User s Guide OME-ET-7000 AND OME-PET-7000 SERIES. Ethernet I/O Modules

Size: px
Start display at page:

Download "User s Guide OME-ET-7000 AND OME-PET-7000 SERIES. Ethernet I/O Modules"

Transcription

1 egister Table User s Guide Shop online at omega.com info@omega.com For latest product manuals omegamanual.info OME-ET-7000 AND OME-PET-7000 SEIES Ethernet I/O Modules

2 OMEGAnet On-Line Service omega.com Internet U.S.A. ISO 9001 Certified OMEGA Engineering, Inc., One Omega Drive P.O. Box 4047, Stamford, CT USA Toll-Free TEL (203) FAX (203) U.S.A. and Canada Sales Service /1-800-TC-OMEGA Customer Service / BEST Engineering Service /1-800-USA-WHEN Servicing Asia China 1698 Yi Shan oad, Unit 102, Min Hang District Shanghai, China P..C. Hotline / Benelux Toll-Free TEL FAX Czech epublic Frystatska Karviná, Czech epublic Toll-Free TEL FAX France Toll-Free TEL FAX Servicing North America Canada 976 Bergar, Laval (Quebec) H7L 5A1, Canada Toll-Free TEL (514) FAX (514) For immediate technical or application assistance Mexico/ Latin America TEL 001 (203) FAX 001 (203) Servicing Europe Germany/ Austria Daimlerstrasse 26 D Deckenpfronn, Germany Toll-Free TEL +49 (0) FAX +49 (0) United Kingdom ISO 9001 Certified OMEGA Engineering Ltd. One Omega Drive iver Bend Technology Centre, Northbank Irlam, Manchester M44 5BD England Toll-Free TEL +44 (0) FAX +44 (0) It is the policy of OMEGA Engineering, Inc. to comply with all worldwide safety and EMC/EMI regulations that apply. OMEGA is constantly pursuing certification of its products to the European New Approach Directives. OMEGA will add the CE mark to every appropriate device upon certification. The information contained in this document is believed to be correct, but OMEGA accepts no liability for any errors it contains, and reserves the right to alter specifications without notice. WANING These products are not designed for use in, and should not be used for, human applications.

3 Table of Contents Preface... 1 About this Manual... 1 Contents in this Manual... 2 OME-ET-7002/OME-PET OME-ET-7015/OME-PET OME-ET-7017/OME-PET OME-ET /OME-PET OME-ET-7018Z/OME-PET-7018Z OME-ET-7019/OME-PET OME-ET-7019Z/OME-PET-7019Z OME-ET-7026/OME-PET OME-ET-7042/OME-PET OME-ET-7044/OME-PET OME-ET-7050/OME-PET OME-ET-7051/OME-PET OME-ET-7052/OME-PET OME-ET-7053/OME-PET OME-ET-7060/OME-PET OME-ET-7067/OME-PET Appendix A. Analog Input Type and Data Format Table B. Analog Output Type and Data Format Table... 68

4 Preface About this Manual This manual is intended to be used as a reference for users who need to communicate with the OME-ET-7000/OME-PET-7000 over a Modbus network. This manual assumes that the user has some knowledge of commissioning and programming of Modbus devices, including some knowledge of the Modbus protocol and knowledge about your OME-ET-7000/OME-PET-7000 module. This manual can be obtained from the companion CD CD\OME-ET-7000_OME-PET-7000\Document\ P. 1

5 Contents in this Manual Each chapter contains the following information for each OME-ET-7000/OME-PET-7000 module I/O Specifications Pin Assignments Wire Connections Modbus egister Table The table below describes the properties of each field in a Modbus register table. egister fields egister Point Description Data Format Attribute Factory Default Description The register addresses 1. DEX Decimal format 2. Hexadecimal format The number of the I/O point The function description for the register address The read or write range of the I/O data The access type ead only W Write only E Save to the EEPOM The factory default value after reset. The reset function can be found in the OME-ET-7000/OME-PET-7000 web page, as shown below. P. 2

6 OME-ET-7002/OME-PET-7002 I/O Specifications Pin Assignments Analog Input Input Channels Input Type Individual Channel Configuration Yes esolution Sampling ate Accuracy Zero Drift Span Drift Normal Mode Fast Mode Normal Mode Fast Mode 3 (Differential) +/-150 mv, +/-500 mv, +/-1 V, +/-5 V, +/-10 V, 0~20 ma, +/-20 ma, 4~20 ma (jumper selectable) 16-bit 12-bit Normal Mode +/-0.1% Fast Mode Overvoltage Protection Overcurrent Protection Input Impedance Voltage Current Common Mode ejection Normal Mode ejection Digital Input/Counter Input Channels 6 Type On Voltage Level Off Voltage Level 10 Samples/Sec. (Total) 60 Samples/Sec. (Total) +/-0.5% or better +/-20 uv/ C +/-25 ppm/ C 240 Vrms 50 ma max. at 110 V DC/V AC max. 2 MΩ 124 Ω 86 db Min. 100 db Wet Contact (Sink or Source) +10 V DC ~ +50 V DC +4V V DC max. Input Impedance 10 KΩ, 0.5W Counter Channels 6 Max. Count Max. Input Frequency 100 Hz Min. Pulse Width Overvoltage Protection Power elay Output Channels 3 Operating Voltage ange 4,294,967,285 (32-bit) 5 ms +50 V DC Power elay Form A (SPST N.O.) Max. Load Current 5.0 A/Channel at 25 C Operate Time elease Time Electrical Life (esistive load) Mechanical Life Intra-module Isolation, Field-to-Logic Power-on Value Safe Value 6 ms (Typical) 3 ms (Typical) VDE UL V AC 30,000ops (10 ops/minute) at 75 C 5 30 V AC 70,000ops (10 ops/minute) at 75 C VAC/30 VDC 6,000 ops VAC/30 VDC 100,000 ops. 20,000,000 ops at no load (300 ops/minute) 3750 V DC Yes, Programmable Yes, Programmable P. 3 OME-ET-7002/OME-PET-7002

7 Voltage/Current Input Selection Jumper Wire Connections Digital Input/ Counter eadback as 1 eadback as ~ +50 V DC Open or <4 V DC Sink Source emove the top case of the module. Power elay ON State eadback as 1 OFF State eadback as 0 The selection jumpers are next to the connector. efer to the table below to set the input type. elay Output Channel Vin0 ± Vin1 ± Vin2 ± Jumper J1 J2 J3 Voltage Input Current Input Tips & Warnings The jumper settings of the input type for each AI channel must correspond to the input range for each AI channel of the web interface. P. 4 OME-ET-7002/OME-PET-7002

8 Modbus egister Table Coils (0xxxx) egister Points Description Data Format Attribute Factory Default 0 Off 3 DO value /W - 1 On A2 00A4 00C2 00C4 6 Clear the DI counter value 1 Clear W - 6 Clear the DI latched value 1 Clear W - 3 Clear 1-ch historical AI max. value 1 Clear W - 3 Clear 1-ch historical AI min. value 1 Clear W E2 1 eset the I/O settings to the factory default state 1 eset W E9 1 eboot the module 1 eboot W E 1 Enable/Disable the DI latch function 0 Disable 1 Enable F Enable/Disable the DI counter function 0 Disable 1 Enable AF 1 Save the DO power-on value to the EEPOM 1 Save W/E B0 1 Save the DO safe value to the EEPOM 1 Save W/E B3 01B5 3 Enable/Disable the DO power-on value function 0 Disable 1 Enable /W Enable/Disable the DO safe value function 0 Disable 1 Enable /W Enable/Disable the AI function 0 Disable 1 Enable /W/E Set the AI sampling rate Set the AI noise filter 0 Normal mode (10 Hz, 16 bits) 1 Fast mode (60 Hz, 12 bits) 0 Frequency 60 Hz 1 Frequency 50 Hz Save preset values for the DI counter to the EEPOM 1 Save W/E Set the AI data format 0 Hexadecimal format 1 Engineering unit eset the AI calibration to the factory settings 1 eset W A 1 Clear all historical AI max. values 1 Clear W B 1 Clear all historical AI min. values 1 Clear W C 027E 3 Enable/Disable the AI high alarm function 0 Disable 1 Enable C 029E 3 Enable/Disable the AI low alarm function 0 Disable 1 Enable BC 02BE 3 Set the AI high alarm mode 0 Momentary mode 1 Latching mode P. 5 OME-ET-7002/OME-PET-7002

9 DC 02DE 3 Set the AI low alarm mode 0 Momentary mode 1 Latching mode FC 02FE 3 Clear the AI high alarm status 1 Clear W C 031E 3 Clear the AI low alarm status 1 Clear W E 1 Enable/Disable the AI calibration 0 Disable 1 Enable /W F 1 Zero calibration for the channel 0 1 Set W Span calibration for the channel 0 1 Set W - Discrete Inputs (1xxxx) egister Points Description Data Format Attribute 0 Off 6 DI value 1 On ead DI high latch status 0 Normal 1 Latched ead DI low latch status 0 Normal 1 Latched E0 00E2 3 ead AI high alarm status. When the AI value is higher than the high alarm value, the status becomes 1. 0 Normal 1 Alarmed ead AI low alarm status. When the AI value is lower than the high alarm value, the status becomes 1. 0 Normal 1 Alarmed Input egister (3xxxx) egister Points No. Per Point 3 1 AI value Description Data Format Attribute B 6 2 DI counter value 0 to EC 00EE 3 1 AI historical max. value C 010E 3 1 AI historical min. value C 1 1 Number of the DI channel Number of the DO channel Number of the AI channel E 1 1 OS image version 0x123 means version F 1 1 Firmware version 0x123 means version I/O version 0x123 means version Communication state of the pair-connection 0 Normal <0 Failed P. 6 OME-ET-7002/OME-PET-7002

10 Holding egister (4xxxx) egister C8 00D3 Points No. Per Point 6 2 Description Data Format Attribute Factory Value Set a preset value for the DI Counter Any values updated based on the Modbus communication will not take immediate effect and not be saved to EEPOM until the register (00630) is changed by a write operation. 0 to /W F 1 1 Set the module identification (Modbus NetID) 1 to 255 /W/E A 3 1 Set the AI high alarm value /W/E (0x7FFF) A 3 1 Set the AI low alarm value /W/E (0x8000) 0x07 4~20 ma 0x08 +/-10 V AB 01AD 3 1 Set the AI range 0x09 +/-5 V 0x0A +/-1 V 0x0B +/-500 mv 0x0C +/-150 mv 0x0D +/-20 ma 0x1A 0~20 ma /W/E 0x B 1 1 ead the module reset status C 1 1 ead the boot count of the module The factory default value is 0 when the settings are set to the factory default values D 1 1 Set the Host WDT timeout (unit second) E 1 1 ead the WDT event count The initial value is 0 when the module is reset, and is increased when the WDT even happens. 1 Power-on 2 Module Watchdog 3 Software eset Command - 1 to Disable the Host WDT 5 to Enable the Host WDT 0 to F 1 1 ead the module name 0x P. 7 OME-ET-7002/OME-PET-7002

11 OME-ET-7015/OME-PET-7015 I/O Specifications Pin Assignments TD Input Input Channels Sensor Type Wire Connection Individual Channel Configuration esolution Sampling ate 7 (Differential) Pt100, Pt1000, Ni120, Cu100, Cu1000 2/3 wire Yes 16-bit Accuracy +/-0.05% Zero Drift Span Drift Common Mode ejection Normal Mode ejection Input Impedance Open Wire Detection 3-wire TD Lead esistance Elimination 12 Samples/Sec. (Total) +/-0.5 μv/ C +/-20 μv/ C 150 db 100 db >1 MΩ Yes Yes Wire Connections TD Input CH0 1, 2, 5 and 6 CH3 and CH4 2-wire of TD 3-wire of TD Tips & Warnings Use AWG wire for signal connections Strip the wire to a length of 7±0.5mm Use a crimp terminal for wiring Avoid high-voltage cables and power equipment as much as possible Use shielded wire and connect the shielding to the Ax terminal of the channel P. 8 OME-ET-7015/OME-PET-7015

12 Modbus egister Table Coils (0xxxx) egister Points Description Data Format Attribute Factory Value E2 1 eset the I/O settings to the factory default state 1 eset W E9 1 eboot the module 1 eboot W Enable/Disable the AI function 0 Disable 1 Enable /W/E Set the AI noise filter Set the AI data format 0 Frequency 60 Hz 1 Frequency 50 Hz 0 Hexadecimal format 1 Engineering unit eset the AI calibration to the factory settings 1 eset W E 1 Enable/Disable the AI calibration 0 Disable 1 Enable /W F 1 Zero calibration for the channel 0 1 Set W Span calibration for the channel 0 1 Set W Zero calibration for the channel 1 1 Set W Span calibration for the channel 1 1 Set W Zero calibration for the channel 2 1 Set W Span calibration for the channel 2 1 Set W Zero calibration for the channel 3 1 Set W Span calibration for the channel 3 1 Set W Zero calibration for the channel 4 1 Set W Span calibration for the channel 4 1 Set W Zero calibration for the channel 5 1 Set W A 1 Span calibration for the channel 5 1 Set W B 1 Zero calibration for the channel 6 1 Set W C 1 Span calibration for the channel 6 1 Set W - Input egister (3xxxx) egister Points No. Per Point 7 1 AI value Description Data Format Attribute Number of the AI channel E 1 1 OS image version 0x123 means version F 1 1 Firmware version 0x123 means version I/O version 0x123 means version P. 9 OME-ET-7015/OME-PET-7015

13 Holding egister (4xxxx) egister 006E 0074 Points No. Per Point Description Data Format Attribute Factory Value 7 1 Set the AI temperature offset value -128 to E Set the AI resistance offset value 0 to F 1 1 Set the module identification (Modbus NetID) AB 01B1 7 1 Set the AI range 1 to 255 /W/E 1 0x20 Platinum 100, α= , -100 C ~ 100 C 0x21 Platinum 100, α= , 0 C ~ 100 C 0x22 Platinum 100, α= , 0 C ~ 200 C 0x23 Platinum 100, α= , 0 C ~ 600 C 0x24 Platinum 100, α= , -100 C ~ 100 C 0x25 Platinum 100, α= , 0 C ~ 100 C 0x26 Platinum 100, α= , 0 C ~ 200 C 0x27 Platinum 100, α= , 0 C ~ 600 C 0x28 Nickel 120, -80 C ~ 100 C 0x29 Nickel 120, 0 C ~ 100 C 0x2A Platinum 1000, α= , -200 C ~ 600 C x20 0x2B Cu 0 C, α= , -20 C ~ 150 C 0x2C Cu 25 C, α= , 0 C ~ 200 C 0x2D Cu 0 C, α= , -20 C ~ 150 C 0x2E Platinum 100, α= , -200 C ~ 200 C 0x2F Platinum 100, α= , -200 C ~ 200 C 0x80 Platinum 100, α= , -200 C ~ 600 C 0x81 Platinum 100, α= , -200 C ~ 600 C 0x82 Cu 0 C, -50 C ~ 150 C 0x83 Nickel 100, -60 C ~ 180 C B 1 1 ead the module reset status 1 Power-on 2 Module Watchdog 3 Software eset Command C D 1 1 ead the boot count of the module The factory default value is 0 when the settings are set to the factory default values. Set the Host WDT timeout (unit second) 1 to Disable the Host WDT 5 to Enable the Host WDT E 1 1 ead the WDT event count The initial value is 0 when the module is reset, and is increased when the WDT even happens. 0 to F 1 1 ead the module name 0x P. 10 OME-ET-7015/OME-PET-7015

14 OME-ET-7017/OME-PET-7017 I/O Specifications Pin Assignments Analog Input Input Channels Input Type Individual Channel Configuration Yes esolution Sampling ate Accuracy Zero Drift Span Drift Normal Mode Fast Mode Normal Mode Fast Mode 8 (Differential) +/-150 mv, +/-500 mv, +/-1 V, +/-5 V, +/-10 V, 0~20 ma, +/-20 ma, 4~20 ma (jumper selectable) 16-bit 12-bit Normal Mode +/-0.1% Fast Mode Overvoltage Protection Input Impedance Voltage Current Common Mode ejection Normal Mode ejection Digital Output Output Channels 4 Type Max. Load Current Load Voltage Overvoltage Protection Overload Protection Short-circuit Protection Power-on Value Safe Value 10 Samples/Sec. (Total) 60 Samples/Sec. (Total) +/-0.5% or better +/-20 uv/ C +/-25 ppm/ C 240 Vrms 2 MΩ 125 Ω 86 db Min. 100 db Isolated Open Collector (Sink) 700 ma/channel 5 V DC~50 V DC 60 V DC 1.4 A Yes Yes, Programmable Yes, Programmable P. 11 OME-ET-7017/OME-PET-7017

15 Voltage/Current Input Selection Jumper Settings Channel Vin6 ± Vin5 ± Vin4 ± Vin3 ± Vin2 ± Vin1 ± Vin0 ± Jumper J7 J6 J5 J4 J3 J2 J1 The selection jumpers are next to the connector. efer to the table below to set the input type. emove the top case of the module. Channel Vin7 ± Jumper J8 Voltage Input Current Input Tips & Warnings The jumper settings of the input type for each AI channel must correspond to the input range for each AI channel of the web interface. Wire Connections Digital Output ON State eadback as 1 OFF State eadback as 0 Open Collector (Sink) P. 12 OME-ET-7017/OME-PET-7017

16 Modbus egister Table Coils (0xxxx) egister Points Description Data Format Attribute Factory Value 4 DO value 0 Off 1 On /W A2 00A9 00C2 00C9 8 Clear 1-ch historical AI max. value 1 Clear W - 8 Clear 1-ch historical AI min. value 1 Clear W E2 1 eset the I/O settings to the factory default state 1 eset W E9 1 eboot the module 1 eboot W AF 1 Save the DO power-on value to the EEPOM 1 Save W/E B0 1 Save the DO safe value to the EEPOM 1 Save W/E B3 01B6 4 Enable/Disable the DO power-on value function 0 Disable 1 Enable /W Enable/Disable the DO safe value function 0 Disable 1 Enable /W A 8 Enable/Disable the AI function 0 Disable 1 Enable /W/E Set the AI sampling rate Set the AI noise filter Set the AI data format 0 Normal mode (10 Hz, 16 bits) 1 Fast mode (60 Hz, 12 bits) 0 Frequency 60 Hz 1 Frequency 50 Hz 0 Hexadecimal format 1 Engineering unit eset the AI calibration to the factory settings 1 eset W A 1 Clear all historical AI max. values 1 Clear W B 1 Clear all historical AI min. values 1 Clear W C Enable/Disable the AI high alarm function 0 Disable 1 Enable C 02A3 8 Enable/Disable the AI low alarm function 0 Disable 1 Enable BC 02C3 8 Set the AI high alarm mode 0 Momentary mode 1 Latching mode DC 02E3 8 Set the AI low alarm mode 0 Momentary mode 1 Latching mode FC C Clear the AI high alarm status 1 Clear W - 8 Clear the AI low alarm status 1 Clear W - P. 13 OME-ET-7017/OME-PET-7017

17 E 1 Enable/Disable the AI calibration 0 Disable 1 Enable /W F 1 Zero calibration for the channel 0 1 Set W Span calibration for the channel 0 1 Set W - Discrete Inputs (1xxxx) egister 00E0 00E7 Points Description Data Format Attribute ead AI high alarm status. 0 Normal 8 When the AI value is higher than the high alarm value, the status becomes 1. 1 Alarmed ead AI low alarm status. When the AI value is lower than the high alarm value, the status becomes 1. 0 Normal 1 Alarmed Input egister (3xxxx) egister Points No. Per Point 8 1 AI value Description Data Format Attribute EC 00F3 8 1 AI historical max. value C AI historical min. value Number of the DO channel Number of the AI channel E 1 1 OS image version 0x123 means version F 1 1 Firmware version 0x123 means version I/O version 0x123 means version Communication state of the pair-connection 0 Normal <0 Failed P. 14 OME-ET-7017/OME-PET-7017

18 Holding egister (4xxxx) egister Points No. Per Point Description Data Format Attribute Factory Value F 1 1 Set the module identification (Modbus NetID) 1 to 255 /W/E F 8 1 Set the AI high alarm value /W/E (0x7FFF) F 8 1 Set the AI low alarm value /W/E (0x8000) 0x07 4 ~ 20 ma 0x08 +/-10 V AB 01B2 8 1 Set the AI range 0x09 +/-5 V 0x0A +/-1 V 0x0B +/-500 mv 0x0C +/-150 mv 0x0D +/-20 ma 0x1A 0~20 ma /W/E 0x B 1 1 ead the module reset status 1 Power-on 2 Module Watchdog 3 Software eset Command C 1 1 ead the boot count of the module The factory default value is 0 when the settings are set to the factory default values D 1 1 Set the Host WDT timeout (unit second) 1 to Disable the Host WDT 5 to Enable the Host WDT E 1 1 ead the WDT event count The initial value is 0 when the module is reset, and is increased when the WDT even happens. 0 to F 1 1 ead the module name 0x P. 15 OME-ET-7017/OME-PET-7017

19 OME-ET /OME-PET I/O Specifications Pin Assignments Analog Input Input Channels Input Type Individual Channel Configuration Yes esolution Sampling ate Accuracy Zero Drift Span Drift Overvoltage Protection Input Impedance Normal Mode Fast Mode Normal Mode Fast Mode 10 differential or 20 single-ended (Note) (software selectable) +/-150 mv, +/-500 mv, +/-1 V, +/-5 V, +/-10 V, 0~20 ma, +/-20 ma, 4~20 ma (jumper selectable) 16-bit 12-bit Normal Mode +/-0.1% Fast Mode Differential Single-ended Voltage Current Common Mode ejection Normal Mode ejection 10 Samples/Sec. (Total) 60 Samples/Sec. (Total) +/-0.5% or better +/-20 uv/ C +/-25 ppm/ C 240 Vrms 150 Vrms 2 MΩ (Differential), 1 MΩ (Single-ended) 125 Ω 86 db Min. 100 db Note Differential mode can be used for voltage input and current input. Single-ended mode can be used for voltage input only P. 16 OME-ET /OME-PET

20 Voltage/Current Input Selection Jumper Settings Channel Vin6 ± Vin5 ± Vin4 ± Vin3 ± Vin2 ± Vin1 ± Vin0 ± Jumper J7 J6 J5 J4 J3 J2 J1 The selection jumpers are next to the connector. efer to the table below to set the input type. emove the top case of the module. Channel Vin7 ± Vin8 ± Vin9 ± Jumper J8 J9 J10 Voltage Input (Differential Mode) Voltage Input (Single-ended Mode) Current Input Tips & Warnings The jumper settings of the input type for each AI channel must correspond to the input range for each AI channel of the web interface. P. 17 OME-ET /OME-PET

21 Modbus egister Table Coils (0xxxx) egister 00A2 00B5 Points Description Data Format Attribute Factory Value 20 Clear 1-ch historical AI max. value 1 Clear W C2 00D5 20 Clear 1-ch historical AI min. value 1 Clear W E2 1 eset the I/O settings to the factory default state 1 eset W E9 1 eboot the module 1 eboot W Enable/Disable the AI function 0 Disable 1 Enable /W/E Set the AI sampling rate Set the AI noise filter Set the AI data format 0 Normal mode (10 Hz, 16 bits) 1 Fast mode (60 Hz, 12 bits) 0 Frequency 60 Hz 1 Frequency 50 Hz 0 Hexadecimal format 1 Engineering unit eset the AI calibration to the factory settings 1 eset W A 1 Clear all historical AI max. values 1 Clear W B 1 Clear all historical AI min. values 1 Clear W C 028F 20 Enable/Disable the AI high alarm function 0 Disable 1 Enable C 02AF 20 Enable/Disable the AI low alarm function 0 Disable 1 Enable BC 02CF 20 Set the AI high alarm mode 0 Momentary mode 1 Latching mode DC 02EF 20 Set the AI low alarm mode 0 Momentary mode 1 Latching mode FC 030F 031C 032F 20 Clear the AI high alarm status 1 Clear W - 20 Clear the AI low alarm status 1 Clear W E 1 Enable/Disable the AI calibration 0 Disable 1 Enable /W F 1 Zero calibration for the channel 0 1 Set W Span calibration for the channel 0 1 Set W Set the AI mode 0 Differential 1 Single-ended P. 18 OME-ET /OME-PET

22 Discrete Inputs (1xxxx) egister 00E0 00F3 Points Description Data Format Attribute ead AI high alarm status. 0 Normal 20 When the AI value is higher than the high alarm value, the status becomes 1. 1 Alarmed ead AI low alarm status. When the AI value is lower than the high alarm value, the status becomes 1. 0 Normal 1 Alarmed Input egister (3xxxx) egister Points No. Per Point 20 1 AI value Description Data Format Attribute EC 00FF 20 1 AI historical max. value C 011F 20 1 AI historical min. value Number of the AI channel 10/ E 1 1 OS image version 0x123 means version F 1 1 Firmware version 0x123 means version I/O version 0x123 means version P. 19 OME-ET /OME-PET

23 Holding egister (4xxxx) egister Points No. Per Point Description Data Format Attribute Factory Value F 1 1 Set the module identification (Modbus NetID) 1 to 255 /W/E B 20 1 Set the AI high alarm value /W/E (0x7FFF) B 20 1 Set the AI low alarm value /W/E (0x8000) 0x07 4 ~ 20 ma 0x08 +/-10 V AB 01BF 20 1 Set the AI range 0x09 +/-5 V 0x0A +/-1 V 0x0B +/-500 mv 0x0C +/-150 mv 0x0D +/-20 ma 0x1A 0~20 ma /W/E 0x B 1 1 ead the module reset status 1 Power-on 2 Module Watchdog 3 Software eset Command C 1 1 ead the boot count of the module The factory default value is 0 when the settings are set to the factory default values D 1 1 Set the Host WDT timeout (unit second) 1 to Disable the Host WDT 5 to Enable the Host WDT E 1 1 ead the WDT event count The initial value is 0 when the module is reset, and is increased when the WDT even happens. 0 to F 1 1 ead the module name 0x P. 20 OME-ET /OME-PET

24 OME-ET-7018Z/OME-PET-7018Z I/O Specifications Analog Input Input Channels Input Type Individual Channel Configuration esolution Sampling ate Accuracy Zero Drift Span Drift Overvoltage Protection Input Impedance Common Mode ejection Normal Mode ejection Temperature Outputs Consistency Stable Temperature Output In The Field Open Wire Detection Digital Output Output Channels 6 Type Max. Load Current Load Voltage Overvoltage Protection Overload Protection Short-circuit Protection Power-on Value Safe Value Pin Assignments 10 (Differential) +/-15 mv, +/-50 mv, +/-100 mv, +/-500 mv, +/-1 V, +/-2.5V 0~20 ma, +/-20 ma, 4~20 ma (equires Optional External 125Ω esistor) Thermocouple (J, K, T, E,, S, B, N, C, L, M and LDIN43710) Yes 16-bit 10 Samples/Sec. (Total) +/-0.1% or better +/-0.5 uv/ C +/-25 ppm/ C 240 Vrms >300 KΩ 150 db Min. 100 db Yes Yes Yes Isolated Open Collector (Sink) 700 ma/channel 5 V DC~50 V DC 60 V DC 1.4 A Yes Yes, Programmable Yes, Programmable P. 21 OME-ET-7018Z/OME-PET-7018Z

25 Wire Connections Voltage Input Thermocouple Input Current Input Note that an optional external 125 Ω resistor is required when connecting to a current source, Digital Output ON State eadback as 1 OFF State eadback as 0 Open Collector (Sink) P. 22 OME-ET-7018Z/OME-PET-7018Z

26 Modbus egister Table Coils (0xxxx) egister Points Description Data Format Attribute Factory Value 6 DO value 0 Off 1 On /W A2 00AB 00C2 00CB 10 Clear 1-ch historical AI max. value 1 Clear W - 10 Clear 1-ch historical AI min. value 1 Clear W E2 1 eset the I/O settings to the factory default state 1 eset W E9 1 eboot the module 1 eboot W AF 1 Save the DO power-on value to the EEPOM 1 Save W/E B0 1 Save the DO safe value to the EEPOM 1 Save W/E B3 01B8 6 Enable/Disable the DO power-on value function 0 Disable 1 Enable /W Enable/Disable the DO safe value function 0 Disable 1 Enable /W C 10 Enable/Disable the AI function 0 Disable 1 Enable /W/E Enable/Disable the CJC function Set the AI noise filter Set the AI data format 0 Disable 1 Enable 0 Frequency 60 Hz 1 Frequency 50 Hz 0 Hexadecimal format 1 Engineering unit /W/E eset the AI calibration to the factory settings 1 eset W A 1 Clear all historical AI max. values 1 Clear W B 1 Clear all historical AI min. values 1 Clear W C Enable/Disable the AI high alarm function 0 Disable 1 Enable C 02A5 10 Enable/Disable the AI low alarm function 0 Disable 1 Enable BC 02C5 10 Set the AI high alarm mode 0 Momentary mode 1 Latching mode DC 02E5 10 Set the AI low alarm mode 0 Momentary mode 1 Latching mode P FC C Clear the AI high alarm status 1 Clear W - 10 Clear the AI low alarm status 1 Clear W - OME-ET-7018Z/OME-PET-7018Z

27 E 1 Enable/Disable the AI calibration 0 Disable 1 Enable /W F 1 Zero calibration for the channel 0 1 Set W Span calibration for the channel 0 1 Set W - Discrete Inputs (1xxxx) egister 00E0 00E9 Points Description Data Format Attribute ead AI high alarm status. 0 Normal 10 When the AI value is higher than the high alarm value, the status becomes 1. 1 Alarmed ead AI low alarm status. When the AI value is lower than the high alarm value, the status becomes 1. 0 Normal 1 Alarmed Input egister (3xxxx) egister Points No. Per Point Description Data Format Attribute AI value F 1 1 CJC value EC 00F AI historical max. value C AI historical min. value Number of the DO channel Number of the AI channel E 1 1 OS image version 0x123 means version F 1 1 Firmware version 0x123 means version I/O version 0x123 means version Communication state of the pair-connection 0 Normal <0 Failed P. 24 OME-ET-7018Z/OME-PET-7018Z

28 Holding egister (4xxxx) egister Points No. Per Point Description Data Format Attribute Factory Value F 1 1 Set the module identification (Modbus NetID) 1 to 255 /W/E Set the AI high alarm value /W/E (0x7FFF) Set the AI low alarm value /W/E (0x8000) 0x00 +/-15 mv 0x01 +/-50 mv 0x02 +/-100 mv 0x03 +/-500 mv 0x04 +/-1 V 0x05 +/-2.5 V 0x06 +/-20 ma 0x07 4 ~ 20 ma 0x0E Type J, -210 C ~ 760 C AB 01B Set the AI range 0x0F Type K, -270 C ~ 1372 C 0x10 Type T, -270 C ~ 400 C 0x11 Type E, -270 C ~ 1000 C 0x12 Type, 0 C ~ 1768 C 0x13 Type S, 0 C ~ 1768 C 0x14 Type B, 0 C ~ 1820 C 0x15 Type N, -270 C ~ 1300 C 0x16 Type C, 0 C ~ 2320 C 0x17 Type L, -200 C ~ 800 C 0x18 Type M, -200 C ~ 100 C 0x19 Type L DIN43710, -200 C ~ 900 C 0x1A 0 ~ 20 ma /W/E 0x EB 01F Set the CJC Offset for the single channel to B 1 1 Set the CJC Offset for all channels to B 1 1 ead the module reset status 1 Power-on 2 Module Watchdog 3 Software eset Command C 1 1 ead the boot count of the module The factory default value is 0 when the settings are set to the factory default values D 1 1 Set the Host WDT timeout (unit second) 1 to Disable the Host WDT 5 to Enable the Host WDT E 1 1 ead the WDT event count The initial value is 0 when the module is reset, and is increased when the WDT even happens. 0 to F 1 1 ead the module name 0x D 1 1 Set the CJC operation status 0 Stop 1 Start 2 ead once /W/E 1 P. 25 OME-ET-7018Z/OME-PET-7018Z

29 OME-ET-7019/OME-PET-7019 I/O Specifications Pin Assignments Analog Input Input Channels Input Type Individual Channel Configuration Yes esolution Sampling ate Accuracy Zero Drift Span Drift Overvoltage Protection Input Impedance Voltage Current Common Mode ejection Normal Mode ejection Open Wire Detection 8 (Differential) +/-15 mv, +/-50 mv, +/-100 mv, +/-150 mv, +/-500 mv, +/-1 V, +/-5 V, +/-10 V, 0~20 ma, +/-20 ma, 4~20 ma Thermocouple (J, K, T, E,, S, B, N, C, L, M and LDIN43710) 16-bit 10 Samples/Sec. (Total) +/-0.1% or better +/-10 uv/ C +/-25 ppm/ C 240 Vrms >1 MΩ 125 Ω 86 db Min. 100 db Yes Digital Output Output Channels 4 Type Max. Load Current Load Voltage Overvoltage Protection Overload Protection Short-circuit Protection Power-on Value Safe Value Isolated Open Collector (Sink) 700 ma/channel 5 V DC~50 V DC 60 V DC 1.4 A Yes Yes, Programmable Yes, Programmable P. 26 OME-ET-7019/OME-PET-7019

30 Voltage/Current Input Selection Jumper Settings Channel Vin6 ± Vin5 ± Vin4 ± Vin3 ± Vin2 ± Vin1 ± Vin0 ± Jumper J7 J6 J5 J4 J3 J2 J1 The selection jumpers are next to the connector. efer to the table below to set the input type. emove the top case of the module. Channel Vin7 ± Jumper J8 Voltage Input Thermocouple Input Current Input Tips & Warnings The jumper settings of the input type for each AI channel must correspond to the input range for each AI channel of the web interface. Wire Connections Digital Output ON State eadback as 1 OFF State eadback as 0 Open Collector (Sink) P. 27 OME-ET-7019/OME-PET-7019

31 Modbus egister Table Coils (0xxxx) egister Points Description Data Format Attribute Factory Value 0 Off 4 DO value /W - 1 On A2 00A9 00C2 00C9 8 Clear 1-ch historical AI max. value 1 Clear W - 8 Clear 1-ch historical AI min. value 1 Clear W E2 1 eset the I/O settings to the factory default state 1 eset W E9 1 eboot the module 1 eboot W AF 1 Save the DO power-on value to the EEPOM 1 Save W/E B0 1 Save the DO safe value to the EEPOM 1 Save W/E B3 01B6 4 Enable/Disable the DO power-on value function 0 Disable 1 Enable /W Enable/Disable the DO safe value function 0 Disable 1 Enable /W A 8 Enable/Disable the AI function 0 Disable 1 Enable /W/E Enable/Disable the CJC function Set the AI noise filter Set the AI data format 0 Disable 1 Enable 0 Frequency 60 Hz 1 Frequency 50 Hz 0 Hexadecimal format 1 Engineering unit /W/E eset the AI calibration to the factory settings 1 eset W A 1 Clear all historical AI max. values 1 Clear W B 1 Clear all historical AI min. values 1 Clear W C Enable/Disable the AI high alarm function 0 Disable 1 Enable C 02A3 8 Enable/Disable the AI low alarm function 0 Disable 1 Enable BC 02C3 8 Set the AI high alarm mode 0 Momentary mode 1 Latching mode DC 02E3 8 Set the AI low alarm mode 0 Momentary mode 1 Latching mode FC C Clear the AI high alarm status 1 Clear W - 8 Clear the AI low alarm status 1 Clear W - P. 28 OME-ET-7019/OME-PET-7019

32 E 1 Enable/Disable the AI calibration 0 Disable 1 Enable /W F 1 Zero calibration for channel 0 1 Active W Span calibration for channel 0 1 Active W - Discrete Inputs (1xxxx) egister 00E0 00E7 Points Description Data Format Attribute ead AI high alarm status. 0 Normal 8 When the AI value is higher than the high alarm value, the status becomes 1. 1 Alarmed ead AI low alarm status. When the AI value is lower than the high alarm value, the status becomes 1. 0 Normal 1 Alarmed Input egister (3xxxx) egister Points No. Per Point 8 1 AI value Description Data Format Attribute F 1 1 CJC value EC 00F3 8 1 AI historical max. value C AI historical min. value Number of the DO channel Number of the AI channel E 1 1 OS image version 0x123 means version F 1 1 Firmware version 0x123 means version I/O version 0x123 means version Communication state of the pair-connection 0 Normal <0 Failed P. 29 OME-ET-7019/OME-PET-7019

33 Holding egister (4xxxx) egister Points No. Per Point Description Data Format Attribute Factory Value F 1 1 Set the module identification (Modbus NetID) 1 to 255 /W/E F 8 1 Set the AI high alarm value /W/E (0x7FFF) F 8 1 Set the AI low alarm value /W/E (0x8000) 0x00 +/-15 mv 0x01 +/-50 mv 0x02 +/-100 mv 0x03 +/-500 mv 0x04 +/-1 V 0x05 +/-2.5 V 0x06 +/-20 ma 0x07 4 ~ 20 ma 0x0E Type J, -210 C ~ 760 C AB 01B2 8 1 Set the AI range 0x0F Type K, -270 C ~ 1372 C 0x10 Type T, -270 C ~ 400 C 0x11 Type E, -270 C ~ 1000 C 0x12 Type, 0 C ~ 1768 C 0x13 Type S, 0 C ~ 1768 C 0x14 Type B, 0 C ~ 1820 C 0x15 Type N, -270 C ~ 1300 C 0x16 Type C, 0 C ~ 2320 C 0x17 Type L, -200 C ~ 800 C 0x18 Type M, -200 C ~ 100 C 0x19 Type L DIN43710, -200 C ~ 900 C 0x1A 0 ~ 20 ma /W/E 0x EB 01F2 8 1 Set the CJC Offset for the single channel to B 1 1 Set the CJC Offset for all channels to B 1 1 ead the module reset status 1 Power-on 2 Module Watchdog 3 Software eset Command C 1 1 ead the boot count of the module The factory default value is 0 when the settings are set to the factory default values D 1 1 Set the Host WDT timeout (unit second) 1 to Disable the Host WDT 5 to Enable the Host WDT E 1 1 ead the WDT event count The initial value is 0 when the module is reset, and is increased when the WDT even happens. 0 to F 1 1 ead the module name 0x D 1 1 Set the CJC operation status 0 Stop 1 Start 2 ead once /W/E 1 P. 30 OME-ET-7019/OME-PET-7019

34 OME-ET-7019Z/OME-PET-7019Z I/O Specifications Analog Input Input Channels Input Type Individual Channel Configuration esolution Sampling ate Accuracy Zero Drift Span Drift Overvoltage Protection Input Impedance Common Mode ejection Normal Mode ejection Temperature Outputs Consistency Stable Temperature Output In The Field Open Wire Detection Digital Output Output Channels 6 Type Max. Load Current Load Voltage Overvoltage Protection Overload Protection Short-circuit Protection Power-on Value Safe Value Pin Assignments 10 (Differential) +/-15 mv, +/-50 mv, +/-100 mv, +/-150 mv, +/-500 mv, +/-1 V, +/-2.5V, +/-5 V, +/-10 V 0~20 ma, +/-20 ma, 4~20 ma (Jumper Selectable) Thermocouple (J, K, T, E,, S, B, N, C, L, M and LDIN43710) Yes 16-bit 10 Samples/Sec. (Total) +/-0.1% or better +/-0.5 uv/ C +/-25 ppm/ C 240 Vrms >300 KΩ 86 db Min. 100 db Yes Yes Yes Isolated Open Collector (Sink) 700 ma/channel 5 V DC~50 V DC 60 V DC 1.4 A Yes Yes, Programmable Yes, Programmable P. 31 OME-ET-7019Z/OME-PET-7019Z

35 Voltage/Current Input Selection Jumper Settings Channel CH0 ± CH1 ± CH2± CH3± CH4± CH5± CH6± CH7± Jumper J1 J2 J3 J4 J5 J6 J7 J8 Channel CH8 ± CH9 ± Jumper J9 J10 emove the top case of the module. The selection jumpers are next to the connector. efer to the table below to set the input type. Voltage Input Thermocouple Input Current Input Tips & Warnings The jumper settings of the input type for each AI channel must correspond to the input range for each AI channel of the web interface. P. 32 OME-ET-7019Z/OME-PET-7019Z

36 Wire Connections Digital Output ON State eadback as 1 OFF State eadback as 0 Open Collector (Sink) P. 33 OME-ET-7019Z/OME-PET-7019Z

37 Modbus egister Table Coils (0xxxx) egister Points Description Data Format Attribute Factory Value 0 Off 6 DO value /W - 1 On A2 00AB 00C2 00CB 10 Clear 1-ch historical AI max. value 1 Clear W - 10 Clear 1-ch historical AI min. value 1 Clear W E2 1 eset the I/O settings to the factory default state 1 eset W E9 1 eboot the module 1 eboot W AF 1 Save the DO power-on value to the EEPOM 1 Save W/E B0 1 Save the DO safe value to the EEPOM 1 Save W/E B3 01B8 6 Enable/Disable the DO power-on value function 0 Disable 1 Enable /W Enable/Disable the DO safe value function 0 Disable 1 Enable /W C 10 Enable/Disable the AI function 0 Disable 1 Enable /W/E Enable/Disable the CJC function Set the AI noise filter Set the AI data format 0 Disable 1 Enable 0 Frequency 60 Hz 1 Frequency 50 Hz 0 Hexadecimal format 1 Engineering unit /W/E eset the AI calibration to the factory settings 1 eset W A 1 Clear all historical AI max. values 1 Clear W B 1 Clear all historical AI min. values 1 Clear W C Enable/Disable the AI high alarm function 0 Disable 1 Enable C 02A5 10 Enable/Disable the AI low alarm function 0 Disable 1 Enable BC 02C5 10 Set the AI high alarm mode 0 Momentary mode 1 Latching mode DC 02E5 10 Set the AI low alarm mode 0 Momentary mode 1 Latching mode P FC C Clear the AI high alarm status 1 Clear W - 10 Clear the AI low alarm status 1 Clear W - OME-ET-7019Z/OME-PET-7019Z

38 E 1 Enable/Disable the AI calibration 0 Disable 1 Enable /W F 1 Zero calibration for the channel 0 1 Set W Span calibration for the channel 0 1 Set W - Discrete Inputs (1xxxx) egister 00E0 00E9 Points Description Data Format Attribute ead AI high alarm status. 0 Normal 10 When the AI value is higher than the high alarm value, the status becomes 1. 1 Alarmed ead AI low alarm status. When the AI value is lower than the high alarm value, the status becomes 1. 0 Normal 1 Alarmed Input egister (3xxxx) egister Points No. Per Point 10 1 AI value Description Data Format Attribute F 1 1 CJC value EC 00F AI historical max. value C AI historical min. value Number of the DO channel Number of the AI channel E 1 1 OS image version 0x123 means version F 1 1 Firmware version 0x123 means version I/O version 0x123 means version Communication state of the pair-connection 0 Normal <0 Failed P. 35 OME-ET-7019Z/OME-PET-7019Z

39 Holding egister (4xxxx) egister Points No. Per Point Description Data Format Attribute Factory Value F 1 1 Set the module identification (Modbus NetID) 1 to 255 /W/E Set the AI high alarm value /W/E (0x7FFF) Set the AI low alarm value /W/E (0x8000) 0x00 +/-15 mv 0x01 +/-50 mv 0x02 +/-100 mv 0x03 +/-500 mv 0x04 +/-1 V 0x05 +/-2.5 V 0x06 +/-20 ma 0x07 4 ~ 20 ma 0x08 +/-10 V 0x09 +/-5 V 0x0A +/-1V 0x0B +/-500 mv AB 01B Set the AI range 0x0C +/-150 mv 0x0D +/-20 ma 0x0E Type J, -210 C ~ 760 C 0x0F Type K, -270 C ~ 1372 C 0x10 Type T, -270 C ~ 400 C 0x11 Type E, -270 C ~ 1000 C 0x12 Type, 0 C ~ 1768 C 0x13 Type S, 0 C ~ 1768 C 0x14 Type B, 0 C ~ 1820 C 0x15 Type N, -270 C ~ 1300 C 0x16 Type C, 0 C ~ 2320 C 0x17 Type L, -200 C ~ 800 C 0x18 Type M, -200 C ~ 100 C 0x19 Type L DIN43710, -200 C ~ 900 C 0x1A 0 ~ 20 ma /W/E 0x EB 01F Set the CJC Offset for the single channel to B 1 1 Set the CJC Offset for all channels to B 1 1 ead the module reset status 1 Power-on 2 Module Watchdog 3 Software eset Command C 1 1 ead the boot count of the module The factory default value is 0 when the settings are set to the factory default values D 1 1 Set the Host WDT timeout (unit second) 1 to Disable the Host WDT 5 to Enable the Host WDT E 1 1 ead the WDT event count The initial value is 0 when the module is reset, and is increased when the WDT even happens. 0 to F 1 1 ead the module name 0x D 1 1 Set the CJC operation status 0 Stop 1 Start 2 ead once /W/E 1 P. 36 OME-ET-7019Z/OME-PET-7019Z

40 OME-ET-7026/OME-PET-7026 I/O Specifications Pin Assignments Analog Input Input Channels Input Type Individual Channel Configuration Yes esolution Sampling ate Accuracy Zero Drift Span Drift Normal Mode Fast Mode Normal Mode Fast Mode 6 (Differential) +/-500 mv, +/-1 V, +/-5 V, +/-10 V, 0~20 ma, +/-20 ma, 4~20 ma (jumper selectable) 16-bit 12-bit Normal Mode +/-0.1% Fast Mode 10 Samples/Sec. (Total) 60 Samples/Sec. (Total) +/-0.5% or better +/-20 uv/ C or better +/-25 ppm/ C Overvoltage Protection 240 Vrms Input Impedance Common Mode ejection Normal Mode ejection Analog Output Output Channels 2 Output Type 2 MΩ 86 db Min. 100 db Individual Channel Configuration Yes esolution Accuracy Voltage Output Capability Current Load esistance Open Wire Detection Power On Value Safe Value Digital Input/Counter Input Channels 2 Dry Contact (Source) Wet Contact (Sink/Source) Counter On Voltage Level Off Voltage Level Effective Distance for Dry Contact On Voltage Level Off Voltage Level Channels 2 Max. Counts Max. Input Frequency Overvoltage Protection Min. Pulse Width Digital Output Output Channels 2 Type Max. Load Current Load Voltage Overvoltage Protection Overload Protection Short-circuit Protection Power-on Value Safe Value 0~5 V, +/-5 V, 0~10 V, +/-10 V 0~20 ma, 4~20 ma (jumper selectable) 12-bit +/-0.1% of FS V 500 Ω Yes, for 4~20 ma only Yes, Programmable Yes, Programmable Close to GND Open 500M max V DC ~ +30V DC +1 V DC max. 4,294,967,285 (32-bit) 100 Hz 5 ms 30 V DC Isolated Open Collector (Sink) 700 ma/channel +5 V DC ~ +50 V DC 60 V DC 1.4 A Yes Yes, Programmable Yes, Programmable P. 37 OME-ET-7026/OME-PET-7026

41 OME ET 7000/OME PET 7000 Series Voltage/Current Input/Output Selection Jumper Settings Channel Vout0 & AGND Vin5 ± Vin4 ± Vin3 ± Vin2 ± Vin1 ± Vin0 ± Jumper JP5 J6 J5 J4 J3 J2 JP1 The selection jumpers are next to the connector. efer to the table below to set the input type. emove the top case of the module. Channel Jumper Vout1+ & AGND JP6 Voltage Input Current Input Voltage Output Current Output The jumper settings of the input type for each AI/AO channel must correspond to the input range for each AI/AO channel of the web interface. Wire Connections Digital Input/ ON State Counter eadback as 1 OFF State eadback as 0 Digital Output ON State eadback as 1 OFF State eadback as 0 Dry Contact Open Collector (Sink) P. 38 OME ET 7026/OME PET 7026

42 Modbus egister Table Coils (0xxxx) egister Points Description Data Format Attribute Factory Value 0 Off 2 DO value /W - 1 On A2 00A7 00C2 00C7 2 Clear the DI counter value 1 Clear W - 2 Clear the DI latched value 1 Clear W - 6 Clear 1-ch historical AI max. value 1 Clear W - 6 Clear 1-ch historical AI min. value 1 Clear W E2 1 eset the I/O settings to the factory default state 1 eset W E9 1 eboot the module 1 eboot W E 1 Enable/Disable the DI latch function 0 Disable 1 Enable F Enable/Disable the DI counter function 0 Disable 1 Enable AF 1 Save the DO power-on value to the EEPOM 1 Save W/E B0 1 Save the DO safe value to the EEPOM 1 Save W/E B3 01B4 2 Enable/Disable the DO power-on value function 0 Disable 1 Enable /W Enable/Disable the DO safe value function 0 Disable 1 Enable /W Enable/Disable the AI function 0 Disable 1 Enable /W/E Set the AI sampling rate Set the AI noise filter 0 Normal mode (10 Hz, 16 bits) 1 Fast mode (60 Hz, 12 bits) 0 Frequency 60 Hz 1 Frequency 50 Hz Save preset values for the DI counter to the EEPOM 1 Save W/E Set the AI/AO data format 0 Hexadecimal format 1 Engineering unit eset the AI calibration to the factory settings 1 eset W A 1 Clear all historical AI max. values 1 Clear W B 1 Clear all historical AI min. values 1 Clear W C Enable/Disable the AI high alarm function 0 Disable 1 Enable C 6 Enable/Disable the AI low alarm function 0 Disable 1 Enable P. 39 OME-ET-7026/OME-PET-7026

43 A BC 02C1 6 Set the AI high alarm mode 0 Momentary mode 1 Latching mode DC 02E1 6 Set the AI low alarm mode 0 Momentary mode 1 Latching mode FC C Clear the AI high alarm status 1 Clear W - 6 Clear the AI high low status 1 Clear W E 1 Enable/Disable the AI calibration 0 Disable 1 Enable /W F 1 Zero calibration for the channel 0 1 Set W Span calibration for the channel 0 1 Set W - Discrete Inputs (1xxxx) egister Points Description Data Format Attribute 0 Off 2 DI value 1 On ead DI high latch status 0 Normal 1 Latched ead DI low latch status 0 Normal 1 Latched E0 00E5 6 ead AI high alarm status. When the AI value is higher than the high alarm value, the status becomes 1. 0 Normal 1 Alarmed ead AI low alarm status. When the AI value is lower than the high alarm value, the status becomes 1. 0 Normal 1 Alarmed P. 40 OME-ET-7026/OME-PET-7026

44 Input egister (3xxxx) egister Points No. Per Point 6 1 AI value Description Data Format Attribute DI counter value 0 to EC 00F1 6 1 AI historical max. value C AI historical min. value C 1 1 Number of the DI channel Number of the DO channel Number of the AI channel A 1 1 Number of the AO channel E 1 1 OS image version 0x123 means version F 1 1 Firmware version 0x123 means version I/O version 0x123 means version Communication state of the pair-connection 0 Normal <0 Failed P. 41 OME-ET-7026/OME-PET-7026

Ethernet Remote I/O Modules. OME-ET-7000/ OME-PET-7000 Series. Features

Ethernet Remote I/O Modules. OME-ET-7000/ OME-PET-7000 Series. Features Ethernet Remote I/O Modules OMEET7000/ OMEPET7000 Series U MultiFunction Web Based Ethernet I/O Modules Models Available For Thermocouple, RTD, Analog Voltage and Current Input U BuiltIn Web Server for

More information

I-7520: RS-232 to RS-485. Input: RS-232 protocol Output:RS-485/RS-422 Speed: Self Tuner 'inside, auto switching baud rate, 300~ BPS

I-7520: RS-232 to RS-485. Input: RS-232 protocol Output:RS-485/RS-422 Speed: Self Tuner 'inside, auto switching baud rate, 300~ BPS I-7520 RS-232 to RS-485 Converter I-7510 RS-485 Repeater RS-232 RS-485 I-7000 SERIES Common Specifications Isolation voltage: 3000VDC Speed: 1200, 2400, 4800, 9600, 19200, 38400, 57600, 115000 Dual watchdog

More information

User s Guide. OM-WEB-TC and OM-WEB-TEMP. Web-Enabled Temperature Measurement Modules. Shop online at

User s Guide. OM-WEB-TC and OM-WEB-TEMP. Web-Enabled Temperature Measurement Modules. Shop online at SM Extended Warranty Program User s Guide Shop online at omega.com e-mail: info@omega.com For latest product manuals: omegamanual.info OM-WEB-TC and OM-WEB-TEMP Web-Enabled Temperature Measurement Modules

More information

User s Guide. DIN-190 and DIN-192 Series. Converter Boxes. Shop online at

User s Guide. DIN-190 and DIN-192 Series. Converter Boxes. Shop online at MADE IN User s Guide Shop online at omega.com e-mail: info@omega.com For latest product manuals: omegamanual.info DIN-190 and DIN-192 Series Converter Boxes OMEGAnet Online Service omega.com Internet e-mail

More information

User s Guide OM-USB-TEMP-AI. 8 Channel Temperature/Voltage Measurement USB Data Acquisition Module. Shop online at

User s Guide OM-USB-TEMP-AI. 8 Channel Temperature/Voltage Measurement USB Data Acquisition Module. Shop online at SM Extended Warranty Program User s Guide Shop online at omega.com e-mail: info@omega.com For latest product manuals: omegamanual.info OM-USB-TEMP-AI 8 Channel Temperature/Voltage Measurement USB Data

More information

Ethernet I/O Module by ICP DAS Co., Ltd. All Rights Reserved. Comparison Item tpet PETL-7000 PET-7000 CPU 32-bit ARM Ethernet

Ethernet I/O Module by ICP DAS Co., Ltd. All Rights Reserved. Comparison Item tpet PETL-7000 PET-7000 CPU 32-bit ARM Ethernet Providing networking ability and various digital I/O functions, the PETL-7000 and tet/tpet series are IP-based Ethernet I/O monitoring and control modules. The module can be remotely controlled through

More information

ET-7000 series Ethernet Remote I/O Module

ET-7000 series Ethernet Remote I/O Module ET-7000 series Ethernet Remote I/O Module User Manual Warranty All products manufactured by ICP DAS are under warranty regarding defective materials for a period of one year, starting from the date of

More information

AMC 8 & IOC 8T. Analog Monitoring Card Type AMC 8 and Input / Output Card Type IOC 8T FEATURES

AMC 8 & IOC 8T. Analog Monitoring Card Type AMC 8 and Input / Output Card Type IOC 8T FEATURES Analog Monitoring Card Type AMC 8 and Input / Output Card Type IOC 8T FEATURES Two cards providing 8 channels of temperature and process monitoring for VM 600 systems 8 channels of software selectable

More information

User s Guide BD9-C2, BD9-C4 (CN9 SERIES) Shop online at. Communications option installation guide. omega.com.

User s Guide BD9-C2, BD9-C4 (CN9 SERIES) Shop online at. Communications option installation guide.  omega.com. OMEGA CARE Extended Warranty Program SM User s Guide Shop online at omega.com www.omega.com e-mail: info@omega.com BD9-C2, BD9-C4 (CN9 SERIES) Communications option installation guide Introduction The

More information

ET-7000/PET-7000 AIO series User Manual

ET-7000/PET-7000 AIO series User Manual ET-7000/PET-7000 AIO series User Manual Service and usage information for ET-7005/PET-7005 ET-7015/PET-7015 ET-7017/PET-7017 ET-7017-10/PET-7017-10 ET-7018Z/PET-7018Z ET-7019/PET-7019 Version 1.0.1 beta3,

More information

ICP DAS. ICP DAS 2015 M2M WLAN Wireless Solutions

ICP DAS. ICP DAS 2015 M2M WLAN Wireless Solutions ICP DAS 2015 M2M WLAN Wireless Solutions Industrial Computer Industrial Product Data Computer Acquisition Product System Data Acquisition System PAC WLAN Wireless Solutions Wi-Fi Products WLAN Converter

More information

RS-485 I/O Modules: ADAM-4000

RS-485 I/O Modules: ADAM-4000 RS-485 I/O Modules: ADAM-4000 23 ADAM-4000 Series Overview ADAM-4000 Series Remote Data Acquisition and Control Modules Overview 23-2 and Controller Module Selection Guide 23-4 I/O Module Selection Guide

More information

User s Guide TX69. Universal Smart Transmitter. Shop online at. omega.com For latest product manuals: omegamanual.

User s Guide TX69. Universal Smart Transmitter. Shop online at. omega.com   For latest product manuals: omegamanual. User s Guide Shop online at omega.com e-mail: info@omega.com For latest product manuals: omegamanual.info MADE IN ISRAEL TX69 Universal Smart Transmitter OMEGAnet Online Service omega.com Internet e-mail

More information

ADAM-5000 Series. I/O Module User's Manual

ADAM-5000 Series. I/O Module User's Manual ADAM-5000 Series I/O Module User's Manual 2.4 rd Edition May 2008 Introduction This manual introduces the detail specifications functions and application wiring of each ADAM-5000 I/O modules. To organize

More information

Features. :. Introduction. :. Leader 5000 Appearance. Ethernet-Based Block I/O System

Features. :. Introduction. :. Leader 5000 Appearance. Ethernet-Based Block I/O System Features 10/100Mbps Ethernet full duplex Auto Negotiation Support C++/C Modbus/TCP drivers and OPC server Support configuration via built-in Web browsing, (HTML), Device Finder and I/O configuration utilities

More information

User s Guide HHM250. AC Clamp Meter. Shop online at. omega.com For latest product manuals: omegamanual.info MADE IN TAIWAN

User s Guide HHM250. AC Clamp Meter. Shop online at. omega.com   For latest product manuals: omegamanual.info MADE IN TAIWAN User s Guide Shop online at omega.com e-mail: info@omega.com For latest product manuals: omegamanual.info MADE IN TAIWAN HHM250 AC Clamp Meter OMEGAnet Online Service omega.com Internet e-mail info@omega.com

More information

R1M-GH THERMOCOUPLE & DC INPUT MODULE MODEL. Remote I/O R1M Series. (16 points)

R1M-GH THERMOCOUPLE & DC INPUT MODULE MODEL. Remote I/O R1M Series. (16 points) Remote I/O R1M Series THERMOCOUPLE & DC INPUT MODULE (16 points) MODEL MODEL & SUFFIX CODE SELECTION R1MGH2T MODEL Modbus protocol I/O TYPE GH2 : Thermocouple or DC input, 16 points FIELD TERMINAL TYPE

More information

I-7017, I-7018, I-7019, M-7017, M-7018 and M-7019 Series User Manual

I-7017, I-7018, I-7019, M-7017, M-7018 and M-7019 Series User Manual I-7017, I-7018, I-7019, M-7017, M-7018 and M-7019 Series User Manual Warranty All products manufactured by ICP DAS are under warranty regarding defective materials for a period of one year from the date

More information

RS 485 Mini Modbus 1AO

RS 485 Mini Modbus 1AO RS 485 Mini Modbus 1AO Version 1.0 14/08/2014 Manufactured for Thank you for choosing our product. This manual will help you with proper support and proper operation of the device. The information contained

More information

8017, 8018, 8019, 8017, M-8018, M-8019 Series User's Manual

8017, 8018, 8019, 8017, M-8018, M-8019 Series User's Manual 8017, 8018, 8019, 8017, M-8018, M-8019 Series User's Manual Warranty All products manufactured by SuperLogics are under warranty regarding defective materials for a period of one year from the date of

More information

User s Guide PHUTX601. Multi-parameter Transmitter. Shop online at. omega.com For latest product manuals: omegamanual.

User s Guide PHUTX601. Multi-parameter Transmitter. Shop online at. omega.com   For latest product manuals: omegamanual. User s Guide Shop online at omega.com e-mail: info@omega.com For latest product manuals: omegamanual.info PHUTX601 Multi-parameter Transmitter OMEGAnet Online Service omega.com Internet e-mail info@omega.com

More information

User s Guide D6000 SERIES. Digital Transmitters Modbus RTU, RS-485 Output. Shop online at omega.com

User s Guide D6000 SERIES. Digital Transmitters Modbus RTU, RS-485 Output. Shop online at omega.com MADE IN SM Extended Warranty Program User s Guide Shop online at omega.com e-mail: info@omega.com For latest product manuals: omegamanual.info D6000 SERIES Digital Transmitters Modbus RTU, RS-485 Output

More information

WF-2000 Series Wi-Fi I/O Module

WF-2000 Series Wi-Fi I/O Module WF-2000 Series Wi-Fi I/O Module AIO User s Manual www.icpdas.com WF-2000 Series AIO User s Manual (Ver. 1.2, May./2014) ------------- 1 Warranty All products manufactured by ICP DAS are under warranty

More information

iothinx 4500 Series (45MR) Modules

iothinx 4500 Series (45MR) Modules iothinx 4500 Series (45MR) Modules Modules for iothinx 4500 Series Feature and Benefits Easy tool-free installation and removal Built-in LED indicators for IO channels Wide operating temperature range:

More information

User s Guide USB Channel Isolated Digital I/O USB Data Acquisition Module. Shop online at

User s Guide USB Channel Isolated Digital I/O USB Data Acquisition Module. Shop online at User s Guide Shop online at omega.com e-mail: info@omega.com For latest product manuals: omegamanual.info USB-4750 32 Channel Isolated Digital I/O USB Data Acquisition Module OMEGAnet Online Service omega.com

More information

ICP DAS. ICP DAS 2013 M2M ZigBee Wireless Solutions

ICP DAS. ICP DAS 2013 M2M ZigBee Wireless Solutions 2013 M2M ZigBee Wireless Solutions Industrial Computer Industrial Product Data Computer Acquisition Product System Data Acquisition System PAC New ZigBee Solutions: ZT-2000 Series Products ZigBee Wireless

More information

iologik R1200 Series User s Manual

iologik R1200 Series User s Manual User s Manual Edition 3.2, November 2017 www.moxa.com/product 2017 Moxa Inc. All rights reserved. User s Manual The software described in this manual is furnished under a license agreement and may be used

More information

User s Guide. DIN-100 Series. DIN Rail Mount Digital Transmitters. Shop online at

User s Guide. DIN-100 Series. DIN Rail Mount Digital Transmitters. Shop online at MADE IN User s Guide Shop online at omega.com e-mail: info@omega.com For latest product manuals: omegamanual.info DIN-100 Series DIN Rail Mount Digital Transmitters OMEGAnet Online Service omega.com Internet

More information

User s Guide OMB-DAQ-2408 SERIES. Multifunction USB Data Acquisition Modules. Shop online at

User s Guide OMB-DAQ-2408 SERIES. Multifunction USB Data Acquisition Modules. Shop online at SM Extended Warranty Program User s Guide Shop online at omega.com e-mail: info@omega.com For latest product manuals: omegamanual.info OMB-DAQ-2408 SERIES Multifunction USB Data Acquisition Modules OMEGAnet

More information

RSTI-EP Slice I/O. Analog Input Modules `EP-3164, EP-3264, EP-3124, EP-3368, EP-3468 EP-3664, EP-3704, EP GFK-2960F September 2018

RSTI-EP Slice I/O. Analog Input Modules `EP-3164, EP-3264, EP-3124, EP-3368, EP-3468 EP-3664, EP-3704, EP GFK-2960F September 2018 September 2018 Module Status LED Channel Status LEDs Digital Input Connector Ground 24 V DC FE Analog Input Module RSTI-EP Slice I/O Analog Input Modules `EP-3164, EP-3264, EP-3124, EP-3368, EP-3468 EP-3664,

More information

iologik R1200 Series User s Manual

iologik R1200 Series User s Manual User s Manual First Edition, April 2013 www.moxa.com/product 2013 Moxa Inc. All rights reserved. User s Manual The software described in this manual is furnished under a license agreement and may be used

More information

DINALOG A 144 x 36 A1400 Light-Strip Indicator

DINALOG A 144 x 36 A1400 Light-Strip Indicator DINALOG A x 6 A00 Light-Strip Indicator -9-0-0 /.00 Front panel dimensions: x 6 mm Light-strip indicator with 7 high-contrast LEDs Red LED display color Digital display range for portrait format: 999 to

More information

User s Guide LDN-PS. Shop online at. omega.com For latest product manuals: omegamanual.info. solartron

User s Guide LDN-PS. Shop online at. omega.com   For latest product manuals: omegamanual.info. solartron User s Guide solartron Shop online at 9 6 5 1 LDN-PS omega.com e-mail: info@omega.com For latest product manuals: omegamanual.info Servicing North America: USA: One Omega Drive, Box 4047 ISO 9001 Certified

More information

User s Guide HHM-MG300. Wireless TRMS Multimeter and Insulation Tester. Shop online at omega.com

User s Guide HHM-MG300. Wireless TRMS Multimeter and Insulation Tester. Shop online at omega.com User s Guide Shop online at omega.com e-mail: info@omega.com For latest product manuals: omegamanual.info MADE IN TAIWAN HHM-MG300 Wireless TRMS Multimeter and Insulation Tester OMEGAnet Online Service

More information

D1000M SERIES FOR MODBUS SENSOR TO COMPUTER INTERFACE MODULES

D1000M SERIES FOR MODBUS SENSOR TO COMPUTER INTERFACE MODULES D1000M SERIES FOR MODBUS SENSOR TO COMPUTER INTERFACE MODULES D1000 FEATURES Complete sensor to RS-232/RS-485 interface. 500V rms analog input isolation. 15 bit measurement resolution. Continuous self-calibration;

More information

User s Guide WTC Shop online at. Wind Tunnel Controller. omega.com For latest product manuals: omegamanual.

User s Guide WTC Shop online at. Wind Tunnel Controller. omega.com   For latest product manuals: omegamanual. User s Guide Shop online at omega.com e-mail: info@omega.com For latest product manuals: omegamanual.info WTC-3000 Wind Tunnel Controller OMEGAnet Online Service omega.com Internet e-mail info@omega.com

More information

User s Guide. CSi8DH SERIES. Benchtop Controllers. Shop online at. omega.com For latest product manuals: omegamanual.

User s Guide. CSi8DH SERIES. Benchtop Controllers. Shop online at. omega.com   For latest product manuals: omegamanual. MADE IN User s Guide Shop online at omega.com e-mail: info@omega.com For latest product manuals: omegamanual.info CSi8DH SERIES Benchtop Controllers OMEGAnet Online Service omega.com Internet e-mail info@omega.com

More information

ET-7000/PET-7000 DIO Series User Manual

ET-7000/PET-7000 DIO Series User Manual ET-7000/PET-7000 DIO Series User Manual Version 1.0.1 beta2, April 2010 Service and usage information for ET-7042 ET-7044 ET-7050 ET-7051 ET-7052 ET-7053 ET-7060 ET-7065 ET-7066 ET-7067 PET-7044 PET-7051

More information

Ethernet I/O Products

Ethernet I/O Products .. Overview P--.2. Modbus TCP I/O Expansion Unit P-2-.. ET-7000/PET-7000/PET-7000-48V Series (Web based) P--.4. PEE-7000/PEE-7000-48V Series (Web based) P-4-.5. tet/tpet Series Modules (IP based) P-5-.6.

More information

ET-2200 Series Ethernet I/O Modules User Manual

ET-2200 Series Ethernet I/O Modules User Manual ET-2200 Series Ethernet I/O Modules User Manual Ethernet I/O Module Ver. 1.3.0, Jun. 2018 WARRANTY All products manufactured by ICP DAS are warranted against defective materials for a period of one year

More information

OMR-6011/D OMR-6014D OMR-6012/D OMR-6017 OMR-6013 OMR Analog Input Modules

OMR-6011/D OMR-6014D OMR-6012/D OMR-6017 OMR-6013 OMR Analog Input Modules OMR-6011/D OMR-6014D OMR-6012/D OMR-6017 OMR-6013 OMR-6018 Analog Input Modules Contents 1 Introduction... 1-1 1. 1. ABOUT THE OMR ANALOG INPUT MODULES...1-1 1. 2. OVERVIEW OF OMR-6011/D...1-1 1. 3. OVERVIEW

More information

LOGGING SOFTWARE FOR TC-08 AND PT-104 DATA ACQUISITION MODULES

LOGGING SOFTWARE FOR TC-08 AND PT-104 DATA ACQUISITION MODULES SM Extended Warranty Program User s Guide PT-104 Shop online at TC-08 omega.com e-mail: info@omega.com For latest product manuals: omegamanual.info LOGGING SOFTWARE FOR TC-08 AND PT-104 DATA ACQUISITION

More information

ZigBee Products. ICP Electronics Australia Pty Ltd Overview P ZigBee Converters P5-2-1

ZigBee Products. ICP Electronics Australia Pty Ltd Overview P ZigBee Converters P5-2-1 ZigBee Products.1 Overview P11.2 ZigBee Converters P21.3 ZigBee I/O Modules P31 Overview.1. Overview ZigBee Products ZigBee Host ZB270T(PA)/20T(PA) ZigBee DIO 1 Overview ZigBee Repeater ZB210T Based on

More information

ADAM-6200 Series. Feature. Transition and Vision on Remote DAQ Device 19-13

ADAM-6200 Series. Feature. Transition and Vision on Remote DAQ Device 19-13 ADAM-6200 Series Feature DI/O LED Indication Flexible user-defined Modbus address 19 20 21 DAQ Boards Signal Conditioning Industrial USB I/O Modules22 Transition and Vision on Remote DAQ Device In 2002,

More information

D7000 SERIES MODBUS TCP/IP ETHERNET INTERFACE MODULES

D7000 SERIES MODBUS TCP/IP ETHERNET INTERFACE MODULES 11/17 D7000 SERIES MODBUS TCP/IP ETHERNET INTERFACE MODULES D7000 FEATURES Complete data acquisition systems. Analog and Digital I/O models available. RJ-45 Ethernet 10/100MB interface. Modbus TCP/IP Ethernet

More information

ZigBee Products 5.1 Overview P ZigBee Converters P ZigBee I/O Modules P5-3-1

ZigBee Products 5.1 Overview P ZigBee Converters P ZigBee I/O Modules P5-3-1 ZigBee Products.1 Overview P11.2 ZigBee Converters P21.3 ZigBee I/O Modules P31 Overview.1. Overview ZigBee Products ZigBee Host ZB270T(PA)/20T(PA) ZigBee DIO 1 Overview ZigBee Repeater ZB210T Based on

More information

PROFIBUS Products. ICP Electronics Australia Pty Ltd Overview P 5-1

PROFIBUS Products. ICP Electronics Australia Pty Ltd Overview P 5-1 5.1 Overview P 5-1 Selection Guide - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - P 5-2 5.2 Converters & Repeaters P 5-3 5.3 Gateways P 5-5 5.4

More information

User s Guide. DP40 and DPF400. Series Indicators RS-232/RS-422/RS-485 Serial Communications. Shop on line at

User s Guide. DP40 and DPF400. Series Indicators RS-232/RS-422/RS-485 Serial Communications. Shop on line at User s Guide Shop on line at www.omega.com e-mail: info@omega.com For latest product manuals www.omegamanual.info DP40 and DPF400 Series Indicators RS-232/RS-422/RS-485 Serial Communications France: TEL:

More information

DBK24. Isolated Digital Output Chassis. Overview

DBK24. Isolated Digital Output Chassis. Overview DBK24 Isolated Digital Output Chassis Overview 1 Power Requirements 2 Hardware Setup 2 Card Connection 2 Card Configuration 3 DaqBook and DaqBoard Connection 4 DaqBoard/2000 Series Board Connection 5 DaqBook

More information

8 Channel Analog Input Module Datasheet. Address / Baud rate / range configurable by the user

8 Channel Analog Input Module Datasheet. Address / Baud rate / range configurable by the user 8 Channel Analog Input Module Datasheet User s Manual Overview: DAM module is a new generation data acquisition and control system based on modular embedded systems. Adopting standard DIN35 rail mounting

More information

INTEGRATED SYSTEMS AND CONTROL, INC. User s Hardware Manual. PCMNET V 7. xx

INTEGRATED SYSTEMS AND CONTROL, INC. User s Hardware Manual. PCMNET V 7. xx INTEGRATED SYSTEMS AND CONTROL, INC. User s Hardware Manual PCMNET V 7. xx INTEGRATED SYSTEMS AND CONTROLS, INC. PCMNET Users Manual Revised 2/4/2005 2003-2005 Integrated Systems and Control. Inc. PO Box

More information

Features and Benefits. Certifications

Features and Benefits. Certifications iologik E2200 Series Smart Ethernet remote I/O with Click&Go Logic Features and Benefits Front-end intelligence with patented Click&Go control logic, up to 24 rules Active communication with MX-AOPC UA

More information

ADAM Data Acquisition Modules User's Manual

ADAM Data Acquisition Modules User's Manual ADAM 4000 Data Acquisition Modules User's Manual ADAM 4000 Series Data Acquisition Modules User s Manual Copyright Notice This document is copyrighted, 1997, by Advantech Co., Ltd. All rights are reserved.

More information

Digital Panel Meters

Digital Panel Meters Digital Panel Meters For, Process, Voltage and Current DP63000 Starts at 81 DP63000B-E, 90, Thermocouple Inputs RTD Inputs Programmable Offset Selectable F or C with 1 or 0.1 Degree Resolution 3 Selectable

More information

Basic Temperature and Limit Controllers

Basic Temperature and Limit Controllers Basic Temperature and Limit Controllers Basic Temperature and Limit Controller Provide Economical Solution for a Wide Range of Applications The basic and limit microprocessor-based controllers from Watlow

More information

iologik E1200 Series User s Manual

iologik E1200 Series User s Manual User s Manual Tenth Edition, April 2013 www.moxa.com/product 2013 Moxa Inc. All rights reserved. Reproduction without permission is prohibited. User s Manual The software described in this manual is furnished

More information

NuDAM-6011/ NuDAM-6014D NuDAM-6012/D NuDAM-6017 NuDAM-6013/ NuDAM-6018 Analog Input Modules User s Guide

NuDAM-6011/ NuDAM-6014D NuDAM-6012/D NuDAM-6017 NuDAM-6013/ NuDAM-6018 Analog Input Modules User s Guide NuDAM-6011/ NuDAM-6014D NuDAM-6012/D NuDAM-6017 NuDAM-6013/ NuDAM-6018 Analog Input Modules User s Guide Copyright 1996~2001 ADLINK Technology Inc. All Rights Reserved. Manual Rev. 5.15: October 2, 2001

More information

12-36 VDC/12-24 VAC Power Option 4-Digit Display, 0.56 (14.2 mm) or 1.20 (30.5 mm)

12-36 VDC/12-24 VAC Power Option 4-Digit Display, 0.56 (14.2 mm) or 1.20 (30.5 mm) 4-20 ma & Relay Output Features 4-20 ma, ± 10 V, TC & RTD Inputs 12-36 VDC/12-24 VAC Power Option 4-Digit Display, 0.56 (14.2 mm) or 1.20 (30.5 mm) 24 VDC @ 200 ma Transmitter Power Supply Options Type

More information

User Manual SUPPORT. Ethernet I/O Modules Ver. 1.8, Jan. 2014

User Manual SUPPORT. Ethernet I/O Modules Ver. 1.8, Jan. 2014 PETL/tET/tPET DIO Series User Manual Ethernet I/O Modules Ver. 1.8, Jan. 2014 WARRANTY All products manufactured by ICP DAS are warranted against defective materials for a period of one year from the date

More information

User s Guide. LVR300 Series. Shop online at. Continuous Level Switch System

User s Guide. LVR300 Series. Shop online at. Continuous Level Switch System User s Guide LVR300 Series Shop online at omega.com e-mail: info@omega.com For latest product manuals: omegamanual.info LVR300 Series Continuous Level Switch System OMEGAnet Online Service omega.com Internet

More information

ADAM-5000 Series. I/O Module User's Manual. Copyright Notice

ADAM-5000 Series. I/O Module User's Manual. Copyright Notice ADAM-5000 Series I/O Module User's Manual Copyright Notice This document is copyrighted, 1997, by Advantech Co., Ltd. All rights are reserved. Advantech Co., Ltd., reserves the right to make improvements

More information

SDM-8AO. Expansion Module 8 analog outputs. Manufactured for

SDM-8AO. Expansion Module 8 analog outputs. Manufactured for Version 1.0 16.05.2014 Manufactured for Thank you for choosing our product. This manual will help you with proper support and proper operation of the device. The information contained in this manual have

More information

OM-DAQLINK-TEMP AND OM-DAQLINK-TEMPRH

OM-DAQLINK-TEMP AND OM-DAQLINK-TEMPRH SM Extended Warranty Program User s Guide OM-DAQLINK-TEMP Shop online at omega.com e-mail: info@omega.com For latest product manuals: omegamanual.info OM-DAQLINK-TEMPRH OM-DAQLINK-TEMP AND OM-DAQLINK-TEMPRH

More information

RSTI-EP Slice I/O. Analog Input Modules `EP-3164, EP-3264, EP-3124, EP-3368, EP-3468 EP-3704, EP GFK-2960B November 2017

RSTI-EP Slice I/O. Analog Input Modules `EP-3164, EP-3264, EP-3124, EP-3368, EP-3468 EP-3704, EP GFK-2960B November 2017 November 2017 Module Status LED Channel Status LEDs Digital Input Connector Ground 24 V DC FE Analog Input Module RSTI-EP Slice I/O Analog Input Modules `EP-3164, EP-3264, EP-3124, EP-3368, EP-3468 EP-3704,

More information

Model IR4000M. Multi-Point Monitor Modbus programming guide

Model IR4000M. Multi-Point Monitor Modbus programming guide Model I4000M Multi-Point Monitor Modbus programming guide The information and technical data disclosed in this document may be used and disseminated only for the purposes and to the extent specifically

More information

Trident and Trident X2 Digital Process and Temperature Panel Meter

Trident and Trident X2 Digital Process and Temperature Panel Meter Sign In New User ISO 9001:2008 Certified Quality System Home Products Online Tools Videos Downloads About Us Store Contact Policies Trident and Trident X2 Digital Process and Temperature Panel Meter Products

More information

iologik R1200 Series User s Manual

iologik R1200 Series User s Manual User s Manual Edition 3.3, February 2018 www.moxa.com/product 2018 Moxa Inc. All rights reserved. User s Manual The software described in this manual is furnished under a license agreement and may be used

More information

Redundant System Redundant System P9-1-1

Redundant System Redundant System P9-1-1 .. P-- Overview - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - P-- idcs-8830/idcs-8830r - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - -

More information

BUENO ELECTRIC. Https://www.bueno-electric.com. BE-6000 Series. Remote I/O Modules. Contact: Fax:

BUENO ELECTRIC. Https://www.bueno-electric.com. BE-6000 Series. Remote I/O Modules. Contact: Fax: Https://www.bueno-electric.com BUENO ELECTRIC BE-6000 s Contact: sales@bueno-electric.com Fax: +86-25-51816989 Chapter 1 Product Overview 1.1 Product Introduction (RS-6000M) RS-6000M RS485-based data acquisition

More information

Basic Temperature and Limit Controllers. Provide Economical Solution for a Wide Range of Applications SPECIFICATION SHEET

Basic Temperature and Limit Controllers. Provide Economical Solution for a Wide Range of Applications SPECIFICATION SHEET SPECIFICATION SHEET Basic Temperature and Limit Controllers Basic Temperature and Limit Controllers Provide Economical Solution for a Wide Range of Applications The basic and limit microprocessor-based

More information

User s Guide CT89 SERIES. Temperature Recorder. Shop online at. omega.com For latest product manuals: omegamanual.

User s Guide CT89 SERIES. Temperature Recorder. Shop online at. omega.com   For latest product manuals: omegamanual. MADE IN User s Guide SM Extended Warranty Program Shop online at omega.com e-mail: info@omega.com For latest product manuals: omegamanual.info CT89 SERIES Temperature Recorder OMEGAnet Online Service omega.com

More information

User s Guide USB-4711A. 150 ks/s, 12-Bit Multifunction USB Data Acquisition Module. Shop online at

User s Guide USB-4711A. 150 ks/s, 12-Bit Multifunction USB Data Acquisition Module. Shop online at User s Guide Shop online at omega.com e-mail: info@omega.com For latest product manuals: omegamanual.info USB-4711A 150 ks/s, 12-Bit Multifunction USB Data Acquisition Module OMEGAnet Online Service omega.com

More information

P2-04DA Analog Output. Removable Terminal Block Specifications

P2-04DA Analog Output. Removable Terminal Block Specifications WARNING: To minimize the risk of potential safety problems, you should follow all applicable local and national codes that regulate the installation and operation of your equipment. These codes vary from

More information

User s Guide TCL Series Portable Sample Cooling Device

User s Guide TCL Series Portable Sample Cooling Device User s Guide Shop online at omega.com e-mail: info@omega.com For latest product manuals: omegamanual.info TCL Series Portable Sample Cooling Device OMEGAnet Online Service omega.com Internet e-mail info@omega.com

More information

User s Guide OMB-NET Channel Ethernet-Based Thermocouple Input Module

User s Guide OMB-NET Channel Ethernet-Based Thermocouple Input Module SM Extended Warranty Program User s Guide Shop online at omega.com e-mail: info@omega.com For latest product manuals: omegamanual.info OMB-NET6222 12-Channel Ethernet-Based Thermocouple Input Module OMEGAnet

More information

ProfiPro Distributed PROFIBUS I/O Modules User Manual

ProfiPro Distributed PROFIBUS I/O Modules User Manual ProfiPro Distributed PROFIBUS I/O Modules User Manual 15/03/2012 V1.0 22/195 Prospect Highway Seven Hills 2147 NSW Australia Tel: +61 (02) 96248376 Fax: +61 (02) 96208709 Email: proconel@proconel.com Web:

More information

RS485 MODBUS Module 8I8O

RS485 MODBUS Module 8I8O Expansion Module 8 digital inputs, 8 digital outputs Version 2.2 12/01/2014 Manufactured for Thank you for choosing our product. This manual will help you with proper support and proper operation of the

More information

S-series Electronic Marshalling

S-series Electronic Marshalling DeltaV Distributed Control System Product Data Sheet July 2017 S-series Electronic Marshalling I/O anywhere you need it Single channel granularity Reduces installed cost of system Fully redundant architecture

More information

iologik 4000 Series (M) Modules

iologik 4000 Series (M) Modules iologik 4000 Series (M) s Remote I/O modules Features and Benefits I/O expansion without a backplane Active communication with MX-AOPC UA Server Supports SNMP v1/v2c Easy configuration with Modular ioadmin

More information

Remote I/O Modules EH-RIO2 Series

Remote I/O Modules EH-RIO2 Series Remote I/O Modules EH-RIO2 Series Fieldbus adapter: ProfiNET, EtherCAT, Modubus TCP / RTU, Profibus-DP, DeviceNet Separation of electronics module and terminal block for easy installation and maintenance

More information

CJ1W-PTS/PDC/PH41U/AD04U

CJ1W-PTS/PDC/PH41U/AD04U CJ-series Process Analog I/O Unit A Single Unit Handling All Types of Inputs such as Temperature Sensor Inputs and Analog Signal Inputs (e.g., 4 to 20 ma or 1 to 5 V) A Unit supports four input channels,

More information

P2-04AD Analog Input. Removable Terminal Block Specifications

P2-04AD Analog Input. Removable Terminal Block Specifications WARNING: To minimize the risk of potential safety problems, you should follow all applicable local and national codes that regulate the installation and operation of your equipment. These codes vary from

More information

I-7000 and M-7000 DIO User Manual

I-7000 and M-7000 DIO User Manual I-7000 and M-7000 DIO User Manual Warranty All products manufactured by ICP DAS are under warranty regarding defective materials for a period of one year from the date of delivery to the original purchaser.

More information

User s Guide. OMB-DAQ-54/55/56 USB Data Acquisition Modules. Shop online at

User s Guide. OMB-DAQ-54/55/56 USB Data Acquisition Modules. Shop online at User s Guide Shop online at omega.com e-mail: info@omega.com For latest product manuals: omegamanual.info OMB-DAQ-54/55/56 USB Data Acquisition Modules OMB-491-0901 rev 6.1 OMEGAnet Online Service omega.com

More information

User s Guide DRF-TCJ, DRF-TCK, DRF-TCT, DRF-TCE, DRF-TCR, AND DRF-TCS THERMOCOUPLE INPUT MODULES. DRF Series Signal Conditioners.

User s Guide DRF-TCJ, DRF-TCK, DRF-TCT, DRF-TCE, DRF-TCR, AND DRF-TCS THERMOCOUPLE INPUT MODULES. DRF Series Signal Conditioners. User s Guide Shop online at omega.com e-mail: info@omega.com For latest product manuals: omegamanual.info DRF-TCJ, DRF-TCK, DRF-TCT, DRF-TCE, DRF-TCR, AND DRF-TCS THERMOCOUPLE INPUT MODULES DRF Series

More information

RS485 MODBUS Module 8AO

RS485 MODBUS Module 8AO Version 1.3 12/02/2013 Manufactured for Thank you for choosing our product. This manual will help you with proper support and proper operation of the device. The information contained in this manual have

More information

I-7000 and M-7000 DIO User Manual

I-7000 and M-7000 DIO User Manual I-7000 and M-7000 DIO User Manual Warranty All products manufactured by ICP DAS are under warranty regarding defective materials for a period of one year from the date of delivery to the original purchaser.

More information

Other standard features include current and voltage monitoring, overvoltage, overtemperature as well as short circuit protection.

Other standard features include current and voltage monitoring, overvoltage, overtemperature as well as short circuit protection. The BPEU Series of AC/DC Converters is available with multiple outputs and output power from 1300 W up to 3000 W. All models incorporate active Power Factor Correction (PFC). Other standard features include

More information

AMC8 and IOC8T Analog monitoring card and input / output card

AMC8 and IOC8T Analog monitoring card and input / output card Analog monitoring card and input / output card FEATURES AMC8» From the Vibro-Meter product line» Two cards providing 8 channels of temperature and process monitoring for VM600 systems» 8 channels of software

More information

User s Guide OM-DN SERIES. Wireless Intelligent Data Logging System. Shop online at

User s Guide OM-DN SERIES. Wireless Intelligent Data Logging System. Shop online at SM Extended Warranty Program User s Guide Shop online at OM-DNR-900 REPEATER omega.com e-mail: info@omega.com For latest product manuals: omegamanual.info OM-DNL-910 TEMPERATURE LOGGER OM-DNL-920 RH/TEMPERATURE

More information

User s Guide HH309A. Data Logger Thermometer. Shop online at. omega.com For latest product manuals: omegamanual.

User s Guide HH309A. Data Logger Thermometer. Shop online at. omega.com   For latest product manuals: omegamanual. User s Guide Shop online at omega.com e-mail: info@omega.com For latest product manuals: omegamanual.info HH309A Data Logger Thermometer OMEGAnet Online Service omega.com Internet e-mail info@omega.com

More information

RS485 MODBUS Module 8I8RO

RS485 MODBUS Module 8I8RO Expansion Module 8 digital inputs, 8 relay outputs Version 1.0 3.12.2014 Manufactured for Thank you for choosing our product. This manual will help you with proper support and proper operation of the device.

More information

Ethernet I/O Modules: ADAM-6000

Ethernet I/O Modules: ADAM-6000 Ethernet I/O Modules: ADAM-6000 16 ADAM-6000 Series Overview ADAM-6000 Series 16-2 Peer-to-Peer Technology 16-4 Graphic Condition Logic (GCL) Technology 16-6 ADAM-6000 Selection Guide 16-8 I/O Modules

More information

LAUREL ELECTRONICS, INC.

LAUREL ELECTRONICS, INC. LAUREL ELECTRONICS, INC. Laureate RTD Temperature Panel Meter / Controller Features Factory calibrated for 100Ω platinum, 10Ω copper & 120Ω nickel RTDs 2, 3 or 4-wire connection with lead resistance compensation

More information

ABB Instrumentation. Specification DataFile COMMANDER 100. the-easy-to use 1. /8 DIN controller with extensive application capabilities

ABB Instrumentation. Specification DataFile COMMANDER 100. the-easy-to use 1. /8 DIN controller with extensive application capabilities COMMANDER Universal Process Controller Specification DataFile PID controller with one shot autotune single loop, heat/cool and ramp/soak as standard Quick code, front face or PC configuration easy commissioning

More information

RoHS 2 Compliant User s Guide Shop on line at omega.com For latest product manuals DP24-E Process Meter

RoHS 2 Compliant User s Guide Shop on line at omega.com   For latest product manuals  DP24-E Process Meter RoHS 2 Compliant User s Guide Shop on line at omega.com e-mail: info@omega.com For latest product manuals www.omegamanual.info DP24-E Process Meter OMEGAnet On-Line Service www.omega.com Internet e-mail

More information

Ethernet I/O Modules: ADAM-6000

Ethernet I/O Modules: ADAM-6000 Ethernet I/O Modules: ADAM-6000 24 EtherNet/IP I/O Modules EtherNet/IP I/O Module Introduction 24-2 ADAM-6100 Series Selection Guide 24-3 ADAM-6117EI (New) ADAM-6118EI (New) ADAM-6150EI (New) ADAM-6160EI

More information

Signal Conditioning Modules and Terminal Boards

Signal Conditioning Modules and Terminal Boards Signal Conditioning Modules and Terminal Boards Terminal Board Selection Guide 17-2 Isolated Signal Conditioning Modules ADAM-3000 Series Isolated Signal Conditioning Modules 17-4 ADAM-3011 ADAM-3013 ADAM-3014

More information

QA-TEMP UNIVERSAL TEMPERATURE CONVERTER UNIVERSAL TEMPERATURE CONVERTER. I4 way isolated - RS485 MODBUS- Datalogger QA-TEMP

QA-TEMP UNIVERSAL TEMPERATURE CONVERTER UNIVERSAL TEMPERATURE CONVERTER. I4 way isolated - RS485 MODBUS- Datalogger QA-TEMP Power Fail x Tx Dout QEED UNIVESAL TEMPEATUE CONVETE 4 way isolated - S485 MODBUS- Datalogger Advanced UNIVESAL TEMPEATUE CONVETE, USB configurable, DIN rail mounting, 4-way galvanically isolated, universal

More information

USB-1616FS. Analog Input and Digital I/O. Specifications

USB-1616FS. Analog Input and Digital I/O. Specifications Analog Input and Digital I/O Specifications Document Revision 1.6 May 2012 Copyright 2012 Specifications All specifications are subject to change without notice. Typical for 25 C unless otherwise specified.

More information