Level probe with ceramic measuring cell
|
|
- Elisabeth Berry
- 5 years ago
- Views:
Transcription
1 Level probe with ceramic measuring cell Type 4391 B Operating Instructions 8.00/
2 1 General M.K. JUCHHEIM GmbH & Co is a company certified to ISO The level probe described below complies with the requirements of DIN and VDE. You have purchased a product which will suit the most demanding applications and fulfills or exceeds all the specifications listed. Nevertheless, if you have any reason for complaint, please return the instrument to us, together with a detailed description of the fault you have observed. Please read these Operating Instructions before commissioning the instrument. We reserve the right to make technical alterations. If any difficulties should arise during commissioning or operation, please contact the nearest subsidiary or the head office. If you have any suggestions how to improve these operating instructions, or a product, please contact our head office. Phone: +49 (0) Fax: +49 (0) The level probe Type 4391 does not require any maintenance. It does not contain any components that can be repaired or replaced by the user. Repairs can only be carried out in the factory! 2 Specific These operating instructions do not take account of all possible applications or product variations. If you cannot find any notes on your particular application task, please contact our head office. If you need detailed technical information on this instrument, please ask for the corresponding Data Sheet. Type Data Sheet Pt
3 You will find the instrument version of your level probe on the nameplate. Made in Germany Typ: / ,25 bar DC V ma F.-Nr.: (1) (2) (3) (4) (5) (1) Type code (4) Supply voltage (2) Range (5) Serial number (3) Output 3 Conditions of use - It is essential to ground the level probe and protect it against electrical discharge (lightning protection)! - The temperature of the medium must lie within the range -20 to +60 C (do not allow the level probe to freeze in the medium). - Like all sensitive measuring devices, the level probe should not be exposed to excessive temperature variations. These will eventually lead to changes in zero and span. - Do not exceed the pressure range or the permissible overpressure. - Under no circumstances must the front-flush diaphragm be touched with pointed objects. - Do not direct a pressure jet onto the diaphragm. - The use of the process connection closed below (658) is recommended for liquids contaminated by coarse particles.
4 4 Safety notes Caution Please observe the relevant regulations when handling potentially harmful media (e.g. flammable and toxic substances). If these regulations are disregarded, this may result in injury to persons or damage to equipment. Only personnel with the appropriate qualifications should be allowed to work on or with this instrument. 5 Electrical connection Caution The level probe may only be connected by suitably qualified personnel. 6 Mounting the attached connecting cable Note - Minimum bending radius 120 mm (fixed installation). - The cable must not be compressed. The end of the cable must terminate in a dry space, to prevent the formation of condensation. It is advantageous to run the cable directly into the connection space (switchgear cabinet). - When lengthening the cable, make sure that pressure equilibration is provided, while avoiding the ingress of moisture.
5 7 Layout and connection diagrams Level probe in 2-wire circuit: layout Supply voltage V DC. All components of the measuring circuit are switched in series. Level probe in 2-wire circuit: connection
6 Level probe in 3-wire circuit: layout Supply voltage 5 V DC. Common negative lead (ground) for supply and measurement signal. Level probe in 3-wire circuit: connection
7 Temperature sensor in 4-wire circuit: connection 8 Fault/ Errors Type of fault Possible cause Measure No output signal Output signal remains constant, even with a change of pressure no supply voltage lead break, wrong connection check supply check connecting cables error on level probe caused by impermissible operating return probe to supplier, conditions together with a description of the fault measuring system of device destroyed by excessive pressure overvoltage causes non-linear output signal (because of current limiting) provide correct supply voltage range too narrow return probe to supplier, together with a description of the fault
8 Type of fault Possible cause Measure Output signal is too high Output signal is too small Zero of the output signal is wrong Characteristic of the output signal is nonlinear selected range is too narrow electronics of level probe is faulty, or supply voltage is too high with current output signal: burden is too large with voltage output signal: burden is too small supply voltage is too low level probe maladjusted because of impermissible operating conditions (e.g. overpressure) level probe maladjusted because of impermissible operating conditions (e.g. overpressure) return probe to supplier, together with a description of the fault alter burden of measuring circuit change supply voltage return probe to supplier, together with a description of the fault
9 9 Dimensions Level probe (a) only with Pt100 temperature sensor (b)customer specification (c) to sensor surface
10 Accessories Clamping case with pressure equilibration, Part No mounting hole Cable holder, Part No
11
12 M. K. JUCHHEIM GmbH & Co Hausadresse: Moltkestraße Fulda, Germany Lieferadresse: Mackenrodtstraße Fulda, Germany Postadresse: Fulda, Germany Telefon: (06 61) Telefax: (06 61) Internet:
JUMO dtrans T02. programmable. transmitter. B Operating Instructions 5.00/
JUMO dtrans T02 programmable transmitter B 95.6521 Operating Instructions 5.00/00380664 Overview of operation JUMO dtrans T02 Standard accessory 1 Type designation (1) Basic version 956521 programmable
More informationJUMO ecotrans Lf 01/02
JUMO ecotrans Lf 01/02 Transmitter/Switching Device for Conductivity Operating Manual 20273100T90Z002K000 V5.00/EN/00435548 Content 1 Notes... 5 2 Identifying the device version... 6 2.1 Type designation...
More informationElectronic Temperature Controller. Instruction Manual Version
Electronic Temperature Controller 701 Instruction Manual Version 1.00.01 Dear Customer, we have made up this operating manual in such a way that all necessary information about the product can be found
More informationIO-PT4. Component identification. User safety and equipment protection guidelines. Unitronics Industrial Automation Systems 1
IO-PT4 I/O Expansion Module 4 PT100 Inputs (-50 to 460 C) The IO-PT4 is an I/O expansion module that can be used in conjunction with specific Unitronics OPLC controllers. The module offers 4 PT100 inputs
More informationThis 4200-RM Rack Mount Kit is for installation in 4200-CAB series cabinets only.
Keithley Instruments, Inc. 28775 Aurora Road Cleveland, Ohio 44139 (440) 248-0400 Fax: (440) 248-6168 www.keithley.com Model 4200-RM Rack Mount Kit Packing List Introduction NOTE This 4200-RM Rack Mount
More informationOperating instructions Evaluation system for flow sensors VS / / 2013
Operating instructions Evaluation system for flow sensors VS3000 7097 / 0 07 / 203 Contents Preliminary note...2 2 Safety instructions...3 3 Function and features... Mounting.... Mounting of the sensors...
More informationBMF400 Input/output module
BMF400 Input/output module Input/output module with six universal inputs/outputs and four floating relay outputs for function extensions of the BMR bus module controller. Issue date: December 6, 2006 Subject
More informationOperating instructions AS-i SmartLine module AC3200 AC /00 06/2016
Operating instructions AS-i SmartLine module AC3200 AC3201 80237876/00 06/2016 Contents 1 Preliminary note...3 1.1 Symbols used...3 1.2 Warnings used...3 2 Safety instructions...3 2.1 General...3 2.2 Target
More informationModel 2600B-PM V Protection Module with 1 A Clamp. Description / April 2015 *PPA * 1
Keithley Instruments 28775 Aurora Road Cleveland, Ohio 44139 1-800-935-5595 http://www.keithley.com Model 2600B-PM-1 200 V Protection Module with 1 A Clamp Description The Model 2600B-PM-1 200 V Protection
More informationModel 8020-STC. Kelvin Standard Triaxial Connector Card. Description / October 2014 *P * 1
Keithley Instruments 28775 Aurora Road Cleveland, Ohio 44139 1-800-935-5595 http://www.keithley.com Model 8020-STC Kelvin Standard Triaxial Connector Card Description The Model 8020-STC Kelvin Standard
More informationModel 8020-KHV. Kelvin Keithley Triaxial Connector Card. Description / October 2014 *P * 1
Keithley Instruments 28775 Aurora Road Cleveland, Ohio 44139 1-800-935-5595 http://www.keithley.com Model 8020-KHV Kelvin Keithley Triaxial Connector Card Description The Model 8020-KHV Keithley HV Connector
More informationOperating instructions. Standstill monitor A / / 2011
Operating instructions Standstill monitor A300 UK 1 2 3 4 5 6 7 8 7390337 / 01 02 / 2011 1 2 3 4 5 6 7 8 switchpoint min max pulse/min power Made in Germany ifm electronic gmbh D 45127 Essen func. I II
More informationIO-AO6X I/O Expansion Module 6 Isolated Analog Outputs
IO-AO6X I/O Expansion Module 6 Isolated Analog Outputs The IO-AO6X is an I/O Expansion Module that can be used in conjunction with specific Unitronics OPLC controllers. The module offers 6 12-bit isolated
More informationModel 2657A-LIM-3 LO Interconnect Module
Keithley Instruments, Inc. 28775 Aurora Road Cleveland, Ohio 44139 1-888-KEITHLEY http://www.keithley.com Model 2657A-LIM-3 LO Interconnect Module User's Guide Description The Model 2657A-LIM-3 LO Interconnect
More informationModel 7705 Control Module
www.keithley.com Model 7705 Control Module User s Guide PA-696 Rev. D / October 2006 A G R E A T E R M E A S U R E O F C O N F I D E N C E Safety Precautions The following safety precautions should be
More informationCVU-3K-KIT. 3 kv Bias Tee Kit. Description. Parts list / October 2014 *P * 1
Keithley Instruments 28775 Aurora Road Cleveland, Ohio 44139 1-800-935-5595 http://www.keithley.com CVU-3K-KIT 3 kv Bias Tee Kit Description The CVU-3K-KIT Bias Tee Kit consists of three bias tees for
More informationEnglish. Operating manual. Universal transmitter UT125. Save for later reference. Companies / brands of GHM
English Operating manual Universal transmitter UT125 Companies / brands of GHM www.ghm-messtechnik.de Save for later reference. Table of contents page 1. Intended use (areas of application)... 3 1.1 Safety
More informationModel 2380 Rack-Mount Kit
Keithley Instruments 28775 Aurora Road Cleveland, Ohio 44139 1-800-935-5595 http://www.tek.com/keithley Model 2380 Rack-Mount Kit Installation Instructions Introduction The Model 2380 Fixed Rack-Mount
More informationL Series Humidity/-temperature sensors for use in heating, ventilation and air conditioning Technical data Humidity
Galltec Mess- und Regeltechnik GmbH MELA Sensortechnik GmbH Boschstr. 4 Raasdorfer Str. 18 71145 Bondorf. Germany 07987 Mohlsdorf-Teichwolframsdorf. Germany Tel. +49 (0)7457-9453-0 Tel. +49(0)3661-62704-0
More informationOperating instructions. Switching amplifier DN0210 DN / / 2015
Operating instructions Switching amplifier DN0210 DN0220 UK 80011079 / 00 01 / 2015 Contents 1 Preliminary note...4 1.1 Symbols used...4 1.2 Warning signs used...4 2 Safety instructions...5 2.1 General...5
More informationOperating manual. Series 450. Compact thermometer. BA01235O/09/en/
Operating manual Series 450 Compact thermometer BA01235O/09/en/01.13 71220279 2 Table of contents 1 Safety instructions... 3 2 Installation... 4 3 Wiring overview... 7 4 Commissioning... 7 5 Operation...
More informationOperating instructions. Speed monitor D / / 2014
Operating instructions Speed monitor D200 80005257 / 00 05 / 2014 Contents 1 Preliminary note...4 1.1 Symbols used...4 1.2 Warning signs used...4 2 Safety instructions...5 2.1 General...5 2.2 Target group...5
More informationIO-DI8-TO8 I/O Expansion Module 8 Inputs, 8 Outputs
IO-DI8-TO8 I/O Expansion Module 8 Inputs, 8 Outputs The IO-DI8-TO8 is an I/O expansion module that can be used in conjunction with specific Unitronics OPLC controllers. The module offers 8 digital inputs,
More informationOperating Instructions
Operating Instructions t i SPAN NOT USED - - 4...20mA DISPLAY t i SPAN END POINT DISPLAY Ð - 4...20mA p Safety information, Note Ex area Safety information Please read this manual carefully, and also take
More informationCVU-200-KIT. 200 V Bias Tee Kit. Description. Parts list / October 2014 *P A* 1
Keithley Instruments 28775 Aurora Road Cleveland, Ohio 44139 1-800-935-5595 http://www.keithley.com CVU-200-KIT 200 V Bias Tee Kit Description The CVU-200-KIT Bias Tee Kit consists of three 2600-RBT-200
More informationPCT2000. User Manual. Precision current transducer 2000 A
PCT2000 User Manual PCT2000 Precision current transducer 2000 A User Manual Status: November 6, 2018 Copyright 2018 ZES ZIMMER Electronic Systems GmbH Pfeiffstraße 12 61440 Oberursel (Taunus), Germany
More informationKOBOLD PDA Series Digital Pressure Transmitter
KOBOLD PDA Series Digital Pressure Transmitter PDA-153 Series User Instructions KOBOLD Instruments Inc. 1801 Parkway View Drive Pittsburgh, PA 15205 Phone (412) 788-2830 Fax (412)-788-4890 www.koboldusa.com
More informationJUMO mtron T. Measuring, Control, and Automation System Operating panels. Operating Manual T90Z001K000 V2.00/EN/
JUMO mtron T Measuring, Control, and Automation System Operating panels Operating Manual 70506500T90Z001K000 V2.00/EN/00672050 Contents 1 Introduction......................................................5
More information2-PHASE STEPPING MOTOR DRIVER FE Z4 TRANSFER
2-PHASE STEPPING MOTOR DRIVER FE Z4 TRANSFER For Diaphragm Dosing Pumps FEM 1.02 / FEM 1.09 Controller board package, without pump: ID 157870 Operating and Installation Manual It is important to read and
More informationModel 2460-KIT. Screw Terminal Connector Kit. Description / September 2014 *P * 1
Keithley Instruments 28775 Aurora Road Cleveland, Ohio 44139 1-800-935-5595 http://www.keithley.com Model 2460-KIT Screw Terminal Connector Kit Description The Model 2460-KIT Screw Terminal Connector Kit
More informationModel 2380 Rack-Mount Kit
Keithley Instruments 28775 Aurora Road Cleveland, Ohio 44139 1-800-935-5595 http://www.tek.com/keithley Model 2380 Rack-Mount Kit Installation Instructions Introduction The Model 2380 Fixed Rack-Mount
More information5504 Thermocouple Analog Input Module
550 Thermocouple Analog Input Installation, Operation and Maintenance Setup Manual 5/9/0 Safety Information The information provided in this documentation contains general descriptions and/or technical
More informationHV-CS kv Edge Mount Triaxial Jack
Keithley Instruments 28775 Aurora Road Cleveland, Ohio 44139 1-800-935-5595 http://www.tek.com/keithley HV-CS-1589 3 kv Edge Mount Triaxial Jack Installation Information Description The Keithley Instruments
More informationPHOENIX CONTACT - 05/2007
Ex Universal Module Carrier (Motherboard) for Accommodating 3-Wire Measuring Transducers, Intrinsically Safe, for a Maximum of 8 PI Ex Modules INTERFACE Data Sheet 103030_00_en PHOENIX CONTACT - 05/2007
More informationUser safety and equipment protection guidelines
Snap-in I/O Module The V200-18-E1 plugs directly into the back of compatible Unitronics OPLCs, creating a selfcontained PLC unit with a local I/O configuration. The module offers: 3 analog inputs 16 digital
More informationM215 (M215-60) Safety
M215 QUICK INSTALL GUIDE M215 (M215-60) Safety Important Safety Information This document contains important instructions to use during installation and maintenance of the Enphase M215 Microinverter. To
More information7KM2112-0BA00-3AA0 SENTRON PAC3200. English. Operating Instructions DANGER CAUTION DANGER. Order-No.: A5E Last update: 18 January 2008
SENTRON PAC3200 Operating Instructions Read and understand these instructions and the relevant manual before installing, operating, or maintaining the equipment. CAUTION DANGER Hazardous voltage. Will
More informationHigh Speed Remote I/O Module
High Speed Remote I/O Module EXF-RC15 The Unitronics EXF-RC15 is a High Speed Remote I/O Module that offers three High Speed Counter inputs and four high speed outputs. Overall, the EXF-RC15 offers 9 digital
More informationPressure transmitter for highest pressure applications Up to 217,500 psi (15,000 bar) Model HP-2
Electronic pressure measurement Pressure transmitter for highest pressure applications Up to 217,500 psi (15,000 bar) Model HP-2 WIKA data sheet PE 81.53 Applications Test bench construction Water jet
More informationOperating Instructions. Intrinsically Safe Isolation Relay for Switches Model: REL manual_rel-6_0505
Operating Instructions Intrinsically Safe Isolation Relay for Switches Model: REL-6003 manual_rel-6_0505 1. Contents 1. Contents...2 2. Note...3 3. Instrument Inspection...3 4. Regulation Use...3 5. Operating
More informationWhen any of the following symbols appear, read the associated information carefully. Symbol Meaning Description
Vision OPLC V350-35-R34/V350-J-R34 Installation Guide The Unitronics V350-35-R34/V350-J-R34 offers the following onboard I/Os: 22 Digital Inputs, configurable via wiring to include 2 Analog and 3 HSC/Shaft-encoder
More informationV E2B Snap-in I/O Module
V200-18-E2B Snap-in I/O Module The V200-18-E2B plugs directly into the back of compatible Unitronics OPLCs, creating a selfcontained PLC unit with a local I/O configuration. Features 16 isolated digital
More informationTap Manager TM100. Operating Instructions
Tap Manager TM100 Operating Instructions 2 Contents Contents 1 General... 5 1.1 Safety instructions... 5 1.2 Application... 5 2 Design... 6 2.1 Controls... 6 2.1.1 Scroll keys in display field... 6 2.1.2
More informationWhen any of the following symbols appear, read the associated information carefully. Symbol Meaning Description
Uni-I/O Modules Installation Guide UID-0808R, UID-0808T, UID-1600,UID-0016R, UID-0016T Uni-I/O is a family of Input/Output modules that are compatible with the UniStream control platform. This guide provides
More informationJ itron DR 100 Microprocessor Controller
JUMO GmbH & Co. KG Delivery address: Mackenrodtstraße 14, 36039 Fulda, Germany Postal address: 36035 Fulda, Germany Phone: +49 661 60030 Fax: +49 661 6003607 Email: mail@jumo.net Internet: www.jumo.net
More informationOperating instructions Hinge safety switch TV.S 335 TV.S About this document. Content
1. About this document Operating instructions.............pages 1 to 6 Original 1.1 Function This operating instructions manual provides all the information you need for the mounting, set-up and commissioning
More informationM250 (M LL) Safety
M250 SAFETY M250 (M250-60-2LL) Safety Important Safety Information This document contains important instructions to use during installation of the Enphase M250 Microinverter. To reduce the risk of electrical
More informationFL MC 2000T. Fiber optic converter for 10/100Base-Tx to single- or multi-mode fiberglass with SC-duplex and ST connections. Data sheet 3379_en_B
Fiber optic converter for 10/100Base-Tx to single- or multi-mode fiberglass with SC-duplex and ST connections Data sheet 3379_en_B 1 Description PHOENIX CONTACT 2015-07-14 2 Features Media converters provide
More informationenglish S-5EC Potentiometer 5-step Operating Instructions Keep for reference! L-BAL-E265-GB 1608 Index 002
S-5EC english Potentiometer 5-step Operating Instructions Keep for reference! Content 1 General notes............................................ 3 1.1 Structure of the operating instructions....................
More informationEnglish. Operating manual. Limit switch GS125. Keep for future reference. Ventures / brands of GHM
English Operating manual Limit switch GS125 Ventures / brands of GHM www.ghm-messtechnik.de Keep for future reference. Table of contents Page 1. Intended use (areas of application)... 3 1.1 Safety signs
More informationOperating instructions Safe AS-i input module ASIM-C-M About this document. Content
7 Set-up and maintenance 7.1 Functional testing....10 7.2 Maintenance...10 EN Operating instructions.............pages 1 to 6 Original 8 Disassembly and disposal 8.1 Disassembly....10 8.2 Disposal...10
More informationMDM 011-Z1 Regen Resistor
MDM 011-Z1 Regen Resistor Date of creation: 10.04.2017 Version date: 10.04.2017 Article number: 09-402-011-Z1-E Publisher: SIGMATEK GmbH & Co KG A-5112 Lamprechtshausen Tel.: 06274/4321 Fax: 06274/4321-18
More informationLight Control SLS ADRIA
Instruction and Mounting Manual Light Control SLS ADRIA 1 Introduction... 2 2 Safety instructions... 2 2.1 Meaning of the safety symbols... 2 2.2 General safety information... 2 3 Brief description...
More informationV E1B Snap-in I/O Module
V200-18-E1B Snap-in I/O Module The V200-18-E1B plugs directly into the back of compatible Unitronics OPLCs, creating a selfcontained PLC unit with a local I/O configuration. Features 16 isolated digital
More informationEXPANSION PERIPHERAL CVM-R10 C. (Code ) INSTRUCTION MANUAL ( M / 00 A ) (c) CIRCUTOR S.A.
EXPANSION PERIPHERAL CVM-R10 C (Code 7 70 217 ) INSTRUCTION MANUAL ( M 981 170 / 00 A ) (c) CIRCUTOR S.A. ------ CVM-R10 C Peripheral --------------- Pag. 1 CVM-R10C EXPANSION PERIPHERAL 1.- DESCRIPTION
More informationPROCESS AUTOMATION. MANUAL Z-System. Zener Barriers ISO9001
PROCESS AUTOMATION MANUAL Z-System Zener Barriers ISO9001 With regard to the supply of products, the current issue of the following document is applicable: The General Terms of Delivery for Products and
More informationJUMO safetym TB/TW 08 Temperature limiter, monitor as per DIN EN
JUMO GmbH & Co. KG Delivery address: Mackenrodtstraße 14 36039 Fulda, Germany Postal address: 36035 Fulda, Germany Phone: +49 661 6003-0 Fax: +49 661 6003-607 E-mail: mail@jumo.net Internet: www.jumo.net
More information2260B-RMK-Series Rack Mount Kit
Keithley Instruments, Inc. 28775 Aurora Road Cleveland, Ohio 44139 1-888-KEITHLEY http://www.keithley.com Assembly and Mounting Instructions Introduction The 2260B-RMK-Series Rack Mount Kit is suited for
More informationEX-RC1 Remote I/O Adapter
EX-RC1 Remote I/O Adapter The EX-RC1 interfaces between Unitronics Vision OPLCs and remote I/O Expansion Modules distributed throughout your system. The adapter is connected to a PLC via CANbus. Each adapter
More informationMicro-OPLC Installation Guide
Jazz OPLC Micro-OPLC Installation Guide 6 Digital Inputs, 4 Relay Outputs 6 Digital, 2 Analog/Digital, 2 Analog Inputs, 6 Relay Outputs Before using this product, the user must read and understand this
More informationWhen any of the following symbols appear, read the associated information carefully. Symbol Meaning Description
Uni-I/O Wide Modules Installation Guide UID-W1616R, UID-W1616T Uni-I/O Wide is a family of Input/Output modules that are compatible with the UniStream control platform. Wide Modules are 1.5 times as wide
More informationVision OPLC V TR6/V350-J-TR6
Vision OPLC V350-35-TR6/V350-J-TR6 Installation Guide The Unitronics V350-35-TR6/V350-J-TR6 offers the following onboard I/Os: 8 Digital Inputs, configurable via wiring to include 2 Analog (current/voltage)
More informationMARTINDALE INSTRUCTIONS MM35 DIGITAL MULTIMETER ELECTRIC. Trusted by professionals
Martindale Electric will carry out routine calibration (on a chargeable basis) if the instrument is returned, carriage paid, to the address on the final page of this document. Alternatively, a chargeable
More informationComponent identification
IO-ATC8 I/O Expansion Module 8 Analog/Thermocouple Inputs The IO-ATC8 is an I/O Expansion Module that can be used in conjunction with specific Unitronics OPLC controllers. The module offers 8 inputs that
More informationPCT200. User Manual. Precision current transducer 200 A
PCT200 User Manual PCT200 Precision current transducer 200 A User Manual Status: November 6, 2018 Copyright 2018 ZES ZIMMER Electronic Systems GmbH Pfeiffstraße 12 61440 Oberursel (Taunus), Germany phone
More informationDCS-E 1kW Series, DLM-E 3kW & 4kW Power Supplies
DCS-E 1kW Series, DLM-E 3kW & 4kW Power Supplies M51A Option: Isolated Analog Programming Manual Power Supplies Elgar Electronics Corporation 9250 Brown Deer Road San Diego, CA 92121-2294 1-800-73ELGAR
More informationIO-DI8-TO8, IO-DI8-TO8-L I/O Expansion Modules 8 Inputs, 8 Outputs
IO-DI8-TO8, IO-DI8-TO8-L I/O Expansion Modules 8 Inputs, 8 Outputs The IO-DI8-TO8 and IO-DI8-TO8-L are I/O expansion modules that can be used in conjunction with specific Unitronics OPLC controllers. The
More informationV E1B Snap-in I/O Module
V200-18-E1B Snap-in I/O Module The V200-18-E1B plugs directly into the back of compatible Unitronics OPLCs, creating a selfcontained PLC unit with a local I/O configuration. Features 16 isolated digital
More informationQuick Guide. English. Appliance. SMAVIA Enterprise JBOD. Rev /
Quick Guide English Appliance IPS 10 000 SMAVIA Enterprise JBOD Rev. 1.0.0 / 2017-02-13 Information about copyright, trademarks, design patents 2017 Dallmeier electronic The reproduction, distribution
More informationADAMCZEWSKI. Ordering data AD-STVEX 710 GVD Option: Factory-software configuration as per customer specifications.
EN ADAMCZEWSKI Elektronische Messtechnik GmbH Felix-Wankel-Str. 13 / 74374 Zaberfeld Tel. +49 (0)7046-875 Fax +49 (0)7046-7678 vertrieb@ad-messtechnik.de Operating Instructions Supply Isolation Amplifier
More informationINSPECTION CAMERA MODEL NO: CIC2410 OPERATION & SAFETY INSTRUCTIONS PART NO: GC0116
INSPECTION CAMERA MODEL NO: CIC2410 PART NO: 6470385 OPERATION & SAFETY INSTRUCTIONS GC0116 INTRODUCTION Thank you for purchasing this CLARKE Inspection Camera. Before attempting to use this product, please
More informationModels 2601B, 2602B, and 2604B System SourceMeter Instruments Quick Start Guide
Models 2601B, 2602B, and 2604B System SourceMeter Instruments Quick Start Guide Safety precautions Observe the following safety precautions before using this product and any associated instrumentation.
More informationEnglish. Operating Manual. Conductive point level switch MLR120. Retain for later reference. Companies / brands of GHM
English Operating Manual Conductive point level switch MLR120 Companies / brands of GHM www.ghm-group.de Retain for later reference Table of contents Page 1. Proper use (application areas)... 3 Safety
More informationmultisys User manual Technical parameters D2-MSMT-1 Gateway from Modbus TCP to Modbus RTU, serial RS _EDEBDA _EN
User manual Technical parameters multisys D2-MSMT-1 Gateway from Modbus TCP to Modbus RTU, serial RS485 System I English Your partner for network analysis KBR Kompensationsanlagenbau GmbH does not accept
More informationORB TM 4-20 ma Input Box Installation & Operation Manual
IOM ORB TM 4-20 ma Input Box Installation & Operation Manual ORB TM 4-20 ma Input Box Installation & Operation Manual CONTENTS I. HANDLING & STORAGE... 1 Inspection and Handling Disposal and Recycling
More informationSafety Precautions A good safety practice is to expect that hazardous voltage is present in any unknown circuit before measuring.
Safety Precautions The following safety precautions should be observed before using this product and any associated instrumentation. Although some instruments and accessories would normally be used with
More informationDTC P0AA6 - High Voltage Isolation Fault
DTC P0AA6 - High Voltage Isolation Fault Product Family Orion BMS [Original] (24-180 Cell) Orion BMS 2 (24-180 Cell) Orion JR (16 Cell) Fault Supported YES YES NO FAULT DESCRIPTION This code is set when
More informationInstruction Manual. M Pump Motor Controller. For file reference, please record the following data:
Instruction Manual M Pump Motor Controller For file reference, please record the following data: Model No: Serial No: Installation Date: Installation Location: When ordering replacement parts for your
More informationWhen any of the following symbols appear, read the associated information carefully. Symbol Meaning Description
Uni-I/O Modules Installation Guide UID-0808THS Uni-I/O is a family of Input/Output modules that are compatible with the UniStream control platform. This guide provides basic installation information for
More informationMINI MCR-SL-PT100-UI(-SP)(-NC)
Configurable Temperature Transducer for PT100 Data Sheet 04/2005 Functions MINI MCR-SL-PT100-UI(-SP)(-NC) is a configurable 3-way isolated temperature measuring transducer. It is suitable for the connection
More informationInstallation, Operation & Maintenance Instructions / Technical Document
Installation, Operation & Maintenance Instructions / Technical Document Model VHL Mini Vibrating Fork Point Level Sensor for Liquids Thank you for purchasing the Model VHL Mini Vibrating Fork Point Level
More informationSX100A. Features. Typical Applications. Description
Datasheet -- Pressure Sensors: Measurement Type: Absolute; 0 psia to 100 psia, Unamplified, Representative photograph, actual product appearance may vary. Due to regional agency approval requirements,
More informationOperating manual Solareg II BASIC DC
Operating manual Solareg II BASIC DC Microcontroller-controlled temperature difference controller for solar thermal systems Explanation of the graphic symbols Attention! Symbol indicates possible dangers
More informationPHOENIX CONTACT - 12/2007
Ex-i NAMUR Isolation Amplifier, With Intrinsically Safe Input and Active Transistor Output, Two-Channel INTERFACE Data Sheet 0943_00_en PHOENIX CONTACT - /007 Description The PI-EX-ME-NAM/TO-A is a two-channel
More informationFailure to comply with appropriate safety guidelines can cause severe injury or property damage.
Jazz OPLC Micro-OPLC Installation Guide 6 Digital Inputs, 4 Relay Outputs 6 Digital, 2 Analog/Digital, 2 Analog Inputs, 6 Relay Outputs Before using this product, the user must read and understand this
More informationPI-EX-ME-2NAM/COC-120VAC
PI-EX-ME-NAM/COC-0VAC Ex-i NAMUR Isolation Amplifier, With Intrinsically Safe Input and Relay Output, PDT, Two-Channel, 0 V AC Supply INTERFACE Data Sheet 0944_00_en PHOENIX CONTACT - 0/008 Description
More informationPortable pressure calibrator Model CPH7600
Calibration technology Portable pressure calibrator Model CPH7600 WIKA data sheet CT 17.01 Wally Box III Applications Calibration service companies and service industry Measurement and control laboratories
More informationOperating Manual UMB ISO Converter ISOCON Order Number: 8160.UISO
Order Number: 8160.UISO Status: V3; 17.09.2010c G. Lufft Mess- und Regeltechnik GmbH, Fellbach, Germany 1 TABLE OF CONTENTS PLEASE READ BEFORE USE... 3 DESCRIPTION... 5 UMB ISO CONVERTER ISOCON... 6 CONFIGURATION...
More informationPI-EX-ME-2NAM/COC-24VDC
Ex-i NAMUR Isolation Amplifier, With Intrinsically Safe Input and Relay Output, PDT, Two-Channel, 4 V DC Supply INTERFACE Data Sheet 0033_0_en PHOENIX CONTACT - /007 Description The PI-EX-ME-NAM/COC-4VDC
More informationControl unit SG-EFS 104/2W. EN Operating instructions. Innovative by tradition. Version SG-EFS 104/2W 24 V=/~
Innovative by tradition. Control unit SG-EFS 104/2W EN Operating instructions Version 0.9 1005196 SG-EFS 104/2W 24 V=/~ Original instructions Mayser GmbH & Co. KG Örlinger Straße 1 3 89073 Ulm GERMANY
More informationOperating Manual / IEC. Explosion-Proofed Junction Boxes, Polyester. Wallücker Bahndamm 7 DE Kirchlengern
Operating Manual / IEC Explosion-Proofed Junction Boxes, Polyester Wallücker Bahndamm 7 DE- 32278 Kirchlengern Tel.: +49 5223 49107-0 Fax: +49 5223 49107-28 info@multi-box.com www.multi-box.com Contents
More informationIO-DI8-RO8, IO-DI8-RO8-L I/O Expansion Modules 8 Inputs, 8 Outputs
IO-DI8-RO8, IO-DI8-RO8-L I/O Expansion Modules 8 Inputs, 8 Outputs The IO-DI8-RO8 and IO-DI8-RO8-L are I/O expansion modules that can be used in conjunction with specific Unitronics OPLC controllers. The
More informationEX-RC1 Remote I/O Adapter
EX-RC1 Remote I/O Adapter The EX-RC1 interfaces between Unitronics Vision OPLCs and remote I/O Expansion Modules distributed throughout your system. The adapter is connected to a PLC via CANbus. Each adapter
More informationThis simple chassis houses one media-converter module and features an external AC power supply and also a terminal block for DC power input.
LMC5103A-R2 1-slot Multipower Desktop Chassis (Module Not Included) This simple chassis houses one media-converter module and features an external AC power supply and also a terminal block for DC power
More informationI-LEVEL OMX 167 Hydrostatic Level Measurement
BA 535O/xx/en/11.04 I-LEVEL OMX 167 Hydrostatic Level Measurement Operating Instructions www.omni-site.net I-LEVEL OMX 167 2 Omni-site.net I-LEVEL OMX 167 Table of contents Table of contents 1 Safety instructions.................
More informationUSER MANUAL. WBV412U01 AC voltage transducer
Designing, Manufacturing and Supplying WB Series Electric Isolated Sensor and Digital Electrical Transducer since 1989 USER MANUAL WBV412U01 AC voltage transducer www.wb-my.com wblch@wbdz.cn Technical
More informationOperating Instructions Differential Pressure Transducer PS27
Operating Instructions Differential Pressure Transducer PS27 halstrup-walcher GmbH Stegener Straße 10 79199 Kirchzarten/Germany Phone: +49 (0) 76 61/39 63 0 Fax: +49 (0) 76 61/39 63 99 E-mail: info@halstrup-walcher.com
More informationOperating Instructions. LSP-KONSTANTER Series 32K Laboratory Power Supply 8/10.13
Operating Instructions LSP-KONSTANTER Series 32K 3-349-285-15 Laboratory Power Supply 8/10.13 Programmable Power Supply LSP-KONSTANTER Series 32K Operating Instructions Table of Contents Safety Precautions,
More informationSX15GD2. Features. Typical Applications. Description
Datasheet -- Pressure Sensors: Measurement Type: Gage; 0 psid to 15 psid, Unamplified, "D2" DIP Representative photograph, actual product appearance may vary. Due to regional agency approval requirements,
More informationPSR-SCP- 24DC/URM4/4X1/2X2/B PSR-SPP- 24DC/URM4/4X1/2X2/B
Safety Relay as a Contact Extension Block INTERFACE Data Sheet PHOENIX CONTACT - 05/2006 Description The PSR-...- 24DC/URM4/4X1/2X2/B safety relay can be used as a contact extension block in safety circuits
More information