signo 727 SSI Operating Instructions Position-Indicator with/without limit values and SSI input from absolute encoder
|
|
- Myles Holland
- 6 years ago
- Views:
Transcription
1 Operating Instructions signo 727 SSI Position-Indicator with/without limit values and SSI input from absolute encoder Contents 1. Safety instructions 1 2. Mounting of the position indicator Mounting the position indicator Connections Terminal connections Description of input and output Description of function of position indicator 3 3. Operation of the position indicator Display and keyboard Setting the reference value and reset of the chain value Changing limit value 1, 2 and set value 4 4. Programming Survey Display of the absolute data of the absolute shaft encoders Changing system parameters Survey on the system parameters and alternatives 5 5. Locking keyboard functions 6 6. Failures and error messages 6 7. Technical data Mechanical Specifications Electrical Spezifications Ordering information Accessories Explanation of technical terms 7 This symbol indicates passages in the text which you have to pay special attention to so as to guarantee proper use and preclude any risk. 1. Safety instructions This instrument has been built and tested in accordance with EN 61010, part1 - Protection Measures for Electronic Measuring Instruments - and have left our works in safe and proper condition. In order to maintain these conditions and to ensure safe operation, the user must observe the instructions and warnings provided in these operating instructions. This units must only be operated if correctly installed! The supply voltage must be derived from a SELV SOURCE (12-24VDC versions) according to EN , since no galvanic separation is provided between power-supply and electronic in-/outputs! When mounting and installing the units, the instructions of the local suppliers of energy are to be considered. The unit must only be opened for setting by trained personnel. The plug-in terminals, at rear of the unit, must not be accessed before first isolating the supply. The identification numbers of the plug-in terminals and of the corresponding socket strip must be observed. Unassigned terminals (NC) may not be connected! Connection terminals are to be protected by installation! In order to ensure hand contact safety at the connection terminals, live wires must be connected properly to the connection terminals. If safe operation can no longer be ensured, the position indicator must be disabled and secured against accidential operation. Installation of electrical devices should only be carried out by a qualified electrican. Panel mounting devices should only be operated when proberly mounted in the panel. Before switching on, make sure that the power and control voltages do not exceed the values specified in the technical data. In a situation where failure of the device could cause harm to people, animals or property, additional safety measures must be employed, e.g. stop switches, protection devices etc. Hengstler counters are intended for industrial applications. The mounting and environment and nearby cabling have an important influence on the EMC (noise radiation and noise immunity) of the counter. When putting into operation, the EMC of the whole installation (unit) has to been secured. In particular, the relay outputs are to be protected from high noise radiation by suitable wiring. The range of applications for those products are industrial processes and controls, where the overvoltages applied to the product at the connection terminals are limited to values of the overvoltage category II. Sach-Nr Version 9/98 1/8
2 2. Mounting of the position indicator Dimensions in mm 2.1 Mounting the position indicator into the panel. 1. Slide installation frame towards the rear and off the position indicator, lift the two self locking catch springs. 2. Turn back the screws of the installation frame by approx. 5 mm. 3. Insert position indicator into the cut-out of panel and snap installation frame into place 4. Fix the position indicator with the screws against the panel. 2.2 Connection Attention: Take care that all parts of system are de-energized during the installation of position indicator and that current is not switched on during assembly! Safety conditions are to be observed during installation, which shall be effected by trained personnel only. Caution: The operation and/or switched voltages can reach VAC! To maintain interference grade 3, all count and control lines shall be shielded. The supply lines should be routed in separate channels Terminal connections AC-Version: here without limit values DC-Version: here with limit values Sach-Nr Version 9/98 2/8
3 2.2.2 Description of input and output Function Terminal Remarks: Power supply of position indicator AC: Terminal 1-4 DC: Terminal 1-2 at 230 VAC: bridge terminals 2-3; at 115 VAC: bridge terminals 1-2 and 3-4; at VDC:Terminals 3 and 4 are not connected Relay output for limit value 1 or limit value 2 Terminal 6-8 or change over contact, Remark: these terminals are not connected at position indicators without limit values Transistor output for limit value 1 or limit value 2 Terminal 14 or 15 PNP transistor output 10 ma, Remark: these terminals are not connected at position indicators without limit values Sensor power supply Terminal 32 and 31 Supply of sensor with VDC / 60 ma (max) DATA + Terminal 30 differential signal data + (data input from SSI - encoder) DATA - Terminal 29 differential signal data - (data input from SSI - encoder) CLOCK + Terminal 28 differential signal clock + (clock output for SSI - encoder) CLOCK - Terminal 27 differential signal clock - (clock output for SSI - encoder) Keylock Terminal 26 locking of operation levels can be programmed (see chapter 4.3) Application input Terminal 25 set value, refernce point, display hold or chain reset, can be programmed ( see chapter 4.3) 2.3 Description of function of position indicator The position indicator is working in range mode, i.e. the output signals (Out 1 and Out 2) are set when reaching the respective limit value. The bistable signal is active until the count value falls below the limit value or the counter is reset to zero. Reset to zero or to the set value is done manually from the keyboard or electrically from the reset input. Attention: Per default, the display range of the indicator is centered, i.e. in conjunction with a 4096 ppr encoder the display reaches from to By means of the reference value, however, the display can be adjusted to show 0 to Program a reference value of 2048, forward the workpiece to the middle position and reset the indicator. count impulses count impulses limit value 2 limit value 2 limit value 1 t set value limit value 1 t Out1 Out1 Out2 Out2 Example 1: (set value = 0) Example 2: (set value between limit value 1 and limit value 2) 3. Operation of the position indicator 3.1 Display and keyboard P1 P2 SET DATA CHAIN Area A: Display, in counting mode showing the actual or absolute position (chain value or absolute value), and in programming mode the changeable parameters. SSI Area B: LED indicators show in counting mode the chain value (chain) or the active output signal (limit value 1 = P1, limit value 2 = P2) 1 or to switch over to the absolute value (DATA). In programming mode the LED's are flashing, so pointing to the changeable parameter (set value = set). Area C: Keyboard: The use of the different keys is explained in chapter only for position indicators with limit values Sach-Nr Version 9/98 3/8
4 3. 2. Setting the reference value or reset of the chain value Explanation to chain value: The chain value (CHAIN) is a second display independent of the main counter. It does not influence the limit values and can be reset to 0 at any point. For example, as a display help when processing chain measured parts. Function Procedure Setting the absolute value to a When absolute value is displayed: Press simultaneously the buttons R and reference value Zerosetting of the chain value When chain value is dis-played (LED CHAIN illuminated): Press R-button. Cancelling reference value Press simultaneously the buttons R and 3.3 Changing of limitation value 1, limitation value 2 and set value Function Procedure Selection of limitation value 1 Press key F1 (LED P1 is flashing) Selection of limitation value 2 Press key F2 (LED P2 is flashing) Selection of set value Press key E and F1 simultaneously (LED SET is flashing) Changing parameters Press -key (arrow up) to change the value of the blinking digit. Press -Key (arrow left) to switch to the next digit. Change sign with the +/- key. Press R-key to reset the value to zero Storage of parameters Press E key shortly to exit and return to display mode Exit without storage by time criterion: the return to the display mode is automatically done 15 sec after the last pressing of a key, without storing the changed parameter 4. Programming 4.1 Survey Sach-Nr Version 9/98 4/8
5 DISPLAYMODE (Normal Count Mode) simultaneous Absolute-Postion-Mode Reset absolute Value switch Mode CHAIN-Mode (CHAIN-LED illuminated) reset Chainvalue to Zero short short short short long (>2s) simultaneous simultaneous Power ON and simultaneous P1: limit-value 1* P2: limit-value 2* SET: Setvalue level 1 * only for position indicators with limitation values singleturn display z.bsp. _4321 multiturn display z.bsp. 8765_ level 2 System parameters: 'F1' = totalresolution in bit 'F2' = singleturn resolution in bit 'F3' = binary/gray code 'F4' = format 'F5 ' = output P1 locked / free 'F6' = output P2 locked / free 'F7' = special bits 'F8' = display per revolution 'F9' = display divisor 'F10' = drive direction 'F11' = multiple transmission 'F12' = decimal point 'F20' = funktion of first limit value 'F24' = switching pnp/npn 'F26' = locking set function 'F27' = locking level 1 'F28' = locking level 2 'F29' = locking buttons F1/F2 'F30' = basic settings 'F31' = function application input 'F35' = display of chain value remarks: -key to switch to the next parameter level Display of the absolute data of the absolute shaft encoders Function Procedure Entering level 2 Press E and F2 simultaneously, light diode DATA is illuminated Select absolute data Press to switch either to single turn or to multi turn data. Editing of the value is not possible. For differentation of the data, the values are displayed: Singleturn: f.e. _4321 Multiturn: f.e. 8765_ 4.3 Changing system parameters Function Procedure Entering level 3 Press keys E and -key (arrow up) key in de-energized state, then switch on power Selection of changeable Press key E shortly, until the desired indication " " in display is flashing (see table parameter chapter 4.4) Changing parameter Selection of the various alternatives for each parameter by pressing -key (arrow up) (see table chapter 4.4) Storage of parameter value Press key E shortly to switch to the next parameter or press Key E for at least 2 sec to exit operation level and return to the display mode Exit level 3 without storage by the time criterion: the return to the display mode is done automatically 15 sec after a key has been pressed last, without the changed parameter being stored 4.4 Survey on the system parameters and alternatives Parameter Display Alternatives / Signification Sach-Nr Version 9/98 5/8
6 total encoder resolution / bit 'F1' '1' to '24'* encoder resolution single 'F2' '0' to turn / bit '12''* Data coding 'F3' 'bin':* 'Gray': Data transfer format 'F4' 'Std':* 'tan': Signal OUT 1 'F5' 'off': 'bi':* Signal OUT 2 'F6' 'off': 'bi':* 0Special bits 'F7' '0':* '2': Display per revolution 'F8' '0'- '4096' * -'9999' Display divisor 'F9' * '10': '100': '1000': Drive direction 'F10' '0':* Multiple transfer 'F11' '0':* Decimal point 'F12' '0':* '2': '3': Function of first limit 'F20' '0':* value 1 total encoder resolution in bits resolution of the singleturn part in bits binary code gray code standard format, MSB-flush pine-tree format no output signal output signal no output signal output signal no special bits alarm parity value, added to or subtracted from the display per revolution value by which the display is divided (f.e. display per revolution = 35, display divisor = 10, display per revolution = 3,5; i.e. first revolution = 3, second revolution = 7). adding in clockwise sense adding in anti-clockwise sense single transfer double transfer in comparison no decimal point -.- decimal point at first digit -.-- decimal point at 2nd digit decimal point at 3rd digit limit value 1 is absolute limit value 1 is relative to limit value 2 Sach-Nr Version 9/98 6/8
7 Parameter Display Alternatives / Signification NPN/PNP selection 'F24' '0': * KEYLOCK and APPL.are low active, npn switching KEYLOCK and APPL.are high active, pnp switching Set funktion key lock 'F26' if key lock input is active, setting and canceling of calibration value is not (calibration) '0':* locked is locked Level 1 key lock 'F27' '0':* if key lock input is active, access to level 1 is not locked access is locked Level 2 key lock 'F28' '0':* if key lock input is active, access to level 2+3 is not locked access is locked F1 and F2 key lock 'F29' '0':* '2': '3': if key lock input is active, keys F1 and F2 are not locked F1 locked F2 locked F1 and F2 are locked Basic setting 'F30' '0':* no function all parameters are set to the * marked values function of application input 'F31' '0': * '2': chain mode 'F35' '0': * setting of reference point display-hold chain reset chain function locked chain function unlocked 1 hint for funktion of limit value 1: if limit value is absolute, OUT 1 will be active as soon as counter position equals to limit value 1. If limit value is in relative function, OUT 1 will be active as soon as the counter position equals to limit value 2 plus limit value 1. Example: limit value 1 = -20, limit value 2 = 100 absolute OUT1 at -20 OUT2 at 100 relative OUT1 at 80 (=100-20) OUT2 at Locking keyboard functions In level 3, the following keyboard functions can be locked: Calibration function, entry to level 1, entry to level 2, buttons F1 and F2. The setting of those keylocks is explained in chapter Failures and error messages failure no display limit and set values are not programmable diagnosis check if supply voltage is correctly connected/ switched on? check if level 1 or F1/F2 buttons are locked? check if level 2 is locked? Set function not possible (calibration function) position indicator does not operate SSI Error keylock set function active? check if counting input is correctly connected? check if display-hold is triggered? check if mass connection position indicator-encoder is correct? check if encoder is in good condition? data format incorrectly set wiring incorrect or connection defective no data compatibility at multiple reading parity check active and no parity output from encoder -... range exceeded; tune back to the range or set display to defined value. _... fallen below range; tune back to the range or set display to defined value If any failure occurs, which is not mentioned above, our sales support for electronic counters will assist you. (Tel /89-0). Sach-Nr Version 9/98 7/8
8 7. Technical data 7.1 Mechanical Specifications Dimensions according to DIN 43700, 96 x 48 x 108 mm Mounting with clamping frame in a panel cutout of 92x45 mm Fixing screws M 3 Panel thickness up to 11 mm Electrical connection three plug-in terminals, 10,8 or 6 poles, 5 mm pattern Connection profile wire end ferrules 1...1,5mm 2 Screw M 2,6 Weight DC version: approx. 200 g; AC version: approx. 420 g 7.2 Electrical Specifications Power Supply DC Voltage U b VDC= SELV (Terminal 1-2) max. Tolerances + 10% / - 5% Current Consumption max. 250 ma (including sensor supply 60 ma) Power Consumption max. 4,5 W AC Voltage 115/230 VAC / Hz max. Tolerances + 6% / - 10% Overload Protection external Fuse:115V: 63mAT 230V: 32mAT Current Consumption max. 50/25 ma (incl. sensor supply) Power failure one mains half wave according to IEC Inputs and outputs of encoder Data input (DATA+ and DATA- terminals 29,30) Input resistance Amplitude max. Clock output (CLOCK+,CLOCKterminals 27,28) Output level Output current Wire length Control Inputs Switching level Amplitude max. Active edge Input resistance Pulse shape Application Input (Terminal 25) Input mode PulseDuration Tmin Keylock input (terminal 26) PulseDuration Tmin Output Values Relay Output Contact Type Contact Guard Circuit SSi conform differential signal, RS 422, clock rate approx. 100kHz approx. 470 Ohm V differential signal, RS 422, clock rate approx. 100kHz high 3,5V typ., low 1,3V typ. +/- 8mA typ.,+/- 60mA max. 400 m max. low < 2 V, high > 8 V 40 V pnp/npn selectable approx. 5 kohm any Setting reference point, display hold, chain reset function see chapter 4.3 static / dynamic; dependent on function min 3 ms static min 3 ms (Terminals 6-8 and 10-12; OUT 1, OUT 2) changeover relay no; externally recommended for capacitive and/or inductive loads Switching Voltage max 30 VDC/250 VAC; min. 5 V AC/DC Switching Current max 1 A; min 10 ma Relay Response Delay ó15 ms Transistor-Output (terminals 14, 15) Switching voltage PNP, 24VDC at AC supply, VDC-2V at DC supply Switching current 10 ma max. Response delay 10 ms max. Sensor Supply (Terminal 31/32) AC operation: VDC, Imax = 60 ma DC operation: Ub -2V, Imax = 60 ma Data Retention Data are retained in a non-volatile memory Write Cycles > Read Cycles Unlimited Data Retention >10 years Display Type Display Colour Digit Height Indicator LED`s 5 7-segment LED, 6 digits, suppression of leading zeros, programmable decimal point red 14 mm Ambient Conditions / Safety Regulations Operating Temperature 0 C C Storage Temperature -20 C C Protection Class front side IP 54, (EN60529) terminals IP 20 Noise immunity EMC according to EN Noise emittance EMC according to EN Vibrostability 10 m/s 2 ( Hz) according to IEC 68-part 2-6 Shock stability 100 m/s 2 (18 ms) according to IEC 68- part 2-27 General Rating DIN EN T1,protection class II, contamination level 2, overvoltage category III Climatic Standards KWF 7.3 Ordering information Type Supply Ordering code signo727 without limit VDC values signo727 without limit 115/230VAC values signo727 with limit VDC values signo727 with limit values 115/230VAC Accessories Adapter frame for panel mounting, cut-out 106 x 55 for panel frame size 4, ordering code Explanation of technical terms You will find a detailled explanation in the glossary of our counter catalogue. Sach-Nr Version 9/98 8/8
9 Sach-Nr Version 9/98 9/8
signo 727 SSI operating instructions
operating instructions signo 727 SSI Position-Indicator with/without limit values and SSI input from absolute encoder 1. Safety instructions This instrument has been built and tested in accordance with
More informationContact protection relay
Contact protection relay Ordering details SVR 450 08 F0000 The protects sensitive control contacts from excessive load. It can be used with latching function or without. Bounce time of control contacts
More informationAssembly. Front view. LED yellow: Relay output I. LED yellow: Relay output II
Switch Amplifier, Timer Relay Features 1-channel signal conditioner Universal usage at different power supplies 3-wire PNP/NPN sensor or push-pull input 2 relay contact outputs Adjustable energized/de-energized
More informationRotary Measuring Technology Absolute encoders, Multiturn, optional with incremental track
Electronic multiturn gear with intelligent sensing technology (IST) Integrative Technology Max. 4 programmable outputs* for the SSI version Programmable parameters include*: code type, resolution per revolution,
More informationTime Counters mini "h", DC Version
Type 633-DC Time Counters mini "h", DC Version Type 633.0 Type 633.7 Type 633.8 High shock resistance Miniature dimensions Electrical connections in standard grid Suitable for PCB mounting Machine-solderable
More informationInstruction Manual. Instrument Amplifier HE 017
Instruction Manual Instrument Amplifier HE 017 List of contents INSTRUCTION MANUAL: HE 017 Date: 20.4.99 Art.-No.: 320999 S General Safety Instructions.......................................... S 1 General
More informationThe Indicator with 3 Limit Contacts
A 1200 The Indicator with 3 Limit Contacts Format: Installation depth: 96x48 mm (1/8-DIN) 122 mm Description and Operating Manual ELOTECH Industrieelektronik GmbH Verbindungsstrasse 27 D 40723 HILDEN FON
More informationOperating instructions. Switching amplifier DN0210 DN / / 2015
Operating instructions Switching amplifier DN0210 DN0220 UK 80011079 / 00 01 / 2015 Contents 1 Preliminary note...4 1.1 Symbols used...4 1.2 Warning signs used...4 2 Safety instructions...5 2.1 General...5
More informationMonitoring technique. VARIMETER Voltage relay MK 9064N, MH 9064
Monitoring technique VARIMETER Voltage relay MK 9064N, MH 9064 0269462 Your Advantages Preventive maintenance For better productivity Quicker fault locating Precise and reliable Min-, Max. value or window
More informationElectronic Preset Counter with 2 Presets and Print interface. NE213 Prog Features
Electronic Preset Counter with 2 Presets and Print interface NE21 Prog. 09 Features Order designation Order no. Interface RS22 Models Connection Functions LED-preset counter with 2 presets Batch counter
More informationRoHS. Shock / vibration resistant. Short circuit proof. Flexible. . XXXX e. . XXXX e
The Sendix multiturn encoders 5862 and 5882, with SSI or RS485 interface and combined optical and magnetic sensor technology, offer a maximum resolution of 25 bits. These encoders are programmable via
More information02/11/2015
DIN Rail Mount 35 mm HSV Part number 84874320 Control of overspeed, underspeed, operating rate, stopping Measurement via discrete sensors - 3-wire PNP or NPN, Namur, voltage 0-30V or volt-free contact
More informationUser safety and equipment protection guidelines
Snap-in I/O Module The V200-18-E1 plugs directly into the back of compatible Unitronics OPLCs, creating a selfcontained PLC unit with a local I/O configuration. The module offers: 3 analog inputs 16 digital
More informationVEO. V2UF230V10 Art.Nr.: TECHNICAL DATA
Continous voltage monitoring Mains fluctuation detection Detects voltage drop / short interruptions of at least 10ms Prevents undefined states in switching and control systems Generates reset pulse after
More informationDemonstration Case BENNING DB 1
Operating manual Demonstration Case BENNING DB 1 part no. 044132 Table of contents 1 Introduction...3 2 Safety instructions...4 3 Applicable regulations...5 4 Device description...5 4.1 Measuring / testing...
More informationOperating instructions. Standstill monitor A / / 2011
Operating instructions Standstill monitor A300 UK 1 2 3 4 5 6 7 8 7390337 / 01 02 / 2011 1 2 3 4 5 6 7 8 switchpoint min max pulse/min power Made in Germany ifm electronic gmbh D 45127 Essen func. I II
More informationAbsolute Encoders Multiturn
The multiturn encoders 6 and 8, with interface and combined optical and magnetic sensor technology, offer a maximum resolution of 5 bits. These encoders are programmable via the Ezturn software. The hollow
More informationIO-DI8-TO8 I/O Expansion Module 8 Inputs, 8 Outputs
IO-DI8-TO8 I/O Expansion Module 8 Inputs, 8 Outputs The IO-DI8-TO8 is an I/O expansion module that can be used in conjunction with specific Unitronics OPLC controllers. The module offers 8 digital inputs,
More informationTechnical data. General specifications. Linearity error ± 0.1 Functional safety related parameters MTTF d 480 a at 40 C Mission Time (T M ) L 10
Model Number Features Very small housing Up to 31 bit overall resolution CANopen interface Free of wear magnetic sampling High resolution and accuracy Description This absolute rotary encoder provides
More informationModel Number Structure
Total Counter/Time Counter (DIN 8 x ) CSM DS_E DIN 8 x -mm Total Counter/Time Counter with Easy-to-read Displays and Water and Oil Resistance Equivalent to IP66 High-visibility, negative transmissive LCD
More information1/32-DIN TEMPERATURE CONTROLLER INSTALLATION, WIRING AND OPERATION MANUAL FORM 3882
1/32-DIN TEMPERATURE CONTROLLER INSTALLATION, WIRING AND OPERATION MANUAL FORM 3882 This manual is intended for use in support of installation, commissioning and configuration of the 1/32-DIN Temperature
More informationJUMO Quantum PID100/PID200/PID300
Data sheet 702020 Page 1/12 JUMO Quantum PID100/PID200/PID300 Universal PID Controller Series Brief description The Quantum series is available in the three DIN formats 48 mm x 48 mm, 48 mm x 96 mm, and
More informationFaults on the system Proximity switch connection technology:
Speed monitor for connection to a base unit from the PNOZmulti modular safety system Approvals Unit features Monitoring of 2 independent axes Connection of 2 incremental encoders or 4 proximity switches
More informationGeneral information. Display. Supply voltage. Input current
Datasheet SIMATIC S7-1200, CPU 1212C, COMPACT CPU, DC/DC/DC, ONBOARD I/O: 8 DI 24V DC; 6 DO 24 V DC; 2 AI 0-10V DC, POWER SUPPLY: DC 20.4-28.8 V DC, PROGRAM/DATA MEMORY: 50 KB General information Engineering
More informationOperating Instructions tico 735 AC Volts/Amps Indicator
Operating Instructions tico 735 AC Volts/Amps Indicator Introduction Your Hengstler tico 735 for AC Volts and Amps is one model in a family of 1/8 DIN units which offers breakthrough display technology
More informationV E1B Snap-in I/O Module
V200-18-E1B Snap-in I/O Module The V200-18-E1B plugs directly into the back of compatible Unitronics OPLCs, creating a selfcontained PLC unit with a local I/O configuration. Features 16 isolated digital
More informationOperating instructions. Speed monitor D / / 2014
Operating instructions Speed monitor D200 80005257 / 00 05 / 2014 Contents 1 Preliminary note...4 1.1 Symbols used...4 1.2 Warning signs used...4 2 Safety instructions...5 2.1 General...5 2.2 Target group...5
More informationAbsolute encoders - SSI
Features Encoder multiturn / SSI Optical sensing Resolution: singleturn 14 bit, multiturn 12 bit Compact design Cost-efficient mounting High reliability by self-diagnostics Counting direction input Available
More informationFEMA ELECTRÓNICA. Series MAG983-X. COUNTERS for IMPULSE signals MAG983-1 MAG983-2 MAG983-3 MAG USER S MANUAL (HT0695-r050705)
COUNTERS for IMPULSES Series MAG983-X COUNTERS for IMPULSE signals FEMA ELECTRÓNICA MAG983-1 MAG983-2 MAG983-3 MAG983-4 IDEAL SOLUTION for impulse counting applications where the operator has no access
More informationTechnical data. General specifications. Linearity error ± 0.1 Functional safety related parameters MTTF d 480 a at 40 C Mission Time (T M ) L 10
Model Number Features Solid shaft Up to 31 bit overall resolution CANopen interface Free of wear magnetic sampling High resolution and accuracy Highly shock / vibration and soiling resistant Sturdy construction
More informationGeneral information Engineering with Programming package. Display with display. Supply voltage 24 V DC Yes. Input current
Datasheet SIMATIC S7-1200, CPU 1214C, COMPACT CPU, DC/DC/DC, ONBOARD I/O: 14 DI 24V DC; 10 DO 24 V DC; 2 AI 0-10V DC, POWER SUPPLY: DC 20.4-28.8 V DC, PROGRAM/DATA MEMORY: 75 KB General information Engineering
More informationDisplays Transducers. Displays and transducers
JJ Displays JJ Transducers Displays and transducers DS_Displays_and_transducers 06/2016 225 Displays and transducers Our electronic devices for flow and volume measurement are suitable for all SIKA flow
More informationDIGITAL DISPLAY. for Industry Applications. Series WAY-SSI. Key-Features:
DIGITAL DISPLAY for Industry Applications Series WAY-SSI Key-Features: Content: Technical Data.2 Technical Drawing...2 Electrical Connection...3 Description...4 Order Code & Accessories...6 - WAY-SSI-S:
More informationElectronic Totalizing Counters
Electronic Totalizing Counters Type tico 731 tico 732 tico 734 tico 735P1 Input control Frequency Prescaler Reset input Control inputs Counting mode Add mode Difference mode Counting direction Add/Add
More informationDisplay. Supply voltage. Input current. Encoder supply. Output current. Power losses. Memory
Datasheet SIMATIC S7-1200, CPU 1214C, COMPACT CPU, DC/DC/DC, ONBOARD I/O: 14 DI 24V DC; 10 DO 24 V DC; 2 AI 0-10V DC, POWER SUPPLY: DC 20.4-28.8 V DC, PROGRAM/DATA MEMORY: 75 KB Display with display Supply
More informationGeneral information Engineering with Programming package. Display with display. Supply voltage 24 V DC Yes. Input current
Datasheet SIPLUS S7-1200 CPU 1214C DC/DC/DC -40... +70 DEGREES C WITH CONFORMAL COATING BASED ON 6ES7214-1AG31-0XB0. COMPACT CPU, DC/DC/DC, ONBOARD I/O: 14 DI 24V DC; 10 DO 24 V DC; 2 AI 0-10V DC, POWER
More informationGeneral information Engineering with Programming package. Display with display. Supply voltage 24 V DC Yes
Datasheet SIMATIC S7-1200, CPU 1215C, COMPACT CPU, DC/DC/DC, 2 PROFINET PORT, ONBOARD I/O: 14 DI 24V DC; 10 DO 24V DC 0.5A 2 AI 0-10V DC, 2 AO 0-20MA DC, POWER SUPPLY: DC 20.4-28.8 V DC, PROGRAM/DATA MEMORY:
More informationGeneral information. Display. Supply voltage. Input current. Encoder supply. Output current
Data sheet SIMATIC S7-1200, CPU 1214C, COMPACT CPU, DC/DC/DC, ONBOARD I/O: 14 DI 24V DC; 10 DO 24 V DC; 2 AI 0-10V DC, POWER SUPPLY: DC 20.4-28.8 V DC, PROGRAM/DATA MEMORY: 75 KB General information Engineering
More information2-Axis Counter BDD 622
2-Axis Counter BDD 622 Technical Description, User's Guide english No. 622-221 D/E. Edition 0701; Subject to modification. www.balluff.com Balluff GmbH Schurwaldstrasse 9 73765 Neuhausen a.d.f. Germany
More informationData Sheet T 6493 EN. TROVIS 6400 Automation System TROVIS 6493 Compact Controller. For panel mounting (front frame 48 x 96 mm/1.89 x 3.
Data Sheet T 6493 EN TROVIS 6400 Automation System TROVIS 6493 Compact Controller For panel mounting (front frame 48 x 96 mm/1.89 x 3.78 inch) Application Digital controller to automate industrial and
More informationVEO. V2PF480Y/277VSY01 Art.Nr.: V2PF480Y/277VSY01P Art.Nr.: TECHNICAL DATA
Monitoring of phase sequence and phase loss Monitoring of asymmetry Supply voltage 208-480 V AC Supply circuit = measuring circuit 1 change-over contact Width 22,5 mm Control elements Asymmetry Status
More informationAssembly instruction / User manual
Assembly instruction / User manual 4-Q motor speed control unit digital, type DLR 24/xx-466 Technical data under reserve technical changes Please read these instruction before using and please keep safe
More informationModel Number Structure
Solid State Relays with Failure Detection Function G3PC CSM_G3PC_DS_E_1_1 Refer to Safety Precautions for All Solid State Relays. Detects failures in SSR used for heater temperature control and simultaneously
More informationVEO. V2ZR V AC/DC Art.Nr.: V2ZR10P V AC/DC Art.Nr.: TECHNICAL DATA
Off-Delay 10 time ranges Supply voltage 24-240V AC/DC 1 change-over contact Width 22,5 mm Control elements Fine adjustment Setting of time range Status indication LED U/t: Supply voltage LED R: Relay status
More informationGeneral information. Display. Supply voltage. Input current. Encoder supply. Power losses
Data sheet SIMATIC S7-1200, CPU 1215C, COMPACT CPU, DC/DC/RELAY, 2 PROFINET PORT, ONBOARD I/O: 14 DI 24V DC; 10 DO RELAY 2A, 2 AI 0-10V DC, 2 AO 0-20MA DC, POWER SUPPLY: DC 20.4-28.8 V DC, PROGRAM/DATA
More informationCompact universal controllers
7 867 Compact universal controllers RWF55... The RWF55 is used mainly for controlling the temperature or pressure in oil- or gas-fired heating plants. If the relevant parameters are set, the RWF55 can
More informationIntrinsically safe batch controller Batching Master 110i
Intrinsically safe batch controller Batching Master 110i Installation Guide BVS 04 AT E 172 Revision 12.2 IBS BatchControl GmbH Im Sträßchen 2-4 Tel.: ++49 2441 9199 801 53925 Kall Fax.: ++49 2441 9199
More informationDisplay. Supply voltage. Input current. Encoder supply. Output current. Power losses. Memory
Datasheet SIMATIC S7-1200, CPU 1214C, COMPACT CPU, AC/DC/RLY, ONBOARD I/O: 14 DI 24V DC; 10 DO RELAY 2A; 2 AI 0-10V DC, POWER SUPPLY: AC 85-264 V AC AT 47-63 HZ, PROGRAM/DATA MEMORY: 75 KB Display with
More informationV E2B Snap-in I/O Module
V200-18-E2B Snap-in I/O Module The V200-18-E2B plugs directly into the back of compatible Unitronics OPLCs, creating a selfcontained PLC unit with a local I/O configuration. Features 16 isolated digital
More informationMINI MCR-SL-UI-2I(-SP)(-NC)
Data Sheet 03/2005 Product Description Features Configurable signal duplicator MINI MCR-SL-UI-2I(-SP)(-NC) is used to electrically isolate, condition, amplify, and filter analog standard signals. On the
More information02/11/2015
24 x 48 Hour CTR24 non-backlit model Part number 87622162 Display : 8-digit LCD, height 8 mm Built-in module for voltage inputs 10 260 VAC/DC () 4 timing ranges : 99,999.99 hrs - 99,999.59 hrs - 999,999.9
More informationTachometers TC-4B-V TC-6A-V Electronic cam-operated switching devices FC-21-V... 50
List of content page Counters and indicators DA5-IU-C... 10 DA5-IU-2K-C... 12 DA5-IU-2K-V... 12 KCM-51-C... 14 KCM-51-V... 14 KCM-70-C... 16 KCM-70-V... 16 KCM-70A-C... 18 KCM-70A-V... 18 KCT-6S-C... 20
More informationRotary Measuring Technology
--20 40... 60 + C 85 Temperature Shock/vibration resistant Short-circuit proof Reverse polarity protection One type for every situation: Version "flameproof-enclosure": approval zones 1, 2 and 21, 22 Zones
More informationGeneral information. Display. Supply voltage. Input current. Encoder supply. Output current
Data sheet *** SPARE PART*** SIMATIC S7-1200, CPU 1214C, COMPACT CPU, DC/DC/DC, ONBOARD I/O: 14 DI 24V DC; 10 DO 24 V DC; 2 AI 0-10V DC, POWER SUPPLY: DC 20.4-28.8 V DC, PROGRAM/DATA MEMORY: 50 KB General
More informationUniversal counter UZ 9648 Counting - length measurement - metering - positioning
+49-(0)40-670 73-0 Fax +49-(0)40-670 73-288 info@martens-elektronik.de www.ghm-messtechnik.de Universal counter UZ 9648 Counting - length measurement - metering - positioning Features M LED-Display 14.2mm
More informationIO-DI8-TO8, IO-DI8-TO8-L I/O Expansion Modules 8 Inputs, 8 Outputs
IO-DI8-TO8, IO-DI8-TO8-L I/O Expansion Modules 8 Inputs, 8 Outputs The IO-DI8-TO8 and IO-DI8-TO8-L are I/O expansion modules that can be used in conjunction with specific Unitronics OPLC controllers. The
More informationGeneral information Engineering with Programming package. Display with display
Datasheet SIPLUS S7-1200 CPU 1212C AC/DC/RLY -40... +70 DEGREES C WITH CONFORMAL COATING BASED ON 6ES7212-1BE31-0XB0. COMPACT CPU, AC/DC/RELAY, ONBOARD I/O: 8 DI 24V DC 6 DO RELAY 2A 2 AI 0-10V DC, POWER
More informationGeneral information. Display. Supply voltage. Input current. Encoder supply. Output current
Data sheet SIMATIC S7-1200, CPU 1214C, COMPACT CPU, DC/DC/RELAY, ONBOARD I/O: 14 DI 24V DC; 10 DO RELAY 2A; 2 AI 0-10V DC, POWER SUPPLY: DC 20.4-28.8 V DC, PROGRAM/DATA MEMORY: 75 KB General information
More informationRotary Measuring Technology Absolute singleturn encoder shaft version
Highest shock resistance on the market ( 2500 m/s 2, 6 ms acc. to DIN IEC 68-2-27) SSI, parallel or current (4... 20 ma) interface Divisions: up to 16384 (14 bits), singleturn Housing Ø 58 mm IP 65 Various
More informationMHAP HDmag. Features
Features MHP 200 - Version for axial screw mounting bsolute encoder with magnetic sensing and without bearings with integrated FPG signal processing bsolute resolution max. 17 bit singleturn dditional
More informationGeneral information. Display. Supply voltage. Input current. Encoder supply. Output current
Data sheet SIMATIC S7-1200, CPU 1215C, COMPACT CPU, DC/DC/DC, 2 PROFINET PORT, ONBOARD I/O: 14 DI 24V DC; 10 DO 24V DC 0.5A 2 AI 0-10V DC, 2 AO 0-20MA DC, POWER SUPPLY: DC 20.4-28.8 V DC, PROGRAM/DATA
More informationFL MC 2000E (SM40) LC
IEC 61850 fiber optic converter with LC fiber optic connection (1310 nm) to convert 100Base-Tx to single- or multi-mode fiber glass Data sheet 3205_en_C 1 Description PHOENIX CONTACT 2014-04-04 2 Features
More informationThe pages in this document have been extracted from a larger document and as such any page numbers are relevant only to the original document.
The pages in this document have been extracted from a larger document and as such any page numbers are relevant only to the original document. Rotary Encoder Solutions Limited Dutton Road Redwither Business
More informationV E1B Snap-in I/O Module
V200-18-E1B Snap-in I/O Module The V200-18-E1B plugs directly into the back of compatible Unitronics OPLCs, creating a selfcontained PLC unit with a local I/O configuration. Features 16 isolated digital
More information4 â Active barrier RN221N with optional HART diagnosis. Technical Information
Technical Information Active barrier with optional HART diagnosis Active barrier with power supply for safe separation of 4 to 20 ma current circuits Application Galvanic isolation of 4 to 20 ma current
More informationDM-918 OPERATIONS MANUAL AUTORANGING MULTIMETER
DM-918 OPERATIONS MANUAL AUTORANGING MULTIMETER SAFETY INFORMATION The following safety information must be observed to ensure maximum personal safety during the operation of this meter: This meter is
More informationOperating Manual. ZX020 Miniature Low Cost Counter for Input Frequencies up to 60 khz. Product Features:
Operating Manual ZX020 Miniature Low Cost Counter for Input Frequencies up to 60 khz Product Features: Miniature panel housing Bright LED display with 6 digits Add-on frame for clip or screw mounting Counting
More informationThread length. 27 (40) mm. 27 (44) mm. 27 (40) mm. 34 (50) mm. 34 (49) mm. 39 (60) mm. 39 (54) mm. 44 (65) mm. 44 (59) mm
Long Distance Cylindrical. Extra long for increased protection and sensing performance triple proximity sensors for flush mounting requirements. designed and tested for extra long life. Ordering Information
More informationIV-30 Operating Manual for Pulse Distributor Cassette with potential separation
IV-30 Operating Manual for Pulse Distributor Cassette with potential separation Edition-/Rev.-Date: 09/08/2006 Document-/Rev.-No.: TR - EAK - BA - GB - 0093-02 Software version: - File name: TR-EAK-BA-GB-0093-02.DOC
More informationSolid-state Timer H3YN
Solid-state Timer H3YN Miniature Timer with Multiple Time Ranges and Multiple Operating Modes Minimizes stock. Pin configuration compatible with MY Power Relay. Standard multiple operating modes and multiple
More informationAbsolute encoders - bus interfaces Solid shaft with clamping or synchro flange Magnetic single- or multiturn encoders 14 bit ST / 18 bit MT
Features Encoder single- or multiturn / CANopen Precise magnetic sensing Angular accuracy up to ±0.15 Additional incremental signals High protection up to IP 67 High resistance to shock and vibrations
More informationPHOENIX CONTACT - 01/2010. Features. DANGER OF EXPLOSION! Only remove equipment when it is disconnected and not in the potentially explosive area.
Uninterruptible power supply with integrated power supply unit INTERFACE Data sheet 104211_en_00 1 Description PHOENIX CONTACT - 01/2010 Features The MINI-DC-UPS provide an uninterruptible DC voltage both
More informationSALES NUMBER NUMBER OF BEAMS PROTECTIVE HEIGHT
SECTION 21 182 Safety Light Curtains Type: SLC-F Finger (14mm) FEATURES: Resolution: 14mm Protective height: 160mm to 1040mm Type 4 according to IEC61496-1 and -2 ORDERING INFORMATION: SALES OF BEAMS PROTECTIVE
More informationModel Number Structure
Solid State Relays with Failure Detection Function G3PC Detects failures in SSR used for heater temperature control and simultaneously outputs alarm signal. This SSR supports the safe design of heater
More information02/11/2015
48 x 48 Max. Counting Speed 5 KHZ Green backlit LCD display Part number 87629111 Counter, Preselection chronometer Maximum input frequency 5 k Hz Simple parameter setting, configuration using text menus
More informationAD-8923-BCD. Remote Controller (BCD) INSTRUCTION MANUAL 1WMPD
AD-8923-BCD Remote Controller (BCD) INSTRUCTION MANUAL 1WMPD4002137 2010 A&D Company, Limited. All rights reserved. No part of this publication may be reproduced, transmitted, transcribed, or translated
More informationXPSMF40. Main. Safety module name. Monitoring safety detection discrete input Monitoring safety dialogue discrete output
Product datasheet Characteristics XPSMF4000 Preventa safety PLC compact - Safe Ethernet Main Range of product Product or component type Safety module name Safety module application Preventa Safety automation
More informationControl elements. Fine adjustment. Status indication. 24 V DC typ. 0,25 W / 0,25 VA. 24 V DC typ. 0,03 W / 0,09 VA. 0,15 3 s. 0,5 10 h.
On-Delay 10 time ranges Supply voltage 24-240V AC/DC 1 change-over contact Width 22,5mm Control elements Fine adjustment Setting of time range Status indication LED U/t: Supply voltage LED R: Relay status
More informationOPERATING INSTRUCTION
OPERATING INSTRUCTION AUTORANGING MULTIMETER MAX Ω F C 10A MAX every 15 min. COM V SAFETY INFORMATION The following safety information must be observed to insure maximum personal safety during the operation
More informationIO-DI8-RO8, IO-DI8-RO8-L I/O Expansion Modules 8 Inputs, 8 Outputs
IO-DI8-RO8, IO-DI8-RO8-L I/O Expansion Modules 8 Inputs, 8 Outputs The IO-DI8-RO8 and IO-DI8-RO8-L are I/O expansion modules that can be used in conjunction with specific Unitronics OPLC controllers. The
More informationG3PC. Model Number Structure. Solid State Relays with Failure Detection Function. Model Number Legend
Solid State Relays with Failure Detection Function G3PC Refer to Warranty and Application Considerations (page 1), Safety Precautions (page 4), and Technical and Safety Information (page 6). Detects failures
More informationPower supply CP-C 24/5.0
2CDC 271 064 F0004 Features Supply voltage ranges: 85-264 V AC, 100-350 V DC Output voltage adjustable from 22-28 V DC, default setting 24 V DC 0,5 % 5 A output current Open-circuit, overload and continous
More informationGeneral information. Display. Supply voltage. Input current. Encoder supply. Output current
Data sheet SIMATIC S7-1200, CPU 1211C, COMPACT CPU, DC/DC/RELAY, ONBOARD I/O: 6 DI 24V DC; 4 DO RELAY 2A; 2 AI 0-10V DC, POWER SUPPLY: DC 20.4-28.8 V DC, PROGRAM/DATA MEMORY: 50 KB General information
More informationRedundancy unit CP-A RU
2CDC 271 010 F0t06 Features Decoupling of CP power supply units with 2 inputs, each up to 20 A per input / channel Output up to 40 A True redundancy by 100 % decoupling of two parallel connected power
More informationS-14 S-14. Compact Digital Multimeter. Compact Digital Multimeter
S-14 Compact Digital Multimeter S-14 Compact Digital Multimeter SAFETY INFORMATION The following safety information must be observed to insure maximum personal safety during the operation at this meter
More informationElectronic timer CT-ERS.21
2CDC 251 057 F0t07 Features Rated control supply voltage 24 240 V AC/DC Single function ON delay timer One device includes 10 time ranges (0.05 s 300 h) 2 c/o contacts 2 LEDs for status indication Width
More informationSpeed Controller ZSU A01
ZSU A01 The ZSU speed controller is a monitor of rotating or oscillating machine parts. The speed controller continuously compares the set speed with the actual speed and produces a switching output in
More informationGeneral information. Display. Supply voltage. Input current. Encoder supply. Output current. Power loss. Memory
Data sheet SIPLUS S7-1200 CPU 1214C DC/DC/DC -40...+70 DEGREES C WITH CONFORMAL COATING BASED ON 6ES7214-1AG40-0XB0. COMPACT CPU, DC/DC/DC, ONBOARD I/O: 14 DI 24V DC 10 DO 24 V DC 2 AI 0-10V DC, POWER
More informationINSTALLATION MANUAL. LC 200 Electronic Overload Guard. Software versione PW0501 R 0.3
INSTALLATION MANUAL LC 200 Electronic Overload Guard Software versione PW0501 R 0.3 CONTENTS MAIN FEATURES LC 200 TECHNICAL FEATURES Page 2 SYMBOLS Page 3 WARNINGS Page 3 IDENTIFICATION DATA PLATE Page
More informationUDC 1000 and UDC 1500 MICRO-PRO SERIES UNIVERSAL DIGITAL CONTROLLERS
UDC 1000 and UDC 1500 MICRO-PRO SERIES UNIVERSAL DIGITAL CONTROLLERS EN0I-6041 12/99 PRODUCT SPECIFICATION SHEET OVERVIEW The UDC 1000 and UDC 1500 are microprocessor-based 1/16 DIN and 1/8 DIN controllers
More informationGeneral information. Display. Supply voltage. Input current
Data sheet SIMATIC S7-1200, CPU 1214C, COMPACT CPU, DC/DC/DC, ONBOARD I/O: 14 DI 24V DC; 10 DO 24 V DC; 2 AI 0-10V DC, POWER SUPPLY: DC 20.4-28.8 V DC, PROGRAM/DATA MEMORY: 100 KB General information Firmware
More information812/ 814/ 815 digital timers
8/ 84/ 85 digital timers 8 84 85 Relay output digital timer Multirange Multivoltage or relay outputs Reset function on panel (imers 85) Data saved in the event of a break in supply (imer 85) Access to
More informationRhino Buffer Module PSM24-BFM600S. Operating Instructions
Rhino Buffer Module PSM24-BFM600S Operating Instructions RHINO BUFFER MODULE PSM24-BFM600S Description The PSM24-BFM600S Buffer Module will hold the output voltage of a 24 VDC power supply after brownouts
More informationThe PM1000 series is a universal 4 digit LED plug-on display for transmitters with 4-20mA 2 wire output and fitted with DIN43650 connector.
PM1000 SERIES PLUG-ON DISPLAY BRIGHT LED DISPLAY INDICATION RANGE -999 TO +9999 FITS TO DIN 43650 CONNECTOR PLUG-ON TO ANY TRANSMITTER WITH 4-20MA OUTPUT EASY TO SCALE ON SITE ROBUST DESIGN SET POINT OPTION
More informationMultiturn absolute encoder
Model Number Features Industrial standard housing Ø58 mm 30 Bit multiturn Galvanically isolated CAN interface DSP 406, CLASS 1 and 2 Servo or clamping flange 2 limit switches Description In addition to
More informationKTC. Preset Counter/ Timer. Programmable Type. Model Number Legend SALIENT FEATURES. Sensing. Digital Panel Meters
Preset Counter/ Timer Programmable Type Model Number Legend SALIENT FEATURES 6 Digits PV, SV Universal Input Dual alarm output MODBUS via RS-485 High Speed - 10 KCPS Multiple output modes Batch Counting,
More informationDT1102 V (PS) Fully Configurable Galvanic Isolator. Operating Instructions
(PS) Fully Configurable Galvanic Isolator Operating Instructions Contents 1. About this document...4 1.1. Function... 4 1.2. Target group... 4 1.3. Symbolism used... 4 2. For your safety...5 2.1. Authorized
More informationSLIMCON-6 24V DC POWERED ISOLATING SIGNAL CONVERTER
SLIMCON-6 24V DC POWERED ISOLATING SIGNAL CONVERTER Whilst every effort has been taken to ensure the accuracy of this document, we accept no responsibility for damage, injury, loss or expense resulting
More informationHybrid AC Driver [GCNC-1110]
Page 1 Installation Manual and Datasheet Page 2 Key Features Smooth and quiet operation at all speeds and extremely low motor heating Industrial grade performance for an alternating current servo motor
More informationSolid-state Timer. Ordering Information. Miniature Timer with Multiple Time Ranges and Multiple Operating Modes H3YN- - Accessories (Order Separately)
Solid-state Timer Miniature Timer with Multiple Time Ranges and Multiple Operating Modes Minimizes stock. Pin configuration compatible with MY Power Relay. Standard multiple operating modes and multiple
More information