HLS34 Modbus FCU/VAV Controllers installation instructions

Similar documents
FCU-MULTI Modbus Fan Coil Unit Controller

CONTENTS CONTROLLERS room controllers room units control units PRODUAL 3 CATALOGUE

PDS2-H Weather Compensator with Modbus Communications

MOD-RI Room Interface Modules with Modbus

Communicative controller for VAV systems

STRA-17 Room controller. Installation and maintenance manual. Content

FCU-4 FAN COIL CONTROLLER

LLR-MOD Modbus Light Level and Occupancy Sensor

SE7600E Series Application Guide

Pre-programmed room controller with display and communication

Pre-programmed room controller with display and communication

Field selectable application type and room module series, via dip-switches on controller

TER-MOD Active Room Temperature Sensors (Controllers) with Modbus

RC-CDTO. Pre-programmed room controller with display, communication and three-point control

CDR Room CO 2 and Temperature Sensor with Modbus

Room controller STRA-17

Suitable for a wide range of installations with wall-mount, flush-mount and hand-held remote control options.

RHR-MOD Combined Room Temperature and Humidity Sensors (Controllers) with Modbus

ExactLogic BACnet Communicating Pressure Dependent VAV Damper Control with Heat EXL01820 Sequence Datasheet

MOD-IO9 Modbus Input / Output Modules, Wall Mounted

ExactLogic BACnet Communicating Zone Damper EXL01710 Sequence Datasheet

CDR-RH Room CO 2, Temperature and Humidity Sensors (Controllers)

FCU-4 FAN COIL CONTROLLER

USER GUIDE TEHR LU / TEHR-M

RCF-230CTD. Room controller for fan-coil applications with outputs for two thermal or one 3-position actuator or function for an electric heater

USER GUIDE TEx LU / TEx-M

Measure & Control Temperature & CO2 levels with analog & digital I/O

5 year. Controllers for comfortable indoor climate and energy efficiency

TC-9102 Terminal Controller

ExactLogic BACnet Communicating Thermostat EXL01716 Sequence Datasheet Duel Deck VAV

ExactLogic BACnet Communicating Thermostat EXL01816 Sequence Datasheet

RCF-230CD. Communicating room thermostat for fan-coil applications with on/off outputs

SE7600E Series Application Guide

CCM-204 MULTI-PURPOSE TEMPERATURE CONTROLLER

Temperature controller Ducted systems

Microprocessor based Temperature / CO2 Controller c/w 365 Day Time Switch & Modbus Communication.

UC102 basic version with display and knob UC102BL version with display, knob and backlight UC102DK version without knob and display

RWD68U Universal Controller

TC-8900 Controller Units with PM-8900 Power Modules

DataNab it8: Intelligent Communicating Thermostat

Millennium Simplicity Elite Parameter Points and Quirks

TLR-D42 with OPA-D42 Intelligent PI fan coil controller for modulating actuators. Cabinet mounted base, wall mounted operation terminal.

RCF-230CAD. Communicating room controller for fan-coil applications with two analogue V DC outputs

Technical data sheet

RTD-RA. realtime. Installation Instructions. English A B. Installation Instructions Control Systems LEDS ALL DIMENSIONS IN MM

Control systems. Efficient room control

Networkable Dual Duct VAV Controller Specification and Installation Instructions

Evolution TH. Pre-configured controller with display, clock and communication. Evolution. Applications. TH version. Sensors

NT50 Series RS485 Modbus RTU Networking LCD Fan Coil Thermostat

NT10 Series RS485 Modbus RTU Networking LCD Fan Coil Thermostat

Viconics VT76x6W Water-source Heat Pump Controllers Engineering Guide Specification

RCF-230CAD. Room controller with communication for fancoil applications with two analogue V DC outputs

Master room unit for RRV controllers

FLTA Wireless Room Transmitter Control Modules

TF243 Series Digital Thermostat Fan Coil Unit Control

MiG2 CONTROLLERS. 2 & 4 Stage General Purpose Controllers, with Air-conditioning Facilities

ATR121 Controller with Dual Setpoint

Room Temperature Controller

UCU Room Display. Operation Modes. Features. Applications DATASHEET

USER GUIDE PEL / PEL-M

Free Energy Band RCC30U Room Temperature Controller for Four-pipe Fan Coil Unit

RXB10.1. Room controller. Siemens Building Technologies Building Automation DESIGO RXB. for chilled ceilings and radiators with EIB bus communication

M1000 INTELLIGENT ZONE CONTROL SYSTEM

DUKE UNIVERSITY DESIGN & CONSTRUCTION STANDARDS

ECON-ZIP-BASE. ZIP Economizer Base Unit. Wiring Diagram USA CANADA LATIN AMERICA / CARIBBEAN

TAC Xenta 101-VF. 3-Speed Fan Coil Controller. TAC Xenta

Non-communicating room controllers

Application program: description and examples

Room Temperature Controller

Description. descriptors, makes set-up and monitoring very user friendly.

USER GUIDE PEL 8K / PEL 8K-M

Temperature controller Multi-zone ducted systems

CDD4 Series Room CO2 Transmitter Installation Instructions

CONDUCTOR W4. Installation instruction for W4.1 and W To mount the controller. Controller. Mounting on a DIN rail

SRT-50 Slimline Touchscreen Thermostats

VZ7000 Series. BACnet Commercial Zoning System

DESIGO RX Individual room controllers. for fan-coil systems, chilled ceilings and radiators, with LONMARK-compatible bus communications

AIAS. Technical description

Universal Controller

RS-485 Modbus RTU Networking Room Thermostats with LCD for Fan Coil Units

SEZ7000 Series. Wireless Commercial Zoning System

Semi flush-mounted room temperature controllers with LCD

Andover ContinuumTM. b3850 Series Terminal Controllers

Fast Route to Reliable Energy Savings ZIP Economizer

SEZ7656E1045B. Installation Guide for BACnet MS/TP RTU Terminal with IAQ Control CONTENTS

THERMOSTATS & CONTROLLERS

FLTA-KP10 Wireless Receiver/ Control Modules for HRP/LRP

MIO12 Intelligent Modbus Input/Output Modules

TEMPERATURE CONTROLLER 2 HEAT/ 2 COOL with Digital Room Temperature Display. Made in Australia 100% Australian Owned Company

FANCOIL CONTROLLER UNIT TC17B01KNX. Product Handbook

RTD-NET Installation Instructions

Modbus RTU/TCP GOLD RX/PX/CX/SD, GENERATION C/D Applicable to program version 1.05 and newer versions

Specification Sheet For electronically commutated motors

Semi flush-mounted room temperature controllers with LCD

Room controller LS 990 / LS plus Stainless Steel / Aluminium

R7426A TEMPERATURE CONTROLLER WITHOUT REAL-TIME CLOCK. MicroniK 200. Order Numbers

Networkable VAV Controller Specification and Installation Instructions. Controller Model EVCB14NIT4X (4 TRIACS / independent / external motor)

FXVMA Variable Air Volume (VAV) Box Controller

Control system. Type FSL-CONTROL II. Modular, stand-alone room control system, specially for decentralised ventilation systems (with bus communication

OP10. Pre-programmed, configurable controller for simple applications

Transcription:

HLS34 Modbus FCU/VAV Controllers installation instructions The HLS34 is specifically designed for individual room temperature and zone control applications. The controllers have built-in RS-485 channel for Modbus communication. The controllers can be connected to any supervisory software/system that supports Modbus RTU. The HLS34 has built-in display and unique touch sensitive buttons for adjusting the user parameters and to configure the controller. The controller supports 0..10V actuators, 3-point controlled actuators and thermic actuators. One of the controller 0..10Vdc outputs can be configured for fan speed control via FCRY3 relay module. Temperature is detected by the internal sensor of the HLS34. If an external temperature sensor such as return air sensor or remote room sensor is required, this can be connected to the wiring terminals provided on the controller. The external sensor type is NTC10. The controller has DAY and NIGHT operating modes. When in the NIGHT mode the controller can be overridden to the DAY mode via a hardware input, by touching day extension button or over the MODBUS network. The controller has also a CO2 measurement input for boosting the ventilation (fan speed) in case of high CO2 level in the room space. Model Type Model Description HLS34 HLS34 Room Temperature Controller with Modbus Networking Capability Technical Data Power Supply 24Vac/dc (20 26V), <1VA NOTE! If using DC-voltage only 0..10V outputs are operational Inputs Built-in Temperature Sensor 1 x NTC10 e.g. TEHY -NTC10 (for control or measurement only) 1 x Volt-Free (PIR normally closed) 1 x Analogue (CO2 measurement) Outputs 2 x 0..10Vdc (Heating/Cooling Actuators, VAV or Fan Speed Control) 4 x 24Vac Triacs, 1A maximum (3-Point Actuators / Thermic Actuators) Communications RS-485 Modbus RTU, 9600/19200/38400 bps, 8 data bits, Parity None, 1 Stop Bit (Up to 128 devices per segment) Set Point Adjustment DAY SETPOINT 21 C ±3 C (factory default); setpoint adjustable pressing + and - buttons within programmable ± range; network setpoint available via Modbus or in the configuration mode NIGHT SETPOINT 5-20 C (factory default 18 C); adjustment available via Modbus or in configuration mode Accuracy ±0.5 C Dead Zone DAY mode Dz = 0..3 C (factory default = 0.3 C) Relaxed mode Dz = 0..10 C Proportional Band Xp = 1..8 C (factory default = 4 C) Integral Action Time Tn = 50..500s (factory default = 300 sec) 3-Point Control Mt = 30..300s (factory default = 180 sec) Actuator Runtime Protection Class IP20 Operating Humidity 0..95% rh non-condensing Wiring Terminals 1.5 mm 2 Housing ABS Plastics Dimensions 87W x 86H x 32D mm Enquiries: T: +358 5 230 9200 F: +358 5 230 9210

Wiring Terminals The electrical installation, device connection and commissioning can only be carried out by qualified professionals and according to the local wiring regulations! AIR-SIDE APPLICATION WIRING

Controller options Operation Modes HLS34 has two operation modes: DAY and NIGHT. The unit can be switched between day and night modes either via Modbus network or via the DAY EXTENSION typically connected to PIR. The user can also change NIGHT mode to DAY mode by pressing MAN IN THE HOUSE (occupancy) button on the unit. After 2-hours (adjustable) DAY mode returns automatically back to the NIGHT mode. When in DAY mode the controller operates the valve outputs according to the below diagram. DAY MODE In the DAY mode the temperature is controlled to the setpoint using PI-control. The controller has adjustable dead zone between heating and cooling modes. The controller DAY setpoint (SP) is calc ulated as follows:- SP = SP network ± SP local, where SP network is setpoint set via Modbus network and SP local is the setpoint set by the user by pressing + and - buttons. SP local range is limited at the commissioning stage (default ±3 C) In the NIGHT mode the controller controls to the NIGHT/FROST setpoint. If the temperature falls below the NIGHT setpoint (5..20 C), the heating output is opened and the fan is overridden on (if fan speed control has been enabled). The NIGHT setpoint is adjustable via Modbus network or in the configuration mode. When the controller returns to the DAY MODE from NIGHT, the controller DAY setpoint can return to the DAY setpoint programmed previous day, or the DAY SP can be reset to the SP network Modbus Network Setpoint. This is a configurable option (configuration parameter SP_ND). If no network setpoint is available 21 C is used as default. Air-side application Description of operation

NIGHT MODE The configuration parameter J7 sets the controller operation during the night time; Relaxed Deadzone or Frost Protection (Thermostat). 1) Relaxed Deadzone at Night The controller operates as in the DAY mode but the deadzone around the controller is expanded to NDz value. Therefore at the night time the controller energy consumption is reduced. NOTE: It is also possible to set the night deadzone to smaller value than day deadzone. 2) Frost Protection (Thermostat) In the NIGHT mode the controller controls to the NIGHT/FROST setpoint. If the temperature falls below the NIGHT setpoint (5..20 C), the heating valve is opened and the fan is overridden on (if fan speed control has been enabled). The NIGHT setpoint is adjustable via Modbus network or in the configuration mode. If the temperature exceeds 2 C the NIGHT setpoint the heating valve is closed and the fan is switched off. Fan Speed Control Fan speed control can be enabled during the commissioning (configuration parameter FAN). When fan speed control is enabled the Heating Analogue output is converted operate as the control signal to the FCRY3 fan speed control relay module. Ventilation Boost (CO2 Control) Day Extension via digital input In automatic control the fan speed output operates as follows:- - Valves closed Fan speed output 0% - Heating/Cooling Valve Opens Fan speed output is set to 3.3V (Speed 1) - Heating/Cooling Valve Opens more than 25% speed output is set to 6.6V (Speed 2) - Heating/Cooling Valve Opens more than 50% speed output is set to 10V (Speed 3) Automatic Speed 3 control is disabled as default. However, the user can manually override speed 3 on through the keypad. Typically speed 3 causes a higher level fan noise and therefore it is recommended that this is manual override option operated by the user. Automatic Speed 3 control can be enabled during the commissioning via basic settings. When the controller switches to NIGHT mode or the temperature is within the dead zone, the fan is automatically switched OFF after 5 minutes timeout. If HDK or HDH CO2 transmitter is connected to the controller analogue input U1, the controller can be enabled to boost the fan speed / switch the fan On in case of high CO2 content in the occupancy space. This is a very useful feature to provide demand based ventilation. High CO2 level overrides the fan speed set by the temperature based fan speed control. The controller has hardware digital input that can be connected to a momentary push button contact (e.g. PJP1) or to a PIR sensor (e.g. LA24) to override the controller to DAY operation. These are ty pically used out of hours to provide comfort control. Alternatively PIR input can be used as the primary means of switching between DAY and NIGHT modes. The digital input is normally closed. Day Extension via keypad VAV Control with Fresh Air Demand Boost Air-side application NOTE: The digital input is activated when it is first time closed. The controller is supplied with the digital input as open contact. The controller can be overridden to DAY operation by pressing the MAN IN THE HOUSE occupancy button. When pressed the controller is overridden to DAY mode for the period of two hours. The extension time is adjustable between 1..480 minutes via Modbus network. The controller can also be used as Variable Air Volume controller by connecting the VAV Box damper to the output Y1. The output Y1 is then modulated according to temperature demand in the room space. If HDK or HDH CO2 transmitter is connected to the controller analogue input U1, the controller can increase the fresh air demand i.e. overdrive the analogue output Y1 when the CO2 content in the room space exceeds the acceptable limit. The CO2 influence is set via configuration parameters CO2 LO (e.g. 750 ppm) and CO2 HI (e.g. 1250 ppm). Between the CO2 limits the influence is calculated using linear relationship i.e. when CO2 measurement is at CO2 HI setpoint, the CO2 influence is 100% (Y1=10V). Air side application controls the temperature by modulating the damper output and 3-point control outputs. When the room temperature is at the setpoint the control output is at 50%. When the temperature increases above the setpoint the control signal starts to drop providing cooling to the room space. When the temperature drops below the setpoint the control output increases to provide heating to the room space. For the air-side application to operate correctly set configuration parameters J1 and J2 to Direct Operation.

Controller Configuration The controller is parameterised locally via a configuration mode, or using HLS34 Handheld Configuration Tool. The HLS34 handheld tool allows quick configuration of large number of controllers. To configure the controller locally, first remove the top cover. A CONFIGURATION MODE JUMPER is located below the LCD display. When the jumper is set the controller is in normal operation. By removing the jumper the controller enters to the configuration mode. Once the configuration has been completed, by setting the jumper the controller returns to the normal operation. Configuration Parameters NOTE: The controller is supplied with the configuration jumper unset i.e. in the configuration mode

Network Diagram Up to 128 HLS34 controllers can be connected to a single network segment. The diagram below illustrated the typical installation where the room controllers are connected on the floor level to the Netbiter embedded web-server. Each Netbiter holds a time schedule for the floor to switch the controller between day and night operation modes.

Modbus Registers The controller supports the following Modbus registers and function codes. The default communication speed is 9600 bps, 8 data bits, Parity None and 1 Stop Bit. Register Parameter Description Data Type Range FUNCTION CODE 01 - READ COILS 1 Overdrive mode Bit0 On - Off 2 NIGHT-mode Bit1 On - Off 3 SERVICE ALARM Bit2 On - Off 5 Fan Speed 1 asked Bit4 On - Off 6 Fan Speed 2 asked Bit5 On - Off 7 Fan Speed 3 asked Bit6 On - Off 8 Fan Speed 4 (Auto) asked Bit7 On - Off FUNCTION CODE 02 - READ DISCRETE INPUTS 1 Occupied by PIR ( NIGHT mode to DAY-mode ) Bit0 On - Off 2 Manually Occupied ( NIGHT mode to DAY-mode ) Bit1 On - Off 3 DAY EXTENSION ( NIGHT mode to DAY-mode ) Bit2 On - Off 4 EXT.S (External Sensor) Bit3 On - Off 5 Fan Speed 1 run Bit4 On - Off 6 Fan Speed 2 run Bit5 On - Off 7 Fan Speed 3 run Bit6 On - Off FUNCTION CODE 03 - READ HOLDING REGISTERS 2 Coils 16-01 16 bit 3 Fan Speed (Set by Network) Signed 16 0-1 - 2-3 - 4 4 Cooling Output (Set by Network) Signed 16 0,0 100,0 (%) 5 Heating Output (Set by Network) Signed 16 0,0 100,0 (%) 6 Set Point (Set by Network) Signed 16 5,0 37,0 (C) 13 DAY EXTENSION period Signed 16 1 480 (min) FUNCTION CODE 04 - READ INPUT REGISTERS 1 Discrete Inputs 16-01 16 bit 2 Coils 16-01 16 bit 3 Fan Speed (Set by Network) Signed 16 0-1 - 2-3 - 4 4 Cooling Output (Set by Network) Signed 16 0,0 100,0 (%) 5 Heating Output (Set by Network) Signed 16 0,0 100,0 (%) 6 Set Point (Set by Network) Signed 16 5,0 37,0 (C) 7 Temperature Signed 16-60,0 60,0 (C) 8 CO2 Signed 16 0 2000 (ppm) 9 Current Cooling Output Signed 16 0,0 100,0 (%) 10 Current Heating Output Signed 16 0,0 100,0 (%) 11 Current Fan Speed Signed 16 0-1 - 2-3

12 Current Setpoint Signed 16 5,0 37,0 (C) 13 DAY EXTENSION period Signed 16 1 480 (min) FUNCTION CODE 05 - WRITE SINGLE COIL 1 Overdrive mode (Cooling and Heating outputs) Bit0 On - Off 2 NIGHT-mode Bit1 On - Off 3 SERVICE ALARM Bit2 On - Off 5 Fan Speed 1 asked Bit4 On - Off 6 Fan Speed 2 asked Bit5 On - Off 7 Fan Speed 3 asked Bit6 On - Off 8 Fan Speed 4 (Auto) asked Bit7 On - Off FUNCTION CODE 06 - WRITE SINGLE REGISTER 2 Coils 16-01 16 bit 3 Set Fan Speed Signed 16 0-1 - 2-3 - 4 4 Cooling Output (Overdrive mode = on ) Signed 16 0,0 100,0 (%) 5 Heating Output (Overdrive mode = on ) Signed 16 0,0 100,0 (%) 6 Set Point by Network ( DAY value only ) Signed 16 5,0 37,0 (C) 13 DAY EXTENSION period Signed 16 1 480 (min) FUNCTION CODE 16 - WRITE MULTIPLE REGISTERS 2 Coils 16-01 16 bit 3 Set Fan Speed Signed 16 0-1 - 2-3 - 4 4 Cooling Output (Overdrive mode = on ) Signed 16 0,0 100,0 (%) 5 Heating Output (Overdrive mode = on ) Signed 16 0,0 100,0 (%) 6 Set Point by Network ( DAY value only ) Signed 16 5,0 37,0 (C) FUNCTION CODE 22 - MASK WRITE REGISTER 2 Coils 16-01 16 bit AND 0 0xFFFF OR 0 0xFFFF