velocity on the local LCD display. The monitor features visual and audible alarms signaling unsafe conditions with illuminating sidebars provide 180 degree visual status. The commissioning software allows quick and thorough setup of the FHM system with the ability to generate a printable test report. Product Features FHM: Measures airflow using a flow measuring station or sidewall sensor High speed flash based microprocessor Multi-stage surge protection against voltage spikes on 24 VAC input Native BACnet MS/TP Connection LED s for BACnet data TX/RX, BACnet wiring fault, and MS/TP termination Pluggable terminal blocks Electrical enclosure with 24 VAC transformer Interface Features: Designed with audible and visual alarms Backlit LCD Screen with LED side bars that offer 180 degree viewing of current room status Password protected menus Easy to use menu system for fast and simple setup of system Service port on back for use with Price LINKER2 setup software Included RJ45 plenum rated cable for fast, error free hookup Setup Wizard walk through setup of FHM when first powered up 1 of 2
SPECIFICATIONS Integrated Transformer: 120 VAC to 24 VAC, 50/60 Hz, 50VA Class 2 Input Power (PRPM): 24 VAC, 50/60 Hz, 10VA (plus eternal loads), Class 2 Environmental (operating): 10 C to 50 C (50 F to 122 F), 0% to 95% R.H. (non-condensing) Environmental (storage): -30 C to 50 C (-22 F to 122 F), 0% to 95% R.H. (non-condensing) Sidewall pressure sensor: Inputs: 2 Binary inputs: (Configurable for duct pressure status from LMX) Outputs: 2 Analog inputs: 0-10 VDC inputs (configurable for sash sensor, sidewall sensor, flow measuring station, or duct pressure from LMX) ±25 Pa (0.1 in. wg), accuracy better than 0.2% FS near zero, temperature compensated 2 dry binary outputs rated at 0.2 amps each (maimum 24 VAC/VDC), protected with thermal fuse 2 analog outputs: (10mA maimum, 0-10 VDC), configurable for pressure and alarm outputs Indicators: RGB LEDs on Monitor side indicator bars and LCD screen Status LEDs on all I/O Connections: RJ45, RJ-12, Removable terminal blocks. Specifications subject to change without notice 2 of 2
PRODUCT OVERVIEW LABORATORY SPACE CONTROLLER (LSC) The LSC is designed for laboratory applications that require airflow and temperature control using a dedicated system that ties into the fume hoods within the space. The digital controller maintains a constant volumetric offset between the supply, general ehaust and fume hood air valves in the VAV system to ensure accurate control of directional airflow. Fume hood controllers are daisy chain wired to the controller and the local network uses Price M-Net for a less than 1 second speed of response between the controllers. The LSC can tie in a room pressure sensor to monitor the pressure in the space with a local visual and audible alarm option available. Room temperature and humidity are measured using a Price thermostat mounted in the occupied space. Simple connection to thermostat is provided with plug and play RJ45 cables. Outputs for the LSC for reheat and humidity include binary (24VAC), staged, and analog (0-10VDC). With Native BACnet MS/TP communication, the LSC can tie into building management systems (BMS). When connected to the network both the space and attached fume hood variables are available for monitoring and control. Commissioning software allows quick and thorough setup of the LSC system with the ability to generate a printable test report. Product Features Laboratory Space Controller (LSC): Volumetric control up to 8 supply or general ehaust valves System control of up to 16 fumehoods Temperature and humidity controls High speed flash based microprocessor Multi-stage surge protection against voltage transients on 24 VAC input Pluggable terminal blocks Panel Enclosure or Valve mount options Two level password protected menus Service port on Thermostat or RPI for use with Linker2 setup software Setup Wizard walk through setup of the PLSC when first powered up Simple plug and play RJ45 connections to the fume hood controllers, thermostats, and pressure monitors. 1 of 4
SPECIFICATIONS Input Power: Environmental (operating): Environmental (storage): Inputs: Optional pressure sensor: Outputs: Indicators: Connections: 24 VAC, 50/60 Hz, 15 VA (plus eternal loads), Class 2 10 C to 50 C (50 F to 122 F), 0% to 95% R.H. (non-condensing) -30 C to 50 C (-22 F to 122 F), 0% to 95% R.H. (non-condensing) 2-6 Binary inputs: (Configurable for duct pressure status from LMX), 8-10 Analog inputs: 0-10 VDC inputs (configurable for valve, terminal airflow, or duct pressure from LMX), 1 temperature input: 10k type J analog thermistor RJ45 jack - Thermostat ±25 Pa (0.1 in. wg), accuracy better than 0.2% FS near zero, temperature compensated 2 dry binary outputs rated at 0.2 amps each (maimum 24 VAC/VDC), protected with thermal fuse 3 24 VAC binary outputs rated at 0.2 amps each (maimum 24 VAC/VDC), protected with thermal fuse 6 analog outputs: (10mA maimum, 0-10 VDC), configurable for pressure and alarm outputs, actuator (Venturi valve), reheat and humidifier Status LEDs on all I/O RJ45, RJ-12, Removable terminal blocks. Communication: Fume hood communication port, RJ-45 connection Optional Native BACnet MS/TP (BTL Listed) Specifications subject to change without notice 2 of 4
TYPICAL WIRING 3 of 4
DIMENSIONAL DATA Electrical Enclosure: 8 W 16 L 3 D Powder Coat White Paint Finish Top view 16 L 8 W Side view 8 W 3 D SELECTION CHART FHM FUME HOOD MONITOR FHC FUME HOOD CONTROLLER LSC LABORATORY SPACE CONTROLLER Side wall Sensor Face Velocity Monitoring Side wall Sensor Face Velocity Control Sash Position Sensor Face Velocity Control Combination Sidewall/Sash Position Face Velocity Control Analog Valve Pressure Output Volumetric Offset Control Temperature Control Humidity Control Room Pressure Monitor Native BACnet PRODUCT CODE LSC-RPI-RPS1-BAC-SENS Product Interface Type # of Pressure Sensors Network Type Thermostat Type LSC - Laboratory Space Controller RPI - LCD Room Pressure Interface RPS1 - One Room Pressure Sensor RPS2 - Two Room Pressure Sensors BAC - Native BACnet MS/TP Network SENS- T-Stat with Blank Face DIAL- T-Stat with Dial Setpoint LCD- T-Stat with LCD Screen LCDH - T-Stat with LCD Screen and Integrated Humidity Sensor MOT- T-Stat with LCD Screen and Motion Sensor C02H- T-Stat with LCD Screen and Integrated CO2 and Humidity Sensors 4 of 4