Integrotech sp. z o.o. Plac Zwycięstwa 2 bud. D lok Łódź, Poland

Size: px
Start display at page:

Download "Integrotech sp. z o.o. Plac Zwycięstwa 2 bud. D lok Łódź, Poland"

Transcription

1 MSP-MK1.x is a group of communication modules which consists of: a metrology communication module MSP-MK1.0 (basic), a 4-port Fast Ethernet switch MSP-MK1.1 and a 3-port Fast Ethernet switch with fibre-optic port MSP-MK1.2 (opto). MSP-MK1.0 consists of: a GPRS modem, Fast Ethernet port, RS-485 port, three ports RS-232/422/485 (software configurable mode), six voltage and digital inputs, one connector outputs and bus port to which one of the remaining devices can be connected: MSP-MK1.1 or MSP-MK1.2. MSP-MK1.0 offers conversion of the media with GPRS and Ethernet on RS-232/422/485 with multiple access the same communication port may be read simultaneously and independently from two networks. The device is supplied with software for monitoring and configuration. This manual contains a description of the device and the configuration software. Integrotech sp. z o.o. Plac Zwycięstwa 2 bud. D lok Łódź, Poland

2 IO/MSP-MK/EN/r1-2 / 17 - Integrotech sp. z o.o. Document title User manual for MSP-MK1.x communication modules Version IO/MSP-MK/EN/r1 Issue date History of amendments r First version of the document. Describes the Configurator software, options for connecting devices and a description of acoustic diagnostics at start-up. This document includes an alphabetical index. Integrotech sp. z o.o. Plac Zwycięstwa 2 bud. D lok Łódź, Poland tel.: fax: office@integrotech.com.pl Document version: IO/MSP-MK/EN/r1

3 Integrotech sp. z o.o. - 3 / 17 - IO/MSP-MK/EN/r1 Contents List of illustrations... 4 List of tables Introduction MSP Modular Measurement System MSP-MK communication modules (MK) in the MSP family MSP-MK1.0 multifunction communications and measurement module MSP-MK1.1 Fast Ethernet switch MSP-MK1.2 (opto) Fast Ethernet switch with fibre-optic port Basic Specifications Operating conditions Common features of the MSP-MK group of units Physical properties Working conditions MSP-MK1.0 (basic) and MSP-MK1.0i Voltage digital inputs Connector (relay) output Communication ports GPRS modem Ethernet Description of outputs MSP-MK1.1 (switch) Description of outputs MSP-MK1.2 (opto) Description of outputs Preparing for operation Installation Start-up procedure Servicing mode Initialising communication Initialising LAN Initialising GPRS Acoustic diagnostics during the start-up procedure Description of the Configurator software Wersja dokumentu: IO/MSP-MK/EN/r

4 IO/MSP-MK/EN/r1-4 / 17 - Integrotech sp. z o.o. 4.1 Connection with the device Maximum time of communication failure Modem settings LAN network settings Routing TCP ports to COM communication ports Settings for COM ports Routing between communication ports (MSP-MK1.0i only) Optimising multiple access Multiplying connections to the target device Maximising the communication speed Adjusting permissible response timeouts Alphabetical Index List of illustrations Figure 1. Distribution of the MSP-MK1.0. module s outputs... 8 Figure 2. MSP-MK1.0 name plate... 9 Figure 3 Front view of the MSP-MK1.0 module... 9 Figure 4. Main window of the Configurator application Figure 5. Communication medium selection window Figure 6. Setting the time of the automatic reset Figure 7. GPRS settings Figure 8. LAN settings Figure 9. GPRS interface s TCP port settings Figure 10. LAN interface s TCP port settings List of tables Table 1. Review of MSP-MK communication modules... 5 Table 2. Distribution of MSP-MK1.0. module s outputs... 8 Table 3. Distribution of MSP-MK1.1 module s outputs... 9 Table 4. Distribution of MSP-MK1.2 module s outputs Table 5. COM4 port s settings in the servicing mode Table 6. Acoustic diagnostics for the MSP-MK1.0 device Document version: IO/MSP-MK/EN/r1

5 Integrotech sp. z o.o. - 5 / 17 - IO/MSP-MK/EN/r1 1 Introduction Thank you for choosing a device from the Integrotech family of MSP (Modular Measurement System) products. Its design and functions are the result of our many years of experience in the field of measurement, communication and automation of processes in the demanding gas appliances market. We welcome any comments concerning satisfaction with your choice, as well as those suggesting further development of the purchased device. 1.1 MSP Modular Measurement System Modular Measurement System is the name of a family of products whose primary purpose is measurement of gaseous fuels, which can operate as independent units or as a set of measuring devices with varying degrees of complexity of architecture. The MSP family includes, among others: MSP-02-FC Flow Computer, (MSP-01WW.2A, MSP-01WW.6D analogue and pulse separators (MSP-01WW.2A, MSP-01WW.6D) analogue and pulse separators and mixed analogue-pulse separators in a spark-free implementation (MSP-SEP01.AA, SEP01.DD SME, SME-SEP01.AD) analogue output modules (MSP-01WY.2A, MSP-01WY.4A) MSP-nCOM and MSP-MK1.x. communication modules 1.2 MSP-MK communication modules (MK) in the MSP family The MSP-MK1.x series of communication modules is a group of sophisticated measuring and communication devices, each of which can operate separately, but can also be easily combined by means of the connector on the housing base. The most advanced and expanded representative of this group is the MSP-MK1.0 module, whose communication options can be further expanded by adding one of the other devices - MSP-MK1.1 (switch) or MSP-MK1.2 (opto). Catalogue name Alias Features Possible operating modes GPRS Modem 1 Fast Ethernet Port (RJ45) as an independent device MSP-MK1.0 BASIC 1 RS-485 Port with attached module 3 RS-232/422/485 ports o MSP-MK1.1 6 voltage-digital inputs 1 connector (relay) output o MSP-MK1.2 MSP-MK1.1 SWITCH 4 Fast Ethernet ports (RJ45) as an independent device attached to the device o MSP-MK1.0 MSP-MK1.2 OPTO as an independent device 3 Fast Ethernet ports (RJ45) attached to the device 1 fibre optic port (SC or ST) o MSP-MK1.0 Table 1. Review of MSP-MK communication modules MSP-MK1.0 multifunction communications and measurement module The MSP-MK1.0 communication module is an intelligent communication and measurement device. This unit features: a four-band GSM (GPRS) modem one Fast Ethernet port in the form of an RJ-45 socket Wersja dokumentu: IO/MSP-MK/EN/r

6 IO/MSP-MK/EN/r1-6 / 17 - Integrotech sp. z o.o. three RS-232/422/485 ports (the operating mode of these ports configured by the software) one RS-485 port, six voltage-digital inputs (each digital input has the ability to switch to 0-30V voltage input operating mode) one low power connector (relay) output The device can be treated as: a media converter (serial ports server): o GPRS -> RS-232/422/485 o Ethernet -> RS-232/422/485 a multiplexer: o GPRS+Ethernet -> RS-232/422/485 access from many different networks can be obtained to one communication port simultaneously a six-port telemetric input module, available via LAN or WAN (GPRS), equipped with: o six signal inputs, or o six voltage inputs or o any combination of signal and voltage inputs, giving a total of six inputs; a control module (relay output), available via LAN or WAN (GPRS) network or as any combination of the above, within the available inputs, outputs, and communications ports. One can connect to this device a MSP-MK1.1 type 4-port Ethernet switch or an MSP-MK1.2 switch with three RJ-45 ports and one fibre-optic port, additionally increasing the number of and expanding the range of available connection types and media conversions to include the following : a media converter (serial ports server): o Ethernet (fibre-optic) -> RS-232/422/485 a multiplexer: o GPRS + Ethernet + fibre-optic -> RS-232/422/485 access from many different networks can be obtained to one communication port simultaneously by means of three different media Note 1. Connecting and disconnecting MSP-MK1.x devices must be carried out with the power disconnected. Note 2. With the MSP-MK1.1 (switch) or MSP-MK1.2 (opto) module connected, the Ethernet port of the MSP-MK1.0 device is inactive (offline) MSP-MK1.1 Fast Ethernet switch The MSP-MK1.1 module is a 4-port Ethernet switch, which can work as an independent unit, or attached via a dedicated connector in the housing to the MSP-MK1.0 module MSP-MK1.2 (opto) Fast Ethernet switch with fibre-optic port The MSP-MK1.1 module is a 3-port Ethernet switch, additionally equipped with one fibre-optic port (SC or ST), which may work as an independent unit, or attached via a dedicated connector in the housing to the MSP-MK1.0 module Document version: IO/MSP-MK/EN/r1

7 Integrotech sp. z o.o. - 7 / 17 - IO/MSP-MK/EN/r1 2 Basic Specifications 2.1 Operating conditions The units can be installed in rooms free of explosive gases and vapours and protected from access by individuals untrained in the operation of the device. 2.2 Common features of the MSP-MK group of units Physical properties Dimensions Installation mm 35 mm DIN rail Working conditions Ambient temperature C Degree of protection IP20 Power supply 6 35 VDC 2.3 MSP-MK1.0 (basic) and MSP-MK1.0i Power consumption 3.6 W Power supply Maximum power With a power supply of consumption 600 ma 6 V 300 ma 12 V 150 ma 24 V 120 ma 30 V 105 ma 35 V Weight < 205 g (without antenna) Voltage digital inputs Number of inputs 6 Range of input voltages 0-30 V Connector (relay) output Maximum power 2 A Maximum voltage 30 V Communication ports Baud rates [bit/s] 600, 1200, 2400, 4800, 9600, 19200, 38400, 57600, RS-232/422/485 3 units, operating mode set by the software RS unit GPRS modem Frequency range 850 / 900 / 1800 / 1900 MHz Power consumption class 4 MHz), 1 MHz) GSM standards handled Phase 2/2+ Characteristics GPRS multi-slot class 10/8, GPRS mobile station class B Ethernet Ethernet Auto-negotiation Auto-MDI/X 1 Fast Ethernet 10/100 Mbps port Yes Yes Wersja dokumentu: IO/MSP-MK/EN/r

8 IO/MSP-MK/EN/r1-8 / 17 - Integrotech sp. z o.o Description of outputs Power, communication and signalling circuits are not galvanically isolated (they have a common ground). The operating mode of the COM1-COM3 communication ports can be selected by means of the software the communication connection method is quoted for each of the options designated RS-232/RS-422/RS-485 (the COM4 port always operates in the RS-485 mode). Power supply Voltage-digital inputs Connector output +V CC GND S1 S2 S3 S4 S5 S6 RL 23 1,2,18,20,24 26,28,30,32 Communication ports COM1 COM2 COM3 COM4 Rx Tx Rx Tx Rx Tx RS-232 R- R+ T- T+ R- R+ T- T+ R- R+ T- T+ RS-422 B A B A B A B A RS Table 2. Distribution of MSP-MK1.0. module s outputs Figure 1. Distribution of the MSP-MK1.0. module s outputs Document version: IO/MSP-MK/EN/r1

9 Integrotech sp. z o.o. - 9 / 17 - IO/MSP-MK/EN/r1 Figure 2. MSP-MK1.0 name plate Figure 3 Front view of the MSP-MK1.0 module 2.4 MSP-MK1.1 (switch) Ethernet 4 Fast Ethernet 10/100 Mbps ports Connections 4 RJ45 sockets on the front wall Auto-negotiation YES Auto-MDI/X YES Weight < 250 g Power consumption 2.4 W Power supply Maximum power Power supply consumption 400 ma 200 ma 100 ma 80 ma 70 ma Description of outputs Table 3 presents the distribution of outputs of the MSP-MK1.1 switch. Power supply NC +V CC GND , 30 Table 3. Distribution of MSP-MK1.1 module s outputs. Wersja dokumentu: IO/MSP-MK/EN/r

10 IO/MSP-MK/EN/r1-10 / 17 - Integrotech sp. z o.o. 2.5 MSP-MK1.2 (opto) Ethernet 4 Fast Ethernet 10/100 Mbps ports Connections 3 RJ45 sockets on the front wall 1 (SC or ST type) fibre-optic connection on the front wall Auto-negotiation YES Auto-MDI/X YES Weight < 250 g Power consumption 4 W Power supply Maximum power Power supply consumption 670 ma 340 ma 170 ma 135 ma 120 ma Description of outputs Table 4 presents the distribution of outputs of the MSP-MK1.2 switch. Power supply NC +V CC GND , 30 Table 4. Distribution of MSP-MK1.2 module s outputs. 3 Preparing for operation 3.1 Installation Before installing the modem, you need to first insert the SIM card in the opening on the base of the unit. Using the six-element DIP-SWITCH, select the operation mode for the voltage-digital inputs. In the ON, position, the appropriate input operates in the digital input mode, and in the OFF position operates as a 0-30 V voltage input. MSP-MK modules are to be mounted on a 35 mm DIN bus and connected to each other before connecting the mains power supply. Table 1. describes acceptable connection alternatives. The mutual orientation of the devices (order of mounting on the DIN bus) does not matter. Note: Where two devices are connected as one unit, the power supply should be connected only to the MSP-MK1.0 or MSP-MK1.0i module. 3.2 Start-up procedure The following procedure must be followed each time the device is powered up or reset Servicing mode Directly after powering up or resetting the device, it remains in the servicing mode for 15 seconds. During this time - if necessary one may connect the Configurator software to it via (exclusively) the COM4 port. It should be remembered that COM4 is an RS-485 port. The connection parameters in servicing mode are shown in Table 5 (there is no need to enter these as the factory installed software is supplied with these settings). During this time, one cannot communicate with the unit by any other communication channel Document version: IO/MSP-MK/EN/r1

11 Integrotech sp. z o.o / 17 - IO/MSP-MK/EN/r1 Parameter Value In the servicing mode Baud rate Number of data bits 8 Number of stop bits 1 Parity control none Table 5. COM4 port s settings in the servicing mode Readiness to communicate in the servicing mode is signalled by a blinking S1-S6, SYS and LAN diode with a frequency of about 1 Hz. After making the connection and for instance reading the configuration, the frequency of the blinking LED diodes is increased to 10 Hz. The device remains in this mode until: the user resets the device by pressing the appropriate button in the Configurator software, or communication on COM4 port is lost for 20 minutes 20 minutes after the last configuration read or write command, the device resets itself. This means that in servicing mode, each configuration read or write command sets back the device s automatic reset by 20 minutes. For the new settings to apply, one must reset the device using the Configurator software (see Chapter 4) or by cutting off the power supply. When not in servicing mode, i.e. under the device s normal operating conditions, configuration of the device is only possible when connecting via LAN or GPRS. Only in the servicing mode with the MSP- MK1.0 unit can one communicate via a serial port - and only via COM Initialising communication After leaving the servicing mode, the device performs diagnostics of the LAN and GPRS connection, signalling any problems found acoustically. Each tone is repeated three times, enabling it to be clearly identified. In the event of communication problems, the whole procedure is repeated three times, which is why entering a wrong PIN will block the SIM card following the start-up procedure (there will be three successive attempts to unlock the SIM card using the wrong PIN). In such cases one must unlock the SIM card, for example by using a compatible mobile phone Initialising LAN In this step of the start-up procedure the device checks whether any of the auxiliary modules (MSP- MK1.1 switch or MSP-MK1.2 opto) have been connected to the internal bus. If an auxiliary module is detected, this is followed by disconnection of the LAN port (RJ-45) on the front of the MSP-MK1.0 unit (connection to the switch is effected using a Fast Ethernet link, set up in the internal bus). If nothing is connected to the LAN port, an appropriate audible signal is generated (see Table 6) Initialising GPRS The device then connects to the GSM network and any errors are signalled by audible notifications, as shown in Table 6 on page 12 (below). If this fails, the procedure is repeated three times, which is why entering the wrong PIN causes three attempts to open the SIM card with the wrong code, which will lead to it being blocked. The SIM card can be unlocked, for example by using a compatible mobile phone and entering PUK. The procedure for unlocking the SIM card is beyond the scope of this document. Wersja dokumentu: IO/MSP-MK/EN/r

12 IO/MSP-MK/EN/r1-12 / 17 - Integrotech sp. z o.o. 3.3 Acoustic diagnostics during the start-up procedure Table 6 lists all audible notifications that may occur, along with the basic troubleshooting procedure. One should read this list before attempting to connect the unit. Problem Number of acoustic signals Lack of communication on both communication channels No communication for a specified period - the device will reset itself Problems with the LAN connection Ethernet cable disconnected 6 14 Problems with the GPRS modem The modem does not 4 respond Remedy This problem occurs whenever during the time specified by the user (a maximum 255 minutes) there is no communication on either channel (LAN and GPRS). The solution is one of the following: increase the time allowed for lack of communication (up to 255 minutes) force periodic communication via LAN or GPRS for a period less than the specified time without communication if the device is to be only occasionally queried this can safely be ignored The solution is one of the following: connect network cable to the LAN port Connect the MSP-MK1.1 or MSP-MK1.2 module ignore if the LAN port is not going to be used Contact your service provider. This may also mean Invalid PIN (follow procedure below) Invalid PIN 8 Entering an incorrect PIN locks the SIM card! Disconnect the power supply, remove the SIM card and unlock it using PUK in another device (e.g. mobile phone). Then set a PIN and enter it in the device using the Configurator software. 1. Check the antenna connection. GPRS connection 2. Check GPRS network coverage at installation site. 10 problem 3. Use an antenna with a higher gain (e.g. external or directional antenna) 1. Insert the SIM card. No SIM card Clean the contacts of the SIM card. 3. Change the SIM card. No PPP connection Wait a few seconds and try again Problem negocjacji PPP If the problem persists, contact your service provider Table 6. Acoustic diagnostics for the MSP-MK1.0 device It should be remembered that each of the signals is repeated three times in order to avoid confusion Document version: IO/MSP-MK/EN/r1

13 Integrotech sp. z o.o / 17 - IO/MSP-MK/EN/r1 4 Description of the Configurator software The MSP-MK1.0 Configurator software is used to set the following aspects of the device s operation: 1. maximum time without communication 2. GPRS network parameters (APN, user name log in, password, PIN) 3. LAN network parameters (IPv4 address, subnet mask, gateway, and device s MAC address) 4. operating modes of COM1-COM3 ports (RS-232/422/485) 5. the communication parameters of the COM1-COM4 ports (speed, parity, number of data bits and stop bits) 6. TCP ports on which LAN and GPRS interfaces are listening and where routing to communication channels takes place (COM1-COM4). Figure 4 presents the appearance of the Configurator software window: Figure 4. Main window of the Configurator application 4.1 Connection with the device To connect to the device in order to configure it, select the communication medium, and then click on "Connect". During normal operation, the device may only be accessed via the LAN or WAN (GPRS) port. In the servicing mode the device may only be accessed via the COM4 (RS-485) communications port. Wersja dokumentu: IO/MSP-MK/EN/r

14 IO/MSP-MK/EN/r1-14 / 17 - Integrotech sp. z o.o. To select a communication medium, close the connection button (if this is open) and then click on the button to open the window for selecting a communication medium. In this window, you can choose a connection via a serial port - if this option is selected, from the list next to it one must select to which port of the PC the device s COM4 is connected - this option only works in the servicing mode. Another option, intended for normal operation is TCP connection to port In the IP Address field, enter one of the two IP addresses that have been assigned to the device s interfaces - or the address set as the LAN address, or the address assigned by the GPRS network, in accordance with the agreement with the network operator. Figure 5 presents the appearance of the window for selection of the communication medium. Figure 5. Communication medium selection window It should be remembered that any configuration action should begin by reading the device s settings by means of the Read button on the toolbar. After making changes, these should be entered in the device using the Save button. For the changes to take effect, reset the unit (using the Reset button or by cutting off the power supply. 4.2 Maximum time of communication failure In the WatchDog section, one should specify the time (in minutes) after which the device will be reset, if there should be no communication on any of the (GPRS or LAN) ports. In the text field one can enter any integer value from 1-255, which corresponds to the time from 1 minute to 4 hours and 15 minutes. WatchDog enables one to re-establish connection to the device, which for any reason ceases to communicate. After counting off the specified number of minutes, in the absence of any communication, the device will emit six beeps three times (see Table 6. ) and reset itself. Figure 6. Setting the time of the automatic reset Document version: IO/MSP-MK/EN/r1

15 Integrotech sp. z o.o / 17 - IO/MSP-MK/EN/r1 This time is based on normal operating conditions; it should be remembered that in the servicing mode, the device will always reset itself after 20 minutes of no communication. 4.3 Modem settings In this section (see Figure 7), one should quote the GPRS parameters for the GSM network: APN (Access Point Name), user name log in and password for access to the network. These values are specified for a given GSM network and provided by your service provider (network operator). In the last field in this section, enter the SIM card s PIN. Note: entering a wrong PIN and turning on the power will block the SIM card! After connecting to the Internet, the device will be assigned an IP address by the network operator. To ensure uninterrupted communication, this address should be constant, i.e., it should not change after resetting of the device. Ensured stability of the IP address is a provision of the contract with the GSM network operator. Figure 7. GPRS settings Figure 8. LAN settings 4.4 LAN network settings In this section (see Figure 8) one must quote the IPv4 protocol parameters for the LAN interface the IP address, subnet mask, and default gateway address. Optionally, one may also change the address of the second layer (MAC). 4.5 Routing TCP ports to COM communication ports In the sections marked GPRS TCP-X port and TCP LAN-X port, where X is the letter A, B, C or D, assignment of a specific TCP port of a given interface to a specified communications port is configured. Any number of TCP ports from each network can be assigned to any communication port (COM1-COM4). Figure 9. GPRS interface s TCP port settings Figure 10. LAN interface s TCP port settings This means that devices connected to a particular communications port may be simultaneously accessible for up to eight clients - controllers, systems, operators etc. In extreme cases a single device may be queried at the same time by eight independent clients (for versions of the MSP-MK1.0 device, subject to the reservations discussed in Chapter 6). Wersja dokumentu: IO/MSP-MK/EN/r

16 IO/MSP-MK/EN/r1-16 / 17 - Integrotech sp. z o.o. 4.6 Settings for COM ports In the group designated COM1-COM4, one may set operating parameters for a given communication port, such as: bitrate (4800, 9600, 19200, 38400, and bits per second) number of data bits (5, 6, 7 or 8), parity control (even, mark, none, odd, or space), number of stop bits (1, 1.5 or 2). In addition, for ports COM1-COM3 one may select the port s operating mode (RS-232/422/485). The COM4 port always operates in the RS-485 mode. 5 Routing between communication ports (MSP-MK1.0i only) In the MSP-MK1.0i version of the device COM3 cannot be used by the ports server and the TCP ports LAN-C and GPRS-C are also not available. All traffic from COM3 is routed to COM4. Routing between ports COM3 and COM4 is permanent and cannot be in any way modified by the user. In addition to the above, the operation of COM4 is the same as in the basic version (MSP-MK1.0) it is available as a routing destination for both LAN and GPRS TCP ports, and also its functions in the servicing mode are the same. Given the above, it should be noted that up to seven clients may use the MSP-MK1.0i device simultaneously (three clients on LAN ports, three on GPRS ports and one on the COM3 port). 6 Optimising multiple access Thanks to the use of intelligent query processing algorithms, the MSP-MK1.0 and MSP-MK1.0i units provide a good approximation of true simultaneous operation. It should be noted however, that communication of many clients with a target device using a single serial link is not and cannot be implemented at the same time. This is due to the nature of these connections, dedicated to the implementation of arrangements in a point-to-point topology (such as RS-232) or a bus topology with a single master unit and many slave units such as RS-485. Emulating simultaneity is possible thanks to among other things buffering and queuing of queries and responses. Both buffering and queuing add a slight (though non-zero) time overhead to all operations. Which is why in designing a solution where many clients connect via a single serial communication channel with one device, one must expect delays in communication that will occur in connection with the need to wait for the processing of queries originating from other clients to be completed. When planning a system of the following type: many clients MSP-MK1.0 target device, one should seek to minimize the waiting time for a response by eliminating all potential sources of time overheads in the communication process so that these do not exceed the response timeout permitted by the master unit. The following sections discuss recommended strategies for this purpose Document version: IO/MSP-MK/EN/r1

17 Integrotech sp. z o.o / 17 - IO/MSP-MK/EN/r1 6.1 Multiplying connections to the target device First of all, one must make sure to use the maximum number of available communication channels between the target device and the MSP-MK1.0. The use of many channels shortens the queries queue, and consequently, the waiting time for a response over a given channel. It also allows for prioritising of clients - for example, the reserving of a dedicated channel for a critical client. An additional advantage gained from multiplication of communication channels is of course increased traffic assurance and the minimising of the effects of potential breakdowns. Whenever possible, one should use the maximum available number of ports. 6.2 Maximising the communication speed Another important factor is selection of the maximum possible communication speed of the target device with the MSP-MK1.0 unit. As a result, the time for transmission of queries and responses will be reduced to a minimum. The speed of communication should each time be adapted to the length of the line connecting the target device to the MSP-MK1.0 unit and should take into consideration the occurrence of other factors that may adversely affect the quality of the connection. The manufacturer recommends confirming proper communication by simulating work under field conditions before handing over the installation. 6.3 Adjusting permissible response timeouts Having taken care of the above, one may also increase the waiting times for responses by master units. Waiting times should be chosen experimentally, confirming correct selection by means of appropriately comprehensive tests. Alphabetical Index COM1-COM3 operating mode selection Modular Measurement System review of devices... 5 MSP-MK1.0 functions... 6 extended... 6 interfaces number of data bits number of stop bits parity control RS RS RS Wersja dokumentu: IO/MSP-MK/EN/r

Industrial Serial Device Server

Industrial Serial Device Server 1. Quick Start Guide This quick start guide describes how to install and use the Industrial Serial Device Server. Capable of operating at temperature extremes of -10 C to +60 C, this is the Serial Device

More information

Motortronics VirtualSCADA VS2-MT Communication Gateway VS2-MT User Manual Revision

Motortronics VirtualSCADA VS2-MT Communication Gateway VS2-MT User Manual Revision Motortronics VirtualSCADA VS2-MT Communication Gateway VS2-MT User Manual Revision 1.03.00 Motortronics / Phasetronics 1600 Sunshine Drive Clearwater, Florida 33765 Tel: 727-573-1819 Fax: 727-573-1803

More information

INDEX. Document Name : User Manual for SC10EJ Serial to Ethernet Converter

INDEX. Document Name : User Manual for SC10EJ Serial to Ethernet Converter Document Name : User Manual for SC10EJ Serial to Ethernet Converter Page 1 of 10 INDEX 1. Technical Specifications 1 2. Modes of Operation 1 3. Configuring the SC10 EJ : Through Serial Port 2 a. Configuring

More information

EGW1-IA3-MB User s Manual

EGW1-IA3-MB User s Manual www.exemys.com Rev. 0 1 Products are in constant evolution to satisfy our customer needs. For that reason, the specifications and capabilities are subject to change without prior notice. Updated information

More information

User Manual A08. User Manual

User Manual A08. User Manual A08 TABLE OF CONTENTS TABLE OF CONTENTS... 1 1. INTRODUCTION... 2 1.1. Key Features... 3 1.2. OS Requirement... 4 1.3. Specification... 4 1.4. Packing List... 4 2. OVERVIEW... 5 2.1. LED Definition...

More information

ECAN-240. (Modbus TCP to 2-port CAN Bus Gateway User manual) ECAN-240 Modbus TCP to 2-port CAN Bus Gateway User Manual, Version 1.0.

ECAN-240. (Modbus TCP to 2-port CAN Bus Gateway User manual) ECAN-240 Modbus TCP to 2-port CAN Bus Gateway User Manual, Version 1.0. ECAN-240 (Modbus TCP to 2-port CAN Bus Gateway User manual) ECAN-240 Modbus TCP to 2-port CAN Bus Gateway User Manual, Version 1.0.0 Page: 1 Table of Contents Table of Contents -----------------------------------------------------------------------------2

More information

GPRS/SerialGateway. GPRS/Serial Gateway. User Manual

GPRS/SerialGateway. GPRS/Serial Gateway. User Manual GPRS/Serial Gateway User Manual 1 TABLE OF CONTENTS SECTION 1 GENERAL INFORMATION...5 1.1 General Information... 5 1.2 Proper Use and Safety Conditions... 6 1.3 Connections and Micro SIM Card Placement...

More information

SMG-1100/6100 User s Manual

SMG-1100/6100 User s Manual User s Manual First Edition, January 2011 www.moxa.com/product 2011 Moxa Inc. All rights reserved. Reproduction without permission is prohibited. User s Manual The software described in this manual is

More information

GEM-10 GPRS/Modbus Gateway User Manual. Rev /2012

GEM-10 GPRS/Modbus Gateway User Manual. Rev /2012 GEM-10 GPRS/Modbus Gateway User Manual Rev 1.04 05/2012 1.Introduction 1.1 General Features ENTES GEM-10 GPRS/Modbus Gateway allows you to connect to your devices which communicate using Modbus protocol

More information

ETOR-4. Ethernet/Serial Gateway USER MANUAL

ETOR-4. Ethernet/Serial Gateway USER MANUAL ETOR-4 Ethernet/Serial Gateway USER MANUAL 1 TABLE OF CONTENTS SECTION 1 GENERAL INFORMATION...6 SECTION 2 INSTALLATION...9 2.1 Definitions on ETOR... 9 2.2 Configuring ETOR...10 2.3 Required Installations

More information

TRP-C37 User s Manual

TRP-C37 User s Manual TRP-C37 User s Manual Ethernet to RS232/422/485 Converter Printed Oct. 2010 Rev 1.0 Trycom Technology Co., Ltd 1F, No.2-11, Sihu street, Yingge Township, Taipei, Taiwan ROC Tel: 886-2-86781191, Fax: 886-2-86781172

More information

TRP-C37. Ethernet to RS232/422/485 Converter. User s Manual. Printed Apr.2014 Rev 1.3

TRP-C37. Ethernet to RS232/422/485 Converter. User s Manual. Printed Apr.2014 Rev 1.3 TRP-C37 Ethernet to RS232/422/485 Converter User s Manual Printed Apr.2014 Rev 1.3 Trycom Technology Co.,Ltd No.35, Zhongxing Rd., Guishan Township, Taoyuan County 333, Taiwan. Tel : 886-3-350-3351 Fax:

More information

ETHM-2. Ethernet Module. SATEL sp. z o.o. ul. Schuberta Gdańsk POLAND tel

ETHM-2. Ethernet Module. SATEL sp. z o.o. ul. Schuberta Gdańsk POLAND tel Ethernet Module ETHM-2 Firmware version 1.0 ethm2_en 09/08 SATEL sp. z o.o. ul. Schuberta 79 80-172 Gdańsk POLAND tel. + 48 58 320 94 00 info@satel.pl www.satel.pl SATEL's goal is to continually improve

More information

GSM-X. Communication module. Quick installation guide. Full manual is available on Firmware version 1.02 gsm-x_sii_en 08/18

GSM-X. Communication module. Quick installation guide. Full manual is available on   Firmware version 1.02 gsm-x_sii_en 08/18 GSM-X Communication module Quick installation guide Full manual is available on www.satel.eu Firmware version 1.02 gsm-x_sii_en 08/18 SATEL sp. z o.o. ul. Budowlanych 66 80-298 Gdańsk Poland tel. +48 58

More information

ETOR-4 Ethernet/Serial Gateway ETOR-4. Ethernet/Serial Gateway USER MANUAL

ETOR-4 Ethernet/Serial Gateway ETOR-4. Ethernet/Serial Gateway USER MANUAL ETOR-4 Ethernet/Serial Gateway USER MANUAL 1 TABLE OF CONTENTS SECTION 1 GENERAL INFORMATION...6 SECTION 2 INSTALLATION...9 2.1 Definitions on ETOR... 9 2.2 Configuring ETOR...10 2.3 Required Installations

More information

Document Name: User Manual for SC10MK, Modbus RTU to Modbus TCP Converter

Document Name: User Manual for SC10MK, Modbus RTU to Modbus TCP Converter Document Name: User Manual for SC10MK, Modbus RTU to Modbus TCP Converter Login for the first time, please use http://192.168.1.100 To key in user name and password is for identifying authorization. Default

More information

Embedded Modbus TCP Module GS11-MT. User Manual REV 1.1. SST Automation.

Embedded Modbus TCP Module GS11-MT. User Manual REV 1.1. SST Automation. Embedded Modbus TCP Module GS11-MT User Manual REV 1.1 SST Automation E-mail: SUPPORT@SSTCOMM.COM WWW.SSTCOMM.COM Catalog 1 About the Embedded Module... 4 1.1 General...4 1.2 Features... 4 1.3 Specifications...4

More information

HARDWARE MANUAL MMS100. M-BUS TO MODBUS GATEWAY Series 07 / 2017 MIKRODEV_HM_MMS100_EN

HARDWARE MANUAL MMS100. M-BUS TO MODBUS GATEWAY Series 07 / 2017 MIKRODEV_HM_MMS100_EN MMS100 HARDWARE MANUAL MMS100 M-BUS TO MODBUS GATEWAY Series 07 / 2017 MIKRODEV_HM_MMS100_EN CONTENTS 1 MMS100 GENERAL INFORMATION... 7 1.1 Physical Interfaces... 7 1.2 General Device Spesifications...

More information

USER S MANUAL. PH485Ex1. #1 RS-485 Serial Port to Ethernet, Terminal Server/Client. Doc No: PH485Ex1-UM-001 IPEX. (IP Electronix)

USER S MANUAL. PH485Ex1. #1 RS-485 Serial Port to Ethernet, Terminal Server/Client. Doc No: PH485Ex1-UM-001 IPEX. (IP Electronix) USER S MANUAL PH485Ex1 Doc No: PH485Ex1-UM-001 #1 RS-485 Serial Port to Ethernet, Terminal Server/Client IPEX (IP Electronix) Contents 1. INTRODUCTION... 3 2. SPECIFICATIONS... 3 3. PACKAGE CHECKLIST...

More information

CONVERTER FOR MONITORING STATION SMET-256

CONVERTER FOR MONITORING STATION SMET-256 CONVERTER FOR MONITORING STATION SMET-256 USER MANUAL Program version v1.07 smet256_en 04/11 SATEL's goal is to continually improve the quality of its products, which may lead to alterations in their technical

More information

GW-7238D J1939 to Modbus TCP Server / RTU Slave Gateway

GW-7238D J1939 to Modbus TCP Server / RTU Slave Gateway GW-7238D J1939 to Modbus TCP Server / RTU Slave Gateway User s Manual www.icpdas.com 1 Warranty All products manufactured by ICP DAS are under warranty regarding defective materials for a period of one

More information

Serial to Ethernet Converter

Serial to Ethernet Converter Serial to Ethernet Converter User s Manual Version 1.1 2004 Infosystem Technology Corporation Disclaimers The information in this manual has been carefully checked and is believed to be accurate. Infosystem

More information

RM6000 GPRS Modem / Router

RM6000 GPRS Modem / Router User Manual Version 6.30 AMG Systems Ltd March 2013 3 The Omega Centre Stratton Business Park Biggleswade Bedfordshire, UK SG18 8QB Tel: 44 (0) 1767 600777 sales@amgsystems.com 1. Introduction 2. RM6000

More information

OnCell G3100 Series Quick Installation Guide

OnCell G3100 Series Quick Installation Guide OnCell G3100 Series Quick Installation Guide Edition 4.1, August 2016 Technical Support Contact Information www.moxa.com/support Moxa Americas: Toll-free: 1-888-669-2872 Tel: 1-714-528-6777 Fax: 1-714-528-6778

More information

DKG-210 UNIVERSAL INTERNET GATEWAY UNIT

DKG-210 UNIVERSAL INTERNET GATEWAY UNIT DKG-210 UNIVERSAL INTERNET GATEWAY UNIT AC & DC SUPPLY VERSIONS DESCRIPTION The DKG-210 is designed for internet monitoring and control of industrial devices using different protocols through the RAINBOW

More information

isma-b-mg-ip User Manual Global Control 5 Sp. z o.o. Poland, Warsaw

isma-b-mg-ip User Manual Global Control 5 Sp. z o.o. Poland, Warsaw isma-b-mg-ip User Manual Global Control 5 Sp. z o.o. Poland, Warsaw www.gc5.pl Table of content 1 Introduction... 4 1.1 Revision history... 5 1.2 Safety rules... 5 1.3 Technical specifications... 6 1.4

More information

MGate 5111 Quick Installation Guide

MGate 5111 Quick Installation Guide MGate 5111 Quick Installation Guide Edition 1.0, December 2017 Technical Support Contact Information www.moxa.com/support Moxa Americas: Toll-free: 1-888-669-2872 Tel: 1-714-528-6777 Fax: 1-714-528-6778

More information

NCOM SERIAL DEVICE SERVER 4XX SERIES USER S MANUAL

NCOM SERIAL DEVICE SERVER 4XX SERIES USER S MANUAL NCOM SERIAL DEVICE SERVER 4XX SERIES USER S MANUAL 2017-07-07 Edition Titan Electronics Inc. Web: www.titan.tw Contents 1. INTRODUCTION... 4 1.1 Key Features... 5 1.2 Specifications... 6 2. PANEL LAYOUT

More information

BAS Router BACnet Multi-Network Router

BAS Router BACnet Multi-Network Router BAS Router BACnet Multi-Network Router The BAS Router provides stand-alone routing between BACnet networks such as BACnet/IP, BACnet Ethernet, and BACnet MS/TP thereby allowing the system integrator to

More information

USER S MANUAL. PH232Ex1. #1 RS-232 Serial Port to Ethernet, Terminal Server/Client. Doc No: PH232Ex1-UM-001 IPEX. (IP Electronix)

USER S MANUAL. PH232Ex1. #1 RS-232 Serial Port to Ethernet, Terminal Server/Client. Doc No: PH232Ex1-UM-001 IPEX. (IP Electronix) USER S MANUAL PH232Ex1 Doc No: PH232Ex1-UM-001 #1 RS-232 Serial Port to Ethernet, Terminal Server/Client IPEX (IP Electronix) Contents 1. INTRODUCTION... 3 2. SPECIFICATIONS... 3 3. PACKAGE CHECKLIST...

More information

MGate TM EIP3000 DF1 to EtherNet/IP Gateway User s Manual

MGate TM EIP3000 DF1 to EtherNet/IP Gateway User s Manual MGate TM EIP3000 DF1 to EtherNet/IP Gateway User s Manual First Edition, June 2009 www.moxa.com/product 2009 Moxa Inc. All rights reserved. Reproduction without permission is prohibited. MGate EIP3000

More information

The accessories described in this manual are of the highest quality, carefully designed and built in order to ensure excellent performance.

The accessories described in this manual are of the highest quality, carefully designed and built in order to ensure excellent performance. INTRODUCTION Thank you for choosing our product. The accessories described in this manual are of the highest quality, carefully designed and built in order to ensure excellent performance. This manual

More information

ROCKETLINX ES8508 ES8508 ES8508F ES8508-XT ES8508F-XT QUICK INSTALLATION GUIDE

ROCKETLINX ES8508 ES8508 ES8508F ES8508-XT ES8508F-XT QUICK INSTALLATION GUIDE ROCKETLINX ES8508 ES8508 ES8508F ES8508-XT ES8508F-XT QUICK INSTALLATION GUIDE 2000577 Rev B Release Date - September, 2013 INTRODUCTION The RocketLinx ES8508 series features advanced Layer 2 management

More information

Quick Installation Guide

Quick Installation Guide Quick Installation Guide DL-200 Cellular Data logger V1.2_201610 TABLE OF CONTENTS CHAPTER 1 INTRODUCTION... 4 1.1 CONTENTS LIST... 5 1.2 HARDWARE INSTALLATION... 6 1.2.1 WARNING... 6 1.2.2 SYSTEM REQUIREMENTS...

More information

User Manual for VE GSM Modem

User Manual for VE GSM Modem User Manual for VE GSM Modem INTRODUCTION GSM/GPRS Smart Modem is a multi-functional, ready to use, rugged unit that can be embedded or plugged into any application. The Smart Modem can be controlled and

More information

ETM350C & ETM450C User Manual

ETM350C & ETM450C User Manual Industrial Ethernet Router ETM350C & ETM450C User Manual Features ETM350C // ETM450C: HSDPA/UMTS 850/900/2100MHz // 850/900/1900/2100MHz GSM/GPRS 900/1800MHz // 850/900/1800/1900MHz HSUPA 14.4Mbps DL,

More information

icex-cmtm General specs and Installation guide

icex-cmtm General specs and Installation guide icex-cmtm General specs and Installation guide 1. General view 2. Specifications 2.1. Common specs: Ethernet 1 x 10/100Base/T, RJ45 connector with traffic and link LED Serial Interface 1 x RS232/485 USB

More information

Industrial 1-port RS422/485 Modbus Gateway IMG-110T

Industrial 1-port RS422/485 Modbus Gateway IMG-110T Industrial 1-port RS422/485 Modbus Gateway IMG-110T Presentation Outlines Product Positioning Applications Product Overview Comparison Product Benefits Appendix Product Features 2 / 43 Product Positioning

More information

Installation and Configuration Quick Guide R2000. Industrial Dual SIM Cellular VPN Router (2 Eth + 2 SIM) Package Contents

Installation and Configuration Quick Guide R2000. Industrial Dual SIM Cellular VPN Router (2 Eth + 2 SIM) Package Contents Package Contents Before installing your R2000 Router, please verify the kit contents as following. 1 x Robustel R2000 Industrial Dual SIM Cellular VPN Router 1 x 3-pin 3.5 mm male terminal block for power

More information

MGate 5118 Quick Installation Guide

MGate 5118 Quick Installation Guide MGate 5118 Quick Installation Guide Edition 1.0, December 2016 Technical Support Contact Information www.moxa.com/support Moxa Americas: Toll-free: 1-888-669-2872 Tel: 1-714-528-6777 Fax: 1-714-528-6778

More information

XPress DR+W Quick Start Guide

XPress DR+W Quick Start Guide Industrial Device Server Quick Start Guide 2006 Copyright Lantronix is a trademark of Lantronix. All rights reserved. 900-446 Rev. A 10/06 XPRESS DR+W QUICK START CONTENTS What s In the Box..........................................................2

More information

EtherSeries. EtherSeries CR-2. CR-2-Opto. User s Guide. Revised October 7, 2013 Firmware Version 1.X

EtherSeries. EtherSeries CR-2. CR-2-Opto. User s Guide. Revised October 7, 2013 Firmware Version 1.X EtherSeries EtherSeries CR-2 & CR-2-Opto User s Guide Revised October 7, 2013 Firmware Version 1.X TABLE OF CONTENTS SECTION 1 - DESCRIPTION... 2 SECTION 2 - SPECIFICATIONS... 4 SECTION 3 - INSTALLATION...

More information

Installation and Configuration Quick Guide. R3000 Lite. Industrial Dual SIM Cellular VPN Router (1 Eth + 1 RS RS USB Host)

Installation and Configuration Quick Guide. R3000 Lite. Industrial Dual SIM Cellular VPN Router (1 Eth + 1 RS RS USB Host) Package Contents Before installing your R3000 Lite Router, please verify the kit contents as following. 1 x Robustel R3000 Lite Industrial Dual SIM Cellular VPN Router 1 x 3-pin pluggable terminal block

More information

MGate MB3000 Modbus Gateway User Manual

MGate MB3000 Modbus Gateway User Manual MGate MB3000 Modbus Gateway User Manual Sixth Edition, July 2012 www.moxa.com/product 2012 Moxa Inc. All rights reserved. MGate MB3000 Modbus Gateway User s Manual The software described in this manual

More information

GPRS ADAPTER INSTALLATION AND USER MANUAL. for module version v2.24 and higher

GPRS ADAPTER INSTALLATION AND USER MANUAL. for module version v2.24 and higher GPRS ADAPTER INSTALLATION AND USER MANUAL for module version v2.24 and higher Table of contents 1 Main function of the Adapter...3 2 System operation...3 2.1 Transmission through GPRS...4 2.1.1 Router

More information

Hardware manual. 1. Overview 2. Technical characteristics 3. Connections. ( Portal (../portal/portal.html)

Hardware manual. 1. Overview 2. Technical characteristics 3. Connections. (  Portal (../portal/portal.html) 1 (http://nethix.com) Portal (../portal/portal.html) WE110 (../we110/we110.html) WE120 (../we120/we120.html) WE300 (../we300/we300.html) WE500 (we500.html) Quick start guide (we500_qsg.html) Hardware manual

More information

MB40 & MB45 MODBUS TCP/IP Gateway Handbook

MB40 & MB45 MODBUS TCP/IP Gateway Handbook MB40 & MB45 MODBUS TCP/IP Gateway Handbook Version 1.2 29 July 2014 Environdata Australia Pty Ltd 42-44 Percy Street Warwick Queensland 4370 Australia Phone: (07) 4661 4699 Fax: (07) 4661 2485 International

More information

KAUGJUHTIMISSÜSTEEMID TELECONTROL SYSTEMS MODEM TELEM-GSM/GPRS 3G. User manual

KAUGJUHTIMISSÜSTEEMID TELECONTROL SYSTEMS MODEM TELEM-GSM/GPRS 3G. User manual KAUGJUHTIMISSÜSTEEMID TELECONTROL SYSTEMS MODEM TELEM-GSM/GPRS 3G User manual Martem AS 2014 CONTENTS 1. Description...3 2. Features...3 3. Interfaces...3 4. Indication and switches...4 4.1 State LED indication...4

More information

SSE232-LE Serial Server- User s Manual

SSE232-LE Serial Server- User s Manual www.exemys.com Rev.6 1 Products are in constant evolution to satisfy our customer needs. For that reason, the specifications and capabilities are subject to change without prior notice. Updated information

More information

GPRS Pager 3 INSTALATION AND USER MANUAL

GPRS Pager 3 INSTALATION AND USER MANUAL GPRS Pager 3 INSTALATION AND USER MANUAL 1 Table of contents 1 Main functions of the GPRS Pager3...3 2 Operating mode, installation...3 2.1 Installation if no local network is available...3 2.2 Instalation

More information

Installation and Configuration Quick Guide. R3000 Quad. Industrial Cellular VPN Router with 4 Ethernet Ports (4 Eth + 1 RS-232/1 RS USB Host)

Installation and Configuration Quick Guide. R3000 Quad. Industrial Cellular VPN Router with 4 Ethernet Ports (4 Eth + 1 RS-232/1 RS USB Host) Package Contents Before installing your R3000 Quad Router, please verify the kit contents as following. 1 x Robustel GoRugged R3000 Quad Industrial Dual SIM Cellular VPN Router with 4 Ethernet Ports 1

More information

Document Name: User Manual for SC10EK4 Serial to Ethernet Converter with 4 TCP Sockets. Index

Document Name: User Manual for SC10EK4 Serial to Ethernet Converter with 4 TCP Sockets. Index Document Name: User Manual for SC10EK4 Serial to Ethernet Converter with 4 TCP Sockets. Index Technical Specifications 1 Installation Procedure 1 LED Indications 2 Configuration Procedure Configuration

More information

Modbus TCP/RTU Gateway

Modbus TCP/RTU Gateway Modbus TCP/RTU Gateway Hardware Installation Guide for models IE-GW-MB-2TX-1RS232/485 IE-GWT-MB-2TX-1RS232/485 Second Edition, June 2014 1516600000/01/06.14 Important note: The detailed user manual, additional

More information

EIDX_M Series INSTALLATION GUIDE INTRODUCTION. A Line of Managed Ethernet Switching Hubs

EIDX_M Series INSTALLATION GUIDE INTRODUCTION. A Line of Managed Ethernet Switching Hubs EIDX_M Series A Line of Managed Ethernet Switching Hubs INTRODUCTION INSTALLATION GUIDE The EIDX_M Series of managed Industrial Ethernet switches provides the user with a sophisticated instrument with

More information

Installation Guide. Network Encoder Model TVI C300

Installation Guide. Network Encoder Model TVI C300 Installation Guide Network Encoder Model TVI C300 Installation Guide Thank you for purchasing your new TVI C300 Encoder. The package you have received contains everything you need to set up an infrastructure

More information

TRP-C37. Ethernet to RS232/422/485 Converter. User s Manual. Printed September Rev 1.6

TRP-C37. Ethernet to RS232/422/485 Converter. User s Manual. Printed September Rev 1.6 TRP-C37 Ethernet to RS232/422/485 Converter User s Manual Printed September 1 2015 Rev 1.6 Trycom Technology Co.,Ltd No.35, Zhongxing Rd., Guishan Township, Taoyuan County 333, Taiwan. Tel : 886-3-350-3351

More information

IPM-01 / IPM-01H MODBUS TCP/RTU Bridge User Guide

IPM-01 / IPM-01H MODBUS TCP/RTU Bridge User Guide VxI Power Ltd. IPM-01 / IPM-01H MODBUS TCP/RTU Bridge User Guide 01/12/2015 Document Number: 14970-020A Issue Number: 2 Contents 1.0 Device Overview... 2 2.0 Getting Started... 3 2.1 Connecting the Device...

More information

SK CU4-PNT-C Part number:

SK CU4-PNT-C Part number: SK CU4-PNT-C Part number: 275 271 515 PROFINET IO Internal Bus Interface The bus interface may only be installed and commissioned by qualified electricians. An electrician is a person who, because of their

More information

S5 Communications. Rev. 1

S5 Communications. Rev. 1 S5 Communications Rev. 1 Page 1 of 15 S5 Communications For a complete understanding of the S5 Battery Validation System (BVS) communication options, it is necessary to understand the measurements performed

More information

MGate MB3000 Modbus Gateway User s Manual

MGate MB3000 Modbus Gateway User s Manual User s Manual Seventh Edition, May 2013 www.moxa.com/product 2013 Moxa Inc. All rights reserved. User s Manual The software described in this manual is furnished under a license agreement and may be used

More information

NCOM SERIAL DEVICE SERVER 1XX SERIES USER S MANUAL

NCOM SERIAL DEVICE SERVER 1XX SERIES USER S MANUAL NCOM SERIAL DEVICE SERVER 1XX SERIES USER S MANUAL 2017-07-07 Edition Titan Electronics Inc. Web: www.titan.tw Contents 1. INTRODUCTION... 4 1.1 Key Features... 5 1.2 Specifications... 6 2. PANEL LAYOUT

More information

Matrix-710. Linux-Ready Cortex-A5 Industry IoT Gateway. Hardware Guide. Version: Nov.

Matrix-710. Linux-Ready Cortex-A5 Industry IoT Gateway. Hardware Guide. Version: Nov. Matrix-710 Linux-Ready Cortex-A5 Industry IoT Gateway Hardware Guide Version: 1.01 2017 Nov. Copyright Artila Electronics Co., Ltd. All Rights Reserved Trademarks The Artila logo is a registered trademark

More information

NetBiter Serial Server User Manual

NetBiter Serial Server User Manual User Manual IntelliCom Innovation AB Linjegatan 3D SE-302 50 Halmstad SWEDEN Phone +46 35 18 21 70 Fax +46 35 17 29 09 email info@intellicom.se web www.intellicom.se Revision List Revision Date Author

More information

HART / EtherNet/IP Gateway GT200-HT-EI User Manual V 1.0 REV A SST Automation

HART / EtherNet/IP Gateway GT200-HT-EI User Manual V 1.0 REV A SST Automation HART / EtherNet/IP Gateway GT200-HT-EI V 1.0 REV A SST Automation E-mail: SUPPORT@SSTCOMM.COM WWW.SSTCOMM.COM Catalog 1 Product Overview... 4 1.1 Product Function...4 1.2 Product Features... 4 1.3 Technical

More information

Wireless Transducer MOTOR PROTECTION ELECTRONICS, INC. INSTRUCTION MANUAL. (407) Phone: Website:

Wireless Transducer MOTOR PROTECTION ELECTRONICS, INC. INSTRUCTION MANUAL. (407) Phone: Website: Wireless Transducer INSTRUCTION MANUAL MOTOR PROTECTION ELECTRONICS, INC. 2464 Vulcan Road Apopka, Florida 32703 Phone: Website: (407) 299-3825 www.mpelectronics.com Operating Program Revision: 2 Revision

More information

MP211 HARDWARE MANUAL

MP211 HARDWARE MANUAL MP211 HARDWARE MANUAL MP211 PLC Series 10 / 2017 MIKRODEV_HM_MP211_EN V1.1 CONTENTS 1 MP211 GENERAL INFORMATION... 6 1.1 Physical Interfaces... 6 1.2 General Device Specifications... 7 2 INSTALLATION INFORMATION...

More information

Installation and Configuration Quick Guide R3000. Industrial Dual SIM Cellular VPN Router 2 Eth + 1 RS RS USB Host.

Installation and Configuration Quick Guide R3000. Industrial Dual SIM Cellular VPN Router 2 Eth + 1 RS RS USB Host. Package Contents Installation and Configuration Quick Guide Before installing your R3000 Router, verify the kit contents as following. 1 x Robustel R3000 Industrial Dual SIM Cellular VPN Router (GPS/WiFi

More information

IntesisBox Modbus Server KILSEN KSA-7xx. User s Manual 08/2013 r1.2 eng

IntesisBox Modbus Server KILSEN KSA-7xx. User s Manual 08/2013 r1.2 eng IntesisBox Modbus Server KILSEN KSA-7xx User s Manual 08/2013 r1.2 eng Intesis Software S.L. 2013 All rights reserved. Information in this document is subject to change without notice. The software described

More information

Modular E1 or Fractional E1 Access Unit. Dial-out for alarm report The E1 main link can be supplied with the following options:

Modular E1 or Fractional E1 Access Unit. Dial-out for alarm report The E1 main link can be supplied with the following options: FEATURES E1 or Fractional E1 access unit Supports one data port with selectable sync data rates: n x 56, n x 64 kbps Optional sub-e1 drop & insert port for PABX connectivity Single slot supports MEGAPLEX

More information

R3-NE1 ETHERNET INTERFACE MODULE MODEL. Remote I/O R3 Series. (Modbus/TCP)

R3-NE1 ETHERNET INTERFACE MODULE MODEL. Remote I/O R3 Series. (Modbus/TCP) Remote I/O R Series ETHERNET INTERFACE MODULE (Modbus/TCP) MODEL R-NE MODEL & SUFFIX CODE SELECTION R NE MODEL POWER INPUT K : V AC L : V AC R : V DC N : No power supply * *. Choose N (no power supply)

More information

SATEL I-LINK 100 MB I/O-converter User Guide, Version 1.1

SATEL I-LINK 100 MB I/O-converter User Guide, Version 1.1 TABLE OF CONTENTS TABLE OF CONTENTS... 1 IMPORTANT NOTICE... 2 PRODUCT CONFORMITY... 3 WARRANTY AND SAFETY INSTRUCTIONS... 4 1 GENERAL... 5 1.1 SATEL I-LINK 100 MODBUS I/O- CONVERTER... 5 2 SPECIFICATIONS...

More information

iopro Mirrored IO System

iopro Mirrored IO System Ph: (877) 343-8467 Fax: (800) 303-5381 Email: info@ioselect.com iopro Mirrored IO System Quick Start Guide (Ver. 6) www.ioselect.com Page 1 Introduction This document will cover how to use the iopro family

More information

BACnet/IP to BACnet MS/TP Router

BACnet/IP to BACnet MS/TP Router BACnet/IP to BACnet MS/TP Router Features Compact Size Routes between BACnet /IP and BACnet MS/TP networks 10/100Mbps Ethernet Auto-MDIX port Optically isolated MS/TP communications port MS/TP baud rates:

More information

RS485 IO Slim Module MOD-ETH

RS485 IO Slim Module MOD-ETH Expansion Module gateway Modbus TCP Version 1.0 01.12.2015 Manufactured for Thank you for choosing our product. This manual will help you with proper support and proper operation of the device. The information

More information

Any device, including routers and hosts, is running an implementation of IP address Host

Any device, including routers and hosts, is running an implementation of IP address Host INSTRUCTION MANUAL IM471-U v0.1 EMI-10L Introduction EMI-10L converter lets you convert a serial RS485 communications port on a bus Ethernet with TCP / IP. The concepts and terms commonly used in the TCP

More information

Ethernet Interface Module

Ethernet Interface Module Interface Manual 1 Ethernet Interface Module SignalFire Number: ENET-DIN The SignalFire Ethernet Gateway has the following features: - Wide range DC power input. 6 to 36VDC - Power Over Ethernet (POE)

More information

T1K MODBUS Base Controller Specifications

T1K MODBUS Base Controller Specifications Base Controller 1 2 In This Chapter.... Base Controller Setting the DIP Switches Setting the Rotary Address Switches Port Pin out and Wiring RJ12 Serial Port Pin out and Wiring 2 2 Base Controller General

More information

USER MANUAL FOR GS100/GS1003G

USER MANUAL FOR GS100/GS1003G USER MANUAL FOR GS100/GS1003G 1 Table of Contents 1. INTRODUCTION... 3 2. FEATURES... 3 3. OPERATION... 3 4.CONNECTION DETAILS... 4 5.CONFIGURATION... 5 5.1 Hyper Terminal Setting... 5 5.2 GS100 Configuration...

More information

RS232/RS485/RS422 to TCP/IP Converter ITEM NO.: RS007

RS232/RS485/RS422 to TCP/IP Converter ITEM NO.: RS007 RS232/RS485/RS422 to TCP/IP Converter ITEM NO.: RS007 RS007 is a universal data converter which support serial RS232, RS422 and RS485 to the TCP / IP intelligent communication converter, it offers RS485/RS422

More information

MODBUS TCP/IP TO MODBUS SERIAL GATEWAY. MODEL No: MGate-1024-DC VER 2.0

MODBUS TCP/IP TO MODBUS SERIAL GATEWAY. MODEL No: MGate-1024-DC VER 2.0 MODBUS TCP/IP TO MODBUS SERIAL GATEWAY MODEL No: MGate-1024-DC VER 2.0 MILLENNIUM TECHNOLOGIES 440, MASTER MIND 1, ROYAL PALMS ESTATE AAREY MILK COLONY, GOREGAON (EAST), MUMBAI-400065. INDIA. PH: - 91-22-65229736,

More information

UR72 & UR75 Industrial Cellular Router

UR72 & UR75 Industrial Cellular Router UR72 & UR75 Industrial Cellular Router Quick Start Guide 1 Ursalink Technology Co., Ltd. Welcome Thank you for choosing Ursalink UR72/UR75 industrial cellular router. This guide describes how to install

More information

Gateway 1400 Reference Manual

Gateway 1400 Reference Manual Profibus-DP Gateway 1400 Reference Manual Copyright All Rights Reserved. No part of this document may be copied, reproduced, republished, uploaded, posted, transmitted, distributed, stored in or introduced

More information

Meter Centraliser Alarm Centraliser Unit LM50-TCP (Code M31521) INSTRUCTION MANUAL (M A)

Meter Centraliser Alarm Centraliser Unit LM50-TCP (Code M31521) INSTRUCTION MANUAL (M A) Meter Centraliser Alarm Centraliser Unit LM50-TCP (Code M31521) INSTRUCTION MANUAL (M9813380120-A) 1.- BASIC INSTRUCTIONS 1.1.- Checks on receipt. This manual assists in the installation and handling of

More information

Canlan INSTALLATION MANUAL

Canlan INSTALLATION MANUAL Canlan INSTALLATION MANUAL August 2014 Table of Contents Introduction... 4 Overview... 5 RJ45 Connector and Status LEDs... 5 Power Input... 6 RS232 / RS485 Connectors... 7 Installing the Canlan Software...

More information

SK CU4-EIP-C Part number:

SK CU4-EIP-C Part number: SK CU4-EIP-C Part number: 275 271 519 EtherNet/IP Internal Bus Interface The bus interface may only be installed and commissioned by qualified electricians. An electrician is a person who, because of their

More information

MODEL: WL40EW2F. Wireless I/O WL40F Series

MODEL: WL40EW2F. Wireless I/O WL40F Series Wireless I/O WL40F Series WIRELESS GATEWAY Modbus/TCP (Ethernet), Modbus-RTU Transparent 900MHz Band Wireless Device (parent device) 60 (2.36) FUTIONS & FEATURES This unit Incorporates 900MHz band wireless

More information

Industrial 4G LTE Cellular Gateway ICG-2420-LTE

Industrial 4G LTE Cellular Gateway ICG-2420-LTE Industrial 4G LTE Cellular Gateway ICG-2420-LTE Quick Installation Guide Table of Contents 1. Package Contents... 3 2. Requirements... 4 3. Starting Web Management... 5 4. Terminal Setup... 8 4.1. Logon

More information

GPRS-T1. Monitoring Converter. SATEL sp. z o.o. ul. Schuberta Gdańsk POLAND tel

GPRS-T1. Monitoring Converter. SATEL sp. z o.o. ul. Schuberta Gdańsk POLAND tel Monitoring Converter GPRS-T1 Program version 1.01 gprs-t1_en 04/09 SATEL sp. z o.o. ul. Schuberta 79 80-172 Gdańsk POLAND tel. + 48 58 320 94 00 info@satel.pl www.satel.pl WARNINGS The module should only

More information

Lantech LSC-1102B SERIAL TO TCPIP CONVERTER. User Manual

Lantech LSC-1102B SERIAL TO TCPIP CONVERTER. User Manual Lantech LSC-1102B SERIAL TO TCPIP CONVERTER User Manual V1.0 Sep 2016 Table of Contents 1. Introduction 3 Overview 4 Product Specifications 8 2. Description & Installation 10 Product Panel Views 10 LED

More information

IntesisBox Modbus Server - Honeywell XLS 80

IntesisBox Modbus Server - Honeywell XLS 80 IntesisBox Server - Honeywell XLS 80 Gateway for integration of Honeywell XLS 80 fire panels into (RTU and TCP) enabled control systems. Integrate your Honeywell fire panels into your master device or

More information

Netbiter EC300 Series

Netbiter EC300 Series Netbiter EC300 Series USER MANUAL SCM-1202-012 2.2 ENGLISH Important User Information Liability Every care has been taken in the preparation of this document. Please inform HMS Industrial Networks AB of

More information

ACE PLUS CORP. APCON100 series Operation Manual RS-232 to Ethernet Converter

ACE PLUS CORP. APCON100 series Operation Manual RS-232 to Ethernet Converter APCON100 series Operation Manual RS-232 to Ethernet Converter Page 1 of 24 APCON100 series Operation Manual Index Chapter 1 Specifications 2 Chapter 2 Introduction 3 Chapter 3 Easy Installation 4 Chapter

More information

KX GPRS M2M I-NET. User s Guide. Version: 1.0. Date: March 17, KORTEX PSI 3 Bd Albert Camus Tel:

KX GPRS M2M I-NET. User s Guide. Version: 1.0. Date: March 17, KORTEX PSI 3 Bd Albert Camus Tel: KX GPRS M2M I-NET User s Guide Version: 1.0 Date: March 17, 2011 KORTEX PSI 3 Bd Albert Camus Tel: +33-1-34043760 e-mail: contact@kortex-psi.fr Revision History Version Date Changes 1.0 March 17, 2011

More information

PAC BI-DP BIM and 8701-CA-BI Carrier

PAC BI-DP BIM and 8701-CA-BI Carrier June 2013 PAC8000 8507-BI-DP BIM and 8701-CA-BI Carrier PROFIBUS DP Bus Interface Module and Carrier The 8507-BI-DP Bus Interface Module (BIM) provides the communications link between the PAC8000 series

More information

IntesisBox Modbus Server Fidelio IP

IntesisBox Modbus Server Fidelio IP IntesisBox Modbus Server Fidelio IP User Manual r1 eng Issue Date: 10/04/2014 Intesis Software S.L. All Rights Reserved. Information in this document is subject to change without notice. The software described

More information

CMU 100 RS485 to 7x, 6x, 5x, 4x Multimode Fiber Optic Star Coupler User Manual

CMU 100 RS485 to 7x, 6x, 5x, 4x Multimode Fiber Optic Star Coupler User Manual CMU 100 RS485 to 7x, 6x, 5x, 4x Multimode Fiber Optic Star Coupler User Manual CMU 100 / 2.5.6.6.6.6.6.6.6 12, CMU 100 / 8.5.6.6.6.6.6.6.6 12, CMU 100 / 2.5.6.6.6.6.6.6 12, CMU 100 / 8.5.6.6.6.6.6.6 12,

More information

INTRINSICALLY SAFE DUPLEXER PROTECTION. ELECTRONICS, INC Vulcan Road Apopka, Florida MOTOR INSTRUCTION MANUAL

INTRINSICALLY SAFE DUPLEXER PROTECTION. ELECTRONICS, INC Vulcan Road Apopka, Florida MOTOR INSTRUCTION MANUAL INTRINSICALLY SAFE DUPLEXER INSTRUCTION MANUAL MOTOR PROTECTION ELECTRONICS, INC. 2464 Vulcan Road Apopka, Florida 32703 Phone: Website: (407) 299-3825 www.mpelectronics.com Operating Program Revision:

More information

Revision History. Version Date Changes Description of bridge mode settings via web interface Initial version

Revision History. Version Date Changes Description of bridge mode settings via web interface Initial version MANUAL ANAGATE CAN ANALYTICA GmbH Vorholzstrasse 36 Tel. +49 721 35043-0 E-mail: info@analytica-gmbh.de D-76137 Karlsruhe Fax: +49 721 35043-20 WWW: http://www.analytica-gmbh.de 1 2004-2006, Analytica

More information

Ethernet to Serial Port Module RS-232/422/485 to Internet Gateway

Ethernet to Serial Port Module RS-232/422/485 to Internet Gateway Ethernet to Serial Port Module RS-232/422/485 to Internet Gateway (Model: IPM-S) Wireless Gateway: Active RFID Gateway Bluetooth to Internet Application: Energy Meter Networks Motor Control Industrial

More information

Managed 100 Mbps Ethernet Switches TOP FRONT. Click 340/341/342

Managed 100 Mbps Ethernet Switches TOP FRONT. Click 340/341/342 Managed 100 Mbps Ethernet Switches Click 340/341/342 The Click 340/341/342 are compact managed Ethernet switches that add network configuration capability, remote monitoring and diagnostics, and integral

More information